Foamed Plastics
26 Mar, 2013
Sao Paulo CD
i
PMMA barrier
plate at balcony (photo: Hiroshima FD
CCTV----TVCC Fire
in Beijing, midnight 9 Feb 2009
cause of fire:
fire works
cladding:
Zn-Titan panel
cored by XPS foam
outlook of burning
behavior
melting down of
XPS
reaction of panel
with metallic
colored flame
damaged
curtain wall
composeded
by PSWP
Meeting of Global COE Program, Tokyo University of Science, 7 December 2010
SWP (Al+PEcore)
Component: fluororesin coated aluminum plate cored with
low density poly- ethylene foam
・Characteristics: smooth surface, lightweight, easy cutting, anti-
condensation, thermal insulation, sound absorption, high
durability by adopting Al and fluororesin coating
・Hazardous: melting point of Al 658℃、pilot ignition point of
polyvinylidene fluoride 240℃、much toxic gasses and dense
smoke, long flame travelling upwards, extinguishing water
rebounded by metal panel W
polyethylene
service coating
aluminum sheet
primer (note from Prof. Ohmiya)
11:20 ? Fire outbreak
11:30 119 recognition
11:36 Arrival of Fire Engine
11:44 Rescue and lead evac-
uation
12:10 10 survived by snorkel
13:00 9 on roof survived by
helicopter.
13:02 Fire suppressed at the
room of fire origin
18:48 All fire suppressed
7
Glass Windows Located in a Curtain Wall
8
Fire Stop between the Stories
90 cm spandrel of Fire-resistive
Performance between the
windows located in different
floors.
Additionally,
Opening Protective Assembly:
Wired Glass.
Risk consideration
Definition of Terms around Risk
• harm: direct or indirect health damage to person
• hazard: potential of danger
• hazardous situation: exposed to hazard
• hazardous event: situation continuing to danger
• risk: combination of probability with severity
• residual risk: risk after taking protective measures
• protective measures: various mitigating activities
aimed to minimizing tolerable risk
• tolerable risk: socially accepted risk
• safety: situation free from unacceptable risk
• intended use: usage following makers’ guidance
• reasonably foreseeable misuse: unforeseen use of
NBK person Shinichi Sugahara 13
Impact
Risk Potential
Heavy Explosion of Nuclear
of disasters Power Plant
Building Fire by SWP
Little accidents
Car Accidents
Middle Daily Accidents
Slight
Frequency
Middle
Slight
Slight Heavy
Middle
Heavy
Amount of Damage
Vector of Hazard Map
Level of Standard
fundamental wide-ranging individual
ISO 6241, CPD ISO2394, ENV1991-1 BSL
Area of Adoption
global
regional
Authorized Standard
performance together prescriptive
(ISO 2394) (BSL) (FSL)
metal siding
ceramic siding
insulation
fire covering
metal siding
花あかり 東山魁夷
Performance design for SWP
guideline:certification, agreement
fire severity
descriptive -------------------
response
(750℃) etc. non-combustibility
fire safety
quasi-non-comb.
bldg.
fire retardant
rate of damage
design fire verification
of anti-heat transfer
escape safety anti-flame leakage
Fire growth rate etc.
Efficiency of (fire compartment)
exhaustion fire resistivity
Fire endurance etc.
time etc. performance
H”
n=w / (H/2)
w 窓幅、H 窓高
Relationship
COE
between opening figure and flame
Shinichi SUGAHARA 21
tr
Windows and Spandrels Located
in a Bearing Wall
Effectiveness of stopping upward fire spread
i
length of spandrel X1 = length of eve 0.5X1
22
Fire Protection for Curtain Wall
1. Fire Stop between the Stories
Non-combustible material should
be installed between curtain
wall and floor.
3. Spandrels
90 cm or more
Fire-resistive Performance
(社)カーテンウォール・防火開口部協会
カーテンウォール耐火設計指針
23
Fire Protection for Curtain Wall
2009-4-14 Nikkei
Architecture
24
Opening Protective Assembly
(Fire Door)
Integrity:20 minutes
Opening Protective
Assembly
Wired Glass
Integrity:60 minutes
Specified Opening
Protective Assembly
Steel Door
25
Opening Protective Assembly
(防火設備)
26
Facarde test apparatus
and
wood exterior cladding
subway in Osaka
Remodeled school fire
test
2012/11/25Mikuriya
Gero city
1F⇒2F(80min)
3F(89min)
Full 木造校舎実大火災実験
scale fire test of
wooden school つくば市国総
2012/2/22 bldg by Mlit
2012/2/22
研
1:15collapse
1:15中央部崩落、2hr全焼
of central part、
Modernization of UA, Dubai, Abudabi
New Test Methodology
Under Development (BRI)
31
Metal Façade cored by Plastics
joint work of TUS with Middle
East countries
④ ⑤
① ② ③ ⑥
photo1 full scale exterior fire test No.1 photo2 full scale exterior fire test No.2
(sandwich panel cored by combustible ) (sandwich panel cored by fire retardant )
(at Dubai Exova) (at Dubai Exova)
Opening
2000 x 2000 mm
Fire source: wooden crib or gas burner, THR 4500 MJ – 30 min, peak rate
3+-0.5 MW
Proposed by EXOVA MIDDLE EAST (Fire test body)
Warrington Fire Exova, Dubai
Fuel for testing
Wood Crib:5MW
recent fire accidents developed
by plastic cored SWP
where when Suppression Main damage
Time
Ichon, Jan, About 8 hours Death 40, injured
Korea 2008 10, burnout 30・103 m2
Aomor, Aug, About 6 hours Burnout 11 ・103 m2
Japan 2008
Inazawa, May, About 9 hours Death 1, injured 4,
Japan 2009 Burnout 5,300m2
Kobe, June, About 14 Death 1(fire fighter),
Japan 2009 hours Burnout 3,500m2
PSWP Fire in Tokyo, May 13, 1977
• place: 1-7-5 Tatsumi, kouto-ku, Tokyo
• company: shinkoh kairiku Transport, Tatsumi
branch
• fire outbreak: about 14:20
• FD recognition: 14:22 by 119
• suppression: 15:47
• put out: 17:08
• burnout: 337m2(1st fl.), 63m2 / 337m2 (2nd fl.)
