Professional Documents
Culture Documents
CONTRACT PS
signed 28.02.2012
Released Vogt, Thorsten IC RL CS&TS TS PM
Thorsten Vogt
signed 28.02.2012
Checked Altmann, Martin IC SG RE EN TP SE
Martin Altmann
signed 28.02.2012
Author Dietrich, Klaus IC RL CS&TS TS EN EP
Klaus Dietrich
Revision Log
The reproduction, transmission or use of this document or its contents is not permitted
without express written authority. Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model or design, are reserved.
Table of Contents
1 SCOPE......................................................................................................... 5
1 Scope
The construction of railway installations generally requires a concept for earthing and bonding
including provisions for lightning protection as a basic document for the involved parties in the
project. This is important particularly for modern systems with high traction currents and the
extensive use of electrical energy for many purposes.
The objectives for earthing and bonding are:
The safety of persons:
The safety of persons is characterised by the value of the touch voltage.
The protection of installations:
Damage of installations may arise from overheating of conductors, by arcing and by
electrical corrosion.
The intended operation of the system:
For the intended operation of the system the aspect of electromagnetic compatibility
(EMC) has to be considered too.
This volume gives on overview of the earthing and bonding measures to be implemented by
Civil Works for KOLKATA METRO RAIL as a precondition for a consistent earthing design. The
principles need to be considered by Civil Works for their design, delivery and installation of
structures.
For general information please refer to Overall Earthing Concept of the KOLKATA METRO
RAIL.
Therefore, the earthing conductors embedded in concrete are an essential part of the earthing
system of the railway and need careful design and installation.
Furthermore, selection of earthing components with different materials shall consider the
danger of electrochemical corrosion.
In case of insulating layers like waterproof membranes are applied to the structure an adequate
solution must be installed below this insulating layer to ensure electrical contact to the soil. This
additional earthing electrode must be connected to the structure earth. Refer to 4.7.
If the cross section of 200 mm² can not be provided by a single rod (diameter less
than 16mm) multiple rods may be used in parallel.
The cross-section of earthing wires is subject of detailed design and will be identified
in the related design drawings
All embedded earthing conductors must be covered by at least 5 cm of concrete for
corrosion protection.
Conductors, which are part of an earth electrode, shall not be covered by more than
10 cm of concrete. That is necessary to ensure sufficient contact to the soil.
Earthing conductors from steel and copper shall not touch each other directly to avoid
galvanic corrosion. Connections inside of the concrete between copper and steel can
be made by thermal welding (Cadweld, Thermoweld), the welding point and the whole
copper cable shall be fully insulated from concrete by plastic tape wrapping or similar.
The down conductors inside of walls have to be connected to the reinforcement at
intervals of 400 mm by means of wire wrapping.
Earthing conductors in soil usually form a part of an earth electrode. Therefore table 7 of
IEC/EN 62305-3 applies.
The protection level defines the distance between down conductors. Corners of buildings are
the preferred locations of down conductors. Additional down conductors will be required in the
following typical intervals:
All earthing conductors embedded to concrete including lightning down conductors have to be
connected to the reinforcement at intervals of 40 cm by means of wire wrapping.
The exact locations of down conductors will be subject of detailed design.
2.8 Welding
Figure 2-1 shows examples for welded connections. The minimum length of two opposite
welded seams is 50 mm. To ensure a fully electrical conductive length of 50 mm, a welding
length of at least 55 mm is recommended. In case of single side welding a minimum length of
the seam of 100 mm is required.
2.9 Terminals
Terminals for the connection of embedded parts to other parts of the earthing systems will be
required. This can be:
copper cables exothermic welded to the reinforcing rods, the cables shall be insulated
for mechanical protection especially where leaving the concrete, the welding zone
including all bare copper parts shall be protected by plastic tape wrapping
flat or round conductors made from hot galvanised steel
specific designed terminals for bolted connections made from hot galvanised steel or
stainless steel These terminals are furnished with a thread inside for 1 bolt M16
fixation elements like C-shaped rails from hot galvanised steel (“Halfen-Rails”),
provided they are welded to the reinforcement before pouring the concrete.
