xmcd
kJ W kg kg
CP2 := 4.18 μ2 := 0.7× mPa× s λ2 := 0.63 ρ2 := 1000× m2 := 1500×
kg× °C m× °C m
3 h
W W
T1E := 80°C T1S := 30°C T2E := 20°C h1 := 1410× h2 := 1935×
2 2
m × °C m × °C
Température de sortie de l'eau : ( )
m1× CP1× T1E - T1S = m2× CP2× T2S - T2E ( )
m1× CP1 3000 ´ 1.38
T2S := T2E +
m2× CP2
( )
× T1E - T1S = 53.0 °C 20 + ( 80 - 30) ×
1500 ´ 4.18
= 53.014
Δθ
( )
20°C 20°C
Φ = m1× CP1× T1E - T1S = U× S× Δθ =
1
U× S
Débit de chaleur transféré
( )
Φ := m1× CP1× T1E - T1S = 57.5 kW
3000
3600
× 1380× ( 80 - 30) = 57500
MH 1/2 15/05/2012
TF06_convection_07.xmcd
Cmin
Ainsi que le rapport des débits de capacité CR := CR = 0.66
thermique Cmax
Φ
Calcul de l'efficacité ε := ε = 83.3× %
Φmax
Calcul du NUT.
Attention les relations entre ε et NUT dépendent de la disposition
contre-courant
1 æ 1 - ε× CR ö
NUT := × ln ç ÷ = 2.922
1 - CR è 1 - ε ø
U× S
NUT =
Cmin
NUT× Cmin
Lta := = 50.3 m
U × π× D 2