ER-4846

Reissued December 1, 2001


ICBO Evaluation Service, Inc. • 5360 Workman Mill Road, Whittier, California 90601 • www.icboes.org

Filing Category: FASTENERS—Concrete and Masonry Anchors

COVERT INJECTION ADHESIVE ANCHORS AND through 14. The allowable tension load values noted in
UNDERCUT ANCHORS Tables 5 through 14 must be adjusted for in-service
temperatures in accordance with Figure 1 when anchors are
COVERT OPERATIONS, INC. installed in locations where the concrete temperatures may
1940 FREEMAN AVENUE exceed 105°F (41°C). Adjustment of loads for reduced edge
LONG BEACH, CALIFORNIA 90804 and end distances are noted in Table 4. Allowable loads for
anchors subjected to combined shear and tension forces
1.0 SUBJECT are determined by the following equation:
Covert Injection Adhesive Anchors and Undercut Anchors. n n
Pa Va
2.0 DESCRIPTION % # 1.0
Pt Vt
2.1 Covert Injection Adhesive:
2.1.1 General: The Covert Injection Adhesive (CIA) is a where:
two-component structural epoxy adhesive for anchoring Pa = Applied service tensile load.
stud-type, threaded steel anchor bolts or deformed steel
Pt = Allowable service tensile load.
reinforcing bars into concrete and unreinforced brick. The
adhesive formulation is designated as CIA-Gel 7000. The Va = Applied service shear load.
CIA-Gel adhesive anchors consist of CIA-Gel 7000 epoxy Vt = Allowable service shear load.
and a threaded steel rod, with a nut and washer, or n
deformed steel reinforcing bars. The installation in normal- = 1 for unreinforced brick masonry
weight and concrete, structural lightweight concrete; = 5
/3 for concrete and concrete masonry
unreinforced masonry; reinforced masonry walls; and
2.1.4 Installation In Concrete:
concrete foundation walls is as described in Sections 2.1.4
through 2.1.8. 2.1.4.1 General: A hole is drilled to the specified depth
with a hand-held electro-pneumatic rotary hammer drill
2.1.2 Materials:
using carbide-tipped drill bits conforming to ANSI
2.1.2.1 Adhesive: The CIA-Gel 7000 epoxy two- Specification B212.15-1994. The holes are cleaned of dust
component adhesive is packaged in equal-volume, side-by- and debris with a nylon brush and a jet of compressed air.
side plastic cartridges. The cartridges are sealed The hole diameter, anchor embedment, spacing and edge
individually with D-shaped plugs and/or a screw-on cap, distances must comply with Tables 5 to 10, 13 and 14. A
which may be reused after partial use of contents. The mixing nozzle is attached to the adhesive cartridge and the
epoxy is mixed when dispensed through a spiral motionless assembly is placed into the hand or pneumatic injection
mixer attached to the cartridge. The epoxy may be tool. Before placement into the hole, a small amount of
dispensed with either a manual or a pneumatically activated epoxy is pumped out of the nozzle until a uniform gray
tool. The CIA-Gel 7000 epoxy adhesive components have material is achieved. Holes are approximately half filled with
a shelf life of one year when stored in a dry environment at the mixed epoxy. The threaded rods or deformed
a temperature of 70°F (21°C). The recommended hardening reinforcement bars are inserted with a rotating motion until
times are noted in Table 3. the anchor contacts the bottom of the hole. The adhesive
2.1.2.2 Threaded Rods: All threaded rods are must be level with the concrete surface after insertion of the
manufactured from steel complying with ASTM A 307, rod or bar. Oil, scale, and rust must be removed from the
Grade C [Fu = 60,000 psi (400 MPa) minimum] ASTM A threaded rod or reinforcing bar prior to installation. During
193, Grade B7; [Fu = 125,000 psi (860 MPa) minimum]; or anchor installation, the hole and surrounding location may
ASTM F 593 Grade F 593A [Fu = 115,000 psi (795 MPa) be wet, and any standing water need not be removed from
minimum] SS304. Specifications and installation of threaded the hole. Anchors shall not be loaded until cure time has
rods are noted in Table 1. passed.

2.1.2.3 Reinforcing Bars: Deformed reinforcement bars 2.1.4.2 Special Considerations: The anchors may be
are manufactured from steel complying with ASTM A 615, used within fire-resistive construction, provided the anchors
Grade 60. Specifications and installation of reinforcing bar only resist wind and/or seismic forces. In this application,
are noted in Table 2. the anchors cannot resist gravity loads, unless special
consideration is given to fire conditions.
2.1.3 Design: Allowable tension and shear values for
threaded rod or reinforcing bar are described in Tables 5

are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as
an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICBO Evaluation Service, Inc., express or implied,
as to any finding or other matter in this report, or as to any product covered by the report.

Copyright © 2001 Page 1 of 16


Page 2 of 16 ER-4846

2.1.5 Installation in Unreinforced Brick Masonry Walls: For the through-bolted anchor, a 1-inch-diameter (25.4
mm), 8-inch-deep (203 mm) hole is drilled and cleaned as
2.1.5.1 General: Anchors installed in unreinforced
noted above. A 7/8-inch-outside-diameter (22 mm) steel
masonry using the CIA-Gel 7000 adhesive are designed to
sleeve is then pushed into an adhesive-filled screen in a
resist seismic loads. The existing unreinforced brick walls
manner similar to the rod. After curing, a hole is drilled
must have a minimum thickness of 13 inches [330 mm (3
through the sleeve and through the remainder of the
wythes of brick)].
masonry wall. Drilling is continued until the entire wall is
Three types of anchor assemblies are used for seismic penetrated. The 5/8-inch-diameter (15.9 mm) rod is then
retrofitting. The anchor assembly resisting tension and inserted and fitted with a plate and nut to complete the
shear loads where the outside of the wall is not accessible through-bolted anchor connection. See Figure 3.
is the “combination” anchor. The anchor is installed in the
2.1.5.3 Conditions of Acceptance: Conditions of
wall at an angle of 221/2 degrees to the horizontal. It
acceptance for threaded rods and reinforcing bars in
consists of a 3/4-inch-diameter (19.1 mm) ASTM A 307
unreinforced brick masonry are as follows:
prebent threaded rod used with a 15/16-inch-outer-diameter
(23.8 mm) screen tube, 13 inches (330 mm) long and made 2.1.5.3.1 Threaded Rods and Through-bolts in Tension
of steel wire cloth. The threaded rod must be embedded a and Shear:
minimum of 13 inches (330 mm) at the 221/2-degree angle. 1. Installation of threaded rods and through-bolts must
Figure 2 shows details of an installed “combination” anchor. comply with Section 2.1.5.
The anchor assembly for tension and shear applications 2. Maximum allowable tension load for the 3/4-inch-
where the outside of the wall is accessible is the “through- diameter (19.1 mm) bent threaded rod or the 5/8-inch-
bolt” anchor. It consists of 5/8-inch-diameter (15.9 mm) diameter (15.9 mm) through-bolt is 1,200 pounds (5340
ASTM A 307 threaded rod, 13/16-inch (20.6 mm) O.D. by N) with no increase for lateral loading.
11
/16-inch (17.5 mm) I.D. AISI 1010 steel sleeve 8 inches
(203 mm) in length, a 15/16-inch-diameter-by-8-inch-long 3. The maximum allowable shear load for the 3/4-inch-
(23.8 mm by 203 mm) wire mesh screen tube, and an diameter (19.1 mm) bent threaded rod is 1,000 pounds
ASTM A 36 steel plate measuring 6 inches by 6 inches by (4450 N) and for the 5/8-inch (15.9 mm) through-bolt is
3
/8 inch (152 mm by 152 mm by 9.5 mm). The plate is bolted 750 pounds (3338 N), with no increase for lateral
to the opposite side of the wall. The steel sleeve has a loading permitted.
plastic plug at one end to prevent leakage of adhesive 4. For the 3/4-inch-diameter (19.1 mm) bent threaded rod
during installation. Figure 3 shows details of an installed or the 5/8-inch-diameter (15.9 mm) through-bolt
“through-bolt” anchor. subjected to tension and shear, the allowable combined
The anchor assembly resisting shear load where the load is determined using the equation in Section 2.1.3.
outside wall is inaccessible is the “shear” anchor. It consists 5. Minimum wall thickness is 13 inches [330 mm (three
of a 3/4-, 5/8- or 1/2-inch-diameter (19.1, 15.9, or 12.7 mm) wythes of brick)].
ASTM A 307 threaded rod or a No. 6, No. 5 or No. 4
reinforcing bar and a 15/16-inch-diameter-by-8-inch-long (23.8 6. The allowable tension and shear is applicable only to
mm by 203 mm) wire mesh screen tube. Figure 4 shows anchors installed in walls where in-place shear tests
details of an installed “shear” anchor. indicate a minimum mortar strength of 50 psi net.

