Protection System A

Generator Protection Relay Test Report


. .

Device Information:
Model: MiCOM P344 Mfc: Schneider Electric, France
Serial no.: P344312E1N0368K Version: 3.4.1

Test Module
Name: OMICRON Quick CMC Version: 3.20
Test Start: 31-Jan-2019 12:02:32 Test End: 31-Jan-2019 12:23:17
User Name: Manager:
Company:NWPGCL

Generator Data:
Rated apparent Power 225 MVA
Rated active Power 180 MW
Rated PF 0.8
Rated Voltage 15 KV
Rated Current 8660 A
Rated Frequency 50 Hz
Xd 2.55
X`d 0.25
X``d 0.19

CT & PT Data:
Phase Side CT 10000/1 A
Neutral Side CT 10000/1 A
Terminal Side PT 15/Γ3:0.1Γ3
Bus Duct Side PT 15/Γ3:0.1/Γ3
Test Results
Title: Stability

.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct I L1 866.0 mA 0.00 ° 50.000 Hz
I L2 866.0 mA -120.00 ° 50.000 Hz
I L3 866.0 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.866A 0.00° +90°

I L3 I(1)-2

I(1)-1 I L1
180° 0°

I L2 I(1)-3

1.0 A -90°
I L2 0.866A -120.00°
I L3 0.866A 120.00°
I(1)-1 0.866A 180.00°
I(1)-2 0.866A 60.00°
I(1)-3 0.866A 300.00°

Binary Inputs
Name Slope Time
Trip 1
Start 0
Overload 0
1. Title: Generator Differential Protection (87G)

Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)
Phase Setting Delay
Any Is1=10%*Irated=0.087A No delay
K1=0%

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°

I(1)-2

I(1)-1
180° 0°

I(1)-3

100.0 mA-90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.090A 180.00°
I(1)-2 0.090A 60.00°
I(1)-3 0.090A 300.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.040s
Start 1->0 n/a
Overload 1->0 n/a
2. Title: Overvoltage Protection 59.1 (Definite Time O/V)
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)
Phase Setting Delay
Any V>1 =120V (P-P) 2.0 s

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 69.40 V 0.00 ° 50.000 Hz
V L2-E 69.40 V -120.00 ° 50.000 Hz
V L3-E 69.40 V 120.00 ° 50.000 Hz
I L1 866.0 mA 0.00 ° 50.000 Hz
I L2 866.0 mA -120.00 ° 50.000 Hz
I L3 866.0 mA 120.00 ° 50.000 Hz

Generator Settings
V L1-E 69.400V 0.00° +90°

V L3-E
I L3

V L1-E
I L1
180° 0°

V L2-E
I L2

80.0 V -90° 1.0 A


V L2-E 69.400V -120.00°
V L3-E 69.400V 120.00°
I L1 0.866A 0.00°
I L2 0.866A -120.00°
I L3 0.866A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 2.039s
Start 1->0 n/a
Overload 1->0 n/a
3. Title: Negative Phase Sequence Protection 46.2
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Three phase I2>2= 0.08*Irated=0.069 A TMS=7.5

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 0.000 V 0.00 ° 50.000 Hz
V L2-E 0.000 V -120.00 ° 50.000 Hz
V L3-E 0.000 V 120.00 ° 50.000 Hz
I L1 210.0 mA 0.00 ° 50.000 Hz
I L2 210.0 mA 120.00 ° 50.000 Hz
I L3 210.0 mA -120.00 ° 50.000 Hz

Generator Settings
V L1-E 0.000V 0.00° +90°

I L2
I L1
180° 0°
I L3

115.5 V -90° 300.0 mA


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.210A 0.00°
I L2 0.210A 120.00°
I L3 0.210A -120.00°

Binary Inputs
Name Slope Time
Trip 0->1 36.007s
Start 1->0 n/a
Overload 1->0 n/a
4. Title: Overcurrent Protection 51
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any I>=1.5*Irated=1.3 A 3.0 s

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 1.300 A 0.00 ° 50.000 Hz
I L2 1.300 A -120.00 ° 50.000 Hz
I L3 1.300 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E
I L3

V IL1-E
L1
180° 0°

I L2
V L2-E
60.0 V -90° 1.5 A
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 1.300A 0.00°
I L2 1.300A -120.00°
I L3 1.300A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 3.048s
Start 1->0 n/a
Overload 1->0 n/a
5. Title: Voltage Controlled Overcurrent Protection, 51V
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any I>1=1.3A, V<1=70V 200 ms