In any case, the requirements of corrosion protection have to be considered to achieve reliable
earthing connections. Inside of buildings and other closed structures hot galvanised steel may
be used. For connections facing outdoor conditions stainless steel terminals shall be used only.
Earthing terminals shall be welded to the reinforcing rods dedicated for earthing according to
the welding requirements above. The earthing terminals shall be accessible in a height from 30
to 50 cm above concrete floor or final ground level.
Terminals are required at the following locations (at minimum, but not limited to):
connection of embedded earthing wires to other parts of the earthing system
connections between different parts of concrete (prefabricated parts, expansion joints)
connection from structure earth to steelwork
connection from structure earth to lightning air termination
connection from structure earth to large metallic parts (elevator guide rails, escalator
support frame, handrails, large E&M equipment like AFC ticket vending machine and
access gate etc.)
connection from structure earth in technical rooms (up to 30 m² 2 terminals, above 4
terminals)
connection from structure earth to neighbouring buildings or to the line, one terminal at
each of the four corners of the building
connection from structure earth to additional earthing electrodes for power substations
on each of the four corners of the building
stainless steel
cylinder Ø 38 mm x
45 mm long with
thread M16
stainless steel plate
50x50 mm, 4 mm thick,
for fixation at the
formwork and as
contact surface
The total cross section of steel bars per track shall be 800 mm² for light rails and 1600 mm² for
metro systems. This corresponds to 4 or 8 steel rods Ø16 mm per track.
Earthing terminals have to be provided at locations, where gaps in the continuously welded
longitudinal bars are necessary (expansion joints) and in regular distances of 50 m to enable
earthing of equipment. The following figure shows an example.
Terminal for
connection of sections
50 m
track slab
earthing rebar
(stray current collector)
welded connection
cross-connection
(at beginning and end of track slab segment)
The detailed arrangement of earthing connections in the track bed depends on its reinforcement
construction. In general, the topmost layer of reinforcement shall form the earthing and stray
current control system.
At least two redundant jumper connections shall be provided at each expansion joints. Lost
connections will cause electrochemical corrosion of the reinforcement.
If continuity of the reinforcement including all jumper connections may not be guaranteed by
Civil Works it may be necessary for them to install an earthing cable which can bridge lost
connections so that a broken link will not interrupt the chain. Refer to 4.4 for details.
system.
3.5 Platforms
The voltage between the running rails and the local earthing system must be limited by a
voltage limiting device like e.g. a voltage fuse.
The protection of passengers against bridging between electrical equipment (e.g. escalator,
ticket vending machine) and train must be settled by clearances.
No earthed equipment shall be located in a distance of 2.5 m from the platform edge to avoid
bridging of train potential to earth by passengers.
Platforms shall be treated like workshops regarding accessible voltages for passenger comfort
according to chapter 7 of EN 50122-1. Therefore, the standing surface of passengers at the
platform edge shall be insulated in a width of 1.45 m at minimum. The insulation resistance
must be 20 kOhm/m2 at minimum in orientation to chapter 413.3 of IEC 60364-4-41.
Direct bonding of all outgoing and incoming metallic installations at the inside of
building boundary like e.g. cable armour and pipes of water, gas etc.
For this purpose earthing terminals must be provided for these connections.
The locations of earthing terminals will be defined in the related drawings during detailed
design.
Service utilities in parallel to or crossing the tracks, which have applied active corrosion
protection, the requirements for separation or additional insulation have to be elaborated in
coordination with the owner of the utility.
4.1 Tunnels
The reinforcement of the tunnel forms the earthing system of tunnel sections.
For tubing tunnels with prefabricated concrete sections, the embedded reinforcement can not
be used as structure earth. Here as shown in Figure 4-1 the trackbed reinforcement provides
the structure earth. The large surface of the track bed located on top of the prefabricated
concrete parts provides sufficient low resistance to earth as long as the surrounding soil has
sufficient conductivity.
