1 P.

1-1 ~1-256

Introduction ··························································································1-2
R407C refrigerant unit
S series PUMY-P125VMA ···········································1-3
PUMY-P125YMA ···········································1-15
Y series PUHY-P200·250·315YEM-A(-BF, -BS) ·············1-27
PUY-P200·250·315YEM-A(-BF, -BS) ·············1-27
Big Y series PUHY-P400·500YEM-A(-BF, -BS) ···················1-43
Super Y series PUHY-P600·650·700·750YSEM-A(-BF, -BS) ···········1-55
R2 series PURY-P200·250YEM-A(-BF, -BS) ···················1-75
Big R2 series PURY-P400·500YEM-A ··································1-87
WY series PQHY-P200·250YEM-A ··································1-99
WR2 series PQRY-P200·250YEM-A ·································1-125
R22 refrigerant unit
S series PUMY-71VM·125VMA ····································1-151
PUMY-125YM·125YMA ··································1-165
Y series PUHY-200·250·315YEM-A(-BF, -BS) ···············1-177
PUY-200·250·315YEM-A(-BF, -BS) ··················1-177
PUHY-250·315YEMK-A ··································1-177
PUHY-200·250·315YEMC-A(-BS) ···················1-177
PUHY-200·250·315TEM-A(-BF) ······················1-193
Big Y series PUHY-400·500YEM-A(-BF, -BS) ······················1-213
PUHY-400·500YEMK-A ··································1-213
PUHY-400·500YEMC-A(-BS) ··························1-213
Super Y series PUHY-600·650·700·750YSEM-A(-BF, -BS) ·············1-225
PUHY-600·650·700·750YSEMK-A ···················1-225
PUHY-600·650·700·750YSEMC-A(-BS) ···········1-225
R2 series PURY-200·250YEMC-A ································1-245

2 P. 2-1 ~2-234

CE indoor unit
Introduction ·····················································································2-2
Ceiling concealed PEFY-P-VML-A1 ·······················2-5
PEFY-P-VMH-A
PEFY-P-VMM-A ························2-35
PEFY-P-VMH-A-F 2-63
Ceiling mounted built-in PDFY-P-VM-A ···························2-77
Floor standing Exposed PFFY-P-VLEM-A ·······················2-101
Cassette ceiling Concealed PFFY-P-VLRM-A
1-way flow PMFY-P-VBM-A ························2-115
2-way flow PLFY-P-VLMD-A ·······················2-127
PLFY-P-VLMD-B ·······················2-127
4-way flow PLFY-P-VKM-A/VAM-A ··············2-151
Wall mounted PKFY-P-VAM-A/VGM-A ·············· 2-169
PKFY-P-VFM-A ························· 2-185
Ceiling suspended PCFY-P-VGM-A ························· 2-195
OA Processing unit Non-humidifier GUF-RD2 ································ 2-205
Include humidifier GUF-RDH2 ································ 2-205
LOSSNAY LGH-RX3-E ································ 2-213
BC controller (with PURY, PQRY) CMB-P-V-F ······························ 2-221
CMB-P-V-FA ······························ 2-221
CMB-P-V-FB ······························ 2-221

3 P. 3-1 ~3-44

Function table of controller ······································································ 3-2


Local remote controller
Wired remote controller PAR-20MAA ······························ 3-3
PAR-F27MEA ···························· 3-4
Simple remote controller PAC-SE51CRA ························· 3-5
Simple MA controller PAC-YT51CRA ························· 3-6
Wireless remote controller PAR-FL31MA ···························· 3-7
PAR-FA31MA
LOSSNAY remote controller PZ-52SF-E ······························· 3-8
Program timer PAC-YT32PTA ·························· 3-9
System controller
Group remote controller PAC-SC30GRA ························· 3-10
System remote controller PAC-SF44SRA ·························· 3-12
Schedule timer PAC-YT34STA ························· 3-14
ON/OFF remote controller PAC-YT40ANRA ······················· 3-16
Centralized controller G-50A ······································
3-18
TG-2000A ································· 3-24
MB-300 ····································3-28
Air conditioner interface LMAP02-E ································ 3-34
Power supply unit PAC-SC34KUA ························· 3-36
PAC-SC50KUA ························· 3-37
Transmission booster unit PAC-SF46EPA ·························· 3-38
System compornent ················································································ 3-39

4 P. 4-1 ~4-68

Electrical Work & M-NET control ···························································· 4-2


Refrigerant & Piping ··············································································· 4-21
Caution For Refrigerant Leak ·································································· 4-66
1

CONTENTS

Introduction ···················································································· 1-2

R407C refrigerant & CE units


S series PUMY-P125VMA ·································· 1-3
PUMY-P125YMA ·································· 1-15
Y series PUHY-P200·250·315YEM-A(-BF, -BS) ············· 1-27
PUY-P200·250·315YEM-A(-BF, -BS) ··············· 1-27
Big Y series PUHY-P400·500YEM-A(-BF, -BS) ········ 1-43
Super Y series PUHY-P600·650·700·750YSEM-A(-BF, -BS) ········ 1-55
R2 series PURY-P200·250YEM-A(-BF, -BS) ······· 1-75
Big R2 series PURY-P400·500YEM-A(-BF, -BS) ······· 1-87
WY series PQHY-P200·250YEM-A························ 1-99
WR2 series PQRY-P200·250YEM-A ······················· 1-125

R22 refrigerant units


S series PUMY-71VM·125VMA ·························· 1-151
PUMY-125YM·125YMA ······················· 1-165
Y series PUHY-200·250·315YEM-A(-BF, -BS) ··· 1-177
PUY-200·250·315YEM-A(-BF, -BS) ······ 1-177
PUHY-250·315YEMK-A ························ 1-177
PUHY-200·250·315YEMC-A(-BS) ········ 1-177
PUHY-200·250·315TEM-A(-BF) ··········· 1-197
Big Y series PUHY-400·500YEM-A(-BF, -BS) ·········· 1-213
PUHY-400·500YEMK-A ······················ 1-213
PUHY-400·500YEMC-A(-BS) ··············· 1-213
Super Y series PUHY-600·650·700·750YSEM-A(-BF, -BS) ·········· 1-225
PUHY-600·650·700·750YSEMK-A ······· 1-225
PUHY-600·650·700·750YSEMC-A(-BS) ····· 1-225
R2 series PURY-200·250YEMC-A ····················· 1-245

1- 1
Introduction
Introduction

Standard Refrigerant Series Model Name 71 125 200 250 315 400 500 600 650 700 750
(2.8HP) (5HP) (8HP) (10HP) (13HP) (16HP) (20HP) (24HP) (26HP) (28HP) (30HP)

PUMY-P-VMA ●
S
PUMY-P-YMA ●
Y / Big Y / PUHY-P-Y(S)EM-A(-BF/-BS) ● ● ● ● ● ● ● ● ●
Super Y PUY-P-YEM-A(-BF/-BS) ● ● ●
R407C
PURY-P-YEM-A(BF/-BS) ● ●
R2 / BigR2
PURY-P-YEM-A ● ● ● ●
WY PQHY-P-YEM-A ● ●
WR2 PQRY-P-YEM-A ● ●
CE
PUMY-VM/VMA ● ●
S
PUMY-YM(A) ●
PUHY-Y(S)EM-A(-BF/-BS) ● ● ● ● ● ● ● ● ●
PUY-YEM-A(-BF/-BS) ● ● ●
Y / Big Y /
R22
Super Y
PUHY-Y(S)EMK-A ● ● ● ● ● ● ● ●
PUHY-Y(S)EMC-A(-BS) ● ● ● ● ● ● ● ● ●
PUHY-TEM-A(-BF) ● ● ●
R2 PURY-YEMC-A ● ●

Meaning of model name

P U H Y - P 200 YEM-A
Packaged Sub name
Air conditioner
Heat source
·U : Air Model size
·Q : Water

Series
·R : R2 unit Refrigerant
·H, M : Y unit ·P : R407C
·Nothing : Cooling ·Nothing : R22
only unit (Y)

Invertor
·Y : Variable capacity unit
(Invertor)
·N : Constant capacity unit

1- 2
PUMY-P125VMA

S-5(R407C)
CONTENTS

1. Specifications ································································· 1-4

2. Capacity Tables ······························································ 1-5


2-1 Correction by temperature ············································ 1-5
2-2 Correction by total indoor ············································· 1-7
2-3 Correction by refrigerant piping length ··························· 1-8
2-4 Correction at frosting and defrosting ···························· 1-9
2-5 Operation limit ······························································· 1-9

3. Sound Levels ·································································· 1-10

4. External Dimensions ···················································· 1-11

5. Electrical Wiring Diagram ·············································· 1-12

6. Refrigerant Circuit Diagram ········································· 1-13


And Thermal Sensor

1- 3
1. Specifications

PUMY-P125VMA
Model name
Cooling Heating

✻1 kW 14.0 16.0
S-5(R407C)

Capacity
✻2 kcal/h 12,500 –

Power source ~/N 220/230/240V,50Hz

Power input kW 6.10 6.03

Current A 28.3/27.1/26.0 28.0/26.8/25.7

Type ✕ Quantity Propeller fan ✕ 2

Fan Airflow rate m3/min 90

Motor output kW 0.06 ✕ 2

Type Hermetic

Compressor Motor output kW 3.5

Crankcase heater kW –

Refrigerant / Lubricant R407C/MEL32

External finish Steel plate painting with polyester powder


<MUNSELL 5Y8/1>
External dimension mm 1280(H)✕1020(W)✕350+30(D)

High pressure protection 3.0MPa


Protection
Compressor / Fan Internal thermal switch / Internal thermal switch
devices
Inverter Over current protection , Overheat protection

Refrigerant piping diameter Liquid / Gas ø9.52 /ø19.05 (Flare)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 125 / 1 ~ 8

Noise level ✻ dB<A> 54

Net weight kg 128

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range
Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 4
2. Capacity Table
2-1. Correction by temperature
Cooling
• Standard Specifications (Outdoor : 35°CDB/- Indoor : 27°CDB/19°CWB)

PUMY-P125

S-5(R407C)
Capacity kW 14.0
Input kW 5.95

Capacity at 100% indoor units running


1.30

1.20

1.10
Ratio

22˚CWB

1.00 20˚CWB

Indoor Temperature(˚CWB)
18˚CWB

0.90 16˚CWB

-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.40

1.20 22˚CWB
20˚CWB
18˚CWB
16˚CWB
1.00
Ratio

Indoor Temperature(˚CWB)

0.80

0.60

0.40
-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

1- 5
Heating
• Standard Specifications (Outdoor 7°CDB/6°CWB Indoor 20°CDB/-)

PUMY-P125
S-5(R407C)

Capacity kW 16.0
Input kW 5.58

Capacity at 100% indoor units running


1.30

15˚CDB
1.20
20˚CDB
1.10

1.00 25˚CDB
Ratio

Indoor Temperature(˚CDB)
0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.20

1.10 20˚CDB

15˚CDB
1.00 Indoor Temperature(˚CDB)
Ratio

25˚CDB
0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 6
2-2. Correction by total indoor

PUMY-P125

1) Capacity
17.00

S-5(R407C)
Heating
15.00 Cooling
Capacity(kW)

13.00

11.00

9.00

7.00
60 80 100 120 140 160 180
Total capacity of indoor units

2) Input
7.00

6.00 Cooling
Input(kW)

5.00 Heating

4.00

3.00

2.00
60 80 100 120 140 160 180 200
Total capacity of indoor units

1- 7
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


S-5(R407C)

PUMY-P125
1.0
Total ca
pacity
of indo
or unit
Cooling capacity
correction factor

0.9 63 (50%)

94 (75%)
0.8
125 (100%)
163 (130%)

0.7
5 10 20 30 40 50 60 70 75
Piping equivalent length (m)

• Heating capacity correction


PUMY-P125
1.0
Heating capacity
correction factor

0.95

0.9
5 10 20 30 40 50 60 70 75
Piping equivalent length (m)

• How to obtain piping equivalent length


PUMY-P125
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 ✕ number of bent on the piping)m

1- 8
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp

S-5(R407C)
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95

2-5. Operation limit

• Cooling
30
Indoor temperature (˚CWB)

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45 50
Outdoor temperature (˚CDB)

• Heating
30
Indoor temperature (˚CDB)

25

20

15

10
-15 -10 -5 0 5 10 15 20
Outdoor temperature (˚CWB)

1- 9
3. Sound Levels

PUMY-P125
Measurement condition 70

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
60
S-5(R407C)

NC60

50 NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
57 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 10
Air intake

Air intake

Air outlet Teminal block for transmission


PUMY-P125VMA

Teminal block for central remote control


Optional parts
Terminal block for power source (base branching
Handle for moving pipe) installation
hole
Optional parts
installation hole
4. External Dimensions

Side air intake

Rear air intake


Handle for
moving

Gas refrigerant-pipe

1- 11
connection ø 19.05 (3/4F)
Liquid refrigerant pipe
connection ø 9.52 (3/8F)

Knock out hole for right piping


Rear piping hole Knock out holes for
Knock out hole for power line 2-ø 27
front piping
Piping cover Knock out holes for power line 2-ø 29

2 - 12 ✕ 36 Oval holes 138


(standard bolt M10)

Bottom piping hole

shaped dotched holes


(standard bolt M10)
Drain hole
✻1...Indicates the dimensions of the cutoff valve connector.
(3-ø 33 hole)
Unit : mm

✻2...Make sure that the panel can be easily removed for maintenance
when a piping cover is used for aesthetic reasons.

S-5(R407C)
5. Electrical Wiring Diagram
PUMY-P125VMA
THHS TH6 TH5 TH2 TH1 63HS
SLEV

3 6

1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 1 2 3 1 2 1 3 1 2 1 3 1 2 1 2 3 1 2 3 4 5 6
CN40 CN41 CN51 CN3D CN3S THHS TH6 TH5 TH2 TH1 63HS SLEV
S-5(R407C)

(WHT) (WHT) (WHT) (WHT) (RED) (BLK) (WHT)(GRN) (GRN)(WHT) (WHT) (WHT)
LD1 SW1 SW2
ON ON
1 CNS2 OFF OFF
2 (YLW) 12345678 1 2 3 4 5 6 7 8 9 10
SW3 SW4 SW5
ON ON ON ACCT 2
1 CNS1 90 1 90 1 90 1 (YLW) 1
2 (RED) OFF OFF OFF
78

78

78
23

23

23
4 56 4 56 4 56 12 1234 12345678
(RED) (YLW) (WHT) (YLW)
SWU3 SWU2 SWU1 CN1 CN2 CN3 CN4
(3rd digit)(2nd digit) (1st digit) 6 3 2 1 6 5 4 3 2 1 7 6 3 2 1 7 6 5 4 3 2 1

<MULTI CONTROLLER BOARD>


MC 49C
U W 4 6 5 7
V

WHT
RED

BLK

YLW
YLW
<POWER SUPPLY BOARD>
TB3 <RESISTOR BOARD>
M1 BRN U V W
TO INDOOR UNIT 3 1 6 3 2 1 6 5 4 3 2 1 7 6 3 2 1 7 6 5 4 3 2 1
RD1
CONNECTING WIRES M2 P N 49C CN1 CN2 CN3 CN4
BRN (YLW) (RED) (YLW) (WHT) (YLW)
DC 30V (Non-polar) RD2 IPM
X (WHT)
CNR C03
S X 1
RB2 RB1 FUSE2 FUSE1 F.C
3 (2A)
+

+
(6.3A) X71 X72 X73
-

-
5
TB7 RS1 6 C01 C02
ORN 8
FOR CENTRALIZED M1 (RED) 10 (BLU) (GRN) (BLK) (WHT) (WHT)
CONTROL (WHT) 52C 21S4 SV1 MF1 MF2
M2 ORN 3 1 CNA 10 8 6 5 3 1 CNR N1 P P1 N E 3 1 3 1 3 1 3 1 3 1
DC 30V (Non-polar)

WHT

WHT
YLW
YLW
WHT

GRN
YLW
YLW

RED

BLU
BLU

BLU

BLU
BLK
BLK
BLU
BLK

6
S
3 1 3 1

WHT

WHT
BLU

BLU
DM DCL 52C 21S4 SV1
3 1 BLK BLK
NO FUSE BREAKER TB1 NF
25A CNA + + MF1 MF2
L1 (RED) CB1
L1 RED RED
LI1 LO1 ~

ORN

ORN
ñ

RED

RED
BLU

L2
POWER SUPPLY L2 WHT LI2 LO2 WHT ~ ZNR
3N~ L3 L3 BLK LI3 LO3 BLK ~ +
380/220-415/240V N CB2 C1 C2
N BLU ñ
50Hz N
GRN/YLW ñ BLU WHT
E
52C
GRN

GROUND

NOTES : 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. : Terminal block, : Connector, :Insertion tab.
3. Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF. (Example)
When the compressor and SV1 are
1. During normal operation turned during cooling operation.
The LED indicates the drive state of the controller in the outdoor unit. 1 23 45 67 8
Bit 1 2 3 4 5 6 7 8
Indication Compressor 52C 21S4 SV1 - - - Always lit
operated
2. When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
ACCT CONNECTOR <CURRENT DETECTION> C1,C2 FAN MOTOR CAPACITOR SV1 SOLENOID VALVE <HOT GAS BYPASS> TH2 THERMISTOR
<LOW PRESSURE SATURATED
CB1,CB2 SMOOTHING CAPACITOR DM DIODE MODULE SW1 SWITCH <DISPLAY SELECTION> TEMPERATURE DETECTION>
CNA CONNECTOR <POWER SUPPLY> DCL REACTOR SW2 SWITCH <FUNCTION SELECTION> TH5 THERMISTOR
<PIPE TEMPERATURE DETECTION
CNR CONNECTOR <DISCHARGE CIRCUIT, POWER SUPPLY> F.C FAN CONTROL SW3 SWITCH <TEST RUN> JUDGING DEFROST>
CNS1 CONNECTOR <MULTI SYSTEM> FUSE1 FUSE (6.3A) SW4 SWITCH <MODEL SELECTION> TH6 THERMISTOR
CNS2 CONNECTOR <CENTRALIZED CONTROL> FUSE2 FUSE (2A) SW5 SWITCH <FUNCTION SELECTION> <OUTDOOR TEMPERATURE DETECTION>

CN1 CONNECTOR <CONTROLLER DRIVE CONTROL> IPM INTELLIGENT POWER MODULE SWU1 SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> X RELAY
CN2 CONNECTOR <POWER SYNC SIGNAL, PROTECTION> LD1 DIGITAL INDICATION LED SWU2 SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> X71 RELAY <MAGNETIC CONTACTOR>
<OPERATION INSPECTION INDICATION> SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> X72 RELAY <4-WAY VALVE>
CN3 CONNECTOR <POWER SUPPLY 30V,12V,5V> SWU3
CN4 CONNECTOR <INVERTER SIGNAL 5V> MC COMPRESSOR <INNER THERMOSTAT> TB1 TERMINAL BLOCK <POWER SUPPLY> X73 RELAY <SOLENOID VALVE>
CN40 CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> MF1,MF2 FAN MOTOR <INNER THERMOSTAT> TB3 TERMINAL BLOCK <TRANSMISSION> ZNR VARISTOR
CN41 CONNECTOR <FOR STORING JUMPER CONNECTOR> NF NOISE FILTER TB7 TERMINAL BLOCK <CENTRALIZED CONTROL> 21S4 4-WAY VALVE
CN51 CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> RS1 RESISTOR <RUSH CURRENT PROTECT> THHS THERMISTOR 49C THERMAL SWITCH <COMPRESSOR>
<IPM RADIATOR PANEL
CN3D CONNECTOR <AUTO CHANGE OVER SIGNAL> RB1,RB2 RESISTOR <VOLTAGE BALANCE ADJUSTMENT> TEMPERATURE DETECTION> 52C MAGNETIC CONTACTOR
CN3S CONNECTOR <DEMAND SIGNAL> RD1,RD2 RESISTOR <DISCHARGE> TH1 THERMISTOR 63HS HIGH PRESSURE SENSOR
<DISCHARGE TEMPERATURE <DISCHARGE PRESSURE DETECTION>
C01,C02 SMOOTHING CAPACITOR SLEV EXPANSION VALVE DETECTION>
C03 CAPACITOR <FILTER>

1- 12
PUMY-P125

(Refrigerant flow)
Cooling
Heating Thermistor TH6
(outdoor air
High-pressure sensor temperature sensor)
discharge pressure sensor
(63HS)
Service port 4-way
Connector valve
Flare Gas pipe Strainer
Thermistor TH23
for monitoring gas
pipe temperature
Oil
Flare separator
Indoor heat Check valve
Strainer
exchanger Check valve (High prssure)
(low pressure)
Thermistor
Thermistor Strainer TH1 (discharge
temperature Thermistor TH5
TH21 (intake (pipng temperature

1- 13
temperature sensor) monitoring and
Capillary Electromag-
detection) tube 1 netic valve determination)
Thermistor TH2 (SV1)
(Saturation temperature Capillary
of suction pressure) Outdoor heat exchanger tube 3
Capillary Compressor Thermistor THHS
tube 2 (Radiator panel
Thermistor (MC)
TH22 (piping Strainer temperature sensor)
temperature Accumulator
detection)
Flare Electronic expansion valve (SLEV)
Linear expansion
valve (LEV)
Liquid pipe Strainer Overcooling heat exchanger
Flare Connector Strainer
Service port
Indoor unit Outdoor unit
6. Refrigerant Circuit Diagram And Thermal Sensor

S-5(R407C)
S-5(R407C)

1- 14
PUMY-P125YMA

CONTENTS

S-5(R407C)
1. Specifications ································································· 1-16

2. Capacity Tables ······························································ 1-17


2-1 Correction by temperature ············································ 1-17
2-2 Correction by total indoor ············································· 1-19
2-3 Correction by refrigerant piping length ··························· 1-20
2-4 Correction at frosting and defrosting ···························· 1-21
2-5 Operation limit ······························································· 1-21

3. Sound Levels ·································································· 1-22

4. External Dimensions ···················································· 1-23

5. Electrical Wiring Diagram ·············································· 1-24

6. Refrigerant Circuit Diagram ········································· 1-25


And Thermal Sensor

1- 15
1. Specifications

PUMY-P125YMA
Model name
Cooling Heating

✻1 kW 14.0 16.0
Capacity
✻2 kcal/h 12,500 –

Power source 3N ~ 380/400/415V 50Hz

Power input kW 5.95 5.58

Current A 9.6/9.1/8.8 9.2/8.8/8.5


S-5(R407C)

Type ✕ Quantity Propeller fan ✕ 2

Fan Airflow rate m3/min 90

Motor output kW 0.06 ✕ 2

Type Hermetic

Compressor Motor output kW 3.5

Crankcase heater kW –

Refrigerant / Lubricant R407C/MEL32

External finish Steel plate painting with polyester powder


<MUNSELL 5Y8/1>
External dimension mm 1280(H)✕1020(W)✕350+30(D)

High pressure protection 3.0MPa


Protection
Compressor / Fan Internal thermal switch / Internal thermal switch
devices
Inverter Over current protection , Overheat protection

Refrigerant piping diameter Liquid / Gas ø9.52 /ø19.05 (Flare)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 125 / 1 ~ 8

Noise level ✻ dB<A> 54

Net weight kg 127

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range
Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 16
2. Capacity Table
2-1. Correction by temperature

Cooling
• Standard Specifications

PUMY-P125
Capacity kW 14.0
Input kW 5.95

Capacity at 100% indoor units running

S-5(R407C)
1.30

1.20

1.10
Ratio

22˚CWB

1.00 20˚CWB

Indoor Temperature(˚CWB)
18˚CWB

0.90 16˚CWB

-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.40

1.20 22˚CWB
20˚CWB
18˚CWB
16˚CWB
1.00
Ratio

Indoor Temperature(˚CWB)

0.80

0.60

0.40
-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

1- 17
Heating
• Standard Specifications (Outdoor : 7°CDB/6°CWB Indoor : 20°CDB/-)

PUMY-P125
Capacity kW 16.0
Input kW 5.58

Capacity at 100% indoor units running


S-5(R407C)

1.30

15˚CDB
1.20
20˚CDB
1.10

1.00 Indoor Temperature(˚CDB) 25˚CDB


Ratio

0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.20

1.10 20˚CDB

15˚CDB
1.00 Indoor Temperature(˚CDB)
Ratio

25˚CDB
0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 18
2-2. Correction by total indoor

PUMY-P125

1) Capacity
17.00
Heating
15.00 Cooling
Capacity(kW)

13.00

S-5(R407C)
11.00

9.00

7.00
60 80 100 120 140 160 180
Total capacity of indoor units

2) Input
7.00

6.00 Cooling
Input(kW)

5.00 Heating

4.00

3.00

2.00
60 80 100 120 140 160 180
Total capacity of indoor units

1- 19
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PUMY-P125
1.0
Total ca
pacity
of indo
or unit
Cooling capacity
correction factor

0.9 63 (50%)
S-5(R407C)

94 (75%)
0.8
125 (100%)
163 (130%)

0.7
5 10 20 30 40 50 60 70 75
Piping equivalent length (m)

• Heating capacity correction


PUMY-P125
1.0
Heating capacity
correction factor

0.95

0.9
5 10 20 30 40 50 60 70 75
Piping equivalent length (m)

• How to obtain piping equivalent length


PUMY-P125
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 ✕ number of bent on the piping)m

1- 20
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95

2-5. Operation limit

S-5(R407C)
• Cooling
Indoor temperature (˚CWB)

30

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25

20

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 21
3. Sound Levels
PUMY-P125
Measurement condition 70

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
60
NC60

50 NC50
1m

40
S-5(R407C)

NC40

Sound pressure level in anechoic room 30


NC30
57 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 22
Air intake

Air intake

Air outlet Teminal block for transmission


PUMY-P125YMA

Teminal block for central remote control


Optional parts
Terminal block for power source (base branching
Handle for moving pipe) installation
hole
Optional parts
installation hole
4. External Dimensions

Side air intake

Rear air intake


Handle for
moving

Gas refrigerant-pipe

1- 23
connection ø 19.05 (3/4F)
Liquid refrigerant pipe
connection ø 9.52 (3/8F)

Knock out hole for right piping


Rear piping hole Knock out holes for
Knock out hole for power line 2-ø 27
front piping
Piping cover Knock out holes for power line 2-ø 29

2 - 12 ✕ 36 Oval holes 138


(standard bolt M10)

Bottom piping hole

shaped dotched holes


(standard bolt M10)
Drain hole
✻1...Indicates the dimensions of the cutoff valve connector.
(3-ø 33 hole)
Unit : mm

✻2...Make sure that the panel can be easily removed for maintenance
when a piping cover is used for aesthetic reasons.

S-5(R407C)
5. Electrical Wiring Diagram
PUMY-P125YMA
THHS TH6 TH5 TH2 TH1 63HS
SLEV

3 6

1 2 3 4 1 2 3 4 1 2 3 4 5 1 2 3 1 2 3 1 2 1 3 1 2 1 3 1 2 1 2 3 1 2 3 4 5 6
CN40 CN41 CN51 CN3D CN3S THHS TH6 TH5 TH2 TH1 63HS SLEV
(WHT) (WHT) (WHT) (WHT) (RED) (BLK) (WHT)(GRN) (GRN)(WHT) (WHT) (WHT)
LD1 SW1 SW2
ON ON
1 CNS2 OFF OFF
2 (YLW) 12345678 1 2 3 4 5 6 7 8 9 10
SW3 SW4 SW5
ON ON ON ACCT 2
1 CNS1 90 1 90 1 90 1 (YLW) 1
2 (RED) OFF OFF OFF
78

78

78
23

23

23
4 56 4 56 4 56 12 1234 12345678
(RED) (YLW) (WHT) (YLW)
SWU3 SWU2 SWU1 CN1 CN2 CN3 CN4
S-5(R407C)

(3rd digit)(2nd digit) (1st digit) 6 3 2 1 6 5 4 3 2 1 7 6 3 2 1 7 6 5 4 3 2 1

<MULTI CONTROLLER BOARD>


MC 49C
U W 4 6 5 7
V

WHT
RED

BLK

YLW
YLW
<POWER SUPPLY BOARD>
TB3 <RESISTOR BOARD>
M1 BRN U V W
TO INDOOR UNIT 3 1 6 3 2 1 6 5 4 3 2 1 7 6 3 2 1 7 6 5 4 3 2 1
RD1
CONNECTING WIRES M2 P N 49C CN1 CN2 CN3 CN4
BRN (YLW) (RED) (YLW) (WHT) (YLW)
DC 30V (Non-polar) RD2 IPM
X (WHT)
CNR C03
S X 1
RB2 RB1 FUSE2 FUSE1 F.C
3 (2A)
+

+
(6.3A) X71 X72 X73
-

-
5
TB7 RS1 6 C01 C02
ORN 8
FOR CENTRALIZED M1 (RED) 10 (BLU) (GRN) (BLK) (WHT) (WHT)
CONTROL (WHT) 52C 21S4 SV1 MF1 MF2
M2 ORN 3 1 CNA 10 8 6 5 3 1 CNR N1 P P1 N E 3 1 3 1 3 1 3 1 3 1
DC 30V (Non-polar)

WHT

WHT
YLW
YLW
WHT

GRN
YLW
YLW

RED

BLU
BLU

BLU

BLU
BLK
BLK
BLU
BLK

6
S
3 1 3 1

WHT

WHT
BLU

BLU
DM DCL 52C 21S4 SV1
3 1 BLK BLK
NO FUSE BREAKER TB1 NF
25A CNA + + MF1 MF2
L1 (RED) CB1
L1 RED RED
LI1 LO1 ~

ORN

ORN
ñ

RED

RED
BLU

L2
POWER SUPPLY L2 WHT LI2 LO2 WHT ~ ZNR
3N~ L3 L3 BLK LI3 LO3 BLK ~ +
380/220-415/240V N CB2 C1 C2
N BLU ñ
50Hz N
GRN/YLW ñ BLU WHT
E
52C
GRN

GROUND

NOTES : 1. Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2. Symbols used in wiring diagram above are. : Terminal block, : Connector, :Insertion tab.
3. Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch (SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF. (Example)
When the compressor and SV1 are
1. During normal operation turned during cooling operation.
The LED indicates the drive state of the controller in the outdoor unit. 1 23 45 67 8
Bit 1 2 3 4 5 6 7 8
Indication Compressor 52C 21S4 SV1 - - - Always lit
operated
2. When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which the fault has occurred.

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
ACCT CONNECTOR <CURRENT DETECTION> C1,C2 FAN MOTOR CAPACITOR SV1 SOLENOID VALVE <HOT GAS BYPASS> TH2 THERMISTOR
<LOW PRESSURE SATURATED
CB1,CB2 SMOOTHING CAPACITOR DM DIODE MODULE SW1 SWITCH <DISPLAY SELECTION> TEMPERATURE DETECTION>
CNA CONNECTOR <POWER SUPPLY> DCL REACTOR SW2 SWITCH <FUNCTION SELECTION> TH5 THERMISTOR
<PIPE TEMPERATURE DETECTION
CNR CONNECTOR <DISCHARGE CIRCUIT, POWER SUPPLY> F.C FAN CONTROL SW3 SWITCH <TEST RUN> JUDGING DEFROST>
CNS1 CONNECTOR <MULTI SYSTEM> FUSE1 FUSE (6.3A) SW4 SWITCH <MODEL SELECTION> TH6 THERMISTOR
CNS2 CONNECTOR <CENTRALIZED CONTROL> FUSE2 FUSE (2A) SW5 SWITCH <FUNCTION SELECTION> <OUTDOOR TEMPERATURE DETECTION>

CN1 CONNECTOR <CONTROLLER DRIVE CONTROL> IPM INTELLIGENT POWER MODULE SWU1 SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> X RELAY
CN2 CONNECTOR <POWER SYNC SIGNAL, PROTECTION> LD1 DIGITAL INDICATION LED SWU2 SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> X71 RELAY <MAGNETIC CONTACTOR>
<OPERATION INSPECTION INDICATION> SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> X72 RELAY <4-WAY VALVE>
CN3 CONNECTOR <POWER SUPPLY 30V,12V,5V> SWU3
CN4 CONNECTOR <INVERTER SIGNAL 5V> MC COMPRESSOR <INNER THERMOSTAT> TB1 TERMINAL BLOCK <POWER SUPPLY> X73 RELAY <SOLENOID VALVE>
CN40 CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> MF1,MF2 FAN MOTOR <INNER THERMOSTAT> TB3 TERMINAL BLOCK <TRANSMISSION> ZNR VARISTOR
CN41 CONNECTOR <FOR STORING JUMPER CONNECTOR> NF NOISE FILTER TB7 TERMINAL BLOCK <CENTRALIZED CONTROL> 21S4 4-WAY VALVE
CN51 CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> RS1 RESISTOR <RUSH CURRENT PROTECT> THHS THERMISTOR 49C THERMAL SWITCH <COMPRESSOR>
<IPM RADIATOR PANEL
CN3D CONNECTOR <AUTO CHANGE OVER SIGNAL> RB1,RB2 RESISTOR <VOLTAGE BALANCE ADJUSTMENT> TEMPERATURE DETECTION> 52C MAGNETIC CONTACTOR
CN3S CONNECTOR <DEMAND SIGNAL> RD1,RD2 RESISTOR <DISCHARGE> TH1 THERMISTOR 63HS HIGH PRESSURE SENSOR
<DISCHARGE TEMPERATURE <DISCHARGE PRESSURE DETECTION>
C01,C02 SMOOTHING CAPACITOR SLEV EXPANSION VALVE DETECTION>
C03 CAPACITOR <FILTER>

1- 24
PUMY-P125

(Refrigerant flow)
Cooling
Heating Thermistor TH6
(outdoor air
High-pressure sensor temperature sensor)
discharge pressure sensor
(63HS)
Service port 4-way
Connector valve
Flare Gas pipe Strainer
Thermistor TH23
for monitoring gas
pipe temperature
Oil
Flare separator
Indoor heat Check valve
Strainer
exchanger Check valve (High prssure)
(low pressure)
Thermistor
Thermistor Strainer TH1 (discharge
temperature Thermistor TH5
TH21 (intake

1- 25
sensor) (pipng temperature
temperature Capillary Electromag- monitoring and
detection) tube 1 netic valve determination)
Thermistor TH2 (SV1)
(Saturation temperature Capillary
of suction pressure) Outdoor heat exchanger tube 3
Capillary Compressor Thermistor THHS
tube 2 (Radiator panel
Thermistor (MC)
TH22 (piping Strainer temperature sensor)
temperature Accumulator
detection)
Flare Electronic expansion valve (SLEV)
Linear expansion
valve (LEV)
Liquid pipe Strainer Overcooling heat exchanger
Flare Connector Strainer
Service port
Indoor unit Outdoor unit
6. Refrigerant Circuit Diagram And Thermal Sensor

S-5(R407C)
S-5(R407C)

1- 26
PUHY-P200·250·315YEM-A (-BF, -BS)
PUY-P200·250·315YEM-A (-BF, -BS)
CONTENTS

1. Specifications ································································· 1-28

2. Capacity Tables ······························································ 1-31


2-1 Correction by temperature ············································ 1-31
2-2 Correction by total indoor ············································· 1-33

Y-8,10,13(R407C)
2-3 Correction by refrigerant piping length ··························· 1-35
2-4 Correction at frosting and defrosting ···························· 1-36
2-5 Operation limit ······························································· 1-36

3. Sound Levels ·································································· 1-37

4. External Dimensions ···················································· 1-39

5. Electrical Wiring Diagram ············································· 1-40

6. Refrigerant Circuit Diagram ········································· 1-41


And Thermal Sensor

1- 27
1. Specifications

PUHY-P200YEM-A (-BF, -BS)


Model name PUY-P200YEM-A (-BF, -BS)
Cooling Heating

✻1 kW 22.4 25.0
Capacity
✻2 kcal/h 20,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 6.32 6.80

Current A 10.6/10.1/9.7 11.4/10.9/10.5

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38


Y-8,10,13(R407C)

Type Hermetic

Compressor Motor output kW 5.3

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R407C/MEL32


External finish Pre-coated galvanized sheets (Powder coating)
<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 13

Noise level ✻ dB<A> 56

Net weight kg 225

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
(0˚CDB ~ 43˚CDB with outdoor
unit at lower position)

Matters Deserving Special Mention A pipe of ø28.58 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 28
PUHY-P250YEM-A (-BF, -BS)
Model name PUY-P250YEM-A (-BF, -BS)
Cooling Heating

✻1 kW 28.0 31.5
Capacity
✻2 kcal/h 25,000 -

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 8.54 8.95

Current A 14.4/13.6/13.2 15.1/14.3/13.8

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Y-8,10,13(R407C)
Type Hermetic

Compressor Motor output kW 6.8

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 57

Net weight kg 225

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB~15.5˚CWB
Operating temperature range (0˚CDB ~ 43˚CDB with outdoor
unit at lower position)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 29
PUHY-P315YEM-A (-BF, -BS)
Model name PUY-P315YEM-A (-BF, -BS)
Cooling Heating
✻1 kW 35.5 40.0
Capacity
✻2 kcal/h 31,500 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 12.30 12.49

Current A 20.3/19.2/18.5 20.6/19.5/18.8

Type✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38


Y-8,10,13(R407C)

Type Hermetic

Compressor Motor output kW 8.6

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 31.75 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 60

Net weight kg 240

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range (0˚CDB~43˚CDB with outdoor unit ( -12˚C(-5˚C)WB ~ 10˚CWB with
at lower position) indoor unit P25(P20) type only is
working )

Matters Deserving Special Mention A pipe of ø34.93 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 30
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications

PU(H)Y-P200 PU(H)Y-P250 PU(H)Y-P315


Capacity kW 22.4 28.0 35.5
Input kW 6.32 8.54 12.3

Capacity at 100% indoor units running


1.30

1.20

Y-8,10,13(R407C)
1.10
Ratio

24˚CWB
22˚CWB
1.00 20˚CWB
19˚CWB
18˚CWB
Indoor Temperature(˚CWB) 16˚CWB
0.90
15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30
24˚CWB

1.20 22˚CWB
20˚CWB
1.10 19˚CWB
18˚CWB
1.00
16˚CWB
0.90 Indoor Temperature(˚CWB)
Ratio

15˚CWB

0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 31
Heating
• Standard Specifications (Outdoor 7°CDB/6°CWB Indoor 20°CDB/-)

PUHY-P200 PUHY-P250 PUHY-P315


Capacity kW 25.0 31.5 40.0
Input kW 6.80 8.95 12.49

Capacity at 100% indoor units running


1.30
15˚CDB
1.20

1.10
Y-8,10,13(R407C)

Indoor Temperature(˚CDB) 20˚CDB


1.00
Ratio

0.90

0.80 25˚CDB

0.70 27˚CDB

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10

1.00 15˚CDB

0.90
20˚CDB
Ratio

0.80

0.70 Indoor Temperature(˚CDB)


25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 32
2-2. Correction by total indoor

PU(H)Y-P200
1) Capacity
30.0

Heating
25.0
Capacity(kW)

20.0 Cooling

15.0

10.0

5.0
100 150 200 250 300
Total capacity of indoor units
2) Input
10.00

Y-8,10,13(R407C)
9.00
8.00
Input(kW)

7.00 Heating
6.00
5.00 Cooling

4.00
3.00
2.00
1.00
100 150 200 250 300
Total capacity of indoor units
PU(H)Y-P250
1) Capacity
35.0

30.0 Heating
Capacity(kW)

25.0 Cooling

20.0

15.0

10.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
12.00
11.00
10.00
9.00
Input(kW)

Heating
8.00
7.00 Cooling
6.00
5.00
4.00
3.00
100 150 200 250 300 350 400
Total capacity of indoor units

1- 33
PU(H)Y-P315

1) Capacity
45.0
Heating
40.0
Capacity(kW)

35.0
Cooling
30.0

25.0

20.0

15.0
150 200 250 300 350 400
Total capacity of indoor units
Y-8,10,13(R407C)

2) Input
14.00
13.00 Cooling
12.00
11.00
Input(kW)

10.00 Heating
9.00
8.00
7.00
6.00
5.00
4.00
3.00
150 200 250 300 350 400
Total capacity of indoor units

1- 34
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PU(H)Y-P200 PU(H)Y-P250
1.0 1.0 Total ca
Total ca pacity
pacity of indo
of indo or unit
or unit
100 125
Cooling capacity

Cooling capacity
correction factor

correction factor
0.9 0.9
150 188
200 250
0.8 0.8
260 325

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PU(H)Y-P315

Y-8,10,13(R407C)
1.0
Total capaci
ty of indoor unit
Cooling capacity
correction factor

158
0.9 237

315

0.8 410

0 20 40 60 80 100 120
Piping equivalent length (m)

• Heating capacity correction


PUHY-P200 PUHY-P250
1.0 1.0
Heating capacity

Heating capacity
correction factor

correction factor

0.9 0.9

0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-P315
1.0
Heating capacity
correction factor

0.9

0.8

0.7
0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PU(H)Y-P200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PU(H)Y-P250
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m
➂ PU(H)Y-P315
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m

1- 35
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

PUHY-P200·250 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95
Correction
factor
PUHY-P315 1.0 0.93 0.82 0.82 0.86 0.9 0.9 0.95 0.95

2-5. Operation limit

• Cooling
30
Indoor temperature (˚CWB)
Y-8,10,13(R407C)

25

(Outdoor door temperature :


20
0˚CDB~43˚CDB with outdoor unit
at lower position in cooling mode.)
15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
30
Indoor temperature (˚CDB)

25
(When the indoor P25(P20)type only is working,
20 the outdoor unit [PUHY-P315] inlet air temperature
becomes -12˚C(-5˚C)WB~10˚CWB.)
15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 36
3. Sound Levels
PU(H)Y-P200
Measurement condition Cooling Heating
90

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
56 dB (A) 30 NC-30

Y-8,10,13(R407C)
20 Approximate minimum NC-20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

PU(H)Y-P250
Measurement condition Cooling Heating
90
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m

80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

57 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 37
PU(H)Y-P315
Cooling Heating
Measurement condition 90

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
30 NC-30
60 dB (A)
Y-8,10,13(R407C)

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 38
<Accessory>

(15)
• Refrigerant (gas) conn. pipe·······1pc.
(The connecting pipe is fixed with the unit)
12 5 Y ø40 Knockout hole • Packing for conn. pipe ··········1pc.
<Bottom side hole for (Attached near the ball valve)
the power supply> • Wiring mounting board
Note1 Y • Conduit mounting plate
ø27 Knockout hole (Painted the same color as the unit body)

840
910
Knockout hole
<Bottom side hole for
Bottom piping hole ø40···························1pc.
the control wiring>

50
<Bottom wiring hole> ø33···························1pc.

880(bolt hole)
2✕2-14✕20 ø27···························1pc.
• Tapping screw 4 ✕ 10············· 6pcs.

237
Oval hole

198
121
Note1.Please leave a space under the outdoor unit

73 80
for the piping When you connect the piping

15
25 160 215 560(bolt hole) (215) from the bottom.
Conn. pipe 778 75
200:ø25.4<brazed> 990 (Please be careful not to close the hole
Crosss section Y-Y 250:ø28.58<brazed> Cross section X-X of the bottom plate by the basement)
315:ø31.75<brazed> Plane view
4. External Dimensions
PU(H)Y-P200,250,315YEM-A(-BF,-BS)

Air outlet

1- 39
Air
inlet
1755

Air
Knockout hole inlet
1490

Refrig. service
60 75 valve (liquid) Service panel
ø12.7<flare>
ø40 Knockout hole X X
<Left side hole for
the power supply>

40

234
100
194
149
99

70
78

48
ø27 Knockout hole Knockout hole
100 251 <Left side hole for Refrig. service 79 80 Front piping hole Knockout hole
the control wiring> 80 40
Knockout hole valve(gas) <Front wiring hole> <Front side hole for
Knockout hole <flange> 813 the power supply>
Left piping hole 31 165 590 55

Rear view Left side view Front view Right side view
Unit : mm

Y-8,10,13(R407C)
5. Electrical Wiring Diagram
PU(H)Y-P200, 250, 315YEM-A(-BF, -BS)

MC1 Motor
Inverter U V W (Compressor)
Controller Box
Red White Black
ACCT
-W
ACCT
Terminal Noise -U
Terminal Diode
Block NF Filter Block stack
TB1A TB1B
L1 L2 L3 N
DS R1 R5 IPM
L1 L1 Red L1 L1 Red L1 Red ZNR4 CNDC2
~+
+
(4P) U V W
Power source L2 L2 L2 L2 L2 C1 C2 R2 C4 P 4
3N~ White White White ~ 3
380/400/415V 52C
C3
+ 2
50/60Hz R3 1
L3 L3 Black L3 L3 Black L3 Black ~-
DCL Gate amp board
(G/A board)
N N Blue N N Blue N Blue DCCT 1 2 3 4 N
Green/
PE Yellow

BOX BODY
PE BOX BODY F3 CNDC1 CNDR1 CN15V1
TB3 (4P) (9P) (14P)
250VAC
Connect to M1 1A F 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1011121314
Indoor and
remote M2
BOX BODY
controller CNTR1

M1 BOX BODY

Orange

Orange

Purple
Brown

Brown

Yellow

White
Black

Black
T01

Gray
Red

Red
Green
M2

White
Y-8,10,13(R407C)

Blue
S
CN20 1 1
123 12 1 2 3(3P) 2 2 5 4 3 2 1 1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1011121314
1 2 3 CNRS3 3
TB7 3 CNAC21 CNCT
CNS2 CNS1 CNTR (7P) 4 4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) F1 (3P) 5 5 (7P) (5P) (4P) (4P) (9P) (14P)
250VAC 6 6
2A F 7 7
F01 F02
CNVCC41 250VAC 700VDC
(2P) 1 CNVCC4
2 2 (2P) 2A T 2A T
CH1 3
Crank case heater 2 CN32 1
2
1 DC-DC
(Compressor) 1 (3P) X01 CNVCC3 3 2
(6P) 3 CNVCC2 Converter 1
4 4 (6P) CNCT2 2
5 5
3 6 (4P) 3
SV1 6
2
1
CN33
(3P) X02 X10
1 1 Power circuit board 4
2 2 X01 (INV board)
3
6 52C 3
CNX10
5 (3P) CN52CAC CNTH CNL2 CNFG
21S4 4 CN34 (3P) X02 (2P) (2P) (2P)
3 (6P) X04 1 2 3 12 12 12
CNFAN
2 (3P)
✻1 1 1
12V 2
3
4
5 4:Compressor ON/OFF
MF1 BOX BODY
CN51 5:Trouble
(5P)
BOX BODY THHS L2
6
5
SV4
SV3 4 CN36 X06 Control circuit board
3 (6P) DEMAND
2 X07
(MAIN board) CN3D 3
2
(3P) 1 NIGHT MODE
CN3N
Mode
1
OR DEMAND
1-2 1-3
CN3S 3 ON ON Auto HEAT
2 SNOW changeover
(3P) 1 OFF COOL
ON OFF Normal
CN3N 3
2
(3P) 1 OFF

L1 L2 L3

CNPOW
(5P) 1 2 3 4 5
X10 F03 250VAC 6.3A F
CN38
(3P) F02 250VAC 6.3A F
63H 1 F01 250VAC 6.3A F
High pressure 2
switch 3 detection
circuit 6 6
5 5 1
Refer to the service handbook CNFC1 4 4 CNFC2 CNFAN 23
1
U
(6P) 3 3 (6P) 2
(5P) 4 V
about the switch operations. W MF
2 2 3
1 1 5 4
N
CN04
Fan motor
Fan control board (Heat exchanger)
N
CN03 CN02 CN01 CNH CNL CNLV1 CNTYP1 (Fancon board)
(3P) (8P) (2P) (3P) (3P) (5P) (2P)
123 12345678 12 1 2 3 1 2 3 1234 5 12
White

White
Black

Black
Red

Red

3 2 1 3 2 1 LEV1
TH6 TH5 TH8 TH7 TH2 TH1 R20
63HS 63LS

<DIFFERENCE OF APPLIANCE>
Appliance Name
PUHY-P200/250/315YEM-A(-BF, -BS) All exists
PUY-P200/250/315YEM-A(-BF, -BS) “✻1” are not existed

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name Symbol Name
DCL DC reactor (Power factor improvement) Solenoid valve L2 Choke coil (Transmission) Thermistor bypass outlet temp. detect
SV3 TH8
DCCT Current Sensor (Heat exchanger capacity control) IPM Intelligent power module at Sub--cool coil
ACCT-U,W Current Sensor Solenoid valve TH1 Thermistor Discharge pipe temp. detect THHS Radiator panel temp. detect
SV4 (Heat exchanger capacity control)
ZNR4 Varistor TH2 Saturation evapo. temp. detect X1~10 Aux. relay
52C Magnetic contactor (Inverter main circuit) Electric expansion valve TH5 Pipe temp. detect
LEV1 Earth terminal
MF1 Fan motor (Radiator panel) (Sub-cool coil bypass) TH6 OA temp. detect
21S4 ✻1 4--way valve 63HS High pressure sensor liquid outlet temp. detect
TH7
SV1 Solenoid valve (Discharge--suction bypass) 63LS Low pressure sensor at Sub--cool coil

1- 40
BV1
ST1

63H

63HS
PUHY-P200, 250, 315

SV3 CJ1 CJ2


ST5

ST8 CP3

CP1
O/S

ST3 SV1 63LS

TH6 Indoor units


TH1

1- 41
Comp ST7
SV4
ST6

ST9 Accumulator
Drier ST10 CP4

TH2
6. Refrigerant Circuit Diagram And Thermal Sensor

TH8

TH5 TH7 ST2 BV2


SCC
LEV1 ST4

Y-8,10,13(R407C)
Y-8,10,13(R407C)

BV1
ST1

63H

63HS
PUY-P200, 250, 315

SV3 CJ1 CJ2


ST5

ST8 CP3

CP1
O/S

ST3 SV1 63LS

TH6 Indoor units


TH1

1- 42
Comp ST7
SV4
ST6

ST9 Accumulator
Drier ST10 CP4

TH2

TH8

TH5 TH7 ST2 BV2


SCC
LEV1 ST4
PUHY-P400·500YEM-A(-BF, -BS)

CONTENTS

1. Specifications ································································· 1-44

2. Capacity Tables ······························································ 1-46


2-1 Correction by temperature ············································ 1-46
2-2 Correction by total indoor ············································· 1-48
2-3 Correction by refrigerant piping length ··························· 1-49
2-4 Correction at frosting and defrosting ···························· 1-50
2-5 Operation limit ······························································· 1-50

3. Sound Levels ·································································· 1-51

Big Y(R407C)
4. External Dimensions ···················································· 1-52

5. Electrical Wiring Diagram ··········································· 1-53

6. Refrigerant Circuit Diagram ········································· 1-54


And Thermal Sensor

1- 43
1. Specifications

PUHY-P400YEM-A(-BF, -BS)
Model name
Cooling Heating
✻1 kW 45.0 50.0
Capacity
✻2 kcal/h 40,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 15.87 14.59

Current A 26.7/25.4/24.5 24.6/23.4/22.5

Type✕ Quantity Propeller fan ✕2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 4.5

Crankcase heater kW 0.045 + 0.045

Refrigerant / Lubricant R407C / MEL32


Big Y(R407C)

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 25 ~ 250 / 1 ~ 20

Noise level ✻ dB<A> 60 / 61

Net weight kg 440

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-12˚CWB ~ 15.5˚CWB
Operating temperature range
(0˚CDB ~43˚CDB with outdoor (-12˚CWB~10˚CWB with indoor unit
unit at lower position.) 25 type only is working)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 44
PUHY-P500YEM-A(-BF, -BS)
Model name
Cooling Heating

✻1 kW 56.0 63.0
Capacity
✻2 kcal/h 50,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 19.89 18.27

Current A 33.5/31.9/30.7 30.8/29.2/28.2

Type✕ Quantity Propeller fan✕ 2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 7.5

Crankcase heater kW 0.045 + 0.056

Refrigerant / Lubricant R407C / MEL32

Big Y(R407C)
External finish Pre-coated galvanized sheets (Powder coating)
<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 25 ~ 250 / 1 ~ 20

Noise level ✻ dB<A> 60 / 61

Net weight kg 475

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-12˚CWB ~ 15.5˚CWB
Operating temperature range
(0˚CDB ~43˚CDB with outdoor (-12˚CWB~10˚CWB with indoor
unit at lower position.) unit 25 type only is working)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 45
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications

PUHY-P400 PUHY-P500
Capacity kW 45.0 56.0
Input kW 15.87 19.89

Capacity at 100% indoor units running


1.30

1.20

1.10
24˚CWB
Ratio

22˚CWB
1.00 20˚CWB

18˚CWB
Big Y(R407C)

0.90 16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30 24˚CWB
22˚CWB
1.20 20˚CWB
18˚CWB
16˚CWB
1.10 15˚CWB

1.00

0.90
Ratio

Indoor Temperature(˚CWB)
0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 46
Heating
• Standard Specifications

PUHY-P400 PUHY-P500
Capacity kW 50.0 63.0
Input kW 14.59 18.27

Capacity at 100% indoor units running


1.30

1.20
15˚CDB
1.10

20˚CDB
1.00 Indoor Temperature(˚CDB)
Ratio

0.90
25˚CDB
0.80
27˚CDB

Big Y(R407C)
0.70

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10

1.00 Indoor Temperature(˚CDB)

15˚CDB
0.90
Ratio

0.80 20˚CDB

0.70
25˚CDB
0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 47
2-2. Correction by total indoor

PUHY-P400
1) Capacity
60
Heating
50
Capacity(kW)

40 Cooling

30

20

10
200 250 300 350 400 450 500
Total capacity of indoor units
2) Input
18.0
Cooling
16.0

14.0
Input(kW)

Heating
12.0

10.0
Big Y(R407C)

8.0

6.0
200 250 300 350 400 450 500
Total capacity of indoor units
PUHY-P500
1) Capacity
70
Heating
60
Capacity(kW)

Cooling
50

40

30

20
250 300 350 400 450 500 550 600 650
Total capacity of indoor units
2) Input
22.0

20.0 Cooling

18.0
Heating
Input(kW)

16.0

14.0

12.0
10.0

8.0
250 300 350 400 450 500 550 600 650
Total capacity of indoor units

1- 48
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction

PUHY-P400 PUHY-P500
1.0 1.0
Total ca Total ca
pacity pacity o

Cooling capacity
correction factor
of indo f indoor
or unit unit
200 250
Cooling capacity

0.9
correction factor

0.9
300 375

500
0.8 0.8
400 650

520 0 20 40 60 80 100 120


0.7
Piping equivalent length (m)

0 20 40 60 80 100 120
Piping equivalent length (m)

• Heating capacity correction


PUHY-P400·500
Cooling capacity
correction factor

Big Y(R407C)
1.0

0.9

0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PUHY-P400
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m
➁ PUHY-P500
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 ✕ number of bent on the piping)m

1- 49
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.89 0.90 0.92 0.95 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

When the indoor unit is located above


25
the outdoor unit for 4m or more, the
outdoor unit inlet air temperature
20
becomes 0~43˚CDB.

15

10
-5 0 5 10 15 20 25 30 35 40 45
Big Y(R407C)

Outdoor temperature (˚CDB)

• Heating
30
Indoor temperature (˚CDB)

25
When the indoor unit 25type only is
working, the outdoor unit inlet air
20 temperature becomes -12~10˚CWB.

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 50
3. Sound Levels
PUHY-P400
Measurement condition
50Hz 60Hz

1m

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


70

60
NC60
1m

50
NC50

Sound pressure level in anechoic room 40


NC40
60 / 61 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10

Big Y(R407C)
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

PUHY-P500
Measurement condition
50Hz 60Hz

1m
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70

60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
60 / 61 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 51
Big Y(R407C)

<Accessorys>

15
• Refrigerant (gas) conn. pipe ················· 1pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. pipe ·························· 1pc. Refrig.service
(Attached near the ball valve) valve (liquid) Refrig. service
valve(gas)
• Conduit mouting plate Service valve ø15.88<flare> <flange>
(Painted the same color as the unit body) (oil balance)
ø62,ø53,ø46 ·································· Each 1pc. ø12.7<flare>
840
910

• Tapping screw 4X10 ····························· 6pcs. Conn. pipe


ø27 Knockout hole ø34.93 <brazed>
• Wiring partition plate ····························· 1pc. <bottom hole for the
control wiring>
880(bolt hole)

Note1. Please leave a space under the outdoor unit


for the piping when you connect the piping

90 80
169

203
152
from the bottom.

111
(Please be careful not to close the hole

73
of the bottom plate by the basement) 3X2-14X20 oval hole
15

230 150 Note.1 215 780(bolt hole) 780(bolt hole) 215


PUHY-P400, 500YEM-A(-BF, -BS)

694 80 82 78 Knockout hole


Bottom piping hole 1990
Bottom hole for the power supply
4. External Dimensions

Changeable to 400:ø46,ø53,ø62 Cross section X-X Plane view


500:ø53,ø62 by using attached
conduit mounting plate (accessory) Air outlet
265

1- 52
Air
inlet

Air
1755

inlet
1490

X Knockout hole X
Service valve
(oil balance)
Refrig. service
745 25 90 75 valve(gas)
100 Service panel
24
149 70

126
86

Knockout hole
48

80 40
70

Left side hole for 218 Knockout hole


the control wiring, Front piping hole
the power supply, the 725 115
Front hole for the power supply Refrig.service
oil balance pipe to the Changeable to 400:ø46,ø53,ø62 45 valve (liquid)
constant capacity unit 500:ø53,ø62 by using attached
conduit mounting plate (accessory)
Rear view Left side view Front view
Unit : mm
MC2 Motor MC1 Motor
<ELECTRICAL WIRING DIAGRAM> U V W (Compressor) U VW (Compressor) <Symbol explanation>
Red White Black Red White Black Symbol Name Symbol Name
Inverter
Controller Box DC reactor TH11,12 Thermistor Discharge pipe temp. detect
DCL (Power factor improvement) TH2 Saturation evapo. temp. detect
FB1 FB2
51C2 52C2 TH3
2 1 2 1 ACCT-U,W Current Sensor Accumurator liquid Lower
4 3 4 3 ACCT ZNR4 Varistor TH4 temp. detect Upper
6 5 6 5 -W
Magnetic contactor TH5 Pipe temp. detect(Hex outlet)
ACCT 52C1
Terminal -U (Inverter main circuit) TH6 OA temp. detect
Terminal Noise Diode
Block
Block L1 L2 L3 N stack 52C2 Magnetic contactor SC coil temp.detect
NF Filter R1 R5 IPM
TB1A TB1B FB5 DS TH7
L1 L1 L1 L1 L1 ZNR4 51C2 Overload relay (Liquid exit area)
~+ U V W
+
Power source L2 L2 L2 L2 L2 C1 C2 R2 52F Magnetic contactor(Fan motor) SC coil temp.detect
3N~ ~ P
52C1 C3+
TH8 (Bypass exit area)
380/400/415V L3 L3 L3 L3 L3 R3 MF1 Fan motor (Radiator panel)
50/60Hz ~-
DCL Gate amp board 21S4a,4b 4-way valve TH9a LEV1 temp.detect(Enttance area)
N N N N N N
Y-C (G/A board)
PE board SV1,22,32 Solenoid valve TH9b Composition sensing temp.
4,6 TH10a Gas pipe temp.
600VAC BOX BODY CNE CNDC1 CNDR1 CN15V1 (Hex outlet)
PE BOX BODY F5 8A F (2P) (4P) (9P) (14P) Solenoid valve TH10b
L1 BOX BODY 12 1234 123456789 1 2 3 4 5 6 7 8 9 1011 12 1314 SV5,6,7,8
TB3 F6 600VAC L2 SNB board (Heat exchanger capacity control) TH10c Compressor shell temp.
8A F EARTH
Connect to M1 L3
Indoor and SLEV Electronic expansion valve(Oil return) THHS Radiator panel temp. detect
M2 F3 FB3
remote 250VAC
controller 1A F BOX BODY LEV1 Electronic expansion valve(SC coil) LD Accumulator liquid level detect
BOX BODY CNTR1
M1 63HS High pressure sensor CH11,12 Crank case heater(Compressor)
M2 BOX BODY 63LS Low pressure sensor CH2,3 Cord heater
T01
S
FB4 63H1,2 High pressure switch SSR Solid state relay
TB7 1 1 L2 Choke coil(Transmission) X1,2,4~12 Aux. relay
123 12 1 2 3
CN20 1 2 3 2 2 5 4 3 2 1 CNAC2 1 2 3 4 123456789 1 2 3 4 5 6 7 8 9 10 11 12 13 14
(3P) CNRS3 3 3 (5P)
CNS2 CNS1 CNTR 4 4 CNRS2 CNVDC CNDR2 CN15V2
5 5
PUHY-P400, 500YEM-A(-BF, -BS)

(3P) (2P) F1 (3P) (7P) 6 6 (7P) (4P) (9P) (14P) IPM Intelligent power module FB1~5 Ferrite core
250VAC 7 7 F01
2A F 1CNVCC4 250VAC T1~10 Terminal
4 CNVCC4 12 Earth terminal
B 3 (2P) 2(2P) 2A F
2 CNAC3
(4P) 1 1
1 2 2 CNVCC2 Power circuit board
A CNVCC343 3 1
CH11 3 (6P) 5 4 (6P)
5
(INV board) CNACCT 2
Crank case heater 6 6 (4P) 3 <Difference of appliance>
2 CN32 4
1 (3P) X01
X101 1
(Compressor) Appliance Name NOTE:Mark indicates terminal bed
2 2 X01 ✻
3 PUHY-400YEM " 1" is not existed connector
SV1 2 CN33 3 52C1 3 CNTH CNR CNL2 CN30V
1 (3P) X02 CNX10 X02 PUHY-500YEM All exists
CN52C (2P) (3P) (2P) (2P) ✻ ✻ ✻ board insertion connector
T10 (3P) (3P) 1 23 CNFAN 1 2 1 2 3 1 2 12 PUHY-400YEM " 1"," 2" and " 3" are not existed
✻ ✻
5. Electrical Wiring Diagram

SV22 6 (3P) PUHY-500YEM " 2" and " 3" are not existed
T9 5
21S4a 4 CN34
3 (6P) X04 MF1
SV32
2
1 X05 <Unit internal layout>
✻ BOX BODY THHS R7 L2 R6
1 SSR
CH2 3 4 3 SV8
1 2 12V 1 TH6
2 CN35 2
1 (3P) 3 A B SV5b 21S4b

1- 53
4 4:Compressor ON/OFF
5
CH3 Control circuit board 5:Trouble 21S4a
6 CN51 CN3D
X11 1
SV7 TH10b
5 (5P) MODE SV7 TH10a
(MAIN board) 1-2 1-3 X12 2
TH5TH8
SV4 21S4b 4 CN36 X06 ON Auto HEAT SV8
3 (6P) ✻3
2 OFF ON Changeover COLL 3 ACCUMULATOR
1 X07 CN3D 32 ON OFF TH2 TH9a
(3P) 1 OFF Normal 4
T7 TH9bTH7 LEV1 SV4 TH3
6 CN3S 32 5 SV6
5 (3P) 1 DEMAND MODE
4 CN3S 1-2 DEMAND SV1
SV6 SV5b CN37 X08 6 63LS 63H1
3 (6P) CN3N 32 SNOW NIGHT ✻3
2 CN3N 1-2 7 TH12
X09 (3P) 1 NIGHT 1-3 SNOW Inverter TH4 SV22
1
8 Controller 63HS MC1 MC2 MC2
High pressure L1 L2 L3 Box Oil separater TH12
CN38 TH11 ✻3
(3P) CN06 TH10c SLEV 63H2 SV32 63H2
switch 63H1
1
X10

2 2
3 detection CNPOW (Front) PUHY-(P)400 PUHY-(P)500
63H2 circuit (5P) 1 2 3 4 5
F03 250VAC 6.3A F
F02 250VAC 6.3A F <Controller box internal layout>
F01 250VAC 6.3A F (Underside)
board (Upside)
CN51C2Relay SW4-6 ✻2
51C2 (3P) 6 T6 6 THHS
1 as connection with R6
5 T5 1 CN04
95 96 2 ON 5
3 PUHN-(P)200/250 CNFC1 4 T4 CNFC2 2 1 RELAY T01 SNB DCL
4 CNFAN U
(6P) 3 T3 (6P) 3 2 X11 X12 board DS
3 (5P) V board
2 T2 4 3 +
OFF 2 W MF2 ZNR4
CN52C2 1 T1 1 5 4 N R2 C2
C1
A1 A2 (5P) X01 -
1
52C2 2 Refer to the service handbook Fan motor
52C2 3 Fan control board 52C2
INV board F5 +
14 13 4 X02
about the switch operations. (Fancon board) N
(Heat exchanger) R3 C3
5 FANCON MAIN board FANCON
CNRT2 - G/A board
CNRT1 51C2 F6
(5P) (5P) board board
CN52F 5 5 (for MF3) (for MF2)
4 4 L1 L2 L3 TB1B
A2 A1 (3P) F3
1 3 3 detection R1 IPM
52F 2 2 2 circuit
3 X03 1 1 R5
ACCT ACCT
CNPOW NF -U -W
(5P) 123 4 5 52F 52C1

F03 250VAC 6.3A F CN04 CN05 R7
2 F02 250VAC 6.3A F TB1A TB3 TB7 L2 MF1
CNOUT1 F01 250VAC 6.3A F
CNOUT2 X12 (6P)
CNCH 6
(3P) (4P) X11 5 52F <Operation of self-diagnosis switch(SW1)and LED display>
CH12 1 4 4 6
3
CN13 CN12 CN09 CN07 CN06 CN05 CN03 CN02 CN01 CNH CNL CNLV1 CNLV2 5 1 2 1 CN05 Display Display at LED lighting (blinking) Remarks SW1 operation
2 3 (4P) (2P) (2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (3P) (5P) (5P)
3 2 2 4 CNFC2 2 1 FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8
1234 12 12 12 12 1234 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 (6P) CNFAN 3 4 3 2 U
1 1 3 (5P) V Relay output During SV22/32 Always
T8 2 4 3 display Compres- 52C1 52C2 21S4a SV1 <LED display>
W MF3 ON:1 (Lighting) sor run
✻1
lighting
1 5 6 5 4 N FLAG8 always
5 OFF:0 Check display1 Display the address and error code by turns LD1
12345678910 lights at
6 Fan motor (at factory shipment) (Blinking) microcomputer
Fan control board (Heat exchanger) power ON
(Fancon board) FLAG1 FLAG8
N FLAG2 FLAG7
LEV1 SV5b is closed
ON:1 FLAG3 FLAG6

White
Red
White
Red

Black
Black
OFF:012345678910 SV4 21S4b SV5b SV6 CH2,3 52F when FLAG3 is FLAG4 FLAG5
turned ON.
3 2 1 3 2 1 SLEV ✻
TH10a TH10b TH9b TH10c TH12 TH9a TH4 TH3 TH6 TH5 TH8 TH7 TH2 TH11 Please refer to the service handbook about other switch settings of LED display.
63HS 63LS
✻ ✻
3 3

Big Y(R407C)
Big Y(R407C)

❇ There are SV22,SV32 only for PUHY-P500.

21S4b

21S4a BV1
TH10a
ST1
HEXB1 HEXF1 CJ1
63HS SV4

ST5

SV6 CJ2
TH10b O/S
CP1
SV7
ST6
CP7
✻ SV1
CP3a SV22 SV32
TH6 HEXF2 TH11
HEXB2 CP3b
TH12 63LS
CV1 CV2
MA

1- 54
63H1 Comp1 63H2 SA
Comp2
SLEV CJ3
TH10c
ST9
CP4
SV8 TH4
Drier TH9b
ST10 CP2 ST4 TH3 ST3
TH2 ✻
ST8
SV5b
TH5 TH8 BV2

TH7 CP5 ST2


TH9a ST7
BV3
LEV1
CV3
6. Refrigerant Circuit Diagram And Thermal Sensor
PUHY-P600·650·700·750YSEM-A (-BF, -BS)

CONTENTS

1. Specifications ································································· 1-56

2. Capacity Tables ······························································ 1-60


2-1 Correction by temperature ············································ 1-60
2-2 Correction by total indoor ············································· 1-62
2-3 Correction by refrigerant piping length ··························· 1-64
2-4 Correction at frosting and defrosting ···························· 1-65
2-5 Operation limit ······························································· 1-65

3. Sound Levels ·································································· 1-66

4. External Dimensions ···················································· 1-68

5. Electrical Wiring Diagram ··········································· 1-71

Super Y(R407C)
6. Refrigerant Circuit Diagram ········································· 1-73
And Thermal Sensor

1- 55
1. Specifications
This unit consists of a conbination of PUHY-P400YEM-A(-BF, -BS) and PUHN-P200YEM-A(-BF, -BS).

PUHY-P600YSEM-A(-BF, -BS)
Model name
Cooling Heating
✻1 kW 67.4 75.0
Capacity
✻2 kcal/h 60,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 23.89 21.08

Current A 40.3/38.3/36.9 35.5/33.8/32.5

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz) 61.5 / 62

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 34.93

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(0˚CDB~43˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

Model name PUHY-P400YEM-A(-BF, -BS) PUHN-P200YEM-A(-BF, -BS)


Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1
Super Y(R407C)

Fan Airflow rate m /min


3
400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic
Compressor Motor output kW 7.5 + 4.5 5.5
Crankcase heater kW 0.045 + 0.045 0.056
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)
High pressure protection 2.94MPa
Protection Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection,

thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 440 248

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 56
This unit consists of a conbination of PUHY-P400YEM-A(-BF, -BS) and PUHN-P250YEM-A(-BF, -BS).

PUHY-P650YSEM-A(-BF, -BS)
Model name
Cooling Heating

✻1 kW 73.0 81.5
Capacity
✻2 kcal/h 65,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 25.71 23.04

Current A 43.4/41.2/39.7 38.8/36.9/35.6

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz) 62.0 / 62.5

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(0˚CDB~43˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

Model name PUHY-P400YEM-A(-BF, -BS) PUHN-P250YEM-A(-BF, -BS)


Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1

Super Y(R407C)
Fan Airflow rate m3/min 400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic
Compressor Motor output kW 7.5 + 4.5 7.5
Crankcase heater kW 0.045 + 0.045 0.056
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)
High pressure protection 2.94MPa
Protection Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection,

thermal switch

Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 440 263

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 57
This unit consists of a combination of PUHY-P500YEM-A(-BF, BS) and PUHN-P200YEM-A(-BF, BS).

PUHY-P700YSEM-A(-BF, -BS)
Model name
Cooling Heating
✻1 kW 78.4 88.0
Capacity
✻2 kcal/h 70,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 27.77 24.98

Current A 46.8/44.5/42.9 42.1/40.0/38.6

Refrigerant / Lubricant R407C/MEL32


External finish Pre-coated galvanized sheets (Powder coating)
<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level dB<A>


✻ (50/60Hz) 61.5 / 62.0

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(0˚CDB~43˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

Model name PUHY-P500YEM-A(-BF, -BS) PUHN-P200YEM-A(-BF, -BS)


Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1
Super Y(R407C)

Fan Airflow rate m3/min 400 200


Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic
Compressor Motor output kW 7.5 + 7.5 5.5
Crankcase heater kW 0.045 + 0.056 0.056

External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)


High pressure protection 2.94MPa

Protection Compressor / Fan Overcurrent protection / Thermal switch


devices
Inverter AC bus current protection,

thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 475 248

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 58
This unit consists of a conbination of PUHY-P500YEM-A(-BF, -BS) and PUHN-P250YEM-A(-BF, -BS).

PUHY-P750YSEM-A(-BF, -BS)
Model name
Cooling Heating
✻1 kW 84.0 94.5
Capacity
✻2 kcal/h 75,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 29.59 26.94


Current A 49.9/47.4/45.7 45.4/43.2/41.6
Refrigerant / Lubricant R407C/MEL32
External finish Pre-coated galvanized sheets (Powder coating)
<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz) 62.0 / 62.5

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
(0˚CDB~43˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

PUHY-P500YEM-A(-BF, -BS) PUHN-P250YEM-A(-BF, -BS)

Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1

Super Y(R407C)
Fan Airflow rate m3/min 400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic
Compressor Motor output kW 7.5 + 7.5 7.5
Crankcase heater kW 0.045 + 0.056 0.056
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)
High pressure protection 2.94MPa

Protection Compressor / Fan Overcurrent protection / Thermal switch


devices
AC bus current protection,
Inverter —
thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 475 263

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 59
2. Capacity Tables
2-1. Correction by temperature
Cooling
•Standard Specifications

PUHY-P600 PUHY-P650 PUHY-P700 PUHY-P750


Capacity kW 67.4 73.0 78.4 84.0
Input kW 23.89 25.71 27.77 29.59

Capacity at 100% indoor units running


1.30

1.20

1.10
24˚CWB
Ratio

22˚CWB
1.00 20˚CWB

18˚CWB
0.90 16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)
Super Y(R407C)

Power Input at 100% indoor units running


1.30 24˚CWB
22˚CWB
1.20 20˚CWB
18˚CWB
16˚CWB
1.10 15˚CWB
Indoor Temperature(˚CWB)
1.00

0.90
Ratio

0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 60
Heating
•Standard Specifications

PUHY-P600 PUHY-P650 PUHY-P700 PUHY-P750


Capacity kW 75.0 81.5 88.0 94.5
Input kW 21.08 23.04 24.98 26.94

Capacity at 100% indoor units running


1.30

1.20
15˚CDB
1.10 Indoor Temperature(˚CDB)

20˚CDB
1.00
Ratio

0.90
25˚CDB
0.80
27˚CDB

0.70

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Super Y(R407C)
Power Input at 100% indoor units running
1.10

Indoor Temperature(˚CDB)
1.00

15˚CDB
0.90
Ratio

0.80
20˚CDB

0.70
25˚CDB
0.60
27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 61
2-2. Correction by total indoor

PUHY-P600
1) Capacity
80
Heating
70
Cooling
Capacity(kW)

60

50

40

30
300 350 400 450 500 550 600 650 700 750
Total capacity of indoor units
2) Input
30.0

Cooling
25.0
Input(kW)

20.0
Heating

15.0

10.0
300 350 400 450 500 550 600 650 700 750
Total capacity of indoor units
PUHY-P650
Super Y(R407C)

1) Capacity
90

80 Heating

70
Capacity(kW)

Cooling
60

50

40

30
300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units
2) Input
30.0
Cooling

25.0
Input(kW)

Heating
20.0

15.0

10.0
300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units

1- 62
PUHY-P700
1) Capacity
100
Heating
90

80
Capacity(kW)

70 Cooling

60

50

40

30
350 400 450 500 550 600 650 700 750 800 850 900
Total capacity of indoor units
2) Input
35.0
Cooling
30.0
Input(kW)

25.0
Heating
20.0

15.0

10.0
350 400 450 500 550 600 650 700 750 800 850 900

Total capacity of indoor units

Super Y(R407C)
PUHY-P750
1) Capacity
100

90
Heating
80
Capacity(kW)

Cooling

70

60

50

40
350 400 450 500 550 600 650 700 750 800 850 900 950
Total capacity of indoor units
2) Input
35.0
Cooling
30.0

25.0
Input(kW)

Heating

20.0

15.0

10.0
350 400 450 500 550 600 650 700 750 800 850 900 950
Total capacity of indoor units

1- 63
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction

PUHY-P600 PUHY-P650
1.0 1.0 Total capa
Total ca city of in
pacity door unit
of indo
Cooling capacity

Cooling capacity
correction factor

correction factor
or unit 325
0.9 300 0.9 488
450 650

8.0 600 8.0 845

780
7.0 7.0

0 20 40 60 80 100 120 0 20 40 60 80 100 120


Piping equivalent length (m) Piping equivalent length (m)

PUHY-P700 PUHY-P750
1.0 Total ca 1.0 Total ca
pacity o pacity
f indoor of indo
unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor

350 375
0.9 525 0.9
563
700 750

8.0 910 8.0 975

7.0 7.0

0 20 40 60 80 100 120 0 20 40 60 80 100 120


Piping equivalent length (m) Piping equivalent length (m)
Super Y(R407C)

•Heating capacity correction

PUHY-P600·650·700·750
Cooling capacity
correction factor

1.0

0.9

0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PUHY-P600
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 ✕ number of bent on the piping)m
➁ PUHY-P650 - 750
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.95 ✕ number of bent on the piping)m

1- 64
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Outdoor inlet air temp


(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.89 0.90 0.92 0.95 0.95 0.95

2-5. Operation limit

• Cooling
30
Indoor temperature (˚CWB)

25
When the indoor unit is located above
the outdoor unit for 4m or more, the
20
outdoor unit inlet air temperature
becomes 0~43˚CDB.
15

10
-5 0 5 10 15 20 25 30 35 40 45
Outdoor temperature (˚CDB)

• Heating

Super Y(R407C)
30
Indoor temperature (˚CDB)

25
When the indoor unit 20 or 25type only is
20 working, the outdoor unit inlet air
temperature becomes -12~10˚CWB.
15

10
-15 -10 -5 0 5 10 15 20
Outdoor temperature (˚CWB)

1- 65
3. Sound Levels

PUHY-P600
Measurement condition
50Hz 60Hz

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
70

60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
61.5 / 62.0 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
Super Y(R407C)

PUHY-P650
Measurement condition
50Hz 60Hz

1m
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70

60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
62.0 / 62.5 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 66
PUHY-P700
Measurement condition
50Hz 60Hz

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
70

60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
61.5 / 62.0 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

Super Y(R407C)
PUHY-P750
Measurement condition 50Hz 60Hz
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m
70

60
NC60
1m

50
NC50

Sound pressure level in anechoic room 40


NC40
62.0 / 62.5 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 67
Super Y(R407C)

<Accessorys>

15
• Refrigerant (gas) conn. pipe ················· 1pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. pipe ·························· 1pc. Refrig.service
(Attached near the ball valve) valve (liquid) Refrig. service
valve(gas)
• Conduit mouting plate Service valve ø15.88<flare> <flange>
(Painted the same color as the unit body) (oil balance)
ø62,ø53,ø46 ·································· Each 1pc. ø12.7<flare>
840
910

• Tapping screw 4X10 ····························· 6pcs. Conn. pipe


ø27 Knockout hole ø34.93 <brazed>
• Wiring partition plate ····························· 1pc. <bottom hole for the
control wiring>
880(bolt hole)

Note1. Please leave a space under the outdoor unit


for the piping when you connect the piping

90 80
169

203
152
from the bottom.

111
(Please be careful not to close the hole

73
of the bottom plate by the basement) 3X2-14X20 oval hole
15

230 150 Note.1 215 780(bolt hole) 780(bolt hole) 215


PUHY-P400, 500YEM-A(-BF, -BS)

694 80 82 78 Knockout hole


Bottom piping hole 1990
Bottom hole for the power supply
4. External Dimensions

Changeable to 400:ø46,ø53,ø62 Cross section X-X Plane view


500:ø53,ø62 by using attached
conduit mounting plate (accessory) Air outlet
265

1- 68
Air
inlet

Air
1755

inlet
1490

X Knockout hole X
Service valve
(oil balance)
Refrig. service
745 25 90 75 valve(gas)
100 Service panel
24
149 70

126
86

Knockout hole
48

80 40
70

Left side hole for 218 Knockout hole


the control wiring, Front piping hole
the power supply, the 725 115
Front hole for the power supply Refrig.service
oil balance pipe to the Changeable to 400:ø46,ø53,ø62 45 valve (liquid)
constant capacity unit 500:ø53,ø62 by using attached
conduit mounting plate (accessory)
Rear view Left side view Front view
Unit : mm
<Accessorys>

15
• Refrigerant (gas) conn. pipe···························1pc.
Note.1 (The connecting pipe has been fixed with the unit)
ø27 Knockout hole Y ø40 Knockout hole • Packing for conn. pipe····································1pc.
12 5 Bottom piping hole Bottom hole for the power supply
(oil balance) Changeable to ø27,ø33 by using (Attached near the ball valve)
attached conduit mounting plate • Conduit mouting plate
Y (accessory)
(Painted the same color as the unit body)
Note.1 ø40,ø33,ø27····················································Each 1pc.

840
910
Knockout hole ø27 Knockout hole
<bottom hole for the • Tapping screw 4✕12·······································4pcs.
Bottom piping hole

600
control wiring> • Oil balance conn. pipe (to the variable capacity unit

880(bolt hole)

50
through the right side panel knockout hole)·········1pc.
• Sealing···························································2pcs.

237
168
130
121

73 80
Note1. Please leave a space under the outdoor unit
25 160 2X2-14X20
for the piping when you connect the piping

15
778 75 135 oval hole 215 560(bolt hole) 215
Conn. pipe 584 from the bottom.
ø28.58<brazed> 990 (Please be careful not to close the hole
PUHN-P200, 250YEM-A(-BF, -BS)

of the bottom plate by the basement)


Cross section Y-Y Cross section X-X Plane view
Air outlet

265

1- 69
Air
inlet
1490

Air
1755

Knockout hole
Front piping hole Service valve inlet
(oil balance) (oil balance)
ø12.7<flare>
Refrig.service
valve (liquid) Service panel
ø12.7<flare>
X X
Knockout hole
Front piping hole
Knockout hole

40
115

100
99

149
142

78

70
Knockout hole

48
79 80 425
48

Right side hole for


80 40 813 40 80 the control wiring,
Knockout hole Refrig. service
Left side hole for refrig. Front hole for the power supply the power supply,
valve(gas) 55 the oil balance pipe to
(liquid,gas) conn. pipe <flange> 31 165 190 345 55 Changeable to ø27,ø33,ø40
Unit : mm

by using attached conduit the variable capacity unit


mounting plate (accessory)

Rear view Left side view Front view Right side view

Super Y(R407C)
Super Y(R407C)

990 10 1990 910


840

Constant capacity unit Variable capacity unit Air outlet

Air
inlet
Air
inlet
PUHY-P600,650,700,750YSEM-A(-BF, -BS)

Note 1.Please install the constant capacity unit

1- 70
and the variable capacity unit on a same
level stand.
2.Pipe size is as follws.
d 3.Please install the constant capacity unit
g
and the variable capacity unit side by side,
Note.1 the constant capacity unit on the left side
and the variable capacity unit on the right
c side.
e
Front view Right side view 4.Distributor kit(Accessory) is needed to compose
PUHY-(P)600~750YSEM-A(-BF,-BS)
f Distributor
(gas) ❇3
Oil balance pipe
❇3 Distributor 600 650 700 750
a b
(liquid) ❇3 Indoor units ~ liquid a ø19.05
Distributor gas b ø34.93 ø41.28
Indoor units
Distributor ~ liquid c ø15.88
Variable capacity unit gas d ø34.93 ❇1 ❇1 This pipe has been fixed.
❇2 The oil balance pipe is usually
Distributor ~ liquid e ø12.7
fixed inside of the unit.
Constant capacity unit gas f ø28.58 ❇3 Accessory
Oil balance pipe g ø12.7 ❇2
Unit : mm
MC2 Motor MC1 Motor
<ELECTRICAL WIRING DIAGRAM> U V W (Compressor) U VW (Compressor) <Symbol explanation>
Red White Black Red White Black Symbol Name Symbol Name
Inverter
Controller Box DC reactor TH11,12 Thermistor Discharge pipe temp. detect
DCL (Power factor improvement) TH2 Saturation evapo. temp. detect
FB1 FB2
51C2 52C2 TH3
2 1 2 1 ACCT-U,W Current Sensor Accumurator liquid Lower
4 3 4 3 ACCT ZNR4 Varistor TH4 temp. detect Upper
6 5 6 5 -W
Magnetic contactor TH5 Pipe temp. detect(Hex outlet)
ACCT 52C1
Terminal -U (Inverter main circuit) TH6 OA temp. detect
Terminal Noise Diode
Block
Block L1 L2 L3 N stack 52C2 Magnetic contactor SC coil temp.detect
NF Filter R1 R5 IPM
TB1A TB1B FB5 DS TH7
L1 L1 L1 L1 L1 ZNR4 51C2 Overload relay (Liquid exit area)
~+ U V W
+
Power source L2 L2 L2 L2 L2 C1 C2 R2 52F Magnetic contactor(Fan motor) SC coil temp.detect
3N~ ~ P
52C1 C3+
TH8 (Bypass exit area)
380/400/415V L3 L3 L3 L3 L3 R3 MF1 Fan motor (Radiator panel)
50/60Hz ~-
DCL Gate amp board 21S4a,4b 4-way valve TH9a LEV1 temp.detect(Enttance area)
N N N N N N
Y-C (G/A board)
PE board SV1,22,32 Solenoid valve TH9b Composition sensing temp.
4,6 TH10a Gas pipe temp.
600VAC BOX BODY CNE CNDC1 CNDR1 CN15V1 (Hex outlet)
PE BOX BODY F5 8A F (2P) (4P) (9P) (14P) Solenoid valve TH10b
L1 BOX BODY 12 1234 123456789 1 2 3 4 5 6 7 8 9 1011 12 1314 SV5,6,7,8
TB3 F6 600VAC L2 SNB board (Heat exchanger capacity control) TH10c Compressor shell temp.
8A F EARTH
Connect to M1 L3
Indoor and SLEV Electronic expansion valve(Oil return) THHS Radiator panel temp. detect
M2 F3 FB3
remote 250VAC
controller 1A F BOX BODY LEV1 Electronic expansion valve(SC coil) LD Accumulator liquid level detect
BOX BODY CNTR1
M1 63HS High pressure sensor CH11,12 Crank case heater(Compressor)
M2 BOX BODY 63LS Low pressure sensor CH2,3 Cord heater
T01
S
FB4 63H1,2 High pressure switch SSR Solid state relay
TB7 1 1 L2 Choke coil(Transmission) X1,2,4~12 Aux. relay
123 12 1 2 3
CN20 1 2 3 2 2 5 4 3 2 1 CNAC2 1 2 3 4 123456789 1 2 3 4 5 6 7 8 9 10 11 12 13 14
(3P) CNRS3 3 3 (5P)
CNS2 CNS1 CNTR 4 4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) F1 (7P) 5 5 (4P) (9P) IPM Intelligent power module FB1~5 Ferrite core
(3P) 6 6 (7P) (14P)
250VAC 7 7 F01
2A F 1CNVCC4 250VAC T1~10 Terminal
4 CNVCC4 12 Earth terminal
B 3 (2P) 2(2P) 2A F
2 CNAC3
(4P) 1 1
1 2 2 CNVCC2 Power circuit board 1
PUHY-P400·500YEM-A(-BF, -BS)

A CNVCC33 3
CH11 3 (6P) 45 4 (6P)
5
(INV board) CNACCT 2
Crank case heater 6 6 (4P) 3 <Difference of appliance>
2 CN32 4
1 (3P) X01
X101 1
(Compressor) Appliance Name NOTE:Mark indicates terminal bed
2 2 X01 ✻
3 PUHY-400YEM " 1" is not existed connector
SV1 2 CN33 3 52C1 3 CNTH CNR CNL2 CN30V
1 (3P) X02 CNX10 X02 PUHY-500YEM All exists
CN52C (2P) (3P) (2P) (2P) ✻ ✻ ✻ board insertion connector
T10 (3P) (3P) 1 23 CNFAN 1 2 1 2 3 1 2 12 PUHY-400YEM " 1"," 2" and " 3" are not existed
✻ ✻
SV22 6 (3P) PUHY-500YEM " 2" and " 3" are not existed
T9 5
21S4a 4 CN34
3 (6P) X04 MF1
SV32
2
1 X05 <Unit internal layout>
✻ BOX BODY THHS R7 L2 R6
1 SSR
5. Electrical Wiring Diagram

CH2 3 4 3 SV8
1 2 12V 1 TH6
2 CN35 2
1 (3P) 3 A B SV5b
4 4:Compressor ON/OFF 21S4b
5
CH3 Control circuit board 5:Trouble 21S4a
6 CN51 CN3D
X11 1
SV7 TH10b
5 (5P) MODE SV7 TH10a
(MAIN board) 1-2 1-3 X12 2
TH5TH8
SV4 21S4b 4 CN36 X06 ON Auto HEAT SV8
3 (6P) ✻3
2 OFF ON Changeover COLL 3 ACCUMULATOR
X07

1- 71
1 CN3D 23 ON OFF TH2 TH9a
(3P) 1 OFF Normal 4
T7 TH9bTH7 LEV1 SV4 TH3
6 CN3S 32 5 SV6
5 (3P) 1 DEMAND MODE
4 CN3S 1-2 DEMAND SV1
SV6 SV5b CN37 X08 6 63LS 63H1
3 (6P) CN3N 32 SNOW 1-2 NIGHT ✻3
2 7 TH12
X09 (3P) 1 NIGHT
CN3N 1-3 SNOW Inverter TH4 SV22
1
8 Controller 63HS MC1 MC2 MC2
High pressure L1 L2 L3 Box Oil separater TH12
CN38 TH11 ✻3
(3P) CN06 TH10c SLEV 63H2 SV32 63H2
switch 63H1
1
X10

2 2
3 detection CNPOW (Front) PUHY-(P)400 PUHY-(P)500
63H2 circuit (5P) 1 2 3 4 5
F03 250VAC 6.3A F
F02 250VAC 6.3A F <Controller box internal layout>
F01 250VAC 6.3A F (Underside)
board (Upside)
CN51C2Relay SW4-6 ✻2
51C2 (3P) 6 T6 6 THHS
1 as connection with R6
5 T5 1 CN04
95 96 2 ON 5
3 PUHN-(P)200/250 CNFC1 4 T4 CNFC2 2 1 RELAY T01 SNB DCL
4 CNFAN U
(6P) 3 T3 (6P) 3 2 X11 X12 board DS
3 (5P) V board
2 T2 4 3 +
OFF 2 W MF2 ZNR4
CN52C2 1 T1 1 5 4 N R2 C2
C1
A1 A2 (5P) X01 -
1
52C2 2 Refer to the service handbook Fan motor
52C2 3 Fan control board 52C2
INV board F5 +
14 13 4 X02
about the switch operations. (Fancon board) N
(Heat exchanger) R3 C3
5 FANCON MAIN board FANCON
CNRT2 - G/A board
CNRT1 51C2 F6
(5P) (5P) board board
CN52F 5 5 (for MF3) (for MF2)
4 4 L1 L2 L3 TB1B
A2 A1 (3P) F3
1 3 3 detection R1 IPM
52F 2 2 2 circuit
3 X03 1 1 R5
ACCT ACCT
CNPOW NF -U -W
(5P) 123 4 5 52F 52C1

F03 250VAC 6.3A F CN04 CN05 R7
2 F02 250VAC 6.3A F TB1A TB3 TB7 L2 MF1
CNOUT1 F01 250VAC 6.3A F
CNOUT2 X12 (6P)
CNCH 6
(3P) (4P) X11 5 52F <Operation of self-diagnosis switch(SW1)and LED display>
CH12 1 4 4 6
3
CN13 CN12 CN09 CN07 CN06 CN05 CN03 CN02 CN01 CNH CNL CNLV1 CNLV2 5 1 2 1 CN05 Display Display at LED lighting (blinking) Remarks SW1 operation
2 3 (4P) (2P) (2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (3P) (5P) (5P)
3 2 2 4 CNFC2 2 1 FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8
1234 12 12 12 12 1234 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 (6P) CNFAN 3 4 3 2 U
1 1 3 (5P) V Relay output During SV22/32 Always
T8 2 4 3 display Compres- 52C1 52C2 21S4a SV1 <LED display>
W MF3 ON:1 (Lighting) sor run
✻1
lighting
1 5 6 5 4 N FLAG8 always
5 OFF:0 Check display1 Display the address and error code by turns LD1
12345678910 lights at
6 Fan motor (at factory shipment) (Blinking) microcomputer
Fan control board (Heat exchanger) power ON
(Fancon board) FLAG1 FLAG8
N FLAG2 FLAG7
LEV1 SV5b is closed
ON:1 FLAG3 FLAG6

White
Red
White
Red

Black
Black
OFF:012345678910 SV4 21S4b SV5b SV6 CH2,3 52F when FLAG3 is FLAG4 FLAG5
turned ON.
3 2 1 3 2 1 SLEV ✻
TH10a TH10b TH9b TH10c TH12 TH9a TH4 TH3 TH6 TH5 TH8 TH7 TH2 TH11 Please refer to the service handbook about other switch settings of LED display.
63HS 63LS
✻ ✻
3 3

Super Y(R407C)
Super Y(R407C)

Controller Box

TB1 51C1 52C1


L1 L1 Red 2 1 2 1 Red Motor (Compressor)

Power source U
3N~ L2 L2 White 4 3 4 3 White
V MC1
380/400/415V W
50Hz/60Hz L3 L3 Black 6 5 6 5 Black

N N Blue Model 200:24A SYMBOL NAME SYMBOL NAME


Model 250:27A ZNR01 TH3
VARISTOR THERMISTER
PE
SSR SOLID STATE RELAY TH4 THERMISTER
F1 FUSE(6.3A) <CONT BOARD> TH5 THERMISTER
PE Box body
F1,F2 FUSE(8A) TH6 THERMISTER
Box body
TB3 F3 FUSE(1A) TH7 THERMISTER
M1 52C1 MAGNET CONTACTOR TH8 THERMISTER
Inverter F3 L3 L2 L1
unit M2 250VAC
1A F 51C1 OVER CURRENT RELAY TH9 THERMISTER
S F2 F1 MC1 ELECTRIC MOTOR OF COMPRESSOR TH10a THERMISTER
T01 600VAC 600VAC
8A F 8A F MF FAN MOTOR(HEAT EXCHANGER) TH10b THERMISTER
CN20
(3P) CH11 CRANK CASE HEATER(COMPRESSOR) LEV1 ELECTRONIC EXPANSION VALVE
1 2 1 2 3 1 2
CNS1 CNTR CH2,CH3 CORD HEATER LEV2 ELECTRONIC EXPANSION VALVE
(2P) F1 (2P)
250VAC
6 6.3A F 21S4 4-WAY VALVE X01~X07 RELAY
21 5 NF SV1,SV4 SW2,SW3
4 ZNR01 L3 L2 L1 SOLENOID VALVE SWITCH
S4 X01 Noise
SV1 3
PUHN-P200·250YEM-A(-BF, -BS)

2 CN33 Filter SV5b SOLENOID VALVE SWU1,2 SWITCH


X02
1 (6P)
SV2,SV3 SOLENOID VALVE TB1 POWER SOURCE TERMINAL BLOCK
T1 X03
3 63H HIGH PRESSURE CUT OUT SWITCH EARTH TERMINAL
SV3 2 CN39 Control circuit board Box body
SV2 1 (3P) L3 L2 L1 SCRM 63LS LOW SIDE PRESSURE SENSOR T1,T2 TERMINAL
T2
(CONT board)
UG1 UK1
UK2 UG2 TH11 THERMISTER
6
SV 5 G K Red

Red
5b 4 CN34 L1 U

Black
White
X04 K G

1- 72
SV4 3 (6P) VK1
2 VG1 CNMF <Difference of appliance>
1 X05 1
G K 2 U
L2 V 3 V Appliance Difference
SSR01 K G W MF
CH2 4 3 VK2 N
1 PUHN-P200·250YEM-A(-BS,-BF) ALL exists
1 2 VG2
2 CN35 CN04 Fan motor
CH3 3 (3P) G K (Heat exchanger)
SW3-10 are OFF for Model 200. L3 W Black
K G
CN38 and ON for Model 250.
(3P)
63H 1 WG1 WK1
2 WK2 WG2
3 Detection
circuit
CN46
51C (3P) 1
2
3 Detection
circuit Fan control board
CH11 3 (Fancon board) 1 UK1
2 CNCH11
1 1 2 UG1
1 (3P) X06 CNFC1 2 2 CNFC2 CNU 3
(6P) 3 3 (6P) (5P) 4
4 4 UK2
5 5 CNW CNV 5 UG2
A2 6 6 (5P)
52 5 (5P)
C1 4 CN52C1 5 4 3 2 1 5 4 3 2 1
A1 52C1
13 14 3 (5P)
2
1 X07
CN12 CN09 CN06 CN05 CN03 CN02 CN01 CNL CNLV1 CNLV2
(2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (5P) (6P)

WG2
WK2
WG1
WK1
VG2
VK2
VG1
VK1

12 12 12 1234 123 12345678 12 1 2 3 12345 123456

White
Red

Black
3 2 1 LEV1 LEV2
TH10b TH10a TH9 TH4 TH3 TH6 TH5 TH8 TH7 TH11
63LS
21S4b ❇ There are SV22,SV32 only for PUHY-P700, 750.
21S4a BV1
TH10a
HEXB1 HEXF1 ST1
CJ1
63HS SV4

ST5
SV6 CJ2
Distributor
TH10b O/S
CP1
ST6
SV7
✻ SV1 SV22 SV32
TH6 CP3a
HEXF2 TH11 CP3b
TH12 63LS
CV1 CV2
MA
63H1 Comp1 63H2 SA
Comp2
HEXB2 SLEV CJ3
TH10c
ST9
CP4
SV8 Drier TH9b TH4
ST10 CP2 ST4 TH3 ST3
TH2 ✻
ST8
SV5b
TH5 TH8 BV2

TH9a ST7 TH7 CP5 ST2


BV3
LEV1
CV3

1- 73
21S4 BV1

ST1
CJ1
ST5 SV4

CV1

CJ2
O/S
CP1
TH10a ST6
SV1 CP3
SV2 SV3
TH11
MA
TH6
63H SA
Comp1
TH3 63LS

HEX1 HEX2 ST3


CP4
6. Refrigerant Circuit Diagram And Thermal Sensor

TH4
ST4
Distributor
TH8 ST10 ST8 CV2 BV2
TH5
ST9

TH7 SV5b CP5 ST2


TH9 ST7
LEV2 BV3
LEV1

TH10b

Super Y(R407C)
Super Y(R407C)

1- 74
PURY-P200·250YEM-A(-BF, -BS)
CONTENTS

1. Specifications ································································· 1-76

2. Capacity Tables ······························································ 1-78


2-1 Correction by temperature ············································ 1-78
2-2 Correction by total indoor ············································· 1-80
2-3 Correction by refrigerant piping length ··························· 1-81
2-4 Correction at frosting and defrosting ···························· 1-82
2-5 Operation limit ······························································· 1-82

3. Sound Levels ·································································· 1-83

4. External Dimensions ···················································· 1-84

5. Electrical Wiring Diagram ·············································· 1-85

6. Refrigerant Circuit Diagram ········································· 1-86


And Thermal Sensor

R2(R407C)

1- 75
1. Specifications

PURY-P200YEM-A(-BF, -BS)
Model name
Cooling Heating

✻1 kW 22.4 25.0
Capacity
✻2 kcal/h 20,000 –

Power source 3N~380/400/415V 50/60Hz

Power input kW 6.32 6.80

Current A 10.6/10.1/9.7 11.4/10.9/10.5

Type✕ Quantity Propeller fan✕1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 5.3

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 25.4 (Flange)

Total capacity 50~150% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20~250 / 1~15
R2(R407C)

Noise level ✻ dB<A> 56

Net weight kg 238

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Matters Deserving Special Mention A pipe of ø 28.58 can be used for the low pressure pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 76
PURY-P250YEM-A(-BF, -BS)
Model name
Cooling Heating

✻1 kW 28.0 31.5
Capacity
✻2 kcal/h 25,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 8.54 8.95

Current A 14.4/13.6/13.2 15.1/14.3/13.8

Type✕ Quantity Propeller fan✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 6.8

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 990(W)✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 150% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

R2(R407C)
Noise level ✻ dB<A> 57

Net weight kg 238

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 77
2. Capacity Tables
2-1. Correction by temperature
Cooling
• Standard Specifications
PURY-P200 PURY-P250
Capacity kW 22.4 28.0
Input kW 6.32 8.54

Capacity at 100% indoor units running


1.30

1.20

1.10 24˚CWB
Ratio

22˚CWB
20˚CWB
1.00
19˚CWB
18˚CWB

0.90 16˚CWB

Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30
24˚CWB

1.20 22˚CWB
20˚CWB
1.10 19˚CWB
Indoor Temperature(˚CWB)
R2(R407C)

18˚CWB
1.00
16˚CWB
0.90
Ratio

15˚CWB

0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 78
Heating
• Standard Specifications
PURY-P200 PURY-P250
Capacity kW 25.0 31.5
Input kW 6.80 8.95

Capacity at 100% indoor units running


1.30
15˚CDB
1.20

1.10
20˚CDB
1.00
Ratio

Indoor Temperature(˚CDB)
0.90

0.80 25˚CDB

0.70 27˚CDB

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10
Indoor Temperature(˚CDB)

1.00 15˚CDB

R2(R407C)
0.90
20˚CDB
Ratio

0.80

0.70
25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 79
2-2. Correction by total indoor

PURY-P200
1) Capacity
30.0

25.0
Capacity(kW)

Heating

20.0 Cooling

15.0

10.0

5.0
100 150 200 250 300
2) Input Total capacity of indoor units

10.00
9.00
8.00
Input(kW)

7.00 Heating
6.00
5.00
Cooling
4.00
3.00
2.00
1.00
100 150 200 250 300
Total capacity of indoor units
PURY-P250
1) Capacity
35.0

30.0 Heating
Capacity(kW)

25.0 Cooling
R2(R407C)

20.0

15.0

10.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
12.00
11.00
10.00 Cooling
Input(kW)

9.00
8.00
7.00 Heating
6.00
5.00
4.00
3.00
100 150 200 250 300 350 400
Total capacity of indoor units

1- 80
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PURY-P200 PURY-P250
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor
100 125
0.9 0.9
150 188
200 250
0.8 0.8
300 375

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PURY-P200 PURY-P250
1.0 Total capacity 1.0 Total capacity
of indoor unit of indoor unit
100 125
Heating capacity

Heating capacity
correction factor

correction factor

0.9 150 0.9 188

200 or more 250 or more


0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PURY-P200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PURY-P250

R2(R407C)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m

1- 81
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25

20

15
R2(R407C)

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

❇ Outdoor temperature : -5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB in cooling/heating mixed mode.

1- 82
3. Sound Levels
PURY-P200
Measurement condition Cooling Heating

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


90

1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

56 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES(Hz)

PURY-P250
Measurement condition Cooling Heating
OCTAVE BAND PRESSURE LEVEL(dB) 0dB = 20µPa

90
1m

80

R2(R407C)
70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

57 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES(Hz)

1- 83
R2(R407C)

<Accessory>
• Refrigerant (gas) conn. pipe ···· 1pc.

(15)
(The connecting pipe is fixed with the unit)
12 5 Y • Packing for conn. pipe ········1pc.
ø40 Knockout hole
<Bottom side hole for (Attached near the ball valve)
the power supply> • Wiring mounting board
Note1 Y • Conduit mounting plate
Knockout hole ø27 Knockout hole (Painted the same color as the unit body)

840
910
Bottom piping hole <Bottom side hole for ø40··························1pc.
<Bottom wiring hole> the control wiring>

50
ø33··························1pc.

880(bolt hole)
2✕2-14✕20 ø27··························1pc.
Oval hole • Tapping screw 4 ✕ 10················ 6pcs.

262
237
Note1.Please leave a space under the outdoor unit

121

73 80
for the piping When , you connect the piping
25 160

15
Conn. pipe 778 75 215 560(bolt hole) (215) from the bottom.
200:ø25.4<brazed> 990 (Please be careful not to close the hole
Crosss section Y-Y 250:ø28.58<brazed> Cross section X-X of the bottom plate by the basement)
Plane view
PURY-P200,250YEM-A(-BF, -BS)
4. External Dimensions

Air outlet

1- 84
Air
inlet
1755

Air
Knockout hole inlet
1490

Refrig. service
valve (high pressure) Service panel
60 75 ø19.05<flare>
ø40 Knockout hole X X
<Left side hole for
the power supply>
14

100
194
149
99

110
78

48
ø27 Knockout hole Knockout hole
<Left side hole for Refrig. service 79 83 Front piping hole Knockout hole
80 40 valve(low pressure)
the control wiring> <Front wiring hole> <Front side hole for
Knockout hole <flange> 813 the power supply>
Left piping hole 31 165 590 55
Rear view Left side view Front view Right side view
Unit : mm
5. Electrical Wiring Diagram
PURY-P200, 250YEM-A(-BF, -BS)

Inverter MC1 Motor


(Compressor)
U V W
Controller Box
Red White Black
ACCT
-W
ACCT
Noise -U
Terminal Terminal Diode
Block NF Filter Block stack
TB1A TB1B
L1 L2 L3 N
DS R1 R5 IPM
L1 L1 Red L1 L1 Red L1 Red ZNR4 CNDC2
~+ (4P) U V W
+
C2 R2
Power source L2 L2 White L2 L2 White L2 White C1 C4 P 4
3N~ ~ 3
52C + 2
380/400/415V L3 DCL C3 R3 1
L3 Black L3 L3 Black L3 Black Gate amp board
50/60Hz ~-
1 2 3 4 (G/A board)
N N Blue N N Blue N Blue DCCT N
Green/
PE Yellow

BOX BODY BOX BODY


PE BOX BODY CNDC1 CNDR1 CN15V1
F3
TB3 250VAC (4P) (9P) (14P)
1A F 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Connect to M1
Indoor and M2
remote CNTR1
BOX BODY
controller

Orange

Orange
Yellow
BOX BODY

Purple
Brown

Brown

White
Black

Black
M1

Gray
T01

Red

Red
M2

Green

White
Blue
S CN20 1 1
123 12 1 2 3
(3P) 1 2 3 2 2 5 4 3 2 1 1 2 3 4 12 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
TB7 CNS2 CNS1 CNTR CNRS3 34 3
4 CNRS2 CNAC2I CNCT CNVDC CNDR2 CN15V2
(3P) (2P) F1 (3P) (7P) 5 5 (7P) (5P) (4P) (4P) (9P) (14P)
250VAC 6 6
2A T 7 7
F01 F02
CNVCC4 1 1 CNVCC4 250VAC 700VDC
(2P) 2 2 (2P) 2A T 2A T
CH1 3
Crank case heater 2 CN32 1
2
1
2
DC-DC
(Compressor) 1 (3P) X01 CNVCC3 3
4
3 CNVCC2
4 (6P)
Converter 1
(6P) CNCT2 2
5 5 (4P) 3
3 6 6
SV1 2 CN33 X10 4
1 (3P) X02 1 1 Power circuit board
2
3
2 X01 (INV board)
6 52C 3
CNX10
5 (3P) CN52CAC CNTH CNL2 CNFG
X02
21S4 4 CN34
X04 (3P) (2P) (2P) (2P)
3 (6P) 1 2 3 1 2 1 2 1 2
CNFAN
2 (3P)
1
12V 1
2
3
4
5 4:Compressor ON/OFF BOX BODY
5:Trouble MF1
CN51
(5P)
BOX BODY THHS L2
6
5

SV4 SV3 4 CN36


3 (6P)
X06
DEMAND
2 CN3D 32
1 X03 (3P) 1 NIGHT MODE
Control circuit board OR DEMAND

6 (MAIN board) CN3S 32


5 (3P) 1 SNOW

SV6 SV5 4 CN37


3 (6P)
X07
2
1 X08

L1 L2 L3

CNPOW
(5P) 1 2 3 4 5
CN38
X10 F03 250VAC 6.3A F
(3P) F02 250VAC 6.3A F
63H 1 F01 250VAC 6.3A F
High pressure 2
switch 3 detection 6
circuit 5
6
5 1
Refer to the service handbook CNFC1 4 4 CNFC2 CNFAN 3
2 1
U
(6P) 3 3 (6P) (5P) 2
V
about the switch operations. 2
1
2 4
5
3
4
W MF
1 N
CN04
Fan motor
Fan control board (Heat exchanger)
N
CN03
(3P)
CN02
(8P)
CN01
(2P)
CNH
(3P)
CNL
(3P)
CNTYP1
(2P)
(Fancon board)

R2(R407C)
123 12345678 12 1 2 3 1 2 3 12
White

White
Black

Black
Red

Red

3 2 1 3 2 1
TH6 TH5 TH7 TH2 TH1 R20
63HS 63LS
✻1

no fuse breaker <DIFFERENCE OF APPLIANCE>


PURY-(P)200YEM-A 30A Appliance Name
PURY-(P)250YEM-A 30A PURY-P200/250YEM-A All exists
PURY-P200/250YEM-A “✻1” are not existed

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name
DC reactor (Power factor improvement)
DCL SV1 Solenoid valve (Discharge--suction bypass) TH2 ✻1 Thermistor Saturation evapo. temp. detect
DCCT Current Sensor Solenoid valve TH5 Pipe temp. detect
SV3~SV6
ACCT-U,W Current Sensor (Heat exchanger capacity control) TH6 OA temp. detect
ZNR4 Varistor 63HS High pressure sensor liquid outlet temp. detect
TH7
Magnetic contactor 63LS Low pressure sensor at Sub--cool coil
52C (Inverter main circuit) L2 Choke coil(Transmission) THHS Radiator panel temp. detect
MF1 Fan motor (Radiator panel) IPM Intelligent power module X1~10 Aux. relay
21S4 4--way valve TH1 Thermistor Discharge pipe temp. detect Earth terminal

1- 85
6. Refrigerant Circuit Diagram And Thermal Sensor
PURY-P200, 250
ST2 Solenoid Valves Block BV1
21S4 ST1

CV2
CV7

ST5
CV3

CJ2

CJ1 SV3 SV4 SV5 SV6


63HS
63LS
63H

HEXb HEXf3 TH7


O/S CP1
CV4
ST3 TH6

TH1 SV1
HEXf2

HEXf1

ST8 ST9 ST11


ST10
CV5

Comp
ST7 CV8 CV9 CV10 Orifice
ST6

Accumulator
CV6 BV2
TH2
TH5
Check Valves Block
CP2 ST4 Drier CS circuit
: Solenoid valve : Thermal sensor
: Orifice : Strainer
: Capillary SP : Service port
: Check valve ACC : Accumulator

SVC

SVA
SVB
R2(R407C)

Gas/liquid separator

TH23

TH12

TH21
Indoor
TH11 units

TH22

63HS1
LEV
LEV1

63HS3

TH15

LEV3

TH16
BC controller
CMB-P104V-F

1- 86
PURY-P400·500YEM-A
CONTENTS

1. Specifications ································································· 1-88

2. Capacity Tables ······························································1-90


2-1 Correction by temperature ············································ 1-90
2-2 Correction by total indoor ············································· 1-92
2-3 Correction by refrigerant piping length ··························· 1-93
2-4 Correction at frosting and defrosting ···························· 1-94
2-5 Operation limit ·······························································1-94

3. Sound Levels ·································································· 1-95

4. External Dimensions ···················································· 1-96

5. Electrical Wiring Diagram ·············································· 1-97

6. Refrigerant Circuit Diagram ·········································1-98


And Thermal Sensor

Big R2(R407C)

1- 87
1. Specifications

PURY-P400YEM-A
Model name
Cooling Heating

✻1 kW 45.0 50.0
Capacity
✻2 kcal/h 40,000 –

Power source 3N~380/400/415V 50/60Hz

Power input kW 15.87 14.59

Current A 26.7/25.4/24.5 24.6/23.4/22.5

Type✕ Quantity Propeller fan✕2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 4.5

Crankcase heater kW 0.045 + 0.045

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕1990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 25.4 (Flange) / ø 34.93 (Flange)

Total capacity 50~150% of outdoor unit capacity


Indoor unit
Model / Quantity Model P20~250 / 2~24

Noise level ✻ dB<A> 60/61

Net weight kg 470

Indoor : 15˚CWB~24˚CWB Indoor : 15˚CDB~27˚CDB


Outdoor : -5˚CDB~43˚CDB Outdoor : -15˚CWB~15.5˚CWB
Big R2(R407C)

Operating temperature range


-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 88
PURY-P500YEM-A
Model name
Cooling Heating
✻1 kW 56.0 63.0
Capacity
✻2 kcal/h 50,000 –

Power source 3N~380/400/415V 50/60Hz

Power input kW 19.89 18.27

Current A 33.5/31.9/30.7 30.8/29.2/28.2

Type✕ Quantity Propeller fan✕2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 7.5

Crankcase heater kW 0.045 + 0.056

Refrigerant / Lubricant R407C/MEL32

External finish Pre-coated galvanized sheets (Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕1990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 25.4 (Flange) / ø 34.93 (Flange)

Total capacity 50~150% of outdoor unit capacity


Indoor unit
Model / Quantity Model P20~250 / 2~24

Noise level ✻ dB<A> 60/61

Net weight kg 500

Indoor : 15˚CWB~24˚CWB Indoor : 15˚CDB~27˚CDB


Big R2(R407C)

Outdoor : -5˚CDB~43˚CDB Outdoor : -15˚CWB~15.5˚CWB


Operating temperature range
-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 89
2. Capacity Tables
2-1. Correction by temperature
Cooling
• Standard Specifications
PURY-P400 PURY-P500
Capacity kW 45.0 56.0
Input kW 15.87 19.89

Capacity at 100%indoor units running


1.30

1.20

1.10
24˚CWB
Ratio

22˚CWB
1.00 20˚CWB

18˚CWB
0.90 16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

Power Input at 100%indoor units running


1.30 24˚CWB
22˚CWB
1.20 20˚CWB
18˚CWB
16˚CWB
1.10 15˚CWB
Indoor Temperature(˚CWB)
1.00

0.90
Ratio

0.80

0.70
Big R2(R407C)

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 90
Heating
• Standard Specifications
PURY-P400 PURY-P500
Capacity kW 50.0 63.0
Input kW 14.59 18.27

Capacity at 100%indoor units running


1.30

1.20
15˚CDB
1.10 Indoor Temperature(˚CDB)

20˚CDB
1.00
Ratio

0.90
25˚CDB
0.80
27˚CDB

0.70

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100%indoor units running


1.10

Indoor Temperature(˚CDB)
1.00

15˚CDB
0.90
Ratio

0.80
20˚CDB

0.70
Big R2(R407C)
25˚CDB
0.60
27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 91
2-2. Correction by total indoor

PURY-P400
1) Capacity
55.0

50.0
Capacity(kW)

45.0 Heating
Cooling
40.0

35.0

30.0

25.0
20.0
200 300 400 500 600 700
Total capacity of indoor units
2) Input 19.00
18.00 Cooling
17.00
16.00
15.00
14.00
Input(kW)

13.00
12.00 Heating
11.00
10.00
9.00
8.00
7.00
200 300 400 500 600 700
Total capacity of indoor units
PURY-P500
1) Capacity
70.0
65.0
60.0
Heating
55.0
Capacity(kW)

Cooling
50.0
45.0
40.0
35.0
Big R2(R407C)

30.0
25.0
250 350 450 550 650 750 850
Total capacity of indoor units
2) Input
24.00
22.00 Cooling
20.00
18.00
Input(kW)

16.00 Heating
14.00
12.00
10.00
8.00
250 350 450 550 650 750 850
Total capacity of indoor units

1- 92
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PURY-P400 PURY-P500
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor
50% 50%
0.9 0.9
75% 75%
100% 100%
0.8 0.8
150% 150%

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PURY-P400 PURY-P500
1.0 Total capacity 1.0 Total capacity
of indoor unit of indoor unit
50% 50%
Heating capacity

Heating capacity
correction factor

correction factor

0.9 75% 0.9 75%

100% or more 100% or more


0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

✻ In case of using ø22.22 pipe


PURY-P400, 500
1.0
Total ca
pacity
Heating capacity
correction factor

of indo
or unit
0.9
50%
75%
0.8 100% or more

0.7
0 20 40 60 80 100 120
Big R2(R407C)

Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PURY-P400
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m
➁ PURY-P500
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80✕ number of bent on the piping)m

1- 93
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25

20

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)


Big R2(R407C)

❇ Outdoor temperature : -5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB in cooling/heating mixed mode.

1- 94
3. Sound Levels
PURY-P400 50Hz 60Hz
Measurement condition

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


70
1m

60
NC60

50
NC50
1m

40
NC40
Sound pressure level in anechoic room

60/61 dB (A) 30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

PURY-P500 50Hz 60Hz


Measurement condition
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m 70

60
NC60

50 NC50
1m

40
Big R2(R407C)

NC40
Sound pressure level in anechoic room

60/61 dB (A) 30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

1- 95
Big R2(R407C)

15
<Accessorys>
• Refrigerant (high pressure) conn. pipe···········1pc. Refrig. service Refrig. service
(The connecting pipe has been fixed with the unit) valve(low pressure) valve(high pressure)
• Refrigerant (low pressure) conn. pipe············1pc. (flange) (flange)
(The connecting pipe has been fixed with the unit) Conn. pipe Conn. pipe
ø34.93<brazed> ø25.4<brazed>
• Packing for conn. high pressure pipe·············1pc.
(Attached near the ball valve)
910

840

• Packing for conn. low pressure pipe···············1pc. ø27 Knockout hole


(Attached near the ball valve) <bottom hole for the
880(bolt hole)

• Conduit mouting plate control wiring>

162
PURY-P400,500YEM-A

(Painted the same color as the unit body)

90
ø62,ø53,ø46····························Each 1pc.

111
• Tapping screw 4X12·············4pcs.
15

• Wiring partition plate············1pc.

73
230 150

156
Note1. 3X2-14X20 oval hole 215 780(bolt hole) 780(bolt hole) 215
Note1.Please leave a space under the outdoor unit 744 190 Knockout hole
Bottom piping hole 1990
for the piping when you connect the piping Bottom hole for the power supply
4. External Dimensions

from the bottom. Changeable to 400:ø46,ø53,ø62 Cross section X-X Plane view
(Please be careful not to close the hole 500:ø53,ø62 by using attached
of the bottom plate by the basement) conduit mounting plate (accessory)

Air outlet
(265)

1- 96
Air
inlet
1755

Air
inlet
1490

X Knockout hole X
Refrig. service
valve(low pressure)
(flange) Refrig. service
valve(high pressure)
Service panel 745 190 (flange)
18

100
149

126
86

48

80 40
94

Knockout hole 218


Left side hole for 782 103 Knockout hole
the control wiring, Front piping hole
Front hole for the power supply
the power supply Changeable to 400:ø46,ø53,ø62
500:ø53,ø62 by using attached
Rear view Left side view conduit mounting plate (accessory) Front view
Unit : mm
5. Electrical Wiring Diagram
PURY-P400, 500YEM-A
MC2 Motor
(Compressor) MC1 Motor
(Compressor)
U V W U V W

Red White Black Red White Black


Inverter
Controller Box

FB1 FB2
51C2 52C2
2 1 2 1
4 3 4 3 ACCT
-W
6 5 6 5
ACCT
-U
Terminal Noise Terminal Diode
Block Filter Block L1 L2 L3 N stack
TB1A
NF
TB1B DS
R1 R5 IPM
FB5
L1 L1 L1 L1 L1 ZNR4
~ + U V W
+
C2 R2
Power source
L2 L2 L2 L2 L2
~
C1 P
+
3N~ L3 L3 L3 L3 L3
52C1 C3 R3
Gate amp board
380/400/415V ~ -
50/60Hz N N N N N
DCL
N
(G/A board)
Y-C
PE board

BOX BODY
CNE CNDC1 CNDR1 CN15V1
PE F5 600VAC
BOX BODY 8A F L1 BOX BODY (2P)
1 2
(4P)
1 2 3 4
(9P)
1 2 3 4 5 6 7 8 9
(14P)
1 2 3 4 5 6 7 8 9 10 11 12 13 14
F6 600VAC
8A F
SNB board
TB3 L2
EARTH
Connect to M1 L3
Indoor and F3 FB3
remote M2
250VAC
controller 1A F BOX BODY
BOX BODY CNTR1
M1
M2 BOX BODY
T01
S
FB4

TB7 CN20 1
2
1
2 CNAC2
123 12 1 2 3 1 2 3 5 4 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
(3P) CNRS3 3 3 (5P)
CNS2 CNS1 F1 4 4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) 250VAC CNTR (7P) 5
6
5
6 (7P) (4P) (9P) (14P)
2A F (3P) 7 7
F01

B 4 CNVCC41
2
1 CNVCC4
2 (2P)
250VAC
2A F
Power circuit board
3
2 CNAC3
(2P)
(INV board)
1
(4P) 1 1
2 2
CH11
A CNVCC3 3 3 CNVCC2 1
3 (6P) 4
5
4
5
(6P) CNACCT2
3
Crank case heater 2 CN32 6 6 (4P)
(Compressor) 1 (3P) X10 1 4
X01 1
2 2 X01
3
SV1 2 CN33 3 52C1 3
1 (3P)
X02 CNX10 X02 CNTH CNR CNL2 CN30V
(3P) CN52C (2P) (3P) (2P) (2P)
T14 (3P) 1 2 3 CNFAN 12 1 2 3 12 12
SV22 T15 6 (3P)
T12 5
4 CN34
SV32 21S4a 21S4b 3 (6P)
X04
MF1
2
T13 1
X05

1 CH2
SSR BOX BODY THHS R7 L2 R6
3 4 3
1 2 12V 1
2 CN35
1 (3P)
2
3 A B
4 X11
5 4:Compressor ON/OFF 1
CH3
6
Control circuit board CN51 5:Trouble
X12
SV4
(5P) 2
5 (MAIN board) X13
SV6
SV4a SV3 4 CN36
3 (6P)
X06 3 T10
2
1
X07 CN3D 32 DEMAND SV8 SV7
(3P) 1 NIGHT MODE 4
T8
6 5
5 T7
SV6a SV5 4 CN37
3 (6P)
X08 6
2 7 T11
1
X09 L1 L2 L3
8
High pressure
CN38
switch (3P) CN06
63H1 1 X10
2 CNPOW
3 detection (5P) 1 2 3 4 5
F03 250VAC 6.3A F
63H2 circuit
F02 250VAC 6.3A F
F01 250VAC 6.3A F

Relay board
CN51C2
6 T6 6
5 T5 1 CN04
51C2 (3P)
1 CNFC1 4 T4
5
4 CNFC2 CNFAN 3
2 1
U
95 96 2 (6P) 3 T3 3 (6P) (5P) 2
V
T2 W MF3
3 2 4 3
2
1 T1 1 5 4 N
CN52C2 Fan motor
A1 A2 (5P)
1
X01 Fan control board (Heat exchanger)
52C2 52C2 2 (Fancon board)
3 Refer to the service handbook N
4
14 13 5 X02 about the switch operations.
CNRT2 CNRT1
(5P) (5P)
CN52F 5 5
(3P) 4 4 L1 L2 L3
A2 A1 1 3 3 detection
52F 2
X03 2 2 circuit
3 1 1

CNPOW
(5P) 1 2 3 4 5
F03 250VAC 6.3A F
F02 250VAC 6.3A F
CNOUT1 F01 250VAC 6.3A F
X12 (6P)
6
CNCH CNOUT2
(4P) X11 5
CH12 (3P)
1
4 4
CN09 CN07 CN06 CN05 CN03 CN02 CN01 CNH CNL CNLV1 CNLV4 6
2
52F
1
2
3 3 5 1 CN05
(2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (3P) (5P) (5P)
3
2 2
12 12 12 1234 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 4 CNFC2 CNFAN 3
2 1
U
1 1
3 (6P) (5P)
4 3 2
V
T9 2 4
6 5
3
W MF2
1 5 4 N
5
6 Fan motor
FB6 Fan control board (Heat exchanger)
(Fancon board) N
White

White
Black

Black

X13
Red

Red

SLEV
Big R2(R407C)
3 2 1 3 2 1
TH10 TH12 TH9 TH4 TH3 TH6 TH5 TH7 TH2 TH11
63HS 63LS

<Symbol explanation> <Difference of appliance>


Symbol Name Symbol Name Appliance Name
DC reactor IPM Intelligent power module PURY-P400 "✻1" are not existed
DCL (Power factor improvement) TH11,12 Thermistor Discharge pipe temp. detect PURY-P500 All exists
ACCT-U,W Current Sensor TH2 Saturation evapo. temp. detect
ZNR4 Varistor TH3 Accumurator liquid Lower
Magnetic contactor TH4 temp. detect Upper
52C1 (Inverter main circuit) TH5 Pipe temp. detect(Hex outlet)
52C2 Magnetic contactor TH6 OA temp. detect
51C2 Overload relay TH7 Pipe temp.(Hex inlet)
52F Magnetic contactor(Fan motor) TH9 High pressure liquid temp.
MF1 Fan motor (Radiator panel) TH10 Compressor shell temp.
21S4a,4b 4-way valve THHS Radiator panel temp. detect
SV1,22,32, Solenoid valve LD Accumulator liquid level detect
4a,6a CH11,12 Crank case heater(Compressor)
SV3,4,5,6, Solenoid valve CH2,3 Cord heater
7,8 (Heat exchanger capacity control) SSR Solid state relay
SLEV Electronic expansion valve(Oil return) X1,2,4~13 Aux. relay
63HS High pressure sensor FB1~6 Ferrite core
63LS Low pressure sensor Earth terminal
63H1,2 High pressure switch
L2 Choke coil(Transmission) T1~15 Terminal
NOTE : Mark indicates terminal bed, connector, board insertion connector

1- 97
Big R2(R407C)

❇ There are SV22,SV32 only for PUHY-P500YMF-C.


PURY-P400, 500

21S4b
SV Block 2
21S4a
SV8
CV7b
SV7

ST2 ST5 SV4a


CJ1

SV Block 1 HEXb2 HEXf4


63HS CJ2
SV6a
O/S SV3 SV5
CP1 SV4 SV6

ST6
❇ 63LS CV7a
SV1 TH7
CP3a SV22 SV32

1- 98
TH11 CP3b
TH12
CV1a HEXb1 HEXf3
CV1b
TH6
ST15
63H1 63H2 SA MA
Comp1 Comp2 HEXf2
SLEV CJ3 CV5b

ST9 HEXf1 CV4b


CV2b CV3b
CV6b
TH4 ST4
TH3 ST3
ST12 CV Block 2
ST11 ST13 ST14
CS Circuit ST8
Drier TH9 ST16 CP2 CV9a CV10a CV5a ST1 BV1
CV8a CV4a
CV2a CV3a
CV6a
TH2
BV2
TH5
Orifice
CV Block 1
6. Refrigerant Circuit Diagram And Thermal Sensor
PQHY-P200·250YEM-A
CONTENTS

1. Specifications ································································· 1-100

2. Capacity Tables ······························································ 1-102


2-1 Correction by temperature ············································ 1-102
2-2 Correction by total indoor ············································· 1-104
2-3 Correction by refrigerant piping length ··························· 1-105
2-4 Operation limit ······························································ 1-105

3. Sound Levels ·································································· 1-106

4. External Dimensions ···················································· 1-107

5. Electrical Wiring Diagram ·············································· 1-108

6. Refrigerant Circuit Diagram ········································· 1-109


And Thermal Sensor

7. System design guide ······················································ 1-110

WY(R407C)

1- 99
1. Specifications

PQHY-P200YEM-A
Model name
Cooling Heating
Capacity kW 22.4 25.0

Power source 3N ~ 380/400/415V 50Hz/60Hz

Power input kW 7.22 7.24

Current A 12.1/11.5/11.1 12.2/11.6/11.1

Type Hermetic

Compressor Motor output kW 5.5

Crankcase heater kW 0.045(240V)

Type Double coil


Heat exchanger
Water volume in the coil l 10.5

Volume m3/ h 4.27


Circulating water
Pressure drop kPa 8
Refrigerant / Lubricant R407C/MEL32

External finish Galvanized sheets


External dimension mm 1670(H)✕ 1150(W) ✕ 500(L)

High pressure protection 2.94MPa


Protection
Compressor Over current protection
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 25.4 (Flange)

Total capacity 50~130% of heat source unit capacity


Indoor unit
Model / Quantity Model 20~250/1~13

Noise level ✻ dB<A> 51

Net weight kg 270

Operating temperature range Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Water :10˚C ~ 45˚C Water :10˚C ~ 45˚C

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27˚CDB/19˚CWB Water temperature : 30˚C
Heating Indoor : 20˚CDB Water temperature : 20˚C
Pipe length : 7.5m Height difference : 0m
2.The ambient temperature of heat source unit has to be kept below 40˚C (dry valve).
WY(R407C)

The ambient relative humidity of heat source unit has to be kept below 80%.
3.This unit can not be installed in the outdoor. (No protection against the weather.)
✻ It is measured in anechoic room.

1- 100
PQHY-P250YEM-A
Model name
Cooling Heating

Capacity kW 28.0 31.5

Power source 3N ~ 380/400/415V 50Hz/60Hz

Power input kW 9.02 9.23

Current A 15.2/14.4/13.9 15.5/14.8/14.2

Type Hermetic

Compressor Motor output kW 7.5

Crankcase heater kW 0.045(240V)

Type Double coil


Heat exchanger
Water volume in the coil l 13

Volume m3/ h 5.79


Circulating water
Pressure drop kPa 10
Refrigerant / Lubricant R407C/MEL32

External finish Galvanized sheets


External dimension mm 1670(H)✕ 1150(W) ✕ 500(L)

High pressure protection 2.94MPa


Protection
Compressor Over current protection
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 28.58 (Flange)

Total capacity 50~130% of heat source unit capacity


Indoor unit
Model / Quantity Model 20~250/1~16

Noise level ✻ dB<A> 52

Net weight kg 280

Operating temperature range Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Water :10˚C ~ 45˚C Water :10˚C ~ 45˚C

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Water temperature : 30˚C
Heating Indoor : 20˚CDB Water temperature : 20˚C
Pipe length : 7.5m Height difference : 0m
WY(R407C)

2.The ambient temperature of heat source unit has to be kept below 40˚C (dry valve).
The ambient relative humidity of heat source unit has to be kept below 80%.
3.This unit can not be installed in the outdoor. (No protection against the weather.)
✻ It is measured in anechoic room.

1- 101
2. Capacity Tables
2-1. Correction by temperature
Cooling
• Standard Specifications
PQHY-P200 PQHY-P250
Capacity kW 22.4 28.0
Input kW 7.22 9.02

Inlet-water temp. Water volume


1.20
: Capacity : Capacity
: Input 1.10 : Input

1.10

1.00

1.00
Ratio

Ratio

0.90

0.90

0.80

0.80

0.75 0.70
10 20 30 40 50 70 90 110 130 150 170
Inlet-water temp. (˚C) The ratio of water volume change (%)

Intake air temp. Water-pressure drop


1.20 40
: Capacity
: Input
35
1.10
Water-pressure drop (kPa)

30

1.00 25 PQHY-P200YEM-A
Ratio

20
0.90 15 PQHY-P250YEM-A

10
0.80
5

0.70 0
15 20 25 2 3 4 5 6 7 8 9 10 11
Intake air temp. (˚CWB) Water-volume (m3/h)
WY(R407C)

(Room temp.)

1- 102
Heating
• Standard Specifications

PQHY-P200 PQHY-P250
Capacity kW 25.0 31.5
Input kW 7.24 9.23

Inlet-water temp. Water volume


1.20
: Capacity : Capacity
: Input 1.10 : Input

1.10

1.00

1.00
Ratio

Ratio

0.90

0.90

0.80

0.80

0.75 0.70
10 20 30 40 50 70 90 110 130 150 170
Inlet-water temp. (˚C) The ratio of water volume change (%)

Intake air temp.


1.20
: Capacity
: Input

1.10

1.00
Ratio

0.90

0.80

0.70
15 20 25
Intake air temp. (˚CDB)
WY(R407C)

(Room temp.)

1- 103
2-2. Correction by total indoor

PQHY-P200
1) Capacity
26.0
24.0 Heating
22.0
Cooling
Capacity(kW)

20.0
18.0
16.0
14.0
12.0
10.0
100 120 140 160 180 200 220 240 260 280 300
Total capacity of indoor units
2) Input
9.00

8.00
Cooling
7.00
Input(kW)

Heating
6.00

5.00

4.00

3.00
100 120 140 160 180 200 220 240 260 280 300
Total capacity of indoor units
PQHY-P250
1) Capacity

34.0
32.0
Heating
30.0
28.0
26.0 Cooling
Capacity(kW)

24.0
22.0
20.0
18.0
16.0
14.0
150 200 250 300 350
Total capacity of indoor units
2) Input
12.00
11.00
10.00 Cooling
WY(R407C)

Input(kW)

9.00
8.00 Heating
7.00
6.00

5.00
4.00
150 200 250 300 350
Total capacity of indoor units

1- 104
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PQHY-P200 PQHY-P250
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor
100 125
0.9 0.9
150 188
200 250
0.8 0.8
260 325

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PQHY-P200 PQHY-P250
1.0 1.0
Heating capacity

Heating capacity
correction factor

correction factor

0.9 0.9

0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PQHY-P200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PQHY-P250
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m

2-4. Operation limit

• Cooling •Heating
Indoor temperature (˚CWB)

Indoor temperature (˚CDB)

30 30

25 25
WY(R407C)

20 20

15 15

10 10
10 15 20 25 30 35 40 45 10 15 20 25 30 35 40 45
Water temperature (˚C) Water temperature (˚C)

1- 105
3. Sound Levels
PQHY-P200

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µbar


Measurement condition 70

1m
60
NC60

50 NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
51 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

PQHY-P250
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µbar

Measurement condition 70
1m

60
NC60

50
NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
52 dB (A)

20
Approximate minimum NC20
audible limit on
WY(R407C)

continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

1- 106
1227
1177 Plane view
4-M12 Female screw 4-ø14 Mounting hole
1120
(for lifting bolt)
<Accessory> Service space

600
.Refrigerant (gas) conn.pipe . . . .1pc. Note1 Water inlet (front side)
(The connecting pipe is fixed with the unit) (PT1 1/2 screw)
.Packing for conn. pipe . . . . . . . . . 1pc. 400
Note1 Water outlet
(Attached near the ball valve)

392
500
437
ø39 Knockout hole (PT1 1/2 screw) Piping space

400
.Lifting bolt M12 . . . . . . . . . . . . . . 4pcs.
<piping hole> (left side pipe)

373
.Bushing . . . . . . . . . . . . . . .. . . . . . 2pcs.

226
Piping space

122
112
Front view

78
(upside pipe)

61
31

49
64 ø28 Knockout hole
ø60 Knockout hole <Hole for the control
<piping hole> 100 wiring>
PQHY-P200,250YEM-A

353 ø39 Knockout hole


693 <Hole for the power supply>

226
Fig. A
Water outlet Plane view
(PT1 1/2 screw) 1150
4. External Dimensions

Refrig. service
225 valve (gas)
ø70 piping hole <flange>
130

Conn. pipe
200 : ø25.4<brazed> ø28 Knockout hole
250 : ø28.58<brazed> <Hole for the control

1- 107
78 wiring>
ø40 piping hole Refrig. service 173
122 valve (liquid) 108
ø12.7<flare>

1590
1670
373

1531
Water inlet 78 ø39 Knockout hole
(PT1 1/2 screw) <Hole for the power
supply>

1161
1076
Knockout hole

863
837
777

Note2
Drain(PT1 screw) Drain(PT1 screw)
257

25
80

Left side view Front view Right side view Rear view
Note1. At the time of product shipment, the left side piping specification serves as the local water piping connection.
When connecting to the upper piping, please remove the plug sealing corks from the upper piping connection,
and attach a left piping connection part.
Ensure there is no leak after the attachment has been fitted.
2. At the time of product shipment,the left side piping specification serves as the local drainage connection.
Unit : mm

When connecting on the right side, please remove the right side plug sealing corks, and attach a left side.
Ensure there is no leak after the attachment has been fitted.
3. Take notice of service space as Fig A.

WY(R407C)
5. Electrical Wiring Diagram
PQHY-P200, 250YEM-A
MC1 Motor
Inverter U V W
(Compressor)
Controller Box
Red White Black
FB1
F5 SNB board
600VAC
8A F ACCT
L1 -W
F6
600VAC
8A F ACCT
L2 -U

L3 EARTH
BOX BODY

Terminal Noise Terminal Diode


Block NF Filter Block stack
TB1A TB1B DS R1 R5 IPM
L1 L1 Red L1 L1 Red L1 Red ZNR4
~+ U V W
+
Power source C2 R2
3N~ L2 L2 White L2 L2 White L2 White
~ C1 P
380/400/415V 52C
C3
+
R3
50/60Hz L3 L3 L3 L3 L3 DCL
Black Black Black
~- Gate amp board
(G/A board)
N N Blue N N Blue N Blue N
Green/
PE Yellow

BOX BODY
PE BOX BODY CNE CNDC1 CNDR1 CN15V1
TB3 F3
250VAC (2P) (4P) (9P) (14P)
Connect to M1 1A F 1 2 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Indoor and
remote M2
controller CNTR1 FB2
BOX BODY
M1 BOX BODY

Orange

Orange
Yellow

Purple
Brown

Brown
T01

White
Black

Black

Gray
Red

Red
M2

Green

White
Blue
S CN20
CNAC3 1 1
(4P) (3P) 2 2 5 4 3 CNAC2
1 2 3 1 2 1 2 3 1 2 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
TB7 4 CNRS3 34 3 (5P)
CNS2 CNS1 CNTR 4 CNRS2 CNVDC CNDR2 CN15V2
AC4 (3P) (2P) F1 (3P) (7P) 5 5 (7P) (4P) (9P) (14P)
3 250VAC 6 6
(to CNAC4) 2 2A F 7 7
AC1 F01
1 250VAC
CNVCC4 1 1 CNVCC4
(2P) 2 2 (2P) 2A F

1 1
CNVCC3 3
2 2
3 CNVCC2
Power circuit board 1
(6P) 4
5
4 (6P)
5
(INV board) CNACCT 2
(4P) 3
CH1 3
6 6
4
X10
Crank case heater 2 CN32 1 1
(Compressor) 1 (3P) X01 2
3
2 X01
52C 3
3 CNX10 CNTH CNR CNL2 CN30V
SV1 2 CN33 (3P)
CN52C
(3P)
X02 (2P) (3P) (2P) (2P)
1 (3P) X02
1 2 3
CNFAN1 2 1 2 3 1 2 1 2
(3P)
6
5

SV2 21S4
4 CN34
3 (6P)
X04
CN3D3 DEMAND MF1
2
X05 (3P) 21
1
THHS R7 L2 R6
1 BOX BODY
12V 2
3
4 4:Compressor ON/OFF
5
5:SW3-3 OFF:water freeze signal
CN51
6
5
Control circuit board (5P) ON :trouble signal

SV4 SV3 4 CN36


X06 (MAIN board)
3 (6P)
2
1 X07
(to CNAC3)
6 AC4 AC1
5

SV6 SV5
4 CN37
3 (6P)
X08
CNAC4 CN81
2 (9P)
X09 (4P) 4 3 2 1 X21
1 9
8
X22 7
6
CN38 X10 X23 5
63H (3P)
1
4 SV73 SV72 SV71
3
High pressure 2 2
switch 3 detection CNPW
(4P) 1
circuit
26W 5
4 4
Freeze protect CN63PW 32 3 CN83
4 Refer to the service handbook (4P) 1 2
(7P) TB8
switch 3 detection 1
7 4 63PW
2 circuit about the switch operations. detection 5 3 Pump interlock
1 6
5
6 circuit 3 2
CNRT1 5 1 1 Unit ON/OFF
(5P) CNOUT14 4 CNOUT2 X25
CN13 CN12 CN09 CN08 CN06 CN03 CN02 CN01 CNH CNL CNLV2
CNLV1 CNLV2 CNLV3 (6P) 3 3 (6P)
(4P) (2P) (2P) (2P) (2P) (3P) (8P) (2P) (3P) (3P) (5P) (5P) (5P) 2
2
1234 12 12 12 12 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 1234 5 1
1
RELAY board
White

White
Black
Black

Red
Red

no fuse breaker 3 2 1 3 2 1 SLEV LEV2 LEV1


PQHY-P200YEM-A 30A 63HS 63LS
TH7 TH8 THINV TH10 TH5 TH9 TH6 TH2 TH1
PQHY-P250YEM-A 50A

<Operation of self-diagnosis switch(SW1)and LED display> <Symbol explanation>


Display Display at LED lighting (blinking) Remarks SW1 operation Symbol Name
FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8 DCL DC reactor
Relay output During Crankcace Always FLAG8 always <LED display> (Power factor improvement)
display Compres- 21S4 SV1 SV2 SV3 SV4 lighting
(Lighting) sor run heater
lights at
ACCT-U,W Current Sensor
ON:1
OFF:0 Check display1 Display the address and error code by turns LD1 ZNR4 Varistor
1 2 3 4 5 6 7 8 910 (Blinking) microcomputer Magnetic contactor
(at factory shipment) 52C
power ON (Inverter main circuit)
FLAG1 FLAG8 MF1 Fan motor (Radiator panel)
FLAG2 FLAG7 21S4 4-way valve
ON:1 FLAG3 FLAG6 SV1,SV2 Solenoid valve (Discharge-suction bypass)
OFF:0 SV5 SV6 SV71 SV72 SV73 FLAG4 FLAG5
1 2 3 4 5 6 7 8 910 SV3~6 Solenoid valve
(Heat exchanger capacity control)
*Please refer to the service handbook about other switch settings of LED display. SV71~73 Solenoid valve
(Heat exchanger capacity control)
LEV1 Electronic expansion valve
<Controller box internal layout> <Unit internal layout> (Sub-cool coil bypass)
(Upside) (Underside) (Upside) LEV2 Electronic expansion valve
(Heat exchanger for inverter)
TH6 SLEV Electronic expansion valve(Oil return)
L2 63HS High pressure sensor
MF1 DCL 26W 63LS Low pressure sensor
L2 Choke coil(Transmission)
INV board R1 R6 R7 INVERTER IPM Intelligent power module
CONTROLLER
F3 TH8 21S4 BOX TH1 Thermistor Discharge pipe temp. detect
THINV
R5 TB1B TH7
ACCT TH2 Saturation evapo. temp. detect
TH5 TH5 Pipe temp. detect
WY(R407C)

LEV1
T01 THHS R3 TH2 TH6 OA temp. detect
SV72 SV71 liquid outlet temp. detect
TH7
IPM
C3 (Underside) at Sub-cool coil
TH8 bypass outlet temp. detect
C2
at Sub-cool coil
RELAY G/A board SV2
ZNR4 R2 NF TH9 High pressure liquid temp.
board MAIN board
C1 OIL SV1 ACCUMULATOR TH10 Compressor shell temp.
DS SEPARATOR THINV Outlet temp. detect of
63H SV73 heat exchanger for inverter
52C
SNB THHS Radiator panel temp. detect
F6 board SV3
F5 MC 63HS TH9 X1~10 Aux. relay
SV4 TH1 SLEV X21~25
TB3 TB7 TB3 TB7
TB8 TB1A TB8 TB1A SV5 FB1~2 Ferrite core
SV6 63LS
TH10 LEV2 Earth terminal

1- 108
ST
: Strainer
CV
: Check valve
SP
4way valve : Service port
SV
PQHY-P200, 250

: Solenoid valve
ST2 TH
: Thermal sensor
SP1 Solenoid Valves CP
High pressure Block Distributor : Capillary
sensor ST8
LEV
ST5 SV3 : Liner valve expansion
SV4 SV6 BV
SV73 SV5
CV11 : Ball valve
Oil
separator
CP1
ST6
SV1
TH1 CJ2
CV1
SV2 CV7
SV72
Water heat exchanger
High pressure (Double coil type)
switch
Compressor
TH6

1- 109
Water
Accumulator circulating
TH10
ST1 BV1
ST4 SLEV SV71
CP4
Air heat exchanger ST7a ST7b ST7c ST7d

TH INV
LEV2 TH2
Low presser sensor CV8 CV9 CV10 CV3
CV4
TH9 CV6 TH5 TH7

Drier ST10 BV2


Check Valves Block SCC
Orifice ST9

LEV1
TH8
6. Refrigerant Circuit Diagram And Thermal Sensor

WY(R407C)
7. System design guide
7-1. Designing of water circuit system

1) Example of basic water circuit


The water circuit of the water heat source CITY MULTI auxiliary heat source and cooling tower is not required.
connects the heat source unit with the cooling In order to control the above thermal balance properly
tower/auxiarily heat source/heat storage tank/circulation and use thermal energy effectively, utilizing of heat stor-
pump with a single system water piping as shown in the age tanks, and night-time discounted electric power as a
figure below. The selector valve automatically controls to auxiliary heat source will be economical.
circulate water toward the cooling tower in the cooling Meantime as this system uses plural sets of heat source
season, while toward the heat storage tank in the heat- unit equipped with water heat exchangers, water quality
ing season. If the circulation water temperature is kept in control is important. Therefore it is recommended to use
a range of 10~45˚C* regardless of the building load, the closed type cooling towers as much as possible to pre-
water heat source CITY MULTI can be operated for vent the circulation water from being contaminated.
either cooling or heating. Therefore in the summer when When open type cooling towers are used, it is essential
only cooling load exists, the temperature rise of circula- to provide proper maintenance control such as that to
tion water will be suppressed by operating the cooling install water treatment system to prevent troubles
tower. While in the winter when heating load increases, caused by contaminated circulation water.
the temperature of circulation water may be dropped
below 10˚C. Under such situation, the circulation water *10~45˚C : 50%~130% of indoor units can be connected
will be heated with the auxiliary heat source if it drops
below a certain temperature.
When the thermal balance between cooling and heating
operation is in a correct proportion, the operation of the

Example of basic water circuit for water heat source CITY MULTI

C.T

E.H

C.T.P
S.T
P T T
3-way valve

S.T : Heating tank


(Heat storage tank)
C.T : Cooling tower
C.T.P : Cooling water pump
WY(R407C)

P : Circulation water pump


T : Thermostat for water
E.H : Electric heater
: Heat source unit for cooling
operation
: Heat source unit for heatin
operation

The indoor unit and refrigerant piping system are excluded in this figure.

1- 110
2) Cooling tower
a) Types of cooling tower
The cooling towers presently used include the open type
Types of cooling towers
cooling tower, open type cooling tower + heat exchang-
er, closed type cooling tower, and air-cooled type cooling Closed type
tower. However, as the quality control of circulation water
is essential when units are installed in decentralized
state inside a building, the closed type cooling tower is
generally employed in such case.
Although the circulation water will not be contaminated
by atmospheric air, it is recommended to periodically
blow water inside the system and replenish fresh water
instead.
In a district where the coil may be frozen in the winter, it Air-cooled type
is necessary to apply antifreeze solution to the circula-
tion water, or take freeze protection measures such as to
automatically discharge water inside the cooling coil at
the stopping of the pump.
When the open type cooling tower is used, be sure to
install a water quality control device in addition to the
freeze protection measures, as the water may be deteri-
orated by atmospheric contaminants entered into the
cooling tower and dissolved into the circulation water.

b) Calculation method of cooling tower capacity


All units of the water heat source CITY MULTI may pos- It is determined in accordance with the value obtained by
sibly be in cooling operation temporarily (at pulling adding the maximum cooling load of an actual building,
down) in the summer, however, it is not necessary to the input heat equivalent value of all CITY MULTI units,
determine the capacity according to the total cooling and the cooling load of the circulating pumps. Please
capacity of all CITY MULTI units as this system has a check for the values of the cooling water volume and cir-
wide operating water temperature range (10~45˚C). culation water volume.

Qc + 860 x (∑Qw + Rw)


Cooling tower capacity = (Refrigeration ton)
3,900

Qc : Maximum cooling load under actual state (kcal/h)


Qw : Total input of water heat source CITY MULTI at simultaneous operation under max-
WY(R407C)

imum state (kW)


Pw : Shaft power of circulation pumps (kW)

1- 111
3) Auxiliary heat source and heat storage tank
When the heating load is larger than the cooling load, The effective temperature difference of an ordinary heat
the circulation water temperature lowers in accordance storage tank shows about 5deg. even with the storing
with the heat balance of the system. It should be heated temperature at 45˚C.
by the auxiliary heat source in order to keep the inlet However with the water heat source CITY MULTI, it can
water temperature within the operating range (10˚C or be utilized as heating heat source up to 15˚C with an
more). effective temperature of a high 30deg. approximately,
thus the capacity of the heat storage tank can be mini-
of the water heat source CITY MULTI. mized.
Further in order to operate the water heat source CITY
MULTI effectively, it is recommended to utilize the heat
a)Auxiliary heat source
The following can be used as the auxiliary heat source.
storage tank to cover the warming up load in the morn-
• Boiler (Heavy oil, kerosine, gas, electricity)
ing and the insufficient heat amount.
• Electric heat (Insertion of electric heater into heat stor-
Effective heat utilization can be expected to cover insuf-
age tank)
ficient heat at the warming up in the next morning or
• Outdoor air (Air-heat source heat pump chiller)
peak load time by storing heat by installing a heat stor-
• Warm discharge water (Exhaust water heat from
age tank or operating a low load auxiliary heat source at
machines inside building and hot water supply)
the stopping of the water heat source CITY MULTI. As it
• Utilization of night-time lighting
can also be possible to reduce the running cost through
•Solar heat
the heat storage by using the discounted night-time elec-
Please note that the auxiliary heat source should be
tric power, using both auxiliary heat source and heat
selected after studying your operating environment and
storage tank together is recommended.
economical feasibility.

Determining the auxiliary heat source capacity


For the CITY MULTI water heat source system, a heat However the auxiliary heat source capacity should be
storage tank is recommended to use. When employment determined by the daily heating load including warming
of the heat storage tank is difficult, the warming up oper- up load on the week day.
ation should be arranged to cover the starting up heat- For the load at the next morning of the holiday, heat stor-
ing load. Since the holding water inside the piping circuit age is required by operating the auxiliary heat source
owns heat capacity and the warming up operation can even outside of the ordinary working hour.
be assumed for about one hour except that in a cold
region, the heat storage tank capacity is required to be
that at the maximum daily heating load including the
warming up load at the next morning of the holiday.

When heat storage tank is not used


1
QH = HCT (1- ) - 1000 x Vw x ∆T - 860 x Pw
COPh

QH : Auxiliary heat source capacity (kcal/h)


HCT : Total heating capacity of each water heat source CITY MULTI (kcal/h)
COPH : COP of water heat source CITY MULTI at heating
VW : Holding water volume inside piping (m3)
∆T : Allowable water temperature drop = TWH - TWL (˚C)
WY(R407C)

TWH : Heat source water temperature at high temperature side (˚C)


TWL : Heat source water temperature at low temperature side (˚C)
PW : Heat source water pump shaft power (kW)

1- 112
When heat storage tank is used;

1
HQ1T = (1- COPh
) - 860 x Pw x T2
QH = xK (Kcal)
T1

QH1T : Total of heating load on weekday including warming up (kcal/day)


T1 : Operating hour of auxiliary heat source (h)
T2 : Operating hour of heat source water pump (h)
K : Allowance factor (Heat storage tank, piping loss, etc.) 1.05~1.10

HQ1T is calculated from the result of steady state load calculation similarly by using the equation below.
HQ1T = 1.15 x (∑Q'a + ∑Q'b + ∑Q'c + ∑Q'd + ∑Q'f) T2 - ψ (∑Qe1 + ∑Qe2 + ∑Qe3) (T2 - 1)

Q'a : Thermal load from external wall/roof in each zone (kcal/h)


Q'b : Thermal load from glass window in each zone (kcal/h)
Q'c : Thermal load from partition/ceiling/floor in each zone (kcal/h)
Q'd : Thermal load by infiltration in each zone (kcal/h)
Q'f : Fresh outdoor air load in each zone (kcal/h)
Q'e1 : Thermal load from human body in each zone (kcal/h)
Q'e2 : Thermal load from lighting fixture in each zone (kcal/h)
Q'e3 : Thermal load from equipment in each zone (kcal/h)
ψ : Radiation load rate 0.6~0.8
T2 : Air conditioning hour

b) Heat storage tank


Heat storage tank can be classified by types into the sidering corrosion problems.
open type heat storage tank exposed to atmosphere, The capacity of heat storage tanks is determined in
and the closed type heat storage tank with structure sep- accordance with the daily maximum heating load that
arated from atmosphere. Although the size of the tank includes warming up load to be applied for the day after
and its installation place should be taken into account, the holiday.
the closed type tank is being usually employed by con-

When auxiliary heat source is operated during operation and even after stopping of water heat source CITY MULTI unit

1
HQ2T (1- COPh
) - 860 x Pw x T2 - QH x T2
V= (ton)
∆T x 1000 x ηV

When auxiliary heat source is operated after stopping of water heat source CITY MULTI unit
1
HQ2T (1- COPh
) - 860 x Pw x T2
V= (ton)
WY(R407C)

∆T x 1000 x ηV

HQ2T : Maximum heating load including load required for the day after the holiday (kcal/day)
∆T : Temperature difference utilized by heat storage tank (deg)
ηV : Heat storage tank efficiency

HQ2T : 1.3 x (∑Q'a + ∑Q'c + ∑Q'd + ∑Q'f) T2 - ψ(∑Qe2 + ∑Qe3) (T2 - 1)

1- 113
4) Piping system
The following items should be kept in your mind in plan- tank to absorb the expansion/contraction of water
ning / designing water circuits. caused by temperature fluctuation.

a) All units should be constituted in a single circuit in princi- e) If the operating temperature range of circulation water
ple. stays within the temperature near the normal tempera-
ture (summer : 30˚C, winter : 20˚C), thermal insulation or
b) When plural numbers of the water heat source CITY anti-sweating work is not required for the piping inside
MULTI unit are installed, the rated circulating water flow buildings.
rate should be kept by making the piping resistance to
each unit almost same value. As an example, the In case of the conditions below, however, thermal insu-
reverse return system as shown below may be lation is required.
employed.
• When well water is used for heat source water.
c) Depending on the structure of a building, the water circuit • When piped to outdoor or a place where freezing may be
may be prefabricated by making the layout uniform. caused.
• When vapor condensation may be generated on piping
d) When a closed type piping circuit is constructed, install an due to an increase in dry bulb temperature caused by
expansion tank usable commonly for a make-up water the entry of fresh outdoor air.

