You are on page 1of 502

3UHIDFH L

7DEOHRI&RQWHQWV Y

SIPROTEC
,QWURGXFWLRQ 1
+DUGZDUHDQG&RQQHFWLRQV 2
Differential Protection
7SD610 *HWWLQJ6WDUWHG 3
V4.0
6,3527(&Š'HYLFHV 4
Manual
&RQILJXUDWLRQ 5
)XQFWLRQV 6
&RQWURO'XULQJ2SHUDWLRQ 7
,QVWDOODWLRQDQG&RPPLVVLRQLQJ 8
0DLQWHQDQFHDQG)DXOW7UDFLQJ 9
7HFKQLFDO'DWD 10
$SSHQGL[ A
,QGH[

C53000-G1176-C145-1
Siemens Aktiengesellschaft Buch-Nr. C53000-G1176-C145-1
Preface

Purpose of This This manual describes the functions, operation, installation, and placing into service
Manual of the device. In particular, one will find:
• General information regarding operation of SIPROTEC® 4 devices → Chapter 4.
• Information regarding customizing of the device → Chapter 5.
• Descriptions of device functions and settings → Chapter 6.
• Instructions for operation while in service → Chapter 7.
• Instructions for mounting and commissioning → Chapter 8.
• Compilation of technical specifications → Chapter 10.
• As well as a compilation of the most significant data for experienced users in the
Appendix.

Target Audience Protection engineers, commissioning engineers, personnel concerned with adjust-
ment, checking, and service of selective protective equipment, automatic and control
facilities, and personnel of electrical facilities and power plants.

Applicability of This manual is valid for SIPROTEC® 4 7SD610 differential protection;


This Manual firmware version 4.0.

Indication of Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the member states relating to electromagnetic
compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equip-
ment for use within certain voltage limits (Low-voltage Directive 73/23/EEC).
This conformity is proved by tests conducted by Siemens AG in accordance with Ar-
ticle 10 of the Council Directive in agreement with the generic standards EN 50081
and EN 50082 for EMC directive, and with the standards EN 60255–6 for the low-volt-
age directive.
The product conforms with international standards of series IEC 60255 and the Ger-
man standard DIN 57435 /Part 303 (corresponds to VDE 0435/Part 303).

Additional Support For questions regarding SIPROTEC® 4 devices, please contact your Siemens repre-
sentative.

7SD610 Manual i
C53000-G1176-C145-1
Preface

Training Courses Individual course offerings may be found in our Training Catalog, or questions can be
directed to our training centre. Please contact your Siemens representative.

Instructions and The following indicators and standard definitions are used:
Warnings
DANGER
means that death, severe personal injury, or considerable equipment damage will oc-
cur if safety precautions are disregarded.
Warning
means that death, severe personal injury, or considerable equipment damage could
occur if safety precautions are disregarded.
Caution
means that light personal injury or equipment damage may occur if safety precautions
are disregarded. This particularly applies to damage to the device and to resulting da-
mage of the protected equipment.
Note
is an important piece of information regarding the product or the part of the manual
that deserves special attention.

Warning!
During operation of electrical equipment, certain parts of these devices are under high
voltage. Severe personal injury or significant equipment damage could result from im-
proper behaviour.
Only qualified personnel should work on this equipment or in the vicinity of this equip-
ment. These personnel must be familiar with all warnings and service procedures de-
scribed in this manual, as well as with safety regulations.
Prerequisites to proper and safe operation of this product are proper transport, proper
storage, setup, installation, operation, and maintenance of the product, as well as
careful operation and servicing of the device within the scope of the warnings and in-
structions of this manual.
In particular, the general facility and safety regulations for work with high-voltage
equipment (e.g. ANSI, IEC, EN, or other national or international regulations) must be
observed. Noncompliance may result in death, injury, or significant equipment dam-
age.

QUALIFIED PERSONNEL
Within the meaning of safety precautions of this manual and the instructions, qualified
personnel are those persons who are qualified to set up, install, place into service, and
operate this device, and who possess the following qualifications:
q Training and instruction (or other qualification) for switching, grounding, and desig-
nating devices and systems.
q Training or instruction in accordance with safety standards for care and use of cer-
tain safety equipment.
q First aid training.

ii 7SD610 Manual
C53000-G1176-C145-1
Preface

Typographic and The following text formats are used to identify concepts giving device information de-
Graphical Conven- scribed by the text flow:
tions
3DUDPHWHUQDPHV, or identifiers for configuration or function parameters that appear
in the device display or on the screen of a PC (with DIGSI® 4) are shown in mono-
script (same point size) bold text. This also applies to header bars for selection menus.
3DUDPHWHUFRQGLWLRQV, or possible settings of parameters that appear in the de-
vice display or on the screen of a PC (with DIGSI® 4), are additionally shown in italic
style. This also applies to selection items for selection menus.
“$QQXQFLDWLRQV”, or identifiers for information produced by the device or required
by other devices or from the switch-gear is shown in mono-script (same point size) and
placed into quotation marks.
For diagrams in which the identifier type results from the representation itself, text con-
ventions may differ from the above-mentioned.
The following symbols are used in diagrams:

GND Fault device-internal (logical) input signal

GND Fault device-internal (logical) output signal

UL1–L2 internal input signal of an analog quantity


F#

>Release
external binary input signal with function number F# (binary input,
respective annunciation to the device)
F#
external binary output signal with function number F# (annunciation
Dev. Trip
from device)

Parameter address
3DUDPHWHUQDPH

 )81&7,21 example of a parameter switch designated )81&7,21 with


2Q address and possible conditions 2Q and 2II
2II

Parameter Conditions

Besides these, graphical symbols are used according to IEC 60617–12 and
IEC 60617–13 or similar. Some of the most frequently used are listed below:

Input signal of an analogue quantity

≥1 OR gate

& AND gate

signal inversion

Exclusive–OR gate (antivalence): output is active, if only one


=1
of the inputs is active

7SD610 Manual iii


C53000-G1176-C145-1
Preface

Coincidence gate (equivalence): output is active, if both input are


=
active or inactive at the same time

≥1 Dynamic inputs (edge–triggered)


above with positive, below with negative edge

Formation of one analogue output signal from


a number of analogue input signals (example: 3)

 ,SK!!

Iph> Limit stage with setting address and parameter designator (name)

 7,SK!!

T 0
Timer (pickup delay T, example adjustable)
with setting address and parameter designator (name)

0 T
Timer (dropout delay T, example non-adjustable)

T Dynamic triggered pulse timer T (monoflop)

S Q Static memory (RS–flipflop) with setting input (S),


R Q resetting input (R), output (Q) and inverted output (Q)

Liability Statement Copyright


We have checked the text of this manual against the Copyright © Siemens AG 2001. All rights reserved.
hardware and software described. Exclusions and devi- Dissemination or reproduction of this document, or evaluation and com-
ations cannot be ruled out; we accept no liability for lack munication of its contents, is not authorized except where expressly per-
of total agreement. mitted. Violations are liable for damages. All rights reserved, particularly
The information in this manual is checked periodically, for the purposes of patent application or trademark registration.
and necessary corrections will be included in future edi-
tions. We appreciate any suggested improvements. Registered trademarks
SIPROTEC®, SIMATIC®, SIMATIC NET ®, SINAUT ®, and SICAM®,
We reserve the right to make technical improvements and DIGSI® 4 are registered trademarks of Siemens AG. Other desig-
without notice. nations in this manual may be trademarks that if used by third parties for
their own purposes may violate the rights of the owner. n

iv 7SD610 Manual
C53000-G1176-C145-1
Table of Contents

Preface................................................................................................................................................... i

Table of Contents ................................................................................................................................ v

1 Introduction....................................................................................................................................... 1-1

1.1 Overall Operation ................................................................................................................ 1-2

1.2 Applications ......................................................................................................................... 1-5

1.3 Features .............................................................................................................................. 1-7

1.4 Scope of Functions.............................................................................................................. 1-8

2 Hardware and Connections ............................................................................................................. 2-1

2.1 Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting....................................... 2-2
2.1.1 Housing ............................................................................................................................... 2-2
2.1.2 Screw Terminal Connections............................................................................................... 2-5
2.1.3 Connections to Plug-In Terminals ....................................................................................... 2-9
2.1.4 Connections to Optical Communication Interfaces............................................................ 2-12
2.1.5 Connections to Electrical Communication Interfaces ........................................................ 2-14

2.2 Version of 7SD610 for Panel Surface Mounting................................................................ 2-15


2.2.1 Housing ............................................................................................................................. 2-15
2.2.2 Screw Terminal Connections............................................................................................. 2-17
2.2.3 Connections to Optical Communication Interfaces............................................................ 2-18
2.2.4 Connections to Electrical Communication Interfaces ........................................................ 2-20

3 Getting Started.................................................................................................................................. 3-1

3.1 Unpacking and Re-packing ................................................................................................. 3-2

3.2 Inspections upon Receipt .................................................................................................... 3-3


3.2.1 Inspection of Features and Ratings..................................................................................... 3-3
3.2.2 Electrical Check................................................................................................................... 3-3

7SD610 Manual v
C53000-G1176-C145-1
Table of Contents

3.3 User Interface ...................................................................................................................... 3-4


3.3.1 Operation Using the Operator Control Panel....................................................................... 3-4
3.3.2 Operation Using DIGSI® 4................................................................................................... 3-7

4 SIPROTEC® 4 Devices....................................................................................................................... 4-1

4.1 General ................................................................................................................................ 4-2


4.1.1 Protection and Control ......................................................................................................... 4-2
4.1.2 Communication.................................................................................................................... 4-3
4.1.3 Settings................................................................................................................................ 4-4
4.1.4 Operations ........................................................................................................................... 4-4
4.1.5 Oscillographic Fault Records............................................................................................... 4-4

4.2 Operator Control Facilities ................................................................................................... 4-5


4.2.1 Operator Control Panel On Device ...................................................................................... 4-5
4.2.2 DIGSI® 4 Tool...................................................................................................................... 4-7

4.3 Information Retrieval............................................................................................................ 4-8


4.3.1 Annunciations ...................................................................................................................... 4-9
4.3.2 Measurements ................................................................................................................... 4-11
4.3.3 Oscillographic Fault Records............................................................................................. 4-12

4.4 Control ............................................................................................................................... 4-14

4.5 Manual Overwrite / Tagging............................................................................................... 4-16

4.6 General about the Setting Procedures .............................................................................. 4-17

4.7 Configuration of the Scope of Device Functions................................................................ 4-20

4.8 Configuration of Inputs and Outputs (Configuration Matrix) .............................................. 4-21

4.9 Programmable Logic CFC ................................................................................................. 4-24

4.10 Power System Data ........................................................................................................... 4-26

4.11 Setting Groups................................................................................................................... 4-27

4.12 General Device Settings .................................................................................................... 4-29

4.13 Time Synchronization ........................................................................................................ 4-30

4.14 Serial Interfaces................................................................................................................. 4-31

4.15 Passwords ......................................................................................................................... 4-33

5 Configuration .................................................................................................................................... 5-1

5.1 Configuration of the Scope of Functions.............................................................................. 5-2


5.1.1 Setting Overview.................................................................................................................. 5-4

vi 7SD610 Manual
C53000-G1176-C145-1
Table of Contents

5.2 Configuration of Information, Measured Values, and Commands....................................... 5-6


5.2.1 Preparation .......................................................................................................................... 5-6
5.2.2 Structure and Operation of the Configuration Matrix ......................................................... 5-10
5.2.3 Establishing Information Properties................................................................................... 5-13
5.2.4 Performing Configuration................................................................................................... 5-19
5.2.5 Transferring Metering Values ............................................................................................ 5-24
5.2.6 Settings for Contact Chatter Blocking................................................................................ 5-25

5.3 Creating User Defined Functions with CFC....................................................................... 5-27

5.4 Serial Interfaces ................................................................................................................ 5-36

5.5 Date and Time Stamping................................................................................................... 5-40

6 Functions........................................................................................................................................... 6-1

6.1 General................................................................................................................................ 6-2


6.1.1 Power System Data 1.......................................................................................................... 6-7
6.1.1.1 Setting Overview ............................................................................................................... 6-12
6.1.2 Setting Groups .................................................................................................................. 6-13
6.1.2.1 Setting Overview .............................................................................................................. 6-15
6.1.2.2 Information Overview ........................................................................................................ 6-15
6.1.3 General Protection Data .................................................................................................... 6-15
6.1.3.1 Setting Overview ............................................................................................................... 6-20
6.1.3.2 Information Overview ........................................................................................................ 6-21

6.2 Differential Protection ........................................................................................................ 6-23


6.2.1 Function Description.......................................................................................................... 6-23
6.2.2 Setting the Function Parameters ....................................................................................... 6-31
6.2.3 Setting Overview ............................................................................................................... 6-34
6.2.4 Information Overview......................................................................................................... 6-34

6.3 Breaker Intertrip and Remote Tripping .............................................................................. 6-36


6.3.1 Function Description.......................................................................................................... 6-36
6.3.2 Setting the Function Parameters ....................................................................................... 6-37
6.3.3 Setting Overview .............................................................................................................. 6-38
6.3.4 Information Overview ........................................................................................................ 6-39

6.4 Protection Data Interfaces and Differential Protection Topology....................................... 6-40


6.4.1 Function Description.......................................................................................................... 6-40
6.4.2 Setting the Function Parameters ....................................................................................... 6-42
6.4.3 Setting Overview ............................................................................................................... 6-45
6.4.4 Information Overview......................................................................................................... 6-46

7SD610 Manual vii


C53000-G1176-C145-1
Table of Contents

6.5 Direct Local Trip................................................................................................................. 6-47


6.5.1 Function Description .......................................................................................................... 6-47
6.5.2 Setting the Function Parameters ....................................................................................... 6-47
6.5.3 Setting Overview ............................................................................................................... 6-48
6.5.4 Information Overview ........................................................................................................ 6-48

6.6 Direct Remote Trip or Transmission of Binary Information................................................ 6-49


6.6.1 Information Overview ........................................................................................................ 6-49

6.7 Instantaneous High-speed SOTF Protection ..................................................................... 6-50


6.7.1 Function Description .......................................................................................................... 6-50
6.7.2 Setting the Function Parameters ....................................................................................... 6-51
6.7.3 Setting Overview................................................................................................................ 6-53
6.7.4 Information Overview ........................................................................................................ 6-53

6.8 Time Overcurrent Protection.............................................................................................. 6-54


6.8.1 Function Description .......................................................................................................... 6-54
6.8.2 Setting the Function Parameters ....................................................................................... 6-60
6.8.3 Setting Overview................................................................................................................ 6-66
6.8.4 Information Overview ........................................................................................................ 6-68

6.9 Automatic Reclosure.......................................................................................................... 6-69


6.9.1 Function Description .......................................................................................................... 6-70
6.9.2 Setting the Function Parameters ....................................................................................... 6-82
6.9.3 Setting Overview ............................................................................................................... 6-88
6.9.4 Information Overview......................................................................................................... 6-91

6.10 Circuit Breaker Failure Protection...................................................................................... 6-95


6.10.1 Method of Operation .......................................................................................................... 6-95
6.10.2 Applying the Function Parameter Settings ...................................................................... 6-106
6.10.3 Setting Overview.............................................................................................................. 6-109
6.10.4 Information Overview ...................................................................................................... 6-110

6.11 Thermal Overload Protection........................................................................................... 6-111


6.11.1 Function Description ........................................................................................................ 6-111
6.11.2 Setting the Function Parameters ..................................................................................... 6-112
6.11.3 Setting Overview.............................................................................................................. 6-114
6.11.4 Information Overview ...................................................................................................... 6-114

6.12 Monitoring functions......................................................................................................... 6-115


6.12.1 Function Description ........................................................................................................ 6-115
6.12.1.1 Hardware Monitoring ....................................................................................................... 6-115
6.12.1.2 Software Monitoring......................................................................................................... 6-117
6.12.1.3 Monitoring of External Transformer Circuits .................................................................... 6-117
6.12.1.4 Trip Circuit Supervision.................................................................................................... 6-119
6.12.1.5 Fault Reactions................................................................................................................ 6-121
6.12.1.6 Group Alarms................................................................................................................... 6-123

viii 7SD610 Manual


C53000-G1176-C145-1
Table of Contents

6.12.2 Setting the Function Parameters ..................................................................................... 6-123


6.12.3 Setting Overview ............................................................................................................. 6-124
6.12.4 Information Overview....................................................................................................... 6-125

6.13 Function Control .............................................................................................................. 6-127


6.13.1 Switch-in Recognition ...................................................................................................... 6-127
6.13.2 Recognition of the Circuit Breaker Status........................................................................ 6-128
6.13.3 Fault Detection Logic of the Entire Device ...................................................................... 6-131
6.13.4 Tripping Logic of the Entire Device.................................................................................. 6-132
6.13.5 Circuit Breaker Test......................................................................................................... 6-136
6.13.6 Setting the function parameters....................................................................................... 6-137
6.13.7 Setting Overview ............................................................................................................. 6-138
6.13.8 Information Overview....................................................................................................... 6-138

6.14 Commissioning Tools ...................................................................................................... 6-139


6.14.1 Function Description........................................................................................................ 6-139
6.14.2 Setting Parameters.......................................................................................................... 6-139
6.14.3 Setting Overview ............................................................................................................ 6-140

6.15 Ancillary Functions .......................................................................................................... 6-141


6.15.1 Processing of Messages ................................................................................................. 6-141
6.15.2 Measurement during Operation....................................................................................... 6-142
6.15.3 Fault Recording ............................................................................................................... 6-145
6.15.4 Setting the Function Parameters ..................................................................................... 6-146
6.15.5 Setting Overview ............................................................................................................ 6-147
6.15.6 Information Overview ...................................................................................................... 6-147

6.16 Processing of Commands ............................................................................................... 6-148


6.16.1 Types of Commands ....................................................................................................... 6-148
6.16.2 Steps in the Command Sequence................................................................................... 6-149
6.16.3 Interlocking ...................................................................................................................... 6-150
6.16.3.1 Interlocked/Non-Interlocked Switching ............................................................................ 6-150
6.16.4 Recording and Acknowledgement of Commands ........................................................... 6-153
6.16.5 Information Overview ...................................................................................................... 6-154

7 Control During Operation ................................................................................................................ 7-1

7.1 Read-out of Information....................................................................................................... 7-2


7.1.1 Messages ............................................................................................................................ 7-2
7.1.1.1 Output of Messages ............................................................................................................ 7-2
7.1.1.2 Event Log (Operating Messages)........................................................................................ 7-5
7.1.1.3 Trip Log (Fault Messages)................................................................................................... 7-6
7.1.1.4 Saving and Erasing the Messages ...................................................................................... 7-9
7.1.1.5 General Interrogation ........................................................................................................ 7-10
7.1.1.6 Spontaneous Messages .................................................................................................... 7-11

7SD610 Manual ix
C53000-G1176-C145-1
Table of Contents

7.1.2 Switching Statistics ............................................................................................................ 7-11


7.1.2.1 Viewing the Switching Statistics ........................................................................................ 7-12
7.1.2.2 Resetting and Setting the Switching Statistics................................................................... 7-13
7.1.3 Measured Values............................................................................................................... 7-14
7.1.3.1 Measured Values............................................................................................................... 7-14
7.1.3.2 Illustrating Measured Values ............................................................................................. 7-19
7.1.3.3 Setting and Retrieval of User Defined Set-points .............................................................. 7-23
7.1.3.4 Retrieval and Resetting of User Defined Pulse Metered Values (PMV) ............................ 7-24
7.1.4 Fault Records .................................................................................................................... 7-25
7.1.4.1 Viewing Fault Records....................................................................................................... 7-26
7.1.4.2 Saving the Fault Records .................................................................................................. 7-27

7.2 Control of Device Functions............................................................................................... 7-28


7.2.1 Read and Set Date and Time ............................................................................................ 7-28
7.2.2 Changeover of Setting Groups .......................................................................................... 7-33
7.2.3 Test Messages to the System (SCADA) Interface during Test Operation......................... 7-36
7.2.4 Changeover of Operating Mode ........................................................................................ 7-38

7.3 Circuit Breaker Test Function ............................................................................................ 7-41

7.4 Control of Switchgear ........................................................................................................ 7-45


7.4.1 Display Equipment Position and Control ........................................................................... 7-46
7.4.2 Manual Overwriting............................................................................................................ 7-49
7.4.3 Set Status .......................................................................................................................... 7-50
7.4.4 Interlocking ........................................................................................................................ 7-52
7.4.5 Tagging.............................................................................................................................. 7-53
7.4.6 Switching Authority ............................................................................................................ 7-54
7.4.7 Switching Mode ................................................................................................................. 7-55
7.4.8 Control Messages.............................................................................................................. 7-56
7.4.9 Other Commands .............................................................................................................. 7-56

8 Installation and Commissioning...................................................................................................... 8-1

8.1 Mounting and Connections .................................................................................................. 8-2


8.1.1 Installation ........................................................................................................................... 8-2
8.1.2 Termination variants ............................................................................................................ 8-5
8.1.3 Hardware Modifications ....................................................................................................... 8-9
8.1.3.1 General ................................................................................................................................ 8-9
8.1.3.2 Disassembling the Device ................................................................................................. 8-10
8.1.3.3 Jumper Settings on Printed Circuit Boards........................................................................ 8-12
8.1.3.4 Interface Modules .............................................................................................................. 8-17
8.1.3.5 To Reassemble the Device................................................................................................ 8-19

8.2 Checking the Connections................................................................................................. 8-20


8.2.1 Data Connections .............................................................................................................. 8-20
8.2.2 Checking the Differential Protection Communication ........................................................ 8-22
8.2.3 Checking Power Plant Connections .................................................................................. 8-22

x 7SD610 Manual
C53000-G1176-C145-1
Table of Contents

8.3 Commissioning .................................................................................................................. 8-25


8.3.1 Testing mode and transmission blocking .......................................................................... 8-26
8.3.2 Checking the System (SCADA) Interface.......................................................................... 8-26
8.3.3 Checking the Binary Inputs and Outputs ........................................................................... 8-28
8.3.4 Checking for Breaker Failure Protection............................................................................ 8-30
8.3.5 Checking the Communication Topology............................................................................ 8-32
8.3.6 Checking the Instrument Transformer Connections of One Line End ............................... 8-37
8.3.7 Checking the Instrument Transformer Connections of Both Line Ends............................. 8-38
8.3.8 Remote Tripping, Remote Signalling etc. .......................................................................... 8-46
8.3.9 Testing User Defined Functions ........................................................................................ 8-47
8.3.10 Trip and Close Test with the Circuit Breaker ..................................................................... 8-47
8.3.11 Stability Check and Triggering Oscillographic Recordings................................................ 8-47

8.4 Final Preparation of the Device ......................................................................................... 8-49

9 Maintenance and Fault Tracing ....................................................................................................... 9-1

9.1 General................................................................................................................................ 9-2

9.2 Routine Checks ................................................................................................................... 9-3

9.3 Maintenance ........................................................................................................................ 9-4


9.3.1 Replacing the Buffer Battery................................................................................................ 9-4
9.3.2 Replacing Interface Modules ............................................................................................... 9-6

9.4 Fault Tracing ....................................................................................................................... 9-7

9.5 Corrective Action/Repairs ................................................................................................... 9-9


9.5.1 Software Procedures ........................................................................................................... 9-9
9.5.2 Hardware Procedures.......................................................................................................... 9-9

9.6 Return................................................................................................................................ 9-13

10 Technical Data ................................................................................................................................ 10-1

10.1 General Device Data ......................................................................................................... 10-2


10.1.1 Analog Inputs and Outputs ................................................................................................ 10-2
10.1.2 Power Supply .................................................................................................................... 10-2
10.1.3 Binary Inputs and Outputs ................................................................................................. 10-3
10.1.4 Communications Interfaces ............................................................................................... 10-4
10.1.5 Electrical Tests .................................................................................................................. 10-6
10.1.6 Mechanical Stress Tests ................................................................................................... 10-7
10.1.7 Climatic Stress Tests......................................................................................................... 10-8
10.1.8 Service Conditions............................................................................................................. 10-9
10.1.9 Construction ...................................................................................................................... 10-9

10.2 Differential Protection ...................................................................................................... 10-10

7SD610 Manual xi
C53000-G1176-C145-1
Table of Contents

10.3 Intertripping, External Direct Local and Remote Tripping ................................................ 10-12

10.4 Direct Remote Trip or Transmission of Binary Information (optional).............................. 10-12

10.5 Protection Data Interface and Differential Protection Topology....................................... 10-13

10.6 Time Overcurrent Protection............................................................................................ 10-14

10.7 High-Current Switch-on-to-Fault Protection..................................................................... 10-19

10.8 Automatic Reclosure Function (optional)......................................................................... 10-19

10.9 Circuit Breaker Failure Protection (optional).................................................................... 10-20

10.10 Thermal Overload Protection........................................................................................... 10-21

10.11 Monitoring Functions ....................................................................................................... 10-23

10.12 Supplementary Functions ................................................................................................ 10-24

10.13 Dimensions ...................................................................................................................... 10-26

A Appendix........................................................................................................................................... A-1

A.1 Ordering Information and Accessories ...............................................................................A-2


A.1.1 Accessories .........................................................................................................................A-4

A.2 General Diagrams................................................................................................................A-6


A.2.1 Panel Flush Mounting or Cubicle Mounting .........................................................................A-6
A.2.2 Panel Surface Mounting ......................................................................................................A-7

A.3 Connection Examples..........................................................................................................A-8

A.4 Preset Configurations ........................................................................................................A-10

A.5 Protocol Dependent Functions ..........................................................................................A-12

A.6 List of Settings ...................................................................................................................A-13

A.7 List of Information .............................................................................................................A-24

Index.............................................................................................................................................Index-i

xii 7SD610 Manual


C53000-G1176-C145-1
Introduction 1
The SIPROTEC® 4 devices 7SD610 are introduced in this chapter. An overview of the
devices is presented in their application, characteristics, and scope of functions.

1.1 Overall Operation 1-2


1.2 Applications 1-5
1.3 Features 1-7
1.4 Scope of Functions 1-8

7SD610 Manual 1-1


C53000-G1176-C145-1
Introduction

1.1 Overall Operation

The numerical differential protection SIPROTEC® 7SD610 is equipped with a powerful


32 Bit microprocessor. This provides fully numerical processing of all functions in the
device, from the acquisition of the measured values up to the output of commands to
the circuit breakers as well as the exchange of measured data with the other end of
the protected area. Figure 1-1 shows the basic structure of the device.

Analogue Inputs The measuring inputs “MI” transform the currents and voltages derived from the instru-
ment transformers and match them to the internal signal levels for processing in the
device. The device has 4 current and 4 voltage inputs. Three current inputs are pro-

MI IA AD µC OA
IL1 ∩ ERROR

RUN
IL2

IL3 Output Relays


user-
programmable
I4

UL1 LEDs
on the front
panel, user-
UL2 programmable

UL3
Display on
µC the Front Panel
U4 #
Front Serial Oper- to
ating Interface PC
7 8 9
Operator Time radio
4 5 6
control panel Synchronization clock
1 2 3
(6& (17(5 . 0 +/-
Rear Serial PC/
Service Interface modem
Binary inputs, programmable

Serial System to
Interface SCADA
PS
Protection Data remote
Uaux Power supply
Interface 1 end

Figure 1-1 Hardware structure of the numerical device 7SD610

1-2 7SD610 Manual


C53000-G1176-C145-1
Overall Operation

vided for measurement of the phase currents, a further measuring input (I4) may be
used for the earth current (current transformer starpoint or a separate earth current
transformer). A voltage measuring input is provided for each phase–earth voltage. In
principle, the differential protection does not require measured voltages. However,
voltages that allow to measure voltages and powers and voltages that enable the user
to measure the line voltage also for automatic reclosure can be switched to the device.
A further voltage input (U4) may optionally be used to measure the displacement volt-
age (e–n–voltage). The analogue signals are then routed to the input amplifier group
“IA”.
The input amplifier group “IA” ensures that there is high impedance termination for the
measured signals and contains filters which are optimized in terms of band-width and
speed with regard to the signal processing.
The analogue/digital converter group “AD” has a multiplexer, analogue/digital convert-
ers and memory modules for the data transfer to the microcomputer “µC”.

Microcomputer Apart from processing the measured values, the microcomputer system also executes
System the actual protection and control functions. In particular, the following are included:
− Filtering and conditioning of the measured signals,
− Continuous supervision of the measured signals,
− Supervision of pickup conditions of each protection function,
− Formation of the local differential protection values (phasor analysis and charge
computation) and creation of the transmission protocol,
− Decoding of the received transmission protocol, synchronism of differential protec-
tion values and summing up of the differential currents and charges,
− Monitoring of the communication with the device of the opposite end,
− Interrogation of threshold values and time sequences,
− Processing of signals for the logic functions,
− Reaching trip and close command decisions,
− Storage of fault messages, fault annunciations as well as fault recording data for
system fault analysis,
− Operating system and related function management such as e.g. data storage, real
time clock, communication, interfaces etc.,
The information is provided via output amplifier “OA”.

Binary Inputs and The microcomputer system obtains external information through the binary inputs
Outputs such as remote resetting or blocking commands for protective elements. The “µC” is-
sues information to external equipment via the output contacts. These outputs include,
in particular, trip commands to the circuit breakers and signals for remote annunciation
of important event and conditions.

Front Elements Light-emitting diodes (LEDs) and a display screen (LCD) on the front panel provide
information such as targets, measured values, messages related to events or faults,
status, and functional status of the 7SD610.

7SD610 Manual 1-3


C53000-G1176-C145-1
Introduction

Integrated control and numeric keys in conjunction with the LCD facilitate local inter-
action with the 7SD610. All information of the device can be accessed using the inte-
grated control and numeric keys. The information includes protective and control set-
tings, operating and fault messages, and measured values (see also Chapter 7). The
settings can be modified as are discussed in Chapter 6.
If the device incorporates switchgear control functions, the control of circuit breakers
and other equipment is possible from the 7SD610 front panel.

Serial Interfaces A serial operating interface on the front panel is provided for local communications
with the 7SD610 through a personal computer. Convenient operation of all functions
of the device is possible using the SIPROTEC® 4 operating program DIGSI® 4.
A separate serial service interface is provided for remote communications via a mo-
dem, or local communications via a substation master computer that is permanently
connected to the 7SD610. DIGSI® 4 is required.
All 7SD610 data can be transferred to a central master or main control system through
the serial system (SCADA) interface. Various protocols and physical arrangements
are available for this interface to suit the particular application.

Another interface is Via additional interface modules further communication protocols may be created.
provided for the
The operating and service interface allows the communication from one PC with both
time synchroniza-
devices at the line ends during commissioning, checking and also during operation of
tion of the internal
the device, using a standard browser. There is a range of PC-tools supporting this
clock via external
function (e.g. “IBS-tool”) which have been optimized with regard to the differential pro-
synchronization
tection system.
sources.

Protection Data The protection data interfaces are a particular case. Via these interfaces the meas-
Interface ured value data of each end of the protected object is transmitted to the other end; dur-
ing this procedure measured values from the other end may also be added. Further
information such as closing the local circuit breaker, pickup of the inrush stabilization
as well as other external trip commands or binary information can be transmitted to
other end via the protection data interfaces.

Power Supply The 7SD610 can be supplied with any of the common power supply voltages. Tran-
sient dips of the supply voltage which may occur during short-circuit in the power sup-
ply system, are bridged by a capacitor (see Technical Data, Sub-section 10.1.2).

1-4 7SD610 Manual


C53000-G1176-C145-1
Applications

1.2 Applications

The numerical Differential Protection SIPROTEC® 7SD610 functions as a selective


short-circuit protection for overhead lines and cables with single- and multi-ended in-
feeds in radial, ring or any type of meshed systems of any transmission level. Dealing
with the system star-point is irrelevant, as measuring data are compared separately
for each phase.
High sensitivity and the inrush current stabilization allow for the application of the
7SD610 even when there is a power transformer within the protected range whose
star point(s) might also be isolated, earthed or provided with a Petersen coil (option).
A major advantage of the differential protection function is the instantaneous tripping
in the event of a short circuit at any point in the entire protected zone. The current
transformers limit the protected zone at the ends towards the line. This rigid limit is the
reason why the differential protection scheme shows such an ideal selectivity.
The differential protection system requires a 7SD610 device as well as a set of current
transformers at either end of the protected zone. Voltage transformers are not re-
quired, they can, however, be connected for the purpose of detecting and indicating
measured values (voltages, power, power factor).
The devices located at the ends of the protected zone exchange measuring informa-
tion via protection data interfaces using dedicated communication links (usually fibre
optic cables) or a communication network. Two type 7SD610 devices can be used for
an object with two ends to be protected: cables, overhead line or both, with or without
unit-connected transformer (option).
A fault-free data transfer being the prerequisite for the proper operation of the protec-
tive system, it is continuously monitored internally.

Protective Recognition of short circuits in the protection zone — even of weak-current or high-
Functions resistive shorting — is the basic function of the device. Also complex multiphase faults
are precisely detected, as the measured values are evaluated phase segregated. The
protection system is stabilized against inrush currents of power transformers. When
switching onto a fault on the entire line, an undelayed trip signal can be emitted.
In the event of a communication failure, the devices can automatically be switched to
emergency operation using an integrated overcurrent time protection until communi-
cation is healthy again. This overcurrent time protection has three definite-time over-
current stages and one inverse-time (IDMT) stage; a series of characteristics accord-
ing to various standards is available for the inverse-time stage. Alternatively, the over-
current time protection can be used as a back-up overcurrent time protection, i.e. it op-
erates independent of and parallel to the differential protection at either end.
The communication link can be used for transmitting further information. Apart from
measured values, binary commands or other information can be transmitted (option).
Depending on the version ordered, the short-circuit protection may also trip single-
pole. It may work in co-operation with an integrated automatic reclosure (available as
an option) with which single-pole, three-pole or single- and three-pole rapid automatic
reclosure as well as multi-shot automatic reclosure are possible on overhead lines.
Apart from the short-circuit protection functions mentioned, a thermal overload protec-
tion has been integrated which protects in particular cables and power transformers
from undue heating through overload. An optional circuit breaker failure protection

7SD610 Manual 1-5


C53000-G1176-C145-1
Introduction

provides rapid back-up fault clearance instruction to the adjacent circuit breakers in
case the local breaker fails to respond.

Messages and A series of operating messages provides information about conditions in the power
Measured Values; system and the 7SD610 itself. Measurement quantities and values that are calculated
Storage of Data for can be displayed locally and communicated via the serial interfaces.
Fault Recordings
Messages of the 7SD610 can be indicated by a number of programmable LEDs on the
front panel, externally processed through programmable output contacts, and commu-
nicated via the serial interfaces (see “Communication” below). With the help of the
CFC graphic tool (Continous Function Chart), user-defined annunciations and logical
combinations of internal or external signals can also be generated.
During a system fault important events and status changes are saved in fault event
records. The instantaneous quantities of the fault values are also recorded in the de-
vices themselves, synchronized in the devices and are then available for fault analy-
sis.

Communication Serial interfaces are available for communications with PCs, RTUs and SCADA sys-
tems.
A 9-pin D-subminiature female connector on the front panel is used for local commu-
nications with a personal computer. DIGSI® 4 software is required to communicate via
this port. Using the DIGSI® 4 software, settings and configuration can be made to the
relay, Real-time operating quantities can be viewed, Waveform capture and Event Log
records can be displayed, and controls can be issued.
A DIGSI® 4 service interface port, a system (SCADA) port and a time-sync port (IRIG-
B or DCF77) are optionally available on the rear of the device.
A rear service interface can be supplied as RS-232, RS-485, or multimode fibre optics
type ST. DIGSI® 4 software is required to communicate via this port.
A rear system interface can be supplied as RS-232, RS-485, or multimode fibre optics
type ST for communications between the 7SD610 and a PCs, RTUs or SCADA sys-
tems Standard Protocols, IEC 60870-5-103 are available via the system port. Integra-
tion of the devices into the automation systems SINAUT® LSA and SICAM® also take
place with this profile.
Alternatively, the device can be interrogated remotely or locally by means of a stand-
ard browser.
A further port provides the communication between the devices at the ends of the pro-
tected object. This protection data interface has been mentioned above with the “Pro-
tective Functions”.

1-6 7SD610 Manual


C53000-G1176-C145-1
Features

1.3 Features

• Powerful 32-bit microprocessor system.


• Complete digital processing of measured values and control, from the sampling of
the analogue input values, the processing and organization of the communication
between devices up to the closing and tripping commands to the circuit breakers.
• Complete galvanic and reliable separation between the internal processing circuits
of the 7SD610 and the external measurement, control, and DC supply circuits be-
cause of the design of the analogue input transducers, binary inputs and outputs,
and the DC/DC or AC/DC converters.
• Differential protection system with 2 ends with digital protection data transmission.
• Permanent supervision of the protection data transmission concerning disturbance,
failure, and transfer time deviation in the transmission network, with automatic
transfer time correction.
• Independent of the method of system starpoint earthing.
• Suited for transformers in the protected area (optional).
• Detection of high-resistant current-weak faults due to high sensitivity.
• Additional functions can be ordered according to requirements.
• Continuous calculation and display of measured quantities on the front of the de-
vice. Indication of measured quantities of the remote line end.
• Integrated help tools for operation and commissioning can be visualized by means
of a standard browser.
• Simple device operation using the integrated operator panel or by means of a con-
nected personal computer running DIGSI® 4.
• Storage of operational data, fault data, and oscillographic fault records with SER in-
formation to be used for analysis and troubleshooting.
• Communication with central control and data storage equipment via serial interfac-
es through the choice of data cable, modem, or optical fibres, as an option.
• Continuous monitoring of the measurement quantities, as well as self-diagnostics
covering the hardware and software.

7SD610 Manual 1-7


C53000-G1176-C145-1
Introduction

1.4 Scope of Functions

The numerical differential protection relay SIPROTEC® 7SD610 has the following
functions:

Differential Protec- • protection for all types of short-circuits in systems with any starpoint conditioning;
tion
• reliable distinction between load and short-circuit conditions, also on high-resistant,
current-weak faults;
• high sensitivity during of a weak load condition, extreme stability against load jumps
and power swings;
• due to phase segregated measurement the pickup sensitivity is independent of the
type of fault;
• insensitive measurement against in-rush and charge currents — also for transform-
ers in the protected area — and against higher-frequency switching transients;
• high stability also for different current transformer saturation;
• adaptive stabilization that is automatically derived from the measured values and
the configured current transformer data;
• low dependence on frequency due to frequency tracking;
• communication between devices via dedicated communication connections (in
general optical fibre) or a communication system;
• communication possible via ISDN-networks or two-wire telephone connections (up
to approx 8 km or 4.8 miles);
• fast phase segregated tripping also on weak or zero infeed ends;
• steady monitoring of the communication ways and the signal propagation delay with
automatic re-adjustment;
• phase segregated tripping (in conjunction with single-pole or single- and three-pole
auto-reclosure) is possible (order option).

External Direct and • tripping of the local end by an external device via binary input;
Remote Tripping
• tripping of the remote end by internal protection functions or an external device via
binary input.

Transmission of • transmission of measured values from both ends of the protected object;
Information
• transmission of up to 4 fast commands or binary signals to the remote end (order
option).

Time Delayed Over- • selectable as emergency function for communication failure or as back-up function
current Protection or as both;
• up to a maximum of three definite time stages (DT) and one inverse time stage
(IDMT), each for phase currents and earth current;
• for IDMT protection a selection from various characteristics based on several stand-
ards is possible;

1-8 7SD610 Manual


C53000-G1176-C145-1
Scope of Functions

• blocking options e.g. for reverse interlocking with any stage;


• non-delayed tripping with any stage when switching on to a fault is possible.

High-Speed Switch- • fast tripping for all faults on total line length;
onto-Fault Protec-
• selectable for manual closure or following each closure of the circuit breaker;
tion
• with integrated line energization detection.

Automatic • for reclosure after single-pole, three-pole or single and three-pole tripping;
Reclosure
• single or multiple shot reclosure (up to 8 reclosure attempts);
(optional)
• with separate action times for every reclosure attempt, optionally without action
times;
• with separate dead times after single-pole and three-pole tripping, separate for the
first four reclosure attempts;
• with the option of an adaptive dead time: in this case only one device controls the
automatic reclosure cycles while at the other end the automatic reclosure solely de-
pends on the one controlling device; the following criteria may apply: voltage meas-
urement and/or close command transmission (“Remote close”);
• automatic reclosure controlled optionally by protection start with separate dead
times after single, two and three-pole starting.

Circuit Breaker • with independent current detectors for monitoring of current flow through each indi-
Failure Protection vidual circuit breaker pole;
(optional)
• with independent delay timers for single-pole trip and three-pole trip;
• initiation by each of the internal trip functions;
• initiation by external trip functions possible via binary inputs;
• single-stage or two-stage delay;
• short reset and overshoot times.

Thermal Overload • provides thermal replica of the current heat losses of the protected object;
Protection
• true r.m.s. measurement of all three conductor currents;
• adjustable thermal and current-dependent warning stages.

User Defined Logic • freely programmable linkage between internal and external signals for the imple-
Functions mentation of user defined logic functions;
• all common logic functions;
• time delays and measured value set point interrogation.

Commissioning; • indication of the local and remote measured values, amplitudes and phase relation;
Operation
• indication of the calculated differential and restraint currents,
• indication of the characteristic values of the communication connection, as transfer
delay times and availability.

7SD610 Manual 1-9


C53000-G1176-C145-1
Introduction

Monitoring • monitoring of the internal measuring circuits, the auxiliary voltage supply, as well as
Functions the hard- and software, resulting in increased reliability;
• monitoring of the current and voltage transformer secondary circuits by means of
summation and symmetry checks;
• monitoring of communication with a statistic showing the availability of transmission
telegrams;
• check of the consistency of protection settings at both line ends: no processor sys-
tem start-up with inconsistent settings which could lead to a malfunction of the dif-
ferential protection system;
• trip circuit supervision is possible;
• check of local and remote measured values and comparison of both;
• broken wire supervision for the secondary CT circuits with fast phase segregated
blocking of the differential protection system in order to avoid malfunction.

Further Functions • battery buffered real time clock, which may be sychronized via a synchronization
signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface;
• automatic time synchronization between the devices at the ends of the protected
object via the protection data transmission;
• fault event memory for the last 8 network faults (faults in the power system), with
real time stamps (ms-resolution);
• fault recording memory and data transfer for analogue and user configurable binary
signal traces with a maximum time range of 15 s, synchronized between the devic-
es of the differential protection system;
• switching statistics: counter with the trip commands issued by the device, as well as
record of the short-circuit current and accumulation of the interrupted short-circuit
currents;
• commissioning aids such as connection and direction checks as well as interface
check and circuit breaker test functions;
• the “IBS-tool” (installed on a PC or a laptop) widely supports the testing and com-
missioning procedure: the communication topology of the differential protection and
communication system, phasor diagrams of all currents and (if applicable) voltages
at both ends of the differential protection system are displayed as a graph.

1-10 7SD610 Manual


C53000-G1176-C145-1
Hardware and Connections 2
This chapter describes the construction and connection of the 7SD610. The different
housing versions and available termination techniques are described.
The recommended and permitted data for the wiring is stated and suitable accessories
and tools are given.

2.1 Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting 2-2
2.2 Version of 7SD610 for Panel Surface Mounting 2-15

7SD610 Manual 2-1


C53000-G1176-C145-1
Hardware and Connections

2.1 Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

The numerical differential protection SIPROTEC® 7SD610 for panel and cubicle flush
mounting is enclosed in a 7XP20 housing, size 1/3 (of 19 inch). It can be used for rack
mounting either.
Each device version offers different ways of connection.

2.1.1 Housing

The housing consists of a rectangular tube with a rear plate specific to the device ver-
sion and a front cover. Guide rail mats are mounted at the top and bottom on the inside
of the tube, to guide the modules during insertion. The connection between the mod-
ules and to the front cover is by means of flat ribbon cables and the corresponding plug
connectors. The rear plate screwed to the tube contains the required connectors for
the external connections to the device.
The front cover can be detached after removal of the covering caps located on the 4
corners of the front cover and the 4 screws that are then revealed. The front cover has
a membrane keypad containing the control and indication elements required for the
user interface with the device. All terminations to the control and indication elements
are combined by a converter module on the front cover, and routed to the processor
module (CPU) via a plug connector.
The name plate containing the principal data of the device, such as auxiliary supply
voltage, the rated test voltage and the ordering code (MLFB) is located on the external
top of the housing and on the inside of the front cover.
The mechanical dimension drawings can be found in Section 10.13.

Front View
11) 11)
SIEMENS SIPROTEC
10) RUN ERROR 7SD610

0$,10(18
$QQXQFLDWLRQ
1)
0HDVXUHPHQW
2)
MENU
3)
9)

8) 4)
LED ESC ENTER

Meldungen F1 7 8 9

7) Messwerte F2 4 5 6
5)
Störfall-
meldung F3 1 2 3

F4 0 +/-
6)

11) 11)
Figure 2-1 Front view of a 7SD610 for panel flush mounting or cubicle mounting

2-2 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

Referring to the operating and display elements in Figure 2-1:


1. Display (LCD)
The LCD shows process and device information as text in various lists. Commonly
displayed information includes measured values, counter values, binary informa-
tion regarding the condition of circuit breakers, status of the device, protection in-
formation, general reports, and alarms.
2. Navigation keys
These keys serve for navigation through operating menus.
3. MENU key
This key activates the main menu.
4. ESC and ENTER keys
These keys serve to escape from specific menues or execute changes (such as
setting changes).
5. Numerical keys
These keys serve for entry of numerical values, such as limit value settings.
6. Function keys
Four function keys allow the quick and simple execution of frequently used ac-
tions. Typical applications include, for example, jumping to a particular position in
the menu tree such as the fault data in the Trip Log or the measured values. The
function keys are programmable, and may be used to execute control functions
such as closing or tripping circuit breakers. Next to the keypad, a labelling strip is
provided on which the user-specified key functions may be written.
7. 9-pin female D-subminiature connector
This serial interface is for the connection of a local PC running DIGSI® 4.
8. LED key
This key has the dual purpose of resetting latched LEDs and the latched contacts
of output relays, as well as testing of the LEDs.
9. Light emitting diodes (LEDs)
The function of these indicators can be programmed. There is a vast selection of
signals from which to choose. Some examples are device status, process or con-
trol information, and binary input or output status. Next to the LEDs on the front
cover, a labelling strip is provided on which the user-specified LED functions may
be written.
10. Operating condition indicators
The two LEDs “RUN” (green) and “ERROR” (red) indicate the operating condition
of the device.
11. Covering caps for the screws that secure the front cover.