The earthing rods of cuttings are the same as in the lower part of tunnels or in the viaduct
segments with plinth. The following figure shows the principle.
4.3 Viaducts
The reinforcement of the viaduct forms the structure earth of viaduct sections. Therefore the
reinforcements of single segments have to be electrically interconnected and the dedicated
earthing rebars shall be welded together via cross connections. Figure 4-3 shows the schematic
earthing connections of viaducts. The foundations of the piers form the earth electrodes for
viaducts. The reinforcement of the foundation shall be electrically connected to the
reinforcement of the piers and the viaduct segments.
Tunnel shell
rail to structure (tubing segments)
trackbed
insulation earthing rod in upper layer
Side View
Tunnel shell
(tubing segments)
It shall be ensured that there is no electrical connection between the return circuit and the
reinforcement of the reinforced track substructure or the earth wire. This shall be proven by
measurement, see 3.1 and 5.6.
Reinforcement in the
substation floor must be Main Earthing Terminal
connected to the main Structure earth of the station must be connected
earthing terminal! to the structure earth of the viaduct to ensure
continuity of the track substructure!!
SIEMENS
Earthing terminal
Revision : D
Infrastructure & Cities
Page 21 of 27
Date : 2012-02-24
Infrastructure & Cities
Figure 4-7
Arrangement of
earth wires in
underground
stations
Telecommunication
& Signalling Room
Down conductor for LPS
Earthing terminal
at each corner Bonding ring conductor
ground level
Structure earth
Earthing terminal
at each corner
welded
connection
Voltage grading grid
(Top layer of reinforcement)
Structure earth
Figure 4-9: Earthing & bonding of low voltage power supply rooms
4.10 Substations
Power supply stations shall as a minimum consider the earthing requirements for power supply
rooms of chapter 4.9. Additionally the substation building shall have a foundation earth
electrode with reduced grid size of 5x5 m.
In case of open air HV switchgear or similar parts separated from the substation building an
earthing grid must be installed in the soil to ensure equipotential bonding of all separated parts.
Further requirements for Power Substations will be derived from the studies prepared by the
power supply subsystem during the basic design phase.
In the depot and workshop area the return circuit shall be insulated against structure earth and
earth similar to the main line. The permanent accessible voltage generated by the railway
system must not exceed 60 V DC.
Potential differences between the structure earth of the workshop area and the return circuit
cause restrictions to operation and service activities. To avoid such restrictions, improve safety
and minimise stray currents at the same time the insulated return circuit shall be connected to
the structure earth exclusively in one centrally located point, accessible for inspection and
removable for measurement.
In order to avoid non-permissible touch voltages caused by the train operation on the main line
and to reduce stray currents the running rails of the depot and workshop area have to be
separated from the main line track system by insulating rail joint (IRJ).
For the purpose of redundancy two rail joints shall be installed in series within each running rail
at the entrance from the main line to the depot area. The distance of the 2 IRJ in each rails shall
be appropriate with respect to strength of running rail (to be determined by trackwork) and shall
not be greater than the distance between two bogies of one single car. No stop signal shall be
located within one train length at both sides of the insulated rail joints to avoid a prolonged
bridging period of the rail joints.
As the return circuit in the depot area is floating while in the workshop area it is earthed another
IRJ shall be installed in each rail in front of the workshop building. Again the position shall avoid
locations of operational train stops to not bridge the rail joints longer than necessary.
To further reduce stray current transfer between depot area and mainline the structure earth
shall also be separated between the two. The IRJ between mainline and depot shall located
near to or in line with the structure earth separation.
To avoid by-passing of IRJ by the return cables mainline, depot and workshop areas shall be
supplied from separate traction rectifiers. For backup purposes temporary feeding of one part
from another rectifier shall be allowed for a limited period of time.