ISIE 2011, International Symposium on Industrial Electronics, Gdansk, Polonia, 27-30 June 2011.

Power Control of Grid-Connected


Photovoltaic Systems
Roberto Zanasi Stefania Cuoghi
DII-Information Engineering Department DII-Information Engineering Department
University of Modena and Reggio Emilia, University of Modena and Reggio Emilia,
Via Vignolese 905, 41100 Modena, Italy Via Vignolese 905, 41100 Modena, Italy
Email: roberto.zanasi@unimore.it Email: stefania.cuoghi@unimore.it

 
Abstract—In this paper the Power Oriented Graph technique
is used for modeling a grid-connected single-phase 3kW DC/AC    

   
power converter for solar energy conversion system. A DC/DC  

stage, controlled by a maximum power point tracking (MPPT)


technique, is used to boost the time-varying input voltage 
  
 
 

provided by photovoltaic panels. A buck DC/AC stage, including    

a PWM inverter, is implemented to transfer the active power to


the grid. A new control scheme for the DC/AC stage is proposed.   



I. I NTRODUCTION Fig. 1. Grid-connected photovoltaic system: blocks scheme.

Solar energy is currently considered to be one of the most


useful natural energy sources because it is a pollution-free 3kW DC/AC power converter, implementing an active-bridge
source of abundant power. Over the last few years, the interest DC/DC converter and a full-bridge DC/AC. This structure
in photovoltaic (PV) applications has grown exponentially. performs high efficiency and the proposed digital control
Economic evaluations show that PV technology is still too allows to reduce the production costs. The paper is organized
costly compared to other energetic technologies [1]. However as follows. In section II the system structure is presented.
the PV cost reduction is improving rapidly and PV systems In section III and IV the DC/DC and DC/AC converters are
require a very long time with almost no maintenance cost. analyzed and modeled. Simulations of the DC/AC converter
These usually unevaluated aspects should motivate govern- and conclusions end the paper.
ments to deploy more PV systems [2]. Innovative inverter
topologies have been suggested in the literature to provide II. S YSTEM STRUCTURE
many benefits and cost reduction. Despite modest production Let us consider the blocks scheme of the grid-connected PV
volumes, inverters have evolved significantly since the 1980s system proposed in [4] and shown in Fig. 1. The hardware
through manufacturer innovations and technology improve- section includes an active-bridge DC/DC converter which is
ments. In 1980s inverters were bulky, heavy, difficult to install, designed to boost the input voltage from a minimum input of
unreliable, and their efficiency was in the 85 − 90% range. 150 V to a DC value regulated at 450 V. Then a single-phase
The early 1990s saw the first large-scale series production buck 3kW DC/AC converter is employed to step down and
of PV inverters (SMA PV-WR). In 1995 the first PV string to modulate the output voltage according to the grid voltage
inverter was produced (SMA SB 700), allowing connection (230 Vrms ±10% and 49.7 − 50.3 Hz). Finally the filter is
of modules in series, modular systems, higher system effi- designed to reduce high-order harmonics introduced by the
ciency, and reliability. Late 1990s saw basic data-acquisition PWM modulation of the DC/AC converter. The control of
system and plug-and-play installation. Transformerless and the system is obtained by a microprocessor. The phase-shift
high frequency (HF) designs reached efficiencies above 95%. control between the input bridge legs and the output bridge
In the past 5 − 10 years, inverters have evolved significantly. legs of the DC/DC converter is determined by a Maximum
Reliability, ease of installation, user friendliness, efficiency, Power Point Tracking (MPPT) algorithm, in order to extract
size and weight have all improved significantly. In this scenario the maximum possible power from the PV panels in all the
modeling tools would be helpful to manufacturers in order to irradiation conditions. The control of the DC/AC converter is
study and simulate new inverter topologies. designed to supply current into the utility line by regulating
In this article we present an accurate model of a PV inverter the bus voltage Vb to 450V. The control of the power flow to
architecture recently proposed in [4]. The model has been the grid, according to the European standards (EN 61727),
obtained using the Power Oriented Graph (POG) technique [5]. is based on the control of active and reactive power. The
The analyzed and simulated system is based on a single-phase required synchronization between the grid voltage and the
(" %"  !" (  !" #$  %" &'
   

  

  


      # #  
 

    



  



  
 


    

Fig. 3. Complete hardware structure of the PV system connected to the grid.


