Professional Documents
Culture Documents
1.0)
A proposed 11KV distribution network for areas A and B is shown in Figure 1.1. Each 33KV/11KV
transformer is rated at 30 MVA with a leakage impedance of 12.9% and all the four transformers are
expected to be operated in parallel. Each neutral of the 11KV terminal is earthed through a 6.5 ohm
resistor. The load at each 11KV/0.4KV substation is 2 MVA in area A, 3MVA in area B and no load at
substations A and B. The capacity of each 11KV copper conductor, XLPE insulated cable is 12MVA
with a k constant of 143 and an average length of 2km. The impedance of the 12 MVA cable is (0.08
+ j0.1) ohm per km. SCADA facilities will not be provided. Only one planning criterion is required; i.e.
the supply should be restored within 10 to 15 minutes for a busbar fault at either substation A or B.
The maximun relay plus breaker operating time is limited to 2 seconds.
Figure 1.1: