Professional Documents
Culture Documents
Andersen
PROGRAM DESCRIPTION
FLD15 is a subprogram of the general purpose magnetic field program FLD8. It consists basically of an
input and an output routine for this program, but everything can now be installed in one directory
(folder). Input and output can be in either metric or English units.
FLD15 is similar to FLD12. It calculates vector potentials as complex numbers, and can be used also
when there are phase shift connections and when the field is influenced by induced eddy currents in
sheet windings. It is applicable both to core type and shell type transformers.
For the straight parts of the coils, calculations are made for flat fields. For the rounded corners, they are
made for axi-symmetric fields. Reactance and eddy current losses are calculated from weighted
averages. However, short circuit forces and stresses are only printed out for the straight parts.
The program can also be used for round core transformers. It will give correct values of reactance and
losses, but if also short circuit forces and stresses are required, FLD12 should be used.
PROGRAM INSTALLATION
FLD15 is transmitted as a zip-file. It is extracted and installed in any directory (folder). The program
can also be installed on a memory stick and run from there.
Here all the Command Prompt commands and file names will be in capital letters. However, they are
case insensitive, and small letters can also be used.
RUN DEMO.INP
After a few seconds, a flux plot with 25 flux lines appears on the screen. It has been drawn on a Visual
Basic Form. If the picture appears to be cropped or too small, adjust the file SIZESCR.FIL. At the same
time a bitmap picture file PLOTFILE.BMP has been produced. Close the form and enter command:
PLOT
–2–
The flux plot now reappears in a standard Windows program. The tic-marks to the left and at the bottom
show the positions of horizontal and vertical finite element grid lines. The conductors are red.
If it is now desired to print the flux plot, crop the picture file first to remove empty space and save it.
Microsoft Office Picture Manager or Microsoft Paint can be used for that. Rather than printing it
directly, it is recommended to transfer the picture file to Microsoft Word. Here it can easily be resized
and comments added before printing.
Output from FLD15 is stored in file OUTPUT. To display it on the screen, enter:
FILE OUTPUT
Batch command FILE starts the standard Windows program NOTEPAD. It will be used here for
viewing, editing and printing text files. The first time it is invoked, it should be set to Courier New size
9, word wrap, and to no top and bottom extra text when printing. The window should always be
maximized.
GRID
After the form is closed, the grid also reappears with the command:
PLOT
INPUT
FILE DEMO.INP
What the numbers mean can be found on the input sheets, page 4 and 5. For an explanation of what else
can be done with the input file, copy it first to a new file with the command:
HEADINGS NEW.INP
-3-
FILE NEW.INP
The abbreviated headings on the input file also explain the numbers. With a little experience, that
explanation suffices to enter new numbers and to make up new input files.
Old input as similar as possible is first copied to a new input file. Then headings are introduced and the
file changed. Numbers always start in columns 1, 11, 21 and so on. They can be entered with or without
decimal point.
Before the new file can be run, the headings must be removed. Do this first with:
CLEANUP NEW.INP
A file without headings can have headings introduced and be viewed at the same time with:
HEADFILE NEW.INP
Headings can also be removed and the file run at the same time with:
CLEANRUN NEW.INP
INPUT.FIL
It consists of lines with a more detailed explanation, followed by a comma and a value. The comma is
interpreted as a delimiter and must be the only one on the line. INPUT.FIL can be copied to a new file,
where also more terminals, layers and segments can be added in the same format:
Then a standard input file NEW.INP can be created with the command:
Input must be entered very carefully, following explanations on the input sheets and instructions
elsewhere in this manual. Small mistakes like a comma instead of a decimal point or a number starting
in the wrong column are not tolerated. Some mistakes are caught by the program and are explained on
the output. Another way to catch mistakes is by giving a command such as:
CHECK NEW.INP
The input must here be in the standard format, without headings. A picture similar to a flux plot, but
without flux lines, will be displayed on the screen. Mistakes with the geometry can be caught this way.
