PIPING SPECIFICATION

Nomor Dokumen Rev. : 0


Nomor Halaman
TLB-050-SP-003 PIPING CLASS SPECIFICATION 1dari6

PEMBERI KERJA : PT. MISI MULIA PETRONUSA


KONTRAKTOR : PT. PP (Persero) Tbk
NAMA PROYEK : TERMINAL LPG BANYUWANGI
LOKASI : BANYUWANGI – JAWA TIMUR
TANGGAL KONTRAK : 16 DESEMBER 2013

FOR
0 21/11/15 6 DCS BMG DS RR RY
CONSTRUCTION
ISSUED FOR
C 11/11/14 6 DCS BMG DS RR RY
CONSTRUCTION
ISSUED FOR
B 30/10/14 6 DCS BMG DS RR RY
APPROVED
ISSUED FOR
A 27/09/14 6 DCS BMG DS RR RY
REVIEW
DIBUAT DIPERIKSA DISETUJUI DIPERIKSA DISETUJUI
JUM OLEH OLEH OLEH OLEH OLEH
REV TGL STATUS
HAL PT. MISI MULIA
PT. PP (PERSERO)
PETRONUSA
REVISION SHEET

No Revisi Tanggal Perubahan

TLB-050-SP-002_0 Piping Class Specification HALAMAN 2 /6


TABLE OF CONTENT

1 INTRODUCTION
1.1 Scope
1.2 Definition
2 ABREVIATIONS
3 AMBIEN CONDITIONS WATER SOURCE
4 REFERENCE DOCUMENTS
5 STANDARD OF MATERIAL PIPING LPG SYSTEM
6 INTERNAL CORROSION ROTECTION
7 REGULAR PIPELINE CLEANING
8 EXTERNAL CORROSION PROTECTION
8.1 Atmospheric Corrosion
8.2 Corrosion Protection
8.3 Fireproofing

TLB-050-SP-002_0 Piping Class Specification HALAMAN 3 /6


1. INTRODUCTION

1.1 Scope

This Piping General Spesification covers the assesment of materials selection


requirements for Terminal LPG located at Banyuwangi. This specification covers the minimum
requirement for the selection of piping fire system components that will be used.

1.2 DEFINITION
The following terms used in this specification shall refer to the meanings given below :

o Company : Company is defined as PT Misi Mulia Petronusa


o Contractor : The contractor is defined as PT. PP (Persero) Tbk
o Vendor : Manufacturer of recoqnized product lines who has been appointed for a
particular scope of supply.

2. ABREVIATION

o CA Corrossion allowance
o CC Crevice corrosion
o CCT Critical crevice corrosion temperature
o CP Cathodic Protection
o CPT Critical pitting corrosion temperature
o CRA Corrosion resistannt alloy
o CS Carbon manganesse steels
o CSCC Chloride induced stress corrossion cracking
o FRP Fiber Reinforced Plastic
o GRP Fiber Reinforced Plastic
o HIC Hydrogen inducedd cracking
o ICCP Impressed Current Cathodic Protection
o LTCS Low Temperature carbon steel
o MIC Microbiological induced corrossion
o NACE Nationnal Association of Corrossion Engineers
o PT Pitting corosion
o ppmv Parts per million b volume
o ppbv Parts per billion by volume
o Pint Equals to 0.125 gaallon
o SS Stainless steel

3. AMBIENT CONDITION WATER SOURCES

Fresh water is utilized as water sources


o Minimum water temperature : 23oC
o Maximum water temperature : 31oC
o Water density : 980 kg/m3

TLB-050-SP-002_0 Piping Class Specification HALAMAN 4 /6


4. REFERENCE DOCUMENTS

o ANSI B31.3 Process Piping


o ANSI B31.4 Piping Transportation Systems for Liquid
Hydrocarbons and Other Liquids
o ANSI B16.5 Pipe Flanges and Flanged Fittings
o NFPA 30 Flammable and Combustible Liquids Code

5. STANDARD OF MATERIAL PIPING LPG SYSTEM

Piping LPG system shall be indicated or suspected to leakage or spill of liquid. Because of the fire
hazard in piping system that are handling flammable and combustible liquids. Piping system
must be able to withstand the intense heat generated by fire for reasonable periods
of time while emergency shutdown procedures are implemented and fire fighting measures
begin. Failure of piping during fire condition can turn moderate hazard into catastropic.

