ALTERNATIVELY, THE STRUCTURE IN SOME


3000 X 19mm DIA. COPPER CLAD AREAS WILL BE EARTHED TO A BURIED EARTH
STEEL EARTH STAKE CONDUCTOR DUE TO ABOVE GROUND EARTH
DRIVEN INTO GROUND CADWELD CONDUCTOR BEING INAPPROPRIATE.
LIFTHOLE
A CABLE A
GROUND LEVEL LADDER

EARTH CLAMP CONDUCTORS, Cu PVC Cu PVC


COPPER CLAD EARTH CONDUCTOR EARTH CONDUCTOR
MIN SIZE 70mm 2 MIN SIZE 70mm 2

B CADWELD B

600mm MIN. DEPTH BARE CONDUCTOR


OF CONDUCTOR CADWELD
BURIED EARTH GRID 600mm
CONDUCTOR 120mm CU BARE STRANDED

EARTHING OF STRUCTURAL STEEL AND MISCELLANEOUS EQUIPMENT EARTHING OF STRUCTURAL STEEL


GROUND WELL INSTALLATION

C NOTE : - POWER EARTH SYSTEM LESS THAN / EQUAL 5 OHM RESISTANCE C


- INSTRUMENT EARTH SYSTEM RESISTANCE LESS THAN/EQUAL TO 1 OHM

CABLE LADDER SHALL BE EARTHED AT


BOTH ENDS AND AT INTERVALS OF
30 METRES VIA PVC INSULATED EARTH
CABLE INSTALLED IN CABLE LADDER.

D D

REFER DETAIL 2 Cu PVC INSULATED


EARTH CONDUCTOR EARTHING BRACKET
MIN SIZE 25mm 2 USE LUG & BOLT
TO BRACKET Cu PVC INSULATED
CABLE 120mm 2

Cu PVC INSULATED
EARTH CONDUCTOR
MIN SIZE 70mm 2
500mm
MIN.
E
Cu PVC INSULATED EQUIPOTENTIAL E
600 MIN DEPTH OF BARE CONDUCTOR
EARTH CONDUCTOR LOOP
70mm 2Cu INSULATED 70mm 2Cu INSULATED
VESSEL EARTHING CADWELD BARE CONDUCTOR
BURIED EARTH GRID
FLEXIBLE COPPER BRAID ACROSS
HINGE MINIMUM 25mm2
1000mm FROM FENCE LINE
Cu PVC INSULATED EARTH CONDUCTOR CADWELD 600mm DEPTH
70mm 2Cu INSULATED TO GROUND GRID
AND TO BELOW CABLE TRAY (IF ANY) CABLE LADDER EARTHING FENCE AND GATE EARTHING

F ELECTRICAL INSTALLATION 'NO-GO' AREAS NOTES : F


SIZES OF EARTHING CONDUCTOR FOR LV MOTOR
1. Cu PVC EARTH CONDUCTORS SHALL BE
POWER CABLE SIZE EARTHING CABLE SIZE RUN IN CABLE LADDERS AS A GENERAL
(mm )2 (mm )2 1. NO CABLE LADDER SHALL BE INSTALLED UNDER AND/OR AROUND MILL FEED CHUTES. RULE BUT MAY BE RUN ALONG
EARTHING BRACKET
USE LUG & BOLT STRUCTURE USING STANDARD ANCHOR
4 4 (MINIMUM) TO BRACKET CLIPS.
2. NO CABLE LADDER SHALL BE INSTALLED UNDER GRIDMESH UNLESS UNAVOIDABLE.
6 IF UNAVOIDABLE, THEN CABLE LADDER TO BE COMPLETE WITH SUITABLE PEAKED COVERS.
10 16 Cu PVC INSULATED 3. NO ELECTRICAL EQUIPMENT, INCLUDING CABLE LADDER AND CONDUIT, IS TO BE INSTALLED IN AREAS
EARTH CONDUCTOR AROUND REMOVABLE GRIDMESH AND REMOVABLE PANELS.
16 MIN SIZE SEE TABLE
25
G
35 G
35
50 BARE CONDUCTOR BURIED
70
70 EARTH GRID 600mm

95 CADWELD
120
120
MOTOR EARTHING

REVIEWER TO COMPLETE NAME SIGN DATE OWNER : TUJUH BUKIT PROJECT


COMPANY ........................................... TITLE :
DRAWN
H NAME ........................................... ELECTRICAL STANDARD H
DESIGNED BUMI SUKSESINDO
SIGNED ........................................... Copper and Gold ELECTRICAL INSTALLATION DETAILS
DATE ...........................................
CHECKED SHEET 1 OF 6
THIS DRAWING HAS BEEN REVIEWED
0 24.07.17 ISSUED FOR CONSTRUCTION HB AS AP - FOR GENERAL COMPLIANCE WITH THE
TECH APP PT. BUMI SUKSESINDO SCALE DRAWING NUMBER REV.
REV DATE DESCRIPTION DRN DGN CHK PROJ REFERENCES DOCUMENTS DOC NO.
REQUIREMENTS OF THE CONTRACT
AND IS ISSUED FOR STATUS APPROVAL PROJ APP A3 N.T.S BSI - STD - DWG - EL - 001 0