technical data

air conditioning systems


CMSQ-A7W1B
technical data

air conditioning systems


CMSQ-A7W1B
• Outdoor Units • R-410A • CMSQ-A7W1B

TABLE OF CONTENTS
CMSQ-A7W1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Selection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 19


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

8 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

9 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

10 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fixation and foundation of units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

12 Refrigerant pipe selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

13 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

• Split Sky Air • Outdoor Units 1


• Outdoor Units • R-410A • CMSQ-A7W1B

1 Features

i n y UB k 1 S W r 7 o At o 0- i d 1Q l t4S pu-M RCS•O Especially developed for light commercial applications (shops, • Maximum piping length up to 200m and level difference (outdoor unit
restaurants, small offices) where multi systems are required - indoor unit) up to 30m
• High efficiency: COP ranges up to 4.1 • Assymetric combination is allowed: combination of different indoor
• These outdoor units can be mounted easily on a roof, placed against units with different capacities is possible
an outside wall or can even be installed indoors • Individual control: up to 4 indoor units can be controlled individually

2 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

2 Specifications

2-1 TECHNICAL SPECIFICATIONS CMSQ200A7W1B CMSQ250A7W1B


Capacity Cooling kW 20.0 25.0
Heating kW 22.4 28.0
COP Cooling 3.03 3.71
Heating 3.86 4.10
Capacity range HP 8 10
Power input Cooling kW 6.60 6.74
(nominal)(50Hz) Heating kW 5.80 6.83
PED category Category II
Max n° of indoor units to be connected 4
Indoor index Minimum 100 125
connection Maximum 200 250
Casing Colour Daikin White
Material Painted galvanised steel
Dimensions Packing Height mm 1,855
Width mm 796 1,055
Depth mm 860
Unit Height mm 1,680
Width mm 635 930
Depth mm 765
Weight Unit kg 159 187
Packed Unit kg 182 217
Packing Material Carton
Weight kg 3.80 4.02
Material Wood
Weight kg 19.15 20.85
Material Plastic
Weight kg 0.215 0.265
Heat Exchanger Dimensions Length mm 1,483 1,778
Nr of Rows 54
Fin Pitch mm 2.00
Nr of Passes 8 18
Face Area m² 1.762 2.112
Nr of Stages 2
Tube type Hi-XSS (8)
Fin Fin type Non-symmetric waffle louvre
Treatment Hydrophylic and anti corrosion resistant
Fan Type Propeller
Quantity 1
Air Flow Rate Cooling m³/min 95 171
(nominal at 230V) Heating m³/min 95 171
Fan External static pressure Pa 50 Pa in high static pressure
Discharge direction Vertical
Motor Quantity 1 1
Model Brushless DC
Output motor W 350 750
Compressor Quantity 1
Motor Quantity 1
Model Inverter
Type Hermetically sealed scroll compressor
Speed rpm 6,300 7,980
Motor Output kW 2.8 3.8
Crankcase W 33
Heater
Cooling Standard Min °CDB -5.0
Operation Range Cooling Max °CDB 43.0
Heating Min °CWB -20.0
Max °CWB 15.0

• Split Sky Air • Outdoor Units 3


• Outdoor Units • R-410A • CMSQ-A7W1B

2 Specifications

2-1 TECHNICAL SPECIFICATIONS CMSQ200A7W1B CMSQ250A7W1B


Sound level Cooling Sound Power dBA 78 81
(Nominal)
Sound Pressure dBA 57 59
(Nominal)

Night quiet Level 1 / level 2 / dBA 55 / 50 / 45


level 3
Refrigerant Name R-410A
Charge kg 6.2 7.7
Control Expansion valve (electronic type)
Nr of Circuits 1
Refrigerant Oil Name Synthetic (ether) oil
Charged Volume l 1.7 2.1
Piping connections Liquid (OD) Type Braze connection
Diameter (OD) mm 9.52
Gas Type Braze connection
Diameter (OD) mm 15.9 19.1
Heat Insulation Both liquid and gas pipes
Max total length m 200
Defrost Method Reversed cycle
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Capacity Control ~ 100
Safety devices HPS
Fan motor driver overload protector
Over current relay
Inverter overload protector
PC board fuse
Standard Accessories Standard Accessories Installation manual
Quantity 1
Standard Accessories Operation manual
Quantity 1
Standard Accessories Connection pipes
Quantity 4
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound pressure
Sound values
Sound values are measured in a semi-anechoic room.

