Al Othaim Commercial Mall – Al Rabweh (2)

2. Flow Rate Calculations


Flow rate calculation for sprinklers:

0 Maximum area served by sprinklers for ordinary hazard (group 1) = 372 m2


& maximum flow rate = 400 GPM
From NFPA13 page 13-83
Refer to attachment (11)
Flow rate calculation for Fire Hose Cabinet:

1 Minimum flow rate for one hose cabinet = 500 GPM


& minimum flow rate for additional hose cabinet =250 GPM
From NFPA14 page 14-17
Refer to attachment (15)

2 In the served area , 3 hose cabinets will be used


& flow rate required for 3 hose cabinets = 500 + 250 + 250 = 1000 GPM
3 Flow rate required at the first point of the fire network
= flow rate for sprinklers + flow rate for hose cabinets
= 400 + 1000 = 1400 GPM
4 Take Flow rate required = 1500 GPM.

Job No Proj. 0557 PC U05 Sheet 1 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

3. FM 200 Gas Extinguishing System Calculations


Bases of Calculations:-

5 According to type of hazard, the fire is class "A".


As per National Fire Protection Association Code 2001 "NFPA2001"
Page 2001-4 Sec 1-3.5

Refer to attachment no. (16).

6 System flow calculation shall be within the manufacturer’s list from NFPA
2001.
As per National Fire Protection Association Code 2001 "NFPA2001"
Page 2001-13 Sec 3-2.1

Refer to attachment no. (17).

7 FM200 concentration for class “A” fire is 7%. From manufacturer’s list.
As per KIDDE FM200 ESC Modular balanced Fire suppression System
Page 117 Table 3-2.1

Refer to attachment no. (18).

8 Nozzle choice and location shall be in accordance with nozzle’s list limitation.

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-21 Sec 5-10

Refer to attachment no. (19).

9 Specific halocarbon clean agent used is HFC-227ea.

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-5 Table 1-5.1.2

Refer to attachment no. (20).

10 Minimum design working pressure of HFC-227ea is (198) PSI (13.65 Bar).

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-10 Table 2-2.1.1.b

Refer to attachment no. (21).


FM-200 Calculations for Electrical Room No (004) At Basement (1) Floor:

Job No Proj. 0557 PC U05 Sheet 2 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Room area (A) = Width x Length

Job No Proj. 0557 PC U05 Sheet 3 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

= 2.65 m x 3.20 m
= 8.48 m2
Room volume (V) = Area x Height
= 8.48 m2 x 2.97 m
= 25.186 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48

Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
25.19 7
( )
0.1374 100  7

= 13.79 Kg
Total Weight of FM- 200 required ( W)
Take Weight of FM- 200 Cylinder = 15.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (023) At Basement (1) Floor:

Job No Proj. 0557 PC U05 Sheet 4 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Room area (A) = Width x Length


= 3.00 m x 3.40 m
= 10.20 m2
Room volume (V) = Area x Height
= 10.20 m2 x 2.97 m
= 30.3 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
30.30 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 16.60 Kg


Take Weight of FM- 200 Cylinder 18.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size 1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

Job No Proj. 0557 PC U05 Sheet 5 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Job No Proj. 0557 PC U05 Sheet 6 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

FM-200 Calculations for Electrical Room No (006) At Basement (2) Floor:

Room area (A) = Width x Length


= 2.40 m x 3.00 m
= 7.20 m2

Room volume (V) = Area x Height


= 7.20 m2 x 3.06 m
= 22.032 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
22.03 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 12.73 Kg


Take Weight of FM- 200 Cylinder = 15.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Job No Proj. 0557 PC U05 Sheet 7 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Electrical Room No (023) At Basement (2) Floor:

Room area (A) = Width x Length


= 3.00 m x 3.40 m
= 10.20 m2

Room volume (V) = Area x Height


= 10.20 m2 x 3.06 m
= 31.21 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
31.21 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 17.10 Kg

Job No Proj. 0557 PC U05 Sheet 8 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Take Weight of FM- 200 Cylinder = 20.00 Kg


As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachment no. (25-1).
FM-200 Calculations for Electrical Room No (017) At Basement (1) Floor:

Room area (A) = Width x Length


= 3.00 m x 3.40 m
= 10.20 m2

Room volume (V) = Area x Height


= 10.20 m2 x 4.73 m
= 48.25 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =

Job No Proj. 0557 PC U05 Sheet 9 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)
48.259 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.43 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (057) At Basement (2) Floor:

Room area (A) = Width x Length


= 3.00 m x 12.20 m
= 36.60 m2

Room volume (V) = Area x Height


= 36.60 m2 x 4.88 m
= 178.60 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

Job No Proj. 0557 PC U05 Sheet 10 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

W =
178.60 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 97.84 Kg


Take Weight of FM- 200 Cylinder = 100.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 2 No. with thread size 2”.