RECTANGULAR CORE TRANSFORMER LEAKAGE FLUX PROGRAM FLD15 INPUT SHEET 2
For the segment data, use one pair of lines for each segment. Up to 200 segments can be entered, in a sequence starting with the
inner layer, and with increasing y-coordinates within each layer. Empty spaces are not considered as segments.
SEGMENT NUMBER 1
Y - COORDINATE, MINIMUM 11
MAXIMUM 21
NUMBER OF TURNS, TOTAL 31
ACTIVE (always positive) 41
NUMBER OF STRANDS, PER TURN (per group) 1
ACROSS LAYER (for all turns) *2 11
STRAND DIMENSION, HORIZONTALLY 21
VERTICALLLY *3 31
SEGMENT NUMBER 1
Y - COORDINATE, MINIMUM 11
MAXIMUM 21
NUMBER OF TURNS, TOTAL 31
ACTIVE (always positive) 41
NUMBER OF STRANDS, PER TURN (per group) 1
ACROSS LAYER (for all turns) *2 11
STRAND DIMENSION, HORIZONTALLY 21
VERTICALLY *3 31
SEGMENT NUMBER 1
Y - COORDINATE, MINIMUM 11
MAXIMUM 21
NUMBER OF TURNS, TOTAL 31
ACTIVE (always positive) 41
NUMBER OF STRANDS, PER TURN (per group) 1
ACROSS LAYER (for all turns) *2 11
STRAND DIMENSION, HORIZONTALLY 21
VERTICALLY *3 31
SEGMENT NUMBER 1
Y - COORDINATE, MINIMUM 11
MAXIMUM 21
NUMBER OF TURNS, TOTAL 31
ACTIVE (always positive) 41
NUMBER OF STRANDS, PER TURN (per group) 1
ACROSS LAYER (for all turns) *2 11
STRAND DIMENSION, HORIZONTALLY 21
VERTICALLY *3 31
*1: 2 for a normal sheet winding with half the window height calculated, otherwise usually 1.
*2: Used to calculate bearing surface for compressive stress in spacer blocks and in insulation, due to accumulated
vertical forces. With machine transposed cable, where the true number of strands across the layer varies between
a minimum and a maximum, the minimum number should be entered.
*3: For a normal sheet winding with half the window height calculated, half the depth of the sheet.
Sheet winding is assumed, if axial strand dimension 100 mm.
Round wire is assumed, if strand dimensions horizontally and vertically are given equal and 4 mm.
-6-
SPECIFICATION OF INPUT
LINE 1. The identification can consist of up to 80 characters, including blanks. Most combinations of
letters, numbers and special symbols on the keyboard can be used.
LINE 2. The y-coordinate for the lower boundary is usually given as zero. It corresponds to the
horizontal centerline if only half the window height is calculated, and to the lower yoke or beyond if the
full window height is calculated. In some cases it is desired to make a second run with the lower
boundary moved down and the upper boundary moved up, in order to approximate the conditions
outside of the transformer window. The y-coordinate of the lower boundary can then be made negative,
which permits the winding segments to remain in the same positions. However, the output y-coordinates
always refer to the lower boundary.
For round cores, the inner corner radius of the inner winding is given as the inner radius of the inner
winding. Core leg width and length are both given equal to the core diameter.
LINE 3. The distance winding-tank is the horizontal distance from the outer perimeter of the outer
layer. In most cases, more than the true distance would be entered, to approximate average conditions
around the perimeter. However, it is not recommended to make the distance more than about half the
depth of the windings. The value is not very critical for core type transformers, more so for shell type.
If an AL/CU shield is specified, the program puts in a flux line with vector potential zero along the tank
wall. Otherwise, flux lines will be forced perpendicular to the tank. A reference potential zero is then put
in by the program at the tank at the horizontal centerline.
