COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-19
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-20
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-21
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-22
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-23
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-24
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-25
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-26
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-27
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-28
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-29
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-30
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-31
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-32
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-33
1W1 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1691.8 -580.1 3.9 1587.0 -582.8 -7.8
2 1566.6 -500.9 5.2 1461.8 -503.1 -10.4
3 1536.0 -514.2 3.8 1431.2 -518.2 -7.7
4 1447.7 -495.0 1.0 1342.9 -497.3 -1.8
5 1654.0 -557.9 3.8 1549.2 -559.0 -7.7
6 1718.1 -587.2 3.7 1613.3 -584.8 -7.3
7 1643.9 -544.8 3.8 1539.1 -547.8 -7.7
8 1421.3 -487.9 1.2 1316.5 -495.4 -2.2
9 1686.5 -683.2 3.9 1581.7 -687.8 -7.8
10 1566.6 -500.9 5.2 1461.8 -503.1 -10.4
11 1551.5 -424.2 3.8 1446.7 -424.4 -7.7
12 1396.0 -881.9 7.6 1306.2 -660.7 -7.5
13 1444.4 -86.6 -1.1 1354.6 -312.2 -5.5
14 1341.8 -247.3 3.3 1251.9 -416.7 -6.5
15 1498.7 -721.2 3.2 1408.8 -556.3 -6.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 1691.8 - 1691.8
M1 (kN.m) -582.8 -33.8 -974.6
M2 (kN.m) -7.8 -19.0 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.071 Le1/b1 = 0.7 < 15.0
Beta = 0.91 Le2/b2 = 12.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 1.4 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.40 / 0.55 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
2W1 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1283.0 -443.2 11.2 1178.2 -453.2 -10.7
2 1187.4 -383.1 14.9 1082.6 -391.6 -14.1
3 1165.3 -393.7 11.0 1060.5 -404.8 -10.5
4 1098.5 -379.3 2.8 993.7 -387.6 -2.8
5 1252.8 -424.0 10.9 1148.0 -431.6 -10.5
6 1302.8 -448.8 10.5 1198.0 -451.5 -10.1
7 1247.3 -416.2 10.9 1142.5 -427.0 -10.5
8 1078.8 -373.8 3.5 974.0 -389.2 -3.3
9 1276.7 -516.3 11.2 1171.9 -530.3 -10.6
10 1187.4 -383.1 14.9 1082.6 -391.6 -14.1
11 1177.2 -328.5 11.0 1072.4 -332.4 -10.5
12 1055.1 -547.1 11.0 965.2 -427.8 -10.1
13 1099.0 -192.9 7.6 1009.2 -328.8 -7.6
14 1034.6 -225.1 9.4 944.8 -358.0 -9.0
15 1119.5 -514.9 9.2 1029.7 -398.6 -8.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 1283.0 - 1283.0
M1 (kN.m) -453.2 -25.7 -757.0
M2 (kN.m) 11.2 14.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.054 Le1/b1 = 0.7 < 15.0
Beta = 0.94 Le2/b2 = 13.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 5.8 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.41 / 0.59 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.01 N/mm2
H.Steel=Y8-170
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-34
3W1 Storey: 3 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 863.2 -294.8 10.0 758.4 -312.0 -9.8
