Part 2 SPECIFICATIONS...................................................................3
2.1 Unit Specifications...........
.................................................................................. 3
2.2 Operation Characteristic Curve............................................................... 7
2.3 CapacityVariationRatio AccordingtoTemperature ................................... 7
2.4 Operation Date........................................................................................ 8
2.5 Noise criteria curve tables for both models ............................................. 8
Part 9 TROUBLESHOOTING.............................................................40
9.1 Precautions before Performing Inspection or Repair..............................40
9.2 Confirmation ............................................................................................40
9.3 Judgement by Flashing LED of Indoor/Outdoor Unit ...............................40
9.4 How to Check simply the main part ..........................................................42
9.5 2-way, 3-way Valve Appearance ..............................................................46
1.Safety Precautions
Important!
or rubbish.
The unit should be installed according to the instructions
This air conditioning system meets strict safety and in order to minimize the risk of damage from earthquakes,
operating standards. As the installer or service person, typhoons or strong winds.
it is an important part of your job to install or service the When the refrigerant touches the fire elc., it was decomposed
system so it operates safely and efficiently. and a poisonous gas is generated.
To prevent injury to the user or other people and Use only the specified refrigerant to charge the regrigerant
property damage, the following instructions must circuit.
Do not mix it with any other refrigerant and do not allow air to
be followed.
remain in the circuit.
Follow each installation or repair step exactly as shown. Air enclosed in the circuit can cause high pressure resulting
Observe all local, state, and national electrical codes. in a rupture and other hazards.
Pay close attention to all warning and caution notices After completing installation work, make sure that refriger-
given in this manual. ant gas has not leaked.
About the pictograms: The limit density is made not to be exceeded even if the refrig-
erant leaks by any chance.
Warning Erroneous handing gives a high possi-
Turn the power off at the main power box (mains) before open-
bility to induce serious results such as
ing the unit to check or repair electrical parts and wiring.
death or heavy injury.
Keep your fingers and clothing away from any moving parts.
Erroneous handing may induce serious Clean up the site after you finish, remembering to check that
Caution
injury depending on the situation. no metal scraps or bits of wiring have been left inside the unit
being serviced.
The unit must be properly earth connected.
Warning
All electric work must be performed by licensed technician,ac-
cording to local regulations and the instructions given in this Caution
manual.
Do not supply power to the unit until all wiring and tubing Never indtall on the place where a combustible gas might
are completed or reconnected and checked. leak. The gas may ignite or explode when the gas leaks and
Highly dangerous electrical voltages are used in this collects in surround of the unit.
system. Carefully refer to the wiring diagram and these When the unit is installed at telecommunication centers or
instructions when wiring. Improper connections and inad- hospitals, take a proper provision against noise.
equate grounding can cause accidental injury or death. When installing at a watery place, provide an electric leak
Ground the unit following local electrical codes. breaker.
Connect all wiring tightly. Loose wiring may cause over- Do not wash the unit with water.
heating at connection points and a possible fire hazard. Be very careful about unit transportation.The unit shoukd not
There is risk of fire, electric shock, explosion, or injury. be carried by only one person if it is more than 20kg. It occasion-
ally causes the damage of th unit and health to be impaired.
Ask your dealer or specialized subcontractor for installation or
Do not touch the heat exchanger fins whth your bear hands.
repair work.
Doing so may cut your hands.
Make sure the ceiling/wall is strong enough to hold the Do not touch the compressor or refrigerant piping whithout
unit’s weight. The outdoor unit shoukd be installed in a wearing glove on your hands. Touching directly such part can
location where air and noise emitted by the unit will not cause a burn or frostbite as it becomes high or low temperature
disturb the neighbours. according to the refrigerant state.
Properly insulate any tubing run inside a room to prevent Do not operate the air conditioner without the air filter set
"sweating" that can cause dripping and water damage to place. Dust may accumulate, and cause a failure.
walls and floors. At emergency (if you smell something burning), stop opera-
The outdoor unit must be installed on stable, level surface, tion and turn the power source switch off.
in a place where there is no accumulation of snow, leaves
2
Specifications
2.SPECIFICATIONS
2.1 Unit Specifications
Models CEVI-09/CEVO-09, EVI-09/EVO-09
Model CEVI-09/CEVO-09 EVI-09/EVO-09
Function COOLING COOLING HEATING
Rated Voltage 220-240V̚ 220-240V̚
Frequency High Hz 78 78 98
(Inverter different Compressor Standard Hz 53 53 72
speed) Low Hz 15 15 24
Total Capacity High W / Btu/h 3230 / 11000 3230 / 11000 4100 / 14000
(Inverter different Compressor Standard W / Btu/h 2650 / 9000 2650 / 9000 3520 / 12000
speed) Low W / Btu/h 450 / 1500 450 / 1500 450 / 1500
Power Input High W 1350 1350 1450
(Inverter different Compressor Standard W 800 800 950
speed) Low W 200 200 200
Rated Input W 1420 1420 1550
Rated Current A 6.3 6.3 6.8
Air Flow Volume H m 3/h 520 520
M m 3/h 370 370
L m 3/h 280 280
Dehumidifying Volume l/h 0.8 0.8
EER / C.O.P W/W 3.3 3.3/3.7
Energy Class A/A A/A
Indoor unit CEVI-09 EVI-09
Fan Motor H r/min 1100 1100
Speed M r/min 900 900
L r/min 700 700
Output W 10 10
Capacitor F 1.2 1.2
RLA A 0.16 0.16
Fan Type-Piece Cross flow fan - 1 Cross flow fan – 1
Diameter-Length mm 92X594 92X594
Evaporator Aluminum fin-copper tube Aluminum fin-copper tube
Pipe Diameter mm 7 7
Row-Fin Gap mm 2-1.4 2-1.4
Coil length (l)×height (H)×
mm 610X294X24 610×294×24
coil width (L)
