McDONALD’S TYPICALS Page 1 of 15

DATE : 7-12-11 UPDATED: xx/xx/xx

OVERVIEW
THESE ASSEMBLIES WERE DEVELOPED USING EXTERIOR ASSEMBLIES CURRENTLY USED ON RECENT McDONALD’S PROJECT. THE
INTENT IS TO HELP STANDARDIZE THE LANGUAGE AND THE COMPONENTS OF EACH ASSEMBLY TO REDUCE CONFLICTS. THE ID
FOR EACH ASSEMBLY IS INTENDED TO REPRESENT THE BASIC COMPONENTS OF EACH ASSEMBLY. WHILE THESE ASSEMBLIES
WILL APPLY TO MOST CONDITIONS THERE MAY BE A NEED ON SOME PROJECTS TO MODIFY THE ASSEMBLY OR CREATE NEW
ASSEMBLIES FOR SPECIFIC JOBS.

DRAWINGS
 ESTABLISHED WHICH ASSEMBLIES APPLY TO EACH PROJECT AND INSERT IN THE DOCUMENTS.
 USE THE ASSEMBLIES TO IDENTIFY “TYPICAL” CONSTRUCTION CONDITIONS. SPECIAL OR UNIQUE
CONDITIONS SHOULD BE DESCRIBED AND DETAILED ON THE DOCUMENTS.
 SOME ASSEMBLIES, BASED ON JOB-SPECIFIC CONDITIONS, MAY REQUIRE MODIFICATION OF AN
ASSEMBLY. MAKE THAT MODIFICATION ON THE ASSEMBLY DESCRIPTION. IF A JOB SPECIFIC CONDITION,
SUCH AS FRAMING OUT A STUD WALL TO ALIGN WITH THE UNKNOWN DIMENSIONS OF AN EXISTING
WALL, SAY THAT THE STUD WALL (INDICATE METAL OR WOOD) SHALL BE “ ’X’ STUDS AT 16” O.C. AS
SHOWN ON DRAWINGS” OR SOME OTHER APPROPRIATE LANGUAGE.
 SOME ASSEMBLIES REQUIRE SELECTIONS (RED – GREEN) BASED ON JOB-SPECIFIC CONDITONS OR
STRUCTURAL INPUT. IF LOAD BEARING MASONRY IS REQUIRED, MAKE THAT SELECTION. IF LOAD
BEARING STEEL STUDS ARE REQUIRED, THE ASSEEMBLY LANGUAGE REFERS TO STRUCTURAL DWGS FOR
THE GAUGE AND TYPE OF STUD. THE ARCH. DWGS WILL SHOW THE DEPTH AND SPACING ONLY. MAKE
SURE THAT THE STRUCTURAL DRAWINGS INDICATE THIS INFORMATION FOR THE STUDS.

NOTES
 WALL CONSTRUCTION IDENTIFICATION IS BASED ON MATERIALS/SYSTEMS USED IN ASSEMBLY
 LET FINISH SCHEDULE ESTABLISH INTERIOR WALL, CEILING AND BASE FINISH. SHOW A GENERIC GRAPHIC
FOR SUCH FINISHES BUT REFERENCE THE FINISH SCHEDULE
 THE GOAL IS TO HAVE EACH IDENTIFYING TAG BE UNIQUE TO EACH WALL ASSEMBLY.
 THE SYSTEM MAY NOT WORK PRECISELY FOR EVERY APPLICATION BUT SHOULD SUFFICE FOR MOST
APPLICATIONS. WE’LL TREAT SPECIAL, SITE SPECIFIC ASSEMBLIES AS THEY ARISE.

LEGEND: ADD ANY NEW ABBREVIATIONS TO OUR McD ABBREVIATION LIST

BR BRICK VENEER; 4” NOMINAL DEPTH

BT THIN BRICK OR BRICK TILE; ½” THICKNESS

CS CULTURED STONE

CM CORRUGATED METAL

CMU8 CONCRETE MASONRY UNIT; SUFFIX NUMBER INDICATES NOMINAL THICKNESS.

NOTE CMU MAY BE A WALL STRUCTURE AND/OR AN EXTERIOR FINISH MATERIAL


McDONALD’S TYPICALS Page 2 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

EF EIFS EXTERIOR WALL SYSTEM. IF THERE ARE MORE THAN ONE TYPE OF EIFS USED SUCH
AS 1-1/2” INSULATION AND 2” INSULATION, ETC. LABEL THEM WITH A “1” OR “2”
SUFFIX

MFR MANUFACTURER (THE PRESENT ABBRV. OF “MFGR” MAKES NO SENSE, THERE’S NO “G”
IN “MANUFACTURER” – REPLACE IT WITH MFR.))