2 798.6 -254.5 13.1 693.8 -269.7 -12.9
3 784.2 -262.7 9.8 679.4 -279.1 -9.6
4 738.7 -252.9 2.9 633.9 -266.8 -2.8
5 842.5 -280.9 9.6 737.6 -296.9 -9.5
6 876.7 -295.8 9.5 771.9 -310.7 -9.4
7 839.4 -276.5 9.6 734.6 -294.9 -9.5
8 725.2 -251.9 3.4 620.4 -268.1 -3.2
9 858.4 -342.4 10.0 753.6 -364.2 -9.8
10 798.6 -254.5 13.1 693.8 -269.7 -12.9
11 792.0 -219.5 9.8 687.2 -228.8 -9.6
12 709.5 -291.6 10.0 619.7 -254.5 -9.9
13 739.6 -200.5 6.6 649.8 -266.4 -6.5
14 707.1 -171.0 8.4 617.2 -267.1 -8.3
15 742.1 -321.2 8.2 652.2 -253.8 -8.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 863.2 - 863.2
M1 (kN.m) -312.0 -17.3 -526.8
M2 (kN.m) 10.0 9.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.036 Le1/b1 = 0.7 < 15.0
Beta = 0.96 Le2/b2 = 13.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.0 / 6.3 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.42 / 0.56 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.01 N/mm2
H.Steel=Y8-170
4W1 Storey: 4 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 435.6 -141.0 12.1 330.8 -165.0 -14.6
2 403.1 -120.9 15.7 298.2 -142.2 -18.8
3 395.8 -125.4 11.8 291.0 -147.8 -14.3
4 371.8 -121.2 3.7 267.0 -140.5 -4.6
5 425.7 -135.3 11.7 320.9 -157.9 -14.2
6 443.1 -141.8 11.5 338.3 -163.2 -13.8
7 423.8 -131.9 11.7 319.0 -157.4 -14.1
8 364.3 -120.5 4.3 259.5 -142.3 -5.4
9 434.0 -165.3 12.1 329.2 -194.3 -14.6
10 403.1 -120.9 15.7 298.2 -142.2 -18.8
11 399.3 -104.6 11.9 294.5 -118.9 -14.3
12 359.9 -103.3 11.2 270.1 -140.4 -13.6
13 371.4 -132.2 8.9 281.5 -135.1 -10.7
14 362.0 -90.9 10.2 272.2 -150.2 -12.3
15 369.3 -144.5 10.0 279.4 -125.3 -12.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 435.6 - 435.6
M1 (kN.m) -165.0 -8.7 0.0
M2 (kN.m) -14.6 -4.9 -21.8 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.018 Le1/b1 = 0.7 < 15.0
Beta = 0.98 Le2/b2 = 12.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 11.0 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.40 / 0.53 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.01 N/mm2
H.Steel=Y8-170
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-35
1W2 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1112.3 -7.6 -2.1 982.7 -14.3 -1.9
2 1089.1 -7.6 -1.8 959.5 -14.3 -1.6
3 1028.1 -7.6 -1.8 898.5 -14.3 -1.6
4 1016.8 49.0 -1.8 887.2 44.9 -1.6
5 1051.3 -56.0 -2.0 921.7 -62.3 -1.7
6 1077.9 -57.7 -2.0 948.3 -72.9 -1.8
7 1058.8 -56.0 -1.9 929.2 -62.3 -1.7
8 1051.2 99.2 -1.9 921.6 103.4 -1.7
9 933.3 -7.6 -2.5 803.7 -14.3 -2.2
10 1089.1 -7.6 -1.8 959.5 -14.3 -1.6
11 1199.5 -7.6 -1.5 1069.9 -14.3 -1.4
12 939.3 614.4 -1.7 828.2 288.8 -1.5
13 939.3 -625.6 -1.7 828.2 -311.2 -1.5
14 1099.4 -2.1 0.1 988.3 -7.5 -1.7
15 779.2 -9.1 -3.6 668.1 -14.9 -1.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 1112.3 - 1112.3
M1 (kN.m) -14.3 -22.2 0.0
M2 (kN.m) -2.1 -12.5 -13.3 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm 5225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.038 Le1/b1 = 0.6 < 15.0
Beta = 0.95 Le2/b2 = 12.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.3 / 0.1 kN As (Required): %0.40 (min) 4702.50 mm2 52Y12
