Professional Documents
Culture Documents
ASHRAE 62.1:
Using the Ventilation
Rate Procedure
ASHRAE 62.1 is best known for its regulation of the amount of ventilation
air delivered to each space by HVAC systems through its Ventilation Rate
Procedure for system design.
W
hile most mechanical design ASHRAE 62 was first published in 1973. It
engineers are familiar with was the first ventilation standard published by
ASHRAE Standard 62.1: Ven- ASHRAE and provided a prescriptive approach
tilation for Acceptable Indoor to minimum and recommended outdoor airflow
Air Quality, many are only rates for various indoor spaces. The intent was
familiar with the versions they’ve used through to provide a comprehensive enforceable method
their careers—most use it to satisfy code or permit of establishing ventilation rates centered around
requirements or to achieve credit compliance for a indoor air quality (IAQ). It provided prescriptive
high-performance building standard. The standard volumetric airflow rates per person and began
is best known for its Ventilation Rate Procedure looking at the concept of acceptable outdoor air
(VRP), and its online spreadsheets and calcula- quality.
tors have made achieving compliance The intent was to provide a comprehensive
(on paper) an “easy” step in HVAC and defensible method for establishing ventila-
L Learning design. What is missing, most times, tion rates. The standard has had many revisions
OBJECTIVES is the understanding behind why since it was first published, each with the intent
• Understand the history, ASHRAE 62 is necessary and how of improving ventilation in buildings. For existing
evolution, and organization the standard evolves to optimize air buildings, it is important to understand the iter-
of ASHRAE Standard 62.1: quality. ations and evolution of the standard to identify
Ventilation for Acceptable Indoor In addition to the VRP, there are how existing buildings might be ventilated based
Air Quality.
two additional methods for ventila- on which version was used at the time of construc-
• Recognize the equations for the tion discussed in ASHRAE 62: nat- tion or retrofit.
Ventilation Rate Procedure and
how to use them.
ural ventilation and the indoor air The second version was published in 1981
quality procedure (IAQP). These and reduced minimum outdoor-air rates, includ-
• Review example to enhance the
understanding of equations in
will not be discussed here, but they ed a VRP, as well as introduced the IAQP. It also
ASHRAE 62.1-2016. are important to mention as options included provisions for cigarette smoking, recog-
within the standard. The natural ven- nizing that “higher ventilation rates are specified
tilation method is appropriate for for spaces where smoking is permitted because
buildings using natural ventilation in lieu of or in tobacco smoke is one of the most difficult contam-
addition to mechanical ventilation. IAQP relies on inants to control at the source.” Additionally, recir-
numerical analysis of contaminant sources, con- culation air was addressed as well as provisions for
taminant concentration targets, and acceptability “air cleaners and adequate temperature control”
targets. For simplicity of a compliance analysis and for recirculation air.
because the VRP is the most common method for The next version, published in 1989, was influ-
compliance, these methods are not discussed fur- enced by a 1984 report from the World Health
ther in this article. Organization (WHO) in which it suggested that
’
for various indoor spaces.
A complete overhaul
Major changes came in the 2004 edition when
the standard was revised in its entirety. The IAQP
was modified to improve enforceability. More
importantly, and with greatest impact to engineers, Figure 2: The calculation-workflow diagram shows the
the VRP was modified. Minimum outdoor airflow calculation methodology and formulas for using the
rates and the procedures for calculating zone-lev- Ventilation Rate Procedure (VRP).
‘
perceived indoor-air acceptability (Standard Sec-
The Ventilation Rate Procedure (VRP) is tion 6.3). The third option is the natural ventila-
tion procedure (Standard Section 6.4), which is a
prescriptive procedure where outdoor air is pro-
the most commonly used for compliance. vided through outdoor openings.