2.1.5.2 Installation: One-inch-diameter (25.4 mm) holes 2.1.5.3.2 Threaded Rods or Reinforcing Bars in Shear:
are drilled using standard carbide-tipped masonry drill bits 1. Installation of threaded rods and reinforcing bars
which meet ANSI Specifications B212.15-1994. A rotary intended to resist shear only must comply with Section
drill, or rotary hammer drill set on “rotation only” is used to 2.1.5.
drill the holes. 2. The allowable shear load for the 3/4-inch-diameter (19.1
Holes for the “combination” anchors (Figure 2) are drilled mm) rod is 1,000 pounds (4450 N) and for the No. 6,
13 inches (330 mm) deep at a 221/2-degree angle. Holes for No. 5 and No. 4 reinforcing bars the allowable shear
the “through-bolt” anchors (Figure 3), and the “shear” loads are 1,000, 750 and 500 pounds (4450, 3338 and
anchors (Figure 4) are drilled perpendicular to the wall. For 2225 N), respectively. No increase for lateral loading is
the “through-bolt” application the holes are drilled permitted with the above-noted loads.
completely through the wall. For shear anchors, the holes 3. Minimum wall thickness is 13 inches [339 mm (three
are drilled 8 inches (203 mm) deep. The holes are cleaned wythes of brick)].
using a nylon brush, and a jet of compressed air. An
extension nozzle must be used to reach the back of the hole 4. Allowable shear value is applicable only to anchors
with compressed air. installed in walls where in-place shear tests indicate a
minimum mortar strength of 50 psi (344.5 kPa) net.
Screen tubes are completely filled with CIA-Gel 7000
epoxy and then placed into the drilled holes. A 3/4-inch- 2.1.5.3.3 Field Inspection:
diameter (19.1 mm) threaded rod for the “combination” 1. Five percent of resisting tension anchors, threaded rods,
anchors and “shear” anchors, and 7/8-inch-diameter (22 mm) and through-bolts must be tested in accordance with the
steel sleeves for the “through-bolt” anchors are then slowly procedure described in ASTM E 488-90, with a
pushed into the screen tube, rotating continuously. The minimum of two tests required. Where the wall thickness
anchors or steel sleeves must be allowed to cure for the varies, at least one test must be performed on an
times listed in Table 3 before anchors are loaded. Bolt-up anchor which has the minimum embedment. Tests must
time refers to that period of cure after which hardware may show that bolts can maintain a tensile load of 3,000
be placed and nuts tightened. Care must be taken not to pounds (13.35 kN) for 5 minutes. The test report must
overtighten nuts nor induce tension in bolts. Design loads include:
may not be applied until minimum cure time has transpired.
Page 3 of 16 ER-4846

a. Test location(s) 2.2 Covert Operations Ductile Undercut (DUC)


b. Brick/mortar condition Anchors:

c. Bolt movement/elongation 2.2.1 General: The DUC anchor is designed to be a


ductile anchor which transfers loads from the anchor stud
d. Embedment depth and sleeve to the concrete through bearing. The DUC
e. Applied load anchors consist of three main components: An expander
coupling, an expansion sleeve and a threaded rod. The
2. Twenty-five percent of installed anchors resisting
anchors are available in 3/8-inch-, 1/2-inch- and 5/8-inch-
tension and shear must be tested by a special inspector
diameters (9.5 mm, 12.7 mm and 15.9 mm). The threaded
using a torque-calibrated wrench. The torque for the 1/2-
rod used with the 60 series anchors complies with ASTM A
inch-diameter (12.7 mm) anchors, the 5/8-inch-diameter
36 specification. The threaded rod used with the 125 series
(15.9 mm) anchors and the 3/4-inch-diameter (19.1 mm)
anchors complies with ASTM A 193, Grade B7
anchors is 40 foot-pounds, 50 foot-pounds and 60 foot-
specification. The 60 series rods have a zinc chromate
pounds (54.2 N-m, 67.8 N-m and 81.3 N-m),
finish and the 125 series rods have a yellow chromate
respectively. No visible deflection or deformation is
finish. The expanded anchor sleeve creates a mechanical
permitted during the above-noted torque tests.
interlock with the surrounding concrete. The pertinent
3. Twenty-five percent of installed threaded rods and installation data is shown in Table 15.
reinforcing bar anchors resisting shear must be tested
2.2.2 Design:
by a special inspector using a torque-calibrated wrench.
The torque for the 3/4-inch-diameter (19.1 mm) rod and 2.2.2.1 Uniform Building Code: Allowable service loads
the No. 6 reinforcing bar is 60 foot-pounds (81.3 N-m). in tension and shear under the UBC are in Tables 16 and
For the No. 5 and No. 4 reinforcing bars, the torque is 17, respectively. Strength design tension and shear values
50 foot-pounds and 40 foot-pounds (67.8 N-m and 54.2 under the UBC are in Tables 18 and 19, respectively.
N-m), respectively. Loads for DUC undercut anchors subjected to combined
2.1.5.4 Miscellaneous: The Covert Injection Adhesive shear and tension loads are determined by the following
Anchors are intended for resisting short-term lateral loads equation:
only, such as wind or seismic loads. The anchors must be (Ps /Pt ) % (Vs /Vt ) # 1
approved by the responsible design engineer and installed
under special inspection in accordance with Section 2.3 of where:
this report. Ps = Applied tension load.
The anchors’ edge distances and vertical and horizontal Pt = Design tension load.
spacings for the three types of anchor assemblies described
Vs = Applied shear load.
in Section 2.1.5.1 shall comply with Table 12.
Vt = Design tension load.
2.1.6 Installation in Concrete Foundation Walls: CIA-
Gel 7000 adhesive is used in concrete foundation walls 2.2.2.2 International Building Code: Strength design of
utilizing 5/8-inch- and 7/8-inch-diameter (15.9 mm and 22 DUC anchors for tension and shear loads under the IBC
mm) anchors. The anchors are threaded rods complying shall comply with Section 1913 of the IBC. The following
with ASTM A 193, Grade B7, A307 or SS304. They must be conditions shall apply:
installed in minimum 2,500 psi (17.3 MPa) normal-weight 1. Installation is only in regions where analysis indicates no
concrete. The installation is as described in Section 2.1.4. cracking at service loads are permitted.
The allowable tension loads, embedment depths, end and
edge distances are shown in Table 9. 2. Only installation in normal-weight concrete is permitted.
2.1.7 Installation in Unreinforced, Grouted, Concrete 3. Design values in Table 15 are used.
Masonry Walls: CIA-Gel 7000 adhesive is installed in 4. The term “l” is the lesser of 8do or hef.
unreinforced, grouted concrete masonry walls, utilizing 3/8-
5. Only Condition B defined in Sections 1913.4.4 and
inch-, 1/2-inch-, 5/8-inch- and 3/4 -inch-diameter (9.5 mm, 12.7
1913.4.5 of the IBC is used for design regardless of
mm, 15.9 mm and 19.1 mm) anchors designed to resist
whether supplementary reinforcement is provided.
tension and shear loads. The anchors are threaded rods as
described in Section 2.1.2.2. The anchors must be installed 6. Special inspection in accordance with Section 2.3 is
in minimum 2,300 psi (15.9 MPa) grouted concrete provided.
masonry. The existing unreinforced concrete masonry walls 2.2.3 Installation of DUC Anchors: A hole is drilled with
must have a minimum thickness of 8 inches (203 mm). The a carbide-tipped drill bit with the same nominal diameter as
installation is as described in Section 2.1.4. Allowable loads, the required hole diameter (see Table 15). The drill bit must
embedment depths, and end and edge distances are noted conform to the tip diameter tolerances of ANSI Specification
in Table 10. B212.15-1994. The hole is drilled to the minimum depth
2.1.8 Installation in Reinforced Brick Masonry Walls: required in Table 15. Dust and debris are cleaned from the
CIA-Gel 7000 adhesive is installed in brick masonry walls, hole using a nylon brush and a blowout bulb or compressed
utilizing 1/2-inch- and 3/4-inch-diameter (12.7 mm and 19.1 air. The undercutting drill bit is attached to a small rotary
mm) anchors. The anchors are threaded rods complying hammer drill. The drill is set into the rotary hammer mode
with ASTM A 193, Grade B7. The existing reinforced brick and inserted into the hole. The drill is turned on and the drill
wall must have a minimum thickness of 9 inches (229 mm). bit is pushed slowly into the hole. The undercutting process
The anchors must be installed in masonry units having a begins once the drill bit bottoms out in the hole and is
minimum 1,300 psi (8.9 MPa) strength. Installation is as completed when the spring-loaded collar is fully
described in Section 2.1.4. Allowable loads are noted in compressed (gap closed). Dust and debris are cleaned out
Table 11. from the hole using a blowout bulb or compressed air. A
Page 4 of 16 ER-4846

washer and nut are placed on the anchor. The anchor is 4.0 FINDINGS
driven through the material to be anchored and into the
That Covert Operations anchors described in this
work surface until the nut and washer are snug with the
report comply with the 1997 Uniform Building Code™
material to be attached or until the anchor bottoms out in
(UBC), the 2000 International Building Code® (IBC), and
the hole. The nut is turned until finger tight, then turned
the 2000 International Residential Code® (IRC), subject
several full turns using a wrench until the expansion sleeve
is set. Should the threaded rod spin inside the sleeve, a to the following conditions:
screw driver or similar tool is placed in the slot to prevent 4.1 The anchors are installed in accordance with this
the threaded rod from spinning. A torque wrench is used to report and the manufacturer’s installation
apply the appropriate amount of installation torque listed in instructions. The anchor size, minimum
Table 15. embedment depths, spacing and edge distances
2.3 Special Inspection: shall conform to pertinent tables in this report.
Adhesive anchor installations require continuous special 4.2 Allowable design or strength design shear and
inspection in accordance with Section 1701 of the 1997 tension loads in concrete are set forth in this
Uniform Building Code™ (UBC) and Section 1704 of the report. Allowable loads for CIA-Gel 7000 Adhesive
2000 International Building Code® (IBC). The special anchors in concrete must be adjusted for
inspector must record product description (including product temperature in accordance with Figure 1.
name), adhesive expiration date, concrete type and 4.3 Allowable loads in concrete subjected to
strength, anchor diameter and steel grade, compliance of combined tension and shear forces are
drill bit with this report, hole diameter and location, determined by the equation in Section 2.1.3 of this
cleanliness of hole and anchor, adhesive application, report.
anchor embedment, and verification that anchor installation
is in accordance with the manufacturer’s published 4.4 The CIA-Gel 7000 Adhesive anchors in concrete
installation instructions and this report. The manufacturer’s may be used to resist long term loads such as
instructions are included in each package. dead or live loads. They may also be used to resist
wind and earthquake forces for compliance under
For the DUC Undercut anchors, when special inspection is
the UBC and IBC for anchors installed in
required, compliance with Section 1701 of the UBC and
accordance with Section 2.1.4 of this report. The
Section 1704 of the IBC is necessary. The special
inspector must be on the jobsite continuously during anchor tabulated allowable load values shown in Tables
installation to verify anchor type, anchor dimensions, 5, 6, and 7 may be increased in accordance with
concrete type, concrete compressive strength, hole Section 1612.3.2 of the UBC and Section 1605.3.2
dimensions, hole cleanliness, anchor spacings, edge of the IBC for wind or earthquake forces. The
distances, slab thickness, anchor embedment and allowable loads in Table 8 may not be increased
tightening torque. for wind or earthquake forces.
2.4 Identification: 4.5 The CIA-Gel 7000 Adhesive anchors installed in
unreinforced masonry walls in accordance with
The CIA-Gel 7000 are identified by a label on the cartridge Section 2.1.5 of this report may only be used to
displaying the name and address of the manufacturer resist short term lateral loads only, such as wind
(Covert Operations), the words “CIA-Gel 7000,” general
or seismic loads.
installation instructions, expiration date, weight and
evaluation report number (ER-4846). Steel sleeves and 4.6 The DUC Undercut anchors may be used to resist
screen tubes are identified by a label on boxes displaying wind and earthquake forces for compliance under
name and address of the manufacturer (Covert Operations) the UBC and the IBC, when installed in
and size and quantity of the contents. Threaded rods and accordance with this report. The load values may
bars are identified by material certification. The DUC be adjusted in accordance with Sections 1909.2
anchors are identified by a label on the boxes displaying the and 1923.2 of the UBC for strength design and
name and address of the manufacturer (Covert Operations) 1612.3 of the UBC for service design. The load
size and quantity of the contents, evaluation report number values may be adjusted in accordance with
(ER-4846) and name of the quality control agency (CEL Section 1605.2 of the IBC for strength design and
Consulting). Section 1605.3.2 of the IBC for service design.
3.0 EVIDENCE SUBMITTED 4.7 Calculations and details showing that the design
3.1 CIA-GEL 7000 Anchors: Data in accordance with the loads for the anchors comply with this report
ICBO ES Acceptance Criteria for Adhesive Anchors in must be submitted to the building official for
Concrete or Masonry Elements (AC01), dated November approval.
2001, including seismic tests, freezing and thawing tests, 4.8 Fatigue and Shock Loading: Since ICBO ES
creep tests and damp (not water-filled) hole tests. acceptance criteria for evaluating data to
3.2 CIA-GEL 7000 Anchors in Unreinforced Masonry: determine the performance of adhesive and
Data in accordance with the ICBO ES Acceptance Criteria undercut anchors subjected to fatigue or shock
for Unreinforced Masonry Anchors (AC60), dated January loading is unavailable at this time, the use of
1995. these anchors under these conditions is beyond
3.3 DUC Undercut Anchors: Reports of static and the scope of this report.
seismic tests in both shear and tension, and a quality 4.9 Anchors are not permitted for use in conjunction
control manual. with fire-resistive construction. Exceptions would
Page 5 of 16 ER-4846