PAR PARAPET ASSEMBLY

STM6 METAL STUD; SUFFIX NUMBER INDICATES NOMINAL OR ACTUAL THICKNESS. A 3-5/8”
METAL STUD WOULD BE CONSIDERED AS 4” NOM. THE TEXT DESCRIPTION OF THE
ASSEMBLY WOULD CLARIFIY THE ACTUAL STUD DEPTH SINCE THERE ARE 4” FULL DEPTH
METAL STUDS AVAILABLE.

STW4 WOOD STUD; SUFFIX NUMBER INDICATES NOMINAL THICKNESS

ST STONE VENEER; REAL OR SYNTHETIC

ASSEMBLY IDENTIFYING METHOD:


NOM. WALL CONSTRUCTION DEPTH+WALL STRUCTURE/TYPE + EXTERIOR FINISH

EXAMPLE: 14 CMU8 BR

 THE NOMINAL DIMENSION IS ONLY AN IDENTIFYING TAG. WHEN DIMENSIONING A DRAWING YOU CAN
USE THE ACTUAL DIMENSION OF THE ASSEMBLY IF IT IS SIGNIFICANTLY DIFFERENT THAN THE NOMINAL.
IN MOST CASES, THE NOMINAL DIMENSION WILL BE VERY CLOSE TO THE ACTUAL.

EXAMPLES:
 A 14-CMU8-BR WALL SHOULD ACTUALLY BE 14” WHICH WILL PRODUCE A 2-3/4” CAVITY.
 A 9.5-CMU8-EF ASSEMBLY IS ACTUALLY 9-1/4” (7-5/8” + 1-1/2”) WHEN CIONSIDERING THE MEASURABLE
COMPONENTS. HOWEVER, WHEN CONSIDERING THE VAPOR BARRIER COATING AND THE EIFS FINISH,
THE COMPLETED ASSEMBLY WILL BE 9-1/2”.
 A 6-STW-EF IS ACTUALLY 5-3/4” (3-1/2” + ½” +1-1/2” + ¼” = 5-3/4”). IN THIS CASE IT’S YOUR CHOICE TO
USE 6” OR 5-3/4” WHEN DIMENSIONING. JUST BE CONSISTENT

DO NOT INCLUDE THE INTERIOR FINISH IN THE EXTERIOR WALL DIMENSION’ LET THE INTERIOR FINISH SCHEDULE
ESTABLISH THAT.

EXAMPLES:

1. AN 8” CMU WALL WITH STANDARD BRICK VENEER: 14CMU8-BR (THIS ASSEMBLY WILL INCLUDE A 2”
CAVITY TO ACCOUNT FOR THE 14” OF DEPTH)
2. A 6” STEEL STUD WALL WITH THIN BRICK VENEER: 8STM6-BT (THIS ASSEMBLY WILL INCLUDE A 1-1/2”
INSULATION TO ACCOUNT FOR THE 8” OF DEPTH)
3. 6” WOOD STUD WALL WITH EIFS: 8STW6 – EF (THIS ASSEMBLY WILL INCLUDE A 1-1/2” INSULATION PLUS
½ OR 5/8” SHEATHINGTO ACCOUNT FOR THE 8” OF DEPTH)

WHERE COLORED TEXT IS SHOWN, YOU MUST SELECT ONE OR THE OTHER BASED ON THE REQUIREMENTS OF THE
JOB.
McDONALD’S TYPICALS Page 3 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

EXTERIOR WALL CONSTRUCTION TYPES - BRICK VENEER/CMU

ID: 14-CMU8-BR
 8” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT (LOAD BEARING, ASTM C90,
HOLLOW UNITS, NORMAL WEIGHT) RUNNING BOND; SEE STRUCT. DWGS FOR REINFORCEMENT.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8”, 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 12-CMU6-BR
 6” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT; RUNNING BOND; SEE
STRUCT. DWGS FOR REINFORCEMENT.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8” , 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 4 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

BRICK VENEER/WOOD STUDS

ID: 12-STW6-BR
 2” X 6” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8”, 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 10-STW4-BR
 2” X 4” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8” , 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 5 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