As per KIDDE Page 130 Table 3.13.3.1 Refer to attachments No. (25-2).
FM-200 Calculations for Control Room No (056) At Basement (2) Floor:

Room area (A) = Width x Length


= 5.25 m x 17.35 m
= 91.09 m2

Room volume (V) = Area x Height


= 91.09 m2 x 4.88 m
= 444.5 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)

Job No Proj. 0557 PC U05 Sheet 11 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

= 0.1374

W =
444.5 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 243.50 Kg


Take Weight of FM- 200 Cylinder = 245.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 2 No. with thread size 2”.


As per KIDDE Page 130 Table 3.13.3.1 Refer to attachments No. (25-2).
FM-200 Calculations for Electrical Room No (021) At Ground Floor:

Room area (A) = Width x Length


= 3.00 m x 3.50 m
= 10.50 m2

Room volume (V) = Area x Height


= 10.50 m2 x 4.88 m
= 51.24 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).
At temperature 21ºC , As per NFPA2001 Page 2001-48

Refer to attachment no. (23).


Job No Proj. 0557 PC U05 Sheet 12 of 29
Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
51.24 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 28.00 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachment no. (25-1).
FM-200 Calculations for Electrical Room No (011) At Ground Floor:

Room area (A) = Width x Length


= 3.00 m x 3.50 m
= 10.50 m2

Room volume (V) = Area x Height


= 10.50 m2 x 4.88 m
= 51.24 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

Job No Proj. 0557 PC U05 Sheet 13 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
51.24 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 28.06 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (018) At Ground Floor:

Room area (A) = Width x Length


= 3.00 m x 4.00 m
= 12.00 m2
Room volume (V) = Area x Height
= 12.00 m2 x 4.88 m
= 58.56 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

Job No Proj. 0557 PC U05 Sheet 14 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
58.56 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 32.08 Kg


Take Weight of FM- 200 Cylinder = 33.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles
As per KIDDE Page 129 Table 3.13.2.1 1 No. with thread size 2”.
Total Weight of FM- 200 required ( W) Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (006) At Ground Floor:

Room area (A) = Width x Length


= 3.00 m x 4.00 m
= 12.00 m2

Room volume (V) = Area x Height


= 12.00 m2 x 4.88 m
= 58.56 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

Job No Proj. 0557 PC U05 Sheet 15 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
58.56 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 32.08 Kg


Take Weight of FM- 200 Cylinder = 33.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles
As per KIDDE Page 129 Table 3.13.2.1 1 No. with thread size 2”.
Total Weight of FM- 200 required ( W) Refer to attachments No. (25-1).

FM-200 Calculations for Electrical Room No (219) At First Floor:

Room area (A) = Width x Length


= 1.80 m x 4.60 m
= 8.28 m2

Room volume (V) = Area x Height


= 8.28 m2 x 4.88 m
= 40.40 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Job No Proj. 0557 PC U05 Sheet 16 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
40.40 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 22.15 Kg


Take Weight of FM- 200 Cylinder = 25.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size 1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (206) At First Floor:

Room area (A) = Width x Length


= (2.00 m x 3.00 m) + (2.20 m x 2.40 m)
= 11.28 m2

Room volume (V) = Area x Height


= 11.28 m2 x 4.88 m
= 55.05 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

Job No Proj. 0557 PC U05 Sheet 17 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
55.05 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 30.15 Kg


Take Weight of FM- 200 Cylinder = 33.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size 2”.


