FAN FAILURE & TEMPERATURE DETECT UNIT WITH AC


POWER SUPPLY

General Specifications:

Fan Failure detect unit is an alarm gadget. A Unique Ana-Digi Circuit which is
designed and developed with a reputed Institution and evaluated and approved.

This unit monitors the AC Fans in marshalling cabinets. It detects,

1) Initial Struck (Power ON Struck)


2) Open Circuitry (both Fan winding open or Fan interface open)
3) Running Struck (due to Mechanical jam or dust / mist accumulation)
4) Short Circuit (winding / lead wire)
5) High Voltage (AC above 270V)

Any of the above fault occurs, an oring Relay contacts changes its position and
gives the potential free contact output (COM, NO, NC) which can connect to PLC /DCS.
At the Same time individual relay contact is disconnect the power to the Load (Fan).
Hence it’s Protects any Electrical hazards.

nandi FFDU unique module will take care 4”, 6” and 8” Fan. It construction is
Universal for adjusting the (setting the Load Current) different Load by adjusting the
front panel Potentiometer.

The front end LED’s indicate over Current-Set Limit, Fan running and Power
Indication.

The Unit Consists of

• Power Supply Module (SMPS type)


• Fan Control Channel Module
• Temperature indicator / controller Module (Option)

All the above modules plugged on to the mother board which is fitted in a rack.Each
Module can be inserted to slot and configured either for 4”, 6” &and 8”.

If any one channel fault occurred to cross verification depress “RESET Switch”. If
problem persist replace the Faulty module “ON-Line” without disturbing adjacent
channel and disconnecting Load wires.

-1-
-2-

SPECIFICATION:
Power Supply : 90 – 270VAC 50Hz 1 Phase.

Load (Fans) : 4”, 6” and 8” 110VAC or 220VAC

Failure Detection :
1) Initial Struck (Power ON Struck)
2) Open Circuitry (Either Fan winding open or Fan interface open)
3) Running struck (Due to Mechanical jam or dust / mist accumulation)
4) Short Circuit (Winding / lead wire)
5) High Voltage (AC above 270V)

Fault Reset : Trip reset Switch provides.

Short CKT : Fuse for power Supply and Channel module provided.

Indication : 1) For Fan Run Green Led Indicates.


2) For Over Limit Red Led Indicates
3) For Set / Power on Amber Led Indicates

Set : Load (Field adjustment potentiometer provided).

Protection : Fan power supply will be disconnected.

Connection : Though Combicon terminals 2.5Sq MM size wire.

Temperature Sensor : RTD PT 100 Sensor.

Temperature Measurement : 0 to 70’C

Temperature Set : Through Push Button & Variable Potentiometer.

Display : 2 Display 0.3”

Output : 4-20mA

Fault O/P : Potential free contact o/p, if the actual temperature


exceeds the set point

Mounting : Din Rail Mounting.


Back Plate Mounting (optional)

Ambient Temperature : 0 to 50’C.

-2-
-3-

Ambient humidity : 5 to 90% relative humidity (non-condensing)

Maximum Power Consumption: 125 V.

Insulation Resistance : Between Power and relay contact outputs: 100M ohm
@ 500 VDC.Between Power and Ground: 100M ohm
@ 500 VDC.

Dielectric strength : Between Power and relay contact outputs: 500 V AC for
1 Minute. Between Power and Ground: 1.5 KV AC for 1
Minute.

Dimensions : 125mm (L) X 105mm(D) X 100mm (H)