be: anchors resist wind or seismic loading only; and/or reinforcing bars is limited to interior
for other than wind or seismic loading, special exposure. Installations exposed to severe,
consideration is given to fire exposure conditions. moderate or negligible exterior weathering
4.10 Cracked Concrete or Masonry: Since an ICBO ES conditions, as defined in Figure 21-1-1 of UBC
acceptance criteria for evaluating the performance Standard 21-1 or Figure 1 of ASTM C 62-97a (IBC
of anchors in cracked concrete or masonry is or IRC), are permitted where SS304 stainless steel
unavailable at this time, the use of anchors is anchors are used. The use of the DUC Undercut
limited to installation in uncracked concrete or anchors is limited to interior use.
masonry. Cracking occurs when ft > fr due to 4.13 Special inspection in accordance with Section 2.3
service loads or deformations. is provided for all adhesive anchor installations.
4.11 Adhesive anchors may be used to resist tension Special inspection is required for DUC anchors
and shear forces in overhead or wall installations only under the conditions described in Section 2.3
only if consideration is given to the effects of of this report.
elevated temperature conditions on anchor 4.14 The CIA-Gel 7000 Adhesive anchors and the DUC
performance. Figure 1 describes load reductions Undercut anchors are manufactured in Long
for elevated temperatures. Beach, California, under a quality control program
4.12 The use of the CIA-Gel 7000 Adhesive anchors in administered by CEL Consulting (AA-639).
conjunction with carbon steel threaded rods This report is subject to re-examination in two years.
Page 6 of 16 ER-4846

TABLE 1—SPECIFICATION AND INSTALLATION DETAILS FOR


THREADED ROD INSTALLED WITH COVERT INJECTION ADHESIVE CIA-GEL 7000

3 1 5 3 7
d Rod diameter (in.) /8 /2 /8 /4 /8 1 11/4

As Tensile stress area (in.2) 0.0775 0.142 0.226 0.334 0.462 0.606 0.969

Ab Nominal area of rod (in.2) 0.1042 0.1867 0.2935 0.4246 0.6013 0.7854 1.227
1 5 3 7 1
do Nominal bit diameter hole size (in.) /2 /8 /4 /8 1 1 /4 11/2

Tmax Maximum tightening torque (ft.-lbf.) 15 30 70 150 200 310 375


For SI: 1 inch = 25.4 mm, 1 in.2 = 645 mm2, 1 ft-lbf = 1356 N-mm.

TABLE 2—SPECIFICATION AND INSTALLATION DETAILS FOR


REINFORCING BAR (REBAR) INSTALLED WITH COVERT INJECTION ADHESIVE CIA-GEL 7000

dr Rebar size #3 #4 #5 #6 #7 #8 #9 #10

Abr Nominal area of rebar (in.2) 0.11 0.20 0.31 0.44 0.60 0.79 1.0 1.27
1 5 3 1 1 3
do Nominal bit diameter hole size (in.) /2 /8 /4 1 1 /8 1 /4 1 /8 11/2
For SI: 1 inch = 25.4 mm.

TABLE 3—MANUFACTURER’S RECOMMENDED HARDENING TIMES FOR


COVERT INJECTION ADHESIVE CIA-7000

TEMPERATURE (EF.)1 BOLT-UP TIME (hours)2 CURE TIME (hours)3

65 – 70 6 48
71 – 80 4 36
> 80 4 24
For SI: 1EC = 0.555(tEF - 32)
1
Installation in substrates colder than 65EF is beyond the scope of this report since data has not been submitted for this application.
2
Section 2.1.5.2, third paragraph, explains bolt-up time.
3
Minimum cure time is the time required for the adhesive to achieve full strength.

TABLE 4—REDUCTION FACTORS FOR REDUCED SPACING AND EDGE DISTANCES


FOR COVERT INJECTION ADHESIVE CIA-GEL 7000 ANCHORS INSTALLED IN CONCRETE1,2

TENSION CAPACITY SHEAR CAPACITY

Factor (Fv)
Spacing (s) and Spacing (s) and
Factor (Ft) Direction of Load
Edge Distance (c) Edge Distance (c)
Thread Rod Reinforced Steel

toward edge 0.73 0.65


smin = 0.25 s 0.65 cmin = 0.50 c
not toward edge 0.73 0.65

toward edge 0.25 0.20


cmin = 0.25 c
not toward edge 0.4 0.40
cmin = 0.50 c 0.85
toward edge 0.6 0.6
smin = 0.25 s
not toward edge 1.0 1.0

1
Linear interpolation is allowed for edge distances which fall between 0.25 c and 0.5 c or 0.5 c and 1.0 c, and anchor spacing which falls between
0.25 s and 1.0 s.
2
Load reduction factors must be combined where applicable. In the case where three or more anchors are used, spacing reduction factors must
be multiplied together. Where two or more edge distances affect performance, edge reduction factors must be multiplied together. When a group
is affected by both reduced spacing and reduced edge distances, the edge and spacing reduction factors must be multiplied together.
Page 7 of 16 ER-4846

