Professional Documents
Culture Documents
JEMStar II
High Accuracy Revenue Meter
FOR GENERATION, TRANSMISSION, AND INDUSTRIAL POWER MEASUREMENT
POWER INSTRUMENTS
P O W E R M E A S U R E M E N T P R O D U C T S
Ease of Use
The JEMStar II is easy to configure with AMETEK’s
intuitive JEMWARE software that includes a
Configuration Wizard which guides you through the
necessary set-ups for your metering application.
The meter display has a User Menu which displays
configuration details without using a PC. Some
configuration details can be edited once you provide
the necessary password access. The meter includes
a built-in USB port that can be used to upload or
download meter configurations, upload firmware or
retrieve metering data using a simple USB memory
stick.
Communications
The JEMStar II can be supplied with up to seven User
communication ports including: Display
Menus
• Optical port
• (2) Serial ports – RS-232 and RS-485
• Analog or cellular modem port
• (2) Ethernet ports
• WIFI port
Communication ports support a variety of metering
protocols including DLMS, IEC-870-5-102, IEC-61850,
DNP, Modbus, and JEM binary. All ports can operate
simultaneously and independently.
SPECIFICATIONS
METER FORMS TIME SYNC USB Port:
• Meter Forms: 5, 6, 8, 9, 45, Universal • Internal clock: 0.5 sec/day accuracy • Compatible w/ USB flash drives
• 50/60HZ line frequency • Upload/download configuration
INPUTS
• External time sync options: NTP • Upgrade firmware
Voltage • Retrieve meter data
• 55-300 VAC auto-ranging OPTIONAL I/O
• Burden*: 0.5 VA @ 300V Internal I/O Communication Protocols
* Does not include auxiliary power • Digital I/O: 8 channel selectable as input or • DLMS (opt)
requirements. output. Isolated power supply for digital inputs • IEC-870-5-102
• Modbus RTU, Modbus TCP/IP (master and
Current Digital Input Rating slave)
• 1 amp: ANSI class 2 • Form A or KYZ • DNP 3.0
• 5 amps: ANSI class 10 • Maximum voltage 40 VDC • IEC 61850 (opt)
• 10 amps: ANSI class 20 Digital Output Rating • JEM binary
• Burden: 0.5 VA maximum • Form A or KYZ
• Overload: 1.5x rated class current continuous
METER DISPLAY
• Maximum open-circuit voltage: 200V DC or • 4.3" color graphic LCD
• Starting current: 0.002 A peak AC
• Registers, phasor diagram, diagnostics
• Frequency range: 45-55 Hz, 55-65 Hz • Maximum switching current: 50 mA
• User menu configuration
AUXILIARY POWER COMMUNICATIONS
MECHANICAL
Swichboard 7 Com Ports Available
• Aux Power: 55-300 VAC or 90-300 VDC
Case Styles
Port 1: Optical (Standard) • IEC
Auxiliary Power Burden • Type 2 – 19,200 baud
• 25 VA maximum
Size and Weight
Port 2: Not used • IEC: 7.5 pounds (3.4 kg)
ACCURACY Port 3: RS-232/485 Serial (opt) ENVIRONMENT
Watt Hour • User selectable: RS-232/485
• 0.05% reading (0.02% typical) • User configurable: 300 to 38400 baud Operating Temperature
• -22º to 185ºF (-30º to 85ºC)
Volts, Amps Port 4: RS-232/485 Serial (opt)
• 0.04% reading • User selectable: RS-232/485 Storage Temperature
• -40º to 185ºF (-40º to 85ºC)
• User configurable: 300 to 38400 baud
MEASUREMENTS
• Bi-directional, 4 quadrant Port 5: Internal Analog Modem (opt) Humidity
• 5 to 95% relative humidity, non-condensing
• Energy, instantaneous: per phase values • 56K baud
• Min/Max/Avg values • With optional phone home on power fail ELECTRICAL STANDARDS
• Demand: peak, present, past, thermal and • With optional RS-485 communication repeater Fast Transient
coincident
• TOU: 8 rates/day, 4 season
Port 5: Internal Cellular Modem • IEC 61000-4-4
(future) Radiated/Conducted Emissions
• TLC, LLC: per phase, delivered and received,
transformer factors or % loss • GSM/GPRS • IEC 61000-4-3, IEC-61000 4-6
Measurement Logging (optional) Port 6: Ethernet (opt) Surge Immunity
• 2 groups x 50 channels • 100 BaseT, unshielded twisted pair • IEC 61000-4-5
• Recording interval: 150/180 cycle • DHCP or fixed IP address
• Up to 12 simultaneous connections Electrostatic Discharge
• Max 407 days of storage of 100ch@ 10 minute • IEC 61000-4-2
recording intervals • WEB server, email notification
Port 7: Ethernet (opt) Surge Withstand (SWC)
REGISTERS • IEEE Standard C37.90.1
• 50 normal, 50 alternate, 50 test • 100 BaseT, unshielded twisted pair
• DHCP or fixed IP address METERING
LOAD PROFILE • IEC 62052-11, 21
• Up to 12 simultaneous connections
• 16 channels storage
• WEB server, email notification • IEC 62053-22, 61
• 1-60 minute intervals
• FCC Part 68, FCC Part 15
• Values stored in scalable counts or 32 bit Port 8: WIFI (future)
engineering units • Fixed IP address
• Optional second independent 16ch LP Group • Up to 12 simultaneous connections
• Max 365 days storage of: 32ch@ 15 minute
recording intervals
POWER INSTRUMENTS
For Customer Support European Headquarters Asia Pacific Headquarters AMETEK Instruments India Pvt. Ltd.
AMETEK Power Instruments 21 Ridgeway No. 43 Changi South Avenue 2 Divyasree NR Enclave, 4th Floor, Block A,
255 North Union Street Donibristle Industrial Estate #04-01 Singapore 486164 Plot No. 1, EPIP Industrial Area,
Rochester, NY 14605 Dalgety Bay Tel: +65.6484.2388 Whitefield, Bengaluru 560 066
Tel: +585.263.7700 Fife, KY11 9JN United Kingdom Fax: +65.6481.6588 Tel: +91-80-67823200
Fax: +585.454.7805 Tel: 0044 (1) 383825630 power.sales-asia@ametek.com Fax: +91-80-67823232
power.sales@ametek.com Fax: 0044 (1) 383826715 power.sales-india@ametek.com
power.sales-europe@ametek.com
©2017, by AMETEK, Inc. All rights reserved. PDF (210135) ISO 9001 Certified