If the optional per unit impedance is not specified (given as zero), the program calculates forces and
stresses for a symmetrical short circuit, using the system impedance (calculated from the system short
circuit GVA) in series with the calculated transformer impedance. Of course, this only makes sense if
windings belonging to only two terminals carry current, because it is only then that the calculated
transformer impedance has any real meaning. If it is desired to get the forces and stresses for a different
current, the optional per unit impedance should be specified as the inverse of "times normal" ac current.
The peak factor is for the maximum dc current component at short circuit. It does not include the 2
factor to get from rms to peak ac current.
LINE 4. If 1 is entered in col. 11, all layers with negative current are displaced in the y-direction by the
amount entered in col. 21. If 2 is entered in col. 11, all layers with negative current are elongated by the
amount entered in col. 21. Y-min is then kept unchanged, and all segments and open spaces belonging to
the layer are elongated in the same ratio. A negative displacement or elongation can also be entered.
It is explained elsewhere how tank, leg and yoke losses are calculated proportional to the factors
specified as input. These factors must be established from tests. They will be different for different sizes
and types of transformers, and for different manufacturers. One difficulty is that distances winding-tank
vary around the perimeter, and there is no fixed ratio between the actual and the calculated flux entering
the different parts. No great accuracy is therefore to be expected from these calculations.
-7-
Loss tests with and without the tank provide a clue about the tank loss, although the other losses will not
be exactly the same in the two cases. A separation of leg and yoke loss can only be done from a
statistical analysis of tests and calculations for several transformers (method of least squares).
Such an analysis for a line of medium size transformers gave the following result:
In the absence of such a study, it is better to give the loss factors as zero, and not perform this part of the
calculation.
The scale of the flux plot is not used anymore on newer computers.
LINES 5-8. The terminals should be numbered consecutively, usually starting with no. 1 for layer 1. "I"
is the connection for single phase units. For three phase units, the MVA rating is for all the phases and
KV is the line kilovolts. The values must correspond to the calculated load condition and tap position,
and must give balanced ampereturns. MVA can be zero, but never KV. Auto and phase shift connections
require special consideration, and will be dealt with separately (pages 8 and 9).
For single phase units, connection code = 1, except for auto connection. If the windings on two single
phase limbs are in series, number of parallel groups = 1, in parallel = 2 (layer data).
LAYER DATA. A layer in this context is a winding or part of a winding belonging to a certain terminal.
Layers are usually concentric, but can also be above each other and belong to different terminals. If so,
enter the lower layer first. Concentric layers do not have to be separated radially, but normally they are.
If a winding has one or two axial cooling ducts, it can be specified with two or three layers.
If the layer has two parallel paths with a lead connection in the middle, the number of parallel groups is
entered as 2, otherwise usually as 1.
In some rare cases a shell type transformer has a LV winding with several parallel circuits
within a group. In such a case with three circuits the total and active number of turns in a
segment in the group is artificially divided by three and total and active strands per turn
multiplied by three. The design must be made very carefully to ensure equal current distribution
between such circuits. Usually the circuits are identical with the same average vector potential.
To provide uniformity among the users, layers belonging to the inner main winding can be specified as
having a negative current, but this is really immaterial as far as the program is concerned.
The pitch and width of spacer blocks are used to calculate compressive stress in the spacers. If there are
no spacer blocks, pitch and width are given as zero.
SEGMENT DATA. A segment is defined as part of a layer which can be considered uniform in
conductor arrangements and current densities. The number of segments which is specified in the input
should be kept to a minimum, and entering individual disks as segments should be avoided.
When because of symmetry only the upper half of the window height is calculated, the segment data
refer to only that half.
-8-
AUTO CONNECTION
Terminal 1 Terminal 2
N1 turns N1 turns
Terminal 2 Terminal 1
N2 turns N2 turns
Fig. 1 Fig. 2
Referring to the figures, in the input N1 is assigned to terminal 1, N2 to terminal 2. If there are also
other terminals which are not auto connected, these are assigned numbers 3 and 4.