vc'(1/2)= 0.43 / 0.52 N/mm2 As (Provided): %0.50 5881.06 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
2W2 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 834.6 0.8 -1.8 705.0 -13.5 -1.3
2 817.4 0.8 -1.5 687.8 -13.5 -1.1
3 770.4 0.8 -1.6 640.8 -13.5 -1.2
4 762.1 41.9 -1.5 632.5 32.8 -1.2
5 790.2 -37.0 -1.7 660.5 -50.1 -1.2
6 808.5 -34.5 -1.7 678.9 -64.1 -1.3
7 793.8 -37.0 -1.6 664.2 -50.1 -1.2
8 788.2 77.2 -1.6 658.6 83.4 -1.2
9 701.8 0.8 -2.1 572.2 -13.5 -1.6
10 817.4 0.8 -1.5 687.8 -13.5 -1.1
11 899.5 0.8 -1.3 769.9 -13.5 -1.0
12 704.7 312.9 -1.5 593.6 70.4 -1.1
13 704.7 -310.4 -1.5 593.6 -91.8 -1.1
14 791.6 2.5 -1.2 680.5 -9.2 -1.1
15 617.8 0.0 -1.7 506.7 -12.2 -1.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 834.6 - 834.6
M1 (kN.m) -13.5 -16.7 0.0
M2 (kN.m) -1.8 -9.4 -10.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm 5225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.028 Le1/b1 = 0.6 < 15.0
Beta = 0.97 Le2/b2 = 14.0 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 0.1 kN As (Required): %0.40 (min) 4702.50 mm2 52Y12
vc'(1/2)= 0.44 / 0.52 N/mm2 As (Provided): %0.50 5881.06 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-36
3W2 Storey: 3 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 556.8 2.0 -1.2 427.2 -13.5 -0.9
2 545.6 2.0 -1.1 416.0 -13.5 -0.8
3 513.1 2.0 -1.1 383.5 -13.5 -0.8
4 508.2 29.4 -1.1 378.6 19.2 -0.8
5 527.8 -23.8 -1.2 398.2 -37.6 -0.8
6 539.3 -22.7 -1.2 409.7 -51.2 -0.8
7 529.4 -23.8 -1.1 399.8 -37.6 -0.8
8 525.6 54.2 -1.1 396.0 56.9 -0.8
9 467.8 2.0 -1.4 338.2 -13.5 -1.0
10 545.6 2.0 -1.1 416.0 -13.5 -0.8
11 600.5 2.0 -0.9 470.9 -13.5 -0.6
12 470.1 119.8 -1.0 359.0 -34.6 -0.7
13 470.1 -115.6 -1.0 359.0 12.9 -0.7
14 506.2 2.1 -0.8 395.1 -10.5 -0.9
15 434.0 2.0 -1.3 322.9 -11.2 -0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 556.8 - 556.8
M1 (kN.m) -13.5 -11.1 0.0
M2 (kN.m) -1.2 -6.3 -6.7 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm 5225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.019 Le1/b1 = 0.6 < 15.0
Beta = 0.98 Le2/b2 = 14.0 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 0.0 kN As (Required): %0.40 (min) 4702.50 mm2 52Y12
vc'(1/2)= 0.41 / 0.52 N/mm2 As (Provided): %0.50 5881.06 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
4W2 Storey: 4 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 276.6 2.4 -0.8 147.0 -15.0 -0.1
2 271.5 2.4 -0.7 141.9 -15.0 -0.1
3 254.5 2.4 -0.7 124.9 -15.0 -0.1
4 252.8 15.5 -0.7 123.2 3.6 -0.1
5 262.3 -10.5 -0.8 132.7 -25.7 -0.1
6 268.2 -7.3 -0.8 138.6 -39.6 -0.1
7 263.2 -10.5 -0.7 133.6 -25.7 -0.1
8 261.3 25.3 -0.7 131.6 28.2 -0.1
9 230.6 2.4 -0.9 101.0 -15.0 -0.1
10 271.5 2.4 -0.7 141.9 -15.0 -0.1
11 299.7 2.4 -0.6 170.1 -15.0 -0.1
12 233.6 27.8 -0.7 122.5 -42.9 -0.1
13 233.6 -23.4 -0.7 122.5 18.2 -0.1
14 241.3 2.0 -0.7 130.2 -12.3 -0.1
15 225.9 2.4 -0.7 114.8 -12.4 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 276.6 - 276.6
M1 (kN.m) -15.0 -5.5 0.0
M2 (kN.m) -0.8 -3.1 -3.6 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm 5225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 0.6 < 15.0
Beta = 0.99 Le2/b2 = 13.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.3 kN As (Required): %0.40 (min) 4702.50 mm2 52Y12
