You are on page 1of 3

Document No.

: 17000045
Document Type: TSW
Version: 02
Creator: AMC
Approver: JNY

Controller Settings
WP2000, M1500-750/175 kW
1 Purpose
Settings for WTG (See point 2)
To obtain correct operation for WTG during all effect as wind, grid, temp etc.

2 Validity

2.1 M1500-750/175 690V 50Hz

2.2 Project No.


P93043

2.3 Program revision:


040130 Standard

3 References

3.1 HO-0352 (Project P93043 WP2000 Program description)

3.2 HO-0376 Mappe 6 (Wiring diagram)

4 Remarks:

Page 1 of 3

NEG Micon Control Systems A/S • Frankrigsvej 15 • DK- 8450 Hammel • Tel.: +45 87 62 26 00 • Fax: +45 87 62 26 01
CVR - Nr: 11 45 04 74 • www.control- systems.com • mail@control - systems.com
Document No.: 17000045
Document Type: TSW
Version: 02
Creator: AMC
Approver: JNY

5 Parameters
Date <YYMMDD> XXXXXX VANE DIF. 15 M T10 WATER FORWARD
Time <HHMMSS> XXXXXX ANEMOM. DEF. 9999 M OFF/ON (0/1) 1
SOMMER 1=-1h/2=+1h 2 GEAR OLIE LOW 30°C ALARM 75°C
START DATE<MMDD> 0330 OILPUMP OFF 40°C
END DATE <MMDD> 1026 OP.INTERV.OFF 70°C T1 WATER RETURN
0:GB 1:DK 2:D 0 T6 MIN. NEG. =0/1 0 SETPOINT OFF 0°C
ID NUMBER XXXXXXXX T6 MIN. 0°C SETPOINT ON 0°C
WP PHONE Turbine T7 CAL. - 0°C
Phone T1 WATER RETURN T2 GENERATOR 2
ALARM PHONE NO. : OFF/ON (0/1) 1 SETPOINT OFF 0°C
1: XXXXXXXX ALARM 75°C SETPOINT ON 0°C
2: XXXXXXXX
3: XXXXXXXX T2 GENERATOR 2 T3 GEN. BEAR. DE
4: XXXXXXXX OFF/ON (0/1) 1 SETPOINT OFF 0°C
5: XXXXXXXX ALARM 155°C SETPOINT ON 0°C
6: XXXXXXXX [Elin 180°C]
DIALING .... T1-3 3 T4 GENERATOR 1
DIALING .... T4-6 3 T3 GEN.BEAR.DE SETPOINT OFF 0°C
MODEM INSTAL.0/1/2 X OFF/ON (0/1) 1 SETPOINT ON 0°C
0:? 1:TONE 2:PULS X ALARM 100°C
BAUD RATE: 1200 T5 GEAR BEARING
STOP. TOO LONG 600M T4 GENERATOR 1 SETPOINT OFF 65°C
BRAKE COOL 600 S OFF/ON (0/1) 1 SETPOINT ON 80°C
AUTO RESET 600 S ALARM 155°C
STARTWIND 2,0 M/S [Elin 180°C] T6 GEAR OIL
FILTER CHOKED 300 S SETPOINT OFF 55°C
R-S-T 120° +/- 6° T5 GEAR BEARING SETPOINT ON 65°C
GRID ERROR 0,2 S OFF/ON (0/1) 1
CAL. LINE-1 U 476 ALARM 110°C T7 OUTDOOR
CAL. LINE-2 U 476 SETPOINT OFF 0°C
CAL. LINE-3 U 476 T6 GEAR OIL SETPOINT ON 20°C
CAL. LINE-1 I 888 OFF/ON (0/1) 1
CAL. LINE-2 I 888 ALARM 85°C T8 MAINBOARD
CAL. LINE-3 I 888 SETPOINT OFF 0°C
MAX CUT.IN 20 S T7 OUTDOOR SETPOINT ON 0°C
BRAKING TIME 10 S OFF/ON (0/1) 1
TIPBR. 0>P 180,0 S ALARM 60°C T9 GEN.BEAR.-NDE
T>M BRAKE 45,0 S SETPOINT OFF 0°C
T>M BRAKE 700 RPM T8 MAINBOARD SETPOINT ON 0°C
G>0 40,3 KW OFF/ON (0/1) 1
MAX P. TIME 20,1 S ALARM 60°C T10 WATER FORWARD
STOP WIND 25,0 M/S SETPOINT OFF 0°C
WIND DOWN 18,0 M/S T9 GEN.BEAR.-NDE SETPOINT ON 0°C
RES.EXT.VIBR 20,0M/S OFF/ON (0/1) 1
VANE DEF. 9999 M ALARM 100°C