System example of water circuit

Heating tank
Cooling tower
Pump 3-way valve
Backflow prevention valve Strainer

Flexible joint

3-way valve

Indoor unit Indoor unit Indoor unit Indoor unit

Refregerant piping

Joint
Valve
Heat Heat Heat Heat
source source source source
unit unit unit unit
WY(R407C)

Y-shape strainer

Drain

1- 114
5) Cleaning of water heat exchanger
For the water heat exchanger, scale adheres in less dure given below.
amount generally in the case of closed type cooling tow- The cleaning work procedure generally used is as fol-
ers. However in a long period of use, scale will adhere lows. However as the cleaning agents have various dif-
that may lower the heat exchange capacity and increase ferences in their cleaning effect, corrosion characteris-
the water resistance. tics, processing time, and condensation for use, conduct
In such case, conduct cleaning work under the proce- the work after consulting the relating maker.

Acid washing Water washing Neutralization Water washing Applying inhibitor

a)Still standing method


This method feeds the raw liquid or diluted solution of • Fully recover the cleaning liquid through the water dis-
cleaning agent into the water circuit and leave it for a charge plug of the heat exchanger, and then fully clean
while, and requires only a simple device. the water circuit with clean water. If the water washing
can not be made sufficiently, neutralization processing
• Since the cleaning time required differs by the agent of will be effective.
each maker, be sufficiently careful for the time and not
to exceed the time specified.

Still standing cleaning device

Cleaning agent

Hose

To be closed

Water discharge plug


T-joint : When no exclusive T-joint is
available, use the connection
of the thermometer or the like.
WY(R407C)

1- 115
b)Circulation method
Although this method can clean in shorter time than that • Check for the connections of piping beforehand so that
required by the still standing method, be careful that the cleaning agent will not leak from the piping during
circulation pump may be damaged if using cleaning cleaning work.
agent with strong corrosive characteristics. • Start cleaning operation after fully mixing the cleaning
agent with water.
• After completing washing work, fully recover the wash- • Cleaning at the earlier timing is recommended as the
ing liquid through the water discharge plug installed at removal of scale will be difficult if it has accumulated
the bottom of the piping and that at the heat exchanger. seriously. Periodical cleaning is necessary in a district
• Conduct water washing for three times or more after with inferior water quality.
removing cleaning agent. If this can not be made satis- • Conduct water washing sufficiently with clear water after
factorily, apply neutralization treatment. Full replace- cleaning work as all cleaning agents own strong acidity.
ment of water can be ascertained by measuring the PH • To verify the completion of cleaning, remove the hose
of the water. and observe the inner wall of the piping whether it is
• Note that it may be required to control the cleaning time clean.
depending on the scale generation or water quality. • Be sufficiently careful for fire when using inflammable
• At cleaning work, remove or shut down the instruments cleaning agent (GOSPEL R).
like water pressure gauges so that the cleaning liquid
will not enter into them.

Circulation method cleaning device

Hose
Filtration net

Cleaning agent

Tank
To be closed

Hose
T-joint

To be closed

T-joint
Pump
Water discharge plug
Water discharge plug

Example of cleaning agents


Name Shape Condensation Time Makers
CLEARLITE RK Powder/Liquid 10~20% 2~3Hr. Koei Kagaku
CLEARLITE ACE Powder/Liquid 3~5% 1~3Hr. Koei Kagaku
GOSPEL R Liquid
WY(R407C)

Gospel Kako
GOSPEL SR Powder 7%
ADDITION DR Powder 1~4Hr. Marusan
SS-100 Liquid
( Upper limit 10%,
lower limit 5%
)
Seiwa kogyo
NEOLUX F Powder
DISCALER Powder 4~7% Saver Kagaku

1- 116
6) Practical System Examples and Circulation
Water Control
Since the water heat source CITY MULTI is of water heat source CITY MULTI stays within a range of 10~45˚C.
source system, versatile systems can be constituted by However, the circulation water temperature near 32˚C for
combining it with various heat sources. cooling and 20˚C for heating is recommended by taking
The practical system examples are given below. the life, power consumption and capacity of the air con-
Either cooling or heating operation can be performed if ditioning units into consideration. The detail of the con-
the circulation water temperature of the water heat trol is also shown below.

Example-1 Combination of closed type cooling tower and hot water heat storage tank (using underground hollow slab)

Expansion tank
Closed type
Cooling water pump cooling tower

Circulation
water pump

V1

XS T1

Heat
source
unit

T2

V2

EH
Heat exchanger MG

T1~T4 : Thermostat
Heat storage T4
V1~V2: Proportional type
motor-driven 3-way valve tank pump
V3 Auxiliary
V3 : Motor-driven 3-way valve
XS : Auxiliary switch heat source
MG : Magnetic switch
EH : Electric heater

Heat storage tank T3

By detecting the circulation water temperature of the water heat source CITY MULTI system with T1 (around 32˚C) and
T2 (around 20˚C), the temperature will be controlled by opening/closing V1 in the summer and V2 in the winter.
In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
WY(R407C)

open to lower the circulation water temperature. While in the winter, as the circulation water temperature drops, V2 will
open following the command of T2 to rise the circulation water temperature.
The water inside the heat storage tank will be heated by the auxiliary heat source by V3 being opened with timer opera-
tion in the night-time. The electric heater of the auxiliary heat source will be controlled by T3 and the timer. The start/stop
control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and pump follow-
ing the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan and pump at
the maximum load thus controlling water temperature and saving motor power.

1- 117
Example-2 Combination of closed type cooling tower and hot water heat storage tank

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat
T3 : Proportional type, insertion system thermostat
V1 : Proportional type, motor-driven 3-way valve
V2 : Proportional type, motor-driven 3-way valve
XS : Auxiliary switch (Duplex switch type)
SC : Step controller
R : Relay
MG : Magnetic
SC MG
Hot water heat
Closed type storage tank
cooling tower

T3

CV

V1

XS

V2

R T2
Heat source
Pump interlock water pump
Heat
source
unit

=In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1
will open to lower the circulation water temperature. In the winter, if the circulation water temperature stays below 25˚C,
V2 will open/close by the command of T2 to keep the circulation water temperature constant.
The temperature of the hot water inside the heat storage tank will be controlled through the step control of the electric
heater by step controller operation following the command of T3.
WY(R407C)

During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking thus pre-
venting the high temperature water from entering into the system at the starting of the pump.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and
pump following the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan
and pump at the maximum load thus controlling water temperature and saving motor power.

1- 118
Example-3 Combination of closed type cooling tower and boiler

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat
T3 : Proportional type, insertion system thermostat
V1 : Proportional type, motor-driven 3-way valve
S : Selector switch
R : Relay
XS : Auxiliary switch (Duplex switch type)

Closed type
cooling tower

XS
V1
Relay board

Heat T1
source
unit

Pump interlock Boiler


Heat source
water pump V2

T2

In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 25˚C, V2 will
conduct water temperature control to keep the circulation water temperature constant.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the com-
WY(R407C)

mand of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.

1- 119
Example-4 Combination of closed type cooling tower and heat exchanger (of other heat source)

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat
V1 : Proportional type, motor-driven 3-way valve
V2 : Proportional type, motor-driven 3-way valve
S : Selector switch
R : Relay
XS : Auxiliary switch (Duplex switch type)

Closed type
cooling tower

XS
V1
Relay board

Heat T1
source
unit

Heat exchanger

Other heat source water


V2

Heat source
water pump

T2

In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 26˚C, V2
will conduct water temperature control to keep the circulation water temperature constant.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the
WY(R407C)

command of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.

1- 120
7) Pump interlock circuit

Heat source • Plural indoor units (8HP:13sets, 16HP:16sets maximum) being connected to
equipment
a single refrigerant system can be controlled individually.
• The transmission line is of a jumper wiring system using non-polar 2 wires.

Refrigerant piping

Water
circuit Indooor Indooor Indooor Indooor
unit unit unit unit

Transmission line

Remote controller
Room-A Room-B Room-C Room-D

Heat source
water pump
(MP)

Site control panel


(Remote controller
operation at two spot)
Room-E Room-F Room-G

Wiring diagram

This circuit uses the “Terminal block for pump interlock (TB8)“ inside the electrical parts box of the heat source equipment.
This circuit is for interlocking of the heat source equipment operation and the heat source water pump.
L N
Site control panel ~ / N 240/230/220V

Heat source equipment MCB

TB8
1
X : Relay
2 TM1, 2 : Timer relay
3
(closes after elapsing
the set time when it is
4 powered, while opens
TM1 promptly when it is not
powered)
Heat source equipment 52P : Magnetic contactor
52P TM1 TM2 for heat source
water pump
TB8 52P
MP : Heat source
WY(R407C)

1
water pump
2 MCB : Circuit breaker
3
*Remove the short circuit
4 wire between 3 and 4
TM2 when wiring to TB8.

MP
To next equipment

1- 121
Operation ON signal

Terminal No. TB8-1, 2

Relay contacts output Rated voltage : L1 - N : 220 ~ 240V


Output
Rated load : 1A
• When Dip switch 2-7 is OFF
Operation The relay closes during compressor operation.
• When DIP switch 2-7 is ON.
The relay closes during reception of cooling or the heating operation signal from the controller.
(Note : It is output even if the thermostat is OFF (when the compressor is stopped).)

Pump Interlock

Terminal No. TB8-3, 4


Input Level signal
Operation If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.
WY(R407C)

1- 122
7-2.WATER PIPING WORK
Although the water piping for the CITY MULTI WY system does not differ from that for ordinary air conditioning
systems, pay special attention to the items below in conducting the piping work.

1) Items to be observed on installation work Installation example of heat source unit


• In order to equalize piping resistance for each unit, adapt
Refrigerant
the reverse return system. piping
Water
• Mount a joint and a valve onto the water outlet/inlet of the outlet

unit to allow for maintenance, inspection and replace- Circulation Stop valve
water main
ment work. Be sure to mount a strainer at the water inlet
piping of the unit. (The strainer is required at the circula-
Stop valve
tion water inlet to protect the heat source unit.)
* The installation example of the heat source unit is shown
right.
Y-shape
• Be sure to provide an air relief opening on the water pip- strainer Water
inlet
ing properly, and purge air after feeding water to the pip-
ing system.
• Condensate will generate at the low temperature part
inside the heat source equipment. Connect drain piping
Drain
to the drain piping connection located at the bottom of pipe

the heat source equipment to discharge it outside the


equipment. 3) Water treatment and water quality control
• At the center of the header of the heat exchanger water For the circulation water cooling tower of the CITY
inlet inside the unit, a plug for water discharge is being MULTI WY system, employment of the closed type is
provided. recommended to keep water quality. However, in the
Use it for maintenance work or the like. case that an open type cooling tower is employed or the
• Mount a backflow prevention valve and a flexible joint for circulating water quality is inferior, scale will adhere onto
vibration control onto the pump. the water heat exchanger leading to the decreased heat
• Provide a sleeve to the penetrating parts of the wall to exchange capacity or the corrosion of the heat exchang-
prevent the piping. er. Be sufficiently careful for water quality control and
• Fasten the piping with metal fitting, arrange the piping not water treatment at the installation of the circulation water
to expose to cutting or bending force, and pay sufficient system.
care for possible vibration. • Removal of impurities inside piping
• Be careful not to erroneously judge the position of the Be careful not to allow impurities such as welding frag-
inlet and outlet of water. ment, remaining sealing material and rust from mixing
(Lower position : Inlet, Upper position : Outlet) into the piping during installation work.
• Water treatment
2) Thermal insulation work The water quality standards have been established by
Thermal insulation or antisweating work is not required the industry (Japan Refrigeration, Air Conditioning
for the piping inside buildings in the case of the CITY Industry Association, in case of Japan) for water treat-
MULTI WY system if the operating temperature range of ment to be applied.
circulation water stays within the temperature near the
normal (summer : 30˚C, winter : 20˚C). Items Standard values
PH(25˚C) 7.0 ~ 8.0
In case of the conditions below, however, thermal insu-
Electric conductivity (25˚C)(µs/cm) 300 or less
lation is required.
Chlorine ion CI- (mg/l) 50 or less
• Use of well water for heat source water Standard items Sulfate ion SO42- (mg/l) 50 or less
WY(R407C)

• Outdoor piping portions M-alkalinity CaCO3 (mg/l) 50 or less


• Indoor piping portions where freezing may be caused in Total hardness CaCO3 (mg/l) 70 or less
winter Iron Fe (mg/l) 1.0 or less

• A place where vapor condensation may be generated on Sulfur ion S2- (mg/l) Not be detected
Reference items Ammonium ion NH4+ (mg/l) Not be detected
piping due to an increase in dry bulb temperature inside Note.1
Silica SiO2 (mg/l) 30 or less
the ceiling caused by the entry of fresh outdoor air
Note.1 It is clearly found that the component of the reference items will
• Drain piping portions be hazardous, however, the quantitative relationship between
the content and hazard has not been clarified yet. Therefore,
they are listed as the reference items.

1- 123
In order to keep the water quality within such standards,
you are kindly requested to conduct bleeding-off by over-
flow and periodical water quality tests, and use inhibitors
to suppress condensation or corrosion. Since piping may
be corroded by some kinds of inhibitor, consult an appro-
priate water treatment expert for proper water treatment.

(4) Pump interlock


Operating the heat source unit without circulation water
inside the water piping can cause a trouble. Be sure to
provide interlocking for the unit operation and water cir-
cuit. Since the terminal block is being provided inside the
unit, use it as required.
WY(R407C)

1- 124
PQRY-P200·250YEM-A

WR2(R407C)
CONTENTS

1. Specifications ································································· 1-126

2. Capacity Tables ······························································ 1-128


2-1 Correction by temperature ············································· 1-128
2-2 Correction by total indoor ············································· 1-130
2-3 Correction by refrigerant piping length ··························· 1-131
2-4 Operation limit ······························································· 1-131

3. Sound Levels ·································································· 1-132

4. External Dimensions ···················································· 1-133

5. Electrical Wiring Diagram ·············································· 1-134

6. Refrigerant Circuit Diagram ········································· 1-135


And Thermal Sensor

7. System design guide ······················································ 1-136

1- 125
1. Specifications

PQRY-P200YEM-A
Model name
Cooling Heating
Capacity kW 22.4 25.0
WR2(R407C)

Power source 3N ~ 380/400/415V 50Hz/60Hz

Power input kW 7.22 7.24

Current A 12.1/11.5/11.1 12.2/11.6/11.1

Type Hermetic

Compressor Motor output kW 5.5

Crankcase heater kW 0.045(240V)

Type Double coil


Heat exchanger
Water volume in the coil l 10.5

Volume m3/ h 4.27


Circulating water
Pressure drop kPa 8
Refrigerant / Lubricant R407C/MEL32

External finish Galvanized sheets


External dimension mm 1670(H)✕ 1150(W) ✕ 500(L)

High pressure protection 2.94MPa


Protection
Compressor Over current protection
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~150% of heat source unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 15

Noise level ✻ dB<A> 51

Net weight kg 270

Operating temperature range Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Water :10˚C ~ 45˚C Water :10˚C ~ 45˚C

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27˚CDB/19˚CWB Water temperature : 30˚C
Heating Indoor : 20˚CDB Water temperature : 20˚C
Pipe length : 7.5m Height difference : 0m
2.When the total capacity of indoor units exceeds 130% of heat source units capacity, the operating temperature
range of circulating water is 15˚C ~ 45˚C.
3.The ambient temperature of heat source unit has to be kept below 40˚C (dry valve).
The ambient relative humidity of heat source unit has to be kept below 80%.
4.This unit can not be installed in the outdoor. (No protection against the weather.)
✻ It is measured in anechoic room.

1- 126
PQRY-P250YEM-A
Model name
Cooling Heating
Capacity kW 28.0 31.5

WR2(R407C)
Power source 3N ~ 380/400/415V 50Hz/60Hz

Power input kW 9.02 9.23

Current A 15.2/14.4/13.9 15.5/14.8/14.2

Type Hermetic

Compressor Motor output kW 7.5

Crankcase heater kW 0.045(240V)

Type Double coil


Heat exchanger
Water volume in the coil l 13

Volume m3/ h 5.79


Circulating water
Pressure drop kPa 10
Refrigerant / Lubricant R407C/MEL32

External finish Galvanized sheets

External dimension mm 1670(H)✕ 1150(W) ✕ 500(L)

High pressure protection 2.94MPa


Protection
Compressor Over current protection
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 150% of heat source unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250/ 1 ~ 16

Noise level ✻ dB<A> 52

Net weight kg 280

Operating temperature range Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Water :10˚C ~ 45˚C Water :10˚C ~ 45˚C

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Water temperature : 30˚C
Heating Indoor : 20˚CDB Water temperature : 20˚C
Pipe length : 7.5m Height difference : 0m
2.When the total capacity of indoor units exceeds 130% of heat source units capacity, the operating temperature
range of circulating water is 15˚C ~ 45˚C.
3.The ambient temperature of heat source unit has to be kept below 40˚C (dry valve).
The ambient relative humidity of heat source unit has to be kept below 80%.
4.This unit can not be installed in the outdoor. (No protection against the weather.)
✻ It is measured in anechoic room.

1- 127
2. Capacity Tables
2-1. Correction by temperature
Cooling
• Standard Specifications
PQRY-P200 PQRY-P250
WR2(R407C)

Capacity kW 22.4 28.0


Input kW 7.22 9.02

Inlet-water temp. Water volume


1.20
: Capacity : Capacity
: Input 1.10 : Input

1.10

1.00

1.00
Ratio

Ratio

0.90

0.90

0.80

0.80

0.75 0.70
10 20 30 40 50 70 90 110 130 150 170
Inlet-water temp. (˚C) The ratio of water volume change (%)

Intake air temp. Water-pressure drop


1.20 40
: Capacity
: Input
35
1.10
Water-pressure drop (kPa)

30

1.00 25 PQRY-P200YEM-A
Ratio

20
0.90 15 PQRY-P250YEM-A

10
0.80
5

0.70 0
15 20 25 2 3 4 5 6 7 8 9 10 11
Intake air temp. (˚CWB) Water-volume (m3/h)
(Room temp.)

1- 128
Heating
• Standard Specifications
PQRY-P200 PQRY-P250

WR2(R407C)
Capacity kW 25.0 31.5
Input kW 7.24 9.23

Inlet-water temp. Water volume


1.20
: Capacity : Capacity
: Input 1.10 : Input

1.10

1.00

1.00
Ratio

Ratio

0.90

0.90

0.80

0.80

0.75 0.70
10 20 30 40 50 70 90 110 130 150 170
Inlet-water temp. (˚C) The ratio of water volume change (%)

Intake air temp.


1.20
: Capacity
: Input

1.10

1.00
Ratio

0.90

0.80

0.70
15 20 25
Intake air temp. (˚CDB)
(Room temp.)

1- 129
2-2. Correction by total indoor

PQRY-P200
1) Capacity
26.0
Heating
WR2(R407C)

24.0
Cooling
Capacity(kW)

22.0
20.0
18.0
16.0
14.0
12.0
10.0
100 120 140 160 180 200 220 240 260 280 300
Total capacity of indoor units
2) Input
9.00
Cooling
8.00

7.00
Input(kW)

6.00 Heating

5.00

4.00

3.00
100 120 140 160 180 200 220 240 260 280 300
Total capacity of indoor units
PQRY-P250
1) Capacity
34.0
32.0
Heating
30.0
Cooling
28.0
Capacity(kW)

26.0
24.0
22.0
20.0
18.0
16.0
14.0
150 200 250 300 350
Total capacity of indoor units
2) Input
12.00
11.00 Cooling
10.00
Input(kW)

9.00
8.00
Heating
7.00
6.00

5.00
4.00
150 200 250 300 350
Total capacity of indoor units

1- 130
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction

WR2(R407C)
PQRY-P200 PQRY-P250
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor
100 125
0.9 0.9
150 188
200 250
0.8 0.8
300 375

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PQRY-P200 PQRY-P250
1.0 Total capacity 1.0 Total capacity
of indoor unit of indoor unit
100 125
Heating capacity

Heating capacity
correction factor

correction factor

0.9 150 0.9 188

200 or more 250 or more


0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PQRY-P200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PQRY-P250
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m

2-4. Operation limit

• Cooling •Heating
Indoor temperature (˚CWB)

Indoor temperature (˚CDB)

30 30

25 25

20 20

15 15

10 10
10 15 20 25 30 35 40 45 10 15 20 25 30 35 40 45

Water temperature (˚C) Water temperature (˚C)

(Indoor capacity 130% : Water temp. 15~45˚C) (Indoor capacity 130% : Water temp. 15~45˚C)

1- 131
3. Sound Levels
PQRY-P200

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


Measurement condition 70

1m
60
NC60
WR2(R407C)

50 NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
51 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

PQRY-P250
Measurement condition
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70
1m

60
NC60

50
NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
52 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

1- 132
1227
4-M12 Female screw
1177 4-ø14 Mounting hole
(for lifting bolt) Plane view
1120
Service space
<Accessory>

600
Note1 Water inlet (front side)
• Refrigerant (low pressure) conn. pipe · · · · · 1pc. (PT1 1/2 screw)
(The connecting pipe is fixed with the unit) 400
• Packing for conn. pipe · · · · · · · · · · · · · · · · 1pc. Note1 Water outlet

392
500
437
(Attached near the ball valve) ø39 Knockout hole (PT1 1/2 screw) Piping space

400

373
• Wiring mounting plate · · · · · · · · · · · · · · · · · 1pc. <piping hole> (left side pipe)

226
• Tapping screw M4 · · · · · · · · · · · · · · · · · · · 2pcs. Piping space

122
112

78
• Lifting bolt M12 · · · · · · · · · · · · · · · · · · · · · · 4pcs. Front view (upside pipe)

61
31

49
• Bushing · · · · · · · · · · · · · · · · · · · · · · · · · · · · 2pcs. ø60 Knockout hole 64 ø28 Knockout hole
<piping hole> 100 <Hole for the control
wiring>
PQRY-P200,250YEM-A

353
ø39 Knockout hole
693 <Hole for the power supply>

226 Plane view Fig. A


Water outlet
(PT1 1/2 screw) 107 1150

ø39 Knockout hole


4. External Dimensions

<Hole for the power supply>

ø28 Knockout hole


<Hole for the control
wiring> Refrig. service
225 valve(low pressure)
ø70 piping hole <flange>
130
Conn. pipe
200:ø25.4<brazed> ø28 Knockout hole
250:ø28.58<brazed> <Hole for the control

1- 133
78 wiring>
ø40 piping hole Refrig. service 163
122 valve 108
(high pressure)
ø19.05<flare>

1590
1670
373

1531
Water inlet 78
ø39 Knockout hole

1345
(PT1 1/2 screw) <Hole for the power

1260
supply>

1161
1076
Knockout hole

863
837
777

Note2
Drain(PT1 screw) Drain(PT1 screw)
257

25
80

Left side view Front view Right side view Rear view
Note1. At the time of product shipment, the left side piping specification serves as the local water piping connection.
When connecting to the upper piping, please remove the plug sealing corks from the upper piping connection,
and attach a left piping connection part.
Ensure there is no leak after the attachment has been fitted.
2. At the time of product shipment,the left side piping specification serves as the local drainage connection.
Unit : mm

When connecting on the right side, please remove the right side plug sealing corks, and attach a left side.
Ensure there is no leak after the attachment has been fitted.
3. Take notice of service space as Fig A.

WR2(R407C)
5. Electrical Wiring Diagram
PQRY-P200, 250YEM-A
Motor
Inverter MC1 (Compressor)
U V W
Controller Box
Red White Black

FB1
F5 SNB board
600VAC
8A F ACCT
F6 L1 -W
600VAC
ACCT
WR2(R407C)

8A F
L2 -U

L3 EARTH
BOX BODY

Terminal Noise Terminal Diode


Block NF Filter Block stack
TB1A TB1B DS R1 R5 IPM
L1 L1 Red L1 L1 Red L1 Red ZNR4
~+ +
U V W
Power source C2 R2
3N~ L2 L2 White L2 L2 White L2 White
~
C1 P
+
380/400/415V 52C
C3 R3
DCL
50/60Hz L3 L3 Black L3 L3 Black L3 Black
~- Gate amp board
(G/A board)
N N Blue N N Blue N Blue N
Green/
PE Yellow

BOX BODY
PE BOX BODY CNE CNDC1 CNDR1 CN15V1
TB3 F3
250VAC (2P) (4P) (9P) (14P)
Connect to M1 1A F 1 2 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Indoor and
remote M2
controller CNTR1 FB2
BOX BODY

Orange

Orange
Yellow
BOX BODY

Purple
Brown

Brown
M1

White
Black

Black

Gray
T01

Red

Red
Green

White
M2

Blue
S CN20
CNAC3 (3P) 1 1 CNAC2
(4P) 123 12 1 2 3 1 2 3 2 2 5 4 3 2 1 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
TB7 4 CNRS3 34 3 (5P)
CNS2 CNS1 CNTR 4 CNRS2 CNVDC CNDR2 CN15V2
AC4 (3P) (2P) F1 (3P) (7P) 5 5 (7P) (4P) (9P) (14P)
3 250VAC 6 6
(to CNAC4) 2 2A F 7 7
AC1 F01
1 250VAC
CNVCC4 1 1 CNVCC4
(2P) 2 2 (2P) 2A F

1 1
CNVCC3 3
2 2
3 CNVCC2
Power circuit board 1
(6P) 4
5
4 (6P)
5
(INV board) CNACCT 2
(4P) 3
CH1 3
6 6
4
X10
Crank case heater 2 CN32 1 1
(Compressor) 1 (3P) X01 2
3
2 X01
52C 3
3 CNX10
SV1 (3P) CN52C CNTH CNR CNL2 CN30V
2 CN33 X02 (2P) (3P) (2P) (2P)
X02 (3P)
1 (3P) 1 2 3
CNFAN 1 2 1 2 3 12 12
(3P)
6
5

SV2 21S4
4 CN34
3 (6P)
X04
CN3D 23 DEMAND MF1
2 (3P) 1
1 X05
THHS R7 L2 R6
1 BOX BODY
12V 2
3
4 4:Compressor ON/OFF
5
5:SW3-3 OFF:water freeze signal
CN51
6
5
Control circuit board (5P) ON :trouble signal

SV4 SV3 4 CN36


X06 (MAIN board)
3 (6P)
2
1 X07
(to CNAC3)
6 AC4 AC1
5

SV6 SV5
4 CN37
3 (6P)
X08
CNAC4 CN81
2
1 X09 (4P) 4 3 2 1 X21 9(9P)
X22 87
X23 65
CN38 X10 4 SV73 SV72 SV71
(3P) 3
63H 1 2
High pressure 2 CNPW
(4P) 1
switch 3 detection
circuit CN63PW 32
4 4
3 CN83
26W 5 Refer to the service handbook (4P) 1
2
(7P) TB8
Freeze protect 4 1
7 4 63PW
switch 3 detection about the switch operations. detection 5 3 Pump interlock
2
1
circuit 6
6 circuit 3 2
5
5 1 1 Unit ON/OFF
CNRT1 CNOUT1 4 4 CNOUT2 X25
(5P) CN12 CN09 CN06 CN03 CN02 CN01 CNH CNL CNLV1 CNLV2 (6P) 3 3 (6P)
(2P) (2P) (2P) (3P) (8P) (2P) (3P) (3P) (5P) (5P) 2
2
12 12 12 123 12345678 12 1 2 3 1 2 3 12345 1234 5 1
1
RELAY board
White

White
Black
Black

Red
Red

3 2 1 3 2 1 SLEV LEV2

THINV TH10 TH9 TH6 TH2 TH1 63HS 63LS

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name Symbol Name
DCL DC reactor (Power factor improvement) Solenoid valve 63LS Low pressure sensor Thermistor Outlet temp. detect of
SV3~6 THINV heat exchanger for inverter
ACCT-U,W Current Sensor (Heat exchanger capacity control) L2 Choke coil (Transmission)
ZNR4 Varistor Solenoid valve IPM Intelligent power module THHS Radiator panel temp. detect
SV71~73
52C Magnetic contactor (Inverter main circuit) (Heat exchanger capacity control) TH1 Thermistor Discharge pipe temp. detect X1~10
X21~25 Aux. relay
MF1 Fan motor (Radiator panel) Electric expansion valve TH2 Saturation evapo. temp. detect
LEV2
21S4 4--way valve (Heat exchanger for inverter) TH6 OA temp. detect FB1~2 Ferrite core
SV1,SV2 Solenoid valve (Discharge--suction bypass) SLEV Electronic expansion valve(Oil return) TH9 High pressure liquid temp.
Earth terminal
63HS High pressure sensor TH10 Compressor shell temp.

1- 134
6. Refrigerant Circuit Diagram And Thermal Sensor
PQRY-P200, 250

4way valve
ST
: Strainer
CV
ST2 : Check valve

WR2(R407C)
SP1 Solenoid Valves SP
High pressure Block
: Service port
sensor Distributor ST8 SV

ST5
: Solenoid valve
SV3
SV4 SV6 TH
SV73 SV5
CV11
: Thermal sensor
CP
Oil : Capillary
separator
LEV
CP1
ST6
: Liner valve expansion
BV
SV1 : Ball valve
TH1 CJ2
CV1
SV2
SV72 CV7
High pressure Water heat exchanger
switch (Double coil type)
Compressor
TH6
Accumulator Water
TH10 circulating

ST4 SLEV SV71


CP4
Air heat exchanger ST7a ST7b ST7c ST7d

TH INV
LEV2 TH2
Low presser sensor CV8 CV9 CV10
CV4 CV5 CV2 CV3 BV1
ST1
TH9 CV6

Drier BV2
Check Valves Block Orifice

SVC

SVA
SVB

Gas/liquid separator

TH23

TH12

TH21
Indoor
TH11 units
TH22

63HS1
LEV
LEV1

63HS3

TH15

LEV3

TH16
BC controller
CMB-P104V-E

1- 135
7. System design guide
7-1. Designing of water circuit system

1) Example of basic water circuit


The water circuit of the water heat source CITY MULTI auxiliary heat source and cooling tower is not required.
connects the heat source unit with the cooling In order to control the above thermal balance properly
WR2(R407C)

tower/auxiarily heat source/heat storage tank/circulation and use thermal energy effectively, utilizing of heat stor-
pump with a single system water piping as shown in the age tanks, and night-time discounted electric power as a
figure below. The selector valve automatically controls to auxiliary heat source will be economical.
circulate water toward the cooling tower in the cooling Meantime as this system uses plural sets of heat source
season, while toward the heat storage tank in the heat- unit equipped with water heat exchangers, water quality
ing season. If the circulation water temperature is kept in control is important. Therefore it is recommended to use
a range of 10~45˚C* regardless of the building load, the closed type cooling towers as much as possible to pre-
water heat source CITY MULTI can be operated for vent the circulation water from being contaminated.
either cooling or heating. Therefore in the summer when When open type cooling towers are used, it is essential
only cooling load exists, the temperature rise of circula- to provide proper maintenance control such as that to
tion water will be suppressed by operating the cooling install water treatment system to prevent troubles
tower. While in the winter when heating load increases, caused by contaminated circulation water.
the temperature of circulation water may be dropped
below 10˚C. Under such situation, the circulation water *15~45˚C : 50%~150% of indoor units can be connected
will be heated with the auxiliary heat source if it drops *10~40˚C : 50%~130% of indoor units can be connected
below a certain temperature.
When the thermal balance between cooling and heating
operation is in a correct proportion, the operation of the

Example of basic water circuit for water heat source CITY MULTI

C.T

E.H

C.T.P
S.T
P T T
3-way valve

S.T : Heating tank


(Heat storage tank)
C.T : Cooling tower
C.T.P : Cooling water pump
P : Circulation water pump
T : Thermostat for water
E.H : Electric heater
: Heat source unit for cooling
operation
: Heat source unit for heatin
operation

The indoor unit and refrigerant piping system are excluded in this figure.

1- 136
2) Cooling tower
a) Types of cooling tower
The cooling towers presently used include the open type
Types of cooling towers
cooling tower, open type cooling tower + heat exchang-
er, closed type cooling tower, and air-cooled type cooling Closed type

WR2(R407C)
tower. However, as the quality control of circulation water
is essential when units are installed in decentralized
state inside a building, the closed type cooling tower is
generally employed in such case.
Although the circulation water will not be contaminated
by atmospheric air, it is recommended to periodically
blow water inside the system and replenish fresh water
instead.
In a district where the coil may be frozen in the winter, it Air-cooled type
is necessary to apply antifreeze solution to the circula-
tion water, or take freeze protection measures such as to
automatically discharge water inside the cooling coil at
the stopping of the pump.
When the open type cooling tower is used, be sure to
install a water quality control device in addition to the
freeze protection measures, as the water may be deteri-
orated by atmospheric contaminants entered into the
cooling tower and dissolved into the circulation water.

b) Calculation method of cooling tower capacity


All units of the water heat source CITY MULTI may pos- It is determined in accordance with the value obtained by
sibly be in cooling operation temporarily (at pulling adding the maximum cooling load of an actual building,
down) in the summer, however, it is not necessary to the input heat equivalent value of all CITY MULTI units,
determine the capacity according to the total cooling and the cooling load of the circulating pumps. Please
capacity of all CITY MULTI units as this system has a check for the values of the cooling water volume and cir-
wide operating water temperature range culation water volume.
15~45˚C : 130% over
( 10~45˚C : 130% or less ).

Qc + 860 x (∑Qw + Rw)


Cooling tower capacity = (Refrigeration ton)
3,900

Qc : Maximum cooling load under actual state (kcal/h)


Qw : Total input of water heat source CITY MULTI at simultaneous operation under max-
imum state (kW)
Pw : Shaft power of circulation pumps (kW)

1- 137
3) Auxiliary heat source and heat storage tank
When the heating load is larger than the cooling load, The effective temperature difference of an ordinary heat
the circulation water temperature lowers in accordance storage tank shows about 5deg. even with the storing
with the heat balance of the system. It should be heated temperature at 45˚C.
by the auxiliary heat source in order to keep the inlet However with the water heat source CITY MULTI, it can
water temperature within the operating range be utilized as heating heat source up to 15˚C with an
WR2(R407C)

15˚C or more : 130% over effective temperature of a high 30deg. approximately,


( 10˚C or more : 130% or less )
thus the capacity of the heat storage tank can be mini-
of the water heat source CITY MULTI. mized.
Further in order to operate the water heat source CITY
MULTI effectively, it is recommended to utilize the heat
a)Auxiliary heat source
The following can be used as the auxiliary heat source.
storage tank to cover the warming up load in the morn-
• Boiler (Heavy oil, kerosine, gas, electricity)
ing and the insufficient heat amount.
• Electric heat (Insertion of electric heater into heat stor-
Effective heat utilization can be expected to cover insuf-
age tank)
ficient heat at the warming up in the next morning or
• Outdoor air (Air-heat source heat pump chiller)
peak load time by storing heat by installing a heat stor-
• Warm discharge water (Exhaust water heat from
age tank or operating a low load auxiliary heat source at
machines inside building and hot water supply)
the stopping of the water heat source CITY MULTI. As it
• Utilization of night-time lighting
can also be possible to reduce the running cost through
•Solar heat
the heat storage by using the discounted night-time elec-
Please note that the auxiliary heat source should be
tric power, using both auxiliary heat source and heat
selected after studying your operating environment and
storage tank together is recommended.
economical feasibility.

Determining the auxiliary heat source capacity


For the CITY MULTI water heat source system, a heat However the auxiliary heat source capacity should be
storage tank is recommended to use. When employment determined by the daily heating load including warming
of the heat storage tank is difficult, the warming up oper- up load on the week day.
ation should be arranged to cover the starting up heat- For the load at the next morning of the holiday, heat stor-
ing load. Since the holding water inside the piping circuit age is required by operating the auxiliary heat source
owns heat capacity and the warming up operation can even outside of the ordinary working hour.
be assumed for about one hour except that in a cold
region, the heat storage tank capacity is required to be
that at the maximum daily heating load including the
warming up load at the next morning of the holiday.

When heat storage tank is not used


1
QH = HCT (1- ) - 1000 x Vw x ∆T - 860 x Pw
COPh

QH : Auxiliary heat source capacity (kcal/h)


HCT : Total heating capacity of each water heat source CITY MULTI (kcal/h)
COPH : COP of water heat source CITY MULTI at heating
VW : Holding water volume inside piping (m3)
∆T : Allowable water temperature drop = TWH - TWL (˚C)
TWH : Heat source water temperature at high temperature side (˚C)
TWL : Heat source water temperature at low temperature side (˚C)
PW : Heat source water pump shaft power (kW)

1- 138
When heat storage tank is used;

1
HQ1T = (1- COPh
) - 860 x Pw x T2
QH = xK (Kcal)
T1

WR2(R407C)
QH1T : Total of heating load on weekday including warming up (kcal/day)
T1 : Operating hour of auxiliary heat source (h)
T2 : Operating hour of heat source water pump (h)
K : Allowance factor (Heat storage tank, piping loss, etc.) 1.05~1.10

HQ1T is calculated from the result of steady state load calculation similarly by using the equation below.
HQ1T = 1.15 x (∑Q'a + ∑Q'b + ∑Q'c + ∑Q'd + ∑Q'f) T2 - ψ (∑Qe1 + ∑Qe2 + ∑Qe3) (T2 - 1)

Q'a : Thermal load from external wall/roof in each zone (kcal/h)


Q'b : Thermal load from glass window in each zone (kcal/h)
Q'c : Thermal load from partition/ceiling/floor in each zone (kcal/h)
Q'd : Thermal load by infiltration in each zone (kcal/h)
Q'f : Fresh outdoor air load in each zone (kcal/h)
Q'e1 : Thermal load from human body in each zone (kcal/h)
Q'e2 : Thermal load from lighting fixture in each zone (kcal/h)
Q'e3 : Thermal load from equipment in each zone (kcal/h)
ψ : Radiation load rate 0.6~0.8
T2 : Air conditioning hour

b) Heat storage tank


Heat storage tank can be classified by types into the sidering corrosion problems.
open type heat storage tank exposed to atmosphere, The capacity of heat storage tanks is determined in
and the closed type heat storage tank with structure sep- accordance with the daily maximum heating load that
arated from atmosphere. Although the size of the tank includes warming up load to be applied for the day after
and its installation place should be taken into account, the holiday.
the closed type tank is being usually employed by con-

When auxiliary heat source is operated during operation and even after stopping of water heat source CITY MULTI unit

1
HQ2T (1- COPh
) - 860 x Pw x T2 - QH x T2
V= (ton)
∆T x 1000 x ηV

When auxiliary heat source is operated after stopping of water heat source CITY MULTI unit
1
HQ2T (1- COPh
) - 860 x Pw x T2
V= (ton)
∆T x 1000 x ηV

HQ2T : Maximum heating load including load required for the day after the holiday (kcal/day)
∆T : Temperature difference utilized by heat storage tank (deg)
ηV : Heat storage tank efficiency

HQ2T : 1.3 x (∑Q'a + ∑Q'c + ∑Q'd + ∑Q'f) T2 - ψ(∑Qe2 + ∑Qe3) (T2 - 1)

1- 139
4) Piping system
The following items should be kept in your mind in plan- tank to absorb the expansion/contraction of water
ning / designing water circuits. caused by temperature fluctuation.

a) All units should be constituted in a single circuit in princi- e) If the operating temperature range of circulation water
ple. stays within the temperature near the normal tempera-
WR2(R407C)

ture (summer : 30˚C, winter : 20˚C), thermal insulation or


b) When plural numbers of the water heat source CITY anti-sweating work is not required for the piping inside
MULTI unit are installed, the rated circulating water flow buildings.
rate should be kept by making the piping resistance to
each unit almost same value. As an example, the In case of the conditions below, however, thermal insu-
reverse return system as shown below may be lation is required.
employed.
• When well water is used for heat source water.
c) Depending on the structure of a building, the water circuit • When piped to outdoor or a place where freezing may be
may be prefabricated by making the layout uniform. caused.
• When vapor condensation may be generated on piping
d) When a closed type piping circuit is constructed, install an due to an increase in dry bulb temperature caused by
expansion tank usable commonly for a make-up water the entry of fresh outdoor air.

System example of water circuit

Heating tank
Cooling tower
Pump 3-way valve
Backflow prevention valve Strainer

Flexible joint

Refregerant piping To indoor unit 3-way valve

BC controller BC controller BC controller BC controller

Refregerant piping

Joint
Valve
Heat Heat Heat Heat
source source source source
unit unit unit unit

Y-shape strainer

Drain

1- 140
5) Cleaning of water heat exchanger
For the water heat exchanger, scale adheres in less dure given below.
amount generally in the case of closed type cooling tow- The cleaning work procedure generally used is as fol-
ers. However in a long period of use, scale will adhere lows. However as the cleaning agents have various dif-
that may lower the heat exchange capacity and increase ferences in their cleaning effect, corrosion characteris-
the water resistance. tics, processing time, and condensation for use, conduct

WR2(R407C)
In such case, conduct cleaning work under the proce- the work after consulting the relating maker.

Acid washing Water washing Neutralization Water washing Applying inhibitor

a)Still standing method


This method feeds the raw liquid or diluted solution of • Fully recover the cleaning liquid through the water dis-
cleaning agent into the water circuit and leave it for a charge plug of the heat exchanger, and then fully clean
while, and requires only a simple device. the water circuit with clean water. If the water washing
can not be made sufficiently, neutralization processing
• Since the cleaning time required differs by the agent of will be effective.
each maker, be sufficiently careful for the time and not
to exceed the time specified.

Still standing cleaning device

Cleaning agent

Hose

To be closed

Water discharge plug


T-joint : When no exclusive T-joint is
available, use the connection
of the thermometer or the like.

1- 141
b)Circulation method
Although this method can clean in shorter time than that • Check for the connections of piping beforehand so that
required by the still standing method, be careful that the cleaning agent will not leak from the piping during
circulation pump may be damaged if using cleaning cleaning work.
agent with strong corrosive characteristics. • Start cleaning operation after fully mixing the cleaning
agent with water.
WR2(R407C)

• After completing washing work, fully recover the wash- • Cleaning at the earlier timing is recommended as the
ing liquid through the water discharge plug installed at removal of scale will be difficult if it has accumulated
the bottom of the piping and that at the heat exchanger. seriously. Periodical cleaning is necessary in a district
• Conduct water washing for three times or more after with inferior water quality.
removing cleaning agent. If this can not be made satis- • Conduct water washing sufficiently with clear water after
factorily, apply neutralization treatment. Full replace- cleaning work as all cleaning agents own strong acidity.
ment of water can be ascertained by measuring the PH • To verify the completion of cleaning, remove the hose
of the water. and observe the inner wall of the piping whether it is
• Note that it may be required to control the cleaning time clean.
depending on the scale generation or water quality. • Be sufficiently careful for fire when using inflammable
• At cleaning work, remove or shut down the instruments cleaning agent (GOSPEL R).
like water pressure gauges so that the cleaning liquid
will not enter into them.

Circulation method cleaning device

Hose
Filtration net

Cleaning agent

Tank
To be closed

Hose
T-joint

To be closed

T-joint
Pump
Water discharge plug
Water discharge plug

Example of cleaning agents


Name Shape Condensation Time Makers
CLEARLITE RK Powder/Liquid 10~20% 2~3Hr. Koei Kagaku
CLEARLITE ACE Powder/Liquid 3~5% 1~3Hr. Koei Kagaku
GOSPEL R Liquid
Gospel Kako
GOSPEL SR Powder 7%
ADDITION DR Powder 1~4Hr. Marusan
SS-100 Liquid
( Upper limit 10%,
lower limit 5%
)
Seiwa kogyo
NEOLUX F Powder
DISCALER Powder 4~7% Saver Kagaku

1- 142
6) Practical System Examples and Circulation
Water Control
Since the water heat source CITY MULTI is of water heat source CITY MULTI stays within a range of 15~45˚C.
source system, versatile systems can be constituted by However, the circulation water temperature near 32˚C for
combining it with various heat sources. cooling and 20˚C for heating is recommended by taking
The practical system examples are given below. the life, power consumption and capacity of the air con-

WR2(R407C)
Either cooling or heating operation can be performed if ditioning units into consideration. The detail of the con-
the circulation water temperature of the water heat trol is also shown below.

Example-1 Combination of closed type cooling tower and hot water heat storage tank (using underground hollow slab)

Expansion tank
Closed type
Cooling water pump cooling tower

Circulation
water pump

V1

XS T1

Heat
source
unit

T2

V2

EH
Heat exchanger MG

T1~T4 : Thermostat
Heat storage T4
V1~V2: Proportional type
motor-driven 3-way valve tank pump
V3 Auxiliary
V3 : Motor-driven 3-way valve
XS : Auxiliary switch heat source
MG : Magnetic switch
EH : Electric heater

Heat storage tank T3

By detecting the circulation water temperature of the water heat source CITY MULTI system with T1 (around 32˚C) and
T2 (around 20˚C), the temperature will be controlled by opening/closing V1 in the summer and V2 in the winter.
In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
open to lower the circulation water temperature. While in the winter, as the circulation water temperature drops, V2 will
open following the command of T2 to rise the circulation water temperature.
The water inside the heat storage tank will be heated by the auxiliary heat source by V3 being opened with timer opera-
tion in the night-time. The electric heater of the auxiliary heat source will be controlled by T3 and the timer. The start/stop
control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and pump follow-
ing the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan and pump at
the maximum load thus controlling water temperature and saving motor power.

1- 143
Example-2 Combination of closed type cooling tower and hot water heat storage tank

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat
WR2(R407C)

T3 : Proportional type, insertion system thermostat


V1 : Proportional type, motor-driven 3-way valve
V2 : Proportional type, motor-driven 3-way valve
XS : Auxiliary switch (Duplex switch type)
SC : Step controller
R : Relay
MG : Magnetic
SC MG
Hot water heat
Closed type storage tank
cooling tower

T3

CV

V1

XS

V2

R T2
Heat source
Pump interlock water pump
Heat
source
unit

=In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1
will open to lower the circulation water temperature. In the winter, if the circulation water temperature stays below 25˚C,
V2 will open/close by the command of T2 to keep the circulation water temperature constant.
The temperature of the hot water inside the heat storage tank will be controlled through the step control of the electric
heater by step controller operation following the command of T3.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking thus pre-
venting the high temperature water from entering into the system at the starting of the pump.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and
pump following the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan
and pump at the maximum load thus controlling water temperature and saving motor power.

1- 144
Example-3 Combination of closed type cooling tower and boiler

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat

WR2(R407C)
T3 : Proportional type, insertion system thermostat
V1 : Proportional type, motor-driven 3-way valve
S : Selector switch
R : Relay
XS : Auxiliary switch (Duplex switch type)

Closed type
cooling tower

XS
V1
Relay board

Heat T1
source
unit

Pump interlock Boiler


Heat source
water pump V2

T2

In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 25˚C, V2 will
conduct water temperature control to keep the circulation water temperature constant.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the com-
mand of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.

1- 145
Example-4 Combination of closed type cooling tower and heat exchanger (of other heat source)

T1 : Proportional type, insertion system thermostat


T2 : Proportional type, insertion system thermostat
WR2(R407C)

V1 : Proportional type, motor-driven 3-way valve


V2 : Proportional type, motor-driven 3-way valve
S : Selector switch
R : Relay
XS : Auxiliary switch (Duplex switch type)

Closed type
cooling tower

XS
V1
Relay board

Heat T1
source
unit

Heat exchanger

Other heat source water


V2

Heat source
water pump

T2

In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 26˚C, V2
will conduct water temperature control to keep the circulation water temperature constant.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the
command of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.

1- 146
7) Pump interlock circuit

Heat source • Plural indoor units (8HP:15sets, 16HP:16sets maximum) being connected to
equipment
a single refrigerant system can be controlled individually.
• The transmission line is of a jumper wiring system using non-polar 2 wires.

WR2(R407C)
Refrigerant piping
BC controller
Transmisson line

Water
circuit Indooor Indooor Indooor Indooor
unit unit unit unit

Remote controller
Room-A Room-B Room-C Room-D

Heat source
water pump
(MP)

Site control panel


(Remote controller
operation at two spot)
Room-E Room-F Room-G

Wiring diagram

This circuit uses the “Terminal block for pump interlock (TB8)“ inside the electrical parts box of the heat source equipment.
This circuit is for interlocking of the heat source equipment operation and the heat source water pump.
L N
Site control panel ~ / N 240/230/220V

Heat source equipment MCB

TB8
1
X : Relay
2 TM1, 2 : Timer relay
3
(closes after elapsing
the set time when it is
4 powered, while opens
TM1 promptly when it is not
powered)
Heat source equipment 52P : Magnetic contactor
52P TM1 TM2 for heat source
water pump
TB8 52P
MP : Heat source
1
water pump
2 MCB : Circuit breaker
3
*Remove the short circuit
4 wire between 3 and 4
TM2 when wiring to TB8.

MP
To next equipment

1- 147
Operation ON signal

Terminal No. TB8-1, 2

Relay contacts output Rated voltage : L1 - N : 220 ~ 240V


Output
WR2(R407C)

Rated load : 1A
• When Dip switch 2-7 is OFF
Operation The relay closes during compressor operation.
• When DIP switch 2-7 is ON.
The relay closes during reception of cooling or the heating operation signal from the controller.
(Note : It is output even if the thermostat is OFF (when the compressor is stopped).)

Pump Interlock

Terminal No. TB8-3, 4


Input Level signal
Operation If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.

1- 148
7-2.WATER PIPING WORK
Although the water piping for the CITY MULTI WR2 system does not differ from that for ordinary air conditioning
systems, pay special attention to the items below in conducting the piping work.

1) Items to be observed on installation work Installation example of heat source unit


• In order to equalize piping resistance for each unit, adapt

WR2(R407C)
Refrigerant
the reverse return system. piping
Water
• Mount a joint and a valve onto the water outlet/inlet of the outlet

unit to allow for maintenance, inspection and replace- Circulation Stop valve
water main
ment work. Be sure to mount a strainer at the water inlet
piping of the unit. (The strainer is required at the circula-
Stop valve
tion water inlet to protect the heat source unit.)
* The installation example of the heat source unit is shown
right.
Y-shape
• Be sure to provide an air relief opening on the water pip- strainer Water
inlet
ing properly, and purge air after feeding water to the pip-
ing system.
• Condensate will generate at the low temperature part
inside the heat source equipment. Connect drain piping
Drain
to the drain piping connection located at the bottom of pipe

the heat source equipment to discharge it outside the


equipment. 3) Water treatment and water quality control
• At the center of the header of the heat exchanger water For the circulation water cooling tower of the CITY
inlet inside the unit, a plug for water discharge is being MULTI WR2 system, employment of the closed type is
provided. recommended to keep water quality. However, in the
Use it for maintenance work or the like. case that an open type cooling tower is employed or the
• Mount a backflow prevention valve and a flexible joint for circulating water quality is inferior, scale will adhere onto
vibration control onto the pump. the water heat exchanger leading to the decreased heat
• Provide a sleeve to the penetrating parts of the wall to exchange capacity or the corrosion of the heat exchang-
prevent the piping. er. Be sufficiently careful for water quality control and
• Fasten the piping with metal fitting, arrange the piping not water treatment at the installation of the circulation water
to expose to cutting or bending force, and pay sufficient system.
care for possible vibration. • Removal of impurities inside piping
• Be careful not to erroneously judge the position of the Be careful not to allow impurities such as welding frag-
inlet and outlet of water. ment, remaining sealing material and rust from mixing
(Lower position : Inlet, Upper position : Outlet) into the piping during installation work.
• Water treatment
2) Thermal insulation work The water quality standards have been established by
Thermal insulation or antisweating work is not required the industry (Japan Refrigeration, Air Conditioning
for the piping inside buildings in the case of the CITY Industry Association, in case of Japan) for water treat-
MULTI WR2 system if the operating temperature range ment to be applied.
of circulation water stays within the temperature near the
normal (summer : 30˚C, winter : 20˚C). Items Standard values
PH(25˚C) 7.0 ~ 8.0
In case of the conditions below, however, thermal insu-
Electric conductivity (25˚C)(µs/cm) 300 or less
lation is required.
Chlorine ion CI- (mg/l) 50 or less
• Use of well water for heat source water Standard items Sulfate ion SO42- (mg/l) 50 or less
• Outdoor piping portions M-alkalinity CaCO3 (mg/l) 50 or less
• Indoor piping portions where freezing may be caused in Total hardness CaCO3 (mg/l) 70 or less
winter Iron Fe (mg/l) 1.0 or less

• A place where vapor condensation may be generated on Sulfur ion S2- (mg/l) Not be detected
Reference items Ammonium ion NH4+ (mg/l) Not be detected
piping due to an increase in dry bulb temperature inside Note.1
Silica SiO2 (mg/l) 30 or less
the ceiling caused by the entry of fresh outdoor air
Note.1 It is clearly found that the component of the reference items will
• Drain piping portions be hazardous, however, the quantitative relationship between
the content and hazard has not been clarified yet. Therefore,
they are listed as the reference items.

1- 149
In order to keep the water quality within such standards,
you are kindly requested to conduct bleeding-off by over-
flow and periodical water quality tests, and use inhibitors
to suppress condensation or corrosion. Since piping may
be corroded by some kinds of inhibitor, consult an appro-
priate water treatment expert for proper water treatment.
WR2(R407C)

(4) Pump interlock


Operating the heat source unit without circulation water
inside the water piping can cause a trouble. Be sure to
provide interlocking for the unit operation and water cir-
cuit. Since the terminal block is being provided inside the
unit, use it as required.

1- 150
PUMY-71VM
PUMY-125VMA
CONTENTS

S-VM(R22)
1. Specifications ································································· 1-152

2. Capacity Tables ······························································ 1-154


2-1 Correction by temperature ············································ 1-154
2-2 Correction by total indoor ············································· 1-156
2-3 Correction by refrigerant piping length ··························· 1-157
2-4 Correction at frosting and defrosting ···························· 1-158
2-5 Operation limit ······························································· 1-158

3. Sound Levels ·································································· 1-159

4. External Dimensions ···················································· 1-160

5. Electrical Wiring Diagram ·············································· 1-162

6. Refrigerant Circuit Diagram ········································· 1-164


And Thermal Sensor

1- 151
1. Specifications

PUMY-71VM
Model name
Cooling Heating

kcal/h 7,100 8,000

Capacity kW 8.3 9.3

BTU/h 28,200 31,800

Power source ~/N 220-230-240V 50Hz / 220V 60Hz


S-VM(R22)

Power input kW 3.50/3.63 3.65/3.53

Current A 17.5-16.7-16.0/18.1 18.2-17.4-16.0/17.6

Type ✕ Quantity Propeller fan ✕ 2

Fan Airflow rate m3/min 95

Motor output kW 0.04 ✕ 2

Type Hermetic

Compressor Motor output kW 2.6

Crankcase heater kW –

Refrigerant / Lubricant R22/MS56

External finish Steel plate painting with polyester powder


<MUNSELL 5Y8/1>
External dimension mm 1200(H)✕900(W)✕320(+30)(D)

High pressure protection 3.0MPa


Protection
Compressor / Fan Internal thermal switch / Internal thermal switch
devices
Inverter Over current protection, Overheat protection

Refrigerant piping diameter Liquid / Gas ø 9.52 /ø 15.88 (Flare)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 80 / 1 ~ 4

Noise level ✻ dB<A> 52

Net weight kg 93

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range
Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 21˚CDB Outdoor : 7˚CDB/6˚CWB
Pipe length : 5m Height difference : 0m

✻ It is measured in anechoic room.

1- 152
PUMY-125VMA
Model name
Cooling Heating

kcal/h 12,500 14,000

Capacity kW 14.5 16.3

BTU/h 49,600 55,600

Power source ~/N 220-230-240V 50Hz / 220V 60Hz

Power input

S-VM(R22)
kW 6.57/6.43 6.10/6.03

Current A 34.9-33.5-32.2/33.6 32.6-31.2-29.9/31.5

Type ✕ Quantity Propeller fan ✕ 2

Fan Airflow rate m3/min 90

Motor output kW 0.06 ✕ 2

Type Hermetic

Compressor Motor output kW 3.5

Crankcase heater kW –

Refrigerant / Lubricant R22/MS32(N-1)

External finish Steel plate painting with polyester powder


<MUNSELL 5Y8/1>
External dimension mm 1280(H)✕1020(W)✕350(+30)(D)

High pressure protection 3.0MPa


Protection
Compressor / Fan Internal thermal switch / Internal thermal switch
devices
Inverter Over current protection, Overheat protection

Refrigerant piping diameter Liquid / Gas ø9.52 /ø19.05 (Flare)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 125 / 1 ~ 8

Noise level ✻ dB<A> 54

Net weight kg 130

Operating temperature range Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 21˚CDB Outdoor : 7˚CDB/6˚CWB
Pipe length : 5m Height difference : 0m

✻ It is measured in anechoic room.

1- 153
2. Capacity Table
2-1. Correction by temperature
Cooling
• Standard Specifications

PUMY-71 PUMY-125
Capacity kW 8.3 14.5
Input kW 3.50 / 3.63 6.57 / 6.43
S-VM(R22)

Capacity at 100% indoor units running

1.20

1.10
Ratio

22˚CWB
1.00
20˚CWB

0.90 Indoor Temperature(˚CWB) 18˚CWB

16˚CWB

0.80
-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.40

1.20 22˚CWB
20˚CWB
18˚CWB
16˚CWB
1.00
Ratio

Indoor Temperature(˚CWB)

0.80

0.60

0.40
-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

1- 154
Heating
• Standard Specifications

PUMY-71 PUMY-125
Capacity kW 9.3 16.3
Input kW 3.65/3.53 6.10/6.03

S-VM(R22)
Capacity at 100% indoor units running
1.30
15˚CDB
1.20
20˚CDB
1.10

1.00 Indoor Temperature(˚CDB) 25˚CDB


Ratio

0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.20

1.10 20˚CDB

Indoor Temperature(˚CDB) 15˚CDB


1.00
Ratio

25˚CDB
0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 155
2-2. Correction by total indoor

PUMY-71
1) Capacity 9,000
Heating
8,000
Cooling
Capacity(kW)

7,000

6,000

5,000
S-VM(R22)

4,000
40 50 60 70 80 90 100
Total capacity of indoor units
2) Input 4.00
60Hz
Cooling
50Hz
3.50
50Hz
Heating
Input(kW)

60Hz
3.00

2.50

2.00
40 50 60 70 80 90 100
Total capacity of indoor units

PUMY-125
1) Capacity 16,000

Heating
14,000
Cooling
Capacity(kW)

12,000

10,000

8,000

6,000
60 80 100 120 140 160 180
Total capacity of indoor units

2) Input 7.00
50Hz
60Hz
Cooling
6.00
50Hz
Heating
5.00 60Hz
Input(kW)

4.00

3.00

2.00
60 80 100 120 140 160 180
Total capacity of indoor units

1- 156
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PUMY-71 PUMY-125
1.0 1.0
Total capacity of indoor unit Total ca
pacity
of indo
or unit
35
Cooling capacity

Cooling capacity
correction factor

correction factor
63
0.9 53 0.9
71 94
93 125

S-VM(R22)
0.8 0.8 163

0.7 0.7
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PUMY-71 PUMY-125
1.0 1.0
Heating capacity

Heating capacity
correction factor

correction factor

0.9 0.9

0.8 0.8

0.7 0.7
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PUMY-71
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.3 ✕ number of bent on the piping)m
➁ PUMY-125
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 ✕ number of bent on the piping)m

1- 157
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95

2-5. Operation limit


S-VM(R22)

• Cooling
Indoor temperature (˚CWB)

30

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25

20

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 158
3. Sound Levels
PUMY-71
Measurement condition 70

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
60
NC60

50 NC50
1m

40

S-VM(R22)
NC40

Sound pressure level in anechoic room 30


NC30
57 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

PUMY-125
Measurement condition 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m

60
NC60

50
NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
58 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 159
S-VM(R22)

Air intake

Air intake

Terminal block for transmission


Air outlet
Terminal block for central remote control
PUMY-71VM

Terminal block for Power source Optional parts


Handle for moving (base branching
pipe) installation
hole
Optional parts
Side air intake installation hole

Handle for
Rear air intake
Service panel
moving
4. External Dimensions

Handing for moving

Gas refrigerant-pipe
connection ø 15.88(5/8F)
Liquid refrigerant-pipe
connection ø 9.52(3/8F)

1- 160
Knock out hole for right piping
Rear piping hole Knock out holes for
Knock out hole power line 2-ø 27
for front piping
Piping cover Knock out holes fo power line 2-ø 27

Oval holes
(standard bolt M10)

Bottom piping hole

shaped notched holes


(standard bolt M10)
Drain hole
(3-ø 33 hole)
✻1...Indicates the dimensions of the cutoff valve connector.
Unit : mm

✻2...Make sure that the panel can be easily removed for maintenance
when a piping cover is used for aesthetic reasons.
Air intake

Air intake

Air outlet Teminal block for transmission


PUMY-125VMA

Teminal block for central remote control


Optional parts
Terminal block for power source (base branching
Handle for moving pipe) installation
hole
Optional parts
installation hole
Side air intake

Rear air intake


Handle for
moving

Gas refrigerant-pipe
connection ø 19.05 (3/4F)

1- 161
Liquid refrigerant pipe
connection ø 9.52 (3/8F)

Knock out hole for right piping


Rear piping hole Knock out holes for
Knock out hole for power line 2-ø 27
front piping
Piping cover Knock out holes for power line 2-ø 29

Oval holes
(standard bolt M10)

Bottom piping hole

shaped dotched holes


(standard bolt M10)
✻1...Indicates the dimensions of the cutoff valve connector. Drain hole
(3-ø 33 hole)
Unit : mm

✻2...Make sure that the panel can be easily removed for maintenance
when a piping cover is used for aesthetic reasons.

S-VM(R22)
5. Electrical Wiring Diagram
PUMY-71VM
THHS TH6 TH5 TH2 TH1 63HS
SLEV
3 6
4321 1234 12345 123 2 1 12 13 12 1 3 1 2 1 23 1 2 3 4 5 6
CN40 CN41 CN51 CN3D CNCT THHS TH6 TH5 TH2 TH1 63HS SLEV
(WHT) (WHT) (WHT) (WHT) (WHT) (BLK) (WHT) (GRN) (GRN) (WHT) (WHT) (WHT)
SW1 SW2
1 CNS2 ON ON
2 (YLW) OFF OFF
LD1 12345678 1 2 3 4 5 6 7 8 910
SW3 SW4 SW5
1 CNS1 901 901 901 ON ON AC,CT 2
2 (RED)

78

78
23

78

23
23
OFF OFF (YLW) 1

WHT
456 4 56 456
121234 12345678

RED
SWU3 SWU2 SWU1
(3rd digit) (2nd digit) (1st digit) CN1(RED) CN2(YLW) CN3 (WHT) CN4 (YLW)
6 321 6 5 43 21 7 63 2 1 7 6 5 4 3 2 1
<MULTI CONTROLLER BOARD>

YLW
4 6 26C 5
S-VM(R22)

YLW
<POWER SUPPLY BOARD>
6 3 2 1 6 5 4 3 2 1 1 2 763 2 1
TB3 CN1 CN2 26C CN3
FUSE2 X1 (RED) (YLW) (BLK) (WHT)
TO INDOOR UNIT (6A) X2 X3 F.C
M1 BRN
CONNECTING WIRES FUSE1(2A) (WHT) (WHT)
DC 30V (Non-polar) M2 BRN CNA CH 52C 21S4 SV1 MF1 MF2 CND(YLW) CN5 CN6
S 13 31 31 31 31 31 31 1 23 1 2 5 6 910 1 2 3

WHT
WHT

RED
RED

BLU
BLK

RED

RED
WHT

BLU
BLK

WHT
WHT

WHT
RED

RED
52C 21S4 SV1 MF1 MF2
TB7

ORN

ORN
RED

RED
FOR CENTRALIZED CH
CONTROL M1 ORN PUMY-71VM R1 6 3 7
DC 30V (Non-polar) Only RED RED C1 C2
M2 ORN DCL
S RED D1 RED
TB1 NF1 52C RED 1256910 1 2 3 76 5 43 21
POWER SUPPLY L P(+) CN5 CN6 CN4
RED RED (WHT) (WHT)
RED 3 (YLW)
Single-phase 220-240V 50Hz FUSE(30A) 1 1 2 + <GATE AMP BOARD>
ZNR C5
Single-phase 220V 60Hz N CNCT WHT C3 U V W
WHT 2 4
R2 N(-)
GRN/YLW WHT WHT
DS

P(+)

U V W
N(-)

WHT

BLU
RED
<IPM>
AC.CT
V
U MC W
1.Refer to the wiring boards of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity.
3.Mark shows the terminal board,mark the connector .Symbols in parentheses ( ) show the colors of connectors.
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to .OFF

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME
AC,CT Current detection F.C Fan control TB3 Terminal block <Transmission>
CH Crankcase heater FUSE1 Fuse(2A) TB7 Terminal block
CNA Connector <Power supply> FUSE2 Fuse(6A) <Transmission> (Centralized control)
CND Connector <DC Power supply> FUSE Fuse(30A) THHS Thermistor
CNS1 Connector <Multi system> IPM Intelligent power module <IPM Radiator panel temperatuer detection>
CNS2 Connector <Centralized control> LD1 Digital indication LED TH1 Thermistor <Discharge temperatuer detection>
CN1 Connector <Controller drive control> <Operation inspection indication> TH2 Thermistor
CN2 Connector <Power sync signal, protection> MC Compressor <Low pressure saturated temperatuer detection>
CN3 Connector <Power supply 30V, 12V, 5V> MF1,2 Fan motor (Inner thermostat) TH5 Thermistor
CN4 Connector <Inverter signal 5V> NF1 Noise filter <Pipe temperatuer detection, judging defrost>
CN5 Connector <IPM power supply> R1 Resistor <Rush current protect> TH6 Thermistor <Outdoor temperatuer detection>
CN6 Connector <IPM power supply, trouble output> R2 Resistor <Discharge> X1 Relay
CN40 Connector <Centralized control power supply> SLEV Expansion valve <Crankcase heater, magnetic contactor>
CN41 Connector <For storing jumper connector> SV1 Solenoid valve <Hot gas bypass> X2 Relay <4-way valve>
CN51 Connector <Compressor drive signal output> SW1 Switch <Display selection selfdiagnosis> X3 Relay <Solenoid valve>
CN3D Connector <Demand signal, silent mode input> SW2 Switch <Function selection> ZNR Varistor
CNCT Connector <Current detection> SW3 Switch <Test run> 21S4 4-Way valve
C1,2 Fan motor capacitor SW4 Switch <Model selection> 26C Thermal switch <Compressor>
C3 Capacitor <Smoothing> SW5 Switch <Function selection> 52C Magnetic contactor
C5 Capacitor <Power factor improvement> SWU1 Switch <Unit address selection,1st digit> <Inverter main circuit>
DS Diode stack SWU2 Switch <Unit address selection,2nd digit> 63HS High pressure sensor
D1 Diode <Power factor improvement> SWU3 Switch <Unit address selection,3rd digit> <Discharge pressure detection>
DCL Reactor TB1 Terminal block <Power supply>

1- 162
PUMY-125VMA
THHS TH6 TH5 TH2 TH1 63HS
SLEV
3 6
1234 1234 12345 123 1 3 12 123 1 3 1 2 1 2 3 123 456
CN40 CN41 CN51 CN3D THHS TH6 TH5 TH2 TH1 63HS SLEV
(WHT) (BLK) (WHT) (GRN) (GRN) (WHT) (WHT) (WHT)
(WHT) (WHT) (WHT)
SW1 SW2
LD1 ON ON
OFF OFF
1 CNS2 12345678 1 2 3 4 5 6 7 8 910
2 (YLW) SW3 SW4 SW5 AC.CT 2
ON ON (YLW) 1

WHT
RED
1 CNS1 OFF OFF
2 (RED) 901 901 901 12 1234 12345678

78

78

78
23

23

23
456 456 456
CN1(RED) CN2 (YLW) CN3 (WHT) CN4 (YLW)
SWU3 SWU2 SWU1
6 32 1 6 5 4 3 2 1 7 6 32 1 7 6 54321
(3rd digit) (2nd digit) (1st digit)
<MULTI CONTROLLER BOARD> 4 6 5
26C

YLW
YLW

S-VM(R22)
<POWER SUPPLY BOARD>
6321 654321 12 7 6 32 1
TB3 CN1(RED) CN2 (YLW) 26C CN3(WHT)
(BLK)
BRN FUSE2 X1
TO INDOOR UNIT M1 (6A) X2 X3 F.C FUSE1
BRN (2A)
CONNECTING WIRES M2 (YLW)
DC 30V (Non-polar) CNA CH 52C 21S4 SV1 MF1 MF2 CND CN5 (WHT) CN6 (WHT)
S 1 3 31 31 3 1 3 1 3 1 3 1 123 1 2 5 6 910 1 23

YLW

WHT
YLW
WHT

WHT
RED

RED
RED
RED
RED
BLU

BLU

RED
WHT

BLU

BLK
6 3 7
CH
52C 21S4 SV1 MF1 MF2
1 2 5 6 9 10 1 23 7 6 54321

RED

RED
ORN
ORN
CN5 CN6 CN4
TB7 CH (WHT) (WHT) (YLW)
PUMY-125VM <GATE AMP BOARD>
FOR CENTRALIZED M1 ORN
Only
CONTROL ORN
DC 30V (Non-polar) M2 C1 C2

S AR DCL D
RED
DB1 DB2 1
RED BLK 2 RED RED
TB1 NF
2 2 WHT3 P(+)
RED RED RED RED
L C3 BLU BLU
RED C5 1 3 3 ZNR C7
RED

POWER SUPPLY FUSE(60A) 6 2 +


BRN BLK BLK

RB CB
BLK BLK 3 C4 X4 -
Single-phase 220-240V 50Hz N 2 4
BLK C6 GRN/YLW
Single-phase 220 60Hz 1 1 BLK 52C
GRN
BLK BLK N(-) U V W
YLW

GRN/YLW
YLW

BRN

X4

RED

WHT

BLU
RS 3 5 <IPM>
AC.CT
8 X4 7 BRN U V
MC W

1.Refer to the wiring boards of the indoor units for details on wiring of each indoor unit.
2.The transmission line is two-wire type and has no polarity .
3.Mark shows the terminal board,mark the connector. Symbols in parentheses( ) show the colors of connectors.
4.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME
AC,CT Current detection DCL Reactor TB3 Terminal block <Transmission>
AR Surge absorber F.C Fan control TB7 Terminal block
CB Smoothing capacitor FUSE1 Fuse(2A) <Transmission> (Centralized control)
CH Crankcase heater FUSE2 Fuse(6A) THHS Thermistor
CNA Connector <Power supply> FUSE Fuse(60A) <IPM radiator panel temperature detection>
CND Connector <DC Power supply IPM Intelligent power module TH1 Thermistor <Discharge temperature detection>
CNS1 Connector <Multi system> LD1 Digital indication LED TH2 Thermistor
CNS2 Connector <Centralized control> <Operatioin inspection indication> <Low pressure saturated temperature detection>
CN1 Connector <Controller drive control> MC Compressor TH5 Thermistor
CN2 Connector <Power sync signal, protection> MF1,2 Fan motor (Inner thermostat) <Pipe temperature detection, judging defrost>
CN3 Connector <Power supply 30V, 12V, 5V> NF Noise filter TH6 Thermistor
CN4 Connector <Inverter signal 5V> RB Resistor <Discharge> <Outdoor temperature detection>
CN5 Connector <IPM Power supply> RS Resistor <Rush current protect> X1 Relay
CN6 Connector <IPM Power supply, trouble output> SLEV Expansion valve <Crankcase heater, magnetic contactor>
CN40 Connector <Centralized control power supply> SV1 Solenoid valve <Hot gas bypass> X2 Relay<4-way valve>
CN41 Connector <For storing jumper connector> SW1 Switch <Display selection selfdiagnosis> X3 Relay<Solenoid valve>
CN51 Connector <Compressor drive signal output> SW2 Switch <Function selection> X4 Relay
CN3D Connector <Demand signal, silent mode input> SW3 Switch <Test run> ZNR Varistor
C1,2 Fan motor capacitor SW4 Switch <Model selection> 21S4 4-way valve
C3,4 Capacitor <Power factor improvement> SW5 Switch <Function selection> 26C Thermal switch <Compressor>
C5,6 Capacitor SWU1 Switch <Unit addres selection , 1st digit> 52C Magnetic contactor
C7 Capacitor <Filter> SWU2 Switch <Unit address selection 2nd digit> <Inverter main circuit>
D Diode <Power factor improvement> SWU3 Switch <Unit address selection 3rd digit> 63HS High pressure sensor
DB1,DB2 Diode stack TB1 Terminal block <Power supply> <Discharge pressure detection>

1- 163
S-VM(R22)

PUMY-71, 125

(Refrigerant flow)
Cooling
Heating Thermistor TH6
(outdoor air
High-pressure sensor temperature sensor)
discharge pressure sensor
(63HS)
Service port 4-way
Connector valve
Flare Gas pipe Strainer
Thermistor TH23
for monitoring gas
pipe temperature
Oil
Flare separator
Indoor heat Check valve
Strainer
exchanger Check valve (High prssure)
(low pressure)
Thermistor
Thermistor Strainer TH1 (discharge
temperature Thermistor TH5
TH21 (intake (pipng temperature
temperature sensor) monitoring and
Capillary Electromag-
detection) tube 1 netic valve determination)

1- 164
Thermistor TH2 (SV1)
(Saturation temperature Capillary
of suction pressure) Outdoor heat exchanger tube 3
Capillary Compressor Thermistor THHS
tube 2 (Radiator panel
Thermistor (MC)
TH22 (piping Strainer temperature sensor)
temperature Accumulator
detection)
Flare Electronic expansion valve (SLEV)
Linear expansion
valve (LEV)
Liquid pipe Strainer Overcooling heat exchanger
Flare Connector Strainer
Service port
Indoor unit Outdoor unit
6. Refrigerant Circuit Diagram And Thermal Sensor
PUMY-125YM
PUMY-125YMA
CONTENTS

1. Specifications ································································· 1-166

2. Capacity Tables ······························································ 1-167


2-1 Correction by temperature ············································ 1-167
2-2 Correction by total indoor ············································· 1-169

S-YM(R22)
2-3 Correction by refrigerant piping length ··························· 1-170
2-4 Correction at frosting and defrosting ···························· 1-171
2-5 Operation limit ······························································· 1-171

3. Sound Levels ·································································· 1-172

4. External Dimensions ···················································· 1-173

5. Electrical Wiring Diagram ·············································· 1-174

6. Refrigerant Circuit Diagram ········································· 1-176


And Thermal Sensor

1- 165
1. Specifications

PUMY-125YM
Model name PUMY-125YMA

Cooling Heating

✻1 kW 14.0 16.0
Capacity
✻2 kcal/h 12,500 –
Power source 3N ~ 380/400/415V 50Hz

Power input kW 5.95 5.58

Current A 9.6/9.1/8.8 9.0/8.6/8.3

Type ✕ Quantity Propeller fan ✕ 2

Fan Airflow rate m3/min 90

Motor output kW 0.06 ✕ 2


S-YM(R22)

Type Hermetic

Compressor Motor output kW 3.5

Crankcase heater kW –

Refrigerant / Lubricant R22/MS32(N-1)

External finish Steel plate painting with polyester powder


<MUNSELL 5Y8/1>
External dimension mm 1280(H)✕1020(W)✕350+30(D)

High pressure protection 3.0MPa


Protection
Compressor / Fan Internal thermal switch / Internal thermal switch
devices
Inverter Over current protection , Overheat protection

Refrigerant piping diameter Liquid / Gas ø 9.52 / ø 19.05 (Flare)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 125 / 1 ~ 8

Noise level ✻ dB<A> 54

Net weight kg 127

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range
Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 166
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications

PUMY-125YM,YMA
Capacity kW 14.0
Input kW 5.95

Capacity at 100% indoor units running


1.30

1.20

S-YM(R22)
1.10
Ratio

22˚CWB

1.00 20˚CWB

Indoor Temperature(˚CWB)
18˚CWB

0.90 16˚CWB

-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.40

1.20 22˚CWB
20˚CWB
18˚CWB
16˚CWB
1.00
Ratio

Indoor Temperature(˚CWB)
0.80

0.60

0.40
-10 0 10 20 30 40 50
Outdoor Temperature (˚CDB)

1- 167
Heating
• Standard Specifications

PUMY-125YM,YMA
Capacity kW 16.0
Input kW 5.58

Capacity at 100% indoor units running


1.30

15˚CDB
1.20
20˚CDB
S-YM(R22)

1.10

1.00 25˚CDB
Ratio

Indoor Temperature(˚CDB)
0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.20

1.10 20˚CDB

15˚CDB
Indoor Temperature(˚CDB)
1.00

25˚CDB
Ratio

0.90

0.80

0.70

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 168
2-2. Correction by total indoor

PUMY-125YM,YMA

1) Capacity
17.00
Heating
15.00 Cooling
Capacity(kW)

13.00

11.00

9.00

7.00
60 80 100 120 140 160 180
Total capacity of indoor units

S-YM(R22)
2) Input
7.00
Cooling
6.00
Input(kW)

5.00
Heating
4.00

3.00

2.00
60 80 100 120 140 160 180
Total capacity of indoor units

1- 169
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PUMY-125YM,YMA
1.0
Total ca
pacity
of indo
or unit
Cooling capacity
correction factor

0.9 63 (50%)

94 (75%)
0.8
125 (100%)
163 (130%)

0.7
5 10 20 30 40 50 60 70 75
S-YM(R22)

Piping equivalent length (m)

• Heating capacity correction


PUMY-125YM PUMY-125YMA
1.0 1.0
Heating capacity

Heating capacity
correction factor

correction factor

0.9
0.95

0.8

0.7 0.9
0 10 20 30 40 50 60 5 10 20 30 40 50 60 70 75
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


PUMY-125YM,YMA
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 ✕ number of bent on the piping)m

1- 170
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.88 0.89 0.9 0.95 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

S-YM(R22)
25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25

20

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 171
3. Sound Levels
PUMY-125YM,YMA
Measurement condition 70

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
60
NC60

50 NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
57 dB (A)
S-YM(R22)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 172
Air intake

Air intake

Air outlet Teminal block for transmission

Teminal block for central remote control


Optional parts
PUMY-125YM,YMA

Terminal block for power source (base branching


Handle for moving pipe) installation
hole

Optional parts
installation hole
Side air intake
4. External Dimensions

Rear air intake


Handle for
moving

Gas refrigerant-pipe
connection ø 19.05 (3/4F)
Liquid refrigerant pipe

1- 173
connection ø 9.52 (3/8F)

Knock out hole for right piping


Rear piping hole Knock out holes for
Knock out hole for power line 2-ø 27
front piping
Piping cover Knock out holes for power line 2-ø 29

Oval holes
(standard bolt M10)

Bottom piping hole

shaped dotched holes


(standard bolt M10)
Drain hole
✻1...Indicates the dimensions of the cutoff valve connector. (3-ø 33 hole)
Unit : mm

✻2...Make sure that the panel can be easily removed for maintenance
when a piping cover is used for aesthetic reasons.

S-YM(R22)
5. Electrical Wiring Diagram
PUMY-125YM
THHS TH6 TH5 TH2 TH1 63HS
SLEV

3 6

1234 1234 12345 123 12 13 12 13 12 123 123456


CN40 CN41 CN51 CN3D THHS TH6 TH5 TH2 TH1 63HS SLEV
(WHT) (WHT) (WHT) (WHT) (BLK) (WHT) (GRN) (GRN) (WHT) (WHT) (WHT)
SW1 SW2
LD1
ON ON
1 CNS2 OFF OFF
2 (YLW) 12345678 1 2 3 4 5 6 7 8 9 10
SW3 SW4 SW5
ON ON ON ACCT 2
1 CNS1 901 901 901 OFF OFF
2 (RED)
OFF (YLW) 1

78
23
78
23

78
23
45 6 45 6 45 6 12 1234 12345678
(RED) (YLW) (WHT) (YLW)
SWU3 SWU2 SWU1 CN1 CN2 CN3 CN4
(3rd digit) (2rd digit) (1rd digit) 6321 654321 76321 7654321

<MULTI CONTROLLER BOARD>


MC 49C
U W 4 6 5 7
V

RED

BLU
WHT

YLW
YLW
<POWER SUPPLY BOARD>
TB3
M1 BRN U V W 31 6321 654321 76321 7654321
TO INDOOR UNIT <RESISTOR BOARD>
P 49C CN1 CN2 CN3 CN4
CONNECTING WIRES M2 BRN RD2 RD1 N (YLW) (RED) (YLW) (WHT) (YLW)
IPM
DC 30V (Non-polar) X (WHT)
CNR C03
S
X 1
RB2 RB1 FUSE2 FUSE1
S-YM(R22)

3 F.C
(2A)

+
-

-
5 (6.3A) X71 X72 X73
RS1 6
TB7 8 C01 C02
M1 ORN
FOR CENTRALIZED 10 (BLU) (GRN) (BLK) (WHT) (WHT)
(RED) (WHT)
CONTROL M2 ORN 3 1 CNA10 8 6 5 3 1 CNR N E 3 1 52C 3 1 21S4 3 1 SV1 3 1 MF1 3 1 MF2
DC 30V (Non-polar) N1 P P1

BLU
BLU

RED
RED
YLW
YLW
GRN

BLU

BLU
YLW
YLW

WHT

WHT
WHT
RED

BLU
BLK
S 6
31 31

BLU

BLU
WHT
WHT
DM DCL BLK 52C 21S4 SV1
31 BLK
NO FUSE BREAKER TB1 CNA NF +
25A + MF1 MF2
RED (RED) RED
L1 L1 CB1

RED
ORN

ORN
LI1 LO1 ~

RED
-
BLU

POWER SUPPLY L2 L2 WHT WHT ~


LI2 LO2 ZNR
3N~ L3 L3 BLK BLK
380/220-415/240V LI3 LO3 ~ +
CB2 C1 C2
50Hz N N BLU -
N -
GRN/YLW BLU WHT
E
52C
GRN

GROUND

1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF .

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
ACCT CURRENT DETECTION C1,C2 FAN MOTOR CAPACITOR SV1 SOLENOID VALVE <HOT GAS BYPASS> TH2 THERMISTOR
CB1,CB2 SMOOTHING CAPACITOR DM DIODE MODULE SW1 SWITCH <DISPLAY SELECTION> <LOW PRESSURE SATURATED TEMP. DETECTION>

CNA CONNECTOR <POWER SUPPLY> DCL REACTOR SW2 SWITCH <FUNCTION SELECTION> TH5 THERMISTOR
CNR CONNECTOR <DISCHARGE CIRCUIT,POWER SUPPLY> F.C FAN CONTROL SW3 SWITCH <TEST RUN> <PIPE TEMP. DETECTION:JUDGING DEFROST>

CNS1 CONNECTOR <MULTI SYSTEM> FUSE1 FUSE(6.3A) SW4 SWITCH <MODEL SELECTION> TH6 THERMISTOR <OUTDOOR TEMP. DETECTION>
CNS2 CONNECTOR <CENTRALIZED CONTROL> FUSE2 FUSE(2A) SW5 SWITCH <FUNCTION SELECTION> X RELAY
CN1 CONNECTOR <CONTROLLER DRIVE CONTROL> IPM INTELLIGENT POWER MODULE SWU1 SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> X71 RELAY <MAGNETIC CONTACTOR>
CN2 CONNECTOR <POWER SYNC SIGNAL,PROTECTION> LD1
DIGITAL INDICATION LED SWU2 SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> X72 RELAY <4-WAY VALVE>
CN3 CONNECTOR <POWER SUPPLY 30V,12V,5V> <OPERATION INSPECTION INDICATION> SWU3 SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> X73 RELAY <SOLENOID VALVE>
CN4 CONNECTOR <INVERTER SIGNAL 5V> MC COMPRESSOR(INNER THERMOSTAT) TB1 TERMINAL BLOCK <POWER SUPPLY> ZNR VARISTOR
CN40 CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> MF1,MF2 FAN MOTOR(INNER THERMOSTAT) TB3 TERMINAL BLOCK <TRANSMISSION> 21S4 4-WAY VALVE
CN41 CONNECTOR <FOR STORING JUMPER CONNECTOR> NF NOISE FILTER TB7 TERMINAL BLOCK <CENTRALIZED CONTROL> 49C THERMAL SWITCH <COMPRESSOR>
CN51 CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> RS1 RESISTOR <RUSH CURRENT PROTECT> THHS THERMISTOR 52C MAGNETIC CONTACTOR
CN3D CONNECTOR <DEMAND SIGNAL/SILENT MODE INPUT> RB1,RB2 RESISTOR <VOLTAGE BALANCE ADJUSTMENT> <IPM RADIATOR PANEL TEMP. DETECTION> 63HS
HIGH PRESSURE SENSOR
C01,C02 SMOOTHING CAPACITOR RD1,RD2 RESISTOR <DISCHARGE> TH1 THERMISTOR <DISCHARGE TEMP. DETECTION> <DISCHARGE PRESSURE DETECTION>
C03 CAPACITOR <FILTER> SLEV EXPANSION VALVE

1- 174
PUMY-125YMA
THHS TH6 TH5 TH2 TH1 63HS
SLEV

3 6

1234 1234 12345 123 12 13 12 13 12 123 123456


CN40 CN41 CN51 CN3D THHS TH6 TH5 TH2 TH1 63HS SLEV
(WHT) (WHT) (WHT) (WHT) (BLK) (WHT) (GRN) (GRN) (WHT) (WHT) (WHT)
SW1 SW2
LD1
ON ON
1 CNS2 OFF OFF
2 (YLW) 12345678 1 2 3 4 5 6 7 8 9 10
SW3 SW4 SW5
ON ON ON ACCT 2
1 CNS1 901 901 901 OFF OFF
2 (RED)
OFF (YLW) 1

78
23
78
23

78
23
45 6 45 6 45 6 12 1234 12345678
(RED) (YLW) (WHT) (YLW)
SWU3 SWU2 SWU1 CN1 CN2 CN3 CN4
(3rd digit) (2rd digit) (1rd digit) 6321 654321 76321 7654321

<MULTI CONTROLLER BOARD>


MC 49C
U W 4 6 5 7
V

RED

BLU
WHT

YLW
YLW
<POWER SUPPLY BOARD>
TB3
M1 BRN U V W 31 6321 654321 76321 7654321
TO INDOOR UNIT <RESISTOR BOARD>
P 49C CN1 CN2 CN3 CN4
CONNECTING WIRES M2 BRN RD2 RD1 N (YLW) (RED) (YLW) (WHT) (YLW)
IPM
DC 30V (Non-polar) X (WHT)
CNR C03
S
X 1
RB2 RB1 FUSE2 FUSE1 F.C

S-YM(R22)
3
(2A)

+
-

-
5 (6.3A) X71 X72 X73
RS1 6
TB7 8 C01 C02
M1 ORN
FOR CENTRALIZED 10 (BLU) (GRN) (BLK) (WHT) (WHT)
(RED) (WHT)
CONTROL M2 ORN 3 1 CNA10 8 6 5 3 1 CNR N E 3 1 52C 3 1 21S4 3 1 SV1 3 1 MF1 3 1 MF2
DC 30V (Non-polar) N1 P P1

BLU
BLU

RED
RED
YLW
YLW
GRN

BLU

BLU
YLW
YLW

WHT

WHT
WHT
RED

BLU
BLK
S 6
31 31

BLU

BLU
WHT
WHT
DM DCL BLK 52C 21S4 SV1
31 BLK
NO FUSE BREAKER TB1 CNA NF +
25A + MF1 MF2
RED (RED) RED
L1 L1 CB1

RED
ORN

ORN
LI1 LO1 ~

RED
-
BLU

POWER SUPPLY L2 L2 WHT WHT ~


LI2 LO2 ZNR
3N~ L3 L3 BLK BLK
380/220-415/240V LI3 LO3 ~ +
CB2 C1 C2
50Hz N N BLU -
N -
380/220V GRN/YLW BLU WHT
E
60Hz 52C
GRN

GROUND

1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
2.Symbols used in wiring diagram above are. :Terminal block, :Connector, :Insertion tab.
3.Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch(SW1) and LD1(LED indication)
found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF .

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME SYMBOL NAME
ACCT CONNECTOR<CURRENT DETECTION> C1,C2 FAN MOTOR CAPACITOR SV1 SOLENOID VALVE <HOT GAS BYPASS> TH2 THERMISTOR
CB1,CB2 SMOOTHING CAPACITOR DM DIODE MODULE SW1 SWITCH <DISPLAY SELECTION> <LOW PRESSURE SATURATED TEMP. DETECTION>

CNA CONNECTOR <POWER SUPPLY> DCL REACTOR SW2 SWITCH <FUNCTION SELECTION> TH5 THERMISTOR
CNR CONNECTOR <DISCHARGE CIRCUIT,POWER SUPPLY> F.C FAN CONTROL SW3 SWITCH <TEST RUN> <PIPE TEMP. DETECTION:JUDGING DEFROST>

CNS1 CONNECTOR <MULTI SYSTEM> FUSE1 FUSE(6.3A) SW4 SWITCH <MODEL SELECTION> TH6 THERMISTOR <OUTDOOR TEMP. DETECTION>
CNS2 CONNECTOR <CENTRALIZED CONTROL> FUSE2 FUSE(2A) SW5 SWITCH <FUNCTION SELECTION> X RELAY
CN1 CONNECTOR <CONTROLLER DRIVE CONTROL> IPM INTELLIGENT POWER MODULE SWU1 SWITCH <UNIT ADDRESS SELECTION,1ST DIGIT> X71 RELAY <MAGNETIC CONTACTOR>
CN2 CONNECTOR <POWER SYNC SIGNAL,PROTECTION> LD1
DIGITAL INDICATION LED SWU2 SWITCH <UNIT ADDRESS SELECTION,2ND DIGIT> X72 RELAY <4-WAY VALVE>
CN3 CONNECTOR <POWER SUPPLY 30V,12V,5V> <OPERATION INSPECTION INDICATION> SWU3 SWITCH <UNIT ADDRESS SELECTION,3RD DIGIT> X73 RELAY <SOLENOID VALVE>
CN4 CONNECTOR <INVERTER SIGNAL 5V> MC COMPRESSOR(INNER THERMOSTAT) TB1 TERMINAL BLOCK <POWER SUPPLY> ZNR VARISTOR
CN40 CONNECTOR <CENTRALIZED CONTROL POWER SUPPLY> MF1,MF2 FAN MOTOR(INNER THERMOSTAT) TB3 TERMINAL BLOCK <TRANSMISSION> 21S4 4-WAY VALVE
CN41 CONNECTOR <FOR STORING JUMPER CONNECTOR> NF NOISE FILTER TB7 TERMINAL BLOCK <CENTRALIZED CONTROL> 49C THERMAL SWITCH <COMPRESSOR>
CN51 CONNECTOR <COMPRESSOR DRIVE SIGNAL OUTPUT> RS1 RESISTOR <RUSH CURRENT PROTECT> THHS THERMISTOR 52C MAGNETIC CONTACTOR
CN3D CONNECTOR <DEMAND SIGNAL/SILENT MODE INPUT> RB1,RB2 RESISTOR <VOLTAGE BALANCE ADJUSTMENT> <IPM RADIATOR PANEL TEMP. DETECTION> 63HS
HIGH PRESSURE SENSOR
C01,C02 SMOOTHING CAPACITOR RD1,RD2 RESISTOR <DISCHARGE> TH1 THERMISTOR <DISCHARGE TEMP. DETECTION> <DISCHARGE PRESSURE DETECTION>
C03 CAPACITOR <FILTER> SLEV EXPANSION VALVE

1- 175
S-YM(R22)

(Refrigerant flow)
PUMY-125YM,YMA

Cooling
Heating Thermistor TH6
(outdoor air
High-pressure sensor temperature sensor)
discharge pressure sensor
(63HS)
Service port 4-way
Connector valve
Flare Gas pipe Strainer
Thermistor TH23
for monitoring gas
pipe temperature
Oil
Flare separator
Indoor heat Check valve
Strainer
exchanger Check valve (High prssure)
(low pressure)
Thermistor
Thermistor Strainer TH1 (discharge
temperature Thermistor TH5
TH21 (intake (pipng temperature
temperature sensor) monitoring and
Capillary Electromag-
determination)

1- 176
detection) tube 1 netic valve
Thermistor TH2 (SV1)
(Saturation temperature Capillary
of suction pressure) Outdoor heat exchanger tube 3
Capillary Compressor Thermistor THHS
tube 2 (Radiator panel
Thermistor (MC)
TH22 (piping Strainer temperature sensor)
temperature Accumulator
detection)
Flare Electronic expansion valve (SLEV)
Linear expansion
valve (LEV)
Liquid pipe Strainer Overcooling heat exchanger
Flare Connector Strainer
Service port
Indoor unit Outdoor unit
6. Refrigerant Circuit Diagram And Thermal Sensor
PUHY-200·250·315YEM-A (-BF, -BS)
PUY-200·250·315YEM-A (-BF, -BS)
PUHY-250·315YEMK-A
PUHY-200·250·315YEMC-A (-BS)
CONTENTS

1. Specifications ·································································1-178

2. Capacity Tables ······························································1-183


2-1 Correction by temperature ············································ 1-183
2-2 Correction by total indoor ············································· 1-185
2-3 Correction by refrigerant piping length ···························1-188
2-4 Correction at frosting and defrosting ···························· 1-189
2-5 Operation limit ·······························································1-189

3. Sound Levels ·································································· 1-190

Y-8,10,13(R22)
4. External Dimensions ···················································· 1-192

5. Electrical Wiring Diagram ·············································1-193

6. Refrigerant Circuit Diagram ·········································1-194


And Thermal Sensor

1- 177
1. Specifications

PUHY-200YEM-A (-BF, -BS)


Model name PUY-200YEM-A (-BF, -BS)
Cooling Heating

✻1 kW 22.4 25.0
Capacity
✻2 kcal/h 20,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 6.19 6.66

Current A 10.4/9.9/9.5 11.2/10.6/10.2

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 5.3

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32 (N-1)


Y-8,10,13(R22)

Pre-coated galvanized sheets(Powder coating)


External finish
<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 13

Noise level ✻ dB<A> 56

Net weight kg 219

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB ~ 46˚CDB with outdoor
unit at lower position)

Matters Deserving Special Mention A pipe of ø28.58 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 178
PUHY-200YEMC-A (-BS)
Model name
Cooling Heating

Capacity ✻1 kW 24.6 25.0

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 7.13 6.66

Current A 12.0/11.4/11.0 11.2/10.6/10.2

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 6.0

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32 (N-1)


External finish Pre-coated galvanized sheets(Powder coating)
<MUNSELL 5Y8/1 or similar>

Y-8,10,13(R22)
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 13

Noise level ✻ dB<A> 56

Net weight kg 219

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
(10˚CDB ~ 46˚CDB with outdoor
unit at lower position)

Matters Deserving Special Mention A pipe of ø28.58 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 179
PUHY-250YEM-A (-BF, -BS), PUHY-250YEMC-A (-BS)
Model name PUY-250YEM-A (-BF, -BS)
Cooling Heating
✻1 kW 28.0 31.5
Capacity
✻2 kcal/h 25,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 8.37 8.77

Current A 14.1/13.4/12.9 14.8/14.0/13.5

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 6.8

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32 (N-1)


Y-8,10,13(R22)

Pre-coated galvanized sheets(Powder coating)


External finish
<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 57

Net weight kg 219

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB~15.5˚CWB
Operating temperature range
(10˚CDB ~ 46˚CDB with outdoor
unit at lower position)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 180
PUHY-250YEMK-A
Model name
Cooling Heating
Capacity ✻1 kW 30.0 31.5

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 11.66 8.77

Current A 19.6/18.6/18.0 14.8/14.0/13.5

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 7.9

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32 (N-1)

External finish Pre-coated galvanized sheets(Powder coating)

Y-8,10,13(R22)
<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 57

Net weight kg 219

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB~15.5˚CWB
(10˚CDB ~ 46˚CDB with outdoor
unit at lower position)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 181
PUHY-315YEM-A (-BF, -BS), PUHY-315YEMK-A
Model name PUY-315YEM-A (-BF, -BS) PUHY-315YEMC-A (-BS)
Cooling Heating
Capacity ✻1 kW 35.5 39.1
Capacity
✻2 kcal/h 31,500 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 12.05 10.91

Current A 19.9/18.9/18.2 18.2/17.3/16.6

Type✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 8.6

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32 (N-1)


Y-8,10,13(R22)

External finish Pre-coated galvanized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 31.75 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 60

Net weight kg 234

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB~46˚CDB with outdoor unit (-12˚C(-5˚C)WB~10˚CWB with indoor
at lower position) unit P25(P20)type only is working)

Matters Deserving Special Mention A pipe of ø 34.93 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 182
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications

PU(H)Y-200YEM PUHY-200YEMC PU(H)Y-250YEM(C) PU(H)Y-250YEMK


Capacity kW 22.4 24.6 28.0 30.0
Input kW 6.19 7.13 8.37 11.66
PUHY-315YEM(K,C)
Capacity kW 35.5
Input kW 12.05

Capacity at 100% indoor units running


1.30

1.20

1.10

Y-8,10,13(R22)
Ratio

24˚CWB
22˚CWB
1.00 20˚CWB
19˚CWB
18˚CWB
0.90 16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30
24˚CWB
1.20 22˚CWB
20˚CWB
1.10 19˚CWB
18˚CWB
1.00
16˚CWB
0.90
Ratio

15˚CWB
Indoor Temperature(˚CWB)
0.80

0.70

0.60

0.50

0.40
-5 0 5 10 15 20 25 30 35 40 45 50
Outdoor Temperature (˚CDB)

1- 183
Heating
• Standard Specifications

PUHY-200YEM(C)-A PUHY-250YEM(K,C)-A PUHY-315YEM(K,C)-A


Capacity kW 25.0 31.5 40.0
Input kW 6.66 8.77 10.91

Capacity at 100% indoor units running


1.30
15˚CDB
1.20

1.10 Indoor Temperature(˚CDB)


20˚CDB
1.00
Ratio

0.90

0.80 25˚CDB
Y-8,10,13(R22)

0.70 27˚CDB

0.60
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10

1.00 15˚CDB

0.90
20˚CDB
Ratio

0.80

0.70
Indoor Temperature(˚CDB) 25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 184
2-2. Correction by total indoor

PU(H)Y-200YEM-A
1) Capacity
30.0

25.0
Heating
Capacity(kW)

20.0 Cooling

15.0

10.0

5.0
100 150 200 250 300
Total capacity of indoor units
2) Input
8.00

7.00

Heating
Input(kW)

6.00
Cooling
5.00

Y-8,10,13(R22)
4.00

3.00
100 150 200 250 300
Total capacity of indoor units
PUHY-200YEMC-A
1) Capacity
30.0

25.0 Heating
Capacity(kW)

20.0
Cooling

15.0

10.0

5.0
100 150 200 250 300
2) Input Total capacity of indoor units
8.00

Cooling
7.00
Input(kW)

6.00 Heating

5.00

4.00

3.00
100 150 200 250 300
Total capacity of indoor units

1- 185
PU(H)Y-250YEM-A
PUHY-250YEMC-A
1) Capacity
35.0
Heating

30.0
Capacity(kW)

Cooling

25.0

20.0

15.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
9.00
Cooling

8.00
Heating
Input(kW)

7.00
Y-8,10,13(R22)

6.00

5.00

4.00
100 150 200 250 300 350 400
Total capacity of indoor units

PUHY-250YEMK-A
1) Capacity
35.0
Heating

30.0
Capacity(kW)

Cooling

25.0

20.0

15.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
12.00
11.00 Cooling

10.00
9.00
Input(kW)

8.00
Heating
7.00
6.00
5.00
4.00
100 150 200 250 300 350 400
Total capacity of indoor units

1- 186
PU(H)Y-315YEM(K,C)-A

1) Capacity
40.0

35.0 Cooling
Heating
Capacity(kW)

30.0

25.0

20.0

15.0
150 200 250 300 350 400 450
2) Input Total capacity of indoor units
13.00
12.00 Cooling

11.00
10.00
Heating
Input(kW)

9.00
8.00

Y-8,10,13(R22)
7.00
6.00
5.00
4.00
150 200 250 300 350 400 450
Total capacity of indoor units

1- 187
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PU(H)Y-200YEM(C)-A PU(H)Y-250YEM(K,C)-A
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
100 125
Cooling capacity

Cooling capacity
correction factor

correction factor
0.9 0.9
150 188
200 250
0.8 0.8
260 325

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PU(H)Y-315YEM(K,C)-A
1.0
Total capaci
Cooling capacity
correction factor

ty of indoor unit
158
0.9 237

315
Y-8,10,13(R22)

0.8 410

0 20 40 60 80 100 120
Piping equivalent length (m)

• Heating capacity correction


PUHY-200YEM(C)-A PUHY-250YEM(K,C)-A
1.0 1.0
Heating capacity

Heating capacity
correction factor

correction factor

0.9 0.9

0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-315YEM(K,C)-A
1.0
Heating capacity
correction factor

0.9

0.8

0.7
0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PU(H)Y-200YEM(C)-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PU(H)Y-250YEM(K,C)-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m
➂ PU(H)Y-315YEM(K,C)-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m

1- 188
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

PUHY-200·250 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95
Correction
factor
PUHY-315 1.0 0.93 0.82 0.82 0.86 0.9 0.9 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

25

20 (Outdoor door temperature :10˚CDB~46˚CDB with


outdoor unit at lower position in cooling mode.)

Y-8,10,13(R22)
15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25
When the indoor P25(P20) type only is working,
20 the outdoor unit [PUHY-315] inlet air temperature
becomes –12˚C(–5˚C)WB~10˚CWB.

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

1- 189
3. Sound Levels
PU(H)Y-200YEM(C)-A
Measurement condition Cooling Heating
90

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
56 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)


Y-8,10,13(R22)

PU(H)Y-250YEM(C)-A
Measurement condition Cooling Heating
90
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m

80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

57 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 190
PU(H)Y-250YEMK-A
Measurement condition Cooling Heating
90

OCTAVE BAND PRESSURE LEVEL(dB) 0dB = 20µPa


1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

57 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

Y-8,10,13(R22)
PU(H)Y-315YEM(K,C)-A
Measurement condition Cooling Heating
90
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
30 NC-30
60 dB (A)

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 191
Y-8,10,13(R22)

<Accessory>

(15)
• Refrigerant (gas) conn. pipe·······1pc.
(The connecting pipe is fixed with the unit)
12 5 Y ø40 Knockout hole • Packing for conn. pipe ··········1pc.
<Bottom side hole for (Attached near the ball valve)
the power supply> • Wiring mounting board
Note1 Y • Conduit mounting plate
ø27 Knockout hole (Painted the same color as the unit body)

840
910
Knockout hole
<Bottom side hole for
Bottom piping hole ø40···························1pc.
the control wiring>

50
<Bottom wiring hole> ø33···························1pc.

880(bolt hole)
2✕2-14✕20 ø27···························1pc.
• Tapping screw 4 ✕ 10············· 6pcs.

237
Oval hole

198
121
Note1.Please leave a space under the outdoor unit

73 80
for the piping When you connect the piping

15
25 160 215 560(bolt hole) (215) from the bottom.
Conn. pipe 778 75
200:ø25.4<brazed> 990 (Please be careful not to close the hole
Crosss section Y-Y 250:ø28.58<brazed> Cross section X-X of the bottom plate by the basement)
315:ø31.75<brazed> Plane view
4. External Dimensions

Air outlet
PU(H)Y-200, 250, 315YEM(K, C)-A(-BF, -BS)

(265)

1- 192
Air
inlet
1755

Air
Knockout hole inlet
1490

Refrig. service
60 75 valve (liquid) Service panel
ø12.7<flare>
ø40 Knockout hole X X
<Left side hole for
the power supply>

40

234
100
194
149
99

70
78

48
ø27 Knockout hole Knockout hole
100 251 <Left side hole for Refrig. service 79 80 Front piping hole Knockout hole
the control wiring> 80 40
Knockout hole valve(gas) <Front wiring hole> <Front side hole for
Knockout hole <flange> 813 the power supply>
Left piping hole 31 165 590 55

Rear view Left side view Front view Right side view
Unit : mm
5. Electrical Wiring Diagram
PU(H)Y-200, 250, 315YEM(K, C)-A(-BF, -BS)

Y-8,10,13(R22)
CN3N
Mode
1-2 1-3
ON ON Auto HEAT
OFF changeover COOL
ON OFF Normal
OFF

<DIFFERENCE OF APPLIANCE>
Appliance Name
PUHY-P200/250/315YEM-A All exists
PUY-P200/250/315YEM-A “✻1” are not existed
PUHY-200/250/315YEM(K,C)-A “✻2” are not existed
PUY-200/250/315YEM(K,C)-A “✻1” and “✻2”are not existed

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name Symbol Name
DCL DC reactor (Power factor improvement) Solenoid valve L2 Choke coil (Transmission) Thermistor bypass outlet temp. detect
SV3 ✻2 TH8
DCCT Current Sensor (Heat exchanger capacity control) IPM Intelligent power module at Sub--cool coil
ACCT-U,W Current Sensor SV4 Solenoid valve TH1 Thermistor Discharge pipe temp. detect THHS Radiator panel temp. detect
ZNR4 Varistor ✻1,✻2 (Discharge--suction bypass) TH2 ✻2 Saturation evapo. temp. detect X1~10 Aux. relay
52C Magnetic contactor (Inverter main circuit) Electric expansion valve TH5 Pipe temp. detect
LEV1 Earth terminal
MF1 Fan motor (Radiator panel) (Sub-cool coil bypass) TH6 OA temp. detect
21S4 ✻1 4--way valve 63HS High pressure sensor liquid outlet temp. detect
TH7
SV1 Solenoid valve (Discharge--suction bypass) 63LS Low pressure sensor at Sub--cool coil

1- 193
Y-8,10,13(R22)

BV1
ST1

63H

CJ1 CJ2

63HS
ST8 CP3
PUHY-200, 250, 315YEM(K,C)-A

CP1
O/S

ST3 SV1 63LS

TH6 Indoor units


TH1

1- 194
Comp ST7
ST6

Accumulator
6. Refrigerant Circuit Diagram And Thermal Sensor

TH8

TH5 TH7 ST2 BV2


SCC
LEV1 ST4
BV1
ST1

63H

CJ1 CJ2

63HS
ST8 CP3
PUY-200, 250, 315YEM-A

CP1
O/S

ST3 SV1 63LS

TH6 Indoor units


TH1

1- 195
Comp ST7
ST6

Accumulator

TH8

TH5 TH7 ST2 BV2


SCC
LEV1 ST4

Y-8,10,13(R22)
Y-8,10,13(R22)

1- 196
PUHY-200·250·315TEM-A(-BF)

CONTENTS

1. Specifications ································································· 1-198

2. Capacity Tables ······························································ 1-201


2-1 Correction by temperature ············································ 1-201
2-2 Correction by total indoor ············································· 1-203
2-3 Correction by refrigerant piping length ··························· 1-205
2-4 Correction at frosting and defrosting ···························· 1-206
2-5 Operation limit ·······························································1-206

3. Sound Levels ·································································· 1-207

4. External Dimensions ···················································· 1-209

5. Electrical Wiring Diagram ··············································1-210

TEM-A
6. Refrigerant Circuit Diagram ········································· 1-211
And Thermal Sensor

1- 197
1. Specifications

PUHY-200TEM-A(-BF)
Model name
Cooling Heating

✻1 kW 22.4 25.0
Capacity
✻2 kcal/h 20,000 –

Power source 3 ~ 208/220/230V 60Hz

Power input kW 6.19 6.66

Current A 19.0/18.0/17.2 20.5/19.4/18.5

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 5.3

Crankcase heater kW 0.045(230V)

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
TEM-A

Inverter DC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 13

Noise level ✻ dB<A> 56

Net weight kg 214

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range (10˚CDB ~ 43˚CDB with outdoor
unit at lower position)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 198
PUHY-250TEM-A(-BF)
Model name
Cooling Heating

✻1 kW 28.0 31.5
Capacity
✻2 kcal/h 25,000 –

Power source 3 ~ 208/220/230V 60Hz

Power input kW 8.37 8.77

Current A 25.8/24.4/23.3 27.0/25.5/24.4

Type ✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 6.8

Crankcase heater kW 0.045(230V)

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕990(W)✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices

TEM-A
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 57

Net weight kg 214

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB~15.5˚CWB
Operating temperature range (10˚CDB ~ 43˚CDB with outdoor
unit at lower position)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 199
PUHY-315TEM-A(-BF)
Model name
Cooling Heating

✻1 kW 35.5 39.1
Capacity
✻2 kcal/h 31,500 –

Power source 3N ~ 208/220/230V 60Hz

Power input kW 12.05 10.91

Current A 36.3/34.3/32.8 33.2/31.4/30.0

Type✕ Quantity Propeller fan ✕ 1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 8.6

Crankcase heater kW 0.045(230V)

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
TEM-A

Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 12.7 (Flare) / ø 31.75 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 60

Net weight kg 229

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
(0˚CDB~43˚CDB with outdoor unit (-12˚C(-5˚C)WB~10˚CWB with indoor
at lower position) unit P25(P20)type only is working.)

Matters Deserving Special Mention A pipe of ø34.93 can be used for the gas pipe

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 200
2. Capacity Table
2-1. Correction by temperature

Cooling
• Standard Specifications

PUHY-200 PUHY-250 PUHY-315


Capacity kW 22.4 28.0 35.5
Input kW 6.19 8.37 12.05

Capacity at 100% indoor units running


1.30

1.20

1.10
Ratio

24˚CWB
22˚CWB
1.00 20˚CWB
19˚CWB
18˚CWB
16˚CWB
0.90
15˚CWB
Indoor Temperature(˚CWB)

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

TEM-A
Power Input at 100% indoor units running
1.30
24˚CWB
1.20 22˚CWB
20˚CWB
1.10 19˚CWB
18˚CWB
1.00
16˚CWB
0.90
Ratio

15˚CWB
Indoor Temperature(˚CWB)
0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

1- 201
Heating
• Standard Specifications

PUHY-200 PUHY-250 PUHY-315


Capacity kW 25.0 31.5 39.1
Input kW 6.66 8.77 10.91

Capacity at 100% indoor units running


1.30
15˚CDB
1.20

1.10

Indoor Temperature(˚CDB) 20˚CDB


1.00
Ratio

0.90

0.80 25˚CDB

0.70 27˚CDB

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)


TEM-A

Power Input at 100% indoor units running


1.10

1.00 15˚CDB

0.90
20˚CDB
Ratio

0.80

0.70 Indoor Temperature(˚CDB)


25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 202
2-2. Correction by total indoor

PUHY-200
1) Capacity
30.0

Heating
25.0
Capacity(kW)

20.0 Cooling

15.0

10.0

5.0
100 150 200 250 300
Total capacity of indoor units
2) Input
10.00
9.00
8.00
Input(kW)

7.00 Heating
6.00
5.00 Cooling

4.00
3.00
2.00
1.00
100 150 200 250 300
Total capacity of indoor units
PUHY-250

TEM-A
1) Capacity
35.0

30.0 Heating
Capacity(kW)

25.0 Cooling

20.0

15.0

10.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
12.00
11.00
10.00
9.00
Input(kW)

Heating
8.00
7.00 Cooling
6.00
5.00
4.00
3.00
100 150 200 250 300 350 400
Total capacity of indoor units

1- 203
2-2. Correction by total indoor

PUHY-315
1) Capacity
40.0

35.0 Cooling
Heating
Capacity(kW)

30.0

25.0

20.0

15.0
150 200 250 300 350 400 450

2) Input Total capacity of indoor units


13.00
12.00
Cooling
11.00
10.00
Input(kW)

9.00 Heating
8.00
7.00
6.00
5.00
4.00
150 200 250 300 350 400 450
Total capacity of indoor units
TEM-A

1- 204
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PUHY-200 PUHY-250
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
or unit or unit
Cooling capacity

Cooling capacity
100
correction factor

correction factor
125
0.9 0.9
150 188
200 250
0.8 0.8
260 325

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-315
1.0
Total capaci
ty of
Cooling capacity
correction factor

indoor unit
158
0.9 237

315

0.8 410

0 20 40 60 80 100 120
Piping equivalent length (m)

• Heating capacity correction


PUHY-200 PUHY-250
1.0 1.0

TEM-A
Heating capacity

Heating capacity
correction factor

correction factor

0.9 0.9

0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

PUHY-315
1.0
Heating capacity
correction factor

0.9

0.8

0.7
0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PUHY-200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PUHY-250
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m
➂ PUHY-315
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m

1- 205
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

PUHY-200·250 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95
Correction
factor
PUHY-315 1.0 0.93 0.82 0.82 0.86 0.90 0.90 0.95 0.95

2-5. Operation limit

• Cooling
30
Indoor temperature (˚CWB)

25

20 (Outdoor temperature :10˚CDB ~ 43˚CDB with


outdoor unit at lower position in cooling mode.)

15

10
-5 0 5 10 15 20 25 30 35 40 45
Outdoor temperature (˚CDB)

• Heating
TEM-A

30
Indoor temperature (˚CDB)

25
When the indoor P25(P20)type only is working,
20 the outdoor unit [PUHY-315] inlet air temperature
becomes –12˚C(–5˚C)WB~ 10˚CWB.
15

10
-15 -10 -5 0 5 10 15 20
Outdoor temperature (˚CWB)

1- 206
3. Sound Levels
PUHY-200 Cooling Heating
Measurement condition 90

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m 80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
30 NC-30
56 dB (A)

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

PUHY-250
Cooling Heating
Measurement condition

TEM-A
90
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room

57 dB (A) 30 NC-30

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 207
PUHY-315
Cooling Heating
Measurement condition 90

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


1m
80

70 NC-70

60 NC-60
1m

50 NC-50

NC-40
40
Sound pressure level in anechoic room
30 NC-30
60 dB (A)

20 Approximate minimum NC-20


audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz)


TEM-A

1- 208
<Accessory>

(15)
• Refrigerant (gas) conn. pipe·······1pc.
(The connecting pipe is fixed with the unit)
12 5 Y ø40 Knockout hole • Packing for conn. pipe ··········1pc.
<Bottom side hole for (Attached near the ball valve)
the power supply> • Wiring mounting board
Note1 Y • Conduit mounting plate
ø27 Knockout hole (Painted the same color as the unit body)

840
910
Knockout hole
<Bottom side hole for
Bottom piping hole ø40···························1pc.
the control wiring>

50
<Bottom wiring hole> ø33···························1pc.

880(bolt hole)
2✕2-14✕20 ø27···························1pc.
• Tapping screw 4 ✕ 10············· 6pcs.

237
Oval hole

198
121
Note1.Please leave a space under the outdoor unit

73 80
for the piping When you connect the piping

15
25 160 215 560(bolt hole) (215) from the bottom.
PUHY-200,250,315TEM-A(-BF)

Conn. pipe 778 75


200:ø25.4<brazed> 990 (Please be careful not to close the hole
Crosss section Y-Y 250:ø28.58<brazed> Cross section X-X of the bottom plate by the basement)
315:ø31.75<brazed> Plane view
4. External Dimensions

Air outlet

(265)

1- 209
Air
inlet
1755

Air
Knockout hole inlet
1490

Refrig. service
60 75 valve (liquid) Service panel
ø12.7<flare>
ø40 Knockout hole X X
<Left side hole for
the power supply>

40

234
100
194
149
99

70
78

48
ø27 Knockout hole Knockout hole
100 251 <Left side hole for Refrig. service 79 80 Front piping hole Knockout hole
the control wiring> 80 40
Knockout hole valve(gas) <Front wiring hole> <Front side hole for
Knockout hole <flange> 813 the power supply>
Left piping hole 31 165 590 55

Rear view Left side view Front view Right side view
Unit : mm

TEM-A
5. Electrical Wiring Diagram
PUHY-200, 250, 315TEM-A(-BF)

U
MC
W
V

ACCT-W

ACCT-U
Noise filter board
Red White Black
(POWER BOARD)
DS(Diode stack) R1 IPM
TB1
R Red
FN1 FN3 FN6 Red P U V W
~ + Inverter drive board
Power source DCL + (G/A PKG) CNE 1
S F01 (2P)
3~208~230V ~ 3.15A 2
C1
50/60Hz T Black
52C FN2 FN4 Black N
~ -
CNDR1 CN15V1
Connect to (9P) (14P)
indoor and 1 2 3 4 Yellow
remote CNDC1 1 2 3 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Green

TB7 (3P)
White

TB3
Black

controller E DCCT
Red

A B A B Shield
E T S R
CN20
Box Body (7P) 1 3 5 7 1 2 3 4 1 2 1 2 3
F2 F1 CNS1 CNS2 1 2 3 4 123 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14

6.3A 6.3A CN40 (2P) (3P) CNCT CNDC2 CNDR2 CN15V2


DSA ZNR1~4 (4P) 52 1 (4P) (3P) (9P) (14P)
C
2 Yellow
1 2 3 4 CN52C
Unit Body Control circuit board 3 (3P)
CN41 (MAIN PKG)
(4P) CNCT2 1
1 1 (4P) 2
CNRS3 2 2 CNRS2 3
(7P) Blue
3 3 (7P) 4
CH1 X01 4 4
3 CN32 5 5
2 (3P) 6 6
7 7 Inverter circuit board
1 (INV PKG)
LD1 1 1
CNVCC3 2 2 CNVCC2
6 CN33 (6P) 3 3 (6P)
5 (6P) 4 4
5 5
4 6 6
X02 1 6 1 4
SV 3 CNVCC4 ON ON
1 2 OFF ON OFF ON OFF ON OFF ON CNVCC5 1 1 (2P)
1 1 1 1 (2P) 2 2
1 Yellow OFF OFF
E 1 CNAC2 SW1 SW2
CNAC3 1
CN34 2 2
6 (6P) (5P) 3 T T 3 (5P)
5 Red 4 4
5 R R 5
4
X04 F01
21 3 2A
S4 2

10 10 10 10
1 1
SW4 SW3 SW2 SW1
TEM-A

CNLV1 1
(5P) 2 Green Red Red
5 CNFAN1 CNTH CNL2 CN30V CNFAN
4 (5P) Red 3 LEV1
MF 3 4 (2P) (2P) (2P) (3P)
SWU2 SWU1
2 Red 5
1 1 2 1 2 1 2 1 2 3
5 Trouble
Unit address setting switch 4 Compressor ON/OFF
63H 3 THHS L2 R2 MF
3 CN38 12V 2 CN51 1
1 (5P)
2 (3P)
1 Green Detection CN3D 3 Compressor ON/OFF
Circuit 2 Night mode
Red BLACK (3P) 1
CNTYP1 CN03 CN02 CN01 CNL CNH 3
(2P) (3P) (8P) (2P) (3P) (3P) 2
1 Snow sensor
1 2 1 2 3 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 3 CN3S • SW4-9 are OFF for Model PUHY.
(3P)
Red and ON for Model PUY.
White

White
Black

Black
Red

Red

R20
3 2 1 3 2 1
TH6 TH5 TH8 TH7 TH1
63LS 63HS
<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name Symbol Name
TB1 Terminal block power source Magnetic contactor TH1 Thermistor discharge pipe temp.detect 63HS High pressure sensor
52C
TB3 Terminal block transmisson (Inverter main circuit) TH5 pipe temp.detect Electric expansion valve
LEV1
Terminal block transmisson MC Motor Compressor TH6 OA temp.detect (Sub-cool coil bypass)
TB7
centralized control MF Motor Fan Heat exchanger liquid outlet temp. L2 Choke coil(Transmission)
TH7
E Earth terminal MF1 Motor Fan Radiator panel detect at Sub-cool coil IPM Itelligent power module
ACCT-U,W Current Sensor CH1 Crankcase heater (Compressor) bypass outlet temp. X01~04 Axu. Relay

TH8
DCCT Current Sensor 21S4 1 4-way valve detect at Sub-cool coil DC reactor
DCL
R1 Resistor rush current protect Solenoid valve THHS Rediator panel temp.detect (Power factor improvement)
SV1
R2 Resistor power regulation (Discharge-suction bypass) 63LS Low pressure sensor
R20 Resistor 63H High pressure switch DSA Surge suppressor
C1 Capacitor Smoothing ZNR1~ZNR4 Varistor F1,F2,F01 Fuse
LD1 LED display

<Difference of appliance>
Appliance Difference (not existed)
PUHY-200, 250, 315TEM-A

PUY-200, 250, 315TEM-A 1

1- 210
BV1
ST1

63H
PUHY-200, 250, 315

CJ1 CJ2

63HS
ST8 CP3

CP1
O/S

ST3 SV1 63LS

TH6 Indoor units


TH1

1- 211
Comp ST7
ST6

Accumulator

TH8
6. Refrigerant Circuit Diagram And Thermal Sensor

TH5 TH7 ST2 BV2


SCC
LEV1 ST4

TEM-A
TEM-A

1- 212
PUHY-400·500YEM-A(-BF, -BS)
PUHY-400·500YEMK-A
PUHY-400·500YEMC-A(-BS)
CONTENTS

1. Specifications ································································· 1-214

2. Capacity Tables ······························································ 1-216


2-1 Correction by temperature ············································ 1-216
2-2 Correction by total indoor ············································· 1-218
2-3 Correction by refrigerant piping length ··························· 1-219
2-4 Correction at frosting and defrosting ···························· 1-220
2-5 Operation limit ······························································· 1-220

3. Sound Levels ·································································· 1-221

4. External Dimensions ···················································· 1-222

5. Electrical Wiring Diagram ··········································· 1-223

6. Refrigerant Circuit Diagram ········································· 1-224


And Thermal Sensor

Big Y(R22)

1- 213
1. Specifications

PUHY-400YEM-A (-BF, -BS)


PUHY-400YEMK-A
Model name
PUHY-400YEMC-A(-BS)
Cooling Heating
✻1 kW 45.0 50.0
Capacity
✻2 kcal/h 40,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 15.87 14.31

Current A 26.7/25.4/24.5 24.1/22.9/22.1

Type✕ Quantity Propeller fan ✕2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 4.5

Crankcase heater kW 0.045 + 0.045

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity


Big Y(R22)

Indoor unit
Model / Quantity Model 25 ~ 250 / 1 ~ 20

Noise level ✻ dB<A> 60 / 61

Net weight kg 432

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-12˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB ~46˚CDB with outdoor (-12˚CWB~10˚CWB with indoor unit
unit at lower position.) 25 type only is working)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 214
PUHY-500YEM-A (-BF, -BS)
PUHY-500YEMK-A
Model name PUHY-500YEMC-A(-BS)
Cooling Heating
✻1 kW 56.0 63.0
Capacity
✻2 kcal/h 50,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 18.98 17.92

Current A 32.0/30.4/29.3 30.2/28.7/27.7

Type✕ Quantity Propeller fan✕ 2

Fan Airflow rate m3/min 400

Motor output kW 0.38 ✕ 2

Type Hermetic

Compressor Motor output kW 7.5 + 7.5

Crankcase heater kW 0.045 + 0.056

Refrigerant / Lubricant R22 / MS32(N-1)

External finish Pre-coated galvanized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H)✕ 1990(W) ✕ 840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection, thermal switch

Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange)

Total capacity 50 ~ 130% of outdoor unit capacity

Big Y(R22)
Indoor unit
Model / Quantity Model 25 ~ 250 / 1 ~ 20

Noise level ✻ dB<A> 60 / 61

Net weight kg 472

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-12˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB ~46˚CDB with outdoor (-12˚CWB~10˚CWB with indoor
unit at lower position.) unit 25 type only is working)

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 5m Height difference : 0m
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 215
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications

PUHY-400 PUHY-500
Capacity kW 45.0 56.0
Input kW 15.87 18.98

Capacity at 100% indoor units running


1.30

1.20

1.10
Ratio

24˚CWB

22˚CWB
1.00
20˚CWB

18˚CWB
0.90
16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30
24˚CWB
22˚CWB
1.20 20˚CWB
18˚CWB
1.10 16˚CWB
Big Y(R22)

15˚CWB

1.00

0.90
Ratio

0.80

0.70

0.60

0.50 Indoor Temperature(˚CWB)

0.40
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor Temperature (˚CDB)

1- 216
Heating
• Standard Specifications

PUHY-400 PUHY-500
Capacity kW 50.0 63.0
Input kW 14.31 17.92

Capacity at 100% indoor units running


1.30

1.20 Indoor Temperature(˚CDB)


15˚CDB

1.10

1.00 20˚CDB
Ratio

0.90
25˚CDB

0.80
27˚CDB

0.70

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10

1.00 Indoor Temperature(˚CDB)

Big Y(R22)
15˚CDB
0.90
Ratio

0.80 20˚CDB

0.70
25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 217
2-2. Correction by total indoor

PUHY-400
1) Capacity
60
Heating
50
Capacity(kW)

40 Cooling

30

20

10
200 250 300 350 400 450 500
2) Input Total capacity of indoor units

18.0
Cooling
16.0

14.0
Input(kW)

Heating
12.0

10.0

8.0

6.0
200 250 300 350 400 450 500
Total capacity of indoor units

PUHY-500
1) Capacity
70
Heating
Big Y(R22)

60
Capacity(kW)

Cooling
50

40

30

20
250 300 350 400 450 500 550 600 650
Total capacity of indoor units
2) Input
20.0
Cooling
18.0
Heating
Input(kW)

16.0

14.0

12.0

10.0

8.0
250 300 350 400 450 500 550 600 650
Total capacity of indoor units

1- 218
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction

PUHY-400 PUHY-500
1.0 1.0
Total ca Total ca
pacity pacity o
of indo f indoor
or unit unit
Cooling capacity

Cooling capacity
correction factor

correction factor
200 250
0.9 0.9
300 375

500
0.8 0.8
400 650

520
0.7 0.7

0 20 40 60 80 100 120 0 20 40 60 80 100 120


Piping equivalent length (m) Piping equivalent length (m)

•Heating capacity correction

PUHY-400·500
Cooling capacity
correction factor

1.0

0.9

0 20 40 60 80 100 120
Piping equivqlent length (m)

• How to obtain piping equivalent length


➀ PUHY-400
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 ✕ number of bent on the piping)m

Big Y(R22)
➁ PUHY-500
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 ✕ number of bent on the piping)m

1- 219
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.89 0.90 0.92 0.95 0.95 0.95

2-5. Operation limit

• Cooling
Indoor temperature (˚CWB)

30

When the indoor unit is located above


25
the outdoor unit for 4m or more, the
outdoor unit inlet air temperature
20
becomes 10~46˚CDB.

15

10
-5 0 5 10 15 20 25 30 35 40 45 50

Outdoor temperature (˚CDB)

• Heating
Indoor temperature (˚CDB)

30

25
When the indoor unit 25type only is
working, the outdoor unit inlet air
20 temperature becomes -12~10˚CWB.
Big Y(R22)

15

10
-15 -10 -5 0 5 10 15 20
Outdoor temperature (˚CWB)

1- 220
3. Sound Levels
PUHY-400
Measurement condition
50Hz 60Hz

1m

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


70

60
NC60
1m

50
NC50

Sound pressure level in anechoic room 40


NC40
60 / 61 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

PUHY-500
Measurement condition
50Hz 60Hz

1m
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70

Big Y(R22)
60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
60 / 61 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 221
Big Y(R22)

<Accessorys> 15
• Refrigerant (gas) conn. pipe ················· 1pc.
Refrig.service
(The connecting pipe has been fixed with the unit) valve (liquid) Refrig. service
• Packing for conn. pipe ·························· 1pc. valve(gas)
Service valve ø15.88<flare> <flange>
(Attached near the ball valve) (oil balance)
• Conduit mouting plate ø12.7<flare>
(Painted the same color as the unit body)
840
910

Conn. pipe
ø62,ø53,ø46 ·································· Each 1pc. ø27 Knockout hole ø34.93 <brazed>
• Tapping screw 4X10 ····························· 4pcs. <bottom hole for the
control wiring>
880(bolt hole)

• Wiring partition plate ····························· 1pc.

90 80
Note1. Please leave a space under the outdoor unit

169

203
152
for the piping when you connect the piping

111
from the bottom.

73
3X2-14X20 oval hole
15

(Please be careful not to close the hole 230 150 Note.1 215 780(bolt hole) 780(bolt hole) 215
of the bottom plate by the basement) 694 80 82 78 Knockout hole
Bottom piping hole 1990
PUHY-400,500YEM(K,C)-A(-BF, BS)
4. External Dimensions

Bottom hole for the power supply


Changeable to 400:ø46,ø53,ø62 Cross section X-X Plane view
500:ø53,ø62 by using attached
conduit mounting plate (accessory) Air outlet
265

1- 222
Air
inlet

Air
1755

inlet
1490

X Knockout hole X
Service valve
(oil balance)
Refrig. service
745 25 90 75 valve(gas)
Service panel
100
24
149 70

126
86

48

80 40
70

218 Knockout hole


Rear view Front piping hole
Knockout hole Left side hole for the control wiring, Front hole for the power supply 725 115
Refrig.service
the power supply, the oil balance pipe to the Changeable to 400:ø46,ø53,ø62 valve (liquid)
500:ø53,ø62 by using attached 45
constant capacity unit
conduit mounting plate (accessory)
Unit : mm

Front view
Left side view
MC2 Motor MC1 Motor
<ELECTRICAL WIRING DIAGRAM> U V W (Compressor) U VW (Compressor) <Symbol explanation>
Red White Black Red White Black Symbol Name Symbol Name
Inverter
Controller Box DC reactor TH11,12 Thermistor Discharge pipe temp. detect
DCL (Power factor improvement) TH2 Saturation evapo. temp. detect
FB1 FB2
51C2 52C2 TH3
2 1 2 1 ACCT-U,W Current Sensor Accumurator liquid Lower
4 3 4 3 ACCT ZNR4 Varistor TH4 temp. detect Upper
6 5 6 5 -W
Magnetic contactor TH5 Pipe temp. detect(Hex outlet)
ACCT 52C1
Terminal -U (Inverter main circuit) TH6 OA temp. detect
Terminal Noise Diode
Block
Block L1 L2 L3 N stack 52C2 Magnetic contactor SC coil temp.detect
NF Filter R1 R5 IPM
TB1A TB1B FB5 DS TH7
L1 L1 L1 L1 L1 ZNR4 51C2 Overload relay (Liquid exit area)
~+ U V W
+
Power source L2 L2 L2 L2 L2 C1 C2 R2 52F Magnetic contactor(Fan motor) SC coil temp.detect
3N~ ~ P
52C1 C3+
TH8 (Bypass exit area)
380/400/415V L3 L3 L3 L3 L3 R3 MF1 Fan motor (Radiator panel)
50/60Hz ~-
DCL Gate amp board 21S4a,4b 4-way valve TH9a LEV1 temp.detect(Enttance area)
N N N N N N
Y-C (G/A board)
PE board SV1,22,32 Solenoid valve TH9b Composition sensing temp.
4,6 TH10a Gas pipe temp.
600VAC BOX BODY CNE CNDC1 CNDR1 CN15V1 (Hex outlet)
PE BOX BODY F5 8A F (2P) (4P) (9P) (14P) Solenoid valve TH10b
L1 BOX BODY 12 1234 123456789 1 2 3 4 5 6 7 8 9 1011 12 1314 SV5,6,7,8
TB3 F6 600VAC L2 SNB board (Heat exchanger capacity control) TH10c Compressor shell temp.
8A F EARTH
Connect to M1 L3
Indoor and SLEV Electronic expansion valve(Oil return) THHS Radiator panel temp. detect
M2 F3 FB3
remote 250VAC
controller 1A F BOX BODY LEV1 Electronic expansion valve(SC coil) LD Accumulator liquid level detect
BOX BODY CNTR1
M1 63HS High pressure sensor CH11,12 Crank case heater(Compressor)
M2 BOX BODY 63LS Low pressure sensor CH2,3 Cord heater
T01
S
FB4 63H1,2 High pressure switch SSR Solid state relay
TB7 1 1 L2 Choke coil(Transmission) X1,2,4~12 Aux. relay
123 12 1 2 3
CN20 1 2 3 2 2 5 4 3 2 1 CNAC2 1 2 3 4 123456789 1 2 3 4 5 6 7 8 9 10 11 12 13 14
(3P) CNRS3 3 3 (5P)
CNS2 CNS1 CNTR 4 4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) F1 (7P) 5 5 (4P) (9P) IPM Intelligent power module FB1~5 Ferrite core
(3P) 6 6 (7P) (14P)
250VAC 7 7 F01
2A F 1CNVCC4 250VAC T1~10 Terminal
4 CNVCC4 12 Earth terminal
B 3 (2P) 2(2P) 2A F
2 CNAC3
(4P) 1 1
1 2 2 CNVCC2 Power circuit board
A CNVCC343 3 1
CH11 3 (6P) 5 4 (6P)
5
(INV board) CNACCT 2
Crank case heater 6 6 (4P) 3 <Difference of appliance>
2 CN32 4
PUHY-400·500YEM(K,C)-A(-BF, -BS)

1 (3P) X01
X101 1
(Compressor) Appliance Name NOTE:Mark indicates terminal bed
2 2 X01 ✻
3 PUHY-P400YEM " 1" is not existed connector
SV1 2 CN33 3 52C1 3 CNTH CNR CNL2 CN30V
1 (3P) X02 CNX10 X02 PUHY-P500YEM All exists
CN52C (2P) (3P) (2P) (2P) ✻ ✻ ✻ board insertion connector
T10 (3P) (3P) 1 23 CNFAN 1 2 1 2 3 1 2 12 PUHY-400YEM " 1"," 2" and " 3" are not existed
✻ ✻
SV22 6 (3P) PUHY-500YEM " 2" and " 3" are not existed
T9 5
4 CN34
5. Electrical Wiring Diagram

21S4a 3 (6P) X04


SV32 MF1
2
1 X05 <Unit internal layout>
✻ BOX BODY THHS R7 L2 R6
1 SSR
CH2 3 4 3 SV8
1 2 12V 1 TH6
2 CN35 2
1 (3P) 3 A B SV5b
4 4:Compressor ON/OFF 21S4b
5
CH3 Control circuit board 5:Trouble
6 CN51 CN3D
X11 1 21S4a
MODE SV7 SV7 TH10b
5 (MAIN board) (5P) 1-2 1-3 TH10a
TH5TH8
X12 2
4 CN36

1- 223
SV4 21S4b 3 (6P) X06 ON Auto HEAT SV8 ✻3
2 OFF ON Changeover COLL 3 ACCUMULATOR
1 X07 CN3D 32 ON OFF TH2 TH9a
(3P) 1 OFF Normal 4
T7 TH9b TH7 LEV1 SV4 TH3
6 CN3S 32 5 SV6
5 (3P) 1 DEMAND MODE
4 CN3S 1-2 DEMAND SV1
SV6 SV5b CN37 X08 6 63LS 63H1
3 (6P) CN3N 32 SNOW NIGHT ✻3
2 CN3N 1-2 7 TH12
X09 (3P) 1 NIGHT 1-3 SNOW Inverter TH4 SV22
1
8 Controller 63HS MC1 MC2 MC2
High pressure L1 L2 L3 Box Oil separater TH12
CN38 CN06 TH11 ✻3
(3P) TH10c SLEV 63H2 SV32 63H2
switch 63H1
1
X10

2 2
3 detection CNPOW (Front) PUHY-(P)400 PUHY-(P)500
63H2 circuit (5P) 1 2 3 4 5
F03 250VAC 6.3A F
F02 250VAC 6.3A F <Controller box internal layout>
F01 250VAC 6.3A F (Underside)
board (Upside)
CN51C2Relay SW4-6 ✻2
51C2 (3P) 6 T6 6 THHS
1 as connection with R6
5 T5 1 CN04
95 96 2 ON 5
3 PUHN-(P)200/250 CNFC1 4 T4 CNFC2 2 1 RELAY T01 SNB DCL
4 CNFAN U
(6P) 3 T3 (6P) 3 2 X11 X12 board DS
3 (5P) V board
2 T2 4 3 +
OFF 2 W MF2 ZNR4
CN52C2 1 T1 1 5 4 N R2 C2
C1
A1 A2 (5P) X01 -
1
52C2 2 Refer to the service handbook Fan motor
52C2 3 Fan control board 52C2
INV board F5 +
14 13 4 X02
about the switch operations. (Fancon board) N
(Heat exchanger) R3 C3
5 FANCON MAIN board FANCON
CNRT2 - G/A board
CNRT1 51C2 F6
(5P) (5P) board board
CN52F 5 5 (for MF3) (for MF2)
4 4 L1 L2 L3 TB1B
A2 A1 (3P) F3
1 3 3 detection R1 IPM
52F 2 2 2 circuit
3 X03 1 1 R5
ACCT ACCT
CNPOW NF -U -W
(5P) 123 4 5 52F 52C1

F03 250VAC 6.3A F CN04 CN05 R7
2 F02 250VAC 6.3A F TB1A TB3 TB7 L2 MF1
CNOUT1 F01 250VAC 6.3A F
CNOUT2 X12 (6P)
CNCH 6
(3P) (4P) X11 5 52F <Operation of self-diagnosis switch(SW1)and LED display>
CH12 1 4 4 6
3
CN13 CN12 CN09 CN07 CN06 CN05 CN03 CN02 CN01 CNH CNL CNLV1 CNLV2 5 1 2 1 CN05 Display Display at LED lighting (blinking) Remarks SW1 operation
2 3 (4P) (2P) (2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (3P) (5P) (5P)
3 2 2 4 CNFC2 2 1 FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8
1234 12 12 12 12 1234 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 (6P) CNFAN 3 4 3 2 U
1 1 3 (5P) V Relay output During SV22/32 Always
T8 2 4 3 display Compres- 52C1 52C2 21S4a SV1 <LED display>
W MF3 ON:1 (Lighting) sor run
✻1
lighting
1 5 6 5 4 N FLAG8 always
5 OFF:0 Check display1 Display the address and error code by turns LD1
12345678910 lights at
6 Fan motor (at factory shipment) (Blinking) microcomputer
Fan control board (Heat exchanger) power ON
(Fancon board) FLAG1 FLAG8
N FLAG2 FLAG7
LEV1 SV5b is closed
ON:1 FLAG3 FLAG6

White
Red
White
Red

Black
Black
OFF:012345678910 SV4 21S4b SV5b SV6 CH2,3 52F when FLAG3 is FLAG4 FLAG5
turned ON.
3 2 1 3 2 1 SLEV ✻
TH10a TH10b TH9b TH10c TH12 TH9a TH4 TH3 TH6 TH5 TH8 TH7 TH2 TH11 Please refer to the service handbook about other switch settings of LED display.
63HS 63LS
✻ ✻
3 3

Big Y(R22)
Big Y(R22)

❇ There are SV22,SV32 only for PUHY-500YEM(K,C)-A.

21S4b

T10a 21S4a BV1

HEX1b HEX2b ST1


CJ1
63HS SV4

ST5
SV6 CJ2
TH6
O/S
CP1

ST6
SV1 ❇
T10b

1- 224
CP3a SV22 SV32
CP3b
TH11 TH12
CV1 CV2

63H1 63H2 SA MA
No.1 No.2
Comp. SLEV CJ3 Comp.

ST9
HEX1a HEX2a CP4
TH4 ST4 ST3 TH2
TH3
SV5b CP2
TH8 ST8
TH5 BV2
6. Refrigerant Circuit Diagram And Thermal Sensor

ST7 ST2
SCC TH9 TH7 CP5
BV3
LEV1
CV3
PUHY-600·650·700·750YSEM-A (-BF, -BS)
PUHY-600·650·700·750YSEMK-A
PUHY-600·650·700·750YSEMC-A(-BS)
CONTENTS

1. Specifications ································································· 1-226

2. Capacity Tables ······························································ 1-230


2-1 Correction by temperature ············································ 1-230
2-2 Correction by total indoor ············································· 1-232
2-3 Correction by refrigerant piping length ··························· 1-234
2-4 Correction at frosting and defrosting ···························· 1-235
2-5 Operation limit ······························································· 1-235

3. Sound Levels ·································································· 1-236

4. External Dimensions ···················································· 1-238

5. Electrical Wiring Diagram ··········································· 1-241

6. Refrigerant Circuit Diagram ········································· 1-243


And Thermal Sensor

Super Y(R22)

1- 225
1. Specifications
This unit consists of a combination of PUHY-400 and PUHN-200.
PUHY-600YSEM-A(-BF, -BS)
PUHY-600YSEMK-A
Model name PUHY-600YSEMC-A(-BS)
Cooling Heating
✻1 kW 67.4 75.0
Capacity
✻2 kcal/h 60,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 23.23 20.80

Current A 39.2/37.2/35.9 35.1/33.3/32.1

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanaized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz)
61.5 / 62.0

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø34.93


Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB
Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB~46˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

PUHY-400YEM-A(-BF, -BS) PUHN-200YEM-A(-BF, -BS)


Model name PUHY-400YEMK-A PUHN-200YEMK-A
PUHY-400YEMC-A(-BS) PUHN-200YEMC-A(-BS)
Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1
Fan Airflow rate 3
m /min 400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic
Compressor Motor output kW 7.5 + 4.5 5.5

Crankcase heater kW 0.045 + 0.045 0.056

External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)

High pressure protection 2.94MPa


Super Y(R22)

Protection Compressor / Fan Overcurrent protection / Thermal switch


devices
AC bus current protection,
Inverter —
thermal switch
Refrigerant piping diameter Liquid / Gas ø15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 432 248

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 226
This unit consists of a combination of PUHY-400 and PUHN-250.
PUHY-650YSEM(-BF, -BS)
PUHY-650YSEMK-A
Model name
PUHY-650YSEMC-A(-BS)
Cooling Heating
✻1 kW 73.0 81.5
Capacity
✻2 kcal/h 65,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 25.06 22.76

Current A 42.2/40.1/38.7 38.4/36.5/35.1

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz) 62.0 / 62.5

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB~46˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

PUHY-400YEM(-BF, -BS) PUHN-250YEM(-BF, -BS)


Model name PUHY-400YEMK-A PUHN-250YEMK-A
PUHY-400YEMC-A(-BS) PUHN-250YEMC-A(-BS)

Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1


Fan Airflow rate m /min
3
400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1
Type Hermetic

Compressor Motor output kW 7.5 + 4.5 7.5

Crankcase heater kW 0.045 + 0.045 0.056


External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)
Super Y(R22)

High pressure protection 2.94MPa


Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices

Inverter AC bus current protection,



thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 432 263

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 227
This unit consists of a combination of PUHY-500 and PUHN-200.
PUHY-700YSEM-A(-BF,-BS)
PUHY-700YSEMK-A
Model name PUHY-700YSEMC-A(-BS)
Cooling Heating
✻1 kW 78.4 88.0
Capacity
✻2 kcal/h 70,000 _

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 26.87 24.60

Current A 45.3/43.0/41.5 41.5/39.4/38.0


Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets(Powder coating)


<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level dB<A>


✻ (50/60Hz) 61.5 / 62.0

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
(10˚CDB~46˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

PUHY-500YEM-A(-BF,-BS) PUHN-200YEM-A(-BF,-BS)
Model name PUHY-500YEMK-A PUHN-200YEMK-A
PUHY-500YEMC-A(-BS) PUHN-200YEMC-A(-BS)
Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1
Fan Airflow rate m3/min 400 200

Motor output kW 0.38 ✕ 2 0.38 ✕ 1

Type Hermetic
Compressor Motor output kW 7.5 + 7.5 5.5

Crankcase heater kW 0.045 + 0.056 0.056

External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)

High pressure protection


Super Y(R22)

2.94MPa
Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
Inverter AC bus current protection,

thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 472 248


Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 228
This unit consists of a conbination of PUHY-500 and PUHN-250.
PUHY-750YSEM-A(-BF, -BS)
PUHY-750YSEMK-A
Model name
PUHY-750YSEMC-A(-BS)
Cooling Heating
✻1 kW 84.0 94.5
Capacity
✻2 kcal/h 75,000 –

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 28.69 26.55


Current A 48.4/46.0/44.3 44.8/42.5/41.0
Refrigerant / Lubricant R22/MS32(N-1)
External finish Pre-coated galvanized sheets(Powder coating)
<MUNSELL 5Y8/1 or similar>
Total capacity 50 ~ 130% of outdoor unit capacity
Indoor unit
Model / Quantity Model 20 ~ 250 / 2 ~ 32

Noise level ✻ dB<A>


(50/60Hz)
62.0 / 62.5

Refrigerant piping diameter (main) Liquid / Gas ø 19.05 / ø 41.28

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Operating temperature range Outdoor:-5˚CDB ~ 46˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
(10˚CDB~46˚CDB with outdoor unit (-12˚CWB~10˚CWB with indoor unit
at lower position) 20 or 25 type only is working)

PUHY-500YEM-A(-BF, -BS) PUHN-200YEM-A(-BF, -BS)


PUHY-500YEMK-A PUHN-250YEMK-A
PUHY-500YEMC-A(-BS) PUHN-250YEMK-A(-BS)

Type✕ Quantity Propeller fan ✕ 2 Propeller fan ✕ 1


Fan Airflow rate m3/min 400 200
Motor output kW 0.38 ✕ 2 0.38 ✕ 1

Type Hermetic

Compressor Motor output kW 7.5 + 7.5 7.5

Crankcase heater kW 0.045 + 0.056 0.056

External dimension mm 1755(H)✕ 1990(W) ✕ 840(L) 1755(H)✕ 990(W)✕ 840(L)

High pressure protection


Super Y(R22)

2.94MPa
Protection
Compressor / Fan Overcurrent protection / Thermal switch
devices
AC bus current protection,
Inverter —
thermal switch
Refrigerant piping diameter Liquid / Gas ø 15.88 (Flare) / ø 34.93 (Flange) ø 12.7 (Flare) / ø 28.58 (Flange)

Net weight kg 472 263

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB ✻2 Cooling Indoor : 27˚CDB/19.5˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB Pipe length : 10m Height difference : 0m
Pipe length : 12.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 229
2. Capacity Tables
2-1. Correction by temperature

Cooling
• Standard Specifications (Outdoor 35°CDB/ - Indoor 27°CDB/19°CWB)

PUHY-600 PUHY-650 PUHY-700 PUHY-750


Capacity kW 67.4 73.0 78.4 84.0
Input kW 23.23 25.06 26.87 28.69

Capacity at 100% indoor units runing


1.30

1.20

1.10
24˚CWB
Ratio

22˚CWB
1.00
20˚CWB

18˚CWB
0.90
16˚CWB
Indoor Temperature(˚CWB) 15˚CWB

0.80
-5 0 5 10 15 20 25 30 35 40 45 50
Outdoor Temperature (˚CDB)

Power Input at 100% indoor units running


1.30 24˚CWB
22˚CWB
1.20 20˚CWB
18˚CWB
16˚CWB
1.10 15˚CWB
Indoor Temperature(˚CWB)
1.00

0.90
Ratio

0.80
Super Y(R22)

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45 50
Outdoor Temperature (˚CDB)

1- 230
Heating
• Standard Specifications (Outdoor 7°CDB/6°CWB Indoor 20°CDB/ - )

PUHY-600 PUHY-650 PUHY-700 PUHY-750


Capacity kW 75.0 81.5 88.0 94.5
Input kW 20.80 22.76 24.60 26.55

Capacity at 100% indoor units runing


1.30

1.20
15˚CDB
1.10 Indoor Temperature(˚CDB)

20˚CDB
1.00
Ratio

0.90
25˚CDB
0.80
27˚CDB

0.70

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100% indoor units running


1.10

1.00
Indoor Temperature(˚CDB)
15˚CDB
0.90
Ratio

0.80
20˚CDB
Super Y(R22)

0.70
25˚CDB
0.60
27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)

1- 231
2-2. Correction by total indoor

PUHY-600
1) Capacity
80

Heating
70
Cooling
Capacity(kW)

60

50

40

30
300 350 400 450 500 550 600 650 700 750
Total capacity of indoor units
2) Input
30.0

Cooling
25.0
Input(kW)

20.0

Heating
15.0

10.0
300 350 400 450 500 550 600 650 700 750
Total capacity of indoor units

PUHY-650
1) Capacity
90

80 Heating
Capacity(kW)

70
Cooling
60

50

40
Super Y(R22)

30
300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units
2) Input
30.0

Cooling
25.0
Input(kW)

20.0
Heating

15.0

10.0
300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units

1- 232
PUHY-700
1) Capacity
100
Heating
90
Capacity(kW)

80

70 Cooling

60

50

40

30
350 400 450 500 550 600 650 700 750 800 850 900
Total capacity of indoor units
2) Input
35.0

30.0 Cooling
Input(kW)

25.0

20.0
Heating
15.0

10.0
350 400 450 500 550 600 650 700 750 800 850 900
Total capacity of indoor units
PUHY-750
1) Capacity
100
Heating
90
Capacity(kW)

80 Cooling

70

60

50
Super Y(R22)

40
350 400 450 500 550 600 650 700 750 800 850 900 950
Total capacity of indoor units
2) Input
35.0

30.0
Cooling
Input(kW)

25.0

20.0 Heating

15.0

10.0
350 400 450 500 550 600 650 700 750 800 850 900 950
Total capacity of indoor units

1- 233
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction

PUHY-600 PUHY-650
1.0 1.0 Total capa
Total ca city of in
pacity door unit
of indo
or unit
Cooling capacity

Cooling capacity
correction factor

correction factor
325
0.9 300 0.9 488
450 650

8.0 600 8.0 845

780
7.0 7.0

0 20 40 60 80 100 120 0 20 40 60 80 100 120


Piping equivalent length (m) Piping equivalent length (m)

PUHY-700 PUHY-750
1.0 Total ca 1.0 Total ca
pacity o pacity
f indoor of indo
unit or unit
Cooling capacity

Cooling capacity
correction factor

correction factor

350 375
0.9 525 0.9
563
700 750

8.0 910 8.0 975

7.0 7.0

0 20 40 60 80 100 120 0 20 40 60 80 100 120


Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction

PUHY-600·650·700·750
Cooling capacity
correction factor

1.0
Super Y(R22)

0.9

0 20 40 60 80 100 120
Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PUHY-600
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 ✕ number of bent on the piping)m
➁ PUHY-650~750
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.95 ✕ number of bent on the piping)m

1- 234
2-4 Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Outdoor inlet air temp


(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.98 0.89 0.89 0.90 0.92 0.95 0.95 0.95

2-5 Operation limit

• Cooling
30
Indoor temperature (˚CWB)

25
When the indoor unit is located above
the outdoor unit for 4m or more, the
20
outdoor unit inlet air temperature
becomes 10~46˚CDB.
15

10
-5 0 5 10 15 20 25 30 35 40 45 50

• Heating
30
Indoor temperature (˚CDB)

25
When the indoor unit 20 or 25type only is
20 working, the outdoor unit inlet air
temperature becomes -12~10˚CWB.
15

10
-15 -10 -5 0 5 10 15 20
Outdoor temperature (˚CWB) Super Y(R22)

1- 235
3. Sound Levels
PUHY-600
Measurement condition
50Hz 60Hz

1m

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


70

60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
61.5 / 62.0 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

PUHY-650
Measurement condition
50Hz 60Hz

1m
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70

60
NC60
1m

50 NC50
Super Y(R22)

Sound pressure level in anechoic room 40


NC40
62.0 / 62.5 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 236
PUHY-700
Measurement condition
50Hz 60Hz

1m
70

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


60
NC60
1m

50 NC50

Sound pressure level in anechoic room 40


NC40
61.5 / 62.0 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

PUHY-750
Measurement condition 50Hz 60Hz

1m
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

60
NC60
1m

50
NC50
Super Y(R22)

Sound pressure level in anechoic room 40


NC40
62.0 / 62.5 dB (A)

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

1- 237
Super Y(R22)

<Accessorys>

15
• Refrigerant (gas) conn. pipe ················· 1pc.
(The connecting pipe has been fixed with the unit)
• Packing for conn. pipe ·························· 1pc. Refrig.service
(Attached near the ball valve) valve (liquid) Refrig. service
valve(gas)
• Conduit mouting plate Service valve ø15.88<flare> <flange>
(Painted the same color as the unit body) (oil balance)
ø62,ø53,ø46 ·································· Each 1pc. ø12.7<flare>
840
910

• Tapping screw 4X10 ····························· 6pcs. Conn. pipe


ø27 Knockout hole ø34.93 <brazed>
• Wiring partition plate ····························· 1pc. <bottom hole for the
control wiring>
880(bolt hole)

Note1. Please leave a space under the outdoor unit


for the piping when you connect the piping

90 80
169

203
152
from the bottom.

111
(Please be careful not to close the hole

73
of the bottom plate by the basement) 3X2-14X20 oval hole
15

230 150 Note.1 215 780(bolt hole) 780(bolt hole) 215


694 80 82 78 Knockout hole
Bottom piping hole 1990
Bottom hole for the power supply
4. External Dimensions

Changeable to 400:ø46,ø53,ø62 Cross section X-X Plane view


500:ø53,ø62 by using attached
PUHY-400,500YEM(-K, -C)-A(-BF, -BS)

conduit mounting plate (accessory) Air outlet


265

1- 238
Air
inlet

Air
1755

inlet
1490

X Knockout hole X
Service valve
(oil balance)
Refrig. service
745 25 90 75 valve(gas)
100 Service panel
24
149 70

126
86

Knockout hole
48

80 40
70

Left side hole for 218 Knockout hole


the control wiring, Front piping hole
the power supply, the 725 115
Front hole for the power supply Refrig.service
oil balance pipe to the Changeable to 400:ø46,ø53,ø62 45 valve (liquid)
constant capacity unit 500:ø53,ø62 by using attached
conduit mounting plate (accessory)
Rear view Left side view Front view
Unit : mm
<Accessorys>

15
• Refrigerant (gas) conn. pipe···························1pc.
Note.1 (The connecting pipe has been fixed with the unit)
ø27 Knockout hole Y ø40 Knockout hole • Packing for conn. pipe····································1pc.
12 5 Bottom piping hole Bottom hole for the power supply
(oil balance) Changeable to ø27,ø33 by using (Attached near the ball valve)
attached conduit mounting plate • Conduit mouting plate
Y (accessory)
(Painted the same color as the unit body)
Note.1 ø40,ø33,ø27····················································Each 1pc.

