You are on page 1of 10

Heating, cooling, ventilation

with KNX
Use cases
HVAC use cases with KNX
Use cases

KNX covers all the heating, The data determined via KNX by If the user would like to automati-
ventilation and air conditioning the heat / cooling generators and cally access the data via the Inter-
applications using the availa- individual room thermostats can be net, the use of KNX web services
ble products. In particular, de- displayed by the visualisation sys- is offered. A gateway displays the
mand-based controllers make tems not only as values, diagrams KNX project so that the data can
a significant contribution to or graphics but also: be accessed via existing web service
implementations such as OBIX,
2 energy saving in buildings. The • stored locally and in the cloud
following pages describe exam- and displayed or evaluated at a OPC UA and BACnet-WS, with-
ples of typical HVAC applica- later point out knowing the specifications of
tions and systematically show • evaluated and checked whether the KNX protocol. The KNX web
how heat / cooling generators, they exceed the limit values service gateway can be operated in
individual room thermostats • linked with events, states and parallel to the visualisation system
and visualisation systems inter- times and trigger actions and is not displayed in the applica-
act via KNX. • converted into Euro amounts tions for reasons of clarity.
and totalled up
• routed as status or fault signals
via push messages or email

Control and monitoring


of the system functions of an HVAC device
Display and remote control of operating modes

The display and remote control KNX solution for case A


of the operating modes (com- Case A: Selection of the operating mode
fort, standby, night reduction) The user toggles the operating The user has different options de-
for the system functions (heat- state via his smartphone. pending on the system configura-
ing, cooling, ventilation and hot tion:
water) of a generator are of Case B: 1. To set the operating mode cen-
particular interest for the user The user starts the one-time trally on the power generation
if he wishes to intervene in the heating of the hot water before system. The system affects the
system control outside of the showering. respective heating circuit (e. g.
standard operation. one floor).
2. To set the operating mode sepa-
rately for each room via the vis-
ualisation using individual room
temperature control.
The setting under 1. has the prima-
ry function.
1. The default operating mode is
Visualisation system Condensing boiler
only carried out on the heat / Setpoint values
with or
cooling generator per heating / smartphone operation Actual values heat pump

Use cases
cooling circuit with a corre-

KNX interface
sponding feedback signal. The
heating system is largely self- HVAC mode status
sufficient. The operating mode is
HVAC mode
only assigned via the KNX either
manually, via a timer or a scene.
A typical application is party
mode in which the comfort mode
should be maintained outside the
programmed period. Another Selection and feedback of operating modes over HVAC mode,
3
1 Byte / DPT 20.102 or 1 Bit / DPT 1.00x
application is e. g. the integration
in a presence scene which is acti- For example for a heat pump control:
0: Auto
vated if the occupants are not at 1: Comfort
home for several days. 2: Standby
3: Economy
4: Building Protection

2. The default operating mode


Setpoint values
is carried out primarily at the Visualisation system
heat / cooling generator as with Actual values
smartphone operation

Condensing boiler
Setpoint temperature per room

well as per room on the indi-

KNX interface

or heat pump
HVAC mode status
vidual room thermostats. Both
the room thermostats and the HVAC mode
HVAC mode per room

heat / cooling generators send


a feedback signal to the visual-
isation about the respective
status. In this constellation, the
HVAC mode status Room
operating mode on the heat /
Room 1
cooling generator is typically
set for the entire building or a Room- Heating actuator
temperature- with
large section of the building. In sensor Actual temperature room thermostat
addition, individual rooms such
as conference rooms, training Room n
rooms or canteens can be op-
Room- Heating actuator
erated in an energetically low temperature- with
state. sensor Actual temperature room thermostat

KNX solution for case B Setpoint values


Visualisation system Condensing boiler
Domestic water heating with or
Actual values
The one-time heating of the hot smartphone operation heat pump
KNX interface

water e. g. via night mode, is trig-


HVAC mode status
gered via a 1-bit command. The
status can be queried at the same HVAC mode
object or a separate status object. DHW request status
Alternatively, a temporary increase
DHW request
of the setpoint temperature of the
hot water is possible.
one-time domestic hot water (DHW) 1 Bit / DTP 1.00x
Control and monitoring of temperatures
Use cases

Display and remote control of setpoint


and actual temperatures

The display of actual and set-


4 point temperatures of rooms, Case A: Case C:
zones / heating circuits as well as The user sets the setpoint tempera- An energy manager optimises the
the remote control of setpoint ture from 19°C to 21°C. inlet temperature of a heating cir-
temperatures and the optional cuit / 
zone using the predefined
creation of setpoint tempera- Case B: room temperatures.
ture time profiles are among the The user would like the room
standard functions of an individ- temperatures to be displayed via a Case D:
ual room temperature control- smartphone. The user configures time profiles so
ler. that the corresponding rooms have
achieved the comfort temperature
at the time of usage.