Page 2 of 3

NEG Micon Control Systems A/S • Frankrigsvej 15 • DK- 8450 Hammel • Tel.: +45 87 62 26 00 • Fax: +45 87 62 26 01
CVR - Nr: 11 45 04 74 • www.control- systems.com • mail@control - systems.com
Document No.: 17000045
Document Type: TSW
Version: 02
Creator: AMC
Approver: JNY

G.PULSES 1 /REV ROTOR MESSURE 50 RPM WIND 0>>G1 9,0 M/S


MAX VOLT. 437 V MAX ROTOR 30 RPM CURR. _>>G1 840 A
MAX VOLT. 60,0 S MAX GENER. 1575 RPM YAW 0>G1 9,0 M/S
MIN VOLT. 358 V CUT IN MAX 1550 RPM YAW 0>G1 0 °
MIN VOLT. 60,0 S MAX POWER 840 KW POWER G2>0 -01 KW
LINE DROP 999,9 S MAX POWER -200,0 POWER G2>0 60 S
NOMINEL FREQ. 50 Hz KW POWER G1>G2 56 KW
MIN FREQ. 48,5 Hz I1-I2-I3 <> 40 A POWER G1>G2 1200 S
MAX FREQ . 51,5 Hz I1-I2-I3 <> 0,8 S POWER G1>>G2 45 KW
C STRATEGY 0-3 1 YAW /360° 121 [14 POWER G1>>G2 600 S
C 0-STRATEGY 0/1 0 old ver.] POWER G2>G1 112 KW
+COMPENSATOR 950 RPM YAW BY FAULT 30 POWER G2>G1 600 S
++COMPENSATOR 450 A YAW COUNT XXX POWER G2>>G1 135 KW
-COMPENSATOR 840 A WAIT YAWING 3,5 S POWER G2>>G1 240 S
COMPENSATOR -_ 60 S EXTRA YAWING 12,0 S G1>G2 ..>G1 1200 RPM
+COMPENSAT. 0 KVAr INV.INP 08-> 00001010 G1>G2 ..>G1 15 S
-COMPENSAT. 0 KVAr INV.INP 16-> 00000000 WIND 0>G1 9,0 M/S
COMPENSAT.1 50 KVAr INV.INP 24-> 00001000 WIND 0>G1 10 S
COMPENSAT.2 50 KVAr INV.INP 32-> 00110101 WIND G2>G1 9,0 M/S
COMPENSAT.3 50 KVAr INV.INP 40-> 10100000 WIND G2>G1 120 S
COMPENSAT.4 50 KVAr FREE WHEEL=0/1 1 C.-IN 0>G2 950 RPM
COMPENSAT.5 50 KVAr RESTART DELAY 5,0 S CURRENT 0>G2 400 A
COMPENSAT.6 0 KVAr DEL. G2>G2 800 RPM CURRENT G1>G2 750 A
COMPENSAT.7 0 KVAr C.-IN G2>G2 1030 RPM PAUSE G1<>G2 600 S
COMPENSAT.8 0 KVAr C.-IN G2>G2 450 A
C.-IN _>G1 1300 RPM
CURR. _>G1 730 A

Page 3 of 3