840
910
Knockout hole ø27 Knockout hole
<bottom hole for the • Tapping screw 4✕12·······································4pcs.
Bottom piping hole

600
control wiring> • Oil balance conn. pipe (to the variable capacity unit

880(bolt hole)

50
through the right side panel knockout hole)·········1pc.
• Sealing···························································2pcs.

237
168
130
121

73 80
Note1. Please leave a space under the outdoor unit
25 160 2X2-14X20
for the piping when you connect the piping

15
778 75 135 oval hole 215 560(bolt hole) 215
Conn. pipe 584 from the bottom.
ø28.58<brazed> 990 (Please be careful not to close the hole
of the bottom plate by the basement)
Cross section Y-Y Cross section X-X Plane view
Air outlet
PUHN-200, 250YEM(-K,-C)-A(-BF, -BS)

265

1- 239
Air
inlet
1490

Air
1755

Knockout hole
Front piping hole Service valve inlet
(oil balance) (oil balance)
ø12.7<flare>
Refrig.service
valve (liquid) Service panel
ø12.7<flare>
X X
Knockout hole
Front piping hole
Knockout hole

40
115

100
99

149
142

78

70
Knockout hole

48
79 80 425
48

Right side hole for


80 40 813 40 80 the control wiring,
Knockout hole Refrig. service
Left side hole for refrig. Front hole for the power supply the power supply,
valve(gas) 55 the oil balance pipe to
(liquid,gas) conn. pipe <flange> 31 165 190 345 55 Changeable to ø27,ø33,ø40
Unit : mm

by using attached conduit the variable capacity unit


mounting plate (accessory)

Rear view Left side view Front view Right side view

Super Y(R22)
Super Y(R22)

990 10 1990 910


840

Constant capacity unit Variable capacity unit Air outlet

Air
inlet
Air
inlet
PUHY-600,650,700,750YSEM-A(-BF, -BS)

Note 1.Please install the constant capacity unit


and the variable capacity unit on a same

1- 240
level stand.
2.Pipe size is as follws.
d 3.Please install the constant capacity unit
g
and the variable capacity unit side by side,
Note.1 the constant capacity unit on the left side
and the variable capacity unit on the right
c side.
e
Front view Right side view 4.Distributor kit(Accessory) is needed to compose
PUHY-600~750YSEM-A(-BF,-BS).
f Distributor
(gas) ❇3
Oil balance pipe
❇3 Distributor 600 650 700 750
a b
(liquid) ❇3 Indoor units ~ liquid a ø19.05
Distributer gas b ø34.93 ø41.28
Indoor units
Distributer ~ liquid c ø15.88
Variable capacity unit gas d ø34.93 ❇1 ❇1 This pipe has been fixed.
❇2 The oil balance pipe is usually
Distributer ~ liquid e ø12.7
fixed inside of the unit.
Constant capacity unit gas f ø28.58 ❇3 Accessory
Oil balance pipe g ø12.7 ❇2
Unit : mm
MC2 Motor MC1 Motor
<ELECTRICAL WIRING DIAGRAM> U V W (Compressor) U VW (Compressor) <Symbol explanation>
Red White Black Red White Black Symbol Name Symbol Name
Inverter
Controller Box DC reactor TH11,12 Thermistor Discharge pipe temp. detect
DCL (Power factor improvement) TH2 Saturation evapo. temp. detect
FB1 FB2
51C2 52C2 TH3
2 1 2 1 ACCT-U,W Current Sensor Accumurator liquid Lower
4 3 4 3 ACCT ZNR4 Varistor TH4 temp. detect Upper
6 5 6 5 -W
Magnetic contactor TH5 Pipe temp. detect(Hex outlet)
ACCT 52C1
Terminal -U (Inverter main circuit) TH6 OA temp. detect
Terminal Noise Diode
Block
Block L1 L2 L3 N stack 52C2 Magnetic contactor SC coil temp.detect
NF Filter R1 R5 IPM
TB1A TB1B FB5 DS TH7
L1 L1 L1 L1 L1 ZNR4 51C2 Overload relay (Liquid exit area)
~+ U V W
+
Power source L2 L2 L2 L2 L2 C1 C2 R2 52F Magnetic contactor(Fan motor) SC coil temp.detect
3N~ ~ P
52C1 C3+
TH8 (Bypass exit area)
380/400/415V L3 L3 L3 L3 L3 R3 MF1 Fan motor (Radiator panel)
50/60Hz ~-
DCL Gate amp board 21S4a,4b 4-way valve TH9a LEV1 temp.detect(Enttance area)
N N N N N N
Y-C (G/A board)
PE board SV1,22,32 Solenoid valve TH9b Composition sensing temp.
4,6 TH10a Gas pipe temp.
600VAC BOX BODY CNE CNDC1 CNDR1 CN15V1 (Hex outlet)
PE BOX BODY F5 8A F (2P) (4P) (9P) (14P) Solenoid valve TH10b
L1 BOX BODY 12 1234 123456789 1 2 3 4 5 6 7 8 9 1011 12 1314 SV5,6,7,8
TB3 F6 600VAC L2 SNB board (Heat exchanger capacity control) TH10c Compressor shell temp.
8A F EARTH
Connect to M1 L3
Indoor and SLEV Electronic expansion valve(Oil return) THHS Radiator panel temp. detect
M2 F3 FB3
remote 250VAC
controller 1A F BOX BODY LEV1 Electronic expansion valve(SC coil) LD Accumulator liquid level detect
BOX BODY CNTR1
M1 63HS High pressure sensor CH11,12 Crank case heater(Compressor)
M2 BOX BODY 63LS Low pressure sensor CH2,3 Cord heater
T01
S
FB4 63H1,2 High pressure switch SSR Solid state relay
TB7 1 1 L2 Choke coil(Transmission) X1,2,4~12 Aux. relay
123 12 1 2 3
CN20 1 2 3 2 2 5 4 3 2 1 CNAC2 1 2 3 4 123456789 1 2 3 4 5 6 7 8 9 10 11 12 13 14
(3P) CNRS3 3 3 (5P)
CNS2 CNS1 CNTR 4 4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) F1 (7P) 5 5 (4P) (9P) IPM Intelligent power module FB1~5 Ferrite core
(3P) 6 6 (7P) (14P)
250VAC 7 7 F01
2A F 1CNVCC4 250VAC T1~10 Terminal
4 CNVCC4 12 Earth terminal
B 3 (2P) 2(2P) 2A F
2 CNAC3
(4P) 1 1
1 2 2 CNVCC2 Power circuit board
A CNVCC33 3 1
CH11 3 (6P) 45 4 (6P)
5
(INV board) CNACCT 2
Crank case heater 6 6 (4P) 3 <Difference of appliance>
2 CN32 4
PUHY-400·500YEM(-K,-C)-A(-BF, -BS)

1 (3P) X01
X101 1
(Compressor) Appliance Name NOTE:Mark indicates terminal bed
2 2 X01 ✻
3 PUHY-P400YEM " 1" is not existed connector
SV1 2 CN33 3 52C1 3 CNTH CNR CNL2 CN30V
1 (3P) X02 CNX10 X02 PUHY-P500YEM All exists
CN52C (2P) (3P) (2P) (2P) ✻ ✻ ✻ board insertion connector
T10 (3P) (3P) 1 23 CNFAN 1 2 1 2 3 1 2 12 PUHY-400YEM " 1"," 2" and " 3" are not existed
✻ ✻
5. Electrical Wiring Diagram

SV22 6 (3P) PUHY-500YEM " 2" and " 3" are not existed
T9 5
21S4a 4 CN34
3 (6P) X04 MF1
SV32
2
1 X05 <Unit internal layout>
✻ BOX BODY THHS R7 L2 R6
1 SSR
CH2 3 4 3 SV8
1 2 12V 1 TH6
2 CN35 2
1 (3P) 3 A B SV5b
4 4:Compressor ON/OFF 21S4b
5
CH3 Control circuit board 5:Trouble 21S4a
CN51

1- 241
X11 1
6 CN3D SV7 TH10b
5 (5P) MODE SV7 TH10a
(MAIN board) 1-2 1-3 X12 2
TH5TH8
SV4 21S4b 4 CN36 X06 ON Auto HEAT SV8
3 (6P) ✻3
2 OFF ON Changeover COLL 3 ACCUMULATOR
1 X07 CN3D 32 ON OFF TH2 TH9a LEV1
(3P) 1 OFF Normal 4
T7 TH9b TH7 SV4 TH3
6 CN3S 32 5 SV6
5 (3P) 1 DEMAND MODE
4 CN37 CN3S 1-2 DEMAND 6 63LS SV1
SV6 SV5b 3 (6P) X08 SNOW 1-2 NIGHT ✻3
63H1
CN3N 32 TH12
2 (3P) 1 CN3N 1-3 SNOW 7 Inverter
1 X09 NIGHT TH4 SV22
8 Controller 63HS MC1 MC2 MC2
High pressure L1 L2 L3 Box Oil separater TH12
CN38 CN06 TH11 ✻3
(3P) TH10c SLEV 63H2 SV32 63H2
switch 63H1
1
X10

2 2
3 detection CNPOW (Front) PUHY-(P)400 PUHY-(P)500
63H2 circuit (5P) 1 2 3 4 5
F03 250VAC 6.3A F
F02 250VAC 6.3A F <Controller box internal layout>
F01 250VAC 6.3A F (Underside)
board (Upside)
CN51C2Relay SW4-6 ✻2
51C2 (3P) 6 T6 6 THHS
1 as connection with R6
5 T5 1 CN04
95 96 2 ON 5
3 PUHN-(P)200/250 CNFC1 4 T4 CNFC2 2 1 RELAY T01 SNB DCL
4 CNFAN U
(6P) 3 T3 (6P) 3 2 X11 X12 board DS
3 (5P) V board
2 T2 4 3 +
OFF 2 W MF2 ZNR4
CN52C2 1 T1 1 5 4 N R2 C2
C1
A1 A2 (5P) X01 -
1
52C2 2 Refer to the service handbook Fan motor
52C2 3 Fan control board 52C2
INV board F5 +
14 13 4 X02
about the switch operations. (Fancon board) N
(Heat exchanger) R3 C3
5 FANCON MAIN board FANCON
CNRT2 - G/A board
CNRT1 51C2 F6
(5P) (5P) board board
CN52F 5 5 (for MF3) (for MF2)
4 4 L1 L2 L3 TB1B
A2 A1 (3P) F3
1 3 3 detection R1 IPM
52F 2 2 2 circuit
3 X03 1 1 R5
ACCT ACCT
CNPOW NF -U -W
(5P) 123 4 5 52F 52C1

F03 250VAC 6.3A F CN04 CN05 R7
2 F02 250VAC 6.3A F TB1A TB3 TB7 L2 MF1
CNOUT1 F01 250VAC 6.3A F
CNOUT2 X12 (6P)
CNCH 6
(3P) (4P) X11 5 52F <Operation of self-diagnosis switch(SW1)and LED display>
CH12 1 4 4 6
3
CN13 CN12 CN09 CN07 CN06 CN05 CN03 CN02 CN01 CNH CNL CNLV1 CNLV2 5 1 2 1 CN05 Display Display at LED lighting (blinking) Remarks SW1 operation
2 3 (4P) (2P) (2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (3P) (5P) (5P)
3 2 2 4 CNFC2 2 1 FLAG1 FLAG2 FLAG3 FLAG4 FLAG5 FLAG6 FLAG7 FLAG8
1234 12 12 12 12 1234 123 12345678 12 1 2 3 1 2 3 1234 5 1234 5 (6P) CNFAN 3 4 3 2 U
1 1 3 (5P) V Relay output During SV22/32 Always
T8 2 4 3 display Compres- 52C1 52C2 21S4a SV1 <LED display>
W MF3 ON:1 (Lighting) sor run
✻1
lighting
1 5 6 5 4 N FLAG8 always
5 OFF:0 Check display1 Display the address and error code by turns LD1
12345678910 (Blinking) lights at
6 Fan motor (at factory shipment) microcomputer
Fan control board (Heat exchanger) power ON
(Fancon board) FLAG1 FLAG8
N FLAG2 FLAG7
LEV1 SV5b is closed
ON:1 FLAG3 FLAG6

White
Red
White
Red

Black
Black
OFF:012345678910 SV4 21S4b SV5b SV6 CH2,3 52F when FLAG3 is FLAG4 FLAG5
turned ON.
3 2 1 3 2 1 SLEV ✻
TH10a TH10b TH9b TH10c TH12 TH9a TH4 TH3 TH6 TH5 TH8 TH7 TH2 TH11 Please refer to the service handbook about other switch settings of LED display.
63HS 63LS
✻ ✻
3 3

Super Y(R22)
Super Y(R22)

Controller Box

TB1 51C1 52C1

L1 L1 Red 2 1 2 1 Red Motor (Compressor)

Power source U
L2 L2 White 4 3 4 3 White
3N~ V MC1
380/400/415V W
50Hz/60Hz 5 5 Black
L3 L3 Black 6 6

N N Blue Model 200:24A SYMBOL NAME SYMBOL NAME

Model 250:27A ZNR01 VARISTOR TH3 THERMISTER


PE
SSR SOLID STATE RELAY TH4 THERMISTER

F1 FUSE(6.3A) <CONT BOARD> TH5 THERMISTER


PE Box body
F1,F2 FUSE(8A) TH6 THERMISTER
Box body
F3 FUSE(1A) TH7 THERMISTER
TB3
M1 52C1 MAGNET CONTACTOR TH8 THERMISTER
F3
Inverter L3 L2 L1
250VAC
unit M2 51C1 OVER CURRENT RELAY TH9 THERMISTER
1A F

S F2 F1 MC1 ELECTRIC MOTOR OF COMPRESSOR TH10a THERMISTER


T01 600VAC 600VAC
8A F 8A F MF FAN MOTOR(HEAT EXCHANGER) TH10b THERMISTER
CN20
CH11 CRANK CASE HEATER(COMPRESSOR) LEV1 ELECTRONIC EXPANSION VALVE
(3P)
1 2 1 2 3 1 2
CNS1 CNTR CH2,CH3 CORD HEATER LEV2 ELECTRONIC EXPANSION VALVE
(2P) F1 (2P)
250VAC
21S4 4-WAY VALVE X01~X07 RELAY
6 6.3A F

21 5 NF SV1,SV4 SOLENOID VALVE SW2,SW3 SWITCH


4 ZNR01 L3 L2 L1
S4 X01 Noise
SV1 3
SV5b SOLENOID VALVE SWU1,2 SWITCH
2 CN33
Filter
X02
1 (6P) 63H HIGH PRESSURE CUT OUT SWITCH TB1 POWER SOURCE TERMINAL BLOCK

X03
PUHN-200·250YEM(-K,-C)-A(-BF, -BS)

3 63LS LOW SIDE PRESSURE SENSOR EARTH TERMINAL


2 CN39 Control circuit board
Box body
1 (3P) L3 L2 L1 SCRM TH11 THERMISTER
(CONT board)
UG1 UK1
UK2 UG2

6
SV 5 G K Red

Red
L1 U
4 CN34

Black
5b

White
SV4 X04 K G
3 (6P)

1- 242
VK1
2 CNMF
X05 VG1
1 1
G K 2 U
L2 V V
SSR01 3
K G W MF
CH2 4 3 VK2 N
1
1 2 VG2
2 CN35 CN04 Fan motor
CH3 G K
3 (3P) SW3-10 are OFF for Model 200. (Heat exchanger)
L3 W
K G Black
and ON for Model 250.
CN38
(3P)
63H 1 WG1 WK1
2 WK2 WG2
3 Detection
circuit
CN46
51C (3P)
1
2
3 Detection
circuit Fan control board
CH11
3 (Fancon board) 1 UK1
2 CNCH11 1 1 2 UG1
1 (3P) X06 CNFC1 2 2 CNFC2 CNU 3
(6P) 3 3 (6P) (5P) 4
4 4 UK2
5 5 5 UG2
CNW CNV
A2 6 6
(5P) (5P)
52 5
5 4 3 2 1 5 4 3 2 1
C1 4 CN52C1
A1 52C1
13 14 3 (5P)
2
X07
1

CN12 CN09 CN06 CN05 CN03 CN02 CN01 CNL CNLV1 CNLV2
(2P) (2P) (2P) (4P) (3P) (8P) (2P) (3P) (5P) (6P)

WG2
WK2
WG1
WK1
VG2
VK2
VG1
1 2 1 2 1 2 1 2 3 4 1 2 3 1 2 3 4 5 6 7 8 1 2 1 2 3 1 2 3 4 5 1 2 3 4 5 6 VK1

White
Red

Black
3 2 1 LEV1 LEV2
TH10b TH10a TH9 TH4 TH3 TH6 TH5 TH8 TH7 TH11
63LS
❇ There are SV22,SV32 only for PUHY-700, 750.
21S4b

21S4a BV1
TH10a
ST1
HEX1b HEX2b CJ1
63HS SV4 Distributer (Gas)

TH6 ST5
SV6 CJ2
O/S
CP1
TH10b ST6 ❇
SV1 SV22 SV32
CP3a
TH11 CP3b
CV1 CV2 TH12

MA
63H1 SA
Comp1 63H2 Comp2 Indoor unit
SLEV CJ3

HEX1a HEX2a ST9


CP4 TH4
ST4 TH3 ST3 TH2
SV5b CP2
TH8 ST10 ST8 BV2
TH5

ST7 ST2
SCC TH9 TH7
BV3
LEV1 CV3

CP5

1- 243
BV1
21S4
CJ1 ST1
SV4 Oil balance
ST5 pipe
CV1

O/S CJ2
CP1
TH10a ST6
CP3
SV1

TH11

TH6 MA
63H Comp1
SA
TH3 Distributer (Liquid)
63LS
HEX1 HEX2 ST3
6. Refrigerant Circuit Diagram And Thermal Sensor

TH4 ST4
TH8
TH5 ST10 ST8 CV2 BV2
ST9

TH7 SV5b CP5 ST2


SCC TH9
LEV2
LEV1 ST7 BV3

TH10b

Super Y(R22)
Super Y(R22)

1- 244
PURY-200·250YEMC-A
CONTENTS

1. Specifications ································································· 1-246

2. Capacity Tables ······························································ 1-248


2-1 Correction by temperature ············································ 1-248
2-2 Correction by total indoor ············································· 1-250
2-3 Correction by refrigerant piping length ··························· 1-251
2-4 Correction at frosting and defrosting ···························· 1-252
2-5 Operation limit ······························································· 1-252

3. Sound Levels ·································································· 1-253

4. External Dimensions ···················································· 1-254

5. Electrical Wiring Diagram ·············································· 1-255

6. Refrigerant Circuit Diagram ········································· 1-256


And Thermal Sensor

R2(R22)

1- 245
1. Specifications

PURY-200YEMC-A
Model name
Cooling Heating
Capacity ✻1 kW 24.6 25.0

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 9.65 7.66

Current A 16.2/15.4/14.9 12.9/12.2/11.8

Type ✕Quantity Propeller fan ✕1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 6.6

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>
External dimension mm 1755(H) ✕990(W) ✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 25.4 (Flange)

Total capacity 50 ~ 150% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 15

Noise level ✻ dB<A> 56

Net weight kg 238

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Matters Deserving Special Mention A pipe of 28.58 can be used for the low pressure pipe

Matters Deserving Special Mention A pipe of 28.58 can be used for the low pressure pipe.
Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
R2(R22)

✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB


Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB
Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 246
PURY-250YEMC-A
Model name
Cooling Heating
Capacity ✻1 kW 28.0 31.5

Power source 3N ~ 380/400/415V 50/60Hz

Power input kW 10.56 9.74

Current A 17.8/16.9/16.3 16.4/15.6/15.0

Type ✕Quantity Propeller fan ✕1

Fan Airflow rate m3/min 200

Motor output kW 0.38

Type Hermetic

Compressor Motor output kW 7.5

Crankcase heater kW 0.045(240V)

Refrigerant / Lubricant R22/MS32(N-1)

External finish Pre-coated galvanized sheets


<MUNSELL 5Y8/1 or similar>

External dimension mm 1755(H) ✕990(W) ✕840(L)

High pressure protection 2.94MPa


Protection
Compressor / Fan Over current protection / Thermal switch
devices
Inverter DC bus current protection, thermal switch

Refrigerant piping diameter High press. / Low press. ø 19.05 (Flare) / ø 28.58 (Flange)

Total capacity 50 ~ 150% of outdoor unit capacity


Indoor unit
Model / Quantity Model 20 ~ 250 / 1 ~ 16

Noise level ✻ dB<A> 57

Net weight kg 240

Indoor:15˚CWB ~ 24˚CWB Indoor:15˚CDB ~ 27˚CDB


Outdoor:-5˚CDB ~ 43˚CDB Outdoor:-15˚CWB ~ 15.5˚CWB
Operating temperature range
-5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB with cooling/heating
mixed operation.

Note: 1.Cooling/heating capacity indicates the maximum value at operation under the following condition.
✻1 Cooling Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB
Heating Indoor : 20˚CDB Outdoor : 7˚CDB/6˚CWB
R2(R22)

Pipe length : 7.5m Height difference : 0m

✻ It is measured in anechoic room.

1- 247
2. Capacity Tables
2-1. Correction by temperature
Cooling
• Standard Specifications
PURY-200 PURY-250
Capacity kW 24.6 28.0
Input kW 9.65 10.56

Capacity at 100%indoor units running


1.30

1.20

1.10
Ratio

24˚CWB
22˚CWB
1.00
20˚CWB
19˚CWB
18˚CWB
16˚CWB
0.90
15˚CWB
Indoor Temperature(˚CWB)

0.80
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)

Power Input at 100%indoor units running


1.30
24˚CWB

1.20 22˚CWB
20˚CWB
1.10 19˚CWB

18˚CWB
1.00
16˚CWB
0.90
Ratio

Indoor Temperature(˚CWB) 15˚CWB

0.80

0.70

0.60

0.50
0.40
-5 0 5 10 15 20 25 30 35 40 45
Outdoor Temperature (˚CDB)
R2(R22)

1- 248
Heating
• Standard Specifications
PURY-200 PURY-250
Capacity kW 25.0 31.5
Input kW 7.66 9.74

Capacity at 100%indoor units running


1.30
15˚CDB
1.20

1.10
20˚CDB
1.00
Ratio

Indoor Temperature(˚CDB)
0.90

0.80 25˚CDB

0.70 27˚CDB

0.60
-15 -10 -5 0 5 10 15 20

Outdoor Temperature (˚CWB)

Power Input at 100%indoor units running


1.10
Indoor Temperature(˚CDB)

1.00 15˚CDB

0.90
20˚CDB
Ratio

0.80

0.70
25˚CDB

0.60 27˚CDB

0.50
-15 -10 -5 0 5 10 15 20
Outdoor Temperature (˚CWB)
R2(R22)

1- 249
2-2. Correction by total indoor

PURY-200
1) Capacity
30.0
Heating
Capacity(kW)

25.0

Cooling
20.0

15.0

10.0

5.0
100 150 200 250 300 350
Total capacity of indoor units
2) Input
12.00
11.00
Cooling
10.00
9.00
Input(kW)

8.00
7.00
Heating
6.00
5.00
4.00
3.00
100 150 200 250 300 350
Total capacity of indoor units

PURY-250
1) Capacity
35.0
Heating
30.0
Capacity(kW)

Cooling
25.0

20.0

15.0

10.0
100 150 200 250 300 350 400
Total capacity of indoor units
2) Input
12.00
11.00
R2(R22)

Cooling
10.00
9.00
Input(kW)

8.00
Heating
7.00
6.00
5.00
4.00
3.00
100 150 200 250 300 350 400
Total capacity of indoor units

1- 250
2-3. Correction by refrigerant piping length

To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity
correction factor based on the refrigerant piping equivalent length in the table below.

• Cooling capacity correction


PURY-200 PURY-250
1.0 1.0
Total ca Total ca
pacity pacity
of indo of indo
Cooling capacity

Cooling capacity
correction factor

correction factor
or unit or unit
100 125
0.9 0.9
150 188
200 250
0.8 0.8
300 375

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• Heating capacity correction


PURY-200 PURY-250
1.0 Total capacity 1.0 Total capacity
of indoor unit of indoor unit
100 125
Heating capacity

Heating capacity
correction factor

correction factor

0.9 150 0.9 188

200 or more 250 or more


0.8 0.8

0.7 0.7
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Piping equivalent length (m) Piping equivalent length (m)

• How to obtain piping equivalent length


➀ PURY-200
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 ✕ number of bent on the piping)m
➁ PURY-250
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m

R2(R22)

1- 251
2-4. Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.

Correction factor table


Outdoor inlet air temp
(˚CWB) 6 4 2 0 -2 -4 -6 -8 -10

Correction factor 1.0 0.95 0.84 0.83 0.87 0.9 0.95 0.95 0.95

2-5. Operation limit

• Cooling
30
Indoor temperature (˚CWB)

25

20

15

10
-5 0 5 10 15 20 25 30 35 40 45

Outdoor temperature (˚CDB)

• Heating
30
Indoor temperature (˚CDB)

25

20

15

10
-15 -10 -5 0 5 10 15 20

Outdoor temperature (˚CWB)

❇ Outdoor temperature : -5˚CDB/-6˚CWB ~ 21˚CDB/15.5˚CWB in cooling/heating mixed mode.


R2(R22)

1- 252
3. Sound Levels
PURY-200

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


Measurement condition 70

1m
60
NC60

50 NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
56 dB (A)

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

PURY-250
Measurement condition
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

70
1m

60
NC60

50
NC50
1m

40
NC40

Sound pressure level in anechoic room 30


NC30
57 dB (A)

20
Approximate minimum NC20
R2(R22)

audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz)

1- 253
R2(R22)

<Accessory>
• Refrigerant (gas) conn. pipe ···· 1pc.

(15)
(The connecting pipe is fixed with the unit)
12 5 Y • Packing for conn. pipe ········1pc.
ø40 Knockout hole
<Bottom side hole for (Attached near the ball valve)
the power supply> • Wiring mounting board
Note1 Y • Conduit mounting plate
Knockout hole ø27 Knockout hole (Painted the same color as the unit body)

840
910
Bottom piping hole <Bottom side hole for ø40··························1pc.
<Bottom wiring hole> the control wiring>

50
ø33··························1pc.

880(bolt hole)
2✕2-14✕20 ø27··························1pc.
Oval hole • Tapping screw 4 ✕ 10················ 6pcs.

262
PURY-200,250YEMC-A

237
Note1.Please leave a space under the outdoor unit

121

73 80
for the piping When , you connect the piping
25 160

15
Conn. pipe 778 75 215 560(bolt hole) (215) from the bottom.
200:ø25.4<brazed> 990 (Please be careful not to close the hole
Crosss section Y-Y 250:ø28.58<brazed> Cross section X-X of the bottom plate by the basement)
Plane view
4. External Dimensions

Air outlet

1- 254
Air
inlet
1755

Air
Knockout hole inlet
1490

Refrig. service
valve (high pressure) Service panel
60 75 ø19.05<flare>
ø40 Knockout hole X X
<Left side hole for
the power supply>
14

100
194
149
99

110
78

48
ø27 Knockout hole Knockout hole
<Left side hole for Refrig. service 79 83 Front piping hole Knockout hole
80 40 valve(low pressure)
the control wiring> <Front wiring hole> <Front side hole for
Knockout hole <flange> 813 the power supply>
Left piping hole 31 165 590 55
Rear view Left side view Front view Right side view
Unit : mm
5. Electrical Wiring Diagram
PURY-200, 250YEMC-A

Inverter MC1 Motor


(compressor)
U V W
controller box
Red White Black
ACCT
-W
ACCT
Terminal Noise Terminal Diode
-U
block NF filter block
L1 L2 L3 N stack R1 R5 IPM
TB1A TB1B DS
L1 L1 Red Red L1 Red ZNR4
L1 L1 ~+
+
U V W
Power source C2 R2
3N- L2 L2 White L2 L2 White L2 White
~
C1 P
380/400/415V 52C +
R3
50/60Hz DCL C3
L3 L3 Black L3 L3 Black L3 Black Gate amp board
~-
(G/A board)
N N Blue N N Blue N Blue N
Green/
PE Yellow

box body
PE box body CNE CNDC1 CNDR1 CN15V1
TB3 F3 (2P) (4P) (9P) (14P)
250VAC
Connect to M1 1A F 1 2 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 101112 1314
indoor and
remote M2
controller CNTR1 FB2
box
box body body
M1

Orange

Orange

Purple
Brown

Brown

Yellow

White
Black

Black
T01

Gray
Red

Red
Green

White
M2

Blue
FB1
S
CN20 1 1 CNAC2
12 3 12 1 2 3
(3P) 1 2 3 2 2 5 4 3 2 1 (5P) 1 2 3 4 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 101112 1314
TB7 CNS2 CNS1 CNTR CNRS3 34 3
4 CNRS2 CNVDC CNDR2 CN15V2
(3P) (2P) F1 (3P) (7P) 5 5 (7P) (4P) (9P) (14P)
250VAC 6 6
2A F 7 7
CNVCC4 F01
CNVCC41 1 (2P) 250VAC
CH1 (2P) 2 2 2A F
3
Crank case heater 2 CN32 1 1
(compressor) 1 (3P) X01 CNVCC3 23 2
3 CNVCC2
Power circuit board 1
(6P) 4
5
4 (6P)
5
(INV board) CNACCT 2
3 6 6 (4P) 3
SV1 4
2 CN33 X02 X10
1 1
1 (3P)
2 2 X01
3
6 52C 3
5 CNX10 CN52C CNTH CNR CNL2 CN30V
(3P) X02 (2P) (3P) (2P) (2P)
SV2 21S4 4 CN34 X04 (3P)
3 (6P) 1 2 3 12 1 2 3 12 12
CNFAN
2 X05 (3P)
1 12V 1
2
3
4 4:Compressor ON/OFF
5
5:Trouble MF1
CN51
(5P)
THHS R7 L2 R6
6 box body
5
SV3 4 CN36 X06
SV4 3 (6P)
2
1
X07 CN3D 32 DEMAND
Control circuit board (3P) 1 NIGHT MODE

6 (MAIN board)
5
SV5 4 CN37 X08
SV6
3 (6P)
2 X09
1
L1 L2 L3

CNPOW
(5P)
1 23 4 5
X10 F03 250VAC 6.3A F
CN38
63H (3P) F02 250VAC 6.3A F
1
High pressure 2 F01 250VAC 6.3A F
switch 3 detection
circuit

FB3
6 6
5 5 1
Refer to the service handbook CNFC1 4 4 CNFC2 CNFAN 2
1
U
(6P) 3 2
3 (6P) (5P) 3 V
about the switch operations. 2 2 4
3
WMF
4
1 1 5 N
CNO 4
FB4 Fan motor
Fan control board (Heat exchanger)
CN09 CN06 CN03 CN02 CN01 CNH CNL CNLV1 N
(2P) (2P) (3P) (8P) (2P) (3P) (3P) (5P) (Fancon board)
12 12 123 12345678 12 123 123 12345
White

White
Black

Black
Red

Red

SLEV
3 2 1 3 2 1
TH10 TH9 TH6 TH5 TH7 TH2 TH1
✻1 ✻1 63HS 63LS

Appliance Name
PURY-P200 / 250 All exists
PURY-200 / 250 ˝ ✻1˝ are not existed

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name Symbol Name
DC reactor SV1,SV2 Solenoid valve (Discharge--suction bypass) TH1 Thermistor Discharge pipe temp. detect THHS Thermistor Radiator panel temp. detect
DCL (Power factor improvement) Solenoid valve TH2 ✻1 Saturation evapo. temp. detect X1,2,4~10 Aux. relay
SV3~SV6
ACCT-U,W Current Sensor (Heat exchanger capacity control) TH5 Pipe temp. detect FB1~4 Ferrite core
R2(R22)

ZNR4 Varistor SLEV Electronic expansion valve(Oil return) TH6 OA temp. detect
Earth terminal
Magnetic contactor 63HS High pressure sensor Liquid outlet temp. detect
52C TH7
(Inverter main circuit) 63LS Low pressure sensor at Sub--cool coil
MF1 Fan motor (Radiator panel) L2 Choke coil (Transmission) TH9 ✻1 High pressure liquid. temp.
21S4 4--way valve IPM Intelligent power module TH10 ✻1 Compressor shell temp.

1- 255
6. Refrigerant Circuit Diagram And Thermal Sensor
PURY-200, 250

: Solenoid valve
: Orifice
: Capillary
: Check valve
Solenoid Valves : Thermal sensor
Block : Strainer
Distributor
CJ1 SP : Service port
ACC : Accumulator
63HS SV4 SV6
SV3
CJ2 SV5

O/S CP1 HEXb

ST6 TH7
CV7
SV1 SV2 HEXf3
CV1 TH1
TH6

63LS
ACC
63H
HEXf2

Comp SA
MA HEXf1

TH10

SLEV
CV2 CV3
BV1
ST1
CV8 CV9 CV10 CV4 CV5

CV6 TH5

BV2

Check Valves Block

SVC

SVA
SVB

Gas/liquid separator

TH23

TH12

TH21
Indoor
TH11 units

TH22

63HS1
LEV
LEV1

63HS3
R2(R22)

TH15

LEV3

TH16
BC controller
CMB-P104V-F

1- 256
2

CONTENTS

Introduction ························································································ 2-2


Ceiling concealed PEFY-P-VML-A1 ·················· 2-5
PEFY-P-VMH-A
PEFY-P-VMM-A ···················· 2-35
PEFY-P-VMH-A-F ················ 2-63

Ceiling mounted built-in PDFY-P-VM-A ······················ 2-77

Floor standing Exposed PFFY-P-VLEM-A ·················· 2-101


Concealed PFFY-P-VLRM-A

Cassette ceiling 1-way flow PMFY-P-VBM-A ··················· 2-115


2-way flow PLFY-P-VLMD-A ·················· 2-127
PLFY-P-VLMD-B
4-way flow PLFY-P-VKM-A/VAM-A ········ 2-151

Wall mounted PKFY-P-VAM-A/VGM-A ········ 2-169


PKFY-P-VFM-A ··················· 2-185

Ceiling suspended PCFY-P-VGM-A ··················· 2-195

OA Processing unit Non-humidifier GUF-RD2 ···························· 2-205


Include humidifier GUF-RDH2

LOSSNAY LGH-RX3-E ··························· 2-213

BC controller (with PURY, PQRY) CMB-P-V-F ··························· 2-221


CMB-P-V-FA
CMB-P-V-FB

2- 1
Introduction
Introduction

Type Model Name 20 25 32 40 50 63 71 80 100 125 140 200 250

PEFY-P-VML-A1 ● ● ●

PEFY-P-VMH-A ● ● ● ● ● ● ● ● ● ●
Ceiling concealed
PEFY-P-VMM-A ● ● ● ● ● ● ● ● ● ● ●

PEFY-P-VMH-A-F ● ●
Ceiling mounted
built-in PDFY-P-VM-A ● ● ● ● ● ● ● ● ● ●
Floor standing
(Exposed) PFFY-P-VLEM-A ● ● ● ● ● ●
Floor standing
PFFY-P-VLRM-A ● ● ● ● ● ●
(Concealed)
Cassette ceiling
(1-way flow) PMFY-P-VBM-A ● ● ● ●

PLFY-P-VLMD-A ● ● ●
Cassette ceiling
(2-way flow)
PLFY-P-VLMD-B ● ● ● ● ● ●

Cassette ceiling
PLFY-P-VKM-A ● ● ● ●
(4-way flow)
PLFY-P-VAM-A ● ● ●

PKFY-P-VAM-A ● ●

Wall mounted PKFY-P-VGM-A ● ● ●

PKFY-P-VFM-A ● ●

Ceiling suspended PCFY-P-VGM-A ● ● ● ●

OA Processing unit ● ●
(Non humidifier) GUF-RD2
(50) (100)
OA Processing unit ● ●
GUF-RDH2
(Include humidifier) (50) (100)

Model Name 25 35 50 80 100 150 200 Model Name 104 105 106 108 1010 1013 1016
LGH-RX3-E ● ● ● ● ● ● ● CMB-P-V-F ● ● ● ● ● ● ●
CMB-P-V-FA ● ● ● ●

CMB-P-V-FB ●

2- 2
Introduction
Meaning of model name

P E F Y - P 20 VML - A
Packaged Sub name
Air conditioner
Model size
Series ·20 : 0.8HP ·100 : 4.0HP
·L : Ceiling cassette ·25 : 1.0HP ·125 : 5.0HP
·E : Ceiling concealed ·32 : 1.25HP ·140 : 6.0HP
·C : Ceiling suspended ·40 : 1.6HP ·200 : 8.0HP
·K : Wall mounted ·50 : 2.0HP ·250 : 10HP
·D : Ceiling mounted bulit-in ·63 : 2.5HP
·F : Floor standing ·71 : 2.8HP
·U : ·80 : 3.2HP

Inverter outdoor units Refrigerant


It is connected with inverter ·P : R407C/R22 commonness
outdoor units ·Nothing : R22

VRF
It can be connected with all
outdoor unit type.

2- 3
Introduction

2- 4
Ceiling concealed PEFY-P-VML-A1

VML-A1/VMH-A
PEFY-P-VMH-A

PEFY-P-
CONTENTS

1. Specifications ································································· 2-6

2. Capacity Tables ······························································2-8


2-1 Cooling Capacity(PUMY) ················································2-8
2-2 Heating Capacity(PUMY) ················································2-10
2-3 Cooling Capacity(Y/R2-8·10·13HP) ····························· 2-11
2-4 Heating Capacity(Y/R2-8·10·13HP) ····························· 2-13
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ····················· 2-14
2-6 Heating Capacity(Big Y, Super Y, Big R2) ····················· 2-16
2-7 Cooling Capacity(WY, WR2) ········································· 2-17
2-8 Heating Capacity(WY, WR2) ········································· 2-18

3. Sound Levels ·······························································2-19


3-1 Noise levels(VML-A1) ···················································· 2-19
3-2 N/C curves(VML-A1) ····················································2-19
3-3 Fan characteristics curves(VML-A1) ······························ 2-19
3-4 Noise levels(VMH-A) ······················································2-20
3-5 N/C curves(VMH-A) ······················································2-20
3-6 Fan characteristics curves(VMH-A) ································2-25

4. External Dimensions ····················································2-28

5. Electrical Wiring Diagrams ···········································2-31

6. Options ··········································································· 2-34

2- 5
1. Specifications
PEFY-P20VML-A1 PEFY-P25VML-A1 PEFY-P32VML-A1
Power source ~ 220-240V 50Hz / 60Hz
❇1 kW 2.2 2.8 3.6
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150
Heating capacity ❇1 kW 2.5 3.2 4.0
Power consumption Cooling kW 0.05/0.06 0.07/0.09
VML-A1/VMH-A

(50/60Hz) Heating kW 0.05/0.06 0.07/0.09


Cooling A 0.24/0.28 0.32/0.42
Current
PEFY-P-

Heating A 0.24/0.28 0.32/0.42


External finish Galvanizing
Height mm 225
Dimension Width mm 720
Depth mm 550
Net weight kg 18
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1
Airflow rate
m3/min 4.8-5.8-7.9 4.8-5.8-9.5
Fan (Lo-Mid-Hi)
External static
Pa 5
pressure
Type Single phase induction motor
Motor
Output kW 0.023 0.032
Air filter PP Honeycomb fabric (washable)
Gas
mm ø 12.7
Refrigerant (Brazing)
pipe dimension Liquid
mm ø 6.35
(Brazing)
Drain pipe dimension R1 (External thread)
Noise level (Lo-Mid-Hi) ❇ 5 dB(A) 29-33-36 30-35-40

PEFY-P40VMH-A PEFY-P50VMH-A PEFY-P63VMH-A PEFY-P71VMH-A


Power source ~ 220-240V 50Hz /60Hz
❇1 kW 4.5 5.6 7.1 8.0
Cooling capacity
❇2 kcal/h 4,000 5,000 6,300 7,100
Heating capacity ❇1 kW 5.0 6.3 8.0 9.0
Power consumption Cooling kW 0.19/0.23 0.24/0.30 0.26/0.33
(50/60Hz) Heating kW 0.19/0.23 0.24/0.30 0.26/0.33
Cooling A 0.88/1.06 1.12/1.38 1.20/1.51
Current
Heating A 0.88/1.06 1.12/1.38 1.20/1.51
External finish Galvanizing
Height mm 380
Dimension Width mm 750 1000
Depth mm 900
Net weight kg 44 45 50
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1
Airflow rate
m3/min 10.0-14.0 13.5-19.0 15.5-22.0
Fan (Lo-Hi)
External static 220V Pa 50/100/200
pressure ❇3 230, 240V Pa 100/150/200
Type Single phase induction motor
Motor
Output ❇4 kW 0.08 0.12 0.14
Air filter (option) Synthethic fiber unwoven cloth filter(long life)
Gas mm ø 12.7 ø 15.88
Refrigerant (Flare)
pipe dimension Liquid
mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension 32 (1-1/4 inch)
Noise level (Lo-Hi) 220V dB(A) 27-34 32-38 32-39
❇ 5 230, 240V dB(A) 31-37 36-41 35-41
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
❇4 The value are that at 240V.
❇5 It is measured in anechoic room.

2- 6
PEFY-P80VMH-A PEFY-P100VMH-A PEFY-P125VMH-A PEFY-P140VMH-A
Power source ~ 220-240V 50Hz /60Hz
❇1 kW 9.0 11.2 14.0 16.0
Cooling capacity
❇2 kcal/h 8,000 10,000 12,500 14,000
Heating capacity ❇1 kW 10.0 12.5 16.0 18.0
Power consumption Cooling kW 0.32/0.40 0.48/0.58 0.48/0.59

VML-A1/VMH-A
(50/60Hz) Heating kW 0.32/0.40 0.48/0.58 0.48/0.59
Cooling A 1.47/1.83 2.34/2.66 2.35/2.70

PEFY-P-
Current
Heating A 1.47/1.83 2.34/2.66 2.35/2.70
External finish Galvanizing
Height mm 380
Dimension Width mm 1000 1200
Depth mm 900
Net weight kg 50 70
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1 Sirocco fan✕ 2
Airflow rate
m3/min 18.0-25.0 26.5-38.0 28.0-40.0
Fan (Lo-Hi)
External static 220V Pa 50/100/200
pressure ❇3 230, 240V Pa 100/150/200
Type Single phase induction motor
Motor
Output ❇4 kW 0.18 0.26
Air filter (option) Synthethic fiber unwoven cloth filter(long life)
Gas mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension 32 (1-1/4 inch)
dB(A) 35-41 34-42
Noise level (Lo-Hi) ❇ 7 220V
230, 240V dB(A) 38-43 38-44

PEFY-P200VMH-A PEFY-P250VMH-A
Power source 3N ~ 380-415V 50Hz / 60Hz
❇1 kW 22.4 28.0
Cooling capacity
❇2 kcal/h 20,000 25,000
Heating capacity ❇1 kW 25.0 31.5
Power consumption Cooling kW 0.99/1.14 1.23/1.41
(50/60Hz) Heating kW 0.99/1.14 1.23/1.41
Cooling A 1.62/1.86 2.0/2.3
Current
Heating A 1.62/1.86 2.0/2.3
External finish Galvanizing
Height mm 470
Dimension Width mm 1250
Depth mm 1120
Net weight kg 100
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 2
3
Airflow rate m /min 58.0 72.0
Fan
External static 380V Pa 110/220
pressure ❇ 5 400, 415V Pa 130/260
Type 3-phase induction motor
Motor
Output ❇6 kW 0.76 1.08
Air filter (option) Synthethic fiber unwoven cloth filter(long life)
Gas
mm ø 25.4 ø 28.58
Refrigerant (Brazing)
pipe dimension Liquid mm ø 12.7
(Brazing)
Drain pipe dimension 32 (1-1/4 inch)
380V dB(A) 42(110Pa)/45(220Pa) 50(110Pa)/52(220Pa)
Noise level ❇7
400, 415V dB(A) 44(130Pa)/47(260Pa) 52(130Pa)/54(260Pa)
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment.
❇ 4 The value are that at 240V.
❇ 5 The external static pressure is set to 110Pa (at 380V) /130Pa (at 400, 415V) at factory shipment.
❇ 6 The value are that at 415V.
❇ 7 It is measured in anechoic room.

2- 7
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Outdoor
air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
VML-A1/VMH-A

20.0 2.2 1.8 2.3 1.9 2.4 1.9 2.6 2.0


PEFY-P-

22.5 2.1 1.8 2.3 1.9 2.4 1.9 2.6 2.0


25.0 2.1 1.8 2.3 1.9 2.4 1.9 2.5 2.0
27.5 2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0
20 30.0 2.1 1.8 2.2 1.9 2.3 1.9 2.5 1.9
(2.2) 32.5 2.0 1.8 2.2 1.9 2.3 1.9 2.5 1.9
35.0 2.0 1.8 2.1 1.9 2.3 1.8 2.4 1.9
37.5 2.0 1.8 2.1 1.9 2.2 1.8 2.4 1.9
40.0 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9
46.0 1.9 1.7 2.0 1.8 2.1 1.8 2.3 1.9
20.0 2.8 2.2 2.9 2.3 3.1 2.3 3.3 2.3
22.5 2.7 2.2 2.9 2.3 3.1 2.2 3.2 2.3
25.0 2.7 2.1 2.9 2.3 3.1 2.2 3.2 2.3
27.5 2.7 2.1 2.8 2.2 3.0 2.2 3.2 2.3
25 30.0 2.6 2.1 2.8 2.2 3.0 2.2 3.2 2.3
(2.8) 32.5 2.6 2.1 2.8 2.2 2.9 2.2 3.1 2.3
35.0 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3
37.5 2.5 2.1 2.7 2.2 2.9 2.2 3.0 2.2
40.0 2.5 2.0 2.7 2.2 2.8 2.1 3.0 2.2
46.0 2.4 2.0 2.6 2.1 2.7 2.1 2.9 2.2
20.0 3.6 2.7 3.7 2.8 4.0 2.8 4.2 2.9
22.5 3.5 2.7 3.7 2.8 4.0 2.8 4.2 2.9
25.0 3.5 2.7 3.7 2.8 3.9 2.8 4.1 2.9
27.5 3.4 2.7 3.6 2.8 3.9 2.8 4.1 2.8
32 30.0 3.4 2.6 3.6 2.8 3.8 2.7 4.1 2.8
(3.6) 32.5 3.3 2.6 3.6 2.7 3.8 2.7 4.0 2.8
35.0 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.8
37.5 3.2 2.6 3.5 2.7 3.7 2.7 3.9 2.8
40.0 3.2 2.5 3.4 2.7 3.6 2.7 3.9 2.7
46.0 3.1 2.5 3.3 2.6 3.5 2.6 3.7 2.7
20.0 4.5 3.3 4.7 3.5 5.0 3.5 5.3 3.6
22.5 4.4 3.3 4.6 3.5 5.0 3.4 5.2 3.5
25.0 4.3 3.3 4.6 3.4 4.9 3.4 5.2 3.5
27.5 4.3 3.3 4.6 3.4 4.9 3.4 5.1 3.5
40 30.0 4.2 3.2 4.5 3.4 4.8 3.4 5.1 3.5
(4.5) 32.5 4.2 3.2 4.4 3.4 4.7 3.3 5.0 3.5
35.0 4.1 3.2 4.4 3.3 4.7 3.3 5.0 3.4
37.5 4.1 3.1 4.3 3.3 4.6 3.3 4.9 3.4
40.0 4.0 3.1 4.3 3.3 4.5 3.3 4.8 3.4
46.0 3.8 3.0 4.1 3.2 4.3 3.2 4.6 3.3
20.0 5.5 3.9 5.8 4.1 6.2 4.1 6.6 4.2
22.5 5.5 3.9 5.8 4.1 6.2 4.0 6.5 4.1
25.0 5.4 3.9 5.7 4.0 6.1 4.0 6.4 4.1
27.5 5.3 3.8 5.7 4.0 6.0 4.0 6.4 4.1
50 30.0 5.3 3.8 5.6 4.0 5.9 3.9 6.3 4.1
(5.6) 32.5 5.2 3.7 5.5 3.9 5.9 3.9 6.2 4.0
35.0 5.1 3.7 5.5 3.9 5.8 3.9 6.2 4.0
37.5 5.0 3.7 5.4 3.9 5.7 3.8 6.1 4.0
40.0 5.0 3.6 5.3 3.8 5.6 3.8 6.0 3.9
46.0 4.8 3.5 5.1 3.7 5.4 3.7 5.8 3.8
20.0 7.0 5.2 7.4 5.4 7.9 5.3 8.3 5.5
22.5 6.9 5.1 7.3 5.3 7.8 5.3 8.2 5.4
25.0 6.9 5.1 7.3 5.3 7.7 5.3 8.2 5.4
27.5 6.8 5.0 7.2 5.3 7.7 5.2 8.1 5.4
63 30.0 6.7 5.0 7.1 5.2 7.5 5.2 8.0 5.3
(7.1) 32.5 6.6 4.9 7.0 5.2 7.5 5.1 7.9 5.3
35.0 6.5 4.9 6.9 5.1 7.3 5.1 7.8 5.3
37.5 6.4 4.8 6.8 5.1 7.2 5.0 7.7 5.2
40.0 6.3 4.8 6.7 5.1 7.2 5.0 7.6 5.2
46.0 6.1 4.7 6.5 4.9 6.9 4.9 7.3 5.1

2- 8
Cooling Capacity (In combination with PUMY)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC

VML-A1/VMH-A
20.0 7.9 5.8 8.3 6.0 8.9 6.0 9.4 6.1

PEFY-P-
22.5 7.8 5.7 8.2 6.0 8.8 5.9 9.3 6.1
25.0 7.7 5.7 8.2 5.9 8.7 5.9 9.2 6.1
27.5 7.6 5.6 8.1 5.9 8.6 5.8 9.1 6.0
71 30.0 7.5 5.6 8.0 5.8 8.5 5.8 9.0 6.0
(8.0) 32.5 7.4 5.5 7.9 5.8 8.4 5.7 8.9 5.9
35.0 7.3 5.4 7.8 5.7 8.3 5.7 8.8 5.9
37.5 7.2 5.4 7.7 5.7 8.2 5.6 8.7 5.8
40.0 7.1 5.4 7.6 5.6 8.1 5.6 8.6 5.8
46.0 6.8 5.2 7.3 5.5 7.7 5.4 8.2 5.6
20.0 8.9 6.5 9.4 6.8 10.0 6.8 10.6 6.9
22.5 8.8 6.5 9.3 6.7 9.9 6.7 10.4 6.9
25.0 8.7 6.4 9.2 6.7 9.8 6.7 10.4 6.8
27.5 8.6 6.4 9.1 6.7 9.7 6.6 10.3 6.8
80 30.0 8.5 6.3 9.0 6.6 9.5 6.5 10.2 6.8
(9.0) 32.5 8.3 6.2 8.9 6.6 9.5 6.5 10.0 6.7
35.0 8.2 6.2 8.8 6.5 9.3 6.4 9.9 6.6
37.5 8.1 6.1 8.6 6.4 9.2 6.4 9.8 6.6
40.0 8.0 6.1 8.6 6.4 9.1 6.3 9.6 6.5
46.0 7.7 5.9 8.2 6.2 8.7 6.1 9.3 6.4
20.0 11.1 8.7 11.6 9.1 12.5 9.1 13.1 9.3
22.5 10.9 8.7 11.5 9.1 12.3 9.0 13.0 9.3
25.0 10.8 8.6 11.5 9.0 12.2 9.0 12.9 9.2
27.5 10.7 8.5 11.3 9.0 12.1 8.9 12.8 9.2
100 30.0 10.5 8.5 11.2 8.9 11.9 8.8 12.6 9.1
(11.2) 32.5 10.4 8.4 11.1 8.8 11.8 8.8 12.5 9.1
35.0 10.2 8.3 10.9 8.8 11.6 8.7 12.3 9.0
37.5 10.1 8.3 10.8 8.7 11.4 8.6 12.2 9.0
40.0 10.0 8.2 10.6 8.6 11.3 8.6 12.0 8.9
46.0 9.6 8.0 10.2 8.5 10.8 8.4 11.5 8.7
20.0 13.9 10.1 14.6 10.5 15.6 10.5 16.4 10.8
22.5 13.7 10.0 14.4 10.4 15.4 10.4 16.2 10.7
25.0 13.5 9.9 14.3 10.4 15.3 10.3 16.1 10.6
27.5 13.4 9.9 14.2 10.3 15.1 10.2 16.0 10.6
125 30.0 13.2 9.8 14.0 10.2 14.9 10.1 15.8 10.5
(14.0) 32.5 13.0 9.6 13.8 10.2 14.7 10.1 15.6 10.4
35.0 12.8 9.6 13.7 10.1 14.5 10.0 15.4 10.3
37.5 12.6 9.5 13.4 10.0 14.3 9.9 15.2 10.2
40.0 12.5 9.4 13.3 9.9 14.1 9.8 15.0 10.1
46.0 12.0 9.2 12.8 9.7 13.5 9.5 14.4 9.9

2- 9
2-2.Heating Capacity (In combination with PUMY)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 5.7 5.6 5.5
VML-A1/VMH-A

-10.0 1.7 1.6 1.6 -10.0 6.0 5.9 5.8


-5.0 1.9 1.9 1.9 -5.0 6.9 6.8 6.7
PEFY-P-

0.0 2.2 2.1 2.1 0.0 7.8 7.7 7.6


20 2.5 2.3 2.3 2.3 2.5 8.3 8.2 8.1
71
6.0 2.5 2.5 2.5 6.0 9.1 9.0 8.9
7.5 2.6 2.6 2.5 7.5 9.4 9.3 8.9
10.0 2.8 2.7 2.5 10.0 9.9 9.9 8.9
12.5 2.9 2.8 2.5 12.5 10.5 9.9 8.9
15.5 3.1 2.8 2.5 15.5 11.1 9.9 8.9
-12.0 2.0 2.0 2.0 -12.0 6.4 6.2 6.1
-10.0 2.1 2.1 2.1 -10.0 6.7 6.6 6.5
-5.0 2.4 2.4 2.4 -5.0 7.6 7.5 7.4
0.0 2.8 2.8 2.7 0.0 8.7 8.6 8.5
25 2.5 3.0 2.9 2.9 2.5 9.2 9.2 9.0
80
6.0 3.2 3.2 3.2 6.0 10.1 10.0 9.9
7.5 3.3 3.3 3.2 7.5 10.4 10.4 9.9
10.0 3.5 3.5 3.2 10.0 11.1 11.0 9.9
12.5 3.7 3.5 3.2 12.5 11.7 11.0 9.9
15.5 3.9 3.5 3.2 15.5 12.3 11.0 9.9
-12.0 2.5 2.5 2.5 -12.0 8.0 7.8 7.7
-10.0 2.7 2.6 2.6 -10.0 8.4 8.2 8.1
-5.0 3.1 3.0 3.0 -5.0 9.6 9.4 9.3
0.0 3.5 3.4 3.4 0.0 10.9 10.7 10.6
32 2.5 3.7 3.7 3.6 2.5 11.5 11.4 11.3
100
6.0 4.0 4.0 3.9 6.0 12.6 12.5 12.3
7.5 4.2 4.1 4.0 7.5 13.0 12.9 12.4
10.0 4.4 4.4 4.0 10.0 13.8 13.7 12.4
12.5 4.7 4.4 4.0 12.5 14.6 13.8 12.4
15.5 4.9 4.4 4.0 15.5 15.4 13.8 12.4
-12.0 3.2 3.1 3.1 -12.0 10.2 10.0 9.8
-10.0 3.4 3.3 3.2 -10.0 10.7 10.6 10.4
-5.0 3.8 3.8 3.7 -5.0 12.2 12.1 11.9
0.0 4.3 4.3 4.2 0.0 13.9 13.8 13.6
40 2.5 4.6 4.6 4.5 2.5 14.8 14.7 14.5
125
6.0 5.0 5.0 4.9 6.0 16.1 16.0 15.8
7.5 5.2 5.2 5.0 7.5 16.7 16.6 15.8
10.0 5.5 5.5 5.0 10.0 17.7 17.6 15.8
12.5 5.9 5.5 5.0 12.5 18.7 17.7 15.8
15.5 6.2 5.5 5.0 15.5 19.7 17.7 15.8
-12.0 4.0 3.9 3.9
-10.0 4.2 4.2 4.1
-5.0 4.8 4.8 4.7
0.0 5.5 5.4 5.3
50 2.5 5.8 5.8 5.7
6.0 6.3 6.3 6.2
7.5 6.6 6.5 6.2
10.0 7.0 6.9 6.2
12.5 7.4 7.0 6.2
15.5 7.7 7.0 6.2
-12.0 5.1 5.0 4.9
-10.0 5.4 5.3 5.2
-5.0 6.1 6.0 5.9
0.0 6.9 6.9 6.8
63 2.5 7.4 7.3 7.2
6.0 8.0 8.0 7.9
7.5 8.3 8.3 7.9
10.0 8.8 8.8 7.9
12.5 9.4 8.8 7.9
15.5 9.8 8.8 7.9

2- 10
2-3.Cooling Capacity (In combination with PU(H)Y,PURY-(P)200·250·315YEM-A, TEM-A)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

VML-A1/VMH-A
20.0 2.2 1.8 2.2 1.9 2.3 1.9 2.3 1.9 2.4 2.0 2.5 1.9 2.6 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.8 2.3 1.9 2.4 1.9 2.4 1.9 2.5 1.9

PEFY-P-
25.0 2.1 1.8 2.2 1.9 2.2 1.8 2.3 1.9 2.3 1.9 2.4 1.9 2.5 1.9
27.5 2.1 1.8 2.1 1.9 2.2 1.8 2.3 1.9 2.3 1.9 2.4 1.9 2.5 1.8
20 30.0 2.1 1.8 2.1 1.9 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
(2.2) 32.5 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.4 1.8
35.0 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.8
37.5 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.8
40.0 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.8 2.4 1.8
43.0 2.0 1.7 2.0 1.8 2.1 1.8 2.1 1.8 2.2 1.9 2.3 1.8 2.3 1.8
20.0 2.7 2.2 2.8 2.2 2.9 2.2 3.0 2.2 3.0 2.3 3.1 2.2 3.2 2.2
22.5 2.7 2.2 2.8 2.2 2.9 2.2 2.9 2.2 3.0 2.3 3.1 2.2 3.2 2.2
25.0 2.7 2.1 2.7 2.2 2.9 2.2 2.9 2.2 3.0 2.3 3.1 2.2 3.2 2.1
27.5 2.7 2.1 2.7 2.2 2.8 2.1 2.9 2.2 2.9 2.2 3.1 2.2 3.2 2.1
25 30.0 2.6 2.1 2.7 2.2 2.8 2.1 2.9 2.2 2.9 2.2 3.0 2.2 3.1 2.1
(2.8) 32.5 2.6 2.1 2.7 2.2 2.8 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.1 2.1
35.0 2.6 2.1 2.6 2.1 2.7 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.1 2.1
37.5 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.1 2.8 2.2 2.9 2.2 3.1 2.1
40.0 2.5 2.1 2.6 2.1 2.7 2.1 2.7 2.1 2.8 2.2 2.9 2.1 3.0 2.1
43.0 2.5 2.0 2.5 2.1 2.7 2.1 2.7 2.1 2.8 2.2 2.9 2.1 3.0 2.1
20.0 3.5 2.7 3.6 2.8 3.7 2.7 3.8 2.7 3.9 2.8 4.0 2.7 4.2 2.7
22.5 3.5 2.7 3.6 2.7 3.7 2.7 3.8 2.7 3.9 2.8 4.0 2.7 4.1 2.7
25.0 3.5 2.7 3.5 2.7 3.7 2.7 3.7 2.7 3.8 2.8 4.0 2.7 4.1 2.6
27.5 3.4 2.6 3.5 2.7 3.6 2.7 3.7 2.7 3.8 2.8 3.9 2.7 4.1 2.6
32 30.0 3.4 2.6 3.5 2.7 3.6 2.6 3.7 2.7 3.7 2.8 3.9 2.7 4.0 2.6
(3.6) 32.5 3.3 2.6 3.4 2.7 3.6 2.6 3.6 2.7 3.7 2.7 3.9 2.7 4.0 2.6
35.0 3.3 2.6 3.4 2.7 3.5 2.6 3.6 2.6 3.7 2.7 3.8 2.7 4.0 2.6
37.5 3.3 2.6 3.3 2.6 3.5 2.6 3.6 2.6 3.6 2.7 3.8 2.7 3.9 2.6
40.0 3.2 2.6 3.3 2.6 3.5 2.6 3.5 2.6 3.6 2.7 3.7 2.6 3.9 2.6
43.0 3.2 2.5 3.3 2.6 3.4 2.6 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.6
20.0 4.4 3.3 4.5 3.4 4.7 3.3 4.8 3.4 4.9 3.5 5.0 3.4 5.2 3.3
22.5 4.4 3.3 4.5 3.4 4.6 3.3 4.7 3.3 4.8 3.4 5.0 3.4 5.2 3.3
25.0 4.3 3.3 4.4 3.4 4.6 3.3 4.7 3.3 4.8 3.4 5.0 3.3 5.1 3.2
27.5 4.3 3.3 4.4 3.3 4.5 3.3 4.6 3.3 4.7 3.4 4.9 3.3 5.1 3.2
40 30.0 4.2 3.2 4.3 3.3 4.5 3.2 4.6 3.3 4.7 3.4 4.9 3.3 5.0 3.2
(4.5) 32.5 4.2 3.2 4.3 3.3 4.5 3.2 4.5 3.3 4.6 3.4 4.8 3.3 5.0 3.2
35.0 4.1 3.2 4.2 3.3 4.4 3.2 4.5 3.2 4.6 3.3 4.8 3.3 5.0 3.2
37.5 4.1 3.2 4.2 3.2 4.4 3.2 4.5 3.2 4.5 3.3 4.7 3.3 4.9 3.2
40.0 4.1 3.1 4.1 3.2 4.3 3.2 4.4 3.2 4.5 3.3 4.7 3.2 4.9 3.2
43.0 4.0 3.1 4.1 3.2 4.3 3.1 4.4 3.2 4.4 3.3 4.6 3.2 4.8 3.1
20.0 5.5 3.9 5.6 4.0 5.8 3.9 5.9 3.9 6.0 4.0 6.3 3.9 6.5 3.8
22.5 5.4 3.9 5.5 3.9 5.8 3.9 5.9 3.9 6.0 4.0 6.2 3.9 6.4 3.8
25.0 5.4 3.8 5.5 3.9 5.7 3.8 5.8 3.8 5.9 4.0 6.2 3.8 6.4 3.7
27.5 5.3 3.8 5.4 3.9 5.7 3.8 5.8 3.8 5.9 3.9 6.1 3.8 6.3 3.7
50 30.0 5.3 3.8 5.4 3.9 5.6 3.8 5.7 3.8 5.8 3.9 6.0 3.8 6.3 3.7
(5.6) 32.5 5.2 3.8 5.3 3.8 5.5 3.7 5.7 3.8 5.8 3.9 6.0 3.8 6.2 3.7
35.0 5.2 3.7 5.3 3.8 5.5 3.7 5.6 3.7 5.7 3.9 5.9 3.8 6.2 3.7
37.5 5.1 3.7 5.2 3.8 5.4 3.7 5.5 3.7 5.7 3.8 5.9 3.7 6.1 3.6
40.0 5.0 3.7 5.2 3.8 5.4 3.7 5.5 3.7 5.6 3.8 5.8 3.7 6.0 3.6
43.0 5.0 3.6 5.1 3.7 5.3 3.6 5.4 3.7 5.5 3.8 5.8 3.7 6.0 3.6
20.0 7.0 5.1 7.1 5.2 7.4 5.1 7.5 5.1 7.7 5.3 8.0 5.2 8.2 5.0
22.5 6.9 5.1 7.0 5.2 7.3 5.1 7.5 5.1 7.6 5.3 7.9 5.1 8.2 5.0
25.0 6.8 5.0 7.0 5.2 7.2 5.0 7.4 5.1 7.5 5.2 7.8 5.1 8.1 5.0
27.5 6.7 5.0 6.9 5.1 7.2 5.0 7.3 5.1 7.5 5.2 7.7 5.1 8.0 4.9
63 30.0 6.7 5.0 6.8 5.1 7.1 5.0 7.2 5.0 7.4 5.2 7.7 5.0 8.0 4.9
(7.1) 32.5 6.6 4.9 6.7 5.1 7.0 4.9 7.2 5.0 7.3 5.2 7.6 5.0 7.9 4.9
35.0 6.5 4.9 6.7 5.0 7.0 4.9 7.1 5.0 7.2 5.1 7.5 5.0 7.8 4.9
37.5 6.5 4.9 6.6 5.0 6.9 4.9 7.0 4.9 7.2 5.1 7.5 5.0 7.7 4.8
40.0 6.4 4.8 6.5 5.0 6.8 4.9 7.0 4.9 7.1 5.1 7.4 4.9 7.7 4.8
43.0 6.3 4.8 6.4 4.9 6.7 4.8 6.9 4.9 7.0 5.0 7.3 4.9 7.6 4.8

2- 11
Cooling Capacity (In combination with PU(H)Y,PURY-(P)200·250·315YEM-A, TEM-A)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
VML-A1/VMH-A

20.0 7.8 5.7 8.0 5.8 8.3 5.7 8.5 5.7 8.6 5.9 9.0 5.8 9.3 5.6
22.5 7.8 5.7 7.9 5.8 8.2 5.7 8.4 5.7 8.6 5.9 8.9 5.7 9.2 5.6
PEFY-P-

25.0 7.7 5.6 7.8 5.8 8.2 5.6 8.3 5.7 8.5 5.8 8.8 5.7 9.1 5.5
27.5 7.6 5.6 7.8 5.7 8.1 5.6 8.2 5.6 8.4 5.8 8.7 5.7 9.0 5.5
71 30.0 7.5 5.6 7.7 5.7 8.0 5.6 8.2 5.6 8.3 5.8 8.6 5.6 9.0 5.5
(8.0) 32.5 7.4 5.5 7.6 5.6 7.9 5.5 8.1 5.6 8.2 5.7 8.6 5.6 8.9 5.4
35.0 7.4 5.5 7.5 5.6 7.8 5.5 8.0 5.5 8.2 5.7 8.5 5.6 8.8 5.4
37.5 7.3 5.4 7.4 5.6 7.8 5.5 7.9 5.5 8.1 5.7 8.4 5.5 8.7 5.4
40.0 7.2 5.4 7.4 5.5 7.7 5.4 7.8 5.5 8.0 5.6 8.3 5.5 8.6 5.4
43.0 7.1 5.4 7.3 5.5 7.6 5.4 7.7 5.4 7.9 5.6 8.2 5.5 8.5 5.3
20.0 8.8 6.5 9.0 6.6 9.4 6.5 9.5 6.5 9.7 6.7 10.1 6.5 10.4 6.3
22.5 8.7 6.4 8.9 6.6 9.3 6.4 9.5 6.5 9.6 6.7 10.0 6.5 10.4 6.3
25.0 8.6 6.4 8.8 6.5 9.2 6.4 9.4 6.4 9.5 6.6 9.9 6.4 10.3 6.3
27.5 8.6 6.3 8.7 6.5 9.1 6.3 9.3 6.4 9.5 6.6 9.8 6.4 10.2 6.2
80 30.0 8.5 6.3 8.6 6.4 9.0 6.3 9.2 6.3 9.4 6.5 9.7 6.4 10.1 6.2
(9.0) 32.5 8.4 6.2 8.6 6.4 8.9 6.2 9.1 6.3 9.3 6.5 9.6 6.3 10.0 6.2
35.0 8.3 6.2 8.5 6.3 8.8 6.2 9.0 6.3 9.2 6.5 9.5 6.3 9.9 6.1
37.5 8.2 6.2 8.4 6.3 8.7 6.2 8.9 6.2 9.1 6.4 9.5 6.3 9.8 6.1
40.0 8.1 6.1 8.3 6.3 8.6 6.1 8.8 6.2 9.0 6.4 9.4 6.2 9.7 6.1
43.0 8.0 6.1 8.2 6.2 8.5 6.1 8.7 6.1 8.9 6.3 9.3 6.2 9.6 6.0
20.0 11.0 8.7 11.2 8.9 11.6 8.7 11.9 8.8 12.1 9.1 12.5 8.9 13.0 8.7
22.5 10.9 8.6 11.1 8.9 11.5 8.7 11.8 8.8 12.0 9.1 12.4 8.9 12.9 8.6
25.0 10.8 8.6 11.0 8.8 11.4 8.6 11.6 8.7 11.9 9.0 12.3 8.8 12.8 8.6
27.5 10.6 8.5 10.9 8.8 11.3 8.6 11.5 8.7 11.8 9.0 12.2 8.8 12.7 8.6
100 30.0 10.5 8.5 10.8 8.7 11.2 8.5 11.4 8.6 11.6 9.0 12.1 8.7 12.5 8.5
(11.2) 32.5 10.4 8.4 10.6 8.6 11.1 8.5 11.3 8.6 11.5 8.9 12.0 8.7 12.4 8.5
35.0 10.3 8.4 10.5 8.6 11.0 8.4 11.2 8.6 11.4 8.9 11.9 8.7 12.3 8.5
37.5 10.2 8.3 10.4 8.5 10.9 8.4 11.1 8.5 11.3 8.8 11.8 8.6 12.2 8.4
40.0 10.1 8.3 10.3 8.5 10.8 8.3 11.0 8.5 11.2 8.8 11.6 8.6 12.1 8.4
43.0 9.9 8.2 10.2 8.4 10.6 8.3 10.8 8.4 11.1 8.7 11.5 8.5 12.0 8.3
20.0 13.7 10.0 14.0 10.2 14.6 10.0 14.8 10.1 15.1 10.4 15.7 10.1 16.2 9.8
22.5 13.6 10.0 13.9 10.2 14.4 9.9 14.7 10.0 15.0 10.3 15.5 10.0 16.1 9.8
25.0 13.4 9.9 13.7 10.1 14.3 9.9 14.6 10.0 14.8 10.3 15.4 10.0 16.0 9.7
27.5 13.3 9.8 13.6 10.0 14.1 9.8 14.4 9.9 14.7 10.2 15.3 9.9 15.8 9.7
125 30.0 13.2 9.8 13.4 10.0 14.0 9.8 14.3 9.8 14.6 10.1 15.1 9.9 15.7 9.6
(14.0) 32.5 13.0 9.7 13.3 9.9 13.9 9.7 14.1 9.8 14.4 10.1 15.0 9.8 15.5 9.6
35.0 12.9 9.6 13.2 9.8 13.7 9.6 14.0 9.7 14.3 10.0 14.8 9.8 15.4 9.5
37.5 12.7 9.5 13.0 9.8 13.6 9.6 13.9 9.7 14.1 10.0 14.7 9.7 15.3 9.5
40.0 12.6 9.5 12.9 9.7 13.4 9.5 13.7 9.6 14.0 9.9 14.6 9.7 15.1 9.4
43.0 12.4 9.4 12.7 9.6 13.3 9.4 13.6 9.5 13.8 9.8 14.4 9.6 15.0 9.4
20.0 15.7 11.5 16.0 11.7 16.6 11.4 17.0 11.5 17.3 11.9 17.9 11.5 18.6 11.2
22.5 15.5 11.4 15.8 11.6 16.5 11.4 16.8 11.4 17.1 11.8 17.8 11.5 18.4 11.2
25.0 15.4 11.3 15.7 11.6 16.3 11.3 16.6 11.4 17.0 11.7 17.6 11.4 18.2 11.1
27.5 15.2 11.2 15.5 11.5 16.2 11.2 16.5 11.3 16.8 11.7 17.4 11.4 18.1 11.0
140 30.0 15.0 11.1 15.4 11.4 16.0 11.2 16.3 11.2 16.6 11.6 17.3 11.3 17.9 11.0
(16.0) 32.5 14.9 11.1 15.2 11.3 15.8 11.1 16.2 11.2 16.5 11.5 17.1 11.2 17.8 10.9
35.0 14.7 11.0 15.0 11.2 15.7 11.0 16.0 11.1 16.3 11.5 17.0 11.2 17.6 10.9
37.5 14.6 10.9 14.9 11.2 15.5 10.9 15.8 11.0 16.2 11.4 16.8 11.1 17.4 10.8
40.0 14.4 10.8 14.7 11.1 15.4 10.9 15.7 11.0 16.0 11.3 16.6 11.1 17.3 10.8
43.0 14.2 10.7 14.5 11.0 15.2 10.8 15.5 10.9 15.8 11.3 16.4 11.0 17.1 10.7
20.0 22.0 16.4 22.4 16.8 23.3 16.4 23.7 16.5 24.2 17.1 25.1 16.6 26.0 16.2
22.5 21.7 16.3 22.2 16.7 23.1 16.3 23.5 16.5 24.0 17.0 24.9 16.5 25.8 16.1
25.0 21.5 16.2 22.0 16.6 22.8 16.2 23.3 16.4 23.7 16.9 24.6 16.5 25.5 16.0
27.5 21.3 16.1 21.7 16.5 22.6 16.1 23.1 16.3 23.5 16.8 24.4 16.4 25.3 15.9
200 30.0 21.1 16.0 21.5 16.4 22.4 16.0 22.8 16.2 23.3 16.7 24.2 16.3 25.1 15.9
(22.4) 32.5 20.8 15.9 21.3 16.3 22.2 15.9 22.6 16.1 23.1 16.6 24.0 16.2 24.9 15.8
35.0 20.6 15.8 21.1 16.1 22.0 15.8 22.4 16.0 22.8 16.5 23.7 16.1 24.6 15.7
37.5 20.4 15.6 20.8 16.0 21.7 15.7 22.2 15.9 22.6 16.4 23.5 16.0 24.4 15.6
40.0 20.2 15.5 20.6 15.9 21.5 15.6 22.0 15.8 22.4 16.3 23.3 16.0 24.2 15.5
43.0 19.9 15.4 20.3 15.8 21.2 15.5 21.7 15.7 22.1 16.2 23.0 15.9 23.9 15.5
20.0 27.4 20.4 28.0 20.9 29.1 20.4 29.7 20.6 30.2 21.2 31.4 20.7 32.5 20.1
22.5 27.2 20.3 27.7 20.7 28.8 20.3 29.4 20.4 30.0 21.1 31.1 20.5 32.2 20.0
25.0 26.9 20.1 27.4 20.6 28.6 20.1 29.1 20.3 29.7 21.0 30.8 20.4 31.9 19.9
27.5 26.6 20.0 27.2 20.5 28.3 20.0 28.8 20.2 29.4 20.9 30.5 20.3 31.6 19.8
30.0 26.3 19.9 26.9 20.3 28.0 19.9 28.6 20.1 29.1 20.7 30.2 20.2 31.4 19.7
250 32.5 26.0 19.7 26.6 20.2 27.7 19.8 28.3 20.0 28.8 20.6 30.0 20.1 31.1 19.6
(28.0) 35.0 25.8 19.6 26.3 20.1 27.4 19.6 28.0 19.9 28.6 20.5 29.7 20.0 30.8 19.5
37.5 25.5 19.4 26.0 19.9 27.2 19.5 27.7 19.7 28.3 20.4 29.4 19.9 30.5 19.4
40.0 25.2 19.3 25.8 19.8 26.9 19.4 27.4 19.6 28.0 20.3 29.1 19.8 30.2 19.3
43.0 24.9 19.2 25.4 19.6 26.5 19.3 27.1 19.5 27.7 20.1 28.8 19.7 29.9 19.2

2- 12
2-4.Heating Capacity (In combination with PU(H)Y,PURY-(P)200·250·315YEM-A, TEM-A)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 6.0 5.9 5.9 5.9

VML-A1/VMH-A
-10.0 1.9 1.9 1.9 1.7 -10.0 6.9 6.8 6.7 6.2
-5.0 2.1 2.1 2.0 1.7 -5.0 7.7 7.6 7.0 6.2

PEFY-P-
0.0 2.4 2.4 2.0 1.7 0.0 8.6 8.5 7.0 6.2
2.5 2.5 2.5 2.0 1.7 2.5 9.0 8.9 7.0 6.2
20 71
6.0 2.5 2.5 2.0 1.7 6.0 9.1 9.0 7.0 6.2
7.5 2.6 2.5 2.0 1.7 7.5 9.5 9.0 7.0 6.2
10.0 2.8 2.5 2.0 1.7 10.0 10.1 9.0 7.0 6.2
12.5 3.0 2.5 2.0 1.7 12.5 10.8 9.0 7.0 6.2
15.5 3.0 2.5 2.0 1.7 15.5 10.9 9.0 7.0 6.2
-15.0 2.1 2.1 2.1 2.1 -15.0 6.7 6.6 6.5 6.5
-10.0 2.4 2.4 2.4 2.2 -10.0 7.6 7.5 7.4 6.9
-5.0 2.7 2.7 2.5 2.2 -5.0 8.6 8.5 7.8 6.9
0.0 3.1 3.0 2.5 2.2 0.0 9.5 9.4 7.8 6.9
2.5 3.2 3.2 2.5 2.2 2.5 10.0 9.9 7.8 6.9
25 80
6.0 3.2 3.2 2.5 2.2 6.0 10.1 10.0 7.8 6.9
7.5 3.4 3.2 2.5 2.2 7.5 10.5 10.0 7.8 6.9
10.0 3.6 3.2 2.5 2.2 10.0 11.2 10.0 7.8 6.9
12.5 3.8 3.2 2.5 2.2 12.5 12.0 10.0 7.8 6.9
15.5 3.9 3.2 2.5 2.2 15.5 12.1 10.0 7.8 6.9
-15.0 2.7 2.6 2.6 2.6 -15.0 8.4 8.2 8.2 8.1
-10.0 3.1 3.0 3.0 2.8 -10.0 9.6 9.4 9.3 8.6
-5.0 3.4 3.4 3.1 2.8 -5.0 10.7 10.6 9.8 8.6
0.0 3.8 3.8 3.1 2.8 0.0 11.9 11.8 9.8 8.6
2.5 4.0 4.0 3.1 2.8 2.5 12.5 12.4 9.8 8.6
32 100
6.0 4.0 4.0 3.1 2.8 6.0 12.6 12.5 9.8 8.6
7.5 4.2 4.0 3.1 2.8 7.5 13.2 12.5 9.8 8.6
10.0 4.5 4.0 3.1 2.8 10.0 14.1 12.5 9.8 8.6
12.5 4.8 4.0 3.1 2.8 12.5 15.0 12.5 9.8 8.6
15.5 4.8 4.0 3.1 2.8 15.5 15.1 12.5 9.8 8.6
-15.0 3.3 3.3 3.3 3.3 -15.0 10.7 10.6 10.5 10.4
-10.0 3.8 3.8 3.7 3.5 -10.0 12.2 12.1 11.9 11.0
-5.0 4.3 4.2 3.9 3.5 -5.0 13.7 13.6 12.5 11.0
0.0 4.8 4.7 3.9 3.5 0.0 15.3 15.1 12.5 11.0
2.5 5.0 5.0 3.9 3.5 2.5 16.0 15.8 12.5 11.0
40 125
6.0 5.1 5.0 3.9 3.5 6.0 16.2 16.0 12.5 11.0
7.5 5.3 5.0 3.9 3.5 7.5 16.8 16.0 12.5 11.0
10.0 5.6 5.0 3.9 3.5 10.0 18.0 16.0 12.5 11.0
12.5 6.0 5.0 3.9 3.5 12.5 19.1 16.0 12.5 11.0
15.5 6.1 5.0 3.9 3.5 15.5 19.4 16.0 12.5 11.0
-15.0 4.2 4.2 4.1 4.1 -15.0 12.1 11.9 11.8 11.7
-10.0 4.8 4.8 4.7 4.3 -10.0 13.8 13.6 13.4 12.4
-5.0 5.4 5.3 4.9 4.3 -5.0 15.5 15.3 14.0 12.4
0.0 6.0 5.9 4.9 4.3 0.0 17.2 17.0 14.0 12.4
2.5 6.3 6.2 4.9 4.3 2.5 18.0 17.8 14.0 12.4
50 140
6.0 6.4 6.3 4.9 4.3 6.0 18.2 18.0 14.0 12.4
7.5 6.6 6.3 4.9 4.3 7.5 19.0 18.0 14.0 12.4
10.0 7.1 6.3 4.9 4.3 10.0 20.2 18.0 14.0 12.4
12.5 7.5 6.3 4.9 4.3 12.5 21.5 18.0 14.0 12.4
15.5 7.6 6.3 4.9 4.3 15.5 21.8 18.0 14.0 12.4
-15.0 5.4 5.3 5.2 5.2 -15.0 16.7 16.5 16.4 16.3
-10.0 6.1 6.0 6.0 5.5 -10.0 19.1 18.9 18.6 17.3
-5.0 6.9 6.8 6.2 5.5 -5.0 21.5 21.2 19.5 17.3
0.0 7.6 7.5 6.2 5.5 0.0 23.8 23.6 19.5 17.3
2.5 8.0 7.9 6.2 5.5 2.5 25.0 24.8 19.5 17.3
63 200
6.0 8.1 8.0 6.2 5.5 6.0 25.3 25.0 19.5 17.3
7.5 8.4 8.0 6.2 5.5 7.5 26.3 25.0 19.5 17.3
10.0 9.0 8.0 6.2 5.5 10.0 28.1 25.0 19.5 17.3
12.5 9.6 8.0 6.2 5.5 12.5 29.9 25.0 19.5 17.3
15.5 9.7 8.0 6.2 5.5 15.5 30.3 25.0 19.5 17.3
-15.0 21.1 20.8 20.6 20.5
-10.0 24.1 23.8 23.4 21.7
-5.0 27.1 26.7 24.6 21.7
0.0 30.0 29.7 24.6 21.7
2.5 31.5 31.2 24.6 21.7
250
6.0 31.8 31.5 24.6 21.7
7.5 33.2 31.5 24.6 21.7
10.0 35.4 31.5 24.6 21.7
12.5 37.7 31.5 24.6 21.7
15.5 38.1 31.5 24.6 21.7

2- 13
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
VML-A1/VMH-A

20.0 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.6 2.0 2.7 1.9
22.5 2.0 1.8 2.1 1.9 2.3 1.8 2.4 2.0 2.6 1.9 2.7 1.9
PEFY-P-

25.0 2.0 1.8 2.1 1.8 2.2 1.8 2.4 2.0 2.5 1.9 2.7 1.9
27.5 2.0 1.8 2.1 1.8 2.2 1.8 2.4 1.9 2.5 1.9 2.6 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.5 1.9 2.6 1.9
32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9
35.0 1.9 1.7 2.0 1.8 2.1 1.8 2.3 1.9 2.4 1.9 2.5 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.4 1.9 2.5 1.8
40.0 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.8
43.0 1.9 1.7 1.9 1.8 2.1 1.8 2.2 1.9 2.3 1.8 2.4 1.8
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3 3.3 2.3 3.4 2.2
25.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.2 2.3 3.4 2.2
27.5 2.5 2.1 2.6 2.2 2.8 2.1 3.0 2.3 3.2 2.2 3.3 2.2
25 30.0 2.5 2.1 2.6 2.1 2.8 2.1 3.0 2.3 3.1 2.2 3.3 2.2
32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.2 3.1 2.2 3.2 2.2
35.0 2.5 2.0 2.6 2.1 2.7 2.1 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.1
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.1
43.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.2 2.9 2.1 3.0 2.1
20.0 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.9 4.2 2.8 4.5 2.8
22.5 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.8 4.2 2.8 4.4 2.8
25.0 3.3 2.6 3.4 2.7 3.7 2.7 3.9 2.8 4.1 2.8 4.4 2.7
27.5 3.3 2.6 3.4 2.7 3.6 2.7 3.9 2.8 4.1 2.8 4.3 2.7
32 30.0 3.2 2.6 3.4 2.7 3.6 2.6 3.8 2.8 4.0 2.7 4.2 2.7
32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.8 2.8 4.0 2.7 4.2 2.7
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.9 2.7 4.1 2.7
37.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.6
40.0 3.1 2.5 3.2 2.6 3.4 2.6 3.6 2.7 3.8 2.7 4.0 2.6
43.0 3.1 2.5 3.2 2.6 3.4 2.5 3.5 2.7 3.7 2.6 3.9 2.6
20.0 4.1 3.2 4.3 3.3 4.7 3.3 5.0 3.5 5.3 3.5 5.6 3.4
22.5 4.1 3.2 4.3 3.3 4.6 3.3 4.9 3.5 5.2 3.4 5.5 3.4
25.0 4.1 3.2 4.3 3.3 4.6 3.3 4.9 3.5 5.2 3.4 5.5 3.4
27.5 4.1 3.2 4.2 3.3 4.5 3.3 4.8 3.4 5.1 3.4 5.4 3.3
40 30.0 4.0 3.1 4.2 3.3 4.5 3.2 4.8 3.4 5.0 3.4 5.3 3.3
32.5 4.0 3.1 4.2 3.2 4.4 3.2 4.7 3.4 5.0 3.3 5.2 3.3
35.0 4.0 3.1 4.1 3.2 4.4 3.2 4.6 3.4 4.9 3.3 5.1 3.2
37.5 3.9 3.1 4.1 3.2 4.3 3.2 4.6 3.3 4.8 3.3 5.1 3.2
40.0 3.9 3.1 4.0 3.2 4.3 3.1 4.5 3.3 4.7 3.3 5.0 3.2
43.0 3.9 3.1 4.0 3.2 4.2 3.1 4.4 3.3 4.7 3.2 4.9 3.2
20.0 5.2 3.7 5.4 3.9 5.8 3.9 6.2 4.1 6.6 4.0 7.0 4.0
22.5 5.2 3.7 5.4 3.9 5.8 3.9 6.2 4.1 6.5 4.0 6.9 3.9
25.0 5.1 3.7 5.3 3.8 5.7 3.8 6.1 4.0 6.4 4.0 6.8 3.9
27.5 5.1 3.7 5.3 3.8 5.6 3.8 6.0 4.0 6.3 3.9 6.7 3.9
50 30.0 5.0 3.7 5.2 3.8 5.6 3.8 5.9 4.0 6.2 3.9 6.6 3.8
32.5 5.0 3.6 5.2 3.8 5.5 3.7 5.8 3.9 6.2 3.9 6.5 3.8
35.0 4.9 3.6 5.1 3.7 5.4 3.7 5.8 3.9 6.1 3.8 6.4 3.7
37.5 4.9 3.6 5.1 3.7 5.4 3.7 5.7 3.9 6.0 3.8 6.3 3.7
40.0 4.9 3.6 5.0 3.7 5.3 3.6 5.6 3.8 5.9 3.7 6.2 3.7
43.0 4.8 3.6 5.0 3.7 5.2 3.6 5.5 3.8 5.8 3.7 6.1 3.6
20.0 6.5 4.9 6.9 5.1 7.4 5.1 7.9 5.4 8.4 5.3 8.9 5.2
22.5 6.5 4.9 6.8 5.1 7.3 5.1 7.8 5.4 8.3 5.3 8.7 5.2
25.0 6.5 4.9 6.8 5.1 7.2 5.0 7.7 5.3 8.1 5.2 8.6 5.1
27.5 6.4 4.9 6.7 5.0 7.2 5.0 7.6 5.3 8.0 5.2 8.5 5.1
63 30.0 6.4 4.8 6.6 5.0 7.1 5.0 7.5 5.2 7.9 5.1 8.4 5.1
32.5 6.3 4.8 6.6 5.0 7.0 4.9 7.4 5.2 7.8 5.1 8.2 5.0
35.0 6.3 4.8 6.5 4.9 6.9 4.9 7.3 5.2 7.7 5.1 8.1 5.0
37.5 6.2 4.8 6.4 4.9 6.8 4.9 7.2 5.1 7.6 5.0 8.0 4.9
40.0 6.2 4.7 6.4 4.9 6.7 4.8 7.1 5.1 7.5 5.0 7.9 4.9
43.0 6.1 4.7 6.3 4.8 6.6 4.8 7.0 5.0 7.3 4.9 7.7 4.8

2- 14
Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

VML-A1/VMH-A
20.0 7.4 5.5 7.7 5.7 8.3 5.7 8.9 6.0 9.4 5.9 10.0 5.8
22.5 7.4 5.5 7.7 5.7 8.2 5.7 8.8 6.0 9.3 5.9 9.8 5.8

PEFY-P-
25.0 7.3 5.5 7.6 5.7 8.2 5.6 8.7 5.9 9.2 5.8 9.7 5.7
27.5 7.2 5.4 7.5 5.6 8.1 5.6 8.6 5.9 9.0 5.8 9.6 5.7
71 30.0 7.2 5.4 7.5 5.6 8.0 5.5 8.5 5.8 8.9 5.7 9.4 5.6
32.5 7.1 5.4 7.4 5.5 7.9 5.5 8.3 5.8 8.8 5.7 9.3 5.6
35.0 7.1 5.3 7.3 5.5 7.8 5.5 8.2 5.7 8.7 5.6 9.1 5.5
37.5 7.0 5.3 7.2 5.5 7.7 5.4 8.1 5.7 8.6 5.6 9.0 5.5
40.0 7.0 5.3 7.2 5.4 7.6 5.4 8.0 5.7 8.4 5.6 8.9 5.4
43.0 6.9 5.2 7.1 5.4 7.5 5.3 7.9 5.6 8.3 5.5 8.7 5.4
20.0 8.3 6.2 8.7 6.5 9.4 6.5 10.0 6.8 10.6 6.7 11.2 6.6
22.5 8.3 6.2 8.7 6.4 9.3 6.4 9.9 6.8 10.5 6.7 11.1 6.6
25.0 8.2 6.2 8.6 6.4 9.2 6.4 9.8 6.7 10.3 6.6 10.9 6.5
27.5 8.1 6.1 8.5 6.4 9.1 6.3 9.6 6.7 10.2 6.6 10.8 6.4
80 30.0 8.1 6.1 8.4 6.3 9.0 6.3 9.5 6.6 10.0 6.5 10.6 6.4
32.5 8.0 6.1 8.3 6.3 8.9 6.2 9.4 6.6 9.9 6.4 10.4 6.3
35.0 8.0 6.0 8.2 6.2 8.8 6.2 9.3 6.5 9.8 6.4 10.3 6.3
37.5 7.9 6.0 8.1 6.2 8.6 6.1 9.1 6.5 9.6 6.3 10.1 6.2
40.0 7.8 6.0 8.1 6.2 8.5 6.1 9.0 6.4 9.5 6.3 10.0 6.2
43.0 7.7 5.9 8.0 6.1 8.4 6.0 8.9 6.3 9.3 6.2 9.8 6.1
20.0 10.3 8.4 10.8 8.7 11.6 8.7 12.5 9.3 13.2 9.2 14.0 9.0
22.5 10.3 8.4 10.8 8.7 11.5 8.7 12.3 9.2 13.0 9.1 13.8 8.9
25.0 10.2 8.3 10.7 8.7 11.4 8.6 12.1 9.2 12.8 9.0 13.6 8.9
27.5 10.1 8.3 10.6 8.6 11.3 8.6 12.0 9.1 12.7 9.0 13.4 8.8
100 30.0 10.1 8.3 10.5 8.6 11.2 8.5 11.8 9.0 12.5 8.9 13.2 8.7
32.5 10.0 8.2 10.3 8.5 11.0 8.5 11.7 9.0 12.3 8.8 13.0 8.7
35.0 9.9 8.2 10.2 8.5 10.9 8.4 11.5 8.9 12.1 8.8 12.8 8.6
37.5 9.8 8.1 10.1 8.4 10.8 8.3 11.4 8.9 12.0 8.7 12.6 8.5
40.0 9.7 8.1 10.0 8.4 10.6 8.3 11.2 8.8 11.8 8.6 12.4 8.5
43.0 9.6 8.1 9.9 8.3 10.5 8.2 11.0 8.7 11.6 8.6 12.2 8.4
20.0 12.9 9.6 13.5 10.0 14.6 10.0 15.6 10.6 16.5 10.4 17.5 10.3
22.5 12.9 9.6 13.5 10.0 14.4 10.0 15.4 10.5 16.3 10.3 17.2 10.2
25.0 12.8 9.6 13.3 9.9 14.3 9.9 15.2 10.4 16.1 10.2 17.0 10.1
27.5 12.7 9.5 13.2 9.9 14.1 9.8 15.0 10.3 15.8 10.2 16.7 10.0
125 30.0 12.6 9.5 13.1 9.8 13.9 9.7 14.8 10.2 15.6 10.1 16.5 9.9
32.5 12.5 9.4 12.9 9.7 13.8 9.7 14.6 10.2 15.4 10.0 16.2 9.8
35.0 12.4 9.4 12.8 9.7 13.6 9.6 14.4 10.1 15.2 9.9 16.0 9.7
37.5 12.3 9.3 12.7 9.6 13.5 9.5 14.2 10.0 15.0 9.8 15.7 9.6
40.0 12.2 9.3 12.5 9.5 13.3 9.4 14.0 9.9 14.8 9.7 15.5 9.5
43.0 12.0 9.2 12.4 9.5 13.1 9.4 13.8 9.8 14.5 9.6 15.2 9.4
20.0 14.7 11.0 15.4 11.4 16.6 11.4 17.8 12.1 18.8 11.9 20.0 11.7
22.5 14.7 11.0 15.4 11.4 16.5 11.4 17.6 12.0 18.6 11.8 19.7 11.6
25.0 14.6 10.9 15.2 11.3 16.3 11.3 17.4 11.9 18.3 11.7 19.4 11.5
27.5 14.5 10.9 15.1 11.3 16.1 11.2 17.1 11.8 18.1 11.6 19.1 11.4
140 30.0 14.4 10.8 14.9 11.2 15.9 11.1 16.9 11.7 17.8 11.5 18.8 11.3
32.5 14.3 10.8 14.8 11.1 15.7 11.0 16.7 11.6 17.6 11.4 18.6 11.2
35.0 14.1 10.7 14.6 11.1 15.6 11.0 16.5 11.5 17.4 11.3 18.3 11.1
37.5 14.0 10.6 14.5 11.0 15.4 10.9 16.2 11.4 17.1 11.2 18.0 11.0
40.0 13.9 10.6 14.3 10.9 15.2 10.8 16.0 11.3 16.9 11.1 17.7 10.9
43.0 13.8 10.5 14.2 10.8 15.0 10.7 15.8 11.2 16.6 11.0 17.4 10.8
20.0 20.6 15.8 21.6 16.4 23.3 16.4 24.9 17.4 26.4 17.1 28.0 16.9
22.5 20.6 15.8 21.5 16.4 23.1 16.3 24.6 17.2 26.0 17.0 27.6 16.7
25.0 20.4 15.7 21.3 16.3 22.8 16.2 24.3 17.1 25.7 16.9 27.2 16.6
27.5 20.3 15.6 21.1 16.2 22.6 16.1 24.0 17.0 25.3 16.7 26.8 16.4
200 30.0 20.1 15.5 20.9 16.1 22.3 16.0 23.7 16.9 25.0 16.6 26.4 16.3
32.5 20.0 15.4 20.7 16.0 22.0 15.9 23.4 16.7 24.6 16.5 26.0 16.2
35.0 19.8 15.4 20.5 15.9 21.8 15.7 23.1 16.6 24.3 16.3 25.6 16.0
37.5 19.6 15.3 20.3 15.8 21.5 15.6 22.7 16.5 23.9 16.2 25.2 15.9
40.0 19.5 15.2 20.1 15.7 21.3 15.5 22.4 16.4 23.6 16.1 24.8 15.8
43.0 19.3 15.1 19.8 15.6 21.0 15.4 22.1 16.2 23.2 15.9 24.3 15.6
20.0 25.8 19.6 27.0 20.4 29.1 20.4 31.1 21.6 33.0 21.3 34.9 20.9
22.5 25.8 19.6 26.9 20.4 28.9 20.3 30.8 21.4 32.5 21.1 34.4 20.8
25.0 25.6 19.5 26.7 20.2 28.5 20.1 30.4 21.3 32.1 20.9 34.0 20.6
27.5 25.4 19.4 26.4 20.1 28.2 20.0 30.0 21.1 31.7 20.8 33.5 20.4
250 30.0 25.1 19.3 26.1 20.0 27.9 19.9 29.6 20.9 31.2 20.6 33.0 20.2
32.5 24.9 19.2 25.9 19.9 27.6 19.7 29.2 20.8 30.8 20.4 32.5 20.1
35.0 24.7 19.1 25.6 19.7 27.2 19.6 28.8 20.6 30.4 20.3 32.0 19.9
37.5 24.5 19.0 25.4 19.6 26.9 19.4 28.4 20.5 29.9 20.1 31.5 19.7
40.0 24.3 18.9 25.1 19.5 26.6 19.3 28.0 20.3 29.5 20.0 31.0 19.6
43.0 24.1 18.8 24.8 19.4 26.2 19.1 27.6 20.1 29.0 19.8 30.4 19.4

2- 15
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 5.6 5.5 5.4 5.3
-10.0 1.8 1.8 1.7 1.7 -10.0 6.4 6.3 6.2 6.1
VML-A1/VMH-A

-5.0 2.0 2.0 2.0 1.9 -5.0 7.2 7.1 7.0 6.9
0.0 2.2 2.2 2.1 1.9 0.0 8.0 8.0 7.7 6.9
PEFY-P-

2.5 2.4 2.3 2.1 1.9 2.5 8.5 8.4 7.7 6.9
20 71
6.0 2.5 2.5 2.1 1.9 6.0 9.1 9.0 7.7 6.9
7.5 2.6 2.5 2.1 1.9 7.5 9.4 9.0 7.7 6.9
10.0 2.7 2.5 2.1 1.9 10.0 9.8 9.0 7.7 6.9
12.5 2.9 2.5 2.1 1.9 12.5 10.3 9.0 7.7 6.9
15.5 2.9 2.5 2.1 1.9 15.5 10.4 9.0 7.7 6.9
-15.0 2.0 2.0 1.9 1.9 -15.0 6.2 6.1 6.0 5.9
-10.0 2.3 2.2 2.2 2.2 -10.0 7.1 7.0 6.9 6.8
-5.0 2.6 2.5 2.5 2.5 -5.0 8.0 7.9 7.8 7.7
0.0 2.9 2.8 2.7 2.5 0.0 8.9 8.8 8.5 7.7
2.5 3.0 3.0 2.7 2.5 2.5 9.4 9.3 8.5 7.7
25 80
6.0 3.2 3.2 2.7 2.5 6.0 10.1 10.0 8.5 7.7
7.5 3.3 3.2 2.7 2.5 7.5 10.4 10.0 8.5 7.7
10.0 3.5 3.2 2.7 2.5 10.0 10.9 10.0 8.5 7.7
12.5 3.7 3.2 2.7 2.5 12.5 11.4 10.0 8.5 7.7
15.5 3.7 3.2 2.7 2.5 15.5 11.5 10.0 8.5 7.7
-15.0 2.5 2.5 2.4 2.4 -15.0 7.8 7.7 7.5 7.4
-10.0 2.8 2.8 2.8 2.7 -10.0 8.9 8.8 8.6 8.5
-5.0 3.2 3.2 3.1 3.1 -5.0 10.0 9.9 9.8 9.6
0.0 3.6 3.5 3.4 3.1 0.0 11.2 11.0 10.6 9.6
2.5 3.8 3.7 3.4 3.1 2.5 11.8 11.6 10.6 9.6
32 100
6.0 4.0 4.0 3.4 3.1 6.0 12.6 12.5 10.6 9.6
7.5 4.2 4.0 3.4 3.1 7.5 13.0 12.5 10.6 9.6
10.0 4.4 4.0 3.4 3.1 10.0 13.6 12.5 10.6 9.6
12.5 4.6 4.0 3.4 3.1 12.5 14.3 12.5 10.6 9.6
15.5 4.6 4.0 3.4 3.1 15.5 14.4 12.5 10.6 9.6
-15.0 3.1 3.1 3.0 3.0 -15.0 10.0 9.8 9.6 9.5
-10.0 3.6 3.5 3.5 3.4 -10.0 11.4 11.2 11.0 10.9
-5.0 4.0 4.0 3.9 3.9 -5.0 12.8 12.6 12.5 12.3
0.0 4.5 4.4 4.3 3.9 0.0 14.3 14.1 13.6 12.3
2.5 4.7 4.7 4.3 3.9 2.5 15.1 14.9 13.6 12.3
40 125
6.0 5.0 5.0 4.3 3.9 6.0 16.2 16.0 13.6 12.3
7.5 5.2 5.0 4.3 3.9 7.5 16.6 16.0 13.6 12.3
10.0 5.4 5.0 4.3 3.9 10.0 17.4 16.0 13.6 12.3
12.5 5.7 5.0 4.3 3.9 12.5 18.3 16.0 13.6 12.3
15.5 5.8 5.0 4.3 3.9 15.5 18.4 16.0 13.6 12.3
-15.0 3.9 3.9 3.8 3.7 -15.0 11.2 11.0 10.9 10.7
-10.0 4.5 4.4 4.3 4.3 -10.0 12.8 12.6 12.4 12.2
-5.0 5.0 5.0 4.9 4.9 -5.0 14.4 14.2 14.1 13.9
0.0 5.6 5.6 5.4 4.9 0.0 16.1 15.9 15.3 13.9
2.5 5.9 5.9 5.4 4.9 2.5 17.0 16.8 15.3 13.9
50 140
6.0 6.4 6.3 5.4 4.9 6.0 18.2 18.0 15.3 13.9
7.5 6.6 6.3 5.4 4.9 7.5 18.7 18.0 15.3 13.9
10.0 6.9 6.3 5.4 4.9 10.0 19.6 18.0 15.3 13.9
12.5 7.2 6.3 5.4 4.9 12.5 20.5 18.0 15.3 13.9
15.5 7.2 6.3 5.4 4.9 15.5 20.7 18.0 15.3 13.9
-15.0 5.0 4.9 4.8 4.7 -15.0 15.6 15.3 15.1 14.8
-10.0 5.7 5.6 5.5 5.4 -10.0 17.8 17.5 17.3 17.0
-5.0 6.4 6.3 6.2 6.2 -5.0 20.0 19.8 19.5 19.3
0.0 7.2 7.1 6.8 6.2 0.0 22.3 22.1 21.3 19.3
2.5 7.5 7.5 6.8 6.2 2.5 23.5 23.3 21.3 19.3
63 200
6.0 8.1 8.0 6.8 6.2 6.0 25.2 25.0 21.3 19.3
7.5 8.3 8.0 6.8 6.2 7.5 26.0 25.0 21.3 19.3
10.0 8.7 8.0 6.8 6.2 10.0 27.2 25.0 21.3 19.3
12.5 9.1 8.0 6.8 6.2 12.5 28.5 25.0 21.3 19.3
15.5 9.2 8.0 6.8 6.2 15.5 28.8 25.0 21.3 19.3
-15.0 19.6 19.3 19.0 18.7
-10.0 22.4 22.1 21.7 21.4
-5.0 25.2 24.9 24.6 24.3
0.0 28.2 27.8 26.8 24.3
2.5 29.7 29.4 26.8 24.3
250
6.0 31.8 31.5 26.8 24.3
7.5 32.8 31.5 26.8 24.3
10.0 34.3 31.5 26.8 24.3
12.5 35.9 31.5 26.8 24.3
15.5 36.2 31.5 26.8 24.3

2- 16
2-7.Cooling Capacity (In combination with WY, WR2)
CA :Capacity(kW)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water
Unit temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

VML-A1/VMH-A
10 2.1 1.8 2.2 1.9 2.4 1.9 2.4 1.9 2.5 2.0 2.6 2.0 2.8 1.9
20 2.1 1.8 2.1 1.9 2.3 1.8 2.3 1.9 2.4 2.0 2.5 1.9 2.7 1.9

PEFY-P-
20 30 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9
40 1.7 1.6 1.8 1.7 1.9 1.7 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.8
45 1.6 1.6 1.7 1.7 1.8 1.6 1.8 1.7 1.9 1.8 2.0 1.7 2.1 1.7
10 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.3 2.3 3.5 2.3
20 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.2
25 30 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.1 2.9 2.2 3.0 2.2 3.2 2.2
40 2.2 1.9 2.2 2.0 2.4 2.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.0
45 2.0 1.8 2.1 1.9 2.2 1.9 2.3 1.9 2.4 2.0 2.5 2.0 2.6 2.0
10 3.5 2.7 3.6 2.8 3.9 2.8 4.0 2.8 4.1 2.9 4.3 2.9 4.5 2.8
20 3.4 2.6 3.5 2.7 3.7 2.7 3.8 2.7 3.9 2.8 4.1 2.8 4.4 2.7
32 30 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.7
40 2.8 2.3 2.9 2.4 3.1 2.4 3.1 2.5 3.2 2.6 3.4 2.5 3.6 2.5
45 2.6 2.3 2.7 2.4 2.9 2.3 3.0 2.4 3.0 2.5 3.2 2.4 3.4 2.4
10 4.4 3.3 4.5 3.4 4.8 3.4 5.0 3.4 5.1 3.6 5.4 3.5 5.7 3.4
20 4.2 3.2 4.4 3.3 4.6 3.3 4.8 3.4 4.9 3.5 5.2 3.4 5.5 3.4
40 30 4.0 3.1 4.1 3.2 4.4 3.2 4.5 3.2 4.6 3.4 4.9 3.3 5.2 3.3
40 3.5 2.9 3.6 3.0 3.8 2.9 3.9 3.0 4.0 3.1 4.3 3.1 4.5 3.0
45 3.3 2.8 3.4 2.9 3.6 2.9 3.7 2.9 3.8 3.0 4.0 3.0 4.2 2.9
10 5.5 3.9 5.6 4.0 6.0 4.0 6.2 4.0 6.3 4.1 6.7 4.1 7.1 4.0
20 5.3 3.8 5.4 3.9 5.8 3.9 5.9 3.9 6.1 4.0 6.5 4.0 6.8 3.9
50 30 5.0 3.6 5.1 3.7 5.5 3.7 5.6 3.7 5.8 3.9 6.1 3.8 6.4 3.8
40 4.3 3.3 4.5 3.4 4.7 3.4 4.9 3.4 5.0 3.6 5.3 3.5 5.6 3.5
45 4.1 3.2 4.2 3.3 4.5 3.3 4.6 3.3 4.7 3.5 5.0 3.4 5.3 3.3
10 6.9 5.1 7.2 5.3 7.6 5.2 7.8 5.3 8.0 5.5 8.5 5.4 9.0 5.3
20 6.7 5.0 6.9 5.1 7.3 5.1 7.5 5.1 7.8 5.3 8.2 5.2 8.6 5.2
63 30 6.3 4.8 6.5 4.9 6.9 4.9 7.1 5.0 7.3 5.2 7.7 5.1 8.1 5.0
40 5.5 4.4 5.7 4.5 6.0 4.5 6.2 4.6 6.4 4.8 6.7 4.7 7.1 4.6
45 5.2 4.3 5.3 4.4 5.7 4.4 5.8 4.4 6.0 4.6 6.3 4.6 6.7 4.5
10 7.8 5.7 8.1 5.9 8.6 5.8 8.8 5.9 9.1 6.1 9.6 6.0 10.1 5.9
20 7.5 5.6 7.8 5.7 8.3 5.7 8.5 5.7 8.7 6.0 9.2 5.9 9.7 5.8
71 30 7.1 5.4 7.3 5.5 7.8 5.5 8.0 5.5 8.2 5.7 8.7 5.7 9.2 5.6
40 6.2 4.9 6.4 5.1 6.8 5.0 7.0 5.1 7.2 5.3 7.6 5.2 8.0 5.1
45 5.8 4.7 6.0 4.9 6.4 4.9 6.6 4.9 6.8 5.1 7.1 5.1 7.5 5.0
10 8.8 6.5 9.1 6.6 9.6 6.6 9.9 6.7 10.2 6.9 10.8 6.8 11.4 6.7
20 8.5 6.3 8.7 6.5 9.3 6.4 9.5 6.5 9.8 6.7 10.4 6.6 10.9 6.5
80 30 8.0 6.1 8.3 6.2 8.8 6.2 9.0 6.3 9.3 6.5 9.8 6.4 10.3 6.3
40 6.9 5.6 7.2 5.7 7.6 5.7 7.8 5.8 8.1 6.0 8.5 5.9 9.0 5.8
45 6.5 5.4 6.8 5.6 7.2 5.5 7.4 5.6 7.6 5.8 8.0 5.7 8.5 5.7
10 10.9 8.7 11.3 9.0 12.0 8.9 12.3 9.0 12.7 9.4 13.4 9.2 14.1 9.1
20 10.5 8.5 10.9 8.8 11.6 8.7 11.9 8.8 12.2 9.2 12.9 9.0 13.6 8.9
100 30 9.9 8.2 10.3 8.5 10.9 8.4 11.2 8.6 11.5 8.9 12.2 8.8 12.8 8.6
40 8.6 7.6 8.9 7.9 9.5 7.8 9.7 8.0 10.0 8.3 10.6 8.2 11.2 8.1
45 8.1 7.4 8.4 7.7 8.9 7.6 9.2 7.8 9.5 8.1 10.0 8.0 10.5 7.9
10 13.7 10.0 14.1 10.3 15.0 10.2 15.4 10.3 15.9 10.7 16.7 10.5 17.7 10.3
20 13.2 9.8 13.6 10.1 14.5 10.0 14.8 10.1 15.3 10.5 16.1 10.3 17.0 10.1
125 30 12.4 9.4 12.8 9.7 13.6 9.6 14.0 9.7 14.4 10.1 15.2 9.9 16.1 9.7
40 10.8 8.6 11.2 8.9 11.9 8.8 12.2 9.0 12.5 9.3 13.2 9.2 14.0 9.0
45 10.2 8.3 10.5 8.6 11.2 8.5 11.5 8.7 11.8 9.0 12.5 8.9 13.2 8.8
10 15.6 11.4 16.1 11.8 17.1 11.7 17.6 11.8 18.1 12.2 19.1 12.0 20.2 11.8
20 15.0 11.2 15.6 11.5 16.5 11.4 17.0 11.5 17.5 11.9 18.4 11.8 19.5 11.5
140 30 14.2 10.7 14.7 11.1 15.6 11.0 16.0 11.1 16.5 11.5 17.4 11.3 18.4 11.1
40 12.3 9.8 12.8 10.2 13.6 10.1 13.9 10.3 14.3 10.7 15.1 10.5 16.0 10.3
45 11.6 9.5 12.0 9.8 12.8 9.8 13.1 9.9 13.5 10.3 14.3 10.2 15.0 10.0
10 21.9 16.4 22.6 16.9 24.0 16.7 24.6 16.9 25.4 17.6 26.8 17.3 28.3 17.0
20 21.1 16.0 21.8 16.5 23.1 16.3 23.7 16.6 24.5 17.2 25.8 16.9 27.2 16.6
200 30 19.9 15.4 20.5 15.9 21.8 15.8 22.4 16.0 23.1 16.6 24.3 16.4 25.7 16.1
40 17.3 14.2 17.9 14.7 19.0 14.5 19.5 14.8 20.1 15.4 21.2 15.2 22.4 14.9
45 16.3 13.7 16.8 14.2 17.9 14.1 18.4 14.4 18.9 15.0 20.0 14.7 21.1 14.5
10 27.3 20.4 28.2 21.0 30.0 20.8 30.8 21.0 31.7 21.8 33.5 21.5 35.3 21.1
20 26.3 19.9 27.2 20.5 28.9 20.3 29.7 20.6 30.6 21.4 32.3 21.0 34.0 20.6
250 30 24.8 19.1 25.7 19.8 27.3 19.6 28.0 19.9 28.8 20.6 30.4 20.3 32.1 20.0
40 21.6 17.6 22.3 18.2 23.7 18.1 24.4 18.4 25.1 19.1 26.5 18.8 27.9 18.5
45 20.4 17.0 21.1 17.7 22.4 17.5 23.0 17.8 23.6 18.6 25.0 18.3 26.3 18.0

2- 17
2-8.Heating Capacity (In combination with WY, WR2)
PEFY-P-VML-A1,VMH-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.:˚CDB
Unit Water temp.
15 19 20 25 27
size
˚C SHC SHC SHC SHC SHC
10 2.2 2.2 2.1 1.7 1.5
VML-A1/VMH-A

20 2.6 2.6 2.5 2.0 1.8


20 30 2.6 2.6 2.5 2.0 1.8
PEFY-P-

40 2.7 2.7 2.6 2.1 1.9


45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 7.9 7.8 7.7 6.1 5.5
20 9.3 9.2 9.0 7.2 6.5
71 30 9.3 9.2 9.0 7.2 6.5
40 9.6 9.5 9.4 7.5 6.7
45 10.6 10.5 10.3 8.2 7.4
10 8.8 8.7 8.5 6.8 6.1
20 10.3 10.2 10.0 8.0 7.2
80 30 10.3 10.2 10.0 8.0 7.2
40 10.7 10.6 10.4 8.3 7.5
45 11.7 11.6 11.4 9.1 8.2
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1
10 15.8 15.6 15.3 12.2 11.0
20 18.5 18.4 18.0 14.4 13.0
140 30 18.5 18.4 18.0 14.4 13.0
40 19.3 19.1 18.7 15.0 13.5
45 21.1 20.9 20.5 16.4 14.8
10 21.9 21.7 21.3 17.0 15.3
20 25.8 25.5 25.0 20.0 18.0
200 30 25.8 25.5 25.0 20.0 18.0
40 26.8 26.5 26.0 20.8 18.7
45 29.4 29.1 28.5 22.8 20.5
10 27.6 27.3 26.8 21.4 19.3
20 32.4 32.1 31.5 25.2 22.7
250 30 32.4 32.1 31.5 25.2 22.7
40 33.7 33.4 32.8 26.2 23.6
45 37.0 36.6 35.9 28.7 25.9

2- 18
3. Sound Levels
3-1. Noise level(VML-A1)

➀ Rear inlet model1


Aux.duct
1m 2m Noise level at anechoic room (Low-Mid-High) Unit : dB(A)

VML-A1/VMH-A
Model Noise level (A weighted)

PEFY-P-
PEFY-P20VML-A1 25-29-36
PEFY-P25VML-A1
1.5m PEFY-P32VML-A1 25-29-40

Measurement location

3-2. NC curves(VML-A1)

PEFY-P20,25VML-A1 PEFY-P32VML-A1
External static pressure : 5Pa External static pressure : 5Pa
Power source : 220·230·240(V) Power source : 220·230·240(V)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

3-3. Fan characteristics curves(VML-A1)

PEFY-P20,25VML-A1 PEFY-P32VML-A1
Power source : 220·230·240(V) Power source : 220·230·240(V)
18 12
50Hz 50Hz
60Hz 60Hz High
16 10
Static pressure (Pa)

14 8
High
Static pressure (Pa)

12 6

10 4
Middle
Middle
8 2
Low

6 0
Low 4 5 6 7 8 9 10
Airflow rate (m3/min)
4

0
4 5 6 7 8 9
Airflow rate (m3/min)

2- 19
3-4. Noise level(VMH-A)

Aux.duct Noise level at anechoic room (Low-High) Unit : dB(A)


1m 2m
Model External static pressure❇
Low Mid High
VML-A1/VMH-A

PEFY-P40, 50 220V 25-30 27-34 30-40


PEFY-P-

VMH-A 230, 240V 30-34 31-37 31-41

PEFY- 220V 31-36 32-38 36-43


1.5m
P63VMH-A 230, 240V 35-39 36-41 38-44

PEFY- 220V 30-36 32-39 35-43


Measurement location
P71VMH-A 230, 240V 34-39 35-41 37-44
PEFY- 220V 32-39 35-41 37-43
P80VMH-A 230, 240V 37-41 38-43 39-45
PEFY-P100, 220V 32-40 34-42 36-46
❇ PEFY-P40~140VMH-A 125, 140VMH-A
230, 240V 36-42 38-44 38-47
Low : 50Pa (at 220V) / 100Pa (at 230, 240V)
Mid : 100Pa (at 220V) / 150Pa (at 230, 240V) PEFY- 380V 42 – 45
High : 200Pa (at 220, 230, 240V) P200VMH-A –
400, 415V 44 47
❇ PEFY-P200, 250VMH-A –
PEFY- 380V 50 52
Low : 110Pa (at 380V) / 130Pa (at 400, 415V)
High : 220Pa (at 380V) / 260Pa (at 400, 415V) P250VMH-A 400, 415V 52 – 54

3-5. NC curves(VMH-A)

PEFY-P40,50VMH-A (External static


pressure 50Pa) PEFY-P40,50VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40,50VMH-A (External static


pressure 200Pa) PEFY-P63VMH-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 20
PEFY-P63VMH-A (External static
pressure 100Pa) PEFY-P63VMH-A (External static
pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
220V-50/60Hz Low speed
220V-50/60Hz Low speed
60 60
NC60 NC60

VML-A1/VMH-A
50 50
NC50 NC50

PEFY-P-
40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P71VMH-A (External static


pressure 50Pa) PEFY-P71VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P71VMH-A (External static PEFY-P80VMH-A (External static


pressure 200Pa) pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A (External static PEFY-P80VMH-A (External static


pressure 100Pa) pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


220V-50/60Hz 220V-50/60Hz
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 21
PEFY-P100,125,140VMH-A (External static
pressure 50Pa) PEFY-P100,125,140VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60
VML-A1/VMH-A

50 50
NC50 NC50
PEFY-P-

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P100,125,140VMH-A (External static


pressure 200Pa) PEFY-P200VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed 220Pa
220V-50/60Hz Low speed 380V-50/60Hz 110Pa
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P250VMH-A (External static


pressure 150Pa) PEFY-P40,50VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

220Pa High speed


380V-50/60Hz 110Pa 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40,50VMH-A (External static


pressure 150Pa) PEFY-P40,50VMH-A (External static
pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


230·240V-50/60Hz Low speed 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 22
PEFY-P63VMH-A (External static
pressure 100Pa) PEFY-P63VMH-A (External static
pressure 150Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230·240V-50/60Hz 230·240V-50/60Hz
Low speed Low speed
60 60
NC60 NC60

VML-A1/VMH-A
50 50
NC50 NC50

PEFY-P-
40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P63VMH-A (External static


pressure 200Pa) PEFY-P71VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230·240V-50/60Hz Low speed 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P71VMH-A (External static


pressure 150Pa) PEFY-P71VMH-A (External static
pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


230·240V-50/60Hz Low speed 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A (External static


pressure 100Pa) PEFY-P80VMH-A (External static
pressure 150Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


230·240V-50/60Hz Low speed 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 23
PEFY-P80VMH-A (External static
pressure 200Pa) PEFY-P100,125,140VMH-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230·240V-50/60Hz 230·240V-50/60Hz
Low speed Low speed
60 60
NC60 NC60
VML-A1/VMH-A

50 50
NC50 NC50
PEFY-P-

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P100,125,140VMH-A (External static


pressure 150Pa) PEFY-P100,125,140VMH-A (External static
pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230·240V-50/60Hz Low speed 230·240V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P200VMH-A (External static (External static


pressure 150Pa) PEFY-P250VMH-A pressure 200Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

260Pa 400·415V-50/60Hz 260Pa


400·415V-50/60Hz 130Pa 130Pa
60 60 NC60
NC60

50 50 NC50
NC50

40 40 NC40
NC40

30 30
NC30
NC30

20 20
NC20
NC20
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 24
3-6. Fan characteristics curves(VMH-A)
PEFY-P40,50VMH-A PEFY-P40,50VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 50,100,200Pa External static pressure : 100,150,200Pa
Power source : 220(V) Power source : 230,240(V)
250 250
50Hz
50Hz
60Hz
60Hz

VML-A1/VMH-A
High(200) High(200)

PEFY-P-
200 200
High(150)

High(100)
Static pressure (Pa)

Static pressure (Pa)


150 150
High(100)

Low Low

100 100

High High
efficiency efficiency
High(50) filter filter
50 50

Long-life Long-life
filter filter
0 0
10 15 10 15
Airflow rate (m3/min) Airflow rate (m /min) 3

PEFY-P63VMH-A PEFY-P63VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 50,100,200Pa External static pressure : 100,150,200Pa
Power source : 220(V) Power source : 230·240(V)
250 250
50Hz 50Hz
High(150)
High(200) 60Hz High(200) 60Hz

High(100)
200 200

High(100)
Static pressure (Pa)

Static pressure (Pa)

150 150

Low Low

High(50)
100 100

High High
efficiency efficiency
filter filter
50 50

Long-life Long-life
filter filter
0 0
15 20 15 20
Airflow rate (m3/min) Airflow rate (m3/min)

PEFY-P71VMH-A PEFY-P71VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 50,100,200Pa External static pressure : 100,150,200Pa
Power source : 220(V) Power source : 230·240(V)
250 250
50Hz High(150) 50Hz
High(200) 60Hz High(200) 60Hz

High(100)
200 200

High(100)

High(50)
Static pressure (Pa)
Static pressure (Pa)

150 150
Low
Low

100 100

High High
50 efficiency 50 efficiency
filter filter

Long-life Long-life
0 filter 0 filter
15 20 25 15 20 25
3
Airflow rate (m /min) Airflow rate (m3/min)

2- 25
PEFY-P80VMH-A PEFY-P80VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 50,100,200Pa External static pressure : 100,150,200Pa
Power source : 220(V) Power source : 230·240(V)
250 250
50Hz
50Hz
60Hz
60Hz
VML-A1/VMH-A

High(200) High(200)
PEFY-P-

200 200

High(100) High(100)
High
(150)
High(50)

Static pressure (Pa)


Static pressure (Pa)

150 150

Low Low

100 100

High High
50 efficiency 50 efficiency
filter filter

Long-life Long-life
filter 0 filter
0
15 20 25 15 20 25
3 3
Airflow rate (m /min) Airflow rate (m /min)

PEFY-P100·125VMH-A PEFY-P100·125VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 50,100,200Pa External static pressure : 100,150,200Pa
Power source : 230·240(V)
Power source : 220(V)
250 250
High(200) 50Hz 50Hz
High(200)
60Hz 60Hz
High(150)

200 200
High(100)

High(100)
Static pressure (Pa)
Static pressure (Pa)

150 150

High(50)
Low
Low

100 100

High
High
efficiency efficiency
50 filter 50 filter

Long-life Long-life
filter filter
0 0
25 30 35 40 45 25 30 35 40 45
Airflow rate (m3/min) Airflow rate (m3/min)

PEFY-P140VMH-A
Suction : Back inlet PEFY-P140VMH-A
External static pressure : 50,100,200Pa Suction : Back inlet
External static pressure : 100,150,200Pa
Power source : 220(V) Power source : 230·240(V)
250 250
50Hz 50Hz
60Hz 60Hz

High(200) High(200)
High(150)
200 200

High(100)
Static pressure (Pa)

150
Static pressure (Pa)

150

High(50)
High(100)
100 100

Low Low
High
High
efficiency efficiency
filter filter
50 50

Long-life Long-life
filter filter
0 0
25 30 35 40 45 50 25 30 35 40 50
45
Airflow rate (m3/min) Airflow rate (m3/min)

2- 26
PEFY-P200VMH-A PEFY-P200VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 110,220Pa External static pressure : 130,260Pa
Power source : 380(V) Power source : 400·415(V)
350 350
50Hz 50Hz
60Hz 60Hz

VML-A1/VMH-A
(260)
300 300
(220)

PEFY-P-
250 250

(130)

Static pressure (Pa)


Static pressure (Pa)

(110)
200 200

150 150

100 100
High High
efficiency efficiency
filter filter
50 50

Long-life Long-life
filter filter
0 0
40 45 55 55 60 65 70 75 40 45 50 55 60 65 70 75
Airflow rate (m3/min) Airflow rate (m3/min)

PEFY-P250VMH-A PEFY-P250VMH-A
Suction : Back inlet Suction : Back inlet
External static pressure : 110,220Pa External static pressure : 130,260Pa
Power source : 400·415(V)
Power source : 380(V)
350 350
50Hz (260) 50Hz
60Hz 60Hz

300 300
(220)

250 250

(130)
Static pressure (Pa)
Static pressure (Pa)

(110)
200 200

150 150

100 100

High High
efficiency efficiency
50 filter 50 filter

Long-life Long-life
filter filter
0 0
55 60 65 70 75 80 85 90 55 60 65 70 75 80 85 90
Airflow rate (m3/min) Airflow rate (m3/min)

2- 27
PEFY-P-
VML-A1/VMH-A

12-ø3
PEFY-P20,25,32VML-A1

610
710
Air inlet Air outlet

50X11=550
Note : 1. Use M10 screw for the lifting bolt (field supply).
2. Keep the service space for the maintenance from the bottom
4. External Dimensions

when the heat exchanger is cleaned.

664 (Lifting bolt pitch)


Refrigerant piping brazing connection (gas ø12.7 copper tube): HP ······ ➀
15 Refrigerant piping brazing connection (liquid ø6.35 copper tube): LP ···· ➁

50
Drain piping connection R1 (External thread) ······· ➂

16
14

2- 28
80
80
23
Lifting bolt Control box
459 (Lifting bolt pitch) 55

510 30
15 582
148 42.5

14
2 1

13.5
Air filter

127
65.5

50 50
225
204.5

Terminal bed
Unit : mm

(Power source)
Terminal bed 3 113
(Transmission)
G-ø3
J-ø3 PEFY-P40,50,63,71,80,
100,125,140VMH-A

D
C
A

50x(J-1)=K
Air inlet Air outlet

50x(G-1)=H
B (Lifting bolt pitch)

50
Less than 300mm

50
15

80
10

41 F

2- 29
70
3

23
3
340 Lifting bolt 383 250
814 (Lifting bolt pitch) 60
904
Model:40~80 (Note3)
900
Less than 550 mm

24 847 29
10 15
Drain hole
Control box (option)
2 When installing the drain water lifting-up mech(option).

Model A B C D E F G H J K M N
250

PEFY-P40VMH-A 800 754 680 600 550 50 11 500 10 450 ø12.7 ø6.35
380

340
77
328

PEFY-P50·63VMH-A 800 754 680 600 550 50 11 500 10 450 ø15.88 ø9.52

50x5=250
50 50 50 50

PEFY-P71·80VMH-A 1050 1004 930 850 800 25 17 800 15 700 ø15.88 ø9.52

50
PEFY-P100·125·140VMH-A 1250 1204 1130 1050 1000 25 21 1000 19 900 ø19.05 ø9.52
130
94

45
41 25

Note : 1. Use M10 screw for the lifting bolt (field supply).
Terminal bed 2. Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned.

17
30 1
(Power source) 3. This chart indicates for PEFY-P100·125·140VMH-A models, which has 2 fans.
92 200 PEFY-P40·50·63·71·80 models have 1 fan.
Terminal box Terminal bed 4. Make sure to install the air filter(field supply) on the air intake side.
(Transmission) 343
In case field supplied air filter is used, attach it where the filter service is easily done.
Unit : mm

Keep duct-work length 850mm or more. 387


Drain hole Refrigerant piping flare connection (gas M copper tube): HP ··· ➀
Refrigerant piping flare connection (liquid N copper tube): LP ··· ➁
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory) ··· ➂

VML-A1/VMH-A
PEFY-P-
PEFY-P-
VML-A1/VMH-A

22-ø3
21-ø3

PEFY-P200, 250VMH-A

1100
1100

1250
1372
Air inlet Air outlet

50x21=1050
50x20=1000
1326 (Lifting bolt pitch)
50
15
10

102 25
100

2- 30
23
3
Lifting bolt
420 1034 (Lifting bolt pitch) 60 340
1124

1120
Note : 1. Use M10 screw for the lifting bolt (field supply).
24 1067 29 2. Keep the service space for the maintenance from the bottom
10 15 when the heat exchanger is cleaned.
Drain hole 3. Make sure to install the air filter(field supply)
(option)
on the air intake side.
Control box In case field supplied air filter is used, attach it where
the filter service is easily done.

Less than 300mm


Model A B
PEFY-P200VMH-A ø25.4 ø12.7
PEFY-P250VMH-A ø28.58 ø12.7
340

44
50x6= 300

3
470

420
Refrigerant piping brazing connection (gas A copper tube): HP ····➀
327

50x7= 350
Refrigerant piping brazing connection (liquid B copper tube): LP ····➁
Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory) ····➂
20

164
105

35
41

30

20
Less than 550mm

Terminal bed 2 1
(Power source) 95 249
Unit : mm

Keep duct-work length 850mm or more. Drain hole


Terminal bed 422
(Transmission) 489

When installing the drain water lifting-up mech(option).


INSIDE SECTION OF CONTROL BOX
I.B
1 SW4 SW3 SW2 TB15 (TRANSMISSION TERMINAL BED)
2 3 2
3 CN42 CN3A 1 1 TO MA REMOTE CONTROLLER
4
1
2 TB5 (TRANSMISSION TERMINAL BED)
3 S(SHIELD)
4 AC250V X06 X05 X04
5 CN81 F1 X01 2 M2 TO OUTDOOR UNIT
6.3A F ZNR CN2M 1
PEFY-P20~32VML-A1

6
( ) M1 BC CONTROLLER
7 ] REMOTE CONTROLLER
8 CN20 CN21 CN29 CN31 CN60 CN3T CNT CND CNP FAN3
21 21 21 21 654321 3 1 31 13 31 1357 S.B TO NEXT INDOOR UNIT
T CN1 1
ZNR1
DSA1 3 PULL BOX
A.B 12 3 45 6
CN82 CN62 TB2
8 L FUSE(16A)
7 SW1 SW5 N
6 PE
5 EF0 12 9 0 1 9 0 1
D 3 8 2 8 2
4 C 4 3 3 BREAKER(16A)
BA 5 7 7
3 9 8 76 6 5 4 6 5 4
2 C ✻ insert
1 SW14 SW12 SW11
❈A 7 6 54321
5. Electrical Wiring Diagrams

(Connection No.) (2nd digit) (1st digit)


(White) 76 54 3 21 7 6 54321
POWER SUPPLY

2- 31
(Blue) ~ 220,230,240V
MF 50,60Hz
PE
TO DUCT
LEV
TH21 TH22 TH23
The motor connector is connected
with 230V,240V power at factory shipment.
SYMBOL EXPLANATION If 220 power is used,
insert the attachment.
SYMBOL NAME SYMBOL NAME
Color/Power source
MF Fan motor TH21 Thermistor (inlet temp.detection) White/230V,240V
C ❈A Capacitor (for MF) TH22 Thermistor (piping temp.detection/liquid) Blue/220V
I.B Indoor controller board TH23 Thermistor (piping temp.detection/gas)
A.B Address board SW11(A.B) Switch (1st digit address set)
TB2 Power source terminal bed SW12(A.B) Switch (2nd digit address set) NOTE : 1.The wirings to TB2,TB5 shown in dotted line are field work.
TB5 Transmission terminal bed SW14(A.B) Switch (connection No.set)
TB15 Transmission terminal bed SW1(A.B) Switch(for mode selection)
2.Mark indicates terminal bed, connector, board
F1 Fuse AC250V 6.3A F SW2(I.B) Switch(for capacity code) insertion connector or fastening connector of control board.
T Transformer SW3(I.B) Switch(for mode selection) ❈A Capacitor
LEV Electronic linear expan. valve SW4(I.B) Switch(for model selection) MODELS 20/25 1.5µF
S.B Surge absorber board SW5(A.B) Switch(for voltage selection) MODEL 32 2.0µF
X04~X06 Aux.relay

VML-A1/VMH-A
PEFY-P-
PEFY-P-
VML-A1/VMH-A

INSIDE SECTION OF CONTROL BOX


I.B TB15 (TRANSMISSION TERMINAL BED)
1 SW4 SW3 SW2 3 2
2 CN3A 1 1 TO MA REMOTE CONTROLLER
3 CN42
4 TB5 (TRANSMISSION TERMINAL BED)
1 REMOTE CENTRALLY REMOTE S(SHIELD)
2 SWITCH CONTROL INDICATION 2 M2 TO OUTDOOR UNIT
3 CN2M
PEFY-P40~140VMH-A

CN32 CN51 CN52 AC250V 1 M1 BC CONTROLLER


4 X06 X05 X04 M-NET REMOTE CONTROLLER
5 CN81 6.3A F X01
6 F1 ZNR TO NEXT INDOOR UNIT
7
8 CN31
CN20 CN21 CN29 CN60 CN3T CNT CND CNP FAN3
21 21 21 21 654321 3 1 13 13 31 13 7 S.B
T CN1 1 PULL BOX
Drain sensor ZNR1

CN31
A DSA1 3
1 1 1 AC250V
A.B 12 3 4 5 6 F2 5A F
3 1 2 2 2
CN82 CN62 L TB2
8 FUSE(16A)
SW1 SW5 ✻ N
7 A connector is
6 attached to the PE
5 EF012 9 0 1 9 0 1 ✻
D 3 8 2 8 2 drain lift up ✻ insert
4 C 4 3 3 mechanism, B
BA 5 7 7 C BREAKER(16A)
3 9876 6 5 4 6 5 4 which is an
2 98 4 31 9 8 4 31
SW14 SW12 SW11 optional part. 98 431
1
(Connection No.) (2nd digit) (1st digit) ✻ (White) 9 8 6 5 4 3 1 986 31 9 8 5 31
DS NOTE 1,2

(Blue) (Red)
NOTE 1

2- 32
MF POWER SUPPLY
PE ~ 220,230,240V
TO DUCT
50,60Hz
attachment to alter the external static pressure on the fan
LEV Color/External Static Pressure
DP
Red/200Pa (at 220,230,240V)
TH21 TH22 TH23 ✻ Blue/50Pa (at 220V),100Pa(at 230,240V)
NOTE 1 White/100Pa (at 220V),150Pa(at 230,240V)
SYMBOL EXPLANATION
SYMBOL NAME SYMBOL NAME NOTE : 1.The part of the broken line indicates the circuit
MF Fan motor S.B Surge absorber board for optional parts.

C B Capacitor (for MF) TH21 Thermistor (inlet temp.detection)
2.✻A in the chart is the connector for a drain pump
I.B Indoor controller board TH22 Thermistor (piping temp.detection/liquid)
A.B Address board TH23 Thermistor (piping temp.detection/gas) test run operation.
TB2 Power source terminal bed SW11(A.B) Switch (1st digit address set) (The Drain Pump operates continuously if the
TB5 Transmission terminal bed SW12(A.B) Switch (2nd digit address set) connector is inserted and the power is supplied.)
TB15 Transmission terminal bed SW14(A.B) Switch (connection No.set) After the test run, make sure to remove the
F1 Fuse AC250V 6.3A F SW1(A.B) Switch(for mode selection) ✻
A connector.
<F2> Fuse AC250V 5A F SW2(I.B) Switch(for capacity code) ✻
Switch(for mode selection) B Capacitor 3.The wirings to TB2,TB5 (shown in dotted line) are
T Transformer SW3(I.B) MODELS 40/50 3.0µF
<DP> Drain Pump SW4(I.B) Switch(for model selection) field work.
MODEL 63 4.0µF
LEV Electronic linear expan. valve SW5(A.B) Switch(for voltage selection) MODELS 71/80 5.0µF 4.Mark indicates terminal bed, connector, board
<DS> Drain sensor X04~X06 Aux.relay MODELS 100/125/140 7.0µF insertion connector or fastening connector of control
inside < > is the optional parts board.
INSIDE SECTION OF CONTROL BOX
I.B TB15 (TRANSMISSION TERMINAL BED)
1 SW4 SW3 SW2 3 2
2 CN3A
3 1 1 TO MA REMOTE CONTROLLER
4 CN42
REMOTE CENTRALLY REMOTE
1 SWITCH CONTROL INDICATION TB5 (TRANSMISSION TERMINAL BED)
2 CN32 CN51 CN52 AC250V X06 X05 X04 S(SHIELD)
3 6.3A F X01 TO OUTDOOR UNIT
4 CN81 2 M2
5 F1 ZNR CN2M 1 M1 BC CONTROLLER
6
PEFY-P200·250VMH-A

7 M-NET REMOTE CONTROLLER


8 CN20 CN21 CN29 CN31 CN60 CN3T CNT CND CNP FAN3
21 21 21 21 654321 3 1 31 13 31 1357
T S.B
CR 52F CN1 1
Drain sensor ZNR1
DSA1 3
CN31
A.B 1 2 3 4 5 6 ✻
3 1 A 1 1 1
CN82 CN62
8
7 2 2 2
6 SW1 SW5
5 ✻ F2 51F 52F TB2 BREAKER
4 A connector is attached L1
EF0 12 901 901 to the drain lift up AC250V POWER SUPPLY
3 D 3 8 2 8 2 L2
2 C 4 mechanism, 5A F L3 3N~
1 B 7 3 7 3
A9 65 which is an optional part. ( 5A ) N 380/400/415V 50/60Hz
87 654 654

NOTE 1,2 PE
SW14 SW12 SW11
(Connection No.) (2nd digit) (1st digit)
DS 6 5 4 3 2 1LEV adapter board

2- 33
654321 654321

NOTE 1 654321 654321 (Blue)
(White) 3 2 1 89 6 54 89
100Pa
200Pa 3 2 1 6 5 4 89
LEV1 LEV2
PE
TO DUCT
TH21 TH22 TH23 DP MF
SYMBOL EXPLANATION 49F connector to alter the external static pressure on the fan
*NOTE 1
SYMBOL NAME SYMBOL NAME Colour/External Static Pressure
Blue/110Pa(at 380V),130Pa(at 400,415V)
MF Fan motor 51F Over current relay (fan motor) White/220Pa(at 380V),260Pa(at 400,415V)
I.B Indoor controller board TH21 Thermistor (inlet temp.detection)
A.B Address board TH22 Thermistor (piping temp.detection/liquid) CAUTION : 1.To protect Fan motor from abnormal current, Over current relays<51F>
TB2 Power source terminal bed TH23 Thermistor (piping temp.detection/gas) is installed. Therefore, do not change factory set value of Over
TB5 Transmission terminal bed SW11(A.B) Switch (1st digit address set)
TB15 Transmission terminal bed SW12(A.B) Switch (2nd digit address set) current relays.
F1 Fuse AC250V 6.3A F SW14(A.B) Switch (connection No.set) NOTE : 1.The part of the broken line indicates the circuit for optional parts.
<F2> Fuse AC250V 5A F SW1(A.B) Switch(for mode selection) 2. ✻A in the chart is the connector for a drain pump test run operation.
T Transformer SW2(I.B) Switch(for capacity code) (The Drain Pump operates continuously if the connector is inserted
<DP> Drain Pump SW3(I.B) Switch(for mode selection) and the power is supplied.)
LEV1,LEV2 Electronic linear expan. valve SW4(I.B) Switch(for model selection) After the test run, make sure to remove the ✻A connector.
<DS> Drain sensor SW5(A.B) Switch(for voltage selection) 3.The wirings to TB2,TB5 shown in dotted line are field work.
S.B Surge absorber board X04~X06 Aux.relay
52F Contactor (fan motor) 49F Inner thermostat
4.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.
inside < > is the optional parts

VML-A1/VMH-A
PEFY-P-
6. Options

Description Model Applicable capacity


PAC-KE32LAF-F P20/P25/P32
VML-A1/VMH-A

PAC-KE86LAF P40/P50/P63
PEFY-P-

Long life filter PAC-KE88LAF P71/P80


PAC-KE89LAF P100/P125/P140
PAC-KE85LAF P200/P250
PAC-KE63TB-F P40/P50/P63
PAC-KE80TB-F P71/P80
Filter box
PAC-KE140TB-F P100/P125/P140
PAC-KE250TB-F P200/P250

P40/P50/P63/P71/P80/P100
Drain water lift-up kit PAC-KE04DM-F
P125/P140/P200/P250

2- 34
Ceiling concealed PEFY-P-VMM-A

CONTENTS

PEFY-P-VMM-A
1. Specifications ································································· 2-36

2. Capacity Tables ······························································2-38


2-1 Cooling Capacity(PUMY) ················································2-38
2-2 Heating Capacity(PUMY) ················································2-40
2-3 Cooling Capacity(Y/R2-8·10·13HP) ······························· 2-41
2-4 Heating Capacity(Y/R2-8·10·13HP) ·······························2-43
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ······················ 2-44
2-6 Heating Capacity(Big Y, Super Y, Big R2) ·······················2-46
2-7 Cooling Capacity(WY, WR2) ········································· 2-47
2-8 Heating Capacity(WY, WR2) ········································· 2-48

3. Sound Levels ·······························································2-49


3-1 Sound levels(VMM-A) ···················································· 2-49
3-2 N/C curves(VMM-A) ······················································ 2-49
3-3 Fan characteristics curves(VMM-A) ······························· 2-56

4. External Dimensions ···················································· 2-58

5. Electrical Wiring Diagrams ··········································· 2-60

6. Options ··········································································· 2-62

2- 35
1. Specifications
PEFY-P20VMM-A PEFY-P25VMM-A PEFY-P32VMM-A PEFY-P40VMM-A
Power source ~220-240V 50Hz
❇1 kW 2.2 2.8 3.6 4.5
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0
Power consumption Cooling kW 0.15 0.17 0.19
(50Hz) Heating kW 0.15 0.17 0.19
Cooling A 0.73 0.81 0.92
Current
Heating A 0.73 0.81 0.92
External finish Galvanizing
Height mm 295
Dimension Width mm 815 935
Depth mm 700
Net weight kg 27 33
PEFY-P-VMM-A

Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1 Sirocco fan✕ 2
Airflow rate m3/min
Fan 6.0-7.2-8.5 7.5-9.0-10.5 10.0-12.0-14.0
(Lo-Mid-Hi)
External static pressure Pa 30/50/100
Type Single phase induction motor
Motor
Output kW 0.075
Air filter PP Honeycomb fabric (washable)
Gas mm ø 12.7
Refrigerant (Flare)
pipe dimension Liquid
mm ø 6.35
(Flare)
Drain pipe dimension R1 (External thread)
Noise level (Lo-Mid-Hi) ❇3 dB(A) 27-30-32 28-32-35 31-34-37

PEFY-P50VMM-A PEFY-P63VMM-A PEFY-P71VMM-A PEFY-P80VMM-A


Power source ~220-240V 50Hz
❇1 kW 5.6 7.1 8.0 9.0
Cooling capacity
❇2 kcal/h 5,000 6,300 7,100 8,000
Heating capacity ❇1 kW 6.3 8.0 9.0 10.0
Power consumption Cooling kW 0.20 0.22 0.25
(50Hz) Heating kW 0.20 0.22 0.25
Cooling A 0.98 1.07 1.15
Current
Heating A 0.98 1.07 1.15
External finish Galvanizing
Height mm 295
Dimension Width mm 935 1175
Depth mm 700
Net weight kg 33 42
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕2
Airflow rate
Fan m3/min 12.0-14.5-17.0 13.5-16.2-19.0 14.5-18.0-21.0
(Lo-Hi)
External static pressure Pa 30/50/100
Type Single phase induction motor
Motor
Output kW 0.075 0.078
Air filter PP Honeycomb fabric (washable)
Gas mm ø 15.88
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension R1 (External thread)
Noise level (Lo-Mid-Hi) ❇3 dB(A) 31-35-38 32-36-39
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 It is measured in anechoic room.

2- 36
PEFY-P100VMM-A PEFY-P125VMM-A PEFY-P140VMM-A
Power source ~220-240V 50Hz
❇1 kW 11.2 14.0 16.0
Cooling capacity
❇2 kcal/h 10,000 12,500 14,000
Heating capacity ❇1 kW 12.5 16.0 18.0
Power consumption Cooling kW 0.29 0.40 0.42
(50/60Hz) Heating kW 0.29 0.40 0.42
Cooling A 1.34 1.90 1.95
Current
Heating A 1.34 1.90 1.95
External finish Galvanizing
Height mm 325
Dimension Width mm 1415 1715
Depth mm 740
Net weight kg 62 65 70

PEFY-P-VMM-A
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕2
Airflow rate
Fan (Lo-Hi) m3/min 23.0-33.0 28.0-40.0 29.5-42.0
External static pressure Pa 50/130
Type Single phase induction motor
Motor
Output kW 0.200 0.280
Air filter PP Honeycomb fabric (washable)
Gas mm ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension R1 (External thread)
Noise level (Lo-Mid-Hi) ❇3 dB(A) 40-44 42-45 42-45
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 It is measured in anechoic room.