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 40.40 V 0.00 ° 50.000 Hz
V L2-E 40.40 V -120.00 ° 50.000 Hz
V L3-E 40.40 V 120.00 ° 50.000 Hz
I L1 1.300 A 0.00 ° 50.000 Hz
I L2 1.300 A -120.00 ° 50.000 Hz
I L3 1.300 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 40.400V 0.00° +90°

I L3
V L3-E
V L1-E
I L1
180° 0°

V L2-E
I L2

50.0 V -90° 1.5 A


V L2-E 40.400V -120.00°
V L3-E 40.400V 120.00°
I L1 1.300A 0.00°
I L2 1.300A -120.00°
I L3 1.300A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 3.045s
Start 1->0 n/a
Overload 1->0 n/a
6. Title: Reverse Power Protection (High Setting and Trip) 32.1
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Three phase -P>=0.05*Γ3*Vrated*Irated= 0.5 s
7.5W

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 130.0 mA 180.00 ° 50.000 Hz
I L2 130.0 mA 60.00 ° 50.000 Hz
I L3 130.0 mA 300.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E I L2

I L1 V L1-E
180° 0°

V L2-E I L3

60.0 V -90° 150.0 mA


V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.130A 180.00°
I L2 0.130A 60.00°
I L3 0.130A 300.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.528s
Start 1->0 n/a
Overload 1->0 n/a
6.1 Title: Reverse Power Protection (High Setting and Trip) 32.1
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 45.00 mA 180.00 ° 50.000 Hz
I L2 45.00 mA 60.00 ° 50.000 Hz
I L3 45.00 mA 300.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E I L2

I L1 V L1-E
180° 0°

V L2-E I L3

60.0 V -90° 50.0 mA


V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.045A 180.00°
I L2 0.045A 60.00°
I L3 0.045A 300.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.513s
Start 1->0 n/a
Overload 1->0 n/a
7.0 Title: Under frequency Protection 81.3 (No blocking, GCB open)

.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any F<3=45.75 Hz 0.15 s

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 45.750 Hz
V L2-E 57.74 V -120.00 ° 45.750 Hz
V L3-E 57.74 V 120.00 ° 45.750 Hz
I L1 0.000 A 0.00 ° 45.750 Hz
I L2 0.000 A -120.00 ° 45.750 Hz
I L3 0.000 A 120.00 ° 45.750 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E

V L1-E
180° 0°

V L2-E
60.0 V -90° 32.0 A
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 6.453s
Start 1->0 n/a
Overload 1->0 n/a
8. Title: V/Hz protection 24G
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any V/Hz>1=2.0 V/Hz TMS=0.2s

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 45.700 Hz
V L2-E 57.74 V -120.00 ° 45.700 Hz
V L3-E 57.74 V 120.00 ° 45.700 Hz
I L1 0.000 A 0.00 ° 45.700 Hz
I L2 0.000 A -120.00 ° 45.700 Hz
I L3 0.000 A 120.00 ° 45.700 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E

V L1-E
180° 0°

V L2-E
60.0 V -90° 32.0 A
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.065s
Start 1->0 n/a
Overload 1->0 n/a
8.1 Title: V/Hz protection 24G
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 68.74 V 0.00 ° 50.000 Hz
V L2-E 68.74 V -120.00 ° 50.000 Hz
V L3-E 68.74 V 120.00 ° 50.000 Hz
I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 68.735V 0.00° +90°

V L3-E

V L1-E
180° 0°

V L2-E

80.0 V -90° 32.0 A


V L2-E 68.735V -120.00°
V L3-E 68.735V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.782s
Start 1->0 n/a
Overload 1->0 n/a
8.2 Title: V/Hz protection 24G
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 65.74 V 0.00 ° 48.000 Hz
V L2-E 65.74 V -120.00 ° 48.000 Hz
V L3-E 65.74 V 120.00 ° 48.000 Hz
I L1 0.000 A 0.00 ° 48.000 Hz
I L2 0.000 A -120.00 ° 48.000 Hz
I L3 0.000 A 120.00 ° 48.000 Hz