4 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

2 Specifications

2-2 ELECTRICAL SPECIFICATIONS CMSQ200A7W1B CMSQ250A7W1B


Power Supply Name W1
Phase 3N~
Frequency Hz 50
Voltage V 400
Current Nominal running Cooling A 9.53 9.73
current (RLA) Heating A 8.38 9.86
Minimum Ssc value kVa 1,218
Minimum circuit amps (MCA) A 11.9 18.5
Maximum fuse amps (MFA) A 16 25
Total overcurrent amps (TOCA) A 15.6 16.5
Full load amps (FLA) A 0.4 0.7
Voltage range Minimum V 360
Maximum V 440
Wiring connections For Power Supply Quantity 5
Remark Earth wire include
For connection with Quantity 2
indoor Remark F1 - F2
Power Supply Intake Both indoor and outdoor unit
Notes MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit
breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature :
35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal
is not below or above listed range limits

• Split Sky Air • Outdoor Units 5


• Outdoor Units • R-410A • CMSQ-A7W1B

3 Electrical data

Minimum Ssc value Zmax


[kVA] [Ω]
CMSQ200 - -
CMSQ250 1218 -
4TW31341-4

Notes:
1. In accordance with EN/IEC 61000-3-11 (1), respectively EN/IEC 61000-3-12 (2), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (4) % Zmax, respectively Ssc (3) ^ minimum Ssc value.
2. (1) European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated % 75A.
(2) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage
system with input current > 16A % 75A per phase.
(3) Short-circuit power
(4) System impedance

6 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

4 Options

Nr Item CMSQ200 CMSQ250


1 Refnet header KHRQ22M29H
KHRQ22M20T
2 Refnet joint
- KHRQ22M29T9
3 Central drain pan kit KWC26B160 KWC26B280
4TW31341-1

Notes:
1. All options are kits.
2. The option should be installed inside the outdoor unit.

• Split Sky Air • Outdoor Units 7


• Outdoor Units • R-410A • CMSQ-A7W1B

5 Selection procedure

CMSQ200-250A

INTEGRATED HEATING CAPACITY COEFFICIENT

The heating capacity tables do not take account of the reduction in capacity, when frost has accumulated or while the defrosting operation is in progress.
The capacity values, which take these factors into account, in other words, the integrated heating capacity values, can be calculated as follows:

Formula:
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
A=BxC

Integrating correction factor for finding integrated heating capacity

Inlet port temperature of heat exchanger (°C/RH 85%) -7 -5 -3 0 3 5 7


Integrating correction factor for frost accumulation 0.96 0.93 0.87 0.81 0.83 0.89 1.0

Defrosting operation Defrosting operation


+
Heating capacity

0 Time

1 cycle

3TW27232-7

NOTE
1 The figure shows that the integrated heating capacity expresses the integrated capacity for a single cycle ( from defrost operation to defrost
operation) in terms or time.

Please note that, when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a
temporary reduction in capacity, although this will of course vary in degree in accordance with a number of other factors, such as the outdoor
temperature (°CDB), relative humidity (RH) and the amount of frosting which occurs.

8 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-1 Cooling capacity tables
Cooling CMSQ200A
Indoor air temp.: °CWB
Combination (%)
Outdoor air 14,0 16,0 18,0 19,0 20,0 22,0 24,0
Capacity index temp. °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
100%
20,00 kW

90%
18,00 kW

80%
16,00 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: The above table shows the average value of conditions which may occur.

3TW31342-1

• Split Sky Air • Outdoor Units 9


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-1 Cooling capacity tables
Cooling CMSQ200A
Indoor air temp.: °CWB
Combination (%)
Outdoor air 14,0 16,0 18,0 19,0 20,0 22,0 24,0
Capacity index temp. °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
70%
14,00 kW

60%
12,00 kW

50%
10,00 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: The above table shows the average value of conditions which may occur.

3TW31342-1

10 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-1 Cooling capacity tables
Cooling CMSQ250A
Indoor air temp.: °CWB
Combination (%)
Outdoor air 14,0 16,0 18,0 19,0 20,0 22,0 24,0
Capacity index temp. °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
100%
25,00 kW

90%
22,50 kW

80%
20,00 kW

70%
17,50 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: The above table shows the average value of conditions which may occur.

3TW31342-1

• Split Sky Air • Outdoor Units 11


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-1 Cooling capacity tables
Cooling CMSQ250A
Indoor air temp.: °CWB
Combination (%)
Outdoor air 14,0 16,0 18,0 19,0 20,0 22,0 24,0
Capacity index temp. °CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
60%
15,00 kW

50%
12,50 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: The above table shows the average value of conditions which may occur.

3TW31342-1

12 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-2 Heating capacity tables
Heating CMSQ200A
Indoor air temp.: °CDB
Outdoor air temp. 16,0 18,0 20,0 21,0 22,0 24,0
TC PI TC PI TC PI TC PI TC PI TC PI
Combination (%) (°CDB) (°CWB) kW kW kW kW kW kW kW kW kW kW kW kW

100%
22,4 kW

90%
20,2 kW

80%
17,9 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: is shown as reference.


When selecting the unit models, avoid the outdoor air temperature range shown by
Note2: The above table shows the average value of conditions which may occur.

3TW31342-2

• Split Sky Air • Outdoor Units 13


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-2 Heating capacity tables
Heating CMSQ200A
Indoor air temp.: °CDB
Outdoor air temp. 16,0 18,0 20,0 21,0 22,0 24,0
TC PI TC PI TC PI TC PI TC PI TC PI
Combination (%) (°CDB) (°CWB) kW kW kW kW kW kW kW kW kW kW kW kW

70%
15,7 kW

60%
13,44 kW

50%
11,20 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: is shown as reference.


When selecting the unit models, avoid the outdoor air temperature range shown by
Note2: The above table shows the average value of conditions which may occur.

