Fire Detection Control Panel FMZ 4100

The Minimax fire detection control panel appear, the programme controlled alarm Minimax's experience collected over many
FMZ 4100 is a compact function centre analysis is interrupted in order to avoid years in the field of evaluation and assess-
with high availability, combining all the ad- any faulty functioning. In this case, the ment of fire characteristics is to be found
vantages of modern micro-electronics. alarm evaluation continues to function by in an extensive, error-tolerant analysis
means of an emergency operational cir- software. The software enables the sys-
The reliable and reasonably priced line cuit. In the case of interference, maximum tem to differentiate between alarm signals
technology is ideal for the monitoring of only one plug-in unit will fail to function and spurious ( parasitic) signals. By means
large areas. In addition, digital information due to the parallel operation of the diffe- of a dialogue between the fire detection
can be transferred from each detector rent analysis units. It is also possible to control panel and himself, the user is led
thus enabling, amongst other things, indi- exchange defective components without through the necessary operational phases
vidual single alarm identification. As a re- any operational interruptions occuring. thereby ruling out, to the greatest possible
sult of this, it is possible to combine many
extent, all possibility of problems arising
small areas or rooms in only one detector The fire detection control panel FMZ 4100
from incorrect operating or stress influ-
group. The activated detector can then be contains all of the essential performance
clearly identified on the LC display of the features of the earlier Minimax devices. enced abnormal behaviour in the case of
fire detection control panel. Additionally, it fulfills all requirements of a alarms or disturbances.
modern comprehensive safety-informa-
The heart of the control panel is a micro The fire detection control panel FMZ 4100
tion system with an integrated detector
processor controlled analysis unit. This fulfills the highest safety requirements
identification system and a large LC dis-
unit is responsible for all monitoring and play as well as having a report printer, sta- which are, of course, indispensable in the
control functions and because of its in- tus and intervention system and an inter- field of fire protection. The control panel
built automatic interrupt control function face to building adminstration systems. including the system's components are in
it can react to alarm signals without delay. These features enable an exact evaluation accordance with the valid guidelines,
The panel itself is monitored by a watch- of the incoming alarms so that prevent- norms and regulations – especially VDE
dog timer which is reactivated each time ative measures may be carried out quickly. and EN 54 – and is approved by the
data passes through the cyclic running ”Verband der Schadenversicherer“ (VdS,
programme. If the trigger impulse fails to Association of German Property Insurers).
Design variants Each group is connected to the line card zone fire extinguishing systems. It func-
via line termination cards. Using one line tions independently from the other sys-
The fire detection control panel is a modu- card, it is possible to supply, evaluate and tems of the fire detection control panel
lar extendable 19" unit assembly system. monitor 4 alarm groups for automatic fire and therefore has its own display and
Even in its smallest basic design (GAB 32), alarms, 4 alarm groups for contact giving fire operating panel.
it is capable of accomodating 2 x 32 fire alarms and 4 primary control groups. A re-
alarm groups and 32 primary control duced version can be supplied when only Each extinguishing zone is controlled and
groups, besides the central equipment 4 automatic fire alarm groups are required. monitored by an autarkical functioning ex-
such as the power supply unit, battery and tinguishing control card. All the important
main alarm tripping. The alarm signals recorded in the fire con- components which are necessary for the
trol panel are digitalized and are then, in trouble-free functioning of an extinguishing
In the larger model (GAB 128), the system comparison between normal condition and system (e.g. detectors, release and alarm)
can be extended to 3 x 128 groups by actual condition, compared with the pro- devices are connected to the extinguishing
means of additional plug-in zone modules. grammed values in the non-volatile mem- control system. In the case of alarm, the
ory. In the case of negative results, either extinguishing control system registers and
In this case, a common central plug-in unit an alarm signal or an interference signal
(master system) takes over the overriding analyses the detector signal, sounds
(e.g. ”wire breakage“, ”short circuit“, ”de- the fire alarm and activates the pre-pro-
control procedure for the otherwise au- tector removed“) is produced. A redundant,
tarkic plug-in zone modules (master-slave grammed control function as well as the fire
independent alarm circuit continues to con- extinguishing system.
process). duct the alarm even in the case of inter-
A total combination of 3072 groups can be ference or breakdown of the control sys- Programming
obtained by joining together up to 8 stand- tem.
ing cabinets of the above type. Important alarm devices are connected to The fire detection control panel FMZ 4100
the quiescent current monitoring of the pri- can be programmed for different applica-
FMZ 4100 - GAB 32 mary control groups. tions. For this purpose a special configur-
ation programme has been developed
is extendable, with each device having 32 Detector identification system which transforms the physical values of
automatic and contact giving fire alarm (ZID-V) entered characteristics (e.g. alarm thres-
groups as well as primary control groups hold, short circuit threshold, etc.) into a
for the electrical monitoring and for the This is a system component which func- ”language“ understandable for the micro-
operating of the important function alarm tions independently from the analysis unit. controller. In this way, the user has the
devices such as alarm horns, release sol- It displays selectively the position and type maximum amount of flexibility which, for
enoids, etc. of the activated, defective or removed de- instance, is required when extending
tectors. already existing systems.
The main component of this device is a Programming is greatly simplified by the
Wall use of modern ”pull-down-menu-techni-
mounted microcontroller which additionally and uni-
directionally requests data from the detec- ques“ and easy-to-understand input in-
cabinet 15U
tor via a secondary network. A specially structions.
developed analysis software checks the
detector’s signal for accuracy and then Secondary groups
evaluates it. The obtained results are trans-
The fire detection control panel FMZ 4100
mitted asynchronously to the analysis unit
can be equipped with free programmable
via FIFO-circuits where they are then dis-
relays in order to enable further alarm or-
played on a comprehensive 8 x 40 figure
ganization, for example: the disconnection
alpha-numerical LC display.
of the air conditioning, the interruption of
The detector identification system, the al- the manufacturing process, the opening of
pha-numerical clear text display and the smoke vent flaps, etc. 2 break contacts
report printer complement each other and (b-contacts) and 2 make contacts (a-con-
together form an important information tacts) with a maximum contact load of 2
system thus enabling the quick introduc- amperes are available for each relay. The
FMZ 4100 - GAB 128
tion of decisive and appropriate measures. operating and logical combination of the
is extendable, with each device having 128 relays is determined for each specific sys-
automatic and contact giving fire alarm Extinguishing control tem by means of the Minimax configu-
zones as well as primary control groups. for the fire extinguishing system ration programme. The standard functions
are as follows: operating tripped by alarm,
The system component ”extinguishing pre-alarm and interferences as well as the
Upright cabinet 31U
control“ is used to control single and multi- disconnection of fire detector groups.

