Professional Documents
Culture Documents
IPC2016
September 26-30, 2016, Calgary, Alberta, Canada
IPC2016-64651
AIV AND FIV IN PIPELINES, PLANTS, AND FACILITIES
Chris B. Harper, P.Eng.
BETA Machinery Analysis
A Wood Group Company
Calgary, Alberta, Canada
ABSTRACT NOMENCLATURE
the RO. This sound energy can also create unwanted vibrations Increase the diameter of
of the pipe wall, and potentially cause fatigue failure of small- the WD risk of FF
Replace the WD with a Extruded tees have axisymmetric welds
bore connections on the pipe. extruded (welding) tee and therefore are not at risk
Change the style of the Sweepolets are more robust than weldolet
An acoustic-induced vibration (AIV) audit was done using WD
the procedure outlined in the Energy Institute “Guideline for Increases the thickness of Thicker mainline piping can lower the risk
the Avoidance of Vibration Induced Fatigue Failure in Process the mainline piping of FF
Pipework” [1], also referred to as EI AVIFF. The risk posed by Reinforce mainline Repads, pipe wraps, and stiffening rings
piping require advanced analysis (phase 3)
AIV is typically to downstream welds that are not Notes:
circumferential, like stub-in branches, small-bore connections, FF Fatigue failure PWL Sound power level
and supports that are welded directly to the pipe. These are PRD Pressure reducing device RO Restrictive orifice plate
PSV Pressure safety valve WD Welded discontinuity
𝑆𝑣
𝐹𝑉 = (2)
𝑑
(2𝑛 − 1) 𝑐
𝐹𝑆 = (3)
Figure 2. Layout of piping 4 𝐿𝑏𝑟𝑎𝑛𝑐ℎ
FLOW-INDUCED VIBRATIONS 𝑐
𝐿𝑏𝑟𝑎𝑛𝑐ℎ = (4)
2 ∗ (𝐹𝑆,𝑛+1 − 𝐹𝑆,𝑛 )
Also during the field visit, pulsation measurements were
taken near the line heaters (H-135A and H-135B) upstream of Assuming a speed of sound in the gas of 396 m/s [1300
the restrictive orifice plate (see Ch. 8 in Figure 2 and Figure 7). ft/s], the deadleg length can be calculated from Eq. (4) to be
The pulsations showed indications of FIV (Figure 5). 11.3 m [37.1 ft]. The field analyst can now begin investigating
the piping system to identify potential sources of the pulsations.
Pulsations can be created in high-velocity gas systems by
flow past the mouth of branch connections that contain zero Typical solutions to FIV problems are listed below:
flow (“deadlegs”). These pulsations are created by the
interaction between vortices and acoustic resonances. An Change the length of the deadleg (typically shorten it)
illustration of this scenario is shown in Figure 4. Avoid certain flowrates of gas
Allow some flow through the deadleg (typically a
The vortices are created when the gas flows past the mouth temporary solution while permanent solutions are
of a deadleg. The vortices are created at a specific frequency developed and installed)
based on Eq. (2). These vortices are amplified by the acoustic Add spoilers to the mouth of the deadleg to eliminate
resonances of the deadleg, which are defined by Eq. (3). When the creation of vortices
there is coincidence between these two frequencies, flow- Add additional supports and bracing to reduce
induced pulsations (FIP) are created in the piping system. vibrations
CH.8 NPS 8”
Figure 5. Upstream pulsation at 1200 e³m³/day (channel 8)
The peak pulsations near the line heater were plotted over
the entire flow range (Figure 6). The area of the circles in the
plot correspond to the pulsation amplitude of the peak. The Figure 7. Piping upstream of orifice plate near line heater
maximum pulsations measured were 76.5 kPa peak-to-peak
[11.1 psi peak-to-peak]. There are no industry guidelines for In discussions with the owner, it was agreed that no
FIP but keeping pulsations less than 3% of line pressure or 225 modifications were required to deal with the flow-induced
kPa peak-to-peak [32.6 psi peak-to-peak] in this case, is pulsations (FIP) that were measured. The reason was the
recommended. The pulsations measured were below guideline. pulsation and vibration levels were low and not predicted to get
worse during the relieving case. Most gas piping system have
The potential forces created by the flow-induced pulsations deadlegs, and most piping systems with deadlegs will have
can be estimated by assuming a worst case situation of the FIPs at certain flow rates. Obviously not all piping systems
pulsations acting on the cross sectional inner area of the pipe have vibration problems, therefore some consideration of the
(Table 2). In general, BETA recommends pulsation-induced pulsation levels should be included in the decision whether to
shaking forces to be less than 4448 N peak-to-peak [1000 lb make modifications.
peak-to-peak]. The worst case forces are acceptable.
SMALL-BORE CONNECTIONS
ACKNOWLEDGMENTS
REFERENCES