wire

capacitor size for


rating star
and cable delta
size…. starter
capacitor KVA wire size in mm size of motor i/c cable o/g cable
1-2 KVR 1.5 5.5-7.5 6 4X2
3-5KVR 2.5 9.3 6 4X2
7.5-10KVR 4 11 6 4X2
15 KVR 6 15 10 6X2
20 KVR 10 18 10 6X2
25 KVR 10 22 16 10X2
30 KVR 16 30 16 10X2
40 KVR 16 37 25 16X2
50 KVR 25 45 25 16X2
KVR 50 35 25X2
KVR 75 50 35 X 2

BUS BAR SIZE


AMPEAR 63 100 125 160 200 250 320 400 500 630
ALMUNIUM 20X3 20X6 25X6 20X10 25X10 25X10 40X10 40X10 50X10 40X10*2
COPPER 20X3 20X3 25X3 20X5 25X5 25X6 30X6 25X10 30X10 40X10

AMPEAR 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
ALMUNIUM (40X10)X2 50X10*2 60X10*2 80X10*2 100X10*2 100X10*3 125X10*3 125X10*4 150X10*4 125X10*6
COPPER 50X12 40X10*2 50X10*2 60X10*2 80X10*2 100x10*2 100X10*3 100X10*4 125X10*4 125X6*8
stander thickness = 3mm 6mm 10mm
standerd widh = 20mm 25mm 30mm 40mm 50mm 60mm 80mm 100mm 125mm 150mm