You are on page 1of 4

CALCULATIONS CORNER

Don't Leave Arc Flash


Protection to Chance—Part 3
A common misconception can lead to dire consequences
By Frank Mercede, RE., Mercede Engineering LLC

his is the final installment of a three-part se- motor disconnect and learned that the level of arc flash risk
ries on the importance of arc flash labeling of can be significant, depending on the amperage and class of
electrical equipment. In Part 1, which ran in the upstream fuses in the motor starter compartment and
the September 2011 issue, we considered the the length of the branch circuit conductors running from the
low-level task of taking measurements within fuses to the safety switch. In Part 2, which ran in the October
a non-fused safety switch that serves as a local 2011 issue, we moved further upstream to a combination

I FUPS
TX-1
l,500kVA
13.2kV-
480Y/277V
|Z| =5.75%

Main switchboard SWBDO

LP2B
Í Í Í Í

Ml M2 M3 M4 M5
/

CP3A
r r
CP3B CP3C CP3D

Fig. 1. One-lme diagram of sample commercial system.

CIO H S s M November 2011 • www.ecmweb.com


CALCULATIONS CÜRIMER >
Arc Flash Hazard Report of Main Switchboard Breakers
Bolted fault Arc fault Arc flash
Arc fault Upstream trip Arc time Incident energy
@480V @480V boundary (cal/cm^)
bus device (sec)
(kA) (kA) (in.)
26.734 11.908 2.371
SWBDO ^ —
M BO 26.734 14.002 0.1 42.2 5.3
Table 1. Results from arc flash calculations per IEEE Std. 1584.

Arc Flash Label Information of Main Switchboard Breakers


Incident energy Nominal rated
Arc flash boundary
Breaker Arc flash label at 18 in. line voltage Date of study
(in.)
(cal/cm^) (V)
L
480 04/16/11
105 480 04/16/11
105 480 04/16/11
)anger ' 105 r 480 04/16/11
1 )anger 480 04/16/11
1 105 1
Table 2. Note bow tbe extreme incident energy level applies to all compartments in this particular switchboard.

motor starter bucket of a motor control


center and learned once again that the
level of arc flash risk can defy expecta-
tions, depending on the instantaneous
setting of the upstream solid-state trip
unit and the feeder length to the motor
control center.
In this final installment, we focus
our attention on the main switch-
board in the example system shown in
Fig. 1 on page CIO. As we can see in the
Arc Flash and Shock Hazard
one-line diagram of Fig. 1, the 3-phase
electric service of the commercial fa-
cility is fed from the electric utility at
DO NOT WORK ENERGIZED
13.2kV and transformed to 480V via
a l,500kVA, dry-type, delta-grounded
wye main transformer (TX-1 ). The main
transformer is protected on the primary
105 incident Energy at 18 in.
side by fused switch FUPS. On the sec-
ondary side, the main switchboard 374 in. Arc Flash Boundary
SWBDO is composed of main secondary
breaker MBO and four feeder break-
ers (FBI, FB2, FB3, and FB4); all are
480VAC Nom. Rated Line Voltage
molded-case circuit breakers equipped
with solid-state trip units. The feeder
breakers serve a motor control center
04/16/11 Date of Study
(MCCl), two lighting panelboards
(LP2A and LP2B), a conveying system Label No. AF010-IVIEC-001002
switchboard (SWBD3), and induction
motor drive (M6). MCCl consists of Fig. 2. Sample of arc flash label for extreme incident energy level.
five combination motor starters with
fused disconnects for induction motors the lighting panelboards travels some and two short subfeeders travel from JB2
Ml through M5. The main feeder for distance from FB2 to a junction box JB2, to the main breakers MB2A and MB2B

C12 H S s M November 2011 • www.ecmweb.com


CALCULATIONS
of LP2A and LP2B, respectively. The four serves as the upstream trip device, then In conclusion, we hope that the
fused disconnects of SWBD3 feed the the incident energy level is much lower examples of this three-part series re-
integral, non-fused disconnects of the (5.3 cal/cm'), which corresponds to a inforce the importance of conducting
conveying system control panels (CP3A, Hazard/Risk Category of 2*. an arc flash study. This type of study
CP3B, CP3C, and CP3D). Based on Table 1, one may mistakenly will help you gather the information
Table 1 on page C12 presents the believe that the extreme incident energy needed to meet the arc Oash labeling
results of arc flash calculations per level applies only to the MBO compart- requirement of Sec. 130.3(C) of NFPA
IEEE Std. 1584 at main switchboard ment of main switchboard SWBDO. 70E-2009, Standard for Electrical Safety
SWBDO. Note that the results depend However, an explosion due to an arc in the Workplace.
on the upstream trip device that clears fault in a feeder breaker compartment Finally, keep in mind that an arc flash
the arc fault. Referring to Table 1, if could spread to all compartments of the study by itself is not a substitute for
primary fused switch FUPS serves as switchboard (because the switchboard electrical safety training and an ongoing
the upstream trip device for an arc fault of this example is not arc resistant in electrical safety program. These types of
at SWBDO, the incident energy level is construction) and render MBO inca- training courses and safety procedures
104.8 cal/cm^. This extreme incident en- pable of clearing the fault. Thus, the are still required for both in-house and
ergy level exceeds the upper limit of the extreme incident energy level applies to contracted workers who work on or near
highest Hazard/Risk Category 4 (i.e., 40 all compartments of the switchboard, as energized electrical equipment. EC&M
cal/cm'), and work on the switchboard shown in Table 2 on page C12. Figure
cannot proceed until it has been put 2 on page C12 provides a sample of an Mercede, P.E., is principal of Mercede
in an electrically safe work condition NFPA 70E-compliant arc flash label for Engineering LLC, based in Bryn Mawr,
per Article 120 of NFPA 70E. However, the extreme incident energy level noted Pa. He can he reached at fmercede@mer-
if the main secondary breaker (MBO) previously. cedeengineering. com.

CADDY CAT LINKS


Now Available in Colors!
CADDY® CAT LINKS, the technologically advanced
cable support system from ERICO, is now available
in six colors. These painted J-Hooks can be
used to more effectively blend into a building's
interior design or to identify various cable runs in
applications, such as security or call centers

• Innovative
• Versatile
• Time-saving X
• Economical

See for yourself how the versatile


CADDY CAT LINKS system can
simplify your next installation
1-800-252-2339 www.erico.com

Circle 24 on Reader Service Card or visit freeproductinfo.net/ecm

C14 E C f i M November 2011 • www.ecmweb.com


© 2011 Penton Media, Inc. All rights reserved.

You might also like