7SD610 Manual 2-3


C53000-G1176-C145-1
Hardware and Connections

Rear View Figure 2-2 is a simplified view of the rear panel of the version of the device with screw-
type terminals.

1 UH +
2 UH -
3 3
4 4
5 5
6 6
7 F 7
8 8
R 9 9
10 10
11 11
12 12
13
14
15
16
17
18
Ch2

1
D C
2
3
Ch1

Q 4
5
RS232 RS485

6
RS232-LWL

7 B A
8
P-Slave
AME

Figure 2-2 Rear view of a 7SD610, (terminal arrangement example only)

2-4 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

2.1.2 Screw Terminal Connections

The following must be distinguished in the case of connection via screw terminals:
terminal plugs for voltage connections and
terminal plugs for current connections.
The terminal screws have a slot head for tightening or loosening with a flat screw driv-
er, sized 6 x 1 mm.

Terminal Blocks for The voltage connection terminal modules are available in 2 variants (Figure 2-3).
Voltage
Connections

2
1
4
3
6
5
8 2
7 1
10 4
9 3
12 6
11 5
14 8
13 7
16 10
15 9
18 12
17 11

18 terminal 12 terminal
Figure 2-3 Connection plug module with screw terminals for voltage connections — rear
view

Figure 2-4 shows an example of the allocation of an individual screw terminals to their
terminal numbers.

2 connection terminal 1
connection terminal 2 1

Figure 2-4 Allocation of screw terminal to terminal number — example

Terminal Block for There is one version of a terminal block for current connections to a 7SD610. The ter-
Current minal block is illustrated in Figure 2-5.
Connections

7SD610 Manual 2-5


C53000-G1176-C145-1
Hardware and Connections

2
1

4
3

6
5

8
7

8 terminal
Figure 2-5 Terminal block of screw terminals for current connections — rear view

The relation between the terminals and their terminal numbers is the same for the cur-
rent terminals as shown in Figure 2-4.
The available poles are arranged into pole pairs, each containing two poles. In this
manner, the two neighbouring terminals form one pair. Accordingly the current termi-
nal module with 8 poles contains 4 pairs.
In combination with the plug connection on the module side, these terminal pairs have
an integrated short-circuiting function which short-circuits the two neighbouring cur-
rent passages when the module is withdrawn. If the current transformer secondary cir-
cuits should become open circuited, large voltages can arise, which may endanger op-
erating personnel and the insulation of the CTs.
When the module is inserted, the current paths have a low impedance termination via
the measuring inputs on the module.
During insertion of the module, the short-circuit of the current path is automatically re-
moved. The interruption of the short-circuit only occurs once a reliable contact to the
plug connector on the module is established. This does not reduce the care that must
be taken when working on the current transformer secondary circuits!
The short-circuiting contacts of the current terminals are located on the housing side,
inside the terminal module connector, while the operating pins are located on the mod-
ule side of the plug connector.

Connections to Ring-type and fork-type lugs may be used. To ensure that the insulation paths are
Voltage Terminals maintained, insulated lugs must be used. Alternatively, the crimping area must be in-
sulated with other methods, e.g. by covering with a shrink sleeve.
The following must be observed:
Connections with cable lugs: inner diameter of lugs, 4 mm;
maximum outer diameter of lugs, 10 mm;
conductor with cross-section of 1 mm2 to 2.6 mm2 (AWG 16 to 14).
Use copper wires only!
Cable lugs of series PIDG from Messrs. Tyco Electronics AMP are recommended, e.g.
Ring cable lug: PIDG PN 320565–0
Forc lug: PIDG PN 321233–0.
Direct cable connections: solid or stranded conductor with connector sleeve;
conductor with cross-section of 0.5 mm2 to 2.6 mm2 (AWG 20 to 14).

2-6 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

When using one single conductor, the conductor end must be inserted such that it will
be drawn into the contact cavity while tightening the screw.
Use copper wires only!
Wire strip length: solid conductor 9 to 10 mm (0.35 to 0.39 in).
Maximum tightening torque: 1.8 Nm (16 in-lb).

Connections to Ring-type and fork-type lugs may be used. To ensure that the insulation paths are
Current Terminals maintained, insulated lugs must be used. Alternatively, the crimping area must be in-
sulated with other methods, e.g. by covering with a shrink sleeve.
The following must be observed:
Connections with cable lugs: inner diameter of lugs, 5 mm;
maximum outer diameter of lugs, 12 mm;
conductor with cross-section of 2.6 mm2 to 6.6 mm2 (AWG 14 to 10).
Use copper wires only!
Cable lugs of series PIDG from Messrs. Tyco Electronics AMP are recommended, e.g.
Ring cable lug: PIDG PN 130171–0
Forc lug: PIDG PN 326865–0
Direct cable connections: solid or stranded conductor with connector sleeve;
conductor with cross-section of 2.6 mm2 to 3.3 mm2 (AWG 14 to 12).
When using one single conductor, the conductor end must be inserted such that it will
be drawn into the contact cavity while tightening the screw.
Use copper wires only!
Wire strip length: solid conductor 10 to 11 mm (0.39 to 0.43 in).
Maximum tightening torque: 2.7 Nm (24 in-lb).

Short-Circuit Links Short-circuit links are available for convenience in making terminal connections.
The short-circuit links can connect two neighbouring terminals located on the same
side of the terminal module. By connecting further links, neighbouring terminals can
be included in the short-circuit. On each terminal it is possible to connect two shot-
circuiting links, or one short-circuit link and one lug, or one individual conductor.
The links meet the safety requirements for protection against electric shock.
There are two types of links, one for voltage connections and one for current connec-
tions. The links are illustrated in Figure 2-6. Ordering information for the links is pro-
vided in Section A.1 in the Appendix.

Short-circuit links for Short-circuit links for


voltage connections current connections
Figure 2-6 Short-circuit links for voltage connections and current connections

7SD610 Manual 2-7


C53000-G1176-C145-1
Hardware and Connections

Covering Caps Terminal covering caps are available for the screw terminal modules, to increase the
protection of personnel against hazardous voltages (degree of protection against ac-
cess to dangerous parts) on the terminal modules. The degree of protection is in-
creased from the standard “back of the hand protection” (IP1x)“ to „finger protection
(IP2x)“.
The terminal covering caps provide an enclosure which securely covers all voltage
carrying components. They are simply snapped onto the terminal module. It must be
noted that all screws on the terminal module must be screws in before snapping the
cover on. The terminal covering cap can simply be removed with a screw driver 6x1.
There are two types of covering caps, as shown in Figure 2-7. Ordering information is
provided in Section A.1 in the Appendix.
>PCGF<
:AMP

>PCGF<
:AMP
C73334-A1-C31-1

C73334-A1-C32-1
SIEMENS

SIEMENS

Covering cap for Covering cap for


18 terminal voltage 12 terminal voltage
connection terminal block or 8 Terminal Current
connection terminal block

Figure 2-7 Covering caps for terminal blocks with screw terminals

2-8 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

2.1.3 Connections to Plug-In Terminals

Plug-in terminals are only available for voltage connections. Current connections are
made with screw terminals on all 7SD610.

Terminal Blocks for There are two versions of plug-in terminal blocks. They are shown in Figure 2-8.
Voltage
Connections
c b a
1

4
5

6
c b a
7 1

8 2

9 3

10 4

11 5

12 6

13 7

14 8

15 9

16 10

17 11

18 12
a b c a b c

18 terminal 12 terminal

Figure 2-8 Terminal blocks of plug-in terminals for voltage connections — rear view

The system of numbers and letters used to designate the plug-in terminals is illustrat-
ed in Figure 2-9.

c b a
Plug-in terminal 1
1

2
Plug-in terminal 2

12
a b c

Figure 2-9 Correlation between plug-in terminals and connection numbers/letters

Each plug-in terminal forms a complete set of connections that consists of three pins
arranged as follows:
Pin a: Signal connection
Pin b: Common connection
Pin c: Shielding connection
The signal pins are the only terminal pins that are directly connected to the internal
printed circuit boards of the 7SD610. Depending on the version of the terminal block,
18 or 12 signal connections are provided. Refer to Figure 2-10.

7SD610 Manual 2-9


C53000-G1176-C145-1
Hardware and Connections

There are two isolated groups of common pins. Within a group the pins are inter-con-
nected as shown in Figure 2-10. The common pins “b” are not connected to the boards
inside the 7SD610. Each common group can, for example, be used for signal multipli-
cation or as a common point for a signal (independent of the signals on the pin “a” ter-
minals). Depending on the version of the terminal block, 18 or 12 common connec-
tions are available.
Grouping of common connections within a terminal block is as follows:
12 terminal block: Group 1 Terminals 1 through 6
Group 2 Terminals 7 through 12
18 terminal block: Group 1 Terminals 1 through 9
Group 2 Terminals 10 through 18
All shielding pins are connected together as shown in Figure 2-10. The shielding pins
are also connected to the housing. Depending on the version of the terminal block, 18
or 12 shielding connections are provided.

12 terminal Signal connection 18 terminal


Common connection
Shielding connection
c b a 1 c b a 1
2 a b c 2 a b c
c b a 3 c b a 3
4 a b c Common connections, group 1 4 a b c
c b a 5 looped together c b a 5
6 a b c 6 a b c
c b a 7 c b a 7
8 a b c 8 a b c
c b a 9 c b a 9
10 a b c 10 a b c
c b a 11 c b a 11
12 a b c Common connections, group 2 12 a b c
looped together c b a 13
14 a b c
c b a 15
16 a b c
Shielding connections c b a 17
looped together 18 a b c

Figure 2-10 Schematic diagram of the plug-in terminal blocks

Connections to Connections to plug-in terminals are made with pin connectors.


Plug-In Terminals
There are two versions of pin connectors:
Version 1: 2-pin connector
Version 2: 3-pin connector

2-10 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

a
b a c b

Figure 2-11 2-pin connector and 3-pin connector

Ordering information for the pin connectors is provided in Section A.1 of the Appendix.
The design of the pin connectors is such that only correct connections can be made.
For example, the design of the 2-pin connector allows connection only to pins “a” and
“b”. An erroneous connection to pins “b” and “c” is excluded.
The pin connectors snap in to the plug-in terminals. The connectors can be removed
without tools.
Control wires are connected to contacts of the pin connectors. Wires with 0.5 mm2 to
2.5 mm2 diameter (AWG 20 to 14) can be accommodated.
Use only flexible copper control wire!
The following crimp connectors can be used:
Tin-plated version:
Diameter 0.5 mm2 to 1.0 mm2:
e.g. Bandware 4000 pieces type: 0–827039–1 from Messrs. Tyco Electronics AMP
Individual piece type: 0–827396–1 from Messrs. Tyco Electronics AMP
Diameter 1.0 mm2 to 2.5 mm2:
e.g. Bandware 4000 pieces type: 0–827040–1 from Messrs. Tyco Electronics AMP
Individual piece type: 0–827397–1 from Messrs. Tyco Electronics AMP
Connection of a conductor to a contact is performed using the following tools:
e.g. Hand crimping tool type: 0–734372–1 from Messrs. Tyco Electronics AMP
Stencil type: 1–734387–1 from Messrs. Tyco Electronics AMP
The use of individual pieces is recommended.
Gold-plated version (recommended):
Diameter 0.75 mm2 to 1.5 mm2:
e.g. Bandware 4000 pieces type: 0–163083–7 from Messrs. Tyco Electronics AMP
Individual piece type: 0–163084–2 from Messrs. Tyco Electronics AMP
Connection of a conductor to a contact is performed using the following tools:
e.g. Hand crimping tool type: 0–539635–1 from Messrs. Tyco Electronics AMP
Stencil type: 1–539668–2 from Messrs. Tyco Electronics AMP
The use of individual pieces is recommended.
After the wires are crimped, the contacts are pressed into the terminals of the connec-
tor until they snap into place.
Stress relief for individual pin connector must be provided with cable ties. Stress relief
must also be provided for the entire set of cables, e.g., cable ties.

7SD610 Manual 2-11


C53000-G1176-C145-1
Hardware and Connections

The following separation tool is needed to remove the contacts from the pin connec-
tors:
Type: 725840–1 from Messrs. Tyco Electronics AMP.
The separation tool contains a small tube that is subject to wear. The tube can be or-
dered separately:
Type: 725841–1 from Messrs. Tyco Electronics AMP.

2.1.4 Connections to Optical Communication Interfaces

Optical Interfaces The three available versions of optical communication interfaces are shown in Figure
ST–Connectors 2-12. The ports are supplied with caps to protect the optical components against dust
or other contaminants. The caps can be removed by turning them 90° to the left.
P-Master Ch2

AMO

UART
Ch1 P-Slave

Ch1 P-Slave

2 channel 1 channel 1 channel


Figure 2-12 Optical communication interfaces with protective caps

Connections to Optical connector type: ST–connector


Optical
Communication Fibre type: Multimode graded-index (“G”) optical fibre
Interfaces G50/125 µm,
G62.5/125 µm,
G100/140 µm
Wavelength: λ = 820 nm (approximately)
Allowable bending radius: For indoor cable rmin = 5 cm (2 in)
For outdoor cable rmin = 20 cm (8 in)

Laser class 1 (acc. EN 60825–1) is achieved with fibre type G50/125 µm and
G62.5/125 µm.

2-12 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Flush Mounting / Cubicle Mounting

Optical Interfaces The optical communication interfaces with FC-connectors and screw connections also
FC-Connectors provide caps to protect the optical components against dust or other contaminants.

Figure 2-13 Optical communication interfaces with caps

Connections to Optical connector type: FC–connector


Optical
Communication Fibre type: Monomode
Interfaces with 9/125 µm,
FC-Connectors Wavelength: λ = 1300 nm (approximately)
Allowable bending radius:For indoor cable rmin = 5 cm (2 in)
For outdoor cable rmin = 20 cm (8 in)

7SD610 Manual 2-13


C53000-G1176-C145-1
Hardware and Connections

2.1.5 Connections to Electrical Communication Interfaces

Electrical 9-pin D-subminiature female socket connectors are provided for all electrical commu-
Communication nication interfaces of the 7SD610. The connector is illustrated in Figure 2-14. The pin
Interfaces assignments are described in Sub-section 8.2.1.

RS232 RS485
5 1 6

RS232-LWL
9 6
9
6 9 5
1 5

P-Slave
Time synchronization

AME
Service interface (rear side)
(front side)
Serial interface
(rear side)
Figure 2-14 9 pin D-subminiature connector

Connections to Standard 9-pin D-subminiature plug connectors per MIL–C–24308 and DIN 41652
Serial can be used.
Communication
The necessary communication cables are dependent on the type of interface:
Interfaces
• RS232/EIA232: Five-wire, twisted and shielded, e.g. interface cable 7XV5100–4.
• RS485/EIA485: Three-wire, twisted and shielded.
• Profibus: Two-wire or four-wire, twisted and shielded:
Wire type A, DIN 19245, part 2 and EN 50170 vol. 2, twisted and shielded,
Wire Resistance: 135 Ω to 165 Ω (f > 100 kHz)
Capacitance: < 30 nF/km (48 nF/mile)
Circuit resistance: < 110 Ω/km (177 Ω/mile)
Conductor diameter: > 0.64 mm
Conductor cross-sectional area: > 0.34 mm2
e.g., SINEC L2 Industrial twisted pair installation wire (see catalog 1K 10 “SIMATIC
NET, Industrial Communications Networks”).
• Time synchronization: At least two-wire, shielded.

2-14 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Surface Mounting

2.2 Version of 7SD610 for Panel Surface Mounting

The numerical differential protection SIPROTEC® 7SD610 for surface mounting is en-
closed in a 7XP20 housing, 1/3 (of 19 inch). The device is fitted into a surface mounting
housing.

2.2.1 Housing

The housing consists of a rectangular tube with a rear plate which is specific to the
device version, and a front cover. Guide rail mats which aid the insertion of the mod-
ules are mounted on the inside of the rectangular tube. Connections between the
modules and from the modules to the front cover are established with flat ribbon ca-
bles and corresponding plug connectors.
The rectangular tube fitted into a surface mounting housing and secured with 4
screws, which are located behind covering caps at the four corners of the front cover.
The surface mounting housing contains the wiring from the back plate specific to the
device version to the screw terminal.
The front cover can be detached after removal of the covering caps located on the 4
corners of the front cover and the 4 screws that are then revealed. The front cover has
a membrane keypad containing the control and indication elements required for the
user interface with the device. All terminations to the control and indication elements
are combined by a converter module on the front cover, and routed to the processor
module (CPU) via a plug connector.
The name plate containing the principal data of the device, such as auxiliary supply
voltage, the rated test voltage and the ordering code (MLFB) is located on the external
top of the housing and on the inside of the front cover.
The mechanical dimension drawings are located in Section 10.13.

7SD610 Manual 2-15


C53000-G1176-C145-1
Hardware and Connections

Front View 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45

46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

11) 11)
SIEMENS SIPROTEC
10) RUN ERROR 7SD610

0$,10(18
$QQXQFLDWLRQ
1)
0HDVXUHPHQW

2)
MENU 3)
9)

8) LED ESC ENTER 4)


Annun-
ciations F1 7 8 9 5)
7) Measured
values
F2 4 5 6

Trip log F3 1 2 3

6) F4 0 +/-

11) 11)

1 2 3 4 5 6 7 8 9 L+ L- 12 13 14 15

17 18 19 20 21 22 23 24 25 26 27 28 29 30

Figure 2-15 Front view, 7SD610 for panel surface mounting, without optical connections

Referring to the operating and display elements in Figure 2-15:


1. Display (LCD)
The LCD shows process and device information as text in various lists. Commonly
displayed information includes measured values, counter values, binary informa-
tion regarding the condition of circuit breakers, status of the device, protection in-
formation, general reports, and alarms.
2. Navigation keys
These keys serve for navigation through operating menus.
3. MENU key
This key activates the main menu.
4. ESC and ENTER keys
These keys serve to escape from specific menus or execute changes (such as set-
ting changes).
5. Numerical keys
These keys serve for entry of numerical values, such as limit value settings.
6. Function keys
Four function keys allow the quick and simple execution of frequently used ac-
tions. Typical applications include, for example, jumping to a particular position in
the menu tree such as the fault data in the Trip Log or the measured values. The

2-16 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Surface Mounting

function keys are programmable, and may be used to execute control functions
such as closing or tripping circuit breakers. Next to the keypad, a labelling strip is
provided on which the user-specified key functions may be written.
7. 9-pin female D-subminiature connector
This serial interface is for the connection of a local PC running DIGSI® 4.
8. LED key
This key has the dual purpose of resetting latched LEDs and the latched contacts
of output relays, as well as testing of the LEDs.
9. Light emitting diodes (LEDs)
The function of these indicators can be programmed. There is a vast selection of
signals from which to choose. Some examples are device status, processing or
control information, and binary input or output status. Next to the LEDs on the front
panel, a labelling strip is provided on which the user-specified LED functions may
be written.
10. Operating condition indicators
The two LEDs “RUN” (green) and “ERROR” (red) indicate the operating condition
of the device.
11. Covering caps for the screws that secure the front panel.

2.2.2 Screw Terminal Connections

Terminal Blocks All connections to the device are by means of 60 two-tier screw terminals located at
the top and bottom of the surface mounting housing.
The plug connection module in the device for the current terminals automatically short-
circuits the current transformer circuits when the modules are withdrawn. This does
not reduce necessary care that must be taken when working on the current transform-
er secondary circuits.

Connections to Solid conductor or stranded wire with lugs can be used.


Terminals The following specifications must be observed:
Direct cable connections: solid or stranded conductor with connector sleeve
conductor with cross-section of 0.5 mm2 to 5 mm2 (AWG 20 to 10).
Use copper wires only!
Note: For the connection of the time synchronization: At least two-wire, shielded.
Wire strip length: solid conductor 7 mm to 8 mm (0.27 in to 0.31 in).
Maximum tightening torque: 15 in-lb (1.7 Nm).

7SD610 Manual 2-17


C53000-G1176-C145-1
Hardware and Connections

2.2.3 Connections to Optical Communication Interfaces

Optical communication interfaces are located in inclined housing. The inclined hous-
ings may be located at the top side (channels “D” and “E”) and/or at the bottom side
of the device (channel “B” and “C”), see Figure 2-16.
A table indicating the available channel designations “B” to “E” is printed onto the in-
clined housing.
Standardly the device is equipped with the housing of the top side (channel “D”). De-
pending on the version there may be a second inclined housing mounted to the bottom
side of the device (channel “B” and/or channel “C”). If it that is not the case, a cover
plate is mounted instead.

Housing for optical communication interfaces,


channel D and E

Housing for optical communication interfaces,


channel B and C
Figure 2-16 Side view of 7SD610, panel surface mounting, possible optical communication
interfaces

There are two versions of optical communications interfaces:


• ST–connectors and
• FC–connectors.

2-18 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Surface Mounting

Optical Interfaces Fibre-optic connections with ST–connectors are supplied with caps to protect the op-
(ST–Connector) tical components against dust or other contaminants. They can be removed by turning
them 90 ° to the left.
The ports are provided with 1 or 2 channels. A maximum of one fibre optic channel is
located in each inclined housing (channel “B” and/or channel “C”).
Fibre-optic connections that are not needed are replaced by plastic studs (see Figure
2-17).

Kanal C Kanal B
Kanal E Kanal D

plastic studs
Figure 2-17 Inclined housing with fibre optic connections (example: channel B fitted)

Connections to Optical connector type: ST–connector


Optical
Communication Fibre type: Multimode graded-index (“G”) optical fibre
Interfaces G50/125 µm,
(ST–Connector) G62.5/125 µm,
G100/140 µm
Wavelength: λ = 820 nm (approximately)
Allowable bending radius: For indoor cable rmin = 5 cm (2 in)
For outdoor cable rmin = 20 cm (8 in)
Laser class 1 (acc. EN 60825–1) is achieved with fibre type G50/125 µm and
G62.5/125 µm.

Optical Interfaces Fibre optic connections with FC–connectors are supplied with caps to protect the op-
(FC–Connector) tical components against dust or other contaminants. They can be removed from the
connectors.
There is only one version with 1 channel.
The fibre optic channel is located in an inclined housing (channel “D”). Fibre optic con-
nections that are not needed are replaced by plastic studs (see Figure 2-18).

7SD610 Manual 2-19


C53000-G1176-C145-1
Hardware and Connections

Kanal C Kanal B
Kanal E Kanal D

plastic studs
Figure 2-18 Inclined housing with fibre optic connections (channel D fitted)

Connections to Optical connector type: FC–connector


Optical
Communication Fibre type: Monomode
Interfaces 9/125 µm,
(FC–Connector) Wavelength: λ = 1300 nm (approximately)
Allowable bending radius: For indoor cable rmin = 5 cm (2 in)
For outdoor cablermin = 20 cm (8 in)

2.2.4 Connections to Electrical Communication Interfaces

Electrical 9-pin D-subminiature female socket connectors are provided for electrical communi-
Communication cation interfaces. The connectors are located in the inclined housing at the bottom
Interfaces side of the device (see Figure 2-19). The pin assignments are described in Sub-sec-
tion 8.2.1.
Fibre optic connections that are not needed are replaced by plastic studs.
The connections for the time synchronization interface are by means of the two-tier
screw terminals (see Sub-section A.2.2 in the Appendix).

2-20 7SD610 Manual


C53000-G1176-C145-1
Version of 7SD610 for Panel Surface Mounting

Kanal C Kanal B Kanal C Kanal B


Kanal E Kanal D Kanal E Kanal D

plastic studs

Figure 2-19 9-pin D-subminiature connector

Connections to Standard 9-pin D-subminiature plug connectors per MIL–C–24308 and DIN 41652
Serial can be used.
Communication
The necessary communication cables are dependent on the type of interface:
Interfaces
• RS232/EIA232: Five-wire, twisted and shielded, e.g. interface cable 7XV5100–4.
• RS485/EIA485: Three-wire, twisted and shielded.

7SD610 Manual 2-21


C53000-G1176-C145-1
Hardware and Connections

2-22 7SD610 Manual


C53000-G1176-C145-1
Getting Started 3
This chapter describes the initial inspections that should be carried out upon recept of
the SIPROTEC® 4 device 7SD610.
Unpacking and re-packing is explained.
Visual and electrical checks that are appropriate for initial inspection are discussed.
The electrical tests include navigating through the operating menus of the device us-
ing the operator control panel on the front of the device, and the operator control win-
dows in DIGSI® 4. For personnel inexperienced with the 7SD610, these checks also
provide a quick and simple method for understanding the operation of the control pan-
el and DIGSI® 4. The electrical tests can be done without measuring quantities being
applied.
Observations relevant to long-term storage of the device are noted.

3.1 Unpacking and Re-packing 3-2


3.2 Inspections upon Receipt 3-3
3.3 User Interface 3-4
Storage 3-12

7SD610 Manual 3-1


C53000-G1176-C145-1
Getting Started

3.1 Unpacking and Re-packing

The 7SD610 is packaged at the factory to meet the requirements of IEC 60255–21.
Unpacking and re-packing must be done with usual care, without using force, and with
appropriate tools. Visually check the device immediately upon arrival for correct me-
chanical condition.
Please observe also the brief reference booklet and all notes and hints that are en-
closed in the packaging.
The transport packaging can be reused in the same manner for further transport. Stor-
age packaging alone, for the individual devices, is not sufficient for transport. If alter-
native packaging is used, shock requirements according to IEC 60255–21–1 Class 2
and IEC 60255–21–2 Class 1 must be met.
The device should be in the final operating area for a minimum of two hours before the
power source is first applied. This time allows the device to attain temperature equilib-
rium, and dampness and condensation to be avoided.

3-2 7SD610 Manual


C53000-G1176-C145-1
Inspections upon Receipt

3.2 Inspections upon Receipt

3.2.1 Inspection of Features and Ratings

Ordering Number Verify that the 7SD610 has the expected features by checking the complete ordering
number with the ordering number codes given in Sub-section A.1 of the Appendix.
Also check that the required and expected accessories are included with the device.
The ordering number of the device is on the nameplate sticker attached to the top of
the housing. The nameplate also indicates the current, voltage, and power supply rat-
ings of the device. A verification that these ratings are the expected values is especial-
ly important. The jumpers for the control voltage of the binary inputs are set at the fac-
tory for a DC control voltage equal to the DC voltage rating of the power supply. The
jumpers can be changed if a different control voltage is to be used.

3.2.2 Electrical Check

Operating conditions that meet VDE 0100/5.73 and VDE 0105 Part 1/7.83, or national
and international standards, are to be observed.
Before applying power supply voltage or any measuring quantities for the first time, be
sure the device has been in the operating area for at least two hours. This time period
allows the device to attain temperature equilibrium, and prevents dampness and con-
densation from occurring.

Warning!
The following inspection steps are done in the presence of dangerous voltages. Only
appropriately qualified personnel familiar with and adhering to safety requirements
and precautionary measures shall perform these steps.

Power-Up For a first electrical inspection of the device it is sufficient to ensure safe grounding of
the housing and to apply the power supply voltage:
o Connect the ground of the device solidly to the ground of the location. The ground of
a 7SD610 designed for flush mounting is on the rear panel; the ground of a device de-
signed for surface mounting is on the terminal with the grounding symbol.
o Prepare the connections to the power supply. Verify that the power supply voltage has
the correct magnitude. Check polarity connections to the device inputs. Follow the ap-
propriate connection diagram in the Appendix, Section A.2.
o Close the protective switches to apply the power supply.
o The green “RUN” LED on the front panel must light after no more than 0.5 second, and
the red “ERROR” LED must go out after no more than 10 seconds.
o After no more than 15 seconds, the start-up messages must vanish from the display
(in which the complete ordering number, the version of firmware implemented, and the
factory number are shown), and the default display must appear. Depending on the
assignment of the LEDs, some indicators may light up during and after power-up.

7SD610 Manual 3-3


C53000-G1176-C145-1
Getting Started

3.3 User Interface

3.3.1 Operation Using the Operator Control Panel

Operator Control The device has a hierarchically structured operating tree, within which movements
Panel and actions are made using the , , , keys and the MENU, ENTER , CTRL , and ESC
keys on the front panel.
The brief discussions below illustrate the navigation techniques using the integrated
operations in the operator control panel. Some typical operations are covered. For
easier understanding, the accompanying figures show the entire contents of the men-
us, while only a limited number of lines can be seen in the display at any time.

Reading Ordering To view the complete ordering number of the device, the version of firmware imple-
Number/Version mented, and the serial number:
q When the device is ready for operation, first press the MENU key. The 0$,10(18 ap-
pears.
q Using the key, select the menu item 6HWWLQJV, and move to the device settings
using the key. The 6(77,1*6 menu appears, as shown in Figure 3-1.
q Using the key, select the menu item 6HWXS([WUDV and switch to the selection
6(783(;75$6 using the key. See Figure 3-2.

0$,10(18

$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²!
!6HWWLQJV²! 6(77,1*6
7HVW'LDJQRVH²! 
'HYLFH&RQILJ²!
0DVNLQJ ,2 ²!
36\VWHP'DWD²!
*URXS$²!
*URXS%²!
*URXS&²!
*URXS'²!
&KDQJH*URXS²!
2VF)DXOW5HF²!
!6HWXS([WUDV²!
'HYLFH²!
Figure 3-1 Main menu and sub-menu 6(77,1*6 — example

q Using the key, select the menu 0/)%9HUVLRQ and view the selection 0/)%
9(56,21 using the key.
The device-specific data appear in two or three lines. Press the key as necessary
to view all of the data:

3-4 7SD610 Manual


C53000-G1176-C145-1
User Interface

6(783(;75$6

'DWH7LPH²!
&ORFN6HWXS²!
6HULDO3RUWV²!
'HYLFH,'²!
!0/)%9HUVLRQ²! 0/)%9(56,21
&RQWUDVW²! 0/)%6'
+$
%)²1U

0/)%9(56,21
)LUPZDUH
%RRWV\VWHP

Figure 3-2 Display of device-specific data — example

Viewing Measured To view the measured values:


Values
q If the main menu is not shown, press the MENU key. The 0$,10(18 appears.
q Using the key, select the menu item 0HDVXUHPHQW, and move to the measure-
ment values using the key. The 0($685(0(17 sub-menu appears.
q Using the key, select the menu item 2SHUDWLRQVHF (operating measured
values, secondary), and switch to the 23(5$7,216(& sub-menu using the
key.
q Using the and keys, all operating measured values can be viewed.
Since no measured AC voltages or currents are present at this time, all operating
measured values show near zero. Deviations of the last digit are insignificant.

Viewing Operation- Reading the operational messages is described to serve as an additional example.
al Messages
q If the main menu is not shown, press the MENU key. The 0$,10(18 appears.
q Using the key, select the menu item $QQXQFLDWLRQ, and switch to the annun-
ciations using the key. The $1181&,$7,21 sub-menu appears.
q Using the key, select the menu item (YHQW/RJ, and move to the (9(17/2*
sub-menu using the key.
The last number in the upper right corner of the display indicates the number of oper-
ational messages stored in memory. The number before the slash indicates the mes-
sage presently being displayed. Upon entering the menu, the latest (newest) message
is shown. The date and time of the event are shown in the display line above the mes-
sage.
q Use the key to read other operational messages.
q Press the LED key; all LEDs should illuminate. Press thekey. The newest mes-
sage in the event log should be “5HVHW/('”, and the number of messages in
memory should increase by one (maximum of 200).
To return to the main menu, press the MENU key once, or repeatedly press the ESC key
or the key.

7SD610 Manual 3-5


C53000-G1176-C145-1
Getting Started

Setting the Display If the image in the integrated LCD does not have satisfactory contrast, adjustments
Contrast can be made. A stronger contrast serves, among other purposes, to improve the read-
ability of the image from an angle. With increasing numbers, the contrast is increased
and the picture gets darker. If the contrast is too weak or too strong, there is a risk that
the display will be unreadable and that no operation will be possible using the integrat-
ed operator control panel. Therefore, the preset contrast value should only be
changed in small steps (1 or 2 levels).
q When the device is ready for operation, first press the MENU key. The 0$,10(18 ap-
pears.
q Using the key, select the menu item 6HWWLQJV, and switch to the settings using
the key. The 6(77,1*6 sub-menu appears.
q Using the key, select the menu item 6HWXS([WUDV and switch to the selection
6(783(;75$6 using the key. See Figure 3-3.
q Using the key, select the sub-menu item &RQWUDVW.
q If a change of the contrast of the integrated LCD is desired, press the ENTER key. The
existing setting appears in a frame with a blinking cursor.
q Overwrite the present setting with the desired setting using the numerical keys. The
setting range is 11 to 22.
q Confirm the change with the ENTER key, or cancel the change with the ESC key.
Exit the sub-menu using the ESC key, or return to the main menu using the MENU key.

6(783(;75$6

'DWH7LPH²!
&ORFN6HWXS²!
6HULDO3RUWV²!
'HYLFH²,'²!
0/)%9HUVLRQ²!
!&RQWUDVW²! ENTER 6(783(;


0/)%9HQ²!
&RQWUDVW²!

Figure 3-3 Operating sub-menu for adjusting the display contrast

3-6 7SD610 Manual


C53000-G1176-C145-1
User Interface

3.3.2 Operation Using DIGSI® 4

DIGSI® 4 User DIGSI® 4 has the typical PC application Windows operating environment to guide the
Interface user. The software has a modern, intuitive, user-interface. Further details are found in
Section 4, as well as in the DIGSI® 4 handbook “Device Configuration”.
Some applications of DIGSI® 4 which are described below concern viewing the meas-
urement values, reading messages, and setting the time clock. The handling of the op-
erator control windows of DIGSI® 4 can be learned quickly by following the simple ex-
amples as described below. To perform the steps in the examples, first connect the
SIPROTEC® 4 device to the PC and match the DIGSI® 4 interface data with the equip-
ment. To accomplish this:
q Establish a physical connection between a serial interface of the PC and the oper-
ating serial interface of the device on the front panel.
q Open the DIGSI® 4 application in the PC.
q Generate a new project by clicking on )LOH → 1HZ in the DIGSI® 4–Manager menu
bar.

Figure 3-4 Dialogue box to open a new project in DIGSI® 4

q Enter a name for the new project in the 1DPH entry field (e.g. test 1) and close the
box with 2..
q Select )ROGHU by clicking on the item in the newly opened window. Then click in
the menu bar the item 'HYLFH and select the option ',*6,!'HYLFH 3OXJ 
3OD\ , as shown in Figure 3-5. The Plug & Play dialogue box opens, as shown in
Figure 3-6.

7SD610 Manual 3-7


C53000-G1176-C145-1
Getting Started

Figure 3-5 Window with selection of Plug and Play

q Enter the designation of the PC serial interface (COM 1,2, 3, or 4) and select in the
dialogue box under )UDPH the transfer format, to be used in making the connection.
q Click on 2.. DIGSI® 4 automatically determines the type of device present and
reads the settings needed for communication (transfer format, transfer speed)
through the interface.

Figure 3-6 Plug & Play dialogue box for communication between device and PC

A direct connection is then established (on-line), the data are exchanged between the
PC and the device, and the initial screen for DIGSI® 4 opens, as shown on Figure 3-7.
q By double clicking 2QOLQH in the navigation window (left window), the structure
opens (directory tree).
q By clicking on one of the menu items offered there, the associated contents become
visible in the right window.

3-8 7SD610 Manual


C53000-G1176-C145-1
User Interface

Figure 3-7 DIGSI® 4 — online initial screen — example

Viewing Measured As an example the procedure for viewing the measured values is described.
Values
q Double click on 0HDVXUHPHQW in the navigation window (left).
q Double click on the subdirectory 6HFRQGDU\9DOXHV in the navigation window.
q Click on 2SHUDWLRQDOYDOXHVVHFRQGDU\.
q The present date and time are shown in the data window (right), as illustrated in Fig-
ure 3-8.
q Double click on this entry in the data window.

Figure 3-8 DIGSI® 4 — Viewing the secondary operating measured values — example

A table of the secondary operating measured values appears, as shown in Figure 3-9.
Since no measured AC currents or voltages are present at this time, all operating
measured values are close to zero. Deviations of the last digit are insignificant. The
measured values are automatically updated.
In the same manner, other measured and counter values can be read out.

7SD610 Manual 3-9


C53000-G1176-C145-1
Getting Started

Figure 3-9 DIGSI® 4 — Table of secondary operating measured values – example

Viewing Operation- The read-out of operating messages is described to serve as an additional example.
al Messages
q Double click on $QQXQFLDWLRQ in the navigation window.
q Click on (YHQW/RJ in the function selection.
The present date and time are shown in the data window.
q Double click on this entry in the data window.
A table of the accumulated event messages is displayed. See Figure 3-10as an ex-
ample. The number designation for an event is provided with a description of the mes-
sage. The corresponding cause, value (ON or OFF), and date and time of the event
are given. The events are listed chronologically; the newest message is shown first.

Figure 3-10 DIGSI® 4 — Operational messages window — example

q Press the LED key on the device; all LEDs should light while the key is pressed.
q The message “Reset LED” appears as the newest message as soon as the window
is updated. The window can be updated by clicking on 9LHZ in the menu bar, and
then on 5HIUHVK. Pressing the F5 function key on the keyboard also updates the
window.
The operating messages can be saved in DIGSI® 4, and also deleted from the de-
vice’s memory as described in Sub-section 7.1.1.

3-10 7SD610 Manual


C53000-G1176-C145-1
User Interface

Setting Date and To enter the date and time:


Time
q Click on 'HYLFH in the menu bar. See Figure 3-11.
q Select 6HW&ORFN.

Figure 3-11 DIGSI® 4 — Selection of the option 6HW&ORFN

The dialog field 6HWFORFN GDWHLQGHYLFH opens. The field shows the present
date and the approximate present time according to the device. The day of the week
is automatically derived from the date and cannot be edited.
• Edit the input fields 'DWH and 7LPH. The format depends on your regional settings
of the PC. See Figure 3-12.
Date: mm/dd/yyyy or dd.mm.yyyyy
Time: hh.mm.ss

Click 2. to download the entered values to the device. The former values are
changed and the dialog field is closed.

Figure 3-12 DIGSI® 4 — Dialog Field: 6HWFORFN GDWHLQGHYLFH

7SD610 Manual 3-11


C53000-G1176-C145-1
Getting Started

Storage

If the device is to be stored, note:


SIPROTEC® 4 devices and associated assemblies should be stored in dry and clean
rooms, with a maximum temperature range of –25° C to +55° C (–12° F to 131° F).
See Sub-section 10.1.7 under Technical Data. To avoid premature aging of the elec-
trolyte capacitors in the power supply, a temperature range of +10° C to +35° C (50° F
to 95° F), is recommended for storage.
The relative humidity must not lead to condensation or ice buildup.
After extended storage, the power supply of the device should be energized, approx-
imately every two years, for one or two days to regenerate the electrolytic capacitors
in the power supply. This procedure should also be done prior to the device being put
in service. Under extreme climatic conditions (tropics), pre-warming is achieved at the
same time, and condensation is prevented.
After long storage, power should not be applied until the device has been in the oper-
ating area for a minimum of two hours. This time period allows the device to attain tem-
perature equilibrium, and prevents dampness and condensation from occurring.

In order to save the energy of the buffer battery inside the device the battery is
switched off automatically without auxiliary supply voltage after a time period of 12 to
24 hours.

3-12 7SD610 Manual


C53000-G1176-C145-1
SIPROTEC® 4 Devices 4
This chapter provides an overview of the family of SIPROTEC ® 4 devices and the in-
tegration of the devices into power plants and substation control systems. Principle
procedures are introduced for setting the devices, controlling primary equipment with
the devices, and performing general operations with the devices.
Please note the SIPROTEC® 4 family of devices is described in general in this chap-
ter, and the examples shown may differ in detail from a specific device. Also, depend-
ing on the type and version of a specific device, some of the functions discussed may
not be available.
Details about the extent of the functions of the devices, the individual settings, and the
representation structure of the system data are found in the following chapters and the
DIGSI® 4 instruction book.

4.1 General 4-2


4.2 Operator Control Facilities 4-5
4.3 Information Retrieval 4-8
4.4 Control 4-14
4.5 Manual Overwrite / Tagging 4-16
4.6 General about the Setting Procedures 4-17
4.7 Configuration of the Scope of Device Functions 4-20
4.8 Configuration of Inputs and Outputs (Configuration Matrix) 4-21
4.9 Programmable Logic CFC 4-24
4.10 Power System Data 4-26
4.11 Setting Groups 4-27
4.12 General Device Settings 4-29
4.13 Time Synchronization 4-30
4.14 Serial Interfaces 4-31
4.15 Passwords 4-33

7SD610 Manual 4-1


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.1 General

The SIPROTEC® 4 family is an innovative product series of numerical protective and


control devices with open communication interfaces for remote control and remote
setting, ergonomically designed operator panels, and highly flexible functionality.

4.1.1 Protection and Control

The devices utilize numerical measuring techniques. Complete numerical signal


processing offers high measurement accuracy and long-term consistency, as well as
reliable handling of harmonics and transients. Digital filtering techniques and adaptive
stabilization of measured values ensure the highest security in establishing the devic-
es’ correct responses. Device errors are recognized and quickly annunciated by inte-
grated self-monitoring routines. Failure of protection during a fault is therefore almost
entirely prevented.
You may choose devices with separate protective and process control functions, or
select a solution that implements both requirements.
The following solutions are available:
q Protection and control in separate devices,
q Protective devices that provide the capability of control of a circuit breaker or prima-
ry switching device through a communication interface,
q Devices with combined features that, in addition to protective functions, offer on-site
operation for several circuit breakers and primary switching devices and extensive
substation control functions.

4-2 7SD610 Manual


C53000-G1176-C145-1
General

4.1.2 Communication

SIPROTEC® 4 devices are completely suited for the requirements of modern commu-
nication technology. They have interfaces that allow for integration into higher-level
control centres, and user friendly operation through an on-site PC or via a modem con-
nection. Simple, comfortable device setup and operation are provided.
SIPROTEC® 4 devices support the widespread, internationally accepted communica-
tion standards, e.g.
q EC 60870-5-103,
q PROFIBUS FMS/DP,
q DNP 3.0,
q Modbus,
q UCA II / Ethernet (future)

Operation and Observation To Network Control Centers


IEC60870-5-101
SICAM WinCC

DIGSI 4
DCF, GPS
Time Synchronization

SICAM SC
IEC60870-5-103

Profibus FMS

Field Devices

Figure 4-1 Integration of field devices in the SICAM substation control system — example

7SD610 Manual 4-3


C53000-G1176-C145-1
SIPROTEC® 4 Devices

In the sample configuration in Figure 4-1, data transmitted from the field devices can
be processed in the sub-station control device SICAM SC, displayed at the operating
and observation station SICAM WinCC, and transferred by the remote terminal unit
interfaces (via the network channels) to network control centres (SCADA).
In the case when commands are sent to the devices, equally flexible processing is
possible; that is, substation switching operations can be initiated from the network
control centres, as well as from the operation and observation unit of the substation
control system.

Note:
All SIPROTEC® 4 devices also operate with the proven star coupler (e.g. 7XV5). Thus,
for simple applications, you can retrieve all information from your office or while on the
road.

The protocol PROFIBUS DP enables the uncomplicated integration of SIPROTEC®


devices into PLC-based process control systems (e.g. SIMATIC S5/S7). The protocols
DNP3.0 and MODBUS ASCII/RTU allow the integration into a large number of pro-
cess control systems and control systems of different manufacturers.

4.1.3 Settings

The devices in the SIPROTEC® 4 family are delivered with default settings. After set-
tings are made for specific applications, the devices are suitable for direct use in power
systems.
The windows-based DIGSI® 4 software program offers an application-oriented inter-
face with thorough guidance for quick and simple setting of the devices.
DIGSI® 4 is installed on a normal personal computer. For local use, the PC is connect-
ed to the operating serial interface on the front panel of the device.

4.1.4 Operations

All on-site operations of a SIPROTEC® 4 device can be done with DIGSI ® 4. Exam-
ples of operations are switching, retrieval of information, or changing of setting groups.
These operations can also be performed using the operator control panel on the front
of the SIPROTEC® 4 device.

4.1.5 Oscillographic Fault Records

DIGSI® 4 can also be used to retrieve oscillographic fault data captured by the
SIPROTEC® 4 device. The DIGRA 4 software program can then be used to provide
several different graphical representations of the captured signals. DIGRA® 4 also cal-
culates additional values on the basis of the captured signals. The program presents
the data in analogue curves with time base, phasor diagrams, locus diagrams, and
harmonic charts.

4-4 7SD610 Manual


C53000-G1176-C145-1
Operator Control Facilities

4.2 Operator Control Facilities

4.2.1 Operator Control Panel On Device

The operating panels of SIPROTEC® 4 devices are ergonomically designed and easy
to read. The operating panels allow on-site control operations to be done, individual
settings to be entered, and all information required for operations to be displayed.
The operating panel contains either a full graphical display or a four-line display, de-
pending on the specific device of the SIPROTEC® 4 family.

Operating Panel
with Four-Line
Display

SIEMENS SIPROTEC
RUN ERROR 7SA522

MAIN MENU 01/05


SIEMENS SIPROTEC
RUN ERROR 7SA522
Annunciation 1
Measurement 2
MAIN MENU 01/04
SIEMENS SIPROTEC
RUN ERROR 7SJ61/62
Annunciation 1
MENU
Measurement 2

MAIN MENU 01/05

Annunciation 1
MENU
Measuremen 2

LED ESC ENTER Trip MENU


Pickup A

Event Log Pickup B


F1 7 8 9
Pickup C
Operation. ENTER
F2 4 5 6 LED Pickup GND ESC
Pri
Device faulty
F3 1 2 3
Meldungen F1 7 8 9
F4 0 +/-
Meßwerte
LED F2 4 5 6 ESC ENTER

F3 1 2 3
Event Log F1 7 8 9
F4 Operation. 0 +/-
Pri F2 4 5 6

Trip Log F3 1 2 3

F4 0 +/-

Figure 4-2 SIPROTEC® 4 Device, operator control panel with four-line display — examples

Note:
Refer to Chapter 2 to determine the type of operating field for your specific
SIPROTEC®4 device.

7SD610 Manual 4-5


C53000-G1176-C145-1
SIPROTEC® 4 Devices

The functions of the operating and display elements on the operator control panel are
described below.