BRICK VENEER/METAL STUDS

ID: 12-STM6-BR
 6” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS.
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8”, 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 10-STM4-BR
 3-5/8” @ 16” O.C. (MAX.) METAL STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS.
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 CAVITY: MINIMUM 2” CLEAR
 RIGID INSULATION BOARD; CLOSED CELL INSULATION COMPLYING WITH ASTM C 578 or C 1289; 1” THICK; R5 MIN.
ADHERED OR MECHANICALLY FASTENED TO BACK UP WALL.
 BRICK VENEER; NOMINAL 4” WYTHE TO MATCH SIZE, COLOR AND TEXTURE OF EXISTING BRICK; MATCH EXISTING
BOND AND MORTAR (AS SELECTED BY MCDONALD’S ACM)
 FLASHING LOCATIONS: MORTAR DRAINAGE COLLECTION DEVICE (MDCD); DEPTH TO SUIT CAVITY. CONTINUOUS 40
MIL, SELF-ADHEREING FLEXIBLE FLASHING INSTALLED OVER CONTINUOUS 60 MIL DRIP EDGE*; PROVIDE FLASHING
END DAMS AT FLASHING TERMINATIONS. PROVIDE WEEPS: 24” O.C. MAX; FULL HT. AND DEPTH; PVC HONEYCOMB
VENTS; COLOR TO MATCH BRICK. PROVIDE AT LINTELS, WINDOW/DOOR HEADS, WINDOW SILLS, BOTTOM OF WALL
AND OTHER INTERRUPTIONS OF THE CAVITY. MIN. FLASHING HEIGHT: 8” , 1” MIN. LAP INTO CMU OR SECURE WITH
MFR. APPROVED TERMINATION BAR ASSEMBLY. TERMINATE FLASHING ABOVE MDCD WHERE APPLICABLE.
*DRIP EDGE AND MDCD SHALL BE OMITTED AT WINDOW SILL FLASHING AND OTHER LOCATIONS WHICH CANNOT
ACCOMMODATE THESE DEVICES; USE 3/8” O.D. PLASTIC WEEPS AT 24” O.C IN LIEU OF HONEYCOMB VENTS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 6 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

CULTURED STONE VENEER/CMU

ID: 10-CMU8-CS
 8” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT (LOAD BEARING, ASTM C90,
HOLLOW UNITS, NORMAL WEIGHT) RUNNING BOND; SEE STRUCT. DWGS FOR REINFORCEMENT.
 PROVIDE CMU MANUFACTURED WITH INTEGRAL LIQUID POLYMERIC WATER REPELLENT COMPLYING WITH ASTM
E514; USE MORTAR /GROUT WITH COMPATIBLE WATER REPELLENT ADMIXTURE.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USED CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 8-CMU6-CS
 6” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT; RUNNING BOND; SEE
STRUCT. DWGS FOR REINFORCEMENT.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USE CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 7 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

CULTURED STONE VENEER/WOOD STUDS

ID: 8-STW6-CS
 2” X 6” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 WATER RESISTIVE BARRIER: 2 LAYERS; NO 15, TYPE 1, ASPHALT SATURATED FELT, ASTM D226.
 MORTAR SCRATCH COAT WITH 2.5 LB. GALV. EXPANDED METAL LATH OR 18 GA. GALV. WOVEN WIRE MESH OR 3.4
LB GALV. EXPANDED RIB LATH. FASTENERS: MFR. RECOMEMNDED GALV. SCREWS
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USED CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 6.5-STW4-CS
 2” X 4” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 WATER RESISTIVE BARRIER: 2 LAYERS; NO 15, TYPE 1, ASPHALT SATURATED FELT, ASTM D226.
 MORTAR SCRATCH COAT WITH 2.5 LB. GALV. EXPANDED METAL LATH OR 18 GA. GALV. WOVEN WIRE MESH OR 3.4
LB GALV. EXPANDED RIB LATH. FASTENERS: MFR. RECOMEMNDED GALV. SCREWS
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USED CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 8 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