TABLE 5—ALLOWABLE TENSILE LOADS FOR THREADED ROD INSTALLED IN


NORMAL-WEIGHT CONCRETE USING COVERT INJECTION ADHESIVE (pounds)1,2,3,4,5,6,7,8

BASED ON BOND
BASED ON STEEL STRENGTH
MINIMUM EDGE STRENGTH
SPACING,
STUD EMBEDMENT DISTANCE,
s
DIAMETER DEPTH c A 193
(inches) fc = 2,000 fc = 4,000 A 307 F 593
hef (inches) (inches) Gr. B7
psi psi (SAE 1018) SS 304
(SAE 4140)

3 33/8 5 21/2 2150 2590


/8 2185 4580 2732
17/8 27/8 11/2 1190 1190

51/2 81/4 13/4 2590 2590


1
/2 21/2 33/4 17/8 1940 1940 3885 8210 4860
41/2 63/4 33/8 3495 3780

7 101/2 13/4 3370 3370


5
/8 31/8 43/4 23/8 2600 2600 6070 12910 7590
55/8 81/2 41/4 5400 5525

77/8 117/8 13/4 4540 4540


3 33/4 55/8 27/8 3915 3915
/4 8740 18680 10925
63/4 10 5 6685 7840
71/2 111/4 55/8 — 9505
7
/8 77/8 117/4 6 8492 9725 11900 25510 14875
1 3
9 13 /2 6 /4 12330 12700
1 15540 33390 19428
11 131/2 81/4 — 16740
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
Allowable load must be the lesser of bond or steel strength.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate dimensions.
3
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of installation.
4
CIA-7000 anchors experience a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1 must
be applied to the values in Table 5 when the anchors are installed in locations where the concrete temperatures may exceed 105EF.
5
The anchors cannot be used to resist pullout forces in overhead and wall installations, unless proper consideration is given to fire conditions.
6
Allowable load based on bond strength may be interpolated for compressive strengths between fNc = 2,000 psi and fNc = 4,000 psi.
7
Allowable loads may be increased in accordance with Section 1612.3.3 of the UBC or Section 1605.3.2 of the IBC by 331/3% for short term loading
due to earthquakes or wind.
8
Bond strength values are based on a safety factor of 4.0.
Page 8 of 16 ER-4846

TABLE 6—ALLOWABLE SHEAR LOADS FOR THREADED ROD INSTALLED IN NORMAL-WEIGHT


CONCRETE USING COVERT INJECTION ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6

STUD MINIMUM SPACING, s EDGE BASED ON STEEL STRENGTH BOND


DIAMETER, EMBEDMENT, (inches) DISTANCE, c STRENGTH
d (inch) hef (inches) (inches)
A 307 A 193 Gr. B7 F 593 fNc = 2,000 psi
(SAE 1018) (SAE 4140) SS 304
3
/8 33/8 5 5 1125 2350 1400 1470
1 1 3 3
/2 4 /2 6 /4 6 /4 2000 4170 2500 3555
5
/8 51/2 61/2 61/2 3125 6520 3900 4765
5
/8 53/4 81/2 13/4 3125 6520 3900 27003
3
/4 63/4 10 10 4500 9390 5610 6905
7
/8 77/8 117/8 117/8 6130 12775 7650 8687

1 83/4 131/2 131/2 8000 16700 10000 11180


For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate dimensions.
2
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of installation.
3
Load based on bond strength. Value is for anchors loaded parallel to the edge.
4
Bond strength values are based on a safety factor of 4.0.
5
Allowable loads may be increased by 331/3 percent in accordance with Section 1612.3.3 of the UBC or Section 1605.3.2 of the IBC for short-term
loading due to earthquakes or wind.
6
CIA anchors experience a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1 must be
applied to the values in Table 12 when the anchors are installed in locations where the concrete temperatures may exceed 105EF.

TABLE 7—ALLOWABLE TENSILE LOADS FOR ASTM A 615 GRADE 60 REINFORCING BAR
(REBAR) INSTALLED IN NORMAL-WEIGHT CONCRETE USING COVERT INJECTION
ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6

BAR SIZE DRILL BIT MINIMUM SPACING, s EDGE BASED ON BASED ON BASED ON
DIAMETER, EMBEDMENT, (inches) DISTANCE, c BOND BOND STEEL
do hef (inches) STRENGTH STRENGTH STRENGTH
(inches) (inches)
fNc = 2,000 psi fNc = 4,000 ASTM A 615
psi Grade 60
1
#3 /2 4 6 3 1925 1925 2650
5
#4 /8 41/2 63/4 33/8 3700 3700 4710
3
#5 /4 55/8 81/2 41/4 4870 4870 7365

#6 1 63/4 101/8 5 7270 7270 10605


#6 1 71/2 111/4 55/8 — 9705 10605

#7 11/8 77/8 12 6 8720 8720 14430

#8 11/4 9 131/2 63/4 12265 12265 18850


#8 11/4 10 15 71/2 — 14610 18850

#10 11/2 11 161/2 81/4 14085 14085 30480


For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
The tabulated values are for rebar installed in concrete having the designated compressive strength or higher at the time of installation.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate dimensions.
3
The anchors cannot be used to resist pullout forces in overhead and wall installations unless proper consideration is given to fire conditions.
4
CIA -7000anchors experience a reduction in capacity with increased ambient temperatures. The load factors noted in Figure 1 must be applied
to the values noted in the above table when the anchors are installed in locations where the concrete temperature may exceed 105EF.
5
Allowable loads may be increased 331/3 percent in accordance with Section 1612.3.3 of the UBC or Section 1605.3.2 of the IBC for short-term
loading due to wind or seismic forces.
6
Bond strength values are based on a safety factor of 4.0.
7
Allowable load must be the lesser of bond or steel strength.
Page 9 of 16 ER-4846

TABLE 8—ALLOWABLE SHEAR LOADS FOR ASTM A 615 GRADE 60 REINFORCING BAR
(REBAR) INSTALLED IN NORMAL-WEIGHT CONCRETE USING COVERT INJECTION ADHESIVE
CIA-GEL 7000 (pounds)1,2,3,4,5,6

BAR SIZE DRILL BIT MINIMUM SPACING, s EDGE BASED ON BASED ON


DIAMETER, EMBEDMENT, (inches) DISTANCE, c CONCRETE STEEL
do hef (inches) fNc = 2,000 psi STRENGTH
(inches) (inches)
ASTM A 615
Grade 60
1
#3 /2 4 6 6 2090 1700
5 1 3 3
#4 /8 4 /2 6 /4 6 /4 3795 3030
3
#5 /4 55/8 81/2 81/2 5885 5150
3 1 1
#6 1 6 /4 10 /8 10 /8 8350 7530

#7 11/8 77/8 12 12 11390 8800


1 1 1
#8 1 /4 9 13 /2 13 /2 11580 9620

#10 11/2 11 161/2 161/2 13275 18200


For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N.
1
The tabulated values are for rebar installed in concrete having the designated compressive strength or higher at the time of installation.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge distances (c). Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate dimensions.
3
The anchors cannot be used to resist pullout forces in overhead and wall installations unless proper consideration is given to fire conditions.
4
Allowable loads shall not be increased for short-term loading due to wind or earthquake.
5
Bond strength values are based on a safety factor of 4.0.
6
Allowable load must be the lesser of bond or steel strength.
7
CIA-GEL 7000 anchors experience a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure
1 must be applied to the values in Table 8 when the anchors are installed in locations where the concrete temperatures may exceed 105EF.