Display Process and device information are displayed in the LCD. Commonly displayed infor-
mation includes measured values, counter values, binary information regarding the
condition of the device, protection information, general messages, and alarms.
The light for the display is normally off. The light automatically turns on whenever a
key is pressed on the operating field. If no input from the operator control panel occurs
for ten minutes, then the light turns off again. The light can be controlled via a binary
input that is configured (programmed) for this purpose.

Keys The keys have various functions.


q Navigation through the operating menus of the device are accomplished with the
, , , keys.
q The main menu is opened with the MENU key.
q Changes are cancelled or confirmed with the ESC and ENTER keys, respectively.
q Numerical values are entered with the 0 to 9 keys, the . key for a decimal
point, and the +/– key for a negative sign. If a value of infinity (∞) is desired, press
the decimal point key twice; ∞ appears in the display.
q The F1 to F4 keys are programmable. The keys are typically used to execute com-
monly performed actions. Labelling strips are provided.
q Latched LEDs and output relays are reset and the group of LEDs are tested with
the LED key.

LEDs q “RUN” and “ERROR” LEDs indicate the condition of the device.
q All other LEDs are freely configured to indicate process information, status, events,
etc. Labelling strips are provided.

Operating Serial Local communication with the device is established through the front operating serial
Interface interface with a PC running DIGSI® 4. The interface on the device is a 9-pin, female,
D-subminiature port.

4-6 7SD610 Manual


C53000-G1176-C145-1
Operator Control Facilities

4.2.2 DIGSI® 4 Tool

DIGSI® 4 uses the familiar Windows operating environment.

User Guide In DIGSI® 4 only the settings that are available within a specific device are shown in
the specific windows. If a protective feature is changed from disabled to enabled in the
Device Configuration, then the settings relevant to that feature become available.
Entering settings for SIPROTEC® 4 devices is easy due to many types of assistance
offered, such as context menus, pop-up lists for the selection of available options, and
specific limits for the entry of numerical values.

Configuring A configuration matrix is used to assign the binary inputs, output relays, and LEDs. In-
Inputs and Outputs formation to be stored in the various buffers and transmitted via the system interface
is also selected in this matrix. The setting options are presented in an easy-to-read
tabular format. Parts of the matrix can be minimized or expanded as desired to simplify
the displayed sections, and therefore the setting process. Filter functions can reduce
the size of the matrix to display only relevant information.

Passwords Password entry is required for tasks such as changing settings, executing control
commands, or exercising the test and diagnostics features. The passwords protect
against unauthorized access to these critical tasks.

Commissioning DIGSI® 4 simplifies commissioning with test functions for the binary inputs, outputs
Aids and LEDs. Control of primary equipment can be done. The measured values of the
device can be viewed with the program. Oscillographic fault records can be triggered
with DIGSI® 4.

Help System The help system clarifies the individual functions and settings, and provides additional
support.

Note:
Detailed information about DIGSI® 4 can be found in the DIGSI® 4 Manual, order
number E50417-H1176-C097.

7SD610 Manual 4-7


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.3 Information Retrieval

A SIPROTEC® 4 device has an abundance of information that can be used to obtain


an overview of the present and past operating conditions of the device and the portion
of the power system being protected or controlled by the device. The information is
represented in separate groups:
q Annunciations,
q Measurements,
q Oscillographic fault records.

Remote If the device is integrated into a substation control system, then information transfer
can take place, via a connection to the system interface of the SIPROTEC® 4 device,
to:
q higher level control systems, or
q substation control devices, e.g. SICAM SC.

Local On site, the operator control panel of the SIPROTEC® 4 device can be used to retrieve
information.

DIGSI® 4 Information retrieval is simple and fast when DIGSI® 4 is used. For local use, connect
a PC to the operating serial interface at the front of the SIPROTEC® 4 device. For re-
mote retrieval of information, communication occurs via a modem connected to the
service serial interface. DIGSI® 4 must operate in the Online mode to obtain informa-
tion from the device.

4-8 7SD610 Manual


C53000-G1176-C145-1
Information Retrieval

4.3.1 Annunciations

The scope of the indication (messages) that are given under Annunciation is deter-
mined when settings for the configuration of functions are applied to the SIPROTEC®
device.
The messages are divided into the following categories, and displayed using DIGSI® 4
or the operator control panel of the device:
q Operating messages: Messages independent of network faults, e.g. messages
about switching operations or monitoring functions;
q Fault messages;
q Ground fault messages (for devices with sensitive ground fault detection);
q General interrogation; display of present condition messages;
q Spontaneous messages; continuous display of important messages from the de-
vice; e.g., after faults, switching operations, etc.

Figure 4-3 DIGSI® 4, annunciations

Display in DIGSI® 4 To view the indications in DIGSI® 4 2QOLQH:


• Select $QQXQFLDWLRQ in the navigation (left) window.
All annunciation groups are shown in the data (right) window.
• Double click on an annunciation group in the data window, such as (YHQW/RJ.
The data and time appear. Double click on the entry. The list of indications appears.

7SD610 Manual 4-9


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Display on To display messages in the operating field of the SIPROTEC® 4 device:


the Device
• Select 0DLQ0HQX → $QQXQFLDWLRQ →
e.g. (YHQW/RJ or 7ULS/RJ.

0$,10(18

!$QQXQFLDWLRQ²!
!0HDVXUHPHQW²! $1181&,$7,21

!(YHQW/RJ²!
!7ULS/RJ²! (9(17/2*


5HVHW/('21

Figure 4-4 SIPROTEC® 4, device display of operating messages in the event log — example

75,3/2*

!/DVW)DXOW²! /$67)$8/7
!QG/DVW)DXOW²! 

1HWZRUN)DXOW21

Figure 4-5 SIPROTEC® 4, device display of fault messages— example

4-10 7SD610 Manual


C53000-G1176-C145-1
Information Retrieval

4.3.2 Measurements

The measured values that are registered are divided into the following categories for
display in DIGSI® 4 or on the operating field of the device:
q Primary values, based on the measured secondary values and the settings entered
for the current transformers and voltage transformers.
q Secondary values, which are the measured values or are derived from the meas-
ured values.
q Percentage values, relative to nominal ratings.
q Other values calculated by the device, e.g. thermal values or user-defined values.
q Statistics values.

Figure 4-6 DIGSI® 4 measured value display — example

Display in DIGSI® 4 To display the measured values in the DIGSI® 4 2QOLQH:


• Select 0HDVXUHPHQW in the navigation (left) window. The measured value groups
appear in the data (right) window.
• Double click on a group, for example 3ULPDU\9DOXHV.
• Double click on the next item in the data window, 2SHUDWLRQDOYDOXHVSUL
PDU\ in the example. The date and time appear.
• Double click on the date and time, and the measured values appear.

7SD610 Manual 4-11


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Display on To display the measured values in the operating field of the SIPROTEC® 4 device:
the Device
• Select 0DLQ0HQX → 0HDVXUHPHQW →
e.g. 2SHUDWLRQSUL.

0$,10(18

!$QQXQFLDWLRQ²!
!0HDVXUHPHQW²! 0($685(0(17

!2SHUDWLRQSUL²!
!2SHUDWLRQVHF²!

0($685(0(17

!2SHUDWLRQSUL²! 23(5$7,2135,
!2SHUDWLRQVHF²! 
!,/ $
!,/ $

Figure 4-7 SIPROTEC® 4, device display of measured values — example

4.3.3 Oscillographic Fault Records

As an option, SIPROTEC® 4 devices can have waveform capturing and event record-
ing. Furthermore, the elements that are shown in the fault records can be selected by
the user.
The fault record data are retrieved from the device memory by DIGSI® 4 and are
stored as oscillographic records in standard COMTRADE format.
The DIGRA 4 program is used to convert the oscillographic data into graphical repre-
sentations that can be used to analyse the fault or the event captured by the device.
DIGRA 4 calculates additional values from the waveform data, e.g. impedances and
rms values, and displays the captured and calculated values in:
q analogue curves with timebase (time signals),
q phasor diagrams,
q locus diagrams, and
q harmonic graphs.

4-12 7SD610 Manual


C53000-G1176-C145-1
Information Retrieval

digra009

Figure 4-8 DIGRA® 4 graphical representations of the waveform data — view examples

Details can be found in the DIGSI® 4 manual, order number E50417-H1176-C097,


and the DIGRA® 4 manual, order number E50417-H1176-C070.

7SD610 Manual 4-13


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.4 Control

The multiple application possibilities for SIPROTEC® 4 devices allow an equally flex-
ible concept for command processing and control.

Remote If the device is integrated into a master control system, then command outputs can be
remotely controlled via the system interface using telegrams from
q Higher-level control systems, or
q substation control devices such as SICAM SC.

Local On-site, the SIPROTEC® 4 device offers the possibility to control a circuit breaker or
primary switching equipment using the operator control panel.

For devices with a four-line display, switching operations are controlled using:
• 0DLQPHQX → &RQWURO → %UHDNHU6ZLWFK → &RQWURO → Equipment and in-
tended direction 21 or 2)) (Figure 4-9), or
• The Function Keys F1 to F4.
The functionality of these keys is programmable.

0$,10(18

0HDVXUHPHQW²!
!&RQWURO²! &21752/

!%UHDNHU6ZLWFK²!
!7DJJLQJ²!

&21752/

!%UHDNHU6ZLWFK²! %5($.(56:,7&+
!7DJJLQJ²! 
!'LVSOD\²!
!&RQWURO²!

Figure 4-9 On-site control using the operator control panel

The status of a primary switch can be read out on the display using %5($.(56:,7&+
→ 'LVSOD\ (Figure 4-10).

%5($.(56:,7&+

!'LVSOD\²! ',63/$<
!&RQWURO²! 
!%UHDNHU23(1
'LVF6ZLW&/26

Figure 4-10 Determining primary switch status using the operator control panel

4-14 7SD610 Manual


C53000-G1176-C145-1
Control

DIGSI® 4 Control operations can be carried out using the DIGSI® 4 Tool. Connect a PC to the
operating interface of the device on site, or communicate with the SIPROTEC ® device
using a modem and the service interface.
DIGSI® 4 must operate in the Online mode for this function.
• Select &RQWURO in the Navigation window and double click on %UHDNHU
6ZLWFKHV in the data window.
In the dialogue window that follows, all relevant primary switching equipment is dis-
played in a table with the present status.
• Enter the intended switching direction in the Scheduled column. Answer the ques-
tion with <HV.
The password is requested, the interlocking conditions are checked, and the com-
mand is issued.

Note:
The control option of DIGSI® 4 is typically used during commissioning, and for test and
diagnostic purposes.

CFC Using the graphically supported design tool CFC for logic functions in DIGSI® 4, infor-
mation can be logically combined. Command outputs can be derived from the output
of logic functions. The link of the output of the CFC functions to the respective device
outputs is determined in the configuration matrix.

Passwords Only authorized personnel can perform switching operations. Switching operations
are protected by passwords.

Interlocking Command outputs may be subject to interlocking checks, which can be configured in-
dividually and graphically using the CFC logic too. Standard interlocking, such as
ground switch closed status indication, may be already contained in the basic settings
of certain device types when delivered from the factory.

Command Process- Details about the command output time, checkback indication monitoring time, etc.,
ing Times are entered within the framework of the settings.

Event Recording All switching operations are recorded in the message list with date and time.

7SD610 Manual 4-15


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.5 Manual Overwrite / Tagging

Manual Overwrite If the breaker/switch position is not available from the switch-gear, the status of the
switchgear device can be manually set to the actual present position using the opera-
tor control panel: 0DLQ0HQX → &RQWURO → %UHDNHU6ZLWFK → 0DQ2YHU
ZULWH. The simulated switching status is used for interlocking checks, and for auto-
matically initiated switching operations.

Set Status For convenience during commissioning or at other times, decoupling of the informa-
tion exchange between the switchgear and the protective device may be desired for a
short period, without disconnecting the wires. This function is activated using the op-
erator control panel: 0DLQ0HQX → &RQWURO → %UHDNHU6ZLWFK → 6HW6WDWXV.

Tagging To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.
• The status of the tagging is displayed on the operating panel, 0DLQ0HQX → &RQ
WURO → 7DJJLQJ → 'LVSOD\ (Figure 4-11),
or changed using
• 0DLQ0HQX → &RQWURO → 7DJJLQJ → 6HW.

0$,10(18

$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²! &21752/

%UHDNHU6ZLWFK²!
7DJJLQJ²! 7$**,1*
,QWHUORFN²! 
'LVSOD\²!
6HW²!

Figure 4-11 Tagging equipment from the operator control panel

Note:
The Manual Overwrite function is always done using the operator control panel on the
SIPROTEC® 4 devices.

4-16 7SD610 Manual


C53000-G1176-C145-1
General about the Setting Procedures

4.6 General about the Setting Procedures

The SIPROTEC® 4 devices are delivered with standard default settings. Changes to
the settings are done with DIGSI ® 4.
The setting procedure for a SIPROTEC® 4 device consists of
q Overall Protection and Control Design:
q determining the functions that are to be used (device configuration),
q assigning the binary inputs, outputs, LEDs, buffers, system port, etc. (I/O-configu-
ration
q defining user-definable logic functions (CFC).
q Specific Settings:
q settings for all elements to be used,
q settings of the protective functions,
q settings of the process control functions.
Settings are first done Off-line. The settings are then loaded into the SIPROTEC® 4
device on-site using the operating serial interface, or remotely by modem and the
service interface.

Figure 4-12Setting a SIPROTEC® 4 device using DIGSI® 4

The transfer of data from DIGSI® 4 to the SIPROTEC® 4 device is indicated in the dis-
play. The progress of the transfer is displayed. See Figure 4-13.

7SD610 Manual 4-17


C53000-G1176-C145-1
SIPROTEC® 4 Devices

/2$'3$5$0(7(5



'RZQORDGDFWLYH

Figure 4-13 Screen of Device during Settings Transfer

Setting Sequence When setting a SIPROTEC® 4 device, adhere to the following sequence:
q Specify the interfaces, the device data, and the time synchronization,
q Determine the device functions to be used,
q Design the assignment of the inputs and outputs using the configuration matrix,
q Set the default display (optional),
q Design all of the special logic that is to be employed using CFC (optional),
q Enter the power system data,
q Apply the settings to groups A to D (groups B to D optional),
q Set the passwords.

Setting steps partially build on the decisions from the previous steps. By following the
sequence listed, unnecessary changes and rework are avoided. The sequence en-
sures that information required for an individual step will be available.

Note:
Changes to the configuration matrix and the control display are protected by password
No. 7 (Password for parameter set).

4-18 7SD610 Manual


C53000-G1176-C145-1
General about the Setting Procedures

Settings for Setting changes to individual protective elements and functions can be done using the
Protective operator control panel on the SIPROTEC® 4 device.
Elements
Other settings such as input/output and device configuration can be viewed from the
front panel, but not changed.
• Display the settings on the LCD using 0DLQ0HQX → 6HWWLQJV →
e.g. 0DVNLQJ ,2 .
• Change settings such as date and time using 0DLQ0HQX → 6HWWLQJV → 6HWXS
([WUDV.

0$,10(18

$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²!
6HWWLQJV²! 6(77,1*6
7HVW'LDJQRVH²! 
'HYLFH&RQILJ²!
0DVNLQJ ,2 ²!
36\VWHP'DWD²!
*URXS$²!
*URXS%²!
*URXS&²!
*URXS'²!
&KDQJH*URXS²!
2VF)DXOW5HF²!
6HWXS([WUDV²!
'HYLFH²!


$FWLYH*URXSLV$

Figure 4-14 Changing settings using the operator control panel — example

Note:
Changes to the individual settings are protected by Password No. 5 (Password for
single settings).

7SD610 Manual 4-19


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.7 Configuration of the Scope of Device Functions

The individual devices within the SIPROTEC® 4 family can be supplied with various
protective functions. The ordering number of the device determines the available func-
tions. The functions are specified more precisely through the process of enabling and
disabling in the Device Configuration area of the settings.
To specify the active functions using DIGSI® 4:
• Double click on 'HYLFH&RQILJXUDWLRQ in the data window.
• Click on the individual fields and select the functions to be enabled.

Figure 4-15 DIGSI® 4, setting the device configuration — example

The device configuration can be viewed from the operator control panel on the
SIPROTEC® 4 device.
• In the main menu, select 6HWWLQJV → 'HYLFH&RQILJ.

'(9,&(&21),*

&ROGORDG3LFNXS
(QDEOHG
Figure 4-16 Viewing device configuration from the operator control panel — example

4-20 7SD610 Manual


C53000-G1176-C145-1
Configuration of Inputs and Outputs (Configuration Matrix)

4.8 Configuration of Inputs and Outputs (Configuration Matrix)

A configuration matrix is used to determine processing of the binary inputs, outputs,


LEDs, and indication buffers.
Configuration is performed with DIGSI® 4.

The configuration matrix is primarily divided into the following columns:


q Device functions
q Information, e.g. indications or command with
q information number, identification of the information,
q display text, representative brief text of the information on the device display,
q long text, extensive description of the information,
q type, identification of the information, e.g. CF_D2 double command with 2 output
contacts and feedback indication;
q Source, that is, origin of the information with
q binary inputs
q function keys F, freely programmable keys on the operating field, e.g. assigned
switching operations, etc. as the origin of the information,
q CFC C (programmable logic), user-specific logic outputs as the origin of the infor-
mation;
q Destination of the information, with
q binary outputs for the output of signals,
q LED, display of information on the device front, e.g. messages,
q system interface S, transmission of information, e.g. to a substation control system,
q CFC C (programmable logic), information as an input to a user-specified logic,
q buffer, in which the information should be entered,
– operation annunciation buffer or
– fault annunciation buffer,
q control menu CR, primary device can be controlled or tagging can be set.

The user determines the configurations by


q clicking on the appropriate column, or by
q Using the context menu: L (latched), U (unlatched), H (activate high),
L (activate low), (configured), (not configured), etc.
DIGSI® 4 checks the entry for plausibility and locks the input field if necessary.
A locked input field is shown in gray.

7SD610 Manual 4-21


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Figure 4-17 DIGSI® 4, input/output assignment with the configuration matrix — example

Filter Functions With the use of filters, either all information can be displayed or a selection can be
done according to indications, commands, or measured values.
Additionally, there is a filter setting that differentiates between information configured
and not configured.
The filters allows for a quick overview and simple checking of the configuration set-
tings.
Also, columns and rows can be temporarily hidden from view, so that you can view
only the sections of the total matrix that are relevant.

New Information A further function of the configuration matrix is the capability to define new information.
This is accomplished by inserting a new line, defining the appropriate information type,
and assigning it to a source and a destination. The new information can also be dis-
played in the LCD of the SIPROTEC® 4 device after it has been downloaded to the
device.

Function Keys The function keys on the operator control panel of the SIPROTEC® 4 device can be
assigned to commonly performed operating functions, e.g. initiation of a switching op-
eration. Select the appropriate function key F1 to F4 in the Source F column for the
related information (e.g. switching command).

4-22 7SD610 Manual


C53000-G1176-C145-1
Configuration of Inputs and Outputs (Configuration Matrix)

CFC SIPROTEC® 4 device information can be connected in a user-specified manner using


the programmable logic components of the DIGSI® 4 CFC. For example, the user can
implement interlocking checks, create grouped messages, or derive limit value viola-
tion messages.
Information can be both a source and a destination in combined CFC editing. The spe-
cific logic’s inputs, e.g. the individual messages that are to be combined to form a
grouped message, must be marked in the Destination C column. The logic’s output,
the grouped message in this example, is derived from the Source C column.

Viewing the Config- The configuration can be seen on the operating panel of the SIPROTEC® 4 device.
uration on the
• In the main menu, select 6HWWLQJV → 0DVNLQJ ,2 .
Operating Panel

0$6.,1* ,2 



!%LQDU\,QSXWV²!
!/('²!

• In the next menu, select 0DVNLQJ ,2 → e.g. %LQDU\,QSXWV.

%,1$5<,13876

!%LQDU\,QSXW²!²
!%LQDU\,QSXW²!²

Figure 4-18 Reading the configuration using the operator control panel, example assignment
of binary input 2

7SD610 Manual 4-23


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.9 Programmable Logic CFC

The CFC program in DIGSI® 4 can be used to create additional logic in SIPROTEC®
4 devices. For example, special interlocking conditions for controlled equipment can
be designed. Limit checks for measured values can be created, and corresponding
control can be designed.
SIPROTEC® 4 devices may have some CFC functions set at the factory, according to
the type and version of the device.
User-defined CFC functions are done in graphical form. Generic logic modules (AND,
OR, NAND, etc.) and analog modules that are specially created for the requirements
of process control engineering (e.g., MAX, MIN, etc.) are available.
The CFC-modules are combined to form complete CFC-logic functions in order to
q perform system-specific checks (e.g. interlocking),
q generate messages if measured values approach a critical value, or
q build group messages for transfer to a substation control systems.

Figure 4-19 DIGSI® 4, CFC basic options — example

4-24 7SD610 Manual


C53000-G1176-C145-1
Programmable Logic CFC

CFC Designing Figure 4-20 shows the graphical nature of the CFC logic tool, and some of the com-
ponents that can be used to build the logic.

Note:
CFC settings are protected in DIGSI® 4 by Password No. 7 (Password for parameter
set).

Details about designing with the CFC program can be found in the instruction book,
order number E50417-H1176-C098.

Figure 4-20 CFC Logic — example

7SD610 Manual 4-25


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.10 Power System Data

Power System In the window for Power System Data 1, important settings are entered that relate to
Data 1 the power system and primary equipment connected to the device. The settings in-
clude:
q system data such as frequency, voltage, etc.
q data for the main current transformers and voltage transformers,
q circuit breaker or primary switch-gear information.

Figure 4-21 DIGSI® 4 window for setting the power system data 1 — example

Power System Power System Data 2 are part of the setting groups, which can be switched over dur-
Data 2 ing operation (see chapter 4.11). These include for example:
q Primary Operating Voltage
q Primary Operating Current
q Characteristic Data of the protected object etc.

4-26 7SD610 Manual


C53000-G1176-C145-1
Setting Groups

4.11 Setting Groups

A SIPROTEC® 4 device has up to four setting groups A through D. The setting options
for each group are the same; however, the applied settings can be, and are typically
intended to be, different in each group. The active setting group can easily be changed
while the device is in-service. A major advantage of multiple setting groups is the ca-
pability of optimizing the protection and control for the existing configuration of the net-
work being protected. In other words, the protection and control can be changed as
the network changes.
The setting groups are saved in the device. The setting groups can be changed during
operation using DIGSI® 4, from the operator control panel on the device, by triggering
binary inputs, or via the system interface.

Figure 4-22 DIGSI® 4, Entering Settings in Setting Group A; Other Groups are Similar

Note:
Settings that are common to all protective functions, such as Power System Data 2,
can be dynamically activated like the settings in Groups A through D.

7SD610 Manual 4-27


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Settings Double click on a protective function shown in the listbox of Figure 4-22 to obtain a
dialogue box for entering the settings associated with this function (Figure 4-23).

Figure 4-23 DIGSI® 4, entering settings for a protective function — example

Changing Setting The setting groups can be changed during operation using DIGSI® 4, from the opera-
Groups tor control panel on the device, by triggering binary inputs, or via the system interface.
The active setting group is indicated.

&+$1*(*5283

$&7,9(*5283
*URXS$
&+$1*(WR
*URXS$

*URXS$
*URXS%
*URXS&
*URXS'
%LQDU\,QSXW
,(&²²

Figure 4-24 SIPROTEC® 4 device, changing setting groups on the operator control panel

4-28 7SD610 Manual


C53000-G1176-C145-1
General Device Settings

4.12 General Device Settings

The settings of the display to show information of network faults on the LEDs and the
LCD on the front of the SIPROTEC® 4 device are defined in the DIGSI® 4 window
shown in Figure 4-25.

Figure 4-25 DIGSI® 4, general device settings (targets) — example

The setting can also be changed at any time using the operator control panel on the
SIPROTEC® 4 device: 0DLQ0HQX → 6HWWLQJV → 'HYLFH.

7SD610 Manual 4-29


C53000-G1176-C145-1
SIPROTEC® 4 Devices

4.13 Time Synchronization

Time tracking in a SIPROTEC® 4 device can be implemented using:


q DCF77 Radio Receiver (Time Signal from PTB Braunschweig),
q IRIG-B Radio Receiver (Time Signal from the global positioning satellite (GPS) sys-
tem),
q signals via the system interface from, for example, a substation control system,
q radio clock using a system-specific synchronizer box,
q minute impulses on a binary input.
Setting of the time synchronization is done exclusively with DIGSI® 4:
• Double click on 7LPH6\QFKURQL]DWLRQ in the data window and enter the set-
tings.

Figure 4-26 DIGSI® 4, setting of the time synchronization — example

Read-out on the Using the SIPROTEC® 4 device operator control panel, the time synchronization set-
Operator Control tings can be retrieved: 0DLQ0HQX → 6HWWLQJV → 6HWXS([WUDV → &ORFN6HW
Panel XS.

6(783(;75$6

'DWH7LPH²!
&ORFN6HWXS²! &/2&.6(783
6HULDO3RUWV²! 
'HYLFH,'²! 2IIVHWPLQ
0/)%9HUVLRQ²! (UURU7LPHPLQ
&RQWUDVW²! 6RXUFH,QWHUQDO

Figure 4-27 Read-out of time synchronization settings from the operator control panel

4-30 7SD610 Manual


C53000-G1176-C145-1
Serial Interfaces

4.14 Serial Interfaces

Devices in the SIPROTEC® 4 family can be equipped with up to four serial interfaces
and a time.
q The system interface is used for connection with higher-level control centers. The
following protocols are presently available:
• IEC 60870-5-103,
• PROFIBUS FMS,
• PROFIBUS DP,
• DNP3.0 Level 2,
• MODBUS ASCII/RTU
q The time control interface is used for time synchronization (e.g. IRIG B),
q The service interface (DIGSI® 4, Modem) is for connection to remote diagnostic
facilities, e.g. DIGSI® 4 via modem and/or a star connection. All DIGSI® 4 opera-
tions are possible via this interface,
q The PC-interface at front is used for on-site connection of a PC, on which DIGSI® 4
is installed. All operations that are possible using DIGSI® 4 can be done at this in-
terface.
In the DIGSI® 4 Interface Settings window (under Serial Ports) you can define,
among other items, settings for:
q Transmission protocols and
q Transmission speeds.

Note:
The service (DIGSI® 4, Modem) and system interface (SCADA) can be equipped with
different modules for connection to other devices via optical fibers or an RS 232/485
bus.

The following an example for the configuring of an IEC-interface. In Chapter 5 you will
learn more about how to configure further protocols.
To set the framing and baud rate:
• Double click on 6HULDO3RUWV in the data window and enter the specific settings
in the window that follows.

7SD610 Manual 4-31


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Figure 4-28 DIGSI® 4, interface settings window

Read-out on the The interface settings can be checked using the SIPROTEC® 4 device operator con-
Operator Control trol panel.
Panel
In the main menu, select 6HWWLQJV → 6HWXS([WUDV → 6HULDO3RUWV → follow-
ing menus.

6(783(;75$6

'DWH7LPH²!
&ORFN6HWXS²!
6HULDO3RUWV²! 6(5,$/32576
'HYLFH²,'²! 
)URQW3RUW²!
0/)%9HUVLRQ²! 6\VWHP3RUW²!
&RQWUDVW²! 6HUYLFH3RUW²!

Figure 4-29 Read-out of serial interface settings from the operator control panel, example

Note:
The interface for connecting a time control device is described in the Sub-section 4.14,
Time Synchronization.

4-32 7SD610 Manual


C53000-G1176-C145-1
Passwords

4.15 Passwords

Passwords are assigned to a SIPROTEC® 4 device to protect against unintended


changes to the device or unauthorized operations from the device, such as switching.
The following access levels are defined:
q Switching/tagging/manual overwrite,
q Non-interlocked switching,
q Test and diagnostics,
q Hardware test menus,
q Individual settings,
q Setting Groups.

Figure 4-30 DIGSI® 4, window indicating the active passwords — example

When using DIGSI® 4 or the operator control panel on the SIPROTEC® 4 device, a
password is requested for the specific functions.

Note:
Password protection against unauthorized access is only in place during on-line op-
eration. The passwords for setting changes are first activated when the settings are
loaded into the device. The passwords are irrelevant in the DIGSI® 4 off-line mode.
To deactivate a password, you must know the password.

7SD610 Manual 4-33


C53000-G1176-C145-1
SIPROTEC® 4 Devices

Passwords can only be changed using DIGSI® 4.


To change an existing password:
• In the Passwords window shown in Figure 4-30, double click on the password to be
changed. In the next window (Figure 4-31), enter the present password, the new
password, and confirm with the new password again and 2..

Figure 4-31 DIGSI® 4, changing passwords

Passwords are numbers up to 8 digits.


At delivery all passwords are set to 000000.

Note:
If the password for setting group switching has been forgotten, a temporary password
can be received from Siemens. The temporary password can be used to define a new
password for this function.
The registration number of the DIGSI® 4 software package will be required to re-
ceive the temporary password.

4-34 7SD610 Manual


C53000-G1176-C145-1
Configuration 5
Configuration is the process of customizing the relay for the intended application.
To accomplish this, the following questions must be answered:
• Which functions do you need?
• Which information and measured quantities need to be retrieved via which inputs?
• Which information, measured data, and control actions need to be issued via which
outputs?
• Which user-definable functions need to be performed in CFC (Continuous Function
Chart)?
• Which information should be displayed on the front panel of the device?
• Which interfaces are to be used?
• Which time source is to be used to synchronize the internal clock?
This chapter describes in details how to configure the 7SD610.

5.1 Configuration of the Scope of Functions 5-2


5.2 Configuration of Information, Measured Values, and Commands 5-6
5.3 Creating User Defined Functions with CFC 5-27
5.4 Serial Interfaces 5-36
5.5 Date and Time Stamping 5-40

7SD610 Manual 5-1


C53000-G1176-C145-1
Configuration

5.1 Configuration of the Scope of Functions

General The 7SD610 relay contains a series of protective and additional functions. The scope
of hardware and firmware is matched to these functions. Furthermore, commands
(control actions) can be suited to individual needs of the protected object. In addition,
individual functions may be enabled or disabled during configuration, or interaction be-
tween functions may be adjusted.
Example for the configuration of the scope of functions:
7SD610 devices should be intended to be used for overhead lines and transformers.
Overload protection should only be applied on transformers. If the device is used for
overhead lines this function is set to 'LVDEOHG and if used for transformers this func-
tion is set to (QDEOHG

Note:
Available functions and default settings are depending on the ordering code of the re-
lay (see ordering code in the Appendix for details).

Figure 5-1 Device Configuration dialogue box in DIGSI® 4 — example

Before closing the dialogue box, transfer the modified functional setting to the relay by
clicking on the item ',*6, → 'HYLFH. The data is stored in the relay in a non-volatile
memory buffer.
The configured functional scope can be viewed at the front of the relay itself, but can-
not be modified there. The settings associated with the functional scope can be found
in the 0$,10(18 under → 6HWWLQJV → 'HYLFH&RQILJ.

Special Cases Most settings are self-explanatory. The special cases are described below.

5-2 7SD610 Manual


C53000-G1176-C145-1
Configuration of the Scope of Functions

If the setting group change-over function is to be used, the setting in address 
*US&KJH237,21 must be set to (QDEOHG. In this case, it is possible to apply up to
four different groups of settings for the function parameters (refer also to Subsection
6.1.2). During normal operation, a convenient and fast switch-over between these set-
ting groups is possible. The setting 'LVDEOHG implies that only one function parame-
ter setting group can be applied and used.
Address  7ULSPRGH applies only to devices with single-pole or three-pole trip-
ping. Set SROH if single-pole is also desired, i. e. if the device is supposed to op-
erate with single-pole or with single-pole/three-pole automatic reclosure. It must be
provided that the device is equipped with an automatic reclosure function or that an
external device is used to carry out the automatic reclosure. Additionally the circuit
breaker must be suited for single-pole tripping.

Note:
When changed address , then first save this alteration by clicking 2.. Reopen
the dialogue box, since there are other settings which are dependent on the selection
in address .

The differential protection function ',))3527(&7,21 (address ) as a main


function of the device should always be (QDEOHG. This also implies the supplementa-
ry functions of the differential protection such as breaker intertrip.
The Direct Local Trip (address  '77'LUHFW7ULS) is a command that is initi-
ated from an external device for tripping the local circuit breaker.
A preselection of the tripping characteristic of the time overcurrent protection can be
made in address  %DFN8S2&. In addition to the definite-time overcurrent pro-
tection (definite time) an inverse-time overcurrent protection can be configured that ei-
ther operates according to an IEC characteristic (2&,(&) or to an ANSI character-
istic (2&$16,). The characteristics are shown in the Technical Data (Section 10.6).
The time overcurrent protection may naturally also be set to 'LVDEOHG.
If the device provides an automatic reclosure function, the addresses  and 
are relevant. If no automatic reclosure is desired for the feeder the device 7SD610 is
connected to, or if an external device carries out the automatic reclosure, address
 $8725(&/26( is set to 'LVDEOHG. Automatic reclosure is only permitted for
overhead lines. It may not be used in any other case. If the protected object consists
of a combination of overhead lines and other equipment (e.g. overhead line in a block
with a transformer or overhead line/cable), reclosure is only permissible if it can be en-
sured that it can only take place in the event of a fault on the overhead line.
In the address mentioned the number of desired reclosure cycles is be set. Choose
the desired number of AR-cycles from a total scope of $5F\FOHV. You can also
set $'7 (adaptive dead time): in this case the behaviour of the automatic reclosure de-
pends on the cycles of the remote end. However, at one end of the line the number of
cycles must be configured. This end must provide an infeed. The other end may op-
erate with adaptive dead time. See Subsection 6.9.1 for detailed information.
The $5FRQWUROPRGH under address  allows a total of four options. You can
determine whether the sequence of automatic reclosure cycles is defined by the fault
situation of the pick-up of the starting protection function(s) or by the type of trip com-
mand. The automatic reclosure can also operate with or without action time.

7SD610 Manual 5-3


C53000-G1176-C145-1
Configuration

The 7ULS ZLWK7DFWLRQ or 7ULS ZLWKRXW7DFWLRQ command setting is pre-


ferred when single-pole or single/three-pole automatic reclosure cycles are planned
and are possible. In this case different dead times (for every AR-cycle) are possible
after single-pole tripping and after three-pole tripping. The tripping protection function
determines the type of tripping: single-pole or three-pole. The dead time is controlled
dependent on this.
Using the3LFNXSZLWK 7DFWLRQ or 3LFNXSZLWKRXW 7DFWLRQsetting, dif-
ferent dead times can be set for the auto-reclosure cycles after single-, two- and three-
phase pickup on faults. The fault detection image of the protection functions at the in-
stant the trip command disappears is decisive. This operating mode also enables the
dead times to be made dependent on the type of fault for three-pole AR-cycles. Trip-
ping is always three-pole.
The 7ULS ZLWK7DFWLRQ or 3LFNXS ZLWK7DFWLRQ setting provides an action
time for every AR-cycle. This is started by the general pickup signal (i. e. logic OR
combination of all internal and external pickup signals of all protection functions which
are configured to start the automatic reclosure function). If there is yet no trip com-
mand when the action time has expired, the corresponding automatic reclosure cycle
cannot be executed. See Subsection 6.12.1 for more information. For the time graded
protection this setting is recommended. If the protection function to operate with re-
closure does not have a general fault detection signal for starting the action times, se-
lect the setting 7ULSZLWKRXW7DFWLRQ or 3LFNXS ZLWKRXW7DFWLRQ.
For the trip circuit supervision the number of trip circuits that shall be monitored is set
in address  7ULS&LUF6XSHUY with the following settings: WULSFLUFXLW,
WULSFLUFXLWV or WULSFLUFXLWV.
If the device is connected to voltage transformers, set this condition in address 
975$16)250(5. Only if set FRQQHFWHG, the voltage dependent functions (meas-
ured values of voltages, power and power factor) can be registered by the device.
If a transformer is located within the protected zone, set this condition in address 
75$16)250(5. The data of the transformer are registered by the device during the
configuration of the general protection data (see “Topological Data for Transformers
(optional)” in Subsection 6.1.3).

5.1.1 Setting Overview

Note: Depending on the type and version of the device it is possible that addresses
are missing or have different default settings.

Addr. Setting Title Setting Options Default Setting Comments


103 Grp Chge OPTION Disabled Disabled Setting Group Change Option
Enabled
110 Trip mode 3pole only 3pole only Trip mode
1-/3pole
112 DIFF.PROTECTION Enabled Enabled Differential Protection
Disabled

5-4 7SD610 Manual


C53000-G1176-C145-1
Configuration of the Scope of Functions

Addr. Setting Title Setting Options Default Setting Comments


122 DTT Direct Trip Disabled Disabled DTT Direct Transfer Trip
Enabled
124 SOTF Overcurr. Disabled Disabled Instantaneous HighSpeed SOTF
Enabled Overcurrent
126 Back-Up O/C Disabled Disabled Backup overcurrent
TOC IEC
TOC ANSI
133 Auto Reclose Disabled Disabled Auto-Reclose Function
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
134 AR control mode Pickup w/ Tact Pickup w/ Tact Auto-Reclose control mode
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
139 Breaker Failure Disabled Disabled Circuit breaker failure protection
Enabled
140 TripCirc.Superv Disabled Disabled Trip Circuit Supervision
1 trip circuit
2 trip circuits
3 trip circuits
142 Therm.Overload Disabled Disabled Thermal Overload Protection
Enabled
143 NUMBER OF RELAY 2 relays 2 relays Number of relays
3 relays
4 relays
5 relays
6 relays
144 V-TRANSFORMER connected not connected Voltage transformers
not connected
145 TRANSFORMER NO NO Transformer inside protection
YES zone

7SD610 Manual 5-5


C53000-G1176-C145-1
Configuration

5.2 Configuration of Information, Measured Values, and Commands

General Upon delivery, the display on the front panel of the relay, some of the function keys,
the binary inputs and outputs (output contacts) are assigned to certain information.
These assignments may be modified, for most information, allowing adaptation to the
local requirements.
During configuration, certain information within the relay is assigned to certain physi-
cal interfaces (e.g., binary inputs and output contacts) or logical interfaces (e.g. user-
defined logic, CFC).
It must be determined which information should be linked with which device interface.
It may also be determined which properties the information should have.
Messages and statistical values from earlier events can be lost during configuration;
therefore, operational and fault data and statistic counters which are memorized in the
relay should be read and saved if desired, prior to changing the configuration.

5.2.1 Preparation

Before configuration is started, the overall interfacing requirements must be assessed.


The required inputs and outputs must be coordinated with the number of physical in-
puts and outputs present on the relay. The types of indications and commands, and
their requirements, must be taken into account.

Indications Indications may be information of the device regarding events and conditions that can
be transmitted via output contacts (e.g. start-up of the processor system or a trip signal
of a protective function). These are defined as output indications. Indications also
include information from the plant to the relay regarding plant events and conditions
(e.g. position of a circuit breaker). These are defined as input indications.
Depending on the type, indications may be further classified. Figures 5-2 and 5-3
show typical indication types schematically. Two binary inputs whose normal condi-
tions are opposite, and which are monitored by the relay, are required for a double
point indication.

(Internal logic
information) (Plant)
Restart

(7SD610) L+ Output indication via relay contact

Figure 5-2 Output indication (OUT)

5-6 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

M
e.g. mcb e.g. Isoloator
(7SD610) (7SD610)
L+ Binary input L+
(e.g. BI1) Binary input
L–
(e.g. BI 2)
(Plant)
(Plant)
Binary input
L– (.e.g. BI 3)

Single point indication (SP) Double point indication (DP)

Figure 5-3 Input indications (SP & DP)

Control Commands Control commands are output indications which are specially configured for the trans-
mission of control signals to power plant switching devices (circuit breakers, isolators,
etc.). Once the type of a command has been established, DIGSI ® 4 reserves a corre-
sponding number of output relay contacts. For this, the corresponding output relays
are numbered consecutively. This must be observed when wiring the relays to the cor-
responding power plant devices to be controlled.
Table 5-1 shows the most important command types. The following Figures 5-4
through 5-8 show time diagrams, control settings, and the order of relay positioning for
frequently used command types.

Table 5-1 Most important command types

Single Command with With 1 relay without feedback &B6


Single Output with feedback &)B6
Double Command with With 2 relays without feedback &B'
Single Outputs with feedback &)B'
Double Command with Single With 3 relays without feedback &B'
Outputs plus Common Output with feedback &)B'
Double Command with Double With 4 relays without feedback &B'
Outputs with feedback &)B'
Double Command with Double With 3 relays without feedback &B'
(Close) and Single (Trip) with feedback &)B'
Outputs

For double commands, the first output relay is selected using DIGSI® 4. The other out-
put relays will be automatically selected by DIGSI® 4. In the sequence of output relays,
each TRIP command is placed before the associated CLOSE command. For
commands with feedback indications, DIGSI® 4 reserves another line in the configu-
ration matrix for the switching device feedback indications. Here, the OPEN position
feedback is placed before the CLOSED position feedback as well.
For Figures 5-4 through 5-8, the following abbreviations apply:
− C+ Relay contact for closing
− C– Relay contact for tripping
− CC Relay contact is common
− CCC Relay contact is common to a bus
− L+; L– Control voltage

7SD610 Manual 5-7


C53000-G1176-C145-1
Configuration

CLOSE
command L+
C+
C+
CLOSE Switching
t device
1
L–
Matrix configuration: X
C+

Figure 5-4 Single command with single contact

CLOSE TRIP
L+
command command
C+ C–
C+
CLOSE Switching TRIP
C– device
L–
1 2 t
Matrix configuration: XX
C–
C+

Figure 5-5 Double command with single contacts

CLOSE TRIP L+
command command C+ C–
C+
CLOSE Switching TRIP
C– device

CC
CC
1 2 3 t
L–
Matrix configuration: XXX
C+
CC
C–

Figure 5-6 Double command with single contacts plus common contact

5-8 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

CLOSE TRIP
command command L+
C+1 C+1 C–1

C+2 CLOSE Switching TRIP


device
C–1
C+2 C–2
C–2
L–
t
1 2 3 4

Matrix configuration: XXXX


C–1
C+1
C–2
C+2

Figure 5-7 Double command with double contacts (with 4 relays)

CLOSE TRIP L+
command command C+1 C–
C+1
CLOSE Switching TRIP
C+2 device

C– C+2

L–
t
1 2 3

Matrix configuration: XXX


C–
C+1
C+2

Figure 5-8 Double command with double and single contacts (with 3 relays)

7SD610 Manual 5-9


C53000-G1176-C145-1
Configuration

5.2.2 Structure and Operation of the Configuration Matrix

General This section deals with the structure and operation of the configuration matrix. The
configuration matrix can be viewed without making any configuration changes. Infor-
mation characteristics and configuration steps are described in Subsection 5.2.3, and
configuration is demonstrated in Subsection 5.2.4.
Configuration of information is performed, using a PC and the DIGSI® 4 software pro-
gram, via the operator or service interface. The configuration is represented in
DIGSI® 4 as a matrix (Figure 5-9). Each row is assigned to an information of the de-
vice. It is identified by a function number No, LCD text (display text D), an explanation
(long text L, minimized in Figure 5-9), and an information type T. The columns give the
interfaces which should be the sources and/or destinations of the information. In ad-
dition to physical device inputs and outputs, there may be internal interfaces for user
definable logic (CFC), message buffers, or the device display.

Filters Information Catalog Standard View Short view

Figure 5-9 Extract from the configuration matrix in the DIGSI® 4 user interface — example

5-10 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Information in the rows is assigned to appropriate interfaces in the columns via an en-
try in the intersecting cell. This establishes which information controls which destina-
tion, or from which source which information is received.
In the configuration matrix, not only the configuration is shown, but also the property
of configuration. For example, information regarding an event which is configured for
display on a LED may be latched or unlatched.
The possible combinations of information and interfaces is dependent on the informa-
tion type. Impossible combinations are filtered out by DIGSI ® 4 plausibility checks.
The matrix columns are divided into three categories: Information, Source, and Desti-
nation. To the left of the matrix, information is divided into information groups.

Reducing the The matrix may become very extensive because of the amount of information con-
Matrix tained within. Therefore, it is useful to limit the display via filtering to certain informa-
tion, thus reducing the number of rows.
The tool-bar below the menu bar contains two pull-down menus by which information
may be filtered. Using the first menu, the rows can be limited to indications, com-
mands, indications and commands, or measured and metered values. The second
menu allows to display only configured information, information configured to physical
inputs and outputs, or non-configured information.
A further reduction in the number of rows is possible, by compressing an information
group to one row. This is done by double-clicking on the group label area (located to
the far left). If this is done, the number of rows is reduced, allowing the user to focus
on the information groups of interest. A second double-click restores all rows in the
information group.
To limit the width of the matrix, two possibilities exist: The tool bar allows to switch be-
tween standard view and short view, or individual columns can be hidden.
In the latter case you double-click on the field with the column heading thus hiding the
contents of the associated column. In the example of Figure 5-9, the long text (/) un-
der IQIRUPDWLRQ is not shown. By double-clicking on long text field (/), the long text
becomes visible again, and vice versa.
With two options on the tool bar you may switch between standard view and short
view, thus modifying the all columns under the 6RXUFH and 'HVWLQDWLRQ title
blocks. The columns associated with the ,QIRUPDWLRQ block remain unchanged.
In standard view, all binary inputs, binary outputs, and LEDs are accessible, as shown
in Figure 5-9 for the binary outputs and LEDs.
In short view (not illustrated in the figure), a common column is displayed for each of
the sources and destinations. Within the individual cells of a common column, infor-
mation regarding the configuration type is available in an abbreviated form. For exam-
ple, the abbreviation H1 in a cell of the common binary input (BI) column means that
the corresponding information is configured with active voltage (High) to binary input
1. If an information is assigned to several sources or destinations, the abbreviations
of all destinations are shown, separated by commas. If there is not enough space in
the cell for the simultaneous display of all abbreviations, a double-click on the cell and
movement of the text cursor within the cell allows to scroll through the entire contents
of the cell.
To switch between standard view and short view, the menu item 9LHZ can also be
used.

