You are on page 1of 2

SIC - 2911

APPLICATION NOTE

Boiler / Feedwater Pump Efficiency Optimization


INTRODUCTION
The primary function of a utility Main
800 - 900 psi
Boiler Drum Pressure
boiler is to convert water into Steam
Header
steam to be used by a steam Steam Flow

turbine / generator in producing Feedwater Flow

electricity. The boiler consists of a


875 -1000 psi
furnace, where air and fuel are Feedwater Pressure
combined and burned to produce
combustion gases, and a
feedwater tube system, the con- Blowdown Flow

tents of which are heated by these


gases. The tubes are connected to
the steam drum, where the gener- Furnace
ated water vapor is drawn. In larger Feedwater
utility boilers, if superheated steam Pump

(low vapor saturation) is to be


generated, the steam through the
drum is passed through super-
heater tubes, which are also Economizer

Air Flow
exposed to combustion gases. Water Flow

Boiler drum pressures can reach Flue Feedwater Flow


2800 psi with temperatures over Gas

680 degrees F. Small to intermedi-


ate size boilers can reach drum
pressures between 800 and 900
psi at temperatures of only 520 feedwater flow is regulated by exhaust is used as a heat source.
degrees F if superheated steam is either controlling the pump speed A steam turbine driven feedwater
desired. Small to intermediate size or by using a process control pump is most often applied be-
boilers are only being considered valve. The normal effect of pure cause of the abundance of avail-
for this application note. water corrosion-erosion (or cavita- able steam.
tion) that causes premature seat
With oil-burning and gas-burning failure within the valve is amplified Boiler Optimization
boiler efficiencies over 90%, power because velocities of 10fps + can
plants are examining all associated be reached. The added cost of With a boiler’s firing rate held
processes and controls for effi- frequent valve replacement makes constant, feedwater pressure and
ciency improvements. Between 1 utilizing a feedwater pump the flow affect boiler pressure. As
and 3% of the gross work pro- preferred method of flow control. electricity demands change, so do
duced by a boiler is used to pump Controlling pressure by varying the associated boiler loads. When
feedwater. One method of improv- pump speed saves on overall more electricity needs to be
ing overall efficiency is by control- pump power usage. generated, the boiler produces
ling feedwater pump speed to save more steam, therefore feedwater
on pump power. Pump Speed Control flow must be increased to the
boiler. Significant savings are
Controlling pump speed is accom- realized if boiler drum pressure
plished by variable-speed electric and feedwater discharge pressure
APPLICATION
drives or by close-coupling a are held to a constant differential.
Feedwater Flow Control steam turbine to the pump. By This can be accomplished by
In electrical power plants, de- definition, cogeneration power accurately measuring this pressure
mineralized feedwater is pumped plants produce both electricity and differential and controlling the
to the boiler tube header. The excess steam where turbine pump speed and feedwater

PD-2911-03A
Revision 1, 8/98
Boiler Optimization
1200

1100 Feedwater
Pressure
1000
Recommended
Pressure (psi) Differential
900
Drum Pressure
800

700 Steam
Header
600
Steam Flow (kg / hr)

Chart 1

flowrate accordingly. Many competitors claim re-zeroing * (Also see Application Note SIC -
their transmitter at static line 2911, Boiler Drum Measurement)
pressure minimizes these zero
In this example, boiler drum shifts but this task may not be
pressures can vary between 800 practical under fluctuating pres- DPharp EJA110A
and 900 psi depending upon the sure conditions. The DPharp
load, (see Chart 1). The feedwater transmitter can be bench cali- • + 0.075% Accuracy
pump discharge pressures can brated and installed into a high • 2000 psi maximum span
vary between 875 and 1000 psi static pressure line without re- • 0.01% Adjustment Resolution
depending upon boiler demand. zeroing. DPharp is unaffected by • 2000 psi Overpressure Protec-
Differential pressure between the these pressure surges due to its tion
two points can be up to 200 psi, (or superior overpressure protection. • 2-year As-left, as found calibra-
even higher in system upset We guarantee its performance for tion guarantee
conditions). This differential two years! • 0.2% Total Probable Error (TPE)
pressure must be accurately
measured, without regard to the The power plant’s control system
800 psi and above changing boiler can use the high pressure differen-
drum static pressure. tial measurement to automatically
set the feedwater rate depending
on the boiler load demand. At
SOLUTION lower demand periods, less steam
is used to power the steam turbine
Use DPharp! DPharp’s EJA110A driven pump and less feedwater is
“V” range capsule can measure consumed. Significant savings are
differential pressures up to 2000 realized through steam conserva-
psid with the same + 0.075% of tion and by lowered maintenance
span reference accuracy of lower costs with the use of the DPharp
ranges! In this common application transmitter.
example, ranging the EJA110A “V”
range transmitter 0 to 300 psid
allows for the measurement of both
boiler pressure and feedwater
pump discharge pressure. During
pump start-up severe pressure
spikes of 500 psi + can occur
which can cause shifts in zero.

PD-2911-03A

You might also like