   
Vp 0
V 0 Vs V V V
Vin -   c1-- K1(s1)- -    KT(s2) b -- s3 - x-   c - -  Vg
2
6 6 6 6
?
? LT -1 ? ?
1 1 1 1 1 1
Rin Cin s ? RT Cb s R1+L1 s Cs R2+L2 s
1
6 s 6 6 6

Iin  ?- -  KT1(s1) ? - - --K2(s2)- -   s3  ? --  ? - Ig


I1 Ip I2 Ix
1 2 3 4 5 6 7 8
Is

Fig. 4. Corresponding POG model of the PV system connected to the grid.

a) elaboration block b) connection block

x1 -  x2 x1 - K - x2 scalar product xT y of the two power vectors x and y involved


in each dashed line of a power-oriented graph, see Fig. 2,
? has the physical meaning of the power flowing through that
particular section. Note, for example, that the dashed lines
G(s) 1 - 8 in Fig. 4 are in direct correspondence with the physical
power sections 1 - 8 of Fig. 3: 1 - 2 is the input filter, 2 -
5 is the DC/DC converter which includes the input bridge,
y ?-y y1  K∗  y2 the high frequency (HF) transformer and the output bridge,
5 - 7 includes the bus capacitor Cb and the DC/AC converter
Fig. 2. POG: a) elaboration block; b) connection block.
and 7 - 8 is LCL filter. It is easy to see that the state space
equations of the POG model of Fig. 4 can be expressed in the
form L ẋ = −A x + B u where:
voltage generated by the converter is done by using a Phase    
Cin 0 0 0 0 0 Vc1
Locked Loop (PLL) algorithm which detects the phase angle  0 LT 0 0 0 0  I ps 
of utility voltage. More details of the system operation are 
 0
    
0 Cb 0 0 0   , x = Vb  , I ps = IP ,
 
given in Sec. III and IV. L = 0 0 0 L 0 0   Ix  Is
The Power-Oriented Graphs, see [5]-[7], is a graphical mod- 
 0
  
0 0 0 C 0   Vc 
eling technique suitable for modeling physical systems. The
0 0 0 0 0 L Ig
POG are normal block diagrams combined with a particular
 1 1
modular structure essentially based on the use of the two
 
Rin
T
K1 0 0 0 0 Rin 0
blocks shown in Fig. 2: the elaboration block stores and/or  −K R
 1 T −K2T 0 0 0 
 0 0 
 
dissipates energy (i.e. springs, masses, dampers, capacities, in-  0 K2 0 s 3 0 0   0 0 
ductances, resistances, etc.); the connection block redistributes A =   , B =  ,
 0 0 −s3 R1 1 0   0 0 


the power within the system without storing or dissipating  0 0 0 −1 0 1   0 0 
energy (i.e. any type of gear reduction, transformers, etc.). 0 0 0 0 −1 R2 0 −1
The main feature of the Power-Oriented Graphs is to keep      
a direct correspondence between the dashed sections of the V L M R 0 K1 (s1 ) = [s1 0]T
u = in , LT = p , RT = p , .
graphs and real power sections of the modeled systems: the Vg M Ls 0 Rs K2 (s2 ) = [0 s2 ]
 
where Vc1 (t) and I1 (t) are respectively the input voltage and
  

' '

current. The dynamic model of the output active bridge is
 

described in Fig. 4 by the connection block 4 - 5 characterized
     
by matrix K2 (s2 ). The control signal s2 (t) can be expressed
  
 
   

as follows (see dashed red line in Fig. 6-b):


&  

  
 


Vs (t) I2 (t) 
!   (
&
s2 (t) = = = M5 (t) I s (t) − M 5 (t) Is (t) ,

 Vb (t) Is (t)
"#

 $  %$&


 
 where Vb (t) and I2 (t) are the output bus voltage and current.
     