Swing Model MP24BA MP24BA
Motor Output W 1.5 1.5
Fuse (A) A PCB 3.15A PCB 3.15A
Sound Pressure Level H dB (A) 38 38
M dB (A) 30 30
L dB (A) 24 24
Sound Power Level H dB (A) 48 48
M dB (A) 40 40
L dB (A) 34 34
Dimension (W×H×D) ( mm) mm 770x283x201 770×283×201
Dimension of Package (L×W×H) mm 844x342x261 844×342×261
Net Weight /Gross Weight kg 8/11 8/11
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
3
Specifications
4
Specifications
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
5
Specifications
6
Specifications
9
7
8
6
7
5
6
Current(A)
Current(A)
5 4
4
3
Condition
3 Condition
Indoor:DB 20ć
Indoor:DB 27ć WB19ć 2 Indoor air flow: Super High
Indoor air flow: Super High
2 Pipe length:5m
Pipe length:5m
Voltage:230V
Voltage:230V 1
1
0 0
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Compressor Speed(rps) Compressor Speed(rps)
2.3CapacityVariationRatioAccordingtoTemperature
Cooling Heating
110 120
100 100
90 80
Capacity ratio(%)
Capacity ratio(%)
80 60
70 40
Condition Condition
Indoor:DB27℃ WB19℃ Indoor:DB20℃
Indoor air flow: Super High Indoor air flow: Super High
60 20 Pipe length:5m
Pipe length:5m
50 0
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 -15 -10 -5 0 5 10
Outdoor temp. (°C) Outdoor temp. (°C)
7
Specifications
Heating
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U
bent. (Thermistor themometer)
(2) Connecting piping condition : 5 m
48
30
46
44 Cooling
09K
42
20
Low Middle High 40
20 30 40 50 60 70 80
Indoor fan motor rotating speed
Compressor frequency(Hz)
8
Constrction views
3. Construction Views
3.1 Indoor Unit
770 201
283
770
126.5 548.5
258.5
283
551
708 317
299
470
9
Refrigerant System Diagram
GAS SIDE
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
COOLING
GAS SIDE
3-WAY VALVE
4-Way valve
Muffler
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE
COOLING
HEATING
10
Schematic Diagram
5. Schematic Diagram
5.1 ELECTRICAL DATA
Indoor Unit
Symbol Color symbol Symbol Color symbol
WH WHITE BN BROWN
YE YELLOW BL BLUE
RD RED BK BLACK
YEGN YELLOW GREEN PROTECTIVE EARTH
Outdoor Unit
Indoor Unit
AC-L XT
OUTDOOR UNIT
11
Schematic Diagram
Outdoor Unit
Models CEVI-09/CEVO-09 ,EVO-12/CEVO-12
HR1 BU XT BU
INDOOR UNIT
HR2 AC2 N(1)
S90 BK BK
S10 S11 S
HA1 2
BN BN
PCB2 BN AC1 3
HA2 HL3 HL2 YEGN
BU S40 S70 YEGN
HN3 HN2 E1
U V W BU YEGN YEGN
RD YE BU PCB1 E2
PE
X1
RD YE BU YEGN
WH WH PE PE
CLAPBOARD ELECTRICAL BOX
YEGN M SUB-ASSY
YEGN U V W WARNING
COMP.
FAN Please don't touch any terminal when the voltage of
SAT PE MOTOR terminal DC+ and DC- at PCB2 is higher than 30V to
PE prevent the risk of electrical shock!
HR1 BU XT
HR2 BU INDOOR UNIT
AC2 N(1)
HA1 S90 S80 BK BK
S10 S11 S 2
HA2 PCB2 BN BN
BN AC1 3
BU HL3 HL2 YEGN
S40 S70 YEGN
U V W HN3 HN2 E1
BU YEGN YEGN
RD YE BU PCB1 E2
X1 PE
YEGN
RD YE BU WH WH PE PE
12
Schematic Diagram
TOP VIEW
BOTTOM VIEW
13
Schematic Diagram
ZLUHXQGHU
]HUROLQH
YROWDJH
FRPPXQLFDWLRQ
ZLUH
ground
wire
GLVSDO\
ERDUG
LQIUDUHG
UHFHLYHU
14
Schematic Diagram
TOP VIEW
BOTTOM VIEW
15
Schematic Diagram
FRONT VIEW
BOTTOM VIEW
16
Schematic Diagram
TOP VIEW
BOTTOM VIEW
17
Function and Control
FAN
FAN speed button
ON/OFF MODE
● Press this button once, fan speed will change
Remote control as below: Auto
High speed
Note:Under the Dry mode, the fan speed isn't
BLOW TEMP TIMER
adjustable, low fan speed is imperative,
TURBO SLEEP LIGHT
but when operating this button, the wireless
remote control will send this signal.
18
Function and Control
FAN AUTO
TIMER
OPER
AIR HEALTH BLOW
Timer button
HUMIDITY
FILTER
● On the status of the unit on, press this
TURBO button to set timer off. On the status of
HOUR
ON/OFF
the unit off, press this button to set timer
off. Press this key once, words Hour on(off)
will appear and flicker. In which case, press
ON/OFF MODE +/- button to adjust time (press+/- button
continuously to change timing value quickly
the setting time range is from 0.5 to 24 hr.;
FAN press this key once again to fix the time,
Remote control
then remote controller will send out the signal
BLOW TEMP TIMER
immediately and hour on/off will stop flickering.
TURBO SLEEP LIGHT
If the time of that no press timer button
under flickering status is above 5s,the timer
setting will quit. If the timer has been set,
press this button once again to quit it.
HEALTH SAVE
HEALTH SAVE button
TEMP
● HEALTH function:there is no this function Temp. display button
for this unit. If press this key, the main unit ● After powered on, displaying presetting
will click, but it also runs under original status. temperature is defaulted,(According to
customer requirements to display,if there
● Save energy function: this unit has no this are no requirements,the presetting temp-
function, press this button, the mian unit will erature displaying is defaulted, there is
click, "SE" will be displayed on the LCD of no signal display on the remote control).
wireless remote control, fan speed automatically Press this button, (display ), display
rotates, when repress this button, the fan speed the presetting temperature; (display ),
will run at previous setting fan speed. display indoor ambient temperature,
(display ), display ambient temperature,
TURBO
Turbo button If current display status is indoor ambient temp.
when received other remote control sginal,
● Set turbo on or off(the characters of turbo
then will display presetting temp., 5s later
will appear or disappear ) by pressing this
return to ambient temp. display.
key under cooling or heating mode.Once
Other models haven't this function. But
energized, the unit will be defaulted to be
pressing this button, the main unit will click
turbo off. This function can not be set under
and keep the original status.
auto, dehumidify or fan mode, and characters
of turbo won't appear.
19
Function and Control
BLOW
Blow button
● Set Blow on (the characters of Blow will
FAN AUTO
appear)or off (the characters of Blow
OPER
AIR HEALTH BLOW
disappears) by pressing this key under
HUMIDITY
cool or dehumidify mode. Once energized,
FILTER
TURBO the unit will be defaulted to be Blow off.
HOUR
ON/OFF This function can not be set under auto,
fan or heat mode, and the characters of
Blow won't appear.
Remote controller ON/OFF MODE
LIGHT
Light button
● Press this button to select LIGHT on or off
FAN
in the displayer. When the LIGHT on is
set,the icon will be displayed and the
BLOW TEMP TIMER indicator light in the displayer will be on.
TURBO SLEEP LIGHT When the LIGHT off is set, the icon will
be displayed and the indicator light in the
displayer will be off.