Terminal 1
N2 turns
Fig. 3 Fig. 4
Since part of the winding is not really auto connected in this case, it is necessary to introduce a third
terminal to handle the situation, as indicated in Fig. 4. For terminal 3 the connection should be specified
with code 1, and the MVA should be the difference of the MVAs for terminals 1 and 2. Buck or boost of
terminal 3 is specified with the direction of the current. With buck connection, terminal 2 has the highest
MVA, with boost terminal 1. For auto connection, per unit impedances will be calculated on the basis of
the MVA for terminal 1.
With Z or zig-zag connection, the neutral connected winding is given code 5 and is assigned to one
terminal, and the terminal connected winding is given code 6 and is assigned to another terminal. With P
or polygon connection, codes 7 and 8 are used in a similar way. With ED or extended delta connection,
code 9 is used for the main and 10 for the terminal connected winding. In all cases, MVA is given as the
total for the two windings for both terminals. FLD15 will take into account differences in phase angles,
when calculating these cases. The two phase shift windings should never be put in above each other,
since that will result in excessive horizontal flux.
The rated voltage for each terminal is given as volts per turn times no. of turns for P and ED
connections, and this times 3 for Z-connection.
For the tank, leg and yoke, losses are set equal to:
Loss = factor * area * (flux/m)2 watts
where for the tank, the area is taken as:
area = 2(core leg length) + (window width) * (vertical depth) mm2
For the core leg:
area = 2(core leg length) + (core leg width) * (vertical depth) mm2
Flux per meter depth:
(flux/m) = Amax - Amin weber/m
Amax and Amin are the maximum and the minimum vector potentials at the tank and the core leg,
respectively.
Index min refers to values at the core leg, max to values at the tank.
Grid density break lines are put in at the core leg, at all layer boundaries and at the tank. They are
assigned numbers so that the maximum grid line spacings do not exceed certain percentages of the
distance between the core leg and the tank.
In sheet windings, there are two vertical grid lines per turn.
- 10 -
E4
Fig. 5
As above for the upper half of the sheet winding, as a mirror image for the lower half.
- 11 -
As above for the upper half of the sheet winding, as a mirror image for the lower half.
- 12 -
E4
Fig. 7
- 13-
E4
E2
The same rules apply as between the upper boundary and
the windings.
Fig. 8
- 14 -
LIST OF SYMBOLS
USER PROGRAMMING
The input and output routines for FLD15 are completely decoupled from the main program, and can be
changed by the program user. The routines are supplied in source code in the files:
They can be reprogrammed and recompiled with the free Watcom Fortran 77 compiler.
PROGRAM OUTPUT
If output in English units is desired, change OUTMET to OUTENG in file RUN.BAT. Commands
OUTMET and OUTENG can also be given separately, after a run has been made.
The first part of the output is simply a repetition of the input, except that now "y - lower boundary" is
always zero, and all y-coordinates are with respect to the lower boundary.
The information for each segment includes forces and stresses at peak short circuit current, and dc and
eddy current losses at normal current.
Losses are at 75 deg. C, and do not include losses in leads and connections. Strands are assumed to have
rounded corners, with an area 0.5 mm2 subtracted if width times depth exceeds 15 mm2, otherwise 0.25
mm2 subtracted. If width = depth and not more than 4 mm, round wire is assumed.
KVA is kilovolts times amperes within the segment. For a negative current, the KVA also comes out
negative. If the KVA does not add up to zero for all the segments, the program aborts and prints an error
message.
Horizontal force per unit vertical length is the total across the width of the layer.
Maximum accumulated vertical forces are given both for each segment and for each layer. For a
segment, it is the force accumulated only within that segment. Forces on the supports from the layers are
for one phase.
Most of the forces can come out negative or positive. The signs then refer to negative and positive
directions along the x and y-axes. If a stress comes out negative, it is due to a negative force.