 

  In Fig. 4, the dynamic model of the transformer is described
)  

  ) 

  in section 3 - 4 by using the matrices LT e RT : L p , Ls and M
are the self and mutual inductances of the transformer, R p and
Fig. 5. Power Management Control (PMC) scheme Rs are the corresponding transformer resistances. The power
Pav transferred to the output in half switching period can be
expressed as follows:
III. DC/DC CONVERTER SECTION 2 dπ   
Vc1 2 δ
Let us now consider the POG model of the single-phase Pav = 2
1 + d − 2d + 4(d 2 + d + 1)
2ω L(2 + d) π (1)
phase-shifted DC/DC converter shown in Fig. 4 between  2 
δ 2
sections 2 - 5 : it is composed by an input full bridge (FB) − π 2(d + 2d + 2) ,
connected to an active half bridge (HB) through an HF
where ω is the switching frequency, L is the primary-referred
transformer. This structure provides galvanic isolation between Vb
leakage inductance, n is the transformer turn ratio, d = nV
the PV array and the utility line, protecting the system against c1

electric shock and improving its safety. The DC/DC converter and δ is the phase shift between the input and the output
is controlled using the zero-voltage-switching (ZVS) PWM bridges. Relation (1) has been obtained using the a method
technique [8] and operates in a soft-switched manner [9]. The similar to the one described in [4] for the active full bridge.
operating principle of the converter is described in [4] with the 
variant of using an active HB instead of active FB. The time 

behaviors of the main variables of the DC/DC converter are

shown in Fig. 6. Variable Mi (t) denotes the control input of
the i-th MOS: when Mi = 1 the MOS is ON, when Mi = 0 the 

MOS is OFF. The DC/DC converter is controlled by regulating  
the phase-shift δ between signal M5 (t) = M 6 (t) of the active
bridge (dashed red line) and signal M1 (t) = M2 (t) of the input 
bridge (blue line). Note that the signals M3 (t) = M4 (t) are
not represented in Fig. 6 because they are equal to signal 
M 1 except during dead time when all MOS of input bridge

are OFF. The basic structure of the control algorithm of the 

DC/DC converter is shown in Fig. 5: it is based on the


Maximum Power Point Tracking (MPPT) algorithm and it 
implements an optimized version of the perturb and observe
method described in [4] and [10]-[12]. This method regulates
the phase-shift δ and it is based on the sensing of current 

and voltage of PV array and on the estimation of DC output
power: the DC current I2 is chosen to maximize the power

operating point of the PV system.
In Fig. 6, the signals Vp (t), I p (t) (blue lines) and Vs (t),
Is (t) (dashed red lines) represent, respectively, the primary
and secondary voltage and current of the transformer. The
dynamic model of the input bridge is described in Fig. 4 by Fig. 6. Time behaviors of the main variables of the DC/DC converter.
the connection block 2 - 3 characterized by matrix K1 (s1 ).
The control signal s1 (t) in time-domain is obtained as follows, IV. DC/AC CONVERTER SECTION
neglecting the dissipative losses of the MOS (see blue line in
Fig. 6-b): Let us now consider the POG model shown in Fig. 4
between sections 6 and 8 : it is composed by a IGBT full-
Vp (t) I1 (t)  bridge DC/AC converter PWM-controlled and a LCL low pass
s1 (t) = = = 2 M1 (t) ⊕ M 3 (t)sgnI p (t) − 0.5 ,
Vc1 (t) I p (t) filter. The filter is used to reduce the high-frequency harmonics
introduced by the PWM modulation on output voltage. The Bode Diagram