3TW31342-2

14 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-2 Heating capacity tables
Heating CMSQ250A
Indoor air temp.: °CDB
Outdoor air temp. 16,0 18,0 20,0 21,0 22,0 24,0
TC PI TC PI TC PI TC PI TC PI TC PI
Combination (%) (°CDB) (°CWB) kW kW kW kW kW kW kW kW kW kW kW kW

100%
28,0 kW

90%
25,2 kW

80%
22,4 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: is shown as reference.


When selecting the unit models, avoid the outdoor air temperature range shown by
Note2: The above table shows the average value of conditions which may occur.

3TW31342-2

• Split Sky Air • Outdoor Units 15


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-2 Heating capacity tables
Heating CMSQ250A
Indoor air temp.: °CDB
Outdoor air temp. 16,0 18,0 20,0 21,0 22,0 24,0
TC PI TC PI TC PI TC PI TC PI TC PI
Combination (%) (°CDB) (°CWB) kW kW kW kW kW kW kW kW kW kW kW kW

70%
19,6 kW

60%
16,8 kW

50%
14,0 kW

Symbols:
TC : Total capacity cooling: kW
PI : Power input: kW (Comp. + outdoor fan motor)

Note1: is shown as reference.


When selecting the unit models, avoid the outdoor air temperature range shown by
Note2: The above table shows the average value of conditions which may occur.

3TW31342-2

16 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-3 Capacity correction factor
CMSQ200A

Correction ratio for cooling capacity Correction ratio for heating capacity
Heigth difference between outdoor and

Heigth difference between outdoor


and farest indoor (m)
farest indoor (m)

Equivalent piping length (m)


Equivalent piping length (m)

Notes
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under
standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is
smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio
X Correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
X Correction ratio of piping to farest indoor
4. When level difference is 50m or more and equivalent pipe lengh is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit - branch sections) must be
increased.
For new diameters, see below.
model Gas pipe Liquid pipe
CMSQ200 19.1 9.5
5. When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual).
Diameter of main pipes (standard size)
model Gas pipe Liquid pipe
CMSQ2OO 15.9 9.5
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Equivalent length of main pipe X Correction factor
+
Equivalent length of branch pipes X Correction factor
Choose the correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (Gas pipe) 1.0 0.5
Heating (Liquid pipe) 1.0 0.5
Example
Main gas pipe size increase Branch gas pipe size increase
Main liquid pipe size increase Branch liquid pipe size increase

In the above case


(Cooling) Overall equivalent length = 80mx0.5 + 40mx1.0 = 80m
(Heating) Overall equivalent length = 80mx1.0 + 40mx1.0 = 120m
The rate of change in:
Cooling capacity when heigth difference = 0 is thus approximately 0.78.
Heating capacity when heigth difference = 0 is thus approximately 1.0

3TW31342-6

• Split Sky Air • Outdoor Units 17


• Outdoor Units • R-410A • CMSQ-A7W1B

6 Capacity tables
6-3 Capacity correction factor
CMSQ250A

Correction ratio for cooling capacity Correction ratio for heating capacity
Heigth difference between outdoor and

Heigth difference between outdoor


and farest indoor (m)
farest indoor (m)

Equivalent piping length (m)


Equivalent piping length (m)

Notes
1. These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to maximum) under
standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3. Method of calculating the capacity of the outdoor units
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is
smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio
X Correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio
X Correction ratio of piping to farest indoor
4. When level difference is 50m or more and equivalent pipe lengh is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit - branch sections) must be
increased.
For new diameters, see below.
model Gas pipe Liquid pipe
CMSQ250 22.2 12.7
5. When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also to installation manual).
Diameter of main pipes (standard size)
model Gas pipe Liquid pipe
CMSQ25O 19.1 9.5
6. Equivalent length used in the above figures is based upon the following equivalent length
Equivalent piping length =
Equivalent length of main pipe X Correction factor
+
Equivalent length of branch pipes X Correction factor
Choose the correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size
Correction factor
Standard size Size increase
Cooling (Gas pipe) 1.0 0.5
Heating (Liquid pipe) 1.0 0.5
Example
Main gas pipe size increase Branch gas pipe size increase
Main liquid pipe size increase Branch liquid pipe size increase

In the above case


(Cooling) Overall equivalent length = 80mx0.5 + 40mx1.0 = 80m
(Heating) Overall equivalent length = 80mx0.5 + 40mx1.0 = 120m
The rate of change in:
Cooling capacity when heigth difference = 0 is thus approximately 0.80.
Heating capacity when heigth difference = 0 is thus approximately 1.0

3TW31342-6

18 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

7 Dimensional drawing & centre of gravity


7-1 Dimensional drawing
CMSQ200A
4-15X22,5-mm-Oblong holes
(Pitch of foundation bolt (foundation bolt hole)
holes)

Note) 1. Detail for front side and detail for bottom side
indicate the dimensions after fixing the attached

(Pitch of foundation bolt holes)


piping.