The VRP is the most commonly used for com-
Frequently overlooked in the VRP is the pliance. Frequently overlooked in the VRP is the
requirement for outdoor-air treatment. When
’
requirement for outdoor-air treatment. using the VRP, it is important to verify if outdoor-
air treatment is required. The requirements are
outlined in Section 6.2.1 and are for ventilation
The 2004 edition separated out residential venti- systems that provide outdoor air through a supply
lation in ASHRAE 62.2 Ventilation and Accept- fan. Verification of outdoor-air treatment is made
able Indoor Air Quality in Low-Rise Residential on a local level and looks at particulates (PM10
Buildings. The original version of the standard and PM2.5) and ozone.
was renamed to ASHRAE 62.1 and included high- Special treatment is required for local condi-
rise residential. It also removed all references to tions that exceed the national standards. When
smoking. national standards are exceeded, HVAC systems
‘
Equipment Fouling!
The most recent edition is
ASHRAE Standard 62.1-2016.
COTTONWOOD
The most significant change is the
FILTER SCREENS™
movement of all residential spaces Stop Airborne Debris
Before it Becomes a Problem!
to Standard 62.2 regardless of
’
building height.
Fixed Mount or Pulley Mount System –
are required to provide additional air filtration depending on Simply Pull the Rope to Raise & Lower Filter.
noncompliance. Ozon-removal systems must be provided in
areas with ozone noncompliance.
Calculations begin in Section 6.2.2. Each zone in a sys-
tem must be looked at individually, and then systems can be
analyzed. Figure 2 outlines the steps required when using the
VRP, and Figure 3 provides the definitions of the symbols
used in the calculations.
Understanding the formulas, symbols, and calculations
for the VRP is best understood through example. An exam-
ple calculation is provided in the sidebar, “Small-office HVAC
calculations.” It is a single floor of an office building. The
HVAC system is overhead VAV with predominantly office and
conference room spaces.
If the Mortenson example in the sidebar is looked at ret-
roactively, back to the initial standard, the variations in min-
imum outdoor-air requirements can be seen. Table 1 in the
sidebar also looks at how taking occupant diversity into
account impacts minimum outdoor-air requirements. And
although there have been minor changes to the required min-
imums since 2004, the other changes surrounding the use of
carbon dioxide control and allowing ventilation to go to zero
when occupancy sensors are used can have larger impacts on
energy consumption. Special Non-stick HVAC Mesh protects chillers, cooling
towers, condenser units, air handling units, dry coolers
It is also good to analyze zone flows and calculation meth- and more by stopping airborne debris before it gets into
ods to iterate to the outdoor airflow the designer is most com- the equipment -Your equipment stays clean all-season
fortable with. The minimum outdoor-air intake flowchart ORQJ&OHDQƓOWHUVZLWKDIHZVZLSHVRIDEURRPEUXVK
illustrates that for 2004-2016 there are four potential compli- shop vacuum or garden hose – even the rain will rinse
ant minimum flows. It illustrates the impact that diversity can them clean!
have as well as how the designer allows for minimum flows FIRST YEAR PAYBACK - LASTS UP TO 15 yrs.
within each zone and if Appendix A is used. cse IT DOESN’T GET ANY EASIER THAN THIS!
Julianne Laue is the director of building performance at Morten- For Information or to locate a Representative Contact:
son. She is a 40 Under 40 award winner, and a member of the
Consulting-Specifying Engineer editorial advisory board.
M More
SOLUTIONS
Find more resources at www.csemag.com, including:
Toll Free -800-819-2869
www.airsolutioncompany.com
t"4)3"&BSUJDMFT
United States and Foreign Patents Granted – Protected under one
t)7"$FOFXTMFUUFS or more of the following U.S. and foreign patents: 5,370,722
t/FX1SPEVDUTGPS&OHJOFFST ŘŘ%ŘŘ
t8FCDBTUTPO)7"$
BJSTPMVUJPOT
BOENPSF Ř%Ř%Ř%Ř*%%
ŘŘOther Patents Pending.