1 PRF-01 STAIRCASE PRESSURISATION FAN STAIRCASE-02 3906 11538 608 PRF-01 11600
SPECIFIED
NOT
2 PRF-02 CORRIDOR PRESSURIZATION FAN CORRIDOR 8960 8960 485 PRF-02 8960
SPECIFIED
ESP (Pa)
610
485
565
420
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL
FAN - PRF-1
I
a)
b)
c)
d)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL
FAN - PRF-1
e)
II
a)
b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL
FAN - PRF-1
c)
d)
e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL
FAN - PRF-1
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL KHAI
FAN - PRF-1
DESCRIPTION
Total no.of floors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Windows Perimeter
Total Lift Well Wall Area
Total Lift Landing Doors Area
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
FAN - PRF-1
Total leakage rate via walls (Qwa)
Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 140) + (0.00011 x 842) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.122 x sqrt (50)}
TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs =Qdc+Qwi+Qld+Qt+Qwa)
Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and Door on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell
{ = 1 x 4.4 }
FAN - PRF-1
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.23 x sqrt (12.5)}
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection
{ = 5.45 x 1000 }
{ = 5448 x 2.118 }
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 2 - AL KHAI
FAN - PRF-1
Calculation Unit
24 Nos
842.18 sq m
140.01 sq m
115.35 m
0.00 sq m
0.00 sq m
0.01 sq m
0.24 sq m
1.41 cu.m/s
0.0042 sq m
0.04 cu.m/s
0 sq m
0 sq m
SE 2 - AL KHAILI
sq m
140 sq m
842 sq m
sq m
0.1220 sq m
0.72 cu.m/s
2.16 cu.m/s
3.247 cu.m/s
2 Nos
1.00 m/s
4.40 sq.m
4.40 cu.m/s
0.01 sq m
0.23 sq m
SE 2 - AL KHAILI
0.67 cu.m/s
0.0042 sq m
0.01 cu.m/s
0 sq m
0 sq m
sq m
140 sq m
842 sq m
0 sq m
0.1220 sq m
0.36 cu.m/s
5.45 cu.m/s
5.45 cu.m/s
5448 LPS
11538 CFM
SE 2 - AL KHAILI
11538
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL
FAN - PRF-3
I
a)
b)
c)
d)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL
FAN - PRF-3
e)
II
a)
b)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL
FAN - PRF-3
c)
d)
e)
f)
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL
FAN - PRF-3
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL KHAI
FAN - PRF-3
DESCRIPTION
Total no.of floors
Total Stairwell wall area (Refer wall area calculation attached)
Total Exterior Building Wall Area
Total Windows Perimeter
Total Lift Well Wall Area
Total Lift Landing Doors Area
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
FAN - PRF-3
Total leakage rate via walls (Qwa)
Exterior Building Wall Area(Leakage area ratio A/A w=0.00021)
Internal and stair wall Area(Leakage area ratio A/Aw=0.00011)
Lift well wall Area(Leakage area ratio A/Aw=0.00084)
Total leakage Area via walls (Awa)
{= (0.00021x 149) + (0.00011 x 882) + (0.00084 x 0)}
Total Leakage through Walls (Qwa) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.1283 x sqrt (50)}
TOTAL AIR SUPPLY REQUIREMENT WITH ALL DOORS CLOSED (Qs =Qdc+Qwi+Qld+Qt+Qwa)
Total air flow needed through open door to prevent smoke infiltration into stairwell
(Qdo)
The total no of doors considered open
(Fire Affected Floor, Above Floor and Door on Ground Floor)
Velocity of air through open Stairwell door to prevent smoke infiltration into Stairwell
{ = 1 x 4.4 }
FAN - PRF-3
Total Leakage through Closed Door Gaps (Q dc) = 0.839 x A x sqrt (delta P)
{= 0.83 x 0.23 x sqrt (12.5)}
Total Leakage through Gaps around Windows (Qwi) = 0.839 x A x (delta P) 0.625
Since Qsdo is Greater than Qs, Qsdo is selected for Fan Selection
{ = 5.46 x 1000 }
{ = 5462 x 2.118 }
STAIRWELL PRESSURIZATION CALCULATION FOR STAIRCASE 1 - AL KHAI
FAN - PRF-3
Calculation Unit
24
882.47 sq m
148.66 sq m
86.55 m
0.00 sq m
0.00 sq m
0.01 sq m
0.24 sq m
1.41 cu.m/s
0.0031 sq m
0.03 cu.m/s
0 sq m
0 sq m
SE 1 - AL KHAILI
sq m
149 sq m
882 sq m
sq m
0.1283 sq m
0.75 cu.m/s
2.19 cu.m/s
3.287 cu.m/s
6961.79 CFM
2 Nos
1.00 m/s