SLEEP
Sleep button Left and right swing button
● Press this button, enter into SLEEP state, ● Simpleness swing mode is defaulted for
when repressed, it will quit. The sleep function wireless remote control,in this mode,
will be canceled with the stop of the unit. press this button, could turn on or turn
There is no SLEEP function under AUTO off the Left and right swing function
and FAN mode. is the icon for sleep ● When unit is turned off, synchronously
function.
press "+" and Left and right swing buttons,
● At COOL mode: the SLEEP mode runs after it could be switched between the simpleness
1hour, the setting temp. will be increased swing mode and stationary swing mode,
by 1ć , 2 hour later, setting temp. will be at this time, blinks 2 seconds.
increased by 2ć and then will run at this
● In Stationary swing mode, press this button,the
setting temperature.
angle for Left and right swing as show in below:
20
Function and Control
ƾ NOTE:
ƽ When changing the batteries, do not use the old or different batteries,
otherwise, it can cause the malfunction of the wireless remote control.
ƽ If the wireless remote control will not be used for a long time, please
take them out, and don't let the leakage liquid damage the wireless
remote control.
ƽ The operation should be in its receiving range.
ƽ It should be placed at where is 1m away from the TV set or stereo sound sets.
ƽ If the wireless remote control can not operate normally, please take them out, Sketch map for
after 30s later and reinsert, if they cannot normally run, please change them. changing batteries
RSHUDWLRQ VWRSIRUFHUXQQLQJ
GXULQJVWRS
VWDUWUXQQLQ
VWDUWIRUFHUXQQLQJ ˄ LQFDVHRINH\FODPS˅
RSHUDWLRQ
GXULQJUXQQLQJ VWRSUXQQLQJ VWRSUXQQLQJ ˉ
RSHUDWLRQGXULQJVWRS
DIWHUUXQQLQJDEQRUPDO
˄ F R P P X Q L F D W L R Q H U U R U˅
21
Function and Control
B
In this mode, the system selects the running mode (cooling, heating, and fan)
automatically according to the ambient temperature. The display shows the
A actual running mode and setting temperature. There will be 30s delay for
Indoor temperature-setting temperature mode conversion. The protection function is the same as that of other modes.
1. When T amb>=25o C, the cooling mode is selected.
2. for heat pump unit: when Tamb<=22o C, the unit runs in heating mode
1. In this mode, the fan motor runs at low fan speed while swing works 3. for cooling only unit: when Tamb < 22o C, the unit runs in fan mode. .
according to setting state. The range of setting temperature is 16~30 o C 4. When 22o C <T indoor amb< 25o C, upon initial startup, the unit will
enter auto mode and run in automatic fan mode. If the other mode
(61~86¨H).
changes into auto mode, the previous running mode will remain.
2. When outdoor malfunction or protection stoppage happen,
the indoor fan will remain the original running state and the error LED will light.
1. In this mode, the indoor fan may run at high, medium, low and automatic
speed. The compressor, outdoor fan and 4-way valve all stop running.
o
2. In this mode, the range of setting temperature is 16~30 C (61~86¨H).
C
2. Protection function: in heating mode, when the compressor stops as
a result of malfunction, the indoor fan blows residual heat.
3. Defrosting control: when the defrosting signal is revived, the
defrosting mark H1 will be shown. The e-heater and indoor fan stop.
22
Function and Control
Timer off: the timer off function can be set when the unit is on. When the
setting time for timer off is reached, the unit will stop. The timing interval is
After energization, the motor of upper and lower swing will enable the air 0.5hour, and the setting range is 0.5~24hours.
deflector to be open and then be close completely. And the air outlet is close. Clock (start and stop time can be set. The accuracy is minute. E.g.: timer
In heating mode, if the swing function is not set, the upper and lower air on at 8:00a.m.; timer off at 17:30p.m.)
Timer on: if the timer on function is set when the system is on, the system
deflector will rotate to maximum in clockwise direction. Then it will rotate
will go on running. If the timer on function is set when the system is off, the
to place D. Under other state, the upper and lower air deflector will rotate to system will start running in the previously set mode when the setting time is
level L. If the swing function is set when starting the unit, the air deflector reached.
Timer off: if the timer off function is set when the system is off, the system
will swing between place L and D. there are 7 states for air deflector: in will keep off even though the setting time is reached. If t he timer off
Place L, Place A, Place B, Place C, Place D, and swing between Place L and function is set when the system is on, the system will stop running when the
place D, stop in any place between Place L and place D. When the unit is setting time is reached.
turned off, the air deflector will stay in place 0. The swing is available only Timer modification: when the system is under timer state, start or stop of the
when the swing function is set and the indoor fan is running. unit can be set via remote ON/OFF button and the timer can be reset. The
system runs according to the latest setting state.
Note: When place L to B, place A to C, and place B and D is set, the air
When both the timer on and timer off are set: the system runs according to
deflector will swing between place L to D.
the current setting state. When the setting time is reached, the unit will start
and stop running. In that case, the unit will run according to the previously
setting mode when the setting time for timer on is reached. The unit will stop
O(0°)
running while the setting time for timer off is reached.
If the setting time for timer on and timer off is the same, the unit will stop
running no matter what the current state is.
L
Memory: mode, up and down swing, light, setting temperature, setting fan
A
speed, general timer (not clock), Fahrenheit / Celsius. After de-energized,
B
the unit can run according to the memory if it is energized again. If the timer
C function is not set in the last remote control, the system will run according to
D the last remote control. If the timer function is set in the last control before it
is de-energized, the system will memorize the last timer setting. The setting
time is recalculated since the energization of the unit. If the timer function is
1. It is applicable to cooling mode, dehumidifying mode and heating mode. set in the last control and the setting time is reached before the unit is
2. In cooling mode or dehumidifying mode, 1 hour after the sleep curve is de-energized, the unit will run according to the previous running mode after
set, the setting temperature will rise by 1 ¡æ. 2 hours later, the setting
it is energized again. But the timer function will terminate. The clock will
temperature will rise by 2 ¡æ. After that, the setting temperature will not
not be memorized.
change any more
(11) Turbo function
set
Set temp. Tset In cooling and heating mode (not available in auto, dehumidify, fan mode),
press the Turbo button, the fan speed displayed super high speed in the
set remote controller and the indoor fan rotates at super high speed.
(12) Health function
set
When the indoor fan motor is running, the Health function is set by pressing
1h 2h About 2h remote controller (If there is no Health button on the remote controller, the
3. In heating mode, 1 hour after the sleep curve is set, the setting temperature Health function opening is defaulted).
will decrease by 1 ¡æ. 2 hours later, the setting temperature will decrease by
2 ¡æ. After that, the setting temperature will not change any more. (13) I Feel function
1h 2h About 2h If the remote controller receives the I Feel order, the controller will work at
set the ambient temperature value which is sent by remote controller (Except the
defrosting and anti-cool wind, which still adopts the sampling value of AC
set itself ambient temperature sensor), the remote controller will send ambient
Set temp. Tset
temperature value to controller at intervals. If the controller hasn’t received
set
the ambient temperature value from the remote controller for long time, then
it will run accroding to the current ambient temperature of AC. If the
The main board has general timer function and clock function. The timer function has not been set, the ambient temperature will adopt the sensor
function can be selected by remote controller with different function sampling value of AC itself. If power off happens, this function will not be
(1) General timer (start and stop time can be set. The accuracy is minute. memorized.