2- 37
2. Capacity Table
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9
22.5 2.1 1.8 2.3 1.9 2.4 1.9 2.6 1.9
25.0 2.1 1.8 2.3 1.9 2.4 1.8 2.5 1.9
27.5 2.1 1.8 2.2 1.9 2.4 1.8 2.5 1.9
20 30.0 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.9
(2.2) 32.5 2.0 1.7 2.2 1.8 2.3 1.8 2.5 1.9
35.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9
37.5 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9
PEFY-P-VMM-A

40.0 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.8


46.0 1.9 1.7 2.0 1.8 2.1 1.7 2.3 1.8
20.0 2.8 2.1 2.9 2.2 3.1 2.2 3.3 2.2
22.5 2.7 2.1 2.9 2.2 3.1 2.1 3.2 2.2
25.0 2.7 2.1 2.9 2.1 3.1 2.1 3.2 2.2
27.5 2.7 2.0 2.8 2.1 3.0 2.1 3.2 2.2
25 30.0 2.6 2.0 2.8 2.1 3.0 2.1 3.2 2.2
(2.8) 32.5 2.6 2.0 2.8 2.1 2.9 2.1 3.1 2.2
35.0 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.1
37.5 2.5 2.0 2.7 2.1 2.9 2.0 3.0 2.1
40.0 2.5 1.9 2.7 2.1 2.8 2.0 3.0 2.1
46.0 2.4 1.9 2.6 2.0 2.7 2.0 2.9 2.1
20.0 3.6 2.6 3.7 2.7 4.0 2.7 4.2 2.8
22.5 3.5 2.6 3.7 2.7 4.0 2.7 4.2 2.8
25.0 3.5 2.6 3.7 2.7 3.9 2.7 4.1 2.8
27.5 3.4 2.6 3.6 2.7 3.9 2.7 4.1 2.8
32 30.0 3.4 2.5 3.6 2.7 3.8 2.6 4.1 2.7
(3.6) 32.5 3.3 2.5 3.6 2.7 3.8 2.6 4.0 2.7
35.0 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.7
37.5 3.2 2.5 3.5 2.6 3.7 2.6 3.9 2.7
40.0 3.2 2.5 3.4 2.6 3.6 2.6 3.9 2.6
46.0 3.1 2.4 3.3 2.5 3.5 2.5 3.7 2.6
20.0 4.5 3.4 4.7 3.5 5.0 3.5 5.3 3.6
22.5 4.4 3.3 4.6 3.5 5.0 3.5 5.2 3.6
25.0 4.3 3.3 4.6 3.5 4.9 3.5 5.2 3.6
27.5 4.3 3.3 4.6 3.5 4.9 3.4 5.1 3.5
40 30.0 4.2 3.3 4.5 3.4 4.8 3.4 5.1 3.5
(4.5) 32.5 4.2 3.2 4.4 3.4 4.7 3.4 5.0 3.5
35.0 4.1 3.2 4.4 3.4 4.7 3.3 5.0 3.5
37.5 4.1 3.2 4.3 3.4 4.6 3.3 4.9 3.4
40.0 4.0 3.2 4.3 3.3 4.5 3.3 4.8 3.4
46.0 3.8 3.1 4.1 3.3 4.3 3.2 4.6 3.3
20.0 5.5 4.1 5.8 4.3 6.2 4.3 6.6 4.4
22.5 5.5 4.1 5.8 4.3 6.2 4.2 6.5 4.4
25.0 5.4 4.0 5.7 4.2 6.1 4.2 6.4 4.3
27.5 5.3 4.0 5.7 4.2 6.0 4.2 6.4 4.3
50 30.0 5.3 4.0 5.6 4.2 5.9 4.1 6.3 4.3
(5.6) 32.5 5.2 3.9 5.5 4.1 5.9 4.1 6.2 4.2
35.0 5.1 3.9 5.5 4.1 5.8 4.1 6.2 4.2
37.5 5.0 3.9 5.4 4.1 5.7 4.0 6.1 4.2
40.0 5.0 3.8 5.3 4.0 5.6 4.0 6.0 4.1
46.0 4.8 3.7 5.1 3.9 5.4 3.9 5.8 4.0
20.0 7.0 5.2 7.4 5.4 7.9 5.3 8.3 5.5
22.5 6.9 5.1 7.3 5.3 7.8 5.3 8.2 5.5
25.0 6.9 5.1 7.3 5.3 7.7 5.3 8.2 5.4
27.5 6.8 5.0 7.2 5.3 7.7 5.2 8.1 5.4
63 30.0 6.7 5.0 7.1 5.2 7.5 5.2 8.0 5.4
(7.1) 32.5 6.6 4.9 7.0 5.2 7.5 5.1 7.9 5.3
35.0 6.5 4.9 6.9 5.1 7.3 5.1 7.8 5.3
37.5 6.4 4.8 6.8 5.1 7.2 5.0 7.7 5.2
40.0 6.3 4.8 6.7 5.1 7.2 5.0 7.6 5.2
46.0 6.1 4.7 6.5 4.9 6.9 4.9 7.3 5.1

2- 38
Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 7.9 5.8 8.3 6.0 8.9 6.0 9.4 6.1
22.5 7.8 5.7 8.2 6.0 8.8 5.9 9.3 6.1
25.0 7.7 5.7 8.2 5.9 8.7 5.9 9.2 6.1
27.5 7.6 5.6 8.1 5.9 8.6 5.9 9.1 6.0
71 30.0 7.5 5.6 8.0 5.9 8.5 5.8 9.0 6.0
(8.0) 32.5 7.4 5.5 7.9 5.8 8.4 5.8 8.9 5.9
35.0 7.3 5.5 7.8 5.8 8.3 5.7 8.8 5.9
37.5 7.2 5.4 7.7 5.7 8.2 5.6 8.7 5.9

PEFY-P-VMM-A
40.0 7.1 5.4 7.6 5.7 8.1 5.6 8.6 5.8
46.0 6.8 5.2 7.3 5.5 7.7 5.4 8.2 5.7
20.0 8.9 6.3 9.4 6.5 10.0 6.5 10.6 6.7
22.5 8.8 6.2 9.3 6.5 9.9 6.5 10.4 6.6
25.0 8.7 6.2 9.2 6.5 9.8 6.4 10.4 6.6
27.5 8.6 6.1 9.1 6.4 9.7 6.4 10.3 6.5
80 30.0 8.5 6.1 9.0 6.4 9.5 6.3 10.2 6.5
(9.0) 32.5 8.3 6.0 8.9 6.3 9.5 6.2 10.0 6.4
35.0 8.2 5.9 8.8 6.2 9.3 6.2 9.9 6.4
37.5 8.1 5.9 8.6 6.2 9.2 6.1 9.8 6.3
40.0 8.0 5.8 8.6 6.1 9.1 6.1 9.6 6.3
46.0 7.7 5.7 8.2 6.0 8.7 5.9 9.3 6.1
20.0 11.1 8.5 11.6 8.9 12.5 8.8 13.1 9.1
22.5 10.9 8.4 11.5 8.8 12.3 8.8 13.0 9.0
25.0 10.8 8.4 11.5 8.8 12.2 8.7 12.9 9.0
27.5 10.7 8.3 11.3 8.7 12.1 8.7 12.8 8.9
100 30.0 10.5 8.2 11.2 8.7 11.9 8.6 12.6 8.9
(11.2) 32.5 10.4 8.2 11.1 8.6 11.8 8.5 12.5 8.8
35.0 10.2 8.1 10.9 8.5 11.6 8.4 12.3 8.8
37.5 10.1 8.0 10.8 8.5 11.4 8.4 12.2 8.7
40.0 10.0 8.0 10.6 8.4 11.3 8.3 12.0 8.6
46.0 9.6 7.8 10.2 8.2 10.8 8.1 11.5 8.4
20.0 13.9 10.4 14.6 10.9 15.6 10.8 16.4 11.1
22.5 13.7 10.3 14.4 10.8 15.4 10.7 16.2 11.1
25.0 13.5 10.3 14.3 10.8 15.3 10.7 16.1 11.0
27.5 13.4 10.2 14.2 10.7 15.1 10.6 16.0 10.9
125 30.0 13.2 10.1 14.0 10.6 14.9 10.5 15.8 10.9
(14.0) 32.5 13.0 10.0 13.8 10.5 14.7 10.4 15.6 10.8
35.0 12.8 9.9 13.7 10.4 14.5 10.3 15.4 10.7
37.5 12.6 9.8 13.4 10.3 14.3 10.2 15.2 10.6
40.0 12.5 9.8 13.3 10.3 14.1 10.2 15.0 10.5
46.0 12.0 9.5 12.8 10.0 13.5 9.9 14.4 10.3
20.0 15.8 11.6 16.6 12.1 17.8 12.0 18.8 12.3
22.5 15.6 11.5 16.5 12.0 17.6 11.9 18.6 12.3
25.0 15.5 11.4 16.4 11.9 17.4 11.9 18.4 12.2
27.5 15.3 11.3 16.2 11.9 17.2 11.8 18.2 12.1
140 30.0 15.0 11.2 16.0 11.8 17.0 11.6 18.0 12.0
(16.0) 32.5 14.8 11.1 15.8 11.7 16.8 11.6 17.9 12.0
35.0 14.6 11.0 15.6 11.6 16.5 11.4 17.6 11.8
37.5 14.4 10.9 15.4 11.4 16.3 11.3 17.4 11.8
40.0 14.2 10.8 15.2 11.4 16.1 11.3 17.2 11.6
46.0 13.7 10.5 14.6 11.1 15.4 11.0 16.5 11.4

2- 39
2-2.Heating Capacity (In combination with PUMY)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 5.7 5.6 5.5
-10.0 1.7 1.6 1.6 -10.0 6.0 5.9 5.8
-5.0 1.9 1.9 1.9 -5.0 6.9 6.8 6.7
0.0 2.2 2.1 2.1 0.0 7.8 7.7 7.6
20 2.5 2.3 2.3 2.3 71 2.5 8.3 8.2 8.1
6.0 2.5 2.5 2.5 6.0 9.1 9.0 8.9
7.5 2.6 2.6 2.5 7.5 9.4 9.3 8.9
10.0 2.8 2.7 2.5 10.0 9.9 9.9 8.9
12.5 2.9 2.8 2.5 12.5 10.5 9.9 8.9
PEFY-P-VMM-A

15.5 3.1 2.8 2.5 15.5 11.1 9.9 8.9


-12.0 2.0 2.0 2.0 -12.0 6.4 6.2 6.1
-10.0 2.1 2.1 2.1 -10.0 6.7 6.6 6.5
-5.0 2.4 2.4 2.4 -5.0 7.6 7.5 7.4
0.0 2.8 2.8 2.7 0.0 8.7 8.6 8.5
25 2.5 3.0 2.9 2.9 80 2.5 9.2 9.2 9.0
6.0 3.2 3.2 3.2 6.0 10.1 10.0 9.9
7.5 3.3 3.3 3.2 7.5 10.4 10.4 9.9
10.0 3.5 3.5 3.2 10.0 11.1 11.0 9.9
12.5 3.7 3.5 3.2 12.5 11.7 11.0 9.9
15.5 3.9 3.5 3.2 15.5 12.3 11.0 9.9
-12.0 2.5 2.5 2.5 -12.0 8.0 7.8 7.7
-10.0 2.7 2.6 2.6 -10.0 8.4 8.2 8.1
-5.0 3.1 3.0 3.0 -5.0 9.6 9.4 9.3
0.0 3.5 3.4 3.4 0.0 10.9 10.7 10.6
32 2.5 3.7 3.7 3.6 100 2.5 11.5 11.4 11.3
6.0 4.0 4.0 3.9 6.0 12.6 12.5 12.3
7.5 4.2 4.1 4.0 7.5 13.0 12.9 12.4
10.0 4.4 4.4 4.0 10.0 13.8 13.7 12.4
12.5 4.7 4.4 4.0 12.5 14.6 13.8 12.4
15.5 4.9 4.4 4.0 15.5 15.4 13.8 12.4
-12.0 3.2 3.1 3.1 -12.0 10.2 10.0 9.8
-10.0 3.4 3.3 3.2 -10.0 10.7 10.6 10.4
-5.0 3.8 3.8 3.7 -5.0 12.2 12.1 11.9
0.0 4.3 4.3 4.2 0.0 13.9 13.8 13.6
40 2.5 4.6 4.6 4.5 125 2.5 14.8 14.7 14.5
6.0 5.0 5.0 4.9 6.0 16.1 16.0 15.8
7.5 5.2 5.2 5.0 7.5 16.7 16.6 15.8
10.0 5.5 5.5 5.0 10.0 17.7 17.6 15.8
12.5 5.9 5.5 5.0 12.5 18.7 17.7 15.8
15.5 6.2 5.5 5.0 15.5 19.7 17.7 15.8
-12.0 4.0 3.9 3.9 -12.0 11.5 11.2 11.0
-10.0 4.2 4.2 4.1 -10.0 12.1 11.9 11.7
-5.0 4.8 4.8 4.7 -5.0 13.8 13.6 13.4
0.0 5.5 5.4 5.3 0.0 15.6 15.5 15.3
50 2.5 5.8 5.8 5.7 140 2.5 16.6 16.5 16.3
6.0 6.3 6.3 6.2 6.0 18.1 18.0 17.8
7.5 6.6 6.5 6.2 7.5 18.8 18.6 17.8
10.0 7.0 6.9 6.2 10.0 19.9 19.8 17.8
12.5 7.4 7.0 6.2 12.5 21.1 19.9 17.8
15.5 7.7 7.0 6.2 15.5 22.1 19.9 17.8
-12.0 5.1 5.0 4.9
-10.0 5.4 5.3 5.2
-5.0 6.1 6.0 5.9
0.0 6.9 6.9 6.8
63 2.5 7.4 7.3 7.2
6.0 8.0 8.0 7.9
7.5 8.3 8.3 7.9
10.0 8.8 8.8 7.9
12.5 9.4 8.8 7.9
15.5 9.8 8.8 7.9

2- 40
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8
22.5 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.4 1.8 2.5 1.8
25.0 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.8 2.3 1.9 2.4 1.8 2.5 1.8
27.5 2.1 1.8 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.9 2.4 1.8 2.5 1.8
20 30.0 2.1 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.5 1.8
(2.2) 32.5 2.0 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.4 1.8
35.0 2.0 1.7 2.1 1.8 2.2 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8
37.5 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8

PEFY-P-VMM-A
40.0 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8
43.0 2.0 1.7 2.0 1.8 2.1 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.7
20.0 2.7 2.1 2.8 2.1 2.9 2.1 3.0 2.1 3.0 2.2 3.1 2.1 3.2 2.0
22.5 2.7 2.1 2.8 2.1 2.9 2.1 2.9 2.1 3.0 2.1 3.1 2.1 3.2 2.0
25.0 2.7 2.0 2.7 2.1 2.9 2.0 2.9 2.1 3.0 2.1 3.1 2.1 3.2 2.0
27.5 2.7 2.0 2.7 2.1 2.8 2.0 2.9 2.1 2.9 2.1 3.1 2.1 3.2 2.0
25 30.0 2.6 2.0 2.7 2.1 2.8 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.1 2.0
(2.8) 32.5 2.6 2.0 2.7 2.1 2.8 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.1 2.0
35.0 2.6 2.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.1 2.0
37.5 2.5 2.0 2.6 2.0 2.7 2.0 2.8 2.0 2.8 2.1 2.9 2.0 3.1 2.0
40.0 2.5 2.0 2.6 2.0 2.7 2.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.0
43.0 2.5 1.9 2.5 2.0 2.7 2.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.0
20.0 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.6 3.9 2.7 4.0 2.6 4.2 2.6
22.5 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.6 3.9 2.7 4.0 2.6 4.1 2.6
25.0 3.5 2.6 3.5 2.6 3.7 2.6 3.7 2.6 3.8 2.7 4.0 2.6 4.1 2.5
27.5 3.4 2.6 3.5 2.6 3.6 2.6 3.7 2.6 3.8 2.7 3.9 2.6 4.1 2.5
32 30.0 3.4 2.5 3.5 2.6 3.6 2.5 3.7 2.6 3.7 2.7 3.9 2.6 4.0 2.5
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.0 2.5
35.0 3.3 2.5 3.4 2.6 3.5 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.0 2.5
37.5 3.3 2.5 3.3 2.6 3.5 2.5 3.6 2.5 3.6 2.6 3.8 2.5 3.9 2.5
40.0 3.2 2.5 3.3 2.5 3.5 2.5 3.5 2.5 3.6 2.6 3.7 2.5 3.9 2.5
43.0 3.2 2.5 3.3 2.5 3.4 2.5 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5
20.0 4.4 3.4 4.5 3.4 4.7 3.4 4.8 3.4 4.9 3.5 5.0 3.4 5.2 3.3
22.5 4.4 3.3 4.5 3.4 4.6 3.3 4.7 3.4 4.8 3.5 5.0 3.4 5.2 3.3
25.0 4.3 3.3 4.4 3.4 4.6 3.3 4.7 3.4 4.8 3.5 5.0 3.4 5.1 3.3
27.5 4.3 3.3 4.4 3.4 4.5 3.3 4.6 3.3 4.7 3.4 4.9 3.4 5.1 3.3
40 30.0 4.2 3.3 4.3 3.4 4.5 3.3 4.6 3.3 4.7 3.4 4.9 3.3 5.0 3.3
(4.5) 32.5 4.2 3.2 4.3 3.3 4.5 3.3 4.5 3.3 4.6 3.4 4.8 3.3 5.0 3.2
35.0 4.1 3.2 4.2 3.3 4.4 3.2 4.5 3.3 4.6 3.4 4.8 3.3 5.0 3.2
37.5 4.1 3.2 4.2 3.3 4.4 3.2 4.5 3.3 4.5 3.4 4.7 3.3 4.9 3.2
40.0 4.1 3.2 4.1 3.3 4.3 3.2 4.4 3.2 4.5 3.4 4.7 3.3 4.9 3.2
43.0 4.0 3.2 4.1 3.2 4.3 3.2 4.4 3.2 4.4 3.3 4.6 3.3 4.8 3.2
20.0 5.5 4.1 5.6 4.2 5.8 4.1 5.9 4.1 6.0 4.2 6.3 4.1 6.5 4.0
22.5 5.4 4.1 5.5 4.1 5.8 4.1 5.9 4.1 6.0 4.2 6.2 4.1 6.4 4.0
25.0 5.4 4.0 5.5 4.1 5.7 4.0 5.8 4.1 5.9 4.2 6.2 4.1 6.4 4.0
27.5 5.3 4.0 5.4 4.1 5.7 4.0 5.8 4.0 5.9 4.2 6.1 4.1 6.3 4.0
50 30.0 5.3 4.0 5.4 4.1 5.6 4.0 5.7 4.0 5.8 4.1 6.0 4.0 6.3 3.9
(5.6) 32.5 5.2 3.9 5.3 4.0 5.5 4.0 5.7 4.0 5.8 4.1 6.0 4.0 6.2 3.9
35.0 5.2 3.9 5.3 4.0 5.5 3.9 5.6 4.0 5.7 4.1 5.9 4.0 6.2 3.9
37.5 5.1 3.9 5.2 4.0 5.4 3.9 5.5 3.9 5.7 4.1 5.9 4.0 6.1 3.9
40.0 5.0 3.9 5.2 4.0 5.4 3.9 5.5 3.9 5.6 4.1 5.8 4.0 6.0 3.9
43.0 5.0 3.8 5.1 3.9 5.3 3.9 5.4 3.9 5.5 4.0 5.8 3.9 6.0 3.8
20.0 7.0 5.1 7.1 5.2 7.4 5.1 7.5 5.1 7.7 5.3 8.0 5.2 8.2 5.0
22.5 6.9 5.1 7.0 5.2 7.3 5.1 7.5 5.1 7.6 5.3 7.9 5.1 8.2 5.0
25.0 6.8 5.0 7.0 5.2 7.2 5.0 7.4 5.1 7.5 5.2 7.8 5.1 8.1 5.0
27.5 6.7 5.0 6.9 5.1 7.2 5.0 7.3 5.1 7.5 5.2 7.7 5.1 8.0 4.9
63 30.0 6.7 5.0 6.8 5.1 7.1 5.0 7.2 5.0 7.4 5.2 7.7 5.1 8.0 4.9
(7.1) 32.5 6.6 4.9 6.7 5.1 7.0 5.0 7.2 5.0 7.3 5.2 7.6 5.0 7.9 4.9
35.0 6.5 4.9 6.7 5.0 7.0 4.9 7.1 5.0 7.2 5.1 7.5 5.0 7.8 4.9
37.5 6.5 4.9 6.6 5.0 6.9 4.9 7.0 4.9 7.2 5.1 7.5 5.0 7.7 4.8
40.0 6.4 4.8 6.5 5.0 6.8 4.9 7.0 4.9 7.1 5.1 7.4 4.9 7.7 4.8
43.0 6.3 4.8 6.4 4.9 6.7 4.8 6.9 4.9 7.0 5.0 7.3 4.9 7.6 4.8

2- 41
Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 7.8 5.7 8.0 5.9 8.3 5.7 8.5 5.8 8.6 5.9 9.0 5.8 9.3 5.6
22.5 7.8 5.7 7.9 5.8 8.2 5.7 8.4 5.7 8.6 5.9 8.9 5.7 9.2 5.6
25.0 7.7 5.7 7.8 5.8 8.2 5.6 8.3 5.7 8.5 5.9 8.8 5.7 9.1 5.6
27.5 7.6 5.6 7.8 5.7 8.1 5.6 8.2 5.7 8.4 5.8 8.7 5.7 9.0 5.5
71 30.0 7.5 5.6 7.7 5.7 8.0 5.6 8.2 5.6 8.3 5.8 8.6 5.7 9.0 5.5
(8.0) 32.5 7.4 5.5 7.6 5.7 7.9 5.5 8.1 5.6 8.2 5.8 8.6 5.6 8.9 5.5
35.0 7.4 5.5 7.5 5.6 7.8 5.5 8.0 5.6 8.2 5.7 8.5 5.6 8.8 5.4
37.5 7.3 5.5 7.4 5.6 7.8 5.5 7.9 5.5 8.1 5.7 8.4 5.6 8.7 5.4
PEFY-P-VMM-A

40.0 7.2 5.4 7.4 5.5 7.7 5.4 7.8 5.5 8.0 5.7 8.3 5.5 8.6 5.4
43.0 7.1 5.4 7.3 5.5 7.6 5.4 7.7 5.4 7.9 5.6 8.2 5.5 8.5 5.3
20.0 8.8 6.2 9.0 6.4 9.4 6.2 9.5 6.2 9.7 6.4 10.1 6.2 10.4 6.0
22.5 8.7 6.2 8.9 6.3 9.3 6.2 9.5 6.2 9.6 6.4 10.0 6.2 10.4 6.0
25.0 8.6 6.1 8.8 6.3 9.2 6.1 9.4 6.1 9.5 6.3 9.9 6.1 10.3 6.0
27.5 8.6 6.1 8.7 6.2 9.1 6.1 9.3 6.1 9.5 6.3 9.8 6.1 10.2 5.9
80 30.0 8.5 6.1 8.6 6.2 9.0 6.0 9.2 6.1 9.4 6.2 9.7 6.1 10.1 5.9
(9.0) 32.5 8.4 6.0 8.6 6.1 8.9 6.0 9.1 6.0 9.3 6.2 9.6 6.0 10.0 5.9
35.0 8.3 6.0 8.5 6.1 8.8 5.9 9.0 6.0 9.2 6.2 9.5 6.0 9.9 5.8
37.5 8.2 5.9 8.4 6.0 8.7 5.9 8.9 5.9 9.1 6.1 9.5 6.0 9.8 5.8
40.0 8.1 5.9 8.3 6.0 8.6 5.9 8.8 5.9 9.0 6.1 9.4 5.9 9.7 5.8
43.0 8.0 5.8 8.2 5.9 8.5 5.8 8.7 5.9 8.9 6.0 9.3 5.9 9.6 5.7
20.0 11.0 8.5 11.2 8.7 11.6 8.5 11.9 8.6 12.1 8.9 12.5 8.6 13.0 8.4
22.5 10.9 8.4 11.1 8.6 11.5 8.4 11.8 8.5 12.0 8.8 12.4 8.6 12.9 8.4
25.0 10.8 8.3 11.0 8.6 11.4 8.4 11.6 8.5 11.9 8.8 12.3 8.5 12.8 8.3
27.5 10.6 8.3 10.9 8.5 11.3 8.3 11.5 8.4 11.8 8.7 12.2 8.5 12.7 8.3
100 30.0 10.5 8.2 10.8 8.5 11.2 8.3 11.4 8.4 11.6 8.7 12.1 8.5 12.5 8.2
(11.2) 32.5 10.4 8.2 10.6 8.4 11.1 8.2 11.3 8.3 11.5 8.6 12.0 8.4 12.4 8.2
35.0 10.3 8.1 10.5 8.4 11.0 8.2 11.2 8.3 11.4 8.6 11.9 8.4 12.3 8.2
37.5 10.2 8.1 10.4 8.3 10.9 8.1 11.1 8.2 11.3 8.5 11.8 8.3 12.2 8.1
40.0 10.1 8.0 10.3 8.2 10.8 8.1 11.0 8.2 11.2 8.5 11.6 8.3 12.1 8.1
43.0 9.9 8.0 10.2 8.2 10.6 8.0 10.8 8.2 11.1 8.4 11.5 8.3 12.0 8.1
20.0 13.7 10.4 14.0 10.6 14.6 10.4 14.8 10.5 15.1 10.8 15.7 10.5 16.2 10.2
22.5 13.6 10.3 13.9 10.5 14.4 10.3 14.7 10.4 15.0 10.7 15.5 10.5 16.1 10.2
25.0 13.4 10.2 13.7 10.5 14.3 10.2 14.6 10.3 14.8 10.7 15.4 10.4 16.0 10.1
27.5 13.3 10.2 13.6 10.4 14.1 10.2 14.4 10.3 14.7 10.6 15.3 10.4 15.8 10.1
125 30.0 13.2 10.1 13.4 10.3 14.0 10.1 14.3 10.2 14.6 10.6 15.1 10.3 15.7 10.0
(14.0) 32.5 13.0 10.0 13.3 10.3 13.9 10.1 14.1 10.2 14.4 10.5 15.0 10.3 15.5 10.0
35.0 12.9 10.0 13.2 10.2 13.7 10.0 14.0 10.1 14.3 10.5 14.8 10.2 15.4 9.9
37.5 12.7 9.9 13.0 10.1 13.6 9.9 13.9 10.1 14.1 10.4 14.7 10.2 15.3 9.9
40.0 12.6 9.8 12.9 10.1 13.4 9.9 13.7 10.0 14.0 10.3 14.6 10.1 15.1 9.9
43.0 12.4 9.7 12.7 10.0 13.3 9.8 13.6 9.9 13.8 10.3 14.4 10.0 15.0 9.8
20.0 15.7 11.5 16.0 11.8 16.6 11.5 17.0 11.6 17.3 11.9 17.9 11.6 18.6 11.3
22.5 15.5 11.4 15.8 11.7 16.5 11.4 16.8 11.5 17.1 11.9 17.8 11.5 18.4 11.2
25.0 15.4 11.4 15.7 11.6 16.3 11.3 16.6 11.4 17.0 11.8 17.6 11.5 18.2 11.2
27.5 15.2 11.3 15.5 11.5 16.2 11.3 16.5 11.4 16.8 11.7 17.4 11.4 18.1 11.1
140 30.0 15.0 11.2 15.4 11.4 16.0 11.2 16.3 11.3 16.6 11.7 17.3 11.4 17.9 11.0
(16.0) 32.5 14.9 11.1 15.2 11.4 15.8 11.1 16.2 11.2 16.5 11.6 17.1 11.3 17.8 11.0
35.0 14.7 11.0 15.0 11.3 15.7 11.1 16.0 11.2 16.3 11.5 17.0 11.2 17.6 10.9
37.5 14.6 11.0 14.9 11.2 15.5 11.0 15.8 11.1 16.2 11.5 16.8 11.2 17.4 10.9
40.0 14.4 10.9 14.7 11.1 15.4 10.9 15.7 11.0 16.0 11.4 16.6 11.1 17.3 10.8
43.0 14.2 10.8 14.5 11.1 15.2 10.8 15.5 10.9 15.8 11.3 16.4 11.0 17.1 10.8

2- 42
2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 6.0 5.9 5.9 5.9
-10.0 1.9 1.9 1.9 1.7 -10.0 6.9 6.8 6.7 6.2
-5.0 2.1 2.1 2.0 1.7 -5.0 7.7 7.6 7.0 6.2
0.0 2.4 2.4 2.0 1.7 0.0 8.6 8.5 7.0 6.2
20 2.5 2.5 2.5 2.0 1.7 71 2.5 9.0 8.9 7.0 6.2
6.0 2.5 2.5 2.0 1.7 6.0 9.1 9.0 7.0 6.2
7.5 2.6 2.5 2.0 1.7 7.5 9.5 9.0 7.0 6.2
10.0 2.8 2.5 2.0 1.7 10.0 10.1 9.0 7.0 6.2
12.5 3.0 2.5 2.0 1.7 12.5 10.8 9.0 7.0 6.2

PEFY-P-VMM-A
15.5 3.0 2.5 2.0 1.7 15.5 10.9 9.0 7.0 6.2
-15.0 2.1 2.1 2.1 2.1 -15.0 6.7 6.6 6.5 6.5
-10.0 2.4 2.4 2.4 2.2 -10.0 7.6 7.5 7.4 6.9
-5.0 2.7 2.7 2.5 2.2 -5.0 8.6 8.5 7.8 6.9
0.0 3.1 3.0 2.5 2.2 0.0 9.5 9.4 7.8 6.9
25 2.5 3.2 3.2 2.5 2.2 80 2.5 10.0 9.9 7.8 6.9
6.0 3.2 3.2 2.5 2.2 6.0 10.1 10.0 7.8 6.9
7.5 3.4 3.2 2.5 2.2 7.5 10.5 10.0 7.8 6.9
10.0 3.6 3.2 2.5 2.2 10.0 11.2 10.0 7.8 6.9
12.5 3.8 3.2 2.5 2.2 12.5 12.0 10.0 7.8 6.9
15.5 3.9 3.2 2.5 2.2 15.5 12.1 10.0 7.8 6.9
-15.0 2.7 2.6 2.6 2.6 -15.0 8.4 8.2 8.2 8.1
-10.0 3.1 3.0 3.0 2.8 -10.0 9.6 9.4 9.3 8.6
-5.0 3.4 3.4 3.1 2.8 -5.0 10.7 10.6 9.8 8.6
0.0 3.8 3.8 3.1 2.8 0.0 11.9 11.8 9.8 8.6
32 2.5 4.0 4.0 3.1 2.8 100 2.5 12.5 12.4 9.8 8.6
6.0 4.0 4.0 3.1 2.8 6.0 12.6 12.5 9.8 8.6
7.5 4.2 4.0 3.1 2.8 7.5 13.2 12.5 9.8 8.6
10.0 4.5 4.0 3.1 2.8 10.0 14.1 12.5 9.8 8.6
12.5 4.8 4.0 3.1 2.8 12.5 15.0 12.5 9.8 8.6
15.5 4.8 4.0 3.1 2.8 15.5 15.1 12.5 9.8 8.6
-15.0 3.3 3.3 3.3 3.3 -15.0 10.7 10.6 10.5 10.4
-10.0 3.8 3.8 3.7 3.5 -10.0 12.2 12.1 11.9 11.0
-5.0 4.3 4.2 3.9 3.5 -5.0 13.7 13.6 12.5 11.0
0.0 4.8 4.7 3.9 3.5 0.0 15.3 15.1 12.5 11.0
40 2.5 5.0 5.0 3.9 3.5 125 2.5 16.0 15.8 12.5 11.0
6.0 5.1 5.0 3.9 3.5 6.0 16.2 16.0 12.5 11.0
7.5 5.3 5.0 3.9 3.5 7.5 16.8 16.0 12.5 11.0
10.0 5.6 5.0 3.9 3.5 10.0 18.0 16.0 12.5 11.0
12.5 6.0 5.0 3.9 3.5 12.5 19.1 16.0 12.5 11.0
15.5 6.1 5.0 3.9 3.5 15.5 19.4 16.0 12.5 11.0
-15.0 4.2 4.2 4.1 4.1 -15.0 12.1 11.9 11.8 11.7
-10.0 4.8 4.8 4.7 4.3 -10.0 13.8 13.6 13.4 12.4
-5.0 5.4 5.3 4.9 4.3 -5.0 15.5 15.3 14.0 12.4
0.0 6.0 5.9 4.9 4.3 0.0 17.2 17.0 14.0 12.4
50 2.5 6.3 6.2 4.9 4.3 140 2.5 18.0 17.8 14.0 12.4
6.0 6.4 6.3 4.9 4.3 6.0 18.2 18.0 14.0 12.4
7.5 6.6 6.3 4.9 4.3 7.5 19.0 18.0 14.0 12.4
10.0 7.1 6.3 4.9 4.3 10.0 20.2 18.0 14.0 12.4
12.5 7.5 6.3 4.9 4.3 12.5 21.5 18.0 14.0 12.4
15.5 7.6 6.3 4.9 4.3 15.5 21.8 18.0 14.0 12.4
-15.0 5.4 5.3 5.2 5.2
-10.0 6.1 6.0 6.0 5.5
-5.0 6.9 6.8 6.2 5.5
0.0 7.6 7.5 6.2 5.5
63 2.5 8.0 7.9 6.2 5.5
6.0 8.1 8.0 6.2 5.5
7.5 8.4 8.0 6.2 5.5
10.0 9.0 8.0 6.2 5.5
12.5 9.6 8.0 6.2 5.5
15.5 9.7 8.0 6.2 5.5

2- 43
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.9 2.7 1.9
22.5 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9 2.5 1.9 2.7 1.8
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9 2.5 1.9 2.6 1.8
20 30.0 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.5 1.9 2.6 1.8
32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.6 1.8
35.0 1.9 1.7 2.0 1.8 2.1 1.7 2.3 1.9 2.4 1.8 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.8
40.0 1.9 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8
PEFY-P-VMM-A

20.0 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.2 3.3 2.2 3.5 2.1
22.5 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.2 3.3 2.1 3.4 2.1
25.0 2.6 2.0 2.7 2.1 2.9 2.0 3.0 2.2 3.2 2.1 3.4 2.1
27.5 2.5 2.0 2.6 2.0 2.8 2.0 3.0 2.1 3.2 2.1 3.3 2.1
25 30.0 2.5 2.0 2.6 2.0 2.8 2.0 3.0 2.1 3.1 2.1 3.3 2.1
32.5 2.5 2.0 2.6 2.0 2.8 2.0 2.9 2.1 3.1 2.1 3.2 2.0
35.0 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.1 3.0 2.1 3.2 2.0
37.5 2.5 1.9 2.5 2.0 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.0
40.0 2.4 1.9 2.5 2.0 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.0
43.0 2.4 1.9 2.5 2.0 2.6 1.9 2.8 2.1 2.9 2.0 3.0 2.0
20.0 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.8 4.2 2.7 4.5 2.7
22.5 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.7 4.2 2.7 4.4 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.9 2.7 4.1 2.7 4.4 2.6
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.9 2.7 4.1 2.7 4.3 2.6
32 30.0 3.2 2.5 3.4 2.6 3.6 2.5 3.8 2.7 4.0 2.6 4.2 2.6
32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.6 3.9 2.6 4.1 2.5
37.5 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.6 3.8 2.6 4.0 2.5
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.6 2.6 3.8 2.6 4.0 2.5
43.0 3.1 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.7 2.5 3.9 2.5
20.0 4.1 3.2 4.3 3.4 4.7 3.4 5.0 3.6 5.3 3.5 5.6 3.5
22.5 4.1 3.2 4.3 3.4 4.6 3.3 4.9 3.5 5.2 3.5 5.5 3.4
25.0 4.1 3.2 4.3 3.3 4.6 3.3 4.9 3.5 5.2 3.5 5.5 3.4
27.5 4.1 3.2 4.2 3.3 4.5 3.3 4.8 3.5 5.1 3.4 5.4 3.4
40 30.0 4.0 3.2 4.2 3.3 4.5 3.3 4.8 3.5 5.0 3.4 5.3 3.3
32.5 4.0 3.2 4.2 3.3 4.4 3.3 4.7 3.4 5.0 3.4 5.2 3.3
35.0 4.0 3.1 4.1 3.3 4.4 3.2 4.6 3.4 4.9 3.4 5.1 3.3
37.5 3.9 3.1 4.1 3.2 4.3 3.2 4.6 3.4 4.8 3.3 5.1 3.3
40.0 3.9 3.1 4.0 3.2 4.3 3.2 4.5 3.4 4.7 3.3 5.0 3.2
43.0 3.9 3.1 4.0 3.2 4.2 3.2 4.4 3.3 4.7 3.3 4.9 3.2
20.0 5.2 3.9 5.4 4.1 5.8 4.1 6.2 4.3 6.6 4.3 7.0 4.2
22.5 5.2 3.9 5.4 4.1 5.8 4.1 6.2 4.3 6.5 4.2 6.9 4.2
25.0 5.1 3.9 5.3 4.0 5.7 4.0 6.1 4.3 6.4 4.2 6.8 4.1
27.5 5.1 3.9 5.3 4.0 5.6 4.0 6.0 4.2 6.3 4.2 6.7 4.1
50 30.0 5.0 3.9 5.2 4.0 5.6 4.0 5.9 4.2 6.2 4.1 6.6 4.1
32.5 5.0 3.8 5.2 4.0 5.5 3.9 5.8 4.2 6.2 4.1 6.5 4.0
35.0 4.9 3.8 5.1 3.9 5.4 3.9 5.8 4.1 6.1 4.1 6.4 4.0
37.5 4.9 3.8 5.1 3.9 5.4 3.9 5.7 4.1 6.0 4.0 6.3 3.9
40.0 4.9 3.8 5.0 3.9 5.3 3.9 5.6 4.1 5.9 4.0 6.2 3.9
43.0 4.8 3.8 5.0 3.9 5.2 3.8 5.5 4.0 5.8 4.0 6.1 3.9
20.0 6.5 4.9 6.9 5.1 7.4 5.1 7.9 5.4 8.4 5.3 8.9 5.2
22.5 6.5 4.9 6.8 5.1 7.3 5.1 7.8 5.4 8.3 5.3 8.7 5.2
25.0 6.5 4.9 6.8 5.1 7.2 5.0 7.7 5.3 8.1 5.2 8.6 5.2
27.5 6.4 4.9 6.7 5.0 7.2 5.0 7.6 5.3 8.0 5.2 8.5 5.1
63 30.0 6.4 4.8 6.6 5.0 7.1 5.0 7.5 5.2 7.9 5.2 8.4 5.1
32.5 6.3 4.8 6.6 5.0 7.0 4.9 7.4 5.2 7.8 5.1 8.2 5.0
35.0 6.3 4.8 6.5 4.9 6.9 4.9 7.3 5.2 7.7 5.1 8.1 5.0
37.5 6.2 4.8 6.4 4.9 6.8 4.9 7.2 5.1 7.6 5.0 8.0 4.9
40.0 6.2 4.7 6.4 4.9 6.7 4.8 7.1 5.1 7.5 5.0 7.9 4.9
43.0 6.1 4.7 6.3 4.8 6.6 4.8 7.0 5.0 7.3 4.9 7.7 4.8

2- 44
Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Outdoor
air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 7.4 5.5 7.7 5.7 8.3 5.7 8.9 6.0 9.4 6.0 10.0 5.9
22.5 7.4 5.5 7.7 5.7 8.2 5.7 8.8 6.0 9.3 5.9 9.8 5.8
25.0 7.3 5.5 7.6 5.7 8.2 5.6 8.7 6.0 9.2 5.9 9.7 5.8
27.5 7.2 5.4 7.5 5.6 8.1 5.6 8.6 5.9 9.0 5.8 9.6 5.7
71 30.0 7.2 5.4 7.5 5.6 8.0 5.6 8.5 5.9 8.9 5.8 9.4 5.7
32.5 7.1 5.4 7.4 5.6 7.9 5.5 8.3 5.8 8.8 5.7 9.3 5.6
35.0 7.1 5.4 7.3 5.5 7.8 5.5 8.2 5.8 8.7 5.7 9.1 5.6
37.5 7.0 5.3 7.2 5.5 7.7 5.4 8.1 5.7 8.6 5.6 9.0 5.5
40.0 7.0 5.3 7.2 5.5 7.6 5.4 8.0 5.7 8.4 5.6 8.9 5.5
43.0 6.9 5.3 7.1 5.4 7.5 5.3 7.9 5.6 8.3 5.5 8.7 5.4

PEFY-P-VMM-A
20.0 8.3 6.0 8.7 6.2 9.4 6.2 10.0 6.5 10.6 6.4 11.2 6.3
22.5 8.3 6.0 8.7 6.2 9.3 6.2 9.9 6.5 10.5 6.4 11.1 6.3
25.0 8.2 5.9 8.6 6.1 9.2 6.1 9.8 6.4 10.3 6.3 10.9 6.2
27.5 8.1 5.9 8.5 6.1 9.1 6.1 9.6 6.4 10.2 6.3 10.8 6.1
80 30.0 8.1 5.9 8.4 6.1 9.0 6.0 9.5 6.3 10.0 6.2 10.6 6.1
32.5 8.0 5.8 8.3 6.0 8.9 6.0 9.4 6.3 9.9 6.1 10.4 6.0
35.0 8.0 5.8 8.2 6.0 8.8 5.9 9.3 6.2 9.8 6.1 10.3 6.0
37.5 7.9 5.8 8.1 5.9 8.6 5.9 9.1 6.1 9.6 6.0 10.1 5.9
40.0 7.8 5.7 8.1 5.9 8.5 5.8 9.0 6.1 9.5 6.0 10.0 5.9
43.0 7.7 5.7 8.0 5.8 8.4 5.8 8.9 6.0 9.3 5.9 9.8 5.8
20.0 10.3 8.1 10.8 8.5 11.6 8.5 12.5 9.0 13.2 8.9 14.0 8.7
22.5 10.3 8.1 10.8 8.5 11.5 8.4 12.3 8.9 13.0 8.8 13.8 8.7
25.0 10.2 8.1 10.7 8.4 11.4 8.4 12.1 8.9 12.8 8.7 13.6 8.6
27.5 10.1 8.1 10.6 8.4 11.3 8.3 12.0 8.8 12.7 8.7 13.4 8.5
100 30.0 10.1 8.0 10.5 8.3 11.2 8.3 11.8 8.8 12.5 8.6 13.2 8.5
32.5 10.0 8.0 10.3 8.3 11.0 8.2 11.7 8.7 12.3 8.6 13.0 8.4
35.0 9.9 7.9 10.2 8.2 10.9 8.2 11.5 8.6 12.1 8.5 12.8 8.3
37.5 9.8 7.9 10.1 8.2 10.8 8.1 11.4 8.6 12.0 8.4 12.6 8.3
40.0 9.7 7.9 10.0 8.1 10.6 8.0 11.2 8.5 11.8 8.4 12.4 8.2
43.0 9.6 7.8 9.9 8.1 10.5 8.0 11.0 8.4 11.6 8.3 12.2 8.1
20.0 12.9 10.0 13.5 10.4 14.6 10.4 15.6 11.0 16.5 10.8 17.5 10.7
22.5 12.9 10.0 13.5 10.4 14.4 10.3 15.4 10.9 16.3 10.8 17.2 10.6
25.0 12.8 9.9 13.3 10.3 14.3 10.2 15.2 10.8 16.1 10.7 17.0 10.5
27.5 12.7 9.9 13.2 10.2 14.1 10.2 15.0 10.8 15.8 10.6 16.7 10.4
125 30.0 12.6 9.8 13.1 10.2 13.9 10.1 14.8 10.7 15.6 10.5 16.5 10.3
32.5 12.5 9.8 12.9 10.1 13.8 10.0 14.6 10.6 15.4 10.4 16.2 10.2
35.0 12.4 9.7 12.8 10.0 13.6 10.0 14.4 10.5 15.2 10.3 16.0 10.2
37.5 12.3 9.7 12.7 10.0 13.5 9.9 14.2 10.4 15.0 10.3 15.7 10.1
40.0 12.2 9.6 12.5 9.9 13.3 9.8 14.0 10.4 14.8 10.2 15.5 10.0
43.0 12.0 9.6 12.4 9.9 13.1 9.7 13.8 10.3 14.5 10.1 15.2 9.9
20.0 14.7 11.0 15.4 11.5 16.6 11.5 17.8 12.1 18.8 12.0 20.0 11.8
22.5 14.7 11.0 15.4 11.5 16.5 11.4 17.6 12.1 18.6 11.9 19.7 11.7
25.0 14.6 11.0 15.2 11.4 16.3 11.3 17.4 12.0 18.3 11.8 19.4 11.6
27.5 14.5 10.9 15.1 11.3 16.1 11.3 17.1 11.9 18.1 11.7 19.1 11.5
140 30.0 14.4 10.9 14.9 11.2 15.9 11.2 16.9 11.8 17.8 11.6 18.8 11.4
32.5 14.3 10.8 14.8 11.2 15.7 11.1 16.7 11.7 17.6 11.5 18.6 11.3
35.0 14.1 10.8 14.6 11.1 15.6 11.0 16.5 11.6 17.4 11.4 18.3 11.2
37.5 14.0 10.7 14.5 11.0 15.4 10.9 16.2 11.5 17.1 11.3 18.0 11.1
40.0 13.9 10.6 14.3 11.0 15.2 10.8 16.0 11.4 16.9 11.2 17.7 11.0
43.0 13.8 10.6 14.2 10.9 15.0 10.7 15.8 11.3 16.6 11.1 17.4 10.9

2- 45
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 5.6 5.5 5.4 5.3
-10.0 1.8 1.8 1.7 1.7 -10.0 6.4 6.3 6.2 6.1
-5.0 2.0 2.0 2.0 1.9 -5.0 7.2 7.1 7.0 6.9
0.0 2.2 2.2 2.1 1.9 0.0 8.0 8.0 7.7 6.9
20 2.5 2.4 2.3 2.1 1.9 71 2.5 8.5 8.4 7.7 6.9
6.0 2.5 2.5 2.1 1.9 6.0 9.1 9.0 7.7 6.9
7.5 2.6 2.5 2.1 1.9 7.5 9.4 9.0 7.7 6.9
10.0 2.7 2.5 2.1 1.9 10.0 9.8 9.0 7.7 6.9
12.5 2.9 2.5 2.1 1.9 12.5 10.3 9.0 7.7 6.9
15.5 2.9 2.5 2.1 1.9 15.5 10.4 9.0 7.7 6.9
PEFY-P-VMM-A

-15.0 2.0 2.0 1.9 1.9 -15.0 6.2 6.1 6.0 5.9
-10.0 2.3 2.2 2.2 2.2 -10.0 7.1 7.0 6.9 6.8
-5.0 2.6 2.5 2.5 2.5 -5.0 8.0 7.9 7.8 7.7
0.0 2.9 2.8 2.7 2.5 0.0 8.9 8.8 8.5 7.7
25 2.5 3.0 3.0 2.7 2.5 80 2.5 9.4 9.3 8.5 7.7
6.0 3.2 3.2 2.7 2.5 6.0 10.1 10.0 8.5 7.7
7.5 3.3 3.2 2.7 2.5 7.5 10.4 10.0 8.5 7.7
10.0 3.5 3.2 2.7 2.5 10.0 10.9 10.0 8.5 7.7
12.5 3.7 3.2 2.7 2.5 12.5 11.4 10.0 8.5 7.7
15.5 3.7 3.2 2.7 2.5 15.5 11.5 10.0 8.5 7.7
-15.0 2.5 2.5 2.4 2.4 -15.0 7.8 7.7 7.5 7.4
-10.0 2.8 2.8 2.8 2.7 -10.0 8.9 8.8 8.6 8.5
-5.0 3.2 3.2 3.1 3.1 -5.0 10.0 9.9 9.8 9.6
0.0 3.6 3.5 3.4 3.1 0.0 11.2 11.0 10.6 9.6
32 2.5 3.8 3.7 3.4 3.1 100 2.5 11.8 11.6 10.6 9.6
6.0 4.0 4.0 3.4 3.1 6.0 12.6 12.5 10.6 9.6
7.5 4.2 4.0 3.4 3.1 7.5 13.0 12.5 10.6 9.6
10.0 4.4 4.0 3.4 3.1 10.0 13.6 12.5 10.6 9.6
12.5 4.6 4.0 3.4 3.1 12.5 14.3 12.5 10.6 9.6
15.5 4.6 4.0 3.4 3.1 15.5 14.4 12.5 10.6 9.6
-15.0 3.1 3.1 3.0 3.0 -15.0 10.0 9.8 9.6 9.5
-10.0 3.6 3.5 3.5 3.4 -10.0 11.4 11.2 11.0 10.9
-5.0 4.0 4.0 3.9 3.9 -5.0 12.8 12.6 12.5 12.3
0.0 4.5 4.4 4.3 3.9 0.0 14.3 14.1 13.6 12.3
40 2.5 4.7 4.7 4.3 3.9 125 2.5 15.1 14.9 13.6 12.3
6.0 5.0 5.0 4.3 3.9 6.0 16.2 16.0 13.6 12.3
7.5 5.2 5.0 4.3 3.9 7.5 16.6 16.0 13.6 12.3
10.0 5.4 5.0 4.3 3.9 10.0 17.4 16.0 13.6 12.3
12.5 5.7 5.0 4.3 3.9 12.5 18.3 16.0 13.6 12.3
15.5 5.8 5.0 4.3 3.9 15.5 18.4 16.0 13.6 12.3
-15.0 3.9 3.9 3.8 3.7 -15.0 11.2 11.0 10.9 10.7
-10.0 4.5 4.4 4.3 4.3 -10.0 12.8 12.6 12.4 12.2
-5.0 5.0 5.0 4.9 4.9 -5.0 14.4 14.2 14.1 13.9
0.0 5.6 5.6 5.4 4.9 0.0 16.1 15.9 15.3 13.9
50 2.5 5.9 5.9 5.4 4.9 140 2.5 17.0 16.8 15.3 13.9
6.0 6.4 6.3 5.4 4.9 6.0 18.2 18.0 15.3 13.9
7.5 6.6 6.3 5.4 4.9 7.5 18.7 18.0 15.3 13.9
10.0 6.9 6.3 5.4 4.9 10.0 19.6 18.0 15.3 13.9
12.5 7.2 6.3 5.4 4.9 12.5 20.5 18.0 15.3 13.9
15.5 7.2 6.3 5.4 4.9 15.5 20.7 18.0 15.3 13.9
-15.0 5.0 4.9 4.8 4.7
-10.0 5.7 5.6 5.5 5.4
-5.0 6.4 6.3 6.2 6.2
0.0 7.2 7.1 6.8 6.2
63 2.5 7.5 7.5 6.8 6.2
6.0 8.1 8.0 6.8 6.2
7.5 8.3 8.0 6.8 6.2
10.0 8.7 8.0 6.8 6.2
12.5 9.1 8.0 6.8 6.2
15.5 9.2 8.0 6.8 6.2

2- 46
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Water
temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.8 2.2 1.9 2.4 1.8 2.4 1.9 2.5 1.9 2.6 1.9 2.8 1.9
20 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.7 1.9
20 30 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.3 1.9 2.4 1.8 2.5 1.8
40 1.7 1.6 1.8 1.6 1.9 1.6 1.9 1.7 2.0 1.7 2.1 1.7 2.2 1.7
45 1.6 1.5 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.7 2.0 1.7 2.1 1.7
10 2.4 1.9 2.5 2.0 2.7 2.0 2.8 2.0 2.8 2.1 3.0 2.0 3.2 2.0
20 2.4 1.9 2.4 1.9 2.6 1.9 2.7 2.0 2.7 2.0 2.9 2.0 3.0 2.0
25 30 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9 2.6 2.0 2.7 1.9 2.9 1.9
40 1.9 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.2 1.8 2.4 1.8 2.5 1.8

PEFY-P-VMM-A
45 1.8 1.6 1.9 1.7 2.0 1.7 2.1 1.7 2.1 1.8 2.2 1.8 2.4 1.7
10 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.7 4.1 2.8 4.3 2.7 4.5 2.7
20 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.6 3.9 2.7 4.1 2.7 4.4 2.6
32 30 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.5 3.7 2.6 3.9 2.6 4.1 2.6
40 2.8 2.3 2.9 2.3 3.1 2.3 3.1 2.4 3.2 2.4 3.4 2.4 3.6 2.4
45 2.6 2.2 2.7 2.3 2.9 2.2 3.0 2.3 3.0 2.4 3.2 2.3 3.4 2.3
10 4.4 3.3 4.5 3.5 4.8 3.4 5.0 3.5 5.1 3.6 5.4 3.5 5.7 3.5
20 4.2 3.3 4.4 3.4 4.6 3.3 4.8 3.4 4.9 3.5 5.2 3.5 5.5 3.4
40 30 4.0 3.2 4.1 3.3 4.4 3.2 4.5 3.3 4.6 3.4 4.9 3.4 5.2 3.3
40 3.5 2.9 3.6 3.0 3.8 3.0 3.9 3.0 4.0 3.2 4.3 3.1 4.5 3.1
45 3.3 2.8 3.4 2.9 3.6 2.9 3.7 3.0 3.8 3.1 4.0 3.0 4.2 3.0
10 5.5 4.1 5.6 4.2 6.0 4.2 6.2 4.2 6.3 4.4 6.7 4.3 7.1 4.2
20 5.3 4.0 5.4 4.1 5.8 4.1 5.9 4.1 6.1 4.3 6.5 4.2 6.8 4.1
50 30 5.0 3.8 5.1 4.0 5.5 3.9 5.6 4.0 5.8 4.1 6.1 4.1 6.4 4.0
40 4.3 3.5 4.5 3.6 4.7 3.6 4.9 3.7 5.0 3.8 5.3 3.8 5.6 3.7
45 4.1 3.4 4.2 3.5 4.5 3.5 4.6 3.6 4.7 3.7 5.0 3.7 5.3 3.6
10 6.9 5.1 7.2 5.3 7.6 5.2 7.8 5.3 8.0 5.5 8.5 5.4 9.0 5.3
20 6.7 5.0 6.9 5.1 7.3 5.1 7.5 5.1 7.8 5.3 8.2 5.3 8.6 5.2
63 30 6.3 4.8 6.5 4.9 6.9 4.9 7.1 5.0 7.3 5.2 7.7 5.1 8.1 5.0
40 5.5 4.4 5.7 4.6 6.0 4.5 6.2 4.6 6.4 4.8 6.7 4.7 7.1 4.6
45 5.2 4.3 5.3 4.4 5.7 4.4 5.8 4.4 6.0 4.6 6.3 4.6 6.7 4.5
10 7.8 5.7 8.1 5.9 8.6 5.8 8.8 5.9 9.1 6.1 9.6 6.0 10.1 5.9
20 7.5 5.6 7.8 5.7 8.3 5.7 8.5 5.8 8.7 6.0 9.2 5.9 9.7 5.8
71 30 7.1 5.4 7.3 5.5 7.8 5.5 8.0 5.6 8.2 5.8 8.7 5.7 9.2 5.6
40 6.2 4.9 6.4 5.1 6.8 5.0 7.0 5.1 7.2 5.3 7.6 5.2 8.0 5.2
45 5.8 4.8 6.0 4.9 6.4 4.9 6.6 5.0 6.8 5.2 7.1 5.1 7.5 5.0
10 8.8 6.2 9.1 6.4 9.6 6.3 9.9 6.4 10.2 6.6 10.8 6.5 11.4 6.4
20 8.5 6.1 8.7 6.2 9.3 6.2 9.5 6.2 9.8 6.4 10.4 6.3 10.9 6.2
80 30 8.0 5.8 8.3 6.0 8.8 5.9 9.0 6.0 9.3 6.2 9.8 6.1 10.3 6.0
40 6.9 5.3 7.2 5.5 7.6 5.4 7.8 5.5 8.1 5.7 8.5 5.6 9.0 5.5
45 6.5 5.1 6.8 5.3 7.2 5.2 7.4 5.3 7.6 5.5 8.0 5.4 8.5 5.3
10 10.9 8.4 11.3 8.7 12.0 8.6 12.3 8.8 12.7 9.1 13.4 9.0 14.1 8.8
20 10.5 8.2 10.9 8.5 11.6 8.4 11.9 8.6 12.2 8.9 12.9 8.8 13.6 8.6
100 30 9.9 8.0 10.3 8.2 10.9 8.2 11.2 8.3 11.5 8.6 12.2 8.5 12.8 8.4
40 8.6 7.4 8.9 7.6 9.5 7.6 9.7 7.7 10.0 8.0 10.6 7.9 11.2 7.8
45 8.1 7.1 8.4 7.4 8.9 7.3 9.2 7.5 9.5 7.8 10.0 7.7 10.5 7.6
10 13.7 10.3 14.1 10.7 15.0 10.6 15.4 10.7 15.9 11.1 16.7 10.9 17.7 10.7
20 13.2 10.1 13.6 10.4 14.5 10.3 14.8 10.5 15.3 10.9 16.1 10.7 17.0 10.5
125 30 12.4 9.7 12.8 10.1 13.6 10.0 14.0 10.1 14.4 10.5 15.2 10.4 16.1 10.2
40 10.8 9.0 11.2 9.3 11.9 9.2 12.2 9.4 12.5 9.8 13.2 9.6 14.0 9.5
45 10.2 8.7 10.5 9.0 11.2 8.9 11.5 9.1 11.8 9.5 12.5 9.4 13.2 9.2
10 15.6 11.5 16.1 11.8 17.1 11.7 17.6 11.8 18.1 12.3 19.1 12.1 20.2 11.9
20 15.0 11.2 15.6 11.5 16.5 11.4 17.0 11.6 17.5 12.0 18.4 11.8 19.5 11.6
140 30 14.2 10.8 14.7 11.1 15.6 11.0 16.0 11.2 16.5 11.6 17.4 11.4 18.4 11.2
40 12.3 9.9 12.8 10.2 13.6 10.1 13.9 10.3 14.3 10.7 15.1 10.6 16.0 10.4
45 11.6 9.6 12.0 9.9 12.8 9.8 13.1 10.0 13.5 10.4 14.3 10.2 15.0 10.1

2- 47
2-8.Heating Capacity (In combination with WY, WR2)
PEFY-P-VMM-A SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp.
size 15 19 20 25 27
˚C SHC(kW) SHC(kW) SHC(kW) SHC(kW) SHC(kW)
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
PEFY-P-VMM-A

10 3.5 3.5 3.4 2.7 2.4


20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 7.9 7.8 7.7 6.1 5.5
20 9.3 9.2 9.0 7.2 6.5
71 30 9.3 9.2 9.0 7.2 6.5
40 9.6 9.5 9.4 7.5 6.7
45 10.6 10.5 10.3 8.2 7.4
10 8.8 8.7 8.5 6.8 6.1
20 10.3 10.2 10.0 8.0 7.2
80 30 10.3 10.2 10.0 8.0 7.2
40 10.7 10.6 10.4 8.3 7.5
45 11.7 11.6 11.4 9.1 8.2
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1
10 15.8 15.6 15.3 12.2 11.0
20 18.5 18.4 18.0 14.4 13.0
140 30 18.5 18.4 18.0 14.4 13.0
40 19.3 19.1 18.7 15.0 13.5
45 21.1 20.9 20.5 16.4 14.8

2- 48
3. Sound Levels
3-1. Noise level(VMM-A)

Ceiling concealed (VMM-A series)

Noise level at anechoic room (Low-Middle-High) Unit : dB(A)


Aux.duct
1m 2m External static pressure❇
Model
Low Mid High
PEFY-P20VMM-A 23-28-31 27-30-32 29-34-39
PEFY-P25VMM-A
PEFY-P32VMM-A 26-30-33 28-32-35 32-36-39
PEFY-P40VMM-A 29-32-35 31-34-37 33-37-41
1.5m

PEFY-P-VMM-A
PEFY-P50VMM-A 29-34-37 31-35-38 34-38-41
PEFY-P63VMM-A 30-34-37 31-35-38 34-38-41
Measurement location PEFY-P71VMM-A 31-34-37 32-36-39 35-39-42
PEFY-P80VMM-A
PEFY-P100VMM-A 40-44 - 43-47
PEFY-P125VMM-A 42-45 - 44-47
PEFY-P140VMM-A 42-45 - 44-47

❇ PEFY-P20~80VMM-A
Low : 30Pa Mid : 50Pa High : 100Pa
❇ PEFY-P100~140VMM-A
Low : 50Pa High : 130Pa

3-2. NC curves(VMM-A)
1) Back inlet

PEFY-P20,25VMM-A (External static


pressure 30Pa) PEFY-P20,25VMM-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P20,25VMM-A (External static


pressure 100Pa) PEFY-P32VMM-A (External static
pressure 30Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 49
PEFY-P32VMM-A (External static
pressure 50Pa) PEFY-P32VMM-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20
PEFY-P-VMM-A

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40VMM-A (External static


pressure 30Pa) PEFY-P40VMM-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40VMM-A (External static


pressure 100Pa) PEFY-P50VMM-A (External static
pressure 30Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P50VMM-A (External static (External static


pressure 50Pa) PEFY-P50VMM-A pressure 100Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
High speed High speed
Middle speed Middle speed
Low speed Low speed
60 NC60 60
NC60

50 NC50 50
NC50

40 NC40 40
NC40

30 30
NC30
NC30

20 NC20 20
NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 50
PEFY-P63VMM-A (External static PEFY-P63VMM-A (External static
pressure 30Pa) pressure 50Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

PEFY-P-VMM-A
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P63VMM-A (External static PEFY-P71,80VMM-A (External static


pressure 100Pa) pressure 30Pa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P71,80VMM-A (External static


pressure 50Pa) PEFY-P71,80VMM-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P100VMM-A (External static


pressure 50Pa) PEFY-P100VMM-A (External static
pressure 130Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
High speed
High speed
Low speed Low speed
60 NC60 60
NC60

50 NC50 50
NC50

40 NC40 40
NC40

30 30
NC30
NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 51
PEFY-P125VMM-A (External static
pressure 50Pa) PEFY-P125VMM-A (External static
pressure 130Pa)
70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


70
High speed High speed
Low speed Low speed
OCTAVE BAND PRESSURE LEVEL(0dB = 20µPa)

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20
PEFY-P-VMM-A

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMM-A (External static


pressure 50Pa) PEFY-P140VMM-A (External static
pressure 130Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2) Bottom inlet

PEFY-P20,25VMM-A (External static


pressure 30Pa) PEFY-P20,25VMM-A (External static
pressure 50Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70 70
High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 52
PEFY-P20,25VMM-A (External static
pressure 100Pa) PEFY-P32VMM-A (External static
pressure 30Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


70
High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

PEFY-P-VMM-A
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P32VMM-A (External static


pressure 50Pa) PEFY-P32VMM-A (External static
pressure 100Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40VMM-A (External static


pressure 30Pa) PEFY-P40VMM-A (External static
pressure 50Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P40VMM-A (External static


pressure 100Pa) PEFY-P50VMM-A (External static
pressure 30Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 53
PEFY-P50VMM-A (External static (External static
pressure 50Pa) PEFY-P50VMM-A pressure 100Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


High speed High speed
Middle speed Middle speed
Low speed Low speed
60 60 NC60
NC60

50 50 NC50
NC50

40 40 NC40
NC40

30 30 NC30
NC30

20 20
NC20
PEFY-P-VMM-A

NC20
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P63VMM-A (External static PEFY-P63VMM-A (External static


pressure 30Pa) pressure 50Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


70
High speed High speed
Middle speed Middle speed
Low speed Low speed
60 NC60 60
NC60

50 NC50 50
NC50

40 NC40 40
NC40

30 30
NC30
NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P63VMM-A (External static PEFY-P71,80VMM-A (External static


pressure 100Pa) pressure 30Pa)
70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 60 NC60
NC60

50 50 NC50
NC50

40 40 NC40
NC40

30 30
NC30
NC30

20 20
NC20 NC20
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P71,80VMM-A (External static


pressure 50Pa) PEFY-P71,80VMM-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Middle speed Middle speed
Low speed Low speed
60 NC60 60
NC60

50 NC50 50
NC50

40 NC40 40
NC40

30 30
NC30
NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 54
PEFY-P100VMM-A (External static
pressure 50Pa) PEFY-P100VMM-A (External static
pressure 130Pa)

OCTAVE BAND PRESSURE LEVEL< dB> (0dB = 20µPa)


OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70 70
High speed
High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

PEFY-P-VMM-A
10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES<Hz>

PEFY-P125VMM-A (External static


pressure 50Pa) PEFY-P125VMM-A (External static
pressure 130Pa)
70 70

OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)


OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMM-A (External static


pressure 50Pa) PEFY-P140VMM-A (External static
pressure 130Pa)
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
OCTAVE BAND PRESSURE LEVEL (dB) (0dB = 20µPa)

70
High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 55
3-3. Fan characteristics curves(VMM-A)

PEFY-P20,25VMM-A PEFY-P32VMM-A PEFY-P40VMM-A


External static pressure : 30,50,100Pa External static pressure : 30,50,100Pa External static pressure : 30,50,100Pa
Power source : 220·240(V) Power source : 220·240(V) Power source : 220·240(V)
150 150 High
150
High High
imit

Low Low Low

imit
Pa L

imit

L
Pa
100

Pa L

100
100
100Pa

100Pa
PEFY-P-VMM-A

100Pa

imit

it
100 100 100

Lim
L
External static pressure (Pa)
External static pressure (Pa)

Pa

External static pressure (Pa)

Pa
50
imit

50
L

imit
50Pa
Pa

it
50

Lim
Pa
50Pa 50Pa
imit

30

100Pa

Pa
30
L

30Pa
Pa

100Pa
30

30Pa

30Pa 100Pa 50Pa


50
50 50

50Pa
50Pa

30Pa

30Pa
30Pa

6 8 10 8 10 12 10 12 14 16
Air volume (m3/min) Air volume (m3/min) Air volume (m3/min)

PEFY-P50VMM-A PEFY-P63VMM-A
External static pressure : 30,50,100Pa External static pressure : 30,50,100Pa
Power source : 220·240(V) Power source : 220·240(V)

150 High 150 High


Low Low
imit

it
im
L

aL
Pa

0P
1 00

10

100Pa
100Pa
it
L im

100 100
Pa

it
External static pressure (Pa)

Lim
External static pressure (Pa)

50Pa
50

Pa

it
50

Lim
it
Lim

50Pa
Pa
Pa

30
30

100Pa 30Pa
30Pa
100Pa

50Pa 50Pa
50 50

30Pa 30Pa

12 14 16 18 15 20
Air volume (m3/min) Air volume (m3/min)

2- 56
PEFY-P71,80VMM-A PEFY-P100VMM-A
External static pressure : 30,50,100Pa External static pressure : 50,130Pa
Power source : 220·240(V) Power source : 220·240(V)
150 High 200
High
Low
Low
it
im
aL

it
0P

130Pa

Lim
10

100Pa

PEFY-P-VMM-A
150

External static pressure (Pa)


50Pa

100
it
External static pressure (Pa)

Lim
Pa

it
50

Lim

50Pa
Pa
30

100Pa 30Pa 100


50,130Pa

50 50Pa

50

30Pa

15 20 25 30 35
Air volume (m3/min) Air volume (m3/min)

PEFY-P125VMM-A PEFY-P140VMM-A
External static pressure : 50,130Pa External static pressure : 50,130Pa
Power source : 220·240(V) Power source : 220·240(V)

200 High
200
High
Low Low

130Pa 130Pa
it

it
m

m
Li

Li

150 150
50Pa 50Pa
External static pressure (Pa)
External static pressure (Pa)

100 100
50,130Pa 50,130Pa

50 50

25 30 35 40 30 35 40 45
Air volume (m3/min) Air volume (m3/min)

2- 57
PEFY-P-VMM-A

Service space:500 or more 10-ø3(P20/25/32/40/50)


450 50˜150 29 A 12-ø3(P63/71/80)
55 81 C B 81
Model A B C D E F G Access door

10
P20,25,32 652 245 710 684 6.35 12.7
P40 772 305 830 804 6.35 12.7
P50 772 305 830 804 9.52 15.88

450
P63,71,80 1012 280 290 1070 1044 9.52 15.88

197
Lifting bolt hole
(14X22)

1 Refrigerant piping flare connection (liquid øF copper tube):HP


PEFY-P20,25,32,40,50,63,71,80VMM-A

2 Refrigerant piping flare connection (gas øG copper tube) :LP


355

3 Drain R1(External thread)

365˜465
4. External Dimensions

4 Electrical parts box

159
5 Drain Pump (Option)
56

Set
6 Drain Pipe (Option)···Flexible joint VP-25(I.D.ø32)

18
10-ø3(P20/25/32/40/50)
10

81 C B 81
7 Filter 12-ø3(P63/71/80)
13 A
44 75 E 13
30 640 30
243 D 30
4 61 227 10

2- 58
In case of rear inlet 10
1 6

3.5
2

21
24
35

40
85
45 80

109
179
Air inlet

277

288
282

256
176
5
7 Air outlet

3.5
Keep duct-work length 850mm or more.
Be sure to apply the air filter (field supply) near the air inlet grille.

In case of bottom inlet


10-ø3(P20/25/32/40/50)
12-ø3(P63/71/80)
7 Air outlet
10

40 176

10
81 C B 81
15 256
A
Air inlet
Unit : mm
Service space:500 or more

450 50˜150 29 A 12-ø3


55 81 C B 81
Model A B C D E Access door

10
P100·125 1252 360 370 1310 1284
P140 1552 460 470 1610 1584

450
Lifting bolt hole

197
(14X22)
PEFY-P100,125,140VMM-A

1 Refrigerant piping flare connection (liquid ø9.52 copper tube):HP


375

2 Refrigerant piping flare connection (gas ø19.05 copper tube) :LP


12-ø3

323
308
3 Drain 25A (male screw)

365˜465
4 Electrical parts box
80

5 Drain Pump (Option)


Set
6 Drain Pipe (Option)···Flexible joint VP25(I.D.ø32) C B 81
10

81
7 Filter A
13 E 13

2- 59
30 680 30
44 75 D 30
53 169 10
243

25
4 2 6

3
1

35
20
In case of rear inlet

40
113

140
210
45 122
307
Air inlet

319
279
181
282
5
7
Air outlet

3
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter (field supply) near the air inlet grille.

In case of bottom inlet

282
Air outlet 12-ø3
7
10

40 181

30
10
81 C B 81
15 279
Unit : mm

A
Air inlet

PEFY-P-VMM-A
PEFY-P-VMM-A

INSIDE SECTION OF CONTROL BOX

TB15 (TRANSMISSION TERMINAL BED)


PEFY-P20~

TO MA REMOTE CONTROLLER
REMOTE CENTRALLY REMOTE
SWITCH CONTROL INDICATION X1
CN32 CN51 CN52
FAN CON
~ 80VMM-A

(Red) (White) (Black) TB5 (TRANSMISSION TERMINAL BED)


X4
S(SHIELD)
M2
TO OUTDOOR UNIT
M1 BC CONTROLLER
M-NET REMOTE CONTROLLER
TO NEXT INDOOR UNIT

PULL BOX

OPTION
SW14 SW12 SW11
(Connection No.) (2nd digit) (1st digit) (White) (White)
FUSE(16A)

TH21 TH22 TH23 DS


TO DUCT
OP
5. Electrical Wiring Diagrams

LEV MF
BREAKER(16A)

2- 60
POWER SUPPLY
˜/N 220-240V 50Hz

NOTE:1.TB2,TB5 shown in dotted line are


field work.
2.Mark indicates terminal bed,
connector, board insertion
connector or fastening connector
of control board.
Capacitor
MODELS 20/25/32 6
MODELS 40/50 8
MODELS 63/71/80 6
INSIDE SECTION OF CONTROL BOX
TB15 (TRANSMISSION TERMINAL BED)
X06 X05X04 TO MA REMOTE CONTROLLER
REMOTE CENTRALLY REMOTE
SWITCH CONTROL INDICATION
CN32 CN51 CN52
TB5 (TRANSMISSION TERMINAL BED)
S(SHIELD)
(Red) (White) (Black)
PEFY-P100~140VMM-A

TO OUTDOOR UNIT
BC CONTROLLER
M-NET REMOTE CONTROLLER
T
TO NEXT INDOOR UNIT
FB

PULL BOX
SW14 SW12 SW11
(Connection No.) (2nd digit) (1st digit)
(White)
FUSE(16A)
TO DUCT
OP
MF
TH21 TH22 TH23 DS
LEV Red Connector White Connector BREAKER(16A)

OPTION
for External static for External static

2- 61
pressure 130Pa C
pressure 50Pa

POWER SUPPLY
˜/N 220-240V 50Hz

NOTE:1.TB2,TB5 shown in dotted line are


field work.
2.Mark indicates terminal bed,
connector, board insertion
connector or fastening connector
of control board.

PEFY-P-VMM-A
6. Options

Description Model Applicable capacity


PAC-KE32EDF-F P20/P25/P32
PAC-KE50EDF-F P40/P50
Circular duct flange PAC-KE80EDF-F P63/P71/P80
PAC-KE125EDF-F P100/P125
PAC-KE140EDF-F P140
PEFY-P-VMM-A

P20/P25/P32/P40/P50/P63/P71
Drain water lift-up kit PAC-KE03DM-F P80/P100/P125/P140

2- 62
Ceiling concealed PEFY-P-VMH-A-F

CONTENTS

1. Specifications ································································ 2-64

2. Capacity Tables ····························································· 2-65


2-1 Cooling Capacity ························································ 2-65

VMH-A-F
PEFY-P-
2-2 Cooling outlet air temp. ·················································2-65
2-3 Heating Capacity ························································ 2-66
2-4 Heating outlet air temp. ··············································· 2-66

3. Sound Levels ······························································ 2-67


3-1 Noise levels(VMH-A-F) ··············································· 2-67
3-2 N/C curves(VMH-A-F) ················································· 2-67
3-3 Fan characteristics curves(VMH-A-F) ························· 2-71

4. External Dimensions ··················································· 2-73

5. Electrical Wiring Diagrams ·········································· 2-74

6. Options ··········································································· 2-75

2- 63
1. Specifications
PEFY-P80VMH-A-F PEFY-P140VMH-A-F
Power source ~ 220-240V 50Hz / ~ 208-230V 60Hz
❇1 kW 9.0 16.0
Cooling capacity
❇2 kcal/h 8,000 14,000
Heating capacity ❇1 kW 8.5 15.1
Power consumption Cooling kW 0.16/0.21 0.29/0.33
(50/60Hz) Heating kW 0.16/0.21 0.29/0.33
Cooling A 0.67/0.91 1.24/1.48
Current
Heating A 0.67/0.91 1.24/1.48
External finish Galvanizing
Height mm 380
Dimension Width mm 1000 1200
Depth mm 900
Net weight kg 50 70
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan ✕ 1 Sirocco fan ✕ 2
3
Airflow rate m /min 9.0 18.0
External 208V Pa 35/85/170 35/85/170
Fan
static 220V Pa 40/115/190 50/115/190
pressure 230V Pa 50/130/210 60/130/220
(Low/Mid/High) 240V Pa 80/170/220 100/170/240
Type Single phase induction motor
VMH-A-F
PEFY-P-

Motor
Output ❇3 kW 0.09 0.14
Air filter (option) Synthethic fiber unwoven cloth filter(long life)
Gas
mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension 32 (1-1/4 inch)
208, 220V dB(A) 27/38/43 28/38/43
Noise level ❇4
230, 240V dB(A) 33/43/45 34/43/45
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 33˚CDB/28˚CWB,Outdoor 33˚CDB
Heating : Indoor 0˚CDB/-2.9˚CWB,Outdoor 0˚CDB/-2.9˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 The value are that at 220V.
❇ 4 It is measured in anechoic room.

a). The cooling and heating capacities are the maximum capacities that were obtained by operating in the above air conditions
and with a refrigerant pipe of about 7.5m.
b). The actual capacity characteristics vary with the combination of indoor and outdoor units. See the technical information.
c). The operating noise is the data that was obtained by measuring it 1.5m from the botton of the unit in an anechoic room.
(Noise meter A-scale value)
d). The figure of Electrical characteristic indicates at 220V.
e). When the 100% fresh air indoor units are connected, the maximum connectable indoor units to 1 outdoor unit are as follows.

Heatpump models Coolling only


110%(100% in case of heating below-5deg) 110%

f). Operational temp range is cooling : from 21degDB/15.5degWB to 43degDB/35degWB.


Heating : from -10degDB to 20degDB
✻Thermo off (Fan) operation automatically starts either when temperature is lower than 21degDB in cooling mode or when
the temperature exceeds 20degDB in heating mode.
g). As the room temp is sensed by the thermo in the remote controller or the one in the room, be sure to use ether remote
controller or room thermo.
h). Autochangeover function or Dry mode is Not available .Fan mode operation during the thermo off in Cooling/Heating mode.
i). The fan would temporaly stops either with R2/WR2 system or in defrost.
j). In any case, the wir flow rate should be kept lower than 110% of the above chart.Please see “ Fan curves “ for the details.
k). When this unit is used as sole A/C system, be careful about the dew in air outlet grilles in cooling mode.
l). Air filter must be installed in the air intake side.The filter should be attached where easy maintenance is possible in case of
usage of field supply filters.
m). Long life filter cannot be used with Hi-efficiency filter together.

2- 64
2. Capacity Tables
2-1.Cooling Capacity
CA :Capacity(kW)
PEFY-P80VMH-A-F SHC:Sensible Heat Capacity(kW)
Outdoor ˚CWB
air temp.
15 17 20 23 26 28 30 32 35
˚CDB
CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
21 4.4 3.0 5.3 2.9 - - - - - - - - - - - - - -
23 4.4 3.4 5.3 3.3 6.5 3.0 - - - - - - - - - - - -
25 4.4 3.8 5.2 3.7 6.4 3.4 - - - - - - - - - - - -
27 - - 5.2 4.0 6.4 3.7 7.5 3.3 - - - - - - - - - -
29 - - - - 6.4 4.1 7.5 3.7 8.5 3.2 - - - - - - - -
31 - - - - 6.3 4.5 7.4 4.0 8.4 3.5 9.1 3.1 - - - - - -
33 - - - - - - 7.3 4.4 8.3 3.8 9.0 3.5 9.6 3.0 - - - -
35 - - - - - - 7.2 4.7 8.2 4.2 8.9 3.8 9.5 3.3 - - - -
37 - - - - - - - - 8.1 4.5 8.8 4.1 9.4 3.7 9.9 3.2 - -
40 - - - - - - - - 8.0 5.0 8.6 4.6 9.1 4.1 9.7 3.7 10.5 2.9

PEFY-P140VMH-A-F
Outdoor ˚CWB
air temp.
15 17 20 23 26 28 30 32 35
˚CDB
CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

VMH-A-F
PEFY-P-
21 7.8 5.6 9.4 5.3 - - - - - - - - - - - - - -
23 7.8 6.3 9.3 6.0 11.5 5.4 - - - - - - - - - - - -
25 7.8 7.1 9.3 6.8 11.5 6.1 - - - - - - - - - - - -
27 - - 9.3 7.5 11.4 6.8 13.4 6.0 - - - - - - - - - -
29 - - - - 11.3 7.5 13.3 6.7 15.2 5.6 - - - - - - - -
31 - - - - 11.2 8.2 13.2 7.3 15.0 6.3 16.2 5.5 - - - - - -
33 - - - - - - 13.0 8.0 14.8 7.0 16.0 6.2 17.1 5.3 - - - -
35 - - - - - - 12.9 8.7 14.6 7.6 15.8 6.8 16.9 6.0 - - - -
37 - - - - - - - - 14.5 8.3 15.6 7.5 16.6 6.6 17.7 5.7 - -
40 - - - - - - - - 14.2 9.3 15.2 8.5 16.3 7.6 17.3 6.7 18.7 5.3
There are times when the cooling capacity is lowered to protect the compressor in cases where the external temperature exceeds 40˚C

2-2.Cooling outlet air temp.


CA :Capacity(kW)
PEFY-P80VMH-A-F SHC:Sensible Heat Capacity(kW)
Outdoor ˚CWB
air temp.
15 17 20 23 26 28 30 32 35
˚CDB
˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB
21 5.1 5.0 5.6 5.6 - - - - - - - - - - - - - -
23 5.1 5.0 5.7 5.6 7.0 7.0 - - - - - - - - - - - -
25 5.1 5.0 5.7 5.7 7.1 7.1 - - - - - - - - - - - -
27 - - 5.8 5.7 7.2 7.2 9.2 9.2 - - - - - - - - - -
29 - - - - 7.4 7.3 9.4 9.4 12.0 12.0 - - - - - - - -
31 - - - - 7.5 7.4 9.6 9.6 12.2 12.2 14.2 14.2 - - - - - -
33 - - - - - - 9.8 9.7 12.4 12.4 14.4 14.4 16.6 16.6 - - - -
35 - - - - - - 10.0 9.9 12.6 12.6 14.6 14.6 16.8 16.8 - - - -
37 - - - - - - - - 12.8 12.8 14.9 14.8 17.1 17.1 19.5 19.5 - -
40 - - - - - - - - 13.2 13.1 15.3 15.2 17.5 17.4 19.9 19.8 23.7 23.7

PEFY-P140VMH-A-F
Outdoor ˚CWB
air temp.
15 17 20 23 26 28 30 32 35
˚CDB
˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB ˚CDB ˚CWB
21 6.3 6.3 7.1 7.0 - - - - - - - - - - - - - -
23 6.3 6.3 7.1 7.1 8.7 8.7 - - - - - - - - - - - -
25 6.4 6.3 7.2 7.1 8.8 8.8 - - - - - - - - - - - -
27 - - 7.2 7.1 8.9 8.9 11.1 11.1 - - - - - - - - - -
29 - - - - 9.0 9.0 11.2 11.2 13.9 13.9 - - - - - - - -
31 - - - - 9.1 9.0 11.4 11.3 14.0 14.0 16.1 16.1 - - - - - -
33 - - - - - - 11.5 11.5 14.2 14.2 16.2 16.2 18.4 18.4 - - - -
35 - - - - - - 11.7 11.6 14.4 14.4 16.4 16.4 18.6 18.6 - - - -
37 - - - - - - - - 14.6 14.5 16.7 16.6 18.8 18.8 21.2 21.1 - -
40 - - - - - - - - 14.9 14.8 17.0 16.9 19.2 19.1 21.5 21.5 25.2 25.2

2- 65
2-3.Heating Capacity
PEFY-P80VMH-A-F SHC:Sensible Heat Capacity(kW)
Outdoor ˚CWB
air temp.
-9 -5 -2.9 0 2 4 6 10 14
˚CDB
SHC SHC SHC SHC SHC SHC SHC SHC SHC
-8 8.2 - - - - - - - -
-3 - 9.1 - - - - - - -
0 - - 8.5 - - - - - -
3 - - - 7.9 7.9 - - - -
7 - - - - 7.1 7.1 7.1 - -
11 - - - - - - 6.3 6.3 -
15 - - - - - - - 5.5 5.5
18 - - - - - - - 5.0 5.0
20 - - - - - - - - 4.6

PEFY-P140VMH-A-F
Outdoor ˚CWB
air temp.
-9 -5 -2.9 0 2 4 6 10 14
˚CDB
SHC SHC SHC SHC SHC SHC SHC SHC SHC
VMH-A-F
PEFY-P-

-8 14.6 - - - - - - - -
-3 - 16.2 - - - - - - -
0 - - 15.1 - - - - - -
3 - - - 14.0 14.0 - - - -
7 - - - - 12.6 12.6 12.6 - -
11 - - - - - - 11.2 11.2 -
15 - - - - - - - 9.8 9.8
18 - - - - - - - 8.8 8.8
20 - - - - - - - - 8.1

2-4.Heating outlet air temp.


PEFY-P80VMH-A-F SHC:Sensible Heat Capacity(kW)
Outdoor ˚CWB
air temp.
-9 -5 -2.9 0 2 4 6 10 14
˚CDB
˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB
-8 40.6 - - - - - - - -
-3 - 53.1 - - - - - - -
0 - - 51.9 - - - - - -
3 - - - 51.3 51.8 - - - -
7 - - - - 50.5 50.5 50.9 - -
11 - - - - - - 49.6 50.1 -
15 - - - - - - - 48.8 49.2
18 - - - - - - - 48.2 48.2
20 - - - - - - - - 47.8

PEFY-P140VMH-A-F
Outdoor ˚CWB
air temp.
-9 -5 -2.9 0 2 4 6 10 14
˚CDB
˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB ˚CDB
-8 34.7 - - - - - - - -
-3 - 45.8 - - - - - - -
0 - - 45.6 - - - - - -
3 - - - 45.4 45.4 - - - -
7 - - - - 45.2 45.2 45.2 - -
11 - - - - - - 45.0 45.0 -
15 - - - - - - - 44.7 45.1
18 - - - - - - - 44.6 44.6
20 - - - - - - - - 44.4

2- 66
3. Sound Levels
3-1. Noise level(VMH-A-F)
Ceiling concealed (VMH-A series)

Aux.duct Noise level at anechoic room Unit : dB(A)


1m 2m
Model External static pressure
Low Mid High
PEFY-P80 208,220V 27 38 43
VMH-A-F 230,240V 33 43 45
1.5m 208,220V 28 38 43
PEFY-P140
VMH-A-F 230,240V 34 43 45

Measurement location

Model Power source 208 220 230 240


Low 40 50 80
50Hz Mid - 115 130 170
High 190 210 220

VMH-A-F
PEFY-P80VMH-A-F

PEFY-P-
Low 35 40 50
60Hz Mid 85 115 130 -
High 170 190 210
Low 50 60 100
50Hz Mid - 115 130 170
High 119 220 240
PEFY-P140VMH-A-F
Low 35 50 60
60Hz Mid 85 115 130 -
High 170 190 220

3-2. NC curves(VMH-A-F)
PEFY-P80VMH-A-F (External static PEFY-P80VMH-A-F (External static
pressure 35Pa) pressure 85Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


208V-60Hz 208V-60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A-F (External static PEFY-P80VMH-A-F (External static


pressure 170Pa) pressure 40Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


208V-60Hz 220V-50/60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 67
PEFY-P80VMH-A-F (External static (External static
pressure 115Pa) PEFY-P80VMH-A-F pressure 190Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
220V-50/60Hz 220V-50/60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A-F (External static PEFY-P80VMH-A-F (External static


pressure 50Pa) pressure 130Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230V-50/60Hz 230V-50/60Hz
VMH-A-F

60 60
PEFY-P-

NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A-F (External static (External static


pressure 210Pa) PEFY-P80VMH-A-F pressure 80Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


230V-50/60Hz 240V-50Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P80VMH-A-F (External static PEFY-P80VMH-A-F (External static


pressure 170Pa) pressure 220Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


240V-50Hz 240V-50Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 68
PEFY-P140VMH-A-F (External static (External static
pressure 35Pa) PEFY-P140VMH-A-F pressure 85Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
208V-60Hz 208V-60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMH-A-F (External static PEFY-P140VMH-A-F (External static


pressure 170Pa) pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
208V-60Hz 220V-50/60Hz

VMH-A-F
PEFY-P-
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMH-A-F (External static (External static


pressure 115Pa) PEFY-P140VMH-A-F pressure 190Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


220V-50/60Hz 220V-50/60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMH-A-F (External static PEFY-P140VMH-A-F (External static


pressure 60Pa) pressure 130Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

High speed High speed


230V-50/60Hz 230V-50/60Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 69
PEFY-P140VMH-A-F (External static (External static
pressure 220Pa) PEFY-P140VMH-A-F pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
230V-50/60Hz 240V-50Hz
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PEFY-P140VMH-A-F (External static PEFY-P140VMH-A-F (External static


pressure 170Pa) pressure 240Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


High speed High speed
VMH-A-F

240V-50Hz 240V-50Hz
PEFY-P-

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 70
3-3. Fan characteristics curves(VMH-A-F)
PEFY-P80VMH-A-F PEFY-P80VMH-A-F
Suction : Back inlet Suction : Back inlet
External static pressure : 35,85,170Pa External static pressure : 40,115,190Pa
Power source : 208V 60Hz Power source : 220V 50/60Hz
250
250
50Hz
60Hz

200
200
190Pa(50Hz)
190Pa(60Hz)
170Pa(60Hz)
External static pressure (Pa)

External static pressure (Pa)


150
150

115Pa(50Hz)
100 115Pa(60Hz)
100
85Pa(60Hz)

50
50 40Pa(50Hz)
35Pa(60Hz)
40Pa(60Hz)

High efficiency filter

VMH-A-F
High efficiency filter

PEFY-P-
Long-life filter
0 Long-life filter
0
7 8 9 10
7 8 9 10
(85%) (110%)
(85%) (110%)
Airflow rate (m3/min)
Airflow rate (m3/min)

PEFY-P80VMH-A-F PEFY-P80VMH-A-F
Suction : Back inlet Suction : Back inlet
External static pressure : 50,130,210Pa External static pressure : 80,170,220Pa
Power source : 230V 50/60Hz Power source : 240V 50Hz
250 250
50Hz
60Hz
220Pa(50Hz)
210Pa(50Hz)
210Pa(60Hz)
200 200

170Pa(50Hz)
External static pressure (Pa)
External static pressure (Pa)

150 150

130Pa(50Hz)
130Pa(60Hz)

100 100

80Pa(50Hz)

50Pa(50Hz)
50 50Pa(60Hz) 50

High efficiency filter High efficiency filter


Long-life filter Long-life filter
0 0
7 8 9 10 7 8 9 10
(85%) (110%) (85%) (110%)
Airflow rate (m3/min) 3
Airflow rate (m /min)

2- 71
PEFY-P140VMH-A-F PEFY-P140VMH-A-F
Suction : Back inlet Suction : Back inlet
External static pressure : 35,85,170Pa External static pressure : 50,115,190Pa
Power source : 208V 60Hz Power source : 220V 50/60Hz
250 250
50Hz
60Hz

200 200 190Pa(50Hz)

190Pa(60Hz)
External static pressure (Pa)

External static pressure (Pa)


170Pa(60Hz)

150 150

115Pa(50Hz)

115Pa(60Hz)

100 100

85Pa(60Hz)

50Pa(50Hz)
50 50 50Pa(60Hz)
35Pa(60Hz)
High efficiency filter High efficiency filter
VMH-A-F
PEFY-P-

Long-life filter Long-life filter


0 0
15 16 17 18 19 20 15 16 17 18 19 20
(85%) (110%)
(85%) (110%)
Airflow rate (m3/min) Airflow rate (m3/min)

PEFY-P140VMH-A-F PEFY-P140VMH-A-F
Suction : Back inlet Suction : Back inlet
External static pressure : 60,130,220Pa External static pressure : 100,170,240Pa
Power source : 230V 50/60Hz Power source : 240V 50Hz
250
50Hz
60Hz
250 240Pa(50Hz)
220Pa(50Hz)

220Pa(60Hz)
200

200
External static pressure (Pa)

External static pressure (Pa)

170Pa(50Hz)

150
130Pa(50Hz)
150
130Pa(60Hz)

100
100Pa(50Hz)
100

60Pa(50Hz)

60Pa(60Hz)
50
50

High efficiency filter


High efficiency filter

Long-life filter
Long-life filter
0 0
15 16 17 18 19 20 15 16 17 18 19 20
(85%) (110%) (85%) (110%)
Airflow rate (m3/min) Airflow rate (m3/min)

2- 72
Required space for service and maintenance
G-ø3
J-ø3

625

700 200
~
100 150
~20
0 L Note2
450 50
50

450
Access door

E
PEFY-P80,140VMH-A-F

D
C
A

50x(J-1)=K

50x(G-1)=H
Air inlet Air outlet

B (Lifting bolt pitch)


More than 20mm
4. External Dimensions

Access door Ceiling surface

Make the access door at the appointed position


properly for service maintenance.

50
More than 20mm

50
15

80
10

41 F
Less than 300mm

70
23

2- 73
3
340 Lifting bolt 383 250
3
814(Lifting bolt pitch) 60
904

Model:80(Note3) 900
24 847 29
10 15
Drain hole
Less than 550mm

Control box (option)


2
When installing the drain
water lifting-up mech(option).

250

340
380
Note 1.Use M10 screw for the lifting bolt (field supply).

77
328

50x5=250
50 50 50 50
2.Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned.
3.This chart indicates for PEFY-P140VMH-A-F models, which have 2 fans.

50
PEFY-P80VMH-A-F model has 1 fan.

130
94

45
4.Make sure to install the air filter(field supply) on the air intake side.

41 25
Terminal bed In case field supplied air filter is used, attach it where the filter service is easily done.

17
1

30
(Power source) Refrigerant piping flare connection(gas M copper tube):LP
92 200 ······ ➀
Terminal box Terminal bed Refrigerant piping flare connection(liquid N copper tube):HP ······ ➁
343
(Transmission) Drain hose 32mm(1-1/4inch) <flexible joint 200mm> (accessory) ······ ➂
Keep duct-work length 850mm or more. 387

Drain hole
Model A B C D E F G H J K L M N
PEFY-P80VMH-A-F 1050 1004 930 850 800 25 17 800 15 700 1030 ø15.88 ø9.52
PEFY-P140VMH-A-F 1250 1204 1130 1050 1000 25 21 1000 19 900 1230 ø19.05 ø9.52

VMH-A-F
PEFY-P-
PEFY-P-
VMH-A-F

INSIDE SECTION OF CONTROL BOX


I.B TB15(TRANSMISSION TERMINAL BED)
1 SW4 SW3 SW2
2 3 2
3 CN42 CN3A 1 1 TO MA REMOTE CONTROLLER
4
1
2 TB5(TRANSMISSION TERMINAL BED)
3 S(SHIELD)
4 X06 X05 X04
5 CN81 F1 X01 2 M2 TO OUTDOOR UNIT
6 (AC250V
6.3A F ) ZNR CN2M 1 M1 ] BC CONTROLLER
7 REMOTE CONTROLLER
8 CN20 CN21 CN29CN22 CN31 CN60 CN3T CNT CND CNP FAN3
PEFY-P80,140VMH-A-F

21
21 21 21 21 65 4 3 2 1 3 1 31 13 31 13 7 S.B
Drain T CN1 1 TO NEXT INDOOR UNIT
sensor ZNR1
CN31 DSA1 3 PULL BOX
❈A 1 1 1
A.B 12 3 4 56 3 1 F2 (AC250V
5A F )
2 2 2 TB2
CN82 CN62 L
8 SW1 SW7
7 N FUSE(16A)
❈A connector is PE
6 9 0 1 9 0 1 attached to the
5 EF0 12
D 3 8 2 8 2 drain lift up *insert
4 C 4 3 3 mechanism,
BA 5 7 7 C
3 9876 6 5 4 6 5 4 which is an 98 4 31 9 8 4 31 BREAKER(16A)
2 optional part. 98 431
1 SW14 SW12 SW11
(Connection No.) (2nd digit) (1st digit) ❈NOTE 1,2 (White) 98 65 4 3 1 986 31 9 8 5 31
DS (Blue) (Red)
5. Electrical Wiring Diagrams

❈NOTE 1 MF PE TO DUCT
POWER SUPPLY
~ 220,230,240V 50Hz

2- 74
attachment to alter the external static pressure on the fan ~ 208,220,230V 60Hz
LEV DP Color /External Static Pressure
REMOTE SENSOR TH22 TH23 TH24 Red /High Pressure
❈NOTE 1 Blue /Low Pressure
White /Middle Pressure
SYMBOL EXPLANATION
SYMBOL NAME SYMBOL NAME
MF Fan motor CN20 Connector (remote sensor)
C ❈B Capacitor (for MF) TH22 Thermistor (piping temp.detection/liquid)
I.B Indoor controller board TH23 Thermistor (piping temp.detection/gas)
<DS> Drain sensor TH24 Thermistor (outdoor air temp.detection) NOTE : 1.The part of the broken line indicates the circuit for optional parts.
A.B Address board SW11(A.B) Switch (1st digit address set)
TB2 SW12(A.B) Switch (2nd digit address set)
2.❈A in the chart is the connector for a drain pump test run
Power source terminal bed
TB5 Transmission terminal bed SW14(A.B) Switch (connection No.set) operation. (The Drain Pump operates continuously if the
TB15 Transmission terminal bed SW1(A.B) Switch(for mode selection) connector is inserted and the power is supplied.) After the test
F1 Fuse AC250V 6.3A F SW2(I.B) Switch(for capacity code)
<F2> Fuse AC250V 5A F SW3(I.B) Switch(for mode selection) run, make sure to remove the ❈A connector.
T Transformer SW4(I.B) Switch(for model selection) 3.The wirings to TB2,TB5 (shown in dotted line) are field work.
<DP> Drain Pump SW7(A.B) Switch(for model selection)
4.Mark indicates terminal bed, connector, board
LEV Electronic linear expan. valve X04 ~ X06 Aux.relay
S.B Surge absorber board insertion connector or fastening connector of control board.
Inside < > is the optional parts.
6. Options

Description Model Applicable capacity


PAC-KE88LAF P80
Long life filter
PAC-KE89LAF P140
PAC-KE80TBA-F P80
Filter box
PAC-KE140TBA-F P140
Drain water lift-up kit PAC-KE04DM-F P80/P140

VMH-A-F
PEFY-P-

2- 75
PEFY-P-
VMH-A-F

2- 76
Ceiling mounted built-in PDFY-P-VM-A

CONTENTS

1. Specifications ·································································2-78

2. Capacity Tables ······························································2-79


2-1 Cooling Capacity(PUMY) ················································2-79
2-2 Heating Capacity(PUMY) ················································2-81
2-3 Cooling Capacity(Y/R2-8·10·13HP) ·······························2-82
2-4 Heating Capacity(Y/R2-8·10·13HP) ·······························2-84
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ······················2-85

PDFY-P-VM-A
2-6 Heating Capacity(Big Y, Super Y, Big R2) ······················2-87
2-7 Cooling Capacity(WY, WR2) ········································ 2-88
2-8 Heating Capacity(WY, WR2) ········································ 2-89

3. Sound Levels ·······························································2-90


3-1 Noise levels ································································· 2-90
3-2 N/C curves ·································································· 2-90
3-3 Fan characteristics curves ·············································2-94

4. External Dimensions ····················································2-95

5. Electrical Wiring Diagrams ··········································· 2-97

6. Option ············································································· 2-99

2- 77
1. Specifications
PDFY-P20VM-A PDFY-P25VM-A PDFY-P32VM-A PDFY-P40VM-A PDFY-P50VM-A
Power source ~ 220-240V 50Hz / ~ 220V 60Hz
❇1 kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000 5,000
Heating capacity kW 2.5 3.2 4.0 5.0 6.3
Power consumption Cooling kW 0.11/0.12 0.13/0.15
(50/60Hz) Heating kW 0.11/0.12 0.13/0.15
Cooling A 0.53/0.58 0.60/0.71
Current
Heating A 0.53/0.58 0.60/0.71
External finish Galvanizing
Height mm 295
Dimension Width mm 710 960
Depth mm 735
Net weight kg 25.5 27 32 34
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1 Sirocco fan✕ 2
Airflow rate
m3/min 6.0-6.5-7.5-8.5 10.0-11.0-12.5-14.0
Fan (Lo-Mid2-Mid1-Hi)
External static
Pa 30/50/100
pressure ❇3
Type Single phase induction motor
Motor
Output ❇4 kW 0.075(at 240V)
Air filter ❇ 5 Synthethic fiber unwoven cloth filter(long life)
Gas
mm ø 12.7 ø 15.88
Refrigerant (Flare)
pipe dimension Liqud
mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension Outer diameter 32(VP-25)
Noise level (Lo-Mid2-Mid1-Hi) ❇ 7 dB(A) 28-30-33-36 34-36-37-39
PDFY-P-VM-A

PDFY-P63VM-A PDFY-P71VM-A PDFY-P80VM-A PDFY-P100VM-A PDFY-P125VM-A


Power source ~ 220-240V 50Hz / ~ 220V 60Hz
❇1 kW 7.1 8.0 9.0 11.2 14.0
Cooling capacity
❇2 kcal/h 6,300 7,100 8,000 10,000 12,500
Heating capacity ❇1 kW 8.0 9.0 10.0 12.5 16.0
Power Cooling kW 0.14/0.17 0.15/0.18 0.17/0.21 0.27-0.31/0.29 0.33-0.38/0.39
consumption Heating kW 0.14/0.17 0.15/0.18 0.17/0.21 0.27-0.31/0.29 0.33-0.38/0.39
Cooling A 0.68/0.82 0.72/0.88 0.82/1.01 1.28-1.34/1.36 1.55-1.63/1.84
Current
Heating A 0.68/0.82 0.72/0.88 0.82/1.01 1.28-1.34/1.36 1.55-1.63/1.84
External finish Galvanizing
Height mm 295 335
Dimension Width mm 1160 1510
Depth mm 735 775
Net weight kg 39 52
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 2
Airflow rate 19.5-28.0 24.0-34.0
m3/min 12.5-14.0-16.0-18.0 13.5-15.5-17.5-19.5 14.5-16.5-18.5-21.0
Fan (Lo-Mid2-Mid1-Hi) (Lo-Hi) (Lo-Hi)
External static
Pa 30/50/100 50/100/130
pressure ❇3
Type Single phase induction motor
Motor
Output ❇4 kW 0.078(at 240V) 0.140(at 240V) 0.190(at 240V)
Air filter ❇ 5 Synthethic fiber unwoven cloth filter(long life)
Gas mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension Outer diameter 32(VP-25)
Noise level (Lo-Mid2-Mid1-Hi) ❇ 7 dB(A) 30-34-36-39 32-35-37-40 34-37-40-42 34-42(37-44)❇6 40-45(42-46)❇6
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27 ˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20 ˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27 ˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 The external static pressure is set to 50Pa at factory shipment.
❇ 4 The value for Models 20-80 are that at the external static pressure of 100Pa, while the value for Models 100-
125 are that at the external static pressure of 130Pa.
❇ 5 Be sure to apply the air filter near the air inlet grille, and make the air inlet ductwork length 850mm or more.
❇ 6 The figure in ( ) indicates noise level at 240V/50Hz.
❇ 7 It is measured in anechoic room.

2- 78
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9
22.5 2.1 1.8 2.3 1.9 2.4 1.9 2.6 1.9
25.0 2.1 1.8 2.3 1.9 2.4 1.8 2.5 1.9
27.5 2.1 1.8 2.2 1.9 2.4 1.8 2.5 1.9
20
30.0 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.9
(2.2)
32.5 2.0 1.7 2.2 1.8 2.3 1.8 2.5 1.9
35.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9
37.5 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9
40.0 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.8
46.0 1.9 1.7 2.0 1.8 2.1 1.7 2.3 1.8
20.0 2.8 2.1 2.9 2.2 3.1 2.2 3.3 2.2
22.5 2.7 2.1 2.9 2.2 3.1 2.1 3.2 2.2
25.0 2.7 2.1 2.9 2.1 3.1 2.1 3.2 2.2
27.5 2.7 2.0 2.8 2.1 3.0 2.1 3.2 2.2
25
30.0 2.6 2.0 2.8 2.1 3.0 2.1 3.2 2.2
(2.8)
32.5 2.6 2.0 2.8 2.1 2.9 2.1 3.1 2.2
35.0 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.1
37.5 2.5 2.0 2.7 2.1 2.9 2.0 3.0 2.1
40.0 2.5 1.9 2.7 2.1 2.8 2.0 3.0 2.1
46.0 2.4 1.9 2.6 2.0 2.7 2.0 2.9 2.1
20.0 3.6 2.5 3.7 2.6 4.0 2.6 4.2 2.7
22.5 3.5 2.5 3.7 2.6 4.0 2.6 4.2 2.7
25.0 3.5 2.5 3.7 2.6 3.9 2.6 4.1 2.7
27.5 3.4 2.5 3.6 2.6 3.9 2.6 4.1 2.6

PDFY-P-VM-A
32 30.0 3.4 2.4 3.6 2.6 3.8 2.5 4.1 2.6
(3.6) 32.5 3.3 2.4 3.6 2.5 3.8 2.5 4.0 2.6
35.0 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6
37.5 3.2 2.4 3.5 2.5 3.7 2.5 3.9 2.6
40.0 3.2 2.4 3.4 2.5 3.6 2.5 3.9 2.5
46.0 3.1 2.3 3.3 2.4 3.5 2.4 3.7 2.5
20.0 4.5 3.3 4.7 3.4 5.0 3.4 5.3 3.5
22.5 4.4 3.3 4.6 3.4 5.0 3.4 5.2 3.5
25.0 4.3 3.2 4.6 3.4 4.9 3.4 5.2 3.5
27.5 4.3 3.2 4.6 3.4 4.9 3.3 5.1 3.4
40
30.0 4.2 3.2 4.5 3.3 4.8 3.3 5.1 3.4
(4.5)
32.5 4.2 3.1 4.4 3.3 4.7 3.3 5.0 3.4
35.0 4.1 3.1 4.4 3.3 4.7 3.2 5.0 3.4
37.5 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.3
40.0 4.0 3.1 4.3 3.2 4.5 3.2 4.8 3.3
46.0 3.8 3.0 4.1 3.2 4.3 3.1 4.6 3.2
20.0 5.5 4.1 5.8 4.2 6.2 4.2 6.6 4.3
22.5 5.5 4.0 5.8 4.2 6.2 4.2 6.5 4.3
25.0 5.4 4.0 5.7 4.2 6.1 4.1 6.4 4.3
27.5 5.3 4.0 5.7 4.1 6.0 4.1 6.4 4.2
50
30.0 5.3 3.9 5.6 4.1 5.9 4.1 6.3 4.2
(5.6)
32.5 5.2 3.9 5.5 4.1 5.9 4.0 6.2 4.2
35.0 5.1 3.8 5.5 4.0 5.8 4.0 6.2 4.1
37.5 5.0 3.8 5.4 4.0 5.7 4.0 6.1 4.1
40.0 5.0 3.8 5.3 4.0 5.6 3.9 6.0 4.1
46.0 4.8 3.7 5.1 3.9 5.4 3.8 5.8 4.0
20.0 7.0 5.1 7.4 5.3 7.9 5.3 8.3 5.4
22.5 6.9 5.0 7.3 5.3 7.8 5.2 8.2 5.4
25.0 6.9 5.0 7.3 5.2 7.7 5.2 8.2 5.3
27.5 6.8 5.0 7.2 5.2 7.7 5.2 8.1 5.3
63 30.0 6.7 4.9 7.1 5.2 7.5 5.1 8.0 5.3
(7.1) 32.5 6.6 4.9 7.0 5.1 7.5 5.1 7.9 5.2
35.0 6.5 4.8 6.9 5.1 7.3 5.0 7.8 5.2
37.5 6.4 4.8 6.8 5.0 7.2 5.0 7.7 5.2
40.0 6.3 4.7 6.7 5.0 7.2 4.9 7.6 5.1
46.0 6.1 4.6 6.5 4.9 6.9 4.8 7.3 5.0

2- 79
Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 7.9 5.8 8.3 6.0 8.9 6.0 9.4 6.1
22.5 7.8 5.7 8.2 5.9 8.8 5.9 9.3 6.1
25.0 7.7 5.7 8.2 5.9 8.7 5.9 9.2 6.0
27.5 7.6 5.6 8.1 5.9 8.6 5.8 9.1 6.0
71 30.0 7.5 5.6 8.0 5.8 8.5 5.8 9.0 6.0
(8.0) 32.5 7.4 5.5 7.9 5.8 8.4 5.7 8.9 5.9
35.0 7.3 5.4 7.8 5.7 8.3 5.7 8.8 5.9
37.5 7.2 5.4 7.7 5.7 8.2 5.6 8.7 5.8
40.0 7.1 5.4 7.6 5.6 8.1 5.6 8.6 5.8
46.0 6.8 5.2 7.3 5.5 7.7 5.4 8.2 5.6
20.0 8.9 6.3 9.4 6.6 10.0 6.5 10.6 6.7
22.5 8.8 6.2 9.3 6.5 9.9 6.5 10.4 6.6
25.0 8.7 6.2 9.2 6.5 9.8 6.4 10.4 6.6
27.5 8.6 6.1 9.1 6.4 9.7 6.4 10.3 6.6
80 30.0 8.5 6.1 9.0 6.4 9.5 6.3 10.2 6.5
(9.0) 32.5 8.3 6.0 8.9 6.3 9.5 6.3 10.0 6.5
35.0 8.2 5.9 8.8 6.3 9.3 6.2 9.9 6.4
37.5 8.1 5.9 8.6 6.2 9.2 6.1 9.8 6.4
40.0 8.0 5.8 8.6 6.1 9.1 6.1 9.6 6.3
46.0 7.7 5.7 8.2 6.0 8.7 5.9 9.3 6.1
20.0 11.1 7.9 11.6 8.2 12.5 8.2 13.1 8.4
22.5 10.9 7.8 11.5 8.2 12.3 8.1 13.0 8.3
25.0 10.8 7.8 11.5 8.1 12.2 8.1 12.9 8.3
27.5 10.7 7.7 11.3 8.1 12.1 8.0 12.8 8.2
PDFY-P-VM-A

100 30.0 10.5 7.6 11.2 8.0 11.9 7.9 12.6 8.2
(11.2) 32.5 10.4 7.5 11.1 7.9 11.8 7.9 12.5 8.1
35.0 10.2 7.5 10.9 7.9 11.6 7.8 12.3 8.0
37.5 10.1 7.4 10.8 7.8 11.4 7.7 12.2 8.0
40.0 10.0 7.3 10.6 7.7 11.3 7.7 12.0 7.9
46.0 9.6 7.1 10.2 7.5 10.8 7.4 11.5 7.7
20.0 13.9 10.0 14.6 10.4 15.6 10.4 16.4 10.7
22.5 13.7 9.9 14.4 10.4 15.4 10.3 16.2 10.6
25.0 13.5 9.8 14.3 10.3 15.3 10.2 16.1 10.5
27.5 13.4 9.8 14.2 10.2 15.1 10.2 16.0 10.5
125 30.0 13.2 9.7 14.0 10.1 14.9 10.0 15.8 10.4
(14.0) 32.5 13.0 9.6 13.8 10.1 14.7 10.0 15.6 10.3
35.0 12.8 9.5 13.7 10.0 14.5 9.9 15.4 10.2
37.5 12.6 9.4 13.4 9.9 14.3 9.8 15.2 10.1
40.0 12.5 9.3 13.3 9.8 14.1 9.7 15.0 10.0
46.0 12.0 9.1 12.8 9.6 13.5 9.4 14.4 9.8

2- 80
2-2.Heating Capacity (In combination with PUMY)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 5.1 5.0 4.9
-10.0 1.7 1.6 1.6 -10.0 5.4 5.3 5.2
-5.0 1.9 1.9 1.9 -5.0 6.1 6.0 5.9
0.0 2.2 2.1 2.1 0.0 6.9 6.9 6.8
20 2.5 2.3 2.3 2.3 63 2.5 7.4 7.3 7.2
6.0 2.5 2.5 2.5 6.0 8.0 8.0 7.9
7.5 2.6 2.6 2.5 7.5 8.3 8.3 7.9
10.0 2.8 2.7 2.5 10.0 8.8 8.8 7.9
12.5 2.9 2.8 2.5 12.5 9.4 8.8 7.9
15.5 3.1 2.8 2.5 15.5 9.8 8.8 7.9
-12.0 2.0 2.0 2.0 -12.0 5.7 5.6 5.5
-10.0 2.1 2.1 2.1 -10.0 6.0 5.9 5.8
-5.0 2.4 2.4 2.4 -5.0 6.9 6.8 6.7
0.0 2.8 2.8 2.7 0.0 7.8 7.7 7.6
25 2.5 3.0 2.9 2.9 71 2.5 8.3 8.2 8.1
6.0 3.2 3.2 3.2 6.0 9.1 9.0 8.9
7.5 3.3 3.3 3.2 7.5 9.4 9.3 8.9
10.0 3.5 3.5 3.2 10.0 9.9 9.9 8.9
12.5 3.7 3.5 3.2 12.5 10.5 9.9 8.9
15.5 3.9 3.5 3.2 15.5 11.1 9.9 8.9
-12.0 2.5 2.5 2.5 -12.0 6.4 6.2 6.1
-10.0 2.7 2.6 2.6 -10.0 6.7 6.6 6.5
-5.0 3.1 3.0 3.0 -5.0 7.6 7.5 7.4
0.0 3.5 3.4 3.4 0.0 8.7 8.6 8.5
32 2.5 3.7 3.7 3.6 80 2.5 9.2 9.2 9.0

PDFY-P-VM-A
6.0 4.0 4.0 3.9 6.0 10.1 10.0 9.9
7.5 4.2 4.1 4.0 7.5 10.4 10.4 9.9
10.0 4.4 4.4 4.0 10.0 11.1 11.0 9.9
12.5 4.7 4.4 4.0 12.5 11.7 11.0 9.9
15.5 4.9 4.4 4.0 15.5 12.3 11.0 9.9
-12.0 3.2 3.1 3.1 -12.0 8.0 7.8 7.7
-10.0 3.4 3.3 3.2 -10.0 8.4 8.2 8.1
-5.0 3.8 3.8 3.7 -5.0 9.6 9.4 9.3
0.0 4.3 4.3 4.2 0.0 10.9 10.7 10.6
40 2.5 4.6 4.6 4.5 100 2.5 11.5 11.4 11.3
6.0 5.0 5.0 4.9 6.0 12.6 12.5 12.3
7.5 5.2 5.2 5.0 7.5 13.0 12.9 12.4
10.0 5.5 5.5 5.0 10.0 13.8 13.7 12.4
12.5 5.9 5.5 5.0 12.5 14.6 13.8 12.4
15.5 6.2 5.5 5.0 15.5 15.4 13.8 12.4
-12.0 4.0 3.9 3.9 -12.0 10.2 10.0 9.8
-10.0 4.2 4.2 4.1 -10.0 10.7 10.6 10.4
-5.0 4.8 4.8 4.7 -5.0 12.2 12.1 11.9
0.0 5.5 5.4 5.3 0.0 13.9 13.8 13.6
2.5 5.8 5.8 5.7 2.5 14.8 14.7 14.5
50 125
6.0 6.3 6.3 6.2 6.0 16.1 16.0 15.8
7.5 6.6 6.5 6.2 7.5 16.7 16.6 15.8
10.0 7.0 6.9 6.2 10.0 17.7 17.6 15.8
12.5 7.4 7.0 6.2 12.5 18.7 17.7 15.8
15.5 7.7 7.0 6.2 15.5 19.7 17.7 15.8

2- 81
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8
22.5 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.4 1.8 2.5 1.8
25.0 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.8 2.3 1.9 2.4 1.8 2.5 1.8
27.5 2.1 1.8 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.9 2.4 1.8 2.5 1.8
20
30.0 2.1 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.5 1.8
(2.2)
32.5 2.0 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.4 1.8
35.0 2.0 1.7 2.1 1.8 2.2 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8
37.5 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8
40.0 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.2 1.8 2.3 1.8 2.4 1.8
43.0 2.0 1.7 2.0 1.8 2.1 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.3 1.7
20.0 2.7 2.1 2.8 2.1 2.9 2.1 3.0 2.1 3.0 2.2 3.1 2.1 3.2 2.0
22.5 2.7 2.1 2.8 2.1 2.9 2.1 2.9 2.1 3.0 2.1 3.1 2.1 3.2 2.0
25.0 2.7 2.0 2.7 2.1 2.9 2.0 2.9 2.1 3.0 2.1 3.1 2.1 3.2 2.0
27.5 2.7 2.0 2.7 2.1 2.8 2.0 2.9 2.1 2.9 2.1 3.1 2.1 3.2 2.0
25
30.0 2.6 2.0 2.7 2.1 2.8 2.0 2.9 2.0 2.9 2.1 3.0 2.1 3.1 2.0
(2.8)
32.5 2.6 2.0 2.7 2.1 2.8 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.1 2.0
35.0 2.6 2.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.1 2.0
37.5 2.5 2.0 2.6 2.0 2.7 2.0 2.8 2.0 2.8 2.1 2.9 2.0 3.1 2.0
40.0 2.5 2.0 2.6 2.0 2.7 2.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.0
43.0 2.5 1.9 2.5 2.0 2.7 2.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.0
20.0 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5 3.9 2.6 4.0 2.5 4.2 2.4
22.5 3.5 2.5 3.6 2.5 3.7 2.5 3.8 2.5 3.9 2.6 4.0 2.5 4.1 2.4
25.0 3.5 2.5 3.5 2.5 3.7 2.5 3.7 2.5 3.8 2.6 4.0 2.5 4.1 2.4
27.5 3.4 2.5 3.5 2.5 3.6 2.5 3.7 2.5 3.8 2.5 3.9 2.5 4.1 2.4
PDFY-P-VM-A

32 30.0 3.4 2.4 3.5 2.5 3.6 2.4 3.7 2.5 3.7 2.5 3.9 2.5 4.0 2.4
(3.6) 32.5 3.3 2.4 3.4 2.5 3.6 2.4 3.6 2.4 3.7 2.5 3.9 2.4 4.0 2.4
35.0 3.3 2.4 3.4 2.5 3.5 2.4 3.6 2.4 3.7 2.5 3.8 2.4 4.0 2.4
37.5 3.3 2.4 3.3 2.4 3.5 2.4 3.6 2.4 3.6 2.5 3.8 2.4 3.9 2.4
40.0 3.2 2.4 3.3 2.4 3.5 2.4 3.5 2.4 3.6 2.5 3.7 2.4 3.9 2.3
43.0 3.2 2.4 3.3 2.4 3.4 2.4 3.5 2.4 3.6 2.4 3.7 2.4 3.8 2.3
20.0 4.4 3.3 4.5 3.3 4.7 3.3 4.8 3.3 4.9 3.4 5.0 3.3 5.2 3.2
22.5 4.4 3.2 4.5 3.3 4.6 3.2 4.7 3.3 4.8 3.4 5.0 3.3 5.2 3.2
25.0 4.3 3.2 4.4 3.3 4.6 3.2 4.7 3.2 4.8 3.3 5.0 3.3 5.1 3.2
27.5 4.3 3.2 4.4 3.3 4.5 3.2 4.6 3.2 4.7 3.3 4.9 3.2 5.1 3.2
40 30.0 4.2 3.2 4.3 3.2 4.5 3.2 4.6 3.2 4.7 3.3 4.9 3.2 5.0 3.1
(4.5) 32.5 4.2 3.2 4.3 3.2 4.5 3.2 4.5 3.2 4.6 3.3 4.8 3.2 5.0 3.1
35.0 4.1 3.1 4.2 3.2 4.4 3.1 4.5 3.2 4.6 3.3 4.8 3.2 5.0 3.1
37.5 4.1 3.1 4.2 3.2 4.4 3.1 4.5 3.2 4.5 3.3 4.7 3.2 4.9 3.1
40.0 4.1 3.1 4.1 3.2 4.3 3.1 4.4 3.1 4.5 3.2 4.7 3.2 4.9 3.1
43.0 4.0 3.1 4.1 3.1 4.3 3.1 4.4 3.1 4.4 3.2 4.6 3.1 4.8 3.1
20.0 5.5 4.0 5.6 4.1 5.8 4.0 5.9 4.0 6.0 4.2 6.3 4.1 6.5 3.9
22.5 5.4 4.0 5.5 4.1 5.8 4.0 5.9 4.0 6.0 4.1 6.2 4.0 6.4 3.9
25.0 5.4 4.0 5.5 4.1 5.7 4.0 5.8 4.0 5.9 4.1 6.2 4.0 6.4 3.9
27.5 5.3 3.9 5.4 4.0 5.7 3.9 5.8 4.0 5.9 4.1 6.1 4.0 6.3 3.9
50 30.0 5.3 3.9 5.4 4.0 5.6 3.9 5.7 4.0 5.8 4.1 6.0 4.0 6.3 3.9
(5.6) 32.5 5.2 3.9 5.3 4.0 5.5 3.9 5.7 3.9 5.8 4.1 6.0 4.0 6.2 3.8
35.0 5.2 3.9 5.3 4.0 5.5 3.9 5.6 3.9 5.7 4.0 5.9 3.9 6.2 3.8
37.5 5.1 3.8 5.2 3.9 5.4 3.8 5.5 3.9 5.7 4.0 5.9 3.9 6.1 3.8
40.0 5.0 3.8 5.2 3.9 5.4 3.8 5.5 3.9 5.6 4.0 5.8 3.9 6.0 3.8
43.0 5.0 3.8 5.1 3.9 5.3 3.8 5.4 3.8 5.5 4.0 5.8 3.9 6.0 3.8
20.0 7.0 5.1 7.1 5.2 7.4 5.0 7.5 5.1 7.7 5.2 8.0 5.1 8.2 4.9
22.5 6.9 5.0 7.0 5.1 7.3 5.0 7.5 5.0 7.6 5.2 7.9 5.1 8.2 4.9
25.0 6.8 5.0 7.0 5.1 7.2 5.0 7.4 5.0 7.5 5.2 7.8 5.0 8.1 4.9
27.5 6.7 4.9 6.9 5.1 7.2 4.9 7.3 5.0 7.5 5.1 7.7 5.0 8.0 4.9
63 30.0 6.7 4.9 6.8 5.0 7.1 4.9 7.2 4.9 7.4 5.1 7.7 5.0 8.0 4.8
(7.1) 32.5 6.6 4.9 6.7 5.0 7.0 4.9 7.2 4.9 7.3 5.1 7.6 4.9 7.9 4.8
35.0 6.5 4.8 6.7 4.9 7.0 4.8 7.1 4.9 7.2 5.0 7.5 4.9 7.8 4.8
37.5 6.5 4.8 6.6 4.9 6.9 4.8 7.0 4.9 7.2 5.0 7.5 4.9 7.7 4.8
40.0 6.4 4.8 6.5 4.9 6.8 4.8 7.0 4.8 7.1 5.0 7.4 4.9 7.7 4.7
43.0 6.3 4.7 6.4 4.8 6.7 4.7 6.9 4.8 7.0 4.9 7.3 4.8 7.6 4.7

2- 82
Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 7.8 5.7 8.0 5.8 8.3 5.7 8.5 5.7 8.6 5.9 9.0 5.7 9.3 5.6
22.5 7.8 5.7 7.9 5.8 8.2 5.7 8.4 5.7 8.6 5.9 8.9 5.7 9.2 5.5
25.0 7.7 5.6 7.8 5.8 8.2 5.6 8.3 5.7 8.5 5.8 8.8 5.7 9.1 5.5
27.5 7.6 5.6 7.8 5.7 8.1 5.6 8.2 5.6 8.4 5.8 8.7 5.7 9.0 5.5
71
30.0 7.5 5.6 7.7 5.7 8.0 5.5 8.2 5.6 8.3 5.8 8.6 5.6 9.0 5.5
(8.0)
32.5 7.4 5.5 7.6 5.6 7.9 5.5 8.1 5.6 8.2 5.7 8.6 5.6 8.9 5.4
35.0 7.4 5.5 7.5 5.6 7.8 5.5 8.0 5.5 8.2 5.7 8.5 5.6 8.8 5.4
37.5 7.3 5.4 7.4 5.6 7.8 5.4 7.9 5.5 8.1 5.7 8.4 5.5 8.7 5.4
40.0 7.2 5.4 7.4 5.5 7.7 5.4 7.8 5.5 8.0 5.6 8.3 5.5 8.6 5.4
43.0 7.1 5.3 7.3 5.5 7.6 5.4 7.7 5.4 7.9 5.6 8.2 5.5 8.5 5.3
20.0 8.8 6.3 9.0 6.4 9.4 6.2 9.5 6.2 9.7 6.4 10.1 6.2 10.4 6.1
22.5 8.7 6.2 8.9 6.3 9.3 6.2 9.5 6.2 9.6 6.4 10.0 6.2 10.4 6.0
25.0 8.6 6.2 8.8 6.3 9.2 6.1 9.4 6.2 9.5 6.3 9.9 6.2 10.3 6.0
27.5 8.6 6.1 8.7 6.2 9.1 6.1 9.3 6.1 9.5 6.3 9.8 6.1 10.2 6.0
80
30.0 8.5 6.1 8.6 6.2 9.0 6.1 9.2 6.1 9.4 6.3 9.7 6.1 10.1 5.9
(9.0)
32.5 8.4 6.0 8.6 6.1 8.9 6.0 9.1 6.0 9.3 6.2 9.6 6.1 10.0 5.9
35.0 8.3 6.0 8.5 6.1 8.8 6.0 9.0 6.0 9.2 6.2 9.5 6.0 9.9 5.9
37.5 8.2 5.9 8.4 6.1 8.7 5.9 8.9 6.0 9.1 6.2 9.5 6.0 9.8 5.8
40.0 8.1 5.9 8.3 6.0 8.6 5.9 8.8 5.9 9.0 6.1 9.4 6.0 9.7 5.8
43.0 8.0 5.8 8.2 6.0 8.5 5.8 8.7 5.9 8.9 6.1 9.3 5.9 9.6 5.8
20.0 11.0 7.9 11.2 8.0 11.6 7.8 11.9 7.8 12.1 8.1 12.5 7.9 13.0 7.6
22.5 10.9 7.8 11.1 8.0 11.5 7.8 11.8 7.8 12.0 8.0 12.4 7.8 12.9 7.6
25.0 10.8 7.7 11.0 7.9 11.4 7.7 11.6 7.8 11.9 8.0 12.3 7.8 12.8 7.5
27.5 10.6 7.7 10.9 7.8 11.3 7.7 11.5 7.7 11.8 7.9 12.2 7.7 12.7 7.5

PDFY-P-VM-A
100
30.0 10.5 7.6 10.8 7.8 11.2 7.6 11.4 7.7 11.6 7.9 12.1 7.7 12.5 7.5
(11.2)
32.5 10.4 7.6 10.6 7.7 11.1 7.6 11.3 7.6 11.5 7.8 12.0 7.6 12.4 7.4
35.0 10.3 7.5 10.5 7.7 11.0 7.5 11.2 7.6 11.4 7.8 11.9 7.6 12.3 7.4
37.5 10.2 7.5 10.4 7.6 10.9 7.5 11.1 7.5 11.3 7.7 11.8 7.5 12.2 7.3
40.0 10.1 7.4 10.3 7.6 10.8 7.4 11.0 7.5 11.2 7.7 11.6 7.5 12.1 7.3
43.0 9.9 7.3 10.2 7.5 10.6 7.3 10.8 7.4 11.1 7.6 11.5 7.5 12.0 7.3
20.0 13.7 9.9 14.0 10.1 14.6 9.9 14.8 10.0 15.1 10.3 15.7 10.0 16.2 9.7
22.5 13.6 9.9 13.9 10.1 14.4 9.8 14.7 9.9 15.0 10.2 15.5 9.9 16.1 9.6
25.0 13.4 9.8 13.7 10.0 14.3 9.8 14.6 9.8 14.8 10.1 15.4 9.9 16.0 9.6
27.5 13.3 9.7 13.6 9.9 14.1 9.7 14.4 9.8 14.7 10.1 15.3 9.8 15.8 9.5
125 30.0 13.2 9.7 13.4 9.9 14.0 9.7 14.3 9.7 14.6 10.0 15.1 9.8 15.7 9.5
(14.0) 32.5 13.0 9.6 13.3 9.8 13.9 9.6 14.1 9.7 14.4 10.0 15.0 9.7 15.5 9.4
35.0 12.9 9.5 13.2 9.7 13.7 9.5 14.0 9.6 14.3 9.9 14.8 9.7 15.4 9.4
37.5 12.7 9.5 13.0 9.7 13.6 9.5 13.9 9.5 14.1 9.9 14.7 9.6 15.3 9.4
40.0 12.6 9.4 12.9 9.6 13.4 9.4 13.7 9.5 14.0 9.8 14.6 9.6 15.1 9.3
43.0 12.4 9.3 12.7 9.5 13.3 9.3 13.6 9.4 13.8 9.7 14.4 9.5 15.0 9.2

2- 83
2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 27.0 size 15.0 20.0 25.0 27.0
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 5.4 5.3 5.2 5.2
-10.0 1.9 1.9 1.9 1.7 -10.0 6.1 6.0 6.0 5.5
-5.0 2.1 2.1 2.0 1.7 -5.0 6.9 6.8 6.2 5.5
0.0 2.4 2.4 2.0 1.7 0.0 7.6 7.5 6.2 5.5
2.5 2.5 2.5 2.0 1.7 2.5 8.0 7.9 6.2 5.5
20 6.0 2.5 2.5 2.0 1.7 63 6.0 8.1 8.0 6.2 5.5
7.5 2.6 2.5 2.0 1.7 7.5 8.4 8.0 6.2 5.5
10.0 2.8 2.5 2.0 1.7 10.0 9.0 8.0 6.2 5.5
12.5 3.0 2.5 2.0 1.7 12.5 9.6 8.0 6.2 5.5
15.5 3.0 2.5 2.0 1.7 15.5 9.7 8.0 6.2 5.5
-15.0 2.1 2.1 2.1 2.1 -15.0 6.0 5.9 5.9 5.9
-10.0 2.4 2.4 2.4 2.2 -10.0 6.9 6.8 6.7 6.2
-5.0 2.7 2.7 2.5 2.2 -5.0 7.7 7.6 7.0 6.2
0.0 3.1 3.0 2.5 2.2 0.0 8.6 8.5 7.0 6.2
2.5 3.2 3.2 2.5 2.2 2.5 9.0 8.9 7.0 6.2
25 71
6.0 3.2 3.2 2.5 2.2 6.0 9.1 9.0 7.0 6.2
7.5 3.4 3.2 2.5 2.2 7.5 9.5 9.0 7.0 6.2
10.0 3.6 3.2 2.5 2.2 10.0 10.1 9.0 7.0 6.2
12.5 3.8 3.2 2.5 2.2 12.5 10.8 9.0 7.0 6.2
15.5 3.9 3.2 2.5 2.2 15.5 10.9 9.0 7.0 6.2
-15.0 2.7 2.6 2.6 2.6 -15.0 6.7 6.6 6.5 6.5
-10.0 3.1 3.0 3.0 2.8 -10.0 7.6 7.5 7.4 6.9
-5.0 3.4 3.4 3.1 2.8 -5.0 8.6 8.5 7.8 6.9
0.0 3.8 3.8 3.1 2.8 0.0 9.5 9.4 7.8 6.9
2.5 4.0 4.0 3.1 2.8 2.5 10.0 9.9 7.8 6.9
PDFY-P-VM-A

32 80
6.0 4.0 4.0 3.1 2.8 6.0 10.1 10.0 7.8 6.9
7.5 4.2 4.0 3.1 2.8 7.5 10.5 10.0 7.8 6.9
10.0 4.5 4.0 3.1 2.8 10.0 11.2 10.0 7.8 6.9
12.5 4.8 4.0 3.1 2.8 12.5 12.0 10.0 7.8 6.9
15.5 4.8 4.0 3.1 2.8 15.5 12.1 10.0 7.8 6.9
-15.0 3.3 3.3 3.3 3.3 -15.0 8.4 8.2 8.2 8.1
-10.0 3.8 3.8 3.7 3.5 -10.0 9.6 9.4 9.3 8.6
-5.0 4.3 4.2 3.9 3.5 -5.0 10.7 10.6 9.8 8.6
0.0 4.8 4.7 3.9 3.5 0.0 11.9 11.8 9.8 8.6
2.5 5.0 5.0 3.9 3.5 2.5 12.5 12.4 9.8 8.6
40 100
6.0 5.1 5.0 3.9 3.5 6.0 12.6 12.5 9.8 8.6
7.5 5.3 5.0 3.9 3.5 7.5 13.2 12.5 9.8 8.6
10.0 5.6 5.0 3.9 3.5 10.0 14.1 12.5 9.8 8.6
12.5 6.0 5.0 3.9 3.5 12.5 15.0 12.5 9.8 8.6
15.5 6.1 5.0 3.9 3.5 15.5 15.1 12.5 9.8 8.6
-15.0 4.2 4.2 4.1 4.1 -15.0 10.7 10.6 10.5 10.4
-10.0 4.8 4.8 4.7 4.3 -10.0 12.2 12.1 11.9 11.0
-5.0 5.4 5.3 4.9 4.3 -5.0 13.7 13.6 12.5 11.0
0.0 6.0 5.9 4.9 4.3 0.0 15.3 15.1 12.5 11.0
50 2.5 6.3 6.2 4.9 4.3 125 2.5 16.0 15.8 12.5 11.0
6.0 6.4 6.3 4.9 4.3 6.0 16.2 16.0 12.5 11.0
7.5 6.6 6.3 4.9 4.3 7.5 16.8 16.0 12.5 11.0
10.0 7.1 6.3 4.9 4.3 10.0 18.0 16.0 12.5 11.0
12.5 7.5 6.3 4.9 4.3 12.5 19.1 16.0 12.5 11.0
15.5 7.6 6.3 4.9 4.3 15.5 19.4 16.0 12.5 11.0

2- 84
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.9 2.7 1.9
22.5 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.9 2.7 1.9
25.0 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9 2.5 1.9 2.7 1.8
27.5 2.0 1.7 2.1 1.8 2.2 1.8 2.4 1.9 2.5 1.9 2.6 1.8
20 30.0 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.9 2.5 1.9 2.6 1.8
32.5 2.0 1.7 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.8 2.6 1.8
35.0 1.9 1.7 2.0 1.8 2.1 1.7 2.3 1.9 2.4 1.8 2.5 1.8
37.5 1.9 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.8
40.0 1.9 1.7 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8
43.0 1.9 1.7 1.9 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.8
20.0 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.2 3.3 2.2 3.5 2.1
22.5 2.6 2.0 2.7 2.1 2.9 2.1 3.1 2.2 3.3 2.1 3.4 2.1
25.0 2.6 2.0 2.7 2.1 2.9 2.0 3.0 2.2 3.2 2.1 3.4 2.1
27.5 2.5 2.0 2.6 2.0 2.8 2.0 3.0 2.1 3.2 2.1 3.3 2.1
30.0 2.5 2.0 2.6 2.0 2.8 2.0 3.0 2.1 3.1 2.1 3.3 2.1
25
32.5 2.5 2.0 2.6 2.0 2.8 2.0 2.9 2.1 3.1 2.1 3.2 2.0
35.0 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.1 3.0 2.1 3.2 2.0
37.5 2.5 1.9 2.5 2.0 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.0
40.0 2.4 1.9 2.5 2.0 2.7 2.0 2.8 2.1 3.0 2.0 3.1 2.0
43.0 2.4 1.9 2.5 2.0 2.6 1.9 2.8 2.1 2.9 2.0 3.0 2.0
20.0 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6 4.2 2.6 4.5 2.6
22.5 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6 4.2 2.6 4.4 2.5
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.9 2.6 4.1 2.6 4.4 2.5
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.9 2.6 4.1 2.5 4.3 2.5
32 30.0 3.2 2.4 3.4 2.5 3.6 2.4 3.8 2.6 4.0 2.5 4.2 2.5
32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.8 2.5 4.0 2.5 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.9 2.5 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.4 4.0 2.4
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.6 2.5 3.8 2.4 4.0 2.4

PDFY-P-VM-A
43.0 3.1 2.3 3.2 2.4 3.4 2.3 3.5 2.4 3.7 2.4 3.9 2.3
20.0 4.1 3.1 4.3 3.3 4.7 3.3 5.0 3.4 5.3 3.4 5.6 3.3
22.5 4.1 3.1 4.3 3.3 4.6 3.2 4.9 3.4 5.2 3.4 5.5 3.3
25.0 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.4 5.2 3.3 5.5 3.3
27.5 4.1 3.1 4.2 3.2 4.5 3.2 4.8 3.4 5.1 3.3 5.4 3.3
30.0 4.0 3.1 4.2 3.2 4.5 3.2 4.8 3.3 5.0 3.3 5.3 3.2
40 32.5 4.0 3.1 4.2 3.2 4.4 3.1 4.7 3.3 5.0 3.3 5.2 3.2
35.0 4.0 3.1 4.1 3.2 4.4 3.1 4.6 3.3 4.9 3.2 5.1 3.2
37.5 3.9 3.0 4.1 3.1 4.3 3.1 4.6 3.3 4.8 3.2 5.1 3.1
40.0 3.9 3.0 4.0 3.1 4.3 3.1 4.5 3.2 4.7 3.2 5.0 3.1
43.0 3.9 3.0 4.0 3.1 4.2 3.1 4.4 3.2 4.7 3.2 4.9 3.1
20.0 5.2 3.9 5.4 4.0 5.8 4.0 6.2 4.3 6.6 4.2 7.0 4.1
22.5 5.2 3.9 5.4 4.0 5.8 4.0 6.2 4.2 6.5 4.2 6.9 4.1
25.0 5.1 3.8 5.3 4.0 5.7 4.0 6.1 4.2 6.4 4.1 6.8 4.1
27.5 5.1 3.8 5.3 4.0 5.6 3.9 6.0 4.2 6.3 4.1 6.7 4.0
30.0 5.0 3.8 5.2 3.9 5.6 3.9 5.9 4.1 6.2 4.1 6.6 4.0
50 32.5 5.0 3.8 5.2 3.9 5.5 3.9 5.8 4.1 6.2 4.0 6.5 3.9
35.0 4.9 3.8 5.1 3.9 5.4 3.9 5.8 4.1 6.1 4.0 6.4 3.9
37.5 4.9 3.7 5.1 3.9 5.4 3.8 5.7 4.0 6.0 4.0 6.3 3.9
40.0 4.9 3.7 5.0 3.8 5.3 3.8 5.6 4.0 5.9 3.9 6.2 3.8
43.0 4.8 3.7 5.0 3.8 5.2 3.8 5.5 4.0 5.8 3.9 6.1 3.8
20.0 6.5 4.8 6.9 5.0 7.4 5.0 7.9 5.3 8.4 5.2 8.9 5.2
22.5 6.5 4.8 6.8 5.0 7.3 5.0 7.8 5.3 8.3 5.2 8.7 5.1
25.0 6.5 4.8 6.8 5.0 7.2 5.0 7.7 5.2 8.1 5.2 8.6 5.1
27.5 6.4 4.8 6.7 5.0 7.2 4.9 7.6 5.2 8.0 5.1 8.5 5.0
30.0 6.4 4.8 6.6 4.9 7.1 4.9 7.5 5.2 7.9 5.1 8.4 5.0
63 32.5 6.3 4.7 6.6 4.9 7.0 4.9 7.4 5.1 7.8 5.0 8.2 4.9
35.0 6.3 4.7 6.5 4.9 6.9 4.8 7.3 5.1 7.7 5.0 8.1 4.9
37.5 6.2 4.7 6.4 4.8 6.8 4.8 7.2 5.0 7.6 4.9 8.0 4.8
40.0 6.2 4.7 6.4 4.8 6.7 4.7 7.1 5.0 7.5 4.9 7.9 4.8
43.0 6.1 4.6 6.3 4.8 6.6 4.7 7.0 4.9 7.3 4.8 7.7 4.7

2- 85
Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 7.4 5.5 7.7 5.7 8.3 5.7 8.9 6.0 9.4 5.9 10.0 5.8
22.5 7.4 5.5 7.7 5.7 8.2 5.7 8.8 6.0 9.3 5.9 9.8 5.8
25.0 7.3 5.4 7.6 5.6 8.2 5.6 8.7 5.9 9.2 5.8 9.7 5.7
27.5 7.2 5.4 7.5 5.6 8.1 5.6 8.6 5.9 9.0 5.8 9.6 5.7
71 30.0 7.2 5.4 7.5 5.6 8.0 5.5 8.5 5.8 8.9 5.7 9.4 5.6
32.5 7.1 5.4 7.4 5.5 7.9 5.5 8.3 5.8 8.8 5.7 9.3 5.6
35.0 7.1 5.3 7.3 5.5 7.8 5.5 8.2 5.7 8.7 5.6 9.1 5.5
37.5 7.0 5.3 7.2 5.5 7.7 5.4 8.1 5.7 8.6 5.6 9.0 5.5
40.0 7.0 5.3 7.2 5.4 7.6 5.4 8.0 5.6 8.4 5.5 8.9 5.4
43.0 6.9 5.2 7.1 5.4 7.5 5.3 7.9 5.6 8.3 5.5 8.7 5.4
20.0 8.3 6.0 8.7 6.2 9.4 6.2 10.0 6.6 10.6 6.5 11.2 6.4
22.5 8.3 6.0 8.7 6.2 9.3 6.2 9.9 6.5 10.5 6.4 11.1 6.3
25.0 8.2 6.0 8.6 6.2 9.2 6.1 9.8 6.4 10.3 6.3 10.9 6.2
27.5 8.1 5.9 8.5 6.1 9.1 6.1 9.6 6.4 10.2 6.3 10.8 6.2
30.0 8.1 5.9 8.4 6.1 9.0 6.0 9.5 6.3 10.0 6.2 10.6 6.1
80
32.5 8.0 5.9 8.3 6.0 8.9 6.0 9.4 6.3 9.9 6.2 10.4 6.1
35.0 8.0 5.8 8.2 6.0 8.8 5.9 9.3 6.2 9.8 6.1 10.3 6.0
37.5 7.9 5.8 8.1 6.0 8.6 5.9 9.1 6.2 9.6 6.1 10.1 5.9
40.0 7.8 5.8 8.1 5.9 8.5 5.8 9.0 6.1 9.5 6.0 10.0 5.9
43.0 7.7 5.7 8.0 5.9 8.4 5.8 8.9 6.1 9.3 5.9 9.8 5.8
20.0 10.3 7.5 10.8 7.8 11.6 7.8 12.5 8.2 13.2 8.1 14.0 8.0
22.5 10.3 7.5 10.8 7.8 11.5 7.8 12.3 8.2 13.0 8.1 13.8 7.9
25.0 10.2 7.5 10.7 7.7 11.4 7.7 12.1 8.1 12.8 8.0 13.6 7.8
27.5 10.1 7.4 10.6 7.7 11.3 7.7 12.0 8.0 12.7 7.9 13.4 7.8
100 30.0 10.1 7.4 10.5 7.6 11.2 7.6 11.8 8.0 12.5 7.8 13.2 7.7
32.5 10.0 7.4 10.3 7.6 11.0 7.5 11.7 7.9 12.3 7.8 13.0 7.6
35.0 9.9 7.3 10.2 7.5 10.9 7.5 11.5 7.8 12.1 7.7 12.8 7.6
37.5 9.8 7.3 10.1 7.5 10.8 7.4 11.4 7.8 12.0 7.6 12.6 7.5
PDFY-P-VM-A

40.0 9.7 7.2 10.0 7.4 10.6 7.4 11.2 7.7 11.8 7.6 12.4 7.4
43.0 9.6 7.2 9.9 7.4 10.5 7.3 11.0 7.6 11.6 7.5 12.2 7.3
20.0 12.9 9.5 13.5 9.9 14.6 9.9 15.6 10.5 16.5 10.3 17.5 10.2
22.5 12.9 9.5 13.5 9.9 14.4 9.9 15.4 10.4 16.3 10.2 17.2 10.1
25.0 12.8 9.5 13.3 9.8 14.3 9.8 15.2 10.3 16.1 10.1 17.0 10.0
27.5 12.7 9.4 13.2 9.8 14.1 9.7 15.0 10.2 15.8 10.1 16.7 9.9
125 30.0 12.6 9.4 13.1 9.7 13.9 9.6 14.8 10.1 15.6 10.0 16.5 9.8
32.5 12.5 9.3 12.9 9.6 13.8 9.6 14.6 10.1 15.4 9.9 16.2 9.7
35.0 12.4 9.3 12.8 9.6 13.6 9.5 14.4 10.0 15.2 9.8 16.0 9.6
37.5 12.3 9.2 12.7 9.5 13.5 9.4 14.2 9.9 15.0 9.7 15.7 9.5
40.0 12.2 9.2 12.5 9.4 13.3 9.3 14.0 9.8 14.8 9.6 15.5 9.4
43.0 12.0 9.1 12.4 9.4 13.1 9.3 13.8 9.7 14.5 9.5 15.2 9.3

2- 86
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 5.0 4.9 4.8 4.7
-10.0 1.8 1.8 1.7 1.7 -10.0 5.7 5.6 5.5 5.4
-5.0 2.0 2.0 2.0 1.9 -5.0 6.4 6.3 6.2 6.2
0.0 2.2 2.2 2.1 1.9 0.0 7.2 7.1 6.8 6.2
20 2.5 2.4 2.3 2.1 1.9 63 2.5 7.5 7.5 6.8 6.2
6.0 2.5 2.5 2.1 1.9 6.0 8.1 8.0 6.8 6.2
7.5 2.6 2.5 2.1 1.9 7.5 8.3 8.0 6.8 6.2
10.0 2.7 2.5 2.1 1.9 10.0 8.7 8.0 6.8 6.2
12.5 2.9 2.5 2.1 1.9 12.5 9.1 8.0 6.8 6.2
15.5 2.9 2.5 2.1 1.9 15.5 9.2 8.0 6.8 6.2
-15.0 2.0 2.0 1.9 1.9 -15.0 5.6 5.5 5.4 5.3
-10.0 2.3 2.2 2.2 2.2 -10.0 6.4 6.3 6.2 6.1
-5.0 2.6 2.5 2.5 2.5 -5.0 7.2 7.1 7.0 6.9
0.0 2.9 2.8 2.7 2.5 0.0 8.0 8.0 7.7 6.9
25 2.5 3.0 3.0 2.7 2.5 71 2.5 8.5 8.4 7.7 6.9
6.0 3.2 3.2 2.7 2.5 6.0 9.1 9.0 7.7 6.9
7.5 3.3 3.2 2.7 2.5 7.5 9.4 9.0 7.7 6.9
10.0 3.5 3.2 2.7 2.5 10.0 9.8 9.0 7.7 6.9
12.5 3.7 3.2 2.7 2.5 12.5 10.3 9.0 7.7 6.9
15.5 3.7 3.2 2.7 2.5 15.5 10.4 9.0 7.7 6.9
-15.0 2.5 2.5 2.4 2.4 -15.0 6.2 6.1 6.0 5.9
-10.0 2.8 2.8 2.8 2.7 -10.0 7.1 7.0 6.9 6.8
-5.0 3.2 3.2 3.1 3.1 -5.0 8.0 7.9 7.8 7.7
0.0 3.6 3.5 3.4 3.1 0.0 8.9 8.8 8.5 7.7
32 2.5 3.8 3.7 3.4 3.1 80 2.5 9.4 9.3 8.5 7.7
6.0 4.0 4.0 3.4 3.1 6.0 10.1 10.0 8.5 7.7
7.5 4.2 4.0 3.4 3.1 7.5 10.4 10.0 8.5 7.7
10.0 4.4 4.0 3.4 3.1 10.0 10.9 10.0 8.5 7.7
12.5 4.6 4.0 3.4 3.1 12.5 11.4 10.0 8.5 7.7
15.5 4.6 15.5 11.5 10.0 8.5 7.7

PDFY-P-VM-A
4.0 3.4 3.1
-15.0 3.1 3.1 3.0 3.0 -15.0 7.8 7.7 7.5 7.4
-10.0 3.6 3.5 3.5 3.4 -10.0 8.9 8.8 8.6 8.5
-5.0 4.0 4.0 3.9 3.9 -5.0 10.0 9.9 9.8 9.6
0.0 4.5 4.4 4.3 3.9 0.0 11.2 11.0 10.6 9.6
40 2.5 4.7 4.7 4.3 3.9 100 2.5 11.8 11.6 10.6 9.6
6.0 5.0 5.0 4.3 3.9 6.0 12.6 12.5 10.6 9.6
7.5 5.2 5.0 4.3 3.9 7.5 13.0 12.5 10.6 9.6
10.0 5.4 5.0 4.3 3.9 10.0 13.6 12.5 10.6 9.6
12.5 5.7 5.0 4.3 3.9 12.5 14.3 12.5 10.6 9.6
15.5 5.8 5.0 4.3 3.9 15.5 14.4 12.5 10.6 9.6
-15.0 3.9 3.9 3.8 3.7 -15.0 10.0 9.8 9.6 9.5
-10.0 4.5 4.4 4.3 4.3 -10.0 11.4 11.2 11.0 10.9
-5.0 5.0 5.0 4.9 4.9 -5.0 12.8 12.6 12.5 12.3
0.0 5.6 5.6 5.4 4.9 0.0 14.3 14.1 13.6 12.3
50 2.5 5.9 5.9 5.4 4.9 125 2.5 15.1 14.9 13.6 12.3
6.0 6.4 6.3 5.4 4.9 6.0 16.2 16.0 13.6 12.3
7.5 6.6 6.3 5.4 4.9 7.5 16.6 16.0 13.6 12.3
10.0 6.9 6.3 5.4 4.9 10.0 17.4 16.0 13.6 12.3
12.5 7.2 6.3 5.4 4.9 12.5 18.3 16.0 13.6 12.3
15.5 7.2 6.3 5.4 4.9 15.5 18.4 16.0 13.6 12.3

2- 87
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water
Unit temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.8 2.2 1.9 2.4 1.8 2.4 1.9 2.5 1.9 2.6 1.9 2.8 1.9
20 2.1 1.8 2.1 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.7 1.9
20 30 2.0 1.7 2.0 1.8 2.1 1.7 2.2 1.8 2.3 1.9 2.4 1.8 2.5 1.8
40 1.7 1.6 1.8 1.6 1.9 1.6 1.9 1.7 2.0 1.7 2.1 1.7 2.2 1.7
45 1.6 1.5 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.7 2.0 1.7 2.1 1.7
10 2.7 2.1 2.8 2.1 3.0 2.1 3.1 2.1 3.2 2.2 3.3 2.2 3.5 2.1
20 2.6 2.0 2.7 2.1 2.9 2.1 3.0 2.1 3.1 2.2 3.2 2.1 3.4 2.1
25 30 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.1 3.2 2.0
40 2.2 1.8 2.2 1.9 2.4 1.8 2.4 1.9 2.5 2.0 2.6 1.9 2.8 1.9
45 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.9 2.5 1.9 2.6 1.8
10 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.6 4.1 2.7 4.3 2.6 4.5 2.6
20 3.4 2.4 3.5 2.5 3.7 2.5 3.8 2.5 3.9 2.6 4.1 2.6 4.4 2.5
32 30 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.4
40 2.8 2.1 2.9 2.2 3.1 2.2 3.1 2.2 3.2 2.3 3.4 2.3 3.6 2.2
45 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.2 3.0 2.2 3.2 2.2 3.4 2.2
10 4.4 3.3 4.5 3.4 4.8 3.3 5.0 3.4 5.1 3.5 5.4 3.4 5.7 3.4
20 4.2 3.2 4.4 3.3 4.6 3.2 4.8 3.3 4.9 3.4 5.2 3.4 5.5 3.3
40 30 4.0 3.1 4.1 3.2 4.4 3.1 4.5 3.2 4.6 3.3 4.9 3.2 5.2 3.2
40 3.5 2.8 3.6 2.9 3.8 2.9 3.9 2.9 4.0 3.1 4.3 3.0 4.5 3.0
45 3.3 2.7 3.4 2.8 3.6 2.8 3.7 2.8 3.8 3.0 4.0 2.9 4.2 2.9
10 5.5 4.0 5.6 4.1 6.0 4.1 6.2 4.1 6.3 4.3 6.7 4.2 7.1 4.2
20 5.3 3.9 5.4 4.0 5.8 4.0 5.9 4.0 6.1 4.2 6.5 4.1 6.8 4.1
50 30 5.0 3.8 5.1 3.9 5.5 3.9 5.6 3.9 5.8 4.1 6.1 4.0 6.4 3.9
40 4.3 3.5 4.5 3.6 4.7 3.5 4.9 3.6 5.0 3.8 5.3 3.7 5.6 3.6
45 4.1 3.3 4.2 3.5 4.5 3.4 4.6 3.5 4.7 3.6 5.0 3.6 5.3 3.5
10 6.9 5.0 7.2 5.2 7.6 5.1 7.8 5.2 8.0 5.4 8.5 5.3 9.0 5.2
PDFY-P-VM-A

20 6.7 4.9 6.9 5.1 7.3 5.0 7.5 5.1 7.8 5.3 8.2 5.2 8.6 5.1
63 30 6.3 4.7 6.5 4.9 6.9 4.8 7.1 4.9 7.3 5.1 7.7 5.0 8.1 4.9
40 5.5 4.3 5.7 4.5 6.0 4.4 6.2 4.5 6.4 4.7 6.7 4.6 7.1 4.5
45 5.2 4.2 5.3 4.3 5.7 4.3 5.8 4.4 6.0 4.5 6.3 4.5 6.7 4.4
10 7.8 5.7 8.1 5.9 8.6 5.8 8.8 5.9 9.1 6.1 9.6 6.0 10.1 5.9
20 7.5 5.6 7.8 5.7 8.3 5.7 8.5 5.7 8.7 5.9 9.2 5.8 9.7 5.7
71 30 7.1 5.3 7.3 5.5 7.8 5.5 8.0 5.5 8.2 5.7 8.7 5.6 9.2 5.5
40 6.2 4.9 6.4 5.1 6.8 5.0 7.0 5.1 7.2 5.3 7.6 5.2 8.0 5.1
45 5.8 4.7 6.0 4.9 6.4 4.8 6.6 4.9 6.8 5.1 7.1 5.1 7.5 5.0
10 8.8 6.2 9.1 6.4 9.6 6.4 9.9 6.4 10.2 6.6 10.8 6.5 11.4 6.4
20 8.5 6.1 8.7 6.3 9.3 6.2 9.5 6.2 9.8 6.5 10.4 6.4 10.9 6.2
80 30 8.0 5.8 8.3 6.0 8.8 5.9 9.0 6.0 9.3 6.2 9.8 6.1 10.3 6.0
40 6.9 5.3 7.2 5.5 7.6 5.4 7.8 5.5 8.1 5.7 8.5 5.6 9.0 5.5
45 6.5 5.1 6.8 5.3 7.2 5.2 7.4 5.3 7.6 5.5 8.0 5.4 8.5 5.4
10 10.9 7.8 11.3 8.1 12.0 8.0 12.3 8.1 12.7 8.3 13.4 8.2 14.1 8.0
20 10.5 7.6 10.9 7.9 11.6 7.8 11.9 7.9 12.2 8.1 12.9 8.0 13.6 7.9
100 30 9.9 7.3 10.3 7.6 10.9 7.5 11.2 7.6 11.5 7.8 12.2 7.7 12.8 7.6
40 8.6 6.7 8.9 6.9 9.5 6.8 9.7 6.9 10.0 7.2 10.6 7.1 11.2 7.0
45 8.1 6.5 8.4 6.7 8.9 6.6 9.2 6.7 9.5 7.0 10.0 6.9 10.5 6.8
10 13.7 9.9 14.1 10.2 15.0 10.1 15.4 10.2 15.9 10.6 16.7 10.4 17.7 10.2
20 13.2 9.7 13.6 10.0 14.5 9.9 14.8 10.0 15.3 10.3 16.1 10.2 17.0 10.0
125 30 12.4 9.3 12.8 9.6 13.6 9.5 14.0 9.6 14.4 10.0 15.2 9.8 16.1 9.6
40 10.8 8.5 11.2 8.8 11.9 8.7 12.2 8.9 12.5 9.2 13.2 9.1 14.0 8.9
45 10.2 8.2 10.5 8.5 11.2 8.4 11.5 8.6 11.8 8.9 12.5 8.8 13.2 8.6

2- 88
2-8.Heatling Capacity (In combination with WY, WR2)
PDFY-P-VM-A SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp.
size 15 19 20 25 27
˚C SHC SHC SHC SHC SHC
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8

PDFY-P-VM-A
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 7.9 7.8 7.7 6.1 5.5
20 9.3 9.2 9.0 7.2 6.5
71 30 9.3 9.2 9.0 7.2 6.5
40 9.6 9.5 9.4 7.5 6.7
45 10.6 10.5 10.3 8.2 7.4
10 8.8 8.7 8.5 6.8 6.1
20 10.3 10.2 10.0 8.0 7.2
80 30 10.3 10.2 10.0 8.0 7.2
40 10.7 10.6 10.4 8.3 7.5
45 11.7 11.6 11.4 9.1 8.2
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1

2- 89
3. Sound Levels
3-1. Noise level

Ceiling mounted built - in Noise level at anechoic room


2.0m (Low-Middle2-Middle1-High) Unit : dB(A)

Model External static pressure❇


Low Mid High
0.27m

Aux. duct
PDFY-P20VM-A
PDFY-P25VM-A 26-28-31-33 28-30-33-36 31-35-39-41
PDFY-P32VM-A
PDFY-P40VM-A 35-35.5-36-37 34-36-37-39 37-39-40-41
PDFY-P50VM-A
1.5m

PDFY-P63VM-A 28-31-34-37 30-34-36-39 33-37-40-42


measurement location PDFY-P71VM-A 30-33-35-38 32-35-37-40 35-38-41-43
❇ PDFY-P20~80VM-A PDFY-P80VM-A 31-34-37-39 34-37-40-42 35-39-42-44
Low : 30Pa Mid : 50Pa High : 100Pa PDFY-P100VM-A 34-42(37-44) 36-44(38-45) 38-45(39-46)
PDFY-P100, 125VM-A
PDFY-P125VM-A 40-45(42-46) 42-46(43-47) 42-46(44-47)
Low : 50Pa Mid : 100Pa High : 130Pa

3-2. NC curves
PDFY-P20,25,32VM-A (External static
pressure 30Pa) PDFY-P20,25,32VM-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50
PDFY-P-VM-A

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P20,25,32VM-A (External static


pressure 100Pa) PDFY-P40VM-A (External static
pressure 30Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P40VM-A (External static PDFY-P40VM-A (External static


pressure 50Pa) pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 90
PDFY-P50VM-A (External static PDFY-P50VM-A (External static
pressure 30Pa) pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P50VM-A (External static PDFY-P63VM-A (External static


pressure 100Pa) pressure 30Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30

PDFY-P-VM-A
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P63VM-A (External static PDFY-P63VM-A (External static


pressure 50Pa) pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P71VM-A (External static PDFY-P71VM-A (External static


pressure 30Pa) pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 91
(External static PDFY-P80VM-A (External static
PDFY-P71VM-A pressure 100Pa) pressure 30Pa)
70 70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P80VM-A (External static PDFY-P80VM-A (External static


pressure 50Pa) pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
PDFY-P-VM-A

NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P100VM-A (External static


pressure 50Pa) PDFY-P100VM-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

220V-50/60Hz High speed High speed


220V-50/60Hz
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P100VM-A (External static


pressure 130Pa) PDFY-P125VM-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


220V-50/60Hz Low speed
220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 92
PDFY-P125VM-A (External static
pressure 100Pa) PDFY-P125VM-A (External static
pressure 130Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


High speed High speed
220V-50/60Hz Low speed 220V-50/60Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P100VM-A (External static


pressure 50Pa) PDFY-P100VM-A (External static
pressure 100Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa


240V-50Hz High speed High speed
Low speed
240V-50Hz Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30

PDFY-P-VM-A
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P100VM-A (External static


pressure 130Pa) PDFY-P125VM-A (External static
pressure 50Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed 240V-50Hz High speed


240V-50Hz Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PDFY-P125VM-A (External static


pressure 100Pa) PDFY-P125VM-A (External static
pressure 130Pa)
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20mPa

High speed High speed


240V-50Hz 240V-50Hz
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 93
3-3. Fan characteristics curves
PDFY-P40,50VM-A
PDFY-P20,25,32VM-A (External static PDFY-P63VM-A
(External static pressure 30,50,100Pa) (External static
pressure 30,50,100Pa) pressure 30,50,100Pa)
High speed

it
limit

a lim
High speed Low speed
High speed
100Pa

100P
Low speed

mit
Low speed

li
Pa
100
150 150 150

mit
it
a lim

a li
50P
50P

limit
limit

Pa
30
30Pa

Static pressure (Pa)

it
Static pressure (Pa)

lim
Static pressure (Pa)

Pa
50
100 100 100
100Pa 100Pa

it
100Pa

lim
Pa
30
50Pa

50 50 50
100Pa 50Pa
50Pa 100Pa 50Pa

100Pa

50Pa 50Pa
30Pa
30Pa
30Pa 30Pa

30Pa
0 30Pa 0 0
6 8 10 10 12 14 16 12 14 16 18 20
Airflow rate (m3/min) Airflow rate (m3/min) Airflow rate (m3/min)

PDFY-P100VM-A
(External static
PDFY-P71VM-A PDFY-P80VM-A pressure 50,100,130Pa) 50Hz
(External static (External static
pressure 30,50,100Pa) pressure 30,50,100Pa) High speed
Low speed

limit
High speed High speed

Pa
Low speed Low speed
limit

130
200
PDFY-P-VM-A

Pa

mit
limit
100

mit
150 150
a li

a li
Pa

50P

0P
100

10
it
lim

it
lim
Pa

Pa
50

50
150
Static pressure (Pa)

130Pa
mit
li
Static pressure (Pa)

Static pressure (Pa)

Pa
30
it
lim

100 100
Pa

100Pa
30

100Pa
100

130Pa 100Pa

50 50
50
100Pa 50Pa 50Pa
100Pa

30Pa 30Pa 50Pa 100Pa 50Pa


30Pa

50Pa 50Pa
30Pa

0 0 0
12 14 16 18 20 22 12 14 16 18 20 22 24 16 18 20 22 24 26 28 30
Airflow rate (m3/min) Airflow rate (m3/min) Airflow rate (m3/min)

PDFY-P125VM-A PDFY-P125VM-A
(External static (External static
PDFY-P100VM-A pressure 50,100,130Pa) 50Hz pressure 50,100,130Pa) 60Hz
(External static
pressure 50,100,130Pa) 250 High speed
60Hz 250 High speed
mit
mit

li

Low speed Low speed


li

Pa
Pa

130
130

High speed
limit

mit

Low speed
Pa

a li
130

mit

0P
mit

10
a li
a li

0P

200 200 200


0P

it
10

lim
10

Pa
it
a lim

50
50P
it
lim
Pa

Static pressure (Pa)

Static pressure (Pa)


50

150 150 150


Static pressure (Pa)

130Pa 130Pa 130Pa

100 100 100

100Pa 100Pa 100Pa

50 50 50
100Pa 130Pa

50Pa 130Pa 50Pa 130Pa

50Pa 100Pa 100Pa 50Pa

50Pa 50Pa

0 0 0
16 18 20 22 24 26 28 30 22 24 26 28 30 32 34 36 22 24 26 28 30 32 34 36
Airflow rate (m3/min) Airflow rate (m3/min) Airflow rate (m3/min)

2- 94
263
Note:1. Use M10 screw for the lifting bolt (field supply).
J
Model
B(Ceiling opening)
20~40 20 20
Gas pipe : LP ø12.7 ··············································· 1 Lifting bolt hole
Liquid pipe : HP ø6.35 ··············································· 4-14✕22 hole
2
63,71,80VM-A
PDFY-P20,25,32,40,50,

Model

31 58
50~60
Gas pipe : LP ø15.88 ··············································· 1
Liquid pipe : HP ø9.5 ··············································· 2

Drain hose VP-25 <flexible joint 200mm> (accessory)··· 3

(❇1) 3

566(Ceiling opening)
MODEL A B C D E F G H J
PDFY-P20·25·32VM-A 790 750 710 686 620 155 200 6 650

670(Lifting bolt pitch)


PDFY-P40·50VM-A 1040 1000 960 936 870 180 200 8 900 2
4. External Dimensions

64
PDFY-P63·71·80VM-A 1240 1200 1160 1136 1070 180 200 10 1100

735 1

670(Lifting bolt pitch) 34


12 D(Lifting bolt pitch) 12
64 126 Fresh air intake ø150 knock out hole 126
(❇1) 3 C
2
Control box 12 D(Lifting bolt pitch) 12
Power source E 50

111
123

2- 95
entry 20 20

172
G G G G F

265
Transmission

295
entry
21
36
27

(❇1) 3
ø1

28
2
Water filling port
198
168

Air filter 190 4-ø3 Mounting hole


1
Drain hole
17
17

140~300
1

47
(❇2)
H-ø3 hole 4-ø3.4 burring

8
(❇2) When fixing the panel to indoor unit, 20 20
this dimensinon may be 50~65.

