Fault Level Calculation For Pragati Maidan

Route Length Description Route Proposed Cable Size No of Resistance p.u. Reactance p.u. Impedance Transformer Total Falt Fault Short Circuit
Length(M) Runs value value of cable Impedance impedance MVA KA Capacity(KA)

Main LT Panel and MDB 20 3.5x400 Sq. mm. 3 0.1023 0.198 0.07 0.135 0.240 4 4.240 11.79 16.41 37.6
MDB and S&T UPS Panel 70 3.5x95 Sq. mm. 2 0.411 4.176 0.074 0.752 4.243 4 8.483 5.89 8.20 8.93
Essential Power Panel & 70 3.5x95 Sq. mm. 2 0.411 4.176 0.074 0.752 4.243 4 8.806 5.68 7.90 8.93
S&T UPS
MDB and Water Pump 50 3.5x50 Sq. mm. 1 0.821 11.918 0.078 1.132 11.971 4 16.211 3.08 4.29 4.7
Panel
MDB & Fire Pump Panel 50 3.5x95 Sq. mm. 1 0.411 5.966 0.074 1.074 6.062 4 10.302 4.85 6.75 8.93
MDB & Essential Power 15 3.5x300 Sq. mm. 2 0.13 0.283 0.071 0.155 0.323 4 4.562 10.96 15.25 28.2
Panel
MDB & Escalator 15 3.5x150 Sq. mm. 1 0.265 1.154 0.072 0.314 1.196 4 5.436 9.20 12.80 14.1
Main Lighting Panel & 15 3.5x150 Sq. mm. 1 0.265 1.154 0.072 0.314 1.196 4 5.758 8.68 12.08 14.1
Essential Power Panel
MDB & Main Lighting Panel 15 3.5x150 Sq. mm. 1 0.265 1.154 0.072 0.314 1.196 4 5.436 9.20 12.80 14.1
DG Set & DG Panel 15 3.5x400 Sq. mm. 1 0.1023 0.445 0.07 0.305 0.540 10 (DG 10.540 4.74 6.60 37.6
Impedence)
MDB & AC Panel 20 3.5x150 Sq. mm. 1 0.265 1.539 0.072 0.418 1.594 4 5.834 8.57 11.92 14.1
Essential Power Panel & 40 3.5x400 Sq. mm. 1 0.1023 1.188 0.07 0.813 1.439 10 (DG 11.979 4.17 5.81 37.6
DG Panel Impedence)
Essential Power Panel & 15 3.5x150 Sq. mm. 1 0.265 1.154 0.072 0.314 1.196 4 5.758 8.68 12.08 14.1
Elevator Panel
PA Panel & MDB 25 3.5x150 Sq. mm. 1 0.265 1.923 0.072 0.523 1.993 4 6.233 8.02 11.16 14.1