Detail for front side

(Knock-out
hole)

(Knock-out hole)

Detail for bottom side

(Knock-out hole)
1 Liquid pipe connection port J9.5 Brazing connection
2 Gas pipe connection port J15.9 Brazing connection
3 Grounding terminal inside of switch box (M8)
4 Power cord routing hole (side) J62
5 Power cord routing hole (front) J45
6 Power cord routing hole (front) J27
7 Power cord routing hole (bottom) J50
8 Wire routing hole (front) J27
9 Pipe routing hole (front)
(Knock-out hole) (Knock-out hole)
10 Pipe routing hole (bottom)
3D051448B

CMSQ250A Note)
4-15X22,5-mm-Oblong holes 1. Detail for front side and detail for bottom side
(foundation bolt hole)
indicate the dimensions after fixing the attached
(Pitch of foundation bolt holes)
piping.
2. Gas pipe (Heat pump type)
J19.1 Brazing connection-- CMSQ250
(Pitch of foundation bolt holes)

Liquid pipe (Heat pump type)


J9,5 Brazing connection-- CMSQ250

(for 8HP)

Detail for front side

(Knock-out
hole)

(Knock-out hole)

(Knock-out hole)
Detail for bottom side

1 Liquid pipe connection port (see note)


2 Gas pipe connection port (see note)
3 Grounding terminal inside of switch box (M8)
4 Power cord routing hole (side) J62
5 Power cord routing hole (front) J45
6 Power cord routing hole (front) J27
7 Power cord routing hole (bottom) J65.5
8 Wire routing hole (front) J27
9 Pipe routing hole (front)
(Knock-out hole)
(Knock-out hole) 10 Pipe routing hole (bottom)
3TW31354-1

• Split Sky Air • Outdoor Units 19


• Outdoor Units • R-410A • CMSQ-A7W1B

7 Dimensional drawing & centre of gravity


7-1 Dimensional drawing
CMSQ200A

3TW27234-1

CMSQ250A

Item Part name Remark


1 Central drain pan kit KWC26B280

3TW27244-1

20 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

7 Dimensional drawing & centre of gravity


7-2 Centre of gravity
CMSQ200A

Center of foundation Center of foundation Center of foundation


bolt hole bolt hole bolt hole

Center of foundation bolt hole (Slot) Center of foundation bolt hole (Slot) 4D052145D

CMSQ250A

Center of foundation bolt


hole Center of foundation Center of foundation
bolt hole bolt hole

Center of foundation bolt hole (Slot)


4D052146H
Center of foundation bolt hole (Slot)

• Split Sky Air • Outdoor Units 21


• Outdoor Units • R-410A • CMSQ-A7W1B

8 Piping diagram

CMSQ200A

Fan

Filter
Pressure regulating
valve

Heat exchanger
Electronic expansion
valve

Solenoid valve

Capillary tube
Accumulator

4-way valve

High pressure
sensor

Filter Check valve

Filter
Oil separator

Filter

Filter

High pressure
Solenoid valve sensor

Compressor

Solenoid valve

Capillary tube

Low pressure
sensor

Stop valve (with service port on field piping side J 7.9mm flare connection)

4TW31345-1

22 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

8 Piping diagram

CMSQ250A

Check valve

Electronic expansion valve


Fan

Electronic expansion
valve Filter

Pressure regulating
valve
Heat exchanger
Accumulator

4-way valve

High pressure
sensor

Solenoid valve

Filter Check valve

Filter

Filter
Oil separator

High pressure
switch

Filter
Solenoid valve

Compressor
Capillary tube

Low pressure
sensor

Stop valve (with service port on field piping side J 7.9mm flare connection)