TABLE 9—ALLOWABLE TENSILE LOADS FOR THREADED ROD INSTALLED


IN CONCRETE FOUNDATION WALL USING COVERT INJECTION ADHESIVE (pounds)1,2,3,4,5,6,7

ROD MINIMUM MINIMUM MINIMUM MINIMUM BASED ON BOND OR


DIAMETER, d EMBEDMENT WALL WIDTH EDGE ANCHOR CONCRETE STRENGTH
(inches) DEPTH, hef (inches) DISTANCE, c1 SPACING, s fNc = 2,500 psi (minimum)
(inches) (inches) (inches)
Center Location Center Location
(c2 $ 12 inches) (5 inches # c2 # 12
inches)
5
/8 9 5 13/4 9 3460 2780
7
/8 121/4 8 23/4 12 5910 4760
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of
installation.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge (c1) distances.
3
c2 is rod spacing in inches.
4
CIA anchors experience a reduction in capacity with increased ambient temperatures. The load factors noted in Figure 1 must
be applied to the values noted in the above table when the anchors are installed in locations where the concrete temperature may
exceed 105EF.
5
Allowable loads may be increased 331/3% in accordance with Section 1612.3.3 of the UBC or Section 1605.3.2 of the IBC for short-term
loading due to wind or seismic forces.
6
Allowable load must be lesser of bond or steel strength. See Table 5 for loads based on steel strength.
7
Bond strength values are based on a safety factor of 4.0.
Page 10 of 16 ER-4846

TABLE 10—ALLOWABLE TENSION AND SHEAR LOADS FOR THREADED ROD INSTALLED IN GROUT-FILLED
NORMAL-WEIGHT CONCRETE MASONRY UNITS USING COVERT INJECTION ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6

STUD DRILL EMBEDMENT, SPACING, s EDGE TENSION SHEAR CELL


DIAMETER DIAMETER hef (inches) DISTANCE, c (pounds)
(inches) (inches) (inches) (inches) Cell Joint
(pounds) (pounds)
3 1
/8 /2 31/2 63/4 33/8 1255 790 1170
1 5 1 1
/2 /8 4 /4 9 4 /2 1610 1060 1880
5 3
/8 /4 47/8 111/4 55/8 1980 1360 2270
3 7 1 1 3
/4 /8 6 /2 13 /2 6 /4 1910 2495 2975
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
Values are for 6- and 8-inch-wide Grade N, type, lightweight, medium weight, or normal weight concrete masonry units conforming to UBC
Standard 21-4 or ASTM C 90-99 (IBC or IRC), with a minimum compressive strength of 2,300 psi. Grout shall meet the proportions of Table 21-B
of the UBC, Table 2103.10 of the IBC, or Table R609.1.1 of the IRC.
2
Allowable load must be the lesser of bond or steel strength. See Tables 5 and 6 for steel strength values.
3
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate spacings.
4
The CIA-GEL 7000 experiences a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1
must be applied to the values in Table 12 tension values when anchors are installed in locations where the concrete temperatures may exceed
105EF.
5
The allowable loads are based on a factor of safety of 5. The tabulated allowable loads may be increased by 25 percent for installations under
the UBC.
6
Moratr must be Type N mortar complying with UBC Section 2103.3 and UBC 21-15 for compliance under the UBC, IBC Section 2103.7 for
compliance under the IBC, or Section R607.1 for compliance under the IRC.

TABLE 11—ALLOWABLE TENSION AND SHEAR VALUES IN CLAY BRICK MASONRY FOR THREADED RODS
USING COVERT INJECTION ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6,7,8

STUD DRILL EMBEDMENT, SPACING, s EDGE TENSION SHEAR BASED


DIAMETER DIAMETER hef (inches) DISTANCE, c BASED ON ON BOND
(inches) (inches) (inches) (inches) BOND STRENGTH
STRENGTH (pounds)
(pounds)
1 5
/2 /8 6 12 6 3090 2385
3 7 3 3
/4 /8 7 /4 15 7 /4 4485 3790
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
Allowable load must be the lesser of bond or steel strength. See Tables 5 and 6 for allowable loads based on steel strength.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear Interpolation may be used for intermediate dimensions.
3
The tabulated values are for anchors installed in minimum 9-inch-thick reinforced clay brick masonry with a minimum fNm = 1,300 psi. The brick
units shall conform to UBC Standard 21-1 or ASTM C 62-97a (IBC or IRC). Grout shall meet the proportions of Table 21-B of the UBC, Table
2103.10 of the IBC, or Table R609.1.1 of the IRC.
4
The CIA-Gel 7000 experiences a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1 must
be applied to the values when anchors are installed in locations where the concrete temperatures may exceed 105EF.
5
The anchors cannot be used to resist pullout forces in overhead and wall installations, unless proper consideration is given to fire conditions.
6
Anchors may be installed in the brick face or the mortar joint.
7
The allowable loads are based on a factor of safety of 5 and may be increased by 25 percent for applications under the UBC.
8
Mortar must be Type N mortar complying with UBC Section 2103.3 and UBC Standard 21-15 for compliance under the UBC, IBC Section 2103.7
for compliance under the IBC, or Section R607.1 for compliance under the IRC.
Page 11 of 16 ER-4846

TABLE 12—MINIMUM SPACING AND EDGE DISTANCE FOR COVERT INJECTION ADHESIVE ANCHORS
IN UNREINFORCED MASONRY (inches)

ANCHOR TYPE MINIMUM VERTICAL MINIMUM HORIZONTAL MINIMUM EDGE DISTANCE


SPACING SPACING

All Types1 16 16 16
For SI: 1 inch = 25.4 mm.
1
"All Types” refers to the three types of anchor assemblies described in Section 2.1.5.1 and Figures 2,3 and 4 of this report.