considered control scheme is shown in Fig. 5: the controller 50

is designed to transfer to the grid, according to the European


standard, the DC power provided by the DC/DC converter 0

Magnitude (dB)
section. The DC/AC converter is modeled in Fig. 4 by the −50
connection block situated between sections 6 and 7 . The
DC/AC converter is controlled by single-phase unipolar PWM −100

modulation. The main advantage of this technique is that no −150


spectral bins appear at the odd multiples of the switching 0

frequency, and no multiples of the switching frequency are

Phase (deg)
present. This essentially doubles the switching frequency, thus −90

allowing the specifications of the LCL filter to be relaxed.


−180
The voltages of points A and B in Fig. 3 are separately
regulated comparing the PWM triangular carrier Vt (t) with −270
the modulation voltage Vmod (t) normalized with respect to the 10
−1 0
10
1
10 10
2
10
3 4
10
5
10
Frequency (Hz)
bus voltage Vb (t). The control signal s3 (t) can be expressed
as follows:
    Fig. 7. Bode diagrams of the transfer function Gx (s) for C = 5 µ F, L1 =
sgn Vt (t) + VVmod(t)(t) − sgn Vt (t) − VVmod(t)(t) 1.8 mH, L2 = 0.9 mH, R1 = 0.1 Ω, R2 = 0.05 Ω.
b b
s3 (t) = , (2)
2
thus the modulated voltage Vx (t) = s3 (t)Vb (t) switches be- to the notation used in [19], the sinusoidal signals can be
tween the three levels {+Vb , −Vb , 0}. expressed using a rotating space vector, i.e.
The structure of the LCL filter is shown in Fig. 4, sections u(t) = Ue j(ω t+φ ) . (5)
7 - 8 . The filter has been designed to reduce the high-order
harmonics on the grid side according to the method described In stationary (x, y) reference frame, (5) can be written in the
in [13] and [4]. In the Laplace’s domain, the transfer functions form u(t) = ux (t) + juy (t), where the x and y components
Gx (s) = Ig (s)/Vx (s) and Gg (s) = Ig (s)/Vg (s) have the follow- are ux (t) = U cos(ω t + φ ) and uy (t) = U sin(ω t + φ ). The
ing structure: following Park transformation matrix
 
G1 G2 G3 −G1 G2 G3 + G3 cos θ sin θ
Gx (s)= , Gg (s)= , (3) TD =
1 + G1 G2 + G2 G3 1 + G1 G2 + G2 G3 − sin θ cos θ
where: converts the ux and uy components uxy = [ux (t) uy (t)]T into dq
1 1 1 components udq = [ud uq ]T , which are constants in steady-state
G1 = , G2 = , G3 = . in a rotating reference frame. The inverse Park transformation
L1 s + R1 Cs L2 s + R2
is: ux,y = TTD ud,q . Using the Park transformation matrix TD , the
As shown in the Bode diagram of the frequency response grid voltage Vg (t) and the grid current Ig (t) are converted in
Gx ( jω ) of Fig. 7, the LCL filter introduces a phase shift constant variables in the dq frame: V̄gdq (t) = Vgd (t) + jVgq (t)
and a gain at the grid frequency ωg . The modulation voltage and I¯gdq (t) = Igd (t) + jIgq (t). The angle θ used in the transfor-
Vmod (t) has to be chosen to compensate the filter effects and to mation matrix TD , is obtained using a digital Phase-Locked
synchronize the grid current Ig (t) with the grid voltage Vg (t). Loop (PLL) designed in the rotating dq frame, see [4] and
In the space vector representation the modulation voltage Fig. 9.
can be expressed as the complex number V mod = Vx (s)|s= jωg ,
where Vx (s) can be expressed as follows from (3): 
 
Vx (s) = Vg (s) (1 + R1Cs + L1Cs2 ) + Ig (s) (L1 L2Cs3 + 

+(L1 R2 +L2 R1 )Cs2 +(R1 R2C+L1 +L2 )s+R1 +R2 ).  