7SD610 Manual 5-11


C53000-G1176-C145-1
Configuration

Information Groups All information is organized into information groups. In addition to general relay infor-
mation, information regarding individual device functions is also included.
By clicking on an information group title area with the right mouse button, a context
menu can be viewed, which contains information regarding the properties of that infor-
mation group. This is particularly useful if the information group is associated with a
function that contains parameter settings.
If the information group belongs to a protective function for the relay, a dialogue win-
dow can be accessed in which the settings of the protective function may be read out
and modified. The procedure for entering settings of a protective function is described
in general in Chapter 4. Details regarding the settings for various functions are found
in Chapter 6.
The settings group to be processed may be selected via the menu item 9LHZ → 6HW
WLQJ*URXS.

Information The column header ,QIRUPDWLRQ contains the function number, the LCD text (dis-
play text), an explanation (long text), and the information type. The following abbrevi-
ations are used for the information types:
• Annunciations:
− SP Single Point indication (binary input, e.g. LED reset, refer also to
Subsection 5.2.1),
− DP Double Point indication (binary input, refer also to Subsection 5.2.1),
− OUT OUTput indication (protection output signals e.g. pickup, trip ...),
− IntSP Internal Single Point indication,
− IntDP Internal Double Point indication.
• Control Commands for switching devices:
− C_S Single Command with Single output without feedback,
− CF_S Single Command with Single output with Feedback,
− C_SN Single Command with Single output Negated without feedback,
− C_D2 Double Command (2 relays) with single outputs without feedback,
− CF_D2 Double Command (2 relays) with single outputs with Feedback,
− C_D12 Double Command with 1 trip outputs and 2 close outputs without feed-
back,
− CF_D12 Double Command with 1 trip outputs and 2 close outputs with Feedback,
− C_D3 Double Command (3 relays) with single outputs and common output
without feedback,
− CF_D3 Double Command (3 relays) with single outputs and common output
with Feedback,
− C_D4 Double Command (4 relays) with double outputs without feedback,
− CF_D4 Double Command (4 relays) with double outputs with Feedback,
− C_D2N Double Command (2 relays) with single outputs Negated without
Feedback,
− CF_D2N Double Command (2 relays) with single outputs Negated with Feedback.
• Measured Values:
− MV Measured Value,
− MVU Measured Value, User defined,
− LVU Limit Value, User defined.

5-12 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

• Metered Values:
− PMV Pulse Metered Value.
The information contains various properties depending on the information type, which
are partially fixed and may be partially influenced.

Source The source denotes the origin of the information which the matrix receives for further
processing. Possible sources are:
− BI Binary Input,
− F Function key, which may serve to introduce a switching action,
− C CFC, i.e., message comes from user-definable logic.

Destination The destination indicates to which interface the information is forwarded. Possible
destinations are:
− BO Binary Output,
− LED LED display on the device front panel,
− O Operation event buffer in the device,
− T Trip log buffer in the device,
− S System Interface,
− C CFC, Information is processed by CFC program of the user-definable logic,
− CM Control of switchgear if a switch plant is indicated in the Control Menu of the
device.

5.2.3 Establishing Information Properties

General Different types of information contain different types of properties. To view the proper-
ties associated with a specific information unit (indication, command, etc.), position the
mouse on the specific row under ,QIRUPDWLRQ, and then use the right mouse button
to access a context menu where 3URSHUWLHV can be selected.
For example, if the cursor is positioned on a specific output indication, the right mouse
button is pressed, and the menu item 3URSHUWLHV is selected, then a choice of
whether the indication should appear in the oscillographic fault records (Figures 5-10,
5-11, and 5-12) is presented. For internal single point indications, the default status of
the indication (on, off, or undefined) after device reset can be selected as well (Figure
5-11).
Note that the possible properties of information for the system interface depend on the
facilities of transmission protocol. See also Section “Protocol Dependent Functions” in
the appendix.

7SD610 Manual 5-13


C53000-G1176-C145-1
Configuration

Output Indication
(OUT)

Figure 5-10 Information properties — example for the information type “Output Indication”
(OUT)

Internal Single
Point Indication
(IntSP)

Figure 5-11 Information properties — example for the information type “Internal Single Point
Indication” (IntSP)

5-14 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Singe Point
Indication (SP)

Figure 5-12 Information properties — example for information type “Single Point Indication”
(SP)

Double Point In addition to the properties entered for single point indications, a “Suppress interme-
Indication (DP) diate position” check box is available, which may be checked to suppress the interme-
diate indication during operations. If this field is marked, then the filter time, which can
also be set (see margin heading “Filtering/Contact Chatter Suppression” below), is
only effective for the intermediate (= undefined position) indication. Hence, briefly un-
defined conditions or contact chattering will not lead to an alarm; however, defined
changes in the condition (final positions) are immediately reported.

Figure 5-13 Information properties — example for information type “Double Point Indication”
(DP)

7SD610 Manual 5-15


C53000-G1176-C145-1
Configuration

Filtering/Contact For input indications (single point indications 63, double point indications '3), filter
Chatter Suppres- times may be entered (pick-up and drop-out delays) to suppress momentary changes
sion in potential at the binary input (e.g. contact chatter), refer also to Figure 5-12 and 5-
13. Filtering occurs during an input change of state, with the same setting values
whether coming or going. Information is only distributed when the new state continues
to exist after a preset time interval (in milliseconds). The setting range is from 0 to
86,400,000 ms, or 24 hours. Whether or not the filter interval is restarted for each
change of state during the filtering (filter re-triggering) is selectable.
It is also possible to set chatter suppression for each indication (Figure 5-12 and 5-13).
The contact chatter settings, themselves, are set the same for all input indications (see
Subsection 5.2.6).

User Defined Meas- For the information type “Measured Values User Defined” (098), the units, the conver-
ured Values (MVU) sion factor, and the number of significant digits following the decimal point may be
and Limit Values specified. For the information type “Limit Values User Defined” (/98), a limit value may
(LVU) be programmed (Figure 5-14).

Figure 5-14 Information properties example for information type “Limit Value User Defined”
(LVU)

If, for example, a low current reporter should be established using the CFC logic, and
the percentage of the measured current should be matched to a certain amp value,
the following values are entered in window according to Figure 5-14:
The 'LPHQVLRQ is A (amps). The &RQYHUVLRQ)DFWRU is 150: 150 A corresponds
to 100 % input current. The limit value upon start-up is set for 120 A.

Entering Your Own The available information in the configuration matrix is determined by the device type
Information and the configured functional scope. If necessary, you may extend the configuration
matrix to information groups or individual information defined and entered by yourself.

5-16 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Such user defined groups and information may be deleted at any time, in contrast to
predefined groups and information.
In order to insert a new information group, click on a cell within a group that is next to
the location where the new group should be located. After pressing the right mouse
button, a context menu appears (Figure 5-15).

Figure 5-15 Dialogue box to insert a new information group

If one of the first two alternatives is selected, a second dialogue box opens, in which
the name of the new information group is entered, in short text (display text) and in
long text (Figure 5-16). After clicking 2., the new group is positioned.

Figure 5-16 Entry of the name of a user defined information group

Information may be entered into the new information group using the information cat-
alog (Figure 5-17). The information catalog is found in the menu bar under the 9LHZ
option, or via an icon in the toolbar. User information may be entered into both the user
defined groups and any other available information group.

Figure 5-17 Information catalog window

7SD610 Manual 5-17


C53000-G1176-C145-1
Configuration

The information catalog is basically structured the same way as the DIGSI® 4 Manag-
er with folders and sub-folders. To proceed to information of sub-folders in the catalog,
click on a plus symbol or double-click on an folder icon. The designation of the initial
levels of the catalog correspond to the information groups $QQXQFLDWLRQV, &RP
PDQGV, 0HDVXUHG9DOXHV and &RXQWHU9DOXHV.
To insert a specific information unit into an information group, first select it in the cat-
alog, and using the left mouse button, it should then be dragged from the information
catalog window to a group area on the left of the matrix. After the mouse button is re-
leased, the new information unit is inserted into the proper group.
In order to change the user defined information, double-click on the field containing
the new information and edit the text.

Note:
When inserting information of the type &RQWUROZLWK)HHG%DFN, two new rows will
be created within the group: one line for the actual command, and one for the associ-
ated feedback message.

Deleting Groups Only user defined groups and information can be deleted. To delete an entire group,
and Information click on the field containing the group designator, then press the right mouse button to
open the context menu, and select 'HOHWH*URXS. A confirmation window will ap-
pear (Figure 5-18).

Figure 5-18 Confirmation window before deleting a user defined group

Click <HV if you actually want to delete the group.

Note:
When deleting a group, all information definitions within this group will be deleted.

To delete individual entries, click under ,QIRUPDWLRQ in the line with the entry to be
deleted. Then press the right mouse button to open the context menu, and select 'H
OHWH,QIRUPDWLRQ. The remaining steps are the same as those for deleting a
group.

5-18 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

5.2.4 Performing Configuration

The actual assignment between the information (rows) and the sources and destina-
tions (columns) of the information is made in the cell of intersection. You click into the
cell and press the right mouse button. A pull down menu appears where you may de-
termine the properties of the assignment. In certain cases, the pull down menu will of-
fer ; (allocated) or B (not allocated) as the configuration choices. In other cases, three
options will be offered (e.g. / = latched, 8 = unlatched, and B = not allocated). Entries
resulting in an implausible configuration are blocked and inaccessible to the user.

Configuring Binary Single point indications, double point indications, and pulse metered values can all be
Inputs as Sources configured as binary inputs. In addition, whether or not binary inputs are activated by
the presence of control voltage can be established. That is,
• “H” (High with voltage active): Control voltage at the binary input terminals activates
the indication;
• “/” (Low with voltage active): Control voltage at the binary input terminals deacti-
vates the indication.

Note:
A single logical indication shall not be configured to two binary inputs, since an OR-
combination of both signals is not ensured. The operating program allows only one
combination, and deletes the first combination when a second is established.

In addition, a single point indication cannot be configured to a binary input and to CFC
as a source at the same time. In this case, an error message would be displayed. Click
on 2., and select another configuration.

Figure 5-19 Error message resulting from double configuration

If a double point indication (DP) is configured to one binary input (e.g. feedback indi-
cations from switching devices), the next binary input is also set in the matrix. If this
configuration is undone, the second binary input is automatically de-configured.

Configuring a The four function keys on the front of the relay may also be configured as sources in
Function Key as a order to establish a link using CFC. In this situation, each function key may be linked
Source with one single internal indication. A function key may be occupied because it has al-

7SD610 Manual 5-19


C53000-G1176-C145-1
Configuration

ready been set as an operating function for the relay. As delivered from the factory,
the device’s function keys F1, F2, and F3 are pre-configured:

F1 operating messages

F2 primary measured values

F3 overview of the last eight fault messages

Note:
When an indication is configured to a function key, its factory-assigned function is de-
leted. Re-establishment of the factory default function of the F-keys is only possible
by initializing the relay with a new factory parameter set created within DIGSI ® 4. All
device settings have to be re-entered.

In order to configure a new indication, select one of the options (OPEN/CLOSE, ON/
OFF, etc.) from the indication group in the information catalog and drag it to the left
side of the matrix. Upon release, a new row appears in the matrix. If the mouse is po-
sitioned at the intersection of this row with column F, and the right mouse button is
pressed, a context menu opens (Figure 5-20) in which the function key may be set as
a source by clicking the proper choice.

Figure 5-20 Selecting a function key as an information source

Configuring CFC as If certain information should be created as a result of the implementation of a user de-
a Source fined logic function (CFC), this information must appear in the matrix as a source from
CFC. Otherwise, this information will not be available to the user when editing the CFC
logic.
You must not configure information to CFC as a source if it is already configured to a
binary input.

Configuring Binary Up to ten (10) information units (commands and indications) may be configured to one
Outputs as a binary output (output relay). One indication may be configured to up to ten (10) binary
Destination outputs (LEDs and output relays).
During configuration of binary outputs, you may select, for each output relay (besides
of the logic function itself), whether it should be latched (/) or unlatched (8). If you se-
lect latched, the output relay remains energized, even after the indication is no longer
present. It must be manually reset by pressing the LED Reset button on the front panel
of the device, or via a binary input with the indication function “!/('5HVHW”, or via
the serial system interface. If unlatched is selected, the output relay disengages as
soon as the indication disappears.

5-20 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Binary Outputs for A special case is the configuring binary outputs for switching devices. For switching
Switching Devices devices, the type of command (e.g., single or double commands, with or without feed-
back) is defined and configured to the output relay. If the preset command types are
not desired, then appropriate command types can be selected from the Information
catalog (see also “Entering Your Own Information” in the previous subsection) and in-
serted into the configuration matrix.

Example:
Double Command with
2 relays (acc. Table 5-1)

Figure 5-21 Window information catalog (example for different command types)

If a command with multiple outputs is configured, all binary outputs required in the ma-
trix for the configuration are automatically defined. If one of these outputs is de-con-
figured, all other binary outputs associated with the command will be automatically de-
configured.
Please pay attention to the comments and switching examples in Section 5.2.1, par-
ticularly the fixed defined sequence of relay assignments (TRIP before CLOSE).
When configuring commands, the context menu is dependent on the type of com-
mand. In some cases, the selection latched/unlatched is not available. Instead, the al-
ternatives are ; (configured), B (not configured), and ) (busy flag). The latter means,
independent of the switching direction, an indication is issued during each operation
of the switching device.
For double commands with a common output, a fourth alternative & (Common contact)
appears. Using this, one binary output may be defined as the common output (com-
mon contact). When this is the case, several double commands with common contacts
may be assigned to the same common output (common contact), thus saving binary
outputs. This assumes the signals at the common outputs have the same potential.
Using the 2EMHFW3URSHUWLHV dialogue window, additional properties for com-
mands issued to the switching device may be defined. Thus, the operating mode
(pulse or latched output of a switching command), the seal-in time for pulse com-
mands, the output delay of the command, and feedback monitoring may be set (see
Figure 5-22). The output delay is relevant for equipment which removes an indication
before the switching is completed.

7SD610 Manual 5-21


C53000-G1176-C145-1
Configuration

Figure 5-22 Dialogue box: object properties for a command with feedback

The conditional checks that should be conducted before execution of a switching com-
mand can also be defined:
• Device position (scheduled/actual): The switching command is ignored and a cor-
responding indication is issued if the switching device is already in the intended po-
sition. If this check is activated, switching direction control occurs not only for inter-
locked, but also for non-interlocked switching.
• Zone controlled (Bay Specific Interlocking): Logic functions created with CFC in the
relay are processed for interlocked switching.
• Blocked by protection: CLOSE commands to the switchgear are blocked as soon
as one of the protective functions or elements in the relay picks up. OPEN com-
mands, in contrast, can always be executed.
• Double operation: Parallel switching operations are blocked with respect to each
other: while one switching operation is being conducted, a second one cannot be
performed with the same switching object.
• Switching Authority – Local Commands: A local control switching command is only
allowed if local control is enabled on the relay (via lock-switch or setting).
• Switching Authority – Remote Commands: A remote control switching command is
only allowed if remote control is enabled on the relay (via lock-switch or setting).

Configuring a LED Single point indications (SP), output indications (OUT), and internal single point indi-
Display as a Desti- cations (IntSP) may be assigned to LEDs. When this is done, you may select whether
nation the indications are to be latched (/) or unlatched (8).
Up to ten (10) indications may be assigned to a LED display. One indication may be
assigned to a maximum of ten (10) outputs (LEDs and output relays).

5-22 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Configuring an Dependent on the type and version of a relay, a maximum of three indication buffers
Indication Buffer may be available for messages: Operation (Event Log) Buffer (2), Fault (Trip Log)
as a Destination Buffer (7) and Earth Fault Message Buffer (E). The indications from protective func-
tions are firmly assigned to these indication buffers. For the others, Table 5-2 provides
an overview of which indication type may be configured to which buffer.

Table 5-2 Overview of Indication Buffers

Information Type ↓ \Message Buffer → O E T


Single Point Indications (SP) X X
Double Point Indications (DP) X
Output Indications (OUT) X X
Internal Single Point Indications (IntSP) X X
Internal Double Point Indications (DP) X

Select one of the following options for the named indication types:
• 2 (on or coming) – the indication is stored in the buffer with the time of its arrival,
• 22 (on/off or coming/going) – the indication is stored in the buffer with the time of
its arrival and departure,
• B (not configured) – the indication is not stored in a buffer.

Configuring CFC Single point, double point, and output indications, as well as limit and measured val-
as a Destination ues, may be configured to CFC as the destination. This is a precondition for this infor-
mation being processed by CFC.

Configuring the In addition to the measured values available in the relay, user defined measured and
Measured Value limit values may be configured into the measured value window. These values also
Window as a Desti- become available in the device display in the assigned measurement window.
nation

Configuring the User defined pulse values derived from the measured values may be configured into
Metered Value the metered value window so that they may be displayed at the front relay panel.
Window as a
Destination

Retrieving Device Retrieving the configurations is also possible from the device front. You may access
Configurations configuration information under 0DLQ0HQX: → 6HWWLQJV → 0DVNLQJ ,2 .
from the Device
The menu title 0$6.,1* ,2 appears in the title bar. Configuration information re-
Front
garding each (physical) input and output is indicated in the display.
Any new user defined information is also shown in the display once loaded into the
relay from DIGSI® 4.
When selecting the 0$6.,1* ,2 menu, either binary inputs, LEDs, or binary out-
puts may be selected. Selection of binary inputs is illustrated in Figure 5-23.

7SD610 Manual 5-23


C53000-G1176-C145-1
Configuration

0$6.,1* ,2 



!%LQDU\,QSXWV²! %,1$5<,13876
!/('²! 
%LQDU\2XWSXWV²! !%LQDU\,QSXW²!²
!%LQDU\,QSXW²!²

Figure 5-23 Reading the configuration in the front display of the device — example

Information regarding a binary input may be displayed by using the navigation keys to
select the binary input. See Figure 5-24.

%,1$5<,1387

!!5HVHW/('63+


6WDWXVDW7HUPLQDO

Figure 5-24 Selection of binary input 2 — example

In the example of Figure 5-24, information is displayed regarding binary input 2. The
display for binary input 2 indicates that it is configured as reset of the latched LEDs
using a single point indication with voltage active (High). The present conditions of bi-
nary input 2 is also given as 0 (not active). If a binary input is active, a 1 is displayed.
Assignment of LEDs may be indicated at the relay, itself, using a replaceable labelling
strip with plain text on the front panel located, directly next to the LEDs.

Presettings The LED indication presettings, those of the binary inputs and outputs are summa-
rized in Appendix A, Section A.4.

5.2.5 Transferring Metering Values

The transferring of metered values from the buffer of a SIPROTEC® device to a sub-
station controller may be performed both cyclically and/or by external polling.
In the configuration matrix, click on 2SWLRQV and then on 5HVWRUH0HWHUHG9DO
XHV. A dialogue box, which contains a register for editing the individual values for cy-
clical transferring will open.

Cyclical Restora- Here, you may specify the source of the cyclical trigger for the transfer. Also, you may
tion set the time interval and determine whether the metered value buffer should be delet-
ed after transfer from the SIPROTEC® device has taken place.

5-24 7SD610 Manual


C53000-G1176-C145-1
Configuration of Information, Measured Values, and Commands

Figure 5-25 Dialogue box to restore metered values and program cyclical restoration

Triggering occurs based on the absolute time set according to the set time interval.

5.2.6 Settings for Contact Chatter Blocking

Contact Chatter The contact chatter filter checks whether the number of condition changes at a binary
Suppression input exceeds a preset value during a predetermined time interval. If this occurs, the
binary input will be blocked for a certain time, so the event list does not contain a large
number of unnecessary entries. The setting values necessary for this feature may be
entered in a dialogue box, as shown in Figure 5-26. This dialogue box can be found
from the open configuration matrix by clicking 2SWLRQV in the menu bar and then se-
lecting &KDWWHU%ORFNLQJ.

Figure 5-26 DIGSI® 4: Setting the chatter blocking feature

Defining the Moni- The operating mode of the chatter blocking feature is determined by five settings:
toring Criteria
• 1XPEHURISHUPLVVLEOHVWDWHFKDQJHV
This setting establishes how often the state of a binary input within the ,QLWLDO
7HVW7LPH may change. If this number is exceeded, the binary input is or remains
blocked. If the setting is 0 the chatter blocking is disabled.
• ,QLWLDOWHVWWLPH
Within this time interval (in seconds), the number of state changes of a binary input

7SD610 Manual 5-25


C53000-G1176-C145-1
Configuration

is checked. The time interval begins with the first activation of a signal to the binary
input.
• 1XPEHURIFKDWWHUWHVWV
This number represents how many check cycles should be conducted before the
binary input is finally blocked. Please consider that even a high set value can be
reached over the normal life span of the device and could lead to blocking of the
binary input. Therefore this value can also be set to infinity. For this, enter the char-
acter sequence of oo.
• &KDWWHU,GOH7LPH
If the 1XPEHURISHUPLVVLEOHVWDWHFKDQJHV at a binary input is exceeded
during the ,QLWLDOWHVWWLPH or the 6XEVHTXHQWWHVWWLPH, the &KDWWHU
LGOHWLPH interval is initiated. The affected binary input is blocked for this time
interval. The &KDWWHULGOHWLPH setting is entered in minutes. This settings can
only be programmed if the 1XPEHURIFKDWWHUWHVWV is not set to zero.
• 6XEVHTXHQWWHVWWLPH – Within this time interval, the number of state changes
at a binary input is checked again. This interval begins after the &KDWWHULGOH
WLPH interval has expired. If the number of state changes is within allowable limits,
the binary input is released. Otherwise, the idle interval is restarted, until the maxi-
mum 1XPEHUFKDWWHUWHVWV is reached again. The 6XEVHTXHQWWHVWWLPH
setting is entered in seconds. This settings can only be programmed if the 1XPEHU
RIFKDWWHU tests is not set to zero.
The settings for the monitoring criteria of the chatter blocking feature are set only once
for all binary inputs; however, the status of the chatter suppression can be set individ-
ually for each binary input. See “Filtering/Contact Chatter Suppression” in Subsection
5.2.3.

Note:
Chatter blocking cannot be activated for any of the standard protective indications.

The following should be noted:


• If there is contact chatter at a binary input and the input is blocked, the correspond-
ing indication will be displayed with “CCF” (example: “!'RRURSHQ&&)21”). Al-
so, the indication “&RQWDFWFKDWWHUILOWHU” reports this condition. Both mes-
sages are shown in the operating buffer (event log).
• Chattering of a single point indication is set as ON (coming) if the binary input is ac-
tivated by energization (configured High-active).
• Chattering of a single point indication is set as OFF (going) if the binary input is de-
activated by energization (configured Low-active).
• If this behaviour causes undesired results in individual situations, an interlocking
may be configured in CFC.
• Chattering of a double point indication will be considered as an “intermediate” con-
dition.

5-26 7SD610 Manual


C53000-G1176-C145-1
Creating User Defined Functions with CFC

5.3 Creating User Defined Functions with CFC

General The 7SD610 relay is capable of implementing user defined logic functions which may
be processed by the relay. This CFC feature (Continuous Function Chart) is needed
to process user defined supervision functions and logic conditions (e.g. interlocking
conditions for switching devices) or to process measured values. Interlocking condi-
tions and command sequences, for example, may be programmed, using pre-defined
function modules, by persons without any specialized software programming abilities.
A total of 21 types of functional modules (FM), with which the desired functions may
be composed, are saved in a library. Detailed explanations are in the CFC manual,
order number E50417–H1176–C098, or in the DIGSI® 4 manual, order number
E50417–H1176–C097.
The creation of a logical PLC function is performed by means of a personal computer
using application DIGSI® 4 and transferred via the operator or service interface. In or-
der to create user defined logic functions, the indications and measured values re-
quired by these functions must first be configured in the matrix with CFC as the source
or destination (see Section 5.2).
CFC can be started by double-clicking on &)&. The names of all available CFC charts
will appear. The desired CFC chart for processing can be selected via a double-click
of the mouse. The CFC program will start, and the chart will be displayed. If no chart
is available yet, you can create a new chart via the menu &UHDWH → &)&²&KDUW.

Run-Time Proper- The functions to be implemented in CFC may be divided into four task levels:
ties
• Measured values: This task is processed cyclically every 600 milliseconds
(09B%($5% = measurement value processing) and might become slower if the de-
vice is in pick-up state.
• System logic: Operation is triggered by events (i.e. these functions are processed
for each change of state at one of its inputs). System logic has lower priority than a
protection function and will be suppressed as soon as the relay picks up
(3/&B%($5% = slow PLC processing).
• Protective functions: These functions have the highest priority, and, like the system
logic functions, are event-controlled and processed immediately after a change of
state (3/&B%($5% = fast PLC processing).
• Switchgear Interlocking: This task is triggered by commands. In addition it is proc-
essed cyclically approximately every second. It might becomes slower if device is
in pick-up state (6)6B%($5% = interlocking).
The function to be implemented must be associated to one of these four task levels.
To implement a function from the 6HWWLQJV → &)& menu, activate the menu by se-
lecting (GLW, then 5XQ6HTXHQFH, and then the desired task level (See Figure 5-27).

7SD610 Manual 5-27


C53000-G1176-C145-1
Configuration

Figure 5-27 Establishing the task level

Within the Run Sequence menu, select (GLW, and then 3UHGHFHVVRUIRU,Q
VWDOODWLRQ, to ensure that the function modules selected from the library will be im-
plemented into the desired task level (Figure 5-28).

Figure 5-28 Assignment of function modules to the selected task level

The proper assignment is important for several reasons. For example, if interlocking
logic were to be set up in the measured values task level, indications would constantly
be created by the cyclical processing, filling the buffer unnecessarily. On the other
hand, the interlocking condition at the moment of a switching operation may not be
processed at the right time, since measured value processing is done only every
600 ms.

Table 5-3 Selection guide for function modules and task levels

Run-Time Level
Function Modules Description MW_BEARB PLC1_BEARB PLC_BEARB SFS_BEARB
Meter process. Slow PLC Fast PLC Interlocking

ABSVALUE Absolute value X – – –


AND AND-gate – X X X
BOOL_TO_CO Boolean to control (conversion) – X X –

5-28 7SD610 Manual


C53000-G1176-C145-1
Creating User Defined Functions with CFC

Table 5-3 Selection guide for function modules and task levels

Run-Time Level
Function Modules Description MW_BEARB PLC1_BEARB PLC_BEARB SFS_BEARB
Meter process. Slow PLC Fast PLC Interlocking

BOOL_TO_DI Boolean to double point (conversion) – X X X


BOOL_TO_IC Boolean to internal annunciation
(conversion)
BUILD_DI Create double point annunciation – X X X
CMD_INF Command information – – – X
CONNECT Connection – X X X
D_FF D-flipflop – X X X
DI_TO_BOOL Double point to boolean – X X X
LIVE_ZERO Live-zero, non linear curve X – – –
LOWER_SETPOINT Lower limit X – – –
NAND NAND-gate – X X X
NEG Negator – X X X
NOR NOR-gate – X X X
OR OR-gate – X X X
RS_FF RS-flipflop – X X X
SR_FF SR-flipflop – X X X
TIMER Timer – X X –
LONG_TIMER Long timer (max. 1193 h) – X X –
UPPER_SETPOINT Upper limit X – – –
X_OR XOR-gate – X X X
ZERO_POINT Zero suppression X – – –

Configuration The configuration is performed within the configuration sheets (see Figure 5-29).
Sheet

Configuration sheet 1
IS1 1
FM1

Input 3 1
FM2 FM3 Output
signals signals
IS2 2 3 1 2 OS4

IS3 2

Function modules

Figure 5-29 Principal representation of function modules in a CFC working page

7SD610 Manual 5-29


C53000-G1176-C145-1
Configuration

The left border column of the configuration sheet shows the inputs; the right border
column shows the outputs of a function. In the above diagram the inputs are connect-
ed with input signals IS1 to IS3. These may be indications from the breaker (via binary
inputs), from device function keys, or from a protective function. The output signal
(OS4 in the diagram) may control an output relay, for example, and can create entries
in the message buffers, depending on the preset configuration.

Configuring and The default run-time sequence is determined by the sequence of the insertion of the
Connecting Func- logic modules. You may redefine the run-time sequence by pressing <CTRL> – <F11>
tion Modules on the PC keyboard. Please refer to the CFC manual. The necessary function mod-
ules (FM) are contained in a library located to the right of the configuration chart. The
module also indicates to which of the four run-time levels it is assigned. The modules
possess at least one input and one output. In addition to these inputs and outputs,
which are displayed on the configuration sheet, a module may have additional inputs.
The additional inputs can be made visible by selecting the module title block, pressing
the right mouse button, selecting the menu option 1XPEHU2I,2V (see Figure
5-30), and then increasing the number.

Figure 5-30 Example of an OR gate: module menu

Under the 2EMHFW3URSHUWLHV menu, you may edit the name of the module, insert
a comment, or edit run-time properties and connection parameters.
Connecting modules with each other, and linking them with system input and output
signals, is performed by selection of the desired modules input or output and subse-
quently pressing the right mouse button, and selecting the menu option ,QVHUW&RQ
QHFWLRQWR2SHUDQG (see Figure 5-31).

Figure 5-31 Example of module input menu

5-30 7SD610 Manual


C53000-G1176-C145-1
Creating User Defined Functions with CFC

A window with a list of input signals will appear. By selecting one of these signals and
activating with 2., the selected signal is entered into the left border panel and, from
there, a connection is created to the module input. Selection of an output is done in
the same manner. A connection between two modules is established by a simple se-
quential clicking on the two connections.
If the link line display becomes unwieldy or impossible because of space limitations,
the CFC editor creates a pair of connectors (target icons) instead. The link is recog-
nizable via correlated numbering (see Figure 5-32).

Connector

Figure 5-32 Connector

Consistency check In addition to the sample configuration chart 1, other configuration sheets may exist.
The contents of any particular configuration sheet is compiled by DIGSI® 4 into a pro-
gram and processed by the protective device. For CFC charts developed by the user,
syntactic correctness can be verified by clicking the menu command &KDUW, and then
&KHFN&RQVLVWHQF\. The consistency check will determine if the modules violate
conventions of various task levels, or any of the space limitations described below.
Check of functional correctness must be performed manually.
The completed CFC chart can be saved via menu item &KDUW, and &ORVH. Likewise,
the CFC chart may be reopened and edited by clicking on &KDUW, selecting the appro-
priate chart, and clicking on 2SHQ.
Please note that certain limits and restrictions exist due to the available memory and
processing time required. For each of the four PLC task levels there is only a finite
processing time available within the processor system. Each module, each input to a
module (whether connected or not), each link generated from the border columns de-
mands a specific amount of processing time. The sum total of the individual process-
ing times in a task level may not exceed the defined maximum processing time for this
level.
The processing time is measured in so called TICKS. In the 7SD610 the following
maximum TICKS are permitted in the various task levels:

Table 5-4 Maximum number of TICKS in the task levels of 7SD610

Run-Time Level Limits in TICKS


0:B%($5% (Measured value processing) 10000

3/&B%($5% (Slow PLC processing) 1900

3/&B%($5% (Fast PLC processing) 200


6)6B%($5% (Interlocking) 10000

7SD610 Manual 5-31


C53000-G1176-C145-1
Configuration

In the following table, the amount of TICKS required by the individual elements of a
CFC chart is shown. A generic module refers to a module for which the number of in-
puts can be changed. Typical examples are the logic modules AND, NAND, OR, NOR.

Table 5-5 Processing times in TICKS required by the individual elements

Individual Element Amount of TICKS


Module, basic requirement 5
each input more than 3 inputs for generic modules 1
Connection to an input 6
Connection to an output signal 7
Additional for each configuration sheet 1

The utilized processor capacity which is available for the CFC can be checked under
2SWLRQ → 5HSRUWV in the register &KHFNFRQVLVWHQF\. By scrolling, an area is
reached, where information regarding the cumulated memory consumption of the
memory reserved for CFC can be read in percent. Figure 5-33 is an example showing
an over-utilization by 56 % in the task level PLC_BEARB (marked in the Figure), while
the other task levels are within the permissible range.

Figure 5-33 Read-out of the CFC configuration degree of utilization

If the limits are exceeded during configuration of the CFC, DIGSI® 4 issues a warning
(refer to Figure 5-34). After acknowledgement of this alarm, the system utilisation can
be viewed as described above.

5-32 7SD610 Manual


C53000-G1176-C145-1
Creating User Defined Functions with CFC

Figure 5-34 Warning message on reaching the limits

A few examples are given below.

Example 1 (MW): A configuration for low-current monitoring alarm (see Figure 5-35) which can be pro-
Low Current duced using CFC, should be a first example. This element may be used to detect op-
Monitor eration without load, or to recognize open circuited conditions. By connecting meas-
ured current values with a limit function via an OR function, an indication may be gen-
erated which can be used to cause switching operations.
• The configuration sheet is assigned to task level MW_BEARB.
• Four function modules (3 lower-value limit modules and an OR gate), are taken
from the function module library and copied into the configuration sheet.
• In the left panel, the measurement values to be monitored (IL1, IL2, IL3 in % of the
nominal current) are each selected and connected with the measured value inputs
of each limit module function.
• A lower limit setpoint value (IL<) is linked with the limit inputs of each of three limit
sensor functions.
• The limit value function outputs are passed on to the OR gate.
• The output of the OR gate is connected to the right border column at annunciation
“,DODUP”.
The limit value message is triggered when the preset limit value is below the setpoint
(low current) in at least one of the three phases. The hysteresis of the limit values is
fixed and need not be entered (5 % of set point plus 0.5 % of nominal value).

7SD610 Manual 5-33


C53000-G1176-C145-1
Configuration

Measurement FM:

Vol
IL1

Annunciation BO
Lower
Setpoint

Set points

Limit
IL<

Measurement FM:

Vol
IL2 FM:

Annunciation BO
Lower
Setpoint
>1 I<
alarm OUT

Limit
Set points
IL<

FM:
Measurement

Vol

Annunciation BO
IL3 Lower
Limit Setpoint

Set points
IL<

Figure 5-35 Under-current monitoring as an example of user defined measurement value


processing

Example 2: Interlocking logic (see Figure 5-36) is to be implemented for the operation of an isolat-
Isolation Switch ing switch using function key 4. The user must take the switch position indications of
Interlocking the corresponding isolation switch and the grounding switch into account. The CLOSE
and TRIP indications from the auxiliary contacts of each switch are used.
• Function modules NOR (2 required), XOR, and AND are taken from the library and
copied into the working page.
• The number of inputs of the AND gate is increased to 7.
• The CLOSE indications from the circuit breaker (CB) and from the grounding switch
(GS) are supplied to the inputs of the NOR functions.
• The OPEN indications from the circuit breaker (CB) and from the grounding switch
(GS) are supplied to the inputs of the AND function.
• The switch position indications from the disconnect switch (IS) are linked to the in-
puts of the XOR function.
• The outputs of the NOR and XOR gates are connected to the inputs of the AND
function.
• Function key 4 is linked with an input of the AND function.
• The output of the AND gate is linked to the right border column at the switching com-
mand “Disconnector Close”.

5-34 7SD610 Manual


C53000-G1176-C145-1
Creating User Defined Functions with CFC

Function
Key 4

CB is
CLOSED
≥1

CB is
OPEN

GS is ≥1
CLOSED
&
GS is Disconnector
OPEN Close

IS is
CLOSED
=1
IS is
OPEN

Door
is CLOSED

Figure 5-36 Interlocking an disconnect switch as an example of a user defined interlock pro-
tective function

Example 3 (PLC1): By using slow PLC processing, an additional, event-driven logic condition may be con-
Additional Logic structed which delivers indications regarding switch-gear operating status. These in-
dications may be passed externally via LEDs or relay contacts, or used as input sig-
nals for further logical links. In the example (see Figure 5-37), the output information
indication from the circuit breaker interlocking logic (CB TRIP) and a joint indication
from all protective element trip signals (Protection TRIP) are linked to a new “&LUFXLW
%UHDNHU2SHUDWLRQ” message. Furthermore, the single point indication (SP) 7HVW
2SHU, which may be coupled via a binary input, is linked with an internal reusable
“7HVWRSHU” message.

CB TRIP
≥1 Circuit Breaker
Protection TRIP
Operation

>Test Oper. Test Oper.

Figure 5-37 Additional logic as an example for a PLC_1 event-driven logic condition

7SD610 Manual 5-35


C53000-G1176-C145-1
Configuration

5.4 Serial Interfaces

The device contains one or more serial interfaces: an operator interface integrated into
the front panel, and — depending on the model ordered — a service interface and a
system interface for connection of a central control system. Certain standards are nec-
essary for communication via these interfaces, which contain device identification,
transfer protocol, and transfer speed.
Configuration of these interfaces is performed using the DIGSI® 4 software program.
Click on 6HWWLQJ in the navigation window and double-click in the data window on
6HULDO3RUWV. Next, select the specific data in the resulting dialogue box (Figure 5-
38). The dialogue box contains a varying number of tabs (depending on the capabili-
ties of the PC and the relay) with setting options for the interfaces.

Figure 5-38 DIGSI® 4, Settings of the PC interface

Serial port on PC In the first tab, you enter the communication interface of the PC which is connected to
the 7SD610 relay (&20&20 etc.). Manual entry of settings for data format and
baud-rate need not be made if these values were taken from the “RSHUDWRULQWHU
IDFH” tab or the “VHUYLFHLQWHUIDFH” tab (if present). In fact, many settings are
read from DIGSI® 4 directly via the interface, and the corresponding setting fields are
then inaccessible (see Figure 5-38). Alternatively, the option ,QGHSHQGHQWRIGH
YLFH may be selected.
Data exchange is monitored by the PC for the reaction times of the device. You may,
within preset limits, configure maximum relay reaction times. The displayed values
RQ 1 and RQ 2 correspond to the preset reaction times in milliseconds. In general,
these values should not be modified. Modification is only necessary if a time-out often
occurs during communication with the device. In order to modify these values, enter
an integer value for RQ 1, between 200 and 9999, and for RQ 2, from 0 to 9999.

5-36 7SD610 Manual


C53000-G1176-C145-1
Serial Interfaces

Service and Opera- Settings for the interfaces at the device can performed in these tabs. The link address-
tor Interface es and maximum message gap appear in the 6HUYLFH,QWHUIDFHand 2SHUDWRU
,QWHUIDFHtab besides the settings for data format and transfer speed (example Fig-
ure 5-39).

Figure 5-39 DIGSI® 4, Settings for the service interface — example

For the ,(& communication, each SIPROTEC® device must have a unique IEC ad-
dress assigned to it. Only the addresses which are within the current address range
and have not yet been occupied are displayed.
The setting for the maximum message gap is only applicable when the device is to
communicate using a modem via one of the interfaces. A gap is the maximum allow-
able time duration of interrupted transmission within one telegram transmission.
Transfer gaps are created when using modems as a result of data compression, error
correction, and baud-rate differences. For good data transmission between modems,
a setting of  sec is recommended. For poor connections, this value should be in-
creased.
Large values slow down communications in case of errors. When using a direct PC
connection, 0D[PHVVDJHJDSV may be set to  sec.

Note:
Do not use operator interface for modem communication!.

Other Interfaces Enter specific settings and addresses to identify devices in the other tabs, if neces-
sary, or check the preset values.

7SD610 Manual 5-37


C53000-G1176-C145-1
Configuration

Device addresses are used by the system to identify each device and must be unique
throughout the substation. Detailed instructions for setting the interfaces are available
in the “DIGSI® 4 Communications” manual.
If you desire to expand or modify interfaces later, refer to the modification instructions
for the interfaces, and if necessary for the hardware, see also instructions in Sub-sec-
tion 8.1.3 of this manual.

Profibus FMS on For a Profibus connection — if available — between a SIPROTEC® device and the
the PC SICAM® SAS or DIGSI® 4, a minimum transfer rate of 500 kBaud is recommended for
disturbance-free communication.

Signal Idle State For optical connections, the signal idle state is preset for “light off.” Modification of the
signal idle state is accomplished in the tab for the interface settings (see Figure 5-40).

Figure 5-40 Settings for an optical interface — example

Reading and Modi- Reading and partial modification of the most important interface settings is possible,
fying Interface Set- using the key-pad and display on the device panel. You may access the setting page
tings at the Device for the interface via 0$,10(18 through 6HWWLQJV → 6HWXS([WUDV → 6HULDO
3RUWV.
Under the sub-menu title 6(5,$/32576, you will find )URQW, 6\VWHP, and 6HUYLFH
3RUW, and selections may be made using the navigation button. By pressing the
button, the sub-menu for a particular interface can be accessed. The display and
the ability to change settings directly at the device are the same at both the front and
service interfaces. Figure 5-41 shows the data of the front (operator) interface, as an
example.

5-38 7SD610 Manual


C53000-G1176-C145-1
Serial Interfaces

)52173257

!3K\V$GGU!!!!!
!%DXGUDWH%DXG
3DULW\( ',*6,
*DSVVHF
Figure 5-41 Reading and setting the front interface at the device panel

The type and number of system interface(s) is dependent on the device type and ver-
sion and might be completely missing. The system interface data may be read at the
device, but cannot be modified there, whereas the data for the operator and service
interface can be modified. In addition to the settings already mentioned for the opera-
tor and service interfaces, the signal idle state for an optical link may also be read at
the device. For an electrical interface, the response “2))²6LJ,QDFWLYH” appears
as shown in Figure 5-42.

6<67(03257

!,(&²²²! ,(&²²
>3URILEXV²! 
!3K\V$GGUHVV!
!%DXGUDWH%DXG
3DULW\( ',*6,
*DSVVHF
2))²6LJ,QDFWLYH

Figure 5-42 Read-out of system interface setting values in the device display — example

7SD610 Manual 5-39


C53000-G1176-C145-1
Configuration

5.5 Date and Time Stamping

Integrated date and time stamping allows for the exact evaluation of sequence of
events, e.g. operational or fault messages (event log or trip log), or limit violations. The
following clock settings are available:
• Internal RTC clock (Real Time Clock),
• External synchronization sources (DCF, IRIG B, SyncBox, IEC 60870-5-103),
• External minute impulses via binary input.

Note:
The device is delivered from the factory with the internal RTC clock selected as the
time source.

For the differential protection with 7SD610 devices the time usually is synchronized in
only one device, the so-called “Timing Master” device; generally it is the device with
index 1. It synchronizes the other device via the protection communication. Thus it can
be assured that both devices of the protection system operate on the same time basis.
Note that this time synchronization is different from synchronization of the measured
values of the differential protection system. The operation of the differential protection
system including the synchronous exchange of measured values works automatically
and independent on this time synchronization.

Time Synchroniza- Settings for time synchronization may be found in DIGSI® 4 under 6HWWLQJV → 7LPH
tion V\QFKURQL]DWLRQ (Figure 5-43).

Figure 5-43 Setting Window in DIGSI® 4 – example

5-40 7SD610 Manual


C53000-G1176-C145-1
Date and Time Stamping

To open the 7LPH6\QFKURQL]DWLRQ )RUPDW window, double-click on 7LPH


6\QFKURQL]DWLRQ. See Figure 5-44.

Figure 5-44 Dialogue box for time synchronization and format in DIGSI® 4

You may select the time standard for internal time stamping from the following modes:

Table 5-6 Operating modes for time synchronization

Item Operating Mode Explanations


1 IQWHUQDO&ORFN Internal synchronization using RTC

2 ,(& ²² External synchronization using the system in-


terface and the IEC 60870–5–103 protocol

3 ,5,*%7LPHVLJQDO External synchronization using IRIG B

4 '&)7LPHVLJQDO External synchronization using DCF 77

5 SIMEAS time signal 6\QF%R[ External synchronization using SIMEAS Sync.


Box

6 3XOVHYLDELQDU\LQSXW External synchronization with pulse via binary


input

7 ,QWHUQDORU7LPLQJ0DVWHU

8 ,E& RU7LPLQJ0DVWHU
9 ,R,*%RU7LPLQJ0DVWHU as Item 1 to 6 but the time is normally synchro-
nized by the timing master; only in case if trans-
10 '&FRU7LPLQJ0DVWHU mission failure the time is synchronized by the
selected source
11 6\QFBR[RU7LPLQJ0DVWHU

12 %LQDU\LQSXWRU7LPLQJ0DV
WHU

7SD610 Manual 5-41


C53000-G1176-C145-1
Configuration

The RTC runs, even when the auxiliary voltage is absent, by means of an internal bat-
tery. During the device powering up, or if the auxiliary voltage has failed, this RTC is
the first synchronization source for the internal clock, independent of operating mode
selected.
In “,QWHUQDO” mode, the system time is controlled using only the RTC as the syn-
chronization source. It may be set manually. The procedure for manual date/time set-
ting is given in Section 7.2.1.
If an external source is selected, only the selected synchronization source is used. If
the source fails, the internal clock continues unsynchronized.
If time synchronization is to take place via a master control system, the option
,(&²²² must be selected (Figure 5-44).
When using radio clock signals, you must take into account that it can take up to three
minutes after device start-up or restored reception for the received time signal to be
decoded. The internal clock is not re-synchronized until then.
With IRIG B, the year must be set manually, because this standard does not include
a year value. Note: If in IRIG B the year date is erroneously set to a year date before
“1991”, the year is set to “1991” during the first synchronization.
For synchronization using pulses via a binary input, the present device time will ad-
vance to 00 seconds of the next minute for values greater than or equal 30 seconds
when the positive slope of the pulse arrives. For second values less than 30, the de-
vice time will be set to 00 seconds of the current minute. Because this signal is not
monitored, each pulse has a direct effect on the internal clock.
For the device wherein the time is normally synchronized by the “Timing Master”, set
one of the options adding “RUWLPLQJPDVWHU” (Item 7 to 12 in Table 5-6). The
indicated time is then only applied by the device if it does not receive a time from the
“Timing master”.

Synchronization The “Synchronization Offset” (7LPHFRUUHFWLRQ) setting allows correlation of the


Offset time signal received from the radio clock to local time (time zone). The maximum set-
table offset is ± 23 h 59 min = ±1439 min.

Error Message The tolerance time (0RQLWRULQJ / )DXOWLQGLFDWLRQDIWHU) for time synchroni-
Based on Toler- zation fault indicates how long cyclical synchronization may be absent until an alarm
ance Time is given.
External or internal synchronization normally occurs every minute. The setting for the
tolerance time must, therefore, always be at least two minutes. Under poor radio clock
reception conditions, you may delay the trigger of the “error” status condition even
longer.