vc'(1/2)= 0.41 / 0.52 N/mm2 As (Provided): %0.50 5881.06 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-37
1W3 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1665.5 -572.0 -1.8 1560.7 -580.9 3.7
2 1540.4 -492.9 -3.1 1435.6 -501.2 6.3
3 1509.8 -506.1 -1.8 1405.0 -516.2 3.6
4 1550.6 -506.9 0.2 1445.8 -514.2 -0.2
5 1521.1 -534.9 -1.8 1416.3 -540.8 3.5
6 1504.0 -506.5 -0.2 1399.2 -519.7 0.6
7 1511.0 -521.8 -1.8 1406.2 -529.6 3.4
8 1712.1 -572.4 -1.4 1607.3 -575.4 2.9
9 1660.3 -675.1 -1.8 1555.5 -685.9 3.7
10 1540.4 -492.9 -3.1 1435.6 -501.2 6.3
11 1525.2 -416.1 -1.8 1420.4 -422.5 3.6
12 1424.2 -80.1 2.8 1334.3 -310.9 2.1
13 1375.8 -875.4 -5.9 1286.0 -659.4 4.1
14 1319.7 -231.1 -1.5 1229.9 -412.8 3.1
15 1480.2 -724.3 -1.5 1390.4 -557.5 3.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 1665.5 - 1665.5
M1 (kN.m) -580.9 -33.3 -967.1
M2 (kN.m) 3.7 18.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.070 Le1/b1 = 0.7 < 15.0
Beta = 0.92 Le2/b2 = 12.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 0.2 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.41 / 0.53 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
2W3 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1264.3 -431.9 -5.5 1159.5 -453.5 5.5
2 1168.7 -371.8 -9.2 1063.9 -392.0 8.9
3 1146.6 -382.4 -5.4 1041.8 -405.2 5.3
4 1176.6 -383.1 0.1 1071.8 -401.1 0.3
5 1153.7 -403.7 -5.2 1048.9 -419.8 5.0
6 1141.6 -382.3 -1.1 1036.8 -408.7 1.3
7 1148.2 -395.8 -5.2 1043.4 -415.1 5.0
8 1299.3 -432.6 -4.3 1194.5 -446.0 4.5
9 1257.9 -504.9 -5.5 1153.1 -530.6 5.5
10 1168.7 -371.8 -9.2 1063.9 -392.0 8.9
11 1158.5 -317.2 -5.4 1053.7 -332.7 5.3
12 1084.6 -183.6 -2.9 994.8 -329.3 3.3
13 1040.7 -537.8 -6.3 950.8 -428.3 5.8
14 1019.4 -211.1 -4.6 929.5 -358.3 4.6
15 1105.9 -510.3 -4.5 1016.1 -399.2 4.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 1264.3 - 1264.3
M1 (kN.m) -453.5 -25.3 -753.2
M2 (kN.m) -5.5 -14.2 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.053 Le1/b1 = 0.7 < 15.0
Beta = 0.94 Le2/b2 = 13.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.1 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.43 / 0.54 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.00 N/mm2
H.Steel=Y8-170
Project: Training_01
SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-38
3W3 Storey: 3 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 849.5 -286.8 -5.4 744.7 -314.7 5.3
2 784.9 -246.5 -8.5 680.1 -272.4 8.4
3 770.5 -254.8 -5.2 665.7 -281.8 5.1
4 790.3 -254.2 -0.6 685.5 -278.1 0.8
5 775.0 -267.9 -4.9 670.2 -290.7 4.7
6 766.3 -256.6 -1.6 661.5 -283.5 1.6
7 772.0 -263.4 -4.8 667.2 -288.7 4.7
8 873.5 -284.4 -4.4 768.7 -309.3 4.5
9 844.7 -334.4 -5.4 739.9 -367.0 5.3
10 784.9 -246.5 -8.5 680.1 -272.4 8.4
11 778.3 -211.5 -5.2 673.5 -231.5 5.1
12 729.0 -194.0 -2.8 639.2 -268.8 2.8
13 698.9 -285.1 -6.2 609.1 -256.9 6.1
14 696.2 -162.8 -4.6 606.4 -270.2 4.5
15 731.7 -316.2 -4.4 641.9 -255.5 4.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 849.5 - 849.5
M1 (kN.m) -314.7 -17.0 -520.6
M2 (kN.m) -5.4 -9.6 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.036 Le1/b1 = 0.7 < 15.0