TABLE 13—ALLOWABLE TENSILE LOADS FOR THREADED ROD INSTALLED IN LIGHTWEIGHT AGGREGATE CONCRETE
USING COVERT INJECTION ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6,7

STUD MINIMUM SPACING, s EDGE BASED ON BASED ON BOND OR


DIAMETER, d EMBEDMENT (inches) DISTANCE, c BOND CONCRETE STRENGTH
(inch) DEPTH, hef (inches) STRENGTH fNc = 2,500 psi (minimum)
(inches)
fNc = 3,000 psi A 307 A 193 Gr. SS 304
B7
3
/8 13/4 5 23/4 820
3 2185 4580 2730
/8 33/8 8 4 2020
1
/2 21/2 5 23/8 1075
1 3885 8210 4860
/2 41/2 9 41/2 2245
5
/8 55/8 11 6 2545 6070 12910 7290
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N. 1EC = 0.555(tEF - 32)
1
Allowable load must be the lesser of bond or steel strength.
2
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate spacings.
3
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of installation.
4
CIA anchors experience a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1 must be
applied to the values in Table 13 when the anchors are installed in locations where the concrete temperatures may exceed 105EF.
5
The anchors cannot be used to resist pullout forces in overhead and wall installations, unless proper consideration is given to fire conditions.
6
Allowable loads may be increased by 331/3 percent in accordance with Section 1612.3.3 of the UBC or Section 1605.3.2 of the IBC for short-term
loading due to earthquakes or wind.
7
Bond strength values are based on a safety factor of 4.0.
Page 12 of 16 ER-4846

TABLE 14—ALLOWABLE SHEAR LOADS FOR THREADED ROD INSTALLED IN LIGHTWEIGHT AGGREGATE CONCRETE
USING COVERT INJECTION ADHESIVE CIA-GEL 7000 (pounds)1,2,3,4,5,6

STUD MINIMUM SPACING, s EDGE BASED ON BASED ON BOND OR


DIAMETER, d EMBEDMENT (inches) DISTANCE, c BOND CONCRETE STRENGTH
(inch) DEPTH, hef (inches) STRENGTH fNc = 2,500 psi (minimum)
(inches)
fNc = 3,000 psi A 307 A 193 Gr. SS 304
B7
3
/8 13/4 5 23/4 726
3 1125 2347 1400
/8 33/8 8 4 726
1
/2 21/2 5 23/8 677
1 2000 4170 2500
/2 41/2 9 41/2 677
5
/8 55/8 11 6 3027 3125 6520 3900
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced
in accordance with Table 4. Linear interpolation may be used for intermediate spacings.
2
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of installation.
3
Allowable load must be the lesser of bond or steel strength.
4
Bond strength values are based on a safety factor of 4.0.
5
Allowable loads may be increased by 331/3% for short-term loading due to earthquakes or wind.
6
CIA anchors experience a reduction in capacity with increased ambient temperatures. The temperature load factors noted in Figure 1 must be
applied to the values in Table 14 when the anchors are installed in locations where the concrete temperatures may exceed 105EF.

TABLE 15—INSTALLATION AND DESIGN INFORMATION FOR DUC UNDERCUT ANCHORS

CATALOG STUD HOLE/SLEEVE MIN. ANCHOR NOMINAL BOLT NOMINAL SLEEVE BOLT BOLT UNDERCUT
NUMBER DIA., d DIA., do HOLE EMBED., hef SLEEVE TENSILE BOLT AREA TENSILE TENSILE YIELD BEARING
(in.) (in.) DEPTH, h (in.) AREA STRESS (in.2) STRESS STRESS STRESS, fy AREA1, Ab
(in.) (in.2) AREA, Ase (fu) (psi) (fu) (psi) (psi) (in.2)
(in.2)

3 5
DUC 38-275 /8 /8 31/2 23/4 0.307 0.0775 0.110 67,000 58,000 36,000 0.308

3 5 1 1
DUC 38-450 /8 /8 5 /4 4 /2 0.307 0.0775 0.110 67,000 125,000 — 0.308

1 3
DUC 12-400 /2 /4 43/4 4 0.442 0.1419 0.196 67,000 58,000 36,000 0.499

1 3
DUC 12-600 /2 /4 63/4 6 0.442 0.1419 0.196 67,000 125,000 — 0.499

5
DUC 58-450 /8 1 51/2 41/2 0.785 0.226 0.307 67,000 58,000 36,000 0.665

5
DUC 58-750 /8 1 81/2 71/2 0.785 0.226 0.307 67,000 125,000 — 0.665

3
DUC 34-500 /4 11/8 61/4 5 0.994 0.334 0.442 67,000 58,000 36,000 0.876

3 1 1
DUC 34-900 /4 1 /8 10 /4 9 0.994 0.334 0.442 67,000 125,000 — 0.876

1
Bearing area conforms to Section 1923.3.1 of the UBC.
Page 13 of 16 ER-4846

TABLE 16—1997 UBC ALLOWABLE TENSION VALUES (SERVICE LOAD OR ALLOWABLE STRESS DESIGN METHOD)
DUC UNDERCUT ANCHORS INSTALLED IN MINIMUM 2,500 PSI STONE-AGGREGATE CONCRETE (pounds)1,2

5,
CATALOG STUD HOLE MINIMUM MINIMUM ANCHOR ANCHOR EDGE INSTALLATION TENSION
6
NUMBER DIAMETER, d DIAMETER, do HOLE EMBEDMENT4, SPACING, s DISTANCE, TORQUE
(inches) (inches) (inches) DEPTH3, h hef (inches) c T1
(inches) (inches) (inches) (foot-pounds)

60 (A36) Series

3 5
DUC38-275 /8 /8 31/2 23/4 51/2 23/4 20 1,130
1 3
DUC12-400 /2 /4 43/4 4 8 4 55 1,800
5
DUC58-450 /8 1 51/2 41/2 9 41/2 90 2,730

125 (B7) Series

3 5 1
DUC38-450 /8 /8 5 /4 41/2 9 41/2 35 1,900
1 3
DUC12-600 /2 /4 63/4 6 12 6 100 3,090
5
DUC58-750 /8 1 81/2 71/2 15 71/2 140 5,360
3 1
DUC34-900 /4 1 /8 101/4 9 18 9 300 7,085
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced using the provisions
of Section 1923.3 of the 1997 UBC.
2
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of installation.
3
Hole depth is measured from the concrete surface to the bottom of the hole.
4
Anchor embedment is measured from the concrete surface to the bottom of the expansion sleeve.
5
These tension values are only applicable when the anchors are installed without special inspection. Where special inspection is provided, allowable tension loads
are twice the tabulated values.
6
The DUC anchors may be used to resist wind and earthquake forces for compliance with the UBC. The load values may be adjusted in accordance with Section
1612.3 of the UBC for service (allowable stress) design.