• building: quasi-fire resistive, storage with rice
damaged 220t / 650t
• injured: fire fighter 16, clerk 5
• phenomena: deflagration with dull sound “bo,
bo” during a few seconds
before fire occurrence, an insulation door was under
installation by welding works. heated particles by
welding touched and burn spray-up polyurethane
foam through deep inside its own body.
Tatsumi storage
vertical distance
upward from lintel
horizontal distance
from window to
exterior direction
height from neutral
zone to upside of
window
in case of free space
above the window
b-h: in case of existing
wall upper side from
window lintel as shown
below
(square window)
where,
n=2xwidth/height
Insulated
cladding
How to be
heated
*Pas/fail criteria:
1) No ignition of window curtain at the
2nd floor,
2) Maximum allowable room
temperature at the 2nd floor: 180OC,
3) No further upward flame spread from
the 2nd floor,
4) No lateral flame spread than 1.5m
and
5) Panel shall not fail/fall.
Testing Facility for evaluating upward fire spread on Façade
Hungary
Méretek cm-ben
Méretek cm-ben
+ 285
20
210
90
Megfigyelõ tér
265
Megfigyelõ tér
480
460
130
+ 627
400
20
24 24 24 24 24
10
10
20
20
50
100
100 100
10 50 50
24 24 24 24 24
100
322
50 1-4 Megfigyelõ tér
5-8
120
10
9-12 50 50
13-16
VI V + 285
± 0,00
90
50
IV III
130
20
20
50
210
90
II I
50
3 5 2,4
Tûztér
130
200
120
50 50
1
265
480
2 4
1,50
Tûztér
50 1,50 5
150
150
0,00
100
1,50
1 3
120
120
50
50
50
30
100
20 180 20 400 20 180 20
30 840
480 90
100
Jelölés:
- a hõelemek jele
- a kiegészítõ sugárzásmérõk jele 50 50
2. ábra: A vizsgálóberendezés /modellépület/ (függõleges metszet) 1. ábra: A vizsgálóberendezés /modellépület/ (vízszintes metszetek)
Insulated
panel test
(The Univ. of insulated cladding(mortal+PS) 15min after
Tokyo,1980)
PS melting
fire-cut by
by flaming
insulation
insulation works
fire source
3-3 cribs(2x3cm)
by 20ml alcohol 5 sec 10 sec
30cm
opening (10x30cm)
Fire Test
of
Foam
Plastics
1984
at Fuji
by K.K
Lab.
cribs for
origin
phenol
foam
effective
6min 9.5min phenol foam
Fire protection of curtain
wall
・External wall composed with
spandrel and existing within
catch fire area should be 1 hour,
not existing catch fire area 30
minutes
・External wall would be different
from curtain wall, but should be
fire protective.
Curtain wall with 60mm slim sash by using face measure method
outside
outside curtain wall
view
view *spandrel should be
fire resistance spandrel
structure
opening
glass
mullion
mullion
spandrel
transom
fire resistive
board
inside mullion
view supporting
angle
rock-wool
fire resistive
spray
board
floor
fire resistive
board
New intermediate scale façade test
--- being developed in Japan as JIS
1820
2,730
Façade Specimen
⑤ 2,500
④ 2,000
③ 1,500
Fire Chamber
② 900
4095
① 500
910
Opening
455
455 910 455
Fire source : 600kW- 20min
cladding
lightning
ellipse ling
opening
wall
inner skin
floor panel
opening
stairwell
basement
wall and
cross section floor
Glass fiber
reinforced
unsaturated
polyester plate
is flammable,
which might be
necessary to
be fire retardant.
However, if
possible to check !
attain fire safety
fire safety
by performance-
based design. *********
This is the case. ・quick escape
・not burn
adjacent
bldg.
不燃材料:20分、8MJ/m2、200kW/m2(10秒以上継続)
発熱量・速度の測定 準不燃 :10分、以下同じ
難燃材料: 5分、以下同じ
*ガス有害性試験必要:基材(不燃200g/m2,準不燃・
難燃100,石膏ボード等400を超える場合)
Specimen
Sandwich Metal
Panel cored by
Urethane Foam
or Phenol Foam
flame retardant
plywood
Results
all specimens
would not
available in a
condition of
enclosed space
composite materials
matrix and reinforcement
Enforcement 107
No.1 fire endurance time to prevent deformation, melting, broken
No.2 wall, floor
No.3 exterior wall, roof
investigation ・ perception・
analysis discovery
inherent intuitive
P
traditional prescription D performance innovative
S
popular
A individual
succession challenge
Shinichi Sugahara