As per KIDDE Page 130 Table 3.13.3.1 Refer to attachments No. (25-2).
FM-200 Calculations for Electrical Room No (218) At First Floor:

Room area (A) = Width x Length


= 1.60 m x 4.20 m
= 6.72 m2

Room volume (V) = Area x Height


= 6.72 m2 x 4.88 m
= 32.79 m3

Total Weight of FM- 200 required ( W) =

Job No Proj. 0557 PC U05 Sheet 18 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)
V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
32.79 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 17.96 Kg


Take Weight of FM- 200 Cylinder = 20.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Electrical Room No (217) At First Floor:

Room area (A) = Width x Length


= (2.24 m x 4.00 m) + (3.20 m x 3.50 m)
= 20.16 m2

Room volume (V) = Area x Height


= 20.16 m2 x 4.88 m
= 98.38 m3

Job No Proj. 0557 PC U05 Sheet 19 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
98.38 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 53.90 Kg


Take Weight of FM- 200 Cylinder = 55.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size 2”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Electrical Room No (043) At Second Floor:

Room area (A) = Width x Length


= 3.00 m x 4.00 m
= 12.00 m2

Job No Proj. 0557 PC U05 Sheet 20 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

V C
( )
S 100 C

Job No Proj. 0557 PC U05 Sheet 21 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
58.56 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 32.07 Kg


Take Weight of FM- 200 Cylinder = 33.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size 2”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Electrical Room No (032) 0At Second Floor:

Room area (A) = Width x Length


= (2.40 m x 3.50 m) + (0.65 m x 3.00 m)
= 10.35 m2

Room volume (V) = Area x Height


= 10.35 m2 x 4.88 m
= 50.50 m3

Job No Proj. 0557 PC U05 Sheet 22 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
50.50 7
( )
0.1374 100  7

Total Weight of FM- 200 required ( W) = 27.67 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Projector Room No (002) At Mezzanine Floor:

Room area (A) = Width x Length


= 2.50 m x 4.00 m
= 10.00 m2

Room volume (V) = Area x Height

Job No Proj. 0557 PC U05 Sheet 23 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

V C
( )
S 100 C

Job No Proj. 0557 PC U05 Sheet 24 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
48.80 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.73 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Projector Room No (003) At Mezzanine Floor:

Room area (A) = Width x Length


= 2.50 m x 4.00 m
= 10.00 m2

Room volume (V) = Area x Height


= 10.00 m2 x 4.88 m
= 48.80 m3

Total Weight of FM- 200 required ( W) =

Job No Proj. 0557 PC U05 Sheet 25 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)
V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
48.80 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.73 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Projector Room No (004) At Mezzanine Floor:

Room area (A) = Width x Length


= 2.50 m x 4.00 m
= 10.00 m2

Room volume (V) = Area x Height


= 10.00 m2 x 4.88 m
= 48.80 m3

Job No Proj. 0557 PC U05 Sheet 26 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
48.80 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.73 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Projector Room No (005) At Mezzanine Floor:

Room area (A) = Width x Length


= 2.50 m x 4.00 m
= 10.00 m2

Job No Proj. 0557 PC U05 Sheet 27 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

Room volume (V) = Area x Height


= 10.00 m2 x 4.88 m
= 48.80 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).

S = 0.1269 + 0.0005 x (21)


= 0.1374

W =
48.80 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.73 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

FM-200 Calculations for Projector Room No (006) At Mezzanine Floor:

Room area (A) = Width x Length

Job No Proj. 0557 PC U05 Sheet 28 of 29


Subject: Fire Fighting calculation Date: JAN, 2005
/conversion/tmp/scratch/411038592.rtf
Al Othaim Commercial Mall – Al Rabweh (2)

= 2.50 m x 4.00 m
= 10.00 m2

Room volume (V) = Area x Height


= 10.00 m2 x 4.88 m
= 48.80 m3

Total Weight of FM- 200 required ( W) =


V C
( )
S 100 C

S = 0.1269 + 0.0005 x (t)

Where (t) = Temperature


(C) = Concentration
(V) = Protected volume

As per National Fire Protection Association Code 2001 "NFPA2001"


Page 2001-62 Table A-3.5.1.(1)
Refer to attachment no. (22).

At temperature 21ºC , As per NFPA2001 Page 2001-48


Refer to attachment no. (23).
S = 0.1269 + 0.0005 x (21)
= 0.1374

W =
48.80 7
( )
0.1374 100 7

Total Weight of FM- 200 required ( W) = 26.73 Kg


Take Weight of FM- 200 Cylinder = 30.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).

Qty. of Nozzles 1 No. with thread size1”.


As per KIDDE Page 129 Table 3.13.2.1 Refer to attachments No. (25-1).

Job No Proj. 0557 PC U05 Sheet 29 of 29


Subject: Fire Fighting calculation Date: JAN, 2005