TABLE 17—1997 UBC ALLOWABLE SHEAR VALUES (SERVICE LOAD OR ALLOWABLE STRESS DESIGN METHOD)
DUC UNDERCUT ANCHORS INSTALLED IN MINIMUM 2,500 PSI STONE-AGGREGATE CONCRETE (pounds)1,2

CATALOG STUD HOLE MINIMUM MINIMUM ANCHOR EDGE INSTALLATION SHEAR5,6


NUMBER DIAMETER, DIAMETER, do HOLE ANCHOR SPACING, s DISTANCE, c TORQUE
(inches) d (inches) DEPTH3, h EMBEDMENT4, (inches) (inches) T1
(inches) (inches) hef (foot-pounds)
(inches)

60 (A36) Series

3 5 1
DUC38-275 /8 /8 3 /2 23/4 51/2 23/4 20 1,400
1 3
DUC12-400 /2 /4 43/4 4 8 4 55 2,510
5
DUC58-450 /8 1 51/2 41/2 9 41/2 90 3,910

125 (B7) Series

3 5
DUC38-450 /8 /8 51/4 41/2 9 41/2 35 2,460
1 3
DUC12-600 /2 /4 63/4 6 12 6 100 3,970
5
DUC58-750 /8 1 81/2 71/2 15 71/2 140 6,320
3 1
DUC34-900 /4 1 /8 101/4 9 18 9 300 9,806
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may be reduced using the provisions
of Section 1923.3 of the UBC.
2
The tabulated values are for anchors installed in normal-weight concrete having the designated compressive strength or higher at the time of installation.
3
Hole depth is measured from the concrete surface to the bottom of the hole.
4
Anchor embedment is measured from the concrete surface to the bottom of the expansion sleeve.
5
The DUC Anchors may be used to resist wind and earthquake forces for compliance with the UBC. The load values may be adjusted in accordance with Section
1612.3 of the UBC for service (allowable stress) design.
6
These shear values apply with or without special inspection.
Page 14 of 16 ER-4846

TABLE 18—1997 UBC STRENGTH DESIGN METHOD TENSION VALUES FOR DUC UNDERCUT ANCHORS
INSTALLED IN STONE-AGGREGATE CONCRETE1,2,3,4,5,6

CATALOG ANCHOR HOLE ANCHOR ANCHOR EDGE φPc Anchor Tensile Strength (lbf) Pss
NUMBER DIAMETER DIAMETER, EMBEDMENT, SPACING, s DISTANCE, c Steel
(in.) do hef (in.) (in.) Concrete Strength (psi) Strength
(in.) (in.)
(lbf)
2,000 3,000 4,000 5,000

A 36 Series
3 5
DUC38-275 /8 /8 2.75 5.50 2.75 2765 3385 3905 4370 4045
1 3
DUC12-400 /2 /4 4.00 8.00 4.00 5845 7158 8266 9240 7410
5
DUC58-450 /8 1 4.50 9.00 4.50 7397 9060 10461 11695 11795
3 1
DUC34-500 /4 1 /8 5.00 10.00 5.00 9130 11185 12915 14440 17435

B7 Series
3 5
DUC38-450 /8 /8 4.50 9.00 4.50 7395 9060 10460 11695 8720
1 3
DUC12-600 /2 /4 6.00 12.00 6.00 13150 16105 18600 20795 15975
5
DUC58-750 /8 1 7.50 15.00 7.50 20550 25165 29060 32490 25425
3
DUC34-900 /4 11/8 9.00 18.00 9.00 29590 36240 41845 46785 37575
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing and edge distances may
be reduced using the provisions of Section 1923.3 of the UBC. Additional strength design static tension loads may be determined
in accordance with Sections 1923.3, 1923.3.3 and 1923.4 of the code.
2
The tabulated values are for anchors installed in concrete having the designated compressive strength or higher at the time of
installation.
3
Pss values are calculated using the formulas in Section 1923.3.2 of the UBC where Ab is the bolt tensile area.
4
Anchor embedment is measured from the concrete surface to the bottom of the expansion sleeve.
5
Use the lesser of Pss and i Pc.
6
The tabulated are based on special inspection in accordance with Section 2.3.
Page 15 of 16 ER-4846

TABLE 19—1997 UBC STRENGTH DESIGN METHOD SHEAR VALUES FOR DUC UNDERCUT ANCHORS
INSTALLED IN STONE-AGGREGATE CONCRETE1,2,3,4,5,6,7,8

CATALOG ANCHOR HOLE ANCHOR ANCHOR EDGE φVc Anchor Shear Strength (pounds) Vss Vsss
NUMBER DIAMETER, DIAMETER, EMBEDMENT, SPACING, s DISTANCE, c Steel Steel
d do hef (in.) (in.) Concrete Strength (psi) Strength Strength
(in.) (in.) (in.)
(lb) (lb)
2,000 3,000 4,000 5,000

A 36 Series
3 5
DUC38-275 /8 /8 2.75 5.50 4.375 3110 3805 4395 4915 3370 15425
1 3
DUC12-400 /2 /4 4 8.00 6 6575 8055 9300 10395 6175 22210
5
DUC58-450 /8 1 4.5 9.00 6.75 8320 10190 11770 13160 9830 39440
3
DUC34-500 /4 11/8 7.5 10.00 7.5 10275 12585 14530 16245 14530 49948

B7 Series
3 5
DUC38-450 /8 /8 6.25 9.00 3.75 7135 8740 10090 11280 7265 15425
1 3
DUC12-600 /2 /4 7.5 12.00 5.00 10275 12585 14529 16245 13305 22210
5
DUC58-750 /8 1 10 15.0 6.25 18265 22370 25830 28880 21190 39445
3 1
DUC34-900 /4 1 /8 11.25 18.00 7.50 23115 28310 32690 36550 31315 49950
For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N.
1
The tabulated values are for anchors installed at the specified spacing (s) and edge (c) distances. Spacing
and edge distances may be reduced using the provisions of Section 1923.3 of the 1997 UBC. Additional
strength design static shear loads may be determined in accordance with Sections 1923.2, 1923.3.2, 1923.3.3
and 1923.4 of the UBC.
2
The tabulated values are for anchors installed in concrete having the designated compressive strength or
higher at the time of installation.
3
Vss is calculated using the formulas in Section 1923.3 of the UBC where Ab is the bolt tensile area. Vss is for
pre-set anchor applications.
4
Vsss is calculated using the formulas in Section 1923.3 of the UBC where Ab is the nominal sleeve area. Vsss
is for through-bolt anchor applications.
5
Vc is calculated using the formulas in Section 1923.3 of the UBC where Ab is the nominal sleeve area. Vc is
for pre-set anchor through-bolt anchor applications.
6
Anchor embedment is measured from the concrete surface to the bottom of the expansion sleeve.
7
Use the lesser of Vss and Vc, or Vsss and Vc.
8
The tabulated values are based on special inspection in accordance with Section 2.3.
Page 16 of 16 ER-4846

FIGURE 1—CONCRETE TEMPERATURE SENSITIVITY TENSION AND SHEAR


LOAD FACTOR FOR CIA ANCHORS

FIGURE 2 FIGURE 3 FIGURE 4


THE COMBINATION ANCHOR THE THRU-BOLT ANCHOR THE SHEAR ANCHOR