4TW31355-1

• Split Sky Air • Outdoor Units 23


• Outdoor Units • R-410A • CMSQ-A7W1B

9 Wiring diagram
9-1 Wiring diagram
CMSQ200A
A1P : Printed circuit board (Main)
A2P : Printed circuit board (Noise filter)
A3P : Printed circuit board (Inverter)
A4P : Printed circuit board (Fan) Power supply
BS1∼BS5 : Push button switch
(Mode, set, return, test, reset)
C1 : Capacitor
C63,C66 : Capacitor
DS1,DS2 : Dip switch
E1HC : Crankcase heater
F1U : Fuse (250V, 8A j B ) (A4P)
F1U,F2U : Fuse (250V, 3.15A j T ) (A1P)
F5U : Field fuse
F400U : Fuse (250V, 6.3A j T ) (A2P)
H1P∼H8P : Pilotlamp (service monitor - orange)
: Prepare test ----------- Flickering
[H2P] : Malfunction detection--- Light up
HAP : Pilotlamp (service monitor - green)
K1 : Magnetic relay
K2 : Magnetic contactor(M1C)
K3R : Magnetic relay (Y1S)
K4R : Magnetic relay (Y2S)
K5R : Magnetic relay (Y3S)
K7R : Magnetic relay (E1HC)
K11R : Magnetic relay (Y4S)
L1R : Reactor
M1C : Motor (compressor)
M1F : Motor (fan)
PS : Switching power supply (A1P,A3P)
Q1RP : Phase reversal detect circuit In-Out Out-Out
Q1DI : Earth leakage breaker
R10 : Resistor (Current sensor) (A4P)
R50,R59 : Resistor
R95 : Resistor (current limiting)
R1T : Thermistor (air) (A1P)
R1T : Thermistor (Fin) (A3P)
R2T : Thermistor (Suction)
R3T : Thermistor (discharge pipe) (M1C)
R4T : Thermistor (Heat exch. deicer)
R5T : Thermistor (liquid pipe)
R6T : Thermistor (air) (Accumulator) Indoor Outdoor
S1NPH : Pressure sensor (High) (F1)(F2) (F1)(F2)
S1NPL : Pressure sensor (Low) Notes:
S1PH : Pressure switch (High) 1. This wiring diagram only applies to the outdoor unit
SD1 : Safety devices input 2. : Field wiring, Q: Indication of parts outside switchbox
V1R : Power module (A4P)
V1R,V2R : Power module (A3P) Position of M1C,M1F 3. : Terminal strip : Connector Front layer
X1A,X2A : Connector (M1F) : Protective earth (screw) : Terminal
X1M : Terminal strip (Power supply)
X1M : Terminal strip (Control) (A1P) 4. When using the option adaptor, refer to the installation manual
X1M : Terminal strip (A5P) El. Compo.
Y1E : Electronic expansion valve (Main) Box 5. Refer to the installation manual, for connection wiring to
Y1S : Solenoid valve (Hot gas) indoor-outdoor transmission F1 - F2. Outdoor-outdoor transmission F1 -
Y2S : Solenoid valve (oil return) F2 and on how to use BS1-BS5 and DS1, DS2 switch. Rear layer
Y3S : Solenoid valve (4-way valve)
Y4S : Solenoid valve (injection) 6. Do not operate the unit by short-circuiting protection device S1PH
Z1C∼Z5C : Noise filter (ferrite core) 7. Colours: BLK: Black / WHT: White / PNK: Pink /
Z1F : Noise filter (with surge absorber) RED: Red /BLU: Blue /BRN: Brown / GRY: Grey /
GRN: Green /YLW: Yellow / ORG: Orange
Outer shell Position in switch box
Detail of M1C

2TW31346-1

CMSQ250A
A1P : Printed circuit board (Main)
A2P : Printed circuit board (Noise filter) Power supply
A3P : Printed circuit board (Inverter)
A4P : Printed circuit board (Fan) 3/N ∼ 400/230V 50Hz
BS1∼BS5 : Push button switch
(Mode, set, return, test, reset)
C1 : Capacitor
C63,C66 : Capacitor
DS1,DS2 : Dip switch
E1HC : Crankcase heater
F1U : Fuse (250V, 8A j B ) (A4P)
F1U,F2U : Fuse (250V, 3.15A j T ) (A1P)
F5U : Field fuse
F400U : Fuse (250V, 6.3A j T ) (A2P)
H1P∼H8P : Pilotlamp (service monitor - orange)
: Prepare test ----------- Flickering
[H2P] : Malfunction detection--- Light up
HAP : Pilotlamp (service monitor - green)
K1 : Magnetic relay
K2 : Magnetic contactor(M1C)
K3R : Magnetic relay (Y1S)
K4R : Magnetic relay (Y2S)
K5R : Magnetic relay (Y3S)
K7R : Magnetic relay (E1HC)
L1R : Reactor
M1C : Motor (compressor)
M1F : Motor (fan)
PS : Switching power supply (A1P,A3P)
Q1RP : Phase reversal detect circuit
Q1DI : Earth leakage breaker In-Out Out-Out
R10 : Resistor (Current sensor) (A4P)
R50,R59 : Resistor
R95 : Resistor (current limiting)
R1T : Thermistor (air) (A1P)
R1T : Thermistor (Fin) (A3P) Male connector: BLU
R2T : Thermistor (Suction)
R3T : Thermistor (discharge pipe) (M1C) Female connector: WHT
R4T : Thermistor (Heat exch. deicer)
R5T : Thermistor (Heat exch. outlet)
R6T : Thermistor (liquid pipe)
R7T : Thermistor (Accumulator) Indoor Outdoor
S1NPH : Pressure sensor (High) (F1)(F2) (F1)(F2)
S1NPL : Pressure sensor (Low) Notes:
S1PH : Pressure switch (High) 1. This wiring diagram only applies to the outdoor unit
SD1 : Safety devices input 2. : Field wiring, Q: Indication of parts outside switchbox
V1R : Power module (A4P)
V1R,V2R : Power module (A3P) Position of M1C,M1F 3. : Terminal strip : Connector Front layer
X1A,X2A : Connector (M1F) : Protective earth (screw) : Terminal
X1M : Terminal strip (Power supply)
X1M : Terminal strip (Control) (A1P)
El. Compo.
4. When using the option adaptor, refer to the installation manual
X1M : Terminal strip (A5P)
Y1E : Electronic expansion valve (Main) Box 5. Refer to the installation manual, for connection wiring to
Y2E : Electronic expansion valve (Subcool) indoor-outdoor transmission F1 - F2. Outdoor-outdoor transmission F1 -
Y1S : Solenoid valve (Hot gas) F2 and on how to use BS1-BS5 and DS1, DS2 switch. Rear layer
Y2S : Solenoid valve (oil return) M1C
Y3S : Solenoid valve (4-way valve) 6. Do not operate the unit by short-circuiting protection device S1PH
Y4S : Solenoid valve (injection) 7. Colours: BLK: Black / WHT: White / PNK: Pink /
Z1C∼Z5C : Noise filter (ferrite core) RED: Red /BLU: Blue /BRN: Brown / GRY: Grey /
Z1F : Noise filter (with surge absorber) GRN: Green /YLW: Yellow / ORG: Orange
Outer shell Position in switch box
Detail of M1C