Alarm and graphics reporting system ZID-V detector


Serial interfaces
The fire detection control panel FMZ 4100 Scheme of control panel FMZ 4100
has standard serial interfaces for connec-
tion to external equipment, e.g. alarm and
Fire brigade
graphics reporting system or printer, as operating panel
well as enabling communication with a
superordinate administration system. An
additional microcontroller circuit which has
been especially developed for the oper- Report
ating of repeater panels as well as exter- printer
nally situated control devices can exchange
information with the fire detection control Building
Serial
panel via a serial interface. There are 768 management interface
programmable outputs available for the system
operating of the LEDs in a repeater panel. Alarm and
Additionally, the microcontroller has a seri- graphics re-
al interface for data transmission, e.g. for a porting system
desk-top printer. The fire detection control
Repeater
panel FMZ 4100 offers further interfaces
panel
for fire brigade control panels as well as for
the so-called ”public main alarm“. An alarm Network
signal can be automatically transmitted fur- Slave control interface
ther to an external service, e.g. fire brigade, panels
by means of the main alarm function. Addi-
Operator panel
tional VdS standard interfaces are avail- extinguishing
able for the connection of fire detection control
equipment from other manufacturers to the Manual
FMZ 4100 extinguishing control system. release

Special applications Second


release
Spark extinguishing systems Field termi-
nation card
The possibility of realizing special applica- Extinguishing extinguish- Multi-zone
tions of fire detection and extinguishing delay ing system extinguishing control system
technology were taken into consideration control
during the development of the fire detec- EMI
System protection
tion control panel FMZ 4100. These spe- monitoring
cial applications are, for example, spark
extinguishing systems for the wood indus- Automatic Field termination
try, fire suppression systems for paint card for primary
release control zones
spraying plants as well as for the protec- EMI protection
tion of equipment in computing centres. If
one takes the spark extinguishing system
as an example, it can be seen that this sys-
tem can be connected to the control panel
without any special or additional analyzing
electronics. All the requirements neces-
sary for operating a spark extinguishing
system such as adjustable extinguishing
times for each extinguishing area, moni- CO 2 low pressure system CO 2 / Argon high
toring of the extinguishing agent supply, pressure system
electrical monitoring of heat tapes and O
leak detectors are to be found in the stan- •

dard programme of the control panel. It is, •
therefore, guaranteed that the evaluation •

of spark alarms as well as the operating of
the automatic extinguishing system will be
carried out with virtually no delay.

Gas detectors
A gas detector is an autonomous subsys- FMZ 4100 multi zone Fire protection for
tem that can be easily integrated in the CO2 extinguishing control panel paint spraying plants
FMZ 4100 fire detection control panel.
Owing to the increasingly complex chemi-
cal processes used in industry, gas detec-
tion at an early stage is often the main
element of a safety scheme and is accor-
dingly very suitable for combination with
fire detection and fire systems. A display
continuously indicates the gas concentra-
tions in the gas detectors. If the gas con-
centration measured exceeds a preset li-
mit, external equipment can be activated
via secondary control lines. All measured
data is passed on to the FMZ 4100 where
it is recorded. This assures the traceability
of events even after a lengthy period.
Fire brigade Mimic panel Fire brigade
key box main alarm