Setpoint values
Visualisation system
KNX solution for case A with Actual values
Changing setpoint temperature smartphone operation

Condensing boiler
Setpoint temperature per room

KNX interface
HVAC mode status

or heat pump
from 19°C to 21°C
An individual setpoint value can be HVAC mode

predefined for each room by the


HVAC Status Room

individual room thermostat via the


Setpoint temperature per room (feedback)

visualisation.
The input is carried out either as a
numerical value or via graphic ele-
ments (e. g. slide). Room 1
The room thermostat sends the re- Room- Heating actuator
spective setpoint value back to the temperature- with
sensor Actual temperature room thermostat
visualisation as confirmation.

Room n

Room- Heating actuator


temperature- with
sensor Actual temperature room thermostat

Actual-/Setpoint temperatures: 2 Byte Float / DPT 9.001


Setpoint values
Visualisation system
Actual values
KNX solution for case B with
smartphone operation

Condensing boiler
Setpoint temperature per room
Display of the room tempera- HVAC mode status

KNX interface

or heat pump
tures on a smartphone
HVAC mode

Use cases
A temperature sensor sends the re-

HVAC Status Room


spective actual value per room via
KNX to the associated room ther-
mostat which routes it for display

Actual temperature per room


on the visualisation.
Room 1

Room- Heating actuator


temperature- with
sensor Actual temperature room thermostat 5
Room n

Room- Heating actuator


temperature- with
sensor Actual temperature room thermostat

Actual-/Setpoint temperatures: 2 Byte Float / DPT 9.001

Setpoint values
Visualisation system
KNX solution for case C with
Actual values

For demand-based control, an smartphone operation

Condensing boiler
Setpoint temperature per room

HVAC mode status

KNX interface

or heat pump
energy manager optimises the
energy consumption HVAC mode

The valve drives send the valve po-


HVAC Status Room

sition per room to the energy man-

Actual temperature per room


ager which calculates the optimum
inlet temperature on the basis of
the current valve positions.
Room 1
Actuating drives
Room-
with
temperature-
Actual temperature Roomtemperature-
sensor
controller Energy manager

Room n
Actuating drives
Room-
with
temperature-
Actual temperature Roomtemperature-
sensor
controller

Actual-/Setpoint temperatures: Value_temp 2 Byte Float / DPT 9.001 • valve stroke: Percent (0 ... 100 %) / 1 Byte / DPT 5.001

Setpoint values
Visualisation system
KNX solution for case D with Actual values
The user configures time profiles smartphone operation
Condensing boiler
Setpoint temperature per room

HVAC mode status


KNX interface

or heat pump

Individual setpoint values can be


preassigned for each room for indi- HVAC mode

vidual room temperature control.


HVAC Status Room

The input of the setpoint values and


Setpoint temperatur per room (feedback)

times is generally carried out via


graphic elements on the user inter-
face of the visualisation. The profile
data is stored in the visualisation Room 1
system. Room- Heating actuator
temperatur- with
sensor Actual temperature room thermostat

Room n

Room- Heating actuator


temperatur- with
sensor Actual temperature room thermostat

Actual-/Setpoint temperatures: 2 Byte Float / DPT 9.001


Visualisation
of HVAC-related parameters
Use cases

Display of HVAC-specific parameters

6
Current condensing boilers and
heat pumps make far more Case A: Case C:
available via KNX than the set- The user would like the power con- The next service interval should be
point and actual temperatures. sumption of HVAC devices to be indicated to the user.
Users can thus be fully informed displayed.
via the KNX visualisation about
the status of the system and the Case B:
HVAC-specific parameters. The user would like the operating
state (normal operation, faults,
service requirements …) to be dis-
played via smartphone.