- 20 -
Max. compressive stress in spacers or insulation normally occurs near the radial centerline. Max.
bending stress between spacer blocks due to vertical forces occurs at the winding ends.
Stresses due to horizontal forces are not in the normal output. They can be calculated by giving
command STRESSES after the program has been run and answering questions on the screen.
LV
HV
LV
In the program, horizontal and vertical directions refer to the picture above, not to directions in the
actual transformer.
POST PROCESSING
After the main program has been run, the run identification and all the essential calculated and input
information are in file FOR.FIL, and can be retrieved for further processing. This includes all the vector
potentials (as calculated for flat fields), current densities and node and contour line coordinates.
A particularly useful post processor determines ideal locations of crossover points. If the calculations
involve a disk or helical winding with N parallel conductors, there will be N-1 crossover points in the
winding, where the conductors change positions. Some manufacturers make these crossover points
evenly spaced, but since the vertical flux density is not uniform, this can lead to quite high losses due to
circulating currents. Ideally, spacings should be inversely proportional to average vertical flux density,
which again is proportional to differences between vector potentials at the outer and inner perimeters of
the winding. Before ideal locations can be determined, the main program must have been run with the
upper boundary approximately twice the yoke distance from the winding ends, to make the leakage field
a weighted average of conditions under and outside of the yoke. The winding must belong to only one
layer in this case. Ideal locations can be calculated simply by giving the command:
LOCATIONS
This should be done after the output from the main program has been printed, because the file OUTPUT
is also used by the post processor. Some questions about the winding will appear on the screen, and it is
useful to have the output from the main program available, in order to answer the questions.
Another post processor is for drawing a graph on the printer, plotter or screen of current density
distribution in individual turns in sheet windings. It is started with the command:
GRAPH
Here also, it is advisable to have the output from the main program available, in order to answer the
questions on the screen. Followed by the command PLOT, the graph can be printed in the same way as
explained earlier for flux plots and grids.
FLD15 also generates an output file SEGMENT.FIL, which contains all the 40 input and output items
for each segment, listed on page 17. They are in metric units if written by Fortran subprogram
OUTMET, in English units if written by OUTENG. The format specification is FORMAT(40(F14.4)).
- 22 -
Only one reactance is calculated each time FLD15 is run, based on the magnetic energy. This is not
sufficient to determine short circuit currents and forces in three winding transformers when all the
windings carry current.
A three winding transformer has an equivalent circuit with three reactances, which can be determined
from three FLD15 calculations, each time with currents in only two windings. In per unit, they must all
relate to the same base MVA. The theory behind this is presumed to be known to the FLD15 user and
will not be gone into here.
From this equivalent circuit, currents can be calculated for different loads or short circuit conditions.
Having done that, a final calculation with FLD15 can have the "optional per unit impedance" on input
line 3 specified different from zero, as the inverse of "times normal" ac current, if short circuit forces are
required.
Sometimes a regulating winding is connected through a series transformer to reduce the current in the
on load tap changer. The regulating winding can be connected in boost or buck position.
The main winding and the regulating winding are assigned to two separate terminals. In boost
connection both MVAs are positive and add up to the base MVA for the transformer. In buck connection
the main winding has positive MVA and the regulating winding negative MVA. Again, the sum is equal
to the base MVA. The specified kV always agrees with the number of active turns.
The impedance in the series transformer should be taken into account in the calculation of forces and
stresses. This can be done by specifying the “optional impedance” in the input different from zero.
- 23 -
Below, in the flux plot to the left, the calculated leakage flux flows radially and enters the outer
boundary at right angles. In reality, this outer boundary usually consists of a tank around at least part of
the perimeter, where the radial leakage flux is counteracted by strong eddy currents, which are here not
taken into account in the calculations and would cause excessive losses in a normal transformer. A
normal transformer can therefore simply not be built like that. Nevertheless, the arrangement is
sometimes used in transformers for short intermittent duty. Due to the neglect of eddy currents in the
tank, the calculated impedance will be much too high, if it is done this way.
