You are on page 1of 3

JKR SPECIFICATION SUMMARY (S-L1)

NO. DESCRIPTION JKR REQUIREMENT REMARKS


1 TYPE OF SWITCH BOARD IEC 60439-1

FLOOR MOUNTED, METAL CLAD FRAME : 2.5mm (MINIMUM) FROM 2B


CUBICLE TYPE (FRONT & REAR PANEL : 2.0mm (MINIMUM) IP41
DUST & VERMIN PROOF
FLOOR MOUNTED, METAL CLAD FRAME : 2.5mm (MINIMUM) CLEAR TRANSPARENT COVER
CUBICLE TYPE (FRONT ACCESS) PANEL : 2.0mm (MINIMUM)

PEDESTRAL, WALL MOUNTED METAL PANEL : 2.0mm (MINIMUM)


CLAD TYPE ( FRONT ACCESS)

WALL MOUNTED, METAL CLAD PANEL : 1.2mm (MINIMUM) IEC 60439-3 (CONSUMER UNIT)

2 TYPE OF FORM

NO INTERNAL SEPARATION FORM 1

SEPARATION OF BUSBARS FROM THE TERMINALS FOR EXTERNAL CONDUCTORS NOT SEPARATED FROM FORM 2A
FUS BUSBARS

TERMINALS FOR EXTERNAL CONDUCTORS SEPARATED FROM FORM 2B


BUSBARS

SEPARATION OF BUSBARS FROM THE TERMINALS FOR EXTERNAL CONDUCTORS NOT SEPARATED FROM FORM 3A
FUS & SEPARATION OF ALL FUS FROM BUSBARS
ONE ANOTHER. SEPARATION OF
TERMINALS FOR EXTERNAL TERMINALS FOR EXTERNAL CONDUCTORS SEPARATED FROM FORM 3B
CONDUCTORS FROM THE FUS, BUT BUSBARS
NOT FROM THOSE OF OTHER FUS

SEPARATION OF BUSBARS FROM ALL TERMINALS FOR EXTERNAL CONDUCTORS IN THE SAME FORM 4A
FUS & SEPARATION OF ALL FUS FROM COMPARTMENT AS THE ASSOCIATED FU
ONE ANOTHER. SEPARATION OF
TERMINALS FOR EXTERNAL TERMINALS FOR EXTERNAL CONDUCTORS NOT IN THE SAME FORM 4B
CONDUCTORS ASSOCIATED WITH A COMPARTMENT AS THE ASSOCIATED FU, BUT IN INDIVIDUAL,
FU FROM THOSE OF ANY OTHER FU & SEPARATE, ENCLOSED PROTECTED SPACES OR COMPARTMENTS
THE BUSBARS

3 ACB 3 / 4 POLES IEC 60947-1


IEC 60947-2
ICW = 50KA AT 415V AT 1 SEC ASTA / KEMA CERTIFIED

FOR BUS COUPLER ACB SHALL BE 4 POLES TYPE


CLOSING MECHANISM SHALL BE STORED ENERGY TYPE

4 MCCB FOR INCOMING FEEDER, THE RATED SERVICE SHORT-CIRCUIT IEC 60947-1
BREAKING CAPACITY (ICS) SHALL BE 100% OF THE RATED IEC 60947-2
ULTIMATE SHORT-CIRCUIT BREAKING CAPACITY (ICU) AT 415
VOLTS

FOR ALL OUTGOING FEEDER, ICS SHALL BE 50% OF ICU

UNLESS OTHERWISE SPECIFY, THE RUPTURING CAPACITY OF THE


MCCB SHALL BE NOT LESS THAN 10 KA FOR DISTRIBUTION BOARD

ALL MCCBS IN THE SWITCHBOARD WHERE THE INCOMING FEEDER


CIRCUIT BREAKER (I.E. ACB/MCCB) ≥ 400A SHALL BE PROVIDED
WITH PANEL MOUNTING EXTERNAL OPERATING HANDLE WITH
PADLOCKING FACILITIES
NO. DESCRIPTION JKR REQUIREMENT REMARKS
5 MCB BREAKING CAPACITY NOT LESS THAN 6 KA IEC 60890

B-TYPE / CURVE WITH CLASS 3 ENERGY LIMITING


CHARACTERISTICS (GENERAL DOMESTIC USE)

C-TYPE / CURVE INSTANTANEOUS TRIP WITH CLASS 3 ENERGY


LIMITING CHARACTERISTICS (MOTORS, FLUORESCENT LIGHTING)

6 RCD RCCD IEC 61008-1


SHALL PROVIDE ANTI NUISANCE TRIPPING IEC 61008-2-1
2/4 POLES

RCBO IEC 61009-1


SHALL PROVIDE ANTI NUISANCE TRIPPING IEC 61009-2-1
2/4 POLES

7 FUSE SWITHGEAR IEC 60947-1


IEC 60947-3

8 ISOLATING SWITCH PROVIDED WITH REMOVABLE TOP AND BOTTOM END PLATES OR IEC 60947-1
KNOCKOUTS FOR CABLE ENTRY IEC 60947-3

9 ATS 2/4 POLES IEC 60947-1


IEC 60947-6-1
PROVIDE OVERCURRENT RELEASE

10 PROTECTION RELAY TYPE OF PROTECTION RELAY

OVER CURRENT, OC CONNECTED CURRENT


TRANSFORMER

EARTH FAULT, EF IDMT TYPE


IEC 60255
C/W TEST BUTTON & LED

EARTH LEAKAGE RELAY, ELR

COMBINE OC/EF
MICROPROCESSOR SHALL BE HOUSED IN ROBUST
ELECTRONIC PANEL FLUSH MOUNTING

INCLUDE SERIAL
COMMUNICATION PORT

11 MEASURING INSTRUMENT AMMETER MS 925


MOVING IRON TYPE IEC 60051
MD INDICATOR

VOLTMETER
MOVING IRON TYPE

POWER FACTOR METER


MEASURING RANGE FROM 0.5 LAGGING TO 0.5 LEADING

FREQUENCY METER
FREQUENCY RANGE FROM 45HZ TO 55HZ

DIGITAL METER (MICROPROCESOR BASED) INCLUDE ONE SERIAL


COMMUNICATION PORT
IEC 60359
IEC 60688
IEC 61000

CURRENT TRANSFORMER MS 1202


SECONDARY RATED 5A IEC 60044-1
VA BURDANS MORE THAN 15VA 5P10
10P10
NO. DESCRIPTION JKR REQUIREMENT REMARKS
12 SPD ONE–PORT SPD: IEC 61643-1
AN SPD CONNECTED IN SHUNT WITH THE CIRCUIT TO BE IEC 61643-12
PROTECTED. A ONE PORT DEVICE MAY HAVE SEPARATE INPUT IEC 62305
AND OUTPUT TERMINALS WITHOUT A SPECIFIC SERIES IEC 60364
IMPEDANCE BETWEEN THESE TERMINALS 4 POLES MCCB/ FUSES

TWO-PORT SPD:
AN SPD WITH TWO SETS OF TERMINALS, INPUT AND OUTPUT.
A SPECIFIC SERIES IMPEDANCE IS INSERTED BETWEEN THESE
TERMINALS. THIS PROTECTION IS NOT VERY EFFECTIVE