KNX solution for case A


Visualisation system Condensing boiler
Current heating controllers main- with Energy consumption or
ly make the energy consumption smartphone operation heat pump
KNX interface

available as an absolute value on the


KNX:
• electricity for heating
• electricity for hot water
• gas for heating
• gas for hot water
Energy consumption: real energy (kWh), 4 Byte / DPT 13.013
The energy consumption values are
prepared in the visualisation system
and displayed as:
• diagrams
• absolute values
• daily, weekly, monthly or annual
values
KNX solution for case B
Visualisation system Condensing boiler
Displaying operating states with Fault message or
on the smartphone smartphone operation heat pump

Use cases
KNX interface
Almost all the operating states can
be queried via the KNX interface Operating status
and displayed in the visualisation
including: heating, cooling, active
Service
heating program, day / night mode,
HV pumps, DHW heating, active
electric night heating, service, etc.
Fault message, Operating status: 1 Bit / DPT 1.00x; 1 Byte / DPT 6.020; 1 Byte / DPT 20.xxx
When there are system errors, er-
ror messages are automatically sent
to the visualisation via the KNX, ei-
7
ther as individual fault messages or
as group messages (“Faults of heat
generator”). Both fault messages
and states can be routed by the vis-
ualisation for immediate display and
push message to a smartphone.

KNX solution for case C


Visualisation system Condensing boiler
Note about with Running times or
the next service interval smartphone operation heat pump
KNX interface

The note about the next service


date can be carried out in different Service
ways.
1. The heat / cooling generator de-
termines the necessity of a ser-
vice appointment itself and sends
a request in the form of a yes / no Running times: TimePeriodHrs / 2 Byte / DPT 7.007
telegram to the visualisation sys-
tem.
2. The running times of the HV and
storage pumps, compressors,
electric heaters etc. are sent as
absolute values to the visualis-
ation, compared with the spec-
ified maintenance intervals and
the next service period is calcu-
lated.
Optimisation for optional power consumption

Anwendungsfälle
of heat pumps
Integration of heat pumps in energy management

8
Heat pumps belong to the most
energy-intensive devices in the Case A: Case C:
building. There is therefore a The service water is heated if the Further energy-intensive processes
high added value for the cus- electricity is reasonable. which exceed the domestic current
tomer to integrate these systems of the PV system are prevented
in the energy management so Case B: from starting during the heating
that they can be operated cost- The heating or cooling is carried out cycles.
effectively. within a tolerance range defined by
the customer if the electricity is Case D:
reasonable. The user can be shown when heat-
ing cycles take place and at what
price.

KNX solution for case A / B current operating status


Heat pumps can represent optional
processes (e. g. heating or cooling) current Actual values
KNX interface

on the communication interface, so Visualisation system


that these processes can be started with SG-Ready ON / OFF Heat pump
energy management
by an energy management system
SG-Ready operating status 1 – 4
under favourable conditions.
SG-Ready-Feedback
Use of SG ready functions for Operating status
heat pumps with Smart Grid
low tariff yes / no
capability ESC lock yes / no
Operating status 1
is backward compatible to utili- Converter
ty lock, incorporates a maximum
lockout period of two hours
tariff information
Operating status 2
the energy-efficient normal opera-
Smart Meter Gateway
tion with pro-rata filling of thermal
store for the maximum lockout pe-
riod of two hours SG-Ready-Operating-status: 1 Bit / DPT 1.00x
SG-Ready-Mode: 1 Byte / DPT 20.xxx
Operating status 3 www.waermepumpe.de/waermepumpe/sg-ready/
is the controller mode for heating
rooms and water
Operating status 4
is a definitive start-up command
KNX solution for case A / B current operating status
Control with a conventional heat
Anwendungsfälle

current Actual values


pump via operating modes and set- Visualisation system
with

KNX interface
point values. energy management
Operating modes Heat pump

Setpoint values

1 x warm water

low tariff yes / no


ESC lock yes / no

9
Converter

tariff information

Smart Meter Gateway

KNX solution for case C / D current operating status


The heat pump determines the Visualisation system current Actual values
thermal energy demand of the with
energy management Forecast
KNX interface
building and communicates the Heat pump
power requirement to the PV sys- with
SG Ready ON / OFF Energy management
tem.
The PV system plans the operating SG-Ready operating status 1 – 4

time of the devices under consid- SG Ready feedback


eration of a yield and consump- operating status
tion forecast so that the power
low tariff yes / no
consumption makes an optimum ESC lock yes / no
contribution to the domestic con-
sumption. PV system with
Converter
The heat pump converts this pro- Energy management

posal dependent on the operating


state and thus increases the domes- tariff information
tic consumption.
Electrical energy is converted into
thermal energy cost-effectively and Energy Meter / Smart Meter Gateway

stored temporarily in the house.

Operating states and forecast data


can be communicated by heat con-
trollers to a visualisation program
via the KNX and displayed as val-
ues, diagrams or graphics.
www.knx.org v2–17

You might also like