300mm or less
A

J
600mmMAX

3
600

(❇1)When installing the drain water lifting-up


Unit : mm

Panel (option)
mech(option).
280

PDFY-P-VM-A
PDFY-P-VM-A

300
1450

1550(Ceiling opening)
20<270> 20
Lifting bolt hole
PDFY-P100, 125VM-A

4-14✕22 hole

31 58
Note:1. Use M10 screw for the lifting bolt (field supply).

Gas pipe : LP ø19.05 ··········································· 1


Liquid pipe : HP ø9.52 ··········································· 2
Drain hose VP-25 <flexible joint 200mm> (accessory)·· 3

566(Ceiling opening)
(❇1) 3

710(Lifting bolt pitch)


2

64
775 1
710(Lifting bolt pitch) 34
274 12 1486(Lifting bolt pitch) 12
(❇1) 3 Fresh air intake ø150 knock out hole 156
2 64 121
1510
Control box 12 1486(Lifting bolt pitch) 12
1420 50

2- 96
139

151
Power source 20 20

206
entry
200 200 200 200 200 200 155

305
335
Transmission
21
36

entry
72
ø1

28
(❇1) 3
Water filling port 1
190 2 4-ø3 Mounting hole
238
216

Air filter Drain hole


17 17

140~300

47
(❇2)
1

8
(❇2) When fixing the panel to indoor unit,
this dimensinon may be 50~65. 14-ø3 hole 4-ø3.4 burring
20 20

300mm or less

1590
600mmMAX

1450
600

(❇1)When installing the drain water lifting-up


Unit : mm

mech(option).
Panel (option)

320
INSIDE SECTION OF CONTROL BOX

I.B
TB15 (TRANSMISSION TERMINAL BED)
SW4 SW3 SW2 3 2
5 3 1
FAN2 CN3A 1 1 TO MA REMOTE CONTROLLER

REMOTE CENTRALLY REMOTE TB5 (TRANSMISSION TERMINAL BED)


1 SWITCH CONTROL INDICATION X1 ZNR S(SHIELD)
2 CN32 CN51 CN52 TO OUTDOOR UNIT
2 M2
3 CN42 FAN CON
CN2M 1 M1 BC CONTROLLER
PDFY-P20~P80VM-A

4
F M-NET REMOTE CONTROLLER
AC250V
(Red) (White) (Black) ( 6.3A F )
X4
CN81 CN20 CN21 CN29 CN31 CN60 CN3T CNT CNP FAN1 CND

A.B 1 2 3 4 5 6
8 7 6 5 4 3 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 3 1 3 1 3 1 5 3 1 3 1 S.B
ZNR1 CN1 1
SWA SWC SW5 CN62

8 T DSA1 3 TO NEXT INDOOR UNIT


SW1 7 C
CN82 6 Drain sensor L TB2
5 PULL BOX
F 0 12 9
0 1
9
0 1 4 CN31 N
E 3
2 3 1

7 8
7 8

2 3
2 3

B CD
345
1 PE
6 F2
FUSE(16A)
7 8 9A 4 5 6 4 5 6

SW14 SW12 SW11


(Connection No.) (2nd digit) (1st digit)
(White) 3 2 1 (White) 4 2 1 (Red) (5A) BREAKER(16A)
5. Electrical Wiring Diagrams

TO DUCT
PE
(Red) POWER SUPPLY

2- 97
TH21 TH22 TH23 ~ 220-240V 50Hz
LEV DP MF
DS 220V 60Hz

✻NOTE 3
For test of pumpout
SYMBOL EXPLANATION ✻NOTE 3
(after confirm drain pump out,
SYMBOL NAME SYMBOL NAME take this connector off.)
MF Fan motor TH22 Thermistor (piping temp.detection/liquid)
C ✻ Capacitor (for MF) TH23 Thermistor (piping temp.detection/gas) NOTE:1.TB2,TB5 shown in dotted line are
I.B Indoor controller board SWA(A.B) Switch (option parts) field work.
2.Mark indicates terminal bed,
A.B Address board SWC(A.B) Switch (option parts) connector, board insertion
TB2 Power source terminal bed SW11(A.B) Switch (1st digit address set) connector or fastening connector
TB5 Transmission terminal bed SW12(A.B) Switch (2nd digit address set) of control board.
TB15 Transmission terminal bed 3. :optional parts
SW14(A.B) Switch (connection No.set)
F Fuse AC250V 6.3A F SW1(A.B) Switch(for mode selection)
<F2> Fuse AC250V 5A F SW2(I.B) Switch(for capacity code)
T Transformer SW3(I.B) Switch(for mode selection)
<DP> Drain pump SW4(I.B) Switch(for model selection)
<DS> Drain sensor SW5(A.B) Switch(for voltage selection)
LEV Electronic linear expan. valve X1,X4 Aux.relay
TH21 Thermistor (inlet temp.detection) S.B Surge absorber board
Inside < > is the optional parts.

PDFY-P-VM-A
PDFY-P-VM-A

INSIDE SECTION OF CONTROL BOX

I.B
TB15 (TRANSMISSION TERMINAL BED)
SW4 SW3 SW2
3 2
CN3A 1 1 TO MA REMOTE CONTROLLER

REMOTE CENTRALLY REMOTE X06 X05 X04


1 SWITCH CONTROL INDICATION X01
2 CN32 CN51 CN52 ZNR 2
3 CN42 CN2M 1
4 TB5 (TRANSMISSION TERMINAL BED)
F
S(SHIELD)
AC250V
PDFY-P100·P125VM-A

(Red) (White) (Black) ( 6.3A F ) M2 TO OUTDOOR UNIT


CN81 CN20 CN21 CN29 CN31 CN60 CN3T CNT CNP FAN3 CND M1 BC CONTROLLER
1 2 3 4 5 6 M-NET REMOTE CONTROLLER
A.B 8 7 6 5 4 3 2 1 2 1 2 1 2 1 2 1 6 5 4 3 2 1 3 1 3 1 3 1 1 3 5 7 3 1 S.B
ZNR1 CN1 1
SW5 CN62

8 T DSA1 3 TO NEXT INDOOR UNIT


SW1 7 C
CN82 6 Drain sensor L TB2
5 PULL BOX
F 0 12 9
0 1
9
0 1 4 CN31 N
E 3
2 3 1

7 8
7 8

2 3
2 3

B CD
345
1 PE
6 F2
FUSE(16A)
7 8 9A 4 5 6 4 5 6

SW14 SW12 SW11


(Connection No.) (2nd digit) (1st digit)
(White) 3 2 1 (White) 4 2 1 (Red) (5A) BREAKER(16A)

TO DUCT
PE
POWER SUPPLY
TH22 TH23 (Red)
TH21

2- 98
LEV DP MF ~ 220-240V 50Hz
DS For test of pumpout 220V 60Hz

(after confirm drain pump out,


SYMBOL EXPLANATION ✻NOTE 3 ✻NOTE 3
C
take this connector off.)
SYMBOL NAME SYMBOL NAME
MF Fan motor TH22 Thermistor (piping temp.detection/liquid) (Red) (Blue)
✻The following external static pressure
C ✻ Capacitor (for MF) TH23 Thermistor (piping temp.detection/gas) 4 2 1 4 2 1
indicate using fore-sided duct flange.
I.B Indoor controller board SWA(A.B) Switch (option parts) Connector color
A.B Address board SWC(A.B) Switch (option parts) White··· In case of used 50Pa.
Red ··· In case of used 100Pa or 70Pa included <h.e.f>.
TB2 Power source terminal bed SW11(A.B) Switch (1st digit address set)
Blue ··· In case of used 130Pa or 100Pa included <h.e.f>.
TB5 Transmission terminal bed SW12(A.B) Switch (2nd digit address set) (<h.e.f>:high efficiency filter)
TB15 Transmission terminal bed SW14(A.B) Switch (connection No.set)
NOTE:1.TB2,TB5 shown in dotted line are
F Fuse AC250V 6.3A F SW1(A.B) Switch(for mode selection)
field work.
<F2> Fuse AC250V 5A F SW2(I.B) Switch(for capacity code) 2.Mark indicates terminal bed,
T Transformer SW3(I.B) Switch(for mode selection) connector, board insertion
<DP> Drain pump SW4(I.B) Switch(for model selection) connector or fastening connector
of control board.
<DS> Drain sensor SW5(A.B) Switch(for voltage selection)
3. :optional parts
LEV Electronic linear expan. valve X01,X04 X06 Aux.relay
˜ ✻Capacitor
TH21 Thermistor (inlet temp.detection) S.B Surge absorber board
MODELS 100 5.0µF
Inside < > is the optional parts.
MODELS 125 8.0µF
6. Option

Description Model Applicable capacity


P20/P25/P32/P40/P50
Drain water lift-up kit PAC-KD02DM-F
P63/P71/P80/P100/P125
PAC-KD32KDF-F P20/P25/P32
PAC-KD50KDF-F P40/P50
Square duct flange
PAC-KD80KDF-F P63/P71/P80

PAC-KD125KDF-F P100/P125
PAC-KD32EDF-F P20/P25/P32
PAC-KD50EDF-F P40/P50
Circular duct flange
PAC-KD80EDF-F P63/P71/P80

PAC-KD125EDF-F P100/P125

PAC-KD80RTB P20/P25/P32
Filter box for rear PAC-KD81RTB P40/P50
suction
PAC-KD83RTB P63/P71/P80

PAC-KD84RTB P100/P125

PDFY-P-VM-A
PAC-KD90DF P20/P25/P32

Canvas duct for bottom PAC-KD91DF P40/P50


suction PAC-KD93DF P63/P71/P80

PAC-KD94DF P100/P125

PAC-KD70TB P20/P25/P32

Filter box for bottom PAC-KD71TB P40/P50


suction
PAC-KD73TB P63/P71/P80

PAC-KD74TB P100/P125
PAC-KD30AF P20/P25/P32
High efficiency filter PAC-KD31AF P40/P50
65%
PAC-KD33AF P63/P71/P80

PAC-KD34AF P100/P125

PAC-KD40AF P20/P25/P32
High efficiency filter PAC-KD41AF P40/P50
90%
PAC-KD43AF P63/P71/P80

PAC-KD44AF P100/P125
CMP-J36DSW P20/P25/P32

Maintenance panel CMP-J56DSW P40/P50


with air intake
CMP-J90DSW P63/P71/P80

CMP-J160DSW P100/P125

2- 99
PDFY-P-VM-A

2- 100
Floor standing(Exposed) PFFY-P-VLEM-A
Floor standing(Concealed) PFFY-P-VLRM-A
CONTENTS

1. Specifications ·································································2-102

2. Capacity Tables ······························································2-103


2-1 Cooling Capacity(PUMY) ················································2-103
2-2 Heating Capacity(PUMY) ················································2-104
2-3 Cooling Capacity(Y/R2-8·10·13HP) ····························· 2-105
2-4 Heating Capacity(Y/R2-8·10·13HP) ····························· 2-106
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ······················2-107
2-6 Heating Capacity(Big Y, Super Y, Big R2) ······················2-108
2-7 Cooling Capacity(WY, WR2) ········································· 2-109
2-8 Heating Capacity(WY, WR2) ········································· 2-109

3. Sound Levels ·······························································2-110

VLEM-A/VLRM-A
3-1 Noise levels ······························································2-110

PFFY-P-
3-2 N/C curves ······························································2-110

4. External Dimensions ····················································2-111

5. Electrical Wiring Diagram ············································2-113

6. Temperature/Airflow distribution ····························2-114

2- 101
1. Specifications
PFFY-P20VLEM-A PFFY-P25VLEM-A PFFY-P32VLEM-A PFFY-P40VLEM-A PFFY-P50VLEM-A PFFY-P63VLEM-A
Power source ~ 220-240V 50Hz / ~ 208-230V 60Hz
❇1 kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000 5,000 6,300
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0 6.3 8.0
Power Cooling kW 0.04 / 0.06 0.06 / 0.07 0.065 / 0.075 0.085 / 0.09 0.1 / 0.11
consumption Heating kW 0.04 / 0.06 0.06 / 0.07 0.065 / 0.075 0.085 / 0.09 0.1 / 0.11
Cooling A 0.19 / 0.25 0.29 / 0.30 0.32 / 0.33 0.40 / 0.41 0.46 / 0.47
Current
Heating A 0.19 / 0.25 0.29 / 0.30 0.32 / 0.33 0.40 / 0.41 0.46 / 0.47
External finish(Munsel No.) Acrylic paint (5Y 8/1)
Height mm 630
Dimension Width mm 1,050 1,170 1,410
Depth mm 220
Net weight kg 23 25 26 30 32
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1 Sirocco fan✕ 2
Airflow rate ❇3 9.0-11.0
m3/min 5.5-6.5 7.0-9.0 12.0-14.0 12.0-15.5
Fan (Low-High)
External static 0
Pa
pressure
Type Single phase induction motor
Motor
Output kW 0.02 0.03 0.035 0.045
Air filter PP Honeycomb fabric (washable)
Gas ø 15.88
mm ø 12.7
Refrigerant (Flare)
pipe dimension Liquid mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension Accessary hose ø 27 (top end : ø 20)
Noise level (Low-High) ❇3 ❇4 ❇5 dB(A) 34-40 35-40 38-43 40-46

PFFY-P20VLRM-A PFFY-P25VLRM-A PFFY-P32VLRM-A PFFY-P40VLRM-A PFFY-P50VLRM-A PFFY-P63VLRM-A


Power source ~ 220-240V 50Hz / ~ 208-230V 60Hz
❇1 kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000 5,000 6,300
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0 6.3 8.0
Power Cooling kW 0.04 / 0.06 0.06 / 0.07 0.065 / 0.075 0.085 / 0.09 0.1 / 0.11
VLEM-A/VLRM-A

consumption Heating kW 0.04 / 0.06 0.06 / 0.07 0.065 / 0.075 0.085 / 0.09 0.1 / 0.11
Cooling A 0.19 / 0.25 0.29 / 0.30 0.32 / 0.33 0.40 / 0.41 0.46 / 0.47
PFFY-P-

Current
Heating A 0.19 / 0.25 0.29 / 0.30 0.32 / 0.33 0.40 / 0.41 0.46 / 0.47
External finish(Munsel No.) Galvanizing
Height mm 639
Dimension Width mm 886 1,006 1,246
Depth mm 220
Net weight kg 18.5 20 21 25 27
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 1 Sirocco fan✕ 2
Airflow rate ❇3 5.5-6.5 7.0-9.0 9.0-11.0 12.0-14.0 12.0-15.5
m3/min
Fan (Low-High)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.02 0.03 0.035 0.045
Air filter PP Honeycomb fabric (washable)
Gas mm ø 12.7 ø 15.88
Refrigerant (Flare)
pipe dimension Liquid mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension Accessary hose ø 27 (top end : ø 20)
Noise level (Low-High) ❇3 ❇4 ❇5 dB(A) 34-40 35-40 38-43 40-46

Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 Air flow rate/noise level are in ( Low-High)
❇ 4 Measured point : 1m✕1m, Power supply : AC240V/50Hz
·1dB(A) lower at AC230V/50Hz
·2dB(A) lower at AC220V/50Hz
·3dB(A) lower at 1.5m✕1.5m point
❇ 5 It is measured in anechoic room.

2- 102
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PFFY-P-VLEM-AVLRM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.9 2.3 2.0 2.4 2.0 2.6 2.1
22.5 2.1 1.9 2.3 2.0 2.4 2.0 2.6 2.1
25.0 2.1 1.9 2.3 2.0 2.4 2.0 2.5 2.0
27.5 2.1 1.9 2.2 2.0 2.4 2.0 2.5 2.0
20 30.0 2.1 1.9 2.2 2.0 2.3 1.9 2.5 2.0
(2.2) 32.5 2.0 1.9 2.2 2.0 2.3 1.9 2.5 2.0
35.0 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.0
37.5 2.0 1.8 2.1 1.9 2.2 1.9 2.4 2.0
40.0 2.0 1.8 2.1 1.9 2.2 1.9 2.4 2.0
46.0 1.9 1.8 2.0 1.9 2.1 1.9 2.3 1.9
20.0 2.8 2.2 2.9 2.3 3.1 2.3 3.3 2.3
22.5 2.7 2.2 2.9 2.3 3.1 2.3 3.2 2.3
25.0 2.7 2.2 2.9 2.3 3.1 2.2 3.2 2.3
27.5 2.7 2.1 2.8 2.3 3.0 2.2 3.2 2.3
25 30.0 2.6 2.1 2.8 2.2 3.0 2.2 3.2 2.3
(2.8) 32.5 2.6 2.1 2.8 2.2 2.9 2.2 3.1 2.3
35.0 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3
37.5 2.5 2.1 2.7 2.2 2.9 2.2 3.0 2.2
40.0 2.5 2.1 2.7 2.2 2.8 2.1 3.0 2.2
46.0 2.4 2.0 2.6 2.1 2.7 2.1 2.9 2.2
20.0 3.6 2.6 3.7 2.7 4.0 2.6 4.2 2.7
22.5 3.5 2.5 3.7 2.6 4.0 2.6 4.2 2.7
25.0 3.5 2.5 3.7 2.6 3.9 2.6 4.1 2.7
27.5 3.4 2.5 3.6 2.6 3.9 2.6 4.1 2.7
32 30.0 3.4 2.5 3.6 2.6 3.8 2.6 4.1 2.6
(3.6) 32.5 3.3 2.4 3.6 2.6 3.8 2.5 4.0 2.6
35.0 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6
37.5 3.2 2.4 3.5 2.5 3.7 2.5 3.9 2.6
40.0 3.2 2.4 3.4 2.5 3.6 2.5 3.9 2.6
46.0 3.1 2.3 3.3 2.4 3.5 2.4 3.7 2.5
20.0 4.5 3.2 4.7 3.3 5.0 3.3 5.3 3.4
22.5 4.4 3.2 4.6 3.3 5.0 3.3 5.2 3.4

VLEM-A/VLRM-A
25.0 4.3 3.1 4.6 3.3 4.9 3.3 5.2 3.4
27.5 4.3 3.1 4.6 3.3 4.9 3.2 5.1 3.3

PFFY-P-
40 30.0 4.2 3.1 4.5 3.2 4.8 3.2 5.1 3.3
(4.5) 32.5 4.2 3.1 4.4 3.2 4.7 3.2 5.0 3.3
35.0 4.1 3.0 4.4 3.2 4.7 3.2 5.0 3.3
37.5 4.1 3.0 4.3 3.2 4.6 3.1 4.9 3.2
40.0 4.0 3.0 4.3 3.1 4.5 3.1 4.8 3.2
46.0 3.8 2.9 4.1 3.1 4.3 3.0 4.6 3.1
20.0 5.5 4.0 5.8 4.2 6.2 4.2 6.6 4.3
22.5 5.5 4.0 5.8 4.2 6.2 4.2 6.5 4.3
25.0 5.4 4.0 5.7 4.2 6.1 4.1 6.4 4.2
27.5 5.3 3.9 5.7 4.1 6.0 4.1 6.4 4.2
50 30.0 5.3 3.9 5.6 4.1 5.9 4.1 6.3 4.2
(5.6) 32.5 5.2 3.9 5.5 4.1 5.9 4.0 6.2 4.2
35.0 5.1 3.8 5.5 4.0 5.8 4.0 6.2 4.1
37.5 5.0 3.8 5.4 4.0 5.7 4.0 6.1 4.1
40.0 5.0 3.8 5.3 4.0 5.6 3.9 6.0 4.1
46.0 4.8 3.7 5.1 3.9 5.4 3.8 5.8 4.0
20.0 7.0 5.0 7.4 5.2 7.9 5.2 8.3 5.3
22.5 6.9 5.0 7.3 5.2 7.8 5.2 8.2 5.3
25.0 6.9 4.9 7.3 5.2 7.7 5.1 8.2 5.3
27.5 6.8 4.9 7.2 5.1 7.7 5.1 8.1 5.2
63 30.0 6.7 4.8 7.1 5.1 7.5 5.0 8.0 5.2
(7.1) 32.5 6.6 4.8 7.0 5.0 7.5 5.0 7.9 5.1
35.0 6.5 4.7 6.9 5.0 7.3 4.9 7.8 5.1
37.5 6.4 4.7 6.8 4.9 7.2 4.9 7.7 5.1
40.0 6.3 4.6 6.7 4.9 7.2 4.8 7.6 5.0
46.0 6.1 4.5 6.5 4.8 6.9 4.7 7.3 4.9

2- 103
2-2.Heating Capacity (In combination with PUMY)

PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 3.2 3.1 3.1
-10.0 1.7 1.6 1.6 -10.0 3.4 3.3 3.2
-5.0 1.9 1.9 1.9 -5.0 3.8 3.8 3.7
0.0 2.2 2.1 2.1 0.0 4.3 4.3 4.2
20 2.5 2.3 2.3 2.3 40 2.5 4.6 4.6 4.5
6.0 2.5 2.5 2.5 6.0 5.0 5.0 4.9
7.5 2.6 2.6 2.5 7.5 5.2 5.2 5.0
10.0 2.8 2.7 2.5 10.0 5.5 5.5 5.0
12.5 2.9 2.8 2.5 12.5 5.9 5.5 5.0
15.5 3.1 2.8 2.5 15.5 6.2 5.5 5.0
-12.0 2.0 2.0 2.0 -12.0 4.0 3.9 3.9
-10.0 2.1 2.1 2.1 -10.0 4.2 4.2 4.1
-5.0 2.4 2.4 2.4 -5.0 4.8 4.8 4.7
0.0 2.8 2.8 2.7 0.0 5.5 5.4 5.3
25 2.5 3.0 2.9 2.9 50 2.5 5.8 5.8 5.7
6.0 3.2 3.2 3.2 6.0 6.3 6.3 6.2
7.5 3.3 3.3 3.2 7.5 6.6 6.5 6.2
10.0 3.5 3.5 3.2 10.0 7.0 6.9 6.2
12.5 3.7 3.5 3.2 12.5 7.4 7.0 6.2
15.5 3.9 3.5 3.2 15.5 7.7 7.0 6.2
-12.0 2.5 2.5 2.5 -12.0 5.1 5.0 4.9
-10.0 2.7 2.6 2.6 -10.0 5.4 5.3 5.2
-5.0 3.1 3.0 3.0 -5.0 6.1 6.0 5.9
0.0 3.5 3.4 3.4 0.0 6.9 6.9 6.8
32 2.5 3.7 3.7 3.6 63 2.5 7.4 7.3 7.2
6.0 4.0 4.0 3.9 6.0 8.0 8.0 7.9
7.5 4.2 4.1 4.0 7.5 8.3 8.3 7.9
10.0 4.4 4.4 4.0 10.0 8.8 8.8 7.9
12.5 4.7 4.4 4.0 12.5 9.4 8.8 7.9
15.5 4.9 4.4 4.0 15.5 9.8 8.8 7.9
VLEM-A/VLRM-A
PFFY-P-

2- 104
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.9 2.2 2.0 2.3 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.0
22.5 2.1 1.9 2.2 2.0 2.3 1.9 2.3 2.0 2.4 2.0 2.4 2.0 2.5 1.9
25.0 2.1 1.9 2.2 1.9 2.2 1.9 2.3 2.0 2.3 2.0 2.4 2.0 2.5 1.9
27.5 2.1 1.9 2.1 1.9 2.2 1.9 2.3 1.9 2.3 2.0 2.4 2.0 2.5 1.9
20 30.0 2.1 1.9 2.1 1.9 2.2 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 1.9
(2.2) 32.5 2.0 1.9 2.1 1.9 2.2 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.4 1.9
35.0 2.0 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.2 2.0 2.3 2.0 2.4 1.9
37.5 2.0 1.8 2.0 1.9 2.1 1.9 2.2 1.9 2.2 2.0 2.3 1.9 2.4 1.9
40.0 2.0 1.8 2.0 1.9 2.1 1.9 2.2 1.9 2.2 2.0 2.3 1.9 2.4 1.9
43.0 2.0 1.8 2.0 1.9 2.1 1.8 2.1 1.9 2.2 2.0 2.3 1.9 2.3 1.9
20.0 2.7 2.2 2.8 2.2 2.9 2.2 3.0 2.2 3.0 2.3 3.1 2.2 3.2 2.2
22.5 2.7 2.2 2.8 2.2 2.9 2.2 2.9 2.2 3.0 2.3 3.1 2.2 3.2 2.2
25.0 2.7 2.2 2.7 2.2 2.9 2.2 2.9 2.2 3.0 2.3 3.1 2.2 3.2 2.2
27.5 2.7 2.1 2.7 2.2 2.8 2.2 2.9 2.2 2.9 2.3 3.1 2.2 3.2 2.2
25 30.0 2.6 2.1 2.7 2.2 2.8 2.1 2.9 2.2 2.9 2.2 3.0 2.2 3.1 2.1
(2.8) 32.5 2.6 2.1 2.7 2.2 2.8 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.1 2.1
35.0 2.6 2.1 2.6 2.2 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.1 2.1
37.5 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.1 2.8 2.2 2.9 2.2 3.1 2.1
40.0 2.5 2.1 2.6 2.1 2.7 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.1
43.0 2.5 2.1 2.5 2.1 2.7 2.1 2.7 2.1 2.8 2.2 2.9 2.1 3.0 2.1
20.0 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5 3.9 2.6 4.0 2.5 4.2 2.5
22.5 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5 3.9 2.6 4.0 2.5 4.1 2.4
25.0 3.5 2.5 3.5 2.5 3.7 2.5 3.7 2.5 3.8 2.6 4.0 2.5 4.1 2.4
27.5 3.4 2.5 3.5 2.5 3.6 2.5 3.7 2.5 3.8 2.6 3.9 2.5 4.1 2.4
32 30.0 3.4 2.5 3.5 2.5 3.6 2.5 3.7 2.5 3.7 2.5 3.9 2.5 4.0 2.4
(3.6) 32.5 3.3 2.4 3.4 2.5 3.6 2.4 3.6 2.5 3.7 2.5 3.9 2.5 4.0 2.4
35.0 3.3 2.4 3.4 2.5 3.5 2.4 3.6 2.4 3.7 2.5 3.8 2.5 4.0 2.4
37.5 3.3 2.4 3.3 2.5 3.5 2.4 3.6 2.4 3.6 2.5 3.8 2.4 3.9 2.4
40.0 3.2 2.4 3.3 2.4 3.5 2.4 3.5 2.4 3.6 2.5 3.7 2.4 3.9 2.4
43.0 3.2 2.4 3.3 2.4 3.4 2.4 3.5 2.4 3.6 2.5 3.7 2.4 3.8 2.3
20.0 4.4 3.2 4.5 3.2 4.7 3.2 4.8 3.2 4.9 3.3 5.0 3.2 5.2 3.1
22.5 4.4 3.2 4.5 3.2 4.6 3.1 4.7 3.2 4.8 3.3 5.0 3.2 5.2 3.1

VLEM-A/VLRM-A
25.0 4.3 3.1 4.4 3.2 4.6 3.1 4.7 3.1 4.8 3.2 5.0 3.2 5.1 3.1
27.5 4.3 3.1 4.4 3.2 4.5 3.1 4.6 3.1 4.7 3.2 4.9 3.1 5.1 3.0

PFFY-P-
40 30.0 4.2 3.1 4.3 3.2 4.5 3.1 4.6 3.1 4.7 3.2 4.9 3.1 5.0 3.0
(4.5) 32.5 4.2 3.1 4.3 3.1 4.5 3.1 4.5 3.1 4.6 3.2 4.8 3.1 5.0 3.0
35.0 4.1 3.0 4.2 3.1 4.4 3.0 4.5 3.1 4.6 3.2 4.8 3.1 5.0 3.0
37.5 4.1 3.0 4.2 3.1 4.4 3.0 4.5 3.0 4.5 3.1 4.7 3.1 4.9 3.0
40.0 4.1 3.0 4.1 3.1 4.3 3.0 4.4 3.0 4.5 3.1 4.7 3.0 4.9 3.0
43.0 4.0 3.0 4.1 3.0 4.3 3.0 4.4 3.0 4.4 3.1 4.6 3.0 4.8 2.9
20.0 5.5 4.0 5.6 4.1 5.8 4.0 5.9 4.0 6.0 4.2 6.3 4.0 6.5 3.9
22.5 5.4 4.0 5.5 4.1 5.8 4.0 5.9 4.0 6.0 4.1 6.2 4.0 6.4 3.9
25.0 5.4 4.0 5.5 4.0 5.7 4.0 5.8 4.0 5.9 4.1 6.2 4.0 6.4 3.9
27.5 5.3 3.9 5.4 4.0 5.7 3.9 5.8 4.0 5.9 4.1 6.1 4.0 6.3 3.9
50 30.0 5.3 3.9 5.4 4.0 5.6 3.9 5.7 3.9 5.8 4.1 6.0 4.0 6.3 3.8
(5.6) 32.5 5.2 3.9 5.3 4.0 5.5 3.9 5.7 3.9 5.8 4.0 6.0 3.9 6.2 3.8
35.0 5.2 3.8 5.3 3.9 5.5 3.9 5.6 3.9 5.7 4.0 5.9 3.9 6.2 3.8
37.5 5.1 3.8 5.2 3.9 5.4 3.8 5.5 3.9 5.7 4.0 5.9 3.9 6.1 3.8
40.0 5.0 3.8 5.2 3.9 5.4 3.8 5.5 3.8 5.6 4.0 5.8 3.9 6.0 3.8
43.0 5.0 3.8 5.1 3.8 5.3 3.8 5.4 3.8 5.5 3.9 5.8 3.8 6.0 3.7
20.0 7.0 5.0 7.1 5.1 7.4 5.0 7.5 5.0 7.7 5.1 8.0 5.0 8.2 4.8
22.5 6.9 4.9 7.0 5.0 7.3 4.9 7.5 4.9 7.6 5.1 7.9 4.9 8.2 4.8
25.0 6.8 4.9 7.0 5.0 7.2 4.9 7.4 4.9 7.5 5.1 7.8 4.9 8.1 4.8
27.5 6.7 4.9 6.9 5.0 7.2 4.9 7.3 4.9 7.5 5.0 7.7 4.9 8.0 4.7
63 30.0 6.7 4.8 6.8 4.9 7.1 4.8 7.2 4.8 7.4 5.0 7.7 4.9 8.0 4.7
(7.1) 32.5 6.6 4.8 6.7 4.9 7.0 4.8 7.2 4.8 7.3 5.0 7.6 4.8 7.9 4.7
35.0 6.5 4.8 6.7 4.9 7.0 4.8 7.1 4.8 7.2 4.9 7.5 4.8 7.8 4.7
37.5 6.5 4.7 6.6 4.8 6.9 4.7 7.0 4.8 7.2 4.9 7.5 4.8 7.7 4.6
40.0 6.4 4.7 6.5 4.8 6.8 4.7 7.0 4.7 7.1 4.9 7.4 4.8 7.7 4.6
43.0 6.3 4.6 6.4 4.7 6.7 4.7 6.9 4.7 7.0 4.8 7.3 4.7 7.6 4.6

2- 105
2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)

PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 27.0 size 15.0 20.0 25.0 27.0
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 3.3 3.3 3.3 3.3
-10.0 1.9 1.9 1.9 1.7 -10.0 3.8 3.8 3.7 3.5
-5.0 2.1 2.1 2.0 1.7 -5.0 4.3 4.2 3.9 3.5
0.0 2.4 2.4 2.0 1.7 0.0 4.8 4.7 3.9 3.5
20 2.5 2.5 2.5 2.0 1.7 40 2.5 5.0 5.0 3.9 3.5
6.0 2.5 2.5 2.0 1.7 6.0 5.1 5.0 3.9 3.5
7.5 2.6 2.5 2.0 1.7 7.5 5.3 5.0 3.9 3.5
10.0 2.8 2.5 2.0 1.7 10.0 5.6 5.0 3.9 3.5
12.5 3.0 2.5 2.0 1.7 12.5 6.0 5.0 3.9 3.5
15.5 3.0 2.5 2.0 1.7 15.5 6.1 5.0 3.9 3.5
-15.0 2.1 2.1 2.1 2.1 -15.0 4.2 4.2 4.1 4.1
-10.0 2.4 2.4 2.4 2.2 -10.0 4.8 4.8 4.7 4.3
-5.0 2.7 2.7 2.5 2.2 -5.0 5.4 5.3 4.9 4.3
0.0 3.1 3.0 2.5 2.2 0.0 6.0 5.9 4.9 4.3
25 2.5 3.2 3.2 2.5 2.2 50 2.5 6.3 6.2 4.9 4.3
6.0 3.2 3.2 2.5 2.2 6.0 6.4 6.3 4.9 4.3
7.5 3.4 3.2 2.5 2.2 7.5 6.6 6.3 4.9 4.3
10.0 3.6 3.2 2.5 2.2 10.0 7.1 6.3 4.9 4.3
12.5 3.8 3.2 2.5 2.2 12.5 7.5 6.3 4.9 4.3
15.5 3.9 3.2 2.5 2.2 15.5 7.6 6.3 4.9 4.3
-15.0 2.7 2.6 2.6 2.6 -15.0 5.4 5.3 5.2 5.2
-10.0 3.1 3.0 3.0 2.8 -10.0 6.1 6.0 6.0 5.5
-5.0 3.4 3.4 3.1 2.8 -5.0 6.9 6.8 6.2 5.5
0.0 3.8 3.8 3.1 2.8 0.0 7.6 7.5 6.2 5.5
32 2.5 4.0 4.0 3.1 2.8 63 2.5 8.0 7.9 6.2 5.5
6.0 4.0 4.0 3.1 2.8 6.0 8.1 8.0 6.2 5.5
7.5 4.2 4.0 3.1 2.8 7.5 8.4 8.0 6.2 5.5
10.0 4.5 4.0 3.1 2.8 10.0 9.0 8.0 6.2 5.5
12.5 4.8 4.0 3.1 2.8 12.5 9.6 8.0 6.2 5.5
15.5 4.8 4.0 3.1 2.8 15.5 9.7 8.0 6.2 5.5
VLEM-A/VLRM-A
PFFY-P-

2- 106
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.1 2.6 2.0 2.7 2.0
22.5 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.1 2.6 2.0 2.7 2.0
25.0 2.0 1.8 2.1 1.9 2.2 1.9 2.4 2.0 2.5 2.0 2.7 2.0
27.5 2.0 1.8 2.1 1.9 2.2 1.9 2.4 2.0 2.5 2.0 2.6 2.0
20 30.0 2.0 1.8 2.1 1.9 2.2 1.9 2.3 2.0 2.5 2.0 2.6 2.0
32.5 2.0 1.8 2.0 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.6 2.0
35.0 1.9 1.8 2.0 1.9 2.1 1.9 2.3 2.0 2.4 2.0 2.5 1.9
37.5 1.9 1.8 2.0 1.9 2.1 1.9 2.2 2.0 2.4 2.0 2.5 1.9
40.0 1.9 1.8 2.0 1.9 2.1 1.8 2.2 2.0 2.3 2.0 2.4 1.9
43.0 1.9 1.8 1.9 1.9 2.1 1.8 2.2 2.0 2.3 1.9 2.4 1.9
20.0 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3 3.3 2.3 3.5 2.3
22.5 2.6 2.1 2.7 2.2 2.9 2.2 3.1 2.3 3.3 2.3 3.4 2.2
25.0 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.3 3.2 2.3 3.4 2.2
27.5 2.5 2.1 2.6 2.2 2.8 2.2 3.0 2.3 3.2 2.3 3.3 2.2
25 30.0 2.5 2.1 2.6 2.2 2.8 2.1 3.0 2.3 3.1 2.2 3.3 2.2
32.5 2.5 2.1 2.6 2.1 2.8 2.1 2.9 2.3 3.1 2.2 3.2 2.2
35.0 2.5 2.1 2.6 2.1 2.7 2.1 2.9 2.2 3.0 2.2 3.2 2.2
37.5 2.5 2.0 2.5 2.1 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.1
40.0 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.2 3.0 2.2 3.1 2.1
43.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.2 2.9 2.2 3.0 2.1
20.0 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.7 4.2 2.6 4.5 2.6
22.5 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6 4.2 2.6 4.4 2.6
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.9 2.6 4.1 2.6 4.4 2.5
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.9 2.6 4.1 2.6 4.3 2.5
32 30.0 3.2 2.4 3.4 2.5 3.6 2.5 3.8 2.6 4.0 2.5 4.2 2.5
32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.8 2.6 4.0 2.5 4.2 2.5
35.0 3.2 2.4 3.3 2.4 3.5 2.4 3.7 2.5 3.9 2.5 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.5 4.0 2.4
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.6 2.5 3.8 2.4 4.0 2.4
43.0 3.1 2.3 3.2 2.4 3.4 2.4 3.5 2.5 3.7 2.4 3.9 2.4
20.0 4.1 3.0 4.3 3.2 4.7 3.2 5.0 3.3 5.3 3.3 5.6 3.2
22.5 4.1 3.0 4.3 3.2 4.6 3.2 4.9 3.3 5.2 3.3 5.5 3.2
25.0 4.1 3.0 4.3 3.1 4.6 3.1 4.9 3.3 5.2 3.2 5.5 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.8 3.3 5.1 3.2 5.4 3.2
40 30.0 4.0 3.0 4.2 3.1 4.5 3.1 4.8 3.2 5.0 3.2 5.3 3.1
32.5 4.0 3.0 4.2 3.1 4.4 3.1 4.7 3.2 5.0 3.2 5.2 3.1
35.0 4.0 3.0 4.1 3.1 4.4 3.0 4.6 3.2 4.9 3.1 5.1 3.1
37.5 3.9 2.9 4.1 3.0 4.3 3.0 4.6 3.2 4.8 3.1 5.1 3.0

VLEM-A/VLRM-A
40.0 3.9 2.9 4.0 3.0 4.3 3.0 4.5 3.1 4.7 3.1 5.0 3.0
43.0 3.9 2.9 4.0 3.0 4.2 3.0 4.4 3.1 4.7 3.0 4.9 3.0

PFFY-P-
20.0 5.2 3.8 5.4 4.0 5.8 4.0 6.2 4.2 6.6 4.2 7.0 4.1
22.5 5.2 3.8 5.4 4.0 5.8 4.0 6.2 4.2 6.5 4.1 6.9 4.1
25.0 5.1 3.8 5.3 4.0 5.7 4.0 6.1 4.2 6.4 4.1 6.8 4.0
27.5 5.1 3.8 5.3 3.9 5.6 3.9 6.0 4.1 6.3 4.1 6.7 4.0
50 30.0 5.0 3.8 5.2 3.9 5.6 3.9 5.9 4.1 6.2 4.0 6.6 4.0
32.5 5.0 3.8 5.2 3.9 5.5 3.9 5.8 4.1 6.2 4.0 6.5 3.9
35.0 4.9 3.7 5.1 3.9 5.4 3.8 5.8 4.0 6.1 4.0 6.4 3.9
37.5 4.9 3.7 5.1 3.8 5.4 3.8 5.7 4.0 6.0 3.9 6.3 3.9
40.0 4.9 3.7 5.0 3.8 5.3 3.8 5.6 4.0 5.9 3.9 6.2 3.8
43.0 4.8 3.7 5.0 3.8 5.2 3.7 5.5 3.9 5.8 3.9 6.1 3.8
20.0 6.5 4.8 6.9 4.9 7.4 5.0 7.9 5.2 8.4 5.1 8.9 5.1
22.5 6.5 4.8 6.8 4.9 7.3 4.9 7.8 5.2 8.3 5.1 8.7 5.0
25.0 6.5 4.7 6.8 4.9 7.2 4.9 7.7 5.1 8.1 5.1 8.6 5.0
27.5 6.4 4.7 6.7 4.9 7.2 4.8 7.6 5.1 8.0 5.0 8.5 4.9
63 30.0 6.4 4.7 6.6 4.8 7.1 4.8 7.5 5.0 7.9 5.0 8.4 4.9
32.5 6.3 4.7 6.6 4.8 7.0 4.8 7.4 5.0 7.8 4.9 8.2 4.8
35.0 6.3 4.6 6.5 4.8 6.9 4.7 7.3 5.0 7.7 4.9 8.1 4.8
37.5 6.2 4.6 6.4 4.7 6.8 4.7 7.2 4.9 7.6 4.8 8.0 4.7
40.0 6.2 4.6 6.4 4.7 6.7 4.7 7.1 4.9 7.5 4.8 7.9 4.7
43.0 6.1 4.5 6.3 4.7 6.6 4.6 7.0 4.8 7.3 4.7 7.7 4.6

2- 107
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)
PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)
Unit Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 3.1 3.1 3.0 3.0
-10.0 1.8 1.8 1.7 1.7 -10.0 3.6 3.5 3.5 3.4
-5.0 2.0 2.0 2.0 1.9 -5.0 4.0 4.0 3.9 3.9
0.0 2.2 2.2 2.1 1.9 0.0 4.5 4.4 4.3 3.9
20 2.5 2.4 2.3 2.1 1.9 40 2.5 4.7 4.7 4.3 3.9
6.0 2.5 2.5 2.1 1.9 6.0 5.0 5.0 4.3 3.9
7.5 2.6 2.5 2.1 1.9 7.5 5.2 5.0 4.3 3.9
10.0 2.7 2.5 2.1 1.9 10.0 5.4 5.0 4.3 3.9
12.5 2.9 2.5 2.1 1.9 12.5 5.7 5.0 4.3 3.9
15.5 2.9 2.5 2.1 1.9 15.5 5.8 5.0 4.3 3.9
-15.0 2.0 2.0 1.9 1.9 -15.0 3.9 3.9 3.8 3.7
-10.0 2.3 2.2 2.2 2.2 -10.0 4.5 4.4 4.3 4.3
-5.0 2.6 2.5 2.5 2.5 -5.0 5.0 5.0 4.9 4.9
0.0 2.9 2.8 2.7 2.5 0.0 5.6 5.6 5.4 4.9
25 2.5 3.0 3.0 2.7 2.5 50 2.5 5.9 5.9 5.4 4.9
6.0 3.2 3.2 2.7 2.5 6.0 6.4 6.3 5.4 4.9
7.5 3.3 3.2 2.7 2.5 7.5 6.6 6.3 5.4 4.9
10.0 3.5 3.2 2.7 2.5 10.0 6.9 6.3 5.4 4.9
12.5 3.7 3.2 2.7 2.5 12.5 7.2 6.3 5.4 4.9
15.5 3.7 3.2 2.7 2.5 15.5 7.2 6.3 5.4 4.9
-15.0 2.5 2.5 2.4 2.4 -15.0 5.0 4.9 4.8 4.7
-10.0 2.8 2.8 2.8 2.7 -10.0 5.7 5.6 5.5 5.4
-5.0 3.2 3.2 3.1 3.1 -5.0 6.4 6.3 6.2 6.2
0.0 3.6 3.5 3.4 3.1 0.0 7.2 7.1 6.8 6.2
32 2.5 3.8 3.7 3.4 3.1 63 2.5 7.5 7.5 6.8 6.2
6.0 4.0 4.0 3.4 3.1 6.0 8.1 8.0 6.8 6.2
7.5 4.2 4.0 3.4 3.1 7.5 8.3 8.0 6.8 6.2
10.0 4.4 4.0 3.4 3.1 10.0 8.7 8.0 6.8 6.2
12.5 4.6 4.0 3.4 3.1 12.5 9.1 8.0 6.8 6.2
15.5 4.6 4.0 3.4 3.1 15.5 9.2 8.0 6.8 6.2
VLEM-A/VLRM-A
PFFY-P-

2- 108
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water
Unit temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.9 2.2 2.0 2.4 2.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.0
20 2.1 1.9 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.1 2.5 2.0 2.7 2.0
20 30 2.0 1.8 2.0 1.9 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 1.9
40 1.7 1.7 1.8 1.8 1.9 1.8 1.9 1.8 2.0 1.9 2.1 1.9 2.2 1.8
45 1.6 1.7 1.7 1.7 1.8 1.7 1.8 1.8 1.9 1.9 2.0 1.8 2.1 1.8
10 2.7 2.2 2.8 2.2 3.0 2.2 3.1 2.3 3.2 2.4 3.3 2.3 3.5 2.3
20 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.2 3.1 2.3 3.2 2.3 3.4 2.2
25 30 2.5 2.1 2.6 2.1 2.7 2.1 2.8 2.2 2.9 2.2 3.0 2.2 3.2 2.2
40 2.2 1.9 2.2 2.0 2.4 2.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.0
45 2.0 1.9 2.1 1.9 2.2 1.9 2.3 2.0 2.4 2.0 2.5 2.0 2.6 2.0
10 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.6 4.1 2.7 4.3 2.6 4.5 2.6
20 3.4 2.5 3.5 2.5 3.7 2.5 3.8 2.5 3.9 2.6 4.1 2.6 4.4 2.5
32 30 3.2 2.4 3.3 2.4 3.5 2.4 3.6 2.4 3.7 2.5 3.9 2.5 4.1 2.4
40 2.8 2.2 2.9 2.2 3.1 2.2 3.1 2.2 3.2 2.3 3.4 2.3 3.6 2.3
45 2.6 2.1 2.7 2.2 2.9 2.1 3.0 2.2 3.0 2.3 3.2 2.2 3.4 2.2
10 4.4 3.2 4.5 3.3 4.8 3.2 5.0 3.3 5.1 3.4 5.4 3.3 5.7 3.3
20 4.2 3.1 4.4 3.2 4.6 3.2 4.8 3.2 4.9 3.3 5.2 3.2 5.5 3.2
40 30 4.0 3.0 4.1 3.1 4.4 3.0 4.5 3.1 4.6 3.2 4.9 3.1 5.2 3.1
40 3.5 2.7 3.6 2.8 3.8 2.8 3.9 2.8 4.0 2.9 4.3 2.9 4.5 2.8
45 3.3 2.6 3.4 2.7 3.6 2.7 3.7 2.7 3.8 2.8 4.0 2.8 4.2 2.8
10 5.5 4.0 5.6 4.1 6.0 4.1 6.2 4.1 6.3 4.3 6.7 4.2 7.1 4.1
20 5.3 3.9 5.4 4.0 5.8 4.0 5.9 4.0 6.1 4.2 6.5 4.1 6.8 4.0
50 30 5.0 3.8 5.1 3.9 5.5 3.8 5.6 3.9 5.8 4.0 6.1 4.0 6.4 3.9
40 4.3 3.4 4.5 3.6 4.7 3.5 4.9 3.6 5.0 3.7 5.3 3.7 5.6 3.6
45 4.1 3.3 4.2 3.4 4.5 3.4 4.6 3.5 4.7 3.6 5.0 3.6 5.3 3.5
10 6.9 5.0 7.2 5.1 7.6 5.1 7.8 5.1 8.0 5.3 8.5 5.2 9.0 5.1
20 6.7 4.8 6.9 5.0 7.3 4.9 7.5 5.0 7.8 5.2 8.2 5.1 8.6 5.0
63 30 6.3 4.6 6.5 4.8 6.9 4.7 7.1 4.8 7.3 5.0 7.7 4.9 8.1 4.8
40 5.5 4.2 5.7 4.4 6.0 4.3 6.2 4.4 6.4 4.6 6.7 4.5 7.1 4.4
45 5.2 4.1 5.3 4.2 5.7 4.2 5.8 4.3 6.0 4.4 6.3 4.4 6.7 4.3

VLEM-A/VLRM-A
2-8.Heatling Capacity (In combination with WY, WR2)

PFFY-P-
PFFY-P-VLEM-A,VLRM-A SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp.
size 15 19 20 25 27
˚C SHC(kW) SHC(kW) SHC(kW) SHC(kW) SHC(kW)
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6

2- 109
3. Sound Levels
3-1. Noise level

Floor standing Noise level at anechoic room (Low-High) Unit : dB(A)

Model Noise level (A weighted)


1.0m
PFFY-P20VLEM-A
Measurement location PFFY-P20VLRM-A
PFFY-P25VLEM-A 34-40
PFFY-P25VLRM-A
PFFY-P32VLEM-A
PFFY-P32VLRM-A 35-40

1.0m
PFFY-P40VLEM-A
PFFY-P40VLRM-A 38-43
PFFY-P50VLEM-A
PFFY-P50VLRM-A

PFFY-P63VLEM-A 40-46
PFFY-P63VLRM-A

3-2. NC curves
PFFY-P20,25VLEM-A,VLRM-A PFFY-P32VLEM-A,VLRM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
Approximate minimum Approximate minimum
NC20 NC20
audible limit on audible limit on
continuous noise continuous noise
VLEM-A/VLRM-A

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)
PFFY-P-

PFFY-P40VLEM-A,VLRM-A PFFY-P50VLEM-A,VLRM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
Approximate minimum Approximate minimum
NC20 audible limit on NC20
audible limit on
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PFFY-P63VLEM-A,VLRM-A
70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed
60
NC60

50
NC50

40
NC40

30
NC30

20
Approximate minimum NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 110
Dimensions
Model A B C D E(Gas) F(Liquid) Air supply grille
PFFY -P20VLEM-A 1050 640 600 610 ø12.7 ø6.35
PFFY -P25VLEM-A 1050 640 600 610 ø12.7 ø6.35

(60)
63VLEM-A

PFFY -P32VLEM-A 1170 760 720 730 ø12.7 ø6.35


PFFY-P20,25,32,40,50,

PFFY -P40VLEM-A 1170 760 720 730 ø12.7 ø6.35 Remote controller

120
PFFY -P50VLEM-A 1410 1000 960 970 ø15.88 ø9.52 (PAR-F25MA)can be built-in.
(Program timer can not be
PFFY -P63VLEM-A 1410 1000 960 970 ø15.88 ø9.52

40
built-in together)

Air outlet C
A
220 80 B 170
15 15 2 ✕ 2-12 ✕16
Refrigerant piping flare Wall mounting hole
4. External Dimensions

35
connection(Gas) E : LP

20
108

Refrigeant piping flare


160

connection(Liquid) F : HP

Drain pan

50
100 35
Strainer 78
310

500
300

630

2- 111
Hose(accessory)
OD ø 27(TOP ø 20)

430
170

( 75 )
Air filter
Level adjusting screw 6 10 45 10
Air
4 pcs.(attached) inlet 90 220 D 220

25 170 B
2-12 ✕16
Floor mounting hole

21
Piping
space

183.5
106
Unit : mm

VLEM-A/VLRM-A
PFFY-P-
PFFY-P-
VLEM-A/VLRM-A

Dimensions
B
Model A B C D E F G(Gas) H(Liquid)

15
PFFY -P20VLRM-A 886 640 572 610 360 4 ø12.7 ø6.35
PFFY -P25VLRM-A 886 640 572 610 360 4 ø12.7 ø6.35
PFFY -P32VLRM-A 1006 760 692 730 480 5 ø12.7 ø6.35
63VLRM-A

132
PFFY -P40VLRM-A 1006 760 692 730 480 5 ø12.7 ø6.35
PFFY-P20,25,32,40,50,

PFFY -P50VLRM-A 1246 1000 932 970 720 7 ø15.88 ø9.52


PFFY -P63VLRM-A 1246 1000 932 970 720 7 ø15.88 ø9.52
Air outlet 167
A
220 C
2 ✕ F - ø 4.7
84 98 30 8 E
Duct mounting hole
49 120
2- ø 4.7 80 2 ✕ 2 - 12 ✕ 16

10
29
Duct mounting hole Refrigerant piping flare Wall mounting hole
connection(Gas) G : LP
90

Refrigeant piping flare


connection(Liquid) H : HP

Drain pan

50
100 35
Strainer
310

300

639
400
Hose(accessory)

2- 112
OD ø 27(TOP ø 20)

430
170

( 75 )
Air filter
9 15
Level adjusting screw Air
90 45
4 pcs.(attached) inlet
76 D 15
B

2-12 ✕ 16
Floor mounting hole
106
Unit : mm
INSIDE SECTION OF CONTROL BOX
I.B
SW4SW3 SW2 TB15 (TRANSMISSION TERMINAL BED)
3 2
CN3A 1 1 TO MA REMOTE CONTROLLER
REMOTE CENTRALLY REMOTE
1 SWITCH CONTROL INDICATION
2 CN32 CN51 CN52 F X06 X05 X04
3 CN42
4 AC250V TB5 (TRANSMISSION TERMINAL BED)
( 6.3A F
) ZNR 2
CN2M 1 S(SHIELD)
(Red) (White) (Black)
CN81 CN20 CN21 CN29 CN60 CN3T M2 TO OUTDOOR UNIT
CN31 CNT CND FAN3
M1 BC CONTROLLER
8 7 6 5 4 3 2 1 2 1 21 21 21 6 5 4 3 2 1 3 1 3 1 13 135 7 M-NET REMOTE CONTROLLER
A.B 123456 T

SW1 SW5 CN62


8
7 S.B
01 9 0 1 9 0 1 6 ZNR1
CN1 1
EF 2
CN82 5

7 8
2 3
7 8
2 3

B CD
345
4
89A
67 4 5 6
5 6
4
3 DSA1 3
2 TO NEXT INDOOR UNIT
SW14 SW12 SW11 1
(Connection No.) (2nd digit) (1st digit) L
N PULL BOX
PE

4 3 2 1
(White) TB2 FUSE(16A)
4 3 2 1
5. Electrical Wiring Diagram

21 3 1 6 5 4 3 2 1
(White) (Black) (White)
21 3 1 6 5 4 3 2 1 MF BREAKER(16A)

C POWER SUPPLY

2- 113
LEV ~ 220-240V 50Hz
TH21 TH22 TH23

SYMBOL EXPLANATION
SYMBOL NAME SYMBOL NAME
MF Fan motor TH22 Thermistor (piping temp.detection/liquid)
C ✻Capacitor (for MF) TH23 Thermistor (piping temp.detection/gas)
I.B Indoor controller board SW11(A.B) Switch (1st digit address set)
A.B Address board SW12(A.B) Switch (2nd digit address set)
TB2 Power source terminal bed SW14(A.B) Switch (connection No.set)
TB5 Transmission terminal bed SW1(A.B) Switch(for mode selection)
TB15 Transmission terminal bed SW2(I.B) Switch(for capacity code)
F Fuse AC250V 6.3A F SW3(I.B) Switch(for mode selection)
✻Capacitor
T Transformer SW4(I.B) Switch(for model selection) MODELS 20/25/32/40 1.5µF
LEV Electronic linear expan. valve SW5(A.B) Switch(for voltage selection) MODEL 50 2.0µF
S.B Surge absorber board X04~06 Aux.relay MODEL 63 2.5µF
TH21 Thermistor (inlet temp.detection)

VLEM-A/VLRM-A
PFFY-P-
6. Temperature/Airflow distribution
● Temperature distribution
<Cooling mode> <Heating mode>
Room temp. : 27˚C Room temp. : 20˚C
3 3
24 25
23 25

29
26 24
Height (m)

Height (m)
2 2
22
30

33
20

1 1

1 2 3 4 1 2 3 4

Floor distance (m) Floor distance (m)

● Airlow distribution

<Cooling mode> <Heating mode>


Room temp. : 27˚C Room temp. : 20˚C
Distance (m) Distance (m)
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
3.0 3.0
1.3
1.4

0. 0.8
0.7

0.6 6
5

2.5 2.5
0.9
1 .7
VLEM-A/VLRM-A

1.
8
0.7

0.
65
0.6
1.0

2.0 1. 2.0 0.
5
PFFY-P-

7 9
0.
0. 4
0. 75
Height (m)

Height (m)

4
1.
1.5 1.5 9
1.
8
0.
4
0. 0.
3 4
1.0 1.0 0.
1. 4
8
1.
9
0.
3 0.
0.5 0.5 3

0 0

2- 114
Cassette ceiling (1-way flow) PMFY-P-VBM-A

CONTENTS

1. Specifications ·································································2-116

2. Capacity Tables ······························································2-117


2-1 Cooling Capacity(PUMY) ················································2-117
2-2 Heating Capacity(PUMY) ················································2-117
2-3 Cooling Capacity(Y/R2-8·10·13HP) ······························· 2-118
2-4 Heating Capacity(Y/R2-8·10·13HP) ······························· 2-118
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ·······················2-119
2-6 Heating Capacity(Big Y, Super Y, Big R2) ·······················2-119
2-7 Cooling Capacity(WY, WR2) ·········································2-120
2-8 Heating Capacity(WY, WR2) ·········································2-120

3. Sound Levels ·······························································2-121


3-1 Noise levels ······························································· 2-121
3-2 N/C curves ··································································2-121

4. External Dimension ····················································2-122

5. Electrical Wiring Diagram ···········································2-123


PMFY-P-VBM-A
6. Temperature/Airflow distribution ································· 2-124

7. Options ············································································2-125

2- 115
1. Specifications
PMFY-P20VBM-A PMFY-P25VBM-A PMFY-P32VBM-A PMFY-P40VBM-A
Power source ~220-240V 50Hz / ~ 200V 60Hz
❇1 kW 2.2 2.8 3.6 4.5
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0
Cooling kW 0.042 0.044 0.054
Power consumption
Heating kW 0.042 0.044 0.054
Cooling A 0.20 0.21 0.26
Current
Heating A 0.20 0.21 0.26
External finish Panel : 0.98Y8.99/0.63
Height mm 230 (30)
Dimension ❇3 Width mm 812 (1000)
Depth mm 395 (470)
Net weight ❇3 kg 14 (3.0)
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Line flow fan ✕ 1
Airflow rate ❇3 m3/min 6.5-7.2-8.0-8.7 7.3-8.0-8.6-9.3 7.7-8.7-9.7-10.7
Fan (Low-Mid2-Mid1-High)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.028
Air filter PP Honeycomb fabric
Gas mm ø 12.7
Refrigerant (Flare)
pipe dimension Liquid mm ø 6.35
(Flare)
Drain pipe dimension VP-20
Noise level (Low-Mid2-Mid1-High) ❇4 dB(A) 27-30-33-35 32-34-36-37 33-35-37-39
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇3 External dimension / net weight are shown in (panel), and airflow rate/noise level are in (low-
middle2-middle1-high).
❇4 It is measured in anechoic room.
PMFY-P-VBM-A

2- 116
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.9 2.3 1.9 2.4 1.9 2.6 2.0
22.5 2.1 1.8 2.3 1.9 2.4 1.9 2.6 2.0
25.0 2.1 1.8 2.3 1.9 2.4 1.9 2.5 2.0
27.5 2.1 1.8 2.2 1.9 2.4 1.9 2.5 2.0
20 30.0 2.1 1.8 2.2 1.9 2.3 1.9 2.5 2.0
(2.2) 32.5 2.0 1.8 2.2 1.9 2.3 1.9 2.5 1.9
35.0 2.0 1.8 2.1 1.9 2.3 1.9 2.4 1.9
37.5 2.0 1.8 2.1 1.9 2.2 1.8 2.4 1.9
40.0 2.0 1.8 2.1 1.8 2.2 1.8 2.4 1.9
46.0 1.9 1.7 2.0 1.8 2.1 1.8 2.3 1.9
20.0 2.8 2.3 2.9 2.4 3.1 2.4 3.3 2.4
22.5 2.7 2.3 2.9 2.4 3.1 2.3 3.2 2.4
25.0 2.7 2.2 2.9 2.4 3.1 2.3 3.2 2.4
27.5 2.7 2.2 2.8 2.3 3.0 2.3 3.2 2.4
25 30.0 2.6 2.2 2.8 2.3 3.0 2.3 3.2 2.4
(2.8) 32.5 2.6 2.2 2.8 2.3 2.9 2.3 3.1 2.4
35.0 2.6 2.2 2.7 2.3 2.9 2.3 3.1 2.4
37.5 2.5 2.2 2.7 2.3 2.9 2.3 3.0 2.3
40.0 2.5 2.1 2.7 2.3 2.8 2.2 3.0 2.3
46.0 2.4 2.1 2.6 2.2 2.7 2.2 2.9 2.3
20.0 3.6 2.6 3.7 2.7 4.0 2.7 4.2 2.8
22.5 3.5 2.6 3.7 2.7 4.0 2.7 4.2 2.8
25.0 3.5 2.6 3.7 2.7 3.9 2.7 4.1 2.8
27.5 3.4 2.6 3.6 2.7 3.9 2.7 4.1 2.8
32 30.0 3.4 2.5 3.6 2.7 3.8 2.6 4.1 2.7
(3.6) 32.5 3.3 2.5 3.6 2.7 3.8 2.6 4.0 2.7
35.0 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.7
37.5 3.2 2.5 3.5 2.6 3.7 2.6 3.9 2.7
40.0 3.2 2.5 3.4 2.6 3.6 2.6 3.9 2.7
46.0 3.1 2.4 3.3 2.5 3.5 2.5 3.7 2.6
20.0 4.5 3.2 4.7 3.4 5.0 3.4 5.3 3.4
22.5 4.4 3.2 4.6 3.3 5.0 3.3 5.2 3.4
25.0 4.3 3.2 4.6 3.3 4.9 3.3 5.2 3.4
27.5 4.3 3.2 4.6 3.3 4.9 3.3 5.1 3.4
40 30.0 4.2 3.1 4.5 3.3 4.8 3.2 5.1 3.4
(4.5) 32.5 4.2 3.1 4.4 3.3 4.7 3.2 5.0 3.3
35.0 4.1 3.1 4.4 3.2 4.7 3.2 5.0 3.3
37.5 4.1 3.0 4.3 3.2 4.6 3.2 4.9 3.3
40.0 4.0 3.0 4.3 3.2 4.5 3.1 4.8 3.2
46.0 3.8 2.9 4.1 3.1 4.3 3.0 4.6 3.2

PMFY-P-VBM-A
2-2.Heating Capacity (In combination with PUMY)
PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
15.0 20.0 25.0 size 15.0 20.0 25.0
size
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 2.5 2.5 2.5
-10.0 1.7 1.6 1.6 -10.0 2.7 2.6 2.6
-5.0 1.9 1.9 1.9 -5.0 3.1 3.0 3.0
0.0 2.2 2.1 2.1 0.0 3.5 3.4 3.4
20 2.5 2.3 2.3 2.3 32 2.5 3.7 3.7 3.6
6.0 2.5 2.5 2.5 6.0 4.0 4.0 3.9
7.5 2.6 2.6 2.5 7.5 4.2 4.1 4.0
10.0 2.8 2.7 2.5 10.0 4.4 4.4 4.0
12.5 2.9 2.8 2.5 12.5 4.7 4.4 4.0
15.5 3.1 2.8 2.5 15.5 4.9 4.4 4.0
-12.0 2.0 2.0 2.0 -12.0 3.2 3.1 3.1
-10.0 2.1 2.1 2.1 -10.0 3.4 3.3 3.2
-5.0 2.4 2.4 2.4 -5.0 3.8 3.8 3.7
0.0 2.8 2.8 2.7 0.0 4.3 4.3 4.2
25 2.5 3.0 2.9 2.9 40 2.5 4.6 4.6 4.5
6.0 3.2 3.2 3.2 6.0 5.0 5.0 4.9
7.5 3.3 3.3 3.2 7.5 5.2 5.2 5.0
10.0 3.5 3.5 3.2 10.0 5.5 5.5 5.0
12.5 3.7 3.5 3.2 12.5 5.9 5.5 5.0
15.5 3.9 3.5 3.2 15.5 6.2 5.5 5.0

2- 117
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.2 1.9 2.3 1.9 2.3 1.9 2.4 2.0 2.5 1.9 2.6 1.9
22.5 2.1 1.8 2.2 1.9 2.3 1.8 2.3 1.9 2.4 2.0 2.4 1.9 2.5 1.9
25.0 2.1 1.8 2.2 1.9 2.2 1.8 2.3 1.9 2.3 1.9 2.4 1.9 2.5 1.9
27.5 2.1 1.8 2.1 1.9 2.2 1.8 2.3 1.9 2.3 1.9 2.4 1.9 2.5 1.9
20 30.0 2.1 1.8 2.1 1.9 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.5 1.8
(2.2) 32.5 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.9 2.4 1.8
35.0 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.8
37.5 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.8
40.0 2.0 1.8 2.0 1.8 2.1 1.8 2.2 1.8 2.2 1.9 2.3 1.9 2.4 1.8
43.0 2.0 1.7 2.0 1.8 2.1 1.8 2.1 1.8 2.2 1.9 2.3 1.8 2.3 1.8
20.0 2.7 2.3 2.8 2.3 2.9 2.3 3.0 2.3 3.0 2.4 3.1 2.3 3.2 2.3
22.5 2.7 2.2 2.8 2.3 2.9 2.3 2.9 2.3 3.0 2.4 3.1 2.3 3.2 2.3
25.0 2.7 2.2 2.7 2.3 2.9 2.3 2.9 2.3 3.0 2.4 3.1 2.3 3.2 2.3
27.5 2.7 2.2 2.7 2.3 2.8 2.2 2.9 2.3 2.9 2.4 3.1 2.3 3.2 2.3
25 30.0 2.6 2.2 2.7 2.3 2.8 2.2 2.9 2.3 2.9 2.4 3.0 2.3 3.1 2.2
(2.8) 32.5 2.6 2.2 2.7 2.3 2.8 2.2 2.8 2.3 2.9 2.3 3.0 2.3 3.1 2.2
35.0 2.6 2.2 2.6 2.3 2.7 2.2 2.8 2.2 2.9 2.3 3.0 2.3 3.1 2.2
37.5 2.5 2.2 2.6 2.2 2.7 2.2 2.8 2.2 2.8 2.3 2.9 2.3 3.1 2.2
40.0 2.5 2.2 2.6 2.2 2.7 2.2 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.2
43.0 2.5 2.1 2.5 2.2 2.7 2.2 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.2
20.0 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.6 3.9 2.7 4.0 2.6 4.2 2.6
22.5 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.6 3.9 2.7 4.0 2.6 4.1 2.6
25.0 3.5 2.6 3.5 2.6 3.7 2.6 3.7 2.6 3.8 2.7 4.0 2.6 4.1 2.5
27.5 3.4 2.6 3.5 2.6 3.6 2.6 3.7 2.6 3.8 2.7 3.9 2.6 4.1 2.5
32 30.0 3.4 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.7 2.7 3.9 2.6 4.0 2.5
(3.6) 32.5 3.3 2.5 3.4 2.6 3.6 2.5 3.6 2.6 3.7 2.6 3.9 2.6 4.0 2.5
35.0 3.3 2.5 3.4 2.6 3.5 2.5 3.6 2.5 3.7 2.6 3.8 2.6 4.0 2.5
37.5 3.3 2.5 3.3 2.6 3.5 2.5 3.6 2.5 3.6 2.6 3.8 2.6 3.9 2.5
40.0 3.2 2.5 3.3 2.5 3.5 2.5 3.5 2.5 3.6 2.6 3.7 2.5 3.9 2.5
43.0 3.2 2.5 3.3 2.5 3.4 2.5 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5
20.0 4.4 3.2 4.5 3.3 4.7 3.2 4.8 3.2 4.9 3.3 5.0 3.2 5.2 3.1
22.5 4.4 3.2 4.5 3.3 4.6 3.2 4.7 3.2 4.8 3.3 5.0 3.2 5.2 3.1
25.0 4.3 3.2 4.4 3.2 4.6 3.2 4.7 3.2 4.8 3.3 5.0 3.2 5.1 3.1
27.5 4.3 3.1 4.4 3.2 4.5 3.1 4.6 3.2 4.7 3.3 4.9 3.2 5.1 3.1
40 30.0 4.2 3.1 4.3 3.2 4.5 3.1 4.6 3.1 4.7 3.2 4.9 3.2 5.0 3.1
(4.5) 32.5 4.2 3.1 4.3 3.2 4.5 3.1 4.5 3.1 4.6 3.2 4.8 3.1 5.0 3.1
35.0 4.1 3.1 4.2 3.1 4.4 3.1 4.5 3.1 4.6 3.2 4.8 3.1 5.0 3.0
37.5 4.1 3.1 4.2 3.1 4.4 3.1 4.5 3.1 4.5 3.2 4.7 3.1 4.9 3.0
40.0 4.1 3.0 4.1 3.1 4.3 3.0 4.4 3.1 4.5 3.2 4.7 3.1 4.9 3.0
43.0 4.0 3.0 4.1 3.1 4.3 3.0 4.4 3.0 4.4 3.1 4.6 3.1 4.8 3.0
PMFY-P-VBM-A

2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)


PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 27.0 size 15.0 20.0 25.0 27.0
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 2.7 2.6 2.6 2.6
-10.0 1.9 1.9 1.9 1.7 -10.0 3.1 3.0 3.0 2.8
-5.0 2.1 2.1 2.0 1.7 -5.0 3.4 3.4 3.1 2.8
0.0 2.4 2.4 2.0 1.7 0.0 3.8 3.8 3.1 2.8
20 2.5 2.5 2.5 2.0 1.7 32 2.5 4.0 4.0 3.1 2.8
6.0 2.5 2.5 2.0 1.7 6.0 4.0 4.0 3.1 2.8
7.5 2.6 2.5 2.0 1.7 7.5 4.2 4.0 3.1 2.8
10.0 2.8 2.5 2.0 1.7 10.0 4.5 4.0 3.1 2.8
12.5 3.0 2.5 2.0 1.7 12.5 4.8 4.0 3.1 2.8
15.5 3.0 2.5 2.0 1.7 15.5 4.8 4.0 3.1 2.8
-15.0 2.1 2.1 2.1 2.1 -15.0 3.3 3.3 3.3 3.3
-10.0 2.4 2.4 2.4 2.2 -10.0 3.8 3.8 3.7 3.5
-5.0 2.7 2.7 2.5 2.2 -5.0 4.3 4.2 3.9 3.5
0.0 3.1 3.0 2.5 2.2 0.0 4.8 4.7 3.9 3.5
25 2.5 3.2 3.2 2.5 2.2 40 2.5 5.0 5.0 3.9 3.5
6.0 3.2 3.2 2.5 2.2 6.0 5.1 5.0 3.9 3.5
7.5 3.4 3.2 2.5 2.2 7.5 5.3 5.0 3.9 3.5
10.0 3.6 3.2 2.5 2.2 10.0 5.6 5.0 3.9 3.5
12.5 3.8 3.2 2.5 2.2 12.5 6.0 5.0 3.9 3.5
15.5 3.9 3.2 2.5 2.2 15.5 6.1 5.0 3.9 3.5

2- 118
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.6 2.0 2.7 1.9
22.5 2.0 1.8 2.1 1.9 2.3 1.9 2.4 2.0 2.6 2.0 2.7 1.9
25.0 2.0 1.8 2.1 1.9 2.2 1.8 2.4 2.0 2.5 1.9 2.7 1.9
27.5 2.0 1.8 2.1 1.8 2.2 1.8 2.4 2.0 2.5 1.9 2.6 1.9
20 30.0 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.5 1.9 2.6 1.9
32.5 2.0 1.8 2.0 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.6 1.9
35.0 1.9 1.7 2.0 1.8 2.1 1.8 2.3 1.9 2.4 1.9 2.5 1.9
37.5 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.4 1.9 2.5 1.8
40.0 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.8
43.0 1.9 1.7 1.9 1.8 2.1 1.8 2.2 1.9 2.3 1.9 2.4 1.8
20.0 2.6 2.2 2.7 2.3 2.9 2.3 3.1 2.4 3.3 2.4 3.5 2.4
22.5 2.6 2.2 2.7 2.3 2.9 2.3 3.1 2.4 3.3 2.4 3.4 2.3
25.0 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.2 2.4 3.4 2.3
27.5 2.5 2.2 2.6 2.3 2.8 2.2 3.0 2.4 3.2 2.4 3.3 2.3
25 30.0 2.5 2.2 2.6 2.2 2.8 2.2 3.0 2.4 3.1 2.3 3.3 2.3
32.5 2.5 2.1 2.6 2.2 2.8 2.2 2.9 2.4 3.1 2.3 3.2 2.3
35.0 2.5 2.1 2.6 2.2 2.7 2.2 2.9 2.3 3.0 2.3 3.2 2.3
37.5 2.5 2.1 2.5 2.2 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.3
40.0 2.4 2.1 2.5 2.2 2.7 2.2 2.8 2.3 3.0 2.3 3.1 2.2
43.0 2.4 2.1 2.5 2.2 2.6 2.2 2.8 2.3 2.9 2.3 3.0 2.2
20.0 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.8 4.2 2.7 4.5 2.7
22.5 3.3 2.5 3.5 2.6 3.7 2.6 4.0 2.7 4.2 2.7 4.4 2.7
25.0 3.3 2.5 3.4 2.6 3.7 2.6 3.9 2.7 4.1 2.7 4.4 2.6
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.9 2.7 4.1 2.7 4.3 2.6
32 30.0 3.2 2.5 3.4 2.6 3.6 2.5 3.8 2.7 4.0 2.6 4.2 2.6
32.5 3.2 2.5 3.3 2.5 3.5 2.5 3.8 2.7 4.0 2.6 4.2 2.6
35.0 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.6 3.9 2.6 4.1 2.5
37.5 3.2 2.4 3.3 2.5 3.5 2.5 3.7 2.6 3.8 2.6 4.0 2.5
40.0 3.1 2.4 3.2 2.5 3.4 2.5 3.6 2.6 3.8 2.6 4.0 2.5
43.0 3.1 2.4 3.2 2.5 3.4 2.4 3.5 2.6 3.7 2.5 3.9 2.5
20.0 4.1 3.1 4.3 3.2 4.7 3.2 5.0 3.4 5.3 3.3 5.6 3.3
22.5 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.4 5.2 3.3 5.5 3.3
25.0 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.3 5.2 3.3 5.5 3.2
27.5 4.1 3.0 4.2 3.2 4.5 3.1 4.8 3.3 5.1 3.2 5.4 3.2
40 30.0 4.0 3.0 4.2 3.1 4.5 3.1 4.8 3.3 5.0 3.2 5.3 3.2
32.5 4.0 3.0 4.2 3.1 4.4 3.1 4.7 3.2 5.0 3.2 5.2 3.1
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.9 3.2 5.1 3.1
37.5 3.9 3.0 4.1 3.1 4.3 3.0 4.6 3.2 4.8 3.1 5.1 3.1
40.0 3.9 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.7 3.1 5.0 3.1
43.0 3.9 2.9 4.0 3.0 4.2 3.0 4.4 3.1 4.7 3.1 4.9 3.0

PMFY-P-VBM-A
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)

PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 2.5 2.5 2.4 2.4
-10.0 1.8 1.8 1.7 1.7 -10.0 2.8 2.8 2.8 2.7
-5.0 2.0 2.0 2.0 1.9 -5.0 3.2 3.2 3.1 3.1
0.0 2.2 2.2 2.1 1.9 0.0 3.6 3.5 3.4 3.1
20 2.5 2.4 2.3 2.1 1.9 32 2.5 3.8 3.7 3.4 3.1
6.0 2.5 2.5 2.1 1.9 6.0 4.0 4.0 3.4 3.1
7.5 2.6 2.5 2.1 1.9 7.5 4.2 4.0 3.4 3.1
10.0 2.7 2.5 2.1 1.9 10.0 4.4 4.0 3.4 3.1
12.5 2.9 2.5 2.1 1.9 12.5 4.6 4.0 3.4 3.1
15.5 2.9 2.5 2.1 1.9 15.5 4.6 4.0 3.4 3.1
-15.0 2.0 2.0 1.9 1.9 -15.0 3.1 3.1 3.0 3.0
-10.0 2.3 2.2 2.2 2.2 -10.0 3.6 3.5 3.5 3.4
-5.0 2.6 2.5 2.5 2.5 -5.0 4.0 4.0 3.9 3.9
0.0 2.9 2.8 2.7 2.5 0.0 4.5 4.4 4.3 3.9
25 2.5 3.0 3.0 2.7 2.5 40 2.5 4.7 4.7 4.3 3.9
6.0 3.2 3.2 2.7 2.5 6.0 5.0 5.0 4.3 3.9
7.5 3.3 3.2 2.7 2.5 7.5 5.2 5.0 4.3 3.9
10.0 3.5 3.2 2.7 2.5 10.0 5.4 5.0 4.3 3.9
12.5 3.7 3.2 2.7 2.5 12.5 5.7 5.0 4.3 3.9
15.5 3.7 3.2 2.7 2.5 15.5 5.8 5.0 4.3 3.9

2- 119
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water
Unit temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.8 2.2 1.9 2.4 1.9 2.4 1.9 2.5 2.0 2.6 2.0 2.8 1.9
20 2.1 1.8 2.1 1.9 2.3 1.9 2.3 1.9 2.4 2.0 2.5 1.9 2.7 1.9
20 30 2.0 1.7 2.0 1.8 2.1 1.8 2.2 1.8 2.3 1.9 2.4 1.9 2.5 1.9
40 1.7 1.6 1.8 1.7 1.9 1.7 1.9 1.7 2.0 1.8 2.1 1.8 2.2 1.8
45 1.6 1.6 1.7 1.7 1.8 1.6 1.8 1.7 1.9 1.8 2.0 1.7 2.1 1.7
10 2.7 2.3 2.8 2.3 3.0 2.3 3.1 2.4 3.2 2.5 3.3 2.4 3.5 2.4
20 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.3 3.1 2.4 3.2 2.4 3.4 2.3
25 30 2.5 2.1 2.6 2.2 2.7 2.2 2.8 2.3 2.9 2.3 3.0 2.3 3.2 2.3
40 2.2 2.0 2.2 2.1 2.4 2.1 2.4 2.1 2.5 2.2 2.6 2.2 2.8 2.1
45 2.0 1.9 2.1 2.0 2.2 2.0 2.3 2.1 2.4 2.2 2.5 2.1 2.6 2.1
10 3.5 2.6 3.6 2.7 3.9 2.7 4.0 2.7 4.1 2.8 4.3 2.8 4.5 2.7
20 3.4 2.5 3.5 2.6 3.7 2.6 3.8 2.6 3.9 2.7 4.1 2.7 4.4 2.6
32 30 3.2 2.5 3.3 2.5 3.5 2.5 3.6 2.5 3.7 2.6 3.9 2.6 4.1 2.6
40 2.8 2.3 2.9 2.3 3.1 2.3 3.1 2.4 3.2 2.4 3.4 2.4 3.6 2.4
45 2.6 2.2 2.7 2.3 2.9 2.2 3.0 2.3 3.0 2.4 3.2 2.3 3.4 2.3
10 4.4 3.2 4.5 3.3 4.8 3.3 5.0 3.3 5.1 3.4 5.4 3.4 5.7 3.3
20 4.2 3.1 4.4 3.2 4.6 3.2 4.8 3.2 4.9 3.3 5.2 3.3 5.5 3.2
40 30 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.1 4.6 3.2 4.9 3.2 5.2 3.1
40 3.5 2.8 3.6 2.8 3.8 2.8 3.9 2.9 4.0 3.0 4.3 2.9 4.5 2.9
45 3.3 2.7 3.4 2.8 3.6 2.7 3.7 2.8 3.8 2.9 4.0 2.8 4.2 2.8

2-8.Heating Capacity (In combination with WY, WR2)

PMFY-P-VBM-A SHC:Sensible Heat Capacity(kW)


Water Indoor air temp.:˚CDB
Unit temp.
size 15 19 20 25 27
˚C SHC(kW) SHC(kW) SHC(kW) SHC(kW) SHC(kW)
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
PMFY-P-VBM-A

10 2.8 2.8 2.7 2.2 2.0


20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1

2- 120
3. Sound Levels
3-1. Noise level
Casette ceiling (VBM-A series)
Noise level at anechoic room
(Low-Middle2-Middle1-High) Unit : dB(A)

Model Noise level (A weighted)


PMFY-P20VBM-A 27-30-33-35
PMFY-P25VBM-A 32-34-36-37
PMFY-P32VBM-A
PMFY-P40VBM-A 33-35-37-39
1.5m

Measurement location

3-2. NC curves
PMFY-P20VBM-A PMFY-P25,32VBM-A
70 High speed
70 High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Middle1 speed Middle1 speed


Middle2 speed Middle2 speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PMFY-P40VBM-A
70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Middle1 speed
Middle2 speed
Low speed
60
NC60

PMFY-P-VBM-A
50
NC50

40
NC40

30
NC30

20
NC20

10
Approximate minimum
audible limit on
continuous noise
0
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 121
PMFY-P-VBM-A

1000 outer side of grille


Top 20 960 seiling opening 20 pipe cover ODø43
811 suspension bolt pitch 74.5 Refrigerant
74.5 Liquid pipe ODø6.35(1/4")
759 26 piping
26 Gas pipe ODø12.7(1/2")
20 20

28
45
20
Drainage piping PVC pipe:VP-20[ODø25(1')]

Details of fresh air intake hole

17.5
46 53
43

247
PMFY-P20,25,32,40VBM-A

4-ø2.8 Burring hole

ceiling opening
17.5

outer side of grille


69
ø100

28
45
20

430
4. External Dimension

470
Air outlet(lower) outer line of grille
Refrigirant pipe(gas)

340 suspension bolt pitch


ODø12.7 center of unit ø1
395
22

Knock out
302
254 812
Drainage pipe 250 288.5
141 759
PVC pipe:VP-20[ODø25] Terminal block for power supply
elect box

ø50

230

198

176
96

2- 122
108

(10)
(20)
( 56) Right side
drain pan Terminal biock for transmission Fresh air intake hole
Refrigirant Front
(96)
pipe(liquid)
ODø6.35 Installation space required
ceiling panel 1000 outer side of grille
around indoor unit
200 600 200
Left side

40
suspension bolt(M10 or W3/8)
235 or more

60
230

110
110

ceiling
drain pan

outer side of grille


panel
same line
mounting plate

470
30
Lower view Panel(grille):PMP-40BM Panel(grille):PMP-40BM
Unit : mm
5. Electrical Wiring Diagram
FUSE BREAKER
PULL BOX (15A) (15A)
POWER SUPPLY TO OUTDOOR UNIT
TO NEXT ~/N 220-230-240V 50Hz BC CONTROLLER
INDOOR UNIT 220V 60Hz REMOTE CONTROLLER
DC24-30V

TB2 L N TB5 M1 M2 (SHIELD)


MF TO MA-REMOTE CONTROLLER
PE

GRN/YLW
DC8.7-13V

BLU
BLU
RED
BLU
1 2
5 TB15

ORN
ORN
I.B
CN2M CN3A
(BLU) 1 2 (BLU) 1 2
M-NET REMOCON CN31 3
LED1 (WHT) 2 DS
DRAIN 1
LED2
CN29 2
(BLK) TH23
GAS 1
FAN CN21
(WHT) 1 2 3 4 5 6 (WHT)
2 TH22
LIQUID 1
CN20 2
FUSE (RED) TH21
RED 1
3 INTAKE
BLU
BLU
1 6
ZNR 4 BRN
CND
CN41
5 ORN
(RED) CN60 4 6
(WHT) (WHT) YLW LEV
POWER
HA LEV 3 RED
1 2 WHT
CN51
5 1
T (WHT)
BLU CENTRALLY
DP
1 CONTROL
3 X1 1 6
BLU X1 BRN
CNP CN52 5 5 1
(GRN) CN6V 4 RED
(YLW) 2
D.U.M REMOTE (GRN) ORN
INDICATION VANE 3 YLW
3 MV
1 2 GRN
4
1 5
SW2 SW3 SW4
*See fig:✻1 0N 0N
0FF 2
0FF
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 12345 1
CN25
A.B 2
(WHT) 1
SW5 4 REMOTE (RED) (RED)
220V 240V (RED) SWITCH ADDRESS ADDRESS CN27
3 CN32 CN42 CN81
ADDRESS
SW1 CN43 2 3 1 1 2 3 4 1 2 3 4 5 6 7 8
1 8
7
(RED)
1 2 3 4 5 6 7 8 9 10 ADDRESS
6
SW12 SW11 SW14 CN82 5

PMFY-P-VBM-A
0 0 SWC 0 4
O 3 4
3RD. 2ND. 1ST. CONNECTION 2
8
DIGIT DIGIT DIGIT No. 1

<SYMBOL EXPLANATION> <✻1>


SYMBOL NAME SYMBOL NAME MODELS SW2 SW3
I.B INDOOR CONTROLLER BOARD MF FAN MOTOR 0N 0N
CN25 HUMIDIFIER MV VANE MOTOR P20VBM 0FF 0FF
CN27 DAMPER DP DRAIN WATER LIFTING-UP MACH. 123456 123456 7 8 9 10
CN32 REMOTE SWITCH DS DRAIN SENSOR
CONNECTOR 0N 0N
CN41 HA TERMINAL-A TB2 POWER SUPPLY P25VBM 0FF 0FF
TERMINAL
CN51 CENTRALLY CONTROL TB5 TRANSMISSION 123456 123456 7 8 9 10
BLOCK
CN52 REMOTE INDICATION TB15 MA-REMOTE CONTROLLER 0N 0N
SW2 CAPACITY CODE TH21 ROOM TEMPERATURE DETECTION P32VBM 0FF 0FF
SW3 SWITCH MODE SELECTION (0˚C/15k‰, 25˚C/5.4k‰) 123456 123456 7 8 9 10
SW4 MODEL SELECTION TH22 THERMISTOR PIPE TEMPERATURE DETECTION/LIQUID 0N 0N
ZNR VARISTOR (0˚C/15k‰, 25˚C/5.4k‰) P40VBM 0FF 0FF
FUSE FUSE(6.3A/250V) TH23 PIPE TEMPERATURE DETECTION/GAS 123456 1 2 3 4 5 6 7 8 9 10

X1 AUX.RELAY DRAIN PUMP (0˚C/15k‰, 25˚C/5.4k‰)


T TRANSFORMER LEV LINEAR EXPANSION VALVE
LED1 POWER SUPPLY(I.B)
LED2 POWER SUPPLY(I.B) NOTES:
A.B CIRCUIT BOARD 1.At servicing for outdoor unit, always follow the wiring
SW1 MODE SELECTION diagram of outdoor unit.
SW5 VOLTAGE SELECTION
SW11 SWITCH ADDRESS SETTING 1ST DIGIT 2.Symbol [S] of TB5 is the shield wire connection.
SW12 ADDRESS SETTING 2ND DIGIT 3.Symbols used in wiring diagram above are,
SW14 CONNECTION NO. :terminal block, :connector.
4.The setting of the SW2 dip switches differs in the capacity for
the detail, see the table <✻1>.
5.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220V side.

2- 123
6. Temperature/Airflow distribution

● Temperature distribution
<Cooling mode> <Heating mode>
Flow angle 30˚ <˚C> Flow angle 70˚ <˚C>
2.7 2.7

19
Height <m>

Height <m>
2 2
33
21

25 23 23 24 30 24
1 1
27
25 21
25

5 4 3 2 1 0 5 4 3 2 1 0
Floor distance <m> Floor distance <m>

● Airflow distribution
<Fan mode> <Fan mode>
Flow angle 30˚ <m/s> Flow angle 70˚ <m/s>
2.7 2.7

3.0 3.0
Height <m>

Height <m>

2 2
2.0
1.0 2.0

1 1
1.0
0.5
0.5 0.5

5 4 3 2 1 0 5 4 3 2 1 0
Floor distance <m> Floor distance <m>
PMFY-P-VBM-A

2- 124
7. Options

Description Model Applicable capacity


Decoration panel PMP-40BM P20/P25/P32/P40

PMFY-P-VBM-A

2- 125
PMFY-P-VBM-A

2- 126
Cassette ceiling(2-way flow) PLFY-P-VLMD-A
PLFY-P-VLMD-B
CONTENTS

1. Specifications ·································································2-128

2. Capacity Tables ····························································· 2-129


2-1 Cooling Capacity(PUMY) ············································ 2-129
2-2 Heating Capacity(PUMY) ············································ 2-131
2-3 Cooling Capacity(Y/R2-8·10·13HP) ···························· 2-132
2-4 Heating Capacity(Y/R2-8·10·13HP) ···························· 2-134
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ····················· 2-135
2-6 Heating Capacity(Big Y, Super Y, Big R2) ····················· 2-137
2-7 Cooling Capacity(WY, WR2) ······································· 2-138
2-8 Heating Capacity(WY, WR2) ······································· 2-139

3. Sound Levels ······························································ 2-140


3-1 Noise levels ······························································· 2-140
3-2 N/C curves ································································2-140
3-3 OA Intake-static pressure curve ····································2-142
3-4 Branch duct Intake-static pressure curve ····················2-142

4. External Dimensions ····················································2-143

5. Electrical Wiring Diagram ············································2-147


VLMD-A/VLMD-B

6. Temperature/Airflow distribution ··································2-149


PLFY-P-

7. Options ············································································· 2-150

2- 127
1. Specifications
PLFY- PLFY- PLFY- PLFY- PLFY- PLFY-
P20VLMD-B P25VLMD-B P32VLMD-B P40VLMD-B P50VLMD-B P63VLMD-B
Power source ~ 220-240V 50Hz / ~ 220-230V 60Hz
❇1 kW 2.2 2.8 3.6 4.5 5.6 7.1
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000 5,000 6,300
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0 6.3 8.0
Power Cooling kW 0.072 / 0.075 0.072 / 0.075 0.072 / 0.075 0.081 / 0.085 0.082 / 0.086 0.101 / 0.105
consumption Heating kW 0.065 / 0.069 0.065 / 0.069 0.065 / 0.069 0.074 / 0.079 0.075 / 0.080 0.094 / 0.099
Cooling A 0.36 / 0.37 0.36 / 0.37 0.36 / 0.37 0.40 / 0.42 0.41 / 0.43 0.49 / 0.51
Current
Heating A 0.30 / 0.32 0.30 / 0.32 0.30 / 0.32 0.34 / 0.37 0.35 / 0.38 0.43 / 0.46
External finish(Munsel No.) Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)
Height mm 290 <20>
Dimension ❇ 3 Width mm 776 <1080> 946 <1250>
Depth mm 634 <710>
Net weight ❇3 kg 23 <6.5> 24 <6.5> 27 <7.5> 28 <7.5>
Heat exchanger Cross fin
Type Turbo fan x 1
Airflow rate
m3/min 6.5-8.0-9.5 7.0-8.5-10.5 9.0-11.0-12.5 10.0-13.0-15.5
Fan (Lo-Mid-Hi)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.015 0.020
Air filter PP honeycomb fabric (long life filter)
Refrigerant Gas(Flare) mm ø 12.7 ø 15.88
pipe dimension Liquid(Flare) mm ø 6.35 ø 9.52
Drain pipe dimension VP-25
Noise level 220V,240V dB(A) 27-30-33 29-33-36 31-34-37 32-37-39
(Lo-Mid-Hi) ❇4 230V dB(A) 28-31-34 30-34-37 32-35-38 33-38-40

PLFY- PLFY- PLFY-


P80VLMD-A P100VLMD-A P125VLMD-A
Power source ~ 220-240V 50Hz
❇1 kW 9.0 11.2 14.0
Cooling capacity
❇2 kcal/h 8,000 10,000 12,500
Heating capacity ❇1 kW 10.0 12.5 16.0
Power Cooling kW 0.23 0.25 0.28
consumption Heating kW 0.22 0.24 0.27
Cooling A 1.10 1.20 1.35
Current
Heating A 1.05 1.15 1.33
External finish(Munsel No.) Unit : Galvanizing Panel : 0.70V8.59/0.97
Height mm 338 <8>
Dimension ❇ 3 Width mm 1,358 <1,650> 1,708 <2,000>
Depth mm 606 <670>
Net weight ❇3 kg 39 <10> 56 <11.5>
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕2 Sirocco fan✕4
Airflow rate
m /min
3
15.0-17.0-19.0-21.0 21.0-23.0-26.0-29.0 24.0-27.0-30.0-33.0
VLMD-A/VLMD-B

Fan (Lo-Mid2-Mid1-Hi)
External static
Pa 0
PLFY-P-

pressure
Type Single phase induction motor
Motor
Output kW 0.078 0.078✕2
Air filter Synthetic fiber unwoven cloth filter (long life)
Gas mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liqud mm ø 9.52
(Flare)
Drain pipe dimension VP-25
Noise level (Lo-Mid2-Mid1-Hi) ❇ 4 dB(A) 36-38-41-43 37-39-41-43 40-42-44-46

Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 The figure in < > indicates panel's
❇ 4 It is measured in anechoic room.

2- 128
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.3 1.8 2.4 1.8 2.6 1.9
22.5 2.1 1.8 2.3 1.8 2.4 1.8 2.6 1.9
25.0 2.1 1.7 2.3 1.8 2.4 1.8 2.5 1.9
27.5 2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.9
20 30.0 2.1 1.7 2.2 1.8 2.3 1.8 2.5 1.9
(2.2) 32.5 2.0 1.7 2.2 1.8 2.3 1.8 2.5 1.8
35.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.8
37.5 2.0 1.7 2.1 1.8 2.2 1.7 2.4 1.8
40.0 2.0 1.7 2.1 1.8 2.2 1.7 2.4 1.8
46.0 1.9 1.6 2.0 1.7 2.1 1.7 2.3 1.8
20.0 2.8 2.1 2.9 2.1 3.1 2.1 3.3 2.2
22.5 2.7 2.0 2.9 2.1 3.1 2.1 3.2 2.2
25.0 2.7 2.0 2.9 2.1 3.1 2.1 3.2 2.2
27.5 2.7 2.0 2.8 2.1 3.0 2.1 3.2 2.2
25 30.0 2.6 2.0 2.8 2.1 3.0 2.1 3.2 2.1
(2.8) 32.5 2.6 2.0 2.8 2.1 2.9 2.1 3.1 2.1
35.0 2.6 1.9 2.7 2.1 2.9 2.0 3.1 2.1
37.5 2.5 1.9 2.7 2.0 2.9 2.0 3.0 2.1
40.0 2.5 1.9 2.7 2.0 2.8 2.0 3.0 2.1
46.0 2.4 1.9 2.6 2.0 2.7 1.9 2.9 2.0
20.0 3.6 2.6 3.7 2.7 4.0 2.7 4.2 2.7
22.5 3.5 2.6 3.7 2.7 4.0 2.6 4.2 2.7
25.0 3.5 2.5 3.7 2.6 3.9 2.6 4.1 2.7
27.5 3.4 2.5 3.6 2.6 3.9 2.6 4.1 2.7
32 30.0 3.4 2.5 3.6 2.6 3.8 2.6 4.1 2.7
(3.6) 32.5 3.3 2.5 3.6 2.6 3.8 2.6 4.0 2.6
35.0 3.3 2.4 3.5 2.6 3.7 2.5 4.0 2.6
37.5 3.2 2.4 3.5 2.5 3.7 2.5 3.9 2.6
40.0 3.2 2.4 3.4 2.5 3.6 2.5 3.9 2.6
46.0 3.1 2.3 3.3 2.5 3.5 2.4 3.7 2.5
20.0 4.5 3.0 4.7 3.2 5.0 3.1 5.3 3.2
22.5 4.4 3.0 4.6 3.1 5.0 3.1 5.2 3.2
25.0 4.3 3.0 4.6 3.1 4.9 3.1 5.2 3.2
27.5 4.3 3.0 4.6 3.1 4.9 3.1 5.1 3.1
40 30.0 4.2 2.9 4.5 3.1 4.8 3.0 5.1 3.1
(4.5) 32.5 4.2 2.9 4.4 3.0 4.7 3.0 5.0 3.1
35.0 4.1 2.8 4.4 3.0 4.7 3.0 5.0 3.1
37.5 4.1 2.8 4.3 3.0 4.6 2.9 4.9 3.0
40.0 4.0 2.8 4.3 2.9 4.5 2.9 4.8 3.0
46.0 3.8 2.7 4.1 2.9 4.3 2.8 4.6 2.9
20.0 5.5 3.8 5.8 4.0 6.2 4.0 6.6 4.1
22.5 5.5 3.8 5.8 3.9 6.2 3.9 6.5 4.0
25.0 5.4 3.7 5.7 3.9 6.1 3.9 6.4 4.0
27.5 5.3 3.7 5.7 3.9 6.0 3.9 6.4 4.0
50 30.0 5.3 3.7 5.6 3.8 5.9 3.8 6.3 3.9
(5.6) 32.5 5.2 3.6 5.5 3.8 5.9 3.8 6.2 3.9
35.0 5.1 3.6 5.5 3.8 5.8 3.7 6.2 3.9
37.5 5.0 3.5 5.4 3.7 5.7 3.7 6.1 3.8
VLMD-A/VLMD-B

40.0 5.0 3.5 5.3 3.7 5.6 3.7 6.0 3.8


46.0 4.8 3.4 5.1 3.6 5.4 3.5 5.8 3.7
PLFY-P-

20.0 7.0 4.9 7.4 5.1 7.9 5.1 8.3 5.2


22.5 6.9 4.9 7.3 5.1 7.8 5.1 8.2 5.2
25.0 6.9 4.8 7.3 5.1 7.7 5.0 8.2 5.2
27.5 6.8 4.8 7.2 5.0 7.7 5.0 8.1 5.1
63 30.0 6.7 4.7 7.1 5.0 7.5 4.9 8.0 5.1
(7.1) 32.5 6.6 4.7 7.0 4.9 7.5 4.9 7.9 5.0
35.0 6.5 4.6 6.9 4.9 7.3 4.8 7.8 5.0
37.5 6.4 4.6 6.8 4.8 7.2 4.8 7.7 5.0
40.0 6.3 4.6 6.7 4.8 7.2 4.7 7.6 4.9
46.0 6.1 4.4 6.5 4.7 6.9 4.6 7.3 4.8

2- 129
Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 8.9 6.3 9.4 6.6 10.0 6.6 10.6 6.7
22.5 8.8 6.3 9.3 6.6 9.9 6.5 10.4 6.7
25.0 8.7 6.2 9.2 6.5 9.8 6.5 10.4 6.7
27.5 8.6 6.2 9.1 6.5 9.7 6.4 10.3 6.6
80 30.0 8.5 6.1 9.0 6.4 9.5 6.4 10.2 6.6
(9.0) 32.5 8.3 6.0 8.9 6.4 9.5 6.3 10.0 6.5
35.0 8.2 6.0 8.8 6.3 9.3 6.2 9.9 6.5
37.5 8.1 5.9 8.6 6.2 9.2 6.2 9.8 6.4
40.0 8.0 5.9 8.6 6.2 9.1 6.1 9.6 6.3
46.0 7.7 5.7 8.2 6.0 8.7 6.0 9.3 6.2
20.0 11.1 8.3 11.6 8.6 12.5 8.6 13.1 8.8
22.5 10.9 8.2 11.5 8.6 12.3 8.5 13.0 8.8
25.0 10.8 8.1 11.5 8.5 12.2 8.5 12.9 8.7
27.5 10.7 8.1 11.3 8.5 12.1 8.4 12.8 8.7
100 30.0 10.5 8.0 11.2 8.4 11.9 8.3 12.6 8.6
(11.2) 32.5 10.4 7.9 11.1 8.3 11.8 8.3 12.5 8.5
35.0 10.2 7.8 10.9 8.3 11.6 8.2 12.3 8.5
37.5 10.1 7.8 10.8 8.2 11.4 8.1 12.2 8.4
40.0 10.0 7.7 10.6 8.1 11.3 8.1 12.0 8.3
46.0 9.6 7.5 10.2 7.9 10.8 7.8 11.5 8.1
20.0 13.9 10.1 14.6 10.5 15.6 10.5 16.4 10.8
22.5 13.7 10.0 14.4 10.5 15.4 10.4 16.2 10.7
25.0 13.5 10.0 14.3 10.4 15.3 10.3 16.1 10.6
27.5 13.4 9.9 14.2 10.3 15.1 10.3 16.0 10.6
125 30.0 13.2 9.8 14.0 10.3 14.9 10.2 15.8 10.5
(14.0) 32.5 13.0 9.7 13.8 10.2 14.7 10.1 15.6 10.4
35.0 12.8 9.6 13.7 10.1 14.5 10.0 15.4 10.3
37.5 12.6 9.5 13.4 10.0 14.3 9.9 15.2 10.3
40.0 12.5 9.4 13.3 9.9 14.1 9.8 15.0 10.2
46.0 12.0 9.2 12.8 9.7 13.5 9.6 14.4 9.9
VLMD-A/VLMD-B
PLFY-P-

2- 130
2-2.Heating Capacity (In combination with PUMY)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 5.1 5.0 4.9
-10.0 1.7 1.6 1.6 -10.0 5.4 5.3 5.2
-5.0 1.9 1.9 1.9 -5.0 6.1 6.0 5.9
0.0 2.2 2.1 2.1 0.0 6.9 6.9 6.8
2.5 2.3 2.3 2.3 2.5 7.4 7.3 7.2
20 63
6.0 2.5 2.5 2.5 6.0 8.0 8.0 7.9
7.5 2.6 2.6 2.5 7.5 8.3 8.3 7.9
10.0 2.8 2.7 2.5 10.0 8.8 8.8 7.9
12.5 2.9 2.8 2.5 12.5 9.4 8.8 7.9
15.5 3.1 2.8 2.5 15.5 9.8 8.8 7.9
-12.0 2.0 2.0 2.0 -12.0 6.4 6.2 6.1
-10.0 2.1 2.1 2.1 -10.0 6.7 6.6 6.5
-5.0 2.4 2.4 2.4 -5.0 7.6 7.5 7.4
0.0 2.8 2.8 2.7 0.0 8.7 8.6 8.5
2.5 3.0 2.9 2.9 2.5 9.2 9.2 9.0
25 80
6.0 3.2 3.2 3.2 6.0 10.1 10.0 9.9
7.5 3.3 3.3 3.2 7.5 10.4 10.4 9.9
10.0 3.5 3.5 3.2 10.0 11.1 11.0 9.9
12.5 3.7 3.5 3.2 12.5 11.7 11.0 9.9
15.5 3.9 3.5 3.2 15.5 12.3 11.0 9.9
-12.0 2.5 2.5 2.5 -12.0 8.0 7.8 7.7
-10.0 2.7 2.6 2.6 -10.0 8.4 8.2 8.1
-5.0 3.1 3.0 3.0 -5.0 9.6 9.4 9.3
0.0 3.5 3.4 3.4 0.0 10.9 10.7 10.6
2.5 3.7 3.7 3.6 2.5 11.5 11.4 11.3
32 100
6.0 4.0 4.0 3.9 6.0 12.6 12.5 12.3
7.5 4.2 4.1 4.0 7.5 13.0 12.9 12.4
10.0 4.4 4.4 4.0 10.0 13.8 13.7 12.4
12.5 4.7 4.4 4.0 12.5 14.6 13.8 12.4
15.5 4.9 4.4 4.0 15.5 15.4 13.8 12.4
-12.0 3.2 3.1 3.1 -12.0 10.2 10.0 9.8
-10.0 3.4 3.3 3.2 -10.0 10.7 10.6 10.4
-5.0 3.8 3.8 3.7 -5.0 12.2 12.1 11.9
0.0 4.3 4.3 4.2 0.0 13.9 13.8 13.6
2.5 4.6 4.6 4.5 2.5 14.8 14.7 14.5
40 125
6.0 5.0 5.0 4.9 6.0 16.1 16.0 15.8
7.5 5.2 5.2 5.0 7.5 16.7 16.6 15.8
10.0 5.5 5.5 5.0 10.0 17.7 17.6 15.8
12.5 5.9 5.5 5.0 12.5 18.7 17.7 15.8
15.5 6.2 5.5 5.0 15.5 19.7 17.7 15.8
-12.0 4.0 3.9 3.9
-10.0 4.2 4.2 4.1
-5.0 4.8 4.8 4.7
0.0 5.5 5.4 5.3
2.5 5.8 5.8 5.7
50
6.0 6.3 6.3 6.2
7.5 6.6 6.5 6.2
10.0 7.0 6.9 6.2
12.5 7.4 7.0 6.2
VLMD-A/VLMD-B

15.5 7.7 7.0 6.2


PLFY-P-

2- 131
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.8 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.8 2.6 1.8
22.5 2.1 1.7 2.2 1.8 2.3 1.8 2.3 1.8 2.4 1.8 2.4 1.8 2.5 1.8
25.0 2.1 1.7 2.2 1.8 2.2 1.7 2.3 1.8 2.3 1.8 2.4 1.8 2.5 1.8
27.5 2.1 1.7 2.1 1.8 2.2 1.7 2.3 1.8 2.3 1.8 2.4 1.8 2.5 1.7
20 30.0 2.1 1.7 2.1 1.8 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7
(2.2) 32.5 2.0 1.7 2.1 1.8 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.8 2.4 1.7
35.0 2.0 1.7 2.1 1.7 2.2 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7
37.5 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7
40.0 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.7 2.2 1.8 2.3 1.8 2.4 1.7
43.0 2.0 1.7 2.0 1.7 2.1 1.7 2.1 1.7 2.2 1.8 2.3 1.7 2.3 1.7
20.0 2.7 2.0 2.8 2.1 2.9 2.0 3.0 2.1 3.0 2.1 3.1 2.1 3.2 2.0
22.5 2.7 2.0 2.8 2.1 2.9 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.0
25.0 2.7 2.0 2.7 2.1 2.9 2.0 2.9 2.0 3.0 2.1 3.1 2.0 3.2 2.0
27.5 2.7 2.0 2.7 2.0 2.8 2.0 2.9 2.0 2.9 2.1 3.1 2.0 3.2 2.0
25 30.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.0 2.9 2.1 3.0 2.0 3.1 2.0
(2.8) 32.5 2.6 2.0 2.7 2.0 2.8 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.1 2.0
35.0 2.6 2.0 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.0 3.0 2.0 3.1 1.9
37.5 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 2.8 2.0 2.9 2.0 3.1 1.9
40.0 2.5 1.9 2.6 2.0 2.7 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.0 1.9
43.0 2.5 1.9 2.5 2.0 2.7 1.9 2.7 1.9 2.8 2.0 2.9 2.0 3.0 1.9
20.0 3.5 2.6 3.6 2.6 3.7 2.5 3.8 2.6 3.9 2.6 4.0 2.6 4.2 2.5
22.5 3.5 2.5 3.6 2.6 3.7 2.5 3.8 2.5 3.9 2.6 4.0 2.6 4.1 2.5
25.0 3.5 2.5 3.5 2.6 3.7 2.5 3.7 2.5 3.8 2.6 4.0 2.5 4.1 2.5
27.5 3.4 2.5 3.5 2.6 3.6 2.5 3.7 2.5 3.8 2.6 3.9 2.5 4.1 2.5
32 30.0 3.4 2.5 3.5 2.5 3.6 2.5 3.7 2.5 3.7 2.6 3.9 2.5 4.0 2.4
(3.6) 32.5 3.3 2.5 3.4 2.5 3.6 2.5 3.6 2.5 3.7 2.6 3.9 2.5 4.0 2.4
35.0 3.3 2.4 3.4 2.5 3.5 2.4 3.6 2.5 3.7 2.5 3.8 2.5 4.0 2.4
37.5 3.3 2.4 3.3 2.5 3.5 2.4 3.6 2.5 3.6 2.5 3.8 2.5 3.9 2.4
40.0 3.2 2.4 3.3 2.5 3.5 2.4 3.5 2.4 3.6 2.5 3.7 2.5 3.9 2.4
43.0 3.2 2.4 3.3 2.4 3.4 2.4 3.5 2.4 3.6 2.5 3.7 2.4 3.8 2.4
20.0 4.4 3.0 4.5 3.1 4.7 3.0 4.8 3.0 4.9 3.1 5.0 3.0 5.2 2.9
22.5 4.4 3.0 4.5 3.0 4.6 3.0 4.7 3.0 4.8 3.0 5.0 2.9 5.2 2.8
25.0 4.3 3.0 4.4 3.0 4.6 2.9 4.7 2.9 4.8 3.0 5.0 2.9 5.1 2.8
27.5 4.3 2.9 4.4 3.0 4.5 2.9 4.6 2.9 4.7 3.0 4.9 2.9 5.1 2.8
40 30.0 4.2 2.9 4.3 3.0 4.5 2.9 4.6 2.9 4.7 3.0 4.9 2.9 5.0 2.8
(4.5) 32.5 4.2 2.9 4.3 2.9 4.5 2.9 4.5 2.9 4.6 2.9 4.8 2.9 5.0 2.8
35.0 4.1 2.9 4.2 2.9 4.4 2.8 4.5 2.8 4.6 2.9 4.8 2.8 5.0 2.8
37.5 4.1 2.8 4.2 2.9 4.4 2.8 4.5 2.8 4.5 2.9 4.7 2.8 4.9 2.7
40.0 4.1 2.8 4.1 2.9 4.3 2.8 4.4 2.8 4.5 2.9 4.7 2.8 4.9 2.7
43.0 4.0 2.8 4.1 2.8 4.3 2.8 4.4 2.8 4.4 2.9 4.6 2.8 4.8 2.7
20.0 5.5 3.8 5.6 3.8 5.8 3.8 5.9 3.8 6.0 3.8 6.3 3.7 6.5 3.6
22.5 5.4 3.8 5.5 3.8 5.8 3.7 5.9 3.7 6.0 3.8 6.2 3.7 6.4 3.6
25.0 5.4 3.7 5.5 3.8 5.7 3.7 5.8 3.7 5.9 3.8 6.2 3.7 6.4 3.6
27.5 5.3 3.7 5.4 3.8 5.7 3.7 5.8 3.7 5.9 3.8 6.1 3.7 6.3 3.6
50 30.0 5.3 3.7 5.4 3.7 5.6 3.6 5.7 3.6 5.8 3.7 6.0 3.6 6.3 3.5
(5.6) 32.5 5.2 3.6 5.3 3.7 5.5 3.6 5.7 3.6 5.8 3.7 6.0 3.6 6.2 3.5
35.0 5.2 3.6 5.3 3.7 5.5 3.6 5.6 3.6 5.7 3.7 5.9 3.6 6.2 3.5
37.5 5.1 3.6 5.2 3.6 5.4 3.6 5.5 3.6 5.7 3.7 5.9 3.6 6.1 3.5
VLMD-A/VLMD-B

40.0 5.0 3.5 5.2 3.6 5.4 3.5 5.5 3.5 5.6 3.6 5.8 3.6 6.0 3.4
43.0 5.0 3.5 5.1 3.6 5.3 3.5 5.4 3.5 5.5 3.6 5.8 3.5 6.0 3.4
PLFY-P-

20.0 7.0 4.9 7.1 5.0 7.4 4.9 7.5 4.9 7.7 5.0 8.0 4.9 8.2 4.7
22.5 6.9 4.9 7.0 4.9 7.3 4.8 7.5 4.8 7.6 5.0 7.9 4.8 8.2 4.7
25.0 6.8 4.8 7.0 4.9 7.2 4.8 7.4 4.8 7.5 4.9 7.8 4.8 8.1 4.7
27.5 6.7 4.8 6.9 4.9 7.2 4.8 7.3 4.8 7.5 4.9 7.7 4.8 8.0 4.6
63 30.0 6.7 4.7 6.8 4.8 7.1 4.7 7.2 4.7 7.4 4.9 7.7 4.7 8.0 4.6
(7.1) 32.5 6.6 4.7 6.7 4.8 7.0 4.7 7.2 4.7 7.3 4.8 7.6 4.7 7.9 4.6
35.0 6.5 4.7 6.7 4.8 7.0 4.7 7.1 4.7 7.2 4.8 7.5 4.7 7.8 4.6
37.5 6.5 4.6 6.6 4.7 6.9 4.6 7.0 4.6 7.2 4.8 7.5 4.7 7.7 4.5
40.0 6.4 4.6 6.5 4.7 6.8 4.6 7.0 4.6 7.1 4.8 7.4 4.6 7.7 4.5
43.0 6.3 4.5 6.4 4.6 6.7 4.5 6.9 4.6 7.0 4.7 7.3 4.6 7.6 4.5

2- 132
Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.8 6.3 9.0 6.4 9.4 6.3 9.5 6.3 9.7 6.5 10.1 6.3 10.4 6.1
22.5 8.7 6.3 8.9 6.4 9.3 6.2 9.5 6.3 9.6 6.4 10.0 6.3 10.4 6.1
25.0 8.6 6.2 8.8 6.3 9.2 6.2 9.4 6.2 9.5 6.4 9.9 6.2 10.3 6.0
27.5 8.6 6.2 8.7 6.3 9.1 6.1 9.3 6.2 9.5 6.4 9.8 6.2 10.2 6.0
80 30.0 8.5 6.1 8.6 6.2 9.0 6.1 9.2 6.1 9.4 6.3 9.7 6.2 10.1 6.0
(9.0) 32.5 8.4 6.1 8.6 6.2 8.9 6.1 9.1 6.1 9.3 6.3 9.6 6.1 10.0 5.9
35.0 8.3 6.0 8.5 6.2 8.8 6.0 9.0 6.1 9.2 6.2 9.5 6.1 9.9 5.9
37.5 8.2 6.0 8.4 6.1 8.7 6.0 8.9 6.0 9.1 6.2 9.5 6.1 9.8 5.9
40.0 8.1 5.9 8.3 6.1 8.6 5.9 8.8 6.0 9.0 6.2 9.4 6.0 9.7 5.9
43.0 8.0 5.9 8.2 6.0 8.5 5.9 8.7 5.9 8.9 6.1 9.3 6.0 9.6 5.8
20.0 11.0 8.2 11.2 8.4 11.6 8.2 11.9 8.3 12.1 8.5 12.5 8.3 13.0 8.1
22.5 10.9 8.2 11.1 8.3 11.5 8.2 11.8 8.2 12.0 8.5 12.4 8.3 12.9 8.1
25.0 10.8 8.1 11.0 8.3 11.4 8.1 11.6 8.2 11.9 8.5 12.3 8.2 12.8 8.0
27.5 10.6 8.0 10.9 8.2 11.3 8.1 11.5 8.1 11.8 8.4 12.2 8.2 12.7 8.0
100 30.0 10.5 8.0 10.8 8.2 11.2 8.0 11.4 8.1 11.6 8.4 12.1 8.2 12.5 7.9
(11.2) 32.5 10.4 7.9 10.6 8.1 11.1 8.0 11.3 8.0 11.5 8.3 12.0 8.1 12.4 7.9
35.0 10.3 7.9 10.5 8.1 11.0 7.9 11.2 8.0 11.4 8.3 11.9 8.1 12.3 7.9
37.5 10.2 7.8 10.4 8.0 10.9 7.9 11.1 8.0 11.3 8.2 11.8 8.0 12.2 7.8
40.0 10.1 7.8 10.3 8.0 10.8 7.8 11.0 7.9 11.2 8.2 11.6 8.0 12.1 7.8
43.0 9.9 7.7 10.2 7.9 10.6 7.8 10.8 7.9 11.1 8.1 11.5 7.9 12.0 7.7
20.0 13.7 10.1 14.0 10.3 14.6 10.0 14.8 10.1 15.1 10.4 15.7 10.1 16.2 9.8
22.5 13.6 10.0 13.9 10.2 14.4 10.0 14.7 10.0 15.0 10.3 15.5 10.1 16.1 9.8
25.0 13.4 9.9 13.7 10.1 14.3 9.9 14.6 10.0 14.8 10.3 15.4 10.0 16.0 9.7
27.5 13.3 9.8 13.6 10.1 14.1 9.8 14.4 9.9 14.7 10.2 15.3 10.0 15.8 9.7
125 30.0 13.2 9.8 13.4 10.0 14.0 9.8 14.3 9.9 14.6 10.2 15.1 9.9 15.7 9.6
(14.0) 32.5 13.0 9.7 13.3 9.9 13.9 9.7 14.1 9.8 14.4 10.1 15.0 9.9 15.5 9.6
35.0 12.9 9.6 13.2 9.9 13.7 9.7 14.0 9.7 14.3 10.1 14.8 9.8 15.4 9.5
37.5 12.7 9.6 13.0 9.8 13.6 9.6 13.9 9.7 14.1 10.0 14.7 9.8 15.3 9.5
40.0 12.6 9.5 12.9 9.7 13.4 9.5 13.7 9.6 14.0 9.9 14.6 9.7 15.1 9.4
43.0 12.4 9.4 12.7 9.6 13.3 9.5 13.6 9.6 13.8 9.9 14.4 9.6 15.0 9.4

VLMD-A/VLMD-B
PLFY-P-

2- 133
2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.: ˚CDB Outdoor Indoor air temp.: ˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 5.4 5.3 5.2 5.2
-10.0 1.9 1.9 1.9 1.7 -10.0 6.1 6.0 6.0 5.5
-5.0 2.1 2.1 2.0 1.7 -5.0 6.9 6.8 6.2 5.5
0.0 2.4 2.4 2.0 1.7 0.0 7.6 7.5 6.2 5.5
2.5 2.5 2.5 2.0 1.7 2.5 8.0 7.9 6.2 5.5
20 63
6.0 2.5 2.5 2.0 1.7 6.0 8.1 8.0 6.2 5.5
7.5 2.6 2.5 2.0 1.7 7.5 8.4 8.0 6.2 5.5
10.0 2.8 2.5 2.0 1.7 10.0 9.0 8.0 6.2 5.5
12.5 3.0 2.5 2.0 1.7 12.5 9.6 8.0 6.2 5.5
15.5 3.0 2.5 2.0 1.7 15.5 9.7 8.0 6.2 5.5
-15.0 2.1 2.1 2.1 2.1 -15.0 6.7 6.6 6.5 6.5
-10.0 2.4 2.4 2.4 2.2 -10.0 7.6 7.5 7.4 6.9
-5.0 2.7 2.7 2.5 2.2 -5.0 8.6 8.5 7.8 6.9
0.0 3.1 3.0 2.5 2.2 0.0 9.5 9.4 7.8 6.9
2.5 3.2 3.2 2.5 2.2 2.5 10.0 9.9 7.8 6.9
25 80
6.0 3.2 3.2 2.5 2.2 6.0 10.1 10.0 7.8 6.9
7.5 3.4 3.2 2.5 2.2 7.5 10.5 10.0 7.8 6.9
10.0 3.6 3.2 2.5 2.2 10.0 11.2 10.0 7.8 6.9
12.5 3.8 3.2 2.5 2.2 12.5 12.0 10.0 7.8 6.9
15.5 3.9 3.2 2.5 2.2 15.5 12.1 10.0 7.8 6.9
-15.0 2.7 2.6 2.6 2.6 -15.0 8.4 8.2 8.2 8.1
-10.0 3.1 3.0 3.0 2.8 -10.0 9.6 9.4 9.3 8.6
-5.0 3.4 3.4 3.1 2.8 -5.0 10.7 10.6 9.8 8.6
0.0 3.8 3.8 3.1 2.8 0.0 11.9 11.8 9.8 8.6
2.5 4.0 4.0 3.1 2.8 2.5 12.5 12.4 9.8 8.6
32 100
6.0 4.0 4.0 3.1 2.8 6.0 12.6 12.5 9.8 8.6
7.5 4.2 4.0 3.1 2.8 7.5 13.2 12.5 9.8 8.6
10.0 4.5 4.0 3.1 2.8 10.0 14.1 12.5 9.8 8.6
12.5 4.8 4.0 3.1 2.8 12.5 15.0 12.5 9.8 8.6
15.5 4.8 4.0 3.1 2.8 15.5 15.1 12.5 9.8 8.6
-15.0 3.3 3.3 3.3 3.3 -15.0 10.7 10.6 10.5 10.4
-10.0 3.8 3.8 3.7 3.5 -10.0 12.2 12.1 11.9 11.0
-5.0 4.3 4.2 3.9 3.5 -5.0 13.7 13.6 12.5 11.0
0.0 4.8 4.7 3.9 3.5 0.0 15.3 15.1 12.5 11.0
2.5 5.0 5.0 3.9 3.5 2.5 16.0 15.8 12.5 11.0
40 125
6.0 5.1 5.0 3.9 3.5 6.0 16.2 16.0 12.5 11.0
7.5 5.3 5.0 3.9 3.5 7.5 16.8 16.0 12.5 11.0
10.0 5.6 5.0 3.9 3.5 10.0 18.0 16.0 12.5 11.0
12.5 6.0 5.0 3.9 3.5 12.5 19.1 16.0 12.5 11.0
15.5 6.1 5.0 3.9 3.5 15.5 19.4 16.0 12.5 11.0
-15.0 4.2 4.2 4.1 4.1
-10.0 4.8 4.8 4.7 4.3
-5.0 5.4 5.3 4.9 4.3
0.0 6.0 5.9 4.9 4.3
2.5 6.3 6.2 4.9 4.3
50
6.0 6.4 6.3 4.9 4.3
7.5 6.6 6.3 4.9 4.3
10.0 7.1 6.3 4.9 4.3
12.5 7.5 6.3 4.9 4.3
VLMD-A/VLMD-B

15.5 7.6 6.3 4.9 4.3


PLFY-P-

2- 134
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PLFY-P-VLMD-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Outdoor
air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.9 2.7 1.8
22.5 2.0 1.7 2.1 1.8 2.3 1.8 2.4 1.9 2.6 1.8 2.7 1.8
25.0 2.0 1.7 2.1 1.8 2.2 1.7 2.4 1.9 2.5 1.8 2.7 1.8
27.5 2.0 1.7 2.1 1.7 2.2 1.7 2.4 1.8 2.5 1.8 2.6 1.8
30.0 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.5 1.8 2.6 1.8
20
32.5 2.0 1.7 2.0 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.6 1.8
35.0 1.9 1.7 2.0 1.7 2.1 1.7 2.3 1.8 2.4 1.8 2.5 1.8
37.5 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.4 1.8 2.5 1.7
40.0 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.8 2.3 1.8 2.4 1.7
43.0 1.9 1.6 1.9 1.7 2.1 1.7 2.2 1.8 2.3 1.7 2.4 1.7
20.0 2.6 2.0 2.7 2.0 2.9 2.0 3.1 2.2 3.3 2.1 3.5 2.1
22.5 2.6 2.0 2.7 2.0 2.9 2.0 3.1 2.1 3.3 2.1 3.4 2.1
25.0 2.6 1.9 2.7 2.0 2.9 2.0 3.0 2.1 3.2 2.1 3.4 2.1
27.5 2.5 1.9 2.6 2.0 2.8 2.0 3.0 2.1 3.2 2.1 3.3 2.0
30.0 2.5 1.9 2.6 2.0 2.8 2.0 3.0 2.1 3.1 2.1 3.3 2.0
25
32.5 2.5 1.9 2.6 2.0 2.8 2.0 2.9 2.1 3.1 2.0 3.2 2.0
35.0 2.5 1.9 2.6 2.0 2.7 2.0 2.9 2.1 3.0 2.0 3.2 2.0
37.5 2.5 1.9 2.5 2.0 2.7 1.9 2.8 2.0 3.0 2.0 3.1 2.0
40.0 2.4 1.9 2.5 1.9 2.7 1.9 2.8 2.0 3.0 2.0 3.1 2.0
43.0 2.4 1.9 2.5 1.9 2.6 1.9 2.8 2.0 2.9 2.0 3.0 1.9
20.0 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6 4.2 2.6 4.5 2.6
22.5 3.3 2.4 3.5 2.5 3.7 2.5 4.0 2.6 4.2 2.6 4.4 2.5
25.0 3.3 2.4 3.4 2.5 3.7 2.5 3.9 2.6 4.1 2.6 4.4 2.5
27.5 3.3 2.4 3.4 2.5 3.6 2.5 3.9 2.6 4.1 2.5 4.3 2.5
30.0 3.2 2.4 3.4 2.5 3.6 2.4 3.8 2.6 4.0 2.5 4.2 2.5
32
32.5 3.2 2.4 3.3 2.4 3.5 2.4 3.8 2.5 4.0 2.5 4.2 2.4
35.0 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.9 2.5 4.1 2.4
37.5 3.2 2.3 3.3 2.4 3.5 2.4 3.7 2.5 3.8 2.4 4.0 2.4
40.0 3.1 2.3 3.2 2.4 3.4 2.4 3.6 2.5 3.8 2.4 4.0 2.4
43.0 3.1 2.3 3.2 2.4 3.4 2.3 3.5 2.4 3.7 2.4 3.9 2.3
20.0 4.1 3.1 4.3 3.2 4.7 3.2 5.0 3.4 5.3 3.3 5.6 3.3
22.5 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.3 5.2 3.3 5.5 3.2
25.0 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.3 5.2 3.3 5.5 3.2
27.5 4.1 3.0 4.2 3.1 4.5 3.1 4.8 3.3 5.1 3.2 5.4 3.2
30.0 4.0 3.0 4.2 3.1 4.5 3.1 4.8 3.3 5.0 3.2 5.3 3.2
40
32.5 4.0 3.0 4.2 3.1 4.4 3.1 4.7 3.2 5.0 3.2 5.2 3.1
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.2 4.9 3.2 5.1 3.1
37.5 3.9 3.0 4.1 3.1 4.3 3.0 4.6 3.2 4.8 3.1 5.1 3.1
40.0 3.9 3.0 4.0 3.0 4.3 3.0 4.5 3.2 4.7 3.1 5.0 3.0
43.0 3.9 2.9 4.0 3.0 4.2 3.0 4.4 3.1 4.7 3.1 4.9 3.0
20.0 5.2 3.8 5.4 3.9 5.8 3.9 6.2 4.1 6.6 4.1 7.0 4.0
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.2 4.1 6.5 4.0 6.9 4.0
25.0 5.1 3.8 5.3 3.9 5.7 3.9 6.1 4.1 6.4 4.0 6.8 3.9
27.5 5.1 3.7 5.3 3.9 5.6 3.8 6.0 4.0 6.3 4.0 6.7 3.9
30.0 5.0 3.7 5.2 3.8 5.6 3.8 5.9 4.0 6.2 3.9 6.6 3.9
50
32.5 5.0 3.7 5.2 3.8 5.5 3.8 5.8 4.0 6.2 3.9 6.5 3.8
35.0 4.9 3.7 5.1 3.8 5.4 3.8 5.8 3.9 6.1 3.9 6.4 3.8
37.5 4.9 3.6 5.1 3.8 5.4 3.7 5.7 3.9 6.0 3.8 6.3 3.8
40.0 4.9 3.6 5.0 3.7 5.3 3.7 5.6 3.9 5.9 3.8 6.2 3.7
43.0 4.8 3.6 5.0 3.7 5.2 3.7 5.5 3.8 5.8 3.8 6.1 3.7
20.0 6.5 4.8 6.9 5.0 7.4 5.0 7.9 5.3 8.4 5.2 8.9 5.1
22.5 6.5 4.8 6.8 5.0 7.3 5.0 7.8 5.3 8.3 5.2 8.7 5.1
25.0 6.5 4.8 6.8 5.0 7.2 5.0 7.7 5.2 8.1 5.1 8.6 5.0
27.5 6.4 4.8 6.7 4.9 7.2 4.9 7.6 5.2 8.0 5.1 8.5 5.0
30.0 6.4 4.7 6.6 4.9 7.1 4.9 7.5 5.1 7.9 5.0 8.4 5.0
63
32.5 6.3 4.7 6.6 4.9 7.0 4.8 7.4 5.1 7.8 5.0 8.2 4.9
35.0 6.3 4.7 6.5 4.8 6.9 4.8 7.3 5.0 7.7 5.0 8.1 4.9
VLMD-A/VLMD-B

37.5 6.2 4.7 6.4 4.8 6.8 4.8 7.2 5.0 7.6 4.9 8.0 4.8
40.0 6.2 4.6 6.4 4.8 6.7 4.7 7.1 5.0 7.5 4.9 7.9 4.8
43.0 6.1 4.6 6.3 4.7 6.6 4.7 7.0 4.9 7.3 4.8 7.7 4.7
PLFY-P-

2- 135
Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PLFY-P-VLMD-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
Unit air temp.
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 8.3 6.0 8.7 6.3 9.4 6.3 10.0 6.6 10.6 6.5 11.2 6.4
22.5 8.3 6.0 8.7 6.3 9.3 6.2 9.9 6.6 10.5 6.5 11.1 6.3
25.0 8.2 6.0 8.6 6.2 9.2 6.2 9.8 6.5 10.3 6.4 10.9 6.3
27.5 8.1 6.0 8.5 6.2 9.1 6.1 9.6 6.4 10.2 6.3 10.8 6.2
30.0 8.1 5.9 8.4 6.1 9.0 6.1 9.5 6.4 10.0 6.3 10.6 6.2
80
32.5 8.0 5.9 8.3 6.1 8.9 6.0 9.4 6.3 9.9 6.2 10.4 6.1
35.0 8.0 5.9 8.2 6.0 8.8 6.0 9.3 6.3 9.8 6.2 10.3 6.1
37.5 7.9 5.8 8.1 6.0 8.6 5.9 9.1 6.2 9.6 6.1 10.1 6.0
40.0 7.8 5.8 8.1 6.0 8.5 5.9 9.0 6.2 9.5 6.1 10.0 5.9
43.0 7.7 5.8 8.0 5.9 8.4 5.8 8.9 6.1 9.3 6.0 9.8 5.9
20.0 10.3 7.9 10.8 8.2 11.6 8.2 12.5 8.7 13.2 8.6 14.0 8.4
22.5 10.3 7.9 10.8 8.2 11.5 8.2 12.3 8.6 13.0 8.5 13.8 8.4
25.0 10.2 7.8 10.7 8.1 11.4 8.1 12.1 8.6 12.8 8.4 13.6 8.3
27.5 10.1 7.8 10.6 8.1 11.3 8.1 12.0 8.5 12.7 8.4 13.4 8.2
30.0 10.1 7.8 10.5 8.0 11.2 8.0 11.8 8.4 12.5 8.3 13.2 8.2
100
32.5 10.0 7.7 10.3 8.0 11.0 7.9 11.7 8.4 12.3 8.2 13.0 8.1
35.0 9.9 7.7 10.2 8.0 10.9 7.9 11.5 8.3 12.1 8.2 12.8 8.0
37.5 9.8 7.7 10.1 7.9 10.8 7.8 11.4 8.3 12.0 8.1 12.6 8.0
40.0 9.7 7.6 10.0 7.9 10.6 7.8 11.2 8.2 11.8 8.0 12.4 7.9
43.0 9.6 7.6 9.9 7.8 10.5 7.7 11.0 8.1 11.6 8.0 12.2 7.8
20.0 12.9 9.6 13.5 10.0 14.6 10.0 15.6 10.6 16.5 10.4 17.5 10.3
22.5 12.9 9.6 13.5 10.0 14.4 10.0 15.4 10.5 16.3 10.4 17.2 10.2
25.0 12.8 9.6 13.3 9.9 14.3 9.9 15.2 10.4 16.1 10.3 17.0 10.1
27.5 12.7 9.5 13.2 9.9 14.1 9.8 15.0 10.4 15.8 10.2 16.7 10.0
30.0 12.6 9.5 13.1 9.8 13.9 9.8 14.8 10.3 15.6 10.1 16.5 9.9
125
32.5 12.5 9.4 12.9 9.8 13.8 9.7 14.6 10.2 15.4 10.0 16.2 9.8
35.0 12.4 9.4 12.8 9.7 13.6 9.6 14.4 10.1 15.2 9.9 16.0 9.8
37.5 12.3 9.3 12.7 9.6 13.5 9.5 14.2 10.0 15.0 9.9 15.7 9.7
40.0 12.2 9.3 12.5 9.6 13.3 9.5 14.0 10.0 14.8 9.8 15.5 9.6
43.0 12.0 9.2 12.4 9.5 13.1 9.4 13.8 9.9 14.5 9.7 15.2 9.5
VLMD-A/VLMD-B
PLFY-P-

2- 136
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)
PLFY-P-VLMD-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 5.0 4.9 4.8 4.7
-10.0 1.8 1.8 1.7 1.7 -10.0 5.7 5.6 5.5 5.4
-5.0 2.0 2.0 2.0 1.9 -5.0 6.4 6.3 6.2 6.2
0.0 2.2 2.2 2.1 1.9 0.0 7.2 7.1 6.8 6.2
20 2.5 2.4 2.3 2.1 1.9 63 2.5 7.5 7.5 6.8 6.2
6.0 2.5 2.5 2.1 1.9 6.0 8.1 8.0 6.8 6.2
7.5 2.6 2.5 2.1 1.9 7.5 8.3 8.0 6.8 6.2
10.0 2.7 2.5 2.1 1.9 10.0 8.7 8.0 6.8 6.2
12.5 2.9 2.5 2.1 1.9 12.5 9.1 8.0 6.8 6.2
15.5 2.9 2.5 2.1 1.9 15.5 9.2 8.0 6.8 6.2
-15.0 2.0 2.0 1.9 1.9 -15.0 6.2 6.1 6.0 5.9
-10.0 2.3 2.2 2.2 2.2 -10.0 7.1 7.0 6.9 6.8
-5.0 2.6 2.5 2.5 2.5 -5.0 8.0 7.9 7.8 7.7
0.0 2.9 2.8 2.7 2.5 0.0 8.9 8.8 8.5 7.7
25 2.5 3.0 3.0 2.7 2.5 80 2.5 9.4 9.3 8.5 7.7
6.0 3.2 3.2 2.7 2.5 6.0 10.1 10.0 8.5 7.7
7.5 3.3 3.2 2.7 2.5 7.5 10.4 10.0 8.5 7.7
10.0 3.5 3.2 2.7 2.5 10.0 10.9 10.0 8.5 7.7
12.5 3.7 3.2 2.7 2.5 12.5 11.4 10.0 8.5 7.7
15.5 3.7 3.2 2.7 2.5 15.5 11.5 10.0 8.5 7.7
-15.0 2.5 2.5 2.4 2.4 -15.0 7.8 7.7 7.5 7.4
-10.0 2.8 2.8 2.8 2.7 -10.0 8.9 8.8 8.6 8.5
-5.0 3.2 3.2 3.1 3.1 -5.0 10.0 9.9 9.8 9.6
0.0 3.6 3.5 3.4 3.1 0.0 11.2 11.0 10.6 9.6
32 2.5 3.8 3.7 3.4 3.1 100 2.5 11.8 11.6 10.6 9.6
6.0 4.0 4.0 3.4 3.1 6.0 12.6 12.5 10.6 9.6
7.5 4.2 4.0 3.4 3.1 7.5 13.0 12.5 10.6 9.6
10.0 4.4 4.0 3.4 3.1 10.0 13.6 12.5 10.6 9.6
12.5 4.6 4.0 3.4 3.1 12.5 14.3 12.5 10.6 9.6
15.5 4.6 4.0 3.4 3.1 15.5 14.4 12.5 10.6 9.6
-15.0 3.1 3.1 3.0 3.0 -15.0 10.0 9.8 9.6 9.5
-10.0 3.6 3.5 3.5 3.4 -10.0 11.4 11.2 11.0 10.9
-5.0 4.0 4.0 3.9 3.9 -5.0 12.8 12.6 12.5 12.3
0.0 4.5 4.4 4.3 3.9 0.0 14.3 14.1 13.6 12.3
40 2.5 4.7 4.7 4.3 3.9 125 2.5 15.1 14.9 13.6 12.3
6.0 5.0 5.0 4.3 3.9 6.0 16.2 16.0 13.6 12.3
7.5 5.2 5.0 4.3 3.9 7.5 16.6 16.0 13.6 12.3
10.0 5.4 5.0 4.3 3.9 10.0 17.4 16.0 13.6 12.3
12.5 5.7 5.0 4.3 3.9 12.5 18.3 16.0 13.6 12.3
15.5 5.8 5.0 4.3 3.9 15.5 18.4 16.0 13.6 12.3
-15.0 3.9 3.9 3.8 3.7
-10.0 4.5 4.4 4.3 4.3
-5.0 5.0 5.0 4.9 4.9
0.0 5.6 5.6 5.4 4.9
50 2.5 5.9 5.9 5.4 4.9
6.0 6.4 6.3 5.4 4.9
7.5 6.6 6.3 5.4 4.9
10.0 6.9 6.3 5.4 4.9
12.5 7.2 6.3 5.4 4.9
15.5 7.2 6.3 5.4 4.9

VLMD-A/VLMD-B
PLFY-P-

2- 137
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water
Unit temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.8 2.2 1.8 2.4 1.8 2.4 1.8 2.5 1.9 2.6 1.9 2.8 1.8
20 2.1 1.7 2.1 1.8 2.3 1.8 2.3 1.8 2.4 1.9 2.5 1.8 2.7 1.8
20 30 2.0 1.7 2.0 1.7 2.1 1.7 2.2 1.7 2.3 1.8 2.4 1.8 2.5 1.8
40 1.7 1.5 1.8 1.6 1.9 1.6 1.9 1.6 2.0 1.7 2.1 1.7 2.2 1.7
45 1.6 1.5 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.7 2.0 1.6 2.1 1.6
10 2.7 2.0 2.8 2.1 3.0 2.1 3.1 2.1 3.2 2.2 3.3 2.1 3.5 2.1
20 2.6 2.0 2.7 2.0 2.9 2.0 3.0 2.1 3.1 2.1 3.2 2.1 3.4 2.1
25 30 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 2.9 2.1 3.0 2.0 3.2 2.0
40 2.2 1.8 2.2 1.8 2.4 1.8 2.4 1.8 2.5 1.9 2.6 1.9 2.8 1.9
45 2.0 1.7 2.1 1.8 2.2 1.7 2.3 1.8 2.4 1.9 2.5 1.8 2.6 1.8
10 3.5 2.5 3.6 2.6 3.9 2.6 4.0 2.6 4.1 2.7 4.3 2.7 4.5 2.6
20 3.4 2.5 3.5 2.6 3.7 2.5 3.8 2.6 3.9 2.7 4.1 2.6 4.4 2.6
32 30 3.2 2.4 3.3 2.5 3.5 2.4 3.6 2.5 3.7 2.6 3.9 2.5 4.1 2.5
40 2.8 2.2 2.9 2.3 3.1 2.2 3.1 2.3 3.2 2.4 3.4 2.3 3.6 2.3
45 2.6 2.1 2.7 2.2 2.9 2.2 3.0 2.2 3.0 2.3 3.2 2.3 3.4 2.2
10 4.4 3.0 4.5 3.1 4.8 3.1 5.0 3.1 5.1 3.2 5.4 3.1 5.7 3.1
20 4.2 2.9 4.4 3.0 4.6 3.0 4.8 3.0 4.9 3.1 5.2 3.0 5.5 3.0
40 30 4.0 2.8 4.1 2.9 4.4 2.8 4.5 2.8 4.6 2.9 4.9 2.9 5.2 2.8
40 3.5 2.5 3.6 2.6 3.8 2.6 3.9 2.6 4.0 2.7 4.3 2.6 4.5 2.6
45 3.3 2.4 3.4 2.5 3.6 2.5 3.7 2.5 3.8 2.6 4.0 2.5 4.2 2.5
10 5.5 3.8 5.6 3.9 6.0 3.8 6.2 3.9 6.3 4.0 6.7 3.9 7.1 3.8
20 5.3 3.7 5.4 3.8 5.8 3.7 5.9 3.8 6.1 3.9 6.5 3.8 6.8 3.7
50 30 5.0 3.5 5.1 3.6 5.5 3.6 5.6 3.6 5.8 3.7 6.1 3.7 6.4 3.6
40 4.3 3.2 4.5 3.3 4.7 3.2 4.9 3.3 5.0 3.4 5.3 3.3 5.6 3.3
45 4.1 3.1 4.2 3.1 4.5 3.1 4.6 3.2 4.7 3.3 5.0 3.2 5.3 3.2
10 6.9 4.9 7.2 5.0 7.6 5.0 7.8 5.0 8.0 5.2 8.5 5.1 9.0 5.0
20 6.7 4.7 6.9 4.9 7.3 4.8 7.5 4.9 7.8 5.0 8.2 5.0 8.6 4.9
63 30 6.3 4.5 6.5 4.7 6.9 4.6 7.1 4.7 7.3 4.8 7.7 4.8 8.1 4.7
40 5.5 4.1 5.7 4.3 6.0 4.2 6.2 4.3 6.4 4.4 6.7 4.4 7.1 4.3
45 5.2 4.0 5.3 4.1 5.7 4.1 5.8 4.1 6.0 4.3 6.3 4.2 6.7 4.1
10 8.8 6.3 9.1 6.5 9.6 6.4 9.9 6.5 10.2 6.7 10.8 6.6 11.4 6.5
20 8.5 6.1 8.7 6.3 9.3 6.2 9.5 6.3 9.8 6.5 10.4 6.4 10.9 6.3
80 30 8.0 5.9 8.3 6.1 8.8 6.0 9.0 6.1 9.3 6.3 9.8 6.2 10.3 6.1
40 6.9 5.4 7.2 5.5 7.6 5.5 7.8 5.6 8.1 5.8 8.5 5.7 9.0 5.6
45 6.5 5.2 6.8 5.3 7.2 5.3 7.4 5.4 7.6 5.6 8.0 5.5 8.5 5.4

10 10.9 8.2 11.3 8.4 12.0 8.4 12.3 8.5 12.7 8.8 13.4 8.7 14.1 8.5
20 10.5 8.0 10.9 8.3 11.6 8.2 11.9 8.3 12.2 8.6 12.9 8.5 13.6 8.3
100 30 9.9 7.7 10.3 8.0 10.9 7.9 11.2 8.0 11.5 8.3 12.2 8.2 12.8 8.0
40 8.6 7.1 8.9 7.3 9.5 7.3 9.7 7.4 10.0 7.7 10.6 7.6 11.2 7.5
45 8.1 6.9 8.4 7.1 8.9 7.1 9.2 7.2 9.5 7.5 10.0 7.4 10.5 7.3

10 13.7 10.0 14.1 10.3 15.0 10.2 15.4 10.3 15.9 10.7 16.7 10.5 17.7 10.4
20 13.2 9.8 13.6 10.1 14.5 10.0 14.8 10.1 15.3 10.5 16.1 10.3 17.0 10.1
125 30 12.4 9.4 12.8 9.7 13.6 9.6 14.0 9.7 14.4 10.1 15.2 10.0 16.1 9.8
40 10.8 8.6 11.2 8.9 11.9 8.8 12.2 9.0 12.5 9.4 13.2 9.2 14.0 9.1
45 10.2 8.3 10.5 8.6 11.2 8.6 11.5 8.7 11.8 9.1 12.5 8.9 13.2 8.8
VLMD-A/VLMD-B
PLFY-P-

2- 138
2-8.Heating Capacity (In combination with WY, WR2)
PLFY-P-VLMD-A, VLMD-B SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp. 15 19 20 25 27
size
˚C SHC SHC SHC SHC SHC
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 8.8 8.7 8.5 6.8 6.1
20 10.3 10.2 10.0 8.0 7.2
80 30 10.3 10.2 10.0 8.0 7.2
40 10.7 10.6 10.4 8.3 7.5
45 11.7 11.6 11.4 9.1 8.2
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1 VLMD-A/VLMD-B
PLFY-P-

2- 139
3. Sound Levels
3-1. Noise level

Casette ceiling Noise level at anechoic room


( Low - Middle - High ) Unit : dB(A)
Noise level (A weighted)
Model
220V,240V 230V
PLFY-P20VLMD-B
PLFY-P25VLMD-B 27-30-33 28-31-34
PLFY-P32VLMD-B
PLFY-P40VLMD-B 29-33-36 30-34-37
1.5m

PLFY-P50VLMD-B 31-34-37 32-35-38


PLFY-P63VLMD-B 32-37-39 33-38-40
Measurement location PLFY-P80VLMD-A 36-38-41-43
PLFY-P100VLMD-A 37-39-41-43
PLFY-P125VLMD-A 40-42-44-46

3-2. NC curves
PLFY-P20,25VLMD-B(220V,240V) PLFY-P20,25VLMD-B(230V)
90 90
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

High High
Middle Middle
80 Low 80 Low

70 70
NC70 NC70

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 Approximate minimum 20 Approximate minimum


audible limit on NC20 audible limit on NC20
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PLFY-P32VLMD-B(220V,240V) PLFY-P32VLMD-B(230V)
90 90
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

High High
Middle Middle
80 Low 80 Low

70 70
NC70 NC70

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
VLMD-A/VLMD-B

Approximate minimum Approximate minimum


audible limit on NC20 audible limit on NC20
continuous noise continuous noise
10 10
PLFY-P-

63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PLFY-P40VLMD-B(220V,240V) PLFY-P40VLMD-B(230V)
90 90
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

High High
Middle Middle
80 Low 80 Low

70 70
NC70 NC70

60 60
NC60 NC60
50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 Approximate minimum 20 Approximate minimum


audible limit on NC20 audible limit on NC20
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 140
PLFY-P50VLMD-B(220V,240V) PLFY-P50VLMD-B(230V)
90 90
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa


High High
Middle Middle
80 80 Low
Low

70 70
NC70 NC70

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 Approximate minimum
20 Approximate minimum
audible limit on NC20 audible limit on NC20
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PLFY-P63VLMD-B(220V,240V) PLFY-P63VLMD-B(230V)
90 90
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa


High High
Middle Middle
80 Low 80 Low

70 70
NC70 NC70

60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 Approximate minimum 20 Approximate minimum


audible limit on NC20 audible limit on NC20
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PLFY-P100VLMD-A(220V-240V) PLFY-P125VLMD-A(220V-240V)
70 70
OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL ( dB) 0dB = 20µPa

High speed High speed


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
VLMD-A/VLMD-B

OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)
PLFY-P-

2- 141
3-3. OA Intake-static pressure curve
30
10

20

10

0
5
Static pressure (Pa)

Static pressure (Pa)


-10
P20~P40
-20

P80 P125
-30
0
P50 · P63 P100
-40

-50

-60
-5

-70
0 1 2 3 4 5 0 1 2 3 4 5 6 7 8
Airflow rate (m3/min) Airflow rate (m3/min)

Please confirm that inlet-air temperature ( which is mixed with outdoor air ) is in the following operating temperature range.
-P-VLMD-B : Operating temperature range
Mode Temperature range of inlet air
Cooling
15˚C~24˚C(Wet bulb)
Dry
Heating 15˚C~27˚C(Dry bulb)
*Relative humidity range is 30~80%.

3-4. Branch duct Intake-static pressure curve


19
18 20

17
16
15
P32
14
Static pressure of branch duct (Pa)
Static pressure of branch duct (Pa)

P40 15
13
12
11
VLMD-A/VLMD-B

P63
10
P50
PLFY-P-

9 10
8
P20·P25
7
6 P125
P100
5
5
4
3 P80
2
1
0
0 1 2 3 4 5 6 0 1 2 3 4
Airflow rate of branch duct (m3/min) Airflow rate of branch duct (m3/min)

2- 142
Note:1.Use M10 screw for the lifing bolt (field supply).

48
2.It is available to connect the branch duct
on right and left side both.

146
< flare >

70
Model Gas pipe : LP ø 12.7 ············· 1
20·25·32·40 Liquid pipe : HP ø 6.35 ············· 2

507

574
634
670
63VLMD-B

Model Gas pipe : LP ø 15.88 ············· 1


50·63 Liquid pipe : HP ø 9.52 ············· 2
Terminal bed(Power source)
Drain hose VP-25<flexible joint> (accessory) ········· 3
PLFY-P20, 25, 32, 40, 50,

Terminal bed(Transmission)

48
108 D(Lifting Bolt Pitch) 108

Terminal box

68 574 (Lifting Bolt Pitch) 68 2


4. External Dimensions

Branch duct 358x110 knock out hole (both side)(Note:2) 6-ø2.9 Mounting hole 634
D(Lifting Bolt Pitch)
C 497 1
240 197 3
199 199 201 70 146
190 222 4-ø2.9 Mounting hole Control Box
358 221
E

52
34
60
122
190

202
110

216
159
266
290

2- 143
More Than 350

45
73
45
20

20 B 20 20 670 20
Air filter
Drain hole
Water filling port
Fresh air intake 240x45 knock out hole

Standard center panel


A

300mm or less

165mm ± 5mm(Actual Length)

710
Model A B C D E
PLFY-P20VLMD-B

583mmMAX
PLFY-P25VLMD-B
3 CMP-40VLW-B 1080 1040 776 824 388
PLFY-P32VLMD-B
PLFY-P40VLMD-B
PLFY-P50VLMD-B
CMP-63VLW-B 1250 1210 946 994 473
PLFY-P63VLMD-B
Unit : mm

VLMD-A/VLMD-B
PLFY-P-
PLFY-P-
VLMD-A/VLMD-B

Note:1.Use M10 screw for the lifing bolt (field supply).

48
45˚
2.It is available to connect the branch duct
on right and left side both. ø172

146
4-ø2.9 Mounting hole

< flare >

70
Model Gas pipe : LP ø 12.7 ············· 1
20·25·32·40 Liquid pipe : HP ø 6.35 ············· 2

507
ø150

90˚

574
634
670
63VLMD-B

Model Gas pipe : LP ø 15.88 ············· 1

128
50·63 Liquid pipe : HP ø 9.52 ············· 2
with OA duct flange

Terminal bed(Power source)


Drain hose VP-25<flexible joint> (accessory) ········· 3
PLFY-P20, 25, 32, 40, 50,

103
Terminal bed(Transmission)

Fresh air intake ø150 knock out hole

48
Fresh air intake knock out dimension
108 D(Lifting Bolt Pitch) 108

Terminal box

68 574 (Lifting Bolt Pitch) 68 2


Branch duct 358x110 knock out hole (both side)(Note:2) 6-ø2.9 Mounting hole
D(Lifting Bolt Pitch) 634
243 C 497 1
256 189 199 199 201
3 70 146
both side 103 Control Box
128 358 221
E

34
52
60
122
190

206
110
159
266
290

2- 144
241
More Than 350

241
138
45
20

20 B 20
20 670 20
Air filter
Drain hole
Water filling port

Standard center panel


A

300mm or less

165mm 5mm(Actual Length)

710
Model A B C D E
PLFY-P20VLMD-B

583mmMAX
PLFY-P25VLMD-B
3 CMP-40VLW-B 1080 1040 776 824 388
PLFY-P32VLMD-B
PLFY-P40VLMD-B
PLFY-P50VLMD-B
CMP-63VLW-B 1250 1210 946 994 473
PLFY-P63VLMD-B
Unit : mm
40
3

1
Note:1.Use M10 screw for the lifing bolt (field supply).
< flare >

630
606
550
Model Gas pipe : LP ø 12.7 ······················ 1

476
20· 25· 32· 40 Liquid pipe : HP ø 6.35 ······················

70
2
PLFY-P80VLMD-A

Model Gas pipe : LP ø 15.88 ···················· 1 2

178
50· 63· 80 Liquid pipe : HP ø 9.52 ······················ 2

40
Drain hose VP-25<flexible joint> (accessory) ······· 3
102 D 102
B

Branch duct ø 200 knock out hole (both side)


60 550 (Lifting bolt pitch) 60
Fresh air intake ø150 knock out hole
606
476 122 D(Lifting bolt pitch) 122
Terminal bed(Power source) 70 178 C 303
3 1 106 Water filling port E
2
45

38
˚
Terminal bed(Transmission) ˚

145
90 72

181

192
ø224 ø1

90
˚

235
F
G

52
135
35
90
˚
Terminal box

45 3~ 18

2- 145
222

8
Air filter 70 350 Drain hole 20 B (Ceiling opening) 20 4- ø2.9Mounting hole
Control box
20 630 (Ceiling opening) 20 4- ø2.9Mounting hole
A F G
Model A B C D E Standard Standard
center panel center panel
PLFY-P20VLMD-A
P25 1060 1020 768 816 386
300mm or less
P32
P40 290 338~353
3 300 1260 1008 1056 506

670
P50
P63 1650 1610 1358 1406 681
P80

600mmMAX
Standard center panel
Unit : mm

VLMD-A/VLMD-B
PLFY-P-
PLFY-P-
VLMD-A/VLMD-B

40
3

Note:1.Use M10 screw for the lifing bolt (field supply).