23
Function and Control
Outline
When starting the compressor, or when conditions are varied due to the change of the room, the frequency must be initialized according
to the D value of the indoor unit and the Q value of the indoor unit.
Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
1. P control
Calculate D value in each sampling time (20 seconds), and adjust the frequency according to its difference from the frequency
previously calculated.
2. I control
If the operating frequency is not change more than a certain fixed time, adjust the frequency up and down according to the D value,
obtaining the fixed D value.
When the D value is small...lower the frequency.
When the D value is large...increase the frequency.
3. Fre uency management hen other controls are functioning
When frequency is drooping;
Frequency management is carried out only when the frequency droops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lo er limit of fre uency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or quiet commands come from indoor unit, the
upper limit frequency must be lowered than the usual setting.
Frequency
FCG 3 88
FCG3
FCG 2 64
FCG2
FCG 1 48 FCG1
TCG1 240
TCG2 360 Time
TCG 1sec TCG 2sec TCG 3sec
TCG3 180
24
Function and Control
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
thermistor Reset zone
temperature
1 Stop zone
2 Drooping zone
3 Keep zone
Reset zone
When a “stop current” continues for 2.5 seconds after rushing on the stop zone, the compressor operation stops.
If a “drooping current” is continues for 1.0 second after rushing on the drooping zone, the frequency will be 2 Hz drooping.
Repeating the above drooping continues until the current rushes on the drooping zone without change.
In the keep zone, the frequency limit will remain.
In the return / reset zone, the frequency limit will be cancelled.
imitation of current drooping and stop value according to the outdoor air temperature
1. In case the operation mode is cooling
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
2. In case the operation mode is heating
* The current droops when outdoor air temperature becomes higher than a certain level (model by model).
25
Function and Control
During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent
freezing of the indoor heat exchanger. (The signal from the indoor unit must be divided into the zones as the followings.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from operation start.
Control in Each one
Heat exchanger
thermistor temperature Return/Reset zone
A Up zone
B Keep zone
C Drooping zone
D Stop zone
E
Stop zone
Drooping zone
Keep zone
Up zone
Heat exchanger
thermistor temperature Reset zone
26
Function and Control
PI control
Frequency
0Hz
60sec.
50sec. 600sec. 50sec.
ON
Compressor
OFF
ON
Four way valve
OFF
5sec. 5sec.
ON
Fan
OFF
27
Installation Manual
Important Notices (1)The air inlet and outlet vent should be far from the obstruction,
make sure that the air can be blown through the whole room.
1. The unit installation work must be done by qualified (2)Select a position where the condensing water can be easily
personnel according to the local rules and this drained out, and the place is easily connected for outdoor unit.
(3)Select a location where the children can not reach.
manual.
(4)Can select the place where is strong enough to withstand the
2. Before installating, please contact with local
full weight and vibration of the unit. And will not increase the noise.
authorized maintenance center, if unit is not installed
(5)Be sure to leave enough space to allow access for routine
by the authorized maintenance center, the malfunction maintenance. The height of the installed location should be
may not solved, due to discommodious contacts. 250cm or more from the floor.
3. When removing the unit to the o.ther place, please (6)Select a place about 1m or more away from TVset or any other
firstly contact with the authorized Maintenance electric appliances.
Center in the local area. (7)Select a place where the filter can be easily taken out.
(8)Make sure that the indoor unit installation should accord with
installation dimension diagram requirements.
Basic Requirements For Installation (9)Do not use the unit in the immediate surroundings of a laun-
Position dry a bath a shower or a swimming pool.
28
Installation Manual
241.7
Pipe
Reamer
41.3 41.3
54.5 160 50 160 54 Point down
Gas pipe end
330.5 331 Through-
the-wall
770 Liquid pipe end hole φ65mm
Keep here the piece cut out Drain hose
from the unit for piping position Unit: mm Putting nut on
* The removed pipe port cover can be
Removed pipe
Remove flare nuts attached to indoor and outdoor unit, then
kept in the mounting plate pocket.
port cover put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
A Mounting plate
Flare nut
Copper tube
• For walls containing metal frame or metal board, be sure to use
a wall embedded pipe and wall cover in the feed-through hole to
prevent possible heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking mate- Flaring ork
rial to prevent water leakage. Firmly hold copper pipe in a die in the dimension shown in
1) Bore a feed-through hole of 65mm in the wall so it has a down the table above.
slope toward the outside. Handle
"A"
Copper
Slanted Uneven Rough = Improper flaring =
pipe 90e
29
Installation Manual
3.2 Connection of piping 5. Insert the connecting cable fully into the terminal block and
1.Align the center of the pipes and sufficiently tighten the flare nut secure it tightly with screws.
by hand. 6. Tightening torque: 1.2 N•m (0.12 kgf•m).
7. Secure the connecting cable with the cord clamp.
8. Attach the terminal cover, rear plate bushing and air inlet grille
on the indoor unit.
Indoor unit tubing Flare nut Pipes
CAUTION
2.Tighten the flare nut with a wrench.
e sure to refer to the iring system diagram
labeled inside the front panel.
Open-end wrench (fixed)
Check local electrical regulations for any
Flare nut specific iring instructions or limitations.
Wrench Connection pipe
Earth wire
If drain hose extension or embedded drain piping is required,
use appropriate parts that match the hose front end. Connecting cable
Insert drain hose into the handle of drain pan, and join
drain hose and connecting hose according to the figure by.
Shield pipe
1
Terminal block
CAUTION
CAUTION
Insert the drain hose and drain cap into the drain port, mak-
ing sure that it comes in contact with the back of the drain
port, and then mount it. If the drain hose is not connected
properly, leaking will occur.
70 mm
Wiring the connecting cable can be carried out ithout remov- 10 mm Earth line
ing the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and
pull it toward you.
2. Remove the terminal cover and cord clamp.
10 mm
3. Insert the connecting cable (or as according to local regula- 50 mm
tions/codes) into the pipe hole on the wall.
4. Pull the connecting cable through the cable slot on the rear
panel so that it protrudes about 15 cm out of the front.
30
Installation Manual
1.After making slits on the front panel with a knife or similar tool,
In the case of bending or curing refrigerant pipes, keep the fol- cut them out with a pair of nippers or an equivalent tool.
lowing precautions in mind.
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom
frame.
2) Do not strongly press the refrigerant pipes on the front grille,
Slit
either.
2.Overlap the connection pipe insulation material and the indoor
unit pipe insulation material. Bind them together with vinyl tape
so that there is no gap.
2)
The piping can be lead out from right, right rear, left left rear.
Right-side, right-back, or right-bottom piping 3.Wrap the area which accommodates the rear piping housing
1)After making slits on the front panel with a knife or similar tool, section with vinyl tape.
cut them out with a pair of nippers or an equivalent tool.