2TW31356-1

24 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

9 Wiring diagram
9-2 External connection diagram
CMSQ200-250A

Power supply
L1 L2 L3 N
NOTES
Main switch
1 All wiring, components and materials to be procured on the site must comply with the applicable local
and national codes.
2 Use copper conductors only.
3 As for details, see wiring diagram.
OUTDOOR UNITS
L1 L2 L3 N 4 Install circuit breaker for safety.
Switch
5 All field wiring and components must be provided by licensed electrician.
Fuse
6 Unit shall be grounded in compliance with the applicable local and national codes.
7 Wiring shown are general points-of-connection guides only and are not intended for or to include all
Power supply
details for a specific installation.
L N
8 Be sure to install the switch and the fuse to the power line of each equipment.
Main switch 9 Install the main switch that can interrupt all the power sources in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
10 If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and
off while the product is operating, attach a reversed phase protection circuit locally.
2 wires cable Running the product in reversed phase may break the compressor and other parts.
(transmission line)
2 wires cable
2 wires cable (transmission line) 2 wires cable
(transmission line) (transmission line)
2 wires cable
(power line)

L N L N L N L N
Switch Switch Switch Switch

Fuse Fuse Fuse Fuse

2 wires cable 2 wires cable 2 wires cable 2 wires cable


(power line) (power line) (power line) (power line)

INDOOR UNITS

3D051452B

• Split Sky Air • Outdoor Units 25


• Outdoor Units • R-410A • CMSQ-A7W1B

10 Sound data
10 - 1 Sound pressure spectrum
CMSQ200A CMSQ250A
Sound pressure level (dB)

Sound pressure level (dB)


Octave band center frequency (Hz) Octave band center frequency (Hz)

Location of microphone Location of microphone


NOTES NOTES
1 Data is valid at free field condition 1 Data is valid at free field condition
2 Data is valid at nominal operation condition 2 Data is valid at nominal operation condition
front side

front side
3 dB(A) = A-weighted sound pressure level (A-scale 3 dB(A) = A-weighted sound pressure level (A-scale
according to IEC) according to IEC)
4 Reference acoustic pressure 0dB = 20μPa 4 Reference acoustic pressure 0dB = 20μPa

3TW31347-1 3TW31357-1

26 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

10 Sound data
10 - 2 Sound power spectrum
CMSQ200A CMSQ250A
Sound power level (dB)

Sound power level (dB)


Octave band center frequency (Hz) Octave band center frequency (Hz)

NOTES NOTES
1 dBA = A-weighted sound power level (A-scale 1 dBA = A-weighted sound power level (A-scale
according to IEC) according to IEC)
2 Reference acoustic intensity 0dB = 10E-6μW/m2 2 Reference acoustic intensity 0dB = 10E-6μW/m2
3 Measured according to ISO 3744 3 Measured according to ISO 3744

3TW31347-2 3TW31357-2

• Split Sky Air • Outdoor Units 27


• Outdoor Units • R-410A • CMSQ-A7W1B

11 Installation
11 - 1 Service space
CMSQ

For single unit installation For installation in rows


<Pattern 1> <Pattern 1>

300 or more 300 or more

<Front> 20 or more 20 or more


10 or more 10 or more <Front> 10 or more
10 or more
500 or more 500 or more

<Pattern 2> 100 or more <Pattern 2> 100 or more

<Front>
50 or more 50 or more 50 or more 100 or more <Front> 100 or more 50 or more
500 or more
500 or more

<Pattern 3>
Wall height unrestricted
<Pattern 3>

300 or more Wall height unrestricted 300 or more

<Front> <Front>
400 or more 400 or more

200 or more 200 or more

Notes:
1 Heights of walls in case of Patterns 1 and 2:
Front: 1500 mm
suction side: 500 mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the space to be shown in this drawing.
2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure
on the right.
3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always
bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D051451L

28 • Split Sky Air • Outdoor Units


• Outdoor Units • R-410A • CMSQ-A7W1B

11 Installation
11 - 1 Service space
CMSQ

For centralized group layout

<Pattern 1>

300 or more 300 or more

10 or more 20 or more 10 or more 10 or more <Front> 20 or more 10 or more


<Front>

500 or more <Front>


600 or more

300 or more
<Front> 20 or more
10 or more 10 or more

500 or more
10 or more 20 or more 10 or more

<Pattern 2>

100 or more
100 or more

50 or more <Front> 100 or more 50 or more


<Front> 100 or more 50 or more 50 or more

500 or more 500 or more <Front>

<Front>
100 or more 50 or more

500 or more 100 or more 100 or more 50 or more


50 or more

<Unit: mm>
Notes:
1 Heights of walls in case of Patterns 1 and 2:
Front: 1500 mm
suction side: 500 mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35
degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds
maximum ability because of much generation load of heat in all outdoor unit, take the
suction side space more broadly than the space to be shown in this drawing.
<suction side>
<Front>

2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front
and suction side service spaces respectively as shown in the figure on the right.
3 When installing the units most appropriate pattern should be selected from those shown
above in order to obtain the best fit in the space available always bearing in mind the need
to leave enough space for a person to pass between units and wall and for the air to
circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout
should take account of the possibility of short circuits.)
4 The units should be installed to leave sufficient space at the front for the on site refrigerant
piping work to be carried out comfortably.