550

630
606
PLFY-P100, 125VLMD-A

476
70
< flare >
Gas pipe : LP ø19.05 ············· 1 2

178
Liquid pipe : HP ø 9.52 ············· 2

40
Drain hose VP-25<flexible joint> (accessory) ······· 3

102 1756 102


1960

60 550 (Lifting bolt pitch) 60 Branch duct ø 200 knock out hole (both side)
Fresh air intake ø 150 knock out hole
606
476 122 1756(Lifting bolt pitch) 122
Terminal bed(Power source) 70 178 1708 303
3 1 106 Water filling port 856
2
45˚

38
Terminal bed(Transmission) ˚
145

90 72
181

192
ø2
24 ø1

235
290
90˚

52
338~ 353

2- 146
135
90

35
˚
Terminal box

45 3~ 18
222

8
Air filter 70 353 Drain hole 20 20 4- ø 2.9Mounting hole
1960 (Ceiling opening)
Control box 4- ø 2.9Mounting hole
20 630 (Ceiling opening) 20

2000

300mm or less

670

600mmMAX
Standard center panel
Unit : mm
MV MV DECORATION PANEL
INSIDE SECTION OF CONTROL BOX
5 2 3 4 1 1 4 3 2 5
T3 I.B
T4
T5
T6
T7 TB15
3 2
( TRANSMISSION TERMINAL BED )
X01 X06 X07 X05 X04 ZNR901 F901 CN3A
5 4 3 2 1 1 1 TO MA REMOTE CONTROLLER
AC250V
CN27 CN41 CN52 6.3AF
CN7V
CN51 CN32

0 0
TB5 ( TRANSMISSION TERMINAL BED )
E
F 0 1 2 9 1 9 1 S(SHIELD)

8
8

2
2
CN2M 2 M2 TO OUTDOOR UNIT

7
7
SW5
● PLFY-P20~63VLMD-B

3
3
SW8

B C D
3 4 5
6 4 4
ZNR1 1 M1 BC CONTROLLER
7 8 9 A 6 5 6 5
REMOTE CONTROLLER
SW14 SW12 SW11 DSA1
(Connection No.) (2nd digit) (1st digit)
SW4 SW7 SW2 SW3 SW1

CN20 CN21 CN29 CN31 CN60 CN3T CNT CNP CN90 CND TO NEXT INDOOR UNIT
T1
TB2
2 1 2 1 2 1 3 1 6 5 4 3 2 1 3 1 3 1 3 1 1 3 5 7 9 5 3 1 L
N
PULL BOX
T T2
PE

C FUSE (16A)

3 2 1 9 7 5 4 3 2 1
5. Electrical Wiring Diagram

BREAKER (16A)

TH21 TH22 TH23 DS POWER SUPPLY


LEV DP MF

2- 147
~220V-240V 50Hz
For test of pump out
220V-230V 60Hz
(after confirm drain pump out,
take this connector off.)

SYMBOL EXPLANATION
SYMBOL NAME SYMBOL NAME SYMBOL NAME NOTE : 1. TB2,TB5, and TB15 shown in dotted line are field work.
MF Fan motor CN27 Connector (Damper) SW11 Switch (1st digit address set) 2. Mark indicates terminal bed, connector, board insertion
C Capacitor(for MF) CN32 Connector (Centrally control) SW12 Switch (2nd digit address set) connector of fastening connector of control board.
I.B Indoor controller board CN41 Connector (HA terminal-A) SW14 Switch (connection No.set)
TB2 Power source terminal bed CN51 Connector (Centrally control) SW1 Switch (for mode selection 1)
TB5 Transmission terminal bed CN52 Connector (Remote indication) SW2 Switch (for capacity code)
TB15 MA Remote controller terminal bed X01 Aux.relay (Drain pump) SW3 Switch (for mode selection 2)
F901 Fuse (6.3A/6A) X04 Aux.relay (L notch:240V) SW4 Switch (for model selection)
ZNR1,ZNR901 Varistor X05 Aux.relay (M/L notch:240V/220-230V) SW5 Switch (for voltage selection)
T Transformer X06 Aux.relay (H notch:220-230V) SW7 Switch (for model selection)
DP Drain pump X07 Aux.relay (H/M notch:240V/220-230V) SW8 Switch (for mode selection 3)
LEV Electronic linear expan.valve TH21 Thermistor (inlet temp.detection) T1~T7 Terminal
DS Drain sensor TH22 Thermistor (pipe temp.detection/liquid)
MV Motor for vane TH23 Thermistor (pipe temp.detection/gas)

VLMD-A/VLMD-B
PLFY-P-
PLFY-P-
VLMD-A/VLMD-B

INSIDE SECTION OF
INSIDE SECTION OF CONTROL BOX TERMINAL BED BOX
I.B TB15 (TRANSMISSION TERMINAL BED)
SW4 SW3 SW2 3 2
REMOTE CENTRALLY REMOTE 5 3 1
SWITCH CONTROL INDICATION CN3A 1 1 TO MA REMOTE CONTROLLER
CN32 CN51 CN52 FAN2
1 S(SHIELD)
2 TB5(TRANSMISSION TERMINAL BED)
3 CN42 X1 X3 ZNR 2
4 CN2M 1 M2
● PLFY-P80~125VLMD-A

FAN CON TO OUTDOOR UNIT


F M1 BC CONTROLLER
(Red) (White) (Black) AC250V
6.3A F M-NET REMOTE CONTROLLER
CN81 CN20 CN21 CN29 CN31 CN23 CN60 CN3T CNT CNP CNV X4 FAN1 CND CN1 S.B
ZNR1 1
87654321 21 21 21 3 1 21 654321 3 1 31 31 31 531 31 TO NEXT INDOOR UNIT
DSA1 3
A.B 1234 5 6 (White)
T 1 L TB2
SWA SWC CN62 2 PULL BOX
3 N
SW1 SW5 8 PE
7 C
6
F0 12 9
0 1 0 1 5
FUSE(16A)
E 9 CN82 4

7 8
2 3
3

7 8
2 3

B CD
345
89A
67
5 6
4
5 6
4 2 BREAKER(16A)
1
SW14 SW12 SW11 C1 C2
(Connection No.) (2nd digit) (1st digit)
(Green) 2 1 3 2 1 (White) 6 5 4 3 2 1 (White) (Red) 2 1 3 2 1 (White) POWER SUPPLY
~ 220-240V 50Hz

LS (Red)
MV LEV DP MF
TH21 TH22 TH23 NOTE;1.TB2,TB5 shown in dotted line

2- 148
DS For test of pump out are field work.
(After confirm drain pump out,take this connector off.)
2.Mark indicates terminal bed,
connector, board insertion
MF1 MF2 connector or fastening connector
PLFY-P100·125VLMD of control board.
SYMBOL EXPLANATION
SYMBOL NAME SYMBOL NAME SYMBOL NAME
LEV Electronic linear expan.valve SW14(A.B) Switch (connection No.set) ✻ Capacitor
MF,MF1,MF2 Fan motor
C,C1,C2 ✻ Capacitor(for MF,MF1,MF2) SW1(A.B) Switch (for mode selection) MODELS 20/25/32 2.5µF
S.B Surge absorber board
SW2(I.B) Switch (for capacity code) MODELS 40/80 5.0µF
I.B Indoor controller board LS Limit switch (MV built in)
MODELS 50 4.0µF
A.B Address board MV Motor for vane (with limit switch) SW3(I.B) Switch (for mode selection)
MODELS 63 6.0µF
TB2 Power source terminal bed DS Drain sensor SW4(I.B) Switch (for model selection)
MODELS 100/125 5.0µF ✕ 2
TB5 Transmission terminal bed TH21 Thermistor (inlet temp.detection) SW5(A.B) Switch (for voltage selection)
TB15 Transmission terminal bed TH22 Thermistor (pipe temp.detection / liquid) SWA(A.B) Switch (option parts)
F Fuse AC250V 6.3A F TH23 Thermistor (pipe temp.detection / gas) SWC(A.B) Switch (option parts)
T Transformer SW11(A.B) Switch (1st digit address set) X1,X3,X4 Aux.relay
DP Dorain pump SW12(A.B) Switch (2nd digit address set)
6. Temperature/Airflow distribution
●Temperature distribution
- PLFY-P20~63VLMD-B
< Cooling mode > < Heating mode >
Airflow angle : Horizontal Room temp.: 27˚C Airflow rate : High Airflow angle : Downward Room temp.: 20˚C Airflow rate : High

2.7 20
2.7
20
22 22
24 24 Unit:(˚C ) Unit:(˚C )
2 2
Height (m)

Height (m)
26 33 33 24
26 27 30 30 27
1 1
21

0 0
4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4
Floor distance (m) Floor distance (m)

- PLFY-P80~125VLMD-A
<Cooling mode> <Heating mode>
Flow angle : 20˚ Room temp. : 27˚C Flow angle : 70˚ Room temp. : 20˚C
3 3
20 20 22
24 22 ˚C ˚C
24
Height (m)

33
Height (m)
33
2 2
26 26 30
24
24 30 27
1 1
27
20 20

0 0
4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4
Floor distance (m) Floor distance (m)

Airflow rate : Low Flow angle : 70˚ Room temp. : 21˚C


˚C
note : These figures show typical temperature distributions 3

in the conditions above. In the actual installation,


they may differ from these figures under the
Height (m)

2
influence of air temperature conditions, ceiling 30 28
height, cooling/heating load,obstacles,etc.
24
1
20 20

0
4 3 2 1 0 1 2 3 4
Floor distance (m)

VLMD-A/VLMD-B
PLFY-P-

2- 149
● Airflow distribution
- PLFY-P20~63VLMD-B
< Cooling mode > < Heating mode >
Airflow angle : Horizontal Room temp.: 27˚C Airflow rate : High Airflow angle : Downward Room temp.: 20˚C Airflow rate : High

2.7 2.0 2.0


2.7
0.1 0.3 0.5 0.5 0.3 0.1 Unit:(m/s )
2 2
Height (m)

Height (m)
1.0 1.0

0.5 0.5 0.1


0.1 0.25 0.25
1 1

0 0
4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4
Floor distance (m) Floor distance (m)

- PLFY-P80~125VLMD-A
<Cooling mode> <Heating mode>
Flow angle : 20˚ Room temp. : 27˚C Flow angle : 70˚ Room temp. : 20˚C
3 3
0.3 0.5 2.0 2.0 0.5 0.3
0.1 m/s 0.1 m/s
Height (m)

Height (m)
2 2
1.0 1.0

0.5 0.5 0.25 0.1


1 1
0.1 0.25

0 0
4 3 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4
Floor distance (m) Floor distance (m)
note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ
from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

7. Options

Description Model Applicable capacity


CMP-40VLW-B P20/P25/P32/P40
CMP-63VLW-B P50/P63
VLMD-A/VLMD-B

Decoration panel
CMP-63LW-F P80
PLFY-P-

CMP-125LW-F P100/P125
OA duct flange PAC-KH11OF P20/P25/P32/P40/P50/P63

2- 150
Cassette ceiling(4-way flow) PLFY-P-VKM-A
PLFY-P-VAM-A
CONTENTS

1. Specifications ·································································2-152

2. Capacity Tables ······························································2-153


2-1 Cooling Capacity(PUMY) ················································2-153
2-2 Heating Capacity(PUMY) ················································2-154
2-3 Cooling Capacity(Y/R2-8·10·13HP) ·······························2-155
2-4 Heating Capacity(Y/R2-8·10·13HP) ·······························2-156
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ······················2-157
2-6 Heating Capacity(Big Y, Super Y, Big R2) ······················2-158
2-7 Cooling Capacity(WY, WR2) ········································· 2-159
2-8 Heating Capacity(WY, WR2) ········································· 2-160

3. Sound Levels ·······························································2-161


3-1 Noise levels ································································2-161
3-2 N/C curves ··································································2-161

4. External Dimensions ····················································2-162

5. Electrical Wiring Diagrams ············································2-164

6. Temperature/Airflow distribution ··································2-166

7. Options ·············································································2-167
VKM-A/VAM-A
PLFY-P-

2- 151
1. Specifications
PLFY-P32VKM-A PLFY-P40VKM-A PLFY-P50VKM-A PLFY-P63VKM-A
Power source ~ 220-240V 50Hz / ~ 220V 60Hz
❇1 kW 3.6 4.5 5.6 7.1
Cooling capacity
❇2 kcal/h 3,150 4,000 5,000 6,300
Heating capacity ❇1 kW 4.0 5.0 6.3 8.0
Power Cooling kW 0.13 0.14 0.15
consumption Heating kW 0.13 0.14 0.15
Cooling A 0.60 0.64 0.68
Current
Heating A 0.60 0.64 0.68
External finish(Munsel No.) Panel : 0.70Y 8.59/0.97
Height mm 298(30)
Dimension ❇ 3 Width mm 660(760)
Depth mm 660(760)
Net weight ❇3 kg 19(3.7) 20(3.7)
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Turbo fan
Airflow rate ❇3
m3/min 13-14-14.5-15 13-14-15-16 14-15-16-17
Fan (Low-Mid2-Mid1-High)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.030
Air filter PP Honeycomb
Gas mm ø 12.7 ø 15.88
Refrigerant (Flare)
pipe dimension
Liquid mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension VP-25
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4 dB(A) 31-32.5-34-35 32-34-35.5-37 35-36.5-38-39

PLFY-P80VAM-A PLFY-P100VAM-A PLFY-P125VAM-A


Power source ~ 220-240V 50Hz / ~ 220V 60Hz
Cooling capacity ❇1 kW 9.0 11.2 14.0
❇2 kcal/h 8,000 10,000 12,500
Heating capacity ❇1 kW 10.0 12.5 16.0
Power Cooling kW 0.18 0.30 0.34
consumption Heating kW 0.18 0.30 0.34
Cooling A 0.86 1.43 1.64
Current
Heating A 0.86 1.43 1.64
External finish(Munsel No.) Panel : 0.70Y 8.59/0.97
Height mm 258(30) 298(30)
Dimension ❇3 Width mm 840(950)
Depth mm 840(950)
Net weight ❇3 kg 24(5) 30(5) 30(5)
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Turbo fan
Airflow rate ❇ 3
m3/min 16-18-20-22 20-23-26-28 22-25-28-30
Fan (Low-Mid2-Mid1-High)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.070 0.120
Air filter PP Honeycomb
Gas mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
VKM-A/VAM-A

(Flare)
Drain pipe dimension VP-25
PLFY-P-

Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4 dB(A) 30-32-35-37 33-36-39-41 35-38-41-43

Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27 ˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 External dimension/ net weight are shown in (unit/panel) , and airflow rate/noise level are in (low-middle2-middle1-high).
❇ 4 It is measured in anechoic room.

2- 152
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA :Capacity(kW)
PLFY-P-VKM-AVAM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 3.6 2.7 3.7 2.8 4.0 2.8 4.2 2.9
22.5 3.5 2.7 3.7 2.8 4.0 2.8 4.2 2.9
25.0 3.5 2.7 3.7 2.8 3.9 2.8 4.1 2.8
27.5 3.4 2.6 3.6 2.8 3.9 2.7 4.1 2.8
32 30.0 3.4 2.6 3.6 2.7 3.8 2.7 4.1 2.8
(3.6) 32.5 3.3 2.6 3.6 2.7 3.8 2.7 4.0 2.8
35.0 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.8
37.5 3.2 2.5 3.5 2.7 3.7 2.6 3.9 2.7
40.0 3.2 2.5 3.4 2.7 3.6 2.6 3.9 2.7
46.0 3.1 2.5 3.3 2.6 3.5 2.6 3.7 2.7
20.0 4.5 3.4 4.7 3.5 5.0 3.5 5.3 3.6
22.5 4.4 3.4 4.6 3.5 5.0 3.5 5.2 3.6
25.0 4.3 3.3 4.6 3.5 4.9 3.5 5.2 3.6
27.5 4.3 3.3 4.6 3.5 4.9 3.5 5.1 3.6
40 30.0 4.2 3.3 4.5 3.5 4.8 3.4 5.1 3.5
(4.5) 32.5 4.2 3.3 4.4 3.4 4.7 3.4 5.0 3.5
35.0 4.1 3.2 4.4 3.4 4.7 3.4 5.0 3.5
37.5 4.1 3.2 4.3 3.4 4.6 3.3 4.9 3.5
40.0 4.0 3.2 4.3 3.4 4.5 3.3 4.8 3.4
46.0 3.8 3.1 4.1 3.3 4.3 3.2 4.6 3.4
20.0 5.5 4.0 5.8 4.2 6.2 4.1 6.6 4.3
22.5 5.5 4.0 5.8 4.1 6.2 4.1 6.5 4.2
25.0 5.4 3.9 5.7 4.1 6.1 4.1 6.4 4.2
27.5 5.3 3.9 5.7 4.1 6.0 4.1 6.4 4.2
50 30.0 5.3 3.9 5.6 4.1 5.9 4.0 6.3 4.1
(5.6) 32.5 5.2 3.8 5.5 4.0 5.9 4.0 6.2 4.1
35.0 5.1 3.8 5.5 4.0 5.8 3.9 6.2 4.1
37.5 5.0 3.7 5.4 3.9 5.7 3.9 6.1 4.0
40.0 5.0 3.7 5.3 3.9 5.6 3.9 6.0 4.0
46.0 4.8 3.6 5.1 3.8 5.4 3.8 5.8 3.9
20.0 7.0 4.9 7.4 5.1 7.9 5.1 8.3 5.2
22.5 6.9 4.9 7.3 5.1 7.8 5.1 8.2 5.2
25.0 6.9 4.8 7.3 5.1 7.7 5.0 8.2 5.2
27.5 6.8 4.8 7.2 5.0 7.7 5.0 8.1 5.1
63 30.0 6.7 4.7 7.1 5.0 7.5 4.9 8.0 5.1
(7.1) 32.5 6.6 4.7 7.0 4.9 7.5 4.9 7.9 5.0
35.0 6.5 4.6 6.9 4.9 7.3 4.8 7.8 5.0
37.5 6.4 4.6 6.8 4.8 7.2 4.8 7.7 5.0
40.0 6.3 4.6 6.7 4.8 7.2 4.7 7.6 4.9
46.0 6.1 4.4 6.5 4.7 6.9 4.6 7.3 4.8
20.0 8.9 6.4 9.4 6.7 10.0 6.7 10.6 6.9
22.5 8.8 6.4 9.3 6.7 9.9 6.6 10.4 6.8
25.0 8.7 6.3 9.2 6.6 9.8 6.6 10.4 6.8
27.5 8.6 6.3 9.1 6.6 9.7 6.5 10.3 6.7
80
30.0 8.5 6.2 9.0 6.5 9.5 6.5 10.2 6.7
(9.0)
32.5 8.3 6.1 8.9 6.5 9.5 6.4 10.0 6.6
35.0 8.2 6.1 8.8 6.4 9.3 6.4 9.9 6.6
37.5 8.1 6.0 8.6 6.4 9.2 6.3 9.8 6.5
40.0 8.0 6.0 8.6 6.3 9.1 6.2 9.6 6.5
46.0 7.7 5.8 8.2 6.2 8.7 6.1 9.3 6.3
20.0 11.1 8.1 11.6 8.4 12.5 8.4 13.1 8.6
22.5 10.9 8.0 11.5 8.4 12.3 8.3 13.0 8.6
25.0 10.8 8.0 11.5 8.3 12.2 8.3 12.9 8.5
27.5 10.7 7.9 11.3 8.3 12.1 8.2 12.8 8.5
100 30.0 10.5 7.8 11.2 8.2 11.9 8.1 12.6 8.4
(11.2) 32.5 10.4 7.7 11.1 8.2 11.8 8.1 12.5 8.4
35.0 10.2 7.7 10.9 8.1 11.6 8.0 12.3 8.3
37.5 10.1 7.6 10.8 8.0 11.4 7.9 12.2 8.2
40.0 10.0 7.5 10.6 7.9 11.3 7.9 12.0 8.1
46.0 9.6 7.4 10.2 7.8 10.8 7.7 11.5 7.9
20.0 13.9 9.7 14.6 10.1 15.6 10.1 16.4 10.3
VKM-A/VAM-A

22.5 13.7 9.6 14.4 10.0 15.4 10.0 16.2 10.2


25.0 13.5 9.5 14.3 10.0 15.3 9.9 16.1 10.2
PLFY-P-

27.5 13.4 9.4 14.2 9.9 15.1 9.8 16.0 10.1


125 30.0 13.2 9.3 14.0 9.8 14.9 9.7 15.8 10.0
(14.0) 32.5 13.0 9.2 13.8 9.7 14.7 9.6 15.6 9.9
35.0 12.8 9.1 13.7 9.6 14.5 9.5 15.4 9.8
37.5 12.6 9.0 13.4 9.5 14.3 9.4 15.2 9.8
40.0 12.5 9.0 13.3 9.4 14.1 9.4 15.0 9.7
46.0 12.0 8.7 12.8 9.2 13.5 9.1 14.4 9.4

2- 153
2-2.Heating Capacity (In combination with PUMY)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 Unit air temp. 15.0 20.0 25.0
size size
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 2.5 2.5 2.5 -12.0 6.4 6.2 6.1
-10.0 2.7 2.6 2.6 -10.0 6.7 6.6 6.5
-5.0 3.1 3.0 3.0 -5.0 7.6 7.5 7.4
0.0 3.5 3.4 3.4 0.0 8.7 8.6 8.5
32 2.5 3.7 3.7 3.6 80 2.5 9.2 9.2 9.0
6.0 4.0 4.0 3.9 6.0 10.1 10.0 9.9
7.5 4.2 4.1 4.0 7.5 10.4 10.4 9.9
10.0 4.4 4.4 4.0 10.0 11.1 11.0 9.9
12.5 4.7 4.4 4.0 12.5 11.7 11.0 9.9
15.5 4.9 4.4 4.0 15.5 12.3 11.0 9.9
-12.0 3.2 3.1 3.1 -12.0 8.0 7.8 7.7
-10.0 3.4 3.3 3.2 -10.0 8.4 8.2 8.1
-5.0 3.8 3.8 3.7 -5.0 9.6 9.4 9.3
0.0 4.3 4.3 4.2 0.0 10.9 10.7 10.6
2.5 4.6 4.6 4.5 2.5 11.5 11.4 11.3
40 100
6.0 5.0 5.0 4.9 6.0 12.6 12.5 12.3
7.5 5.2 5.2 5.0 7.5 13.0 12.9 12.4
10.0 5.5 5.5 5.0 10.0 13.8 13.7 12.4
12.5 5.9 5.5 5.0 12.5 14.6 13.8 12.4
15.5 6.2 5.5 5.0 15.5 15.4 13.8 12.4
-12.0 4.0 3.9 3.9 -12.0 10.2 10.0 9.8
-10.0 4.2 4.2 4.1 -10.0 10.7 10.6 10.4
-5.0 4.8 4.8 4.7 -5.0 12.2 12.1 11.9
0.0 5.5 5.4 5.3 0.0 13.9 13.8 13.6
2.5 5.8 5.8 5.7 2.5 14.8 14.7 14.5
50 125
6.0 6.3 6.3 6.2 6.0 16.1 16.0 15.8
7.5 6.6 6.5 6.2 7.5 16.7 16.6 15.8
10.0 7.0 6.9 6.2 10.0 17.7 17.6 15.8
12.5 7.4 7.0 6.2 12.5 18.7 17.7 15.8
15.5 7.7 7.0 6.2 15.5 19.7 17.7 15.8
-12.0 5.1 5.0 4.9
-10.0 5.4 5.3 5.2
-5.0 6.1 6.0 5.9
0.0 6.9 6.9 6.8
2.5 7.4 7.3 7.2
63
6.0 8.0 8.0 7.9
7.5 8.3 8.3 7.9
10.0 8.8 8.8 7.9
12.5 9.4 8.8 7.9
15.5 9.8 8.8 7.9
VKM-A/VAM-A
PLFY-P-

2- 154
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA :Capacity(kW)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.5 2.7 3.6 2.7 3.7 2.7 3.8 2.7 3.9 2.8 4.0 2.7 4.2 2.6
22.5 3.5 2.7 3.6 2.7 3.7 2.7 3.8 2.7 3.9 2.8 4.0 2.7 4.1 2.6
25.0 3.5 2.6 3.5 2.7 3.7 2.6 3.7 2.7 3.8 2.8 4.0 2.7 4.1 2.6
27.5 3.4 2.6 3.5 2.7 3.6 2.6 3.7 2.7 3.8 2.7 3.9 2.7 4.1 2.6
32 30.0 3.4 2.6 3.5 2.7 3.6 2.6 3.7 2.6 3.7 2.7 3.9 2.7 4.0 2.6
(3.6)
32.5 3.3 2.6 3.4 2.7 3.6 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.0 2.6
35.0 3.3 2.6 3.4 2.6 3.5 2.6 3.6 2.6 3.7 2.7 3.8 2.6 4.0 2.6
37.5 3.3 2.6 3.3 2.6 3.5 2.6 3.6 2.6 3.6 2.7 3.8 2.6 3.9 2.6
40.0 3.2 2.5 3.3 2.6 3.5 2.6 3.5 2.6 3.6 2.7 3.7 2.6 3.9 2.5
43.0 3.2 2.5 3.3 2.6 3.4 2.5 3.5 2.6 3.6 2.7 3.7 2.6 3.8 2.5
20.0 4.4 3.4 4.5 3.5 4.7 3.4 4.8 3.4 4.9 3.5 5.0 3.4 5.2 3.3
22.5 4.4 3.4 4.5 3.4 4.6 3.4 4.7 3.4 4.8 3.5 5.0 3.4 5.2 3.3
25.0 4.3 3.3 4.4 3.4 4.6 3.3 4.7 3.4 4.8 3.5 5.0 3.4 5.1 3.3
27.5 4.3 3.3 4.4 3.4 4.5 3.3 4.6 3.4 4.7 3.5 4.9 3.4 5.1 3.3
40 30.0 4.2 3.3 4.3 3.4 4.5 3.3 4.6 3.3 4.7 3.5 4.9 3.4 5.0 3.3
(4.5)
32.5 4.2 3.3 4.3 3.4 4.5 3.3 4.5 3.3 4.6 3.4 4.8 3.4 5.0 3.3
35.0 4.1 3.2 4.2 3.3 4.4 3.3 4.5 3.3 4.6 3.4 4.8 3.3 5.0 3.3
37.5 4.1 3.2 4.2 3.3 4.4 3.2 4.5 3.3 4.5 3.4 4.7 3.3 4.9 3.2
40.0 4.1 3.2 4.1 3.3 4.3 3.2 4.4 3.3 4.5 3.4 4.7 3.3 4.9 3.2
43.0 4.0 3.2 4.1 3.3 4.3 3.2 4.4 3.2 4.4 3.4 4.6 3.3 4.8 3.2
20.0 5.5 4.0 5.6 4.1 5.8 4.0 5.9 4.0 6.0 4.1 6.3 4.0 6.5 3.9
22.5 5.4 3.9 5.5 4.0 5.8 3.9 5.9 4.0 6.0 4.1 6.2 4.0 6.4 3.9
25.0 5.4 3.9 5.5 4.0 5.7 3.9 5.8 3.9 5.9 4.1 6.2 3.9 6.4 3.8
27.5 5.3 3.9 5.4 4.0 5.7 3.9 5.8 3.9 5.9 4.0 6.1 3.9 6.3 3.8
50 30.0 5.3 3.9 5.4 3.9 5.6 3.9 5.7 3.9 5.8 4.0 6.0 3.9 6.3 3.8
(5.6)
32.5 5.2 3.8 5.3 3.9 5.5 3.8 5.7 3.9 5.8 4.0 6.0 3.9 6.2 3.8
35.0 5.2 3.8 5.3 3.9 5.5 3.8 5.6 3.8 5.7 4.0 5.9 3.9 6.2 3.8
37.5 5.1 3.8 5.2 3.9 5.4 3.8 5.5 3.8 5.7 3.9 5.9 3.8 6.1 3.7
40.0 5.0 3.7 5.2 3.8 5.4 3.8 5.5 3.8 5.6 3.9 5.8 3.8 6.0 3.7
43.0 5.0 3.7 5.1 3.8 5.3 3.7 5.4 3.8 5.5 3.9 5.8 3.8 6.0 3.7
20.0 7.0 4.9 7.1 5.0 7.4 4.9 7.5 4.9 7.7 5.0 8.0 4.9 8.2 4.7
22.5 6.9 4.9 7.0 4.9 7.3 4.8 7.5 4.8 7.6 5.0 7.9 4.8 8.2 4.7
25.0 6.8 4.8 7.0 4.9 7.2 4.8 7.4 4.8 7.5 4.9 7.8 4.8 8.1 4.7
27.5 6.7 4.8 6.9 4.9 7.2 4.8 7.3 4.8 7.5 4.9 7.7 4.8 8.0 4.6
63 30.0 6.7 4.7 6.8 4.8 7.1 4.7 7.2 4.7 7.4 4.9 7.7 4.7 8.0 4.6
(7.1)
32.5 6.6 4.7 6.7 4.8 7.0 4.7 7.2 4.7 7.3 4.8 7.6 4.7 7.9 4.6
35.0 6.5 4.7 6.7 4.8 7.0 4.7 7.1 4.7 7.2 4.8 7.5 4.7 7.8 4.6
37.5 6.5 4.6 6.6 4.7 6.9 4.6 7.0 4.6 7.2 4.8 7.5 4.7 7.7 4.5
40.0 6.4 4.6 6.5 4.7 6.8 4.6 7.0 4.6 7.1 4.8 7.4 4.6 7.7 4.5
43.0 6.3 4.6 6.4 4.6 6.7 4.6 6.9 4.6 7.0 4.7 7.3 4.6 7.6 4.5
20.0 8.8 6.4 9.0 6.5 9.4 6.4 9.5 6.4 9.7 6.6 10.1 6.4 10.4 6.2
22.5 8.7 6.4 8.9 6.5 9.3 6.3 9.5 6.4 9.6 6.6 10.0 6.4 10.4 6.2
25.0 8.6 6.3 8.8 6.4 9.2 6.3 9.4 6.3 9.5 6.5 9.9 6.4 10.3 6.2
27.5 8.6 6.3 8.7 6.4 9.1 6.3 9.3 6.3 9.5 6.5 9.8 6.3 10.2 6.1
80 30.0 8.5 6.2 8.6 6.4 9.0 6.2 9.2 6.3 9.4 6.5 9.7 6.3 10.1 6.1
(9.0)
32.5 8.4 6.2 8.6 6.3 8.9 6.2 9.1 6.2 9.3 6.4 9.6 6.3 10.0 6.1
35.0 8.3 6.1 8.5 6.3 8.8 6.1 9.0 6.2 9.2 6.4 9.5 6.2 9.9 6.0
37.5 8.2 6.1 8.4 6.2 8.7 6.1 8.9 6.1 9.1 6.3 9.5 6.2 9.8 6.0
40.0 8.1 6.0 8.3 6.2 8.6 6.1 8.8 6.1 9.0 6.3 9.4 6.1 9.7 6.0
43.0 8.0 6.0 8.2 6.1 8.5 6.0 8.7 6.1 8.9 6.3 9.3 6.1 9.6 5.9
20.0 11.0 8.0 11.2 8.2 11.6 8.0 11.9 8.1 12.1 8.3 12.5 8.1 13.0 7.9
22.5 10.9 8.0 11.1 8.2 11.5 8.0 11.8 8.0 12.0 8.3 12.4 8.1 12.9 7.8
25.0 10.8 7.9 11.0 8.1 11.4 7.9 11.6 8.0 11.9 8.2 12.3 8.0 12.8 7.8
27.5 10.6 7.9 10.9 8.1 11.3 7.9 11.5 7.9 11.8 8.2 12.2 8.0 12.7 7.8
100 30.0 10.5 7.8 10.8 8.0 11.2 7.8 11.4 7.9 11.6 8.1 12.1 7.9 12.5 7.7
(11.2)
32.5 10.4 7.8 10.6 7.9 11.1 7.8 11.3 7.8 11.5 8.1 12.0 7.9 12.4 7.7
35.0 10.3 7.7 10.5 7.9 11.0 7.7 11.2 7.8 11.4 8.1 11.9 7.9 12.3 7.6
37.5 10.2 7.7 10.4 7.8 10.9 7.7 11.1 7.8 11.3 8.0 11.8 7.8 12.2 7.6
40.0 10.1 7.6 10.3 7.8 10.8 7.6 11.0 7.7 11.2 8.0 11.6 7.8 12.1 7.6
43.0 9.9 7.5 10.2 7.7 10.6 7.6 10.8 7.6 11.1 7.9 11.5 7.7 12.0 7.5
20.0 13.7 9.6 14.0 9.8 14.6 9.6 14.8 9.6 15.1 9.9 15.7 9.6 16.2 9.3
VKM-A/VAM-A

22.5 13.6 9.6 13.9 9.7 14.4 9.5 14.7 9.5 15.0 9.8 15.5 9.5 16.1 9.2
25.0 13.4 9.5 13.7 9.7 14.3 9.4 14.6 9.5 14.8 9.7 15.4 9.5 16.0 9.2
PLFY-P-

27.5 13.3 9.4 13.6 9.6 14.1 9.4 14.4 9.4 14.7 9.7 15.3 9.4 15.8 9.1
125 30.0 13.2 9.3 13.4 9.5 14.0 9.3 14.3 9.3 14.6 9.6 15.1 9.3 15.7 9.1
(14.0)
32.5 13.0 9.3 13.3 9.4 13.9 9.2 14.1 9.3 14.4 9.5 15.0 9.3 15.5 9.0
35.0 12.9 9.2 13.2 9.4 13.7 9.2 14.0 9.2 14.3 9.5 14.8 9.2 15.4 9.0
37.5 12.7 9.1 13.0 9.3 13.6 9.1 13.9 9.1 14.1 9.4 14.7 9.2 15.3 8.9
40.0 12.6 9.0 12.9 9.2 13.4 9.0 13.7 9.1 14.0 9.4 14.6 9.1 15.1 8.9
43.0 12.4 9.0 12.7 9.1 13.3 9.0 13.6 9.0 13.8 9.3 14.4 9.1 15.0 8.8

2- 155
2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 2.7 2.6 2.6 2.6 -15.0 6.7 6.6 6.5 6.5
-10.0 3.1 3.0 3.0 2.8 -10.0 7.6 7.5 7.4 6.9
-5.0 3.4 3.4 3.1 2.8 -5.0 8.6 8.5 7.8 6.9
0.0 3.8 3.8 3.1 2.8 0.0 9.5 9.4 7.8 6.9
2.5 4.0 4.0 3.1 2.8 2.5 10.0 9.9 7.8 6.9
32 80
6.0 4.0 4.0 3.1 2.8 6.0 10.1 10.0 7.8 6.9
7.5 4.2 4.0 3.1 2.8 7.5 10.5 10.0 7.8 6.9
10.0 4.5 4.0 3.1 2.8 10.0 11.2 10.0 7.8 6.9
12.5 4.8 4.0 3.1 2.8 12.5 12.0 10.0 7.8 6.9
15.5 4.8 4.0 3.1 2.8 15.5 12.1 10.0 7.8 6.9
-15.0 3.3 3.3 3.3 3.3 -15.0 8.4 8.2 8.2 8.1
-10.0 3.8 3.8 3.7 3.5 -10.0 9.6 9.4 9.3 8.6
-5.0 4.3 4.2 3.9 3.5 -5.0 10.7 10.6 9.8 8.6
0.0 4.8 4.7 3.9 3.5 0.0 11.9 11.8 9.8 8.6
2.5 5.0 5.0 3.9 3.5 2.5 12.5 12.4 9.8 8.6
40 100
6.0 5.1 5.0 3.9 3.5 6.0 12.6 12.5 9.8 8.6
7.5 5.3 5.0 3.9 3.5 7.5 13.2 12.5 9.8 8.6
10.0 5.6 5.0 3.9 3.5 10.0 14.1 12.5 9.8 8.6
12.5 6.0 5.0 3.9 3.5 12.5 15.0 12.5 9.8 8.6
15.5 6.1 5.0 3.9 3.5 15.5 15.1 12.5 9.8 8.6
-15.0 4.2 4.2 4.1 4.1 -15.0 10.7 10.6 10.5 10.4
-10.0 4.8 4.8 4.7 4.3 -10.0 12.2 12.1 11.9 11.0
-5.0 5.4 5.3 4.9 4.3 -5.0 13.7 13.6 12.5 11.0
0.0 6.0 5.9 4.9 4.3 0.0 15.3 15.1 12.5 11.0
2.5 6.3 6.2 4.9 4.3 2.5 16.0 15.8 12.5 11.0
50 125
6.0 6.4 6.3 4.9 4.3 6.0 16.2 16.0 12.5 11.0
7.5 6.6 6.3 4.9 4.3 7.5 16.8 16.0 12.5 11.0
10.0 7.1 6.3 4.9 4.3 10.0 18.0 16.0 12.5 11.0
12.5 7.5 6.3 4.9 4.3 12.5 19.1 16.0 12.5 11.0
15.5 7.6 6.3 4.9 4.3 15.5 19.4 16.0 12.5 11.0
-15.0 5.4 5.3 5.2 5.2
-10.0 6.1 6.0 6.0 5.5
-5.0 6.9 6.8 6.2 5.5
0.0 7.6 7.5 6.2 5.5
2.5 8.0 7.9 6.2 5.5
63
6.0 8.1 8.0 6.2 5.5
7.5 8.4 8.0 6.2 5.5
10.0 9.0 8.0 6.2 5.5
12.5 9.6 8.0 6.2 5.5
15.5 9.7 8.0 6.2 5.5
VKM-A/VAM-A
PLFY-P-

2- 156
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA :Capacity(kW)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.8 4.2 2.8 4.5 2.8
22.5 3.3 2.6 3.5 2.7 3.7 2.7 4.0 2.8 4.2 2.8 4.4 2.7
25.0 3.3 2.6 3.4 2.7 3.7 2.6 3.9 2.8 4.1 2.8 4.4 2.7
27.5 3.3 2.5 3.4 2.6 3.6 2.6 3.9 2.8 4.1 2.7 4.3 2.7
32 30.0 3.2 2.5 3.4 2.6 3.6 2.6 3.8 2.8 4.0 2.7 4.2 2.7
32.5 3.2 2.5 3.3 2.6 3.5 2.6 3.8 2.7 4.0 2.7 4.2 2.6
35.0 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.9 2.7 4.1 2.6
37.5 3.2 2.5 3.3 2.6 3.5 2.6 3.7 2.7 3.8 2.7 4.0 2.6
40.0 3.1 2.5 3.2 2.6 3.4 2.5 3.6 2.7 3.8 2.6 4.0 2.6
43.0 3.1 2.5 3.2 2.5 3.4 2.5 3.5 2.7 3.7 2.6 3.9 2.6
20.0 4.1 3.2 4.3 3.4 4.7 3.4 5.0 3.6 5.3 3.5 5.6 3.5
22.5 4.1 3.2 4.3 3.4 4.6 3.4 4.9 3.6 5.2 3.5 5.5 3.5
25.0 4.1 3.2 4.3 3.4 4.6 3.3 4.9 3.5 5.2 3.5 5.5 3.4
27.5 4.1 3.2 4.2 3.3 4.5 3.3 4.8 3.5 5.1 3.5 5.4 3.4
40 30.0 4.0 3.2 4.2 3.3 4.5 3.3 4.8 3.5 5.0 3.4 5.3 3.4
32.5 4.0 3.2 4.2 3.3 4.4 3.3 4.7 3.5 5.0 3.4 5.2 3.3
35.0 4.0 3.2 4.1 3.3 4.4 3.3 4.6 3.4 4.9 3.4 5.1 3.3
37.5 3.9 3.2 4.1 3.3 4.3 3.2 4.6 3.4 4.8 3.4 5.1 3.3
40.0 3.9 3.1 4.0 3.2 4.3 3.2 4.5 3.4 4.7 3.3 5.0 3.3
43.0 3.9 3.1 4.0 3.2 4.2 3.2 4.4 3.4 4.7 3.3 4.9 3.2
20.0 5.2 3.8 5.4 4.0 5.8 4.0 6.2 4.2 6.6 4.1 7.0 4.1
22.5 5.2 3.8 5.4 3.9 5.8 3.9 6.2 4.1 6.5 4.1 6.9 4.0
25.0 5.1 3.8 5.3 3.9 5.7 3.9 6.1 4.1 6.4 4.0 6.8 4.0
27.5 5.1 3.8 5.3 3.9 5.6 3.9 6.0 4.1 6.3 4.0 6.7 3.9
50 30.0 5.0 3.7 5.2 3.9 5.6 3.8 5.9 4.0 6.2 4.0 6.6 3.9
32.5 5.0 3.7 5.2 3.8 5.5 3.8 5.8 4.0 6.2 3.9 6.5 3.9
35.0 4.9 3.7 5.1 3.8 5.4 3.8 5.8 4.0 6.1 3.9 6.4 3.8
37.5 4.9 3.7 5.1 3.8 5.4 3.8 5.7 3.9 6.0 3.9 6.3 3.8
40.0 4.9 3.7 5.0 3.8 5.3 3.7 5.6 3.9 5.9 3.8 6.2 3.8
43.0 4.8 3.6 5.0 3.7 5.2 3.7 5.5 3.9 5.8 3.8 6.1 3.7
20.0 6.5 4.7 6.9 4.9 7.4 4.9 7.9 5.1 8.4 5.0 8.9 5.0
22.5 6.5 4.7 6.8 4.8 7.3 4.8 7.8 5.1 8.3 5.0 8.7 4.9
25.0 6.5 4.6 6.8 4.8 7.2 4.8 7.7 5.0 8.1 4.9 8.6 4.9
27.5 6.4 4.6 6.7 4.8 7.2 4.8 7.6 5.0 8.0 4.9 8.5 4.8
63 30.0 6.4 4.6 6.6 4.7 7.1 4.7 7.5 4.9 7.9 4.9 8.4 4.8
32.5 6.3 4.6 6.6 4.7 7.0 4.7 7.4 4.9 7.8 4.8 8.2 4.7
35.0 6.3 4.5 6.5 4.7 6.9 4.6 7.3 4.8 7.7 4.8 8.1 4.7
37.5 6.2 4.5 6.4 4.6 6.8 4.6 7.2 4.8 7.6 4.7 8.0 4.6
40.0 6.2 4.5 6.4 4.6 6.7 4.6 7.1 4.8 7.5 4.7 7.9 4.6
43.0 6.1 4.5 6.3 4.6 6.6 4.5 7.0 4.7 7.3 4.6 7.7 4.5
20.0 8.3 6.1 8.7 6.4 9.4 6.4 10.0 6.7 10.6 6.6 11.2 6.5
22.5 8.3 6.1 8.7 6.4 9.3 6.3 9.9 6.7 10.5 6.6 11.1 6.5
25.0 8.2 6.1 8.6 6.3 9.2 6.3 9.8 6.6 10.3 6.5 10.9 6.4
27.5 8.1 6.1 8.5 6.3 9.1 6.2 9.6 6.6 10.2 6.5 10.8 6.4
80 30.0 8.1 6.0 8.4 6.2 9.0 6.2 9.5 6.5 10.0 6.4 10.6 6.3
32.5 8.0 6.0 8.3 6.2 8.9 6.2 9.4 6.5 9.9 6.4 10.4 6.2
35.0 8.0 6.0 8.2 6.2 8.8 6.1 9.3 6.4 9.8 6.3 10.3 6.2
37.5 7.9 5.9 8.1 6.1 8.6 6.1 9.1 6.4 9.6 6.3 10.1 6.1
40.0 7.8 5.9 8.1 6.1 8.5 6.0 9.0 6.3 9.5 6.2 10.0 6.1
43.0 7.7 5.9 8.0 6.0 8.4 6.0 8.9 6.2 9.3 6.1 9.8 6.0
20.0 10.3 7.7 10.8 8.0 11.6 8.0 12.5 8.5 13.2 8.4 14.0 8.2
22.5 10.3 7.7 10.8 8.0 11.5 8.0 12.3 8.4 13.0 8.3 13.8 8.2
25.0 10.2 7.7 10.7 8.0 11.4 7.9 12.1 8.4 12.8 8.2 13.6 8.1
27.5 10.1 7.6 10.6 7.9 11.3 7.9 12.0 8.3 12.7 8.2 13.4 8.0
100 30.0 10.1 7.6 10.5 7.9 11.2 7.8 11.8 8.2 12.5 8.1 13.2 7.9
32.5 10.0 7.6 10.3 7.8 11.0 7.8 11.7 8.2 12.3 8.0 13.0 7.9
35.0 9.9 7.5 10.2 7.8 10.9 7.7 11.5 8.1 12.1 8.0 12.8 7.8
37.5 9.8 7.5 10.1 7.7 10.8 7.6 11.4 8.0 12.0 7.9 12.6 7.7
40.0 9.7 7.4 10.0 7.7 10.6 7.6 11.2 8.0 11.8 7.8 12.4 7.7
43.0 9.6 7.4 9.9 7.6 10.5 7.5 11.0 7.9 11.6 7.7 12.2 7.6
20.0 12.9 9.2 13.5 9.6 14.6 9.6 15.6 10.1 16.5 9.9 17.5 9.7
22.5 12.9 9.2 13.5 9.5 14.4 9.5 15.4 10.0 16.3 9.8 17.2 9.7
25.0 12.8 9.1 13.3 9.5 14.3 9.4 15.2 9.9 16.1 9.7 17.0 9.6
27.5 12.7 9.1 13.2 9.4 14.1 9.4 15.0 9.8 15.8 9.6 16.7 9.5
125 30.0 12.6 9.0 13.1 9.3 13.9 9.3 14.8 9.7 15.6 9.6 16.5 9.4
32.5 12.5 9.0 12.9 9.3 13.8 9.2 14.6 9.6 15.4 9.5 16.2 9.3
35.0 12.4 8.9 12.8 9.2 13.6 9.1 14.4 9.5 15.2 9.4 16.0 9.2
VKM-A/VAM-A

37.5 12.3 8.9 12.7 9.1 13.5 9.0 14.2 9.5 15.0 9.3 15.7 9.1
40.0 12.2 8.8 12.5 9.1 13.3 9.0 14.0 9.4 14.8 9.2 15.5 9.0
PLFY-P-

43.0 12.0 8.8 12.4 9.0 13.1 8.9 13.8 9.3 14.5 9.1 15.2 8.9

2- 157
2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)

PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 2.5 2.5 2.4 2.4 -15.0 6.2 6.1 6.0 5.9
-10.0 2.8 2.8 2.8 2.7 -10.0 7.1 7.0 6.9 6.8
-5.0 3.2 3.2 3.1 3.1 -5.0 8.0 7.9 7.8 7.7
0.0 3.6 3.5 3.4 3.1 0.0 8.9 8.8 8.5 7.7
2.5 3.8 3.7 3.4 3.1 2.5 9.4 9.3 8.5 7.7
32 80
6.0 4.0 4.0 3.4 3.1 6.0 10.1 10.0 8.5 7.7
7.5 4.2 4.0 3.4 3.1 7.5 10.4 10.0 8.5 7.7
10.0 4.4 4.0 3.4 3.1 10.0 10.9 10.0 8.5 7.7
12.5 4.6 4.0 3.4 3.1 12.5 11.4 10.0 8.5 7.7
15.5 4.6 4.0 3.4 3.1 15.5 11.5 10.0 8.5 7.7
-15.0 3.1 3.1 3.0 3.0 -15.0 7.8 7.7 7.5 7.4
-10.0 3.6 3.5 3.5 3.4 -10.0 8.9 8.8 8.6 8.5
-5.0 4.0 4.0 3.9 3.9 -5.0 10.0 9.9 9.8 9.6
0.0 4.5 4.4 4.3 3.9 0.0 11.2 11.0 10.6 9.6
2.5 4.7 4.7 4.3 3.9 2.5 11.8 11.6 10.6 9.6
40 100
6.0 5.0 5.0 4.3 3.9 6.0 12.6 12.5 10.6 9.6
7.5 5.2 5.0 4.3 3.9 7.5 13.0 12.5 10.6 9.6
10.0 5.4 5.0 4.3 3.9 10.0 13.6 12.5 10.6 9.6
12.5 5.7 5.0 4.3 3.9 12.5 14.3 12.5 10.6 9.6
15.5 5.8 5.0 4.3 3.9 15.5 14.4 12.5 10.6 9.6
-15.0 3.9 3.9 3.8 3.7 -15.0 10.0 9.8 9.6 9.5
-10.0 4.5 4.4 4.3 4.3 -10.0 11.4 11.2 11.0 10.9
-5.0 5.0 5.0 4.9 4.9 -5.0 12.8 12.6 12.5 12.3
0.0 5.6 5.6 5.4 4.9 0.0 14.3 14.1 13.6 12.3
2.5 5.9 5.9 5.4 4.9 2.5 15.1 14.9 13.6 12.3
50 125
6.0 6.4 6.3 5.4 4.9 6.0 16.2 16.0 13.6 12.3
7.5 6.6 6.3 5.4 4.9 7.5 16.6 16.0 13.6 12.3
10.0 6.9 6.3 5.4 4.9 10.0 17.4 16.0 13.6 12.3
12.5 7.2 6.3 5.4 4.9 12.5 18.3 16.0 13.6 12.3
15.5 7.2 6.3 5.4 4.9 15.5 18.4 16.0 13.6 12.3
-15.0 5.0 4.9 4.8 4.7
-10.0 5.7 5.6 5.5 5.4
-5.0 6.4 6.3 6.2 6.2
0.0 7.2 7.1 6.8 6.2
2.5 7.5 7.5 6.8 6.2
63
6.0 8.1 8.0 6.8 6.2
7.5 8.3 8.0 6.8 6.2
10.0 8.7 8.0 6.8 6.2
12.5 9.1 8.0 6.8 6.2
15.5 9.2 8.0 6.8 6.2
VKM-A/VAM-A
PLFY-P-

2- 158
2-7.Cooling Capacity (In combination with WY, WR2)
CA :Capacity(kW)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Water 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
Unit temp.
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 3.5 2.7 3.6 2.8 3.9 2.7 4.0 2.8 4.1 2.9 4.3 2.8 4.5 2.8
20 3.4 2.6 3.5 2.7 3.7 2.7 3.8 2.7 3.9 2.8 4.1 2.8 4.4 2.7
32 30 3.2 2.5 3.3 2.6 3.5 2.6 3.6 2.6 3.7 2.7 3.9 2.7 4.1 2.6
40 2.8 2.3 2.9 2.4 3.1 2.4 3.1 2.4 3.2 2.5 3.4 2.5 3.6 2.5
45 2.6 2.2 2.7 2.3 2.9 2.3 3.0 2.4 3.0 2.5 3.2 2.4 3.4 2.4
10 4.4 3.4 4.5 3.5 4.8 3.4 5.0 3.5 5.1 3.6 5.4 3.6 5.7 3.5
20 4.2 3.3 4.4 3.4 4.6 3.4 4.8 3.4 4.9 3.5 5.2 3.5 5.5 3.4
40 30 4.0 3.2 4.1 3.3 4.4 3.3 4.5 3.3 4.6 3.4 4.9 3.4 5.2 3.3
40 3.5 2.9 3.6 3.0 3.8 3.0 3.9 3.1 4.0 3.2 4.3 3.2 4.5 3.1
45 3.3 2.8 3.4 2.9 3.6 2.9 3.7 3.0 3.8 3.1 4.0 3.1 4.2 3.0
10 5.5 4.0 5.6 4.1 6.0 4.0 6.2 4.1 6.3 4.2 6.7 4.2 7.1 4.1
20 5.3 3.9 5.4 4.0 5.8 3.9 5.9 4.0 6.1 4.1 6.5 4.1 6.8 4.0
50 30 5.0 3.7 5.1 3.8 5.5 3.8 5.6 3.8 5.8 4.0 6.1 3.9 6.4 3.8
40 4.3 3.4 4.5 3.5 4.7 3.5 4.9 3.5 5.0 3.7 5.3 3.6 5.6 3.6
45 4.1 3.3 4.2 3.4 4.5 3.4 4.6 3.4 4.7 3.6 5.0 3.5 5.3 3.4
10 6.9 4.9 7.2 5.0 7.6 5.0 7.8 5.0 8.0 5.2 8.5 5.1 9.0 5.0
20 6.7 4.7 6.9 4.9 7.3 4.8 7.5 4.9 7.8 5.0 8.2 5.0 8.6 4.9
63 30 6.3 4.5 6.5 4.7 6.9 4.6 7.1 4.7 7.3 4.9 7.7 4.8 8.1 4.7
40 5.5 4.1 5.7 4.3 6.0 4.2 6.2 4.3 6.4 4.4 6.7 4.4 7.1 4.3
45 5.2 4.0 5.3 4.1 5.7 4.1 5.8 4.1 6.0 4.3 6.3 4.2 6.7 4.2
10 8.8 6.4 9.1 6.6 9.6 6.5 9.9 6.6 10.2 6.8 10.8 6.7 11.4 6.6
20 8.5 6.2 8.7 6.4 9.3 6.3 9.5 6.4 9.8 6.7 10.4 6.5 10.9 6.4
80 30 8.0 6.0 8.3 6.2 8.8 6.1 9.0 6.2 9.3 6.4 9.8 6.3 10.3 6.2
40 6.9 5.5 7.2 5.7 7.6 5.6 7.8 5.7 8.1 5.9 8.5 5.8 9.0 5.7
45 6.5 5.3 6.8 5.5 7.2 5.4 7.4 5.5 7.6 5.7 8.0 5.6 8.5 5.6
10 10.9 8.0 11.3 8.3 12.0 8.2 12.3 8.3 12.7 8.6 13.4 8.4 14.1 8.3
20 10.5 7.8 10.9 8.1 11.6 8.0 11.9 8.1 12.2 8.4 12.9 8.3 13.6 8.1
100 30 9.9 7.5 10.3 7.8 10.9 7.7 11.2 7.8 11.5 8.1 12.2 8.0 12.8 7.8
40 8.6 6.9 8.9 7.2 9.5 7.1 9.7 7.2 10.0 7.5 10.6 7.4 11.2 7.3
45 8.1 6.7 8.4 6.9 8.9 6.9 9.2 7.0 9.5 7.3 10.0 7.2 10.5 7.0
10 13.7 9.6 14.1 9.9 15.0 9.8 15.4 9.8 15.9 10.2 16.7 10.0 17.7 9.8
20 13.2 9.3 13.6 9.6 14.5 9.5 14.8 9.6 15.3 9.9 16.1 9.8 17.0 9.6
125 30 12.4 9.0 12.8 9.2 13.6 9.1 14.0 9.2 14.4 9.5 15.2 9.4 16.1 9.2
40 10.8 8.1 11.2 8.4 11.9 8.3 12.2 8.4 12.5 8.7 13.2 8.6 14.0 8.5
45 10.2 7.8 10.5 8.1 11.2 8.0 11.5 8.1 11.8 8.5 12.5 8.3 13.2 8.2

VKM-A/VAM-A
PLFY-P-

2- 159
2-8.Heatling Capacity (In combination with WY, WR2)
PLFY-P-VKM-A,VAM-A SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp. 15 19 20 25 27
size
˚C SHC SHC SHC SHC SHC
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 8.8 8.7 8.5 6.8 6.1
20 10.3 10.2 10.0 8.0 7.2
80 30 10.3 10.2 10.0 8.0 7.2
40 10.7 10.6 10.4 8.3 7.5
45 11.7 11.6 11.4 9.1 8.2
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1
VKM-A/VAM-A
PLFY-P-

2- 160
3. Sound Levels
3-1. Noise level

Casette ceiling (VKM-A/VAM-A series)


Noise level at anechoic room
(Low-Middle2-Middle1-High) Unit : dB(A)

Model Noise level (A weighted)


PLFY-P32VKM-A 31-32.5-34-35
PLFY-P40VKM-A
PLFY-P50VKM-A 32-34-35.5-37
PLFY-P63VKM-A 35-36.5-38-39
PLFY-P80VAM-A 30-32-35-37
1.5m

PLFY-P100VAM-A 33-36-39-41
PLFY-P125VAM-A 35-38-41-43
Measurement location

3-2. NC curves
PLFY-P32,40VKM-A PLFY-P50VLMD-A
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa


High speed High speed
Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz) OCTAVE BAND CENTER FREQUENCIES(Hz)

PLFY-P63VKM-A PLFY-P80VAM-A
70 70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa

High speed
Middle1 speed
Low speed Middle2 speed
Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz) OCTAVE BAND CENTER FREQUENCIES(Hz)

PLFY-P100VAM-A PLFY-P125VAM-A
70 70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20 Pa

High speed High speed


Middle1 speed Middle1 speed
Middle2 speed Middle2 speed
Low speed Low speed
60 60
NC60 NC60
VKM-A/VAM-A

50 50
NC50 NC50
PLFY-P-

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz) OCTAVE BAND CENTER FREQUENCIES(Hz)

2- 161
PLFY-P-
VKM-A/VAM-A

Ceiling hole NOTE 1. The electrical parts box may be removed during servic-
25~35 690~710 25~35 ing.When connecting the pow er line and the control
640 wire,pro vide enough length to the electric wires.
NOTE 2. When installing the optional high-efficiency filter,the
Suspension bolt pitch 117 dimension between the transom and ceiling shall be
more than 440mm. Also ,when installing the optional
fresh air intake casement or the multi-functional case-
ment,the dimension between the transom and ceiling

25~35
117
Terminal block for shall be more than 440mm. (The optional high-
power supply efficiency filter can also be installed.)

507
660
PLFY-P32,40,50,63VKM-A

Terminal block for control

690~710
Ceiling hole
Drain hole

Suspension bolt pitch


117

64
77
4. External Dimensions

13

25~35
68
186 117
Optional high-efficiency filter
135

660
435

Drain pipe
VP-25 connection
75 2 42
Suspension bolt M10 65 Feeding hole
or W3/8 1 (Drain pump)
-2
54 +3

2- 162
115
253
243
Leave space of 10~15mm between the

298

156
top surface of the unit and the ceiling slab

166
65~80
Suspension bolt lower edge

+3
30
Ceiling surface

54 -2
Control wire entry
Power line entry
Refrigerant piping side 466 Grill
electric wire entry side Air intake hole
Vane motor

A 4-Auto vanes

< flare >


Model Gas pipe : LP ø12.7 ··················· 2
32• 40 Liquid pipe : HP ø 6.35 ··················· 1

760
460
466 Model Gas pipe : LP ø15.88 ·················· 2
Air intake hole

Air outlet hole


50• 63 Liquid pipe : HP ø9.52 ·················· 1

Intake grill opening/closing side

66
Unit : mm

35
460
66 35
Air intake grill Air outlet hole
760
Ceiling hole
20~45 860~910 20~45
Branch duct hole 810
(Cut out hole) Fresh air intake
90 100 100 90 159 Suspension bolt pitch

20~45

100
130

70˚
159

167
155
Branch
Branch duct hole duct hole
350 Terminal block
ø 175 14 - ø 2.8

840
605
Burring hole

860~910
PLFY-P80,100,125VAM-A

Ceiling hole
ø 150

Suspension bolt pitch

192
16
159
Deteil drawing of fresh air intake

89
98
3 - ø2.8
Burring hole
197 159
120˚
20~45

840

Suspension bolt M10

120˚
Feeding hole
ø 100 or W3/8 Drain pipe
ø125 (Drain pump)

158
(Cut out hole) VP-25connection
1 60 286 374
(O.D.ø 32)

2
Ceiling surface
A

2- 163
B

190

170
140
105
30

Susppension bolt lower edge Control wire entry Ceiling surface

50~70
17 +50

Power line entry

Air intake grille 577 Grille


Air intake hole
Drain hole

135
M

High efficiency filter M

17 +50
Auto vane
& Fresh air intake casement (option)

Models ➀ ➁ A B C
950
411
577

Refrigerant pipe Refrigerant pipe


(9.52mm dia.) (15.88mm dia.)
Air outlet hole
Air intake hole

PLFY-P80VAM-A 241 258 80


flared connection flared connection
3/8F 5/8F
Unit : mm

Refrigerant pipe Refrigerant pipe M


(9.52mm dia.) (19.05mm dia.)
PLFY-P100, 125VAM-A 281 298 84
flared connection flared connection
M
77

3/8F 3/4F Vane motor

411
51

77 51
Air outlet hole
950

VKM-A/VAM-A
PLFY-P-
PLFY-P-
VKM-A/VAM-A

M-NET
● PLFY-P32~63VKM-A

NOTE
1.At servicing for outdoor unit,always follow the wiring
diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect
to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to
5. Electrical Wiring Diagrams

[ LEGEND ]
TB5.(Transmission line is non-polar.)
SYMBOL NAME SYMBOL NAME
I.B INDOOR CONTROLLER BOARD A.B CIRCUIT BOARD (ADDRESS) 4.Symbol[S] of TB5 is the shield wire connection.
CN25 HUMIDIFIER SW1 MODE SELECTION 5.Symbols used in wiring diagram above are,

2- 164
CN27 DAMPER SW5 VOLTAGE SELECTION :Terminal block, :Connector.
CN32 REMOTE SWITCH SW11 ADDRESS SETTING 1ST DIGIT
CONNECTOR SW12 6.The setting of the SW2 dip switches differs in the
CN41 HA TERMINAL-A ADDRESS SETTING 2ND DIGIT
CN51 CENTRALLY CONTROL SW14 SWITCH CONNECTION NO. capacity. For the detail,refer to the fig: ❇1.
CN52 REMOTE INDICATION SWA CEILING HEIGHT SELECTOR 7.Please set the switch SW5 according to the power
SW2 CAPACITY CODE SWB DISCHARGE OUTLET NUMBER
SW3 SWITCH MODE SELECTION SELECTOR supply voltage.
SW4 MODEL SELECTION SWC OPTION SELECTOR Set SW5 to 240V side when the power supply is 230
ZNR VARISTOR
TH21 ROOM TEMP.DETECTION and 240 volts.
FUSE FUSE(6.3A) (0˚C/15kΩ,25˚C/5.4kΩ)
F.C FAN PHASE CONTROL PIPE TEMP.DETECTION/LIQUID When the power supply is 220 volts,set SW5 to 220V
TH22 THERMISTOR
X1 DRAIN PUMP (0˚C/15kΩ ,25˚C/5.4kΩ) side.
X3 AUX.RELAY VANE PIPE TEMP.DETECTION/GAS
TH23 <fig:❇1>
X4 FANMOTOR (0˚C/15kΩ ,25˚C/5.4kΩ)
LED1 POWER SUPPLY(I.B) LEV LINEAR EXPANSION VALVE MODELS SW2 MODELS SW2
LED2 POWER SUPPLY(I.B) P.B INDOOR POWER BOARD
MF FAN MOTOR(WITH INNER THERMO.) C CAPACITOR(FAN MOTOR) ON ON
MV VANE MOTOR LS LIMIT SWITCH P32 OFF P50 OFF
1 2 3 4 5 6 1 2 3 4 5 6
TB2 POWER SUPPLY H2 DEW PREVENTION HEATER
TB5 TERMINAL TRANSMISSION DP DRAIN WATER LIFTING-UP MACH. ON ON
TB15 BLOCK MA-REMOTE CONTROLLER DS DRAIN SENSOR P40 OFF P63 OFF
1 2 3 4 5 6 1 2 3 4 5 6

Led on indoor board for sevice <fig:❇2>


Mark Meaning Function MODELS SW3
Main power supply (indoor unit:220-240V)
LED1 Main power supply ON
power on lamp is lit P32,P40 OFF
1 2 3 4 5 6 7 8 9 10
Power supply for Power supply for MA-Remote controller
LED2 MA-Remote controller on lamp is lit ON
P50,P63 OFF
1 2 3 4 5 6 7 8 9 10
● PLFY-P80~125VAM-A

<SYMBOL EXPLANATION>
SYMBOL NAME SYMBOL NAME SYMBOL NAME
P.B INDOOR POWER BOARD C CAPACITOR(FAN MOTOR) PIPE TEMPERATURE
I.B INDOOR CONTROLLER BOARD MF FAN MOTOR(WITH INNER THERMO) TH23 THERMISTOR DETECTION / GAS
CN25 HUMIDIFIER MV VANE MOTOR (0˚C/15kΩ, 25˚C/5.4kΩ)
CN32 REMOTE SWITCH DP DRAIN WATER LIFTING-UP MACH A.B CIRCUIT BOARD
CN41 DS SW1 MODE SELECTION
CONNECTOR HA TERMINAL-A DRAIN SENSOR
CN51 CENTRALLY CONTROL H2 DEW PREVENTION HEATER SW5 VOLTAGE SELECTION
CN52 REMOTE INDICATION TB2 POWER SUPPLY SW11 ADDRESS SETTING 1ST DIGIT
TB5 TERMINAL
SW2 CAPACITY CODE TRANSMISSION SW12 ADDRESS SETTING 2ND DIGIT
BLOCK SWITCH
SW3 SWITCH MODE SELECTION TB15 TRANSMISSION SW14 CONNECTION No.
SW4 MODEL SELECTION LEV LINEAR EXPANSION VALVE SWA CEILING HEIGHT SELECTOR
ZNR VARISTOR ROOM TEMPERATURE SWB DISCHARGE OUTLET NUMBER
FUSE FUSE (6.3A/250V) TH21 DETECTION SELECTOR
F.C FAN PHASE CONTROL (0˚C/15kΩ, 25˚C/5.4kΩ) SWC OPTION SELECTOR
THERMISTOR
X1 DRAIN PUMP PIPE TEMPERATURE
AUX.RELAY
X4 FAN MOTOR TH22 DETECTION / LIQUID
LED1 POWER SUPPLY(I.B) (0˚C/15kΩ, 25˚C/5.4kΩ)
LED2 POWER SUPPLY(I.B)

GRILLE
POWER SUPPLY
MV MV MV MV ~ 220-240V 50Hz
H2
220V 60Hz
5 5 5 5
5 BREAKER
(15A)
1 2 3 6 7 4 8 9 5 10
FUSE(15A)
YLW
YLW

RED L TB2
BLU N PULL BOX

(AC220-240V) (DC13.1V) P.B GRN/YLW


MF DP CNSK (RED) CN2S (WHT)
PE TO NEXT
INDOOR UNIT
TRANS
1 2 3 1 2 3
2 2
YLW
YLW

1 1
1 2 3
C
WHT
WHT

BRN
BRN
RED
RED

WHT
BLU
BLK

BLK

BLK

I.B
TB5
FAN 1 3 5 POWER 1 3 1 3 D.U.M 1 3 POWER 1 2 CN2M 1 BLU M1 TO OUTDOOR UNIT
(WHT) CND
(RED) FUSE
CNP
(BLU)
CND
(RED)
CN2D
(WHT)
(BLU) 2 BLU M2 } BC CONTROLLER
M-NET REMOTE CONTROLLER
LED1 M-NET
X4 S (SHIELD) DC24-30V
HA (WHT)
REMOTE TB15
ZNR CN41 CN3A 1 ORN 1
F.C X4 X1 X1
(WHT)
(WHT)
SWITCH
CN32 (BLU) 3 ORN 2 }TODC8.7-13V
MA-REMOTE CONTROLLER
(WHT) REMOCON
HUMIDIFIER LEV 4 1 1 3
CN25 (GRN) (WHT) CN60
REMOTE CENTRALLY 6 5 4 3 2 1
2 1 INDICATION CONTROL
(GRN) (RED) (RED) CN52 CN51 LED2
VANE ADDRESS ADDRESS 5 1 5 1 (WHT) (BLK) (WHT) (RED)
(RED) CN6N CN81 CN42 SW2 SW3 SW4 DRAN GAS LIQUID INTAKE
DAMPER 6 5 4 3 2 1 8 7 6 5 4 3 2 1 4 3 2 1 ON ON CN31 CN29 CN21 CN20
CN27 OFF OFF 3 2 1 2 1 2 1 2 1
2 1 123456 12345678910 12345
BLK

BLK

BLK
BLK

BLK
BLK

8 4 6 (❇ 1)
5
See fig : ❇ 1 MODELS SW2
A.B ON
P80VAM
WHT
ORN

OFF
YLW

SW5 SWA SWB


BRN
RED
ADDRESS

4
BLU

220V 240V 3 123456


(RED)

3
CN43

2
2 3 2
SW1 1 4 1 8 ON
ON DS TH23 TH22 TH21 P100VAM OFF
7
ADDRESS

OFF 123456
6 LEV
(RED)

12345678910
CN82

SW14 5
SW12 SW11 SWC 4 ON
0 P125VAM OFF
0 0 3
2 123456
CONNECTION
3RD.DIGIT 2ND.DIGIT 1ST.DIGIT 1
No.

NOTE
VKM-A/VAM-A

1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.Symbol(S) of TB5 is the shield wire connection.
PLFY-P-

3.Symbols used in wiring diagram above are, :Terminal block, :Connector.


4.The setting of the SW2 dip switches differs in the capacity for the detail, see the table below.
5.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts,set SW5 to 220V side.

2- 165
6. Temperature/Airflow distribution

● Temperature distribution
<Cooling mode> <Heating mode>
Flow angle 30˚ Flow angle 70˚
<˚C> <˚C>
2.7 2.7

27
2 2 35
21 23

Height <m>
Height <m>

31

1 1
23 25
25 27
23
19
19
0 0
4 3 2 1 0 4 3 2 1 0
Floor distance <m> Floor distance <m>

<Cooling mode>
Flow angle 70˚
<˚C>
2.7

21
2
Height <m>

25
23

25

0
4 3 2 1 0
Floor distance <m>

● Airflow distribution
<Fan mode> <Fan mode>
Flow angle 70˚ Flow angle 30˚
<m/s> <m/s>
2.7 2.7

4.0
3.0 4.0
2 2
2.0 3.0
Height <m>

Height <m>

1.0
2.0
VKM-A/VAM-A

1 1
1.0
0.5
PLFY-P-

0.5

0 0
4 3 2 1 0 4 3 2 1 0
Floor distance <m> Floor distance <m>

2- 166
7. Options

Description Model Applicable capacity

Decoration panel PLP-25KB

Space panel PAC-SE01AS-E


P32/P40/P50/P63
Wide panel PAC-SE06WP-E

PAC-SE14SP-E
Air outlet shutter plate
PAC-SG06SP-E P80/P100/P125

PAC-SE13KF-E
(PAC-SE21TM-E is P32/P40/P50/P63
High efficiency filter element necessary to use this filter)

PAC-SG01KF P80/P100/P125

Multi-function casement
High efficiency filter casement PAC-SE21TM-E P32/P40/P50/P63
Flesh air intake casement

Multi-function casement PAC-SG03TM-E P80/P100/P125

VKM-A/VAM-A
PLFY-P-

2- 167
PLFY-P-
VKM-A/VAM-A

2- 168
VAM-A/VGM-A
PKFY-P-
Wall mounted PKFY-P-VAM-A
PKFY-P-VGM-A
CONTENTS

1. Specifications ·································································2-170

2. Capacity Tables ······························································2-171


2-1 Cooling Capacity(PUMY) ················································2-171
2-2 Heating Capacity(PUMY) ················································2-172
2-3 Cooling Capacity(Y/R2-8·10·13HP) ······························· 2-173
2-4 Heating Capacity(Y/R2-8·10·13HP) ······························· 2-174
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ······················ 2-175
2-6 Heating Capacity(Big Y, Super Y, Big R2) ······················ 2-176
2-7 Cooling Capacity(WY, WR2) ···········································2-177
2-8 Heating Capacity(WY, WR2) ···········································2-177

3. Sound Levels ·······························································2-178


3-1 Noise levels ·································································2-178
3-2 N/C curves ································································ 2-178

4. External Dimensions ····················································2-179

5. Electrical Wiring Diagrams ···········································2-181


5-1 PKFY-P-VAM-A ·······························································2-181
5-2 PKFY-P-VGM-A ·······························································2-182

6. Temperature/Airflow distribution ··································2-183


6-1 PKFY-P-VAM-A ·······························································2-183
6-2 PKFY-P-VGM-A ·······························································2-184

2- 169
1. Specifications
VAM-A/VGM-A
PKFY-P-

PKFY-P20VAM-A PKFY-P25VAM-A PKFY-P32VGM-A PKFY-P40VGM-A PKFY-P50VGM-A


Power source ~ 220-240V 50Hz ~ 220V 60Hz
❇1 kW 2.2 2.8 3.6 4.5 5.6
Cooling capacity
❇2 kcal/h 2,000 2,500 3,150 4,000 5,000
Heating capacity ❇1 kW 2.5 3.2 4.0 5.0 6.3
Power Cooling kW 0.04 0.07
consumption Heating kW 0.04 0.07
Cooling A 0.20 0.32
Current
Heating A 0.20 0.32
External finish(Munsel No.) Plastic 2.60Y 8.66/0.69 Plastic <PS,ABS> white 0.70Y 8.59/0.97
Height mm 295 340
Dimension Width mm 815 990
Depth mm 158 235
Net weight kg 8.5 16
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Line flow fan ✕ 1
Airflow rate ❇3
m3/min 4.9-5.2-5.6-5.9 8-9.5-10.5-11.5 9-10-11-12
Fan (Lo-Mid2-Mid1-Hi)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.017 0.030
Air filter PP Honeycomb (long life)
Gas mm ø 12.7 ø 15.88
Refrigerant (Flare)
pipe dimension Liquid mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension ø 28,VP-16 VP-20
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4 dB(A) 32-33-35-36 33-36-38-41 34-37-40-43
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 Airflow rate/noise level are in (low-middle2-middle1-high).
❇ 4 It is measured in anechoic room.

2- 170
2. Capacity Tables

VAM-A/VGM-A
2-1.Cooling Capacity (In combination with PUMY)

PKFY-P-
CA:Capacity(kW)
PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.5 2.3 1.6 2.4 1.6 2.6 1.6
22.5 2.1 1.5 2.3 1.6 2.4 1.6 2.6 1.6
25.0 2.1 1.5 2.3 1.6 2.4 1.6 2.5 1.6
27.5 2.1 1.5 2.2 1.6 2.4 1.6 2.5 1.6
20 30.0 2.1 1.5 2.2 1.5 2.3 1.5 2.5 1.6
(2.2) 32.5 2.0 1.5 2.2 1.5 2.3 1.5 2.5 1.6
35.0 2.0 1.4 2.1 1.5 2.3 1.5 2.4 1.6
37.5 2.0 1.4 2.1 1.5 2.2 1.5 2.4 1.5
40.0 2.0 1.4 2.1 1.5 2.2 1.5 2.4 1.5
46.0 1.9 1.4 2.0 1.5 2.1 1.4 2.3 1.5
20.0 2.8 1.9 2.9 2.0 3.1 2.0 3.3 2.0
22.5 2.7 1.9 2.9 2.0 3.1 2.0 3.2 2.0
25.0 2.7 1.9 2.9 2.0 3.1 2.0 3.2 2.0
27.5 2.7 1.9 2.8 2.0 3.0 1.9 3.2 2.0
25 30.0 2.6 1.8 2.8 1.9 3.0 1.9 3.2 2.0
(2.8) 32.5 2.6 1.8 2.8 1.9 2.9 1.9 3.1 2.0
35.0 2.6 1.8 2.7 1.9 2.9 1.9 3.1 1.9
37.5 2.5 1.8 2.7 1.9 2.9 1.9 3.0 1.9
40.0 2.5 1.8 2.7 1.9 2.8 1.8 3.0 1.9
46.0 2.4 1.7 2.6 1.8 2.7 1.8 2.9 1.9
20.0 3.6 2.8 3.7 3.0 4.0 3.0 4.2 3.1
22.5 3.5 2.8 3.7 3.0 4.0 2.9 4.2 3.0
25.0 3.5 2.8 3.7 2.9 3.9 2.9 4.1 3.0
27.5 3.4 2.8 3.6 2.9 3.9 2.9 4.1 3.0
32 30.0 3.4 2.8 3.6 2.9 3.8 2.9 4.1 3.0
(3.6) 32.5 3.3 2.7 3.6 2.9 3.8 2.9 4.0 3.0
35.0 3.3 2.7 3.5 2.9 3.7 2.8 4.0 2.9
37.5 3.2 2.7 3.5 2.8 3.7 2.8 3.9 2.9
40.0 3.2 2.7 3.4 2.8 3.6 2.8 3.9 2.9
46.0 3.1 2.6 3.3 2.8 3.5 2.7 3.7 2.8
20.0 4.5 3.3 4.7 3.4 5.0 3.4 5.3 3.5
22.5 4.4 3.2 4.6 3.4 5.0 3.4 5.2 3.4
25.0 4.3 3.2 4.6 3.4 4.9 3.3 5.2 3.4
27.5 4.3 3.2 4.6 3.3 4.9 3.3 5.1 3.4
40 30.0 4.2 3.1 4.5 3.3 4.8 3.3 5.1 3.4
(4.5) 32.5 4.2 3.1 4.4 3.3 4.7 3.2 5.0 3.4
35.0 4.1 3.1 4.4 3.2 4.7 3.2 5.0 3.3
37.5 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.3
40.0 4.0 3.0 4.3 3.2 4.5 3.2 4.8 3.3
46.0 3.8 3.0 4.1 3.1 4.3 3.1 4.6 3.2
20.0 5.5 3.8 5.8 4.0 6.2 4.0 6.6 4.1
22.5 5.5 3.8 5.8 3.9 6.2 3.9 6.5 4.0
25.0 5.4 3.8 5.7 3.9 6.1 3.9 6.4 4.0
27.5 5.3 3.7 5.7 3.9 6.0 3.9 6.4 4.0
50 30.0 5.3 3.7 5.6 3.9 5.9 3.8 6.3 3.9
(5.6) 32.5 5.2 3.6 5.5 3.8 5.9 3.8 6.2 3.9
35.0 5.1 3.6 5.5 3.8 5.8 3.7 6.2 3.9
37.5 5.0 3.6 5.4 3.7 5.7 3.7 6.1 3.8
40.0 5.0 3.5 5.3 3.7 5.6 3.7 6.0 3.8
46.0 4.8 3.4 5.1 3.6 5.4 3.6 5.8 3.7

2- 171
VAM-A/VGM-A

2-2.Heating Capacity (In combination with PUMY)


PKFY-P-

PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 1.6 1.6 1.5 -12.0 2.5 2.5 2.5
-10.0 1.7 1.6 1.6 -10.0 2.7 2.6 2.6
-5.0 1.9 1.9 1.9 -5.0 3.1 3.0 3.0
0.0 2.2 2.1 2.1 0.0 3.5 3.4 3.4
20 2.5 2.3 2.3 2.3 32 2.5 3.7 3.7 3.6
6.0 2.5 2.5 2.5 6.0 4.0 4.0 3.9
7.5 2.6 2.6 2.5 7.5 4.2 4.1 4.0
10.0 2.8 2.7 2.5 10.0 4.4 4.4 4.0
12.5 2.9 2.8 2.5 12.5 4.7 4.4 4.0
15.5 3.1 2.8 2.5 15.5 4.9 4.4 4.0
-12.0 2.0 2.0 2.0 -12.0 3.2 3.1 3.1
-10.0 2.1 2.1 2.1 -10.0 3.4 3.3 3.2
-5.0 2.4 2.4 2.4 -5.0 3.8 3.8 3.7
0.0 2.8 2.8 2.7 0.0 4.3 4.3 4.2
25 2.5 3.0 2.9 2.9 40 2.5 4.6 4.6 4.5
6.0 3.2 3.2 3.2 6.0 5.0 5.0 4.9
7.5 3.3 3.3 3.2 7.5 5.2 5.2 5.0
10.0 3.5 3.5 3.2 10.0 5.5 5.5 5.0
12.5 3.7 3.5 3.2 12.5 5.9 5.5 5.0
15.5 3.9 3.5 3.2 15.5 6.2 5.5 5.0
-12.0 4.0 3.9 3.9
-10.0 4.2 4.2 4.1
-5.0 4.8 4.8 4.7
0.0 5.5 5.4 5.3
50 2.5 5.8 5.8 5.7
6.0 6.3 6.3 6.2
7.5 6.6 6.5 6.2
10.0 7.0 6.9 6.2
12.5 7.4 7.0 6.2
15.5 7.7 7.0 6.2

2- 172
VAM-A/VGM-A
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)

PKFY-P-
CA:Capacity(kW)
PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.2 1.5 2.2 1.5 2.3 1.5 2.3 1.5 2.4 1.6 2.5 1.5 2.6 1.5
22.5 2.1 1.5 2.2 1.5 2.3 1.5 2.3 1.5 2.4 1.5 2.4 1.5 2.5 1.5
25.0 2.1 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.3 1.5 2.4 1.5 2.5 1.5
27.5 2.1 1.5 2.1 1.5 2.2 1.5 2.3 1.5 2.3 1.5 2.4 1.5 2.5 1.4
20 30.0 2.1 1.5 2.1 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.4 1.5 2.5 1.4
(2.2) 32.5 2.0 1.5 2.1 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.4 1.5 2.4 1.4
35.0 2.0 1.5 2.1 1.5 2.2 1.5 2.2 1.5 2.2 1.5 2.3 1.5 2.4 1.4
37.5 2.0 1.4 2.0 1.5 2.1 1.4 2.2 1.4 2.2 1.5 2.3 1.5 2.4 1.4
40.0 2.0 1.4 2.0 1.5 2.1 1.4 2.2 1.4 2.2 1.5 2.3 1.4 2.4 1.4
43.0 2.0 1.4 2.0 1.4 2.1 1.4 2.1 1.4 2.2 1.5 2.3 1.4 2.3 1.4
20.0 2.7 1.9 2.8 1.9 2.9 1.9 3.0 1.9 3.0 1.9 3.1 1.9 3.2 1.8
22.5 2.7 1.9 2.8 1.9 2.9 1.9 2.9 1.9 3.0 1.9 3.1 1.9 3.2 1.8
25.0 2.7 1.9 2.7 1.9 2.9 1.9 2.9 1.9 3.0 1.9 3.1 1.9 3.2 1.8
27.5 2.7 1.9 2.7 1.9 2.8 1.8 2.9 1.9 2.9 1.9 3.1 1.9 3.2 1.8
25 30.0 2.6 1.8 2.7 1.9 2.8 1.8 2.9 1.8 2.9 1.9 3.0 1.8 3.1 1.8
(2.8) 32.5 2.6 1.8 2.7 1.9 2.8 1.8 2.8 1.8 2.9 1.9 3.0 1.8 3.1 1.8
35.0 2.6 1.8 2.6 1.9 2.7 1.8 2.8 1.8 2.9 1.9 3.0 1.8 3.1 1.8
37.5 2.5 1.8 2.6 1.8 2.7 1.8 2.8 1.8 2.8 1.9 2.9 1.8 3.1 1.8
40.0 2.5 1.8 2.6 1.8 2.7 1.8 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.7
43.0 2.5 1.8 2.5 1.8 2.7 1.8 2.7 1.8 2.8 1.8 2.9 1.8 3.0 1.7
20.0 3.5 2.8 3.6 2.9 3.7 2.8 3.8 2.9 3.9 3.0 4.0 2.9 4.2 2.8
22.5 3.5 2.8 3.6 2.9 3.7 2.8 3.8 2.9 3.9 3.0 4.0 2.9 4.1 2.8
25.0 3.5 2.8 3.5 2.9 3.7 2.8 3.7 2.9 3.8 3.0 4.0 2.9 4.1 2.8
27.5 3.4 2.8 3.5 2.9 3.6 2.8 3.7 2.8 3.8 2.9 3.9 2.9 4.1 2.8
32 30.0 3.4 2.8 3.5 2.8 3.6 2.8 3.7 2.8 3.7 2.9 3.9 2.9 4.0 2.8
(3.6) 32.5 3.3 2.7 3.4 2.8 3.6 2.8 3.6 2.8 3.7 2.9 3.9 2.9 4.0 2.8
35.0 3.3 2.7 3.4 2.8 3.5 2.8 3.6 2.8 3.7 2.9 3.8 2.8 4.0 2.8
37.5 3.3 2.7 3.3 2.8 3.5 2.7 3.6 2.8 3.6 2.9 3.8 2.8 3.9 2.8
40.0 3.2 2.7 3.3 2.8 3.5 2.7 3.5 2.8 3.6 2.9 3.7 2.8 3.9 2.7
43.0 3.2 2.7 3.3 2.8 3.4 2.7 3.5 2.8 3.6 2.9 3.7 2.8 3.8 2.7
20.0 4.4 3.2 4.5 3.3 4.7 3.2 4.8 3.2 4.9 3.3 5.0 3.3 5.2 3.2
22.5 4.4 3.2 4.5 3.3 4.6 3.2 4.7 3.2 4.8 3.3 5.0 3.2 5.2 3.2
25.0 4.3 3.2 4.4 3.3 4.6 3.2 4.7 3.2 4.8 3.3 5.0 3.2 5.1 3.1
27.5 4.3 3.2 4.4 3.2 4.5 3.2 4.6 3.2 4.7 3.3 4.9 3.2 5.1 3.1
40 30.0 4.2 3.1 4.3 3.2 4.5 3.1 4.6 3.2 4.7 3.3 4.9 3.2 5.0 3.1
(4.5) 32.5 4.2 3.1 4.3 3.2 4.5 3.1 4.5 3.2 4.6 3.3 4.8 3.2 5.0 3.1
35.0 4.1 3.1 4.2 3.2 4.4 3.1 4.5 3.1 4.6 3.2 4.8 3.2 5.0 3.1
37.5 4.1 3.1 4.2 3.2 4.4 3.1 4.5 3.1 4.5 3.2 4.7 3.1 4.9 3.1
40.0 4.1 3.1 4.1 3.1 4.3 3.1 4.4 3.1 4.5 3.2 4.7 3.1 4.9 3.0
43.0 4.0 3.0 4.1 3.1 4.3 3.0 4.4 3.1 4.4 3.2 4.6 3.1 4.8 3.0
20.0 5.5 3.8 5.6 3.9 5.8 3.8 5.9 3.8 6.0 3.9 6.3 3.7 6.5 3.6
22.5 5.4 3.8 5.5 3.8 5.8 3.7 5.9 3.7 6.0 3.8 6.2 3.7 6.4 3.6
25.0 5.4 3.7 5.5 3.8 5.7 3.7 5.8 3.7 5.9 3.8 6.2 3.7 6.4 3.6
27.5 5.3 3.7 5.4 3.8 5.7 3.7 5.8 3.7 5.9 3.8 6.1 3.7 6.3 3.6
50 30.0 5.3 3.7 5.4 3.7 5.6 3.7 5.7 3.7 5.8 3.8 6.0 3.7 6.3 3.5
(5.6) 32.5 5.2 3.6 5.3 3.7 5.5 3.6 5.7 3.6 5.8 3.7 6.0 3.6 6.2 3.5
35.0 5.2 3.6 5.3 3.7 5.5 3.6 5.6 3.6 5.7 3.7 5.9 3.6 6.2 3.5
37.5 5.1 3.6 5.2 3.7 5.4 3.6 5.5 3.6 5.7 3.7 5.9 3.6 6.1 3.5
40.0 5.0 3.6 5.2 3.6 5.4 3.5 5.5 3.6 5.6 3.7 5.8 3.6 6.0 3.5
43.0 5.0 3.5 5.1 3.6 5.3 3.5 5.4 3.5 5.5 3.6 5.8 3.5 6.0 3.4

2- 173
VAM-A/VGM-A

2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)


PKFY-P-

PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 27.0 size 15.0 20.0 25.0 27.0
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.7 1.6 1.6 1.6 -15.0 2.7 2.6 2.6 2.6
-10.0 1.9 1.9 1.9 1.7 -10.0 3.1 3.0 3.0 2.8
-5.0 2.1 2.1 2.0 1.7 -5.0 3.4 3.4 3.1 2.8
0.0 2.4 2.4 2.0 1.7 0.0 3.8 3.8 3.1 2.8
20 2.5 2.5 2.5 2.0 1.7 32 2.5 4.0 4.0 3.1 2.8
6.0 2.5 2.5 2.0 1.7 6.0 4.0 4.0 3.1 2.8
7.5 2.6 2.5 2.0 1.7 7.5 4.2 4.0 3.1 2.8
10.0 2.8 2.5 2.0 1.7 10.0 4.5 4.0 3.1 2.8
12.5 3.0 2.5 2.0 1.7 12.5 4.8 4.0 3.1 2.8
15.5 3.0 2.5 2.0 1.7 15.5 4.8 4.0 3.1 2.8
-15.0 2.1 2.1 2.1 2.1 -15.0 3.3 3.3 3.3 3.3
-10.0 2.4 2.4 2.4 2.2 -10.0 3.8 3.8 3.7 3.5
-5.0 2.7 2.7 2.5 2.2 -5.0 4.3 4.2 3.9 3.5
0.0 3.1 3.0 2.5 2.2 0.0 4.8 4.7 3.9 3.5
25 2.5 3.2 3.2 2.5 2.2 40 2.5 5.0 5.0 3.9 3.5
6.0 3.2 3.2 2.5 2.2 6.0 5.1 5.0 3.9 3.5
7.5 3.4 3.2 2.5 2.2 7.5 5.3 5.0 3.9 3.5
10.0 3.6 3.2 2.5 2.2 10.0 5.6 5.0 3.9 3.5
12.5 3.8 3.2 2.5 2.2 12.5 6.0 5.0 3.9 3.5
15.5 3.9 3.2 2.5 2.2 15.5 6.1 5.0 3.9 3.5
-15.0 4.2 4.2 4.1 4.1
-10.0 4.8 4.8 4.7 4.3
-5.0 5.4 5.3 4.9 4.3
0.0 6.0 5.9 4.9 4.3
50 2.5 6.3 6.2 4.9 4.3
6.0 6.4 6.3 4.9 4.3
7.5 6.6 6.3 4.9 4.3
10.0 7.1 6.3 4.9 4.3
12.5 7.5 6.3 4.9 4.3
15.5 7.6 6.3 4.9 4.3

2- 174
VAM-A/VGM-A
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)

PKFY-P-
CA:Capacity(kW)
PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.:˚CDB
Unit Outdoor
air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 2.0 1.5 2.1 1.5 2.3 1.5 2.4 1.6 2.6 1.6 2.7 1.5
22.5 2.0 1.5 2.1 1.5 2.3 1.5 2.4 1.6 2.6 1.6 2.7 1.5
25.0 2.0 1.4 2.1 1.5 2.2 1.5 2.4 1.6 2.5 1.5 2.7 1.5
27.5 2.0 1.4 2.1 1.5 2.2 1.5 2.4 1.6 2.5 1.5 2.6 1.5
20 30.0 2.0 1.4 2.1 1.5 2.2 1.5 2.3 1.5 2.5 1.5 2.6 1.5
32.5 2.0 1.4 2.0 1.5 2.2 1.5 2.3 1.5 2.4 1.5 2.6 1.5
35.0 1.9 1.4 2.0 1.5 2.1 1.4 2.3 1.5 2.4 1.5 2.5 1.5
37.5 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.4 1.5 2.5 1.4
40.0 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.4
43.0 1.9 1.4 1.9 1.4 2.1 1.4 2.2 1.5 2.3 1.4 2.4 1.4
20.0 2.6 1.8 2.7 1.9 2.9 1.9 3.1 2.0 3.3 2.0 3.5 1.9
22.5 2.6 1.8 2.7 1.9 2.9 1.9 3.1 2.0 3.3 1.9 3.4 1.9
25.0 2.6 1.8 2.7 1.9 2.9 1.9 3.0 1.9 3.2 1.9 3.4 1.9
27.5 2.5 1.8 2.6 1.9 2.8 1.8 3.0 1.9 3.2 1.9 3.3 1.9
25 30.0 2.5 1.8 2.6 1.8 2.8 1.8 3.0 1.9 3.1 1.9 3.3 1.8
32.5 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.9 3.1 1.9 3.2 1.8
35.0 2.5 1.8 2.6 1.8 2.7 1.8 2.9 1.9 3.0 1.8 3.2 1.8
37.5 2.5 1.8 2.5 1.8 2.7 1.8 2.8 1.9 3.0 1.8 3.1 1.8
40.0 2.4 1.7 2.5 1.8 2.7 1.8 2.8 1.8 3.0 1.8 3.1 1.8
43.0 2.4 1.7 2.5 1.8 2.6 1.8 2.8 1.8 2.9 1.8 3.0 1.7
20.0 3.3 2.7 3.5 2.9 3.7 2.8 4.0 3.0 4.2 3.0 4.5 2.9
22.5 3.3 2.7 3.5 2.8 3.7 2.8 4.0 3.0 4.2 3.0 4.4 2.9
25.0 3.3 2.7 3.4 2.8 3.7 2.8 3.9 3.0 4.1 3.0 4.4 2.9
27.5 3.3 2.7 3.4 2.8 3.6 2.8 3.9 3.0 4.1 2.9 4.3 2.9
32 30.0 3.2 2.7 3.4 2.8 3.6 2.8 3.8 3.0 4.0 2.9 4.2 2.9
32.5 3.2 2.7 3.3 2.8 3.5 2.8 3.8 2.9 4.0 2.9 4.2 2.8
35.0 3.2 2.7 3.3 2.8 3.5 2.7 3.7 2.9 3.9 2.9 4.1 2.8
37.5 3.2 2.7 3.3 2.8 3.5 2.7 3.7 2.9 3.8 2.9 4.0 2.8
40.0 3.1 2.6 3.2 2.7 3.4 2.7 3.6 2.9 3.8 2.8 4.0 2.8
43.0 3.1 2.6 3.2 2.7 3.4 2.7 3.5 2.9 3.7 2.8 3.9 2.8
20.0 4.1 3.1 4.3 3.2 4.7 3.2 5.0 3.4 5.3 3.4 5.6 3.3
22.5 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.4 5.2 3.3 5.5 3.3
25.0 4.1 3.1 4.3 3.2 4.6 3.2 4.9 3.4 5.2 3.3 5.5 3.3
27.5 4.1 3.1 4.2 3.2 4.5 3.2 4.8 3.3 5.1 3.3 5.4 3.2
40 30.0 4.0 3.1 4.2 3.2 4.5 3.1 4.8 3.3 5.0 3.3 5.3 3.2
32.5 4.0 3.0 4.2 3.1 4.4 3.1 4.7 3.3 5.0 3.2 5.2 3.2
35.0 4.0 3.0 4.1 3.1 4.4 3.1 4.6 3.3 4.9 3.2 5.1 3.1
37.5 3.9 3.0 4.1 3.1 4.3 3.1 4.6 3.2 4.8 3.2 5.1 3.1
40.0 3.9 3.0 4.0 3.1 4.3 3.0 4.5 3.2 4.7 3.1 5.0 3.1
43.0 3.9 3.0 4.0 3.1 4.2 3.0 4.4 3.2 4.7 3.1 4.9 3.1
20.0 5.2 3.6 5.4 3.8 5.8 3.8 6.2 3.9 6.6 3.9 7.0 3.8
22.5 5.2 3.6 5.4 3.7 5.8 3.7 6.2 3.9 6.5 3.9 6.9 3.8
25.0 5.1 3.6 5.3 3.7 5.7 3.7 6.1 3.9 6.4 3.8 6.8 3.7
27.5 5.1 3.6 5.3 3.7 5.6 3.7 6.0 3.8 6.3 3.8 6.7 3.7
50 30.0 5.0 3.6 5.2 3.7 5.6 3.6 5.9 3.8 6.2 3.7 6.6 3.7
32.5 5.0 3.5 5.2 3.6 5.5 3.6 5.8 3.8 6.2 3.7 6.5 3.6
35.0 4.9 3.5 5.1 3.6 5.4 3.6 5.8 3.7 6.1 3.7 6.4 3.6
37.5 4.9 3.5 5.1 3.6 5.4 3.5 5.7 3.7 6.0 3.6 6.3 3.6
40.0 4.9 3.5 5.0 3.6 5.3 3.5 5.6 3.7 5.9 3.6 6.2 3.5
43.0 4.8 3.4 5.0 3.5 5.2 3.5 5.5 3.6 5.8 3.6 6.1 3.5

2- 175
VAM-A/VGM-A

2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)


PKFY-P-

PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15 21 25 27 size 15 21 25 27
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 1.6 1.5 1.5 1.5 -15.0 3.1 3.1 3.0 3.0
-10.0 1.8 1.8 1.7 1.7 -10.0 3.6 3.5 3.5 3.4
-5.0 2.0 2.0 2.0 1.9 -5.0 4.0 4.0 3.9 3.9
0.0 2.2 2.2 2.1 1.9 0.0 4.5 4.4 4.3 3.9
20 2.5 2.4 2.3 2.1 1.9 40 2.5 4.7 4.7 4.3 3.9
6.0 2.5 2.5 2.1 1.9 6.0 5.0 5.0 4.3 3.9
7.5 2.6 2.5 2.1 1.9 7.5 5.2 5.0 4.3 3.9
10.0 2.7 2.5 2.1 1.9 10.0 5.4 5.0 4.3 3.9
12.5 2.9 2.5 2.1 1.9 12.5 5.7 5.0 4.3 3.9
15.5 2.9 2.5 2.1 1.9 15.5 5.8 5.0 4.3 3.9
-15.0 2.0 2.0 1.9 1.9 -15.0 3.9 3.9 3.8 3.7
-10.0 2.3 2.2 2.2 2.2 -10.0 4.5 4.4 4.3 4.3
-5.0 2.6 2.5 2.5 2.5 -5.0 5.0 5.0 4.9 4.9
0.0 2.9 2.8 2.7 2.5 0.0 5.6 5.6 5.4 4.9
25 2.5 3.0 3.0 2.7 2.5 50 2.5 5.9 5.9 5.4 4.9
6.0 3.2 3.2 2.7 2.5 6.0 6.4 6.3 5.4 4.9
7.5 3.3 3.2 2.7 2.5 7.5 6.6 6.3 5.4 4.9
10.0 3.5 3.2 2.7 2.5 10.0 6.9 6.3 5.4 4.9
12.5 3.7 3.2 2.7 2.5 12.5 7.2 6.3 5.4 4.9
15.5 3.7 3.2 2.7 2.5 15.5 7.2 6.3 5.4 4.9
-15.0 2.5 2.5 2.4 2.4
-10.0 2.8 2.8 2.8 2.7
-5.0 3.2 3.2 3.1 3.1
0.0 3.6 3.5 3.4 3.1
32 2.5 3.8 3.7 3.4 3.1
6.0 4.0 4.0 3.4 3.1
7.5 4.2 4.0 3.4 3.1
10.0 4.4 4.0 3.4 3.1
12.5 4.6 4.0 3.4 3.1
15.5 4.6 4.0 3.4 3.1

2- 176
VAM-A/VGM-A
2-7.Cooling Capacity (In combination with WY, WR2)

PKFY-P-
CA:Capacity(kW)
PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Water
temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 2.1 1.5 2.2 1.6 2.4 1.5 2.4 1.6 2.5 1.6 2.6 1.6 2.8 1.6
20 2.1 1.5 2.1 1.5 2.3 1.5 2.3 1.5 2.4 1.6 2.5 1.5 2.7 1.5
20 30 2.0 1.4 2.0 1.5 2.1 1.4 2.2 1.5 2.3 1.5 2.4 1.5 2.5 1.5
40 1.7 1.3 1.8 1.3 1.9 1.3 1.9 1.3 2.0 1.4 2.1 1.4 2.2 1.3
45 1.6 1.2 1.7 1.3 1.8 1.3 1.8 1.3 1.9 1.3 2.0 1.3 2.1 1.3
10 2.7 1.9 2.8 2.0 3.0 1.9 3.1 1.9 3.2 2.0 3.3 2.0 3.5 1.9
20 2.6 1.8 2.7 1.9 2.9 1.9 3.0 1.9 3.1 2.0 3.2 1.9 3.4 1.9
25 30 2.5 1.8 2.6 1.8 2.7 1.8 2.8 1.8 2.9 1.9 3.0 1.8 3.2 1.8
40 2.2 1.6 2.2 1.7 2.4 1.6 2.4 1.7 2.5 1.7 2.6 1.7 2.8 1.7
45 2.0 1.5 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.7 2.5 1.6 2.6 1.6
10 3.5 2.8 3.6 2.9 3.9 2.9 4.0 2.9 4.1 3.1 4.3 3.0 4.5 3.0
20 3.4 2.8 3.5 2.9 3.7 2.8 3.8 2.9 3.9 3.0 4.1 3.0 4.4 2.9
32 30 3.2 2.7 3.3 2.8 3.5 2.7 3.6 2.8 3.7 2.9 3.9 2.9 4.1 2.8
40 2.8 2.5 2.9 2.6 3.1 2.6 3.1 2.6 3.2 2.7 3.4 2.7 3.6 2.7
45 2.6 2.4 2.7 2.5 2.9 2.5 3.0 2.6 3.0 2.7 3.2 2.6 3.4 2.6
10 4.4 3.2 4.5 3.3 4.8 3.3 5.0 3.3 5.1 3.5 5.4 3.4 5.7 3.3
20 4.2 3.1 4.4 3.2 4.6 3.2 4.8 3.3 4.9 3.4 5.2 3.3 5.5 3.3
40 30 4.0 3.0 4.1 3.1 4.4 3.1 4.5 3.1 4.6 3.3 4.9 3.2 5.2 3.1
40 3.5 2.8 3.6 2.9 3.8 2.8 3.9 2.9 4.0 3.0 4.3 3.0 4.5 2.9
45 3.3 2.7 3.4 2.8 3.6 2.8 3.7 2.8 3.8 2.9 4.0 2.9 4.2 2.8
10 5.5 3.8 5.6 3.9 6.0 3.8 6.2 3.9 6.3 4.0 6.7 3.9 7.1 3.9
20 5.3 3.7 5.4 3.8 5.8 3.7 5.9 3.8 6.1 3.9 6.5 3.8 6.8 3.8
50 30 5.0 3.5 5.1 3.6 5.5 3.6 5.6 3.6 5.8 3.7 6.1 3.7 6.4 3.6
40 4.3 3.2 4.5 3.3 4.7 3.3 4.9 3.3 5.0 3.4 5.3 3.4 5.6 3.3
45 4.1 3.1 4.2 3.2 4.5 3.1 4.6 3.2 4.7 3.3 5.0 3.2 5.3 3.2

2-8.Heating Capacity (In combination with WY, WR2)


PKFY-P-VAM-A,VGM-A SHC:Sensible Heat Capacity(kW)
Water Indoor air temp.:˚CDB
Unit temp.
size 15 19 20 25 27
˚C SHC(kW) SHC(kW) SHC(kW) SHC(kW) SHC(kW)
10 2.2 2.2 2.1 1.7 1.5
20 2.6 2.6 2.5 2.0 1.8
20 30 2.6 2.6 2.5 2.0 1.8
40 2.7 2.7 2.6 2.1 1.9
45 2.9 2.9 2.9 2.3 2.1
10 2.8 2.8 2.7 2.2 2.0
20 3.3 3.3 3.2 2.6 2.3
25 30 3.3 3.3 3.2 2.6 2.3
40 3.4 3.4 3.3 2.7 2.4
45 3.8 3.7 3.6 2.9 2.6
10 3.5 3.5 3.4 2.7 2.4
20 4.1 4.1 4.0 3.2 2.9
32 30 4.1 4.1 4.0 3.2 2.9
40 4.3 4.2 4.2 3.3 3.0
45 4.7 4.7 4.6 3.6 3.3
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 5.5 5.5 5.4 4.3 3.9
20 6.5 6.4 6.3 5.0 4.5
50 30 6.5 6.4 6.3 5.0 4.5
40 6.7 6.7 6.6 5.2 4.7
45 7.4 7.3 7.2 5.7 5.2

2- 177
3. Sound Levels
VAM-A/VGM-A

3-1. Noise level


PKFY-P-

Wall mounted
Noise level at anechoic room
(Low-Middle2-Middle1-High) Unit : dB(A)

Model Noise level (A weighted)


PKFY-P20VAM-A 32-33-35-36
PKFY-P25VAM-A
PKFY-P32VGM-A
33-36-38-41
PKFY-P40VGM-A
PKFY-P50VGM-A 34-37-40-43
1.0m

Measurement location 1.0m

3-2. NC curves
PKFY-P20VAM-A PKFY-P25VAM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
Approximate minimum NC20 Approximate minimum NC20
audible limit on audible limit on
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES(Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PKFY-P32VGM-A PKFY-P40VGM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
Approximate minimum Approximate minimum
audible limit on
NC20 audible limit on NC20
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PKFY-P50VGM-A
70
High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed
60
NC60

50
NC50

40
NC40

30
NC30

20
Approximate minimum
NC20
audible limit on
continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 178
PKFY-P20, 25VAM-A

783 Liquid pipe ø6.35


Gas pipe ø12.7

Intake dimensions
25.5
The address board is protected by

13
a plastic cover.
Remove the cover with a screwdriver
4. External Dimensions

815
(one screw) to set the board.
21.5 247.5 Intake dimensions
158 5
2.5 60 150

13
Intake
Remote control direction Installation board
terminal plate
Power terminal plate

295

2- 179
Adress board
MITSUBISHI PKFY-VAM

37.4
17˚
630 Intake dimensions 146 Outlet
angle 70.3
695 Outlet dimensions 60 Address board
Outlet
Outlet dimensions Terminal plate
direction
Rotary switch (pair No.)
Rotary switch (own address)

660 Total length of drain piping 760 110


Dip switch (switches functions)

450 Gas pipe


520 Liquid pipe 116
Unit : mm

VAM-A/VGM-A
PKFY-P-
PKFY-P-
VAM-A/VGM-A

Front view 715 Air intake 225


Left side Right side Less than 15
340 Air intake 80 280 Air intake 233

245
245
PKFY-P32,40,50VGM-A

340
198 Air intake

70 21
70 21
MITSUBISHI ELECTRIC

53
Knock out hole for right piping
Refrigerant pipe.Drain pipe.
60 Auto vane 60
990 Wiring hole
235

Lower side 705 Air outlet 235


Address board
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole. 160 40
12-Louvers (manual) Knock out hole for under piping
Refrigerant piping.Drain pipe.

79
Wiring hole

80
60

2- 180
50 70 35
190
Service panel
400 395 (Power supply access)
Front view(to open the grille)
Filter grip
Terminal block for
remote control
Terminal block for
280

power supply
31

Model Liquid pipe Gas pipe


481 54
32,40 ø6.35 ø12.7
(Left side piping
35 installation) 549 86
50 ø9.52 ø15.88
(Right side piping
700 (Flexible hose total length 800) 153 installation)
Drain pipe (VP-20) Liquid pipe
Gas pipe
Unit : mm
5. Electrical Wiring Diagrams

VAM-A/VGM-A
5-1 PKFY-P-VAM-A

PKFY-P-
<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name
M.B Indoor controller board Pipe temp. detection/Gas TB2 Power supply
TH23 Thermistor Terminal block
CN32 Remote switch (0˚C / 15kΩ, 25˚C / 5.4kΩ) TB5 MA-Remote controller
CN41 HA terminal - A P.B Indoor power board A.B Circuit board Address
Connector
CN51 Centrally control ZNR Varistor SW1 <A.B> Mode selection
CN52 Remote indication FUSE Fuse (6.3A) SW5 <A.B> Voltage selection
SW2 Capacity code F.C Fan phase control SW11 <A.B> Switch Address setting 1st digit
Switch
SW3 Mode selection MF Fan motor SW12 <A.B> Address setting 2nd digit
Room temp. detection C1 Capacity (fan motor) SW14 <A.B> Connection No.
TH21
(0˚C / 15kΩ, 25˚C / 5.4kΩ) MV Vane motor
Thermistor
Pipe temp. detection/liquid LEV Linear expansion valve
TH22
(0˚C / 15kΩ, 25˚C / 5.4kΩ)

TO MA REMOTE TB5
CONTROLLER S(SHIELD) T O NEXT
DC8.7-13V TO OUTDOOR UNIT INDOOR UNIT
M2 { BC CONTROLLER
TH23 TH22 TH21
RED M1 M-NET REMOTE CONTROLLER
PNK DC24-30V TB2
BLU
MV ORN L
YLW
5 PULL
N BOX
6 GRN/YLW
BRN MF
RED
BLU

BLU
BLU
1 2 3 FUSE
LEV ORN 1 61 5 1 2 3 4 1 2 31 2 1 2 (15A)
YLW

WHT

RED
RED
BLK

BLU
WHT CN32 CN33
CN60 CN5V HA CN29 CN21
LEV (BLU) REMOTE REVOLUTION GAS
CN41 LIQUID 1 2
(WHT) SWITCH (GRN)
(BLK) F AN1 1 4 6 CND 1 3 BREAKER
A.B (WHT) (WHT) (WHT) (15A)
(GRN) (RED)
ORN

CN2M
ORN

SW5 4 1 5 1 5
220V 240V (RED) 4 8 1 3 1 2 M-NET
ADDRESS 1 4 1 1 3 (BLU)
CN51 CN52 POWER SUPPLY
SW1 CN43 ~/N 220-240V50Hz
CENTRALLY REMOTE CN42 CN35-P C1
ON 1 8 CONTROL INDICATION CN81 CN3A CN20 ~/N 220V 60Hz
(RED) 8 ADDRESS ADDRESS (BLU) INTAKE MICON FUSE
OFF (WHT) (WHT) LED5
0FF

(RED) 5 BOARD
0N

1 2 3 4 5 6 7 8 9 10
ADDRESS (RED) (RED) (BLU) ZNR 250V
CN82
1 2 3 4 5 6 7 8 9 10

CN53-P F.C 6.3A


SW12 SW11 SW14
MICON
SW3

0 0 0 BOARD
LED2 1 (RED)
3RD 2ND 1ST CONNECTION 1 CN53-M 1 5
DIGIT DIGIT DIGIT NO. POWER BOARD
(RED)
1234

SW2

See fig:❈1 CN35-M 1 3 LED1


POWER BOARD
(BLU) P.B
M.B

Note
1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15.(Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to the wire.(BLU, two wire) <M1, M2>of CN2M
(Transmission line is non-polar.)
4. Symbols used in wiring diagram above are, : terminal block, : connector, : direct wire connection.
5. The setting of the SW2 dip switches differs in the capacity for the detail, refer to the fig: ❈1.
6. Please set the switch SW5 accordng to the power supply voltage.
SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220V side.

Led on indoor board for sevice


Mark Meaning Function
Main power supply (indoor unit:220-240V)
LED1 Main power supply
power on lamp is lit
Power supply for Power supply for MA-Remote controller
LED2 MA-Remote controller on lamp is lit
<❈ 1>
MODELS SW2 MODELS SW2
ON ON
PKFY-P20VAM OFF PKFY-P25VAM OFF
1 2 3 4 1 2 3 4

2- 181
VAM-A/VGM-A

5-2 PKFY-P-VGM-A
PKFY-P-

<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name
I.B Indoor controller board TH21 Room temp. detection A.B Circuit board
CN32 Connector Remote switch (0˚C/15kΩ,25˚C/5.4kΩ) SW1 Mode selection
CN41 HA terminal-A TH22 Pipe temp. detection/liquid SW5 Voltage selection
Thermistor
CN51 Centrally control (0˚C/15kΩ,25˚C/5.4kΩ) SW11 Address setting 1st digit
Switch
CN52 Remote indication TH23 Pipe temp. detection/Gas SW12 Address setting 2nd digit
SW2 Switch Capacity code (0˚C/15kΩ,25˚C/5.4kΩ) SW14 Connection No.
SW3 Mode selection MF Fan motor (with inner thermostat) SWC Option selector
SW4 Model selection C1 Capacitor (fan motor) P.B Indoor power board
ZNR Varistor MV Vane motor
X4 Aux.Relay (Fan motor) TB2 Power supply
Terminal
FUSE Fuse (6.3A) TB5 block Transmission
F.C Fan phase control TB15 MA-Remote controller
LEV Linear expansion valve

TO NEXT INDOOR UNIT


TB2
RED L
BLU N PULL BOX
GRN/YLW
P.B AC220-240V DC13.1V
MF (RED)
TRANS
(WHT)
CNSK CN2S
3 2 1 FUSE(15A)
3 2
WHT
RED

BLK

2 1
1 BREAKER
RED

WHT
BLU

BLK

C1 (15A)
I.B
FAN 1 3 5 CND 1 3 1 3 CNDK POWER SUPPLY
(WHT) (RED) BLK
(RED) ~220-240V 50Hz
FUSE
LED1 CN2D 1 WHT
250V ~220V 60Hz
X4
6.3A (WHT) 2
(WHT) (WHT) TB5 S(SHIELD)
HA DRAIN
F.C ZNR
4
(BLU) 1
1 3 2 1 (M-NET)
CN41 CN31 BLU
BLU
M2
M1
{ TO OUTDOOR UNIT
BC CONTROLLER
(GRN) (WHT) (WHT) CN2M 2 M-NET REMOTE CONTROLLER
X4 (WHT) REMOTE DC24-30V
REMOTE CENTRALLY LEV ORN
INDICATIONCONTROL SWITCH
CN52 CN51 CN60 CN32 CN3A 1 TB15
1 { TO MA-REMOTE
5 15 1 6 5 4 3 2 1 1 3 (BLU) 2 ORN 2 CONTROLLER
3 DC8.7-13V
(GRN) (RED) (RED)
VANE ADDRESS ADDRESS SW2 SW3 SW4 (RED) (WHT) (BLK)
CN6V CN81 CN42 0N 0N INTAKE LIQUID GAS
CN20 CN21 CN29
6 5 4 3 2 1 8 7 6 5 4 3 2 1 4 3 2 1 0FF 0FF
2 1 2 1 2 1 LED2
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 12345
ORN
YLW
BRN
RED

BLU
PIN

6
WHT
ORN
YLW

8 4
BRN
RED
BLU

MV See fig:❇1
A.B
SW5 4 LEV TH21 TH22 TH23
(RED)
220V 240V ADDRESS 3
CN43
2
SW1 1
ON
8
OFF (RED) 7 <❇1>
ADDRESS
1 2 3 4 5 6 7 8 910 CN82 6 Models SW2 SW3 SW4
SW12 SW11 SWC SW14 5
0 0 0 4 ON ON ON
P32 OFF
0 3 OFF
123456
OFF
1 2 3 4 5 6 7 8 9 10 1 234 5
3RD 2ND 1ST CONNECTION
2
ON ON ON
DIGIT DIGIT DIGIT NO. 1 P40 OFF OFF OFF
123456 1 2 3 4 5 6 7 8 9 10 1 234 5

NOTE ON ON ON
P50 OFF OFF OFF
123456 1 2 3 4 5 6 7 8 910 1 234 5
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5.(Transmission line is non-polar.)
4.Symbol[S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are, Led on indoor board for sevice
:Terminal block, :Connector. Mark Meaning Function
6.The setting of the SW2 dip switches differs in the capacity. For the detail,refer to the fig: ❇1. Main power supply (indoor unit:220-240V)
LED1 Main power supply
7.Please set the switch SW5 according to the power supply voltage. power on lamp is lit
Set SW5 to 240V side when the power supply is 230 and 240 volts. Power supply for Power supply for MA-Remote controller
LED2 MA-Remote controller on lamp is lit
When the power supply is 220 volts,set SW5 to 220V side.

2- 182
6. Temperature/Airflow distribution

VAM-A/VGM-A
6-1 PKFY-P-VAM-A

PKFY-P-
● Temperature distribution
<Cooling mode> <Heating mode>
Horizontal air flow Downward air flow
2.7 2.7

2 27 2
Height (m)

Height (m)
33
25
1 1
21 23 23
31

25 25
23 29
31
27 29 27
0 0
0 1 2 3 4 0 1 2 3 4
Floor distance (m) Floor distance (m)

● Airflow distribution

<Fan mode> <Fan mode>


Horizontal air flow Downward air flow
2.7 2.7

2 2
3.0
Height (m)

Height (m)

2.0

3.0
1.0 2.0
1 1
0.5

1.0 0.5
0.5 1.0
0 0
0 1 2 3 4 0 1 2 3 4
Floor distance (m) Floor distance (m)

2- 183
VAM-A/VGM-A

6-2 PKFY-P-VGM-A
PKFY-P-

● Temperature distribution
<Cooling mode> <Heating mode>
Flow angle : 10˚ Flow angle : 70˚
2.7 2.7
27
25

2 2
35
Height (m)

Height (m)
21 23

27 23
23
1 1
25
25 33
27

23 25 29 31 31 29
0 0
0 1 2 3 4 5 5.5 0 1 2 3 4 5 5.5
Floor distance (m) Floor distance (m)

● Airflow distribution

<Fan mode> <Fan mode>


Flow angle : 10˚ Flow angle : 70˚
2.7 2.7

2 4.0 2
Height (m)

Height (m)

3.0 0.5
4.0

2.0
1 1 3.0

1.0
0.5
0.5 0.5
1.0 2.0 1.0
0 0
0 1 2 3 4 5 5.5 0 1 2 3 4 5 5.5
Floor distance (m) Floor distance (m)

2- 184
Wall mounted PKFY-P-VFM-A

PKFY(Non-CE)
CONTENTS

1. Specifications ·································································2-186

2. Capacity Tables ······························································2-187


2-1 Cooling Capacity(PUMY) ················································2-187
2-2 Heating Capacity(PUMY) ················································2-187
2-3 Cooling Capacity(Y/R2-8·10·13HP) ·······························2-188
2-4 Heating Capacity(Y/R2-8·10·13HP) ·······························2-188
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ····················· 2-189
2-6 Heating Capacity(Big Y, Super Y, Big R2) ····················· 2-189
2-7 Cooling Capacity(WY, WR2) ········································· 2-190
2-8 Heating Capacity(WY, WR2) ········································· 2-190

3. Sound Levels ·······························································2-191


3-1 Noise levels ·································································2-191
3-2 N/C curves ································································ 2-191

4. External Dimensions ····················································2-192

5. Electrical Wiring Diagrams ···········································2-194


5-1 PKFY-P-VFM-A ·······························································2-194

2- 185
1. Specifications
PKFY-P63VFM-A PKFY-P100VFM-A
Power source ~ 220-240V 50Hz / ~ 220V 60Hz
❇1 kW 7.1 11.2
Cooling capacity
❇2 kcal/h 6,300 10,000
Heating capacity ❇1 kW 8.0 12.5
Power Cooling kW 0.11-0.12 0.13-0.14
PKFY(Non-CE)

consumption Heating kW 0.11-0.12 0.13-0.14


Cooling A 0.54-0.55 0.63-0.64
Current
Heating A 0.54-0.55 0.63-0.64
External finish(Munsel No.) Plastic, white : <3.4Y7.7/0.8>
Height mm 340
Dimension Width mm 1,400 1,680
Depth mm 235
Net weight kg 24 28
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Line flow fan ✕ 2
Airflow rate ❇3
Fan (Lo-Hi) m3/min 15-20 22-28
External static pressure Pa 0
Type Single phase induction motor
Motor
Output kW 0.04 0.07
Air filter PP Honeycomb fabric
Gas mm ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid mm ø 9.52
(Flare)
Drain pipe dimension VP-20
Noise level (Lo-Hi) ❇3 ❇4 dB(A) 39-45 41-46
Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 Airflow rate/noise level are in (low-high).
❇ 4 It is measured in anechoic room.

2- 186
2. Capacity Table
2-1.Cooling Capacity (In combination with PUMY)
CA:Capacity(kW)
PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB

PKFY(Non-CE)
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 7.0 5.3 7.4 5.6 7.9 5.5 8.3 5.7
22.5 6.9 5.3 7.3 5.5 7.8 5.5 8.2 5.7
25.0 6.9 5.2 7.3 5.5 7.7 5.5 8.2 5.6
27.5 6.8 5.2 7.2 5.5 7.7 5.4 8.1 5.6
63 30.0 6.7 5.2 7.1 5.4 7.5 5.4 8.0 5.6
(7.1) 32.5 6.6 5.1 7.0 5.4 7.5 5.3 7.9 5.5
35.0 6.5 5.1 6.9 5.3 7.3 5.3 7.8 5.5
37.5 6.4 5.0 6.8 5.3 7.2 5.2 7.7 5.4
40.0 6.3 5.0 6.7 5.3 7.2 5.2 7.6 5.4
46.0 6.1 4.9 6.5 5.1 6.9 5.1 7.3 5.3
20.0 11.1 8.0 11.6 8.3 12.5 8.3 13.1 8.5
22.5 10.9 7.9 11.5 8.3 12.3 8.2 13.0 8.4
25.0 10.8 7.9 11.5 8.2 12.2 8.2 12.9 8.4
27.5 10.7 7.8 11.3 8.2 12.1 8.1 12.8 8.3
100 30.0 10.5 7.7 11.2 8.1 11.9 8.0 12.6 8.3
(11.2) 32.5 10.4 7.6 11.1 8.0 11.8 8.0 12.5 8.2
35.0 10.2 7.6 10.9 8.0 11.6 7.9 12.3 8.1
37.5 10.1 7.5 10.8 7.9 11.4 7.8 12.2 8.1
40.0 10.0 7.4 10.6 7.8 11.3 7.7 12.0 8.0
46.0 9.6 7.2 10.2 7.6 10.8 7.5 11.5 7.8

2-2.Heating Capacity (In combination with PUMY)


PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 Unit air temp. 15.0 20.0 25.0
size size
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 5.1 5.0 4.9 -12.0 8.0 7.8 7.7
-10.0 5.4 5.3 5.2 -10.0 8.4 8.2 8.1
-5.0 6.1 6.0 5.9 -5.0 9.6 9.4 9.3
0.0 6.9 6.9 6.8 0.0 10.9 10.7 10.6
63 2.5 7.4 7.3 7.2 100 2.5 11.5 11.4 11.3
6.0 8.0 8.0 7.9 6.0 12.6 12.5 12.3
7.5 8.3 8.3 7.9 7.5 13.0 12.9 12.4
10.0 8.8 8.8 7.9 10.0 13.8 13.7 12.4
12.5 9.4 8.8 7.9 12.5 14.6 13.8 12.4
15.5 9.8 8.8 7.9 15.5 15.4 13.8 12.4

2- 187
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)
CA:Capacity(kW)
PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
PKFY(Non-CE)

˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC


20.0 7.0 5.3 7.1 5.4 7.4 5.3 7.5 5.4 7.7 5.5 8.0 5.4 8.2 5.2
22.5 6.9 5.3 7.0 5.4 7.3 5.3 7.5 5.3 7.6 5.5 7.9 5.4 8.2 5.2
25.0 6.8 5.2 7.0 5.4 7.2 5.2 7.4 5.3 7.5 5.5 7.8 5.3 8.1 5.2
27.5 6.7 5.2 6.9 5.3 7.2 5.2 7.3 5.3 7.5 5.4 7.7 5.3 8.0 5.2
63 30.0 6.7 5.2 6.8 5.3 7.1 5.2 7.2 5.2 7.4 5.4 7.7 5.3 8.0 5.1
(7.1) 32.5 6.6 5.1 6.7 5.3 7.0 5.1 7.2 5.2 7.3 5.4 7.6 5.3 7.9 5.1
35.0 6.5 5.1 6.7 5.2 7.0 5.1 7.1 5.2 7.2 5.4 7.5 5.2 7.8 5.1
37.5 6.5 5.1 6.6 5.2 6.9 5.1 7.0 5.2 7.2 5.3 7.5 5.2 7.7 5.1
40.0 6.4 5.0 6.5 5.2 6.8 5.1 7.0 5.1 7.1 5.3 7.4 5.2 7.7 5.1
43.0 6.3 5.0 6.4 5.1 6.7 5.0 6.9 5.1 7.0 5.3 7.3 5.1 7.6 5.0
20.0 11.0 7.9 11.2 8.1 11.6 7.9 11.9 8.0 12.1 8.2 12.5 8.0 13.0 7.7
22.5 10.9 7.9 11.1 8.0 11.5 7.9 11.8 7.9 12.0 8.1 12.4 7.9 12.9 7.7
25.0 10.8 7.8 11.0 8.0 11.4 7.8 11.6 7.9 11.9 8.1 12.3 7.9 12.8 7.7
27.5 10.6 7.8 10.9 7.9 11.3 7.8 11.5 7.8 11.8 8.0 12.2 7.8 12.7 7.6
100 30.0 10.5 7.7 10.8 7.9 11.2 7.7 11.4 7.8 11.6 8.0 12.1 7.8 12.5 7.6
(11.2) 32.5 10.4 7.7 10.6 7.8 11.1 7.7 11.3 7.7 11.5 8.0 12.0 7.8 12.4 7.5
35.0 10.3 7.6 10.5 7.8 11.0 7.6 11.2 7.7 11.4 7.9 11.9 7.7 12.3 7.5
37.5 10.2 7.5 10.4 7.7 10.9 7.6 11.1 7.6 11.3 7.9 11.8 7.7 12.2 7.5
40.0 10.1 7.5 10.3 7.7 10.8 7.5 11.0 7.6 11.2 7.8 11.6 7.6 12.1 7.4
43.0 9.9 7.4 10.2 7.6 10.6 7.4 10.8 7.5 11.1 7.8 11.5 7.6 12.0 7.4

2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A, TEM-A)


PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15.0 20.0 25.0 27.0 Unit air temp. 15.0 20.0 25.0 27.0
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 5.4 5.3 5.2 5.2 -15.0 8.4 8.2 8.2 8.1
-10.0 6.1 6.0 6.0 5.5 -10.0 9.6 9.4 9.3 8.6
-5.0 6.9 6.8 6.2 5.5 -5.0 10.7 10.6 9.8 8.6
0.0 7.6 7.5 6.2 5.5 0.0 11.9 11.8 9.8 8.6
63 2.5 8.0 7.9 6.2 5.5 2.5 12.5 12.4 9.8 8.6
6.0 8.1 8.0 6.2 5.5 100 6.0 12.6 12.5 9.8 8.6
7.5 8.4 8.0 6.2 5.5 7.5 13.2 12.5 9.8 8.6
10.0 9.0 8.0 6.2 5.5 10.0 14.1 12.5 9.8 8.6
12.5 9.6 8.0 6.2 5.5 12.5 15.0 12.5 9.8 8.6
15.5 9.7 8.0 6.2 5.5 15.5 15.1 12.5 9.8 8.6

2- 188
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA:Capacity(kW)
PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC

PKFY(Non-CE)
20.0 6.5 5.1 6.9 5.3 7.4 5.3 7.9 5.6 8.4 5.5 8.9 5.5
22.5 6.5 5.1 6.8 5.3 7.3 5.3 7.8 5.6 8.3 5.5 8.7 5.4
25.0 6.5 5.1 6.8 5.3 7.2 5.2 7.7 5.5 8.1 5.5 8.6 5.4
27.5 6.4 5.0 6.7 5.2 7.2 5.2 7.6 5.5 8.0 5.4 8.5 5.3
30.0 6.4 5.0 6.6 5.2 7.1 5.2 7.5 5.5 7.9 5.4 8.4 5.3
63 32.5 6.3 5.0 6.6 5.2 7.0 5.1 7.4 5.4 7.8 5.3 8.2 5.2
35.0 6.3 5.0 6.5 5.1 6.9 5.1 7.3 5.4 7.7 5.3 8.1 5.2
37.5 6.2 4.9 6.4 5.1 6.8 5.1 7.2 5.3 7.6 5.3 8.0 5.2
40.0 6.2 4.9 6.4 5.1 6.7 5.0 7.1 5.3 7.5 5.2 7.9 5.1
43.0 6.1 4.9 6.3 5.0 6.6 5.0 7.0 5.3 7.3 5.2 7.7 5.1
20.0 10.3 7.6 10.8 7.9 11.6 7.9 12.5 8.4 13.2 8.2 14.0 8.1
22.5 10.3 7.6 10.8 7.9 11.5 7.9 12.3 8.3 13.0 8.2 13.8 8.0
25.0 10.2 7.6 10.7 7.8 11.4 7.8 12.1 8.2 12.8 8.1 13.6 8.0
27.5 10.1 7.5 10.6 7.8 11.3 7.7 12.0 8.2 12.7 8.0 13.4 7.9
100 30.0 10.1 7.5 10.5 7.7 11.2 7.7 11.8 8.1 12.5 8.0 13.2 7.8
32.5 10.0 7.4 10.3 7.7 11.0 7.6 11.7 8.0 12.3 7.9 13.0 7.7
35.0 9.9 7.4 10.2 7.6 10.9 7.6 11.5 8.0 12.1 7.8 12.8 7.7
37.5 9.8 7.4 10.1 7.6 10.8 7.5 11.4 7.9 12.0 7.8 12.6 7.6
40.0 9.7 7.3 10.0 7.5 10.6 7.5 11.2 7.8 11.8 7.7 12.4 7.5
43.0 9.6 7.3 9.9 7.5 10.5 7.4 11.0 7.7 11.6 7.6 12.2 7.4

2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)

PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)


Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15 21 25 27 Unit air temp. 15 21 25 27
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 3.1 3.1 3.0 3.0 -15.0 7.8 7.7 7.5 7.4
-10.0 3.6 3.5 3.5 3.4 -10.0 8.9 8.8 8.6 8.5
-5.0 4.0 4.0 3.9 3.9 -5.0 10.0 9.9 9.8 9.6
0.0 4.5 4.4 4.3 3.9 0.0 11.2 11.0 10.6 9.6
40 2.5 4.7 4.7 4.3 3.9 100 2.5 11.8 11.6 10.6 9.6
6.0 5.0 5.0 4.3 3.9 6.0 12.6 12.5 10.6 9.6
7.5 5.2 5.0 4.3 3.9 7.5 13.0 12.5 10.6 9.6
10.0 5.4 5.0 4.3 3.9 10.0 13.6 12.5 10.6 9.6
12.5 5.7 5.0 4.3 3.9 12.5 14.3 12.5 10.6 9.6
15.5 5.8 5.0 4.3 3.9 15.5 14.4 12.5 10.6 9.6

2- 189
2-7.Cooling Capacity (In combination with WY, WR2)
CA:Capacity(kW)
PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Water
temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
PKFY(Non-CE)

10 6.9 5.3 7.2 5.5 7.6 5.4 7.8 5.5 8.0 5.7 8.5 5.6 9.0 5.5
20 6.7 5.2 6.9 5.3 7.3 5.3 7.5 5.4 7.8 5.6 8.2 5.5 8.6 5.4
63 30 6.3 5.0 6.5 5.1 6.9 5.1 7.1 5.2 7.3 5.4 7.7 5.3 8.1 5.2
40 5.5 4.6 5.7 4.8 6.0 4.7 6.2 4.8 6.4 5.0 6.7 4.9 7.1 4.9
45 5.2 4.5 5.3 4.6 5.7 4.6 5.8 4.7 6.0 4.9 6.3 4.8 6.7 4.7
10 10.9 7.9 11.3 8.2 12.0 8.1 12.3 8.2 12.7 8.5 13.4 8.3 14.1 8.2
20 10.5 7.7 10.9 7.9 11.6 7.9 11.9 8.0 12.2 8.3 12.9 8.1 13.6 8.0
100 30 9.9 7.4 10.3 7.6 10.9 7.6 11.2 7.7 11.5 8.0 12.2 7.8 12.8 7.7
40 8.6 6.8 8.9 7.0 9.5 7.0 9.7 7.1 10.0 7.3 10.6 7.2 11.2 7.1
45 8.1 6.6 8.4 6.8 8.9 6.7 9.2 6.8 9.5 7.1 10.0 7.0 10.5 6.9

2-8.Heatling Capacity (In combination with WY, WR2)

PKFY-P-VFM-A SHC:Sensible Heat Capacity(kW)


Water Indoor air temp.:˚CDB
Unit temp. 15 19 20 25 27
size
˚C SHC SHC SHC SHC SHC
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3

2- 190
3. Sound Levels
3-1. Noise level

Wall mounted
Noise level at anechoic room
(Low-Middle2-Middle1-High) Unit : dB(A)

PKFY(Non-CE)
Model Noise level (A weighted)
PKFY-P63VFM-A 39-45 (Low-High)
PKFY-P100VFM-A 41-46 (Low-High)
1.0m

Measurement location 1.0m

3-2. NC curves
PKFY-P63VFM-A PKFY-P100VFM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB =20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
Approximate minimum Approximate minimum
NC20 NC20
audible limit on audible limit on
continuous noise continuous noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 191
PKFY(Non-CE)

Top

62.5
235 45 235 45 235 45 235

13
PKFY-P63VFM-A

Front Right side

Left side 1400 235


Knock out hole for right piping
1090 Air intake
Refrigerant pipe. Drain pipe

A C

197

340
Terminal block
4. External Dimensions

15 and less
Liquid pipe for remote control
Knock out hole for piping Knock out hole for Terminal block for power supply
left piping
Gas pipe
A B C
30 30 Bolt

42
58

100

100
65
39

37
25 Drain hose
Drain hose for Drain hose
37 39 37

2- 192
55 (Gas pipe) 107

4 39
left-hand side piping

4
74 98 32 74 1110 183 120 111
(Liquid pipe)

Lower side
Liquid pipe 9.52(3/8F)
Auto vane Gas pipe 15.88(5/8F)
Unit center
1120 240
990 245 552 Air outlet 552 Air outlet
455
10 91=(910) 285
900 19
Wall fixture 18 18 Drainage range Drainage range 91
on left-hand side on right-hand side

29

10
30
Under panel Change vane (manual)
66-ø6 hole for B
Removable at left-hand

80
tapping screw side piping Knock out hole for under-piping

280

30
184
Refrigerant pipe. Drain pipe

60
32-ø12 hole for bolt

30
225 240 180 280 314
610 90 Rear piping opening
12-ø6 hole for
Unit : mm

tapping screw Range for left rear piping opening


Top

62.5
235 45 235 45 235 45 235 45 235

13
PKFY-P100VFM-A

Front Knock out hole for right piping


Right side
Left side 1680
235
1370 Air intake

A C

197

340
Knock out hole for wiring
Knock out hole for left piping
Terminal block
A B C for remote control 15 and less
Liquid pipe
30 30 Terminal block for power supply
Gas pipe

Bolt

100

100
65
39

37
37 39 37

4 39
42
58

4
98 65

2- 193
74 74
25
Drain hose
55 (Gas pipe) 102
Drain hose for left-hand side piping 1110 Drain hose 120
183 111
Lower side (Liquid pipe)
1400 240 Gas pipe 19.05(3/4F)
Liquid pipe 9.52(3/8F)
694 Air outlet 694 Air outlet
Unit center
Unit out line
1270 245
595
Wall fixture
13 91=(1183) 285
84-ø6 hole for 18 18 900 19
tapping screw Drainage range Drainage range 91
on left-hand side on right-hand side Change vane (manual)

29
B

10
30
Under panel
(Removable at left-hand side piping)

80
Auto vane

280

30
184
Knock out hole for under-piping
60 Refrigerant pipe. Drain pipe
41-ø12 hole for bolt

30
295 225 240 180 280 314
90 Rear piping opening
Unit : mm

750
Range for left rear piping opening Range for left rear piping opening

12-ø6 hole for tapping screw

PKFY(Non-CE)
5. Electrical Wiring Diagram
5-1 PKFY-P-VFM-A
<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name
I.B Indoor controller board TH21 Room temp. detection A.B Circuit board
CN32 Remote switch (0˚C/15kΩ,25˚C/5.4kΩ) SW1 Mode selection
CN41 HA terminal-A TH22 Pipe temp. detection/liquid SW5 Voltage selection
PKFY(Non-CE)

Thermistor
CN51 Connector Centrally control (0˚C/15kΩ,25˚C/5.4kΩ) SW11 Address setting 1st digit
Switch
CN52 Remote indication TH23 Pipe temp. detection/Gas SW12 Address setting 2nd digit
CNP D. Heater (0˚C/15kΩ,25˚C/5.4kΩ) SW14 Connection No.
SW2 Capacity code MF Fan motor (with inner thermostat) SWC Option selector
SW3 Switch Mode selection C1 Capacitor (fan motor) P.B Indoor power board
SW4 Model selection MV Vane motor DP Drain-up machine (OPTION)
ZNR Varistor TB2 Power supply DS Drain sensor (OPTION)
Terminal
X4 Aux.Relay (Fan motor) TB5 Transmission
block
X1 Aux.Relay D. Heater TB15 MA-Remote controller
FUSE Fuse (6.3A) LEV Linear expansion valve
F.C Fan phase control H2 Dew prevention heater

TO NEXT INDOOR UNIT


TB2
RED L
BLU N PULL BOX
GRN/YLW
P.B AC220-240V DC13.1V
MF (RED)
TRANS
(WHT)
H2 CNSK CN2S
3 2 1 FUSE(15A)
3 2
WHT
RED

BLK

2 1
1 BREAKER
RED

WHT
BLU

BLK

C1 (15A)
I.B
FAN 1 3 5 CND 1 3 CNP 1 3 1 3 CNDK POWER SUPPLY
(WHT) (RED) BLK
(RED) ~220-240V 50Hz
FUSE
LED1 CN2D 1 WHT
250V ~220V 60Hz
X4
6.3A (WHT) 2
(WHT) (WHT) TB5 S(SHIELD)
HA DRAIN
F.C ZNR X1 CN41
(BLU) 1 CN31 BLU M2 { TO OUTDOOR UNIT
4 1 3 2 1 (M-NET) BLU M1 BC CONTROLLER
CN2M 2 M-NET REMOTE CONTROLLER
(GRN) (WHT) (WHT) (WHT)
X4 X1 REMOTE CENTRALLY REMOTE DC24-30V
LEV SWITCH ORN
INDICATIONCONTROL
CN52 CN51 CN60 CN32 CN3A 1 TB15
1 { TO MA-REMOTE
5 15 1 6 5 4 3 2 1 1 3 (BLU) 2 ORN 2 CONTROLLER
3 DC8.7-13V
(GRN) (RED) (RED)
VANE ADDRESS ADDRESS SW2 SW3 SW4 (RED) (WHT) (BLK)
CN6V CN81 CN42 0N 0N INTAKE LIQUID GAS
CN20 CN21 CN29
6 5 4 3 2 1 8 7 6 5 4 3 2 1 4 3 2 1 0FF 0FF
2 1 2 1 2 1 LED2
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 12345
ORN
YLW
BRN
RED

BLU
PIN

6
WHT
ORN
YLW

8 4
BRN
RED
BLU

MV See fig:❇1
A.B
SW5 4 LEV TH21 TH22 TH23
(RED)
220V 240V ADDRESS 3
CN43
2
SW1 1
ON
8
OFF (RED) 7
ADDRESS
1 2 3 4 5 6 7 8 910 CN82 6
SW12 SW11 SWC SW14 5
0 0 0 4
0 3
3RD 2ND 1ST CONNECTION
2
DIGIT DIGIT DIGIT NO. 1
<❇1>
Models SW2 SW3 SW4
NOTE
ON ON ON
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit. P63 OFF OFF OFF
123456 1 2 3 4 5 6 7 8 9 10 1 234 5
2.In case of using MA-Remote controller, please connect to TB15.
ON ON ON
(Remote controller wire is non-polar.) P100 OFF OFF OFF
123456 1 2 3 4 5 6 7 8 9 10 1 234 5
3.In case of using M-NET, please connect to TB5.(Transmission line is non-polar.)
4.Symbol[S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are, Led on indoor board for sevice
:Terminal block, :Connector. Mark Meaning Function
6.The setting of the SW2 dip switches differs in the capacity. For the detail,refer to the fig: ❇1. Main power supply (indoor unit:220-240V)
LED1 Main power supply
7.Please set the switch SW5 according to the power supply voltage. power on lamp is lit
Set SW5 to 240V side when the power supply is 230 and 240 volts. Power supply for Power supply for MA-Remote controller
LED2 MA-Remote controller on lamp is lit
When the power supply is 220 volts,set SW5 to 220V side.

2- 194
Ceiling suspended PCFY-P-VGM-A

CONTENTS

PCFY-P-VGM-A
1. Specifications ·································································2-196

2. Capacity Tables ······························································2-197


2-1 Cooling Capacity(PUMY) ················································2-197
2-2 Heating Capacity(PUMY) ················································2-197
2-3 Cooling Capacity(Y/R2-8·10·13HP) ······························· 2-198
2-4 Heating Capacity(Y/R2-8·10·13HP) ······························· 2-198
2-5 Cooling Capacity(Big Y, Super Y, Big R2) ·······················2-199
2-6 Heating Capacity(Big Y, Super Y, Big R2) ·······················2-199
2-7 Cooling Capacity(WY, WR2) ··········································2-200
2-8 Heating Capacity(WY, WR2) ··········································2-200

3. Sound Levels ·······························································2-201


3-1 Sound levels ·································································2-201
3-2 N/C curves ·································································· 2-201

4. External Dimension ····················································2-202

5. Wiring Diagram ····························································· 2-203

6. Temperature/Airflow distribution ································· 2-204

2- 195
1. Specifications
PCFY-P40VGM-A PCFY-P63VGM-A PCFY-P100VGM-A PCFY-P125VGM-A
Power source ~ 220-240V 50Hz / ~220V 60Hz
❇1 kW 4.5 7.1 11.2 14.0
Cooling capacity
❇2 kcal/h 4,000 6,300 10,000 12,500
Heating capacity ❇1 kW 5.0 8.0 12.5 16.0
Power Cooling kW 0.10 0.13 0.16 0.24
consumption Heating kW 0.10 0.13 0.16 0.24
Cooling A 0.46 0.60 0.73 1.10
Current
Heating A 0.46 0.60 0.73 1.10
External finish(Munsel No.) 0.70Y 8.59/0.97
Height mm 210 270
Dimension ❇ 3 Width mm 1,000 1,310 1,620
Depth mm 680
PCFY-P-VGM-A

Net weight ❇3 kg 27 34 37 43
Heat exchanger Cross fin (Aluminum plate fin and copper tube)
Type Sirocco fan✕ 2 Sirocco fan✕ 3 Sirocco fan✕ 4
Airflow rate ❇3
m3/min 8-10-11-12 12-14-16-18 18-20-23-25 26-28-32-35
Fan (Lo-Mid2-Mid1-Hi)
External static
Pa 0
pressure
Type Single phase induction motor
Motor
Output kW 0.054 0.070 0.090 0.150
Air filter PP Honeycomb (long life)
Gas
mm ø 12.7 ø 15.88 ø 19.05
Refrigerant (Flare)
pipe dimension Liquid
mm ø 6.35 ø 9.52
(Flare)
Drain pipe dimension VP-25
Noise level (Lo-Mid2-Mid1-Hi) ❇3 ❇4 dB(A) 29-33-36-38 32-34-37-39 36-38-41-43 37-39-42-44

Note: ❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇3 External dimension/net weight are shown in (unit/panel),and airflw rate/noise level are in (low-middle 2-middle
1-high).
❇4 It is measured in anechoic room.