Connection Indoor
Attach the drain hose to the underside of the refrigerant pipes pipe unit pipe
with an adhesive vinyl tape. Vinyl tape Wrap with vinyl tape
2) Wrap the refrigerant pipes and drain hose together with an (wide)
Wrap with vinyl tape
insulation tape.
Pipe
Vinyl tape(wide)
Drain hose
Bind with vinyl tape
Right piping Indoor unit
Pipe (top) Auxiliary pipes
Rear piping Connecting
cable
Bottom Indoor unit drain hose
piping (bottom) Installation
plate
eft-side, left-back, or left-bottom piping
• Interchange the drain cap and the drain hose. 4.Bundle the piping and drain hose together by wrapping them
CAUTION
with vinyl tape for enough to cover where they fit into the rear
(1) In order to align the drain hose and drain cap, be piping housing section.
sure to insert securely and vertically. Incline inser- Indoor unit installation
tion will cause water leakage.
(2) When inserting, be sure not to attach any material 1) Pass the drain hose and refrigerant pipes through the wall
besides water. If any other material is attached, it hole, then set the indoor unit on the mounting plate hooks by
will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget using the markings at the top of the indoor unit as a guide.
mounting drain cap.
(4) Be sure to fix the drain hose with tape to the bottom A Mounting plate
of piping.
Marking
(5) Prevent drain water frozen under low tempera-
ture environment.
When installing indoor unit's drain hose outdoors, necessary
measure for frost protection should be taken to prevent drain
water frozen.
• Under low temperature environment (when outdoor tem-
perature under 32 °F), after cooling operation is executed,
water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked
and water leakage may be resulted for indoor unit. 2) Swing the indoor unit to right and left to confirm that it is firmly
For left outlet piping, cut off the
hooked on the installation plate.
piping outlet cutting groove 3)While pressing the indoor unit onto the wall, hook it at the
with a hacksaw.
lower part on the installation plate.
Remove the drain cap by pulling Pull the indoor unit toward you to confirm that it is firmly
Indoor unit at the projection at the end of
drain hose Drain cap
hooked on the installation plate.
the cap with pliers, etc.
31
Installation Manual
For detaching the indoor unit from the installation plate pull the
indoor unit toward you while pushing the bottom up at the speci-
fied places.
Push
Push
* Holes are provided on the base plate of the outdoor unit to 2.Overlap the connection pipe insulation material and the indoor
ensure that the defrost water produced during heating opera- unit pipe insulation material. Bind them together with vinyl tape
tions is drained off efficiently. so that there is no gap.
* If a centralized drain is required when installing the unit on a
balcony or wall. After the piping has been connected to the indoor unit, perform
* If the drain port is covered by a mounting base or floor surface, the air purge.
place additional foot bases of at least 30mm in height under the
outdoor unit’s feet. AIR PURGE
* In cold areas, do not use a drain hose with the outdoor unit. Evacuate the air in the connecting pipes and in the indoor
(Otherwise, drain water may freeze, impairing heating unit using a vacuum pump.
performance.) Do not use the refrigerant in the outdoor unit.
For details, see the vacuum pump manual.
32
Installation Manual
CAUTION
IMPORTANT POINTS FOR PIPING WORK
1. Keep dust and moisture from entering the pipes.
Electric parts
2. Tighten connections carefully (between pipes and unit).
3. Evacuate the air in the connecting pipes using a VACUUM
Check places
PUMP. for outdoor unit
4. Check for gas leaks at all connections.
Packed Valve handling precautions
• Open the valve stem all the way; but do not try to open it beyond
the stopper.
• Securely tighten the valve stem cap with torque in the following
1)Switch on power, press “ON/OFF” button on the wireless re-
table:
mote control to start the operation.
Gas side (Ø9.52 mm) 33 to 42 N• m (3.3 to 4.2 kgf •m) 2)Press MODE button, to select the COOL, HEAT (Cooling only
unit is not available), FAN to check whether the operation is nor-
Liquid side (Ø6.35 mm) 14 to 18 N• m (1.4 to 1.8 kgf •m) mal or not.
Service port 14 to 18 N• m (1.4 to 1.8 kgf • m) Perform test operation and check items 1 and 2 below.
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?
Cap
Hexagon wrench(4mm) 2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the
neighbors?
(3) Is there any gas leakage?
33
Exploded Views and Parts list
34
Exploded Views and Parts list
Outdoor Unit
35
Exploded Views and Parts list
36
Exploded Views and Parts list
Part Code
No Description Qty
CEVI-09 EVI-09
1 Decorative Strip 20192292 20192292 1
2 Front Panel 2001232501T 2001232501T 1
3 Filter Sub-Assy 1112208201 1112208201 2
4 Front Case 20012324 20012324 1
5 Guide Louver 10512119 10512119 1
6 Air Louver 10512160 10512160 2
7 Shaft of guide louver 1054202001 1054202001 2
8 Front Panel Assy 2001237601 2001237601 1
9 Drainage Pipe Sub-assy 0523204101 0523204101 1
10 Evaporator Support 24212108 24212108 1
11 Cross Flow Fan 10352423 10352423 1
12 Evaporator Assy 01002270 01002270 1
13 Helicoid tongue 26112486 26112486 1
14 Rear Case assy 2220211901 2220211901 1
15 Wall Mounting Frame 0125201801 0125201801 1
16 Electric Box Cover 20122106 20122106 1
17 Electric Box Assy 2020225303 2020225302 1
18 Motor Press Plate 26112191 26112191 1
19 Electric Box Cover Sub-Assy 20122109 20122109 1
20 Terminal Board 42011233 42011233 1
21 Crank 73012005 73012005 1
22 Step Motor 1521210701 1521210701 1
23 Pipe plug (outlet) 76712020 76712020 1
24 Electric Box 20112086 20112086 1
25 Motor Sub-Assy 15002002 15002002 1
26 Baffle Plate 26112218 26112218 1
27 Fan Motor 15012093 15012093 1
28 Front Case Assy 2001237501 2001237501 1
29 Remote Controller 30510061 30510061 1
30 Power Cord 400204643 400204643 1
31 Connecting Cable 400205236 400205236 1
32 Screw Cover 24252019 24252019 1
33 Main Board 30138124 30138120 1
34 XY Capacitor 33030013 33030013 1
35 Ambient Temperature Sensor 390000453 390000453 1
36 Fan Bearing 76512210 76512210 1
37 Damping washer sub-assy 76512011 76512011 1
38 Axile Bush sub-assy 10542024 10542024 1
39 Electric Box Sub-Assy 2020225703 2020225702 1
37
Exploded Views and Parts list
Part Code
No Description Qty
CEVI-12 EVI-12
1 Decorative Strip 20192292 20192292 1