4.40 sq.m
4.40 cu.m/s
0.01 sq m
0.23 sq m
SE 1 - AL KHAILI
0.67 cu.m/s
0.0031 sq m
0.01 cu.m/s
0 sq m
0 sq m
sq m
149 sq m
882 sq m
0 sq m
0.1283 sq m
0.38 cu.m/s
5.46 cu.m/s
5.46 cu.m/s
5462 LPS
11569 CFM
SE 1 - AL KHAILI
11569
STAIRCASE INNER
STAIRCASE-1
LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY
7 GROUND (G) 4700 4600 2 43.24 1150 4600 1 5.29 1000 2100 1 2.10
9 MEZZANINE FLOOR 4950 4200 2 41.58 2400 4200 1 10.08 1000 2100 1 2.10 5175 1200 1
11 TYPICAL FLOOR 4950 3000 36 534.60 2400 3000 18 129.60 1000 2100 18 37.80 1050 1000 18
13 TECH. ROOF FLOOR 4950 3000 2 29.70 2400 3000 1 7.20 1000 2100 1 2.10
PERIMETER LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY AREA LENGTH HEIGHT QTY
6.21 12.75 4650 4200 2 39.06 2400 4200 1 10.08 1000 2100 1 2.10 5175 1200 1 6.21
18.90 73.80 4650 3000 36 502.20 2400 3000 18 129.60 1000 2100 18 37.80 1850 1000 18 33.30
PERIMETER
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
12.75
0.00
102.60
0.00
0.00
0.00
115.35
STAIRWELL PRESSURISATION CALCULATION - DOOR OPENING FORCE
(AL KHAILI)
As per BS 5588-4:1998: The maximum pressure differential across a door opening into a pressurised space is
determined using the following equation:
Fdc is the force required to open the door without a pressure differential applied
across the door. E.g. The door closer mechanism etc (in N)
W is the width of the door (in M)
A is the area of cross section of the door (in m
d is the distance from the door knob to the knob side of the door (in m)
If at design stage, the force required to overcome the door closer is unknown, a maximum pressure differential of
60 Pa may be utilised for design purpose.
I STAIRCASE -01
ΔP (Q/(0.839 X A))2
307.28
P - 307.28
Fdc - Unknown
W - 1
A - 2.2
d - 0.1
Fo = (P x A x W)
2 x (W-d)
(307.28 x 2.2 x 1)
=
2 x (1 - 0.1)
376
A 0.509
II STAIRCASE -02
ΔP (Q/(0.839 X A))2
314.39
P - 314.39
Fdc - Unknown
W - 1
A - 2.2
d - 0.1
Fo = (P x A x W)
2 x (W-d)
(314.39 x 2.2 x 1)
=
2 x (1 - 0.1)
384
A 0.511
ATION CALCULATION - DOOR OPENING FORCE
(AL KHAILI)
pressure differential across a door opening into a pressurised space is
:
m3/s
m2
Pa
Pa
m
m2
m
m3/s
m3/s
Sqmt
m3/s
m2
Pa
Pa
m
m2
m
m3/s
m3/s
Sqmt
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-01
S.P LOSS/
INITIAL FINAL S.P TO STRAIGHT TOTAL
SR DUCT WORK INITIAL SIZE IN FINAL SIZE IN VOLUME 100FT
VELOCITY VELOCITY CHANGE IN EQUIVALENT QTY S.P
NO REF (INCH) (INCH) OF AIR LENGTH OF
PRESSURE PRESSURE VELOCITY LENGTH LOSS
DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg) (iwg)
608
in Pa
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-02
S.P LOSS/
INITIAL FINAL S.P TO STRAIGHT TOTAL
SR DUCT WORK INITIAL SIZE IN FINAL SIZE IN VOLUME 100FT
VELOCITY VELOCITY CHANGE IN EQUIVALENT QTY S.P
NO REF (INCH) (INCH) OF AIR LENGTH OF
PRESSURE PRESSURE VELOCITY LENGTH LOSS
DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg) (iwg)
485
in Pa
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-03
S.P LOSS/
INITIAL FINAL S.P TO STRAIGHT TOTAL
SR DUCT WORK INITIAL SIZE IN FINAL SIZE IN VOLUME 100FT
VELOCITY VELOCITY CHANGE IN EQUIVALENT QTY S.P
NO REF (INCH) (INCH) OF AIR LENGTH OF
PRESSURE PRESSURE VELOCITY LENGTH LOSS
DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg) (iwg)
560
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-03
S.P LOSS/
INITIAL FINAL S.P TO STRAIGHT TOTAL
SR DUCT WORK INITIAL SIZE IN FINAL SIZE IN VOLUME 100FT
VELOCITY VELOCITY CHANGE IN EQUIVALENT QTY S.P
NO REF (INCH) (INCH) OF AIR LENGTH OF
PRESSURE PRESSURE VELOCITY LENGTH LOSS
DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg) (iwg)
in Pa
EXTERNAL STATIC PRESSURE CALCULATION FOR PRF-04
S.P LOSS/
INITIAL FINAL S.P TO STRAIGHT TOTAL
SR DUCT WORK INITIAL SIZE IN FINAL SIZE IN VOLUME 100FT
VELOCITY VELOCITY CHANGE IN EQUIVALENT QTY S.P
NO REF (INCH) (INCH) OF AIR LENGTH OF
PRESSURE PRESSURE VELOCITY LENGTH LOSS
DUCT
W H W H CFM (hv1) (hv2) (iwg) (FT) (iwg) (iwg)
419
in Pa
AREA HEIGHT VOLUME NO OF FLOORS TOTAL VOLUME ACPH CFM
234