2- 196
2. Capacity Tables
2-1.Cooling Capacity (In combination with PUMY)
CA :Capacity(kW)
PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Unit Outdoor
air temp. 23˚CDB 25˚CDB 28˚CDB 30˚CDB
size 16˚CWB 18˚CWB 20˚CWB 22˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC
20.0 4.5 3.1 4.7 3.2 5.0 3.2 5.3 3.3
22.5 4.4 3.1 4.6 3.2 5.0 3.2 5.2 3.3
25.0 4.3 3.1 4.6 3.2 4.9 3.2 5.2 3.3
27.5 4.3 3.0 4.6 3.2 4.9 3.2 5.1 3.2
40 30.0 4.2 3.0 4.5 3.2 4.8 3.1 5.1 3.2
(4.5) 32.5 4.2 3.0 4.4 3.1 4.7 3.1 5.0 3.2
35.0 4.1 2.9 4.4 3.1 4.7 3.1 5.0 3.2
37.5 4.1 2.9 4.3 3.1 4.6 3.0 4.9 3.1

PCFY-P-VGM-A
40.0 4.0 2.9 4.3 3.0 4.5 3.0 4.8 3.1
46.0 3.8 2.8 4.1 3.0 4.3 2.9 4.6 3.0
20.0 7.0 5.0 7.4 5.1 7.9 5.1 8.3 5.3
22.5 6.9 4.9 7.3 5.1 7.8 5.1 8.2 5.2
25.0 6.9 4.9 7.3 5.1 7.7 5.1 8.2 5.2
27.5 6.8 4.8 7.2 5.0 7.7 5.0 8.1 5.2
63 30.0 6.7 4.8 7.1 5.0 7.5 5.0 8.0 5.1
(7.1) 32.5 6.6 4.7 7.0 5.0 7.5 4.9 7.9 5.1
35.0 6.5 4.7 6.9 4.9 7.3 4.9 7.8 5.0
37.5 6.4 4.6 6.8 4.9 7.2 4.8 7.7 5.0
40.0 6.3 4.6 6.7 4.8 7.2 4.8 7.6 4.9
46.0 6.1 4.5 6.5 4.7 6.9 4.6 7.3 4.8
20.0 11.1 7.8 11.6 8.1 12.5 8.1 13.1 8.3
22.5 10.9 7.8 11.5 8.1 12.3 8.0 13.0 8.3
25.0 10.8 7.7 11.5 8.0 12.2 8.0 12.9 8.2
27.5 10.7 7.6 11.3 8.0 12.1 7.9 12.8 8.2
100 30.0 10.5 7.5 11.2 7.9 11.9 7.8 12.6 8.1
(11.2) 32.5 10.4 7.5 11.1 7.8 11.8 7.8 12.5 8.0
35.0 10.2 7.4 10.9 7.8 11.6 7.7 12.3 7.9
37.5 10.1 7.3 10.8 7.7 11.4 7.6 12.2 7.9
40.0 10.0 7.3 10.6 7.6 11.3 7.6 12.0 7.8
46.0 9.6 7.1 10.2 7.4 10.8 7.3 11.5 7.6
20.0 13.9 9.9 14.6 10.3 15.6 10.2 16.4 10.5
22.5 13.7 9.8 14.4 10.2 15.4 10.1 16.2 10.4
25.0 13.5 9.7 14.3 10.1 15.3 10.1 16.1 10.3
27.5 13.4 9.6 14.2 10.1 15.1 10.0 16.0 10.3
125 30.0 13.2 9.5 14.0 10.0 14.9 9.9 15.8 10.2
(14.0) 32.5 13.0 9.4 13.8 9.9 14.7 9.8 15.6 10.1
35.0 12.8 9.3 13.7 9.8 14.5 9.7 15.4 10.0
37.5 12.6 9.2 13.4 9.7 14.3 9.6 15.2 9.9
40.0 12.5 9.1 13.3 9.6 14.1 9.5 15.0 9.8
46.0 12.0 8.9 12.8 9.4 13.5 9.2 14.4 9.6

2-2.Heating Capacity (In combination with PUMY)


PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 size 15.0 20.0 25.0
˚CWB SHC SHC SHC ˚CWB SHC SHC SHC
-12.0 3.2 3.1 3.1 -12.0 8.0 7.8 7.7
-10.0 3.4 3.3 3.2 -10.0 8.4 8.2 8.1
-5.0 3.8 3.8 3.7 -5.0 9.6 9.4 9.3
0.0 4.3 4.3 4.2 0.0 10.9 10.7 10.6
2.5 4.6 4.6 4.5 100 2.5 11.5 11.4 11.3
40
6.0 5.0 5.0 4.9 6.0 12.6 12.5 12.3
7.5 5.2 5.2 5.0 7.5 13.0 12.9 12.4
10.0 5.5 5.5 5.0 10.0 13.8 13.7 12.4
12.5 5.9 5.5 5.0 12.5 14.6 13.8 12.4
15.5 6.2 5.5 5.0 15.5 15.4 13.8 12.4
-12.0 5.1 5.0 4.9 -12.0 10.2 10.0 9.8
-10.0 5.4 5.3 5.2 -10.0 10.7 10.6 10.4
-5.0 6.1 6.0 5.9 -5.0 12.2 12.1 11.9
0.0 6.9 6.9 6.8 0.0 13.9 13.8 13.6
2.5 7.4 7.3 7.2 125 2.5 14.8 14.7 14.5
63
6.0 8.0 8.0 7.9 6.0 16.1 16.0 15.8
7.5 8.3 8.3 7.9 7.5 16.7 16.6 15.8
10.0 8.8 8.8 7.9 10.0 17.7 17.6 15.8
12.5 9.4 8.8 7.9 12.5 18.7 17.7 15.8
15.5 9.8 8.8 7.9 15.5 19.7 17.7 15.8

2- 197
2-3.Cooling Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A)
CA :Capacity(kW)
PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.4 3.1 4.5 3.2 4.7 3.1 4.8 3.1 4.9 3.2 5.0 3.1 5.2 3.0
22.5 4.4 3.1 4.5 3.1 4.6 3.1 4.7 3.1 4.8 3.1 5.0 3.1 5.2 3.0
25.0 4.3 3.1 4.4 3.1 4.6 3.0 4.7 3.0 4.8 3.1 5.0 3.0 5.1 3.0
27.5 4.3 3.0 4.4 3.1 4.5 3.0 4.6 3.0 4.7 3.1 4.9 3.0 5.1 2.9
40 30.0 4.2 3.0 4.3 3.1 4.5 3.0 4.6 3.0 4.7 3.1 4.9 3.0 5.0 2.9
(4.5) 32.5 4.2 3.0 4.3 3.0 4.5 3.0 4.5 3.0 4.6 3.1 4.8 3.0 5.0 2.9
35.0 4.1 3.0 4.2 3.0 4.4 2.9 4.5 3.0 4.6 3.0 4.8 3.0 5.0 2.9
37.5 4.1 2.9 4.2 3.0 4.4 2.9 4.5 2.9 4.5 3.0 4.7 3.0 4.9 2.9
PCFY-P-VGM-A

40.0 4.1 2.9 4.1 3.0 4.3 2.9 4.4 2.9 4.5 3.0 4.7 2.9 4.9 2.9
43.0 4.0 2.9 4.1 2.9 4.3 2.9 4.4 2.9 4.4 3.0 4.6 2.9 4.8 2.8
20.0 7.0 4.9 7.1 5.0 7.4 4.9 7.5 4.9 7.7 5.0 8.0 4.9 8.2 4.7
22.5 6.9 4.9 7.0 5.0 7.3 4.8 7.5 4.9 7.6 5.0 7.9 4.9 8.2 4.7
25.0 6.8 4.8 7.0 4.9 7.2 4.8 7.4 4.8 7.5 5.0 7.8 4.8 8.1 4.7
27.5 6.7 4.8 6.9 4.9 7.2 4.8 7.3 4.8 7.5 4.9 7.7 4.8 8.0 4.7
63 30.0 6.7 4.8 6.8 4.9 7.1 4.7 7.2 4.8 7.4 4.9 7.7 4.8 8.0 4.6
(7.1) 32.5 6.6 4.7 6.7 4.8 7.0 4.7 7.2 4.7 7.3 4.9 7.6 4.7 7.9 4.6
35.0 6.5 4.7 6.7 4.8 7.0 4.7 7.1 4.7 7.2 4.8 7.5 4.7 7.8 4.6
37.5 6.5 4.7 6.6 4.7 6.9 4.6 7.0 4.7 7.2 4.8 7.5 4.7 7.7 4.6
40.0 6.4 4.6 6.5 4.7 6.8 4.6 7.0 4.6 7.1 4.8 7.4 4.7 7.7 4.5
43.0 6.3 4.6 6.4 4.7 6.7 4.6 6.9 4.6 7.0 4.7 7.3 4.6 7.6 4.5
20.0 11.0 7.8 11.2 7.9 11.6 7.7 11.9 7.7 12.1 8.0 12.5 7.7 13.0 7.5
22.5 10.9 7.7 11.1 7.9 11.5 7.7 11.8 7.7 12.0 7.9 12.4 7.7 12.9 7.5
25.0 10.8 7.7 11.0 7.8 11.4 7.6 11.6 7.7 11.9 7.9 12.3 7.7 12.8 7.4
27.5 10.6 7.6 10.9 7.7 11.3 7.6 11.5 7.6 11.8 7.8 12.2 7.6 12.7 7.4
100 30.0 10.5 7.5 10.8 7.7 11.2 7.5 11.4 7.6 11.6 7.8 12.1 7.6 12.5 7.3
(11.2) 32.5 10.4 7.5 10.6 7.6 11.1 7.5 11.3 7.5 11.5 7.7 12.0 7.5 12.4 7.3
35.0 10.3 7.4 10.5 7.6 11.0 7.4 11.2 7.5 11.4 7.7 11.9 7.5 12.3 7.3
37.5 10.2 7.4 10.4 7.5 10.9 7.4 11.1 7.4 11.3 7.6 11.8 7.4 12.2 7.2
40.0 10.1 7.3 10.3 7.5 10.8 7.3 11.0 7.4 11.2 7.6 11.6 7.4 12.1 7.2
43.0 9.9 7.2 10.2 7.4 10.6 7.2 10.8 7.3 11.1 7.5 11.5 7.3 12.0 7.1
20.0 13.7 9.8 14.0 10.0 14.6 9.7 14.8 9.8 15.1 10.1 15.7 9.8 16.2 9.5
22.5 13.6 9.7 13.9 9.9 14.4 9.7 14.7 9.7 15.0 10.0 15.5 9.7 16.1 9.4
25.0 13.4 9.6 13.7 9.8 14.3 9.6 14.6 9.6 14.8 9.9 15.4 9.7 16.0 9.4
27.5 13.3 9.6 13.6 9.8 14.1 9.5 14.4 9.6 14.7 9.9 15.3 9.6 15.8 9.3
125 30.0 13.2 9.5 13.4 9.7 14.0 9.5 14.3 9.5 14.6 9.8 15.1 9.6 15.7 9.3
(14.0) 32.5 13.0 9.4 13.3 9.6 13.9 9.4 14.1 9.5 14.4 9.8 15.0 9.5 15.5 9.2
35.0 12.9 9.4 13.2 9.6 13.7 9.3 14.0 9.4 14.3 9.7 14.8 9.4 15.4 9.2
37.5 12.7 9.3 13.0 9.5 13.6 9.3 13.9 9.3 14.1 9.6 14.7 9.4 15.3 9.1
40.0 12.6 9.2 12.9 9.4 13.4 9.2 13.7 9.3 14.0 9.6 14.6 9.3 15.1 9.1
43.0 12.4 9.1 12.7 9.3 13.3 9.1 13.6 9.2 13.8 9.5 14.4 9.3 15.0 9.0

2-4.Heating Capacity (In combination with PU(H)Y, PURY-(P)200·250·315YEM-A)


PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. Unit air temp.
size 15.0 20.0 25.0 27.0 size 15.0 20.0 25.0 27.0
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 3.3 3.3 3.3 3.3 -15.0 8.4 8.2 8.2 8.1
-10.0 3.8 3.8 3.7 3.5 -10.0 9.6 9.4 9.3 8.6
-5.0 4.3 4.2 3.9 3.5 -5.0 10.7 10.6 9.8 8.6
0.0 4.8 4.7 3.9 3.5 0.0 11.9 11.8 9.8 8.6
2.5 5.0 5.0 3.9 3.5 2.5 12.5 12.4 9.8 8.6
40 100
6.0 5.1 5.0 3.9 3.5 6.0 12.6 12.5 9.8 8.6
7.5 5.3 5.0 3.9 3.5 7.5 13.2 12.5 9.8 8.6
10.0 5.6 5.0 3.9 3.5 10.0 14.1 12.5 9.8 8.6
12.5 6.0 5.0 3.9 3.5 12.5 15.0 12.5 9.8 8.6
15.5 6.1 5.0 3.9 3.5 15.5 15.1 12.5 9.8 8.6
-15.0 5.4 5.3 5.2 5.2 -15.0 10.7 10.6 10.5 10.4
-10.0 6.1 6.0 6.0 5.5 -10.0 12.2 12.1 11.9 11.0
-5.0 6.9 6.8 6.2 5.5 -5.0 13.7 13.6 12.5 11.0
0.0 7.6 7.5 6.2 5.5 0.0 15.3 15.1 12.5 11.0
2.5 8.0 7.9 6.2 5.5 2.5 16.0 15.8 12.5 11.0
63 125
6.0 8.1 8.0 6.2 5.5 6.0 16.2 16.0 12.5 11.0
7.5 8.4 8.0 6.2 5.5 7.5 16.8 16.0 12.5 11.0
10.0 9.0 8.0 6.2 5.5 10.0 18.0 16.0 12.5 11.0
12.5 9.6 8.0 6.2 5.5 12.5 19.1 16.0 12.5 11.0
15.5 9.7 8.0 6.2 5.5 15.5 19.4 16.0 12.5 11.0

2- 198
2-5.Cooling Capacity (In combination with Big Y, Super Y, Big R2)
CA :Capacity(kW)
PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 20˚CWB 22˚CWB 24˚CWB
˚CDB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
20.0 4.1 3.0 4.3 3.1 4.7 3.1 5.0 3.2 5.3 3.2 5.6 3.1
22.5 4.1 3.0 4.3 3.1 4.6 3.1 4.9 3.2 5.2 3.2 5.5 3.1
25.0 4.1 2.9 4.3 3.0 4.6 3.0 4.9 3.2 5.2 3.1 5.5 3.1
27.5 4.1 2.9 4.2 3.0 4.5 3.0 4.8 3.2 5.1 3.1 5.4 3.0
40 30.0 4.0 2.9 4.2 3.0 4.5 3.0 4.8 3.1 5.0 3.1 5.3 3.0
32.5 4.0 2.9 4.2 3.0 4.4 3.0 4.7 3.1 5.0 3.0 5.2 3.0
35.0 4.0 2.9 4.1 3.0 4.4 2.9 4.6 3.1 4.9 3.0 5.1 3.0
37.5 3.9 2.9 4.1 2.9 4.3 2.9 4.6 3.0 4.8 3.0 5.1 2.9
40.0 3.9 2.8 4.0 2.9 4.3 2.9 4.5 3.0 4.7 3.0 5.0 2.9
43.0 3.9 2.8 4.0 2.9 4.2 2.9 4.4 3.0 4.7 2.9 4.9 2.9

PCFY-P-VGM-A
20.0 6.5 4.7 6.9 4.9 7.4 4.9 7.9 5.1 8.4 5.1 8.9 5.0
22.5 6.5 4.7 6.8 4.9 7.3 4.9 7.8 5.1 8.3 5.0 8.7 4.9
25.0 6.5 4.7 6.8 4.8 7.2 4.8 7.7 5.0 8.1 5.0 8.6 4.9
27.5 6.4 4.6 6.7 4.8 7.2 4.8 7.6 5.0 8.0 4.9 8.5 4.8
63 30.0 6.4 4.6 6.6 4.8 7.1 4.7 7.5 5.0 7.9 4.9 8.4 4.8
32.5 6.3 4.6 6.6 4.7 7.0 4.7 7.4 4.9 7.8 4.8 8.2 4.7
35.0 6.3 4.6 6.5 4.7 6.9 4.7 7.3 4.9 7.7 4.8 8.1 4.7
37.5 6.2 4.5 6.4 4.7 6.8 4.6 7.2 4.8 7.6 4.7 8.0 4.7
40.0 6.2 4.5 6.4 4.6 6.7 4.6 7.1 4.8 7.5 4.7 7.9 4.6
43.0 6.1 4.5 6.3 4.6 6.6 4.5 7.0 4.7 7.3 4.7 7.7 4.5
20.0 10.3 7.4 10.8 7.7 11.6 7.7 12.5 8.1 13.2 8.0 14.0 7.9
22.5 10.3 7.4 10.8 7.7 11.5 7.7 12.3 8.1 13.0 7.9 13.8 7.8
25.0 10.2 7.4 10.7 7.6 11.4 7.6 12.1 8.0 12.8 7.9 13.6 7.7
27.5 10.1 7.3 10.6 7.6 11.3 7.6 12.0 7.9 12.7 7.8 13.4 7.7
100 30.0 10.1 7.3 10.5 7.5 11.2 7.5 11.8 7.9 12.5 7.7 13.2 7.6
32.5 10.0 7.3 10.3 7.5 11.0 7.4 11.7 7.8 12.3 7.7 13.0 7.5
35.0 9.9 7.2 10.2 7.4 10.9 7.4 11.5 7.7 12.1 7.6 12.8 7.4
37.5 9.8 7.2 10.1 7.4 10.8 7.3 11.4 7.7 12.0 7.5 12.6 7.4
40.0 9.7 7.1 10.0 7.3 10.6 7.3 11.2 7.6 11.8 7.5 12.4 7.3
43.0 9.6 7.1 9.9 7.3 10.5 7.2 11.0 7.5 11.6 7.4 12.2 7.2
20.0 12.9 9.4 13.5 9.7 14.6 9.7 15.6 10.3 16.5 10.1 17.5 9.9
22.5 12.9 9.4 13.5 9.7 14.4 9.7 15.4 10.2 16.3 10.0 17.2 9.9
25.0 12.8 9.3 13.3 9.6 14.3 9.6 15.2 10.1 16.1 9.9 17.0 9.8
27.5 12.7 9.3 13.2 9.6 14.1 9.5 15.0 10.0 15.8 9.8 16.7 9.7
125 30.0 12.6 9.2 13.1 9.5 13.9 9.5 14.8 9.9 15.6 9.8 16.5 9.6
32.5 12.5 9.2 12.9 9.4 13.8 9.4 14.6 9.8 15.4 9.7 16.2 9.5
35.0 12.4 9.1 12.8 9.4 13.6 9.3 14.4 9.8 15.2 9.6 16.0 9.4
37.5 12.3 9.0 12.7 9.3 13.5 9.2 14.2 9.7 15.0 9.5 15.7 9.3
40.0 12.2 9.0 12.5 9.3 13.3 9.2 14.0 9.6 14.8 9.4 15.5 9.2
43.0 12.0 8.9 12.4 9.2 13.1 9.1 13.8 9.5 14.5 9.3 15.2 9.1

2-6.Heating Capacity (In combination with Big Y, Super Y, Big R2)


PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB Outdoor Indoor air temp.:˚CDB
Unit air temp. 15 21 25 27 Unit air temp. 15 21 25 27
size size
˚CWB SHC SHC SHC SHC ˚CWB SHC SHC SHC SHC
-15.0 3.1 3.1 3.0 3.0 -15.0 7.8 7.7 7.5 7.4
-10.0 3.6 3.5 3.5 3.4 -10.0 8.9 8.8 8.6 8.5
-5.0 4.0 4.0 3.9 3.9 -5.0 10.0 9.9 9.8 9.6
0.0 4.5 4.4 4.3 3.9 0.0 11.2 11.0 10.6 9.6
2.5 4.7 4.7 4.3 3.9 2.5 11.8 11.6 10.6 9.6
40 100
6.0 5.0 5.0 4.3 3.9 6.0 12.6 12.5 10.6 9.6
7.5 5.2 5.0 4.3 3.9 7.5 13.0 12.5 10.6 9.6
10.0 5.4 5.0 4.3 3.9 10.0 13.6 12.5 10.6 9.6
12.5 5.7 5.0 4.3 3.9 12.5 14.3 12.5 10.6 9.6
15.5 5.8 5.0 4.3 3.9 15.5 14.4 12.5 10.6 9.6
-15.0 5.0 4.9 4.8 4.7 -15.0 10.0 9.8 9.6 9.5
-10.0 5.7 5.6 5.5 5.4 -10.0 11.4 11.2 11.0 10.9
-5.0 6.4 6.3 6.2 6.2 -5.0 12.8 12.6 12.5 12.3
0.0 7.2 7.1 6.8 6.2 0.0 14.3 14.1 13.6 12.3
2.5 7.5 7.5 6.8 6.2 2.5 15.1 14.9 13.6 12.3
63 125
6.0 8.1 8.0 6.8 6.2 6.0 16.2 16.0 13.6 12.3
7.5 8.3 8.0 6.8 6.2 7.5 16.6 16.0 13.6 12.3
10.0 8.7 8.0 6.8 6.2 10.0 17.4 16.0 13.6 12.3
12.5 9.1 8.0 6.8 6.2 12.5 18.3 16.0 13.6 12.3
15.5 9.2 8.0 6.8 6.2 15.5 18.4 16.0 13.6 12.3

2- 199
2-7.Cooling Capacity (In combination with WY, WR2)
CA :Capacity(kW)
PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Indoor air temp.
Outdoor
Unit air temp. 21.5˚CDB 23˚CDB 25˚CDB 27˚CDB 28˚CDB 30˚CDB 32˚CDB
size 15˚CWB 16˚CWB 18˚CWB 19˚CWB 20˚CWB 22˚CWB 24˚CWB
˚C CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
10 4.4 3.1 4.5 3.2 4.8 3.1 5.0 3.2 5.1 3.3 5.4 3.2 5.7 3.2
20 4.2 3.0 4.4 3.1 4.6 3.1 4.8 3.1 4.9 3.2 5.2 3.1 5.5 3.1
40 30 4.0 2.9 4.1 3.0 4.4 2.9 4.5 3.0 4.6 3.1 4.9 3.0 5.2 3.0
40 3.5 2.6 3.6 2.7 3.8 2.7 3.9 2.7 4.0 2.8 4.3 2.8 4.5 2.7
45 3.3 2.5 3.4 2.6 3.6 2.6 3.7 2.6 3.8 2.7 4.0 2.7 4.2 2.6
10 6.9 4.9 7.2 5.0 7.6 5.0 7.8 5.0 8.0 5.2 8.5 5.1 9.0 5.0
20 6.7 4.8 6.9 4.9 7.3 4.9 7.5 4.9 7.8 5.1 8.2 5.0 8.6 4.9
63 30 6.3 4.6 6.5 4.7 6.9 4.7 7.1 4.7 7.3 4.9 7.7 4.8 8.1 4.7
40 5.5 4.2 5.7 4.3 6.0 4.3 6.2 4.3 6.4 4.5 6.7 4.4 7.1 4.3
PCFY-P-VGM-A

45 5.2 4.0 5.3 4.1 5.7 4.1 5.8 4.2 6.0 4.3 6.3 4.3 6.7 4.2
10 10.9 7.8 11.3 8.0 12.0 7.9 12.3 8.0 12.7 8.2 13.4 8.1 14.1 7.9
20 10.5 7.5 10.9 7.8 11.6 7.7 11.9 7.8 12.2 8.0 12.9 7.9 13.6 7.8
100 30 9.9 7.2 10.3 7.5 10.9 7.4 11.2 7.5 11.5 7.7 12.2 7.6 12.8 7.5
40 8.6 6.6 8.9 6.8 9.5 6.7 9.7 6.8 10.0 7.1 10.6 7.0 11.2 6.9
45 8.1 6.4 8.4 6.6 8.9 6.5 9.2 6.6 9.5 6.9 10.0 6.8 10.5 6.6
10 13.7 9.8 14.1 10.0 15.0 9.9 15.4 10.0 15.9 10.4 16.7 10.2 17.7 10.0
20 13.2 9.5 13.6 9.8 14.5 9.7 14.8 9.8 15.3 10.1 16.1 10.0 17.0 9.8
125 30 12.4 9.1 12.8 9.4 13.6 9.3 14.0 9.4 14.4 9.8 15.2 9.6 16.1 9.4
40 10.8 8.3 11.2 8.6 11.9 8.5 12.2 8.6 12.5 9.0 13.2 8.8 14.0 8.7
45 10.2 8.0 10.5 8.3 11.2 8.2 11.5 8.4 11.8 8.7 12.5 8.5 13.2 8.4

2-8.Heating Capacity (In combination with WY, WR2)


PCFY-P-VGM-A SHC:Sensible Heat Capacity(kW)
Outdoor Indoor air temp.:˚CDB
Unit air temp. 15 19 20 25 27
size
˚C SHC SHC SHC SHC SHC
10 4.4 4.3 4.3 3.4 3.1
20 5.2 5.1 5.0 4.0 3.6
40 30 5.2 5.1 5.0 4.0 3.6
40 5.4 5.3 5.2 4.2 3.7
45 5.9 5.8 5.7 4.6 4.1
10 7.0 6.9 6.8 5.4 4.9
20 8.2 8.2 8.0 6.4 5.8
63 30 8.2 8.2 8.0 6.4 5.8
40 8.6 8.5 8.3 6.7 6.0
45 9.4 9.3 9.1 7.3 6.6
10 10.9 10.8 10.6 8.5 7.7
20 12.9 12.8 12.5 10.0 9.0
100 30 12.9 12.8 12.5 10.0 9.0
40 13.4 13.3 13.0 10.4 9.4
45 14.7 14.5 14.3 11.4 10.3
10 14.0 13.9 13.6 10.9 9.8
20 16.5 16.3 16.0 12.8 11.5
125 30 16.5 16.3 16.0 12.8 11.5
40 17.1 17.0 16.6 13.3 12.0
45 18.8 18.6 18.2 14.6 13.1

2- 200
3. Sound Levels
3-1. Noise level

Ceiling suspended
Noise level at anechoic room
(Low-Middle2-Middle1-High) Unit : dB(A)

Model Noise level (A weighted)

PCFY-P40VGM-A 29-33-36-38
PCFY-P63VGM-A 32-34-37-39
1.0m

PCFY-P100VGM-A 36-38-41-43

PCFY-P-VGM-A
PCFY-P125VGM-A 37-39-42-44
Measurement location 1.0m

3-2. NC curves

PCFY-P40VGM-A PCFY-P63VGM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa


Low speed Low speed
60 60
NC60 NC60

50 50
NC50 NC50

40 40
20µPa

NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

PCFY-P100VGM-A PCFY-P125VGM-A
70 70
High speed High speed
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa

Low speed Low speed


60 60
NC60 NC60

50 50
NC50 NC50

40 40
NC40 NC40

30 30
NC30 NC30

20 20
NC20 NC20

10 10
Approximate minimum Approximate minimum
audible limit on audible limit on
continuous noise continuous noise
0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND CENTER FREQUENCIES (Hz)

2- 201
PCFY-P-VGM-A

80

150 18
140 70

320
PCFY-P40,63,100,125VGM-A

E
4. External Dimension

(Suspension bolt pitch)


87
70 D 16
Electrical box

H
F
G
Model Liquid Gas

81 96
40 ø6.35 ø12.7
229 Air outlet B 182 63 ø9.52 ø15.88
High press.

2- 202
A I Low press. 100,125 ø9.52 ø19.05
J (Drainage)

56
680
506
254

161 90
Air intake C

Model A B C D E F G H I J
PCFY -P40VGM-A 1,000 904 918 983 933 210 180 157 201 241
PCFY -P63VGM-A 1,310 1,214 1,228 1,290 1,240 210 180 157 201 241
Unit : mm

PCFY -P100VGM-A 1,310 1,214 1,228 1,290 1,240 270 207 217 198 245
PCFY -P125VGM-A 1,620 1,524 1,535 1,600 1,547 270 207 217 198 245
5. Electrical Wiring Diagram
<SYMBOL EXPLANATION>
Symbol Name Symbol Name Symbol Name
I.B Indoor controller board C1 Capacitor(fan motor) A.B Circuit board Address
CN32 Remote switch LEV Linear expansion valve SW1 Mode selection
CN51 Centrally control MF Fan motor(with inner thermo) SW5 Voltage selection
Connector
CN52 Remote indication MV Vane motor SW11 Switch Address setting 1st digit
CNP Drain-up machine Room temp. detection SW12 Address setting 2nd digit
TH21
F.C Fan phase control (0˚C/15kΩ,25˚C/5.4kΩ) SW14 Connection No.
FUSE Fuse (6.3A) Pipe temp. detection / Liquid SWA Ceiling heigh selector
TH22 Thermistor
SW2 Capacity code (0˚C/15kΩ,25˚C/5.4kΩ) SWC Option selector
SW3 Switch Mode selection Pipe temp. detection / Gas
TH23 Led on indoor board for sevice
SW4 Model selection (0˚C/15kΩ,25˚C/5.4kΩ)
Mark Meaning Function

PCFY-P-VGM-A
X1 Drain-up machine TB2 Power supply
Aux.Relay Terminal Main power supply (indoor unit:220-240V)
X4 Fan motor TB5 block Transmission LED1 Main power supply power on lamp is lit
ZNR Varistor TB15 MA-remote controller Power supply for Power supply for MA-Remote controller
DP Drain-up machine (OPTION) LED2 MA-Remote controller on lamp is lit
P.B Indoor power board TO NEXT INDOOR UNIT
DS Drain sensor (OPTION)
TB2
❇1
TO NEXT INDOOR UNIT
Models SW2 SW3
TB2 ON ON
RED L PCFY-P40VGM OFF OFF
BLU N 123456 1 2 3 4 5 6 7 8 9 10
PULL BOX
GRN/YLW ON
PCFY-P63VGM OFF
123456
P.B AC220~240V DC13.1V ON ON
PCFY-P100VGM OFF OFF
MF (OPTION) (RED) TRANS (WHT) FUSE(15A)
123456 1 2 3 4 5 6 7 8 9 10
CNSK CN2S
1 3 5 ON
3 2
WHT

DP PCFY-P125VGM OFF
RED

BLK

2 1 BREAKER 123456
C1 1 (15A)
RED

WHT
BLU

BLK

I.B
~/N 220-240V 50Hz
FAN 1 3 5 CND 1 3 CNP 1 3 1 3 CNDK ~/N 220V 60Hz
CN2D BLK A.B
(WHT) (RED) (BLU) (RED) 1
FUSE LED1 (WHT) WHT
X4 250V 2 SW5 SWA (RED) 4
6.3A (WHT) (WHT) ADDRESS 3
220V 240V
HA DRAIN 3 CN43 2
BLU TB5 S(SHIELD)
CN41 CN31 CN2M { SW1 2
ZNR X1 1 TO OUTDOOR UNIT 1 1 8
F.C 1 4 3 2 1 (BLU) BLU M2 ON
(RED) 7
M-NET 2 BC CONTROLLER OFF ADDRESS
(GRN) (WHT) (WHT) M1 REMOTE CONTROLLER
REMOTE CENTRALLY (WHT) REMOTO
1 2 3 4 5 6 7 8 910 CN82 6
X4 X1 INDICATION CONTROL LEV SWITCH 1
ORN
TB15
DC24-30V
SW12 SW11 SWC
SW14 5

5
CN52 CN51
1 5 1 6 5 4 3 2 1
CN60
1
CN32
3
CN3A
(BLU) 2
ORN
1
2
{TO MA-REMOTE
CONTROLLER 0
0 0 0 4
3
3 DC8.7-13V
(GRN) (RED) (RED) 3RD 2ND 1ST CONNECTION 2
VANE ADDRESS ADDRESS SW2 SW3 SW4 (RED) (WHT) (BLK) DIGIT DIGIT DIGIT NO. 1
CN6V CN81 CN42 0N 0N INTAKE LIQUID GAS MODELS
0FF
CN20 CN21 CN29
6 5 4 3 2 1 8 7 6 5 4 3 2 1 4 3 2 1 0FF LED2 PCFY-P100,P125VGM
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 12345 2 1 2 1 2 1
(GRN)
6 VANE
CN6V
6
2 1 2 1
6 5 4 3 2 1 (WHT)
8 4 See fig: ❇1 6 5 4 3 2 1 DRAIN
CN31
WHT
ORN
YLW
RED
BRN

BLU

6 5 4 3 2 1 6 3 2 1
WHT
ORN
YLW
BRN
RED

BLU

WHT
ORN
YLW
BRN
RED

BLU

I.B

TH21 TH22 TH23 6 5 4 3 2 1


MV LEV DS
MV
DS(OPTION)

Note
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5.(Transmission line is non-polar.)
4.Symbol[S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
:Terminal block, :Connector.
6. The setting of the SW2 dip switches differs in the capacity. For the detail,refer to the fig: ❇1.
7. Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts,set SW5 to 220V side.
8. Fasten terminal of the terminal board "TB5" equips lock system.
To remove the fasten terminal,pull it while pressing the protrudingn portion (locking lever)of the terminal.
Connection of the fasten terminal,protruding portion shouid face upward.

2- 203
6. Temperature/Airflow distribution
● Temperature distribution
<Cooling mode> <Heating mode>
Flow angle : 0˚ Flow angle : 60˚
3 3
20 22 24

2 2
Height (m)

Height (m)
24 33
27 24

24
1 1
21 21
30

27
0 0
PCFY-P-VGM-A

0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Floor distance (m) Floor distance (m)

● Airflow distribution
<Fan mode> <Fan mode>
Flow angle : 0˚ Flow angle : 60˚
3 3
4.0
3.0 2.0 0.5

4.0
3.0
2 2
Height (m)

Height (m)

1.0

0.5
1 2.0
0.5 1
1.0

0 0
0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8
Floor distance (m) Floor distance (m)

2- 204
OA Processing unit GUF-RD2
GUF-RDH2
CONTENTS

1. Specifications ··································································· 2-206


2. Sound Levels ··································································· 2-207

OA Processing unit
2-1 NC-curves ······································································ 2-207
2-2 Fan characteristics curves ············································· 2-208

3. External Dimension ······················································ 2-209

4. Wiring Diagrams ····························································· 2-210

2- 205
1. Specifications

Item Model GUF-50RDH2 GUF-100RDH2 GUF-50RD2 GUF-100RD2


Power supply Single phase 220-240V ~50Hz
Current A 1.15 2.20 1.15 2.20
Input W 235-265 480-505 235-265 480-505
Cooling capacity kW 5.29<1.66> 10.81<3.49> 5.29<1.66> 10.81<3.49>
Heating capacity kW 6.42<2.25> 13.00<4.70> 6.42<2.25> 13.00<4.70>
SA : Centrifugal fan [Sirocco fan] ✕1
Type ✕ No.
EA : Centrifugal fan [Sirocco fan] ✕1
m3/h 500 1000 500 1000
Fan Air volume
L/S 139 278 139 278
External static 125 135 140
pressure Pa 140
Noise level (Low-High) ❇ dB(A) 33.5-34.5 38-39 33.5-34.5 38-39
Humidifying capacity kg/h 2.7 5.4 - -
Cladding Galvanized steel plate
Height mm 317 398 317 398
Dimensions Width mm 1016 1231 1016 1231
Depth mm 1288 1580 1288 1580
Weight (drying) kg 57 98 54 93
OA Processing unit

Motor - Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units
Air filter Non-woven fabrics filter : Gravitational method 82%
Supply air
+High efficiency filter : Colorimetric method 65% (optional parts)
Exhaust air Non-woven fabrics filter : Gravitational method 82%
Total heat exchanger
Partition, spacing plate-special treated paper
(Lossnay element)
Direct expansion heat
Aluminum plate fins and copper tubes
exchanger coil
Humidifying Permeable film humidifier –
Refrigerant Gas ø mm 12.7 15.88 12.7 15.88
pipe dimension Liquid ø mm 6.35 9.52 6.35 9.52
Drain pipe dimension VP25
Capacity equivalent
P32 P63 P32 P63
to the indoor unit
Note: 1 The figures in < > indicates the heat recovery at Lossnay element.
2 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor : 27˚C DB/19.5˚C WB Outdoor : 35˚C DB/24˚C WB
Heating : Indoor : 21˚C DB/14.6˚C WB Outdoor : 7˚C DB/6˚C WB
3 The values given in the table for the noise level reflect the levels measured at a position 1.5 meters
immediately below the unit in anechoic chamber.
4 The noise at the air outlets (at a 45˚ angel, 1.5 meters in front) is about 5-6 dB(A) higher than the values
given in the table.
5 The above values apply during Lossnay ventilation when the fan speed is set to high speed.
6 Specification may be subject to change without notice.
❇ It is measured in anechoic room.

2- 206
2. Sound Levels
2-1. NC curves
GUF-50RDH2/50RD2
Directly below (Measurement point A) Outlet (Measurement point B)

90 90
85 85
80 80
75 75
Octave band sound level (dB)

Octave band sound level (dB)


70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 20

OA Processing unit
15 NC-20 15 NC-20
NC-10 NC-10
10 10
Overall 62.5 125 250 500 1K 2K 4K 8K Overall 62.5 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)

GUF-100RDH2/100RD2
Directly below (Measurement point A) Outlet (Measurement point B)

90 90
85 85
80 80
75 75
70
Octave band sound level (dB)

Octave band sound level (dB)

70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
45 NC-50 45 NC-50
40 40
35 NC-40 NC-40
35
30 30
25 NC-30 NC-30
25
20 20
15 NC-20 15 NC-20
NC-10 NC-10
10 10
Overall 62.5 125 250 500 1K 2K 4K 8K Overall 62.5 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)

● Measurement Condition

Measurement site:
Mitsubishi Electric Co., Supply/ To indoor unit
Nakatsugawa Works Exhaust air
Anechoic chamber Main unit
<Ceiling recessed type>
1.5 m
1.5 m

A B

2- 207
2-2. Fan characteristics curves
Humidifying Type
GUF-50RDH2 GUF-100RDH2

90
Exchange efficiency (%)

Tem
efficieperature 200mm 90
Tem
80 ncy excha dia
Enth nge efficieperature

Exchange efficiency(%)
pipe excha
efficiealpy excha length 80 Enth
ncy
nge
70 n cy(Hea e ng
En ting) efficiealpy excha
efficthalpy e 100m ncy(H nge
60 400 ienc xch En eating
y(Co ange )
efficthalpy e
40 50 70 500
oling
) ienc xch
y(Co ange 250mm

External static pressure(mmH2O)


50
oling
External static pressure(mmH2O)

80m ) dia
40 60 400 pipe
30 300
length
External static pressure

High 60m 30 50 300 100m


High
High
80m

External static pressure


20 200
(Pa)

40m
20 200 Low
Low 60m

40m

(Pa)
Low 10 100
10 100
20m
OA Processing unit

20m

0
0 200 400 600 800 1000 1200 1400
0 (m3/h)
0 200 400 600 800
(m3/h) 0 50 100 150 200 250 300 350 400
Air volume (L/s)
0 20 40 60 80 100 120 140 160 180 200 220
Air volume (L/s)

Non-Humidifying Type
GUF-50RD2 GUF-100RD2

90
Exchange efficiency (%)

Tem 200mm
80
efficieperature e dia
90
ncy xchan Tem
Enth ge efficieperature
Exchange efficiency (%)

pipe
efficiealpy exch length ncy excha
70 En n c a
y(Hea gen 80 Enth nge
efficthalpy e ting)
100m efficiealpy exch
ienc xch ncy(H ange
40 60 400 y(Co ange En eatin
oling g)
) 50 70 500 efficthalpy e
50 ienc xch
y(Co ange 250mm
External static pressure(mmH2O)
External static pressure(mmH2O)

80m oling dia


40 60 400 )
30 300 pipe
length
External static pressure

High 60m 100m


30 50 300
High
200 80m
External static pressure

20
(Pa)

40m 20 200 Low 60m

40m
(Pa)

10 100 Low 10 100


20m
20m

0
0 200 400 600 800 1000 1200 1400
0 (m3/h)
0 200 400 600 800
(m3/h)
0 50 100 150 200 250 300 350 400
0 20 40 60 80 100 120 140 160 180 200 220 Air volume (L/s)
Air volume (L/s)

2- 208
3. External Dimension
GUF-50, 100RD(H)2 Unit : mm

Humidifying Type GUF-50/100RDH2 Position where duct direction cange is possible

C Damper plate

P
Air exhaust fan Ceiling suspension fixture

EA RA
(Exhaust air) (Return air)

Air supply fan

J
K
A

E
SA
(Supply air)
OA

100
Solenoid valve unit
(Outdoor air) with pressure requlator

600 or more

20
Maintenance space for

F
G
Heat recovery unit 150-250 L
Inspection Inspection Maintenance space for
(Lossnay Core)
Air filters, Blower opening opening Heat exchanger M
High-efficiency filter Permeable-film humidifier

Maintenance cover H
Control box Power supply opening

Heat recovery unit High efficiency filter


Direct Expansion coil

OA Processing unit
(Lossnay Core) (Optional parts)
79 N 79
Permeable-film humidifier
Ceiling suspension P 79 Q
fixture 60
Maintenance cover(humidifier)

øR
øS
Gas pipe (Flare ¿ T)
Y
W
30

V
Air filters Liquid pipe (Flare ¿ U)
Model A B C D E F G H J K L
Position where duct Water intake Drain discharge hole
GUF-50RDH2 745 1,016 124 1,185 1,048 22 124 450 372.5 435 158.5 direction change is possible Strainer(R1/2 of External thread) (VP25 connection)
GUF-100RDH2 920 1,231 149 1,465 1,271 16 149 600 460 670 199
Model M N P Q R S T U V W Y
GUF-50RDH2 317 1,288 124 266 192 208 12.7 6.35 347 99 135
GUF-100RDH2 398 1,580 149 280 242 258 15.88 9.52 361 110 169

Non-Humidifying Type GUF-50/100RD2

Position where duct direction change is possible

C Damper plate

D
Air exhaust fan Ceiling suspension fixture

EA RA
(Exhaust air) (Return air)

Air supply fan


J
K
A

SA
(Supply air)
OA
100

(Outdoor air)
600 or more

Maintenance spase for


20
F

Heat recovery unit G L


150-250

(Lossnay Core) Inspection Inspection Maintenance space for


Air filters, Blower opening opening Heat exchanger M
High-efficiency filter

Maintenance cover H
Control box Power supply opening

Heat recovery unit High-efficiency filter


(Lossnay Core) (Optional parts) Direct Expansion coil
79 N 79
Ceiling suspension
P Q
60

fixture Maintenance cover(humidifier)


øR
øS
W

30

V Gas pipe (Flare ¿ T)

Air filters Liquid pipe (Flare ¿ U)

Model A B C D E F G H J K L Position where duct direction Drain discharge hole


change is possible (VP25 connection)
GUF-50RD2 745 1,016 124 1,185 1,048 22 124 450 372.5 435 158.5
GUF-100RD2 920 1,231 149 1,465 1,271 16 149 600 460 670 199
Model M N P Q R S T U V W
GUF-50RD2 317 1,288 124 266 192 208 12.7 6.35 347 135
GUF-100RD2 398 1,580 149 280 242 258 15.88 9.52 361 169

2- 209
4. Wiring Diagrams
Humidifying Type GUF-50/100RDH2

● TM1, TM2 shown in dotted lines are field work.


● Be sure to connect the grounding wire.
● Breakers and controller switches should be provided by the customer.

GREEN/YELLOW
BROWN
RED BROWN BLUE POWER SUPPLY
WHITE FAN2 CND1 TM1 220-240V ~50Hz
CND2
GREEN/YELLOW
M2 ORANGE TR
PINK PURPLE
5 SW4 L L
BLACK PURPLE YELLOW X06
SUPPLY FAN C YELLOW
GREEN/YELLOW
PINK
BLACK X07
N N
FAN4 1

BROWN
BROWN
C FAN1 BREAKER(16A)

BLUE
PINK PINK

RED
BLACK
RED
RED GREEN
/YELLOW PE
5 SW5
M1 WHITE WHITE X04
BLUE WHITE 1 3
ORANGE ORANGE X05 CNT CN3T
FAN3 1
FUSE1 TM3
EXHAUST FAN
OA Processing unit

PURPLE
RED 7 ZNR9D2 DSA1 ZNR901
SV2 PURPLE 12 Humidistat
RED + − X03
Uncharged a-contact
SV1 RED CN70
RED
RSV(1k )
DB901 11 240VAC more than 10mA
1
RED 6 Operation monitor output
10 MAX MIN
GM CNL X02 X08
AC240V 1A AC220V 100mA
YELLOW
1 9 DC 24V 1A DC 5V 100mA
ORANGE
Malfunction monitor output
ORANGE CN27 BROWN
8 MAX MIN
X09
LS RED CN32 AC240V 1A AC220V 100mA
YELLOW
PURPLE
7 DC 24V 1A DC 5V 100mA

YELLOW CN4D LEV ORANGE CN51 Remote Controller


PINK
TM2
<PAR-20MAA>
W.S GREY WHITE CN52
TH1(OA) GREY CN20 LED3
CN60
1
WHITE 2
TH4(RA) WHITE CN22 LED2 M-NET transmission cable
YELLOW
SW2 A To Outdoor Unit , BC Controller

TH3 Gas
Fresh Master
pipe CN29 LED1 SW14
YELLOW
B M-NET Remote controller
SW3 SW1 < PAR-F27MEA>
PINK
SW12 SW11
TH2 Liquid
pipe PINK CN21 S Shield wire

MARK : indicates terminal block, : connector


: board insertion connector or fastening connector of control board.

Symbol Explanation
Symbol Name Symbol Name Symbol Name
M1 Fan motor (exhaust) TM1 Terminal block (power supply) 1, 2 Remote control terminal
M2 Fan motor (supply) TM2 Terminal block (transmission) A, B M-NET transmission terminal
C Capacitor TM3 Terminal block (humidistat, monitor) S Shield
W.S Water sensor SW1 Switch (function selection) CND1, CND2 Connector (power supply)
SV1 Solenoid valve (pressure regulator) SW2 Switch (capacity code setting) X02-X09 Relay
SV2 Solenoid valve (exhaust) SW3 Switch (function selection) TR Transformer
TH1 Thermistor (outdoor air temp. detection) SW4,SW5 Switch GM Damper motor
TH2 Thermistor (pipe temp. detection/liquid) SW11 Switch (1st digit address set) LS Limit switch
TH3 Thermistor (pipe temp. detection/gas) SW12 Switch (2nd digit address set) LED1 Power supply monitor
TH4 Thermistor (room air temp. detection) SW14 Switch (branch NO. set) LED2 MA Remote contolle
LEV Electronic linear expansion valve CN32 Connecter (Remote input) Power supply monitor
RSV Resistance (solenoid valve) CN51,CN52 Connecter (Remote input/output) LED3 M-NET Power supply monitor

2- 210
Non-Humidifying Type GUF-50/100RD2

● TM1, TM2 shown in dotted lines are field work.


● Be sure to connect the grounding wire.
● Breakers and controller switches should be provided by the customer.

GREEN/YELLOW
BROWN
RED BROWN BLUE POWER SUPPLY
WHITE FAN2 CND1 TM1 220-240V ~50Hz
CND2
GREEN/YELLOW
M2 ORANGE TR
PINK PURPLE 5 SW4 L L
BLACK PURPLE YELLOW X06
SUPPLY FAN C YELLOW
GREEN/YELLOW
PINK
BLACK X07
N N
FAN4 1

BROWN
BROWN
C BREAKER(16A)

BLUE
PINK PINK FAN1

RED
BLAK
RED
RED GREEN
/YELLOW PE
5 SW5
M1 WHITE WHITE X04
BLUE WHITE 1 3
ORANGE ORANGE X05 CNT CN3T
FAN3 1
FUSE1 TM3
EXHAUST FAN

OA Processing unit
ZNR9D2 DSA1 ZNR901
7
12
+ − X03
CN70
DB901 11
1
RED 6 Operation monitor output
10 MAX MIN
GM CNL X02
X08
AC240V 1A AC220V 100mA
YELLOW
1 9 DC 24V 1A DC 5V 100mA
ORANGE
Malfunction monitor output
ORANGE CN27 BROWN
8 MAX MIN
X09
LS RED CN32 AC240V 1A AC220V 100mA
YELLOW
PURPLE
7 DC 24V 1A DC 5V 100mA

YELLOW CN4D LEV ORANGE CN51 Remote Controller


PINK
TM2
<PAR-20MAA>
W.S GREY WHITE CN52
TH1(OA) GREY CN20 LED3
CN60
1
WHITE 2
TH4(RA) WHITE CN22 LED2 M-NET transmission cable
YELLOW
SW2 A To Outdoor Unit , BC Controller

TH3 Gas
Fresh Master
pipe CN29 LED1 SW14
YELLOW
B M-NET Remote controller
SW3 SW1 < PAR-F27MEA>
PINK
SW12 SW11
TH2 Liquid
pipe PINK CN21 S Shield wire

MARK : indicates terminal block, : connector


: board insertion connector or fastening connector of control board.

Symbol Explanation
Symbol Name Symbol Name Symbol Name
M1 Fan motor (exhaust) TM1 Terminal block (power supply) 1, 2 Remote control terminal
M2 Fan motor (supply) TM2 Terminal block (transmission) A, B M-NET transmission terminal
C Capacitor TM3 Terminal block (humidistat, monitor) S Shield
W.S Water sensor SW1 Switch (function selection) CND1, CND2 Connector (power supply)
TH1 Thermistor (outdoor air temp. detection) SW2 Switch (capacity code setting) X02-X09 Relay
TH2 Thermistor (pipe temp. detection/liquid) SW3 Switch (function selection) TR Transformer
TH3 Thermistor (pipe temp. detection/gas) SW4,SW5 Switch GM Damper motor
TH4 Thermistor (room air temp. detection) SW11 Switch (1st digit address set) LS Limit switch
LEV Electronic linear expansion valve SW12 Switch (2nd digit address set) LED1 Power supply monitor
SW14 Switch (branch NO. set) LED2 MA Remote contoller
CN32 Connecter (Remote input) Power supply monitor
CN51,CN52 Connecter (Remote input/output) LED3 M-NET Power supply monitor

2- 211
OA Processing unit

2- 212
LOSSNAY unit LGH-RX3-E

CONTENTS

1. Dimensions ···································································· 2-214


2. Performance ···································································· 2-215
3. Specifications ·································································· 2-216
4. Sample Installations ······················································ 2-217
5. Electrical Installations ··················································· 2-219

LOSSNAY
6. Wiring Diagrams ···························································· 2-220

2- 213
1. Dimensions

LGH-15RX3-E to LGH-100RX3-E LGH-150RX3-E and LGH-200RX3-E

Position where duct direction change is possible


M Damper plate Air exhaust fan Damper plate Air supply fan
Air exhaust fan D Ceiling suspension fixture
(4-13×30 oval) 1030

EA
L

(exhaust RA EA RA

ø350
air outlet) (return air) (exhaust (return
air outlet) air

C
D
A

B
B
K

OA SA
(outside (supply
air intake) air)
OA
(outside SA
90

100
More than 600
150~250
(supply air)

26
air intake) Lossnay 800
Maintenance cover
More than 600

Power cord F Core, air filter,


22

opening fan, mainte- Inspection Ceiling suspension


M C
150~250

Lossnay Core, air nance space opening fixture(4-15 x 30 oval)


Inspection Air supply fan
filter, High-efficien- 1662
cy filter, fan, main- opening Control box
130 249 1164 249 130
Maintenance cover
LOSSNAY

tenance space
High-efficiency filter Lossnay Cores
Lossnay Core (sold separately) attachment position
J A J

ø350
705
Ceiling suspension
fixture (models Maintenance
øG
øH

LGH-15 and 25RX3-E) covers

Control box
Ceiling suspension fixture Air filters Air filters
(models LGH-35 to 100RX3-E)

Accessory parts Accessory parts


• Mounting screws...................................................... ×18 • Duct connecting flanges...........................................×4
• Duct connecting flanges .......................................... ×4 • Mounting screws...................................................... ×34
(double flanges at SA and EA sides) • Washers................................................................... ×32
• Protective cover........................................................×1 • Protective cover....................................................... ×1
<for installing upside down> <for installing upside down>
• Slim-Lossnay connection cable (gray: two wires).... ×1 • Slim-Lossnay connection cable (gray: two wires).... ×1

LGH-15RX3-E to LGH-100RX3-E Unit (mm)


Ceiling suspension
Dimensions Nominal Duct connecting flange Duct pitch Weight
Model fixture pitch
diameter (kg)
A B C D E F G H J K L M
LGH-15RX3-E 780 610 275 700 641 10 ✻
ø100 97.5 110 54 450 80 119 17
LGH-25RX3-E 780 735 275 700 765 10 ✻
ø150 142 160 63 530 102.5 102 21
LGH-35RX3-E 888 874 317 790 906 40 ø150 142 160 63 650 112 124 30
LGH-50RX3-E 888 1,016 317 790 1,048 40 ø200 192 208 79 745 135.5 124 33
LGH-80RX3-E 1,164 1,004 398 1,030 1,036 10 ø250 242 258 79 690 157 149 61
LGH-100RX3-E 1,164 1,231 398 1,030 1,263 10 ø250 242 258 79 920 155.5 149 72

Shows the distance from the ceiling.

Unit (mm)
Weight
Model A B C D
(kg)
LGH-150RX3-E 1,004 510 964 1,046 154
LGH-200RX3-E 1,231 740 1,194 1,273 179

2- 214
2. Performance
LGH-15RX3-E LGH-80RX3-E
50 Hz 50 Hz
60 Hz 60 Hz
Recovery efficiency (%)

90 90
Tem Tem
Enth p Enth pera
efficie erature efficie ture

Recovery efficiency (%)


alpy ncy reco alpy ncy re
80 reco very 100 mm reco cove
very 80 very ry
effic dia effic
ienc pipe ienc
70 30 300 y (H Ent y (H
Enth eati
ng) length 70 50 500 effic halpy eati
ng)
effic alpy re ien reco
cy (
60 25 250 ienc c
y (C overy
20 m Coo very
ooli ling
ng) 60 40 400 ) 250 mm
Extra high dia
50 20 200 15 m Extra high pipe
External static pressure

50 30 300 length
150 High
15

External static pressure


10 m High 100 m
(mmH2O)

20 200
100 80 m
(Pa)

10

(Pa)
(mmH2O)
Low 60 m
Low 5m
5 50 10 100 40 m
20 m
0 0 0 0
50 100 150 200 250 200 400 600 800 1000 1200
(m3/h) (m3/h)
0 10 20 30 40 50 60 70 0 50 100 150 200 250 300 350
Air volume (L/s) Air volume (L/s)

LGH-25RX3-E LGH-100RX3-E
50 Hz 50 Hz
60 Hz
Recovery efficiency (%)

90 60 Hz
Tem pe 90
Enth ra Tem pe
alpy efficien ture recove Ent ra

Recovery efficiency (%)


reco cy ry halp efficien ture recove
80 very y re cy ry
effic 80 cov
ienc ery
y (H effic
70 eatin En ien
Enth g) t h
effic alpy cy (
effic alpy re 70 50 500 ien rec Hea
ting
ienc cy
60 c
y (C overy (C over
ooli y
) 250 mm
ooli 150 mm ng) dia
ng)
dia 60 40 400 pipe
50 25 250 Extra high pipe Extra high length
length
200
External static pressure

20 50 30 300 High 100 m


40 m
External static pressure

15 150 80 m
(mmH2O)

30 m 20 200
60 m
(Pa)

(Pa)
(mmH2O)

10 100 Low
20 m

LOSSNAY
High 40 m
10 100
5 50 Low 10 m 20 m
0 0 0 0
50 100 150 200 250 300 350 400 200 400 600 800 1000 1200 1400
(m3/h) (m3/h)
0 10 20 30 40 50 60 70 80 90 100 0 50 100 150 200 250 300 350 400
Air volume (L/s) Air volume (L/s)

LGH-35RX3-E LGH-150RX3-E
50 Hz 50 Hz
60 Hz 60 Hz
90
Recovery efficiency (%)

90 T em p Tempe
Enth erature Ent ra ture re
alpy e halp e
reco fficiency recove ff ic
Recovery efficiency (%)

ry y re iency c overy
80 very cov
effic 80 ery
Enth ienc effic
y (H ienc
70 35 350 effic alpy re eati
ng) En y (He
ie c o 150 mm atin
ncy
(Co very dia
70 50 500 effic thalpy g)
60 30 300 olin ien rec
g) cy o
pipe (Co very
length olin
60 40 400 g)
50 25 250 Extra high
30 m 350 mm
Extra high
20 200 50 30 dia
External static pressure

300
pipe
External static pressure

15 150 20 m High length


(mmH2O)

20 200
(Pa)

(Pa)

100 100 m
10
(mmH2O)

High Low 80 m
10 m
Low 10 100 60 m
5 50 40 m
20 m
0 0 0 0
50 100 150 200 250 300 350 400 450 500 500 1000 1500 2000 2500
(m3/h) (m3/h)
0 20 40 60 80 100 120 140 0 100 200 300 400 500 600 700
Air volume (L/s) Air volume (L/s)

LGH-50RX3-E LGH-200RX3-E
50 Hz 50 Hz
60 Hz 60 Hz
Recovery efficiency (%)

90 Tempe 90 Enth Temp


Enth ra e
alpy efficienc ture recove alp
y re efficie rature reco
Recovery efficiency (%)

reco y ry cov ncy very


80 40 400 E nt very ery
halp effic 80 effic
y re ienc ien
y (H En cy (He
70 35 350 cov eati
ery
effic ng) effic thalpy atin
g)
ienc 70 50 500 ie ncy reco
60 30 300 y (C 200 mm (Co very
ooli dia olin
ng) g)
50 25 250 pipe 60 40 400
Extra high length Extra high 350 mm
dia
20 200
External static pressure

60 m 50 30 300 pipe
50 m High length
External static pressure

15 150
(mmH2O)

40 m 20 200 100 m
(Pa)

(Pa)

10 100 80 m
(mmH2O)

Low High 30 m Low


20 m 10 100 60 m
5 50 40 m
10 m 20 m
0 0 0 0
100 200 300 400 500 600 700 500 1000 1500 2000 2500
(m3/h) (m3/h)
0 20 40 60 80 100 120 140 160 180 200 0 100 200 300 400 500 600 700
Air volume (L/s) Air volume (L/s)

2- 215
3. Specifications
LGH-15RX3-E
Model LGH-15RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 0.48-0.52/0.57 0.34-0.35/0.39 0.24-0.25/0.27 0.48-0.52/0.58 0.34-0.36/0.40 0.24-0.25/0.27
Input (W) 104-122/119 74-83/85 52-59/58 104-123/120 74-85/85 52-59/58
(m3/h) 150/150 150/150 120/110 150/150 150/150 120/110
Air volume
(L/s) 42/42 42/42 33/31 42/42 42/42 33/31
(mmH2O) 9.2/12.2 4.1/6.1 2.6/3.6 9.2/12.2 4.1/6.1 2.6/3.6
External static pressure
(Pa) 90/120 40/60 25/35 90/120 40/60 25/35
Temperature recovery efficiency (%) 77/77 77/77 80/81
Enthalpy recovery Heating 69/69 69/69 72/73
efficiency (%) Cooling 62.5/62.5 62.5/62.5 66/67
(Measured at 1.5m under
Noise (dB) 26-27/28 24-25/25 21-22/22 26-27/28 24-25/25.5 21-22/22
the center of the unit)
Weight (kg) 17
Starting current Under 0.8/0.7A or less

LGH-25RX3-E
Model LGH-25RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 0.51-0.54/0.63 0.42-0.44/0.49 0.25-0.27/0.28 0.52-0.55/0.63 0.42-0.45/0.50 0.25-0.27/0.27
Input (W) 111-128/131 91-104/106 54-64/60 112-130/132 91-105/107 54-64/58
(m3/h) 250/250 250/250 165/150 250/250 250/250 165/150
Air volume
(L/s) 69/69 69/69 46/42 69/69 69/69 46/42
(mmH2O) 6.6/10.2 4.1/5.1 2.0/2.0 6.6/10.2 4.1/5.1 2.0/2.0
External static pressure
(Pa) 65/100 40/50 20/20 65/100 40/50 20/20
Temperature recovery efficiency (%) 78/78 78/78 83/84
LOSSNAY

Enthalpy recovery Heating 69/69 69/69 74/75


efficiency (%) Cooling 62.5/62.5 62.5/62.5 68/70
(Measured at 1.5m under
Noise (dB) 26.5-27.5/28.5 25-26/25.5 21-22/21 27-28/29 25.5-26.5/26 21-22/21
the center of the unit)
Weight (kg) 21
Starting current Under 0.8/0.7A or less

LGH-35RX3-E
Model LGH-35RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 0.78-0.79/0.99 0.71-0.71/0.83 0.46-0.48/0.46 0.81-0.82/1.00 0.72-0.73/0.83 0.46-0.49/0.46
Input (W) 169-187/215 154-167/180 97-110/97 176-192/217 156-172/180 97-111/97
(m3/h) 350/350 350/350 230/210 350/350 350/320 230/210
Air volume
(L/s) 97/97 97/97 64/58 97/97 97/89 64/58
(mmH2O) 15.3/19.4 7.1/5.1 2.6/2.0 15.3/19.4 7.1/5.1 2.7/2.0
External static pressure
(Pa) 150/190 70/50 25/20 150/190 70/50 26/20
Temperature recovery efficiency (%) 79/79 79/79 84/85
Enthalpy recovery Heating 68.5/68.5 68.5/68.5 75.5/76.5
efficiency (%) Cooling 65.5/65.5 65.5/65.5 72/73
(Measured at 1.5m under
Noise (dB) 31-32/32.5 28-30/27 23-24/21 31.5-32.5/33.5 28-30/28 23-24/21
the center of the unit)
Weight (kg) 30
Starting current Under 1.6/1.5A or less

LGH-50RX3-E
Model LGH-50RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 0.94-0.95/1.21 0.89-0.90/1.05 0.57-0.60/0.60 0.95-0.96/1.22 0.90-0.93/1.05 0.58-0.60/0.60
Input (W) 204-225/262 193-214/231 123-142/130 206-228/263 196-221/228 125-142/130
(m3/h) 500/500 500/500 350/300 500/500 500/500 350/300
Air volume
(L/s) 139/139 139/139 97/83 139/139 139/139 97/83
(mmH2O) 15.3/20.4 6.1/6.1 3.1/2.0 15.3/20.4 6.1/6.1 3.1/2.0
External static pressure
(Pa) 150/200 60/60 30/20 150/200 60/60 30/20
Temperature recovery efficiency (%) 77/77 77/77 82/83.5
Enthalpy recovery Heating 67/67 67/67 73/75
efficiency (%) Cooling 61.5/61.5 61.5/61.5 68/70
(Measured at 1.5m under
Noise (dB) 32.5-33.5/32.5 30-31/28.5 23.5-24.5/23 33.5-34.5/33.5 30.5-31.5/29.5 23.5-24.5/23
the center of the unit)
Weight (kg) 33
Starting current Under 1.9/1.7A or less

2- 216
LGH-80RX3-E
Model LGH-80RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 1.8-1.8/2.1 1.7-1.7/1.9 1.4-1.4/1.5 1.7-1.7/2.0 1.6-1.6/1.8 1.4-1.4/1.4
Input (W) 392-418/455 368-396/405 304-332/315 370-394/425 348-374/390 298-330/305
(m3/h) 800/800 800/800 670/660 800/800 800/800 670/660
Air volume
(L/s) 222/222 222/222 186/183 222/222 222/222 186/183
(mmH2O) 14.3/23.5 10.2/12.2 7.1/8.2 14.3/23.5 10.2/12.2 7.1/8.2
External static pressure
(Pa) 140/230 100/120 70/80 140/230 100/120 70/80
Temperature recovery efficiency (%) 78/78 78/78 80.5/81
Enthalpy recovery Heating 71/71 71/71 73/73.5
efficiency (%) Cooling 64.5/64.5 64.5/64.5 68/68.5
(Measured at 1.5m under
Noise (dB) 33.5-34.5/35 32-33/31 30-31/29 34.5-35.5/36 33-34/32 30.5-31.5/29.5
the center of the unit)
Weight (kg) 61
Starting current Under 3.8/3.1A or less

LGH-100RX3-E
Model LGH-100RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 2.3-2.3/2.8 2.3-2.3/2.6 2.2-2.2/1.7 2.3-2.3/2.8 2.3-2.2/2.6 2.1-2.1/1.7
Input (W) 500-525/600 495-515/555 465-475/365 505-525/595 500-515/550 455-485/365
(m3/h) 1000/1000 1000/1000 870/720 1000/1000 1000/1000 870/720
Air volume
(L/s) 278/278 278/278 242/200 278/278 278/278 242/200
(mmH2O) 16.3/20.4 10.2/11.2 8.2/6.1 16.3/20.4 10.2/11.2 8.2/6.1
External static pressure
(Pa) 160/200 100/110 80/60 160/200 100/110 80/60
Temperature recovery efficiency (%) 79/79 79/79 81/83

LOSSNAY
Enthalpy recovery Heating 70/70 70/70 73/76
efficiency (%) Cooling 64.5/64.5 64.5/64.5 67/71
(Measured at 1.5m under
Noise (dB) 36-37/36 34-35/34 31.5-32.5/30 37-38/37 35-36/35 33-34/31
the center of the unit)
Weight (kg) 72
Starting current Under 5.7/5.0A or less

LGH-150RX3-E
Model LGH-150RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 3.3-3.3/4.2 3.1-3.1/3.7 2.7-2.8/2.9 3.2-3.2/4.2 3.0-3.0/3.7 2.6-2.6/2.9
Input (W) 720-785/915 670-730/805 585-660/630 695-760/905 650-705/800 565-615/630
(m3/h) 1500/1500 1500/1500 1200/1200 1500/1500 1500/1500 1200/1200
Air volume
(L/s) 417/417 417/417 333/333 417/417 417/417 333/333
(mmH2O) 14.0/21.0 10.2/12.0 5.1/7.0 14.0/21.0 10.2/12.0 5.1/7.0
External static pressure
(Pa) 137/206 100/118 50/69 137/206 100/118 50/69
Temperature recovery efficiency (%) 79/79 79/79 81/81
Enthalpy recovery Heating 72/72 72/72 75/75
efficiency (%) Cooling 65.5/65.5 65.5/65.5 69/69
(Measured at 1.5m under
Noise (dB) 36.5-37.5/37 35.5-36.5/36 32.5-33.5/33 36.5-37.5/37 35.5-36.5/36 32.5-33.5/33
the center of the unit)
Weight (kg) 154
Starting current Under 6.8/5.9A or less

LGH-200RX3-E
Model LGH-200RX3-E
Power source Single phase 220-240V 50Hz/220V 60Hz
Ventilation mode Lossnay ventilation Bypass ventilation
Speed Extra high High Low Extra high High Low
Current (A) 4.6-4.3/5.4 4.6-4.3/5.2 4.1-3.8/3.3 4.4-4.2/5.3 4.4-4.1/5.0 4.1-3.8/3.3
Input (W) 1000-1020/1175 995-1020/1130 900-905/735 960-995/1155 955-975/1090 885-900/720
(m3/h) 2000/2000 2000/2000 1400/1400 2000/2000 2000/2000 1400/1400
Air volume
(L/s) 556/556 556/556 389/389 556/556 556/556 389/389
(mmH2O) 14.0/20.0 8.2/9.0 8.5/7.0 14.0/20.0 8.2/9.0 8.5/7.0
External static pressure
(Pa) 137/196 80/88 83/69 137/196 80/88 83/69
Temperature recovery efficiency (%) 79/79 79/79 83/83
Enthalpy recovery Heating 70/70 70/70 76/76
efficiency (%) Cooling 64.5/64.5 64.5/64.5 71/71
(Measured at 1.5m under
Noise (dB) 39-40/38.5 37-38/36.5 35.5-36.5/34.5 39.5-40.5/38.5 37.5-38.5/36.5 36-37/34.5
the center of the unit)
Weight (kg) 179
Starting current Under 13.0/9.7A or less

2- 217
4. Sample Installations

LGH-15RX3-E to 100RX3-E LGH-150RX3-E and 200RX3-E


Ceiling
Ceiling
suspension
suspension Ceiling
bolt position Air-supply grille
Air exhaust grille bolt position Exhaust grille suspension Exhaust grille
(user supplied) bolt position (user supplied)
A
A Ceiling suspension
EA bolt position

C
(exhaust-air outlet)
EA

C
B
(exhaust-air outlet)

B
OA Ceiling Y piping, Dwindle pipe
(fresh-air intake) suspension (user-supplied)
OA
150~250

Heat exchanger/filter bolt position


maintenance space (fresh-air intake)
Min. 600

Min. 600
Air-supply grille 450 ( 600) Duct diameter
450 ( 600)
(user supplied) ø350 (user-supplied)
Inspection port Air-supply grille Inspection port
D
150~250
Duct diameter Heat exchanger/filter

D
ø350 (user-supplied) maintenance space
Duct normal diameter Ceiling suspension bolt
(user-supplied) position (user-supplied)
Ceiling suspension Air-supply grille
bolt position

Weather cover Duct incline


Over 1/30 (toward the wall) Ceiling suspension
(to prevent entry of rainwater) bolt position

EA
(exhaust-air outlet) Air-supply
EA 450 ( 600)
exhaust grille
(fresh-air intake) Inspection port RA SA
Duct incline EA
Over 1/30 (toward the wall) (return air) (supply air) (exhaust-air outlet)
(to prevent entry of rainwater)
OA
(fresh-air intake)

• An inspection port ( 450 or 600) must be installed on the filter and Lossnay Core
removing side. 450 ( 600)

• Provide heat insulation to prevent moisture condensation along the two outside ducts Inspection port
RA SA SA
(fresh-air intake and exhaust-air outlet). Air exhaust grille (return air) (supply air) Air-supply grille (supply air)

• Ceiling installation hardware can be attached to the top of the unit.


(models LGH-35 to 100RX3-E)
• Do not use vent caps or round hoods in places directly exposed to rain. (Unit: mm)
• An inspection port ( 450 or 600) must be installed on the filter and Lossnay
A B C D Core removing side.
• Provide heat insulation to prevent moisture condensation along the two outside ducts
LOSSNAY

LGH-15RX3-E 700 641 334 334


(fresh-air intake and exhaust-air outlet).
LGH-25RX3-E 700 765 334 334
• Where rain falls directly on the machinery, use the weather cover to prevent entry
LGH-35RX3-E 790 906 334 334 of rainwater. (Unit: mm)

LGH-50RX3-E 790 1,048 414 414 A B C D


LGH-80RX3-E 1,030 1,036 414 414 LGH-150RX3-E 1,030 1,046 414 414
LGH-100RX3-E 1,030 1,263 414 414 LGH-200RX3-E 1,030 1,273 414 414

Installation conditions:
• Ambient conditions: Temperature -10°C to +40°C, relative humidity less than 80%. When condensation is expected to form, heat up the outside air using a duct heater, etc.
• Outside air intake conditions: Temperature -15°C to +40°C, relative humidity less than 80%.

2- 218
5. Electrical Installations

LGH-15RX3-E to 100RX3-E

Earth pole TM1

SW4

SW3

LED4
SW1
LED1
SW2
LED2
SW5
LED6

TM3 Bush
If connecting an AC
TM2 TB5 power cable to the
SA2 TM3, remove this
bush and use a PG
SA1 connector to fix the
Bush power cable.

LOSSNAY
LGH-150RX3-E and 200RX3-E

SW1
SW5
SW2

SW4 SA2
SA1
SW3

SW1
SW5 TM3
SW2
LED4 LED6
SW4
SA2
SW3 SA1
LED2
TM1 TM3

LED1
Cord Clip TB5
TM2

Bush

2- 219
6. Wiring Diagrams
LGH-15RX3-E to 100RX3-E

BROWN

RED
GREEN/YELLOW
TM1 BREKER
• Connect the wires shown as dotted lines.
CN8-1 CN8-2 PE N • Be sure to connect the grounding wire.
CN10
BLACK
5
×3
ZNR102 DSA1 FUSE
250V6.3A
S1
BLUE
N
L • Breaker should be provided by the customer.
GREY HIGH ZNR101
SW4 ×4
C101 POWER SUPPLY
M2 YELLOW
BROWN
L
220-240V ~ 50HZ
C
1 EXTRA
HIGH
S2
SUPPLY 220V ~ 60HZ
FAN MOTOR (Invalid in EU)
3 WHITE
CN9 5
CN1
ORANGE ×1 1 WHITE
YELLOW TR
BLUE HIGH
SW3 ×5 1
×2
M1 WHITE
1 EXTRA
C HIGH CN7
EXHAUST
FAN MOTOR
6
GM Symbol explanation
RED
LS
BROWN M1: Motor for exhaust fan
CN2 M2: Motor for supply fan
BROWN

Operation monitor output TM3 CN32 CN16 C: Capacitor


MAX MIN
10
AC240V 2A AC220V 100mA
DC 24V 2A DC 5V 100mA 9
×7
SW2 SW1 TH1 (OA)
GM: Motor for Bypass movement
GREY
8
7
×8
CN5
GREY
BLUE
LS: Microswitch
Malfunction monitor output SW5 BLUE
TH1: Thermistor for outside air
MAX MIN ORANGE TH2 (RA)
AC240V 1A AC220V 100mA
DC 24V 1A DC 5V 100mA SA1 SA2
CN6
ORANGE
TH2: Thermistor for return air
TM2 TB5
1 2 3 4 5 6 A B S
Shield wire
SW1: Switch (Main/Sub change)
SW2, 5: Switch (Function selection)
12V or
24V DC M-NET-transmissiion cable
SW3: High/E. High select switch (Exhaust fan)
Mr. Slim
(non-polar)
Transmissiion SW4: High/E. High select switch (Supply fan)
cable CN16
1 3 PZ- Lossnay unit PZ- Unchaged
TM1: Terminal block (Power supply)
High
41SLB-E Max 15 units 52SF-E a-contact TM2: Terminal block
Uncharged Low
a-contact (Transmission cable and external control input)
External control input High/Low select connector
TM3: Terminal block (Monitor output)
LOSSNAY

LGH-150RX3-E and 200RX3-E TB5: Terminal block (M-NET Transmission cable)


S1, S2: Connector (Power supply)
LS TH1 (OA) TH2 (RA) TR: Control circuit transformer
GM X7: Relay contact (for operation monitor output)
BROWN
TR
X8: Relay contact (for malfunction monitor output)
WHITE

YELLOW

BROWN

BROWN

GREY
GREY
BLUE
BLUE
ORANGE

ORANGE
RED
WHITE

(CN16)
BLUE
S1 S2 CN1 CN1: Connector (Transformer primary)
6
1
×5 1

CN6
3

FUSE
CN7 CN2 CN5
Connector (Transformer secondary)
C101

250V6.3A
(CN32)
(TB5) CN2:
ZNR102 DSA1

S
B CN5: Connector (Thermistor)
ZNR101

SW1 (Subordination)
M1 CN8-2
A

SUPPLY SA2 6
CN6: Connector (Microswitch)
BROWN

FAN MOTOR
SA1 4
5
CN7: Connector (Motor for bypass operation)
RED

3
×3

×4

×1

×2

CN8-1 SW2 SW5 2 CN8-1: Tab connector (Fan motor)


1
M2 SW4 SW3
CN8-2: Tab connector (Fan motor)
×7

×8

(TM2)
1 EXTRA

1 EXTRA
HIGH

HIGH

HIGH

HIGH

EXHAUST (TM3)
CN9: Connector (Fan motor)
5

FAN MOTOR 10 9 8 7
CN10 CN9
ORANGE
YELLOW
BLACK

WHITE

Connector (Fan motor)


GREY

CN10:
BLUE

C CN16: Connector (High/Low switch)


C CN32: Connector (Remote control selection)
TH1 (OA)TH2 (RA)
SA1: Address setting rotary switch (10 digit)
LS
GM
SA2: Address setting rotary switch (1 digit)
BROWN
TR LED1: Inspection indicator lamp
WHITE

YELLOW

BROWN

BROWN

GREY
GREY
BLUE
BLUE

ORANGE

ORANGE
RED
WHITE

BLUE CN16 LED2: Inspection indicator lamp


S1 S2 CN1 CN7
6
1
×5 1
3

FUSE
CN2 CN5 CN6
LED4: Power supply indicator lamp
C101

SUPPLY 250V6.3A TB5


FAN MOTOR CN32
ZNR102 DSA1

S
B
LED6: M-NET indicator lamp
ZNR101

M2 SW1 (Main)
A
MARK : Indicates terminal block
RED BROWN

SA2 6
CN8-2
5
: Connector
SA1
EXHAUST
4
3
: Board insertion connector or fastening
×3

×4

×1

×2

FAN MOTOR
CN8-1 SW2 SW5 2 connector of control board
M1 SW4 SW3
1
×7

×8

TM2
1 EXTRA

1 EXTRA
HIGH

HIGH

HIGH

HIGH

TM3
5

10 9 8 7
C

CN10 CN9
ORANGE
YELLOW
BLACK

WHITE
GREY

BLUE

GREEN/YELLOW

TM1
L N PE
TM2
5 6 A B S
TB5
Shield wire
• PZ-41SLB-E and PZ-52SF-E cannot be used
simultaneously.
Unchaged
a-contact
High Low
M-NET-transmissiion cable 12V or CN16
POWER SUPPLY L N 24V DC
Mr. Slim
220 - 240V ~ 50HZ Operation monitor output (non-polar)
220V ~ 60HZ PZ- PZ- MAX MIN High/Low select connector
(Invalid in EU) 41SLB-E 52SF-E AC240V 2A AC220V 100mA
DC 24V 2A DC 5V 100mA
3

Uncharged
Malfunction monitor output a-contact
1

MAX MIN
AC240V 1A AC220V 100mA External control input
Transmissiion cable DC 24V 1A DC 5V 100mA
Lossnay unit
Max 7 units

2- 220
CMB-P-V-F
BC controller CMB-P-V-FA
CMB-P-V-FB
CONTENTS

1. Specifications ··································································· 2-222


2. External Dimension ······················································ 2-224
3. Wiring Diagrams ····························································· 2-227
4. Refrigerant circuit ··························································2-233

BC controller

2- 221
1. Specifications

Model name CMB-P104V-F CMB-P105V-F CMB-P106V-F CMB-P108V-F CMB-P1010V-F CMB-P1013V-F CMB-P1016V-F

Number of branch 4 5 6 8 10 13 16

Power source ~220/230/240V 50Hz/60Hz

Power input kW 0.068 0.083 0.098 0.128 0.158 0.203 0.248

Current A 0.31/0.30/0.28 0.38/0.36/0.35 0.45/0.43/0.41 0.58/0.56/0.53 0.72/0.69/0.66 0.92/0.88/0.85 1.13/1.08/1.03

External finish Galvanizing

Model 80 or smaller
Indoor unit capacity •Use optional joint pipe combining 2-branch when the total unit capacity exceeds 81.
connectable to 1 branch •Use the reducer (standard accessory) when the indoor unit Model 40 or smaller is connected.

Height mm 284

Width mm 362 + 70 (control box)

Depth mm 648 1098


High pressure
To ø19.05 Brazed
pipe
outdoor
unit Low pressure 200type : ø25.4 Brazed
Refrigerant pipe 250type : ø28.58 Brazed
piping
diameter Liquid pipe ø9.52 Flare
To (ø6.35 with attached reducer used, ø12.7 with optional joint pipe used)
indoor
ø15.88 Flare
BC controller

unit Gas pipe


(ø12.7 with attached reducer used, ø19.05 with optional joint pipe used)

Drain pipe VP-25

Net weight kg 24 27 29 34 39 47 54

Accessories •Drain connection pipe (with flexible hose and insulation)


•Reducer

Note: 1.Works not included : Installation/foundation work, electrical connection work, duct work, insulation work, power
source switch and other items not specified in this specification.

2- 222
Model name CMB-P108V-FA CMB-P1010V-FA CMB-P1013V-FA CMB-P1016V-FA CMB-P108V-FB

Number of branch 8 10 13 16 8

Power source ~220/230/240V 50Hz/60Hz


Power input kW 0.138 0.168 0.213 0.258 0.128
Current A 0.63/0.60/0.58 0.76/0.73/0.70 0.97/0.93/0.89 1.17/1.12/1.08 0.58/0.56/0.53

External finish Galvanizing

Model 80 or smaller
Indoor unit capacity
•Use optional joint pipe combining 2-branch when the total unit capacity exceeds 81.
connectable to 1 branch
•Use the reducer (standard accessory) when the indoor unit Model 40 or smaller is connected.

Height mm 289 284

Width mm 450 + 70 (control box) 362 + 70 (control box)


Depth mm 1110 648
High pressure
To pipe ø25.4 Brazed
outdoor
unit Low pressure
ø34.93 Brazed
pipe

Liquid pipe ø9.52 Flare


To
(ø6.35 with attached reducer used, ø12.7 with optional joint pipe used)
Refrigerant indoor
unit ø15.88 Flare

BC controller
piping Gas pipe
diameter (ø12.7 with attached reducer used, ø19.05 with optional joint pipe used)
Low press
ø28.58 Brazed
gas pipe
To
another High press
ø19.05 Brazed
BC gas pipe
controller
Liquid pipe ø12.7 Brazed

Drain pipe VP-25

Net weight kg 44 49 57 64 32

Accessories •Drain connection pipe (with flexible hose and insulation)


•Reducer

Note: 1.Works not included : Installation/foundation work, electrical connection work, duct work, insulation work, power
source switch and other items not specified in this specification.

2- 223
BC controller

<Accessories>
• Refrigerant<Low pressure> conn. pipe····1pc.
Band(Accessory)
• Reducer(Large,Small)······························Quantity for all connections
Drain hose(Accessory) • Drain hose(VP-25 connection)·················1pc.
• Pipe cover for drain hose·························1pc.

30
12
• Hose band················································1pc.

ø31
• Tie band···················································2pcs.
Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
14 prepare in the field.
2. Take notice of service space as follows.
CMB-P104,105,106,108,1010,

(Please give attention not to occupy service


1013,1016V-F

Detail of X section Dtail of Y section space by letting ducts and pipes through.)

Drain piping Connection pipe of


VP-25 connection outdoor unit
2. External Dimension

(High pressure)
ø19.05<Brazed>
Y
Control box

70
X 200

Access
door
450■

298
362
Service

248
space

2- 224
(Lifting bolt pitch)

181
700

103
250

64

64
130 23 A

B
Connection pipe of (Lifting bolt pitch)
outdoor unit 200
(Low pressure) 70 76 60XC=D Connection pipe of
224:ø25.4 <Brazed> indoor unit(Liquid)
280:ø28.58<Brazed> 60

27
ø9.52<Flare> A B C D
CMB-P104V-F 3 180

58
CMB-P105V-F 4 240

128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 CMB-P106V-F 648 702 5 300
CMB-P108V-F 7 420

255
284
CMB-P1010V-F 9 540
CMB-P1013V-F 12 720
1098 1152
Connection pipe of CMB-P1016V-F 15 900
indoor unit(Gas)
185 ø15.88<Flare>
Unit : mm
<Accessories>
Band(Accessory)
• Reducer(Large,Small)····················Quantity for all connections
Drain hose(Accessory) • Drain hose(VP-25 connection)·······1pc.

30
12
A B • Pipe cover for drain hose···············1pc.
CMB-P108V-FA 7 420 • Hose band······································1pc.

ø31
CMB-P1010V-FA 9 540 • Tie band·········································2pcs.
14 CMB-P1013V-FA 12 720 Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
CMB-P1016V-FA 15 900 prepare in the field.
2. Take notice of service space as follows.
Detail of X section Dtail of Y section (Please give attention not to occupy service
CMB-P108,1010,1013,1016V-FA

Drain piping Connection pipe of space by letting ducts and pipes through.)
VP-25 connection outdoor unit 3. Please take space to connect SUB BC CONTROLLER.
(High pressure)
ø25.4<Brazed> Connection pipe of
Y SUB BC CONTROLLER
Control box

70
(High pressure)
X ø19.05(Brazed)
128 Connection pipe of
SUB BC CONTROLLER
(Liquid)
ø12.7(Brazed)

388
450
66

333
(Lifting bolt pitch)
Connection pipe of

268
268

2- 225
210
SUB BC CONTROLLER
(Low pressure)

103
103

ø28.56(Brazed)

64

64
(Note 3.)
1110 74 200 200
130 23
1164
(Lifting bolt pitch) Access
Connection pipe of door
450■
outdoor unit Connection pipe of
(Low pressure) indoor unit(Liquid)
90 76 60XA=B Service
ø34.93<Brazed> ø9.52 <Flare>
700

space
60 70

27
250

74
128
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

260
289
70
Connection pipe of 200
indoor unit(Gas)
185 ø15.88 <Flare>
Unit : mm

BC controller
BC controller

Band(Accessory)
<Accessories>
Drain hose(Accessory) • Reducer(Large,Small)····················Quantity for all connections
• Drain hose(VP-25 connection)·······1pc.

30
12
• Pipe cover for drain hose···············1pc.

ø31
• Hose band······································1pc.
CMB-P108V-FB

• Tie band·········································2pcs.
14
Note1. Suspension bolt(ø10),washer(M10),and nut(M10)
prepare in the field.
Dtail of Y section 2. Take notice of service space as follows.
Detail of X section
(Please give attention not to occupy service
space by letting ducts and pipes through.)
Connection pipe of Connection pipe of 3. Can't use singleness.(MASTER BC CONTROLLER is necessary.)
MASTER BC CONTOROLLER MASTER BC CONTROLLER
(High pressure) (Liquid)
ø19.05<Brazed> ø12.7<Brazed>
Y
Control box

70
Drain piping
VP-25 connection
45 X

200

298
362
Access

248
door

(Lifting bolt pitch)

2- 226
181
450■

169
103
Connection pipe of
700

64

64
MASTER BC CONTROLLER
(Low pressure) Service space
130 23 648
250

ø28.6 <Brazed>
702
(Lifting bolt pitch)
Connection pipe of
indoor unit(Liquid)
70 76 60X7=420
60 ø9.52<Flare> 200

27
58
128
1 2 3 4 5 6 7 8

255
284
Connection pipe of
185 indoor unit(Gas)
ø15.88<Flare>
Unit : mm
TR
22V 220~240V TB02 Symbol explanation
Shield wire
M2 line
M1
} Transmission
DC 30V Symbo Name
TR Transformer
CONT.board TH11,12,15,16 Thermister sensor
1 1 1 LEV1,3 Expansion valve
2 2 CNP1 CNTR 3
PS1 3 2 1 2 1 PS1,3 Pressure sensor
3 3 1 1
CN03 CN02 CN26 1 1 Terminal block
X2 1 2 2 TB0
2 2 SV1B (for power source)
X1 3 3 3 T1
3 3 SV1A Terminal block
X30 5 4 4 TB02
4 4 SV1C (for Transmission)
7
CMB-P104, P105, P106V-F

1 1 1
SV1~6A Solenoid valve
1
2 2 X4
CN27
3. Wiring Diagrams

PS3 CNP3 1 2 2 SV1~6B Solenoid valve


3 5 5 SV2B
3 X3 3 3 3 T2 SV1~6C Solenoid valve
6 6 SV2A
X31 5 4 4
1 7 7 SV2C T1~6 Terminal
CN13 7
2
1 1 F01 Fuse AC250V 6.3A F
X6
CN28 2
1 1 2
TH11 8 8 SV3B Note:TB02 is terminal block for transmission.
2 X5 3 3 3 T3
9 9 SV3A
3 X32 5 4 4 Never connect power line to it.
TH12 10 10 SV3C
4 7
CN10
5 1 1
6 X8 CN29 2 2
1
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A
8 X33 5 4 4
13 13 SV4C
7
1
1 1

2- 227
TH15
2
X10
CN30
CN11 1 2 2
3 14 14 SV5B
TH16 X9 3 3 3 T5
4 15 15 SV5A
X34 5 4 4
16 16 SV5C
7
1 1
X12
CN31
1 2 2
1 1 SV6B
X11 3 3 3 T6
2 2 SV6A
X35 5 4 4
3 3 SV6C
7
4 4

F01
250VAC
6.3A F
CN07 CN05 CN12
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5

TB01
L Power source
N } ~220V~240V 50/60Hz
LEV3 LEV1
EARTH
PE

BC controller
BC controller

TR
TB02
22V 220~240V Shield wire Symbol explanation
M2
Transmission line
M1
}DC 30V Symbol Name
CONT.board
1 6 5 4 3 2 1 7 6 5 4 3 2 1
TR Transformer
1
1 CN51 CN50
PS1 2 2 CNP1 CNTR 3
TH11,12,15,16 Thermister sensor
3 3 2 1 2 1 1 3
3 1 1 LEV1,3 Expansion valve
CN03 CN02 CN38 CN26 1 1
X2 1 2 2
2 2 SV1B PS1,3 Pressure sensor
X1 3 3 3 T1
3 3 SV1A Terminal block
X30 5 4 4 TB0
CMB-P108, P1010V-F

4 4 SV1C (for power source)


7
1
Terminal block
1 1 1 TB0 (for Transmission)
PS3 2 CN27
2 CNP3 X4 1 2 2
3 5 5 SV2B SV1~10 Solenoid valve
3 X3 3
3 3 T2
6 6 SV2A
X31 5 4 4 SV1~10B Solenoid valve
1 7 7 SV2C
CN13 7 SV1~10C Solenoid valve
2
1 1
CN28 T1~10 Terminal
1 X6 1 2 2
TH11 8 8 SV3B F01 Fuse AC250V 6.3A F
2 X5 3 3 3 T3
9 9 SV3A
3 X32 5 4 4 Note:TB02 is terminal block for transmission.
TH12 10 10 SV3C
4 7
CN10 Never connect power line to it.
5 1 1
CN29
6 X8 1 2 2
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A
8 X33 5 4 4
13 13 SV4C
7
1
TH15 1 1
SV9C
SV9B
SV8C
SV8B
SV7C
SV7B

SV9A
SV8A
SV7A

SV10C
SV10B
SV10A

2 CN30
CN11 X10 1 2 2
3 14 14 SV5B
TH16 X9 3 3 3 T5
4
15 15 SV5A T10 T9 T8 T7
X34 5 4 4 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
16 16 SV5C

2- 228
7
1 1
CN31
X12 1 2 2 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
1 1 SV6B
X11 3 3 3 T6
2 2 SV6A
X35 5 4 4 16 15 14 13 12 11 10 9 8 7 6 5 4
3 3 SV6C 15 14 13 9 8 7 6 5 4
16 12 11 10
7

F01 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
250VAC
6.3A F
CN33
CN32

CN35
CN34

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN07 CN05 CN12


1 2 3 4 5 6 1 2 3 4 5 6 1 3 5

3
1 CN39
6 5 4 3 2 1 7 6 5 4 3 2 1
TB01
L
Power source CN53 CN52
N } ~220V~240V 50/60Hz
RELAY4 Board
EARTH
LEV3 LEV1 PE
TR TB02
22V 220~240V Shield wire Symbol explanation
M2 Transmission line
}
M1 DC 30V Symbol Name
CONT.board
1 1 1
TR Transformer
2 2 CNTR 3 TH11,12,15,16 Thermister sensor
PS1 CNP1
3 3 2 1 3 2 1 2 1 1 3
3 1 1
CNVCC1 CN03 CN02 CN38 CN26 1 1 LEV1,3 Expansion valve
X2 1 2 2
2 2 SV1B PS1,3 Pressure sensor
X1 3 3 3 T1
3 3 SV1A
X30 5 4 4 TB0 Terminal block
4 4 SV1C
CMB-P1013, P1016V-F

7 (for power source)


1 1 1 1
2 2 CN27 TB0 Terminal block
PS3 CNP3 CNOUT1 X4 1 2 2
3 3 5 5 SV2B (for Transmission)
1 X3 3 3 3 T2
6 6 SV2A
1 2 X31 5 4 4 SV1~16A Solenoid valve
7 7 SV2C
2 CN13 3 7 SV1~16B Solenoid valve

SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

SV10C
SV10A
SV10B
4 1 1
1
CN28 SV1~16C Solenoid valve
5 X6 1 2 2
TH11 8 8 SV3B T10 T9 T8 T7
2 6 X5 3 3 3 T3 T1~16 Terminal
SV3A 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
9 9
3 7 X32 5 4 4 F01 Fuse AC250V 6.3A F
TH12 10 10 SV3C
4 8 7
CN10
5 1 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
6 1 CN29
X8 1 2 2
2
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A 16 15 14 13 12 11 10 9 8 7 6 5 4
8 3 16 15 14 13 12 11 10 9 8 7 6 5 4
X33 5 4 4
13 13 SV4C
4
7
1
CNOUT3 1 1
TH15 2 CN30
CN11 X10 1 2 2
3 14 14 SV5B RELAY10 board
X9 3 3 3 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
TH16 4 15 15 SV5A 1 1
X34 5 4 4 CN40
16 16 SV5C 1 2 2
1 3 3 2 1 1 1 SV11B

2- 229
7
X41 3 3 3 T11

CN35
CN34
CN33
CN32

CN39 CNVCC2 2 2 SV11A

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

1 1
CN31 X40 5 4 4
X12 1 2 2 3 3 SV11C
1 1 SV6B X42 7 1 1
X11 3 3 3 T6
2 2 SV6A CN41 2
1 2
X35 5 4 4 4 4 SV12B
3 3 SV6C X44 3 3 3 T12
7 5 5 SV12A
X43 5 4 4
6 6 SV12C
X45 7 1 1
F01 CN42 1 2 2
7 7 SV13B
250VAC X47 3 3 3 T13
8 8 SV13A
6.3A F X46 5 4 4
CN07 CN05 CN12 9 9 SV13C
X48 7 1 1
1 2 3 4 5 6 1 2 3 4 5 6 1 3 5
CN43 1 2 2
TB01 10 10 SV14B
X50 3 3 3 T14
L Power source 11 11 SV14A
X49 5 4 4
N } ~220V~240V 50/60Hz 12 12 SV14C
EARTH X51 7 1 1
PE CN44 1 2 2
1 13 13 SV15B
2 X53 3 3 3 T15
LEV3 LEV1 3 14 14 SV15A
4 X52 5 4 4
CNOUT2 15 15 SV15C
5
X54 7 1 1
6 16 16
7 CN45 2
1 2
8 1 1 SV16B
Note1:TB02 is terminal block for transmission. X56 3 3 3 T16
1 2 2 SV16A
Never connect power line to it. X55 5 4 4
2 3 3 SV16C
3
CNOUT4
X57 7
4 4 4

BC controller
BC controller

TR
TB02 Symbol explanation
22V 220~240V Shield wire
M2 Transmission line
M1
} DC 30V
Symbol Name
CONT.board TR Transformer
1 6 5 4 3 2 1 7 6 5 4 3 2 1 1
1
TH11,12,15,16 Thermister sensor
2 CN51 CN50
PS1 2 CNP1 CNTR 3
3 3 2 1 2 1 1 3 LEV1,3 Expansion valve
3 1 1
CN03 CN02 CN38 CN26 1 1
X2 1 2 2
PS1,3 Pressure sensor
2 2 SV1B
X1 3 3 3 T1
TB0 Terminal block
3 3 SV1A (for power source)
X30 5 4 4
CMB-P108, 1010V-FA

4 4 SV1C
7
Terminal block
TB02 (for Transmission)
1 1 1
1
2 CN27 SV1~10A Solenoid valve
PS3 2 CNP3 X4 1 2 2
3 5 5 SV2B
3 X3 3
3 3 T2 SV1~10B Solenoid valve
6 6 SV2A
X31 5 4 4
1 7 7 SV2C SV1~10C Solenoid valve
CN13 7
2
1 1
SVM1,2 Solenoid valve
CN28
1 X6 1 2 2 T1~10 Terminal
TH11 8 8 SV3B
2 X5 3 3 3 T3
9 9 SV3A F01 Fuse AC250V 6.3A F
3 X32 5 4 4
TH12 10 10 SV3C
4 7
Note1:TB02 is terminal block for transmission.
CN10
5 1 1 Never connect power line to it.
CN29
6 X8 1 2 2
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A
8 X33 5 4 4
13 13 SV4C
7
1
1 1
TH15
SV9C
SV9A
SV9B
SV8C
SV8A
SV8B
SV7C
SV7A
SV7B

SV10C
SV10A
SV10B

SVM2
SVM1

2 CN30
CN11 X10 1 2 2
3 14 14 SV5B
TH16 X9 3 3 3 T5
4
15 15 SV5A T10 T9 T8 T7
X34 5 4 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
16 16 SV5C

2- 230
7
1 1
CN31
X12 1 2 2 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
1 1 SV6B
X11 3 3 3 T6
2 2 SV6A
X35 5 4 4 4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
3 3 SV6C
4 3 2 1 16 15 14 13 12 11 10 9 8 7 6 5 4
7

CN36
X21 1
3
1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
CN46
X60 1
3
CN35
CN34
CN33
CN32

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

CN07 CN05 CN12


1 2 3 4 5 6 1 2 3 4 5 6 1 3 5 F01
250VAC 3
1 CN39
6.3A F
6 5 4 3 2 1 7 6 5 4 3 2 1
TB01
L
Power source CN53 CN52
N } ~220V~240V 50/60Hz
RELAY4 Board
EARTH
LEV3 LEV1 PE
TR TB02
Symbol explanation
22V 220~240V Shield wire
M2 Transmission line Symbol Name
M1
} DC 30V TR Transformer
CONT.board
1 1
TH11,12,15,16 Thermister sensor
1
2 2 CNP1 CNTR 3 LEV1,3 Expansion valve
PS1 3 2 1 3 2 1 2 1 1 3
3 3 1 1
CNVCC1 CN03 CN02 CN38 CN26 1 1 PS1,3 Pressure sensor
X2 1 2 2
2 2 SV1B TB0 Terminal block
X1 3 3 3 T1
3 3 SV1A (for power source)
X30 5 4 4
4 4 SV1C
7 TB0 Terminal block
1 1 1
1
CMB-P1013, P1016V-FA

2 CN27
(for Transmission)
PS3 2 CNP3 CNOUT1 X4 1 2 2
3 5 5 SV2B SV1~16A Solenoid valve
3 X3 3 3
1 3 T2
6 6 SV2A
2 X31 5 4 4 SV1~16B Solenoid valve
1 7 7 SV2C
CN13 3 7
2 SV1~16C Solenoid valve

SV9C
SV9B
SV8C
SV8B
SV7C
SV7B

SV9A
SV8A
SV7A

SV10C
SV10A
SV10B
4 1 1
CN28 SVM1,2 Solenoid valve
1 5 X6 1 2 2
TH11 8 8 SV3B T10 T9 T8 T7
2 6 X5 3 3 3 T3 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
T1~16 Terminal
9 9 SV3A
3 7 X32 5 4 4 F01 Fuse AC250V 6.3A F
TH12 10 10 SV3C
4 8 7
CN10
5 1 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
1 CN29
6 X8 1 2 2
2
11 11 SV4B
7 X7 3 3 3 T4 16 15 14 13 12 11 10 9 8 7 6 5 4
3 12 12 SV4A
8 X33 5 4 4 16 15 14 13 12 11 10 9 8 7 6 5 4
4
13 13 SV4C
7
1 1
TH15 CNOUT3 1
2 CN30
CN11 X10 1 2 2
3 14 14 SV5B RELAY10 board
TH16 X9 3 3 3 T5 1 3 5 7 1 3 5 7 1 3 5 7 1 3 5 7
15 15 SV5A 1 1
4
X34 5 4 4 CN40
16 16 SV5C 1 3 3 2 1 1 2 2
7 1 1 SV11B
X41 3 3

CN35
CN34
CN33
CN32

CN39 CNVCC2 3 T11

2- 231
2 2 SV11A

X20
X19
X39
X18
X17
X38
X16
X15
X37
X14
X13
X36

1 1
CN31 X40 5 4 4
X12 2 2 3 3 SV11C
1
1 1 SV6B X42 7 1 1
X11 3 3 3 T6
2 2 SV6A CN41 1 2 2
F01 X35 5 4 4 4 4 SV12B
250VAC 3 3 SV6C X44 3 3 3 T12
7 5 5 SV12A
6.3A F X43 5 4 4
6 6 SV12C
CN36 X45 7 1
X21 1 1

3
CN42 1 2 2
7 7 SV13B
X47 3 3 3 T13
8 8 SV13A
CN46 X46 5 4 4
X60 1
CN07 CN05 9 9 SV13C
CN12 X48 7
1 3 5 3 1 1
1 2 3 4 5 6 1 2 3 4 5 6
CN43 1 2 2
1010 SV14B
TB01 X50 3 3 3 T14
L Power source 1111 SV14A
X49 5 4 4
N ~220V~240V 50/60Hz 1212 SV14C
X51 7
} EARTH
CN44
1 1
PE 1 1 2 2
1313 SV15B
2
X53 3 3 3 T15
LEV3 LEV1 3 1414 SV15A
4 X52 5 4 4
5 CNOUT2 1515 SV15C
6 X54 7 1 1
1616
7 CN45 1 2
8 1 1 2 SV16B
X56 3 3
3 T16
1 2 2 SV16A
2 X55 5 4
CNOUT4 3 3 4 SV16C
Note1:TB02 is terminal block for transmission. 3
X57 7 1
4 4 4 1
Never connect power line to it. 2 2
SVM1
3 3
SVM2

BC controller
BC controller

TR
TB02
22V 220~240V Shield wire Symbol explanation
M2 Transmission line
M1
} DC 30V Symbol Name
CONT.board
7 6 5 4 3 2 1
TR Transformer
1
CMB-P108V-FB

CN50 TH12,15 Thermister sensor


CNTR 3
3 2 1 2 1 1 3
1 1 LEV3 Expansion valve
CN03 CN02 CN38 CN26 1 1
X2 1 2 2 Terminal block
2 2 SV1B TB0
X1 3 3 3 T1 (for power source)
3 3 SV1A
X30 5 4 4 Terminal block
4 4 SV1C TB0
7 (for Transmission)
1 1 SV1~8A Solenoid valve
CN27
X4 1 2 2
5 5 SV2B SV1~8B Solenoid valve
X3 3 3 3 T2
6 6 SV2A
X31 5 4 4 SV1~8C Solenoid valve
1 7 7 SV2C
CN13 7
2 T1~8 Terminal
1 1
CN28 F01 Fuse AC250V 6.3A F
1 X6 1 2 2
8 8 SV3B
2 X5 3 3 3 T3 Note1:TB02 is terminal block for transmission.
9 9 SV3A
3 X32 5 4 4 Never connect power line to it.
TH12 10 10 SV3C
4 7
CN10
5 1 1
CN29
6 X8 1 2 2
11 11 SV4B
7 X7 3 3 3 T4
12 12 SV4A
8 X33 5 4 4
13 13 SV4C
7
1
1 1
SV8C
SV8B
SV7C
SV7B

TH15
SV8A
SV7A

2 CN30
CN11 X10 1 2 2
3 14 14 SV5B
X9 3 3 3 T5
4
15 15 SV5A T8 T7
X34 5 4 4 4 3 2 1 4 3 2 1

2- 232
16 16 SV5C
7
1 1
CN31
X12 1 2 2 4 3 2 1 4 3 2 1
1 1 SV6B
X11 3 3 3 T6
2 2 SV6A
X35 5 4 4 16 15 14 13 12 11 10 9 8 7 6 5 4
3 3 SV6C 16 15 14 13 12 11 10 9 8 7 6 5 4
7

F01 1 3 5 7 1 3 5 7
250VAC
6.3A F
CN33
CN32

X16
X15
X37
X14
X13
X36

CN07 CN12
1 2 3 4 5 6 1 3 5

3
CN39
1
7 6 5 4 3 2 1
TB01
L
Power source CN52
N } ~220V~240V 50/60Hz
EARTH RELAY4 Board
LEV3 PE
4. Refrigerant Circuit
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-F

SVC

SVA
Outdoor unit SVB

Gas/liquid separator

TH12
Indoor units

TH11

63HS1

BC controller
LEV1

63HS3

TH15

LEV3

TH16

2- 233
CMB-P108, P1010, P1013, P1016V-FA

Solenoid
valve block

Gas/Liquid TH15
separator LEV3 SVM2
TH12

TH11 LEV1 TH16

PS3 Check
PS1 SVM1 valve block

CMB-P108V-FB
BC controller

Solenoid
valve block

TH22
CP
TH25
LEV3a

Check
valve block

2- 234
3

CONTENTS

1. Function table of controllers 3-2


2. Local remote controller
2-1 Wired remote controller PAR-20MAA 3-3
PAR-F27MEA 3-4
2-2 Simple remote controller PAC-SE51CRA 3-5

2-3 Simple MA controller PAC-YT51CRA 3-6

2-4 Wireless remote controller PAR-FL31MA 3-7


PAR-FA31MA

2-5 LOSSNAY remote controller PZ-52SF-E 3-8

2-6 Program timer PAC-YT32PTA 3-9

3. System controller
3-1 Group remote controller PAC-SC30GRA 3-10

3-2 System remote controller PAC-SF44SRA 3-12

3-3 Schedule timer PAC-YT34STA 3-14

3-4 ON/OFF remote controller PAC-YT40ANRA 3-16

3-5 Centralized controller G-50A 3-18


TG-2000A 3-24
MB-300 3-28

3-6 Air conditioner interface LMAP02-E 3-34

3-7 Power supply unit PAC-SC34KUA 3-36


PAC-SC50KUA 3-37

3-8 Transmission booster unit PAC-SF46EPA 3-38

4.System component 3-39

3- 1
1. Function table of controllers
Function

Local remote controller MELANS series (Man-machine type) Interface type


Simple Wireless ON/OFF Group System Schedule Air
Model Remote controller remote remote remote remote remote timer Centralized controller conditioner
controller controller controller controller controller interface
PAR-20MAA PAR-F27MEA PAC-SE51CRA PAR-FL31MA PAC-YT40ANRA PAC-SC30GRA PAC-SF44SRA PAC-YT34STA G-50A TG-2000A LMAP02-E
No. of units controllable 50G/50units ✻7
1G/16units 1G/16units 1G/16units 1G/16units 16/50 8G/16units 50/50 50G/50U 2000G/2000units 50G/50units
(Groups (G) / units) G-50A browser ✻4
Start / Stop

Operation mode ✕ ✕ ✕
Operation

Temperature setting ✕ ✕
Permit / Prohibit direction ✕ ✕ ✕ ✕ ✕ ✕ ✕
Fan speed ✕ ✕
Air flow direction ✕ ✕ ✕
Status ✕ ✕
Error flashing

Error content ✕
Filter sign ✕ ✕ ✕ ✕
Operating hour ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
Monitoring

Operation mode ✕ ✕
Setting temperature ✕ ✕

Specifications vary depending on host system device.


Indoor temperature (intake) ✕ ✕ ✕ ✕ ✕
Permit / Prohibit ✕ ✕
Fan speed ✕ ✕
Air flow direction ✕ ✕ ✕
✻1 ✻1 ✻1 ✻1
Weekly ✕/ ✕/ ✕ ✕ ✕ ✕/ ✕
Annual (Designated day setting) ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
One day ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
Scheduling

✻1 ✻2 ✻1 ✻1 ✻1
Times of stops / Starts per day 1/1 / 48 1/1 / 48 ✕ 1/1 ✕ ✕ /48 ✕ 16 3/3 12 12
✻1 ✻1
Times of stops / Starts per week ✕ ✕ ✕ ✕ ✕ ✕ /336 ✕ 112 21/21 84 84
Auto off timer ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
✻1 ✻1 ✻1 ✻1
Minimum setting unit (minutes) 10/30 10/30 ✕ 10 ✕ ✕ /30 ✕ 5 10 1 1
Error history ✕ ✕ ✕ ✕ ✕ ✕
Recording

Daily / Monthly reports ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕


Electricity charges ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
✻6
Set temperature range limit ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
Others

Auto lock ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
✻5
Ventilation (group / interlocked) ✕/ ✕/ ✕ ✕ ✕ ✕/ ✕ / /
management
Control and

✻3 ✻5
Group setting ✕ ✕ ✕ ✕ ✕
✻5
Block setting ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
Revision of electricity charges ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕ ✕
(group / interlocked) (group / interlocked)

Start / Stop –/ –/ –/ –/ ✕ –/ / ✕ / / /
Ventilation
Operation

Fan speed –/ –/ –/✕ –/✕ ✕ –/ / ✕ / / /


Ventilation mode –/✕ –/✕ –/✕ –/✕ ✕ –/✕ /✕ ✕ /✕ /✕ /✕
Status –/ –/ –/✕ –/✕ ✕ –/ / ✕ / / /
Ventilation
Monitoring

Fan speed –/ –/ –/✕ –/✕ ✕ –/ / ✕ / / /


Ventilation mode –/✕ –/✕ –/✕ –/✕ ✕ –/✕ /✕ ✕ /✕ /✕ /✕
: Each group / Batched : Each group : Depend on the Building management system : Block (City Multi indoor unit only)
: Set up by a local remote controller : Please inquire ✕ : Not available – : Not used : G50 license registration possible.

✻1: When PAC-YT32PTA is connected. ✻2: daily timer availability ✻3: For group operation, cross-over wring is required between indoor unit.
✻4: Contact the retailer for questions relating to the browser. ✻5: Installation possible at Initial setting tool. ✻6: Ver,4.10 or more.
✻7: Web monitor license is required for G-50.

3- 2
2. Local remote controller

PAR-20MAA
2-1 Wired remote controller ■ Functions :Each unit :Each group ● :Each block
2-1-1 PAR-20MAA :Each floor :Collective ✕ :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode Operation modes vary depending on the air conditioner unit.
switching Auto mode is the City Multi R2 and WR2 series only.
Sets the temperature for a single group
CENTRALLY CONTROLLED 1Hr. Range of temperature setting
CLOCK
ON OFF ˚C
TEMP. Temperature Cool/Dry : 19˚C - 30˚C
CHECK
FILTER setting Heat : 17˚C - 28˚C
CHECK MODE
˚C TEST RUN Auto : 19˚C - 28˚C
STAND BY
DEFROST
ERROR CODE NOT AVAILABLE FUNCTION

TEMP. ON/OFF Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Fan speed
Models with 3 air flow speed settings: Hi/Mid/Low
setting
Models with 2 air flow speed settings: Hi/Low
FILTER
Air flow Air flow direction angles 100% - 80% - 60% - 40%, Swing,
CHECK TEST direction Louver ON/OFF
setting Air flow direction settings vary depending on the model.
PAR-20MAA TIMER SET

One ON/OFF setting can be set for one day.


TIMER SET Timer By connecting the Program timer, set 48 ON/OFF settings
operation every 30 minutes. By loading only one pattern, it can operate
as a weekly schedule.

Individually prohibit operation of each local remote control


● Group operation is possible without requiring function (Start/Stop, Change operation mode, Set
temperature, Reset filter). ✻1
address setting. Permit / Prohibit
✻1: When the local remote controller inactivation command ✕
local operation
● Usable as the local remote controller for System is received from the master system controller,
"- CENTRALLY CONTROLLED -" is displayed.
Controller (MELANS).
● Remote controller automatically judges the func- Prohibition/permission By the setting from System Controller, the operation for the
of specified mode following modes is prohibited.
tion required for indoor unit such as vane/louver (Cooling prohibited At cooling prohibited : Cool, Dry, Auto, ✕
selection. /heating prohibited At heating prohibited : Heat, Auto,
/cooling-heating prohibited) At cooling-heating prohibited : Cool, Heat, Dry, Auto
(✻) For group operation, cross-over wiring is required
between indoor units. Indoor unit intake Measures the intake temperature of the indoor unit when

temperature the indoor unit is operating.
(✻) Combined use with M-NET remote controller
(F27MEA, Simple R/C, LOSSNAY R/C) can not be Error
When an error is currently occurring on an air conditioner

conducted inside a group. unit, the afflicted unit and the error code are displayed.

Test run This operates air conditioner units in test run mode.

Up to 16 indoor units can be connected to an interlocked


Ventilation system that has one LOSSNAY. LOSSNAY items that can
equipment be set are "Hi" "Low" "Stop". Ventilation mode switching is
■ System example not available.

By connecting the Program timer "PAC-YT32PTA", a weekly


External schedule can be controlled. External start/stop control and
input/output emergency stop is not supported.

Non-polarized
Non-polarized 2-wire
2-wire
MA MA
remote remote
controller controller

■ External dimension

(Front view) (Side view) (Rear view) Unit:mm


120

83.5

130 19 46

3- 3
PAR-F27MEA

■ Functions :Each unit :Each group ● :Each block


2-1-2 PAR-F27MEA :Each floor :Collective ✕ :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode Operation modes vary depending on the air conditioner unit.
switching Auto mode is the City Multi R2 and WR2 series only.
Sets the temperature for a single group
Range of temperature setting
CENTRALLY CONTROLLED
DAILY ON OFF
1Hr.
TEMP. Temperature Cool/Dry : 19˚C - 30˚C
˚C
AUTO OFF CLOCK setting Heat : 17˚C - 28˚C
REMAINDER FILTER
CHECK MODE Auto : 19˚C - 28˚C
TEST RUN
STAND BY
DEFROST ˚C ERROR CODE NOT AVAILABLE LIMIT TEMP.
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
TEMP. Fan speed
ON/OFF Models with 3 air flow speed settings: Hi/Mid/Low
setting
Models with 2 air flow speed settings: Hi/Low
CLOCK→ON→OFF
FILTER Air flow Air flow direction angles 100% - 80% - 60% - 40%, Swing,
direction Louver ON/OFF
CHECK TEST setting Air flow direction settings vary depending on the model.
TIMER SET
PAR-F27MEA Individually prohibit operation of each local remote control
function (Start/Stop, Change operation mode, Set
temperature, Reset filter). ✻1
Permit / Prohibit
local operation ✻1: When the local remote controller inactivation command ✕
is received from the master system controller, "-
CENTRALLY CONTROLLED -" is displayed.
● Three timer modes are prepared by enriching the
Prohibition/permission By the setting from System Controller, the operation for the
timer function.The timer mode can selectively be of specified mode following modes is prohibited.
used depending on the application configuration. (Cooling prohibited At cooling prohibited : Cool, Dry, Auto,
/heating prohibited At heating prohibited : Heat, Auto,

● The range of room temperature setting can be /cooling-heating prohibited) At cooling-heating prohibited : Cool, Heat, Dry, Auto
limited by the initial setting.By setting the room Indoor unit intake Measures the intake temperature of the indoor unit when
temperature range narrower than usual setting, temperature the indoor unit is operating. ✕
cooling/heating operation with excessive tempera- When an error is currently occurring on an air conditioner
ture can be prevented thus saving energy easily. Error
unit, the afflicted unit and the error code are displayed. ✕
● Equipped with simplified button locking function. Thanks to the three timer modes equipped, a proper mode
can be selected to meet the usage.
One day timer : ON/OFF setting of one time on one day can be applied.
Daily timer : ON/OFF setting by the One day timer can be repeated for
Timer operation everyday.
Auto OFF timer : OFF timer can be set in a range from 30 minutes to 4 hours.
✻Setting of Auto OFF timer automatically activates OFF timer at the next operation.
This function can be utilized to prevent the negligence of OFF setting.
✻Weekly schedule in only one patterns can be employed by connecting Program timer. ✻2
■ System example
Test run This operates air conditioner units in test run mode.

Up to 16 indoor units can be connected to an interlocked


Ventilation system that has one LOSSNAY. LOSSNAY items that can
equipment be set are "Hi" "Low" "Stop". Ventilation mode switching is
not available.

Function to limit The range of room temperature setting can be limited by the
the setting range initial setting.The lowest limit temperature can be made higher
of room than the usual (19˚C) at cooling/drying, while the upper limit
temperature temperature lower than the usual (28˚C) at heating.
(Set temperature ✻When making the function to limit room temperature setting range
range limit) effective, the operation mode can not be set to the auto mode.

Remote Remote Easy-to-operate Setting/releasing of simplified locking for remote control


controller controller simplified locking switch can be performed.
function · Locking of all switches
(Auto lock function) · Locking of all switches except Start/Stop switch

By connecting the Program timer "PAC-YT32PTA", a weekly


External schedule can be controlled. External start/stop control and
■ External dimension input/output emergency stop is not supported.

(Front view) (Side view) (Rear view) Unit:mm


120

83.5

130 19 46

3- 4
PAC-SE51CRA
■ Functions :Each unit :Each group ● :Each block
2-2 Simple remote controller :Each floor :Collective ✕ :Not available
(PAC-SE51CRA) Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode
CENTRAL TEMP.CHECK switching
Operation modes vary depending on the air conditioner unit. ✕
Auto mode is the City Multi R2 and WR2 series only.
˚C Sets the temperature for a single group
Temperature Range of temperature setting
setting Cool/Dry : 19˚C - 30˚C
Heat : 17˚C - 28˚C
Auto : 19˚C - 28˚C

ON/OFF Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Fan speed setting
Models with 2 air flow speed settings: Hi/Low
TEMP.
Air flow direction Air flow direction angles 100% - 80% - 60% - 40%, Swing,
setting Louver ON/OFF ✕ ✕
Air flow direction settings vary depending on the model.
PAC-SE51CRA
Timer operation Not available ✕ ✕
Individually prohibit operation of each local remote control
● To simplify operation of the system, the range of Permit / Prohibit function (Start/Stop, Set temperature).
local operation ✻1
controls has been limited to Start/Stop, room tem- ✻1: When the local remote controller inactivation command is ✕
received from the master system controller, "- CENTRALLY
perature and fan speed. CONTROLLED -" is displayed.
● The only wiring required is cross-over wiring based
Indoor unit intake Measures the intake temperature of the indoor unit only when
on two-wire signal lines. temperature the indoor unit is operating. ✕ ✕
● Room temperature sensor is built-in to the unit. The When an error is currently occurring on an air conditioner unit,
Error
indoor unit can be replaced this with the body ther- the afflicted unit and the error code are displayed. ✕
mostat. This operates air conditioner units in test run mode. ✻2
❇: This equipment does not have functions such as operation mode Test run ✻2: The display for test run mode will be the same as for normal ✕
switching, test run mode, self checking ability and settings for start/stop (no display "test run").
interlocking. Therefore, always use this equipment together with a
Ventilation Up to 16 indoor units can be connected to an interlocked system
PAR-F27ME or other system controller. ✕ ✕
equipment that has one LOSSNAY.
❇: Combined use with MA remote controller (PAR-20MAA) can not
be conducted inside a group. By connecting the Program timer, allocate A/B2 mode for a
External week and control a week's schedule. External start/stop control
input/output and emergency stop is not supported.
✕ ✕

■ System example

Centralized controller
UP

Power supply unit

Simple Simple
controller controller

■ External dimension

ABS

REMOTE CONTROLLER
MODEL
PAC-SE51CRA
INPUT VOLTAGE DC30V
0.02A
83.5

WEIGHT 0.15kg
78
120

SERIAL No.

MADE IN JAPAN KT79C117H01

ON/OFF
TEMP.

PAC-SE51CRA

70 8 33
(41)

48

3- 5
PAC-YT51CRA

2-3 Simple MA controller ■ Functions :Each unit :Each group ● :Each block
(PAC-YT51CRA) :Each floor :Collective ✕ :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Auto / Fan / Heat.
Operation mode
CENTRAL TEMP.CHECK
switching
Operation modes vary depending on the air conditioner unit. ✕
Auto mode is the City Multi R2 and WR2 series only.
˚C Sets the temperature for a single group
Temperature Range of temperature setting
setting Cool/Dry : 19˚C - 30˚C
Heat : 17˚C - 28˚C
Auto : 19˚C - 28˚C
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
ON/OFF Fan speed setting
Models with 3 air flow speed settings: Hi/Mid/Low
TEMP. Models with 2 air flow speed settings: Hi/Low

Air flow direction Air flow direction angles 100% - 80% - 60% - 40%, Swing,

PAC-YT51CRA
setting Louver ON/OFF ✕ ✕
Air flow direction settings vary depending on the model.

Timer operation Not available ✕ ✕


● To simplify operation of the system, the range of
Individually prohibit operation of each local remote control
controls has been limited to Start/Stop, room tem- Permit / Prohibit function (Start/Stop, Set temperature).
local operation ✻1: When the local remote controller inactivation command is ✻1
perature and fan speed. received from the master system controller, "- CENTRALLY ✕
● The only wiring required is cross-over wiring based CONTROLLED -" is displayed.
on two-wire signal lines. Indoor unit intake Measures the intake temperature of the indoor unit only when
● Room temperature sensor is built-in to the unit. The temperature the indoor unit is operating. ✕ ✕
indoor unit can be replaced this with the body ther- When an error is currently occurring on an air conditioner unit,
Error
mostat. the afflicted unit and the error code are displayed. ✕
❇: This equipment does not have functions such as operation mode This operates air conditioner units in test run mode. ✻2
switching, test run mode, self checking ability and settings for Test run
interlocking. Therefore, always use this equipment together with a
✻2: The display for test run mode will be the same as for normal ✕
start/stop (no display "test run").
PAR-20MAA or other system controller.
❇: Combined use with M-NET remote controller (PAR-F27MEA) can Ventilation Up to 16 indoor units can be connected to an interlocked system
equipment that has one LOSSNAY. ✕ ✕
not be conducted inside a group.
By connecting the Program timer, allocate A/B2 mode for a
External week and control a week's schedule. External start/stop control
input/output and emergency stop is not supported.
✕ ✕
■ System example

Centralized controller
UP

Power supply unit

Simple MA Simple MA
controller controller

■ External dimension
Unit:mm

ABS
83.5
78
120

ON/OFF
TEMP.

PAC-YT51CRA

70 8 33
(41)

48

3- 6
PAR-FL31MA
2-4 Wireless remote controller ■ Functions :Each unit :Each group ● :Each block
Controller :PAR-FL31MA :Each floor :Collective ✕ :Not available
Signal receiving unit :PAR-FA31MA Item Description Operations Display
ON/OFF Run and stop operation for a single group
Switches between Cool / Dry / Fan / Heat / Auto.
Operation mode
CHECK TEST RUN
Operation modes vary depending on the air conditioner unit.
˚C switching
Auto mode is the City Multi R2 and WR2 series only.
AM
PM
Sets the temperature for a single group
AM
PM ON/OFF
Temperature Range of temperature setting
NOT AVAILABLE

setting Cool/Dry : 19˚C - 30˚C


ON/OFF Heat : 17˚C - 28˚C
Auto : 19˚C - 28˚C
MODE
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low
FAN
CLOCK
Fan speed setting
Models with 2 air flow speed settings: Hi/Low ❇ ❇
HEAT COOL

VANE STOP START Air flow direction Air flow direction angles 100% - 80% - 60% - 40%, Swing.
HR. MIN. setting Air flow direction settings vary depending on the model. ❇ ❇
Timer operation One ON/OFF setting can be set for one day.

PAR-FL31MA PAR-FA31MA Individually prohibit operation of each local remote control


Permit / Prohibit function (Start/Stop, Change operation mode, Set temperature,
local operation Reset filter). ✻1

✻1: If operation is performed when the local remote controller ✕


● It can operate in a group system without requiring inactivation command is received from the master system
controller, a buzzer will ring and an LED will flash.
address settings.
● When operating, it displays LED lamps. When
Indoor unit intake Measures the intake temperature of the indoor unit when the
errors occur, the error code can be shown by the temperature indoor unit is operating. ✕ ✕
LED flash count. When an error occurs on the air conditioner unit, the operation
❇: If an indoor unit with different functionality is operating inside the Error lamp on the signal receiving unit will flash. ✕
same group, please note there may be cases when functionality
is partially disabled for batch control. Test run This operates air conditioner units in test run mode.
❇: Wireless remote controllers can only be used for a single refrig-
erant system. Ventilation Up to 16 indoor units can be connected to an interlocked system
equipment that has one LOSSNAY. ✕ ✕
❇: If you use a system controller to centrally control a group, you
will need cross-wiring between indoor units when using a wire- External By connecting the Program timer, allocate A/B2 mode for a
input/output week and control a week's schedule. ✕ ✕
less remote controller.
Also ensure there is no difference between the group setting of ❇ Some models will have different display for the air flowdirection and fan speed.
the master system controller and the cross wiring across indoor Set the air flow direction and fan speed when performing initial setting.
units when wiring and setting cross wires.

■ System example

Non- Non-
Non-polarized polarized polarized
2-wire 2-wire 2-wire
Signal Signal Signal
receiving receiving receiving
unit unit unit

Wireless Wireless Wireless


remote remote remote
controller controller controller

■ External dimension
57 PAR-FL31MA Unit:mm
PAR-FA31MA

CHECK TEST RUN

˚C 70 22.5 9.9
AM 4.8
PM

AM
PM
NOT AVAILABLE
19

ON/OFF ON/OFF
153

•Use two 24A size alkaline


batteries. Make sure you align
the battery polarities correctly.
•Remove the batteries if you do
83.5

not expect to use the controller


for a long time.
120

TEMP.
Reset
After refilling batteries,
press the reset button.
35.2

HEAT COOL
Nrm Set
4.6

9.2

55

OPEN
18
3

3- 7
PZ-52SF-E

2-5 LOSSNAY remote controller ■ Functions :Each unit :Each group ● :Each block
(PZ-52SF-E) :Each floor :Collective ✕ :Not available
Item Description Operations Display
ON/OFF Run and stop operation for a LOSSNAY unit
Switches between automatic ventilation/ vent - heat
interchange/ normal ventilation
CENTRAL INTERLOCKED Note: Operation modes vary depending on the model.
Operation mode When connecting to only models without a damper,
HEAT EX.
BY-PASS switching these models cannot be used.("NOT AVAILABLE" will
AUTO
appear in the display.)
CHECK
NOT AVAILABLE FILTER Temperature
setting
Not available ✕ ✕
Models with 2 air flow speed settings: Hi/Low
Fan speed setting When only connected to single notch models, this function is
ON/OFF disabled.

Air flow direction


setting
Not available ✕ ✕
Timer operation Not available ✕ ✕
FILTER
Individually prohibit operation of each local remote control
Permit / Prohibit function (Start/Stop, Reset filter). ✻1
local operation ✻1: When the local remote controller inactivation command is ✕
received from a master system controller, " CENTRAL " is
● Stand-alone LOSSNAY operation is possible by displayed.

commands from a centralized controller or LOSS- Indoor unit intake Not available
✕ ✕
temperature
NAY remote controller. (G-50A is a centralized
When an error occurs on the air conditioner unit, the operation
controller that supports LOSSNAY operation.) Error
lamp on the signal receiving unit will flash.

● The LOSSNAY remote controller is capable of There is no test run switch for LOSSNAY remote controllers.
Test run
changing the air flow and vent modes. Set test run on a LOSSNAY by using the test run switch on the ✻2
LOSSNAY unit. ✕
● All the wiring is cross-wiring that uses non-polar ✻2: Cancel by operating the start/stop switch after switching off
two wire system signal cables. the LOSSNAY unit test run switch.
❇ : When setting up a LOSSNAY stand-alone system or when set- Ventilation Up to 16 indoor units can be connected to an interlocked system
ting up a LOSSNAY and centralized controller system, connect equipment that has one LOSSNAY.
a power supply unit for the signal cables.
This is displayed to indicate it is being operated by an operation
❇ : It is impossible to use a LOSSNAY remote controller for LOSS- Interlocked control unit's external control terminal for an interlocked system
NAY unit that is interlocked other indoor unit (except for some operation that contains LOSSNAY units and indoor units.

models).
External The program timer (PAC-YT30ST) cannot be connected.
input/output When external ON/OFF is required, use the LOSSNAY unit's ✕ ✕
external control input.

■ System example ■ External dimension

Unit:mm

LOSSNAY LOSSNAY LOSSNAY LOSSNAY ABS


unit unit unit unit

LOSSNAY remote LOSSNAY remote REMOTE CONTROLLER


controller controller MODEL
PZ-52S F-E
INPUT VOLTAGE DC30V
0.02A
83.5

WEIGHT 0.15kg
78
120

SERIAL No.

MADE IN JAPAN KT79C117H01

ON/OFF

UP

FILTER
LOSSNAY LOSSNAY LOSSNAY LOSSNAY
unit unit unit unit Power supply unit

LOSSNAY remote LOSSNAY remote


controller controller
70 8 33
(41)

48

3- 8
PAC-YT32PTA
2-6 Program timer
(PAC-YT32PTA)

● To be set the ON/OFF schedule each 30 minutes. (2 pattern)


● To be set the effective/ineffective of schedule in each individual
days.
● To be set the set-buck temperature. (0, 1, 2, 6, 8 deg.)

SET/MONITOR MODEA/B/OFF DAY SET BACK DAILY TIMER MODEA/B

WEEKRY SETTING
ON/OFF/SET BACK

PAC-YT32PTA CLOCK TODAY DAILY SETTING

■ System example

ME remote Program
controller timer

MA remote Program Simple MA


controller timer controller

3- 9
3. System controller
PAC-SC30GRA

3-1 Group remote controller ■ Functions :Each unit :Each group ● :Each block
(PAC-SC30GRA) :Each floor :Collective ✕ :Not available

Item Description Operations Display


ON/OFF Run and stop operation for the air conditioner units ✻1

ON/OFF ✻1: Even when only a single indoor unit connected to the group remote
CENTRALLY CONTROLLED
controller is operated, the collective ON/OFF lamp will light up.
CHECK ADDRESS ON OFF ˚C FILTER
CHECK MODE Operation mode Switches between Cool / Dry / Auto / Fan / Heat.
˚C
COLLECTIVE
TEST RUN
switching ✻2: When collective operation is set, the display will show ✻2
NOT AVAILABLE
GROUP
"COLLECTIVE" in the bottom left of the LCD screen.
Operation modes vary depending on the air conditioner unit.
Auto mode is the City Multi R2 and WR2 series only.
TEMP. ON/OFF FILTER
Sets the temperature for a single group
Temperature Range of temperature setting
CHECK Cool/Dry : 19˚C - 30˚C
setting ✻3
Heat : 17˚C - 28˚C
GROUP GROUP TEST RUN Auto : 19˚C - 28˚C
REMOTE CONTROLLER
PAC-SC30GRA ✻3: When collective operation is set, the display will show
"COLLECTIVE" in the bottom left of the LCD screen.
Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low ✻4
Fan speed setting Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low
✻4: When collective operation is set, the display will show
"COLLECTIVE" in the bottom left of the LCD screen.

Air flow direction angles 100% - 80% - 60% - 40%, Swing,


● Up to 8 groups can be operated (maximum of 16 Air flow direction
setting Louver ON/OFF ✻5

units). Just by pressing switches, groups can be Air flow direction settings vary depending on the model.
✻5: When collective operation is set, the display will show
started and stopped individually, or all groups can "COLLECTIVE" in the bottom left of the LCD screen.
be started and stopped as a batch. Timer operation It is impossible to set schedules by only using this group
● Detailed settings and operations can also be remote controller.
By connecting a program timer, set 48 ON/OFF settings ✻6
made for each individual group. every 30 minutes. By loading only one pattern, it can operate
as a weekly schedule.
● All the wiring is simply done with non-polarized ✻6: If the Program timer is connected, you can
two wire signal lines. The connection is the same enable/disable timer operation for each group.
as the connection to the master system controller. Individually prohibit operation of each local remote control
Permit / Prohibit
● It supports operation of groups that can extend local operation
function (Start/Stop, Change operation mode, Set temperature,
✻7
Reset filter).
beyond one refrigerant system. Furthermore, it is ✻7: When the local remote controller inactivation command is ✕
received from a master system controller, "- CENTRALLY
possible to drive interlocked systems that use ven- CONTROLLED -" is displayed.
tilator equipment or drive ventilator equipment in a
stand-alone situation. Indoor unit intake Measures the intake temperature of the indoor unit only when
temperature the indoor unit is operating. ✕
❇: With the group remote controller, you cannot control groups
that only contain the LOSSNAY remote controller. When an error is currently occurring on an air conditioner unit, ✻8
Error
❇: It is impossible to use the group remote controller to control the afflicted unit and the error code are displayed.
✻8: This is indicated by the batch operation lamp.

K control units.
❇: When connecting to signal cables for central control, it must Test run This operates air conditioner units in test run mode.
use a power supply unit for the signal cables. Up to 16 indoor units can be connected to an interlocked system ✻9
Ventilation that has one LOSSNAY. LOSSNAY items that can be set are
equipment "Hi" "Low" "Stop". Ventilation mode switching is not possible.
✻9: When collective operation is set, the display will show
"COLLECTIVE" in the bottom left of the LCD screen.

By connecting the Program timer "PAC-YT32PTA", a weekly


External schedule can be controlled. External start/stop control and
input/output emergency stop is not supported.

3- 10
PAC-SC30GRA
■ System example

Connect to the centralized transmission line

Group remote
controller

UP

Power supply
unit
MA MA
remote remote
controller controller

Connect to the indoor/outdoor transmission line

MA MA
Group remote remote remote
controller controller controller

■ External dimension

Unit:mm
130 18

ON/OFF
CENTRALLY CONTROLLED
CHECK ADDRESS ON OFF ˚C FILTER
GROUP
CHECK MODE
˚C TEST RUN
COLLECTIVE
GROUP NOT AVAILABLE
120

83.5

46

3- 11
PAC-SF44SRA

3-2 System remote controller ■ Functions : Each unit : Each group ● : Each block
(PAC-SF44SRA) : Each floor : Collective ✕: Not available
Item Remarks Operations Display
ON/OFF Run and stop operation for the air conditioner units

Operation mode
ON/OFF Switches between Cool / Dry / Auto / Fan / Heat.
switching
COLLECTIVE CENTRALIZED TEMP. PROHIBIT
GROUP ˚F ON/OFF FILTER ✻ There are modes that cannot be selected depending on the unit.
ON OFF ˚C MODE TEMP.
1 2 3 4 5 6 7 8 9 10 AUTO MODE LOCK
10 HEATEX. NO COOL HEAT
20 BY-PASS FILTER CHECK
30
40 CHECK LIMIT TEMP The temperature can be set within the following range. Values in
parentheses are for the medium-temperature indoor unit.
Temperature
setting
Cool/Dry : 19°C~30°C 14°C~30°C
Heat : 17°C~28°C 17°C~28°C
Automatic : 17°C~28°C 17°C~28°C
( )
Fan speed setting The fan speed cannot be set.

Air flow direction setting The air flow direction cannot be set.

When set as the master, the ON/OFF, operation mode, setting


Manual operation temperature and filter sign reset operations using the local
prohibit/permit remote controllers can be prohibited.
(ON/OFF, mode change, ✻ [PROHIBIT] will appear when prohibited.
setting temperature, filter reset) Only ON/OFF and filter reset can be prohibited for the
LOSSNAY group.

● 50 groups/50 units of air conditioners can be con- Specific mode When set as the master, operation of the following modes with
operation prohibit the local remote controllers can be prohibited.
trolled. When cooling is prohibited: Cooling, dry, automatic can not be chosen.
(Cooling prohibit, heating
· Up to 50 groups/50 units of air conditioners can be prohibit, cooling/heating prohibit) When heating is prohibited: Heating, automatic can not be chosen.
When cooling/heating is prohibited: Cooling, dry, heating, automatic can not be chosen.
operated with one remote controller.
● Operation status displayed on easy-to-read LCD Room temperature display The room temperature cannot be displayed. – ✕
· The group currently operating can be seen at a The details of the currently occurring error are displayed with
glance with the operation status display for each Error display the address.

✻ The address may not be displayed depending on the details
group. of the error.
● Simple remote controller limited to basic opera-
tions. Two patterns of weekly schedules can be operated with
Schedule operation the Schedule timer.(PAC-YT34STA)
· The only operations required for the air conditioner ✻ The schedule validity can be set for each group.
are "ON/OFF", "Operation mode changeover",
"Temperature setting" and "Prohibit operation by Group operation of only the free plan LOSSNAY is possible.
Ventilation
✻ The operation mode of these groups is automatic ventilation,
(independent)
local remote controller", so anyone can easily ventilation with heat exchanger and normal ventilation.
operate the unit.
· Using collective control from the system remote The LOSSNAY will run in interlock with the operation of indoor
Ventilation unit.
controller, operation mode settings using the local (interlocked) ✻ The fan rate and mode cannot be changed. The LED will turn
ON during operation after interlocking.
remote controllers can be prohibited.
(Operation mode limit function)

● Schedule operation is available


· Groups of air conditioners are available for opera-
tion at a set schedule using the Schedule timer
(PAC-YT34STA).
● Independent LOSSNAY operation is possible
· LOSSNAY units can be grouped the same as the
Central remote controller and ON/OFF remote
controller.
· "Automatic ventilation", "Normal ventilation" and
"Ventilation with heat exchanger" can be switched
from the system controller.

3- 12
PAC-SF44SRA
■ System example

System UP

remote
controller
Power
supply
unit

MA remote MA remote
controller controller

LOSSNAY LOSSNAY LOSSNAY

LOSSNAY
LOSSNAY remote
remote controller controller

■ External dimension

Unit:mm
(Front view) (Side view)
130 2 18.5
(Rear view)
83.5
120

19 46

3- 13
PAC-YT34STA

3-3 Schedule timer ■ Functions : Each unit : Each group ●: Each block
(PAC-YT34STA) : Each floor : Collective ✕: Not available
Item Details Operations Display
Unit control 50 units/50 groups (Maximum 16 units connected in one group)

Schedule control One week


ON/OFF
MONITOR
WEEKLY SET
PATTERN Sun Mon TueWed Thu Fri Sat TIMER OFF ON/OFF operations can be carried out collectively or for each
COLLECTIVE ON/OFF group.
PROH. PERMIT
GROUP
OPERATION
SET TEMP.
ON/OFF
Operation
ON ˚F
MODE
˚C
ON CHECK
OFF TEMP. Timer reset The timer setting details can be disabled collectively

ON/OFF
Setting COOL/HEAT
details Room temperature setting (19°C to 28°C)
Operation prohibit (ON/OFF, operation mode, setting temperature)
Schedule
Number of setting patterns: Ten (no setting + nine patterns)
function Number of (Operation for a week can be set by selecting one of ten
settings patterns for each day.)
Number of operations: Up to 16 operations can be set in one pattern

Time setting unit The item can be set in five-minute units

Current time and day

Display Error state


● The weekly schedule of up to 50 groups/50 units Unit operation state ✕
can be controlled with one schedule timer.
The following can be input with the level signals or pulse signals.
● The weekly schedule of up to ten patterns (no set- External input Level signal: "Emergency stop input" or "Collective ON/OFF"
(Timer connection, Pulse signal: "Collective ON/OFF" or "Local remote controller
ting + nine patterns) is available for setting. emergency stop prohibit/permit"
● "ON/OFF", "Operation Prohibit", "COOL/HEAT" input, etc.) One input can be selected from those above.
and "Set Temperature" can be scheduled with up External output
"ON/OFF" and "error/normal" are output with the level signal.
to 16 settings in one pattern. (Error output,
✻ The optional output cable is required.
operation output)
● It can be connected to the center control transmis-
sion line or to the indoor/outdoor transmission line Indoor/outdoor transmission line: Connectable
without the power supply unit (PAC-SC34KUA). It Connection position Central system transmission line: Connectable (Optional power
supply unit (PAC-SC34KUA) is needed.)
is nonpolar 2-wire.
● It can be interlocked with a building management
system using the external input/output managing
function.
An error unit address and error code appear on
the display.
(✻) Use in combination with other system con-
trollers.

3- 14
PAC-YT34STA
■ System example

System UP

remote
controller LOSSNAY
Power supply
unit for ME remote
transmission
line controller

Schedule timer

MA remote Simple
controller remote controller

■ External dimension

Unit:mm
(Front view) (Side view)
130 2 18.5 (Rear view)
83.5
120

19 46

3- 15
PAC-YT40ANRA

3-4 ON/OFF remote controller ■ Functions : Each unit : Each group ● : Each block
(PAC-YT40ANRA) : Each floor : Collective ✕: Not available
Item Description Operations Display

ON/OFF Run and stop operation for the air conditioner units

Operation mode
switching
Not available ✕ ✕

Temperature setting Not available ✕ ✕

Fan speed setting Not available ✕ ✕

Air flow direction setting Not available ✕ ✕


Manual operation
prohibit/permit Compatible only with external input. ✕ ✕
(ON/OFF, operation mode,
setting temperature, filter reset)

Specific mode
operation prohibit
(Cooling prohibit, heating Not available ✕ ✕
prohibit, cooling/heating prohibit)

Room temperature display Not available ✕


● 16 groups/50 units can be controlled.
LED flashes during failure.
· Up to 16 groups/50 units can be operated with Error display (The error code can be confirmed by removing the cover.)
one ON/OFF remote controller.
Schedule operation Not available ✕ ✕
· A general-purpose interface is available for con-
Ventilation operation Group operation of only LOSSNAY units possible.
trol, so general devices can also be turned ON (independent) ✻ Only ON/OFF of group.
and OFF.
The LOSSNAY will run in interlock with the operation of indoor
● Just press a switch to start. Ventilation operation unit.
· All of the units can be started and stopped by (interlocked) ✻ The fan rate and mode cannot be changed. The LED will turn
ON only during operation after interlocking.
pressing the main switch, and each unit in the
External output
group can be started and stopped with individual (Error output,
"ON/OFF" and "error/normal" are output with the level signal.
✻ The optional output cable is required.
switches. operation output)
· A general-purpose interface is available for con- Indoor/outdoor transmission line: Connectable
trol, so general devices can also be turned ON Connection position Central system transmission line: Connectable (Power supply
unit (PAC-SC34KUA) is needed.)
and OFF.
● LED flashing during failure.
· If any error should occur in the air conditioner, its
details can be confirmed easily with the flashing
LED. The LED also indicates whether each group
is running or stopped.
● Interlock operation with external system possible.
· It can be flexibly interlocked with a card reader,
fire alarm system or building management sys-
tem, etc., using the incorporated external
input/output function.
● Flexible group setting.
· The groups can be easily configured, so the
group pattern can be freely set according to the
layout.
· The ON/OFF remote controller can be connected
at the indoor/outdoor transmission line with out
the power supply unit.

3- 16
PAC-YT40ANRA
■ System example

Free plan
LOSSNAY
LOSSNAY
MA remote remote
controller controller
ON/OFF
remote
controller

MA
remote M-NET compact
controller remote controller

■ External dimension

Unit:mm
(Front view) (Side view)
18.0
130 (Rear view)
83.5
120

46
19

3- 17
3-5 Centralized controller ■ Functions
G-50A

:Each unit :Each group ● :Each block


3-5-1 G-50A :Each floor :Collective ✕ :Not available
Item Description Operations Display

ON/OFF Run and stop operation for the air conditioner units
ON/OFF Switches between Cool / Dry / Auto / Fan / Heat.
TEST RUN
ON/OFF MODE FAN SPEED (Group of LOSSNAY unit : automatic ventilation/ vent - heat
1 2 3 GROUP
SELECT Operation mode interchange/ normal ventilation)
AIR

4 5
DIRECTION
6
BACK
SCREEN
switching Operation modes vary depending on the air conditioner unit.
TEMP. CLOCK/
PATTERN VENTILATION
Auto mode is the City Multi R2 and WR2 series only.
7 8 9 INS.

CENTRAL CONTROLLER
REMOTE
PROHIBITION
TIMER
MODE RESET
Range of temperature setting
ENTER
0
G-50A DEL.
Temperature Cool/Dry : 19˚C - 30˚C
setting Heat : 17˚C - 28˚C
Auto : 19˚C - 28˚C
✻ Range of temperature settings vary depending on model.

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Fan speed setting
Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low

Air flow direction Air flow direction angles 100% - 80% - 60% - 40%, Swing, ✻1
● Adds a web server function (optional) to the con- setting ✻1: Louver cannot be set.
Air flow direction settings vary depending on the model.
ventional central controller, thus allowing central
Timer operation For one day, you can set start/stop three times and you can set
monitoring of air-conditioners using browser soft- enable/disable three times. ✻2
ware✻ on a PC. For a week's schedule, you can store three start/stop patterns
and one enable/disable pattern.
Use of a public telephone line allows long-distance ✻2: When the timer is set, "Timer enabled" is shown on the
monitoring and operation, as well as central control operation setting screen of the LCD.

of air-conditioners in two or more buildings. Individually prohibit operation of each local remote control
Permit / Prohibit function (Start/Stop, Change operation mode, Set temperature,
(❇) Internet Explorer Ver.5 or later. Microsoft® Internet local operation ✻3
Reset filter).
Explorer is a registered trademark of Microsoft ✻3: When the local remote controller inactivation command is
Corporation US in the United States of America and received from the master system controller, "Disabled"
appears in inverted display on the operation setting screen.
other countries.
Indoor unit intake Measures the intake temperature of the indoor unit only when
temperature the indoor unit is operating. ✕
● Incorporation of system expansion software (eg
'Proportional Power Distribution', 'Energy-saving When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
Operation', and 'Yearly Schedule Setting')✻1 allows ✻4: When an error occurs, the LED flashes. The operation ✻4

addition of a variety of functions required for control Error monitor screen shows the abnormal unit by flashing it. The ✕
error monitor screen shows the abnormal unit address,
of building air-conditioning. error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit
address, error code and source of detection.
● A maximum of 50 indoor units may be monitored
Test run This operates air conditioner units in test run mode.
and operated from one G50, and the incorporation
The interlocked system settings can be performed by the master
of multiple central controllers in a system network Ventilation
system controller.
equipment
allows a maximum of 2000 indoor units to be oper- When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
ated and managed from a PC. "Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
● The use of 'Energy-saving Operation' software (✻1) and "Automatic ventilation".
(optional) allows the temperature setting to be By using accessory cables you can set and monitor the
changed automatically (✻2) in consideration of the External following.
input/output Input
temperature in the vicinity of the air-conditioner, By level signal: "Batch start/stop", "Batch emergency stop"
✻5 ✻5
thus allowing energy-saving air-conditioning without By pulse signal: "Batch start/stop", "Enable/disable local
remote controller"
loss of comfort. Output
"Start/stop", "Error/Normal"
Energy-saving operation is also possible using ✻5: Requires the external I/O cable (PAC-YG10HA-E) sold
rotating ventilation and air-conditioning perfor- separately.
mance saving operation.

● If a fault occurs in the air-conditioner, fault details


are sent to a specified email address (✻3) (option-
al).
This ensures security of operation while no opera-
tor is present (eg holidays, night-time).

✻1 ('Proportional Power Distribution', 'Energy-sav-


ing Operation', and 'Yearly Schedule Setting')
expansion software scheduled for release.
✻2 The system considers the intake temperature
and temperature setting at pre-set intervals in
order to set the temperature slightly high when
cooling and slightly low when heating.
✻3 Notification may be delayed in some cases (eg
out of transmission range, service provider
problems).

3- 18
■ System example

G-50A
LAN
M-MET

12V DC
Centralized controller
G-50A
UP

POWER SUPPLY UNIT


MODEL
PAC-SC50KUA
POWER RATING

WEIGHT 2.11kg
SERIAL No.
MITSUBISHI ELECTRIC CORPORATION

Power supply unit


PAC-SC50KUA
ME remote ME remote
controller controller

LOSSNAY unit

ME remote LOSSNAY remote


controller controller

■ External dimension

Unit:mm
300
25

ON/OFF
120

70

CENTRAL CONTROLLER
G-50A

3 19 57

220
Installation plate
288
280
138
47

9 CN2 1 1 CN1 5 RS232C 12VDC GND S B A


21

POWER M-NET Ethernet


13

83.6
106
83.5
28

91 47

3- 19
■ External input/output usage method
G-50A

1. External signal input function


✻ External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (DC12V or DC24V) contact signal from an external source.
(Select with the function select setting)
Function
No External signal input function Remarks
No.6 No.7
1 Do not use external input signal OFF OFF
(factory setting)
2 Execute emergency stop/normal OFF ON The local remote controller ON/OFF operations, and the
with level signal controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
3 Perform ON/OFF with level signal ON OFF The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
4 Perform ON/OFF, prohibit/enable ON ON Set the pulse width while the contact is ON to 0.5 to 1 sec.
with pulse signals.

(2) Level signal and pulse signal (DC12V or DC24V)


(A) Level signal (B) Pulse signal
(Example) for ON/OFF
Contact ON
0.5 to 1 sec
Contact OFF
Contact ON
Stop Run Stop Signal 1 (run)
Contact OFF

Contact ON 0.5 to 1 sec


Contact ON
Contact OFF Signal 2 (stop)
Normal Emergency stop Normal Contact OFF
OFF ON OFF

✻ The prohibit/enable input is the same.

(3)External input specifications


CN2 Lead wire Emergency stop/normal level signal ON/OFF, level signal ON/OFF, prohibit/enable pulse signal
No.5 Orange Emergency stop/normal input ON/OFF input ON input
No.6 Yellow Not used Not used OFF input
Local remote controller operation
No.7 Blue Not used Not used
prohibit input
Local remote controller operation
No.8 Gray Not used Not used
enable input
No.9 Red External DC source “+”

(A) For level signal


➀ When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF.
➁ When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.

(B) For pulse signal


➀ Even if the ON signal is input during ON, the status will remain ON.
➁ If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
➂ Set the pulse width (contact ON time) to 0.5 to 1 sec.

3- 20
(4)Recommended circuit example

G-50A
(A) For level signal

CN2 CN2 Power supply(✻1)


Red
9 9 Red (DC12V or DC24V)
X1
5
Orange X1 Orange
Run/stop or 5 X1
X1 Run
6 Emergency stop 6 Yellow X2 Stop
X2
7 7 Blue Y1 Y1 Prohibit
8 Power supply(✻1) 8 Purple Y2 Enable
Y2
(DC12V or DC24V)
Max.10m Max.10m
This unit This unit

➀ The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
➁ The connection cable can be extended up to 10m. (Use a 0.3mm2 or larger wire.)
➂ Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

2. External signal output function


✻ External signal output requires the external I/o adapter (Model: PAC-YG10HA-E) sold separately.
(1) External output
When one or more air conditioners are running, the “ON” signal will be output and if a malfunction occurs in one or more air
conditioners, the “Malfunction” signal will be shown.

(2)External output specifications


CN 2 Lead wire Details of each terminal ➀ " ON" signal and " Malfunction" signal will
No.1 Green Common (External ground) both be output.

No.2 Black ON/OFF


No.3 Brown Malfunction/normal
No.9 Red Common (External power supply) (✻1)

(3)Recommended circuit example

CN2 Diode(✻2) Use Z1 and Z2 relays having the following specifications.


Z1 Operation coil
Black Rated voltage :DC12V,DC24V
Brown Power Consumption : 0.9W or less
(✻1)Prepare a power supply separately according to the
Z2
relay being used. (DC12V or DC24V)
(✻2)Always insert a diode on both ends of the relay coil.
Power (✻1)
Supply
Green

Max.10m
L1:Run display lamp
L2:Malfunction display lamp

➀ Each element will turn on while ON operation or a malfunction occurs.


➁ The connection cable can be extended up to 10m.
➂ The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CAUTION Peel off the label

When connecting the external input/output cables to


connector CN2 on the controller, Peel off the label on
the controller connector section.
Ethernet M-NET POWER

A B S 12VDC GND RS232C 1 CN1 5 1 CN2 9

3- 21
3. LAN connection function
G-50A

When using the LAN connection function, connect the LAN cable to the Ethernet connector of this device.
✻ Procure the LAN cable at the site, and use an enhanced category 5UTP cable.
✻ For a description of the IP address setting method, refer to Installation Manual.
✻ LAN is 10 BASE-T Specification.

Ethernet M-NET POWER

A B S 12VDC GND RS232C 1 CN1 5 1 CN2 9

NOTE
✻ Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-
NET transmission line.
✻ When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
✻ When connecting an LAN connector, space for the connector and wiring is required. Provide this space at
this unit and the rear of the electric box. Refer to Installation Manual.
✻ When the G-50A cover is opened, the LAN status lamp and LAN changeover switch are accessed. For de-
tailed information, refer to sections 3-2 and 5-9 of the Instruction Book.

4. RS232C connection function


When using an RS232C port, connect the cable to the RS232C connector of this device.
✻ The RS232C cable is procured at the site, and the connector of the cable that connects to this device is a D-
Sub9pin (female). RS-232C cable is maximum 15m.
✻ When using an RS-232C cable, to suppress the noise radiated from the RS-232C communication line, always
procure the option Model PAC-YG11FC-E and install it so that the RS-232C communication line is inserted
near the D-sub connector of the G-50A.

Ethernet M-NET POWER

A B S 12VDC GND RS232C 1 CN1 5 1 CN2 9

Remove the cap

NOTE
✻ When installing G-50A to the electric box, the D-sub connector does not pass through the conduit.
In this case, use a type that can be separated from the D-sub connector cable. Remove the D-sub connector
from the cable, pass the cable through the conduit, connect the cable to the D-sub connector using solder,
etc., and then connect the D-sub connector to this unit.
✻ When connecting the RS-232C connector, a connector and wiring space is required. Provide this space at
this unit and the rear of the electric box. Refer to Installation Manual.
✻ Wire the RS-232C before installation, and wire up to the body by the same method as wiring the M-NET
transmission line.

3- 22
■ Browser screen

G-50A
Condition List (Overview) Condition List (Block)

Operation Malfunction List

Malfunction Log Weekly Schedule

3- 23
TG-2000A

3-5-2 TG-2000A
(1) Example of Basic System Configuration.
Single-phase 200V

Charge Input
license G-50A

Web Power feed unit for


monitor transmission line
license Single-phase 200V
UP

POWER SUPPLY UNIT


MODEL
PAC-SC50KUA
POWER RATING

WEIGHT 2.11kg
SERIAL No.
MITSUBISHI ELECTRIC CORPORATION

Schedule
license

Compatible with TG-2000A Ver. 4.10 and higher


Indoor unit system ✻ The electric amount count software or separately
3-phase 200V watt-hour meter procured parts must be used with the designated PLC.
Indoor unit
power source
watt-hour meter Indoor unit system
watt-hour meter
Outdoor unit system
watt-hour meter Indoor unit
watt-hour meter

RS-485 Outdoor unit system


RS-232C watt-hour meter
Converter
PLC (with electric amount count
Uninterruptive Central control software)
power supply (UPS) personal computer
TG2000A
Central control
Uninterruptible
power supply (UPS) personal computer
TG-2000A

Integrated Integrated centralized control


centralized control software installation
software installation

The TG-2000A can realize the following functions


using the G-50 option (license).
❈ Operation/monitor
❈ Annual/weekly schedule
❈ Charge
❈ Energy saving ✻1
❈ Peak cut ✻1
✻1: Compatible with TG-2000A Ver. 4.10 and
higher, G-50A Ver. 2.50 and higher.
■ Main features of TG-2000A
1 Up to 2000 indoor units (40 G-50A units) can be operated and monitored simultaneously.
2 The air-conditioner layout can be displayed on the screen, making control and operation easier.
3 The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be
saved in the weekly schedule.
4 Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment
percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment
function, and can be output as a CSV format file. ✻ Power apportionment charging is not possible with the old model, A control or K control.
Charging without WHM : The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
RS-485 WHM charging : The RS-485 WHM value is automatically tabulated to calculate the air-conditioning charges.
PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the air-
conditioning charges.
5 Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and
"performance save operation (60% to 90%)" functions.
Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count
software.
6 Defrost protection operation is possible with schedule settings. ✻1
7 General equipment can be operated and monitored. ✻2
✻1: Compatible with TG-2000A Ver. 4.10 and higher, G-50A Ver. 2.50 and higher.
✻2: Compatible with TG-2000A Ver. 4.30 and higher, G-50A Ver. 2.50 and higher.

3- 24
TG-2000A
(2) List of functions
The data for each G-50A can be grouped and used to control the operation of up to 2000 units in floor or block units, etc.,
from the personal computer screen. By using a PLC or a watt-hour meter, the power rate can be apportioned, energy saving
control can be executed, and other general equipment can be controlled.

List of integral software functions


G-50 license

Web monitor

Charge

Schedule

Energy saving

(peak cut)
Energy saving
Item Details

ON/OFF The units can be turned ON and OFF for all floors or in block, floor or group units. V
The general equipment can be turned ON and OFF.
V
(✻ A PLC and the general equipment control PLC software required.) ✻2

Operation modes The operation mode can be switched between COOL, DRY, FAN, AUTO and
HEAT for all floors or in block, floor or group units. V

Temperature setting The room temperature can be set for all floors or in block, floor or group units.
Set temperature range COOL / DRY : 19˚C to 30˚C
HEAT : 17˚C to 28˚C V
AUTO : 19˚C to 28˚C
❇ Depend on unit type

Fan speed The fan speed can be set to four stages for all floors or in block, floor or group units. V
Air direction The air direction can be set in four vertical directions or to swing for all floors or in block,
V
floor or group units. (The selectable air direction differs according to the model.)

Interlocked unit ON/OFF If there is an interlocked unit (LOSSNAY), the unit can be turned ON (strong/weak) or OFF for all floors
V
(LOSSNAY) or in block, floor or group units. (Note that the ventilation mode cannot be selected for interlocked units.)

Local operation The items for which operation with the local remote controller are to be prohibited can be selected for
prohibit all floors or in block, floor or group units. (The items that can be prohibited are ON/OFF, operation mode, V
set temperature and filter sign reset.)

Annual / weekly The annual/weekly schedule function can be used by registering the license.
V V
schedule Two settings, such as seasonal settings for summer and winter, can be saved.

Power rate By registering the G-50A unit license number, the power rate apportionment percentage data for
apportionment charging each indoor unit can be output in CSV format. The power rate for each tenant can be easily V V
(power rate manual input) calculated by having each user input the power rate manually.

Power rate An RS-485 watt-hour meter is connected to calculate the air-conditioning charges based on the
apportionment charging amount each tenant's air-conditioner has operated. Two charging rates can be applied per day.

By using a PLC (with electric amount count software) and a watt-hour meter with pulse transmitter, V V
the air-conditioning charges can be calculated based on the amount each tenant's air-conditioner has
operated. Up to five charging rates can be applied per day. ✻1

History Up to 3000 items for the error history and up to 10000 items for operation history can be saved.
V
Each history file can be output as a daily report or monthly report in CSV format.
The operation history consists only of the operations carried out with the TG-2000A, and is limited to some limited operation items.

Operation time monitor The cumulative operation time of each indoor unit can be viewed or output as a CSV format file.
(This function is valid only when the charging function license is registered.) V V

Filter sign display Automatic display of the filter sign can be disabled. (System batch.)
V
mask In this case, the filter sign state is confirmed with manual operations.

Energy saving Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation
V V
control ✻1 changeover" and "performance save operation" functions.

Energy saving Energy saving operation matching the amount of power in use is possible.
V V
(peak cut) ✻1 (PLC (with electric amount count software) and watt-hour meter with pulse transmitter are required.)

Frost protect ✻1 Heating from 12˚C and higher can be set using the schedule. V
Set temperature limit ✻1 The set temperature lower limit can be set for cooling and the upper limit for heating. V

✻1: Compatible with TG-2000A Ver. 4.10 and higher, G-50A Ver. 2.50 and higher.
✻2: Compatible with TG-2000A Ver. 4.30 and higher, G-50A Ver. 2.50 and higher.

3- 25
TG-2000A

(3) Screen images

Weekly schedule screen

Floor screen

Annual schedule screen

Block screen

All floor screen Operation setting screen

Air-conditioning charge screen

3- 26
TG-2000A
(4) Requirements (system recommendations)
We recommend the following software and hardware when using this application (TG-2000A).
Item Requirement Recommended
PC PC/AT interchangeable machine Operation check completed, using IBM, COMPAQ,
and DELL
CPU Within 1000 indoor units : Pentium 4 2.8GHz or faster
Pentium 4 1.8GHz or faster
1001 indoor units or over :
Pentium 4 1.8GHz or faster
(Case of temp, trend use : 2.8GHz or faster.)
Memory 128MB or more (In Windows XP : 256MB or more) 256MB or more
HDD 6GB or more (2GB or more of C drive free 4GB or more of C drive free space necessary
space necessary) When using the trend function, the drive used for au-
tomatic output must have the following free space ac-
cording to the number of groups.
200 groups = 2GB, 500 groups = 5GB,
1000 groups = 10GB, 2000 groups = 20GB
Storage device FDD, CD-ROM drive Devices other than those shown at the left may also
be installed.
Resolution 1024 ✕ 768 or higher, 65536 colors or more
Serial port 1 port or more Required when using RS-485 communication WHM
LAN Internal LAN (10/100 Mbps) ✻1
OS Windows XP Professional English version only
Windows 2000 Professional ✻ Personal computer must support each OS.
Service Pack 2 and above
Other Computer must be dedicated for this use
(TG-2000A).
✻1 Purchase the option, or use the equipment recommended for the personal computer when purchasing the
personal computer.

(5) Compatible Units


The TG-2000A has two main functions: air conditioner controller and cost accounting. However, not all functions are
available with all air conditioners.
Table: Compatible units and function list ( : supported, : Certain restrictions apply, ✕ : Not supported)

Function Control/ Charging (Billing)


Charging (Billing) with WHM
Model Maintenance without WHM

Y series ✻1
Super Y series ✻1
R2 series ✻1
WR2 series ✻1
WY series ✻1
Multi S series ✻1
Free plan Indoor unit ✻1
Free plan LOSSNAY ✕ (A separate watt hour meter is
required. Billing is done with
watt-hour units)
OA processing unit ✕ (A separate watt hour meter is
✻2 required. Billing is done with
watt-hour units(Only the fan part))
“A” control type ✕ (A separate watt hour meter is
(Adapter required) required. Billing is done with
watt-hour units)
“K” control type ✕ (A separate watt hour meter is
(Adapter required) required. Billing is done with
watt-hour units)

✻1 : Can be calculated for each charging block.


May not be available with some older models.
✻2 : When used with IC attributes, it becomes the same as an indoor unit and billing is possible.

3- 27
3-5-3 MB-300
MB-300

Example

Serial Gateway
interface unit unit
10V
TRANSMISSION LINE
MAIN-BUS

TB1
B1, B2:DATA LINE
S: SHELD WIRE

L N
220V-240V ~/N
UP
UP
S

TB4
B1 B2
RS-232C-2

30V
MAIN-BUS M-NET TRANSMISSION
TB2

A B S

A,B: DATA LINE


10V S: SHILD WIRE
TRANSMISSION LINE LINE
RS-232C-1

S
TB4

B1 B2
TB1

B1,B2:DATA LINE
S: SHILD WIRE
L N
220-240V ~/N

SERIAL INTERFACE UNIT


MODEL
IFU-1000SA
INPUT VOLTAGE 220-240V ~/N50Hz
POWER CONSUMPTION MAX 6W
MASS 6

UP

Remote Remote
Power controller
supply controller
unit

Remote Simple remote


controller controller
Gateway
unit
TB1
L N
220V-240V ~/N

UP
30V
MAIN-BUS M-NET TRANSMISSION
TB2

A B S

A,B: DATA LINE


10V S: SHILD WIRE
TRANSMISSION LINE LINE
S
TB4

B1 B2

B1,B2:DATA LINE
S: SHILD WIRE

UP

Remote
Power supply controller
unit

Remote Remote Remote


controller controller controller

● Main features of MB-300 system


✻ The air-conditioner can be centrally controlled from the building control system by connecting the building control
system and air-conditioner with serial communication (RS-232-C).

3- 28
1. MB-300

MB-300
■ Functions
Functions of main controller
<Standard functions>
Function MB-300 Remarks

Separation of operat- The exact nature of operation depends on the specification of the building management
ing window system.
Password for mainte-
nance window
The building management system is capable of performing ON/OFF operation by group
ON/OFF unit.
The building management system is also capable of monitoring ON/OFF status.

Operation The building management system is able to switch and monitor operation modes (cool,
mode heat, fan, dry) by group unit.

The building management system is able to set and monitor the temperature by group
unit.
Operation & setting

Set
temperature Set temperature range (in 1˚C unit)
COOL/DRY 19˚C - 30˚C HEAT 17˚C - 28˚C
Monitoring

Air speed Operation cannot be performed by the building management system.

The building management system is capable of setting and monitoring the inactiva-
tion/activation of local remote controller operation by group unit.
Remote controller
When an inactivation has been set, operation by the local remote controller is disabled
prohibit / permit
and only operation by the building management system is possible.
It is possible to individually disable/enable operation functions (ON/OFF, operation
mode, temperature) of the local remote controller.

Abnormality The building management system keeps track of error occurrence. It keeps track of the
monitor error code and the unit address of the unit from where there error is occurring.

Room The room temperature is monitored by monitoring requests from the building manage-
temperature ment system.
monitor

Calendar function
Control

The calendar and schedule function vary depending on the specification of the building
Scheduled management system.
ON/OFF control
The power save amount is totaled for each unit by request from the building manage-
Measurement

ment system.
Operation time The total count is calculated at the 15 and 45 minute mark every hour. The total count
accumulation will increase until 999999 and when the count exceeds this number, it will loop and
start at 0.
This counter can also be freely preset by the building management system.

Abnormality
history
Record

Operation history Recording varies depending on the specification of the building management system.
Daily and monthly
reports
Control

Grouping The monitor display and the operation method varies depending on the specification of
the building management system.

Plane image setting


Application

(CRT display)

Input operation

Summer time Daylight savings varies depending on the building management system clock function.