2 Front Panel 2001232501T 2001232501T 1
3 Filter Sub-Assy 1112208201 1112208201 2
4 Front Case 20012324 20012324 1
5 Guide Louver 10512119 10512119 1
6 Air Louver 10512160 10512160 2
7 Shaft of guide louver 1054202001 1054202001 2
8 Front Panel Assy 2001237601 2001237601 1
9 Drainage Pipe Sub-assy 0523204101 0523204101 1
10 Evaporator Support 24212108 24212108 1
11 Cross Flow Fan 10352423 10352423 1
12 Evaporator Assy 01002745 01002745 1
13 Helicoid tongue 26112486 26112486 1
14 Rear Case assy 2220211901 2220211901 1
15 Wall Mounting Frame 0125201801 0125201801 1
16 Electric Box Cover 20122106 20122106 1
17 Electric Box Assy 2020225301 20202253 1
18 Motor Press Plate 26112191 26112191 1
19 Electric Box Cover Sub-Assy 20122109 20122109 1
20 Terminal Board 42011233 42011233 1
21 Crank 73012005 73012005 1
22 Step Motor 1521210701 1521210701 1
23 Pipe plug (outlet) 76712020 76712020 1
24 Electric Box 20112086 20112086 1
25 Motor Sub-Assy 15002002 15002002 1
26 Baffle Plate 26112218 26112218 1
27 Fan Motor 15012093 15012093 1
28 Front Case Assy 2001237501 2001237501 1
29 Remote Controller 30510061 30510061 1
30 Power Cord 400204643 400204643 1
31 Connecting Cable 400205236 400205236 1
32 Screw Cover 24252019 24252019 1
33 Main Board 30138125 30138121 1
34 XY Capacitor 33030013 33030013 1
35 Ambient Temperature Sensor 390000453 390000453 1
36 Fan Bearing 76512210 76512210 1
37 Damping washer sub-assy 76512011 76512011 1
38 Axile Bush sub-assy 10542024 10542024 1
39 Electric Box Sub-Assy 2020225701 20202257 1
38
Exploded Views and Parts list
Outdoor Unit
(1) Cooling Only Models
Part Code
NO. Description Qty
CEVO-09 CEVO-12
1 Front Grill 22413017 22413017 1
2 Cabinet 01433044P 01433044P 1
3 Axial Flow Fan Sub-Assy 1033300901 1033300901 1
4 Fan Motor 15013073 15013073 1
5 Motor Support 0170311101 01703111 1
6 Left Side Plate 20053001 20053001 1
7 Top Cover Sub-Assy 0125304001 0125304001 1
8 Electric Box Assy 0260325603 0260325602 1
9 Main Board 30138099 30138100 1
10 Relay 44020382 44020382 1
11 Clapboard 01233088 01233088 1
12 Chassis Sub-assy 0120390901P 0120390901P 1
13 Condenser Assy 01113463 01113501 1
14 Cut-off Valve Assy 07133164 07133602 1
15 Capillary Sub-Assy 03103936 03063056 1
16 Valve Support 01713089 01713089 1
17 Right Side Plate Sub-Assy 0130318001 0130318001 1
18 Handle assy 26233046 26233046 1
19 Thermal baffle 26113005 26113005 1
20 Discharge Tube 03713424 03733025 1
21 Cut-off valve Sub-Assy 07133189 07133189 1
22 Compressor and fittings 00103761 00103761 1
23 Overload Protector 00181067 00181067 0
24 Terminal cap 22243001 22243001 1
Part Code
No Description Qty
EVO-09 EVO-12
1 Front Grill 22413017 22413017 1
2 Front Plate 01433044P 01433044P 1
3 Axial Flow Fan Sub-Assy 1033300901 1033300901 1
4 Fan Motor 15013073 15013073 1
5 Motor Support 0170311101 01703111 1
6 Left Side Plate 20053001 20053001 1
7 Top Cover Sub-Assy 0125304001 0125304001 1
8 Electric Box Assy 02603256 0260325601 1
9 Main Board 30138087 30138096 1
10 Relay 44020382 44020382 2
11 Clapboard 01233088 01233088 1
12 Chassis Sub-assy 0120390901P 0120390901P 1
13 Condenser Assy 01113463 01113501 1
14 Cut-off Valve Assy 07133164 07133163 1
15 Capillary Sub-Assy 03103936 03103937 1
16 Valve Support 01713089 01713089 1
17 Right Side Plate Sub-Assy 0130318001 0130318001 1
18 Handle assy 26233046 26233046 1
19 Thermal baffle 26113005 26113005 1
20 Magnet Coil 4300040050 4300040050 1
21 4-way Valve Assy 0312323701 0312327201 1
22 Compressor and fittings 00103761 00103761 1
23 Overload Protector 00181067 00181067 0
24 Terminal cap 22243001 22243001 1
25 Drainage Joint 06123024 06123024 1
39
Troubleshooting
9. TROUBLESHOOTING
9.1 Precautions before Performing Inspection or Repair
Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power.
At times such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position.
Normally,diagnose troubles according to the trouble diagnosis procedure as described below.(Refer to the check points in servicing
written on the wiring diagrams attached to the indoor/outdoor units.)
9.2 Confirmation
(1)Confirmation of Power Supply
Confirm that the power breaker operates(ON) normally;
(2)Confirmation of Power Voltage
Confirm that power voltage is AC 220–230–240 ± 10%.
If power voltage is not in this range, the unit may not operate normally.
40
Troubleshooting
code malfunctio Error display Repair method co malfunction Error display Repair method
n Dual 8 LED de Dual 8 LED
display display
1 Storage EE Heating LED-pause Replace indoor main 15 Sync failure H7 Heating Check if the resistance
slug 3s and blink 15 board LED-pause 3s and of compressor and
times blink 7 times resistance to ground is
normal. If the
compressor is normal,
the outdoor main boar
d may be wrong.
2 Indoor EE Heating LED-pause Replace indoor main 16 Current diction U5 Cooling Replace outdoor main
PCB 3s and blink 15 board malfunction of LED-pause 3s and board
malfunctio times complete unit blink 13 times
n
3 Anti-freezi E2 Running LED- Outdoor ambient 17 Outdoor ambient F3 Cooling Is it loose? Measure
ng pause 3s and blink 2 temperature is too low temperature sensor LED-pause 3s and the resistance value
protection times malfunction blink 3 times with universal meter
4 Overload H4 Heating LED-pause System is abnormal, 18 Discharge E4 Running Is it loose? Measure
of system 3s and blink 4 times check if the evaporator protection of LED-pause 3s and the resistance value
and condenser is dirty compressor blink 4 times with universal meter
and blocked
5 No motor H6 Running LED- Is electromotor 19 Break-circuit and F5 cooling LED- Is it loose? Measure
of indoor pause 3s and blink mounted normally? short-circuit of pause 3s and blink the resistance value
unit 11 times outdoor discharge 5 times with universal meter
feedback temperature sensor
6 Indoor F2 cooling LED- pause Is it loose? Measure 20 Break-circuit and F4 cooling LED- Is it loose? Measure
pipe 3s and blink 2 times the resistance value short-circuit of pause 3s and blink the resistance value
temperatur with universal meter outdoor condenser 18 times with universal meter
e sensor temperature sensor
malfunctio
n
7 Internal F1 Cooling LED- pause Is it loose? Measure 21 Overheat of carbon P8 heating LED- Is outdoor ambient
ambient 3s and blink 1 times the resistance value fin pause 3s and blink temperature is too
temperatur with universal meter 19 times high? Is radiator
e sensor mounted correctly?