CULTURED STONE VENEER/METAL STUDS

ID: 8.5-STM6-CS
 6” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS.
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 WATER RESISTIVE BARRIER: 2 LAYERS; NO 15, TYPE 1, ASPHALT SATURATED FELT, ASTM D226.
 MORTAR SCRATCH COAT WITH 2.5 LB. GALV. EXPANDED METAL LATH OR 18 GA. GALV. WOVEN WIRE MESH OR 3.4
LB GALV. EXPANDED RIB LATH. FASTENERS: MFR. RECOMEMNDED GALV. SCREWS
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USED CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 6.5-STM4-CS
 3-5/8” @ 16” O.C. (MAX.) METAL STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS.
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 WATER RESISTIVE BARRIER: 2 LAYERS; NO 15, TYPE 1, ASPHALT SATURATED FELT, ASTM D226.
 MORTAR SCRATCH COAT WITH 2.5 LB. GALV. EXPANDED METAL LATH OR 18 GA. GALV. WOVEN WIRE MESH OR 3.4
LB GALV. EXPANDED RIB LATH. FASTENERS: MFR. RECOMEMNDED GALV. SCREWS
 STONE INSTALLATION SETTING BED: TYPE N OR S MORTAR
 CULTURED STONE VENEER; OWENS-CORNING, BORAL STONE PRODUCTS LLC; PRODUCT “COBBLEFIELD”, AVERAGE
DEPTH 1-3/4”; COLOR TEXAS CREAM – CVS-2083 EXCEPT WHERE OTHER COLOR OR PRODUCT IS SELECTED BY
MCDONALD’S ACM.
 CULTURED STONE DETAILS: FOLLOW MFR STANDARD DETAILS INCLUDING DRIP SCREEDS AT THE BASE OF STONE
VENEER, AT HEADS OF WINDOWS AND DOORS AND OTHER SIMILAR LOCATIONS; USED CASING BEADS WHERE
RECOMMENDED BY THE MFR.
 MORTAR: PREMIXED TYPE N OR S OR MORTAR MIXED FOLLOWING MFR. SPECIFICATIONS. COMPLY WITH ASTM
C270. COLOR AS SELECTED BY MCDONALD’S ACM
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 9 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

EIFS VENEER/CMU

ID: 9.5-CMU8-EF
 8” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT (LOAD BEARING, ASTM C90,
HOLLOW UNITS, NORMAL WEIGHT) RUNNING BOND; SEE STRUCT. DWGS FOR REINFORCEMENT.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 7.5-CMU6-EF
 6” CMU, NON-LOAD BEARING, ASTM C129, HOLLOW UNITS, NORMAL OR LIGHTWEIGHT; RUNNING BOND; SEE
STRUCT. DWGS FOR REINFORCEMENT.
 JOINT REINFORCEMENT AT 16” OC. MAX. VERT.;ADJUSTABLE MULTI-WYTHE , LADDER TYPE WITH LOCKING
ADJUSTABLE ANCHORS AT 16” O.C.; RODS: ASTM A 82/A 82M STEEL WIRE MILL GALV. TO ASTM A 641/A 641M, CLASS
3; 0.1875 INCH. SIZE REINF. TO PROVIDE BETWEEN ½” AND 1” OF MORTAR COVER.
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 10 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

EIFS VENEER/WOOD STUDS

ID: 5.5-STW4-EF
 2” X 4” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 7.5-STW6-EF
 2” X 6” @ 16” O.C. (MAX.) WOOD STUDS; SEE STRUCTURAL DWGS. FOR SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 11 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

EIFS VENEER/METAL STUDS

ID: 8-STM6-EF
 6” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 6” NOM. R-19 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE

ID: 6-STM4-EF
 3-5/8” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
 FIBERGLASS BATT INSULATION; 3-1/2” NOM. R-13 WITH FACTORY APPLIED VAPOR BARRIER FACING.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH. USE MFR’S HIGH IMPACT MESH FROM FOUNDATION UP TO
CANOPY, TRELLIS OR OTHER HORIZONTAL EXTERIOR ELEMENT WHICH IS A MINIMUM OF 8’-0” ABOVE
GRADE WHICHEVER IS GREATER.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
 INTERIOR FINISH: SEE FINISH SCHEDULE
McDONALD’S TYPICALS Page 12 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

PARAPET ASSEMBLIES

CORRUGATED METAL EXTERIOR/WOOD STUDS

ID: PAR-STW4-CM
 2” X 4” @ 16” O.C. (MAX.) WOOD STUDS; REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION. SEE
STRUCTURAL DWGS. FOR SPECIFICATIONS.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 VAPOR BARRIER; MAX. 0.05 PERMS (ASTM 98); 30# FELT WITH HORIZONTAL OVERLAPS AND ENDLAPS STAGGERED
BETWEEN LAYERS.
 7/8” X 2.67” PREFINISHED CORRUGATED METAL PANELS ANCHORED WITH MFR. RECOMMENDED GASKETED SCREWS,
TRIM, FLASHINGS,CLOSURES ,ETC; INSTALL AS RECOMMENDED BY MFR. EXCEPT WHERE OTHERWISE INDICATED
INSTALL WITH MFR. STANDARED DETAILS
 PANELS: MFR: PAC-CLAD/PETERSEN ALUMINUM CORP. SMOOTH 24 GAUGE STEEL; PREFINISHED - KYNAR 500 OR
HYLAR 500 WITH A 20 YEAR MFR. NON-PRORATED WARRANTY; COLOR: CITYSCAPE
 ALTERNATE PANEL MFR: EQUAL PRODUCTS BY BERRIDGE MANUFACTURING CO.; COLOR LEAD-COTE