Changing the Syn- When changing synchronization mode, the hardware will change over to the new
chronization Mode source within one second. This causes breakdown of cyclical synchronization, and the
internal clock will be disrupted — as at start-up — until the new synchronization
source takes over.
After modification to the synchronization offset in the time signal/operating mode, or
when changing year in IRIG B, the cyclical synchronization is not lost, but there is a
jump. To call attention to this, the time value causing a jump is reported with “7LPH

5-42 7SD610 Manual


C53000-G1176-C145-1
Date and Time Stamping

LQWHUUXSWLRQ21” — without the synchronization offset, and subsequently with


“7LPHLQWHUUXSWLRQ2))” — with the synchronization offset.

Operating Messag- After the “7LPHLQWHUUXSWLRQ21” message, the you must take into account that
es from the Timing the clock will jump. This message is issued under the following circumstances:
System
− if a synchronization interruption lasts longer than the tolerance time interval men-
tioned above, or as mentioned above, if the synchronization mode is changed;
− if a time jump is anticipated. The message itself is stamped with the old time.
The message “7LPHLQWHUUXSWLRQ2))” is triggered:
− when the synchronization is re-established (e.g., after a break in reception by the
radio clock);
− immediately after a time jump. This message is stamped with the new time after the
jump, thus allowing determination of the jump interval.

Time Format The time display may be set using either the European format (DD.MM.YYYY) or the
US format (MM/DD/YYYY).

7SD610 Manual 5-43


C53000-G1176-C145-1
Configuration

5-44 7SD610 Manual


C53000-G1176-C145-1
Functions 6
This chapter describes the numerous functions available in the SIPROTEC® 7SD610
relay. The setting options for each function are defined, including instructions for re-
porting setting values and formulae where required.

6.1 General 6-2


6.2 Differential Protection 6-23
6.3 Breaker Intertrip and Remote Tripping 6-36
6.4 Protection Data Interfaces and Differential Protection Topology 6-40
6.5 Direct Local Trip 6-47
6.6 Direct Remote Trip or Transmission of Binary Information 6-49
6.7 Instantaneous High-speed SOTF Protection 6-50
6.8 Time Overcurrent Protection 6-54
6.9 Automatic Reclosure 6-69
6.10 Circuit Breaker Failure Protection 6-95
6.11 Thermal Overload Protection 6-111
6.12 Monitoring functions 6-115
6.13 Function Control 6-127
6.14 Commissioning Tools 6-139
6.15 Ancillary Functions 6-141
6.16 Processing of Commands 6-148

7SD610 Manual 6-1


C53000-G1176-C145-1
Functions

6.1 General

A few seconds after the device is switched on, the initial display appears in the LCD.
In the 7SD610 the measured values are displayed.
The setting parameters can be entered via the keypad and display on the front of the
device, or by means of a personal computer connected to the front or service interface
of the device utilising the DIGSI® 4 software package. The level 5 password (individ-
ual parameters) is required.

From the Select the 0$,10(18 by pressing the MENU key. Using the key, select 6HWWLQJV,
Device Front and then press the key to navigate to the 6(77,1*6 display (see Figure 6-1).
In the 6(77,1*6 display, use the key to select the desired function, and then use
the key to navigate to that function (e.g., use the key to select the 36\VWHP
'DWD function, and then use the key to navigate to the 36<67(0'$7$display,
as shown in Figure 6-2.
In general, an item number appears in the menu list to the right of each selection. Nav-
igation can be accomplished using the item number in place of the and keys.
This feature is particularly helpful in large menus (e.g., setting lists). Based on the ex-
ample above, from the 0$,10(18, the 6(77,1*6 display can be reached by press-
ing 4 on the keypad, and then the 36<67(0'$7$ display can be reached by
pressing 0 3 on the keypad.

0$,10(18

$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²!
6HWWLQJV²! 6(77,1*6
7HVW'LDJQRVLV²! 
'HYLFH&RQILJ²!
0DVNLQJ ,2 ²!
36\VWHP'DWD²!
$FWLYH*URXSLV$

Figure 6-1 Example of navigation from the front control panel

Each setting contains a four-digit address number followed by the setting title as
shown in Figure 6-2. The value of the current setting is displayed in the line just below
the setting address number and title. The value may be text (Figure 6-2, setting )
or numerical (Figure 6-2, setting ).

36<67(0'$7$

&76WDUSRLQW
WRZDUGV/LQH
8QRP35,0$5<
N9

Figure 6-2 Example of power system data display

6-2 7SD610 Manual


C53000-G1176-C145-1
General

Settings are selected using the and keys. When the ENTER key is pressed, the
user is prompted for a password. The user should enter Password No. 5 and then
press the ENTER key. The current value of the setting appears in a text box, with a blink-
ing text insertion cursor.

Text Values A text setting may be modified using the and keys to select one of two or more
options.

Numerical Values A numerical setting may be modified by overwriting the current value using the numer-
(including ∞) ical keypad. See Figure 6-3. A value of “infinity” may be entered by pressing the dec-
imal key twice . . . The “∞”−symbol will appear in the display.
If the number entered is not within allowable limits, the maximum or minimum allow-
able value will appear in the lower portion of the display. To enter a new, allowable
value, the ENTER key should be pressed again.
Note that measured values and limit values must be entered in secondary quantities
when using the front control panel of the device.

Confirmation Any modification to a setting value must be confirmed by pressing the ENTER key. A
blinking asterisk is an indication that setting modification mode is still open. Other
modifications can be made to settings, even in sub-menus (if present), as long as set-
ting modification mode is still open. The actual modification of settings occurs once
setting modification mode is closed (see below, “Exiting the Setting Mode”).

Example for numerical setting:


36<67(0'$7$

!8QRP35,0$5< ENTER
!!N9

3:6HWWLQJV" Enter password No. 5 and confirm with


  ENTER


8QRP35,0$5< Enter the new value and confirm with ENTER

36<67(0'$7$[ The modified setting value appears in the


 list; a blinking asterisk in the title bar indi-
8QRP35,0$5< cates setting modification mode is still
> > > N9
open.
Figure 6-3 Example of setting modification using the front control panel

If a setting modification is not confirmed with the ENTER key, the original value reappears
after one minute, and a message window appears after three minutes notifying the
user that the setting modification period has expired. When the ENTER key is pressed, a
further message window appears, notifying the user that the setting modifications
were discarded. Further modification of settings is possible by pressing the ENTER key
and re-entering the password.

7SD610 Manual 6-3


C53000-G1176-C145-1
Functions

Exiting the Setting If an attempt is made to exit setting modification mode using the key or the MENU key,
Mode the message $UH\RXVXUH" will be displayed followed by the responses <HV1R
and (VFDSH (see Figure 6-4). If the response <HV is selected, modification of settings
can be confirmed by pressing the ENTER key. To cancel pending modifications to settings
and exit setting modification mode, the response 1R must be selected. Press the
key until the response 1Ris highlighted. Press the ENTER key to confirm and exit. Incor-
rect entries may be retracted in this manner. To remain in the setting modification
mode, press the key until the response (VFDSHis highlighted. Press the ENTER key
to confirm, and the user can remain in setting modification mode without down-loading
modifications.

$UH\RXVXUH"
ENTER
!<HV1R(VFDSH

6HWWLQJVDUHRN
!&RQWLQXH ENTER

Figure 6-4 Ending the setting mode using the front control panel

:
From PC with When using DIGSI® 4, the settings can be carried out 2IIOLQH. Double-click on
DIGSI® 4 3DUDPHWHUVto display the relevant selection.
Select the desired option, e.g. 3RZHU6\VWHP'DWD, in the right-hand panel of the
window and double-click it (Figure 6-5).

Figure 6-5 Parameterizing with DIGSI® 4 — an example

The dialogue box for defining the individual parameters of the selected function is dis-
played. In our example we selected 3RZHU6\VWHPGDWD (Figure 6-6). For exten-
sive functions, the parameters may be span several pages that can be accessed by
clicking on the tabs at the top border (in example Figure 6-6 3RZHUV\VWHP data and
%UHDNHU).

6-4 7SD610 Manual


C53000-G1176-C145-1
General

Figure 6-6 Power system data with DIGSI® 4 — an example

Each parameter has a 4-digit address number (under 1R) followed by the designation
of the parameter (under 6HWWLQJV). Column 9DOXH can contain a figure or text. If you
position the cursor in the column 9DOXH on a field with a numerical value, the admis-
sible input range will be indicated.
Click on the value which you want to alter.

Text Values A drop-down list with the possible statuses is displayed for text parameters. Click on
the desired option. The drop-down list closes and the new “value” appears in the text
field.

Numerical Values Numerical values are entered by direct input, if necessary with decimal comma (not
(incl. ∞) dot!). For infinite you enter two small letters “oo” one after the other. Confirm the input
with the button $FFHSW or proceed to a different value which you want to alter.
If the value entered is not within the admissible range of values or if a symbol has been
entered which is not admissible, a corresponding message will appear on the display.
After acknowledging with 2., the unaltered value is displayed. You can now make a
new input or alter a different parameter.

Primary or Second- Numerical values derived from measured quantities can be entered as either primary
ary Values or secondary values. DIGSI® 4 converts them automatically provided that the CT data
and the transformation ratios have been entered correctly.

7SD610 Manual 6-5


C53000-G1176-C145-1
Functions

To toggle between the input of secondary and primary values, proceed as follows:
q Click on 2SWLRQV in the menu bar (see Figure 6-7).
q Select the desired alternative by clicking on it.

Figure 6-7 Selecting the input of primary or secondary values - an example

Additional Settings Some parameters which are only used in exceptional cases or for special applications
may be hidden initially. They can be viewed if you click on 'LVSOD\$GGLWLRQDO
6HWWLQJV.

Confirmation Each entry may be confirmed by clicking $SSO\. Valid values are accepted automat-
ically when another field is selected.
The final acceptance of a modified setting takes place once the setting mode is exited
(see below “Exiting the Setting Mode”).
The dialogue box may be closed by clicking 2.. Once closed, another function may
be selected for setting modification, or you can exit the setting mode.

Exiting the Setting In order to transfer the modified setting values to the relay, the user should click on
Mode ',*6, → 'HYLFH. The user will be prompted for Password No. 5. After entering the
password and confirming with 2., data is transferred to the relay where modifications
become effective.

6-6 7SD610 Manual


C53000-G1176-C145-1
General

6.1.1 Power System Data 1

The device requires some plant and power system data in order to be able to adapt its
functions accordingly. The data required include for instance rated data of the station
and the measuring transformer, polarity and connection of the measured quantities, if
necessary features of the circuit breakers, and others. These data are grouped under
Power System Data 1.
Press MENU to open the main menu. Select the option 6(77,1*6with key and with
key the menu 6HWWLQJV. Select 3RZHU6\VWHP'DWD  in the menu 6(77,1*6
to enter the power system data.
With DIGSI® 4 double-click on 6HWWLQJV to display the relevant selection.

Polarity of the Cur- Address  &76WDUSRLQW asks for the polarity of the current transformers, i.e.
rent Transformers the position of the transformer star-point (Figure 6-8). The setting defines the measur-
ing direction of the device (current in line direction is defined as positive at both line
ends). The reversal of this parameter also reverses the polarity of the ground current
input IE.

Busbar

IL1 IE
IL2
IL3
IL1
IE IL2
IL3
Line Line
&76WDUSRLQW &76WDUSRLQW
/LQH %XVEDU
Figure 6-8 Polarity of the current transformers

Rated Quantities of In principle, the differential protection is designed such that it can operate without
the Instrument measured voltages. However, voltages can be connected. These voltages allow to
Transformers display and log voltages, and to calculate various components of power. If necessary,
they can also serve for determining the line voltage in case of automatic reclosure.
During configuration of the device functions (Section 5.1), it has been determined
whether the device is to work with or without measured voltages.
In the addresses  8QRP35,0$5< and  8QRP6(&21'$5< you inform the
device of the primary and secondary rated voltage (phase-to-phase) of the voltage
transformers. These settings are not relevant if no voltage transformers are connected
and configured when determining the functional scope according to Section 5.1.
In the addresses  &735,0$5< and  &76(&21'$5< you inform the device
of the primary and secondary rated currents of the voltage transformers (phases).
Address &76(&21'$5< must correspond to the nominal current of the device,
otherwise the processor system cannot be started. Also make sure that the secondary
rated CT currents are in accordance with the rated current of the device, because oth-
erwise the device will calculate wrong primary data.

7SD610 Manual 6-7


C53000-G1176-C145-1
Functions

The correct primary data are required for the calculation of the proper primary infor-
mation of the operational measured values. If the device is configured with primary
values using DIGSI® 4, these primary data are an indispensable requirement for the
fault-free operation of the device.

Connection of the Four inputs for measured voltages are available if the device is connected to the volt-
Voltages age transformers. This section is not relevant if no voltages are connected.
Three voltage inputs are connected to the voltage transformer set. Various possibili-
ties exist for the fourth voltage input U4:
• Connect the input U4 to the open delta winding e–n of the voltage transformer set,
see also Appendix A, Figure A-6:
Address  is set in that case to: 8WUDQVIRUPHU = 8GHOWDWUDQVIRUPHU.
With U4 connected to the e–n–windings of the voltage transformer set, the voltage
transformation of the transformer is normally

⁄ --------------
- ⁄ ---------------
U Nprim U Nsec U Nsec
-----------------
3 3 3

The factor Uph/Uen (secondary voltage, address  8SK8GHOWD) must be set
to 3/√3 = √3 ≈ 1.73. For other transformation ratios, e.g. for the calculation of the
residual voltage via interposed transformer set, the factor must be adapted accord-
ingly. This factor is important for the monitoring of measured quantities and the scal-
ing of the measured values and fault values.
• If the input U4 is not required, set:
Address  8WUDQVIRUPHU = QRWFRQQHFWHG.
In this case as well, the factor 8SK8GHOWD (address , see above) is im-
portant, since it is used for the scaling of the measured values and the fault values.

Connection of the The device has four measured current inputs, three of which are connected to the cur-
Currents rent transformer set. Various possibilities exist for the fourth current input I4:
• Connect the input I4 to the residual current of the CT star-point of the protected line
(standard circuit arrangement, see also Appendix A, Figure A-3):
Address  is set in that case to: ,WUDQVIRUPHU = 1HXWUDOFXUUHQWand
Address  ,,SK&7 = .
• Connect the input I4 to a separate ground current transformer of the protected line
(e.g. a summation current transformer, see also Appendix A, Figure A-4).
Address  is set in that case to: ,WUDQVIRUPHU = 1HXWUDOFXUUHQWand
Address  ,,SK&7 is set to:
Transformation of ground current transformer
I 4 ⁄ I ph CT = ------------------------------------------------------------------------------------------------------------------------
Transformation of phase current transformers

Example:
Phase-current transformer 500 A/5 A
Ground-leakage current transformer 60 A/1 A

60 ⁄ 1
I 4 ⁄ I ph CT = ----------------- = 0.600
500 ⁄ 5

6-8 7SD610 Manual


C53000-G1176-C145-1
General

• If the input I4 is not required, set:


Address  ,WUDQVIRUPHU = QRWFRQQHFWHG,
Address  ,,SK&7 is not relevant.
In this case, the neutral current is calculated from the sum total of the phase cur-
rents.

Rated Frequency The rated frequency of the network is set under address  5DWHG)UHTXHQF\.
The default setting is made in the factory in accordance with the design variant and
needs to be changed only if the device is to be used for a different purpose than or-
dered for. It can be set to  +] or  +].

Trip Command The minimum trip command duration 70LQ75,3&0' is set in address $. This
Duration duration is valid for all protection and control functions which can issue a trip com-
mand. It also determines the duration of a tripping pulse during the circuit breaker test
via the device. This parameter can only be changed with DIGSI® 4 under “Additional
Settings”.
The maximum duration of a closing command 70D[&/26(&0' is set in address
$. This setting is valid for all closing commands of the device. It also determines
the duration of a closing pulse during the circuit breaker test via the device. This du-
ration must be long enough to ensure that the circuit breaker has closed. There is no
risk in setting it too long, because the closing command is interrupted in any case as
soon as a protective function trips the circuit breaker again. This parameter can only
be changed with DIGSI® 4 under “Additional Settings”.

Circuit Breaker 7SD610 allows a circuit breaker test during operation by means of a tripping and a
Test closing command entered on the front panel or via DIGSI® 4. The duration of the com-
mands is set as explained above. Address  7&%WHVWGHDG determines the
time from the end of the tripping command until the beginning of the closing command
during the test. It should not be less than 0.1 s.

Current Transform- The basic principle of the differential protection assumes that all currents flowing into
er Characteristics a healthy protected section add up to zero. If the current transformer sets at the line
ends have different transformation errors in the overcurrent range, the sum of the sec-
ondary currents can reach considerable peaks due to the saturation of the transform-
ers when a short-circuit current flows through the line. These peaks may feign an in-
ternal short-circuit. The features included in the 7SD610 to prevent errors in case of
current-transformer saturation work completely satisfying if the protection knows the
response characteristic of the current transformers.
For this, the characteristic data of the current transformers and of their secondary cir-
cuits are set (see also Figure 6-15 in Subsection 6.2.1, page 6-25). The preset values
are adequate in most cases; they correspond to usual current transformers for protec-
tion purposes.
The rated accuracy limit factor n of the current transformers and the rated power PN
are usually stated on the rating plate of the current transformers. The information stat-
ed refers to reference conditions (rated current, rated burden). For example (accord-
ing to DIN 0414/Part 1 or IEC 60185)
Current transformer 10P10; 30 VA → n = 10; PN = 30 VA
Current transformer 10P20; 20 VA → n = 20; PN = 20 VA

7SD610 Manual 6-9


C53000-G1176-C145-1
Functions

The operational accuracy limit factor n’ is derived from this rated data and the actual
secondary burden P’:
n' PN + Pi
---- = -------------------
n P' + P i

with n’ = operational accuracy limit factor (effective accuracy limit factor)


n = rated accuracy limit factor of CTs (distinctive number behind P)
PN= rated burden of current transformers [VA] for rated current
Pi = inherent burden of the current transformers [VA] at rated current
P’ = actually connected burden (devices + secondary lines) [VA] at rated current

Usually, the inherent burden of current transformers is stated in the test report. If un-
known, it can be calculated roughly from the d.c. resistance Ri of the secondary wind-
ing.
P i ≈ Ri · I N 2
The ratio between the operational accuracy limit factor and the rated accuracy limit
factor n'/n is parameterized under address  .B$/).B$/)B1.
The CT error at rated current is set under address  ($/)$/)B1. It is equal
to the “current measuring deviation for primary rated current intensity F1” according to
DIN 0414/ Part 1 or IEC 60185. It is
– 1 % for a 5P transformer,
– 3 % for a 10P transformer.
The CT error for rated accuracy limit factors is set under address  (.B$/)B1.
It is derived from the number preceding the “P” of the transformer data.
With this data the device establishes an approximate CT error characteristic and cal-
culates the restraint (see also Section 6.2.1).

Exemplary calculation:
Current transformer 5P10; 20 VA
transformation 600 A/5 A
inherent burden 2 VA
Secondary lines 4 mm2 Cu
length 20 m
Device 7SD610 IN = 5 A
burden at 5 A 0.3 VA
The resistance of secondary lines is (with the resistivity for copper ρCu =
0.0175 Ωmm2/m)
2
Ωmm 20 m
R i = 2 ⋅ 0.0175 ------------------ ⋅ ----------------- = 0.175 Ω
2
m 4 mm
Here, the most unfavourable case is assumed, i.e. the current (as it is the case with
single-phase faults) flows back and forth via the secondary lines (factor 2). From that
the power for rated current IN = 5 A is calculated
Pi = 0.175 Ω · (5 A)2 = 4.375 VA
The entire connected burden consists of the burden of the incoming lines and the bur-
den of the device:

6-10 7SD610 Manual


C53000-G1176-C145-1
General

P’ = 4.375 VA + 0.3 VA = 4.675 VA


Thus the ratio of the accuracy limit factors is as follows
n' PN + Pi 20 VA + 2 VA
---- = ------------------- = -------------------------------------------- = 3.30
n P' + P i 4.375 VA + 2 VA

This leads to the following setting values:


Address  .B$/).B$/)B1 =  (from the calculation above)
Address  ($/)$/)B1 =  (from the accuracy for rated current)
Address  (.B$/)B1 =  (from 5 P10)
The presettings correspond to current transformers 10P with rated burden.
Naturally only those settings are sensible where address  ($/)$/)B1 is set
lower than address  (.B$/)B1.

Power Transformer If the protected object covers a power transformer with voltage regulation, a differen-
with Voltage Regu- tial current may occur even during normal healthy operation under steady-state con-
lation ditions. This differential current depends on the current intensity as well as on the po-
sition of the tap changer of the transformer. Since this current is current-proportional
it is meaningful to consider it like a current transformer error. You may calculate the
maximum differential current at the limits of the tap changer under nominal conditions
(referred to the mean current) and add it to the current transformer error as discussed
above (addresses  and ). This correction is performed only at that relay fac-
ing the regulated winding of the power transformer.

Exemplary calculation:
Transformer YNd5
35 MVA
110 kV/25 kV
Y–side regulated ±10 %
From this resulting:
rated current at nominal voltage I N = 184 A
rated current at UN + 10 % Imin = 167 A
rated current at UN – 10 % Imax = 202 A
I min + I max 167 A + 202 A
mean current value I mean = --------------------------- = ------------------------------------- = 184.5 A
2 2
The maximum deviation from this mean current is
I max – I mean 202 A – 184.5 A
max. deviation δ max = ------------------------------- = ------------------------------------------ = 0.095 = 9.5 %
I mean 184.5 A

This maximum deviation δmax [in %] is added to the current transformer errors as de-
terminded above, addresses  ($/)$/)B1 and  (.B$/)B1.
It must be considered that this deviation is referred to the mean current value between
the extrema of the tap changer position at rated apparent power, not to the current val-
ue at rated voltage and rated power. This demands a further correnction of the data of
the pretected object as discussed in Sub-section 6.1.3 under subtitle “Topological
Data for Transformers (optional)” (page 6-16).

7SD610 Manual 6-11


C53000-G1176-C145-1
Functions

6.1.1.1 Setting Overview

Note: The setting ranges and presettings listed in this table refer to a nominal current
value IN = 1 A. For a secondary nominal current value IN = 5 A the current values are
to be multiplied by 5. For setting primary values the transformation ratio of the trans-
formers also must be taken into consideration. The presetting of the nominal frequen-
cy corresponds to the nominal frequency according to the device version.

Addr. Setting Title Setting Options Default Setting Comments


201 CT Starpoint towards Line towards Line CT Starpoint
towards Busbar

203 Unom PRIMARY 0.4..800.0 kV 11.0 kV Rated Primary Voltage

204 Unom SECOND- 80..125 V 100 V Rated Secondary Voltage (L-L)


ARY

205 CT PRIMARY 10..5000 A 400 A CT Rated Primary Current

206 CT SECONDARY 1A 1A CT Rated Secondary Current


5A

210 U4 transformer not connected not connected U4 voltage transformer is


Udelta transformer

211 Uph / Udelta 0.10..9.99 1.73 Matching ratio Phase-VT To


Open-Delta-VT

220 I4 transformer not connected not connected I4 current transformer is


Neutral Current (of the pro-
tected line)

221 I4/Iph CT 0.010..5.000 1.000 Matching ratio I4/Iph for CT’s

230 Rated Frequency 50 Hz 50 Hz Rated Frequency


60 Hz

240A TMin TRIP CMD 0.02..30.00 sec 0.10 sec Minimum TRIP Command Dura-
tion
241A TMax CLOSE CMD 0.01..30.00 sec 1.00 sec Maximum Close Command Du-
ration

242 T-CBtest-dead 0.00..30.00 sec 0.10 sec Dead Time for CB test-autore-
closure

251 K_ALF/K_ALF_N 1.00..10.00 1.00 k_alf/k_alf nominal

253 E% ALF/ALF_N 0.5..50.0 % 5.0 % CT Error in % at k_alf/k_alf


nominal

254 E% K_ALF_N 0.5..50.0 % 10.0 % CT Error in % at k_alf nominal

6-12 7SD610 Manual


C53000-G1176-C145-1
General

6.1.2 Setting Groups

Purpose of Setting A setting group is a collection of setting values to be used for a particular application.
Groups In the 7SD610 relay, four independent setting groups (A to D) are possible. The user
can switch between setting groups locally, via binary inputs (if so configured), via the
operator or service interface using a personal computer, or via the system interface.
A setting group includes the setting values for all functions that have been selected as
(QDEOHG during configuration (see Chapter 5). Whilst setting values may vary among
the four setting groups, the selected functions of each setting group remain the same.
Multiple setting groups allows a specific relay to be used for more than one application.
While all setting groups are stored in the relay, only one setting group may be active
at a given time.
If multiple setting groups are not required, Group A is the default selection, and the
rest of this sub-section is of no importance.
If multiple setting groups are desired, address  *US&KJH237,21 must have
been set to (QDEOHG in the relay configuration. Refer to Chapter 5. Each of these sets
(A to D) is adjusted one after the other.

Copying Setting In most cases, only a few settings will vary from setting group to setting group. For this
Groups reason, an option exists to copy stored setting values from one setting group to anoth-
er setting group using DIGSI® 4:
To copy the setting values from setting group to another setting group, you should
highlight the setting group in the list whose setting values are to be copied. Next, go
to the menu bar, click on(GLW and select &RS\ (see Figure 6-9).

Figure 6-9 Copying a setting group in DIGSI® 4

7SD610 Manual 6-13


C53000-G1176-C145-1
Functions

The next step is to highlight the name of setting group in the list into which the setting
values should be copied. Go to the menu bar, click on (GLW and select 3DVWH. A con-
firmation box will appear (see Figure 6-10). Select <HV to copy the setting values.

Note:
All existing setting values in the setting group that has been copied to will be overwrit-
ten. An inadvertent copy operation can be reversed by closing and reopening the
DIGSI® 4 session without saving changes.

Figure 6-10 DIGSI® 4: Confirmation before copying a setting group

Setting groups may be copied more easily using the “Drag & Drop” feature. To use the
“Drag & Drop” feature, the name of the setting group in the list whose setting values
are to be copied should be highlighted. Holding down the left mouse button, the cursor
can then be dragged to the name of the setting group into which the setting values are
to be copied.
After copying setting groups, it is only necessary to modify those setting values that
are to be set differently.

Restoring Factory The factory settings may be restored for a modified setting group. To restore factory
Settings settings to a setting group, the name of the setting group whose settings are to be re-
stored is highlighted. Next, select the menu option (GLW and then click on 5HVHW. A
confirmation box appears, click on <HV to confirm restoration of factory settings.

Note:
All setting values in the setting group being restored to factory settings will be over-
written. An inadvertent reset operation can be reversed by closing and reopening the
DIGSI® 4 session without saving changes.

Switching between The procedure to switch from one setting group to another during operations is de-
Setting Groups scribed in Sub-section 7.2.2. The option of switching between several setting groups
externally via binary inputs is described in Subsection 8.1.2.

6-14 7SD610 Manual


C53000-G1176-C145-1
General

6.1.2.1 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


301 ACTIVE GROUP Group A Group A Active Setting Group is
Group B
Group C
Group D

302 CHANGE Group A Group A Change to Another Setting


Group B Group
Group C
Group D
Binary Input
Protocol

6.1.2.2 Information Overview

F.No. Alarm Comments


7 >Set Group Bit0 >Setting Group Select Bit 0
8 >Set Group Bit1 >Setting Group Select Bit 1

Group A Group A

Group B Group B

Group C Group C

Group D Group D

6.1.3 General Protection Data

General protection data (36<67(0'$7$) includes settings associated with all


functions rather than a specific protective or monitoring function. In contrast to the
36<67(0'$7$ as discussed in Sub-section 6.1.1, these settings can be changed
over with the setting groups. To modify these settings, select the 6(77,1*6 menu op-
tion *URXS$ (setting group A), and then 36\VWHP'DWD.
The other setting groups are *URXS%*URXS&, and *URXS', as described in
Subsection 6.1.2.

Rated Values of The statements under this subtitle refer to protected lines (cables or overhead lines) if
Protected Lines no power transformer is situated within the protected zone, i.e. for models without
transformer option or if the transformer option is disabled during configuration of the
scope of function (address  75$16)250(5 = 12, see Section 5.1). If a transform-
er is part of the protected zone, proceed with the next subtitle “Topological Data for
Transformers (optional)”.

7SD610 Manual 6-15


C53000-G1176-C145-1
Functions

With address  )XOO6FDOH9ROW you inform the device of the primary rated volt-
age (phase-to-phase) of the equipment to be protected. This setting influence the dis-
plays of the operational measured values in %.
The primary rated current (address  )XOO6FDOH&XUU) is that of the protected
object. For cables the thermal continuous current-loading capacity can be selected.
For overhead lines the rated current is usually not defined; set the rated current of the
current transformers (as set in address , Section 6.1.1). If the current transform-
ers have different rated currents at the ends of the protected object, set the highest
rated current value for both ends.
This setting will not only have an impact on the indication of the operational measured
values in per cent, but must also be exactly the same for both ends of the protect-
ed object, since it is the base for the current comparison at both ends.

Topological Data The statements under this subtitle apply to protected objects which cover a power
for Transformers transformer being situated within the protected zone, i.e. for models with transformer
(optional) option and if the transformer option is enabled during configuration of the scope of
function (address  75$16)250(5 = <(6, see Section 5.1). If no transformer is
part of the protected zone, this subtitle can be passed over.
The topological data make it possible to relate all measured quantities to the rated
data of the power transformer.
With address  )XOO6FDOH9ROW you inform the device of the primary rated volt-
age (phase-to-phase) of the transformer to be protected. This setting is also needed
for computing the current reference value of the differential protection. Therefore, it is
important to set the correct rated voltage for each end of the protected object
even if no measured voltages are connected to the relay.
In general, select the rated voltage of the transformer winding facing the device. But,
if the protected transformer is equipped with a voltage tap changer at one winding,
then do not use the rated voltage of that winding but the voltage that corresponds to
the means value of the currents at the ends of the control range of the tap changer. In
this way the fault currents caused by voltage regulation are minimized.

Exemplary calculation:
Transformer YNd5
35 MVA
110 kV/25 kV
Y–side regulated ±10 %
Thus resulting for the regulated winding (110 kV):
maximum voltage Umax = 121 kV
minimum voltage Umin = 99 kV
Setting value for the rated voltage at this side (address )
2 2
FullScaleVolt. = -------------------------------- = ---------------------------------------- = 108.9 kV
1 1 1 1
------------- + ------------ ------------------ + ---------------
U max U min 121 kV 99 kV

The 23(5$7,2132:(5 (address ) is the direct primary rated apparent power
for transformers and other machines. The same operation power value must be in-
dicated for both ends of the protected object since it is the basis for the current
comparison at both ends.

6-16 7SD610 Manual


C53000-G1176-C145-1
General

The power must always be entered as a primary value, even if the device is generally
configured in secondary values. The device calculates the rated current of the protect-
ed object from this power.
The 9(&725*5283, (address ) is the vector group of the power transformer,
always from the device’s perspective. The device which is used for the reference end
of the transformer, normally the one at the high voltage side, must keep the numerical
index  (default setting). The relevant vector group index must be stated for the other
winding.

Example:
Transformer Yd5
For the Y–end is set: 9(&725*5283,= ,
for the d–end is set: 9(&725*5283 , = .
If the other winding is chosen as reference winding, i.e. the d-winding, this has to be
taken into consideration:
For the Y–end is set: 9(&725*5283, =  (12 - 5),
For the d–end is set: 9(&725*5283, =  (5 – 5 = 0 = reference side).
Address  9(&725*52838is set in the same way as address 9(&725
*5283,.
If the vector group of the transformer is adapted with external means, e.g. because
there are matching transformers in the measuring circuit that are still used, set 9(&
725*5283, , at both ends. In this case the differential protection operates with-
out proper matching computation. Then the measuring voltages transmitted via the
transformer would not be adapted via the transformer and therefore not correctly cal-
culated and displayed. Address  9(&725*52838 serves to remove this dis-
advantage. Indicate the correct vector group of the transformer according to the
above-mentioned criteria.
Address  9(&725*5283, is therefore relevant for the differential protection,
whereas address  9(&725*52838 serves as a basis for the computation of
measured voltages beyond the transformer.
Address  75$16673,6 is used to set whether the power transformer starpoint
facing the device is grounded or not. If the starpoint is grounded, the device will elim-
inate the neutral current of the relevant side, since this neutral current may cause a
spurious tripping in case of a ground fault outside of the protected zone.

Circuit Breaker Various protection and ancillary functions require information on the status of the cir-
Status cuit breaker for faultless operation. The device has a circuit breaker status recognition
which processes the status of the circuit breaker auxiliary contacts and it also contains
a metrological opening and closing recognition (see also Section 6.13).
The cutoff current 3ROH2SHQ&XUUHQW, which safely falls short when the circuit break-
er pole is open, is set in address $. High sensitivity may be set if parasitic cur-
rents (e.g. from induction) can be excluded when the line is de-energized. Otherwise
the value must be increased correspondingly.
The seal-in time 6,7LPHDOO&O (address $) determines how long the pro-
tection functions that are effective when the line is energized (e.g. the increased pick-
up threshold for the differential protection) are enabled when the internal status rec-
ognition has recognized the closing of the breaker or when the device receives a sig-
nal via a binary input and the CB auxiliary contact that the circuit breaker has been

7SD610 Manual 6-17


C53000-G1176-C145-1
Functions

closed. Therefore, the seal-in time must be longer than the CB operating time during
the closing plus the command duration of the relevant protective function plus the CB
operating time during opening. This parameter can only be changed with DIGSI® 4 un-
der “Additional Settings”.
Address  /LQHVWDWXV determines the criteria for the functioning of the inte-
grated status recognition. With &XUUHQW2SHQ3ROH the rise of the residual current
above the threshold set in address $ (3ROH2SHQ&XUUHQW, see above) is inter-
preted as the closing of the circuit-breaker. &XUUHQW$1'&%, on the other hand,
means that both the currents and the position of the circuit-breaker auxiliary contacts
are processed for the status recognition. This means, that &XUUHQW$1'&%should
be set if the auxiliary contacts of the circuit breaker exist and are connected and allo-
cated to corresponding binary inputs, and &XUUHQW2SHQ3ROHin all other cases.
Note that the I>>>–stage of the instantaneous high-speed trip (see Section 6.7) can
only work if the auxiliary contacts for both devices at the ends of the protected object
are connected.
While the 6,7LPHDOO&O (address $, see above) becomes effective with
each energization of the line, 6,7LPH0DQ&O (address $) determines the time
during which a possible influence on the protection functions becomes effective after
the manual–closing (e.g. the switch-on pickup threshold for differential protection or
overcurrent protection, see loc cit). This parameter can only be changed with DIGSI®
4 under “Additional Settings”.

Three-Pole Three-pole coupling is only relevant if single-pole auto-reclosures are carried out. If
Coupling not, tripping is always three-pole. The rest of this subtitle is then irrelevant.
Address SROHFRXSOLQJ determines whether any multi-phase pickup leads
to a three-pole tripping command or whether only multi-pole tripping decision results
in a three-pole tripping command. This setting is only relevant for versions with single-
pole and three-pole tripping and is only available there. It does not have an impact on
the differential protection since pickup and tripping are equivalent. The time overcur-
rent protection function, however, can also pick up in the event of a short-circuit oc-
curred outside the protected object, without tripping. More information on the functions
is also contained in Section 6.13.3, “Fault Detection Logic of the Entire Device”.
With the setting ZLWK3LFNXS, each multiphase pickup causes a three-pole tripping,
even if only a single-phase ground fault has occurred in the protected area and a fur-
ther external fault, e.g. through overcurrent, is recognized. Even if a single-pole trip-
ping command is already present, each further pick-up will lead to a three-pole cou-
pling.
If, on the other hand, the address is set on ZLWK7ULS (normal setting for differential
protection), only multi-pole tripping commands will lead to a three-pole tripping. There-
fore, if a single-phase fault occurs within the protected zone and a further fault outside
of it, single-pole tripping is possible. A further fault during the single-pole tripping will
only lead to a three-pole coupling, if it occurs within the protected zone.
This parameter is valid for all protection functions of 7SD610 which are capable of
single-pole tripping. Standard setting: ZLWK7ULS.
Applying the time overcurrent protection function the difference is noticeable if multiple
faults occur, which means faults that nearly occur at the same time at different places
in the system.
If, for example, two single-phase ground faults occur on different lines — these may
also be parallel lines — (Figure 6-11), the protective relays of all four line ends detect

6-18 7SD610 Manual


C53000-G1176-C145-1
General

a fault L1–L2–E, i.e. the pickup image is consistent with a two-phase ground fault. But
since each of the two lines has only a single-phase fault, a single-phase auto-reclos-
ure on each of the two lines is desirable. This is possible with setting  SROH
FRXSOLQJ to ZLWK7ULS. Each of the four devices recognizes a single-pole internal
fault and is therefore able to perform a single-pole trip.

L1–E

L2–E

Figure 6-11 Multiple fault on a double-circuit line

In some cases, however, a three-pole trip would be preferable in this fault scenario,
e.g. if the double-circuit line is located next to a large generator unit (Figure 6-12). This
is because the generator considers the two single-phase ground faults as one double
ground fault, with correspondingly high dynamic stress of the turbine shaft. With 
SROHFRXSOLQJ set to ZLWK3LFNXS, the two lines are switched off, since each
device picks up as with L1–L2–E, i.e. as with a multi-phase fault.

L1–E

L2–E

Figure 6-12 Multiple fault on a double-circuit line next to a generator

Address $ 7ULSSK)OW determines that the short-circuit protection functions


perform only a single-pole trip in case of isolated two-phase faults (clear of ground),
provided that single-pole tripping is possible and permitted. This allows a single-pole
reclosure cycle for this kind of fault. The trip type can be set to SROHOHDGLQJ
SKDVH or SROHODJJLQJSKDVH. The parameter is only available in versions with
single-pole and three-pole tripping. This parameter can only be changed with DIGSI®
4 under “Additional Settings”. If this possibility is to be used, you have to bear in mind
that the phase selection should be the same throughout the entire network and that it
must be the same at all ends of one line. More information on the functions is also con-
tained in Section 6.13.3 “Fault Detection Logic of the Entire Device”. The usual default
setting is WULSOHSROH.

7SD610 Manual 6-19


C53000-G1176-C145-1
Functions

6.1.3.1 Setting Overview

Note: The setting ranges and presettings listed in this table refer to a nominal current
value IN = 1 A. For a secondary nominal current value IN = 5 A the current values are
to be multiplied by 5. For setting primary values, the transformation ratio of the trans-
formers must also be taken into consideration.

Add. Setting Title Setting Options Default Setting Comments


1106 OPERATION POWER 0.2..1000.0 MVA 7.6 MVA Operational power of protec-
tion zone

1161 VECTOR GROUP U 0..11 0 Vector group numeral for


voltage

1162 VECTOR GROUP I 0..11 0 Vector group numeral for


current

1163 TRANS STP IS Solid Earthed Solid Earthed Transformer starpoint is


Not Earthed

1103 FullScaleVolt. 0.4..800.0 kV 11.0 kV Measurement: Full Scale


Voltage (100%)

1104 FullScaleCurr. 10..5000 A 400 A Measurement: Full Scale


Current (100%)

1130A PoleOpenCurrent 0.05..1.00 A 0.10 A Pole Open Current Thresh-


old

1132A SI Time all Cl. 0.01..30.00 sec 0.10 sec Seal-in Time after ALL clo-
sures

1134 Line status with Pole Open Current with Pole Open Cur- Line status
Threshold only rent Threshold only
with CBaux AND Pole Open
Current

1150A SI Time Man.Cl 0.01..30.00 sec 0.30 sec Seal-in Time after MANUAL
closures

1155 3pole coupling with Pickup with Trip 3 pole coupling


with Trip

1156A Trip2phFlt 3pole 3pole Trip type with 2phase faults


1pole, leading phase
1pole, lagging phase

6-20 7SD610 Manual


C53000-G1176-C145-1
General

6.1.3.2 Information Overview

F.No. Alarm Comments


301 Pow.Sys.Flt. Power System fault

302 Fault Event Fault Event

351 >CB Aux. L1 >Circuit breaker aux. contact: Pole L1

352 >CB Aux. L2 >Circuit breaker aux. contact: Pole L2

353 >CB Aux. L3 >Circuit breaker aux. contact: Phase L3

356 >Manual Close >Manual close signal

357 >CloseCmd.Blo >Block all close commands from external

361 >FAIL:Feeder VT >Failure: Feeder VT (MCB tripped)

366 >CB1 Pole L1 >CB1 Pole L1 (Pos. Contact=Breaker)

367 >CB1 Pole L2 >CB1 Pole L2 (Pos. Contact=Breaker)

368 >CB1 Pole L3 >CB1 Pole L3 (Pos. Contact=Breaker)

371 >CB1 Ready >Circuit Breaker 1 READY for reclosing

378 >CB faulty >CB faulty (for breaker failure protection)

379 >CB 3p Closed >CB aux. contact 3pole Closed

380 >CB 3p Open >CB aux. contact 3pole Open

381 >1p Trip Perm >Single-phase trip permitted from ext.AR

382 >Only 1ph AR >External AR programmed for 1phase only

383 >Enable ARzones >Enable all AR Zones / Stages

385 >Lockout SET >Lockout SET

386 >Lockout RESET >Lockout RESET

410 >CB1 3p Closed >CB1 aux. 3p Closed (for AR, CB-Test)

411 >CB1 3p Open >CB1 aux. 3p Open (for AR, CB-Test)

501 Relay PICKUP Relay PICKUP

503 Relay PICKUP L1 Relay PICKUP Phase L1

504 Relay PICKUP L2 Relay PICKUP Phase L2

505 Relay PICKUP L3 Relay PICKUP Phase L3

506 Relay PICKUP E Relay PICKUP Earth

507 Relay TRIP L1 Relay TRIP command Phase L1

508 Relay TRIP L2 Relay TRIP command Phase L2

509 Relay TRIP L3 Relay TRIP command Phase L3

510 Relay CLOSE General CLOSE of relay

511 Relay TRIP Relay GENERAL TRIP command

512 Relay TRIP 1pL1 Relay TRIP command - Only Phase L1

7SD610 Manual 6-21


C53000-G1176-C145-1
Functions

F.No. Alarm Comments


513 Relay TRIP 1pL2 Relay TRIP command - Only Phase L2

514 Relay TRIP 1pL3 Relay TRIP command - Only Phase L3

515 Relay TRIP 3ph. Relay TRIP command Phases L123

530 LOCKOUT LOCKOUT is active

533 IL1 = Primary fault current IL1

534 IL2 = Primary fault current IL2

535 IL3 = Primary fault current IL3

536 Final Trip Final Trip

545 PU Time Time from Pickup to drop out

546 TRIP Time Time from Pickup to TRIP

560 Trip Coupled 3p Single-phase trip was coupled 3phase

561 Man.Clos.Detect Manual close signal detected

563 CB Alarm Supp CB alarm suppressed

6-22 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

6.2 Differential Protection

The differential protection is the main feature of the device. It is based on current com-
parison. For this, one device must be installed at each end of the zone to be protected.
The devices exchange their measured quantities via communications links and com-
pare the received currents with their own. In case of an internal short-circuit the allo-
cated circuit breaker is tripped.
7SD610 is designed for protected objects with 2 ends. A version which covers power
transformers or machines in unit connection is available as an option. The protected
zone is limited selectively at its ends by the current transformer sets.

6.2.1 Function Description

Basic Principle Differential protection is based on current comparison. It makes use of the fact that
e.g. a line section L (Figure 6-13) carries always the same current i (dashed line) at
its two ends in healthy operation. This current flows into on one side of the considered
zone and leaves it again on the other side. A difference in current marks is a clear in-
dication of a fault within this line section. If the actual current transformation ratio is the
same, the secondary windings of the current transformers CT1 and CT2 at the line
ends can be connected to form a closed electric circuit with a secondary current I; a
measuring element M which is connected to the electrical balance point remains at
zero current in healthy operation.
When a fault occurs in the zone limited by the transformers, a current I1 + I2 which is
proportional to the fault currents i1 + i2 flowing in from both sides is fed to the meas-
uring element. As a result, the simple circuit shown in Figure 6-13 ensures a reliable
tripping of the protection if the fault current flowing through the protected zone during
a short-circuit is high enough for the measuring element M to respond.

i i1 L i2 i
Station 1 Station 2
CT1 CT2
I i1 + i2 I
I1 I2

I1 + I 2

Figure 6-13 Basic principle of differential protection for a line

Transmission of If the entire protected object is located in one place — as is the case with generators,
Measured Values transformers, busbars —, the measured quantities can be processed immediately.
This is different for lines where the protected zone spans a certain distance from one
station to the other. To be able to process the measured quantities of both line ends

7SD610 Manual 6-23


C53000-G1176-C145-1
Functions

at each line end, these have to be transmitted in a suitable form. In this way, the trip-
ping condition at each line end can be checked and the respective local circuit breaker
can be operated if necessary.
7SD610 transmits the measured quantities as digital telegrams via communication
channels. For this, each device is equipped with a protection data interface.
Figure 6-14 shows this for a line. Each device measures the local current and sends
the information on its intensity and phase relation to the opposite end. The interface
for this communication between protection devices is called the protection data inter-
face. As a result, the currents can be added up an processed in each device.

1 2
i1 i2

I1 I2
I1 I1
I1 + I2 I1 + I2
I2 I2
7SD610 7SD610

Figure 6-14 Differential protection for a line

You will find detailed information on the topology of device communication in


Section 6.4.

Measured Value The devices measure the local currents asynchronously. This means that each device
Synchronization measures, digitizes and pre-processes the associated currents of the current trans-
formers with its own, random processor pulse. If the currents of two line ends are to
be compared, it is necessary, however, to process all currents with the same time
base.
Both devices exchange their time with each telegram. The device with index 1 func-
tions as a “timing master” thus determining the time base. The other device then cal-
culates the time delay from the transmission and processing times related on the tim-
ing master. With this rough synchronization the equality of the time bases with a pre-
cision of ± 0.5 ms is provided.
To reach a sufficiently precise synchronization all current values are marked with a
“time stamp” before they are transmitted from one device to the other as digital tele-
grams. This time stamp indicates at which point in time the transmitted current data
were valid. Therefore, the receiving device can carry through an ideal synchronization
of the current comparisons from the received time stamp and its own time manage-
ment, i.e. it can compare the currents (<5 µs tolerance) which were actually measured
at exactly the same time.
The transmission periods are permanently monitored by the devices with measuring
messages and considered at the respective receiving end.
The frequency of the measured quantities, which is decisive for the comparison of
complex phasors, is also continuously measured and, if necessary, corrected to
achieve a synchronous comparison of the phasors. If the device is connected to volt-
age transformers and at least one voltage of a sufficient level is available, the frequen-
cy is derived from this voltage. If not, the measured currents are used for the determi-
nation of the frequency. The measured frequencies are interchanged between the de-

6-24 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

vices via the communication link. Under these conditions both devices work with the
currently valid frequency.