(4)  
 
The grid voltage is given by sensing system while the desired 

 
grid current is given by the feedback control loop shown
in Fig. 5. This control scheme is an improved version of Fig. 9. Block diagram representation of PLL algorithm
the control algorithm described in [4]. In particular, using an
indirect control, the grid current Ig (t) is chosen to force the The “Power Park evaluation” block shown in Fig. 5 cal-
bus voltage Vb (t) to be equal to a desired reference value Vbre f culates the active power P and the reactive power Q flowing
in order to balance the power flowing through the system. The towards the grid: P̄(t) = P(t) + jQ(t) = V̄gdq (t) I¯gdq (t). In the
considered control scheme becomes very simple using the Park dq frame, the desired grid current can be expressed as follows:
transformations and Akagi’s pq theory [14]-[19]. Referring I¯gre f (t) = Idre f (t) + j Iqre f (t). The reactive grid current Idre f (t)
Vb Vx Vg
s3

Connection block

V
1 Grid
Cb.s FILTER

I
Current from
DC/DC converter Connection block 2
Ib
Ig
I2 s3
Ib Ix

Re Modulation
Iq_ref Voltage
Vb_ref REGULATOR Im Igd+jIgq
Re(u) Vd
Rq(s)
Error Vx Vmod
Reference Vx_dq (Ig) Vxd+jVxq
bus Voltage REVERSE
Vgd+jVgq
Im(u) Vq
PARK

Vy Vy
theta
Qrif REGULATOR
Rd(s) Id_ref theta
Error Vgd PLL theta
Reference
Reactive Power

Vx
Vgd
Vgd

Re
Im
DIRECT Vy
PARK
90°
Vgq
Vgd theta
Vgd
P P
Vgq
POWER Vgq
Active Power PARK
EVALUATION Igd Igd

Q Ix
Reactive Power Igq
Igq Ix
Id
Igd

DIRECT Iy
[Vb] Iy
PARK
PWM GENERATION s3 Iq 90°
Igq
[Vmod] Control signal theta

Fig. 8. Simulink scheme of DC/AC section implemented for the model validation.

is regulated by a PI compensator in order to have zero reactive Grid voltage Vg


400

power Q. The active grid current Iqre f (t) is dynamically 200


Vg [V ]

controlled by a second PI compensator in order to maintain the 0

bus voltage Vb (t) equal to the desired value Vbre f . Notch filters −200

−400
are inserted in cascate to the PI regulators in order to filter the 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

high frequency ripple due to PWM modulation. Note that the Grid current Ig
50
inner double PI structure used in [4] to generate the modulation
Ig [A]

voltage in the dq frame is here substituted by block “Vxdq (Ig )” 0


shown in Fig. 5 which is defined as follows, see relation (4):
Vxdq (t) = V̄gqd (t)(1 − L1Cωg2 + jR1Cωg )+ −50
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

+I¯gre f (t)[R1 + R2 − (L1 R2 + L2 R1 )Cωg2 + Zoom for t ∈ [0.8, 1]


Vg [V ], Ig [A]

