Professional Documents
Culture Documents
APPLICATION NOTE
Air Flow
exposed to combustion gases. Water Flow
PD-2911-03A
Revision 1, 8/98
Boiler Optimization
1200
1100 Feedwater
Pressure
1000
Recommended
Pressure (psi) Differential
900
Drum Pressure
800
700 Steam
Header
600
Steam Flow (kg / hr)
Chart 1
flowrate accordingly. Many competitors claim re-zeroing * (Also see Application Note SIC -
their transmitter at static line 2911, Boiler Drum Measurement)
pressure minimizes these zero
In this example, boiler drum shifts but this task may not be
pressures can vary between 800 practical under fluctuating pres- DPharp EJA110A
and 900 psi depending upon the sure conditions. The DPharp
load, (see Chart 1). The feedwater transmitter can be bench cali- + 0.075% Accuracy
pump discharge pressures can brated and installed into a high 2000 psi maximum span
vary between 875 and 1000 psi static pressure line without re- 0.01% Adjustment Resolution
depending upon boiler demand. zeroing. DPharp is unaffected by 2000 psi Overpressure Protec-
Differential pressure between the these pressure surges due to its tion
two points can be up to 200 psi, (or superior overpressure protection. 2-year As-left, as found calibra-
even higher in system upset We guarantee its performance for tion guarantee
conditions). This differential two years! 0.2% Total Probable Error (TPE)
pressure must be accurately
measured, without regard to the The power plants control system
800 psi and above changing boiler can use the high pressure differen-
drum static pressure. tial measurement to automatically
set the feedwater rate depending
on the boiler load demand. At
SOLUTION lower demand periods, less steam
is used to power the steam turbine
Use DPharp! DPharps EJA110A driven pump and less feedwater is
V range capsule can measure consumed. Significant savings are
differential pressures up to 2000 realized through steam conserva-
psid with the same + 0.075% of tion and by lowered maintenance
span reference accuracy of lower costs with the use of the DPharp
ranges! In this common application transmitter.
example, ranging the EJA110A V
range transmitter 0 to 300 psid
allows for the measurement of both
boiler pressure and feedwater
pump discharge pressure. During
pump start-up severe pressure
spikes of 500 psi + can occur
which can cause shifts in zero.
PD-2911-03A