malfunctio
n
8 Zero UF Heating and cooling Replace indoor main 22 DC overcurrent UU Heating and
passage LED blinks 7 times board cooling LED blink
abnormal at the same time 11 times at the
same time
9 Overload H3 heating LED- pause Inspect connection 23 Temperature sensor P7 heating LED- Replace outdoor main
of 3s and blink 3 times state of the overload malfunction of pause 3s and blink board.
compresso wire. carbon fin 18 times
r
10 Startup Lc heating LED- pause Check if the resistance 24 Lack of Freon or F0 cooling LED-
failure 3s and blink 11 of compressor and block protection pause 3s and blink
times resistance to ground is 10 times
normal. If the
compressor is normal,
the outdoor main boar
d may be wrong.
11 No motor UH Heating and cooling This malfunction may 25 DC input voltage is PH cooling LED- Is voltage of AC power
of outdoor LED blink 8 times at happen when outdoor too high pause 3s and blink supply normal?
unit the same time DC electromotor is 11 times
feedback used.
12 Overcurren E5 Running LED- Is electric network 26 DC input voltage is PL Heating LED- Is voltage of AC power
t pause 3s and blink 5 variable? too low pause 3s and blink supply normal?
protection times 21 times
13 4-way U7 cooling LED- pause Replace 4-way valve. 27 Communication E6 Running LED- Is outdoor connecting
valve 3s and blink 20 malfunction pause 3s and blink wire reliably
conversion times 6 times connected?
abnormal
14 Phase U1 Heating LED- pause Replace outdoor main 28 Setting error, UA Heating and Outdoor unit is not
current 3s and blink 13 board. indoor and outdoor cooling LED blink matched with indoor
detection times unit abnormal 12 times at the unit.
malfunctio same time
n of
compresso
r
remarks 4min after protection stop of compressor, the malfunction is shown in error code. In other situation, the malfunction will be displayed by press the light button for 6 times within
4s.
41
Troubleshooting
Measure voltage
between L and N
Voltage > 200V? Y of outdoor wiring
block
Normal wiring? N
Voltage > 200V? N
Y Y
Indoor main board error Adjust wiring Outdoor electric indoor and outdoor
box error wiring error
Remove malfunction
z Is the input voltage within the normal range (measure the voltage between L and N of the wiring block XT with AC voltage gauge.)?
42
Troubleshooting
Energize the
unit and start it
9ROWDJHEHWZHHQ
/DQG1RI
LQGRRUZLULQJ
EORFN
&KHFNWKH
FRQQHFWLQJ
9ROWDJH!9" Y VWDWHRIWKH
FRQQHFWLQJ
WHUPLQDO
5HOLDEOH $GMXVW
FRQQHFWLRQ N FRQQHFWLQJ
N VWDWH
Y
5HSODFHPDLQ UHPRYHWKH
&KHFNSRZHU N
VXSSO\ ERDUGRILQGRRU HUURU"
XQLW
5HPRYHWKH N
HUURU"
Y
5HSODFHPRWRU
Y
)LQLVK
&KHFNFRQQHFWLQJ
,QGRRUXQLW VWDWHRILQGRRU
GLVSOD\)) Y
WHPSHUDWXUH
VHQVRU
N
,QGRRUXQLW UHOLDEOH
FRQQHFWHG" N
GLVSOD\))
Y $GMXVW
FRQQHFWLQJVWDWH
&KHFNFRQQHFWLQJ
VWDWHRIRXWGRRU Y
WHPSHUDWXUHVHQVRU
5HSODFH
5HOLDEOH $GMXVW WHPSHUDWXUH 5HPRYHHUURU"
FRQQHFWHG" N
FRQQHFWLQJVWDWH VHQVRU
N
Y
5HSODFH
WHPSHUDWXUH N 5HPRYHHUURU" 5HPRYHHUURU"
VHQVRU"
Y
N
5HPRYHHUURU"
5HSODFHPDLQ
ERDUGRILQGRRU
XQLW Y
N
Y Y
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
ILQLVK
43
Troubleshooting
Energize the
(4) Malfunction diagnosis of startup failure unit and start it
z Is compressor damaged? Y
Connect it according
Is compressor wire connected correctly? N
to line chart
Replace
compressor
finish
,VWKHVWRSWLPH ,VIDQZHOO
N RIFRPSUHVVRUPRUH ,VRXWGRRUIDQQRUPDO" N FRQQHFWHG"
WKDQPLQ˛
Y
Y
,VRXWGRRUIDQ 5HPRYH N 5HOLDEOH
EORFNHGE\ Y FRQQHFWHG"
VWXII
VWXII"
,VZLUHRIFRPSUHVVRU Y
ZHOOFRQQHFWHG" N
5HSODFHSDUWV
5HSODFHSDUWV RIRXWGRRU
N RIRXWGRRU HOHFWULFER[
HOHFWULFER[
Y
$GMXVW 5HSODFHSDUWV
FRQQHFWLQJZLUH RIRXWGRRU Y 5HPRYHHUURU"
HOHFWULFER[
5HPRYHHUURU"
N
Y 5HPRYHHUURU" N
Y 5HSODFH
RXWGRRUIDQ
N
5HSODFH
FRPSUHVVRU
5HSODFH
FRPSUHVVRU
)LQLVK
)LQLVK
44
Troubleshooting
z Is refrigerant leaked?
z Is overload wire connection normal?
,VHOHFWULF
Malfunction diagnosis process: H[SDQVLRQYDOYH N
ZHOOFRQQHFWHG"
,VRYHUORDGZLUH N
UHOLDEO\FRQQHFWHG"
5HSODFHHOHFWULF $GMXVW
H[SDQVLRQYDOYH FRQQHFWLQJZLUH
5HPRYH
Y
PDOIXQFWLRQ"
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
5HPRYHPDOIXQFWLRQ" Y
5HIULJHUDQWOHDNDJH
UHFKDUJHWKH
UHIULJHUDQW
)LQLVK
(FRPPXQLFDWLRQ
HUURULV
GLVSOD\HG
,VFRQQHFWLQJ
ZLUHUHOLDEO\ N
FRQQHFWHG"
5HSODFHPDLQ $GMXVW
ERDUGRILQGRRU
XQLW FRQQHFWLQJZLUH
5HPRYHPDOIXQFWLRQ" Y
5HSODFHSDUWV
RIRXWGRRU
HOHFWULFER[
)LQLVK
45
Troubleshooting
Valve cap
Hexagonal wrench (4mm) Open position
Flare nut Flare nut Closed position
Open position
Closed position Pin
To To
piping piping Service Service
connection connection port cap port
To outdoor unit To outdoor unit
46
Troubleshooting
Gas side
Clsed
3-way
valve
Vacuum pump
Lo
OPEN CLOSE
* Procedure
(1)Connect the charge hose from the manifold valve to the ser- CAUTION:
vice port of the gas side packed valve. If gas leakage are discovered in step 5 above, take the
following mesures :
(2)Connect the charge hose to the port of the vacuum pump. If the gas leaks stop when the piping connections are
tightened further, continue working from step 6. If the
(3) Open fully the low pressure side handle of the gauge mani- gas leaks do not stop when the connections are
fold valve.