+ j((R1 R2C + L1 + L2 )ωg − L1 L2Cωg3 )], 200

0
where Vgdq (t) is the grid voltage expressed in the dq frame.
−200
The DC/AC control voltage Vmod (t) is finally obtained from
V̄xdq (t) using the inverse Park transformation. 0.8 0.82 0.84 0.86 0.88 0.9 0.92 0.94 0.96 0.98 1
Time[s]
V. VALIDATION OF THE MODEL AND SIMULATION RESULTS Fig. 10. Step responses of grid voltage V g and grid current Ig for I2 = 7 A.
Due to the complexity of the overall system, in this paper
we present only the simulation results of the DC/AC section,
see the Simulink scheme in Fig. 8. The simulation results have in Fig. 10 clearly shows the good synchronization between
been obtained using the following parameters: PWM carrier signals Vg and Ig . The Park transformed signal V̄gdq is exactly
frequency ωc = 17 kHz; grid frequency ωg = 50 Hz; filter equal to the expected value: V̄gdq = − jVg0 . The bus voltage
parameters: C = 5 µ F, L1 = 1.8 mH, L2 = 0.9 mH, R1 = 0.1 Ω, Vb and the control signals Idre f and Iqre f generated in the
R2 = 0.05 Ω; Vbre f = 450 V; the PI controller Rq (s) of variable rotating frame by regulators Rq (s) and Rd (s) are shown in
Iqre f : Rq (s) = 1.8 + 25
s ; the PI controller Rd (s) of variable Fig. 11. The powers P5 , P6 and P8 flowing through different
Idre f : Rd (s) = 0.001 + 0.01
s ; the PI controller RL (s) in the PLL sections of the system in steady-state condition are shown in
algorithm: RL (s) = 1 + 30 s . Fig. 12. In particular the blue line represents the input power
The waveform of the main system signals when a step P5 = Vb I2 flowing through section 5 , while the black and red
input current I2 = 7 A is applied are shown in Fig. 10-12. lines represent the powers flowing through sections 6 and 8
In particular, Fig. 10 shows the dynamical behavior of grid of the POG scheme of Fig. 4. The ripple present on the power
voltage Vg = Vg0 sin(ωgt) and grid current Ig . The zoom signals is mainly due to the current ripple and it depends on
the LCL filter design [4]. The magenta and green lines shown VI. C ONCLUSION
Fig. 12 represent the active power P and the reactive power Q In this paper a recent and innovative inverter for PV system
flowing towards the grid. In particular one can notice that the grid-connected is modeled using the POG technique. The
mean value of Q is equal to zero and the mean value of P is main advantages of the proposed approach are the direct
nearly equal to power P5 . The system currents I2 , Igd , Igq , Idre f correspondence between POG sections and real power sections
and Iqre f obtained with a I2 sawtooth reference are shown in of the modeled system and the easy implementation of the
Fig. 13, see [4]. POG graphs in Matlab-Simulink environment [7]. A simplified
and robust control structure has been proposed. The presented
470
Bus voltage Vb simulation results confirm the validity of the model and
seems to be useful to reduce the Levelized Energy Cost for
460
photovoltaic systems.
Vb [V ]

450
ACKNOWLEDGMENT
440
The authors would like to thank S. Culzoni, C. Tebaldi and
430
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
M. Candeli.

Reference current I¯gre f


R EFERENCES
50
40 [1] EIA, 2011, Levelized cost of new generation resources in the Annual
Idre f , Iqre f [A]

30 Energy Outlook 2011. U.S. Energy Information Administration.


20 [2] K. Zweibel, Should solar photovoltaics be deployed sooner because of
10 long operating life at low, predictable cost? Energy Policy, 38:7519-
0
7530,2010.
−10
[3] Review of PV inverter technology cost and performance projections. Nat.
−20
−30
Renewable Lab. Energy, Golden, CO, NREL Report SR-620-38771, 2006.
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
[4] M. Cacciato, A. Casoli, R. Attanasio and F. Gennaro Soft-switching
Time[s] converter with HF transformer for grid-connected photovoltaic systems,
IEEE Transactions on Industrial Electronics, 57(5):1678-86,2010.
Fig. 11. Bus voltage Vb , reference active grid current Iqre f (red) and reactive
[5] R. Zanasi, “The Power-Oriented Graphs technique: System modeling and
grid current Idre f (blue).
basic properties”, Vehicle Power and Propulsion Conference (VPPC),
2010 IEEE, Lille, France, 1-3 Sept. 2010
[6] R. Zanasi, G. H. Geitner, A. Bouscayrol, W. Lhomme, “Different ener-
7000 getic techniques for modelling traction drives”, ELECTRIMACS 2008,
6000 P5 Qubec, Canada, June 8-11 2008.
P6 [7] R. Zanasi, “Power Oriented Modelling of Dynamical System for Sim-
Power (W )

