You are on page 1of 1

ABB Process Automation Division

LBU Service OGP A08753-SAT


Prepared by Dept. Date Language Revision Nr. Pages

Operation SSG 06/03/13 en 0 1 (1)

3BJT 202302
Weekly Report Mod. 006

CUSTOMER RAS LANUF OIL & GAS PROCESSING COMPANY


CUSTOMER ORDER 182 / 2010 (re-issued)
PLANT POLIETHILENE
SITE RAS LANUF (LIBYA)
Activities description Technician Date
Survey of the installation, check of the components already in service MALINVERNI A. 06/03/2013
and to be installed. Check of the system and application software. NAKHLI M.
FO communication from Main Control Room to Harbour: spiders have MALINVERNI A. 07/03/2013
been mounted and connected to existing patch panels end testing of NAKHLI M..
the FO line has started.
Testing activity of the F.O. line to Harbour completed successfully. MALINVERNI A. 08/03/2013
Debugging of the domain controllers DCAS1 & DCS2: the two Domain NAKHLI M.
Controllers were turned off for long time (from Nov.2009 to May 2010)
and an internal flag called “tombstone lifetime” was expired and no
replication of the active directory data was possible (this may also lead
to other problems reported in the punch list).
Minor activities: modified operator workplace, checked Hardware
Status of servers (connectivity server 1 gives error on Sata Cable B,
this problem is probably due to the motherboard, KVM cable for
DCAS2 not working properly and to be replaced).
Equipment (200m FO cable, spiders and RJ cables) for connection of MALINVERNI A. 09/03/2013
OS5&6 to Compound Room laid down. NAKHLI M.
Repair of ASDC2 (demoted to workstation and promoted again to
Domain Controller) and testing of active directory functions.
Uploaded tags from DCS Controllers to populate the control structure.
Started checks and corrections on graphic displays. MALINVERNI A. 10/03/2013
Configuration of RTA board of CS1 and CS2 and Tag upload of NAKHLI M.
Safeguard Nodes 71/72 and 81/82.
Checks and corrections on graphic displays. MALINVERNI A. 11/03/2013
Screens and FX100 for operator stations 1,2,4 are were put in NAKHLI M.
service.
Fixed OS1 problem (not possible to see graphic displays).
OS7 was mounted into the cabinet, connected to CS network and MALINVERNI A. 12/03/2013
spider and loaded with XP and 800xA software. NAKHLI M.
Minor activities: screen saver and power saving options removed from
clients, tuning of 800xA for OS6 (7).
ABB Nome / Name Signature Date
MALINVERNI A.
NAKHLI M.
Customer Company Name / Signature Date
RAS LANUF OIL & GAS PROCESSING Ahmed Al zawawi
COMPANY