retightened, repair the location of the leak, discharge
all of the gas through the service port, and then recharge
(4)Operate the vacuum pump to begin evacuating. Perform
with the specified amount of gas from a gas cylinder.
evacuating for about 15 minutes if the piping length is 20 meters
(15 minutes for 20 meters) (assuming a pump capacity of 27
liters per minute). Confirm that the compound pressure gauge
reading is –101 kPa (–76 cmHg).
(8)Mount the valve stem nuts to the 2-way and 3-way valves.
47
Troubleshooting
Gas side
Closed
3-Way
valve
Lo
CLOSE CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves are set to (7) Immediately set the 3-way valve to the closed position.
the open position. – Do this quickly so that the gauge ends up indicating 3 to 5kg/
– Remove the valve stem caps and confirm that the valve stems cm2g.
are in the raised position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(8) Disconnect the charge set, and mount the 2-way and 3-
way valve’s stem nuts and the service port nut.
(2) Operate the unit for 10 to 15 minutes. – Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Stop operation and wait for 3 minutes, then connect the
charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to the service port.
(6) Operate the air conditioner at the cooling cycle and stop it
when the gauge indicates 1kg/cm2g.
48
Troubleshooting
Gas side
Closed
3-Way
valve
Gas cylinder
Lo
R410A OPEN CLOSE
• Procedure
(1) Confirm that both the liquid side valve and the gas side (6) Disconnect the charge set and the gas cylinder, and set
balve are set to the closed position. the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate the valve stems.
(2) Connect the charge set and a gas cylinder to the service
port of the Gas side valve. (8) Mount the valve stem nuts and the service port nut.
– Leave the valve on the gas cylinder closed. – Use torque wrench to tighten the service port nut to a torque of
1.8 kg.m.
– Be sure to check for gas leakage.
(3) Air purging.
– Open the valves on the gas cylinder and the charge set. Purge
the air by loosening the flare nut on the liquid side valve ap-
proximately 45o or 3 seconds then closing it for 1 minute;repeat
3 times. CAUTION: Do not leak the gas in the air during Air Purging.
– After purging the air, use a torque wrench to tighten the flare
nut on liquid side valve.
49
Troubleshooting
Gas side
3-Way
valve Open
Lo
OPEN CLOSE
• Procedure
(1) Confirm that both the 2-way and 3-way valves (3) Open the valve (Lo side) on the charge set and
are set to the back seat. discharge the refrigerant until the gauge indi-
cates 0 kg/cm2G.
(2) Connect the charge set to the 3-way valve’s – If there is no air in the refrigerant cycle (the
port. pressure when the air conditioner is not running
– Leave the valve on the charge set closed. is higher than 1 kg/cm2G), discharge the refrig-
– Connect the charge hose to the service port. erant until the gauge indicates 0.5 to 1
kg/cm2G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
50
Troubleshooting
Evacuation
(All amount of refrigerant leaked)
Gas side
3-Way
valve Open
Vacuum pump
Lo
OPEN CLOSE
• Procedure
(1) Connect the vacuum pump to the center hose (3) Close the valve (Lo side) on the charge set,
of charge set center hose turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
(2) Evacuation for approximately one hour. tely 5 minutes after turning off the vacuum
– Confirm that the gauge needle has moved pump).
toward -76 cmHg (vacuum of 4 mmHg or less).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
51
Troubleshooting
Gas Charging
(After Evacuation)
Gas side
Open
3-Way
Check valve valve
Charging
cylinder
Lo
(1) OPEN CLOSE
• Procedure
\
(1) Connect the charge hose to the charging This is different from previous procedures.
cylinder. Because you are charging with liquid refrigerant
– Connect the charge hose which you dis-con- from the gas side, absolutely do not attempt to
nected from the vacuum pump to the valve at charge with larger amounts of liquid refrigerant
the bottom of the cylinder. while operating the air conditioner.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys-
tem can be charged with liquid. (4) Immediately disconnect the charge hose from
the 3-way valve’s service port.
(2) Purge the air from the charge hose. – Stopping partway will allow the gas to be dis-
– Open the valve at the bottom of the cylinder charged.
and press the check valve on the charge set to – If the system has been charged with liquid
purge the air. (Be careful of the liquid refriger- refrigerant while operating the air conditioner
ant). The procedure is the same if using a gas turn off the air conditioner before disconnecting
cylinder. the hose.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant. (5) Mount the valve stem nuts and the service
– If the system can not be charged with the spec- port nut.
ified amount of refrigerant, it can be charged – Use torque wrench to tighten the service port
with a little at a time (approximately 150g each nut to a torque of 1.8 kg.m.
time) while operating the air conditioner in the – Be sure to check for gas leakage.
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure (pumping down-pin).
52
Removal Procedure
Hooks
53
Removal Procedure
Right
Rotary shaft
54
Removal Procedure
1 Remove a service
cover mounting screw.
Open service cover
upward.
screws
5. Removal of front grille assembly
55
Removal Procedure
Hook
1 Unfasten the hooks at
the upper 2 positions.
Hook
Vertical blade
56
Removal Procedure
Terminal board
2 Disconnect the
connection wires.
Connecting
wires
(R11268)
(R11244)
57
Removal Pr ocedur e
Bottom frame
Hook
58
Removal Procedure
Hook
59
Removal Procedure
Swing motor
60
Removal Procedure
61
Removal Pr ocedur e
CAUTION
Wooden base
Do not contaminate any gas
(including air) other than the
specified refrigerant (R-410A)
into refrigerant cycle.
(Contaminating of air or other
2 Place a plastic sheet gas causes abnormal high
under the drain pan as pressure in refrigerating
remaining drain may cycle, and this results in pipe
leak.
breakage or personal
injuries.)
Drain hose
Extension drain hose
Connecting wires
62
Removal Pr ocedur e
Liquid piping
Gas piping (R8019)
63
Removal Procedure
Auxiliary piping
64
Removal Procedure
Bearing
65
Removal Procedure
66
Removal Procedure
Fan motor
Partition plate
69
Removal Procedure
Sound blanket.
Caution
Be careful about the four way
valve, pipes and so on, which
were heated up by a gas
brazing machine, so as not
to get burnt your hands.
70
Removal Procedure
71