Restraint The precondition for the basic principle of differential protection is that the sum total of
all currents flowing into the protected object is zero in healthy operation. This precon-
dition is only valid for the primary system and even there only if shunt currents of a
kind produced by line capacitances or magnetizing currents of transformers and reac-
tors can be neglected.
The secondary currents which are offered to the devices via the current transformers,
are subject to measuring errors caused by the response characteristic of the current
transformers and the input circuits of the devices. Transmission errors such as signal
jitters can also cause deviations of the measured quantities. As a result of all these
influences, the sum total of all currents processed in the devices in healthy operation
is not zero. The differential protection is stabilized against these influences.

Charging Currents Due to the capacitances of the three phases flowing against ground and against one
another, charging currents are present even in healthy operation and cause a differ-
ence of currents at the ends of the protected zone. Especially when cables are used,
the capacitive charging currents can reach considerable peaks.
Charging currents do not depend on the intensity of the measured currents. In healthy
operation they can be considered as being almost constant under steady-state condi-
tions, since they are only determined by the voltage and the capacitances of the lines.
They can therefore be taken into account during the setting of the sensitivity of the dif-
ferential protection (see also Section 6.2.2 under “Pickup Value of Differential Cur-
rent”). The same is true of the stationary magnetizing currents before shunt reactanc-
es. For transient inrush currents the devices have a separate inrush restraint (see be-
low under the subtitle “Inrush Restraint”).

Current To consider the influences of current transformer errors, each device calculates a self-
Transformer Errors stabilizing quantity ∆I. This is calculated by estimating the possible local transformer
errors from the data of the local current transformers and the intensity of the measured
currents. The transformer data have been parameterized under the power system
data (cf. Sub-section 6.1.1 under “Current Transformer Characteristics”) and are valid
individually for each device.

Ifault
IN

Approximation

Current Tansformer Error

n’/n Itransformer/IN
Figure 6-15 Approximation of the current transformer error

7SD610 Manual 6-25


C53000-G1176-C145-1
Functions

Further Influences Further measuring errors which can be caused in the device itself by hardware toler-
ances, calculation tolerances, deviations in time or which are due to the “quality” of the
measured quantities such as harmonics and deviations in frequency, are also estimat-
ed by the device and increase the local self-stabilizing quantity automatically. Here,
the permissible variations in the transmission and processing periods are also consid-
ered.
Deviations in time are caused by residual errors during the synchronization of meas-
ured quantities, transmission and operating time variations, and similar events.
If an influencing parameter cannot be determined — e.g. the frequency if no sufficient
measured quantities are available — it will be set by definition to the maximum per-
missible deviation. For the frequency this means that if the frequency cannot be deter-
mined, because no sufficient measured quantities are available, the device will as-
sume rated frequency. But since the actual frequency can deviate from the rated fre-
quency within the permissible range (±20 % of the rated frequency), the stabilization
will be increased automatically. As soon as the frequency has been determined (max.
100 ms), the stabilization will be decreased correspondingly. This is important during
operation if no measured quantities are existing in the protected area before a short-
circuit occurs, e.g. if a line with the voltage transformers on the line side is switched
onto a fault. Since the frequency is not yet known at this point of time, an increased
restraint will be active until the actual frequency is determined. This may delay the trip-
ping somewhat, but only at the pickup threshold, i.e. in case of very low-current faults.
These self-restraining quantities are calculated by each device from the sum total of
the possible deviations and transmitted to the other device. In the same way as the
total currents (differential currents) are calculated (see above, “Transmission of Meas-
ured Values“), each device calculates thus the sum total of the restraining quantities
and thereby stabilizes the differential currents.
It is due to the self-restraint that the differential protection works with a maximum of
sensitivity at all times, since the restraining quantities adapt themselves automatically
in a dynamic way to possible errors. In this way, even high-resistance faults with high
load currents at the same time, can be detected effectively.

Inrush Restraint If the protected area includes a power transformer, a high inrush current is to be ex-
pected when connecting the transformer. This inrush current flows into the protected
zone but does not leave it again.
The inrush current can reach a multiple of the rated current and is characterized by a
relatively high content in second harmonics (double rated frequency) which is almost
absent in the case of a short-circuit. If the content in second harmonics exceeds an
adjustable threshold in differential current, the tripping will be prevented.
The inrush restraint has an upper limit: if a certain (adjustable) current value is exceed-
ed, it will not be effective any more, since there must be an internal current-intensive
short-circuit.
Figure 6-16 shows a simplified logic diagram. The conditions for the inrush restraint
are examined in each device in which this function has been activated. The blocking
condition is transmitted to both devices so that it is effective at both ends of the pro-
tected object.

6-26 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

 ,1586+5(67
2II
„1“
2Q

QG+$5021,& 
fN
ILx
& Inrush detect. Lx
2fN

0$;,153($.
Lx = L1, L2, L3
depending on phase

Figure 6-16 Logic diagram of the inrush restraint for one phase

Since the inrush restraint works individually for each phase, the protection is fully ef-
fective even with the transformer switched onto a single-phase fault, whereas it is pos-
sible that an inrush current may be flowing in a different, healthy phase. It is, however,
possible to set the protection in a way that when the permissible harmonic content in
the current of only one single phase is exceeded, not only the phase with the inrush
current but also the remaining phases of the differential stage are blocked. This so-
called “crossblock” function can be limited in time. Figure 6-17 shows the logic dia-
gram.
The “crossblock” function affects both devices as well, since it extends the inrush re-
straint to all three phases.

Opposite end

Inrush detect. L1
≥1 Inrush block. L1

Inrush detect. L2
≥1 Inrush block. L2

Inrush detect. L3
≥1 Inrush block. L3

 &5266%+0

 &5266%/2&.
≥1 T &
1R
„1“
<HV

Figure 6-17 Logic diagram of the “crossblock” function for one end

7SD610 Manual 6-27


C53000-G1176-C145-1
Functions

Evaluation of The evaluation of measured values is performed separately for each phase. Addition-
Measured Values ally the earth current is evaluated.
Each device calculates a differential current from the total of the current phasors that
were formed at each end of the protected zone and transmitted to the other end. The
differential current value is equal to the value of the fault current that is registered by
the differential protection system. In the ideal case it is equal to the short-circuit current
value. In a healthy system the differential current value is low and nearly similar to the
charging current.
The stabilizing current counteracts the differential current. It is the total of the maxi-
mum measured errors at the ends of the protected object and is calculated from the
actual measured values and power system parameters that were set. Therefore the
highest possible error value of current transformers within the nominal range and/or
the short-circuit current range is multiplied with the current flowing through each end
of the protected object. The total value, including the measured internal errors, is then
transmitted to the other end. This is the reason why the stabilizing current is adequate
to the greatest possible measurement error of the differential protection system.
The pickup characteristic of the differential protection (Figure 6-18) derives from the
stabilizing characteristic Idiff = Irest (45°–curve) that is cut below the setting value ,
',))!. It complies with the formula

Irest = ,',))! + Σ (fault currents)


If the calculated differential current exceeds the pickup limit and the greatest possible
measurement error, the fault must be internal (hatched area in Figure 6-18)

Idiff

Tripping

,',))!

Irest

Figure 6-18 Pickup characteristic of the differential protection Idiff>–stage

6-28 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

Fast Charge Com- The charge comparison protection function is a differential stage which is part of the
parison current comparison (the actual differential protection). If a high-current fault occurs,
very fast tripping decision is then possible.
The charge comparison protection function does not sum up the complex current
phasors at the ends of the protected object, but the integral of currents calculated ac-
cording to the following formula:

t2

Q = ∫ i(t) dt
t1

It includes the integration interval from t1 to t2, for the 7SD610 device determined as
a quarter a.c. cycle.
The calculated charge Q is a scalar value which is easier to determine and to transmit
than a complex phasor.
The charges of both ends of the protected object are added in the same way as done
with the current phasors of the differential protection. Thus the total of the charges is
available at both ends of the protected zone.
Right after a fault occurrence within the protected zone a charge difference emerges.
For high fault currents that can lead to a saturation of current transformers a decision
is taken no later than the saturation begins.
The charge difference of external faults is theoretically equal to zero at the beginning.
The charge comparison protection function immediately registers the external fault
and blocks its own function. If saturation begins in one or more current transformers
which limit the protected zone, the before-mentioned function keeps being blocked.
Thus possible differences resulting from the saturation are excluded. Generally it is
assumed that an initial saturation of transformers only takes place after the expiration
of at least one integration interval (1/4 cycle) that commenced with the occurrence of
a fault.
Each phase is subject to the charge comparison. Therefore an internal fault (evolving
fault) in a different phase after the external fault occurred is registered immediately.
The limitation of the charge comparison is reached, if an internal fault (evolving fault)
coming after an external fault appears with considerable transformer saturation in the
same phase; this must be detected by the actual differential protection.
Furthermore the charge comparison is influenced by charge currents from lines and
shunt currents from transformers (steady-sate and transient) that also cause a charge
difference. Therefore the charge comparison is, as aforesaid, a function suited to com-
plete the differential protection ensuring a fast tripping for high-current short-circuits.

Blocking/Inter- The differential protection can be blocked via a binary input. The blocking at one end
blocking of a protected object affects via the communications link both ends (interblocking). If
the overcurrent protection is configured as an emergency function, both devices will
automatically switch over to this emergency operation.

Pickup of the Differ- Figure 6-19 shows the logic diagram of the differential protection. The phase-segre-
ential Protection gated stages are totalled to phase information. Additionally the device informs the user
which stage picked up.

7SD610 Manual 6-29


C53000-G1176-C145-1
Functions

As soon as the differential protection function registered a fault within its tripping zone,
the signal “'LII*HQ)OW” (general fault detection of the differential protection)
is issued. For the differential protection function itself, this pickup signal is of no con-
cern since the tripping conditions are available at the same time. This signal, however,
is necessary for the initiation of internal or external supplementary functions (e.g. fault
recording, automatic reclosure).

FNr 
!'LIIEORFN
see Figure 6-20

Diff>> L1

Diff>> L3
Diff>> L2
Qrest L1 –
Qrest L2 + Q>
Qrest L3
 ,',))!!
&
FNr 
Qdiff L1 ≥1
Q> ,'LII!!)OW
Qdiff L2
Qdiff L3

Irest L1 – FNr  ... 


Irest L2 + I> ≥1 'LII)OW/
Irest L3 'LII)OW/
 ,',))! 'LII)OW/

Idiff L1
Idiff L2
I>
≥1 & FNr 
≥1 ,'LII!)OW
Idiff L3
 ,',)!6:,7&+21

I> & Diff> L1


Diff> L2
Diff> L3
Rushblock. L1
Rushblock. L2 see Figure 6-20
Rushblock. L3
L1
L2
L3

Add on recognition

Figure 6-19 Logic diagram of the differential protection

Tripping Logic of The pickup signals that identify the concerned stages of the differential protection can
the Differential Pro- be delayed via the time stage 7,',)>. Independently from this condition, a single-
tection phase pickup can be blocked for a short time in order to bridge the transient oscilla-
tions on occurrence of a simple earth fault in a resonant-earthed system.
The output signals generated by the stages are combined to the output signals
“'LII*HQ75,3”, “'LII75,3S/”, “'LII75,3S/”, “'LII75,3S
/”, “'LII75,3/” in the tripping logic. Here, the single-pole information indi-
cates that only single-pole tripping is to be carried out. The actual generation of the
commands for the tripping (output) relay is executed in the tripping logic of the entire
device (see Section 6.13.4).

6-30 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

from Figure 6-19


Diff>> L1
FNr 
Diff>> L2 'LII*HQ75,3
Diff>> L3
 7,3+$6
L1 FNr 
L2 =1 T
'LII75,3S/
L3
FNr 
'LII75,3S/
 7'(/$<,',))!
L1 Tripping logic FNr 
T 0
L2 of the unit 'LII75,3S/
≥1
L3
&
FNr 
L1 L1
Diff> L1 'LII75,3/
from Figure 6-19

&
FNr 
L2 L2
Diff> L2 'LII75,3SROH

FNr 
&
'LII75,3SROH
L3 L3
Diff> L3

Figure 6-20 Tripping logic of the differential protection

6.2.2 Setting the Function Parameters

General The differential protection can be switched RQ or RII with address  67$7(2)
',)). If a single device is switched off at any end of a protective object, the calcula-
tion of measured values becomes impossible. The entire differential protection system
of both ends then is blocked.

Pickup Value of The current sensitivity is set with address  ,',))!. It is determined by the en-
Differential Current tire current flowing into a protected zone in case of a short-circuit. This is the total fault
current regardless of how it is distributed between the ends of the protected object.
This pick-up value must be set to a value that is higher than the total steady-state
shunt current of the protected object. For cables and long overhead lines, the charging
current is to be considered in particular. It is calculated from the service capacitance:
IC = 3.63 · 10-6 · UN · fN · CB' · s
With IC Charging current to be calculated in A primary
UN Rated voltage of the network in kV
fN Rated frequency of the network in Hz
CB' Per unit line length service capacitance of the line in nF/km or nF/mile
s Length of the line in km or miles

7SD610 Manual 6-31


C53000-G1176-C145-1
Functions

Considering the variations of voltage and frequency, the value set should be at least
two to two and a half times higher than the calculated charging current. Moreover, the
pick-up value should not be less than 15 % of the operating rated current. The oper-
ating rated current either derives from the rated apparent power of a transformer in the
protected area (see “Topological Data for Transformers (optional)” in Subsection
6.1.3, page 6-16) or from the addresses  )XOO6FDOH&XUU according to Sub-
section 6.1.3, “Rated Values of Protected Lines” (page 6-15). It must be equal at both
ends of the protected objects.
If the parameterization is performed from a personal computer using DIGSI® 4, the pa-
rameters can be set either as primary or as secondary quantities. If secondary quan-
tities are set, all currents must be converted to the secondary side of the current trans-
formers.

Exemplary calculation:
110 kV single-conductor oil-filled cable 240 mm2 in a 50-Hz-network with the data:
s (length) = 16 km
CB ’ = 310 nF/km
Current transformers 600 A/5 A
From that the steady-state charging current is calculated:
IC = 3.63 · 10-6 · UN · fN · CB' · s = 3.63 · 10-6 · 110 · 50 · 310 · 16 = 99 A
For the setting with primary values approximately the double value is to be set, i.e.:
Setting value ,',))! = 198 A
For the setting with secondary values this value has to be converted to secondary
quantity:
198 A
Setting value ,',))! = --------------- ⋅ 5 A = 1.65 A
600 A

Pickup Value dur- When switching on long, unloaded cables, overhead lines and arc-compensated lines,
ing Switch-on pronounced higher-frequency transient reactions may take place. Although these are
damped considerably by means of digital filters in the differential protection, a pickup
value ,',)!6:,7&+21 (address ) can be set to reliably prevent one-sided
pickup of the protection. This pickup value is always active when a device has recog-
nized the connection of its line end. For the duration of the seal-in time 6,7LPHDOO
&O which was set with the general protection data under address $ (Section
6.1.3), both devices are then switched over to this particular pickup value. A setting to
three or four times the steady-state charging current ensures usually the stability of
the protection during switch-on of the line. For switch-on of a transformer or shunt re-
actor, an inrush restraint is incorporated (see below under Subtitle “Inrush Restraint”,
page 6-33).
Final checks will be carried out during commissioning (see Section 8.3.11).

Delays In special cases of application it can be useful to delay the tripping of the differential
protection with an additional time stage, e.g. in case of reverse interlocking. The delay
time 7'(/$<,',))! (address $) is only started upon detection of an internal
fault. This parameter can only be changed with DIGSI® 4 under “Additional Set-
tings”.

6-32 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

If the differential protection is applied to an isolated or resonant-earthed network, it


must be ensured that the tripping is avoided during the transient oscillations of a
simple earth fault. With address $ 7,3+$6 the pickup to a simple earth fault
is therefore delayed for 0.04 s. In extended resonant-earthed networks this time
should be risen. Setting the address to ∞ the single-phase tripping is totally sup-
pressed. This parameter can only be changed with DIGSI® 4 under “Additional Set-
tings”.

Pickup Value of The pickup threshold of the charge comparison stage is set in address  ,
Charge Compari- ',))!!. The r.m.s. value of the current is decisive. The conversion into charge value
son Stage is carried out by the device itself.
Setting near the operational nominal current is adequate in most cases.
Since this stage reacts very fast, a pickup of capacitive charging currents (for lines)
and inductive magnetizing currents (for transformers or reactors) — also for switch-on
operation — must be excluded.
For overhead lines and cables the setting value should not be lower than 4 times the
steady-state charging current value (as already calculated in the above calculation ex-
ample). In resonant-earthed systems also the value of the non-compensated system
earth fault current may not be undershot. It derives from the total capacitive earth fault
current without considering the Petersen coil. As the Petersen coil serves to compen-
sate nearly the total earth fault current, its rated current can be taken as a base.
For transformers set the value INTrafo/ukTrafo.
The pickup thresholds are finally checked during commissioning (Section 8.3.11).

Inrush Restraint The inrush restraint of the differential protection is only necessary when the devices
are operated on a transformer or on lines which end on transformers. It can be
switched RQ and RII with address  ,1586+5(67.
It is based on the evaluation of the second harmonic which exists in the inrush current.
Ex-works a ratio of  % of the QG+$5021,& I2fN/IfN is set under address ,
which can normally be taken over. The fraction necessary for the stabilization can
however be configured. In order to be able to achieve a higher degree of restraint in
case of exceptionally unfavourable inrush conditions, you may also set a smaller val-
ue.
However, if the local measured current exceeds a value set in address  0$;,1
586+3($., there will be no inrush restraint. The peak value is decisive. The value
should be higher than the maximum inrush current peak value that can be expected.
For transformers a value of above √2·INTrafo/ukTrafo can be set. If a line ends on a
transformer, a smaller value may be selected, considering the damping of the current
by the line.
The “crossblock” function can be activated (<HV) or deactivated (1R) with address
 &5266%/2&.. The time after exceeding of the current threshold for which this
crossblock is to be activated is set under address  &5266%+0. With setting ∞
the “crossblock” function is always active until the second harmonic content in all
phases has dropped below the set value.

7SD610 Manual 6-33


C53000-G1176-C145-1
Functions

6.2.3 Setting Overview

Note: The indicated setting ranges and default settings refer to a secondary rated cur-
rent of IN = 1 A. For the secondary rated current of IN = 5 A these values are to be
multiplied by 5. For the setting of primary values the transformation ratio of the trans-
formers must also be taken into consideration.

Addr. Setting Title Setting Options Default Setting Comments


1201 STATE OF DIFF. OFF ON State of differential protection
ON

1210 I-DIFF> 0.10..20.00 A 0.30 A I-DIFF>: Pickup value

1213 I-DIF>SWITCH ON 0.10..20.00 A 0.30 A I-DIFF>: Value under switch on


condition

1217A T-DELAY I-DIFF> 0.00..60.00 sec; ∞ 0.00 sec I-DIFF>: Trip time delay

1218A T3I0 1PHAS 0.00..60.00 sec; ∞ 0.00 sec Delay 1ph-faults (comp/isol.
star-point)

1233 I-DIFF>> 0.8..100.0 A 1.2 A I-DIFF>>: Pickup value

2301 INRUSH REST. OFF OFF Inrush Restraint


ON

2302 2nd HARMONIC 10..45 % 15 % 2nd. harmonic in % of funda-


mental

2303 CROSS BLOCK NO NO Cross Block


YES

2305 MAX INRUSH 1.1..25.0 A 15.0 A Maximum inrush-peak value


PEAK

2310 CROSSB 2HM 0.00..60.00 sec; ∞ 0.00 sec Time for Crossblock with 2nd
harmonic

6.2.4 Information Overview

F.No. Alarm Comments


3102 2nd Harmonic L1 Diff: 2nd Harmonic detected in phase L1
3103 2nd Harmonic L2 Diff: 2nd Harmonic detected in phase L2
3104 2nd Harmonic L3 Diff: 2nd Harmonic detected in phase L3
3120 Diff active Diff: Active
3132 Diff. Gen. Flt. Diff: Fault detection
3133 Diff. Flt. L1 Diff: Fault detection in phase L1
3134 Diff. Flt. L2 Diff: Fault detection in phase L2

6-34 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

F.No. Alarm Comments


3135 Diff. Flt. L3 Diff: Fault detection in phase L3
3136 Diff. Flt. E Diff: Earth fault detection
3137 I-Diff>> Flt. Diff: Fault detection of I-Diff>>
3139 I-Diff> Flt. Diff: Fault detection of I-Diff>
3141 Diff. Gen. TRIP Diff: General TRIP
3142 Diff TRIP 1p L1 Diff: TRIP - Only L1
3143 Diff TRIP 1p L2 Diff: TRIP - Only L2
3144 Diff TRIP 1p L3 Diff: TRIP - Only L3
3145 Diff TRIP L123 Diff: TRIP L123
3146 Diff TRIP 1pole Diff: TRIP 1pole
3147 Diff TRIP 3pole Diff: TRIP 3pole
3148 Diff block Diff: Differential protection is blocked
3149 Diff OFF Diff: Diff. protection is switched off
3176 Diff Flt. 1p.L1 Diff: Fault detection L1 (only)
3177 Diff Flt. L1E Diff: Fault detection L1E
3178 Diff Flt. 1p.L2 Diff: Fault detection L2 (only)
3179 Diff Flt. L2E Diff: Fault detection L2E
3180 Diff Flt. L12 Diff: Fault detection L12
3181 Diff Flt. L12E Diff: Fault detection L12E
3182 Diff Flt. 1p.L3 Diff: Fault detection L3 (only)
3183 Diff Flt. L3E Diff: Fault detection L3E
3184 Diff Flt. L31 Diff: Fault detection L31
3185 Diff Flt. L31E Diff: Fault detection L31E
3186 Diff Flt. L23 Diff: Fault detection L23
3187 Diff Flt. L23E Diff: Fault detection L23E
3188 Diff Flt. L123 Diff: Fault detection L123
3189 Diff Flt. L123E Diff: Fault detection L123E
3190 Test Diff. Diff: Set Teststate of Diff. protection
3191 Comm. Diff Diff: Set Commissioning state of Diff.
3192 TestDiff.remote Diff: Remote relay in Teststate
3193 Comm.Diff act. Diff: Commissioning state is active
3194 >Test Diff. Diff: >Test Diff.
3195 >Comm. Diff Diff: >Comm. Diff
3525 > Diff block >Differential protection blocking signal
3526 Diffblk.rec PI1 Differential blocking received at PI1
3528 Diffblk.sen PI1 Differential blocking sending via PI1

7SD610 Manual 6-35


C53000-G1176-C145-1
Functions

6.3 Breaker Intertrip and Remote Tripping

7SD610 allows to transmit a tripping command created by the local differential protec-
tion to the other end of the protected object (intertripping). Likewise, any desired com-
mand of another internal protection function or of an external protection, monitoring or
control equipment can be transmitted for remote tripping.
The reaction when such a command is received can be set individually for each de-
vice.
Commands are transmitted separately for each phase, so that a simultaneous single-
pole auto-reclosure is always possible, provided that devices and circuit-breakers are
designed for single-pole tripping.

6.3.1 Function Description

Transmission The transmission signal can originate from two different sources (Figure 6-21). If the
Circuit parameter ,75,36(1' is set to <HV, each tripping command of the differential pro-
tection is routed immediately to the transmission function “ITrp.sen. L1” to “...L3” (in-
tertrip) and transmitted to the protection data interfaces via the communications links.
Furthermore, it is possible to trigger the transmission function via binary inputs (re-
mote tripping). This can be done either separately for each phase via the input func-
tions “!,QWHUWULS/”, “!,QWHUWULS/” and “!,QWHUWULS/”, or for all phases
together (three-pole) via the binary input function “!,QWHUWULSSRO”. The transmis-
sion signal can be delayed with 7,75,3%, and prolonged with 7,75,3352/%,.

 7,75,3%,
,75,36(1'   7,75,3352/%,

1R
Diff TRIP L1 <HV
Diff TRIP L2
Diff TRIP L3
≥1
ITrp.sen. L1
>Intertrip L1 T T
>Intertrip L2 ≥1 ITrp.sen. L2
ITrp.sen. L3
>Intertrip L3

L1
L2
L3

>Intertrip 3pol

Protection Protection
Data Interface Data Interface

Figure 6-21 Logic diagram of the intertrip — transmission cycle

6-36 7SD610 Manual


C53000-G1176-C145-1
Breaker Intertrip and Remote Tripping

Receiving Circuit On the receiving end the signal can lead to a trip. Alternatively it can also cause only
an alarm.
Figure 6-22 shows the logic diagram. If the received signal is supposed to cause a trip,
it will be forwarded to the tripping logic. The tripping logic of the device (see also Sec-
tion 6.13.4) ensures, if necessary, that the conditions for single-pole tripping are ful-
filled (e.g. single-pole tripping permissible, auto-reclosure device ready).

)1R
 ,75,35(&
ITrp.TRIP 1p L1
)1R
ITrp.TRIP 1p L2
7ULS )1R
≥1 ITrp.TRIP 1p L3
$ODUP Tripping logic
Protection Data )1R
Interface
ITrp.TRIP L123
)1R
ITrp.TRIP 1pole
)1R
ITrp.TRIP 3pole
)1R
ITrip. Gen. TRIP

)1R
I-TRIP REC PIx L1
L1 I-TRIP REC PIx L2
L2 I-TRIP REC PIx L3
L3 [ 
Figure 6-22 Logic diagram of the intertrip — receiving cycle

Further Options Since the signals for remote tripping can be set to cause only an alarm, any other de-
sired signals can be transmitted in this way as well. After the binary input(s) have been
activated, the signals which cause an alarm at the receiving end are transmitted.
These alarms can in turn execute any desired actions at the receiving end.It should be
noted that for the transmission of remote commands or alarms a further 4 fast trans-
mission channels are optionally available (see also Section 6.6).

6.3.2 Setting the Function Parameters

General Informa- The intertrip function for tripping caused by the differential protection can be activated
tion (<HV) or deactivated (1R) with address  ,75,36(1'. Since the differential pro-
tection devices theoretically operate with the same measured values at both ends of
the protected object, a tripping in the event of an internal fault normally is also carried
out at both ends, regardless of the infeed conditions at the ends. In special cases, i.e.
if short-circuit currents are to be expected near to the pickup threshold, it may occur
that one end do not issue a tripping command due to inevitable device tolerances. For
these cases ,75,36(1' <HVensures the tripping at both ends of the protected
object.

7SD610 Manual 6-37


C53000-G1176-C145-1
Functions

Intertrip/Remote If the intertrip function is activated, it will automatically start when the differential pro-
Tripping tection trips.
If the relevant binary inputs are allocated and activated by an external source, the in-
tertrip signal is transmitted as well. In this case, the signal to be transmitted can be
delayed with address  7,75,3%,. This delay stabilizes the transmitted signal
against dynamic interferences which may possibly occur on the control lines. Address
 7,75,3352/%, is used to extend a signal which was effectively injected
from an external source.
The reaction of a device to receiving an intertrip/remote tripping signal is set in ad-
dress  ,75,35(&(,9(. If it is supposed to cause tripping, 7ULS must be set.
If the received signal, however, is supposed to cause only an alarm, $ODUPRQO\
must be set even if this annunciation is to be processed externally.
The setting times depend on the individual case of application. A delay is necessary if
the external control signal originates from a disturbed source and a stabilization
seems appropriate. Of course, the control signal has to be longer than the delay for
the signal to work. If the signal is processed externally at the receiving end, a prolon-
gation time might become necessary for the transmitting end so that the reaction de-
sired at the receiving end can be executed reliably.

6.3.3 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


1301 I-TRIP SEND YES NO State of transmit. the intertrip
NO command

1302 I-TRIP RECEIVE Alarm only Trip Reaction if intertrip command is


Trip receiv.

1303 T-ITRIP BI 0.00..30.00 sec 0.02 sec Delay for intertrip via binary in-
put

1304 T-ITRIP PROL BI 0.00..30.00 sec 0.00 sec Prolongation for intertrip via
bin.input

6-38 7SD610 Manual


C53000-G1176-C145-1
Breaker Intertrip and Remote Tripping

6.3.4 Information Overview

F.No. Alarm Comments


3501 >Intertrip L1 I.Trip: >Intertrip L1 signal input

3502 >Intertrip L2 I.Trip: >Intertrip L2 signal input

3503 >Intertrip L3 I.Trip: >Intertrip L3 signal input

3504 >Intertrip 3pol I.Trip: >Intertrip 3 pole signal input

3505 ITrp.rec.PI1.L1 I.Trip: Received at Prot.Interface 1 L1

3506 ITrp.rec.PI1.L2 I.Trip: Received at Prot.Interface 1 L2

3507 ITrp.rec.PI1.L3 I.Trip: Received at Prot.Interface 1 L3

3511 ITrp.sen.PI1.L1 I.Trip: Sending at Prot.Interface 1 L1

3512 ITrp.sen.PI1.L2 I.Trip: Sending at Prot.Interface 1 L2

3513 ITrp.sen.PI1.L3 I.Trip: Sending at Prot.Interface 1 L3

3517 ITrp. Gen. TRIP I.Trip: General TRIP

3518 ITrp.TRIP 1p L1 I.Trip: TRIP - Only L1

3519 ITrp.TRIP 1p L2 I.Trip: TRIP - Only L2

3520 ITrp.TRIP 1p L3 I.Trip: TRIP - Only L3

3521 ITrp.TRIP L123 I.Trip: TRIP L123

3522 Diff TRIP 1pole I.Trip: TRIP 1pole

3523 Diff TRIP 3pole I.Trip: TRIP 3pole

7SD610 Manual 6-39


C53000-G1176-C145-1
Functions

6.4 Protection Data Interfaces and Differential Protection Topology

As described in the explanation of the function principle of differential protection (Sec-


tion 6.2.1), the devices which belong to the protected object limited by the current
transformer sets, have to exchange the data of the ends of the protected object. This
does not only apply for the measured quantities relevant for the differential protection
itself, but also for all data which are to be available at both ends. This includes the syn-
chronization and topological data as well as the intertripping, transfer trip, remote an-
nunciation signals and measured values. The layout of the protected object, the allo-
cation of the devices to the ends of the protected object and the allocation of the ways
of communication to the devices’ protection data interface form the topology of the dif-
ferential protection system and its communication.

6.4.1 Function Description

Communication For each device you require one protection data interface PI 1. Both protection data
Topology interfaces are connected with each other (see also Figure 6-23). When setting the
function parameters, each device are identified with an index number: Index 1 and
Index 2.

1 2

PI1 PI1
Index 1 Index 2

7SD52 7SD52

Figure 6-23 Differential protection with two 7SD610 devices, using the protection
data interface (transmitter/receiver)

Communication The communication is enabled via direct optical fibre connections or via communica-
Media tion networks. Which kind of media is used, depends on the distance and on the com-
munication media available. For shorter distances a direct connection via optical fibres
having a transmission rate of 512 kBit/s is possible. Otherwise we recommend com-
munication converters. A transmission via modem and communication networks can
also be realized. Please take into consideration that the tripping times of the differen-
tial protection devices depend on the transmission quality and that they are prolonged
in case of a reduced transmission quality and /or an increased transmission time.
Figure 6-24 shows some examples for communication connections. In case of a direct
connection the distance depends on the type of the optical fibre. Table 6-1 lists the
available options. Different types of communication modules can be installed in the
device. For ordering information see Appendix A, Subsection A.1.1.

6-40 7SD610 Manual


C53000-G1176-C145-1
Protection Data Interfaces and Differential Protection Topology

Table 6-1 Communication via direct connection

Module Connector Fibre type Optical Permissible path Distance,


type type wavelength attenuation typical
FO5 ST Multimode 820 nm 8 dB 1,5 km
62,5/125 µm
FO6 ST Multimode 820 nm 16 dB 3,5 km
62,5/125 µm
FO7 ST Monomode 1300 nm 7 dB 10 km
9/125 µm
FO8 FC Monomode 1300 nm 18 dB 35 km
9/125 µm

If communication converters are used, the device and the communication converter
are always linked with a FO5 module via optical fibres. The converter itself is equipped
with different interfaces for the connection to the communication network. For ordering
information see Appendix A, Subsection A.1.1.

typical 1,5 km with typical 3,5 km with


62,5/125 µm Multimode fibre 62,5/125 µm Multimode fibre
7SD610 7SD610 7SD610 7SD610
FO5 with FO6 with
ST-connector ST-connector
at both ends at both ends

typical 10 km with typical 35 km with


9/125 µm Monomode fibre 62,5/125 µm Monomode fibre
7SD610 7SD610 7SD610 7SD610
FO7 with FO7 with
ST-connector FC-connector
at both ends at both ends

Communication Communication
typical 1,5 km with Converter Converter typical 1,5 km with
62,5/125 µm Multimode fibre 62,5/125 µm Multimode fibre
7SD610
o Communication Network e 7SD610
e o
FO5 with FO5 with
ST-connector X21 or X21 or ST-connector
at both ends G703.1 G703.1 at both ends
Figure 6-24 Examples for communication connections

7SD610 Manual 6-41


C53000-G1176-C145-1
Functions

Transmission Fault The communication is continuously monitored by the devices.


and Transmission
Single faulty data telegrams are not a direct risk if they occur only occasionally. They
Failure
are recognized and counted in the device which detects the disturbance and can be
read out as statistical information.
If several faulty telegrams or no data telegrams at all are received, this can be regard-
ed as a data fault as soon as a time delay for data disturbance alarm (default setting
100 ms, can be altered) is exceeded. A corresponding alarm is output. The differential
protection will stop operating. Both devices are affected by the disturbance, since the
formation of differential currents and restraint currents is no longer possible at any of
the ends. If the backup overcurrent protection is configured, it will be the only short-
circuit protection still active. As soon as the data traffic works faultlessly again, the de-
vices will automatically switch back to differential protection operation.
Transmission time jumps that, for example, can occur in case of switchover in the
communication network can be recognized and corrected by the device. The differen-
tial protection system continues to operate without any loss of sensitivity. After at least
2 seconds the transmission times are measured again.
If the communication is interrupted for a permanent period (which is longer than a set-
table time period), this can be regarded as a transmission failure. A corresponding
alarm is output. The same reactions apply as for the data fault.

6.4.2 Setting the Function Parameters

General The protection data interfaces connect the devices with the communication media.
Information on The communication is permanently monitored by the devices. Address  7'$7$
Protection Data ',6785% defines after which delay time the user is informed about a faulty or missing
Interfaces telegram. Address  7'$7$)$,/ is used to set the time after which a transmis-
sion failure alarm is output.

Protection Data The protection data interface 1 can be switched RQ or RIIwith address  67$7(
Interface 1 3527,. If it is switched RII, this can be regarded as a transmission failure. The
differential protection and all functions which require the transmission of data, cannot
continue their operation.
Address  &211(&29(5to set the transmission media that you want to con-
nect to protection data interface PI 1. The following media are possible
)RSWLFGLUHFW, i.e. communication directly by fibre-optic cable with 512 kBit/s,
&RPFRQYN%, i.e. via communication converters with 64 kBit/s (G703,1 or X21)
&RPFRQYN%, i.e. via communication converters 128 kBit/s (X21)
&RPFRQYN%, i.e. via communication converters 512 kBit/s (X21).
The possibilities may vary for the different device versions. The data must be identical
at both ends of a communication route.
The setting depends on the features of the communication media. As a general rule,
it can be said that the higher the transmission rate is the shorter the response time of
the differential protection system will be.

6-42 7SD610 Manual


C53000-G1176-C145-1
Protection Data Interfaces and Differential Protection Topology

The devices measure and monitor the transmission times. Deviations are corrected,
as long as they are within the permissible range. These permissible ranges are set un-
der addresses $ and $ and can normally be left at their default setting.
The maximum permissible delay time (address $ 35277'(/$<) is preset
to a value that does not exceed the usual value of communication networks. This pa-
rameter can only be changed with DIGSI® 4 under “Additional Settings”. If it is ex-
ceeded (e.g. when a different way of transmission is used), the message “3,77
DODUP” is issued. Increased delay times only have an impact on the tripping times of
the differential protection.
The maximum transmission time difference (outgoing signal vs. return signal) can be
altered in address $ 3527816<0. With a direct fibre-optic connection, this
value can remain at . For transmission via communication networks a higher value
must be set. The reference value is 100 µs (presetting). This parameter can only be
changed with DIGSI® 4 under “Additional Settings”.
The permissible transmission time difference (addresses $ and $) have a
direct influence on the sensitivity of the differential protection. The automatic self-re-
straint of the protection adapts the restraint quantities to these tolerances so that a
spurious operation of the differential protection due to these influences is prevented.
Thus, higher tolerance values reduce the sensitivity of the protection, which may be
noticeable in case of very low-current faults.

Communication First of all, define the device index numbers: One relay gets index no. 1, the other in-
Topology dex no. 2. For the differential protection system the device with index 1 is always the
timing master, i.e. the absolute time management of both devices which belong to-
gether depends on the absolute time management of this device. As a result the time
information of both devices is comparable at all times.
Allocate also an identification number (device–ID) for each device. The device–ID is
used by the communication system to identify each individual device. It must be be-
tween 1 and 65534 and must be unique within the communication system. The ID
number identifies the devices in the communication system since the exchange of in-
formation between several differential protection systems (thus also for several pro-
tected objects) can be executed via the same communication system. Please make
sure that the communications link and the existing interfaces are in accordance with
each other.
Next, the addresses  ,'2)5(/$<and  ,'2)5(/$< are set, e.g.
for device 1 the device-ID  and for device 2 the device-ID  (Figure 6-25, compare
also with Figure 6-23). The indices of the devices and the device-IDs do not have to
match here, as mentioned above.

7SD610 Manual 6-43


C53000-G1176-C145-1
Functions

Figure 6-25 Differential protection topology for 2 ends with 2 devices - example

Finally, you enter in address  /2&$/5(/$< the index of the actual local device.
Enter the index 1 or 2 of that relay which is under consideration.
Make sure that the parameters of the differential protection topology for the differential
protection system are consistent:
• Each device index can only be used once;
• Each device index must be allocated unambiguously to one device ID;
• Each device index must be the index of a local device once;
• The device with index 1 is the source for the absolute time management (timing
master).
During the start-up of the protection system, the above listed conditions are checked.
If one out of these conditions is not fulfilled, no differential protection operation is pos-
sible. The device signals “'7LQFRQVLVWHQW” (“Device table inconsistent”).

6-44 7SD610 Manual


C53000-G1176-C145-1
Protection Data Interfaces and Differential Protection Topology

6.4.3 Setting Overview

Protection Data
Interfaces

Addr. Setting Title Setting Options Default Setting Comments


1509 T-DATA DISTURB 0.05..2.00 sec 0.10 sec Time delay for data disturbance
alarm

1510 T-DATAFAIL 0.0..60.0 sec 6.0 sec Time delay for transmission
failure alarm

1501 STATE PROT I 1 ON ON State of protection data interface


OFF 1

1502 CONNEC. 1 OVER Direct connection with fibre Direct connection Connection 1 over
optic cable with fibre optic
Communication converter cable
with 64 kBit/s
Communication converter
with 128 kBit/s
Communication converter
with 512 kBit/s

1505A PROT 1 T-DELAY 0.1..30.0 ms 30.0 ms Prot 1: Maximal permissible


delay time

1506A PROT 1 UNSYM. 0.000..3.000 ms 0.000 ms Prot 1: Diff. in send and receive
time

Topological Data

Addr. Setting Title Setting Options Default Setting Comments


1701 ID OF RELAY 1 1..65534 1 Identification number of relay 1

1702 ID OF RELAY 2 1..65534 2 Identification number of relay 2

1710 LOCAL RELAY relay 1 relay 1 Local relay is


relay 2

7SD610 Manual 6-45


C53000-G1176-C145-1
Functions

6.4.4 Information Overview

Protection Data
Interfaces

F.No. Alarm Comments


3215 Wrong Firmware Incompatible Firmware Versions

3217 PI1 Data reflec Prot Int 1: Own Datas received

3227 >PI1 light off >Prot Int 1: Transmitter is switched off

3229 PI1 Data fault Prot Int 1: Reception of faulty datas

3230 PI1 Datafailure Prot Int 1: Total receiption failure

3233 DT inconsistent Device table has inconsistent numbers

3234 DT unequal Device tables are unequal

3235 Par. different Differences between common parameters

3239 PI1 TT alarm Prot Int 1: Transmission time to high

3243 PI1 with Prot Int 1: Connected with relay ID

Topological Data

F.No. Alarm Comments


3451 >Logout > Logout input signal

3458 Chaintopology System operates in a open Chaintopology

3464 Topol complete Communication topology is complete

3475 Rel1Logout Relay 1 in Logout state


3476 Rel2Logout Relay 2 in Logout state

3484 Logout Local activation of Logout state

3487 Equal IDs Equal IDs in constellation

6-46 7SD610 Manual


C53000-G1176-C145-1
Direct Local Trip

6.5 Direct Local Trip

6.5.1 Function Description

Direct Trip of the Any signal from an external protection, monitoring or control device can be injected
Local Circuit into the processing of 7SD610 via binary inputs. It can be delayed, output as an alarm
Breaker and be routed to one or several output relays. Figure 6-26 shows the logic diagram. If
the devices and circuit breakers are designed for single-pole control, single-pole trip-
ping is possible. The tripping logic of the device ensures that the conditions for single-
pole tripping are fulfilled (e.g. single-pole tripping permissible, reclosure device ready).
The direct transfer trip can be switched on and off by parameters, and blocked via a
binary input.

)1R  7ULS7LPH'(/$<


>DTT TRIP 3p
)1R
)1R ≥1 T 0
& DTT TRIP 1p L1
>DTT TRIP L1
)1R
)1R ≥1 T 0 DTT TRIP 1p L2
>DTT TRIP L2 & Tripping logic )1R
DTT TRIP 1p L3
)1R ≥1 T 0
)1R
>DTT TRIP L3 &
DTT TRIP L123

2201 )&7'LUHFW7ULS )1R


21 DTT TRIP off
„1“
2))
≥1
)1R
)1R & DTT TRIP block
>DTT TRIP

Figure 6-26 Logic diagram of the direct local trip (DTT)

6.5.2 Setting the Function Parameters

A precondition for the direct local trip is that during the configuration of the functions
(Section 5.1) )&7'LUHFW7ULS = ([LVW has been configured in address . It
can also be switched RQ and RII with address  )&7'LUHFW7ULS.
For direct local trip a trip time delay can be set in address  7ULS7LPH'(/$<.
This delay can be used as a grading margin.
A tripping command which has been issued is maintained for at least the minimum trip-
ping command duration 70LQ75,3&0' which was configured for the device in ad-
dress$ (Section 6.1.1). This ensures that the circuit breaker can be operated
reliably even if the control pulse is very short.

7SD610 Manual 6-47


C53000-G1176-C145-1
Functions

6.5.3 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


2201 FCT Direct Trip ON OFF Direct Transfer Trip (DTT)
OFF

2202 Trip Time DELAY 0.00..30.00 sec; ∞ 0.01 sec Trip Time Delay

6.5.4 Information Overview

F.No. Alarm Comments


4403 >BLOCK DTT >BLOCK Direct Transfer Trip function

4412 >DTT Trip L1 >Direct Transfer Trip INPUT Phase L1

4413 >DTT Trip L2 >Direct Transfer Trip INPUT Phase L2

4414 >DTT Trip L3 >Direct Transfer Trip INPUT Phase L3

4417 >DTT Trip L123 >Direct Transfer Trip INPUT 3ph L123

4421 DTT OFF Direct Transfer Trip is switched OFF

4422 DTT BLOCK Direct Transfer Trip is BLOCKED

4432 DTT TRIP 1p. L1 DTT TRIP command - Only L1

4433 DTT TRIP 1p. L2 DTT TRIP command - Only L2

4434 DTT TRIP 1p. L3 DTT TRIP command - Only L3

4435 DTT TRIP L123 DTT TRIP command L123

6-48 7SD610 Manual


C53000-G1176-C145-1
Direct Remote Trip or Transmission of Binary Information

6.6 Direct Remote Trip or Transmission of Binary Information

7SD610 allows the transmission of up to 4 items of binary information of any type from
one device to the other via the communications links provided for protection tasks.
These are transmitted like protection signals with high priority, i.e. very fast, and are
therefore especially suitable for the transmission of external protection signals which
are generated outside of 7SD610. Of course, they are suitable for any information,
such as information on the events taking place in a station which may also be useful
in the other station as well.
The information is injected into the device via binary inputs and can be output at the
other end again via binary outputs. The integrated user-defined CFC logic allows to
perform on both the transmitting and the receiving side logical operations on the sig-
nals and on other information from the device’s protection and monitoring functions.
The binary outputs and the binary inputs to be used must be allocated appropriately
during the configuration of the input and output functions (see Section 5.2). The sig-
nals, arrive at the device via the binary inputs “!5HPRWH7ULS” to “!5HPRWH
7ULS”, transmitted to the device at the other end and can be processed at the receiv-
ing side with the output functions “5HPRWH7ULSUHF” to “5HPRWH7ULSUHF”.
No settings are required for the transmission of binary information. Each device sends
the injected information immediately to the other.

6.6.1 Information Overview

F.No. Alarm Comments


3541 >Remote Trip1 >Remote Trip 1 signal input

3542 >Remote Trip2 >Remote Trip 2 signal input

3543 >Remote Trip3 >Remote Trip 3 signal input

3544 >Remote Trip4 >Remote Trip 4 signal input

3545 RemoteTrip1 rec Remote Trip 1 received

3546 RemoteTrip2 rec Remote Trip 2 received

3547 RemoteTrip3 rec Remote Trip 3 received

3548 RemoteTrip4 rec Remote Trip 4 received

7SD610 Manual 6-49


C53000-G1176-C145-1
Functions

6.7 Instantaneous High-speed SOTF Protection

6.7.1 Function Description

General Informa- The instantaneous high-speed SOTF O/C function is provided to disconnect
tion immediately and without delay feeders that are switched onto a high-current fault. It
serves e.g. as a rapid protection for connecting a feeder with closed grounding
disconnector. In order to function properly, the devices at both ends of the protective
object must know the circuit breaker positions (breaker auxiliary contacts).
A second stage works fast and without delay, regardless of the circuit breaker position.