3D051451L

• Split Sky Air • Outdoor Units 29


• Outdoor Units • R-410A • CMSQ-A7W1B

11 Installation
11 - 2 Fixation and foundation of units
CMSQ200-250A
Foundation bolt type: JA
Nut Size: M12
Spring washer Four bolts are required
3 thread ridges or more
Frame

Foundation bolt executing method


Drain ditch

(Smooth down grade of Notes:


about 1/50) 1 The proportions of cement: sand: gravel for the concrete shall be 1:2:4, and
the reinforcement bars that their diameter are 10mm, (approx. 300mm
intervals) shall be placed.
Y ditch
Except for CMSQ200 2 The surface shall be finished with mortar. The corner edges shall be
model chamfered.
3 When the foundation is built on a concrete floor, rubble is not necessary.
Drain ditch However, the surface of the section on which the foundation is built shall
When building a When building a have rough finish.
foundation on the foundation on the
ground concrete floor 4 A drain ditch shall be made around the foundation to thoroughly drain
water from the equipment installation area.
5 When installing the equipment on a roof, the floor strength shall be
Ditch Ditch
checked, and water-proofing measures shall be taken.
6 Y ditch is not necessary for CMSQ200 model.
Floor

Cross section

Model A B
CMSQ200 497 697
CMSQ250 792 992

3TW31349-6

30 • Split Sky Air • Outdoor Units


12

CMSQ200-250A

Example of connection Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
(Connection of 4 indoor units Heat pump system)
One outdoor unit installed
f
a a
indoor unit A B
a b c d H1 g
A B C D H1 b
h 4 H1
refnet joint e f g H2
1 2 3 H2 c d e b c d e
1 2 3 1 2 3 H2
4
refnet header 4

Pipe length between outdoor and indoor units <165 m


Actual pipe length
[Example] unit 4: a+b+c+d+h<165 m [Example] unit 3: a+b+e<165 m, unit 4: a+f+g<165 m [Example] unit 4: a+e<165 m
Maximum
Between outdoor and indoor units Equivalent pipe length between outdoor and indoor units <190 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for
allowable length Equivalent length
calculation purposes))
Total extension length Total piping length from outdoor unit to all indoor units <200 m
Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units (H1)<30 m
Refrigerant pipe selection

Allowable height
Between indoor and indoor units Difference in height Difference in height between adjacent indoor units (H2)<4 m

• Split Sky Air • Outdoor Units


Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit <40 m (See note on next page)
Allowable length after the branch Actual pipe length
[Example] unit 4: b+c+d+h<40 m [Example] unit 3: b+e<40 m, unit 4: f+g<40 m [Example] unit 4: e<40 m
Refrigerant branch kit selection How to select the refnet joint How to select the refnet header
• When using refnet joints at the first branch counted from the outdoor unit side. • Choose from the following table in accordance with the total capacity of all the indoor
Refrigerant branch kits can only be used with R410A. Choose from the following table in accordance with the capacity of the outdoor unit. units connected below the refnet header.
• Outdoor Units • R-410A • CMSQ-A7W1B

Outdoor unit capacity type Refrigerant branch kit name Indoor capacity type Refrigerant branch kit name
CMSQ200 KHRQ22M20T 50~125 KHRQ22M29H
CMSQ250 KHRQ22M29T9
• For refnet joints other than the first branch, select the proper branch kit model based on
the total capacity index.
Indoor capacity type Refrigerant branch kit name
<200 KHRQ22M20T
200<x<250 KHRQ22M29T9

[Example] [Example] [Example]


Example of downstream indoor units in case of refnet joint C; indoor units 3+4 in case of refnet joint B; indoor unit 4, in case of refnet header;
in case of refnet header; indoor units 1+2+3 indoor units 1+2+3+4

4PW47543-1

31
32
12

CMSQ200-250A

Pipe size selection A,B,C. Piping between outdoor unit and refrigerant branch kit D. Piping between refrigerant branch kits E. Piping between refrigerant branch kit and indoor unit
• Choose from the following table in accordance with the outdoor unit total • Choose from the following table in accordance with the total capacity of • Pipe size for direct connection to indoor unit must be the same as the
capacity type, connected downstream. all the indoor units connected below this. connection size of indoor unit.
Outdoor unit connection piping size • Do not let the connection piping exceed the refrigerant piping size
chosen by general system model name. Piping size (outer diameter) (mm)
Outdoor unit Piping size (outer diameter) (mm) Indoor capacity type Gas pipe Liquid pipe
capacity type Gas pipe Liquid pipe Indoor or outdoor unit Piping size (outer diameter) (mm)
50 Ø12.7 Ø6.4
CMSQ200 Ø15.9 total capacity Gas pipe Liquid pipe
Ø9.5 60~125 Ø15.9 Ø9.5
CMSQ250 Ø19.1 <150 Ø15.9
150<x<200 Ø19.1 Ø9.5
200<x<250 Ø22.2

When the equivalent pipe length between outdoor and indoor units is 90 m or more, the size of the main pipes (both gas side and liquid side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such a case it is possible to increase the size of the main pipes.