If a code=1 is put in for the AL/CU SHIELD in the FLD15 input, it changes the boundary condition for
the outer boundary into something which is probably more realistic in this case, as shown in the flux
plot to the right. However, the calculated short circuit impedance will be strongly dependent upon the
specified distance between the winding and the outer boundary and will be impossible to estimate
accurately without access to tests and calculations for similar transformers.
SEQUENCE IMPEDANCES
Positive sequence current produces an MMF, which rotates in the same direction as the rotor. In a
synchronous machine, the resulting flux is dc with respect to the rotor. In an induction machine, the
frequency is very low. Negative sequence current sets up an MMF, which rotates opposite to the rotor
and produces large opposing induced currents. Zero sequence current sets up essentially zero MMF in
the air gap. The differences are profound and produce very different positive, negative and zero
sequence reactances.
- 24-
In a transformer, there is no difference in reactance for positive and negative sequence. However, zero
sequence reactance is usually different.
Zero sequence current flows simultaneously without the usual 120 degree phase shift in the different
phases. It can only flow from the outside into a Y, Z or auto connected winding with the neutral
connected, so that the current has a return path. If the transformer also has a delta connected winding, it
will always act as if short circuited. Induced zero sequence current flows in a closed loop within the
delta.
If zero sequence current flows into a winding and there is no possibility of ampereturn balance with
induced current in another winding, the zero sequence reactance depends on the type of core. In a five
legged core and in single phase units, zero sequence flux has a return path through the core, and zero
sequence reactance will assume the very high value of a magnetizing reactance. In a three legged core,
the flux has no return path through the core and must find its way elsewhere, usually through oil,
structural parts and tank. In the tank and core clamps there will be induced currents, which lower the
reactance. The reactance will be much lower than a magnetizing reactance, but still very much higher
than a short circuit reactance. Without ampereturn balance, the reactance can not be calculated with
FLD15.
In the discussion which follows, zero sequence current is assumed to flow into a winding, where
ampereturn balance results from induced currents in other windings.
In a two winding transformer with Y-Y or Y-D connection, the zero sequence reactance will tend to be
the same as the positive and negative sequence reactance, also in a transformer with auto connection
without tertiary winding. With a three legged core, induced currents in tank and core clamps will lower
the reactance slightly.
Since a delta connected tertiary winding acts as if short circuited, its presence always influences the
reactance between the main windings.
As an example, say from the inside the transformer has a delta connected tertiary, a secondary and a
primary winding, where zero sequence current is fed into the outer primary. The secondary is shorted,
and the inner tertiary acts as if shorted. The current sharing between secondary and tertiary can be found
as explained on page 23. Say 100 MVA is specified for the primary, then perhaps 120 MVA for the
secondary and –20 MVA for the tertiary will be about right.
Phase shift connections also require special treatment. In extended delta connection, the main delta
connected winding acts as if short circuited, whereas the series winding is open. In zig-zag (Z) and
polygon (P) connections, the two winding parts on one core leg carry currents of the same phase in
opposite directions. Ampereturns are balanced within the same winding if the two parts have the same
number of turns. In calculations with FLD15, the two parts can be considered belonging to two separate
terminals. The Z-connection can be replaced by Y and the P by D.
- 25 -
Short circuit currents are found by the method of symmetrical components, which is presumed to be
known.
Unsymmetrical short circuits must be calculated for single phase and one limb with code 1 for all the
terminals. Voltages are volts/turn times number of turns. It is recommended to specify MVAs at short
circuit divided by 10 to make them more reasonable for calculation of losses. Optional per unit
impedance should then be 0.1 to make forces and stresses come out right.
LINE TO LINE
The transformer is presumed to be unloaded when the fault occurs. The figure shows a wye connected
winding, but the result is the same also for other connections.