ID: PAR-STW6-CM
 2” X 6” @ 16” O.C. (MAX.) WOOD STUDS; REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION. SEE
STRUCTURAL DWGS. FOR SPECIFICATIONS.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 VAPOR BARRIER; MAX. 0.05 PERMS (ASTM 98); 30# FELT WITH HORIZONTAL OVERLAPS AND ENDLAPS STAGGERED
BETWEEN LAYERS.
 7/8” X 2.67” PREFINISHED CORRUGATED METAL PANELS ANCHORED WITH MFR. RECOMMENDED GASKETED SCREWS,
TRIM, FLASHINGS,CLOSURES ,ETC; INSTALL AS RECOMMENDED BY MFR. EXCEPT WHERE OTHERWISE INDICATED
INSTALL WITH MFR. STANDARED DETAILS
 PANELS: MFR: PAC-CLAD/PETERSEN ALUMINUM CORP. SMOOTH 24 GAUGE STEEL; PREFINISHED - KYNAR 500 OR
HYLAR 500 WITH A 20 YEAR MFR. NON-PRORATED WARRANTY; COLOR: CITYSCAPE
 ALTERNATE PANEL MFR: EQUAL PRODUCTS BY BERRIDGE MANUFACTURING CO.; COLOR LEAD-COTE

CORRUGATED METAL EXTERIOR/METAL STUDS

ID: PAR-STM4-CM
 3-5/8” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION..
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 VAPOR BARRIER; MAX. 0.05 PERMS (ASTM 98); 30# FELT WITH HORIZONTAL OVERLAPS AND ENDLAPS STAGGERED
BETWEEN LAYERS.
 7/8” X 2.67” PREFINISHED CORRUGATED METAL PANELS ANCHORED WITH MFR. RECOMMENDED GASKETED SCREWS,
TRIM, FLASHINGS,CLOSURES ,ETC; INSTALL AS RECOMMENDED BY MFR. EXCEPT WHERE OTHERWISE INDICATED
INSTALL WITH MFR. STANDARED DETAILS
 PANELS: MFR: PAC-CLAD/PETERSEN ALUMINUM CORP. SMOOTH 24 GAUGE STEEL; PREFINISHED - KYNAR 500 OR
HYLAR 500 WITH A 20 YEAR MFR. NON-PRORATED WARRANTY; COLOR: CITYSCAPE
 ALTERNATE PANEL MFR: EQUAL PRODUCTS BY BERRIDGE MANUFACTURING CO.; COLOR LEAD-COTE
McDONALD’S TYPICALS Page 13 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

ID: PAR-STM6-CM
 6” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 VAPOR BARRIER; MAX. 0.05 PERMS (ASTM 98); 30# FELT WITH HORIZONTAL OVERLAPS AND ENDLAPS STAGGERED
BETWEEN LAYERS.
 7/8” X 2.67” PREFINISHED CORRUGATED METAL PANELS ANCHORED WITH MFR. RECOMMENDED GASKETED SCREWS,
TRIM, FLASHINGS,CLOSURES ,ETC; INSTALL AS RECOMMENDED BY MFR. EXCEPT WHERE OTHERWISE INDICATED
INSTALL WITH MFR. STANDARED DETAILS
 PANELS: MFR: PAC-CLAD/PETERSEN ALUMINUM CORP. SMOOTH 24 GAUGE STEEL; PREFINISHED - KYNAR 500 OR
HYLAR 500 WITH A 20 YEAR MFR. NON-PRORATED WARRANTY; COLOR: CITYSCAPE
 ALTERNATE PANEL MFR: EQUAL PRODUCTS BY BERRIDGE MANUFACTURING CO.; COLOR LEAD-COTE

PARAPET: EIFS EXTERIOR/WOOD STUDS

ID: PAR-STW4-EF
 2” X 4” @ 16” O.C. (MAX.) WOOD STUDS; REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION. SEE
STRUCTURAL DWGS. FOR SPECIFICATIONS.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.

