The new Centric uPS
from 25 to 200 kw/kvA
Gamatronic is proud to present the Centric, an innovative UPS
available in 10 configurations
(25, 50, 75, 100, 125 , 150, 175, 200 kW/kVA).
For a complete IT solution we offer 2 models of the Centric
with internal batteries as a 25kVA and a 50kVA unit.
The Centric provides reliable, clean, regulated ac power at an attractive price.
For users with greater power requirements, the Centric can be operated in up
to four units in parallel.
The Centric’s double conversion topology provides high quality power regulation in accordance with
IEC 62040 VFI-SS-111 and ac-ac efficiency up to 96%.
The Centric battery is true online as per IEC 62040, guaranteeing instant availability of backup power
in the event of mains failure and provides high unique dc –ac efficiency of up to 98%.
The Centric’s vertical and horizontal modularity reduce the down time thus providing a fault tolerant
power source to critical load and application.
The Centric’s reliability flexibility, intelligent features and design make it a great choice for your data
center.
2
Power usage effectiveness (Pue) efficiency
Centric is an ideal efficient UPS for Tier 3 and 4 data centers with a low load.
The Centric can achieve 96% efficiency in a load between 20% to 60%.
100% IT LOAD
3
The PC based centric controller enhances data centre
management systems with its unique abilities:
• RS232
• Modbus RS485
• Modbus TCP/IP
• USB
• SNMP
• Web interface
• Configurable web interface
• Unlimited server’s shutdown
• Unlimited email notifications
• Smart and fault proof diagnostic events history
• Multi language interface
4
Centric Power density
foot Print Power: 49w / cm2 ׀Power density: 0.4w / cm3
120 cm
76 cm
54 cm
120 cm
76 cm
162 cm
5
Centric MTTr
Conventional or Stand Alone uPS MTTr:
• Diagnostics – can take hours to days
• Required Parts – can take days or even weeks to arrive. Immediate spare parts
are very expensive to obtain
• Skills & qualifications – special expensive experts are required
• Testing – it is usually extremely difficult to run 100% required testing in the field
Stand alone
modular
Vertical modularity in basic unit is 25kW/kVA per power module; the vertical stack is
scalable to up to 8 power modules (200kW).
Horizontal modularity of basic unit is up to 200kW, the horizontal scalability is up to 5
units (1000kW).
front view
7
Solutions
Vertical and Horizontal redundancy with decentralized or centralized redundant battery
8
CenTrIC 3x400 vac uPS: system specifications
Topology Modular, double-conversion, VFI, on-line battery
Operation Continuous
Input
Voltage (V) 3x400 (4 wires + Gnd)
-20 / +15
Voltage range (%)
(360 ~ 460 Vac: full power; 320 ~ 360 Vac: derated 20 %)
Current (A) 3 × 42 per module – no inrush current at startup
Frequency (Hz) 47 – 63
Power walk-in (sec) 1 ~ 30 in 1 sec increments
Power factor correction >0.99
THDI (%) <3
Inrush current None
output
Rated Power (kVA/kW) 25/25 ~ 200/200
Nominal frequency (Hz) 50/60
Frequency tracking range (Hz) ±(0.5, 1, 2, 3, 4), selectable
Frequency tracking slew rate (Hz/sec) 1
Frequency (in free-running mode) (Hz) 50/60 ±0.1 %
Nominal voltage (Vac) 3x400 (4 wires + Gnd)
Static voltage regulation (%) ±1
Regulation for 100 % unbalanced load (%) ±1
Dynamic response to 100 % load step (%) ±2
Overload withstand Inverter mode 110 % : 10 min, 125 % : 60 s, 150 % : 30 s
Bypass mode 125 % : 10 min, 1000 % : 1 cycle
Waveform Sinusoidal
THD (%) Linear load: <2; non-linear load: <6
Load CF (max) 6:1
Power factor Any
Ac-Ac efficiency (nominal) (%) Up to 96
Batteries
Dc-link voltage (Vdc) 300 ~ 405 (405 floating, accuracy to ±1 %)
Quantity 60 × 12 Vdc
Type Sealed, lead-acid. Lithium-ion batteries also supported.
General
Maximum power dissipation (Po=25 kW) N*1041 W (N*3552 BTU/h), where N = # modules
Ambient temperature (°C) -10 to +40 (operating), -20 to +60 (storage)
Relative humidity (%) 95 maximum, non-condensing
Altitude (m) 1500 without derating
Enclosure IP20
Cooling system Multi-fan with speed control (forced)
Design & manufacturing standards
Safety IEC 62040-1
EMC IEC 62040-2
Design classification IEC 62040-3
Low magnetic field radiation EMF as per ICNIRP
dimensions
UPS model 50 kW 100 kW 200 kW
# of power modules 1 2 2 3 4 4 5 6 7 8
Power output (kW/kVA) 25 50 50 75 100 100 125 150 175 200
Height (mm) (w/o wheels) 665 932 1200
width (mm) 540
depth (mm) 757
weight (kg) w/o batt. box 72.2 92.0 102.4 122.2 142 149.3 169.1 188.9 208.7 228.5
dimensions (H x w x d, mm) & weight of batt.
985 x 540 x 743, 66 kg
box for 50 kw system
* All specifications are subject to change without advance notice.
9
CenTrIC:
Technical specifications for the system controller
Display LCD flat panel, touch-sensitive
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Output dry contacts Battery test failure
Over/under temperature
Overload
(Each system alarm type can be routed to the dry contact of your
choice.)
Load bar-graph
3-phase voltages
3-phase currents
On-screen parameters Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
April 2015