I b1
<
a Ia = 0 Positive sequence
^ I b1 = Ib2
Z1 = Ib/2
I b2
<
c b
Ib = -Ic Z2 Negative sequence
Since the sum of the three phase currents is zero, there is no zero sequence current in this case. The
sequence equivalent network is drawn for phase b. Positive sequence current I b1 is equal to negative
sequence current Ib2, both of them equal to half the phase current I b. As noted earlier, positive and
negative sequence impedances Z1 and Z2 are the same as the three phase short circuit impedance.
A driving voltage is only present for the positive sequence.
The resultant short circuit current will be the same as for a symmetrical three phase short circuit.
- 26 -
LINE TO NEUTRAL
I a1
<
a
Positive sequence
Ia Z1
^ I a1 = Ia2
= I a0 = Ia/3
<
c b I a2
Z2 Negative sequence
<
I a0 Zero sequence
Z0
Again, the transformer is presumed to be unloaded before the fault, so that I b=Ic=0. Positive, negative
and zero sequence currents are all the same in this case, equal to one third of the phase current I a. Z1 and
Z2 are equal to the three phase short circuit impedance, as before, but now zero sequence impedance Z 0
also enters into the sequence network. If Z 0 is also the same as Z1 and Z2, the short circuit current will
again be the same as for a three phase symmetrical short circuit. That is approximately true for a two
winding transformer with the other winding either delta connected, or wye connected with the neutral
grounded. Another case will now be discussed.
A three winding transformer has a primary high voltage winding with isolated neutral, a delta connected
stabilizing (tertiary) winding and a secondary wye connected winding with a line to neutral fault
through an external impedance Ze.
The figure shows the three windings. Phase windings which are drawn above each other are on the same
core leg. For a one per unit fault current, the principle of balanced ampereturns on each core leg gives
other per unit currents, as shown.
- 27 -
I=2/3 1/3 H
I=1/3 T
I=1 Ze L
a b c
The critical phase is phase a, where the fault occurs. With I La=1, IHa=2/3 and ITa=1/3, MVAs for the three
windings must be specified accordingly, and an optional per unit impedance as the inverse of the per
unit short circuit current, calculated from the sequence network. Zero sequence impedance Z 0 is
approximately equal to the short circuit impedance ZLT between secondary and tertiary windings. With
the short circuit through an external impedance Ze, Z0 in the sequence network on the previous page
must be replaced by Z0+3Ze.
- 28 -
The Command Prompt window should be maximized and the size adjusted to fill the screen after right
clicking the top title bar. Cursor size small and letter size 12x16 pixels are recommended. If Command
Prompt goes into full screen mode by an application, it can be brought back with Alt-Enter.
Since many PC users are not familiar with Command Prompt, here are some hints and frequently used
commands. The commands are examples and may be modified in obvious manners. Large and small
letters are interchangeable.
Other commands:
C: Moves to unit C or another unit.
CD\ Changes to base directory.
MD GRAPHICS Makes directory GRAPHICS.
CD\GRAPHICS Changes directory to GRAPHICS, just below the base directory.
COPY OLD.INP NEW.INP Copies old file OLD.INP to a new file NEW.INP.
COPY /? Explains options available for command COPY.
REN OLD.INP NEW.INP Renames OLD.INP as NEW.INP.
DEL OLD.INP Deletes OLD.INP.
DIR *.INP Lists all files in the directory with extension INP.
DIR *.I?? Lists all files in the directory with three letter extension starting with I.
START NOTEPAD OUTPUT Invokes Windows program NOTEPAD with file OUTPUT.
START PLOTFILE.BMP Starts a standard Windows program to process the bitmap file.