The Material, design, fabrication, assembly, test and inspection piping systems containing liquids
shall be suitable for the expected working pressure and structural stresses. Conformitty with the
applicable section of ANSI B31.3, American National Standard Code for Process Piping, and
ANSI B31.4 Pipe Line Transportation For Liquid Hydrocarbon and Other Liquids .

The other material plastic or similar materials, as permitted and shall be designed to specification
embodying recognized engineering principles or shall be listed and shall be compatible with the
fluid services. Consideration Material is;

a. Ressistance to damage by fire


b. The any leakage resulting of failure will not unduly expose person and, others important
building, or others structure
c. The locate any leakage can readily by controlled by operation of accessible remote located
valve.

There is need to consider to external coating with fire proofing coating for pipe support and other
structure to holding sufficient fire resistance. Carbon steel pipe must be applied for fire water line.
Utilization of FRP & GRP pipe is strickly not allowed.

The General pipe properties as follows:


Carbon Steel Pipe
 Roughness corroded : 0.022 inch
 Roughness non corroded : 0,0002 inch
 Matterial : Carrbon Steel
 Temperature Max : More than 93 deg C
 Code and Appliccable Standard : API 5 L, ASTM A106 Grade B
 Size and length : 1 to 32 inch, 6 meter
 Fire Resistance : good
 Type of Jointing : Welding
 Wall thicknes : Refer to Pipe Scchedule

TLB-050-SP-002_0 Piping Class Specification HALAMAN 5 /6


6. INTERNAL CORROSION PROTECTION

Internal corrosion protection is not applied for LPG service

7. REGULAR PIPE CLEANING

Regular pipe cleaning is not required for LPG service

8. EXTERNAL CORROSION PROTECTION

8.1 Atmospheric Corrosion

Carbon steel piping and equipment expose to a humid atmospheere will be subject to atmospheric
corrosion. Since atmospheric corrosion is an electrolytic proccess, the presence of water is required.
Apart from wetting by rainstorms, surfaces can have an adsorbed layer of water if the relative
humidity of the surrounding atmosphere is sufficiently high. It is generally accepted that relative
humidity in excess of about 70% lead to adsorbed layers of water molecules.
This layer in combination with salt contamination from the marine environment will lead
to general surface corrosion and Possible pitting corrosion. The corrosion of bare carbon steel in
atmosphere is severe and hence all surfaces shall be coated in atmospheric.

8.2. Corrotion Protection

External corrosion protection of piping and equipment will be accomplished by the


application of protective coatings in accordance with the project coating specification. The
external corrosion is assumed to be zero on the basis all exposed coatings will be
maintainned as required.
Stainless steel material is only applied for odorant injection line, the others piping material
applied for LPG services is Carbon steel. Insulation is also not applied for high pressure LPG
system.

8.3 Fireproofing

API 218, Fireproofing practices in petroleum and petrochemical processing plant,


contains guidance on selecting and installing fire resistant coatings to protect exposed
steel supports from a high–challenge fire exposure. It also contains a general discussion
on determining need for such protection and estimating the extent of the area exposed.

a) Drainage to a safe location to prevent liquid from accumulating under pipe ways
b) Fire resistive construction
c) Fire resistant protective coating system
d) Water spray system designed and installed in accordance with NFPA 15, standard
for water spray fixed system for fire protection
e) Other alternative material acceptable and as long having jurisdiction.

TLB-050-SP-002_0 Piping Class Specification HALAMAN 6 /6