Beta = 0.96 Le2/b2 = 13.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.2 / 3.9 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.44 / 0.56 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.01 / 0.00 N/mm2
H.Steel=Y8-170
4W3 Storey: 4 (Con.:C20/25 / Steel:Grade 410 (Type 2) - Web:Grade 410 (Type 2))
Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 425.9 -136.0 -6.9 321.1 -172.1 8.6
2 393.3 -115.9 -10.6 288.5 -149.3 12.9
3 386.1 -120.4 -6.7 281.3 -154.9 8.3
4 396.0 -120.7 -1.3 291.2 -151.7 1.8
5 389.0 -128.4 -6.2 284.2 -158.3 7.8
6 382.9 -121.6 -2.5 278.1 -155.7 3.4
7 387.2 -125.0 -6.2 282.4 -157.8 7.8
8 439.1 -135.1 -5.7 334.3 -168.1 7.0
9 424.3 -160.3 -6.9 319.5 -201.4 8.6
10 393.3 -115.9 -10.6 288.5 -149.3 12.9
11 389.5 -99.6 -6.7 284.7 -126.1 8.4
12 363.7 -128.1 -4.6 273.8 -141.1 5.8
13 352.2 -99.1 -7.0 262.4 -146.4 8.6
14 354.3 -86.8 -5.9 264.5 -156.4 7.3
15 361.6 -140.4 -5.7 271.7 -131.1 7.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 425.9 - 425.9
M1 (kN.m) -172.1 -8.5 0.0
M2 (kN.m) 8.6 4.8 16.1 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
4225
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.018 Le1/b1 = 0.7 < 15.0
Beta = 0.98 Le2/b2 = 12.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.0 / 7.4 kN As (Required): %0.40 (min) 3802.50 mm2 42Y12
vc'(1/2)= 0.42 / 0.53 N/mm2 As (Provided): %0.50 4750.09 mm2
v (1/2)= 0.00 / 0.01 N/mm2
H.Steel=Y8-170
Project: Training_01
Project: Training_01 - SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
JOIST SLAB ANALYSIS REPORT Orion Building Design System 18.0 (04.2012) / Page: NER-1
/-- SUPPORT MOMENT -\ /--- SHEAR FORCE ---\ /-- MAX.SPAN MOMENT -\
Beam M-I M-J V-I V-J M-a X
(kN.m) (kN.m) (kN) (kN) (kN.m) (m)
-------- ---------- ---------- ---------- ---------- ---------- -----------
4R1-x4 16.6 0.0 19.6 12.9 12.2 0.000
/-- SUPPORT MOMENT -\ /--- SHEAR FORCE ---\ /-- MAX.SPAN MOMENT -\
Beam M-I M-J V-I V-J M-a X
(kN.m) (kN.m) (kN) (kN) (kN.m) (m)
-------- ---------- ---------- ---------- ---------- ---------- -----------
4R2-x3 4.7 -4.8 4.7 3.4 4.5 0.000
/-- SUPPORT MOMENT -\ /--- SHEAR FORCE ---\ /-- MAX.SPAN MOMENT -\
Beam M-I M-J V-I V-J M-a X
(kN.m) (kN.m) (kN) (kN) (kN.m) (m)
-------- ---------- ---------- ---------- ---------- ---------- -----------
4R2-y6 0.3 -2.7 3.7 4.9 5.9 0.000
Project: Training_01
Project: Training_01 - SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-1
NOTATION:
d/h = Effective/Total Depth of Slab (d=h-conc.cover)
g/q = Dead/Live Load (not factored)
L1 = Width of the Slab Along the Strip Direction
L2 = Width of the Slab Perpendicular to the Strip Direction
C = Moment Coefficient M=C p / L^2
M-spn = Ultimate Design Span Moment
M-sup = Ultimate Design Support Moment
Mc = Balanced Support Moment
As = Steel Area (Required/Supplied)
Project: Training_01
Project: Training_01 - SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-2
Project: Training_01
Project: Training_01 - SIMCONS (*1EF-ZLFQ-9FLH-RWEC)
SLAB ANALYSIS AND DESIGN REPORT Orion Building Design System 18.0 (04.2012) / Page: DSM-3
Support Mc = 0.0
Project: Training_01