Gas side Liquid side


1 2 3 4 5 1 Outdoor unit
CMSQ200 Ø15.9 ➞ Ø19.1 CMSQ200 Ø9.5 —
2 Main pipes
CMSQ250 Ø19.1 ➞ Ø22.2 CMSQ250 Ø9.5 ➞ Ø12.7
3 Increase
— Increase is not allowed
4 First refrigerant branch kit
5 Indoor unit
Refrigerant pipe selection

• Split Sky Air • Outdoor Units


How to calculate the additional
refrigerant to be charged
Additional refrigerant to be
charged R (kg) X1...6 = Total length (m) of liquid piping size at Øa
R should be rounded off in units
of 0.1 kg Example for refrigerant branch using refnet joint and refnet header for CMSQ250
If the outdoor unit is CMSQ250 and the piping lengths are as below
• Outdoor Units • R-410A • CMSQ-A7W1B

Note Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are fulfilled.
Required conditions Example drawings
It is necessary to increase the pipe size of the liquid and the gas pipe if the pipe length between the first indoor unit 4: b+c+d<90 m Increase the pipe size as follows
and the final branch kit is over 40 m (reducers must be procured on site). increase the pipe size of b, c, d
If the increased pipe size is larger than the pipe size of the main pipe, then the pipe size of the main pipe Ø9.5 ➞ Ø12.7 Ø15.9 ➞ Ø19.1 Ø22.2 ➞ Ø25.4*
needs to be increased as well. Ø12.7 ➞ Ø15.9 Ø19.1 ➞ Ø22.2
* If available on the site. Otherwise it can not be increased.
For calculation of total extension length, the actual length of above pipes must be doubled (except main a+b*2+c*2+d*2<200 m
pipe and the pipes that not increase the pipe size). 1

Indoor unit to the nearest branch kit <40 m. e, f, g, h<40 m a b c d H1


1 Outdoor unit
A B C D
2 h
2 Refnet joints (A~D)
The difference between the distance of the outdoor unit to the farthest indoor unit and the distance of the The farthest indoor unit 4 e f g
3 1 2 3 H2 3 Indoor units (1~4)
outdoor unit to the nearest indoor unit <40 m. The nearest indoor unit 1 4
(a+b+c+d)–(a+e)<40 m

4PW47543-1
• Outdoor Units • R-410A • CMSQ-A7W1B

13 Operation range

CMSQ200-250A

Cooling
Heating

15.5

Outdoor temperature (°C WB)


Range for pull down operation
Outdoor temperature (°C DB)

Range for warming up operation


Operation range

Operation range

Indoor temperature (°C WB) Indoor temperature (°C DB)

4TW25797-3C

NOTES

1 These figures assume the following operation conditions:


indoor and outdoor units:
• equivalent pipe lenght: 7.5 m
• level difference: 0 m
2 Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).
3 To reduce the freeze-up operation (indoor de-icing) frequency it is recommended to install the outdoor unit in a location not exposed to
wind.

• Split Sky Air • Outdoor Units 33


Daikin’s unique position as a manufacturer of air Daikin Europe N.V. is approved by LRQA for its Quality The present publication is drawn up by way of information only and does not
conditioning equipment, compressors and Management System in accordance with the ISO9001 constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
refrigerants has led to its close involvement in standard. ISO9001 pertains to quality assurance regarding compiled the content of this publication to the best of its knowledge. No
environmental issues. For several years Daikin has design, development, manufacturing as well as to services express or implied warranty is given for the completeness, accuracy,
had the intension to become a leader in the provision related to the product. reliability or fitness for particular purpose of its content and the products and
of products that have limited impact on the services presented therein. Specifications are subject to change without
environment. This challenge demands the eco design prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or
and development of a wide range of products and an indirect damage, in the broadest sense, arising from or related to the use
energy management system, resulting in energy and/or interpretation of this publication. All content is copyrighted by Daikin
conservation and a reduction of waste. Europe N.V..
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for

Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende

ISO14001 assures an effective environmental


management system in order to help protect human health
and the environment from the potential impact of our
activities, products and services and to assist in
maintaining and improving the quality of the environment.
the environmont is set in the EMAS and ISO 14001 systems.

Daikin units comply with the European regulations that


guarantee the safety of the product.

Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
Daikin Europe N.V. is participating in the EUROVENT
www.daikin.eu Certification Programme. Products are as listed in the
BTW: BE 0412 120 336 EUROVENT Directory of Certified Products.
RPR Oostende

You might also like