Generator Settings
V L1-E 65.740V 0.00° +90°

V L3-E
V L1-E
180° 0°

V L2-E

80.0 V -90° 32.0 A


V L2-E 65.740V -120.00°
V L3-E 65.740V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.669s
Start 1->0 n/a
Overload 1->0 n/a
9. Title: Minimal Impedance Protection 21
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any Z<1=11.72 Ohm 0.5 s

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 6.670 V 0.00 ° 50.000 Hz
V L2-E 6.670 V -120.00 ° 50.000 Hz
V L3-E 6.670 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 6.670V 0.00° +90°
I L3
V L3-E

V L1-E
I L1
180° 0°

V L2-E
I L2
8.0 V -90° 1.0 A
V L2-E 6.670V -120.00°
V L3-E 6.670V 120.00°
I L1 1.000A 0.00°
I L2 1.000A -120.00°
I L3 1.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.535s
Start 1->0 n/a
Overload 1->0 n/a
9.1 Title: Minimal Impedance Protection 21
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 11.55 V 0.00 ° 50.000 Hz
V L2-E 0.000 V -120.00 ° 50.000 Hz
V L3-E 0.000 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
V L1-E 11.550V 0.00° +90°

V L1-EI L1
180° 0°

15.0 V -90° 1.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 1.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.531s
Start 1->0 n/a
Overload 1->0 n/a
10. Title: Loss of Excitation Protection 40.1G
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any -Xa1=8.33 Ohm, Xb1=170 2.0 s
Ohm

Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 866.0 mA 30.00 ° 50.000 Hz
I L2 866.0 mA -90.00 ° 50.000 Hz
I L3 866.0 mA 150.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E
I L3 I L1

V L1-E
180° 0°

V L2-E I L2
60.0 V -90° 1.0 A
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.866A 30.00°
I L2 0.866A -90.00°
I L3 0.866A 150.00°

Binary Inputs
Name Slope Time
Trip 0->1 2.036s
Start 1->0 n/a
Overload 1->0 n/a
10.1 Title: Loss of Excitation Protection 40.1G
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 430.0 mA 51.00 ° 50.000 Hz
I L2 430.0 mA -69.00 ° 50.000 Hz
I L3 430.0 mA 171.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E
I L1
I L3
V L1-E
180° 0°

V L2-E I L2

60.0 V -90° 500.0 mA


V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.430A 51.00°
I L2 0.430A -69.00°
I L3 0.430A 171.00°

Binary Inputs
Name Slope Time
Trip 0->1 2.038s
Start 1->0 n/a
Overload 1->0 n/a
10.2 Title: Loss of Excitation Protection 40.1G
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 430.0 mA 128.00 ° 50.000 Hz
I L2 430.0 mA 8.00 ° 50.000 Hz
I L3 430.0 mA 248.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E
I L1
I L2
V L1-E
180° 0°

I L3
V L2-E
60.0 V -90° 500.0 mA
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.430A 128.00°
I L2 0.430A 8.00°
I L3 0.430A 248.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.530s
Start 1->0 n/a
Overload 1->0 n/a
10.3 Title: Loss of Excitation Protection 40.1G
.
Fault Calculator:
Table Input mode Parameters (All values are secondary)
Direct V L1-E 57.74 V 0.00 ° 50.000 Hz
V L2-E 57.74 V -120.00 ° 50.000 Hz
V L3-E 57.74 V 120.00 ° 50.000 Hz
I L1 866.0 mA 150.00 ° 50.000 Hz
I L2 866.0 mA 30.00 ° 50.000 Hz
I L3 866.0 mA 270.00 ° 50.000 Hz

Generator Settings
V L1-E 57.735V 0.00° +90°
V L3-E
I L1 I L2

V L1-E
180° 0°

V L2-E I L3
60.0 V -90° 1.0 A
V L2-E 57.735V -120.00°
V L3-E 57.735V 120.00°
I L1 0.866A 150.00°
I L2 0.866A 30.00°
I L3 0.866A 270.00°

Binary Inputs
Name Slope Time
Trip 0->1 0.529s
Start 1->0 n/a
Overload 1->0 n/a
11. Title: MV Bus Duct Earth Fault Protection 59NB.1
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Any VN>5=20V 1.0 s

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 22.00 V 0.00 ° 50.000 Hz
V L2-E 0.000 V -120.00 ° 50.000 Hz
V L3-E 0.000 V 120.00 ° 50.000 Hz
I L1 0.000 A -210.00 ° 50.000 Hz
I L2 0.000 A -330.00 ° 50.000 Hz
I L3 0.000 A -90.00 ° 50.000 Hz