ID: PAR-STW6-EF
 2” X 6” @ 16” O.C. (MAX.) WOOD STUDS; REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION. SEE
STRUCTURAL DWGS. FOR SPECIFICATIONS.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
McDONALD’S TYPICALS Page 14 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

PARAPET: EIFS EXTERIOR/METAL STUDS

ID: PAR-STM4-EF
 3-5/8” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.

PAR-STM6-EF
 6” STEEL STUDS @ 16” O.C. (MAX.) SEE STRUCTURAL DWGS. FOR GAUGE, STUD TYPE AND SPECIFICATIONS
REFER TO DWGS FOR RAFTERS AND PARAPET CONFIGURATION.
 ½” PLYWOOD SHEATHING; EXTERIOR EXPOSURE CLASS, APA-PRP 108, STRUCTURAL 1; SPAN RATING 24/0
 LIQUID APPLIED VAPOR BARRIER; COLD APPLIED, UV AND FUNGUS RESISTANT, 40 MIL MIN. THICKNESS, COMPLYING
WITH ASTM C 836; VOC COMPLIANT; MAX. 0.2 PERM AS PER ASTM E 96/E 96M.
 NON-BARRIER TYPE EIFS EXTERIOR WALL SYSTEM: USE ONLY MANUFACTURER RECOMMENDED COMPONENTS
-1-1/2” GROOVED EPS RIGID INSULATION MECHANICALLY FASTENED OVER PEMEABLE MEMBRANE
-CORRUGATED PLASTIC DRAINAGE STRIP AT BASE OF PANEL WITH CONTINUOUS PVC “J” CHANNEL WITH
INTEGRAL WEEPS.
- OPEN WEAVE FIBER REINFORCING MESH.
-MANUFACTURER’S REINFORCED BASE COAT BASE COAT WITH COLORED FINISH COAT OVER.
-SEE ELEVATIONS FOR EIFS FINISH COLORS.
McDONALD’S TYPICALS Page 15 of 15
DATE : 7-12-11 UPDATED: xx/xx/xx

MISCELLANEOUS ASSEMBLIES

FURRED WALLS (OVER EXTERIOR MASONRY WALL ASSEMBLIES – NEW OR EXISTING)

ID: 2-FW
 1-1/2”DEEP WOOD FURRING @16” O.C.; PRESERVATIVE TREATED; DRAFTSTOP AT TOP AND BOTTOM; MECHANICALLY
FASTEN TO CMU.
 ½” GWB; REFER TO FINISH SCHEDULE REGARDING TYPE OF GWB.
 PROVIDE STRIP OF ½”FIBER REINFORCED CEMENT BOARD BEHIND BASE – SEE FINISH SCHEDULE; HOLD ½” ABOVE
FLOOR SLAB.

ID: 1.5-FW
 7/8” DEEP WOOD FURRING @16” O.C.; PRESERVATIVE TREATED; DRAFTSTOP AT TOP AND BOTTOM; MECHANICALLY
FASTEN TO CMU.
 ½” GWB; REFER TO FINISH SCHEDULE REGARDING TYPE OF GWB.
 PROVIDE STRIP OF ½”FIBER REINFORCED CEMENT BOARD BEHIND BASE – SEE FINISH SCHEDULE; HOLD ½” ABOVE
FLOOR SLAB.

ID: 2-FM
 1-1/2” METAL FURRING @16” O.C.; PRESERVATIVE TREATED; DRAFTSTOP AT TOP AND BOTTOM; MECHANICALLY
FASTEN TO CMU.
 ½” GWB; REFER TO FINISH SCHEDULE REGARDING TYPE OF GWB.
 PROVIDE STRIP OF ½”FIBER REINFORCED CEMENT BOARD BEHIND BASE – SEE FINISH SCHEDULE; HOLD ½” ABOVE
FLOOR SLAB.

ID: 1.5-FM
 7/8” METAL FURRING @16” O.C.; PRESERVATIVE TREATED; DRAFTSTOP AT TOP AND BOTTOM; MECHANICALLY
FASTEN TO CMU.
 ½” GWB; REFER TO FINISH SCHEDULE REGARDING TYPE OF GWB.
 PROVIDE STRIP OF ½”FIBER REINFORCED CEMENT BOARD BEHIND BASE – SEE FINISH SCHEDULE; HOLD ½” ABOVE
FLOOR SLAB.