You are on page 1of 5

Technical Bid

600VA Line Interactive UPS Specifications: (Single Phase Input / Single Phase Output)

Specification
Description Specification Yes No
quoted by Agency

General :
Capacity : 600VA / 360 Watts
Type : Line Interactive
Protections for : Discharge, Over-charge & Overload
Power Saving : With Auto-Sleep Power-saving mode
Indicators for : AC Mode & Backup Mode
Audible Alarms for : Backup Mode, Low battery, Overload &
Fault

Input Parameters :
Nominal Input : 220 V AC – Single Phase with Neutral &
Voltage Earth
Input Voltage Range : 140 V – 300 V AC on Full Load
Nominal Input : 50 Hz
Frequency

Output Parameters :
Nominal Output : 230 V AC – Single Phase
Voltage
Voltage Regulation : +/- 10% in Battery Mode
Voltage harmonic : 3% - 6% (non-linear load)
distortion
Frequency : 50 Hz +/- 1Hz in battery mode
Overload Capacity : 110% for 5 Minutes on Mains
Transfer time – : 4 - 8 ms typically
Normal<->Battery

Battery :
Parameters
Battery : 12V – 7 Ah – 01 No.
:
Other Parameters :
Noise : Not more than 50 dB
Weight : Not more than 10 Kgs.

Communication :
Communication Port : RS 232 as standard
Monitoring Software : Required

Seal & Signature of Agency Signature of GHMC Authorities


1 KVA Online UPS Specifications: (Single Phase Input / Single Phase Output)

Specification
Description Specification Yes No
quoted by Agency

General
Capacity : 1 KVA
Type : True Online Double Conversion
Technology : IGBT based technology for
Inverter
Configuration : Stand Alone
Compatibility with Generator : Required

Input Parameters
Nominal Input Voltage : 220 V AC – Single Phase with
Neutral & Earth
Input Voltage Range : 160 V – 300 V AC on Full Load
Nominal Input Frequency : 50 Hz
Input Frequency Range : 46 – 54 Hz
Input Power factor : >0.97 at 220 V AC for Full
resistive Load

Output Parameters
Nominal Output Voltage : 220 / 230 / 240 V AC – Single
Phase
Line regulation : <2% (0 to 100% linear load)
Voltage harmonic distortion : 3% - 6% (non-linear load)
Output Power Factor : 0.7
Frequency : 50 Hz +/- 0.05 Hz
Inverter Overload Capacity : 108 to 150% for 30 Seconds
Crest Factor : 3:1
Transfer time – Normal<- : 0 ms
>Battery

DC Parameters
External Battery Voltage : 36 VDC or more
Charging Current : 4 Amps minimum

Other Parameters
Noise : Not more than 50 dB
Protection : IP 20 (Static State)

Communication
Communication Port : RS 232 as standard
Monitoring Software : Required

Seal & Signature of Agency Signature of GHMC Authorities

3 KVA Online UPS Specifications: (Single Phase Input / Single Phase Output
Specification
Description Specification Yes No
quoted by Agency

General
Capacity : 3 KVA / 2100 Watts
Type : True Online Double Conversion
Technology : IGBT based technology for
Inverter
Configuration : Stand Alone
Compatibility with Generator : Required

Input Parameters
Nominal Input Voltage : 220 V AC – Single Phase with
Neutral & Earth
Input Voltage Range : 160 V – 300 V AC on Full Load
Nominal Input Frequency : 50 Hz
Input Frequency Range : 46 – 54 Hz
Input Power factor : >0.97 at 220 V AC for Full
resistive Load

Output Parameters
Nominal Output Voltage : 220 / 230 / 240 V AC – Single
Phase
Line regulation : <2% (0 to 100% linear load)
Voltage harmonic distortion : 3% - 6% (non-linear load)
Output Power Factor : 0.7 ( greater preferable)
Frequency : 50 Hz
Inverter Overload Capacity : 100 to 150% for 30 Seconds

DC Parameters
External Battery Voltage : 96 VDC or more
Charging Current : 8 Amps minimum

Other Parameters
Noise : Not more than 50 dB
Protection : IP 20 (Static State)

Communication
Communication Port : RS 232 as standard
Monitoring Software : Required

Seal & Signature of Agency Signature of GHMC Authorities


6 KVA Online UPS Specifications: (Single Phase Input / Single Phase Output

Specification
Description Specification Yes No
quoted by Agency

General
Capacity : 6 KVA / 4200 Watts
Type : True Online Double Conversion
Technology : IGBT based technology for
Inverter
Configuration : Can be configured Parallel
Redundant System – PRS
Compatibility with : Required
Generator

Input Parameters
Nominal Input Voltage : 220 V AC – Single Phase with
Neutral & Earth
Input Voltage Range : 180 V – 270 V AC
Nominal Input Frequency : 50 Hz
Input Frequency Range : 46 – 54 Hz
Input Power factor : >0.98 at 220 V AC for Full
resistive Load
(near to unity preferable)

Output Parameters
Nominal Output Voltage : 220 / 230 / 240 V AC – Single
Phase
Line regulation : <1% (0 to 100% linear load)
Voltage harmonic distortion : 2% - 6% (non-linear load)
Output Power Factor : 0.7 ((near to unity preferable))
Frequency : 50 Hz +/- 0.05 Hz
Inverter Overload Capacity : 100% - 10 minutes in normal AC
Mains

DC Parameters
External Battery Voltage : 240 VDC or more
Charging Current : 8 Amps minimum

Other Parameters
Noise : Not more than 55 dB
Protection : IP 20 (Static State)
Relative Humidity : <95% non-condensing
Only UPS Weight : Not more than 100 Kgs.

Communication
Communication Port : RS 232 as standard
Monitoring Software : Required

Seal & Signature of Agency Signature of GHMC Authorities


Specification for UPS 10KVA,15KVA & 20KVAs

Specification
Required specification of GHMC Yes No
quoted by Agency

True Online Double


Topology :
Conversion

Technology : IGBT Based rectifier

380 to 420 VAC 3 phase


Input Range : input with tolerance +/-
20%
Input and Output near to
Power Factor :
unity (preferable)
220 to 240 VAC single
Output Range : overall efficiency above
90%
Sealed maintenance
batteries with suitable for 2
Battery :
hours backup on full load
(VAH)
Minimum 9A (before
Charger Capacity :
uploading please confirm)

Bypass input : 230 V

Preferable – System
Software : shutdown through system
battery monitoring soft

Noise : <50 db

Inverter Overload
: 125% for 1 min
Capacity

Output Frequency : 50 Hz

Operating Temperature : 0 to 45 C

Safety Certifications : To be attached

Seal & Signature of Agency Signature of GHMC Authorities