5000
P8
4000
P ulation”, IMACS Symp. on Modelling and Control, Lille, France, May
3000
Q 1991.
2000
1000
[8] Y. Jang, M. Jovanovic, Y. Chang, A new ZVS-PWM full-bridge converter.
0 IEEE Trans. on Power Electron.: 18(5):1122-1129, Sept. 2003.
−1000 [9] R.W. De Doncker, D.M. Divan, M.H. Kheraluwala, A three-phase soft-
1958 1960 1962 1964 1966 1968 1970 1972
Time(ms) switched high-power-density DC/DC converter for high-power applica-
tions. IEEE Trans. on Industry Applications: 27(1):63-73, Jan/Feb 1991.
Fig. 12. Power flows P5 , P6 and P8 through sections 5, 6 and 8 of the POG [10] N. Femia, G. Petrone, G. Spagnuolo, and M. Vitelli, Optimization of
scheme of Fig. 4. Active and reactive powers P and Q. perturb and observe maximum power point tracking method. IEEE
Trans. Power Electron.: 20(4): 963973, Jul. 2005.
[11] D. Sera, R. Teodorescu, J. Hantschel, and M. Knoll, Optimized maximum
power point tracker for fast-changing environmental conditions. IEEE
Trans. Ind. Electron.: 55(7): 26262637, Jul. 2008.
System currents I2 , Igd , Igq , Idre f and Iqre f [12] T. Esram and P. L. Chapman, Comparison of photovoltaic array maxi-
30
I2 mum power point tracking techniques. IEEE Trans. Energy Convers.:
I gq 22(2):439449, Jun. 2007.
Currents [A]

20
I qre f [13] M. Liserre, R. Teoderuscu, and F. Blaabjerg, Stability of photovoltaic and
10 I gd
Idre f wind turbine grid-connected inverters for a large set of grid impedance
0 values. IEEE Trans. Power Electron.: 21(1), 263272, Jan. 2006.
[14] J.M. Kwon, K.H. Nam and B.H. Kwon. Photovoltaic power conditioning
−10
system with line connection. IEEE Trans.Ind.Electron.: 53(4):1048-1054,
1 1.2 1.4 1.6 1.8 2 Jun. 2006.
[15] R. Teodorescu and F. Blaabjerg, Flexible control of small wind turbines
30
Grid current Ig with grid failure detection operating in stand-alone and grid-connected
20
mode. IEEE Trans. on Power Electron.: 19(5):1323-1332, Sept. 2004.
[16] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Sys-
10
tems. IEEE Pressed 2010.
Ig [A]

0
[17] K. J. strm and B. Wittenmark, Computer-Controlled Systems Theory and
−10 Design. 3rd ed. Englewood Cliffs, NJ: Prentice-Hall, 1984.
−20 [18] H. Akagi, Y. Kanagawae, and A. Nabae, Instantaneous reactive power
−30 compensator comprising switching devices without energy storage com-
1 1.2 1.4 1.6 1.8 2
ponents. IEEE Trans. Ind. Appl.:IA-20(3), 625634, May/Jun. 1984.
Time[s]
[19] L. G. B. Rolim, D. R. da Costa, and M. Aredes, Analysis and software
Fig. 13. Main system currents when I2 is a sawtooth reference. implementation of a robust synchronizing PLL circuit based on the pq
theory. IEEE Trans. Ind. Electron.: 53(6), 19191926, Dec. 2006.