Generator Settings
V L1-E 22.000V 0.00° +90°

V L1-E
180° 0°

30.0 V -90° 32.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.000A -210.00°
I L2 0.000A -330.00°
I L3 0.000A -90.00°

Binary Inputs
Name Slope Time
Trip 0->1 1.064s
Start 1->0 n/a
Overload 1->0 n/a
12. Pole Slip Testing.seq:
.
Relay Setting:
Irated= 8660/10000= 0.87A (Secondary)
Vrated= 100V (Secondary)

Phase Setting Delay


Three phase Za = (xT + xs) x P.U. x K = (0.132 + No delay
0.024) x 1 x 66.7 = 10.41 Ohm,
Zb = 2 x x’d x P.U. x K = 2 x 0.255 x
1 x 66.7 = 33.34 Ohm,
Zc = 0.9 x xT x P.U. x K = 0.9 x
0.132 x 1 x 66.7 = 7.93 Ohm (90%
xT)

Test Settings
State State 1 State 2 State 3 State 4 State 5
V L1-E 57.74 V 36.00 V 6.000 V 6.000 V 60.00 V
0.00 ° 0.00 ° 0.00 ° 0.00 ° 0.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L2-E 57.74 V 36.00 V 6.000 V 6.000 V 60.00 V
-120.00 ° -120.00 ° -120.00 ° -120.00 ° -120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
V L3-E 57.74 V 36.00 V 6.000 V 6.000 V 60.00 V
120.00 ° 120.00 ° 120.00 ° 120.00 ° 120.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I L1 1.000 A 2.000 A 2.000 A 2.000 A 2.000 A
10.00 ° 10.00 ° 50.00 ° 150.00 ° 140.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I L2 1.000 A 2.000 A 2.000 A 2.000 A 2.000 A
-110.00 ° -110.00 ° -70.00 ° 30.00 ° 20.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
I L3 1.000 A 2.000 A 2.000 A 2.000 A 2.000 A
130.00 ° 130.00 ° 170.00 ° 270.00 ° 260.00 °
50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
Bin. out 1 0 0 0 0 0
Bin. out 2 0 0 0 0 0
Bin. out 3 0 0 0 0 0
Bin. out 4 0 0 0 0 0
Max. State Time 1.000 s 250.0 ms 250.0 ms 250.0 ms 3.000 s
Trigger Logic
User interaction no no no no no
CMGPS trigger no no no no no
IRIG-B/PTP trigger no no no no no
Pulses / seconds 1 1 1 1 1
Delay after Tr. 0.000 s 0.000 s 0.000 s 0.000 s 0.000 s
On trigger jump to test no no no no no
end
+90° +90° +90° +90° +90°
Diagrams
180° 0° 180° 0° 180° 0° 180° 0° 180° 0°

115.5
-90°V
32.0 A 115.5
-90°V
32.0 A 115.5
-90°V
32.0 A 115.5
-90°V
32.0 A 115.5
-90°V
32.0 A

Comment
. .
Test Module
Name: OMICRON State Sequencer Version: 3.20
Test Start: Test End:
User Name: Manager:
Company:

Test Results
.
Time Assessment
Name Ignore Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
before
o
Assess: + .. Passed x .. Failed o .. Not assessed

State 1 State 3 State 5


State 2 State 4

C M C 3 5 6 V A /V

60
40
20
0
-2 0 0 .5 1 .0 1 .5 2 .0 2 .5 3 .0 3 .5 4 .0
t/s
-4 0
-6 0
-8 0

V L 1 -E V L 2 -E V L 3 -E

CMC356 I A/A

2.0

1.0

0.0
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
t/s
-1.0

-2.0

-3.0
I L1 I L2 I L3
Bin. out 1
Bin. out 2
Bin. out 3
Bin. out 4

0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0


t/s

Trip

0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 t/s

.
Cursor Data
Time Signal Value
Cursor 1 0.000 s <none> n/a
Cursor 2 4.750 s <none> n/a
C2 - C1 4.750 s n/a

.
Event recorder
Time Type Signal name Slope

Comment

Summary
18 tests passed, 1 tests failed, 0 tests not assessed 94.74% passed
Test failed

Tested by Witnessed by