,!!!6WDJH The pickup of the I>>> stage measures each phase current and compares it to the set-
ting value ,!!!. The currents are numerically filtered so that only the fundamental
component is evaluated. This high-current pickup is practically unaffected by d.c. com-
ponents in short-circuit current as well as in secondary current after switching off high
currents. If the setting value is exceeded by more than twice its value, the stage will
automatically use the peak value of the unfiltered measured quantity so that extremely
short command times are possible.
This stage is only enabled when the local circuit breaker is connected while all remain-
ing line ends of the protective object are open. The devices exchange the status of
their respective circuit-breakers continuously via the communication link. If the pro-
tected object is already live (from the other end) the stage is not effective. An indis-
pensable precondition for the functioning of the I>>> stage is that the auxiliary con-
tacts of the circuit breakers are connected at both ends of the protected object and
allocated on the relevant binary inputs. If this is not the case, this stage is not effective.
A central function control communicates the information of the circuit breaker position
to the high-current instantaneous tripping (see also Section 6.13.2)
Figure 6-27 shows the logic diagram. The I>>> stage at the bottom of the diagram op-
erates separately for each phase. During the manual closing of the circuit breaker all
three phases are enabled via the signal “+662)75,3/” which is issued by the
central functional control of the protection, provided that the manual closing can be
recognized there (see Section 6.13).
Tripping can also be enabled separately for each phase by the signals “62)75,3
S/[”. This applies also to e.g. automatic reclosure after single-pole tripping. Then,
single-pole tripping with this stage is possible, but only if the device is designed for
single-pole tripping.

I>>>> Stage The I>>> stage trips regardless of the position of the circuit breakers. Here, the cur-
rents are also numerically filtered and the peak-value of the currents is measured from
the double setting value onwards. Figure 6-27 shows the logic diagram in the upper
part.
Therefore, this stage is used when current grading is possible. This is possible with a
small source impedance and at the same time a high impedance of the protected ob-
ject (example can be found with the advice on setting, Section 6.7.2).
The I>>> stage is enabled automatically by the current-step monitoring dI/dt of the de-
vice for a duration of 50 ms. This stage works separately for each phase.

6-50 7SD610 Manual


C53000-G1176-C145-1
Instantaneous High-speed SOTF Protection

 ,!!!!

I>>>> )1R
d
≥1 SOTF PU I>>>>L1
dt 50 ms
SOTF PU I>>>>L2
2·√2·I>>>> SOTF PU I>>>>L3
)1R
 ,!!! SOTF TRIP 1pL1
)1R
SOTF TRIP 1pL2
IL1 )1R
I>>>
IL2
≥1 SOTF TRIP 1pL3
≥1
IL3
)1R
Tripping logic SOTF TRIP L123
2·√2·I>>>
)1R
SOTF TRIP 1p
SOTF enab. L1 )1R
SOTF enab. L2. (all ends SOTF TRIP 3p
SOTF enab. L3 open)
≥1 )1R
&
SOTF enab. L123 SOTF PU I>>> L1
L1 SOTF PU I>>> L2
L2 SOTF PU I>>> L3
L3
Figure 6-27 Logic diagram of the instantaneous high-speed SOTF overcurrent function

6.7.2 Setting the Function Parameters

A precondition for the use of the instantaneous high-speed SOTF overcurrent function
is that during the configuration of the device functions (Section 5.1) 627))XQF =
([LVWhas configured in address . It can also be switched RQ and RII with ad-
dress  )&7+6627)2&.

,!!! Stage The intensity of the short-circuit current which leads to the pickup of the I>>>-stage is
set as ,!!! in address . This stage works only during the connecting of local end
while the circuit breaker at the other end is open. Choose a value which is too high for
the protection to respond to the r.m.s. value of the inrush current produced during the
connection of the protected object. On the other hand, short-circuit currents flowing
through the protected object need not be considered.
During the configuration with a personal computer and DIGSI ® 4 the values can be en-
tered in primary or secondary quantities. If secondary quantities are configured, the
currents are converted to the secondary side of the current transformers.

I>>>> Stage The ,!!!!stage (address 2405A) works regardless of the circuit breaker position.
Since it trips extremely fast it must be set high enough not to respond to the short-cir-
cuit current flowing through the protected object. This means that it can be used only
if the protected object allows current grading, as is the case with transformers, series
reactors or long lines with small source impedance. In other cases it is set to ∞ (default

7SD610 Manual 6-51


C53000-G1176-C145-1
Functions

setting). This parameter can only be changed with DIGSI® 4 under “Additional Set-
tings”.
During the configuration with a personal computer and DIGSI® 4 the values can be en-
tered in primary or secondary quantities. If secondary quantities are configured, the
currents are converted to the secondary side of the current transformers.

Exemplary calculation:
110 kV overhead line 150 mm2 with the data:
s (length) = 60 km
R1/s = 0.19 Ω/km
X1/s = 0.42 Ω/km
Short-circuit power at the transmitting end:
Sk" = 3.5 GVA (subtransient, since the I>>>> stage can respond to the first
peak value)
Current transformer 600 A/5 A
From that the line impedance ZL and the source impedance ZS are calculated:
Z1/s = √0.192 + 0.422 Ω/km = 0.46 Ω/km
ZL = 0.46 Ω/km · 60 km = 27.66 Ω
2 2
110 kV
ZS = ------------------------------ = 3.46 Ω
3500 MVA
The three-phase short-circuit current at the line end is I"k end:
1.1 ⋅ U N 1.1 ⋅ 110 kV
I" k end = ------------------------------------- = ---------------------------------------------------------------- = 2245 A
3 ⋅ ( ZV + ZL ) 3 ⋅ (3.46 Ω + 27.66 Ω )

With a safety factor of 10 % the following primary setting value results:


Setting value ,!!!! = 1.1 · 2245 A = 2470 A
Or the secondary setting value:
2245 A
Settingvalue I>>>> = 1.1 ⋅ ------------------- ⋅ 5 A = 20.6 A
600 A

i.e. in case of short-circuit currents exceeding 2470 A (primary) or 20.6 A (secondary)


you can be sure that a short-circuit has occurred on the protected line. This line can
be disconnected immediately.

Note:
The calculation was carried out with absolute values, which is sufficiently precise for
overhead lines. If the angles of the source impedance and the line impedance vary
considerably, a complex calculation will have to be carried out.

6-52 7SD610 Manual


C53000-G1176-C145-1
Instantaneous High-speed SOTF Protection

6.7.3 Setting Overview

Note: The indicated setting ranges and default settings refer to a secondary rated cur-
rent of IN = 1 A. For the secondary rated current of IN = 5 A these values are to be
multiplied by 5. For the setting of primary values the transformation ratio of the trans-
formers must also be taken into consideration.

Addr. Setting Title Setting Options Default Setting Comments


2401 FCT SOTF-O/C ON ON Inst. High Speed SOTF-O/C is
OFF

2404 I>>> 0.10..15.00 A; ∞ 1.50 A I>>> Pickup

2405A I>>>> 1.00..25.00 A; ∞ ∞A I>>>> Pickup

6.7.4 Information Overview

F.No. Alarm Comments


4253 >BLOCK SOTF-O/C >BLOCK Instantaneous SOTF Overcurrent
4271 SOTF-O/C OFF SOTF-O/C is switched OFF
4272 SOTF-O/C BLOCK SOTF-O/C is BLOCKED
4273 SOTF-O/C ACTIVE SOTF-O/C is ACTIVE
4281 SOTF-O/C PICKUP SOTF-O/C PICKED UP
4282 SOF O/CpickupL1 SOTF-O/C Pickup L1
4283 SOF O/CpickupL2 SOTF-O/C Pickup L2
4284 SOF O/CpickupL3 SOTF-O/C Pickup L3
4285 I>>>>O/C p.upL1 High Speed-O/C Pickup I>>>> L1
4286 I>>>>O/C p.upL2 High Speed-O/C Pickup I>>>> L2
4287 I>>>>O/C p.upL3 High Speed-O/C Pickup I>>>> L3
4289 HS/SOF TRIP1pL1 High Speed/SOTF-O/C TRIP - Only L1
4290 HS/SOF TRIP1pL2 High Speed/SOTF-O/C TRIP - Only L2
4291 HS/SOF TRIP1pL3 High Speed/SOTF-O/C TRIP - Only L3
4292 HS/SOF TRIP 1p High Speed/SOTF-O/C TRIP 1pole
4293 HS/SOF Gen.TRIP High Speed/SOTF-O/C General TRIP
4294 HS/SOF TRIP 3p High Speed/SOTF-O/C TRIP 3pole
4295 HS/SOF TRIPL123 High Speed/SOTF-O/C TRIP command L123

7SD610 Manual 6-53


C53000-G1176-C145-1
Functions

6.8 Time Overcurrent Protection

General Informa- The 7SD610 has a time overcurrent protection function which can be used as either a
tion back-up or an emergency overcurrent protection.
Whereas the differential protection can only operate correctly if each device receives
the data of the other device properly, the emergency overcurrent protection requires
only the local currents. The emergency overcurrent protection is automatically activat-
ed when the data communication of the differential protection is disturbed (emergency
operation) and the differential protection is blocked as a result.
This means that emergency operation will replace the differential protection for short-
circuit protection if the data communication fails.
If the overcurrent protection is set as a back-up overcurrent protection, it will work in-
dependently of other protection and monitoring functions, i.e. also independently of
the differential protection. The back-up overcurrent protection can also be used as
sole short-circuit protection if no suitable channels for the communication between the
protection devices are available during the initial commissioning.
The overcurrent protection has a total of four stages for each phase current and for
the ground current; these are:
• Two overcurrent stages with independent trip time (definite-time overcurrent protec-
tion),
• One overcurrent stage with current-dependent trip time (inverse-time overcurrent
protection),
• A further overcurrent stage which has an additional enable input and can therefore
be used as an emergency stage e.g. if the remaining stages are used as back-up
stages.
These four stages do not depend on one another and can be combined as desired.
Blocking from external criteria is possible via binary inputs just like instantaneous trip-
ping. It is also possible to switch to any one or more of the stages if the protected ob-
ject is switched onto a fault. The stages not required can be deactived by setting the
pickup value to ∞.

6.8.1 Function Description

Measured Quanti- The phase currents are fed to the device via the input transformers of the measure-
ties ment input. The ground current 3·I0 is either measured directly or calculated, depend-
ing on the version ordered and the use of the device’s fourth current input I4.
If I4 is connected to the starpoint of the current transformer set, the ground current will
be available directly as measured quantity.
If I4 is connected to a separate ground current transformer, this will be used, while con-
sidering the factor ,,SK&7 (address , see Section 6.1.1) of the “Power Sys-
tem Data 1”.

6-54 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

If the ground current is not connected to the fourth current input I4 (address  ,
WUDQVIRUPHU = QRWFRQQHFWHG, see Section 6.1.1), the device will calculate the
ground current from the phase currents. Of course, all three phase currents of three
star-connected current transformers must be available and connected in this case.

Definite Time High- Each phase current is compared with the setting value ,SK!! after numerical filtering;
current Stage I>> the ground current is compared with ,!!3,&.83. When the relevant delay times
7,SK!! or 7,!! are expired, a tripping command is issued. The reset value is
approximately 5 % less than the pickup value, but at least 1.5 % of the rated current
below it.
Figure 6-28 shows the logic diagram of the I>> stages. They can be blocked via the
binary input “!%/2&.2&,!!”. In addition, the ground current stage can be blocked
separately via the binary input “!%/2&.2&,H!!”, e.g. during a single-pole pause
before reclosure in order to avoid a spurious tripping with the zero phase-sequence
system which is present then.

,SK!!   7,SK!!

I>> PU L1
I>> PU L2
IL1 T 0
I>> PU L3
Iph>> &
IL2
≥1 I>> TRIP L1
IL3
I>> TRIP L2
I>> TRIP L3
&

L1
L2
L3

,!!   7,!!

I>> PU E
IE
3I0>> T 0
& ≥1 I>> TRIP E

&

E
)1R
>O/C Ie>> blk
)1R
>O/C I>> blk
 ,!!7HOHS%,
)1R <HV
≥1
>O/C InstTRIP 1R

Switching <HV
onto a T 0
fault 1R
 627),!!
7627)  further
stages
Figure 6-28 Logic diagram of the I>> stage

7SD610 Manual 6-55


C53000-G1176-C145-1
Functions

The binary input “!2&,QVW75,3” and the function block “Switch onto fault” are the
same for all stages and explained in detail below. They can, however, affect the phase
and/ or ground stages separately. This can be achieved with two parameters:
• ,!!7HOHS%, (address ) defines whether an instantaneous tripping without
delay of this stage is possible (<HV) via the binary input “!2&,QVW75,3” or im-
possible (1R). This parameter is also used for instantaneous tripping before auto-
matic reclosure.
• ,!!627) (address ) defines whether an instantaneous tripping is to be per-
formed by this stage (<HV) or not (1R) if the line is switched onto a fault.

Definite Time Over- The logic of the overcurrent stages I> is designed like the I>> stages, except that in all
current Stage I> designations ,SK!! is replaced by ,SK! and ,!!3,&.83 by ,!.

Inverse Time Over- The logic of the current-dependent (inverse time) stage works basically like the other
current Stage Ip stages. However, the time delay is calculated here from the type of the set character-
istic (parameter ,(&&XUYH), the intensity of the current and a time multiplier (Figure
6-29). A preselection of the possible characteristics has been made during the config-
uration of the protection functions. Moreover, a constant additional time 7,S$GG or
7,S$GG can be selected which is added to the current-dependent time. The pos-
sible characteristics are shown in Section 10.6, Technical data.
Figure 6-29 shows the logic diagram. Here, exemplary setting addresses for the IEC
characteristics are shown. The setting notes (Section 6.8.2) explain the various setting
addresses in detail.

6-56 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

 ,(&&XUYH
 ,3!  7,S7LPH'LDO

Ip PU L1
Ip PU L2
Ip PU L3
IL1
t
IL2 IP & T 0
IL3 I ≥1 Ip TRIP L1
Ip TRIP L2
Ip TRIP L3
 7,3$GG
7,3
&
L1
L2
L3

,S3,&.83   7,S7LPH'LDO

Ip PU E
IE
T 0 t
3I0P
&
I
≥1 Ip TRIP E

 7,3$GG

&

)1R
>O/C Iep blk
)1R
>O/C Ip blk
 , , S7HOH%,
)1R <HV
≥1
>O/C InstTRIP 1R
Switching <HV
onto a T 0
fault 1R
 , , S627)
627)7'(/  further
stages
Figure 6-29 Logic diagram of the Ipstage (inverse-time overcurrent protection) — example for IEC characteris-
tics

Additional Overcur- The additional definite time or instantaneous overcurrent stage Iph> STUB has an ex-
rent Stage I STUB tra enable input (Figure 6-30) and is therefore also suitable e.g. as a stub protection
or as an emergency stage if the remaining stages are used as back-up stages. The
enable input “!,678%(1$%/(” can be assigned the output signal “(PHUPRGH”
(either via binary outputs and inputs or via the user-definable logic CFC functions).
The input is then automatically in operation when the differential protection is not ef-
fective any more due to a data disturbance.

7SD610 Manual 6-57


C53000-G1176-C145-1
Functions

The Iph> STUB stage can, however, also be used as a standard additional and inde-
pendent overcurrent stage, since it works independent of the other stages. In this
case, the release input “!,678%(1$%/(” must be permanently activated (via a bi-
nary input or CFC).

,SK!678%   7,SK678%

I-STUB PU L1
I-STUB PU L2
IL1 T 0
I-STUB PU L3
Iph &
IL2
≥1 I-STUB TRIP L1
IL3
I-STUB TRIP L2
I-STUB TRIP L3
&

L1
L2
L3
,!678%   7,678%

I-STUB PU E
IE
3I0 & T 0
≥1 I-STUB TRIP E

&

E
)1R
>BLOCK O/CIe>>>
)1R
>BLOCK I-STUB
)1R ≥1
>I-STUB ENABLE

 ,678%7HOHS%,
)1R <HV
≥1
>O/C InstTRIP. 1R
Switching <HV
onto a T 0
fault 1R
 ,678%627)
627)7'(/ 
further
stages

Figure 6-30 Logic diagram of the I>>> stage

Instantaneous If an automatic reclosure is to be carried out, a rapid clearing of the fault is usually de-
Tripping before sirable before reclosure. A “ready for reclosure” signal from an external automatic re-
Automatic closure device can be injected via binary input “!2&,QVW75,3”. The internal auto-
Reclosure matic reclosure function — if existent — acts on this input as well. Any stage of the
overcurrent protection can thus perform an instantaneous trip before reclosure via the
parameters ,...7HOHS%,.

6-58 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

Switching onto a To to perform an instantaneous trip if the circuit breaker is manually closed onto a
Fault dead fault, the manual closing command of the control-discrepancy switch can be fed
to the device via a binary input. The overcurrent protection then perform a three-pole
trip with no or almost no delay. The stage(s) for which the instantaneous trip after man-
ual closing is valid are determined by parameters (see also logic diagrams Figure 6-
28, 6-29 and 6-30).

Pickup and Trip- The pickup signals of the individual phases (or the ground) and of the stages are linked
ping Logic in such a way that both the phase information and the stage which has picked up are
output (Table 6-2).
For the tripping signals, the stage which caused the tripping is output as well. For
single-pole tripping, the pole is identified (see also Section 6.13.4 Tripping Logic of the
Entire Device).

Table 6-2 Pickup signals of the overcurrent protection


Internal message Figure Output message FNo
I>> PU L1 6-28
I> PU L1
2&3LFNXS/ 7162
Ip PU L1 6-29
I-STUB PU L1 6-30
I>> PU L2 6-28
I> PU L2
2&3LFNXS/ 7163
Ip PU L2 6-29
I-STUB PU L2 6-30
I>> PU L3 6-28
I> PU L3
2&3LFNXS/ 7164
Ip PU L3 6-29
I-STUB PU L3 6-30
I>> PU E 6-28
I> PU E
2&3LFNXS( 7165
Ip PU E 6-29
I-STUB PU E 6-30
I>> PU L1 6-28
I>> PU L2 6-28
2&3,&.83,!! 7191
I>> PU L3 6-28
I>> PU E 6-28
I> PU L1
I> PU L2
2&3,&.83,! 7192
I> PU L3
I> PU E
Ip PU L1 6-29
Ip PU L2 6-29
2&3,&.83,S 7193
Ip PU L3 6-29
Ip PU E 6-29
I-STUB PU L1 6-30
I-STUB PU L2 6-30
,678%3,&.83 7201
I-STUB PU L3 6-30
I-STUB PU E 6-30
(all pick-ups) 2&3,&.83 7161

7SD610 Manual 6-59


C53000-G1176-C145-1
Functions

6.8.2 Setting the Function Parameters

General During the configuration of the device functions (see Section 5.1, address ) the
Information available characteristics have been defined. Depending on the configuration and de-
pending on the version ordered, only those parameters are accessible which are valid
for the available characteristics.
Address  is set according to the desired mode of operation of the overcurrent
protection: 2SHUDWLQJ0RGH = 2Q means that the overcurrent protection works in-
dependently of other protection functions, i.e. as a backup overcurrent protection. If it
is to work only as an emergency function in case of a transmission failure, 2QO\
(PHUJHQF\SURWHFWLRQ must be set. Finally, it can also be set to 2II.
If some stages are not needed, those not needed can be deactivated by setting the
pickup value to ∞. But if you set an associated time delay to ∞ this does not suppress
the pickup signals but prevents the time from running.
The I>>> stage is even effective if 2QO\(PHUJHQF\SURWHFWLRQ has been set for
the operating mode of the overcurrent protection.
One or several stages can be set as instantaneous tripping stages when switching
onto a fault. This is chosen during the setting of the individual stages (see below). To
avoid a spurious tripping due to transient overcurrents a delay 627)7LPH'(/$<
(address ) can be set. Normally the default setting  is correct. A short delay can
be useful in case of long cables for which high inrush currents can be expected, or for
transformers. This delay depends on the intensity and duration the of the transient
phenomena and on the stages used for the instantaneous tripping.

High-Current The I>> stages ,SK!! (address ) and ,!!3,&.83 (address ) together
Stages Iph>>, with the I> stages or the Ip stages result in a two-stage characteristic. Of course, all
3I0>> PICKUP three stages can be combined as well. If a stage is not required, the pickup value is
set to ∞. The I>> stages always operate with a defined delay.
If the I>> stages are used for instantaneous tripping before the automatic reclosure,
the current-setting corresponds to the I> or Ip stages. In this case only the different de-
lay times are of interest. The times 7,SK!! (address ) and 7,!! (address
) can than be set to 0 or a very low value, as the fast reclosure of the short-circuit
current takes priority over the selectivity before the automatic reclosure is initiated. In
order to achieve the selectivity these stages have to be blocked before final reclosure.
For very long lines with a small source impedance or before large reactances (e.g.
transformers, series reactors), the I>> stages can also be used for current grading. In
this case they must be set in such a way that they do not pick up in case of a fault at
the end of the line. The times can then be set to  or to a small value.
During the parameterization from a personal computer using DIGSI® 4, the parame-
ters can be set as primary or secondary quantities. If secondary quantities are used,
all currents will be converted to the secondary side of the current transformers.

Exemplary calculation:
110 kV overhead line 150 mm2 with the data:
s (length) = 60 km
R1/s = 0.19 Ω/km
X1/s = 0.42 Ω/km

6-60 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

Short-circuit power at the beginning of the line:


Sk’ = 2.5 GVA
Current transformers 600 A/5 A
From that the line impedance ZL and the source impedance ZS are calculated:
Z1/s = √0.192 + 0.422 Ω/km = 0.46 Ω/km
ZL = 0.46 Ω/km · 60 km = 27.66 Ω
2 2
110 kV
ZS = ------------------------------ = 4.84 Ω
2500 MVA

The three-phase fault current at the line end is Ik End:


1.1 ⋅ U N 1, 1 ⋅ 110 kV
I k End = ------------------------------------- = ---------------------------------------------------------------- = 2150 A
3 ⋅ ( ZS + ZL ) 3 ⋅ ( 4.84 Ω + 27.66 Ω )

With a safety factor of 10 %, the following primary setting value is calculated:


Setting value I>> = 1.1 · 2150 A = 2365 A
Or the secondary setting value:
2150 A
Settingvalue I>> = 1.1 ⋅ ------------------- ⋅ 5 A = 19.7 A
600 A

i.e. in case of fault currents exceeding 2365 A (primary) or 19.7 A (secondary) you can
be sure that a short-circuit has occurred on the protected line. It can be disconnected
by the overcurrent protection immediately.
Note: the calculation was carried out with absolute values, which is sufficiently precise
for overhead lines. If the angles of the source impedance and the line impedance vary
considerably, a complex calculation will have to be carried out.
A similar calculation can be carried out for ground faults, with the maximum earth cur-
rent occurring at the line end during a short-circuit being decisive.
The set times are pure additional delays which do not include the inherent operating
time of the protection.
The parameter ,!!7HOHS%, (address ) defines whether the time delays 7
,SK!! (address ) and 7,!! (address ) can be bypassed by the binary
input “!2&,QVW75,3” (FNo ) or by the operational automatic reclosure func-
tion. The binary input (if allocated) is the same for all stages of the overcurrent protec-
tion. With ,!!7HOHS%, = <HV you define that the I>> stages trip without delay after
pickup if the binary input was activated. For ,!!7HOHS%, = 1Rthe set delays are
always active. Instantaneous tripping by the operational auto-reclosure function
should only be chosen if the overcurrent protection is set to emergency function. Since
the differential protection guarantees a fast and selective tripping with or without auto-
reclosure, the overcurrent protection as a back-up protection may not perform a non-
selective trip, even before auto-reclosure.
If the I>> stage is to perform an instantaneous trip (when the line is switched onto a
fault) or a trip with a short time delay 627)7LPH'(/$< (address , refer to
“General Information” above), set the parameter ,!!627) (address ) to <HV.
Any other stage can be selected as well for this instantaneous tripping.

7SD610 Manual 6-61


C53000-G1176-C145-1
Functions

Overcurrent Stages For the setting of the current pickup value, ,SK! (address ), the maximum oper-
Iph>, 3I0> for ating current is most decisive. Pickup through overload must be excluded, since the
Definite Time Over- device works in this operating mode as a short-circuit protection, not as an overload
current Protection protection, and the command times are commensurately short. The pickup value
should therefore be set to a higher value than the maximum (over-)load to be expect-
ed, i.e. approx. 10 % for lines and approximately 20 % for transformers and motors.
During configuration from a personal computer using DIGSI® 4 the parameters can be
set either to primary or secondary quantities. If secondary quantities are used, all cur-
rents will be converted to the secondary side of the current transformers.

Exemplary calculation:
110 kV overhead line 150 mm2 as above:
Maximum transmitted power
Pmax = 120 MVA corresponding to
Imax = 630 A
Current transformer 600 A/5 A
Safety factor 1.1
With settings in primary quantities the following setting value is calculated:
Setting value I> = 1.1 · 630 A = 693 A
With settings in secondary quantities the following setting value is calculated:
630 A
Setting value I> = 1.1 ⋅ ---------------- ⋅ 5 A = 5.8 A
600 A
The ground current stage ,! (address ) should be set to detect the smallest
ground fault current to be expected.
The time delay 7,SK! (address ) results from the time grading schedule de-
signed for the network. For use as an emergency overcurrent protection, shorter delay
times make sense (one grading time step above instantaneous tripping), since this
function is to work only in case of an interruption of the data communication of the dif-
ferential protection.
The time 7,! (address ) can normally be set shorter, according to a separate
time grading schedule for ground currents.
The set times are mere additional delays for the independent stages, which do not in-
clude the inherent operating time of the protection. If only the phase currents are to be
monitored for a stage, set the pickup value of the ground current stage to ∞.
The parameter ,!7HOHS%, (address ) defines whether the time delays 7
,SK! (address ) and 7,! (address ) can be bypassed by the binary
input “!2&,QVW75,3” (FNo ) or by the operational automatic reclosure func-
tion. The binary input (if allocated) is the same for all stages of the overcurrent protec-
tion. With ,!7HOHS%, = <HV you define that the I> stages trip without delay after
pickup if the binary input was activated. For ,!7HOHS%, = 1R the set delays are
always active. Instantaneous tripping by the operational auto-reclosure function
should only be chosen if the overcurrent protection is set to emergency function. Since
the differential protection guarantees a fast and selective tripping with or without auto-
reclosure, the overcurrent protection as a back-up protection may not perform a non-
selective trip, even before auto-reclosure.

6-62 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

If the I> stage is to perform an instantaneous trip, when the line is switched onto a fault,
or a trip with a short time delay 627)7LPH'(/$< (address , refer to “General
Information” above), set the parameter ,!627) (address ) to Yes. However,
the stage selected for instantaneous tripping should not be too sensitive since a strong
fault current is to be expected when switching onto a fault, and transient pickup of the
selected stage on switching on must be avoided.

Overcurrent Stages Various characteristics can be chosen for the current-dependent stages, depending
IP, 3I0P for Inverse on the version ordered and the configuration (Section 5.1, address ). Under ad-
Time Overcurrent dress  ,(&&XUYH the following IEC characteristics (address  3URW21
Protection with IEC 2)) = 2&,(&) are available:
Characteristics
,QYHUVH (Type A in accordance with IEC 60255–3),
9HU\,QYHUVH (Type B in accordance with IEC 60255–3),
([WUHPHO\,QY (Type C in accordance with IEC 60255–3), and
Inverse-time overcurrent /RQJWLPH (Type B in accordance with IEC 60255–3).
The characteristics and the formula on which they are based, are shown in the tech-
nical data (Section 10.6).
The considerations for the overcurrent stages of the definite-time overcurrent protec-
tion (see above) are also valid for the setting of the pickup values ,S! (address )
and ,S3,&.83 (address ). It should be noted that a safety margin has al-
ready been included between the pickup value and the setting value and that the pro-
tection picks up only when the setting value is exceeded by 10 %.
Referring to the above example, the maximum operational current to be expected can
be set here:
Primary: Setting value ,S! =  A,
Secondary: Setting value ,S! =  A, i.e. (630 A / 600 A) · 5 A.
The time multiplier 7,S7LPH'LDO (address ) derives from the time grading
schedule set for the network. For the use as emergency overcurrent protection shorter
delay times make sense (one grading time step above instantaneous tripping), since
this function is to work only in case of an interruption of the data communication of the
differential protection.
The time multiplier 7,S7LPH'LDO (address ) can normally be set shorter,
according to a separate time grading schedule for ground currents. If only the phase
currents are to be monitored, set the pickup value of the ground current stage to ∞.
In addition to the current-dependent delays, a delay of constant length can be set, if
necessary. The settings 7,S$GG (address  for phase currents) and 7,S
$GG (address  for ground current) are added to the times of the set characteris-
tics.
The parameter , , S7HOH%, (address ) defines whether the time delays
7,S7LPH'LDO (address ) including the additional time 7,S$GG (address
) and 7,S7LPH'LDO (address ) including the additional time 7,S
$GG (address ) can be bypassed by the binary input “!2&,QVW75,3” (FNo
) or by the operational automatic reclosure function. The binary input (if allocat-
ed) is the same for all stages of the overcurrent protection. With , , S7HOH%,
= <HV you define that the IPstages trip without delay after pickup if the binary input was
activated. For , , S7HOH%, = 1R the set delays are always active. Instantane-
ous tripping by the operational auto-reclosure function should only be chosen if the
overcurrent protection is set to emergency function. Since the differential protection

7SD610 Manual 6-63


C53000-G1176-C145-1
Functions

guarantees a fast and selective tripping with or without auto-reclosure, the overcurrent
protection as a back-up protection may not perform a non-selective trip, even before
auto-reclosure.
If the inverse time stage is to perform an instantaneous trip, when the line is switched
onto a fault, or a trip with a short time delay 627)7LPH'(/$< (address , refer
to “General Information” above), set the parameter , , S627) (address )
to Yes. However, the stage selected for instantaneous tripping should not be too sen-
sitive since a strong fault current is to be expected when switching onto a fault, and
transient pickup of the selected stage on switching on must be avoided.

Overcurrent Stages Various characteristics can be chosen for the current-dependent stages, depending
IP, 3I0P for Inverse- on the version ordered and the configuration (Section 5.1, address ). Under ad-
time Overcurrent dress  $16,&XUYH the following ANSI characteristics (address  3URW21
Protection with 2)) = 2&$16,) are available:
ANSI Characteris-
,QYHUVH,
tics
6KRUW,QYHUVH,
/RQJ,QYHUVH,
0RGHUDWHO\,QY,
9HU\,QYHUVH,
([WUHPHO\,QY and
'HILQLWH,QY
The characteristics and the formula on which they are based, are shown in the tech-
nical data (Section 10.6).
The considerations for the overcurrent stages of the definite-time overcurrent protec-
tion (see above) are also valid for the setting of the pickup values ,S! (address )
and ,S3,&.83 (address ). It should be noted that a safety margin has al-
ready been included between the pickup value and the setting value and that the pro-
tection picks up only when the setting value is exceeded by 10 %.
Referring to the above example, the maximum operational current to be expected can
be set here:
Primary: setting value ,S! = 630 A,
Secondary: setting value ,S! = 5.25 A, i.e. (630 A / 600 A) · 5 A.
The time multiplier 7LPH'LDO7',S (address ) derives from the time grading
schedule set for the network. For the use as emergency overcurrent protection shorter
delay times make sense (one grading time step above instantaneous tripping), since
this function is to work only in the case of an interruption of the data communication of
the differential protection.
The time multiplier 7LPH'LDO7',S (address ) can normally be set shorter,
according to a separate time grading schedule for ground currents. If only the phase
currents are to be monitored, set the pickup value of the ground current stage to ∞.
In addition to the current-dependent delays, a delay of constant length can be set, if
necessary. The settings 7,S$GG (address  for phase currents) and 7,S
$GG (address  for ground current) are added to the times of the set characteris-
tics.
The parameter , , S7HOH%, (address ) defines whether the time delays
7LPH'LDO7',S (address  including the additional time7,S$GG (ad-
dress ) and 7LPH'LDO7',S (address ) including the additional time 7

6-64 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

,S$GG (address ) can be bypassed by the binary input “!2&,QVW75,3”


(FNo ) or by the operational automatic reclosure function. The binary input (if al-
located) is the same for all stages of the overcurrent protection. With , , S7HOH
%, = <HV you define that the IP stages trip without delay after pickup if the binary input
was activated. For , , S7HOH%, = 1R the set delays are always active. Instan-
taneous tripping by the operational auto-reclosure function should only be chosen if
the overcurrent protection is set to emergency function. Since the differential protec-
tion guarantees a fast and selective tripping with or without auto-reclosure, the over-
current protection as a back-up protection may not perform a non-selective trip, even
before auto-reclosure.
If the inverse time stage is to perform an instantaneous trip (when the line is switched
onto a fault) or a trip with a short time delay 627)7LPH'(/$< (address , refer
to “General Information” above), set the parameter , , S627) (address )
to Yes. However, the stage selected for instantaneous tripping should not be too sen-
sitive since a strong fault current is to be expected when switching onto a fault, and
transient pickup of the selected stage on switching on must be avoided.

Additional Stage The Iph> STUB stage can be used as an additional definite time overcurrent stage,
Iph> STUB since it works independently of the other stages. In this case, the enable input “!,
678%(1$%/(” (FNo ) must be activated permanently (via a binary input or
CFC). Alternatively, it can be used as a stub bus protection. In this case, the enable
input “!,678%(1$%/(” is activated by the indication of the open line disconnector.
Since the Iph> STUB stage has an additional enable input, it is also suitable e.g. as
an emergency stage if the remaining stages are used as back-up stages. The to re-
lease input “!,678%(1$%/(” (FNo ) can be assigned the output signal “(P
HUPRGH” (either via binary outputs and inputs or via the user-definable logic CFC
functions).
The considerations for the use of the Iph> STUB stage as an emergency function are
the same as for the I> stages. The setting value ,SK!678% (address ) must
here too be higher than the maximum operational current to be expected, in order to
avoid pickup without short-circuit. The delay 7,SK678% (address ), however,
can be shorter than defined in the time grading schedule, since this stage works only
in emergency operation, i.e. in case of a communication failure of the differential pro-
tection. Normally, one time step above the base time of the differential protection is
sufficient.
The ground current stage ,!678% (address ) should correspondingly pick up
on the smallest ground current to be expected during a ground fault and the delay 7
,678% (address ) should exceed the base time of the differential protection
by a grading time. If only the phase currents are to be monitored, set the pickup value
of the ground fault stage to ∞.
The Iph> STUB stage can also be accelerated by the enable signal “!2&,QVW
75,3” (FNo ), e.g. before an auto-reclosure. This is defined with parameter ,
678%7HOHS%, (address ). Set it on <HV if the Iph> STUB stage is to trip with-
out delay as long as the binary input “!2&,QVW75,3” is activated or the internal
auto-reclosure function is ready to operate. Instantaneous tripping by the operational
auto-reclosure should only be chosen if the Iph> STUB stage is set as an emergency
function. If the differential protection is out of operation, this emergency stage guaran-
tees instantaneous tripping before auto-reclosure.

7SD610 Manual 6-65


C53000-G1176-C145-1
Functions

Instantaneous tripping when the line is switched onto a fault is also possible with the
Iph> STUB stage. Set parameter ,678%627) (address ) to Yes, if instanta-
neous tripping is desired.

6.8.3 Setting Overview

Note: The indicated setting ranges and default settings refer to a secondary rated cur-
rent of IN = 1 A. For the secondary rated current of IN = 5 A these values are to be
multiplied by 5. For the setting of primary values the transformation ratio of the trans-
formers must also be taken into consideration.

Addr. Setting Title Setting Options Default Setting Comments


2601 Operating Mode ON ON Operating mode
Only Emergency protection
OFF

2680 SOTF Time DELAY 0.00..30.00 sec 0.00 sec Trip time delay after SOTF

2610 Iph>> 0.10..25.00 A; ∞ 2.00 A Iph>> Pickup

2611 T Iph>> 0.00..30.00 sec; ∞ 0.30 sec T Iph>> Time delay

2612 3I0>> PICKUP 0.05..25.00 A; ∞ 0.50 A 3I0>> Pickup

2613 T 3I0>> 0.00..30.00 sec; ∞ 2.00 sec T 3I0>> Time delay

2614 I>> Telep/BI NO YES Instantaneous trip via Teleprot./


YES BI

2615 I>> SOTF NO NO Instantaneous trip after Swit-


YES chOnToFault

2620 Iph> 0.10..25.00 A; ∞ 1.50 A Iph> Pickup

2621 T Iph> 0.00..30.00 sec; ∞ 0.50 sec T Iph> Time delay

2622 3I0> 0.05..25.00 A; ∞ 0.20 A 3I0> Pickup

2623 T 3I0> 0.00..30.00 sec; ∞ 2.00 sec T 3I0> Time delay

2624 I> Telep/BI NO NO Instantaneous trip via Teleprot./


YES BI

2625 I> SOTF NO NO Instantaneous trip after Swit-


YES chOnToFault

2640 Ip> 0.10..4.00 A; ∞ ∞A Ip> Pickup

2642 T Ip Time Dial 0.05..3.00 sec; ∞ 0.50 sec T Ip Time Dial

2643 Time Dial TD Ip 0.50..15.00; ∞ 5.00 Time Dial TD Ip

2646 T Ip Add 0.00..30.00 sec 0.00 sec T Ip Additional Time Delay

2650 3I0p PICKUP 0.05..4.00 A; ∞ ∞A 3I0p Pickup

2652 T 3I0p TimeDial 0.05..3.00 sec; ∞ 0.50 sec T 3I0p Time Dial

6-66 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

Addr. Setting Title Setting Options Default Setting Comments


2653 TimeDial TD3I0p 0.50..15.00; ∞ 5.00 Time Dial TD 3I0p

2656 T 3I0p Add 0.00..30.00 sec 0.00 sec T 3I0p Additional Time Delay

2660 IEC Curve Normal Inverse Normal Inverse IEC Curve


Very Inverse
Extremely Inverse
Long time inverse

2661 ANSI Curve Inverse Inverse ANSI Curve


Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse

2670 I(3I0)p Tele/BI NO NO Instantaneous trip via Teleprot./


YES BI

2671 I(3I0)p SOTF NO NO Instantaneous trip after Swit-


YES chOnToFault

2630 Iph> STUB 0.10..25.00 A; ∞ 1.50 A Iph> STUB Pickup

2631 T Iph STUB 0.00..30.00 sec; ∞ 0.30 sec T Iph STUB Time delay

2632 3I0> STUB 0.05..25.00 A; ∞ 0.20 A 3I0> STUB Pickup

2633 T 3I0 STUB 0.00..30.00 sec; ∞ 2.00 sec T 3I0 STUB Time delay

2634 I-STUB Telep/BI NO NO Instantaneous trip via Teleprot./


YES BI

2635 I-STUB SOTF NO NO Instantaneous trip after Swit-


YES chOnToFault

7SD610 Manual 6-67


C53000-G1176-C145-1
Functions

6.8.4 Information Overview

F.No. Alarm Comments


7104 >BLOCK O/C I>> >BLOCK Backup OverCurrent I>>

7105 >BLOCK O/C I> >BLOCK Backup OverCurrent I>

7106 >BLOCK O/C Ip >BLOCK Backup OverCurrent Ip

7107 >BLOCK O/C Ie>> >BLOCK Backup OverCurrent Ie>>

7108 >BLOCK O/C Ie> >BLOCK Backup OverCurrent Ie>

7109 >BLOCK O/C Iep >BLOCK Backup OverCurrent Iep

7110 >O/C InstTRIP >Backup OverCurrent InstantaneousTrip

7130 >BLOCK I-STUB >BLOCK I-STUB

7131 >I-STUB ENABLE >Enable I-STUB-Bus function

7132 >BLOCK O/CIe>>> >BLOCK Backup OverCurrent Ie>>>

7151 O/C OFF Backup O/C is switched OFF

7152 O/C BLOCK Backup O/C is BLOCKED

7153 O/C ACTIVE Backup O/C is ACTIVE

7161 O/C PICKUP Backup O/C PICKED UP

7162 O/C Pickup L1 Backup O/C PICKUP L1

7163 O/C Pickup L2 Backup O/C PICKUP L2

7164 O/C Pickup L3 Backup O/C PICKUP L3

7165 O/C Pickup E Backup O/C PICKUP EARTH

7191 O/C PICKUP I>> Backup O/C Pickup I>>

7192 O/C PICKUP I> Backup O/C Pickup I>

7193 O/C PICKUP Ip Backup O/C Pickup Ip

7201 I-STUB PICKUP O/C I-STUB Pickup

7211 O/C TRIP Backup O/C General TRIP command

7212 O/C TRIP 1p.L1 Backup O/C TRIP - Only L1

7213 O/C TRIP 1p.L2 Backup O/C TRIP - Only L2

7214 O/C TRIP 1p.L3 Backup O/C TRIP - Only L3

7215 O/C TRIP L123 Backup O/C TRIP Phases L123

7221 O/C TRIP I>> Backup O/C TRIP I>>

7222 O/C TRIP I> Backup O/C TRIP I>

7223 O/C TRIP Ip Backup O/C TRIP Ip

7235 I-STUB TRIP O/C I-STUB TRIP

6-68 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

6.9 Automatic Reclosure

Experience shows that about 85 % of the arc faults on overhead lines are extinguished
automatically after being tripped by the protection. The line can therefore be re-closed.
Reclosure is performed by an automatic reclosure function (AR). An example of the
normal time sequence of a double-shot reclosure is shown in Figure 6-31.
If the circuit breaker poles can be operated individually, a single-pole auto-reclosure
is often initiated in the case of single-phase faults and a three-pole auto-reclosure in
the case of multi-phase faults in the network with earthed star point. If the fault still ex-
ists after reclosure (arc not extinguished or metallic short-circuit), the protection ulti-
mately trips. Several reclosure attempts are made in some networks.
Automatic reclosure is only permitted on overhead lines because the possibility of
automatic extinguishing of a fault arc only exists there. It may not be used in any other
case. If the protected object consists of a mixture of overhead lines and other equip-
ment (e.g. overhead line in block with a transformer or overhead line/cable), it must be
ensured that reclosure can only be performed in the event of a fault on the overhead
line.
In the version with single-pole tripping, 7SD610 allows phase-segregated, single-pole
tripping. A single- and three-pole, single and multiple shot automatic reclosure func-
tion is integrated, depending on the order variant.
7SD610 can also operate together with an external automatic reclosure device provid-
ed the binary inputs and outputs are available. In this case the signal exchange be-
tween 7SD610 and the external reclosure device must take place via the binary inputs
and outputs. It is also possible to have the integrated automatic reclosure function
controlled by an external protection (e.g. alternate protection).

Pickup

aborted aborted

Action
time

Trip
command
dead time dead time
Close 1st reclosure 2nd reclosure
command

aborted reclaim
Reclaim
time
time
1st reclosure unsuccessful; further 2nd reclosure successful, no further
tripping during off time tripping during off time
Reclosure
active start with 1st trip command

Figure 6-31 Timing diagram of a double-shot reclosure with action time (2nd reclosure successful)

7SD610 Manual 6-69


C53000-G1176-C145-1
Functions

6.9.1 Function Description

The integrated automatic reclosure function allows up to 8 reclosure attempts. The


first four reclosure cycles may operate with different parameters (active and dead
times, single/three-pole). The parameters of the fourth cycle apply from the fifth cycle
onwards.

Selectivity before In order for the automatic reclosure to be successful, all faults on the whole overhead
Reclosure line should be eliminated at both line ends at the same — as short as possible — time.
This is the usual case in differential protection because the strict selective zone defi-
nition of the protected object by the current transformer sets always allows undelayed
tripping.
However, fast tripping of the protection may also be desired before reclosure after trip-
ping by other short-circuit functions. For this purpose, every short-circuit protection
which can start the automatic reclosure function has the possibility of initiating unde-
layed tripping in at least one stage when the automatic reclosure function is ready for
the first reclosure cycle.
Fast tripping before reclosure is also possible for multiple reclosures. Appropriate links
between the output messages (e.g. 2nd reclosure ready: “$5&\F=RQH5HO”) and
the inputs for undelayed tripping of the protective functions can be established via the
binary inputs and outputs or the integrated user-definable logic functions (CFC).

Start Starting the automatic reclosure function means saving the first trip signal of a network
fault generated by a protection function operating with automatic reclosure. In the case
of multiple reclosure, starting therefore only takes place once with the first trip com-
mand. Saving this signal is the prerequisite for all subsequent activities of the auto-
matic reclosure function.
The starting is important when the first trip command does not appear until the end of
an action time (see below under “Action Times”).
Automatic reclosure is not started if the circuit breaker has not been ready for at least
one TRIP–CLOSE–TRIP–cycle at the instant of the first trip command. This can be
achieved by setting parameters. See also subtitle “Interrogation of Circuit Breaker
Ready” (page 6-72).
Setting parameters can be used for every short-circuit function to determine whether
or not this is to operate with reclosure, i.e. whether or not it is to start the automatic
reclosure function. The same applies accordingly for trip commands which are cou-
pled in externally via binary inputs and/or generated by transfer trip signals/remote
tripping.
The protection and monitoring functions of the device which do not react to short-cir-
cuit-like phenomena do not start the automatic reclosure because reclosure is of no
use here. In 7SD610, for example, this is the overload protection.

Action Times It is often desirable to suppress the readiness for reclosure if the short-circuit has ex-
isted for a certain time, e.g. because it is assumed that the arc has burned in to such
an extent that there is no longer any chance of automatic extinguishing during the
dead time. For reasons of selectivity also (see above), frequently delayed tripped
faults should not lead to reclosure.

