HVAC SYSTEM

Department Engineering & Document HVAC/EM/AHU-773


Maintenance No.

Area Media Preparation Page No. 1 of 2

1. Purpose: To determine the Media Preparation area, Air Handling Unit (BV-EM-AHU-773),
Room wise Grade classification, differential pressures, supply and return air grills details &
schematic air circulation of the Air Handling Units.

2. Scope: This document is applicable for Media Preparation area Air Handling Unit
(BV-EM-AHU-773), in M/s. Biovet Private Limited.

3. Description of AHU with Reference to connected room & class.

S.No Room Name Room Grade/ Differential Air Changes /Hr


No Classification Pressure
(mm/WC) (Criteria:NLT)

1 Media R115 C 0.5 To 1.5 40


Preparation

2 Media CHR2 R114 D 0.5 To 1.5 20

4. List of Supply & Return Air Filters Connected to AHU Room Wise.

S.No Room Room Supply Air Filter Return Air Filter


Name No (0.3μ) (10μ)

1 Media R115 BV-EM-AHU-773-SA-001 BV-EM-AHU-773-RA-001


Preparation BV-EM-AHU-773-SA-002 BV-EM-AHU-773-RA-002
BV-EM-AHU-773-SA-003 BV-EM-AHU-773-RA-003
BV-EM-AHU-773-SA-004 BV-EM-AHU-773-RA-004
BV-EM-AHU-773-SA-005 BV-EM-AHU-773-RA-005
BV-EM-AHU-773-SA-006 BV-EM-AHU-773-RA-006
BV-EM-AHU-773-SA-007 BV-EM-AHU-773-RA-007
BV-EM-AHU-773-SA-008 BV-EM-AHU-773-RA-008
BV-EM-AHU-773-SA-009 BV-EM-AHU-773-RA-009
BV-EM-AHU-773-SA-010 BV-EM-AHU-773-RA-010
BV-EM-AHU-773-SA-011 BV-EM-AHU-773-RA-011
BV-EM-AHU-773-SA-012 BV-EM-AHU-773-RA-012
2 Media R114 BV-EM-AHU-773-SA-013 BV-EM-AHU-773-RA-013
Change BV-EM-AHU-773-SA-014 BV-EM-AHU-773-RA-014
Room 2
HVAC SYSTEM

Department Engineering & Document HVAC/EM/AHU-773


Maintenance No.

Area Media Preparation Page No. 2 of 2

5. AHU Air Circulation Details:

This AHU air circulation is as follows

Capacity : 7500 CFM

Fresh Air : 10%

Re-circulation Air : 90%

Exhaust Air : NA

Total Supply Air : 100%

6. Schematic Air Circulation drawing

The schematic air circulation drawing of Air Handling Unit (BV-EM-AHU-773) is as per
following attachment.