Field termi- Automatic


Operator panel Group LEDs nation card
for detector detectors
groups
EMI protec- Contact giving
Line tion
detectors
card

Master CPU Field termi- Optical / acoustic


peripheral evaluation nation card
for primary alarm
and control
control groups
EMI protec- Trigger solenoid
tion
valve

Air condition
off
Relay
control
card Machinery
Slave CPU 1 off
evaluation and control Relay
card
Smoke vent
unlock

Field
termination
card Detector
Detector detector identification
identification identification for automatic and
system EMI protec- contact giving detectors
System tion
Gas detection
Gas line card
Termi- Gas detector
nation
and
control
card Optical / acoustic
Concentration alarm
display and
operating panel
Machinery
off

Digital system monitoring Evaluation and control system


Quiescent current monitoring Detector identification system
Other extinguishing systems
Non monitored lines Extinguishing control system
• Deluge-
• Foam-/Powder- Gas detection system
• Spark-
• Pre-action Sprinkler-
• Argon extinguishing system

Minimax detector collection Fire protection for EDP installations Repeater panel
Interface to slave module Processor card

Master plug-in card

Field termination
card detector
identification

Interface to master module

Detector identification card

Relay card

Extinguishing control card Relay control card

Fire detection and extinguishing control panel


for 384 groups

Field
termination
card for Field termination Field termination
detector card for primary card for detector
groups control groups groups

Line card for 4 automatic, contact Line card for


giving and primary control groups 4 automatic
groups
Technical Data
Fire Detection Control Panel FMZ 4100 GAB 32, GAB 96, GAB 128

Specific System Data


Power supply 230 V /110 V, 50/60 Hz, (+10 %, -15 %) switchable by jumper at power supply
Operating voltages 15 V, 12 V, 5 V
Control voltage of external devices 24 V DC
Emergency power supply 24 V DC (2 x 12 V maintenance free and sealed batteries, independent of
position, deep-discharge resitant, capacity range application specific)
Control relay rating 30 W/60 VA /1.5 A / 250 V
Control signal of main alarm 24 V DC, constant or pulses, adjustable from 1 to 10 seconds
Permissible ambient temperature -5 - +40 °C
Permissible ambient air humidity 12 g /m3
Place of installation dry operating areas with restricted access
VdS approval G 29013
FM approval OY4AO.AY

Specific Data FMZ 4100 GAB32 FMZ 4100 GAB96 FMZ 4100 GAB128
Max. number of groups 32/ 32/ 321 96/ 96/ 961 128 /128 /1281
Serial interfaces RS 232C 2 3 2
Number of control relays with full complement 80 224 296
Housing type wall-mounted 15U upright cabinet 31U upright cabinet 40U
swivel frame swivel frame swivel frame
Colour RAL 7032, grey, structured RAL 7032, grey, structured RAL 7032, grey, structured
Weight of complete unit (without batteries) approx. 48 kg approx. 135 kg approx. 160 kg
IP rating IP 42 IP 54 IP 54
Dimensions in mm (W x H x D) 2 525 x 709 x 275 800 x 1600 x 500 800 x 2060 x 600

Line cards 3

Automatic detector groups


Detection Group voltage 9V
Detection Group quiescent current approx. 5 mA
Detection Group alarm current ≥ 9 mA (spark extinguishing system: ≥ 15 mA) 4
Detection Group terminating resistance 1800 
Alarm resistance (detector) 470  - 1000 
Permissible max. line resistance 50 
Permissible max. number of detectors per group 10 manual call points or 60 sprinkler monitoring modules 5

Contact giving detector groups


Detection Group current approx. 2.2 mA
Detection Group quiescent voltage 3.9 - 4.1 V
Detection Group alarm voltage 2.7 V 4
Detection Group terminating zener diode ZPD 4V3 (spark extinguishing system BZX 4V3)
Detection Group alarm zener diode ZPD 2V7 (spark extinguishing system BZX 2V4)6
Permissible max. line resistance 50 
Permissible max. amount of detectors per groups 10 5

Primary control groups


Detection Group current approx. 2.6 mA
Control voltage 24 V DC
Detection Group quiescent voltage approx. 2.6 V
Max. load 2 A ( limited by fuse)
Detection Group terminating resistance 1000  /1 Watt

Fire extinguishing control system


4 groups for automatic detectors 7
4 groups for contact giving detectors 7
4 primary control groups7
8 free programmable relays for non monitored groups

1 For 32, 96 or 128 automatic and contact giving groups and primary control groups
2 Other cabinet sizes available
3 A reduced version can be supplied when only automatic fire alarm groups are required
4 Other current/voltage threshold values programmable
5 VdS standard value
6 For evaluation of different interferences in sparc extinguishing systems, e.g. continuous extinguishing, water supply fault, 3 additional thershold voltage values are monitored
7 Technical data for groups of the extinguishing control system are similar to the line card
Printed in Gernmany

The right is reserved to modify any specification without prior notice.