PROGRAM FLD15 RECTANGULAR CORE TRANSFORMER LEAKAGE FLUX
LAYER LAST DIST. THICK- TERM. PAR. DIR. CU/AL SPACER BLOCKS
NO. SEGM. CORE NESS NO. GROUPS CUR. PITCH WIDTH
1.0 1.0 18.0 500.0 1.0 1.0 -1.0 CU 103.0 40.0
2.0 2.0 18.0 500.0 2.0 1.0 1.0 CU 103.0 40.0
3.0 3.0 18.0 500.0 1.0 1.0 -1.0 CU 103.0 40.0
THE FIELD IS ASSUMED TO BE FLAT ALONG THE STRAIGHT PARTS OF THE COILS,
AXI-SYMMETRIC AROUND THE CORNERS. REACTANCE AND EDDY CURRENT LOSSES ARE
CALCULATED FROM WEIGHTED AVERAGES. HOWEVER, FORCES ARE ONLY CALCULATED FOR THE
STRAIGHT PARTS AS NEWTON PER METER LENGTH PERPENDICULAR TO THE PLANE.
LAYER NUMBER 1
DC LOSS, KW 14.067
EDDY CURRENT LOSS
KW DUE TO VERTICAL FLUX 0.065
KW DUE TO HORIZONTAL FLUX 6.631
KW TOTAL 6.697
PER UNIT, AVERAGE 0.4760
PER UNIT, MAXIMUM 1.7701
OCCURS BETWEEN
X-MIN X-MAX Y-MIN Y-MAX
196.6 214.4 127.4 140.0
FORCES AT PEAK SHORT CIRCUIT CURRENT, NEWTON/METER
MAX. ACCUMULATED VERTICALLY 842715.2
OCCURS IN SEGMENT NO. 1
ON UPPER SUPPORT 0.0
ON LOWER SUPPORT 842258.9
FLUX LINKAGE, WB/M REFERRED TO ONE TURN -0.00821302
LAYER NUMBER 3
DC LOSS, KW 14.067
EDDY CURRENT LOSS
KW DUE TO VERTICAL FLUX 0.066
KW DUE TO HORIZONTAL FLUX 6.613
KW TOTAL 6.678
PER UNIT, AVERAGE 0.4747
PER UNIT, MAXIMUM 1.7531
OCCURS BETWEEN
X-MIN X-MAX Y-MIN Y-MAX
196.6 214.4 400.0 413.5
FORCES AT PEAK SHORT CIRCUIT CURRENT, NEWTON/METER
MAX. ACCUMULATED VERTICALLY 841794.9
OCCURS IN SEGMENT NO. 3
ON UPPER SUPPORT 841193.4
ON LOWER SUPPORT 0.0
FLUX LINKAGE, WB/M REFERRED TO ONE TURN -0.00821637
TERMINAL NUMBER 1
DC LOSS, KW 84.404
EDDY CURRENT LOSS, KW 40.124
PER UNIT 0.4754
PERCENT DEVIATION, VOLTS/TURN 0.000
LAYER NUMBER 2
DC LOSS, KW 21.917
EDDY CURRENT LOSS
KW DUE TO VERTICAL FLUX 0.128
KW DUE TO HORIZONTAL FLUX 38.063
KW TOTAL 38.191
PER UNIT, AVERAGE 1.7425
PER UNIT, MAXIMUM 5.4253
OCCURS BETWEEN
X-MIN X-MAX Y-MIN Y-MAX
196.6 214.4 343.6 370.0
FORCES AT PEAK SHORT CIRCUIT CURRENT, NEWTON/METER
MAX. ACCUMULATED VERTICALLY 859386.6
OCCURS IN SEGMENT NO. 2
ON UPPER SUPPORT 0.0
ON LOWER SUPPORT 0.0
FLUX LINKAGE, WB/M REFERRED TO ONE TURN 0.00876709
TERMINAL NUMBER 2
DC LOSS, KW 65.752
EDDY CURRENT LOSS, KW 114.573
PER UNIT 1.7425
PERCENT DEVIATION, VOLTS/TURN -0.024