Power Generation/Variable Load


Review: Lesson 6

The previous Lesson was about Gas turbine Power station. The student/User is expected to remember the following from the
lesson 6.

Basics: Definition
Arrangements: components that make up a gas turbine power station.
Advantages & Disadvantages: How this station measures up

Preview: Lesson 6

This Lesson is about Variable loads on Power stations. The student/User is expected to understand the following at the end of the
lesson.

Definitions Selecting generation units for a power station


Load Curves Base & Peak loads
Types of loads on a power station Methods of meeting load

To begin this lesson we look at definitions that will be used. learn these well.

Maximum demand ( MD ): Demand Factor ( Average load ( MD ):


The greatest demand of load on the power station
Dem.F ): This is the average of loads occuring on the
during a given period. The highest peak on the Ratio of maximum demand to power station in a given period.
power station load curve. connected load. this is usually
less than 1.

Daily average load: Monthly average Yearly average load:


Average of loads occuring on a power station in 1
load: Average of loads occuring on a power station
day (24Hrs). Average of loads occuring on in 1 year (8760Hrs).
a power station in 1 month
(24Hrs x No. of days).

Load factor ( LF ): Diversity factor ( DF Plant capacity factor ( PCF ):


The ratio of average load to maximum demand.
): The ratio of actual energy produced to the
typical ≈ less than 1. This is the measure of the The ratio of the sum of all maximum possible energy that could have
effective use of the power station. individual maximum demands been produced on a given period.
on the power station to the
Maximum demand on the
station. Consumer maximum

https://en.wikiversity.org/wiki/Power_Generation/Variable_Load 1/4
3/8/2019 Power Generation/Variable Load - Wikiversity

High LF = Low MD = Low plant capacity = Low cost demands donot occur at the This indicates the reserve capacity of a plant.
per unit generated. same time thus maximum From these we can see that:
demand on power station will
always be less than the sum
of individual demands.

High DF = Low MD = Low


plant capacity = Low
investment capital required.

Objectives of a Power station:

The power station is constructed, comissioned and operated to supply required power to consumers with generators running at
rated capacity for maximum efficiency.

we saw in lesson one that the fundamental problem in generation, transmission and distribution of electrical energy is the fact
that electrical energy can not be stored. It must be generated, transmitted and distributed as and when needed.

This lesson looks at problems associated with variable loads on power stations, and discusses the complexities met in deciding the
make, size and capacity of Generators (Generating units) that must be installed in a power plant to successfully meet these
varying energy demands on a day to day basis.

Variable load:

The load on a power station varies from time to time due to uncertain demands of consumers. Energy demand of one consumer at
any given time is distinct/differs from the energy demand of another consumer. This results in the total demand on the power
station to vary over a given period of time and may necesitate the following:

Additional equipment/Generating units to meet demand

Increase in production cost to recuperate use of more material/equipment


In order to study the pattern and effect of the varying load, station engineers use load curves.

A load curve is a graph showing the variation of load on the power station with respect to time. the following load curves are used
in power stations:

Daily load curve: -- Load variations captured during the day ( 24Hrs ), recorded either half-hourly or hourly.

Monthly load curve: -- Load variations captured during the month at different times of the day plotted aginst No. of days.

Yearly load curve: -- Load variations captured during the Year, this is derived from monthly load curves of a particular year.

Information obtained from load curves:

Area under load curve = Units generated

Highest point of the curve = MD

(Area under curve) ÷ (by total hours) = Average load

(Area under load curve) ÷ (Area of rectangle containing load curve) = LF

Helps to select size & number of generating units.


https://en.wikiversity.org/wiki/Power_Generation/Variable_Load 2/4
3/8/2019 Power Generation/Variable Load - Wikiversity

Helps to create operating schedule of the power plant.


Selecting generating units:

The following must be considered when selecting the number and size of Generating units (Generators):

Number and size of units to aproximately fit the annual load curve.

Units to be of different capacities to meet load requirements.

Atleast 15 - 20% of extra capacity for future expansion should be allowed for.

Spare generating capacity must be allowed for to cater for repairs and overhauling of working units without affecting supply of
minimum demand.

Avoid selecting smaller units to closely fit load curve.


Meeting Load:

The best method to meet load requirements on power station is to Interconnect two different power stations in paralell as follows:

More efficient Plant → Carries Base load( The unvarying load on the load curve ).
-- Generally thermal & Nuclear power stations.

Less efficient Plant → Carries Peak load ( Various load peak demands on the load curve ).
-- Generally Hydro, Pumped storage & gas turbine power stations.

Careful study of load curves must be undertaken before deciding which type of station will be used for what purpose as this is
greatly dependant on enviromental issues and availability of fuel used by a particular power station.

The power grid is constructed by connecting several generating stations together in parallel. This method has helped solve most
transmission and distribution problems facing power engineers. Below are the advantages of using a power grid:

Economical operation:
Sharing of load among stations allows for more efficient stations to work constantly at high load factors and less efficient stations
to be used for peak supply only.

Increased diversity factor:


Different stations have different load curves thus the total maximum demand of the system is decreased, thus effectively
increasing the diversity factor of the system.

Reduces Plant Reserve Capacity:


The stand-by capacity required of individual plants is reduced when they are interconnected in a grid.

Increased reliability:
If major breakdown occurs on one station, supply is maintained by other stations.

Exchange of peak loads:


Excess load can be shared from highly stressed plants to plant with lower peak loads ( Identified from load curves ).

Older plants can still be used:


Older plants which are less efficient can still be used to carry peak loads of short durations.

References
This resource is prepared from Lecture notes by Thuvack.