3- 29
2. Basic configuration
MB-300

■Basic configuration

Building RS-232C
management Trans. bus Air conditioners (Big-Y series)
system Command for air cond
Main bus (M-NET) Trans.bus in air cond
Main controller Serial Control Outdoor Indoor
(Man-machine I/F) interface gateway unit unit
Monitor
Remote
Trans.wire
controller
power supply
unit Indoor
UPS
unit
(separate procurement) Centralized ✻1
✻1 Remote
controller ✻1 controller
✻2

Deliverable equipment list


Description Function

Main controller Man-machine device to monitor, operate, and record air conditioners

Serial I/F Interface for host system to exchange comm. data with MELANS main bus

Control gateway Exchanges comm. data between MELANS main bus and air-cond. transmission bus

Centralized Centrally controls each group for backup when host system cannot control M-NET
controller units due to trouble
Trans. wire Provides DC power to air-conditioner transmission bus to communicate each unit connected
power supply unit to air-conditioner transmission bus

Remote controller Operates and monitors the Y, R2, Super-Y series air conditioners

Notes ✻1 Continued to similar organization (omitted)


✻2 Adding gateway board enables extension of air conditioners. G/W = max.20 units

Figure 1. 2 Restriction on wiring


Building Air cond Air conditioners (Big-Y series)
management interface board Gateway board Trans. bus
system for air cond Trans.bus in air cond
Main bus (M-NET)
Main controller Serial Control Outdoor Indoor
(Man-machine I/F) interface gateway unit unit
Max. 15m

Trans.wire Remote
power supply controller
unit
Total length of transmission Indoor
wire is up to 500m unit
✻1
Centralized Remote
controller ✻1 controller

The furthest length of transmission


✻1
wire is up to 500m

Notes ✻1 Continued to similar organization (omitted)

3- 30
3. Serial Interface unit

MB-300
(IFU-1000SA)
■ Specification
Source power Input voltage AC220V~AC240V, 0.1A(Maximum loading) / 50Hz,
Single-phase
Fuse: 2.0A Time-delay type (IEC-127-2 S.S.3)

MAIN-BUS transmission line ; AMI signal


Interface condition for RS-232C transmission line ; V.24/V.28
transmission line Pin Arrangement 1: FG, 2: SD, 3: RD,
4: RS, 5: CS, 6: DR,
7: SG, 8: CD, 20: ER
Environmental Temperature Operating 0~40˚C
condition Non operating 0~70˚C
Humidity 30~90%RH(No condensation)
Dimensions 380(High) ✕ 400(Width) ✕ 59.2(Depth)

Weight 3.6kg

■ External dimension

400 59.2
280 Unit:mm
10V
TRANSMISSION LINE
MAIN-BUS
B1, B2:DATA LINE
S: SHELD WIRE

UP
S

TB4

185
B1 B2

340

380
RS-232C-2

180
RS-232C-1

TB1
L N
220-240V ~/N

SERIAL INTERFACE UNIT


MODEL
IFU-1000SA
INPUT VOLTAGE 220-240V ~/N50Hz
POWER CONSUMPTION MAX 6W
MASS 6

3- 31
■ Parts prepared at site
MB-300

Please prepare the following parts before installation of the unit.


Preparation parts Specification
Unit fixing screw M4 screw ✕ 4 pcs
Please prepare the power cable complied with your applicable technical standard in consider with
Power cable
power requirement of the unit.
Protective earth cable
✻Recommend type; ø1.5mm ~ ø2.0mm
(H03VV-F, H03VVH2-F, H05VV-F, H05VVH2-F2)
Main power switch Qty. : 1 pc
(Circuit breaker) Type : 250VAC Single-phase 50Hz 3A
✻Recommend type; CP30-BA series (MITSUBISHI ELECTRIC) or equivalent.
Transmission cable 1. MAIN-BUS transmission line:
Sheathed vinyl cords or cable which comply with the following specification or equivalent.
CPEVS ø1.2mm ~ ø1.6mm
CVVS 1.25mm2 ~ 2mm2
✻CPEV; PE insulated, PCV jacketed shielded communication cable
✻CVVS; PVC insulated, PVC jacketed shielded control cable
2. RS-232C transmission line:
Please prepare the RS-232C cable which comply with the pin arrangement in “Specification”.
NOTE Cable length; There is a limitation for the transmission line.
Please refer to section “System limitation”.

3- 32
4. Gateway unit

MB-300
(GW-50A)

■ Specification

Source power Input voltage AC220V~AC240V ; 0.1A/50Hz


requirement Single-phase

Fuse : 2.0A Time-delay type (IEC-127-2 S.S.3)

Interface condition MAIN-BUS transmission line ; AMI signal


for transmission line M-NET transmission line ; DC30V+AMI signal

Temperature Operating 0~40˚C


Environmental condition
Non operating 0~70˚C

Humidity 30~90%RH(No condensation)


Dimensions 340(Height) ✕ 360(Width) ✕ 59.2(Depth)

Weight 3.2kg

■ External dimension
360 59.2
240 Unit:mm

TB1
L N
220V-240V ~/N

UP
165
300

340
30V
MAIN-BUS M-NET TRANSMISSION
TB2

160
A B S

A,B: DATA LINE


10V S: SHILD WIRE
TRANSMISSION LINE LINE
S
TB4

B1 B2

B1,B2:DATA LINE
S: SHILD WIRE

3- 33
LMAP02-E

3-6 Air conditioner interface


(LMAP02-E)
Item
● Achieve an open network by using LONWORKS. Request On/Off
The demand is growing for open network systems that
Request Mode
cater for demands such as the ability to freely select
Setpoint from network(Both cool and heat)
the facility equipment that will connect to the building
management system regardless of maker or demands Operation Request Fanspeed
to cut back on the interface kit or gateway that links the Request Local Prohibit On/Off
building management system with the facility equip- Request Local Prohibit mode
ment. By using LONWORKS, Mitsubishi Electric has Request Local Prohibit SetPoint
achieved an open network for operation information at Request All Off
the remote controller level for the multiple air condition- On/Off run state
er units used in a building.
Mode state
● This has created the potential for system architec-
Setpoint state(both cool and heat)
tures that require simpler design and reduced
labor cost. FanSpeed state
By first making the functional profile (protocol specifi- Monitor Thermo On/Off state
cation) open, the onsite system integrators can enjoy Temperature state of indoor
design freedom. Furthermore, because LONWORKS Alarm state
provides a means for each facility equipment to con- Local Prohibit On/Off state
nect to a single network, you can cut back on the Local Prohibit mode state
wiring labor cost as your system will require less
Local Prohibit SetPoint state
wiring.
● One LM ADAPTER unit can connect up to 50
indoor units.
Using a single LONWORKS adapter (LM ADAPTER),
you can connect up to a maximum of 50 indoor units.

■ System example

LMAP

Building management system

Protocol : LONWORKS

LMAP

Lighting

Elevator

By assembling a network based on the commercially sold LONWORKS, it is possible to design


your building's control system to use one network for operating the air conditioning and lighting
etc. It also means that you will be able to easily add facility equipment with reduced change to
the infrastructure, less wiring and less labor.

3- 34
LMAP02-E
■ Environment specification

Item Description

Connected Equipment MITSUBISHI ELECTRIC Multiple split type air conditioners CITY MULTI
Split-type air conditioners Mr.SLIM
Heat recovery ventilators LOSSNAY
(✻For details of the connected models,please contact the dealer.)
Number of Units LM-AP can control 50 indoor units (including LOSSNAY)
Neuron CHIP TMPN3150 (10MHz)
Network Transceiver FTT-10A (Free Topology 78kbps)
Average communication capacity 2.5 inputs/second
Performance
Peak communication capacity 50 inputs/second (for one second)
✻ The proper communication is not obtainable when communication intervals exceed its performance, assure sufficeint intervals.
✻ ACK Service is recommended for the network service.
✻ Detailed specifications for the LONWORKS network can be found in “ FTT-10A Free Topology Transceiver User's Guide ” by Echelon Corporation.

<LMAP02-E Network Variables>

Network Variables

Request On/Off nv1n nviOnOff_n nv2n nvoOnOff_n On/Off run state

Request Mode nv3n nviMode_n nv4n nvoMode_n Mode state

Setpoint from network Setpoint state


nv5n nviSetPoint_n nv6n nvoSetPoint_n
(Both cool and heat) (both cool and heat)

Request Fanspeed nv7n nviFanSpeed_n nv8n nvoFanSpeed_n FanSpeed state

nv10n nvoThermo_n Thermo On/Off state

nv12n nvoSpaceTemp_n Temperature state


of indoor

nv16n nvoAlarm_n Alarm state

Request Local nv19n nviProOnOff_n nv20n nvoProOnOff_n Local Prohibit (note3, 4)


(note3,4) Prohibit On/Off On/Off state

Request Local nv21n nviProMode_n nv22n nviProMode_n Local Prohibit (note3, 4)


(note3,4) Prohibit mode mode state

Request Local nv23n nviProSetPoint_n Local Prohibit


(note3,4) Prohibit SetPoint nv24n nviProSetPoint_n SetPoint state (note3, 4)

(note1) The case of CITY MULTI is indicated.


(note2) There is a case which cannot be used with the system configuration of the air conditioners units.
(note3) “n” of the network variable shows indoor unit address (M-NET).
(note4) It is possible to use when the “MA” remote controller.

■ External dimension
360
Unit:mm
59.6 240 60
A
9.6

Item Description
Dimensions 340 (H) x 360 (W) x 59.6 (D) mm
Net Weight 3.3 kg
Power Source ~ 220 - 240V (50/60 Hz)
Current Consumption 50 mA (Maximum)
Operating Range -15 to 43˚C
Operation Temperature
Storage Range -20 to 60˚C
325

Environment
340

Humidity 30 to 95 RH (No condensation)


Installation Environment In the control box

Detail of A section
4.5
10

R
7.5

ø1
0

3- 35
PAC-SC34KUA

3-7 Power supply unit


3-7-1 PAC-SC34KUA
● This unit is recommended when the air conditioner system has up to two system controller units.
● This unit is designed to supply power to MELANS controllers and remote controllers. When your local remote con-
trollers are not powered from the outside unit, always use it for local remoter controllers as well.

■ System example

LOSSNAY
unit

Group remote controller LOSSNAY remote


ME remote
controller controller

UP

Power supply unit

MA remote Simple MA
controller controller

■ External dimension

4.5
R Unit:mm

ø 10
265 59.2
150
115
214
200

240
110

2-ø 4.5hole

3- 36
PAC-SC50KUA
3-7-2 PAC-SC50KUA
● This unit supplies DC power to the central controller G-50A by means of the central controller system M-NET transmis-
sion line and DC power line.
Number of the loading unit: G-50A Central Controller 1 unit
In addition to one G-50A unit, a total of four PAC-SC30GRA/ SF44SRA/YT34STA units can be connected.
(Up to two units can be connected when using the PAC-YT40ANRA.)

■ System example

Centralized controller
(G-50A)
12V DC LOSSNAY
unit

ME remote LOSSNAY remote


controller controller
UP

POWER SUPPLY UNIT


MODEL
PAC-SC50KUA

M-NET
POWER RATING

WEIGHT 2.11kg
SERIAL No.
MITSUBISHI ELECTRIC CORPORATION

Power supply unit


PAC-SC50KUA

MA remote Simple MA
controller controller

■ External dimension

265
150 59.2 Unit:mm

UP
225
240

TB3
POWER SUPPLY UNIT
MODEL

POWER RATING
PAC-SC50KUA
TB2
WEIGHT 2.11kg
SERIAL No.
MITSUBISHI ELECTRIC CORPORATION

Cable fixture Cable fixture


TB1

3- 37
PAC-SF46EPA

3-8 Transmission booster unit


(PAC-SF46EPA)

●Use this unit when adding more Y (16HP, 20HP) or SUPER Y indoor units or local remote controllers. Requirement
depends on the number of indoor units connected to the same refrigerant system.
● See the Y (16HP, 20HP) or SUPER Y installation documentation for more information.
● This unit is also suitable when adding more LOSSNAY remote controllers.
● Requirement depends on the performance of the unit supplying power to the signal cables and on the number of LOSS-
NAY remote controllers (PZ-52SF and PZ-52SKF2) that are connected. In this case, a power supply expansion unit for
signal cables can provide power for up to 50 LOSSNAY remote controllers. Please use the power supply expansion unit
for the signal cable if the power supply exceeds the amount prescribed in the following table.

■ System example

UP

TRANSMISSION BOOSTER
MODEL PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N


50
WEIGHT 3.4kg

MADE IN JAPAN

Centralized
controller Transmission
(G-50A) booster
Outdoor unit
12VDC
UP
ME remote ME remote
controller controller

Power supply
unit
UP

PAC-SC50KUA
TRANSMISSION BOOSTER
MODEL PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N


50
WEIGHT 3.4kg

MADE IN JAPAN

Transmission
LOSSNAY LOSSNAY booster LOSSNAY
unit unit unit

LOSSNAY remote LOSSNAY remote


controller controller

Note: This unit cannot be used to extend the transmission line.

■ External dimension

360 Unit:mm
240

■ Restriction of connecting, LOSSNAY


remote controller
UP

Use the transmission booster, when the value


165

of power supply to the remote controllers from


the power supply unit over the one of the
under table.

Power supply unit


300

340

PAC-SC34KUA LOSSNAY
Centralized controller Remote controller
Multi panel
160

0 30
TRANSMISSION BOOSTER
MODEL PAC-SF46EPA
1 26
POWER RATING 220-240V:0.7A ~/N
50

2 22
WEIGHT 3.4kg

MADE IN JAPAN

3 18
4 14

3- 38
4. System component

component
System
In a multi air conditioner system that is a free plan direct-expansion type, a connector for inputting and outputting signals
to/from the outside is fitted as standard on the control board of the indoor and outdoor units. Use this when you want
each unit to input/output signals individually. (Note: When there are many control units it is recommended that you use
MELANS. This would enable you to save on labor.) In order to have an input output signal from each connector, you must
have a dedicated adapter (sold separately) and a relay circuit (onsite arrangements).
Note : See next page for actual examples of use.

■ Types of control that uses connectors for the outdoor unit input output signal (connection for each type of option).

Connector
Category Application Function
Y, Super Y R2,Big R2 WR2
Method of disabling cool and heat operation (thermo Comp ON/OFF
CN3S CN3D —
off) by input from the outside to the outdoor unit.
Input
The low noise operation of the indoor unit can be
commenced by the external input to the outdoor
unit.(The night mode can be adapted only under Night mode CN3D
the outdoor temperature condition of 30˚C or less
CN3D —
for cooling and 3˚C or more for heating)
You can switch the operation mode between cooling
and heating by input from the outside to the outdoor Autochangeover —
unit.
Method of receiving a signal from the outdoor unit to Compressor is
the outside. run state
✻ Can be used as a device that displays the oper-
Output CN51 CN51 CN51
ation state.
✻ Can be used as an interlocked control with ex-
Error state
ternal equipment.

■ Types of control that uses connectors for the indoor unit input output signal (connection for each type of option)

Category Application Function Connector

Method of ON/OFF control by turning on and off switches or con- Distant/local


Input tacts from an outside to each indoor unit group. switching (note 1)
(Note 2,3) CN32
Can be used as a timer adapter (Note 1)
Can be used as a "forget to switch off prevention" or "forced stop". ON/OFF (level)

Method of ON/OFF control by inverting start/stop using external


ON/OFF (pulse) CN51
pulse (a-contact) for each indoor unit group.

Method of sending signals to outside for each indoor unit group. Operation state
Output CN51
It can be used as a device to display operation states. Error state
It can be used as an interlocked control with the external equip-
ment. Operation mode
(heat) state
Operation mode CN52
(cool, dry) state
Thermo ON
(fan) state

Note 1: Connect the signal input only to the principal unit in a group.
(However, the demand input is required to enter into indoor units individually.)
Note 2: When using start/stop input at group operation, Local remote controller is necessary.
(MA remote controller or M-NET remote controller)
Note 3: When setting to Remote, operation can not be performed from Local remote controller.
The remote controller displays [CENTRALLY CONTROLLED].
Note 4: When using start/stop input at group operation, [Automatic address start-up] can not be performed.
Note 5: When CN51 or CN52 is commonly used as an output signal, be sure to use the remote display kit.
Note 6: The remote display kit can be used for the input signal of CN51 and CN52.
Note 7: Connect to the principal unit only when using [Operating status] or [Operation mode (Heating/Cooling-
Dry) of signal output. Connect to indoor units individually when using [Error status] or [Thermostat ON
(or fan) status]

3- 39
component
System

It is possible to have ON/OFF control by turning the indoor unit power on and off. You can select functions by set-
ting the DipSW1-9 and 1-10 on the indoor unit.
■ Types of ON/OFF control (indoor unit settings)
It is possible to have ON/OFF control for each indoor unit (or group) by dip switches 9 and 10 (SW1-9, SW1-10)
of the indoor unit.
Setting SW2 (note 1)
Function Operation when indoor unit recovers
9 10
All auto All indoor units will always restart regardless of the state that was be- –
restart fore the power was turned off (POWER OFF) (after 5 minutes). ON

Auto Indoor units which are operated before the power was turned off
recovery (POWER OFF)will restart (after 5 minutes). ON OFF

Operation stays stopped regardless of the state that was before the
All OFF OFF OFF
power was turned off.

Note 1. The dip switch setting for all units in the indoor unit group is required.
Note 2. Do not cut-off the power to the outdoor unit. If you do, it will disconnect the power to the crank-
case heater of the outdoor unit and that could cause damage to the compressor.
Note 3. This cannot be applied to the power ON/OFF of the drain pump and humidifier equipment.

■ Description of when using distant/local switching (CN32)

SW1 SW2
State Remote controller display/operation
Local switching ON/OFF
OFF OFF Local / Permit The operation permit
It displays "CENTRALLY CONTROLLED", while
ON OFF Distant / Stop the state is distant.
It prohibits ON/OFF operation of remote
ON ON Distant / Operate controller.

■ System example
Outdoor unit

Outdoor unit
power supply
Indoor unit

Indoor unit
power supply Local
Switch remote
controller

When the power to the outdoor unit is cut-off for a long time, the crankcase heater for the compressor also stops. If the
compressor is started soon after the power is restored, there is a chance that a fault will occur in the compressor.
When using the above function, make sure the power to the outdoor units will not be cut-off.

■ Limitations to combining system controls

Control combining
Description Pulse ON/OFF Power ON/OFF Automatic recover
distant/local
1 Control combining distant/local CN32 — ✕ ✻1 ✕ ✻1 ✕ ✻1
2 Pulse ON/OFF CN51 —

3 HA ON/OFF (JEMA) CN51

4 Power ON/OFF - — ✕

5 Automatic recover - —

✻1: Pulse ON/OFF, Power ON/OFF and automatic recover can only be used when the distant/local setting
(CN32) is set to local. Therefore, always avoid this function when combining control.

3- 40
component
■ Outdoor unit input/output connector

System
(1)All units
• State (CN51)
Distant control
board Relay circuit Adapter Outdoor unit
X control board
Lamp power

L1 X
Y CN51
L2 Y 5
4
3

Preparations
in the field Maximum cable
length is 10m
L1 : Error display lamp
L2 : Compressor operation lamp
X, Y : Relay (Coil standard of 0.9W or less for DC12V)

(2)PUMY-P
• Demand (CN3S) • Autochangeover (CN3D)
Outdoor unit Distant control
Adapter board Relay circuit Adapter
control board Outdoor unit
control board

Lamp power
CN3S
X 1 SW1 X CN3D
2 1
X 2
3 SW2 3
Y
Y
Preparations
in the field
Preparations
Maximum cable in the field Maximum cable
length is 10m length is 10m
X : Relay SW1 : Cooling / Heating
Demand : The compressor is stopped when X is closed. SW2 : Validity / Invalidity of SW1
X, Y : Relay (Point of contact rating : DC1mA)

(3)PUMY
• Demand (CN3D)
Outdoor unit
Adapter control board
CN3D
1
X
3

Preparations
in the field
Maximum cable
length is 10m

Demand : The compressor is stopped when X is closed.

(4)PURY, PU(H)Y-(P)200·250·315
• Step demand (CN3D + DipSW4-7 ON) • Night mode (CN3D + DipSW4-7 OFF)
Outdoor unit Outdoor unit
Adapter control board Adapter control board
CN3D CN3D
X 1 X 1
2 2
Y 3 3

Preparations Preparations
in the field in the field
Maximum cable Maximum cable
length is 10m length is 10m
X : Relay
X Night mode : The noise level is reduced by controlling the maximum
fan frequency to be lower under the flowing condition.
OFF ON
Cooling mode : ambient temp. (TH6) < 30˚C
OFF 100% 75% Heating mode : ambient temp. (TH6) > 3˚C
Y -Note-
ON 0% 50%
The noise level can not be reduced. When the fan frequency
❈They are rough values. is not maximum.

3- 41
component
System

• Snow sensor (CN3S) • Autochangeover (CN3N) ❈ Y series only


Outdoor unit Distant control External output
Adapter board Relay circuit adapter
control board Outdoor unit
control board

Lamp power
CN3S
X 1 SW1 X CN3D
1
2 X 2
3 SW2 3
Y
Y

Preparations
in the field
Preparations
Maximum cable in the field Maximum cable
length is 10m length is 10m
X : Relay SW1 : Cooling / Heating
Snow sensor : The outdoor fun runs when X is closed SW2 : Validity / Invalidity of SW1
in stop mode or thermostat mode. X, Y : Relay (Point of contact rating : DC1mA)

(5)Big Y, Super Y, Big R2


• Demand (CN3S) • Snow and Night mode (CN3N)
Outdoor unit Outdoor unit
Adapter control board Adapter control board

CN3S CN3S
1 X 1
X 2 2
3 Y 3

Preparations Preparations
in the field in the field
Maximum cable Maximum cable
length is 10m length is 10m
X : Relay X : Night mode
Demand : The compressor is stopped when X is closed. Y : Snow mode

• Autochangeover (CN3D) ❈ Big Y and Super Y only


Distant control External output
board Relay circuit adapter Outdoor unit
control board
Lamp power

SW1 X CN3D
1
X 2
SW2 3
Y
Y

Preparations
in the field Maximum cable
length is 10m
SW1 : Cooling / Heating
SW2 : Validity / Invalidity of SW1
X, Y : Relay (Point of contact rating : DC1mA)

(6)WR2, WY
• Demand (CN3D)
Outdoor unit
Adapter control board
CN3D
1
X
3

Preparations
in the field
Maximum cable
length is 10m

Demand : The compressor is stopped when X is closed.

3- 42
component
■ Indoor unit input/output connector

System
● ON/OFF (Pulse) input specification

Item Description
Input signal Pulse sign (a connect)

Standard of pulse

200msec or more

● Input ● Output

CN51 CN52
Distant control board Relay circuit Adapter Distant control board Relay circuit Adapter Indoor unit
Indoor unit
control board
SW
1
control board 1
Power supply Power supply
X X CN52
of relay 2 CN51 of relay L1 X
2
X
3 Y 3
L2 Y
Y 4 Z
L1 Y 4
L3 Z
Z 5
L2 Z

Maximum cable
Maximum cable length is 10m
L1 : Status lamp
SW : Distant ON/OFF switch length is 10m Fan motor output (SW1-5 OFF)
L1 : Status lamp ❇ Every time the SW is pushed Thermostat ON (SW1-5 ON)
L2 : Error lamp (the pulse is inputted), it make L2 : Cooling/Dry status lamp
X : Relay (a point of contact, fixed DC1mA) to react against ON/OFF. L3 : Heating status lamp
Y, Z : Relay (Coil with fixed DC12V, a power consumption of 0.9W or less) X, Y, Z : Relay (Coil with fixed DC12V, a power consumption of 0.9W or less)

CN32
Distant control board Relay circuit Adapter Indoor unit
control board

Power supply 1
CN32
of relay SW2
X
2
X

SW1
Y 3
Y

Maximum cable
length is 10m
❇ SW2 is available when SW1
SW1 : Distant/Local switching
is ON.
SW2 : ON/OFF switch
X, Y : Relay (a point of contact, fixed DC1mA)

CN52
Distant control board Relay circuit Adapter Indoor unit
control board

Power supply 1
CN52
of relay

SW1
X 5
X

Maximum cable
length is 10m
SW1 : Demand switch
X : Relay (coil with fixed DC12V, a power consumption of 0.9W or less)

3- 43
System
component

3- 44
4

CONTENTS

1. Electrical Work & M-NET control


1-1 Attention ············································································ 4-2
1-2 Allowable length of transmission line ························· 4-3
1-3 Electrical work ································································· 4-6
1-4 System configuration restrictions ··························· 4-9
1-5 Address setting ······························································ 4-12

2. Refrigerant & Piping


2-1 System examples ·························································· 4-21
2-2 Restrictions on refrigerant piping lengths ················ 4-23
2-3 Refrigerant piping selection ········································· 4-29
2-4 Example of refrigerant piping selection ·················· 4-33
2-5 Calculation of additional refrigerant charge ············· 4-38
2-6 Electric characteristics ················································· 4-44
2-7 Installation ······································································· 4-50
2-8 Joint / Header / Reduction ··········································· 4-64

3. Caution For Refrigerant Leak


3-1 Introduction ····································································· 4-66
3-2 Checking procedure of limiting concentration ········ 4-66

4- 1
1. Electrical Work & M-NET control
System Design

1-1 Attention
➀ Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
➁ Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power source wiring so
that it is not influenced by electric noise from power source wiring. (Do not insert transmission line and power source wire
in the same conduit.)
➂ Be sure to provide designated grounding work to outdoor unit.
➃ Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
➄ Never connect 380~415V(220~240V )power source to terminal block of transmission line.If connected,electrical parts
will be burnt out
➅ Use 2-core shield cable for transmission line. If transmission lines of different systems are wired with the same multiple-
core cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit Indoor unit


Outdoor Outdoor
unit unit

OK NG
2-core cable
Multiple-
core cable Remote
Remote controller
controller
BC controller BC controller

2-core cable

4- 2
System Design
1-2 Allowable length of transmission line
➀ PUHY, PUY, PUMY
MA Remote controller L1

OC Group1 Group3 Group5


IC IC IC IC
(51)
(01) (04) (05) c2 (06)
TB3 TB5 TB15 TB5 TB5 TB15 TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S M1M2 S 1 2 M1M2 S 1 2
TB7

c1
c4

c1
L2

c2
Shielded

c2
A B A B A B

c3
wire

MA MA MA

OC L3 L4
IC IC IC
(52)
(02) (03) (07)
TB3 TB5 TB15 TB5 TB15 TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
TB7

c1
Power Supply Unit
L6

M1M2 S 12VDC GND

A B
L7

G-50A
MA
A B S 12VDC GND

• Max length via outdoor unit (M-NET cable) : L1+L2+L3+L4 and L1+L2+L6+L7 and L6 and L3+L4+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length (M-NET cable) : L1 and L3+L4 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : c1+c2 and c1+c2+c3+c4 = 200 m (0.3 to 1.25 mm2)
• DC12V power supply line : n = 10m (0.75 to 2mm2 )

M-NET Remote controller


L1

OC Group1 Group3 Group5


IC IC IC IC
(51)
(01) (04) (05) (06)
TB3 TB5 TB5 TB5 TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S M1M2 S
TB7
r1

r2

r3
L2

Shielded A B A B A B
wire (101) (105) (155)
RC RC RC

OC L3 L4
IC IC IC
(52)
(02) (03) (07)
TB3 TB5 TB5 TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S
TB7
L5

Power Supply Unit


L6

r4

M1M2S 12VDC GND

A B
(103)
L7

G-50A RC
A B S 12VDC GND

• Max length via outdoor units : L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length : L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : r1, r2, r3, r4 = 10 m (0.3 to 1.25 mm2 )
If the length exceeds 10 m, use a 1.25 mm2 shielded wire. The length of this section (L8)
should be included in the calculation of the maximum length and overall length.
• DC12V power supply line : n = 10m (0.75 to 2mm2 )

4- 3
System Design

➁ PURY, PQRY <In case of 1 BC controller system>


MA Remote controller L1

OC
Group1 Group5
IC IC IC IC
BC
(51) c2 c2
(52) (01) (02) (05) (06)
TB3 M1M2 S TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
TB7

c1
c4

c1
L2

c3
Shielded A B A B A B

c3
wire

MA MA MA
E
OC L3 L4
IC IC IC
BC
(53)
(54) (03) (04) (07)
TB3 M1M2 S TB5 TB15 TB5 TB15 TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
TB7

c1
Power Supply Unit
L6

M1M2 S 12VDC GND


A B

Group3
MA
L7

G-50A

A B S 12VDC GND

• Max length via outdoor unit (M-NET cable) : L1+L2+L3+L4 and L1+L2+L6+L7 and L3+L4+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length (M-NET cable) : L1 and L3+L4 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : c1 and c1+c2+c3 and c1+c2+c3+C4 = 200 m (0.3 to 1.25 mm2)
• DC12V power supply line : n =10m (0.75 to 2mm2 )

M-NET Remote controller L1

OC
Group1 Group5
IC IC IC IC
BC
(51)
(52) (01) (02) (05) (06)
TB3 M1M2 S TB5 TB5 TB5 TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S M1M2 S
TB7
r1

r2

r3
L2

Shielded A B A B A B
wire (101) (105) (155)
RC RC RC

OC L3 L4
IC IC IC
BC
(53)
(54) (03) (04) (07)
TB3 M1M2 S TB5 TB5 TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S
TB7
L5

Power Supply Unit


L6

r4

M1M2 S 12VDC GND


A B
(104)
Group3
RC
L7

G-50A

A B S 12VDC GND

• Max length via outdoor units : L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length : L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : r1, r2, r3, r4 = 10 m (0.3 to 1.25 mm2 )
If the length exceeds 10 m, use a 1.25 mm2 shielded wire. The length of this section (L8)
should be included in the calculation of the maximum length and overall length.
• DC12V power supply line : n =10m (0.75 to 2mm2 )

4- 4
System Design
➂ PURY-P400·500 <In case of 2 BC controllers system> L1
MA Remote controller Group1 Group5
OC
IC IC IC IC
BC(Master) BC(Slave)
(51) c2 c2
(52) (01) (02) (55) (05) (06)
TB3 M1M2 S TB5 TB15 TB5 TB15 M1M2 S TB5 TB15 TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
TB7

c1
c4

c1
L2

c3
Shielded A B A B A B

c3
wire

MA MA MA
E
OC L3 L4
IC IC IC
BC(Master) BC(Slave)
(53)
(54) (03) (04) (57) (07)
TB3 M1M2 S TB5 TB15 TB5 TB15 M1M2 S TB5 TB15
M1M2 S M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
TB7

Power Supply Unit

c1
L6

M1M2 S 12VDC GND

A B

Group3
L7

G-50A
MA
A B S 12VDC GND

• Max length via outdoor unit (M-NET cable) : L1+L2+L3+L4 and L1+L2+L6+L7 and L3+L4+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length (M-NET cable) : L1 and L3+L4 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : c1 and c1+c2+c3 and c1+c2+c3+c4 = 200 m (0.3 to 1.25 mm2)
• DC12V power supply line : n =10m (0.75 to 2mm2 )

M-NET Remote controller L1

OC
Group1 Group5
IC IC IC IC
BC(Master) BC(Slave)
(51)
(52) (01) (02) (55) (05) (06)
TB3 M1M2 S TB5 TB5 M1M2 S TB5 TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S M1M2 S
TB7
r1

r2

r3
L2

Shielded A B A B A B
wire (101) (105) (155)
RC RC RC

OC L3 L4
IC IC IC
BC(Master) BC(Slave)
(53)
(54) (03) (04) (57) (07)
TB3 M1M2 S TB5 TB5 M1M2 S TB5
M1M2 S M1M2 M1M2 S M1M2 S M1M2 S
TB7
L5

Power Supply Unit


L6

r4

M1M2 S 12VDC GND

A B
(104)
Group3
L7

G-50A RC
A B S 12VDC GND

• Max length via outdoor units : L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7 = 500 m (1.25 mm2 or more)
• Max transmission cable length : L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7 = 200 m (1.25 mm2 or more)
• Remote controller cable length : r1, r2, r3, r4 = 10 m (0.3 to 1.25 mm2 )
If the length exceeds 10 m, use a 1.25 mm2 shielded wire. The length of this section (L8)
should be included in the calculation of the maximum length and overall length.
• DC12V power supply line : n =10m (0.75 to 2mm2 )

City Multi is a systemized product of which components are outdoor unit , BC controller , indoor unit ,and remote controller .
Each system part has its own microcomputer, and operated by no-polarity two wires multiple transmission system. Therefore, in
order for several microcomputers connected to the common two wires to identify transmitter, identification No. (address) must be
set for each microcomputer.
Be sure to set address numbers at the time of installation work by using switches for setting addresses for outdoor unit ,
BC controller , indoor unit ,and remote controller .
When signal receiving unit is used, connect the accessory cable (polarity 2 lines) to the specified connector (CN3A) on the printed
circuit board.

4- 5
System Design

1-3 Electrical work


(1) Main power supply connections and equipment capacities
The selection of capacities should be determined in accordance with the relevant standards.
Outdoor unit (PURY)
➀ PUMY, (Heat source unit (PQRY))
PU(H)Y-(P)200·250·315
PURY-(P)200·250, PQRY, PQHY Note 1.The transmission line is non-polarity two wires.
PE 2.Symbol means a screw terminal.
breakers for 3.Earth of transmission line shall be grounded
Power supply current leakage switch
on the earth terminal( ) of only variable capacity unit.
3N~380/400/415V L1,L2,L3,N And shield of transmission line between each indoor units
TB7 S TB3 shall be connected to shield terminal (S) of each indoor units
DC12V power supply line
or connected themselves.
0.75~2mm2 G-50A
(10m or less)
breakers for
current leakage switch BC controller
Power supply L.N
~220/230/240V M1.M2 PE
S
PAC-SC50KUA
(Power supply unit) (Shield) pull box
Power supply
~220/230/240V
breakers for switch Indoor unit
current leakage L.N L.N
PE PE L.N PE L.N PE
M1.M2 TB15 M1.M2 TB15 M1.M2 TB15 M1.M2 TB15
Transmission line TB5 S TB5 S TB5 S TB5 S
1.25mm2 or more
(Shield cable) (Shield)
(CVVS,CPEVS) Outdoor unit (PUHY,PUMY)
0.3~1.25mm2
(10m or less)
PAR-20MAA PAR-20MAA PAR-FA31MA
breakers for PE
Power supply current leakage switch (Signal receiving unit)
3N~380/400/415V
L1,L2,L3,N
TB7 S TB3
breakers for
current leakage switch
Power supply
~220/230/240V
L.N L.N L.N
M1.M2 M1.M2 M1.M2
TB5 S TB5 S TB5 S
The number of indoor units which (Shield) (Shield) (Shield)
can be connected to a switch is
the number applying when the 1.25mm2 or more
total operating current of the (Shield cable)
indoor units is less than 16A.
PAC-SC32PTA PAR-F27MEA PAC-SE51CRA PAR-F27MEA
(Program timer) (Remote controller) (Simple R/C)

➁ PUHY-(P)400·500
breakers for
switch current leakage Power supply
3N~380/400/415V
Variable capacity unit Note 1.The transmission line is non-polarity two wires.
2.Symbol means a screw terminal.
3.Earth of transmission line shall be grounded on the earth terminal
( ) of only variable capacity unit.
And shield of transmission line between each indoor units shall be
connected to shield terminal (S) of each indoor units or connected
PE themselves.
L1,L2,L3,N
4.It is necessary to connect the transmission booster when indoor
TB3 units over than 16 units are connected.
In addition, be sure to connect the shield cable at the terminal (S)
Pull box in the transmission booster.
breakers for breakers for
current leakage switch switch current leakage Power supply
Power supply
~220/230/240V 3N~380/400/415V
PE PE PE
Power supply
L.N L.N ~220/230/240V L.N L.N
PE L1,L2,L3,N PE
PE
Transmission line TB5 TB5 TB5 TB5 TB5
M1.M2 S M1.M2 S L.N M1.M2 S M1.M2 S M1.M2 S
1.25mm2 or more
(Shield cable) Indoor unit (Shield) (Shield) TB2 TB3 (Shield) (Shield) (Shield)
(CVVS,CPEVS) (PEFY-P200·250VMH)
S S
0.3~1.25mm2 (Shield) (Shield)
(10m or less) Remote 1.25mm2 or more Transmission booster
controller (Shield cable)
PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA
Note 4

4- 6
➂ PUHY-(P)600·650·700·750

System Design
breakers for breakers for
Power supply current leakage current leakage Power supply
3N~380/400/415V 3N~380/400/415V

switch switch Note 1.The transmission line is non-polarity two wires.


Constant capacity unit Variable capacity unit 2.Symbol means a screw terminal.
3.Earth of transmission line shall be grounded on the earth terminal
( ) of only variable capacity unit.
And shield of transmission line between each indoor units shall be
PE
connected to shield terminal (S) of each indoor units or connected
themselves.
L1,L2,L3,N L1,L2,L3,N And shield of transmission line for constant capacity unit shall be
TB3 PE
S TB3 connected to shield terminal (S) of constant capacity unit.
(Shield) 4.It is necessary to connect the transmission booster when indoor
units over than 16 units are connected.
In addition, be sure to connect the shied cable at the terminal (S)
Transmission line in the transmission booster.
1.25mm2 or more Pull box
(Shield cable) breakers for
(CVVS,CPEVS) switch current leakage
Power supply Power supply
~220/230/240V breakers for switch 3N~380/400/415V
PE PE Power supply PE PE
current leakage
L.N L.N ~220/230/240V L.N L.N
PE L1,L2,L3,N PE
Transmission line TB5 TB5 TB5 TB5 TB5
M1.M2 S M1.M2 S L.N M1.M2 S M1.M2 S M1.M2 S
1.25mm2 or more
(Shield cable) Indoor unit (Shield) (Shield) TB2 TB3 (Shield) (Shield) (Shield)
(CVVS,CPEVS) (PEFY-P200·250VMH)
S S
0.3~1.25mm2 (Shield) (Shield)
(10m or less) Remote 1.25mm2 or more Transmission booster
controller (Shield cable)
PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA Note 4

➃ PURY-P400·500

Note 1.The transmission line is non-polarity two wires.


2.Symbol means a screw terminal.
3.Earth of transmission line shall be grounded on the earth terminal
breakers for ( ) of only variable capacity unit.
switch current leakage
Power supply And shield of transmission line between each indoor units shall be
3N~380/400/415V connected to shield terminal (S) of each indoor units or connected
Variable capacity unit themselves.
4.It is necessary to connect the transmission booster when indoor
units over than 16 units are connected.
In addition, be sure to connect the shield cable at the terminal (S)
in the transmission booster.
PE
L1.L2.L3.N

TB3 BC controller BC controller


L.N PE L.N PE
M1.M2 M1.M2
S S Pull box
breakers for breakers for
current leakage switch switch current leakage Power supply
Power supply
~220/230/240V 3N~380/400/415V
PE PE PE PE
Power supply
L.N L.N ~220/230/240V L.N L.N
PE L1.L2.L3.N PE
Transmission line TB5 TB5 TB5 TB5 TB5
M1.M2 S M1.M2 S L.N M1.M2 S M1.M2 S M1.M2 S
1.25mm2 or more
(Shield cable) Indoor unit (Shield) (Shield) TB2 TB3 (Shield) (Shield) (Shield)
(CVVS,CPEVS) (PEFY-P200·250VMH)
S S
0.3~1.25mm2 (Shield) (Shield)
(10m or less) Remote 1.25mm2 or more Transmission booster
controller (Shield cable)
PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA PAR-F27MEA
Note 4

4- 7
System Design

Specific wiring requirements should adhere to the wiring regulations of the region.
Minimum Wire Thickness (mm2) Switch(A) Breaker for Wiring
Model Breaker for Current Leakage
Main Cable Branch Ground Capacity Fuse (NFB)
200 4.0 - 4.0 25 25 30A 30A 100mA 0.1sec. or less
250 4.0 - 4.0 32 32 30A 30A 100mA 0.1sec. or less
315 6.0 - 6.0 40 40 40A 40A 100mA 0.1sec. or less
400 10.0 - 10.0
63 63 75A 75A 100mA 0.1sec. or less
Outdoor unit

500 16.0 - 16.0


400 10.0 - 10.0 63 63 75A 75A 100mA 0.1sec. or less
600
200 4.0 - 4.0 32 32 40A 30A 100mA 0.1sec. or less
400 10.0 - 10.0 63 63 75A 75A 100mA 0.1sec. or less
650
250 6.0 - 6.0 40 40 40A 40A 100mA 0.1sec. or less
500 16.0 - 16.0 63 63 75A 75A 100mA 0.1sec. or less
700
200 4.0 - 4.0 32 32 40A 30A 100mA 0.1sec. or less
500 16.0 - 16.0 63 63 75A 75A 100mA 0.1sec. or less
750
250 6.0 - 6.0 40 40 40A 40A 100mA 0.1sec. or less
Heat source unit

200 4.0 - 4.0 32 32 40A 30A 100mA 0.1sec. or less

250 6.0 - 6.0 40 40 40A 40A 100mA 0.1sec. or less

Wire Thickness (mm2) Switch(A) Breaker for


Model Breaker for Current Leakage
Main Cable Branch Ground Capacity Fuse Wiring
16A or less 1.5 1.5 1.5 16 16 20A 20A 30mA 0.1sec. or less
Total operating
current of the 25A or less 2.5 2.5 2.5 25 25 30A 30A 30mA 0.1sec. or less
indoor units ✻1
32A or less 4.0 4.0 4.0 32 32 40A 40A 30mA 0.1sec. or less

✻1 Use a separate power supply for the outdoor unit and indoor unit.
✻2 Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc. ) when proceeding with the
wiring and connections.
✻3 The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker with
consideration of voltage drops.
Make sure the power supply voltage does not drop more than 10%.
✻4 Specific wiring requirements should adhere to the wiring regulations of the region.
✻5 Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord (design 245 IEC57).
✻6 A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.

(2) Types of control cables


Transmission cables M-NET Remote controller cables MA Remote controller cables
Shielding wire (2-core) Sheathed 2-core cable (unshielded)
Type of cable CVVS or CPEVS CVV
0.3 ~ 1.25mm2 0.3 ~ 1.25mm2
Cable diameter More than 1.25mm2
(0.75 ~ 1.25mm2) ✻1 (0.75 ~ 1.25mm2) ✻1

— When 10m is exceeded, use cables with


Remarks Max length : 200m
the same specification as transmission cables.
✻1 Connected with simple remote controller.
CVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable

4- 8
1-4 System configuration restrictions (Common matters for each unit regarding system limits)

System Design

Refer to section [1.1 Device configuration table] for details on limits for connecting each unit.
Set-up With Connection to System Controller (Note 5)
Set-up For indoor/outdoor For indoor/outdoor
automatic address manual address Connection to Central Connection to Indoor/outdoor
startup (Note 4) startup Control Transmission Transmission Line (TB3) (Note 10)
Item
Line (Note 13) SC1 SC2 SC3
Number of connected remote controller. one or two units per group

Number of indoor units connected per group. 1 to 16 units

Number of ventilation units connected to indoor unit. 1 unit per indoor unit
All indoor units
in same
Number of indoor units connected to ventilation unit. refrigerant system Random between 1 and 16 units per ventilation unit (Note 7)
(Note 6)
Number of ventilation units connected in
refrigeration system. 1 unit - - -

Number of system controllers connected when


indoor/outdoor transmission line connected. - - - Max. 3 units in same refrigerant system

Total number of units With no All indoor units Max. 30 units Max. 28 units Max. 26units
Max. 32units (excluding LOSSNAY)
connected in distribution under Type 200. Above numbers exclusive of LOSSNAY (Note 11, 12)
refrigerant system controller Max. 24units Max. 22units Max. 20units
<MA Remote Controller> Type 200 or higher Max. 26units (Note 8)
(Note 11,12)
(Note 2).
With All indoor units Max. 29/28units Max. 27/26units Max. 25/24units
distribution Max. 31/30units (excluding LOSSNAY)
under Type 200.
controller, (Note 11,12)
one BC unit Max. 23/22units Max. 21/20units Max. 19/18units
/two BC units Type 200 or higher Max. 25/24units (Note 8)
(Note 11,12)
With no Max. 18units Max. 16units Max. 14units
Total number of units All indoor units Max. 20units (40units) (38units) (36units) (34units)
connected in distribution under Type 200. (Note 8,9)
controller (Note 9,11,12)
same refrigerant system
Max. 14units Max. 12units Max. 10units
<M-NET Remote Controller> Max. 16units (32units) (30units) (28units) (26units)
(Note 2, 3). Type 200 or higher (Note 8,9)
(Note 9,11,12)

With Max. 17/16units Max. 15/14units Max. 13/12units


All indoor units Max. 19/18units (Max. 38/36 units) (36/34units) (34/32units) (32/30units)
distribution under Type 200. (Note 8,9)
controller, (Note 9,11,12)
one BC unit Max. 13/12units Max. 11/10units Max. 9/8units
/two BC units Type 200 or higher Max. 15/14units (Max. 30/28 units) (28/26units) (26/24 units) (24/22units)
(Note 8,9)
(Note 9,11,12)

Note 1 "Indoor/outdoor unit automatic address startup" cannot be used when sequencing the ventilation unit with 16 or more indoor units in the same refrigerant
system, or when connecting two or more ventilation units to the refrigeration system.

Select 'Automatic Address Set-up' or 'Set-up With Connection to System Controller'.
Note 2 The total number of connected units is the total of indoor units and ventilation units (LOSSNAY with heating and humidifying functions).
Note 3 The number of units limited when using the MA remote controller and M-NET remote controller is the number of units indicated for <M-NET remote
controller connection>.
Note 4 'Automatic Address Set-up' is not possible when Start/Stop input is used with group operation or when the system is with two distribution controllers.
Note 5 When MA and M-NET remote controllers are used together the system controller is connected and 'Set-up With Connection to System Controller' is
used.
Note 6 All indoor units within the refirigerant system are automatically linked and registered when a ventilation unit is connected by 'Automatic Address Set-
up'.
Note 7 Linking and registration of indoor units and ventilation unit must be performed manually except when using 'Automatic Address Set-up'.
Note 8 The power feed expansion unit for transmission line is required when the maximum number of units is exceeded.
Note 9 Figures in brackets are the total number of indoor units and M-NET remote controllers.
Note 10 The system controllers that can be connected to the indoor/outdoor transmission line are the G-50A, PAC-SF44SRA, PAC-YT34STA,
PAC-YT40ANRA and PAC-SC30GRA.
Note that the system controller cannot be connected to the indoor/outdoor transmission line when using the City-Multi S (PUMY)
outdoor unit.
Operation from the system controller will be impossible if the outdoor unit power supply is shut off while the system controller is
connected to the indoor/outdoor transmission line .
When using "power apportion billing", an option for the central controller (G-50A), do not connect the G-50A to the indoor/outdoor
transmission line. The G-50A will also stop when the indoor/outdoor unit's power is shut off. If the other outdoor units operate during this
time, the charges will not be calculated.
Note 11 The number of indoor units which may be connected is reduced two for each system controller.
A maximum of three system controllers can be connected in the same refrigerant system.
Note that when using the G-50A, only one unit can be connected. The number of connectable indoor units will decrease by four units.
Note 12 A transmission booster must not be used when the system controller is connected to the indoor/outdoor transmission line.
Connect the system controller to the 'Central Control Transmission Line' when the maximum number of units is exceeded.
Note 13 Up to five system controllers can be connected. (Excluding when G-50A is connected.)

4- 9
Connecting the power feed expansion unit for transmission line
System Design

A transmission booster is required when the total number of units within the same refirigerant system
exceeds the maximum number of units.
Ensure that the number of indoor units (N1) between the outdoor unit and the transmission booster,
and the number of indoor units (N2) after the transmission booster, are within the restrictions in the following table.

Type of MA M-NET
remote remote remote
controller
controller controller
(Note 1) (Note 2)

Number of indoor units Without BC 20


32 (40)
(All indoor units under
With BC 19/18
Type 200.) (one unit 31/30
/two units) (38/36)

Number of indoor units Without BC 16


26 (32)
(Type 200 or higher)
With BC 15/14
(one unit 25/24
/two units) (30/28)

Figures in brackets are the total number of indoor units and M-NET remote controllers.
Note 1 'MA remote controller' refers to the MA remote controller and wireless remote controller.
Note 2 The M-NET remote controller refers to the ME remote controller and compact remote controller.

Group Group IC : Indoor unit


OC
✻1 OS ✻2 BC IC IC IC RP IC IC RC : M-NET remote controller
51 OC : Outdoor unit
(52) (52) 01 02 03 20 21
TB3 TB7 TB3 TB3 TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15 TB5 TB15 RP : Transmission booster
M1 M 2 S M1 M2 S M 1 M2 M1 M2 S M1 M 2 S 1 2 M1 M2 S 1 2 M1 M 2 S 1 2 M 1 M2 S M1 M2 S M1 M2 S 1 2 M1 M 2 S 1 2

A1 B2 A1 B2 A1 B2
101 102 120
RC RC RC
M1 M 2 S
TB3

(70)
N1 N2
✻3 BS

✻1 OS : Exists only with ✻✻✻ YSEM type.


✻2 BC : Exists only with R2/WR2/BIG R2 system.
✻3 BS : Connectable only when using BIG R2 system

4- 10
System Design
Power supply for system controller
The system controller is fed power from the M-NET transmission line. (Excluding the G-50A, LM adapter.)
1. Connecting to the transmission line for central control
The power feed unit for transmission line (PAC-SC50KUA/PAC-SC34KUA) is required.
The number of system controllers that can be connected differ according to the power feed unit for transmission line.

System controller
System remote controller, ON/OFF Central controller
Power feed unit schedule timer, remote controller (G-50A)(Note 1)
for transmission line group remote controller(Note 1) (Note 1)
PAC-SC50KUA 1 to 10 units 1 to 5 units 1 to 2 units

PAC-SC34KUA 1 to 10 units 1 to 5 units -

Note 1: The power consumption of the system remote controller, schedule timer (M-NET compatible)
and group remote controller is one-half compared to the ON/OFF remote controller.

Outdoor unit

Group Group

Indoor unit

M-NET
MA remote transmission line
M-NET transmission line (Indoor/outdoor
controller
(Transmission line for central control) transmission line)

Outdoor unit Group Group

Indoor unit

M-NET
MA remote transmission line
controller (Indoor/outdoor
Power feed unit
for transmission line transmission line)

System
controller

2. Connecting to the indoor/outdoor transmission line (Excluding LM adaptor)


Up to three system controllers can be connected to the M-NET transmission line's indoor/outdoor transmission line.
The power feed unit for transmission line is not required in this case.

The number of connectable system controllers will differ according to the limits on the total number of connectable units
in the refrigerant system.
Always refer to section [V. 1 (5) System configuration restrictions].

< When system controller is connected to indoor/outdoor transmission line >


System controller
Outdoor unit (Excluding LM adaptor)

Group Group

Indoor unit

M-NET
MA remote transmission line
controller (Indoor/outdoor
transmission line)

3. Using the LM adapter


A single-phase 200VAC power supply is required.

The power feed unit for transmission line is not required when connecting only the LM adaptor,
but the LM adaptor power feed changeover connector must be changed from (CN41) to (CN40).

4- 11
System Design

1-5 Address setting


(1) Switch operation
In order to constitute CITY MULTI in a complete system, switch Rotary switch
operation for setting the unit address No. and connection No. is Branch
required. No. setting Unit address No. setting

➀ Unit address No., group No. and branch No. F 01 90 1 90 1

23
BCDE

7 8

7 8
2 3

2 3
456
The unit address No. is determined by the address setting switch of
78 9 A 4 5 6 4 5 6
the outdoor unit, indoor unit and remote controller.
Set the indoor unit branch No. switch to branch No. of the BC
controller connecting the piping and that indoor unit.
When using two or more branches, set the lowest branch No.
The indoor unit capacity that can be connected per branch is P80 or
less and the maximum number of connectable units is 3.

➁ Caution for switch operations


• Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
• No units with identical unit address shall exist in one system. If set erroneously, system can not
operate.

➂ MA remote controller
• When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
• The factory setting is “Main”.
ON

Setting the dip switches


1 2 3 4

The dip switches are at the bottom of the remote controller. ON

1 2 3 4

Remote controller Main/Sub and other function settings are performed


using these switches.
Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all “ON”.)

SW No SW contents Main ON OFF Comment


Remote controller
1 Main Sub Set one of the two remote controllers at one group to “Main”.
Main/Sub setting
When remote control- When you want to return to the timer mode when the power is restored after
2 Normally on Timer mode on
ler power turned on a power failure when a Program timer is connected, select “Timer mode”.
Cooling/heating dis- When you do not want to display “Cooling” and “Heating” in the
3 Yes No
play in AUTO mode Auto mode, set to “No”.
Intake temperature
4 Yes No When you do not want to display the intake temperature, set to “No”.
display

4- 12
System Design
(2) Rule of address setting

Unit Address setting Example Note

90 1 90 1
Use the most recent address within the same group of
Indoor indoor units. Make the indoor units address connected

7 8

7 8
2 3

2 3
01 ~ 50
unit
4 5 6 4 5 6
to the BC controller (Slave) larger than the indoor units
10 1 address connected to the BC controller (Master).

The smallest address of indoor unit in same refrigerant


90 1 90 1
Outdoor unit system + 50

7 8
7 8

2 3

2 3
Heat source unit 51 ~ 99, 100
✻ The address automatically becomes "100" if it is set
4 5 6 4 5 6

10 1 as "01~ 50"

The address of outdoor unit + 1


90 1 90 1
BC controller ✻ Please re-set another address between 01 and 50

7 8
7 8

2 3

2 3
52 ~ 99, 100 4 5 6 4 5 6
when two addresses overlap.
(Master)
10 1 ✻ The address automatically becomes "100" if it is set
as "01~ 50"
90 1 90 1 Lowest address within the indoor units connected to
BC controller
7 8
7 8

2 3

2 3

53 ~ 99, 100 4 5 6 4 5 6 the BC controller (Slave) plus 50.


(Slave)
10 1
Local remote controller

M-NET, LOSSNAY 90 1 90 1
The smallest address of indoor unit in the group + 100
7 8

7 8
2 3

2 3

Remote controller
(Main)
101 ~ 150 1 4 5 6 4 5 6
✻ The place of "100" is fixed to "1"
Fixed 10 1

M-NET, LOSSNAY 90 1 90 1 The address of main remote controller + 50


7 8

7 8
2 3

2 3

Remote controller 151 ~ 199, 200 1 4 5 6 4 5 6 ✻ The address automatically becomes "200" if it is set
(Sub) Fixed as "00"
10 1

90 1 90 1 The smallest group No. to be managed + 200


7 8

7 8

Group remote
2 3

2 3

controller
201 ~ 250 2 4 5 6 4 5 6
Fixed
10 1

90 1 90 1 90 1
7 8

7 8

7 8
2 3

2 3

2 3

System remote
000, 201 ~ 250 4 5 6 4 5 6 4 5 6
controller
System controller

100 10 1

90 1 90 1 90 1
7 8

7 8

7 8
2 3

2 3

2 3

ON/OFF remote
000, 201 ~ 250 4 5 6 4 5 6 4 5 6
controller
100 10 1

90 1 90 1 90 1
7 8

7 8

7 8
2 3

2 3

2 3

G-50A 000, 201 ~ 250 4 5 6 4 5 6 4 5 6

100 10 1

90 1 90 1
7 8
7 8

2
2 3

2 3

LMAP02-E 201 ~ 250 4 5 6 4 5 6


Fixed
10 1

4- 13
System Design

(3) System example

Setting of the switches when the units are shipped from the factory is as follows.
• Outdoor unit : Address : 00
On CN41
SW2-1: OFF
• Indoor unit : Address : 00
• Remote controller : Address : 100
• LMAP : Address : 247
On CN41
SW 1-2 : OFF

Example 1

Outdoor unit

00
Indoor unit

CN41 CN40 00 00 00 00 00
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
DipSW2-1
OFF TB3

SRU 1
MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1 Wireless R/C

MA R/C : PAR-20MAA
SRU(Signal receiving unit) : PAR-FA31MA NOTE
Wireless R/C : PAR-FL31MA • It is not necessary to set all of address.

Example 2

Outdoor unit

51
Indoor unit

CN41 CN40 01 02 03 04 05
Power supply unit
(PAC-SC34KUA) TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
DipSW2-1
ON TB3
TB7
SRU 1
MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)
000
MJ103 1 Wireless R/C

MA R/C : PAR-20MAA
SRU(Signal receiving unit) : PAR-FA31MA NOTE
Wireless R/C : PAR-FL31MA • It is necessary to set addresses indoor
Programme timer : PAC-SC32PTA unit and outdoor unit with MJ103.

4- 14
System Design
Example 3
Outdoor unit
(PUMY, PUHY, PUY)
51
Indoor unit

CN41 CN40 01 02 03 04 05
TB3
DipSW2-1
OFF

Main R/C : PAR-F27MEA 101 103 153 105


Sub R/C : PAR-F27MEA Simple R/C Main Sub Main Program
Program timer : PAC-SC32PTA R/C R/C R/C timer

NOTE
• It is necessary to install the other polarity wires when the wireless R/C is used.
Example 4
Outdoor unit
(PURY, PQRY) Group 1 Group 2
51
BC controller
CN41 CN40 52 01 02 03 04 05
TB3 TB2
DipSW2-1
OFF

101 104 154


Main Sub
R/C R/C

NOTE
• BC address = O/U address + 1
• R/C address = the smallest address of indoor unit + 100 in same group
• Sub R/C address = Main R/C address + 50
• Indoor units should be set with a branch number.

Example 5
NOTE
Outdoor unit • Indoor units should be set with a branch number.
(Big R2) • Be sure to set up the address number of the indoor unit connected to BC
controller (slave) more higher than the address numbers of the indoor units
51
connected to BC controller (master).
• BC (master) address = O/U address + 1
CN41 CN40 • BC (slave) address = Lowest address within the indoor units connected to the
BC controller (slave) + 50
DipSW2-1
OFF : M-NET wiring
TB3
: Piping
52 54
BC controllers BC controllers
TB2 CMB-V-FA(master) CMB-V-FB(slave)

01 02 03 04 05 06

101 104 106

Group 1 Group 2 Group 3

4- 15
System Design

Example 6

Outdoor unit
(Super Y)
Variable capacity unit Constant capacity unit
51 52

CN41 CN40
DipSW2-1 OA Processing unit LOSSNAY
OFF 01 02 03 04 05
TB3 TB3

101 102 103 104

NOTE
• Constant capacity unit address = Variable capacity unit address + 1

Example 7
Outdoor unit
(Super Y)
Variable capacity unit Constant capacity unit
51 52

CN41 CN40
DipSW2-1
OFF 01 02 17
TB3 TB3
TB2 TB3
Transmission
booster
101 102 (PAC-SF46EPA) 117

Notes
The transmission booster (RP) is required when the number of connected indoor unit models in cooling system
exceeds the number of models specified in the chart below.

The maximum number of units that can be controlled is determined by the indoor unit model, M-NET remote
controller (PAR-F27MEA) and their capabilities.

Number of BC controllers
Zero One Two

( 1)
F27MEA
Capability of the connected indoor units
Under 200 20(40) 19(38) 18(36)
Over 200 16(32) 15(30) 14(28)
The number of indoor units and the total number of remote controllers is displayed within the parenthesis ( ).

1 If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be over 200.

4- 16
System Design
Example 8
Outdoor unit
(Super Y)
Variable capacity unit Constant capacity unit
Max. 32 indoor units.
00 00
Indoor unit

CN41 CN40 00 00 00 00
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
DipSW2-1
OFF
TB3

MA R/C MA R/C MA R/C MA R/C


(Main) (Sub)
Max. 40 MA remote controllers.

MA R/C : PAR-20MAA
NOTE
• It is not necessary to install the transmission
booster on the MA remote controller system.

Example 9
Outdoor unit
(PUMY, PUHY, PUY)
51

CN41 CN40 01 02 03 04 05
TB7 DipSW2-1 TB3
ON

202 101 102 103 104 105


Group R/C Power supply unit
Simple R/C Simple R/C Simple R/C Simple R/C Simple R/C
(PAC-SC50KUA)

NOTE
000
• It is necessary to turn on the DipSW 2-1 on the outdoor unit control board when the
G-50A centralized controller is connected.
• Be sure to connect other controllers (Ex. G50A) when the simple R/C is used
because the running mode can not be changed by simple R/C.

Example 10
Outdoor unit
(PUMY, PUHY, PUY)
51

CN41 CN40 01 02 03 04 05

DipSW2-1 TB3
ON
G-50A 000
TB3 TB2 101 102 103 104 105
Simple R/C Simple R/C Simple R/C Simple R/C Simple R/C
Power supply unit
(PAC-SC50KUA)

NOTE
• It is not necessary to connect the M-NET line between G-50A and Power supply
unit (TB2) when G-50A is connected on the indoor line.

4- 17
System Design

Example 11

Outdoor unit
(PUMY, PUHY, PUY)
51 Group 1 Group 2

CN41 CN40 01 02 03 04 05
TB7 DipSW2-1 TB3
OFF

Outdoor unit 101 105


(PUMY,PUHY,PUY)
Group 4 Group 3
56

CN41 CN40 10 09 08 07 06

DipSW2-1 TB3
TB7 OFF

110 107

NOTE
• It is necessary to change the connecter to CN40 on the outdoor unit control board (only
one outdoor unit) when the group is set between other refrigerant systems.
• It is necessary to set on the remote controller by manual when group sets on the
different refrigerant system. Please refer to remote controller installation manual.

Example 12
Outdoor unit
(PUMY,PUHY, PUY)
51

CN41 CN40 01 02 03 04
TB7 DipSW2-1 TB3
ON

Outdoor unit
101 102 103
(PURY, PQRY)
55
Group
BC controller
CN41 CN40 56 05 06 07 08 09
TB3 TB15 TB15 TB15 TB15
TB7 DipSW2-1
ON
Power supply unit
(PAC-SC50KUA) 1 Signal receiving 2 2 3
unit

000 1 Wireless R/C 2 3


G-50A

4- 18
System Design
Example 13
Outdoor unit
(PUMY, PUHY, PUY)
51

CN41 CN40 01 02 03
TB7 DipSW2-1 TB3
ON

101 102 103

Outdoor unit
G-50A (PURY, PQRY)
54
P/S BC controller
CN41 CN40 55 04 05 06
LAN DipSW2-1 TB3
ON

Outdoor unit 104 105 106


(PUMY, PUHY, PUY)
51
LOSSNAY
HUB
CN41 CN40
01 02 03
TB3
TB7 DipSW2-1
G-50A ON

101 102
P/S Outdoor unit
(PURY, PQRY)
TG-2000A
51
BC controller

CN41 CN40 52 01 02 03
TB7 DipSW2-1 TB3
G-50A ON

P/S 101 102 103


Outdoor unit
(PUMY, PUHY, PUY)
51

CN41 CN40 01 02 03
TB7 DipSW2-1 TB3
ON

101 102 103 153


Outdoor unit
(PURY, PQRY)
G-50A 54
BC controller
P/S CN41 CN40 55 04 05 06
DipSW2-1 TB3
ON
P/S = Power supply unit
(PAC-SC50KUA) 104 105 106

NOTE
• G-50A can control 50 indoor units.
• TG-2000A can control 40 G-50As.
• TG-2000A can control 2000 indoor units.

4- 19
System Design

Outdoor unit
Example 14 G-50A
(PUMY, PUHY, PUY)
000 51
Power supply unit
(PAC-SC50KUA) P/S 01 02 03
CN41 CN40
TB7 DipSW2-1 TB3
LMAP ON

247 101 102 103


Outdoor unit
(PURY, PQRY)
CN41 CN40 54
DipSW1-2 BC controller
ON
CN41 CN40 55 04 05 06
DipSW2-1 TB3
TB7 ON

Outdoor unit 104 105 106


(PUMY, PUHY, PUY)
51
LOSSNAY
LMAP
CN41 CN40
01 02 03
247
TB3
TB7 DipSW2-1
CN41 CN40 OFF
DipSW1-2
OFF
101 102
Outdoor unit
(PURY, PQRY)
51
LMAP BC controller

247 CN41 CN40 52 01 02 03


TB7 TB3
LONWORKS

DipSW2-1
CN41 CN40 OFF
DipSW1-2
OFF 101 102 103
Outdoor unit
(PUMY, PUHY, PUY)
51
LMAP
247 CN41 CN40 01 02 03
TB7 TB3
DipSW2-1
CN41 CN40 OFF
DipSW1-2
OFF
101 102 103 153
Outdoor unit
(PURY, PQRY)
54
LMAP BC controller
247 CN41 CN40 55 04 05 06
PC TB7 TB3
DipSW2-1
CN41 CN40 OFF
LONWORKS card DipSW1-2
OFF 104 105 106
LONWORKS card

LONWORKS card Other equipments (lighting, security, elevator etc.)

NOTE
• LMAP (LMAP02-E) can control 50 indoor units.
• It is necessary to turn on the DipSW1-2 on the LMAP control board and the DipSW2-1 on the
outdoor unit control board with centralized controllers (Power supply unit).
• It is necessary to change the connector to CN40 on the LMAP control board without
centralized controllers (Power supply unit).

4- 20
2. Refrigerant & Piping

System Design
2-1 System examples

Using line branches, header branches and combinations of these branches, a "free piping system" involving minimal
restrictions can be configured to give a free hand in indoor and outdoor unit refrigerant piping design.

➀ PUMY, PUHY, PUY


Multi-distribution system (PUMY only)

Outdoor unit

Indoor unit
CMY-S65

Remote Note: Cannot redistribute the pipe.


controller

Outdoor
unit
Line branching system

Branch joint

Indoor
unit

Remote
controller

Note: No further branching in the pipes is possible after the header branch.
Outdoor
unit
Header branching system

Branch header

Indoor
unit

Remote
controller
Combined line / header branching system

Outdoor Branch header


unit

Branch joint

Indoor
unit

Note: No further branching in the pipes


Remote is possible after the header branch.
controller

4- 21
➁ PURY, PQRY
System Design

Total capacity : 200 Total capacity : 252

Outdoor unit BC controller Outdoor unit


4 connections (Heat source unit) 4 connections

Heat source
unit
50 50 50 50 63 63 63 63
Indoor unit Indoor unit

Total capacity : 248 Total capacity : 250

Joint pipe
Outdoor unit 5 connections 64 connections
(Heat source unit) Reducer Outdoor unit
(Heat source unit)
Branch pipe

250
40 63 50 32 63

Refer to 2-3 Refrigerant piping selection 3 PURY,PQRY.


Cooling/heating same mode
Max. 3 sets for 1 connection
Total capacity below 160 ( 2 branches joint)

Total capacity : 310

Outdoor unit 8 connections


(Heat source unit)

25 25 20 20 40 40 40 20 40 40

Cooling/heating same mode Cooling/heating same mode


Max. 3 sets for 1 connection
Total capacity below 80 ( 1 branch)

Total capacity : 700

Outdoor unit 8 connections 6 connections


Big R2

100 100 100 100 100 100 100

4- 22
2-2 Restrictions on refrigerant piping lengths

System Design
➀ PUMY Item Pipe section Allowable length
A+B+C
Total pipe length +a+b+c+d+e 100m max.
Outdoor unit
Furthest pipe length (L) A+C+e or A+B+c 70m max.

Furthest pipe length (l) after


C+e or B+c 30m max.
first branch
Outdoor unit
H 30m max.
Btwn. indoor & installed above
outdoor units Outdoor unit
installed below H' 20m max.
A
Btwn. indoor & indoor units h 12m max.

Branch header
B Cap

a b c
First branch
(branch joint) C Indoor unit Indoor unit Indoor unit
H, H'

h
Branch joint d
Indoor unit
e
Indoor unit

Outdoor unit
L

Item Pipe section Allowable length

Total pipe length a+b+c+d+e 100m max.

Furthest pipe length (L) e 30m max.


CMY-S65
Outdoor unit
H 30m max.
Btwn. indoor & installed above
outdoor units Outdoor unit
a b
20m max.
H, H'

installed below H'

Indoor unit Indoor unit Btwn. indoor & indoor units h 12m max.
c d

Indoor unit Indoor unit


h

Indoor unit

4- 23
System Design

➁ PU(H)Y-(P)200·250·315 Item Pipe section Allowable length Equivalent length


Outdoor unit A+B+C+D
Total pipe length +a+b+c+d+e+f+g 240m max. –

Furthest pipe length (L) A+C+D+g or A+B+d 120m 140m

Furthest pipe length (r) after


C+D+g or B+d 40m max. 40m max.
first branch
Outdoor unit
H 50m max. –
H'= 40m (when the outdoor units installed below : Note 2)

Btwn. indoor & installed above


H= 50m (when the outdoor units installed above)

A outdoor units Outdoor unit


installed below H' 40m max. –

Btwn. indoor & indoor units h 15m max. –

B Branch header
d
a b c
Indoor
First branch Indoor Indoor Indoor unit
unit unit unit
(branch joint)

Difference in height between


C Furthest pipe length : L = 120m max

indoor units : 15m max.


Furthest pipe length after 1st joint :r= 40m max.

D
e f g
Branch joint
Indoor Indoor
unit unit
Indoor
unit
Notes: 1. No further branching in the pipes is possible after the header branch.
2. When cooling operation is performed when the outdoor temp. is 10˚C or lower (R407C units : 0˚C or lower) : H'= 4m or less.
model 200 : 0.47
3. Equivalent pipe length (m) : Actual pipe length + model 250 : 0.50 ✕ number of bent.
model 315 : 0.70
➂ PUHY-(P)400·500
Item Pipe section Allowable length Equivalent length
A+B+C+D
Total pipe length +a+b+c+d+e+f+g 220m max. –
Outdoor
unit
Furthest pipe length (L) A+C+D+g or A+B+d 100m 125m

Furthest pipe length (r) after


C+D+g or B+d 30m max. 30m max.
first branch
Outdoor unit
H 50m max. –
Btwn. indoor & installed above
A outdoor units Outdoor unit
H' = 40m (when the outdoor units installed below : Note 2)

installed below H' 40m max. –


H = 50m (when the outdoor units installed above)

Btwn. indoor & indoor units h 15m max. –

B Branch header
d
a b c Indoor
First branch
(branch joint) Indoor Indoor Indoor unit
unit unit unit
Difference in height between

C
Furthest piping length: L = 100m max.
indoor units: 15m max.

Furthest piping length after 1st joint: r = 40m max.

D h
e f g
Branch joint Indoor Indoor
unit unit
Indoor
unit
Notes: 1. No further branching in the pipes is possible after the header branch.
2. When cooling operation is performed when the outdoor temp. is 10˚C or lower : H'= 4m or less.

3. Equivalent pipe length (m) : Actual pipe length + model 400 : 0.70 ✕ number of bent.
model 500 : 0.80

4- 24
System Design
➃ PUHY-(P)600·650·700·750 Constant Variable
capacity unit capacity unit
Distributor(gas)
Constant Variable Oil balance pipe (accessory)
capacity unit capacity unit (accessory) I
Gas pipe B
(for distribution
within the unit)

Gas pipe A
Liquid pipe B
Liquid pipe A Distributor (liquid)(accessory)
Gas pipe (main) C Liquid pipe (main) C
G : Indicates piping connection points
A (Note 5) B
H' = 40m (when the outdoor units installed below : Note 3)

Distributor(liquid)
Distributor(gas)
H = 50m (when the outdoor units installed above)

Branch header
C F
✕ Cap
First branch
d e f
(branch joint) Indoor Indoor Indoor
unit unit unit

Difference in height between


Furthest piping length: L = 100m max.

indoor units: 15m max.


Furthest piping length after 1st joint: R = 40m max.

E h
a b c
Branch joint
Indoor Indoor
unit unit
Indoor
unit

Notes: 1. Connect the variable capacity unit and constant capacity unit with Distributor kit (accessory) in the filed.
2. Distributor kit is attached with Constant capacity unit.
3. Mount the constant capacity unit on the left and variable capacity unit on the right.
(as seen from the front of the unit)
4. When cooling operation is performed when the outdoor temp. is 10˚C or lower : H'= 4m or less.
model 600 : 0.80
model 650 : 0.95
model 700 : 0.95
5. Equivalent pipe length (m) : Actual pipe length + ✕ number of bent.
model 750 : 0.95
6. Set the constant capacity unit and variable capacity unit in accordance with the G dimension given
in the figure above. (G = 0.01m)
7. No further branching in the pipes is possible after the header branch.

Item Pipe section Allowable length Equivalent length


A+B+C+D+E+F
Total pipe length +a+b+c+d+e+f 220m max. –

Furthest pipe length (L) A(B)+C+D+E+c 100m max 125m

Furthest pipe length (R) after


D+E+c 40m max. –
first branch
The oil balance pipe (Distributor kit: accessory) must be
used. If any other piping is used, the length of the oil bal-
Oil balance pipe I ance pipe must be no more than 3m (max. equivalent –
length 4m), and height from the bottom of the unit must
be no more than 0.1m.
Btwn. distributor (liquid) &
variable capacity unit, A, B (Liquid line) 4m max. 5m
constant capacity unit
Btwn. distributor (gas) &
A (Gas line) 4m max. 5m
constant capacity unit

Outdoor unit
installed above H 50m max. –
Btwn. indoor &
outdoor units Outdoor unit
installed below H' 40m max. –

Btwn. indoor & indoor units h 15m max. –


Btwn. variable ca pacity unit & Must be installed on same frame, and
constant capacity unit – there must be no high/low difference. –

4- 25
System Design

➄ PURY-(P)200·250
Pipe Allowable Equivalent
Item section
Note: length(max) length(max)
The value in ( ) in the right A+B+a+b 240m
Outdoor unit table is applied when indoor Total pipe length +c+d+e ✻

220m
(Heat source unit) total capacity exceeds 130%
120m (110m) 140m (132.5m)
of outdoor unit capacity. Farthest pipe length A+e ✻
100m (90m) ✻125m (115m)

Between outdoor and 80m (70m) 80m(70m)


A ✻ ✻
BC controller 70m (60m) 70m (60m)
Less than 80 (70)m
40m 40m
H = Less than 50m (Higher outdoor unit than indoor unit)
H' = Less than 40m (Lower outdoor unit than indoor unit)

✻ ✻
Indoor - BC controllers e 30m 30m

A H
Indoor - Higher outdoor 50m –
Outdoor Lower outdoor
H' 40m –

Indoor - BC controller h1 15m –

BC controller Indoor - Indoor h2 15m –


✻for PURY-200·250YEMC-A
Less than 30m

a Joint pipe
✻h1 = Less than 15m

(option) Branch pipe


Indoor CMY-Y102S-F
unit b B
✻h2 = Less than 15m

Indoor
unit c d e
(Models over 81) Indoor Indoor
unit unit

Max. 3 sets for 1 connection


Total capacity 80 and below

Indoor
unit

model 200 : 0.47


Equivalent pipe length (m) : Actual pipe length + ✕ number of bent.
model 250 : 0.50
✻When over 125 capacity index of indoor unit is connected, it is less than 10m not only between indoor to indoor but also
indoor and BC controller.

✻For PURY-P200·250YEM-A
130% or less
over 130%
245

240

Additional refrigerant
235
charge 22.5kg
230
Total pipe length (m)

225

220
operation area
215

210

205

200

195
0 10 20 30 40 50 60 70 80 90

Between outdoor unit and BC controller (m)

Please follow the following steps to ensure that piping lengths are within specified limits.
1. If a plot of piping lengths falls within the shaded area, piping lengths are within specification.
2. If a plot of piping lengths falls out of the shaded area then check the additional refrigerant charge amount.
✻If the additional refrigerant charge amount is less than 22.5kg then the piping lengths are within specification.
✻If the additional refrigerant charge amount is above 22.5kg then the piping lengths are out of specification and must be
shortened or the indoor unit sizes must be reduced.

4- 26
System Design
➅ PURY-P400·500

*Note :
Connecting indoor units 80-160 capacity index Connecting indoor units 200, 250 capacity index

Liquid Liquid
pipe pipe
Gas pipe Gas pipe
Outdoor unit

90(80)m max.

BC controller (Master)
C h3 =15(10)m max.
BC controller (Slave)
H

Branch pipe

h1 =15(10)m max.
h1 =15(10)m max.

CMY-Y-102S-F
a b B

indoor 1 c d 40m max. e


indoor 2
h2 =15(10)m max.

(Models 200, 250) indoor 3 indoor 4


(Models 81 to 160)
Max.3 sets indoor units to
1 connection.
Total capacity 80 and below
indoor 5

Item Pipe section Allowable length

Total pipe length A+B+C+a+b+c+d+e 250m max. (220m max. when Outdoor to BC (Master) is over 70m)

Furthest pipe length A+C+e 100m max. (90m max. when over 130% connection) ✻
Length
Outdoor-BC (Master) A 90m max. (80m max. when over 130% connection)

BC(Master or Slave)-Indoor B+d or C+e 40m max.

Indoor-Outdoor H 50m max. (Lower position of outdoor than indoor)

Height Indoor-BC (Master, Slave) h1 15m max. (10m max. on 125, 140 indoor)
difference
Indoor-Indoor h2 15m max. (10m max. on 125, 140 indoor)

BC (Master)-BC (Slave) h3 15m max. (10m max. on 125, 140 indoor)

✻ Equivalent length 125m max. (115m max. when over 130% connection)
Equivalent pipe length : Allowable pipe length + model 400 : 0.7 ✕ number of bent model 500 : 0.8

4- 27
System Design

➆ PQRY Pipe Allowable Equivalent


Item section
Note: length length
Heat source unit The value in ( ) in the right A+B+a+b
table is applied when indoor Total pipe length 220m max. –
+c+d+e
total capacity exceeds 130%
of outdoor unit capacity. Farthest pipe length A+e 100m ( 90m) 125m (115m)

Between outdoor and 70m max. 70m max.


Less than 70 (60)m A (60m max.) (60m max.)
BC controller
H = Less than 50m (Higher outdoor unit than indoor unit)
H' = Less than 40m (Lower outdoor unit than indoor unit)

Indoor - BC controllers e 30m max. 30m max.


A H
Indoor - Higher outdoor 50m max. –
Outdoor Lower outdoor
H' 40m max. –

Indoor - BC controller h1 15m max. –


BC controller Indoor - Indoor h2 15m max. –

Less than 30m

a Joint pipe
✻h1 = Less than 15m

(option) Branch pipe


Indoor CMY-Y102S-F
unit b B
✻h2 = Less than 15m

Indoor
unit c d e
(Models over 81) Indoor Indoor
unit unit

Max. 3 sets for 1 connection


Total capacity 80 and below

Indoor
unit

model 200 : 0.47


Equivalent pipe length (m) : Actual pipe length + ✕ number of bent.
model 250 : 0.50
✻When over 125 capacity index of indoor unit is connected, it is less than 10m not only between indoor to indoor but also
indoor and BC controller.

Item Pipe section Allowable length Equivalent length


➇ PQHY
A+B+C+D
Total pipe length +a+b+c+d+e+f+g 220m max. –

Heat source unit Furthest pipe length (L) A+C+D+g or A+B+d 100m 125m

Furthest pipe length (r) after


C+D+g or B+d 30m max. 30m max.
first branch
Outdoor unit
H 50m max. –
Btwn. indoor & installed above
H'= 40m (when the outdoor units installed below : Note 2)

outdoor units Outdoor unit


H= 50m (when the outdoor units installed above)

A installed below H' 40m max. –

Btwn. indoor & indoor units h 15m max. –

Branch header
B
d
a b c Indoor
First branch Indoor Indoor Indoor unit
unit unit unit
(branch joint)
Difference in height between

C Furthest pipe length : L = 100m max


indoor units : 15m max.

Furthest pipe length after 1st joint :r= 40m max.

D
e f g
Branch joint
Indoor Indoor
unit unit
Indoor
unit
Notes: 1. No further branching in the pipes is possible after the header branch.
2. Equivalent pipe length (m) : Actual pipe length + model 200 : 0.47 ✕ number of bent.
model 250 : 0.50

4- 28
System Design
2-3 Refrigerant piping selection
➀ PUMY
Outdoor unit Branch header
B

Branch joint
a b c d
C Indoor unit Indoor unit Indoor unit Indoor unit
A
e f
Branch joint
Indoor unit Indoor unit

Outdoor unit

a b c d e

CMY-S65 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Note : • No further branching is possible after the header branch.


• Model 100 and 125 of indoor unit can not be connected with CMY-Y68 and CMY-S65.

(1) Outdoor unit - 1st branch (Pipe A)


Outdoor unit model Liquid pipe Gas pipe

PUMY-125 ø 9.52 ✕ 0.8t ø 19.05 ✕ 1.0t

(2) Branch joint / Header


Type of
branch pipe Branch number Branch pipe model

Joint - CMY-Y62-C-E
For 4 branches CMY-Y64-C
Header
For 8 branches CMY-Y68
Multi-distribution For 5 branches CMY-S65
pipe

(3) Branch - Branch (Pipe B,C)


Total capacity Liquid pipe Gas pipe
of indoor units
~ 80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t
81 ~ ø9.52 ✕ 0.8t ø19.05 ✕ 1.0t

(4) Branch - Indoor unit (Pipe a, b, c, d, e, f)


• Indoor unit capacities
Indoor unit model Liquid pipe Gas pipe
The capacity of an indoor unit is the same
20,25,32,40 ø6.35 ✕ 0.8t ø12.7 ✕ 0.8t as the number used for its type
identification.
50,63,71,80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t
Examples:
100,125 ø9.52 ✕ 0.8t ø19.05 ✕ 1.0t PEFY-P63VM ➞ Capacity = 63
✻ The thickness of pipe is Japanese
Standard. Please choose the thickness
according to your country standard
referring to above chart.

4- 29
➁PUHY, PUY
System Design

Outdoor unit Branch header


B

a b c d
First branch
(branch joint) C Indoor unit Indoor unit Indoor unit Indoor unit
A
D
e f g
Branch joint
Indoor unit Indoor unit Indoor unit
• Super Y
Constant Variable
Constant capacity unit Variable capacity unit capacity unit capacity unit
(PUHN-(P)200·250) (PUHY-(P)400·500)
Distributor(gas)
Oil balance pipe (accessory)
(accessory)
Gas pipe B
(for distribution
• This unit requires a within the unit)
Distributor kit (accessory).
Gas pipe A
(ø 28.58) Liquid pipe B (ø 15.88)
A1 A2 Liquid pipe A Distributor (liquid)(accessory)
Distributor(liquid) (ø 12.7)
Distributor(gas) Gas pipe (main) C Liquid pipe (main) C
Branch header : Indicates piping connection points
A3 F
✕ Cap
First branch a b c
(branch joint) D Indoor unit Indoor unit Indoor unit

E
d e f
Branch joint
Indoor unit Indoor unit Indoor unit
Note : • No further branching is possible after the header branch.
• Arrange the total capacity of the indoor units less than 330, connected on the downstream side by the header branch. It over
that, branch pipes on the upstream side using the branch joint.
• Model 200 and 250 can not be connected with header branch.
• Model 20 can not be connected with PUHY-(P) 315, 400, 500.
• Always select CMY-302-F for the first branch of PUHY-(P) 600, 650, 700, 750.
• Distributor kit is attached with Constant capacity unit (PUHN).
(1) Outdoor unit - 1st branch (Pipe A,A1,A2,A3) (2) Branch joint / Header
Outdoor unit model Liquid pipe Gas pipe Type of Total capacity of
✻1 branch pipe indoor units Branch pipe model
PU(H)Y-(P)200 ø 12.7 ✕ 0.8t ø 25.4 ✕ 1.3t
PUHN-(P)200 ø 12.7 ✕ 0.8t ø 28.58 ✕ 1.45t ~ 160 CMY-Y102S-F
PU(H)Y-(P)250 161 ~ 330 CMY-Y102L-F
ø 12.7 ✕ 0.8t ø 28.58 ✕ 1.45t
PUHN-(P)250 331 ~ 630
PUHY-(P)315 ø 12.7 ✕ 0.8t ✻2
ø 31.75 ✕ 1.6t Joint CMY-Y202-F
The 1st branch of
✻3
PUHY-(P)400 ø 15.88 ✕ 1.0t ø 34.93 ✕ 1.75t PUHY-(P)315, 400, 500
✻4
PUHY-(P)500 ø 15.88 ✕ 1.0t ø 34.93 ✕ 1.75t 631 or above
✻5
PUHY-(P)600 ø 19.05 ✕ 1.0t ø 34.93 ✕ 1.75t The 1st branch of CMY-Y302-F
PUHY-(P)650 ø 19.05 ✕ 1.0t ø 41.28 ✕ 2.1t PUHY-(P)600, 650, 700, 750
PUHY-(P)700 ø 19.05 ✕ 1.0t ø 41.28 ✕ 2.1t PUHY-(P)600, 650, 700, 750 Distributor kit (accessory)
PUHY-(P)750 ø 19.05 ✕ 1.0t ø 41.28 ✕ 2.1t For 4 branches CMY-Y104-F
✻1 The pipe of 28.58mm can be used for the gas pipe of PU(H)Y-(P)200. Header For 7 branches CMY-Y107-F
✻2 The pipe of 34.93mm can be used for the gas pipe of PUHY-(P)315. For 10 branches CMY-Y1010-F
✻3 The pipe of 31.75mm can be used for the gas pipe of PUHY-(P)400.
✻4 The pipe of 38.1mm can be used for the gas pipe of PUHY-(P)500.
✻5 The pipe of 38.1mm can be used for the gas pipe of PUHY-(P)600.
(4) Branch - Indoor unit (Pipe a, b, c, d, e, f, g)
(3) Branch - Branch (Pipe B,C,D,E,F) Indoor unit model Liquid pipe Gas pipe
Total capacity 20,25,32,40 ø6.35 ✕ 0.8t ø12.7 ✕ 0.8t
Liquid pipe Gas pipe
of indoor units 50,63,71,80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t
~ 80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t 100,125,140 ø9.52 ✕ 0.8t ø19.05 ✕ 1.0t
81 ~ 160 ø12.7 ✕ 0.8t ø19.05 ✕ 1.0t 200 ø12.7 ✕ 0.8t ø25.4 ✕ 1.3t
✻✻
161 ~ 330 ø12.7 ✕ 0.8t ø25.4 ✕ 1.3t 250 ø12.7 ✕ 0.8t ø28.58 ✕ 1.3t
ø31.75 ✕ 1.6t
331 ~ 480 ø15.88 ✕ 1.0t or • Indoor unit capacities
ø34.93 ✕ 1.75t The capacity of an indoor unit is the same as the number used
ø38.1 ✕ 1.9t for its type identification.
481 ~ 630 ø15.88 ✕ 1.0t or Examples:
ø34.93 ✕ 1.75t PEFY-P63VM ➞ Capacity = 63
631 ~ ø19.05 ✕ 1.0t ø41.28 ✕ 2.1t
✻✻ The pipe of 28.58mm can be used for the gas pipe of PU(H)Y-(P)200.
❇ The thickness of pipe is Japanese Standard.
Please choose the thickness according to your country standard
referring to above chart.
4- 30
System Design
➂PURY, PQRY
Outdoor unit
(Heat source unit)

A
BC controller Reduction (attached) Branch joint
B

a Joint pipe b c d e
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

(1) Outdoor unit - BC controller (Pipe A)


Outdoor unit model High press. pipe Low press. pipe
PURY-(P)200
ø 19.05 ✕ 1.0t *ø 25.4 ✕ 1.3t
PQRY-P200

PURY-(P)250
ø 19.05 ✕ 1.0t ø 28.58 ✕ 1.45t
PQRY-P250

The pipe of 28.58mm can be used for the gas pipe of (P)200.

(2) Branch joint


• Joint pipe CMY-R160-H
Total capacity of 234
Branch joint
indoor units
~ 160 CMY-Y102S-F

Liquid line side: ø9.52 ID


Gas line side : ø19.05 ID
Liquid line side: 3/8F (Flare)
Gas line side : 5/8F (Flare) With insulation cover

(3) BC controller - Branch (Pipe B)


Total capacity of Gas pipe
Liquid pipe
indoor units
~ 80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t
81 ~ 160 ø9.52 ✕ 0.8t ø19.05 ✕ 1.0t

(4) Branch or BC controller - Indoor unit (Pipe a,b,c,d,e,f,g)


Indoor unit model Liquid pipe Gas pipe ✻ The thickness of pipe is Japanese Standard.
Please choose the thickness according to your
20,25,32,40 ø6.35 ✕ 0.8t ø12.7 ✕ 0.8t country standard referring to above chart.
• Indoor unit capacities
50,63,71,80 ø9.52 ✕ 0.8t ø15.88 ✕ 1.0t
The capacity of an indoor unit is the same as the
100,125,140 ø9.52 ✕ 0.8t ø19.05 ✕ 1.0t number used for its type identification.
Examples:PEFY-P63VM ➞ Capacity = 63

Liquid pipe Gas pipe


Model number
h i j k r
200 ø12.7 ø9.52 ø25.4 ø19.05 ø15.88
250 ø12.7 ø9.52 ø28.58 ø19.05 ø15.88

4- 31
System Design

4PURY-P400·500

Outdoor unit
i BC controller

CMY-R160-HA
BC controller h
k
CMY-R160-H r j
A C
BC controller Indoor unit
Reduction (attached) Branch joint
B

a Joint pipe b c d e

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

• Joint pipe CMY-R160-H


(1) Outdoor unit - BC controller (Pipe A) 234
Outdoor unit model High press. pipe Low press. pipe

PURY-P400 ✻ ø 25.4 ø 34.93

PURY-P500 High pressure line side: ø9.52 ID


✻ ø 25.4 ø 34.93
Low pressure line side : ø19.05 ID
✻ The pipe of ø 22.22 can be used for the high press pipe. High pressure line side:3/8F (Flare)
Low pressure line side :5/8F (Flare) With insulation cover

(2) Branch joint CMY-R160-HA


Total capacity of
Branch joint
indoor units 377
~ 160 CMY-Y102S-F ø19.1
160 ~ CMY-Y102L-F
ø19.1
ø25.4 ID

(3) BC controller - Branch (Pipe B) (4) BC controller - BC controller (Pipe C)


Total capacity of Liquid pipe Gas pipe High press Low press
indoor units Liquid pipe
gas pipe gas pipe
~ 80 ø9.52 ø15.88
81 ~ 160 ø9.52 ø19.05 ø19.05 ø28.58 ø12.7

(5) Branch or BC controller - Indoor unit (Pipe a,b,c,d,e,f,g)


Indoor unit model Liquid pipe Gas pipe ✻ The thickness of pipe is Japanese Standard.
Please choose the thickness according to your
20,25,32,40 ø6.35 ø12.7 country standard referring to above chart.
• Indoor unit capacities
50,63,71,80 ø9.52 ø15.88
The capacity of an indoor unit is the same as the
100,125,140 ø9.52 ø19.05 number used for its type identification.
Examples:PEFY-P63VM ➞ Capacity = 63

Liquid pipe Gas pipe


Model number
h i j k r
200 ø12.7 ø9.52 ø25.4 ø19.05 ø15.88
250 ø12.7 ø9.52 ø28.58 ø19.05 ø15.88

4- 32
System Design
2-4 Example of refrigerant piping selection

➀ Example 1

Outdoor unit : PUHY-200

Pipe A
Select by outdoor unit
capacity. (Table 1)
Pipe B
Liquid pipe Branch header
ø12.7 Select by total capacity of
Gas pipe ø 25.4 indoor units on Select by number of
downstream side. indoor units connected.
A (Table-3) (Table-2)
Liquid pipe ø12.7
Model CMY-Y104-F
Gas pipe ø 25.4
Branch joint 1
Select by total capacity of
indoor units on
downstream side. (Table-
2)
Model CMY-Y102L-F 4-branch header
Joint 1
B
Joint 2
C
Pipe C d e a b c
Select by total capacity of
indoor units on 32 50 40 63 63
downstream side.
(Table-3) Type Type Type Type Type
Liquid pipe ø12.7
Gas pipe ø 19.05
Branch joint 2 Pipes a to e
Select by total capacity of
indoor units on Same as size of indoor unit
downstream side. (Table-4) pipes.
(Table-2)
Model CMY-Y102L-F

(1) Selection of branch pipe kit


Branch area Branch pipe kit selection method Branch pipe kit model
Joint 1 32 + 40 + 50 + 63 + 63 = 248 (161 or above) CMY-Y102L-F
Joint 2 32 + 50 = 82 (160 or below) CMY-Y102S-F
Header For 4 branches with 8 HP outdoor unit CMY-Y104-F

(2) Selection of pipe size


Pipe area Refrigerant pipe selection method Liquid pipe size Gas pipe size
A Same as size of outdoor unit's refrigerant pipe ø12.7 ø25.4
B 40 + 63 + 63 = 166 (160 or above) ø12.7
C 32 + 50 = 82 (81 ~ 160) ø19.05
a Same as size of indoor unit's refrigerant pipe ø6.35 ø12.7
b ø9.52 ø15.88
c
d ø6.35 ø12.7
e ø9.52 ø15.88

4- 33
System Design

➁ Example 2

Outdoor unit : PUHY-400

Pipe A
Select by outdoor unit
capacity. (Table 1)
Pipe B
Liquid pipe Branch header
ø15.88 Select by total capacity of
Gas pipe ø 31.75 indoor units on Select by number of
downstream side. indoor units connected.
A (Table-3) (Table-2)
Liquid pipe ø12.7
Model CMY-Y104-F
Gas pipe ø 25.4
Branch joint 1

CMY-Y202-F

Joint 1 4-branch header


B
Joint 2 Joint 3
C D
Pipe C e f g a b c d
Select by total capacity of
indoor units on 100 32 50 40 63 100 125
downstream side.
(Table-3) Type Type Type Type Type Type Type
Liquid pipe ø12.7
Gas pipe ø 25.4
Pipes a to g
Pipe D Branch joint3 Same as size of indoor unit
Branch joint2 Select by total capacity of Select by total capacity of (Table-4) pipes.
Select by total capacity of indoor units on indoor units on
indoor units on downstream side. downstream side.
downstream side. (Table-3) (Table-2)
(Table-2) Model CMY-Y102S-F
Liquid pipe ø12.7
Model CMY-Y102L-F
Gas pipe ø 19.05

(1) Selection of branch pipe kit


Branch area Branch pipe kit selection method Branch pipe kit model
Joint 1 – CMY-Y202-F
Joint 2 32 + 50 + 100 = 182 (160 or above) CMY-Y102L-F
Joint 3 32 + 50 = 82 (160 or below) CMY-Y102S-F
Header For 4 branches with 8 HP outdoor unit CMY-Y104-F

(2) Selection of pipe size


Pipe area Refrigerant pipe selection method Liquid pipe size Gas pipe size
A Same as size of outdoor unit's refrigerant pipe ø15.88 ø31.75
B 40 + 63 + 100+ 125 = 328 (161 ~ 330) ø12.7 ø25.4
C 32 + 50 + 100 = 182 (161 ~ 330)
D 32 + 50 + = 82 (81 ~ 160) ø19.05
a Same as size of indoor unit's refrigerant pipe ø6.35 ø12.7
b ø9.52 ø15.88
c ø19.05
d
e
f ø6.35 ø12.7
g ø9.52 ø15.88

4- 34
System Design
➂ Example 3
Outdoor unit : PUHY-750

Pipe A, X, Y
X Select by outdoor unit Pipe E, F
capacity. (Table 1)
Select by total capacity of
Y Joint 0 Liquid pipe ø 19.05 indoor units on downstream Branch header
A side. (Table-3)
Gas pipe ø 41.28 Select by number of
Liquid pipe ø 12.7 indoor units connected.
Liquid pipe ø 15.88 E
X Gas pipe ø 25.4 (Table-2)
Branch joint 0, 1 Gas pipe ø 38.1
Liquid pipe ø 12.7 Model CMY-Y104-E
Distributor kit Liquid pipe ø 12.7 F
Joint 0 (accessory) A Y Gas pipe ø 28.58
Gas pipe ø 28.58
Joint 1 CMY-Y302-F
Joint 1 Joint 4 4-branch header
B E
Joint 2 Joint 3
Pipe B, C, D C D
Select by total capacity of F
indoor units on downstream g
side. (Table-3) e f a b c d
Liquid pipe ø 15.88
B 100 32 50 40 63 100 125
Gas pipe ø 38.1
Type Type Type Type Type Type Type
Liquid pipe ø 12.7
C
Gas pipe ø 25.4 Pipes a to i
Liquid pipe Branch joint 2, 3 Branch joint 4, 5 Joint 5
ø 12.7 Same as size of
D Select by total capacity of Select by total capacity of
Gas pipe ø 19.05 indoor units on indoor unit
indoor units on i (Table-4) pipes.
downstream side. (Table-2) downstream side. (Table-2) h
Joint 2 CMY-Y102L-F Joint 4 CMY-Y202-F 125 125
Joint 3 CMY-Y102S-F Joint 5 CMY-Y102L-F Type Type

(1) Selection of branch pipe kit


Branch area Branch pipe kit selection method Branch pipe kit model
Joint 0 – Distributor kit (accessory)
Joint 1 – CMY-Y302-F
Joint 2 32 + 50 + 100 = 182 (161 ~ 330) CMY-Y102L-F
Joint 3 32 + 50 = 82 (160 or below) CMY-Y102S-F
Joint 4 40 + 63 + 100 + 125 ✕ 3 = 578 (331 ~ 630) CMY-Y202-F
Joint 5 125 ✕ 2 = 250 (161 ~ 330) CMY-Y102L-F
Header For 4 branches with 8 HP outdoor unit CMY-Y104-F

(2) Selection of pipe size


Pipe area Refrigerant pipe selection method Liquid pipe size Gas pipe size
X Same as size of outdoor unit's refrigerant pipe ø15.88 ø38.1
Y Same as size of outdoor unit's refrigerant pipe ø12.7 ø28.58
A Same as size of outdoor unit's refrigerant pipe ø19.05 ø41.28
B 40 + 63 + 100 + 125 ✕ 3 = 578 (331 ~ 630) ø15.88 ø38.1
C 32 + 50 + 100 = 182 (161 ~ 330) ø12.7 ø25.4
D 32 + 50 = 82 (81 ~ 160) ˝ ø19.05
E 40 + 63 + 100 +125 = 328 (161 ~ 330) ˝ ø34.93
F 125 ✕ 2 = 250 (161 ~ 330) ˝ ø28.58
a Same as size of outdoor unit's refrigerant pipe ø6.35 ø12.7
b ˝ ø9.52 ø15.88
c ˝ ø19.05
˝
d, h ,i ˝ ˝
˝
e ˝ ˝
˝
f ˝ ø6.35 ø12.7
g ˝ ø9.52 ø15.88

4- 35
System Design

4 Example 4
Outdoor unit : PURY-P250

BC controller
A
Joint

c T branch 2 T branch 3
d e
b

a
T branch 1

f g
h i j

20 100 20 100 20 20 25

Max 3 indoors for 1 connection Max 3 indoors for 1 connection


Total capacity below 160 using Joint Total capacity below 80
(using 2 branches)

(1) Selection
(1) Selection of branch
of branch pipe
pipe kitkit
Branch area Branch pipe kit selection method Branch pipe kit model
Joint – CMY-R160-H
T branch 1 Capacity Index = 100 + 20 = 120 CMY-Y102L-F
T branch 2 Capacity Index = 20 + 20 + 25 = 65 CMY-Y102S-F
T branch 3 Capacity Index = 20 + 25 = 45 CMY-Y102S-F

(2) Selection
(2) Selection of pipe
of pipe size
size
Pipe area Refrigerant pipe selection method High pressure Low pressure
A Outdoor unit pipe ø19.05 ø28.58
a Capacity Index = 20 ø6.35 ø12.7
b Capacity Index = 120 (100+20) ø12.7 ø19.05
c Capacity Index = 100 ø9.52 ø19.05
d Capacity Index = 65 (20+20+25) ø9.52 ø15.88
e Capacity Index = 45 (20+25) ø9.52 ø15.88
f Capacity Index = 100 ø9.52 ø19.05
g Capacity Index = 20 ø6.35 ø12.7
h Capacity Index = 20 ø6.35 ø12.7
i Capacity Index = 20 ø6.35 ø12.7
j Capacity Index = 25 ø6.35 ø12.7

4- 36
System Design
➄ Example 5
Outdoor unit : PURY-P500

A CMB-P106V-FA B CMB-P108V-FB
(Master) (Slave)

Joint 2
Joint 1 Joint 3
T branch 2 T branch 3
c d e Joint 4

T branch 1

f g h i j k l m n

20 100 20 100 20 20 25 200 125

Max 3 indoors for 1 connection. Max 3 indoors for 1 connection.


Total capacity below 160 using Joint. Total capacity below 80 for 1 branch.
(using 2 branches)

(1) Selection of branch pipe kit


Branch area Branch pipe kit selection method Branch pipe kit model
Joint 1,2,3 - CMY-R160-H
Joint 4 - CMY-R160-HA
T branch 1 Capacity Index = 100 + 20 = 120 CMY-Y102L-F
T branch 2 Capacity Index = 20 + 20 + 25= 65 CMY-Y102S-F
T branch 3 Capacity Index = 20 + 25 = 45 CMY-Y102S-F

(2) Selection of pipe size


Pipe area Refrigerant pipe selection method High pressure Low pressure
A Outdoor unit pipe ø25.4 ø34.93

Pipe area Refrigerant pipe selection method Low pressure gas High pressure gas Liquid
B BC-BC pipe ø28.58 ø19.05 ø12.7

Pipe area Refrigerant pipe selection method Liquid pipe size Gas pipe size
c Capacity Index = 120 (100 + 20) ø12.7 ø19.05
d Capacity Index = 65 (20 + 20 + 25) ø9.52 ø15.88
e Capacity Index = 45 (20 + 25) ø9.52 ø15.88
f Capacity Index = 20 ø6.35 ø12.7
g Capacity Index = 100 ø9.52 ø19.05
h Capacity Index = 20 ø6.35 ø12.7
i Capacity Index = 100 ø9.52 ø19.05
j Capacity Index = 20 ø6.35 ø12.7
k Capacity Index = 20 ø6.35 ø12.7
l Capacity Index = 25 ø6.35 ø12.7
m Capacity Index = 200 ø12.7 ø25.4
n Capacity Index = 125 ø9.52 ø15.88

4- 37
System Design

2-5 Calculation of additional refrigerant charge

➀ PUMY-(P)125YM(A)
(1) Refrigerant charge
The following amount of refrigerant is being charged into the outdoor unit at factory shipment.
Refrigerant of 3kg equivalent to 50-m total extended piping length is already included when the outdoor unit is
shipped. Thus, if the total extended piping length is 50m or less, there is no need to change with additional
refrigerant.
If the total extended piping length exceeds 50m, calculate the required additional refrigerant charge using the
procedure shown on the below.
If the calculated additional refrigerant charge is a negative amount, do not charge with any refrigerant.

Outdoor unit PUMY-(P)125YM(A)

Refrigerant charge 8.5kg

(2) Formula to obtain an amount of additional refrigerant charge


The additional amount of refrigerant to be added is calculated from the size of the extended liquid pipes and
their length (in meters).
Additional amount (kg) = (0.06 ✕ L1) + (0.024 ✕ L2) - 3kg

Where L1 : Length of ø9.52 liquid pipe (m)


L2 : Length of ø6.35 liquid pipe (m)

❇1 : Any fractions below 0.01kg in the result of the calculation should be round up.
(Examples : 10.52 ➞ 10.6kg)

Example: PUMY-125YM

ø9.52 (10m) Capped

ø9.52 (20m)

ø9.52 ø6.35 ø6.35 ø6.35 ø6.35(5m)


(5m) (10m) (5m) (5m)
ø9.52 (10m)
Type 50 Type 25 Type 40 Type 25 Type 20

This calculation concerns only the liquid pipes.

ø9.52 : 10m + 20m + 10m + 5m = 45m


ø6.35 : 10m + 5m + 5m + 5m = 25m

Calculation of additional amount :


Additional amount (kg) = (0.06 ✕ 45) + (0.024 ✕ 25) - 3.0 = 0.3 kg (rounded up)

4- 38
System Design
➁ PU(H)Y-(P)200·250·315, PQHY-P200·250
(1) Refrigerant charge
The following amount of refrigerant is being charged into the outdoor unit at factory shipment. As the amount does not
include that for extended piping, charge it additionally in the filed.

PUHY-P200 PUHY-P250 PUHY-P315 PUHY-200 PUHY-250 PUHY-315


Outdoor unit PUY-P200 PUY-P250 PUY-P315 PUY-200 PUY-250 PUY-315 PQHY-P200 PQHY-P250

Refrigerant charge 7.0kg 7.0kg 9.0kg 7.0kg 7.0kg 9.0kg 7.0kg 8.0kg

(2) Formula to obtain an amount of additional refrigerant charge


The additional amount of refrigerant to be added is calculated from the size of the extended liquid pipes and
their length (in meters).
Additional amount (kg) = (0.25 ✕ L1) + (0.12 ✕ L2) + (0.06 ✕ L3) + (0.024 ✕ L4) + A

Where L1 : Length of ø15.88 liquid pipe (m)


A: Additional refrigerant charge
L2 : Length of ø12.7 liquid pipe (m)
by total capacity of indoor
L3 : Length of ø9.52 liquid pipe (m)
units connected.
L4 : Length of ø6.35 liquid pipe (m)

Additional refrigerant
Total capacity of indoor units connected
charge (A)

~ 160 1.5
161 ~ 330 2.0
331 ~ 480 2.5
481 ~ 630 3.0
631 ~ 4.0

❇1 : Any fractions below 0.01kg in the result of the calculation should be round up.
(Examples : 10.52 ➞ 10.6kg)

Example: PUHY-200

ø12.7 (20m) Capped

ø9.52 (10m)

ø9.52 ø6.35 ø6.35 ø6.35 ø6.35(10m)


(10m) (20m) (10m) (10m)
ø12.7 (30m)
Type 50 Type 25 Type 40 Type 25 Type 25

This calculation concerns only the liquid pipes.


ø12.7 : 30m + 20m = 50m
ø9.52 : 10m + 10m = 20m
ø6.35 : 20m + 10m + 10m + 10m = 50m

Total capacity of indoor units connected:


40 + 25 + 40 + 25 + 25 = 155

Calculation of additional amount :


Additional amount (kg) = (0.12 ✕ 50) + (0.06 ✕ 20) + (0.024 ✕ 50) + 1.5 = 9.90 kg

The result of 9.90 kg is rounded up to one decimal place (0.1kg). Therefore,


Additional amount = 9.9 kg

4- 39
System Design

➂ PURY, PQRY
(1) Refrigerant charge
The following amount of refrigerant is being charged into the outdoor unit at factory shipment. As the amount does not
include that for extended piping, charge it additionally in the filed.

Outdoor unit PURY-P200 PURY-P250 PURY-200 PURY-250 PQRY-P200 PQRY-P250 PURY-P400 PURY-P500

Refrigerant charge 10.5kg 10.5kg 10.0kg 11.0kg 7.5kg 8.5kg 20.0kg 22.0kg

(2) Formula to obtain an amount of additional refrigerant charge


The calculation of additional refrigerant charge is based on the size and length of extended high pressure side piping.
Additional amount (kg) = (0.31 ✕ L0) + (0.25 ✕ L0') + (0.16 ✕ L1) + (0.12 ✕ L2) + (0.06 ✕ L3) + (0.024 ✕ L4) + A + B

Where L0 : Length of high pressure pipe ø25.4 (m) A: Additional refrigerant charge by total
✻L0' : Length of high pressure pipe ø22.22 (m) capacity of indoor units connected.
L1 : Length of high pressure pipe ø19.05 (m) B: Additional refrigerant charge for BC
L2 : Length of liquid pipe ø12.7 (m) controller. (Slave)
L3 : Length of liquid pipe ø9.52 (m)
L4 : Length of liquid pipe ø6.35 (m)

Additional Total capacity of


Total capacity of indoor units connected refrigerant indoor units Additional refrigerant charge
charge connected
PURY-200 PURY-250 PURY-P400, P500 A B
PURY-P200 PURY-P250 A
PQRY-P200 PQRY-P250 ~ 330 2.0
100 ~ 160 125 ~ 160 1.5
331 ~ 480 2.5
161 ~ 300 161 ~ 375 2.0 3.0
481 ~ 630 3.0

631 ~ 4.0

Note: Raise a fraction of the calculation result less than 0.01kg to a unit. (Examples : 10.52 ➞ 10.6kg)
✻ ø22.22 pipe can be used in place of ø25.4 pipe.

Example: PURY-200

ø19.05 (40m)

BC controller
ø6.35 (15m) ø9.52 (15m)
ø9.52 (10m) ø9.52 (5m)

Type 32 Type 63 Type 63 Type 63

This calculation concerns only the liquid (high press) pipes.


ø19.05 : 40m
ø9.52 : 10m + 15m = 25m
ø6.35 : 15m
Total capacity of indoor units connected:
32 + 63 + 63 + 63 = 221
Calculation of additional amount :
Additional amount (kg) = (0.16 ✕ 40) + (0.06 ✕ 30) + (0.024 ✕ 15) + 2 = 10.56 kg
The result of 10.56 kg is rounded up to one decimal place (0.1kg). Therefore,
Additional amount = 10.6 kg

4- 40
System Design
➃ PUHY-(P)400·500
The amounts of refrigerant given in the table below are added in the outdoor units at the factory prior to shipment.
However, they do not cover the requirements for piping extensions, and additional refrigerant must be added at
the installation site.

Outdoor unit model PUHY-(P)400 PUHY-(P)500

Amount of refrigerant being added


at the factory prior to shipment 16kg 21kg

(1) Formula for calculation


The additional amount of refrigerant to be added is calculated from the size of the extended liquid pipes and
their length (in meters).
Additional amount (kg) = (0.29 ✕ L1) + (0.25 ✕ L2) + (0.12 ✕ L3) + (0.06 ✕ L4) + (0.024 ✕ L5) + A

Where L1 : Length of ø19.05 liquid pipe (m) A: Additional refrigerant charge


L2 : Length of ø15.88 liquid pipe (m) by total capacity of indoor
L3 : Length of ø12.7 liquid pipe (m) units connected.
L4 : Length of ø9.52 liquid pipe (m)
L5 : Length of ø6.35 liquid pipe (m)

Additional refrigerant
Total capacity of indoor units connected charge (A)
~ 160 1.5
161 ~ 330 2.0
331 ~ 480 2.5
481 ~ 630 3.0
631 ~ 4.0

❇1 : Any fractions below 0.01kg in the result of the calculation should be round up.
(Examples : 10.52 ➞ 10.6kg)

(2) Example: PUHY-P500

ø12.7 (20m) Capped

ø12.7 (10m)

ø9.52 ø9.52 ø9.52 ø9.52 ø63.5


(10m) (20m) (10m) (10m) (10m)
ø15.88 (30m)
Type 125 Type 100 Type 125 Type 63 Type 25

This calculation concerns only the liquid pipes.


ø15.88 : 30m
ø12.7 : 10m + 20m = 30m
ø9.52 : 10m + 20m + 10m + 10m = 50m
ø6.35 : 10m

Total capacity of indoor units connected:


125 + 100 + 125 + 63 + 25 = 438

Using the above formula:


Additional amount (kg) = (0.25 ✕ 30) + (0.12 ✕ 30) + (0.06 ✕ 50) + (0.024 ✕ 10) + 2.5 = 16.84 kg

The result of 9.90 kg is rounded up to one decimal place (0.1kg). Therefore,


Additional amount = 1.69 kg

4- 41
System Design

➄ PUHY-(P)600·650·700·750
The amounts of refrigerant given in the table below are added in the outdoor units at the factory prior to shipment.
However, they do not cover the requirements for piping extensions, and additional refrigerant must be added at
the installation site.

Outdoor unit model PUHN-(P)200 PUHN-(P)250 PUHY-(P)400 PUHY-(P)500

Amount of refrigerant being added


6.5kg 8.5kg 16kg 21kg
at the factory prior to shipment

(1) Formula for calculation


The additional amount of refrigerant to be added is calculated from the size of the extended liquid pipes and
their length (in meters).
Additional amount (kg) = (0.29 ✕ L1) + (0.25 ✕ L2) + (0.12 ✕ L3) + (0.06 ✕ L4) + (0.024 ✕ L5) + A
Where L1 : Length of ø19.05 liquid pipe (m)
L2 : Length of ø15.88 liquid pipe (m) A: Additional refrigerant charge
L3 : Length of ø12.7 liquid pipe (m) by total capacity of indoor
L4 : Length of ø9.52 liquid pipe (m) units connected.
L5 : Length of ø6.35 liquid pipe (m)

Additional refrigerant
Total capacity of indoor units connected
charge (A)

~ 160 1.5
161 ~ 330 2.0
331 ~ 480 2.5
481 ~ 630 3.0
631 ~ 4.0

✻1 : Any fractions below 0.01kg in the result of the calculation should be round up.
(Examples : 10.52 ➞ 10.6kg)
✻2 : PUHY-(P)600·650·700·750
Additional amount (kg) 73kg - (Amount of refrigerant being added at the factory prior to shipment)

ex. PUHY-750YSMC
Additional amount (kg) 73kg - (22 + 8.5)
42.5kg

4- 42
System Design
(2) Example: PUHY-750

ø12.7 (2m) ø15.88 (1m)


ø15.88 (25m) ø12.7 (4m) ø9.52 (1m)
Type 100
ø19.05 (70m)
ø9.52 (1m)
Type 125
ø12.7 (4m) ø9.52 (1m)
ø15.88 (1m) Type 80
ø6.35 (1m)
Type 40
ø12.7 (2m) ø12.7 (24m) ø9.52 (1m)
Type 50

ø6.35 (1m)
Type 32

ø12.7 (24m) ø6.35 (1m)


Type 40

ø9.52 (1m)
Type 80
ø12.7 (2m) ø12.7 (24m) ø9.52 (1m)
Type 63
ø6.35 (1m)
Type 32

ø12.7 (24m) ø9.52 (1m)


Type 71

ø6.35 (1m)
This calculation concerns only the liquid pipes. Type 20
ø19.05 : 70 + 1 = 71m
ø15.88 : 1 + 25 = 26m
ø12.7 : 2 + 4 + 4 + 2 + 24 + 24 + 2 + 24 + 24 = 110m
ø9.52 : 1 + 1 + 1 + 1 + 1 + 1 + 1 = 7m
ø6.35 : 1 + 1 + 1 + 1 + 1 = 5m

Total capacity of indoor units connected:


125 + 100 + 80 ✕ 2 + 71 + 63 + 50 + 40 ✕ 2 + 32 ✕ 2 +20 = 733

Using the above formula:


Additional amount (kg) = (0.29 ✕ 71) + (0.25 ✕ 26) + (0.12 ✕ 110) + (0.06 ✕ 7) + (0.024 ✕ 5) + 4 = 44.83kg

Additional amount 73kg - (Amount of refrigerant to be added). Therefore,

Additional amount (kg) = 73kg - (22 + 8.5) = 42.5kg

4- 43
2-6 Electric characteristics
System Design

(1) Indoor unit Symbols: MCA : Max. Circuit Amps (=1.25✕FLA) FLA : Full Load Amps
IFM : Indoor Fan Motor Output : Fan motor rated output
Units Power supply IFM
Model
Volts / Hz Voltage range MCA(A) Output(kW) FLA(A)
20 0.25 0.028 0.20
PMFY-P-VBM-A 25·32 0.26 0.028 0.21
40 0.33 0.028 0.26
32·40 0.75 0.030 0.60
PLFY-P-VKM-A 50 220-240V / 50Hz 0.80 0.030 0.64
220V / 60Hz 0.85 0.030
63 0.68
80 1.08 0.070 0.86
PLFY-P-VAM-A 100 1.79 0.120 1.43
125 2.05 0.120 1.64
20·25 0.54 0.033 0.43
32 0.60 0.033 0.48
PLFY-P-VLMD-B 40 Max.: 264V 0.96 0.075 0.77
50 Min.: 198V 0.96 0.075 0.77
220-240V / 50Hz
63 1.31 0.078 1.05
80 1.38 0.078 1.10
PLFY-P-VLMD-A 100 1.50 0.078 ✕ 2 1.20
125 1.69 0.078 ✕ 2 1.35
20·25 0.63 0.033 0.50
32 0.68 0.033 0.54
40 1.10 0.075 0.88
50 1.10 0.075 0.88
PLFY-NLMD 220V / 60Hz
63 1.25 0.078 1.00
80 1.35 0.078 1.08
100 2.29 0.078 ✕ 2 1.83
125 2.35 0.078 ✕ 2 1.85
20·25 0.30/0.35 0.023 0.24/0.28
PEFY-P-VML-A
32 0.40/0.53 0.032 0.32/0.42
40·50 1.21/1.61 0.08 0.97/1.29
63 220-240V / 50Hz 1.49/1.95 0.12 1.19/1.56
71 220-240V / 60Hz 1.58/2.18 0.14 1.26/1.74
80 1.85/2.40 0.18 1.48/1.92
PEFY-P-VMH-A
100·125 3.03/3.93 0.26 2.42/3.14
140 3.10/3.98 0.26 2.48/3.18
200 380-415V / 50Hz Max.: 456V 2.03/2.33 0.54 1.62/1.86
250 380-415V / 60Hz Min.: 342V 2.50/2.88 0.87 2.00/2.30
20·25 0.91 0.15 0.73
32 1.01 0.17 0.81
40 1.15 0.19 0.92
50 1.23 0.20 0.98
Max.: 264V
PEFY-P-VMM-A 63 220-240V / 50Hz Min.: 198V 1.34 0.22 1.07
71·80 1.44 0.25 1.15
100 1.68 0.29 1.34
125 2.38 0.40 1.90
140 2.44 0.42 1.95

4- 44
System Design
Units Power supply IFM
Model
Volts / Hz Voltage range MCA(A) Output(kW) FLA(A)
20·25·32 0.66/0.73 0.075 0.53/0.58
40·50 0.75/0.89 0.075 0.60/0.71
63 0.85/1.03 0.078 0.68/0.82
PDFY-P-VM-A 71 0.90/1.10 0.078 0.72/0.88
80 1.03/1.26 0.078 0.82/1.01
100 1.60-1.68/1.70 0.140 1.28-1.34/1.36
125 1.94-2.04/2.30 0.190 1.55-1.63/1.84 (50/60Hz)
PKFY-P-VAM-A 20·25 220-240V / 50Hz Max.: 264V 0.25 0.017 0.20
PKFY-P-VGM-A 32·40·50 220V / 60Hz Min.: 198V 0.40 0.030 0.32
63 0.54 0.04 0.43
PKFY-P-VFM-A
100 0.65 0.07 0.52
40 0.58 0.054 0.46
63 0.75 0.070 0.60
PCFY-P-VGM-A
100 0.91 0.090 0.73
125 1.38 0.150 1.10
20·25 0.24 / 0.31 0.020 0.19 / 0.25
32 0.36 / 0.38 0.030 0.29 / 0.30
PFFY-P-VLEM-A 40 0.40 / 0.41 0.035 0.32 / 0.33
50 0.50 / 0.51 0.035 0.40 / 0.41
63 0.58 / 0.59 0.045 0.46 / 0.47
20·25 Max.: 264V 0.24 / 0.31 0.020 0.19 / 0.25
220-240V / 50Hz
32 Min.: 198V 0.36 / 0.38 0.030 0.29 / 0.30
PFFY-P-VLRM-A 40 0.40 / 0.41 0.035 0.32 / 0.33
50 0.50 / 0.51 0.035 0.40 / 0.41
63 0.58 / 0.59 0.045 0.46 / 0.47
50 1.85 0.081 ✕ 2 1.48
GUF-RD(H)2
100 3.49 0.16 ✕ 2 2.79

4- 45
(2) Outdoor unit (Cooling)
Symbols: MCA : Max.Circuit Amps
System Design

Refrigerant type : R407C SC : Starting Current RLA : Rated Load Amps


Units Power supply Compressor Fan
Model RLA(A)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output(kW)
220 28.3
Max.: 253V
PUMY-P125VMA 50 230 35.38 3.5 22 0.06 ✕ 2 27.1
Min.: 188V
240 26.0
380 9.6
PUMY-P125YM(A) 400 12.0 3.5 8 0.06 ✕ 2 9.1
415 8.8
380 10.6
PUHY-P200YEM-A 0.38
400 16.01 5.3 8 10.1
PUY-P200YEM-A
415 9.7
380 14.4
PUHY-P250YEM-A 0.38
400 17.75 6.8 8 13.6
PUY-P250YEM-A
415 13.2
380 20.3
PUHY-P315YEM-A 400 25.38 8.6 8 0.38 19.2
PUY-P315YEM-A
415 18.5
380 26.7
103(50Hz)
PUHY-P400YEM-A 400 33.38 4.5+7.5 0.38 ✕ 2 25.4
96(60Hz)
415 24.5
380 33.5
138(50Hz)
PUHY-P500YEM-A 400 41.88 7.5+7.5 0.38 ✕ 2 31.9
125(60Hz)
415 30.7
380 40.3
145(50Hz)
PUHY-P600YSEM-A 400 50.38 4.5+7.5+5.5 0.38 ✕ 3 38.3
132(60Hz)
415 36.9
380 43.4
150(50Hz)
PUHY-P650YSEM-A 400 54.25 4.5+7.5+7.5 137(60Hz) 0.38 ✕ 3 41.2
50 Max.: 456V
415 39.7
/
60 380 Min.: 342V 46.8
145(50Hz)
PUHY-P700YSEM-A 400 58.50 7.5+7.5+5.5 132(60Hz) 0.38 ✕ 3 44.5
415 42.9
380 49.9
150(50Hz)
PUHY-P750YSEM-A 400 62.38 7.5+7.5+7.5 137(60Hz) 0.38 ✕ 3 47.4
415 45.7
380 10.4
PURY-P200YEM-A 400 16.01 5.3 8 0.38 9.9
415 9.5
380 14.1
PURY-P250YEM-A 400 17.75 6.8 8 0.38 13.3
415 12.9
380 26.7
7.5+4.5 103(50Hz) 0.38 ✕ 2
PURY-P400YEM-A 400 33.38 25.4
96(60Hz)
415 24.5
380 33.5
138(50Hz)
PURY-P500YEM-A 400 41.88 7.5+7.5 0.38 ✕ 2 31.9
125(60Hz)
415 30.7
380 12.1
PQHY-P200YEM-A 400 16.01 5.5 12 0.35✕2
– 11.5
415 11.1
380 15.2
PQHY-P250YEM-A 400 19.00 7.5 12 – 14.4
415 13.9

4- 46
System Design
Units Power supply Compressor Fan
Model RLA(A)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output(kW)
380 12.1
PQRY-P200YEM-A 400 16.01 5.5 12 – 11.5
50 415 Max.: 456V 11.1
/
60 380 Min.: 342V 15.2
PQRY-P250YEM-A 400 19.00 7.5 12 – 14.4
415 13.9

Symbols: MCA : Max.Circuit Amps


Refrigerant type : R22 SC : Starting Current RLA : Rated Load Amps
Units Power supply Compressor Fan
Model RLA(A)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output(kW)
220 17.5
50 230 23.00 2.6 15 0.04 ✕ 2 16.7
PUMY-71VM
240 16.0
60 220 18.1
220 34.9
50 230 33.5
PUMY-125VMA 44.00 3.5 22 0.06 ✕ 2
240 32.2
60 220 Max.: 253V 33.6
Min.: 188V 19.0
PUHY-200TEM-A 208 16.01 5.3 15 0.38 18.0
17.2
25.8
PUHY-250TEM-A 60 220 17.63 6.8 15 0.38 24.4
23.3
36.3
PUHY-315TEM-A 230 34.3
24.88 8.6 15 0.38
32.8
380 9.6
PUMY-125YM
400 12.00 3.5 8 0.06 ✕ 2 9.1
PUMY-125YMA
415 8.8
380 10.4
PUHY-200YEM-A
400 16.01 5.3 8 0.38 9.9
PUY-200YEM-A 50
415 Max.: 456V 9.5
/
60 380 Min.: 342V 12.0
PUHY-200YEMC-A 400 16.01 6.0 8 0.38 11.4
415 11.0
PUHY-250YEM-A 380 14.1
PUHY-250YEMC-A 400 17.75 6.8 8 0.38 13.3
PUY-250YEM-A 415 12.9
380 19.6
PUHY-250YEMK-A 400 24.50 7.9 8 0.38 18.6
415 18.0
PUHY-315YEM-A 380 19.9
PUHY-315YEMK-A 400 18.9
PUHY-315YEMC-A 25.38 8.6 8 0.38
PUY-315YEM-A 415 18.2
380 26.7
PUHY-400YEM-A
400 103(50Hz)
PUHY-400YEMK-A 33.38 7.5+4.5 0.38 ✕ 2 25.4
96(60Hz)
PUHY-400YEMC-A 415 24.5

4- 47
System Design

Units Power supply Compressor Fan


Model RLA(A)
Hz Volts Voltage range MCA(A) Output(kW) SC(A) Output(kW)
380 32.0
PUHY-500YEM-A 138(50Hz)
PUHY-500YEMK-A 400 40.00 7.5+7.5 0.38✕ 2 30.4
125(60Hz)
PUHY-500YEMC-A 415 29.3
380 39.2
PUHY-600YSEM-A 145(50Hz)
PUHY-600YSEMK-A 400 49.00 7.5+4.5+5.5 0.35 ✕ 3 37.2
132(60Hz)
PUHY-600YSEMC-A 415 35.9
PUHY-650YSEM-A 380 42.2
PUHY-650YSEMK-A 400 52.75 7.5+4.5+7.5 150(50Hz) 0.35 ✕ 3 40.1
137(60Hz)
PUHY-650YSEMC-A 415 38.7
50 380 Max.: 456V 45.3
PUHY-700YSEM-A 145(50Hz)
/ 56.63 7.5+7.5+5.5 0.35 ✕ 3
PUHY-700YSEMK-A 400 Min.: 342V 132(60Hz) 43.0
60
PUHY-700YSEMC-A 415 41.5
PUHY-750YSEM-A 380 48.4
PUHY-750YSEMK-A 400 60.50 7.5+7.5+7.5 150(50Hz) 0.35 ✕ 3 46.0
137(60Hz)
PUHY-750YSEMC-A 44.3
415
380 16.2
PURY-P200YEMC-A 400 20.25 5.5 12 0.38 15.4
415 14.9
380 17.8
PURY-P250YEMC-A 400 22.25 7.5 12 0.38 16.9
415 16.3

4- 48
System Design
(3) BC controller
Units Power supply
Model RLA(A)
Hz Volts Voltage range MCA(A) MFA(A)
220 0.31
CMB-P104V-F 230 0.39 15 0.30
240 0.28
220 0.38
CMB-P105V-F 230 0.48 15 0.36
240 0.35
220 0.45
CMB-P106V-F 230 0.57 15 0.43
240 0.41
220 0.58
CMB-P108V-F 230 0.87 15 0.56
240 0.53
220 0.72
CMB-P1010V-F 230 0.90 15 0.69
240 0.66
220 0.92
CMB-P1013V-F 230 1.17 15 0.88
50 240 Max.: 264V 0.85
/
60 220 Min.: 198V 1.13
CMB-P1016V-F 230 1.42 15 1.08
240 1.03
220 0.63
CMB-P108V-FA 230 0.79 15 0.60
240 0.58
220 0.76
CMB-P1010V-FA 230 0.95 15 0.73
240 0.70
220 0.97
230 1.22 15 0.93
CMB-P1013V-FA
240 0.89
220 1.17
230 1.47 15 1.12
CMB-P1016V-FA
240 1.08
220 0.58
230 0.73 15 0.56
CMB-P108V-FB
240 0.53

Symbols
MCA : Max.Circuit Amps (=1.25 × max. RLA)
MFA : Max. Fuse Amps
RLA : Rated Load Amps

4- 49
2-7 Installation
2-7-1 Selection of installation site
System Design

➀ PUMY, PUHY, PUY


Select space for installing outdoor unit, which will meet the following conditions:

• no direct thermal radiation from other heat sources


• no possibility of annoying neighbors by noise from unit
• no exposition to strong wind
• with strength which bears weight of unit
• note that drain flows out of unit when heating
• with space for air passage and service work shown 2-7-2 Space required around unit
Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and
leak of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• When having cooling operation at an outside air temperature of below 10°C, in order to obtain steady
operation of unit, select an installation site not exposed directly to rain and snow, or install air outlet and
inlet ducts. Install the outdoor unit at the same position on the same floor, or above, the indoor unit.
• Do not use unit in any special environment where oil, steam and sulfuric gas exist.

Installation restriction on outdoor unit when cooling operation is performed when the outdoor air
temperature is 10°C or lower.

OK NG A A 4 m or less

(Same floor as indoor unit, or floor above)

➁ PURY

Select space for installing heat source unit, which will meet the following conditions:
• no direct thermal radiation from other heat sources
• no possibility of annoying neighbors by noise from unit
• with strength which bears weight of unit
• note that drain flows out of unit when heating
• with space and service work shown 2-7-2 Space required around unit
Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak of
combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit in any special environment where oil, steam and sulfuric gas exist.

➂ PQHY, PQRY
Select space for installing heat source unit, which will meet the following conditions:

• no direct thermal radiation from other heat sources


• no possibility of annoying neighbors by noise from unit
• with strength which bears weight of unit
• note that drain flows out of unit when heating
• with space and service work shown 2-7-2 Space required around unit
Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and leak of
combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit in any special environment where oil, steam and sulfuric gas exist.
• No exposure to rain or other moisture. (the heat source unit should only be used indoors)
• The declining gradient of the exhaust pipe should be higher than 1/100.

4- 50
System Design
➃ BC controller
• Place not exposed to rain. (BC controller is a special machine for indoor use.)
• Place with large enough service space.
• Place in which refrigerant pipes can be provided within the limitations.
• Place not exposed to direct radiant heat from other heat sources.
• Do not install the unit in any oily steamy place or near any machine that generates high frequencies. Doing so may
cause a risk of fire, erroneous operation or dew drop.
• Place with less noise effect generated from other units.
• Place in which water piping, refrigerant piping and electrical wiring can be done easily.
• Avoid places exposed to the generation, inflow, accumulation or leakage of flammable and sulfuric gases.
• Place in which a downward pitch of more than 1/100 can be taken for drain piping.

1. For hanging from the ceiling

• Provide a inspection hole 450 mm square to the ceiling surface as


shown in 2-7-2 Space required around unit.
• Above the ceiling of corridor, bath room, ., where persons are not
regularly there
(Avoid installing at around center of the room.)
• Place with strength to the degree that hanging bolts can be mounted
(that sustains a pull-out load of 60kg per bolt)
• Be sure to install BC controllers at level.

2. For stacking on a rack


• Place in which sufficient space can be obtained around a rack
• Place with floor strength that sustains the entire weight

Warning:
Be sure to install the unit in a place that well sustains the entire
weight.
If there is a lack of strength, it may cause the unit to fall down,
resulting in an injury.

Caution:
Be sure to install the unit at level.

4- 51
2-7-2 Space required around unit
System Design

➀ PUMY
Service space around the outdoor unit
• If an optional air guide is needed, install it according to the manual or technical documents supplied with the air guide.
• In the case of an optional branch pipe kit, the service space specified in the manual supplied with the kit is required
around the outdoor unit, so refer to the manual when installing it.
(mm)

(1) When installing a single outdoor unit


➀ Service space

Min.
500
Maintain an easily accessible service space in front of the unit
as shown in the diagram. Min. 10
Min. Service space
500

➁ Top obstacles
If there are no obstacles in front or at the left or right of the unit, obstacles above the unit are permitted as shown
in the diagram.
• The front, right and left sides must be free of obstacles.

➂ Unobstructed front (blowing side)


If the size of the space reserved for the unit is as shown in the diagram, the unit can be installed so that obstacles
are at the right, left and rear.
• The front and top must be unobstructed.
• The height of obstacles on either side must be the same or lower than that of the outdoor unit.

➃ Obstacles in the front (blowing side) only


If there are obstacles in front of the unit, keep the back, left/right, & top unobstructed.
➁ ➂ ➃
(mm) 10
in.
Min. M
500

Min.
10
0
150 Min.
10 n.
50
i n. Mi
M (mm) (mm)

➄ Obstacles at the front & rear only


The outdoor unit cannot be used except if the following conditions are met:
An optional outdoor air outlet guide (left/right & top unobstructed) must be fit- Min.150
ted.
Moreover, if there is no natural wind flowing between the obstacles, keep the
height or width of the obstacles within the following range to prevent the risk of
short cycling. (If either the front or rear satisfies the requirements, there is no
special restriction on the remaining side).
Min.
500

Obstruction width: 1.5 times the width of outdoor unit or smaller


Obstruction height: Unit height or lower
(mm)
Obstruction Air outlet guide

➅ Obstacles on 4 surrounding sides


The unit cannot be used if there are obstacles on all 4 surrounding sides, even if there is more than the pre-
scribed amount of space around the outdoor unit and if the top is unobstructed.

➆ Obstacles at the front & rear ➅ ➆


This unit cannot be used if the
following conditions are met: NG NG
Max.
150
3800
Max.

(mm)

4- 52
System Design
(2) When installing many outdoor units
➀ Side-by-side arrangement
Remove the side screw on the pipe cover.
Keep the top unobstructed.
• Refrigerant piping and electric wiring cannot be attached on the right side.

Min. 300
Min.
Min. Min. 10
Up to 10 units 1000
150 (mm)
Keep the top side open

➁ Face-to-face arrangement (with air outlet guide)


Fit an optional outdoor air outlet guide on each unit and set them to “upward blow”.

Min. 300

(mm)
Min. 500

➂ Face-to-face arrangement (without air outlet guides)

Min. 300

Min. 1500
(mm)

➃ Parallel arrangement (with air outlet guides)


Fit an optional outdoor air outlet guide on each unit.

(mm)
Min.1500

➄ Parallel arrangement (without air outlet guides)

Min. 3800
(mm)

4- 53
➁ PUHY, PUY
System Design

(1) Individual installation


Basic space required
A space of at least 250(450) mm is necessary at the back for inlet air. Taking servicing, etc. from the rear into account,
a space of about 450 mm should be provided, the same as at the front.

< Model : 200·250·315> D


L1 L2
B R407C units 450mm 450mm
R22 units 450mm 100mm

A L1 mm or more
E F B L2 mm or more
C Front (outside of machine room)
D Top discharge (open in principle)
A E Front inlet (open in principle)
F Rear inlet (open in principle)
C <Side view>
<Top view>

< Model : 400·500> < Model : 600·650·700·750>

B B

A A

C C
<Top view> <Top view>

When inlet air enters from right and left sides of unit
A B
h

< Model : 200·250·315>

C
H

A L1 or more
C B L2 or more
A C Front
D No restrictions on wall
D <Top view> <Side view> height (left and right)

L1 L2
R407C units 450mm 450mm
< Model : 400·500> < Model : 600·650·700·750> R22 units 450mm 100mm

B B

C A C A

D <Top view> D <Top view>

Note:
• Wall heights (H) of the front and the back sides shall be within overall height of unit.
• When the total height is exceeded, add the “h” dimension of the figure above to L1 and
L2 in the table above.

4- 54
System Design
When unit is surrounded by walls
< Model : 200·250·315>
A B A L1 or more
B L2 or more
B C Front
C D Front panel

h
E E Rear panel
D

h
L1 L2

650

325
H
A R407C units 450mm 450mm

H
R22 units 450mm 100mm
<Side view>
C
<Top view> Note:
< Model : 400·500> < Model : 600·650·700·750> • Wall heights (H) of the front and the
back sides shall be within height of
front panel and rear panel.
B B • If the panel height is exceeded,
add the “h” dimension of the figure
above to L1 and L2 in the table

Example: When h is 100


A A
The L1 dimension becomes
450+100 = 550 mm.
C C
<Top view> <Top view>

When there is an obstruction above the unit


< Model : 200·250·315>

E
A
D
When there is little space
B up to an obstruction

C F A 45° or more
B 300 mm or more
C Front
D 1000 mm or more
E Air outlet guide (procured at the site)
<Side view>
<Front view> F Rear

< Model : 400·500> < Model : 600·650·700·750>

A
A

B B

<Front view> <Front view>

4- 55
(2) Collective installation and continuous installation
System Design

Space required for collective installation and continuous installation:When installing several units, leave the space between each
block as shown below considering passage for air and people.
< Model : 200·250·315>
✻E
B A
B B
A A C C C C C

C C
✻F F F F F ✻E
D B ✻F
A

B B E
E

A
A C C G A C C G

D E D A D
B

H
A (Must be open) E L2 mm or more L1 L2
B Wall height (H) F L1 mm or more R407C units 450mm 450mm
C C C C Front G 900 mm or more R22 units 450mm 250mm
F F D 1000 mm or more H No restrictions on wall height

Note:
• Open in the two directions
• In case wall height (H) exceeds overall height of unit, add “h” dimension (h=wall height <H> – overall height
of unit) to ✻ marked dimension.
• If there is a wall at both the front and the rear of the unit, install up to three units consecutively in the side
direction and provide a space of 1000 mm or more as inlet space/passage space for each three units.

< Model : 400·500> A


B ✻E
B B
A A C C C C C
C C

D B ✻F ✻F F F F F ✻E
A

B B E
E

A
A C C G A C C G

D E D A D
B

A (Must be open) D 1000 mm or more G 900 mm or more L1 L2


B Wall height (H) E L2 mm or more H No restrictions on wall height R407C units 450mm 450mm
C Front F L1 mm or more
R22 units 450mm 250mm
Note:
• Open in the two directions
• In case wall height (H) exceeds overall height of unit, add “h” dimension (h=wall height <H> – overall height
of unit) to ✻ marked dimension.
• If there is a wall at both the front and the rear of the unit, install up to three units consecutively in the side
direction and provide a space of 1000 mm or more as inlet space/passage space for each three units.

4- 56
System Design
< Model : 600·650·700·750>
A
B ✻E
A A
C C C C
B B
C C
D ✻F
B
✻F F F F ✻E

A
B E
A (Must be open)
B Wall height (H)
C Front
A C C G A D 1000 mm or more
E L2 mm or more
F L1 mm or more
G 900 mm or more
D B E H No restrictions on wall height

L1 L2
R407C units 450mm 450mm
B R22 units 450mm 250mm
E
Note:
• Open in the two directions
C C G • In case wall height (H) exceeds overall height of unit,
add “h” dimension (h=wall height <H> – overall
height of unit) to ✻ marked dimension.
• If there is a wall at both the front and the rear of the
D D
unit, install up to three units consecutively in the
A side direction and provide a space of 1000 mm or
more as inlet space/passage space for each three
units.

4- 57
➂ PURY
System Design

(1) Individual installation


Basic space required When unit is surrounded by walls
Taking servicing, etc. from the rear into account, a space of < Model : 200·250>
about 450 mm should be provided, the same as at the front.

A B
< Model : 200·250> B

D
C E
B

h
D

h
A

650

325
H

H
E F C
<Side view>
< Model : 400·500>
A A L1 or more
B B L2 or more
c C Front
<Top view> <Side view>
D Front panel
A E Rear panel
< Model : 400·500> A 450 mm or more c
B 450 mm or more Note:
B C Front (outside of machine room) • Wall heights (H) of the front and the back sides shall
D Top discharge (open in principle) be within height of front panel and rear panel.
E Front inlet (open in principle) • If the panel height is exceeded, add the “h” dimension
F Rear inlet (open in principle) of the figure above to L1 and L2 in the table above.

L1 L2
A 450 450
c Example: When1h is 100
The L dimension becomes 450+100 = 550 mm.

When inlet air enters from right and left sides of unit When there is an obstruction above the unit

< Model : 200·250> < Model : 200·250>


A B
h

A
B
C
C B
H

C A
D
D
<Side view>

< Model : 400·500>


A L1 or more When there is little space
< Model : 400·500> up to an obstruction
B L2 or more
B
C Front
D No restrictions on wall height A 45° or more
(left and right)
C A B 300 mm or more
A
C 1000 mm or more
D D Air outlet guide
(Procured at the site)
Note: B
• Wall heights (H) of the front and the back sides shall be
within overall height of unit.
• When the total height is exceeded, add the “h” dimension
of the figure above to L1 and L2 in the table above.

L1 L2
450 450

4- 58
(2) Collective installation and continuous installation

System Design
Space required for collective installation and continuous installation:When installing several units, leave the space
between each block as shown below considering passage for air and people.

✻E
B

A A
C C

D B ✻F
A (Must be open)
B Wall height (H)
C Front
A D 1000 mm or more
B B E 450 mm or more
C C C C C F 450 mm or more
G 900 mm or more
H No restrictions on wall height
✻F F F F F ✻E
A

B E

A C C G A
Note:
• Open in the two directions
• In case wall height (H) exceeds overall height of unit,
D B E add “h” dimension (h=wall height <H> – overall
height of unit) to ✻ marked dimension.
• If there is a wall at both the front and the rear of the
unit, install up to three units consecutively in the
B E side direction and provide a space of 1000 mm or
more as inlet space/passage space for each three
units.
A
C C G

D A D

C C C

F F

4- 59
➃ PQHY, PQRY
System Design

• Please allow for the following service spaces after installation.


(All servicing can be performed from the front of the unit)
400 1150
A

400
E
500

F
G
C
600

400 1150
D

H
A Piping space (for left piping) E Piping space (for top piping)
B Heat source unit F Piping space (for left piping)
C Service space (front side) G Heat source unit
D (Top view) H (Front view)

➄ BC controller

1. For hanging from the ceiling


<Front view> (when hanging to install)
✻1 Dimensions with which pipe connection can be handled at site
100

A
Model name A Model name A
CMB-P104V-F 702 CMB-P108V-FA 1164
CMB-P105V-F 702 CMB-P1010V-FA 1164
CMB-P106V-F 702 CMB-P1013V-FA 1164
CMB-P108V-F 702 CMB-P1016V-FA 1164
CMB-P1010V-F 702 CMB-P108V-FB 702
CMB-P1013V-F 1152
CMB-P1016V-F 1152

2. When stacking on a rack


(This is a reference view showing the least installation space.)

Model name B
CMB-P104V-F 298
CMB-P105V-F 298
CMB-P106V-F 298
CMB-P108V-F 298
CMB-P1010V-F 298
CMB-P1013V-F 298
CMB-P1016V-F 298
500

CMB-P108V-FA 388
CMB-P1010V-FA 388
CMB-P1013V-FA 388
CMB-P1016V-FA 388
150 B 85 50 A 50
CMB-P108V-FB 298

4- 60
2-7-3 Connecting direction for refrigerant piping

System Design
➀ PUMY
Gas/Liquid
ø12.7
ø6.35
ø12.7
ø6.35
ø12.7
ø6.35
ø15.88
ø9.52
A ø15.88
ø9.52

As viewed from A
Rear piping

Piping cover
Secure with band
Front piping Right piping
(knockout) (knockout) Liquid line Piping cover
Gas line
Lower piping

➁ PUHY. PURY
<Model : 200·250·315> <Model : 400·500>

A
A

B C
D D
C

<Model : 600·650·700·750> A Knock-out hole


B Left piping
C Bottom piping
D Front piping
A
E Connect piping (to constant capacity unit)

Note:
A In the case of bottom piping, build a 100 mm
C
D or higher foundation so that piping will go
through the bottom of the unit.
E
C

➂ PQHY, PQRY
Refrigerant Refrigerant
piping (left) piping (right)
Water Water outlet
circulation
pipe Close valve

Close valve

Y-type
strainer Water
inlet

Drain pipe

4- 61
2-7-4 Caution for snow and seasonal wind
System Design

➀ PUMY
Precautions
Installation on a rooftop or other windy places
When installing the unit on a rooftop or other location unprotected from the wind, situate the unit’s air outlet so that it is
not directly exposed to strong winds. Strong wind entering the air outlet may impede the normal airflow and cause mal-
functions.
The following shows three examples of precautions against strong winds.

Air outlet guide

Face the outlet toward any Install an optional air outlet guide and
available wall at least 50 cm if the unit is installed at a place where
away from the wall. the powerful blast of a typhoon, etc.
comes directly into the air outlet.

Strong wind

90°

Position the unit so that the air outlet blows


perpendicularly to the seasonal wind direction,
if possible.

4- 62
➁ PU(H)Y, PURY

System Design
In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in
normal and good condition in winter time. Even in the other areas, full consideration is required for installation of unit in
order to prevent abnormal operations caused by wind or snow. When rain and snow directly fall on unit in the case
of air-conditioning operations in 10 or less degrees centigrade outdoor air, mount inlet and outlet ducts on unit
for assuring stable operations.

(1) Snow and wind


Prevention of wind and snow damages in cold or snowy areas:
Refer to the figure of snow hood shown below:

• Snow hood
<Model 200·250·315> <Model 400·500>
1093 888 1888
903

A
821
1145

B
(670)

500 (840) 500 990 (1990)

B
H

<Side view> <Front view> <Front view>


A Outlet B Inlet

Note:
1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame
base shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that
snow and wind slip through the structure. (If frame base is too wide, snow will be accumulated on it.)
2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T
Painting : Overall painting with polyester powder
Color : Munsell 5Y8/1 (same as that of unit)
4. When the unit is used in a cold region and the heating operation is continuously performed for a long time when the
outside air temperature is below freezing, install a heater to the unit base or take other appropriate measures to
prevent water from freezing on the base.

(2) Countermeasure to wind


Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.

A A

A Wind

4- 63
2-8 Joint / Header / Reduction
System Design

Liquid side Gas side


ø9.52 ø15.88
ø15.88 ø19.05 ø19.05 ø15.88

ø9.52 ø6.35
ø9.52 ø12.7 ø19.05 ø12.7

80
80
CMY-Y62C-E ø9.52 ø9.52 ø19.05 ø19.05
ø9.52 ø12.7
ø19.05 ø22.2 ø15.88 ø12.7

100 150

Reduction 70 70
Use flare nut
attached to BC 3/8F(Flare) ø6.35 ID 5/8F(Flare) ø12.7 ID
controller
234 234

CMY-R160-H ø9.52 ID ø19.05 ID


3/8F(Flare) 5/8F(Flare)

377

ø19.1
CMY-R160-HA ø25.4 ID
ø19.1

ø 15.88
ø 9.52 ø 12.7

24
ø12.7 ø 19.05
Deformed pipe ø 19.05
16.5

(Accessory) 151
Deformed pipe
CMY-Y102S-F (Accessory) 101 ø 15.88 ø 12.7 ø 19.05 ø 12.7
(OD) (OD)
ø 9.52 (OD)
ø 12.7 ø 6.35 ø 6.35 ø 19.05
(OD) ø 25.4 ø 19.05 ø 15.88
(OD) (OD)
ø 12.7 ø 9.52 NOTE: Pipe diameter is indicated ø 19.05 ø 28.6
(OD) by inside diameter. (OD) NOTE: Pipe diameter is indicated
by inside diameter.

ø 12.7 ø 19.05
ø 9.52
ø 12.7

30
ø 25.4
16.5

Deformed pipe ø 25.4


151
(Accessory)
Deformed pipe 101
(Accessory) ø 19.05 ø 15.88
CMY-Y102L-F ø 25.4 ø 19.05
ø 9.52 (OD) (OD) (OD)
ø 12.7 ø 6.35 ø 12.7
(OD) ø 19.05 ø 12.7
ø 15.88
(OD) ø 25.4
(OD)
ø 12.7 ø 9.52 NOTE: Pipe diameter is indicated ø 25.4 ø 28.6
(OD) by inside diameter. NOTE: Pipe diameter is indicated by
(OD)
inside diameter.

ø31.75 ø25.4
36

ø12.7
18.5

ø15.88
Deformed pipe
(Accessory) 170 ø31.8
Deformed pipe
ø15.88 ø25.4 ø12.7 ø25.4 ø19.05 ø25.4 ø28.6
(Accessory) 101 (OD) (OD) (OD)
CMY-Y202-F
ø15.88 ø12.7 ø12.7 ø6.35 ø25.4 ø15.88 ø31.75 ø25.4 ø31.75 ø34.93
(OD) (OD) (OD) (OD)
(OD)
ø31.75 ø28.6 (2Pcs.)
ø12.7 ø9.52 (OD) ø31.75 ø38.1
(OD) (OD)
NOTE: Pipe diameter is indicated by inside diameter. (2Pcs.)

ø31.75 ø44.45
ø44.45
ø15.88
57

ø19.05 ø19.05
24

Deformed pipe
(Accessory)
176
151 ø44.45 ø31.75
ø31.75 ø12.7 ø31.75 (OD)
Deformed pipe ø25.4
(OD) (OD)
(Accessory)
ø12.7 ø19.05 ø15.88 ø44.45 ø34.93
CMY-Y302-F ø15.88 ø31.75 ø15.88 (OD)
(OD) (OD) (OD) ø31.75 ø28.58
(OD)
ø15.88 (2Pcs.)
ø15.88 ø9.52 (OD) ø6.35 ø31.75 ø19.05 ø44.45 ø38.1
(OD) (OD) ø34.93 ø31.75 (OD)
(OD)
(2Pcs.)
ø44.45 ø41.28
(OD)
NOTE: Pipe diameter is indicated by inside diameter.
(2Pcs.)

4- 64
System Design
Liquid side Gas side

ø 9.52 ø 15.88
ø 9.52 ø 15.88 ø 19.05

ø 9.52 ø 9.52 ø 19.05 (OD) ø 15.88 ø 15.88


CMY-Y64-C
ø 6.35 ø 12.7 ø 12.7
ø 6.35
ø 9.52✕2 ø 15.88✕2 ø 15.88(OD)
(OD)
6.35✕2 ø 12.7✕2 ø 19.05
ø 9.52 ø 22.2 ø 15.88
ø 12.7 ø 19.05

ø 9.52 ø 15.88
CMY-Y68
ø 6.35 ø 6.35 ø 12.7 ø 12.7
ø 6.35 ø 12.7
ø 6.35 ø 12.7

ø 12.7 ø 9.52 ø 25.4


ø 28.6
ø 19.05
ø 19.05 ø 15.88
CMY-Y104-F ø 9.52 ø 6.35 ø 9.52 ø 15.88 ø 19.05 ø 15.88

ø 9.52 ø 6.35 ø 6.35 ø 9.52 ø 15.88 ø 12.7 ø 19.05 ø 15.88 ø 15.88 ø 19.05 ø 19.05 ø 12.7
(OD) (OD) (OD) (OD) (OD) (OD)

ø 12.7 ø 9.52 ø 15.88 ø 15.88 ø 15.88 ø 25.4 ø 28.6

ø 19.05
CMY-Y107-F
ø 6.35 ø 9.52 ø 6.35 ø 9.52 ø 6.35 ø 9.52 ø 12.7 ø 12.7 ø 12.7 ø 19.05

ø 9.52 ø 6.35 ø 6.35 ø 9.52 ø 12.7 ø 15.88 ø 15.88 ø 19.05 ø 15.88 ø 12.7 ø 19.05 ø 12.7
(OD) (OD) (OD) (OD) (OD) (OD)

ø 12.7 ø 12.7 ø 12.7 ø 12.7 ø 12.7 ø 15.88 ø 25.4 ø 28.6

ø 19.05
CMY-Y1010-F
ø 6.35 ø 6.35 ø 6.35 ø 6.35 ø 6.35 ø 15.88 ø 15.88 ø 15.88 ø 19.05 ø 19.05
ø 9.52 ø 9.52 ø 9.52 ø 9.52 ø 9.52

ø 15.88 ø 12.7 ø 19.05 ø 12.7 ø 19.05 ø 15.88


ø 9.52 ø 6.35 (OD) (OD) (OD)
(OD)

ø 41.28
ø 38.1
ø 34.93

ø 28.58
ø 19.05 ø 15.88 ø 44.5

CMC-30A

ø 12.7

Gas/Liquid
ø12.7
ø6.35 ø 6.35 ø 9.52 ø 9.52 ø 6.35
ø12.7
ø6.35 ✕2
CMY-S65 ø12.7
(PUMY only) A ø6.35
ø15.88
ø9.52 ø 12.7 ø 15.88 ø 15.88 ø 12.7
ø15.88
ø9.52 ✕2
As viewed from A

OD:Outside Diameter

4- 65
3. Caution For Refrigerant Leak
System Design

The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.

3-1 Introduction
In addition to City Multi almost all air conditioners utilize R22 or R407C as refrigerant. Though the R22, R407C is
harmless and incombustible in itself , the room to equip the air conditioner should be large to such an extent that
the refrigerant gas will not exceed the limiting concentration even if the refrigerant gas leaks in the room.

• Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken
without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described
in the unit of kg/m3 (Freon gas weight in /m3 air) for facilitating calculation.
Limiting concentration: 0.3kg/m3(R22), 0.31kg/m3(R407C) (ISO5149, EN378-1)

Outdoor unit

Flow of
(No.1 system) refrigerant

Indoor unit Room where refrigerant leaks


(Refrigerant of the whole No.1
system flows out.)

3-2 Checking procedure of limiting concentration


Check limiting concentration following step ➀~➃, and take appropriate measure depending on the situation.
➀ Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.

Amount of replenished Amount of additional Total amount of replenished


=
refrigerant per one outdoor + replenished refrigerant refrigerant in refrigerant
unit system facility (kg)

Amount of replenished Amount of additionally Note : In case one refrigerant facility is


refrigerant at factory shipment replenished refrigerant divided into 2 or more refrigerant
depending on piping systems and each system is
length or piping independent, amount of replenished
diameter at customer refrigerant of each system shall be
adopted.

➁ Calculate minimum room capacity.


Calculate room capacity by regarding portion as one room or the smaller room.
(a) Without partition (b) With partition and with opening which serve as passage
of air to adjoining room
Outdoor unit Outdoor unit

In the case of opening


Indoor unit Indoor unit
without door , or 0.15
Opening
% or more openings
(to floor space) both
Partition above and below door)

4- 66
System Design
(c) With partition and without opening which serve as passage of air to adjoining room
Outdoor unit

Indoor unit

Smallest
room

➂ Calculate refrigerant concentration with the results of ➀


Total amount of replenished
refrigerant in refrigerant facility (kg) In case the result of calculation exceeds
= Refrigerant concentration the limiting concentration, perform the
Capacity of smallest room where (kg/m )3

indoor unit is installed (m3) same calculations by shifting to the


(R22 or R407C) second smallest, and the third smallest
rooms until at last the result is below the
limiting concentration.

➃ In case limiting concentration is exceed


When limiting concentration is exceeded, change original plan or take one of the countermeasures shown below:
• Countermeasure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.

• Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.

Gas leak alarm


Countermeasure 2
Mechanical ventilator

Indoor unit

Countermeasure 1 Opening effective to ventilation

Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant
is heavier than air.

4- 67
System Design