6-70 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

The automatic reclosure function of 7SD610 can be operated with or without action
times (configuration parameter $5FRQWUROPRGH, address , see Section 5.1).
No starting signal is necessary for the protective functions or external protection
equipment without action time. Starting takes place as soon as the first trip command
appears.
In operation with action time, an action time is available for every reclosure cycle. The
action times are always started by the pickup signals linked with OR of all protective
functions which can start the automatic reclosure function. If there is still no trip com-
mand available at the end of an action time, the corresponding reclosure cycle cannot
be performed.
For every reclosure cycle, it can be set whether or not it allows a start. With the first
general fault detection, only those action times the cycles of which allow a start are
important because the other cycles may not start. Using the action times and the start
permission you can control which cycles can be run under different command time
conditions.
Example 1: 3 cycles are set. Starting is allowed for at least the first cycle. It is assumed
that the action times are set as follows:
$57$&7,21 = 0.2 s;
$57$&7,21 = 0.8 s;
$57$&7,21 = 1.2 s;
Since reclosure is ready before the fault occurs, the first trip following a fault is fast,
i.e. before the end of any action time. The automatic reclosure function is started as a
result. After unsuccessful reclosure the 2nd cycle would then become active; but the
time-overcurrent protection would not trip in this example until after 1 s according to
its grading plan. Since the action time for the second cycle was exceeded here, it is
disabled. The 3rd cycle with its parameters is therefore performed now. If the trip com-
mand after the 1st reclosure did not appear until after more than 1.2 s after the 1st re-
closure, there would be no further reclosure.
Example 2: 3 cycles are set. Starting is only allowed for the first. The action times are
set as in example 1.
The first protection trip takes place 0.5 s after starting. Since the action time for the 1st
cycle has already expired at this time, this cannot start the automatic reclosure func-
tion. However, the 2nd and 3rd cycles cannot take place because they do not allow a
start. There is therefore no reclosure, because no starting at all takes place.
Example 3: 3 cycles are set. Starting is allowed for at least the first two cycles.
The action times are set as in example 1.
The first protection trip takes place 0.5 s after starting. Since the action time for the 1st
cycle has already expired at this time, it cannot start the automatic reclosure function
but the 2nd cycle, for which starting is allowed, is activated immediately. This starts
the automatic reclosure function, the 1st cycle is practically skipped.

Operating Modes of The dead times — these are the times from elimination of the fault (drop off of the trip
the Automatic command or signalling via auxiliary contacts) to the start of the automatic close com-
Reclosure mand — may vary, depending on the automatic reclosure operating mode selected
when determining the function scope (Section 5.1) and the resulting signals of the
starting protective functions.
In the ZLWK75,3... operating mode single-pole or single/three-pole reclosure cycles
are possible if the device and the circuit-breaker are suitable. In this case different
dead times after single-pole tripping on the one hand and after three-pole tripping on
the other hand are possible (for every reclosure cycle). The tripping protective function

7SD610 Manual 6-71


C53000-G1176-C145-1
Functions

determines the type of tripping: single-pole or three-pole. Control of the dead time de-
pends on this.
In the ZLWK3,&.83... operating mode, different dead times can be set for every re-
closure cycle after single-, two- and three-phase faults. Decisive here is the starting
configuration of the protective functions at the time the trip command disappears. This
operating mode enables the dead times to be made dependent on the type of fault in
the case of three-pole reclosure cycles.

Blocking Reclosure Different events lead to blocking of automatic reclosure. No reclosure is possible for
example if it is blocked via a binary input. If the automatic reclosure has not yet been
started, it cannot be started at all. If a reclosure cycle is already in progress, dynamic
blocking takes place (see below).
Every cycle can also be blocked individually by a binary input. In this case the cycle
concerned is invalid and will be skipped in the sequence of permissible cycles. If block-
ing takes place while the cycle concerned is already running, this leads to aborting of
the reclosure, i.e. no reclosure takes place even if other valid cycles have been pa-
rameterized.
Internal blockings limited to certain times occur during the course of reclosure cycles:
The reclaim time 75(&/$,0 begins with every automatic reclosure command. If the
reclosure is successful, all the functions of the automatic reclosure return to the idle
state at the end of the reclaim time; a fault after the end of the reclaim time is treated
as a new fault in the network. Re-tripping of a protective function within this time initi-
ates the next reclosure cycle in the case of multiple reclosure; if no further reclosure
is permitted, the last reclosure is treated as unsuccessful in the case of re-tripping
within the reclaim time. The automatic reclosure is blocked dynamically.
The dynamic lock-out locks the reclosure for the duration of the dynamic lock-out time
(0.5 s). This occurs for example after a final tripping or other events which block the
automatic reclosure circuit after starting. Restarting is locked for this time. When the
time runs out, the automatic reclosure returns to its idle position and is ready for a new
fault in the network.
If the circuit-breaker is closed manually (by the control discrepancy switch via a binary
input, see also Section 6.13.1), the automatic reclosure is blocked for a manual–
close–blocking time 7%/2&.0&. If a trip command is given during this time, it can
be assumed that a metallic short-circuit has been reacted to (e.g. closed earthing iso-
lator). Every trip command within this time is therefore final. With the user definable
logic functions (CFC) other control functions such as a manual–close command can
be handled.

Interrogation of Precondition for a reclose attempt after fault clearance is that the circuit breaker is
Circuit Breaker ready for at least one TRIP–CLOSE–TRIP–cycle at the instant the automatic reclos-
Ready ure function is started (i.e. at the beginning of the first trip command). The readiness
of the circuit breaker is signalled to the device through the binary input “!&%5HDG\”
(FNo ). If no such signal is available, the circuit breaker interrogation can be sup-
pressed (presetting) because no automatic reclosure at all would be possible other-
wise.
This interrogation usually suffices for a single reclosure. Since, for example, the air
pressure or the spring tension for the circuit breaker actuation drops after the trip pro-
cedure, no further interrogation should take place.

6-72 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

It is of advantage, particularly in the case of multiple reclosure, to interrogate the


readiness of the circuit breaker not only at the instant of the first trip command but also
before every reclosure. The reclosure is blocked as long as the CB does not signal its
readiness for another TRIP–CLOSE–cycle.
The recovery time of the circuit breaker can be monitored by the 7SD610. This moni-
toring time &%7,0(287 begins as soon as the CB sends no ready signal. The dead
time may become longer if no readiness is signalled at the end of it. However, if the
circuit breaker does not signal readiness for a longer period than the monitoring time,
reclosure is locked out dynamically (see also above under subtitle “Blocking Reclos-
ure” page 6-72).

Processing the If the circuit breaker auxiliary contacts are connected to the device, the reaction of the
Auxiliary Contact circuit breaker is also checked for plausibility.
Position of the
In the case of individual control of the individual breaker poles this concerns every
Circuit Breaker
single breaker pole. This assumes that the auxiliary contacts are connected to the ap-
propriate binary inputs (“!&%3ROH/” (FNo ); “!&%3ROH/” (FNo )
and “!&%3ROH/” (FNo ) for each pole.
If the series circuits of the pole make contacts and break contacts are connected in-
stead of the individual poles, the CB is assumed to have all poles open when the se-
ries circuit of the break contacts is closed (binary input “!&%S2SHQ” (FNo )).
It is assumed to have all poles closed when the series circuit of the make contacts is
closed (binary input “!&%S&ORVHG” (FNo )). If none of these input messages
is available, it is assumed that the switch is open at one pole (even if this condition
also exists theoretically in a two-pole open CB).
The device checks the position of the circuit-breaker continuously: As long as the aux-
iliary contacts signal that the CB is not closed (three-pole), the automatic reclosure
function cannot be started. This guarantees that a close command can only be given
when the CB was previously tripped (out of the closed state).
The valid dead time begins when the trip command disappears or a signal is available
via the auxiliary contacts that the CB (pole) has opened.
If the CB opens at three-pole after a single-pole trip command, this is considered as a
three-pole tripping. If three-pole reclosure cycles are allowed, the dead time for three-
pole tripping becomes active in the operating mode with control by trip command (see
above under subtitle “Operating Modes of the Automatic Reclosure”, page 6-71); in
control by starting, the starting configuration of the starting protective function(s) is still
decisive. If three-pole cycles are not allowed, the reclosure is blocked dynamically.
The trip command was final.
The latter also applies if the CB is tripped at two poles by a single-pole trip command.
The device only detects this if the auxiliary contacts for every pole are connected in-
dividually. The device couples immediately with three poles resulting in a three-pole
trip command.
If the CB auxiliary contacts signal that at least one other pole has opened in the dead
time after single-pole tripping, a three-pole reclosure cycle is initiated with the dead
time for three-pole reclosure if allowed. If the auxiliary contacts are connected for eve-
ry pole individually, the device can detect a two-pole open CB. In this case the device
immediately sends a three-pole trip command providing the three-pole intertrip is ac-
tivated (see Sub-section 6.9.2 under subtitle “Three-pole Intertrip”, page 6-84).

7SD610 Manual 6-73


C53000-G1176-C145-1
Functions

Sequence of a If the automatic reclosure is ready, the short-circuit protection trips at three poles for
Three-pole all faults within the stage parameterized for auto-reclosure. The automatic reclosure
Auto-reclosure circuit is started. When the trip command drops off or the circuit breaker opens (aux-
iliary contact criterion) an (adjustable) dead time starts. At the end of this dead time
the circuit breaker receives a close command. At the same time the (adjustable) block-
ing time is started. If $5FRQWUROPRGH ZLWK3,&.83 ... was set under address
during configuration of the protective functions, different dead times can be pa-
rameterized depending on the type of protection start.
When the fault has been eliminated (successful reclosure), the reclaim time runs out
and all functions return to their rest state. The fault is cleared.
If the fault has not been eliminated (unsuccessful reclosure), the short-circuit protec-
tion finally trips after the protection stage valid without reclosure. Every fault during the
reclaim time also leads to final tripping.
After unsuccessful reclosure (final tripping), the automatic reclosure is locked out dy-
namically (see also above under subtitle “Blocking Reclosure”, page 6-72).
The sequence above applies for single-shot reclosure. In the 7SD610 multiple reclos-
ure (up to 8 shots) is also possible (see below).

Sequence of a Single-pole auto-reclosure cycles are only possible if the device is designed for single-
Single-pole pole tripping and this has been allowed in the protective function configuration (ad-
Auto-reclosure dress , see also Section 5.1). Of course, the circuit breaker must also be suitable
for single-pole tripping.
If the automatic reclosure is ready, the short-circuit protection trips at a single pole for
all single-phase faults within the stage parameterized for reclosure. It can also be de-
termined, by setting (address $ 7ULSSK)OW, see also Section 6.1.3), that
single-pole tripping takes place for two-phase, earth-free faults. Single-pole tripping is
only possible of course by short-circuit protective functions which can determine the
faulty phase.
In the case of multi-phase faults, the short-circuit protection trips finally at three poles
with the stage valid without reclosure. Every three-pole tripping is final. The automatic
reclosure is locked dynamically (see also above under subtitle “Blocking Reclosure”,
page 6-72).
The automatic reclosure is started in the case of single-pole tripping. The (adjustable)
dead time for the single-pole auto-reclosure cycle begins with dropping off of the trip
command or opening of the circuit breaker pole (auxiliary contact criterion). The circuit
breaker gets a close command after this. At the same time the (adjustable) reclaim
time is started. If the reclosure is blocked during the dead time after single-pole trip-
ping, immediate three-pole tripping can take place as an option (Three-pole Intertrip,
see below, page 6-84).
When the fault has been eliminated (successful reclosure), the reclaim time runs out
and all functions return to their rest state. The fault is cleared.
If the fault has not been eliminated (unsuccessful reclosure), the short-circuit protec-
tion finally trips after the protection stage valid without reclosure. Every fault during the
reclaim time also leads to final tripping.
After unsuccessful reclosure (final tripping) the automatic reclosure circuit is locked
dynamically (see also above under subtitle “Blocking Reclosure”, page 6-72).

6-74 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

The sequence above applies for single-shot reclosure. In the 7SD610 multiple reclos-
ure (up to 8 shots) is also possible (see below).

Sequence of a This operating mode is only possible if the device is designed for single-pole tripping
Single and Three- and this was allowed in the protective functions configuration (address 110, see also
pole Auto- section 5.1). Of course, the circuit-breaker must also be suitable for single-pole trip-
reclosure ping.
If the automatic reclosure circuit is ready, the short-circuit protection trips at one pole
for single-phase faults within the stage(s) configured for automatic reclosure and at
three poles for multi-phase faults. It can also be determined, by setting (address
$ 7ULSSK)OW, see also Section 6.1.3), that single-pole tripping takes place for
two-phase, earth-free faults. Single-pole tripping is only possible of course for short-
circuit protective functions which can determine the faulty phase. The stage valid be-
fore auto-reclosure applies for all fault types.
The automatic reclosure function is started in the case of tripping. Depending on the
type of fault the (adjustable) dead time for the single-pole auto-reclosure cycle or the
(separately adjustable) dead time for the three-pole auto-reclosure cycle begins with
the drop off of the trip command or opening of the circuit-breaker (pole). After this the
circuit-breaker receives a close command. At the same time the (adjustable) reclaim
time is started. If the reclosure is blocked during the pause after single-pole tripping,
immediate three-pole tripping can take place as an option (Three-pole Intertrip, see
below, page 6-84).
When the fault has been eliminated (successful reclosure), the reclaim time runs out
and all functions return to their rest state. The fault is cleared.
If the fault has not been eliminated (unsuccessful reclosure), the short-circuit protec-
tion initiates a final three-pole tripping with the protection stage valid without auto-
reclosure. Every fault during the reclaim time also leads to final three-pole tripping.
After unsuccessful reclosure (final tripping) the automatic reclosure function is locked
dynamically (see also above under subtitle “Blocking Reclosure”, page 6-72).
The sequence above applies for single-shot reclosure. In the 7SD610 multiple reclos-
ure (up to 8 shots) is also possible (see below).

Multiple Auto-re- If a fault still exists after a reclosure attempt, further reclosure attempts can be made.
closure Up to 8 reclosure attempts are possible with the automatic reclosure function integrat-
ed in 7SD610.
The first four reclosure cycles are independent of each other. Each one has separate
action and dead times, can operate with single- or three-pole trip and can be blocked
separately via binary inputs. The parameters and intervention possibilities of the fourth
cycle apply from the fifth cycle onwards.
The sequence is the same in principle as in the different reclosure programs described
above. However, if the first reclosure attempt is unsuccessful, the reclosure is not
blocked and the next reclosure cycle begins. The appropriate dead time starts with the
dropping off of the trip command or opening of the circuit breaker (pole) (auxiliary con-
tact criterion). The circuit breaker gets a new close command after this. At the same
time the reclaim time is started.
Until the set number of permissible AR-shots has been reached, the reclaim time is
reset with a new trip command after reclosure and starts again with the next close
command.

7SD610 Manual 6-75


C53000-G1176-C145-1
Functions

If one of the cycles is successful, i.e. the fault no longer exists after reclosure, the re-
claim time expires and all functions go into their rest states. The fault is cleared.
If none of the cycles is successful, a final three-pole tripping after the grading time valid
without reclosure takes place after the last permissible reclosure of the short-circuit
protection. The automatic reclosure is locked dynamically (see also above under sub-
title “Blocking Reclosure”, page 6-72).

Handling When single-pole or single- and three-pole reclosure cycles are executed in the
Evolving Faults network, particular attention must be paid to evolving faults.
Evolving faults are faults which occur during the dead time after eliminating the first
fault.
There are various ways of handling evolving faults in the 7SD610 depending on the
requirements of the network:
For detection of an evolving fault you can select whether the trip command of a pro-
tective function during the dead time or every further fault detection (pick-up) is the cri-
terion for an evolving fault.
There are also various selectable possibilities for the response of the internal auto-
reclosure to a detected evolving fault.
a) (9)/702'(Stops AutoRecl:
The reclosure is blocked as soon as a evolving fault is detected. Tripping caused
by the evolving fault is three-pole. This applies irrespective of whether three-pole
cycles have been permitted or not. There are no further reclosure attempts; the
auto-reclosure is locked dynamically (see also above under subtitle “Blocking Re-
closure”, page 6-72).
b) (9)/702'( VWDUWVS$5:
As soon as an evolving fault is detected it switches over to a cycle for three-pole
auto-reclosure. Every trip command is three-pole. The separately settable dead
time for evolving faults begins with elimination of the evolving fault; after this the cir-
cuit-breaker gets a close command. The further procedure is the same as for single-
and three-pole cycles.
The complete dead time in this case consists of the part of the dead time for the
single-pole reclosure up to elimination of the evolving fault plus the dead time for
the evolving fault. This is useful because especially the duration of the dead time
during the three-pole tripping is important for the stability of the network.
If auto-reclosure is blocked due to an evolving fault without the protection sending a
three-pole trip command (e.g. for evolving fault detection with pickup), the device can
send a three pole trip command so that the circuit-breaker does not remain open at
one pole (Three-pole Intertrip, see below, page 6-84).

Dead Line Check If the voltage of a disconnected phase does not disappear after tripping on a fault, the
(DLC) auto-reclosure can be prevented. This presupposes that the voltage transformers are
arranged on the line side and connected to the device. This has to be in accordance
with the configuration described in Section 5.1. To do this the dead line check is
switched active. The automatic reclosure function then checks the disconnected line
for no-voltage: The line must have been dead for at least an adequate measuring time
during the dead time. If not the reclosure is locked dynamically.

6-76 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

This dead-line check on the line is of advantage if a small generator (e.g. wind gener-
ator) is linked along the line.

Adaptive In all the previous possibilities it has been assumed that defined and equal dead times
Dead Time (ADT) have been set at both line ends, if necessary for different fault types and/or auto-re-
closure cycles.
It is also possible to set the dead times (if necessary different for various fault types
and/or auto-reclosure cycles) at one line end only and to configure the adaptive dead
time at the other end. This presumes that the voltage transformers are arranged on
the line side.
Figure 6-32 shows an example. It is assumed that the device I is operating with de-
fined dead times whereas the adaptive dead time is configured at position II. It is im-
portant that the line is fed from busbar A at least, i.e. the side with the defined dead
times.
With the adaptive dead time the automatic reclosure function at the line end II decides
independently whether and when reclosure is useful and permissible and when it is
not. The criterion is the line voltage at end II, which was through-connected from end
I after fault clearance. Reclosure therefore takes place at end II as soon as it is clear
that voltage has been re-applied to the line from end I.
In the implied fault, the lines in the example are disconnected at positions I and II. In
I reclosure takes place after the dead time parameterized there. I
If the fault has been cleared (successful reclosure), line A–B is re-connected to the
voltage at busbar A through position I. Device II detects this voltage and also recloses
after a short delay (to ensure a sufficient voltage measuring time). The fault is cleared.
If the fault has not been cleared after reclosure at I (unsuccessful reclosure), the fault
is re-connected at I, no healthy voltage appears at II. The device there detects this
and does not reclose.
In the case of multiple reclosure the process may be repeated several times in the
case of unsuccessful reclosure until one of the reclosures is successful or a final trip-
ping takes place.

A B overreaching time-graded protection

I Diff–zone II A, B busbars
(defined pauses) (ADT) I, II relais locations

Figure 6-32 Example of adaptive dead time (ADT)

As the example shows, the adaptive dead time has the following advantages:
• The circuit-breaker at position II is not reclosed at all if the fault persists and is con-
served as a result.
• With non-selective tripping on an external fault due to an overreaching time-graded
protection at position I no further auto-reclosure attempts can occur here because
the fault path via busbar B and position II remains interrupted even after several re-
closure attempts.

7SD610 Manual 6-77


C53000-G1176-C145-1
Functions

• At position I overreaching is allowed in the case of multiple reclosures and even in


the case of final tripping because the line remains open at position II and no actual
overreach can occur as a result at I.

Close Command With close command transmission the dead times are only set at one line end. The
Transmission other is set to “adaptive dead time”. The latter only reacts to the received close com-
(Remote Close) mands from the transmitting end.
The transmission of the close command at the transmitting line end is delayed long
enough to make sure that a close command is only sent when the local reclosure was
successful. This means one more possible local fault detection is awaited after reclos-
ure. This delay prevents unnecessary closing at the remote end on the one hand but
also lengthens the time until reclosure takes place there. This is not critical for a single-
pole auto-reclosure or in radial or meshed networks because no stability problems are
to be expected.
In the differential protection the protection data interfaces are used to transmit the
close command.

Control of the If 7SD610 is equipped with the internal automatic reclosure function, this can also be
Internal Automatic controlled by an external protection device. This is useful for example for line ends with
Reclosure by an redundant protection or backup protection when a second protection is used for the
External Protection same line end and is to work with the automatic reclosure function integrated in the
Device 7SD610.
The binary inputs and outputs provided must be observed in this case. It must be de-
cided whether the internal auto-reclosure is to be controlled by the starting (pickup) or
by the trip command of the external protection (see also above under “Operating
Modes of the Automatic Reclosure“, page 6-71).
If the auto-reclosure is controlled by the trip command, the following inputs and out-
puts are to be recommended:
The auto-reclosure is started via the binary inputs:
!$56WDUW general fault detection (pickup for the automatic reclosure (on-
ly required for action time),
!7ULS/$5 trip command L1 for automatic reclosure,
!7ULS/$5 trip command L2 for automatic reclosure,
!7ULS/$5 trip command L3 for automatic reclosure,
The general fault detection is decisive for starting the action times. It is also necessary
if the automatic reclosure is to detect evolving faults by fault detection. In other cases
this input information is superfluous.
The trip commands decide whether the dead time for single-pole or three-pole auto-
reclosure cycles is active or whether the reclosure is blocked in three-pole tripping (de-
pending on the parameterization of dead times).
Figure 6-33 shows the interconnection between the internal automatic reclosure of
7SD610 and an external protection device as a connection example.
To couple the external protection at three poles and to release its accelerated stages
before reclosure if necessary, the following output functions are suitable:

6-78 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

$5S7ULS3HUP internal automatic reclosure ready for 1-pole reclose


cycle, i.e. allows 1-pole tripping (logic inversion of the 3-
pole coupling).
$5&\F=RQH5HO internal automatic reclosure ready for the first reclose
cycle, i.e. enables the stage of the external protection de-
cisive for reclosure, the appropriate outputs can be used
for other cycles. The output can be omitted if the external
protection requires no overreach stage (e.g. differential
protection or comparison schemes with distance protec-
tion).
$53URJUDPSROHi internal automatic reclosure is programmed for single-
pole AR, i.e. only reclosures after single-pole tripping.
The output can be omitted if no overreach stage is used
(e.g. differential protection or comparison schemes with
distance protection).
Instead of the three phase-dedicated trip commands, the single-pole and three-pole
tripping can be signalled to the internal automatic reclosure — providing the external
protection device allows—, i.e. assign the following binary inputs of the 7SD610:
!$56WDUW general fault detection for the internal automatic
reclosure (only required for action time),
!7ULSSIRU$5 trip command 1-pole for the internal automatic reclosure,
!7ULSSIRU$5 trip command 3-pole for the internal automatic reclosure.
If only three-pole reclosure cycles are to be executed, it is sufficient to assign the bi-
nary input “!7ULSSIRU$5” (FNo ) for the trip signal. Figure 6-34 shows an
example. Any overreaching stages of the external protection are enabled again by “$5
&\F=RQH5HO” (FNo ) and of further cycles if necessary.

7SD610 Manual 6-79


C53000-G1176-C145-1
Functions

external
protection 7SD610
device
AR Start >AR Start

Tripping L1 >Trip L1 AR

Tripping L2 >Trip L2 AR

Tripping L3 >Trip L3 AR

L+ L–
Relay Pickup AR 1.CycZoneRel
(if nec. for further AR)

3-phase coupling AR 1p Trip Perm

only 1-pole AR Program1pole

L– L–

Figure 6-33 Connection example with external protection device for 1-/3-pole reclosure;
AR control mode = ZLWK3,&.83

external
protection 7SD610
device
trip >AR Start

Tripping AR 1p Trip Perm

L+ L–

Relay Pickup AR 1.CycZoneRel


(if nec. for further AR)
L– L+

Figure 6-34 Connection example with external protection device for 3-pole reclosure;
AR control mode = ZLWK75,3

If, on the other hand, the internal automatic reclosure function is controlled by the pick-
up, the phase-dedicated pickup signals must be connected by the external protection.
The general trip command then suffices for tripping (FNo ). Figure 6-35 shows
connection examples.

6-80 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

external
protection 7SD610
device
Pick-up L1 !3LFNXS/$5

Pick-up L2 !3LFNXS/$5

Pick-up L3 !3LFNXS/$5

Tripping !7ULSIRU$5

L+ L–
Release AR Stage AR 1.CycZoneRel
(if nec. for other AR)
L– L+
Pickup signal for each phase

external
protection 7SD610
device
Pick-up 1-phase !3LFNXSSK$5

Pick-up 2-phase !3LFNXSSK$5

Pick-up 3-phase !3LFNXSSK$5

Tripping !7ULSIRU$5

L+ L–
Release AR Stage $5&\F=RQH5HO
(if nec. for other AR)
L– L+
Pickup signal 1-phase, 2-phase and 3-phase

Figure 6-35 Connection example with external protection device for fault detection depend-
ent dead time — dead time control by start signals of the protection device;
AR control mode = ZLWK3,&.83

7SD610 Manual 6-81


C53000-G1176-C145-1
Functions

6.9.2 Setting the Function Parameters

General If no reclosure takes place on the branch for which the differential protection 7SD610
is used (e.g. for cables, transformers, motors or similar), the automatic reclosure func-
tion must be removed from the configuration (see Section 5.1, address ). The au-
tomatic reclosure circuit is then totally inactive, i.e. the automatic reclosure is not op-
erated in the 7SD610. There are no signals to this effect, binary inputs for the auto-
matic reclosure are ignored. All parameters for setting the automatic reclosure are in-
accessible and insignificant.
If, on the other hand, the internal automatic reclosure circuit is to be used, the type of
reclosure must be set in the configuration of the device scope (see Section 5.1) under
address  $8725(&/26( and the $5FRQWUROPRGHunder address .
Up to 8 reclosure attempts are possible with the integrated automatic reclosure func-
tion of 7SD610. Whereas the settings in the addresses  to  are common to
all reclosure cycles, the individual settings of the cycles are made from address 
onwards. You can set different individual parameters for the first four reclosure cycles.
The parameters of the fourth cycle apply from the fifth cycle onwards.
Under address  $8725(&/26( the automatic reclosure function can be
switched 2Q or 2II.
Prerequisite for an automatic reclosure being possible after a short-circuit tripping is
that the circuit breaker is ready for at least one TRIP–CLOSE–TRIP–cycle at the in-
stant the auto-reclosure is started (i.e. at the start of the first trip command). The read-
iness of the circuit breaker is signalled to the device through the binary input “!&%
5HDG\” (FNo ). If no such signal is available, leave the setting under address
 &%"75,3 = 1R because no auto-reclosure would be possible at all other-
wise. If circuit breaker interrogation is possible, you should set &%"75,3 = <HV.
The readiness of the circuit breaker can still be interrogated before every reclosure.
This is set when setting the individual reclosure cycles (see below).
To check the circuit breaker is ready again during the dead times, you can set a circuit
breaker–ready–monitor time under address  &%7,0(287. The time is set
slightly higher than the recovery time of the circuit breaker after a TRIP–CLOSE–
TRIP–cycle. If the circuit breaker is not ready again by the time this runs out, there is
no reclosure, the auto-reclosure is locked dynamically.
Waiting for the circuit breaker to be ready can lead to a lengthening of the dead times.
Interrogation of a synchronism check (if used) can also delay reclosure. To avoid un-
controlled prolongation you can set a maximum lengthening of the dead time in this
case under address $ 7'($'(;7. This lengthening is unlimited if you set ∞.
This parameter can only be changed with DIGSI® 4 under “Additional Settings”. Re-
member that longer dead times are only permissible after three-pole tripping when no
stability problems occur or a synchronism check takes place before reclosure.
The reclaim time 75(&/$,0 (address ) is the time after which the network fault
is considered ended after a successful reclosure. Re-tripping of a protective function
within this time initiates the next reclosure cycle in the case of multiple reclosure; if no
further reclosure is permitted, the last reclosure is treated as unsuccessful. The re-
claim time must therefore be longer than the longest command time of a protective
function which can start the automatic reclosure function.

6-82 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

A few seconds are generally sufficient. In regions with frequent thunderstorms or


storms a shorter reclaim time is advisable to reduce the danger of final tripping as a
result of repeated lightning strikes or conductor flashovers (conductor vibration).
A long reclaim time must be selected if there is no circuit breaker monitoring possibility
in the case of multiple reclosure (see above) (e.g. due to missing auxiliary contacts
and CB–ready–information). Then the reclaim time must be longer than the recovery
time of the circuit breaker.
The blocking duration in manual–close–detection 7%/2&.0& (address ) must
guarantee safe switching on and off of the circuit-breaker (0.5 s to 1 s). If a fault was
detected by a protective function within this time after detected closing of the circuit
breaker, no reclosure takes place and final three-pole tripping takes place. If this is un-
desirable, address  is set to .
The options for handling evolving faults are described in Section 6.9.1 under subtitle
“Handling Evolving Faults”, page 6-76. The handling of evolving faults is not relevant
for line ends where the adaptive dead time is applied (address  $XWR5HFORVH
= ADT, Section 5.1). Addresses  and  are therefore insignificant and inac-
cessible for these devices.
You can define recognition of an evolving fault under address . (9)/75(&
2* ZLWK3,&.83means that, during a dead time, every fault detection (pickup) of
a protective function will be interpreted as an evolving fault. With (9)/75(&2*
ZLWK75,3a fault during a dead time is only interpreted as an evolving fault if it has
led to a trip command of a protective function. This may also include trip commands
which are coupled in externally via a binary input or which have been transmitted from
the other end of the protected object. If an external protection device operates togeth-
er with the auto-reclosure, evolving fault detection with pickup presupposes that a
pickup signal of the external device is also connected to the 7SD610; otherwise an
evolving fault can only be detected with the external trip command even if ZLWK
3,&.83 was set here.
Select the reaction to evolving faults under address . (9)/702'( EORFNV
$5 means that no reclosure takes place after detection of an evolving fault. This is al-
ways useful when only single-pole reclosure is to take place or when stability problems
are to be expected due to closing after an subsequent three-pole dead time. If a three-
pole reclosure cycle is to be initiated by tripping of the evolving fault, set (9)/7
02'( 6WDUW7GHDG(9. In this case a three-pole reclosure with separately adjust-
able dead time is started with the three-pole trip command on the evolving fault. This
is only useful if three-pole reclosure is also permitted.
Address  76WDUW021,725 monitors the reaction of the circuit breaker after a
trip command. If the CB has not opened after this time (from the beginning of the trip
command), the automatic reclosure is locked dynamically. The criterion for opening is
the position of the circuit breaker auxiliary contact(s) or the disappearance of the trip
command. If a circuit breaker failure protection (internal or external) is used on the
feeder, this time should be shorter than the delay time of the circuit breaker failure pro-
tection so that no reclosure takes place if the circuit breaker fails.
If the reclosure command is transmitted to the other end, you can delay this transmis-
sion with address  75HPRWH&ORVH. This transmission requires that the device
at the remote end operates with adaptive dead time (address $8725(&/26(
= $GDSWLYH'HDG7LPHat the remote end, see also Section 5.1). This parameter
is otherwise irrelevant. If no transmission of the close command is desired, although
ASP is set at the other end, set 75HPRWH&ORVH = ∞. On the one hand, this delay
can prevent the device being reclosed unnecessarily at the remote end when local re-

7SD610 Manual 6-83


C53000-G1176-C145-1
Functions

closure is unsuccessful. It should therefore be a total of the closing time of the circuit
breaker, the maximum response time and command duration of the protection func-
tion, the tripping time of the circuit breaker, the drop-off time of the protection function
and a safety margin. On the other hand, it must be noted that the line is not available
for energy transport until the remote end has also closed. It must therefore be added
to the dead time in the consideration of the network stability.

Configuration of The configuration concerns the interaction between the protective and additional func-
the Automatic tions of the device and the automatic reclosure function. Here you can determine
Reclosure which functions of the device are to start the automatic reclosure and which not.
In 7SD610 this concerns:
Address  $5:,7+',)), i.e. with differential protection,
Address  $5Z627)2&, i.e. with instantaneous high–speed overcurrent
tripping,
Address  $5:,7+,75,3, i.e. with intertrip and remote trip,
Address  $5Z'77, i.e. with externally coupled direct trip command,
Address  $5Z%DFN8S2&, i.e. with time overcurrent protection.
For the functions which are to start the automatic reclosure circuit, the corresponding
address is set to <HV, for the others to 1R. The other functions (overload protection,
breaker failure protection) cannot start the automatic reclosure because reclosure is
of no use here.

Three-pole If reclosure is blocked during the dead time of a single-pole cycle without a three-pole
Intertrip trip command having been given, the breaker remains open at one pole. With address
 $575,3SROH you determine that the tripping logic of the device sends a
three-pole trip command in this case (synchronized pole-unit operation). Set this ad-
dress to <HV if the breaker can be controlled single-pole and has no pole discrepancy
supervision itself. But otherwise the device pre-empts the pole discrepancy supervi-
sion of the CB because the three-pole transfer trip of the device is immediately active
as soon as the reclosure is blocked after single-pole tripping or the CB auxiliary con-
tacts report an implausible switch position (see also Section 6.9.1 under subtitle
“Processing the Auxiliary Contact Position of the Circuit Breaker“, page 6-73). The
three-pole intertrip is also active when only three-pole cycles are allowed but a single-
pole tripping is signalled externally through a binary input.
The transfer trip is unnecessary if only a common three-pole control of the circuit
breaker is possible.

Dead Line Check Under address  the dead line check can be switched active. It presupposes that
(DLC) the voltage transformers are arranged on the line side of the feeder. If this is not the
case or the function is not used, set '/&5'7 = ZLWKRXW.
'/&5'7 = '/& means that the dead line check is used. An automatic reclosure is
only possible if it was clear on beforehand that the line was dead. In this case, the
phase-earth voltage limit is set in address  8OLYH! below which the line is to
be considered voltage-free (disconnected). The setting is made in Volts secondary.
This value can be entered as a primary value when parameterizing with a PC and
DIGSI® 4. Address  78VWDEOHdetermines the measuring time available for
determining the no-voltage state.

Adaptive When operating with adaptive dead time, it should be ensured in advance that one end
Dead Time (ADT) per line operates with defined dead times and has an infeed. The other may operate

6-84 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

with adaptive dead time. You will find details about the procedure in Section 6.9.1 un-
der subtitle “Adaptive Dead Time (ADT)” on page 6-77 and “Close Command Trans-
mission (Remote Close)“, page 6-78.
For the line end with defined dead times the number of desired reclosure cycles must
be set in the configuration of the protective functions (Section 5.1) under address
 $8725(&/26(. Additionally the intertrip command of the differential protection
should be activated (see Section 6.4.2, address ,75,36(1' = <HV). For the
devices operating with adaptive dead time $8725(&/26( = $'7 must be set in the
configuration of the protective functions (Section 5.1) under address . Only the
parameters described below are interrogated in the latter case. No settings are then
made for the individual reclosure cycles.
The adaptive dead time may be voltage-controlled or Remote–CLOSE–controlled.
Both is even possible at the same time. In the first case, reclosure after tripping takes
place as soon as the voltage from the re-energized remote end is detected. This re-
quires that the voltage transformers are arranged on the line side of the feeder and
connected to the device. With Remote–CLOSE–controlled adaptive dead time, the
auto-reclosure function waits for the reception of the remote close command from the
remote end.
The action time 7$&7,21$'7 (address ) is the time after pickup by any pro-
tective function which can start the automatic reclosure and within which the trip com-
mand must appear. If the command does not appear until after the action time, there
is no reclosure. Depending on the configuration of the functional scope (see Section
5.1) the action time may also be omitted; this applies especially when a starting pro-
tective function has no pickup signal.
The dead times are determined by the reclosure command of the device at the line
end with the defined dead times. In cases where this reclosure command is absent,
e.g. because the reclosure has been blocked there in the meantime, the auto-reclos-
ure function of the local device must return to the rest state at some time. This takes
place after the maximum wait time 70$;$'7 (address ). It must be long
enough to include the last reclosure of the remote end. In the case of single-shot re-
closure, the sum of maximum dead time plus reclaim time of the device of the opposite
end is sufficient. In the case of multiple reclosure the worst case is that all reclosures
of the other end except the last are unsuccessful. The time of all these cycles must be
taken into account. To save having to make exact calculations, you can use the sum
of all dead times and all command times of the trippings plus a reclaim time.
Under address  $'7SDOORZHG you can determine whether single-pole trip-
ping is to be allowed (on condition that single-pole tripping is at all possible). If 1R, the
protection trips three-pole for all fault types. If <HV the tripping possibilities of the start-
ing protective functions are decisive.
Under address  $'7&%"&/26( you determine whether circuit breaker ready
is to be interrogated before reclosure after adaptive dead time. If you set <HV the dead
time may be longer if at the end of this time the circuit breaker is not ready for a
CLOSE–TRIP–cycle, by the circuit-breaker–monitoring time at the most; this was set
for all reclosure cycles under address  (see above). You will find details about
the circuit-breaker–monitoring in the function description, Section 6.9.1, under subtitle
“Interrogation of Circuit Breaker Ready“, page 6-72.
If there is a danger of stability problems in the network during a three-pole reclosure
cycle, you should set address  $'76\Q5HTXHVW to <HV. In this case a check
is made before reclosure following three-pole tripping whether the voltages of the
feeder and busbar are sufficiently synchronized. This on condition that an external

7SD610 Manual 6-85


C53000-G1176-C145-1
Functions

synchro-check device is available for this. If only single-pole reclosure cycles are ex-
ecuted or no stability problems are to be expected during three-pole dead times (e.g.
due to close meshing of the network or in radial networks), set address  to 1R.
Addresses  and  are only significant if the voltage-controlled adaptive dead
time is used. Set under address  8OLYH! the limit voltage phase–earth above
which the line is to be considered fault-free. It must be lower than the smallest operat-
ing voltage to be expected. The setting is made in Volts secondary. This value can be
entered as a primary value when parameterizing with a PC and DIGSI ® 4. Address
 78VWDEOH determines the measuring time available for determining the volt-
age. It should be longer than any transient oscillations when connecting the line.

1st Reclosure If you are working on a line with adaptive dead time, no other parameters are interro-
Cycle gated for the individual reclosure cycles here. All following parameters assigned to the
individual cycles are then superfluous and inaccessible.
Under address  $567$57 is only available, if the automatic reclosure oper-
ates with action time, i.e. if the address $5FRQWUROPRGH ZLWK3LFNXS
DQG7DFWLRQ or ZLWK 7ULSDQG7DFWLRQ(the first only for three-pole tripping)
was already set during the configuration of the protective functions (refer to Section
5.1). It determines whether an automatic reclosure start is to take place at all with the
first cycle. This address is included mainly for the sake of uniformity of the parameters
for every reclosure attempt and must be answered with <HV for the first cycle. If sev-
eral cycles are run you can control the effectivity of the cycles with this parameter and
different action times. Notes and examples can be found in Section 6.9.1 under sub-
title “Action Times” (page 6-70).
The action time $57$&7,21 (address ) is the time after pickup of any pro-
tective function which can start the automatic reclosure function within which the trip
command must appear. If the command does not appear until after the action time,
there is no reclosure. Depending on the configuration of the functional scope (see
Section 5.1) the action time may also be omitted; this applies especially when a start-
ing protective function has no pickup information.
Depending on the configured operating mode of the automatic reclosure (see Section
5.1 under address  $5FRQWUROPRGH) only addresses  and  (if op-
erating mode ZLWK7ULS...) or the addresses  to  (if operating mode ZLWK
3LFNXS) are available.
In the operating mode with Trip... you can set different dead times for single-pole and
three-pole reclosure cycles. Whether single-pole or three-pole tripping takes place de-
pends solely on the starting protective functions. Single-pole tripping is only possible
of course if the device and the corresponding protective function are also suitable for
single-pole tripping.
Address  $57GHDG7ULS is the dead time after 1-pole tripping,
address  $57GHDG7ULS is the dead time after 3-pole tripping.
If you only want to allow a single-pole reclosure cycle, set the dead time for three-pole
tripping to ∞. If you only want to allow a three-pole reclosure cycle, set the dead time
for single-pole tripping to ∞; the protection then trips three-pole for every fault type.
The dead time after single-pole tripping (if set) $57GHDG7ULS (address )
should be long enough for the fault arc to be extinguished and the surrounding air is
de-ionized so that the reclosure promises to be successful. The longer the line, the
longer this time due to the recharging of the conductor capacitances. The usual values
are 0.9 s to 1.5 s.

6-86 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

For three-pole tripping (address  $57GHDG7ULS) the stability of the network
is the main concern. Since the disconnected line cannot develop any synchronizing
power, only a short dead time is often permitted. The usual values are 0.3 s to 0.6 s.
If the device is operating with a synchronism checker, a longer dead time may be tol-
erated under certain circumstances. Longer three-pole pauses are also possible in ra-
dial networks.
In the control mode with 3LFNXS... you can make the dead times dependent on the
type of pickup of the starting protective function(s):
address  $57GHDG)OW is the dead time after 1-phase pickup,
address  $57GHDG)OW is the dead time after 2-phase pickup,
address  $57GHDG)OW is the dead time after 3-phase pickup.
If the dead time is to be the same for all types of faults, set all three parameters the
same. Note that these settings only cause different dead times for different pickups.
The tripping can only be three-pole.
If you have set VWDUWVS$5when setting the reaction to evolving faults (see above
under “General”, page 6-82) address  (9)/702'(, you can set a separate
dead time $57GHDG(9 (address ) for the three-pole pause after tripping
the evolving fault. Stability aspects are also decisive here. Normally it can be set such
as address  $57GHDG7ULS.
Under address  $5&%"&/26( you determine whether circuit-breaker
ready is to be interrogated before this first reclosure. If you set <HV, the dead time may
be longer if at the end of it the circuit breaker is not ready for a CLOSE–TRIP–cycle,
by the circuit-breaker–monitoring time at the most; this was set for all reclosure cycles
together under address  (see above). You will find details about the circuit-break-
er–monitoring in the function description, Section 6.9.1, under subtitle “Interrogation
of Circuit Breaker Ready”, page 6-72.
If there is a danger of stability problems in the network during a three-pole reclosure
cycle, you should set address  $56\Q5HTXHVW to <HV. In this case a check
is made first before every reclosure following three-pole tripping whether the voltages
of the feeder and busbar are sufficiently synchronized. This on condition that an exter-
nal device is available for synchronism checking. If only single-pole reclosure cycles
are executed or no stability problems are to be expected during three-pole dead times
(e.g. due to close meshing of the network or in radial networks), set address  to
1R.

2nd to 4th If several cycles have been set in the configuration of the function scope (Section 5.1),
Reclosure Cycle you can set individual reclosure parameters for the 2nd to 4th cycles. The possibilities
are the same as for the 1st cycle. Only some of the following parameters may be avail-
able here depending on the configuration of the protective function (Section 5.1).
For the 2nd cycle:
Address  $567$57; start in 2nd cycle allowed at all
Address  $57$&7,21; active time for the 2nd cycle
Address  $57GHDG)OW; dead time after 1-phase starting
Address  $57GHDG)OW; dead time after 2-phase starting
Address  $57GHDG)OW; dead time after 3-phase starting
Address  $57GHDG7ULS; dead time after 1-pole tripping
Address  $57GHDG7ULS; dead time after 3-pole tripping
Address  $57GHDG(9; dead time in case of sequential fault

7SD610 Manual 6-87


C53000-G1176-C145-1
Functions

Address  $5&%"&/26(; check CB ready before reclosure


Address  $56\Q5HTXHVW; synchronism check after 3-pole tripping
For the 3rd cycle:
Address  $567$57; start in 3rd cycle allowed at all
Address  $57$&7,21; active time for the 3rd cycle
Address  $57GHDG)OW; dead time after 1-phase starting
Address  $57GHDG)OW; dead time after 2-phase starting
Address  $57GHDG)OW; dead time after 3-phase starting
Address  $57GHDG7ULS; dead time after 1-pole tripping
Address  $57GHDG7ULS; dead time after 3-pole tripping
Address  $57GHDG(9; dead time in case of sequential fault
Address  $5&%"&/26(; check CB ready before reclosure
Address  $56\Q5HTXHVW; synchronism check after 3-pole tripping
For the 4th cycle:
Address  $567$57; start in the 4th cycle allowed at all
Address  $57$&7,21; active time for the 4th cycle
Address  $57GHDG)OW; dead time after 1-phase starting
Address  $57GHDG)OW; dead time after 2-phase starting
Address  $57GHDG)OW; dead time after 3-phase starting
Address  $57GHDG7ULS; dead time after 1-pole tripping
Address  $57GHDG7ULS; dead time after 3-pole tripping
Address  $57GHDG(9; dead time in case of sequential fault
Address  $5&%"&/26(; check CB ready before reclosure
Address  $56\Q5HTXHVW; synchronism check after 3-pole tripping

5th to 8th If more than 4 cycles have been set in the configuration of the function scope (Section
Reclosure Cycles 5.1), the cycles following the fourth cycle operate with the same settings as the fourth
cycle.

6.9.3 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


3401 AUTO RECLOSE OFF ON Auto-Reclose Function
ON

3402 CB? 1.TRIP YES NO CB ready interrogation at 1st trip


NO

3403 T-RECLAIM 0.50..300.00 sec 3.00 sec Reclaim time after successful
AR cycle

3404 T-BLOCK MC 0.50..300.00 sec; 4 1.00 sec AR blocking duration after man-
ual close

3406 EV. FLT. RECOG. with Pickup with Trip Evolving fault recognition
with Trip

3407 EV. FLT. MODE Stops Auto Reclose starts 3pole AR-cy- Evolving fault (during the dead
starts 3pole AR-cycle cle time)

6-88 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

Addr. Setting Title Setting Options Default Setting Comments


3408 T-Start MONITOR 0.01..300.00 sec 0.50 sec AR start-signal monitoring time

3409 CB TIME OUT 0.01..300.00 sec 3.00 sec Circuit Breaker (CB) Supervision
Time

3410 T RemoteClose 0.00..300.00 sec; ∞ 0.20 sec Send delay for remote close
command

3411A T-DEAD EXT. 0.50..300.00 sec; ∞ ∞ sec Maximum dead time extension

3450 1.AR: START YES YES Start of AR allowed in this cycle


NO

3451 1.AR: T-ACTION 0.01..300.00 sec; ∞ 0.20 sec Action time

3453 1.AR Tdead 1Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults

3454 1.AR Tdead 2Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults

3455 1.AR Tdead 3Flt 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults

3456 1.AR Tdead1Trip 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip

3457 1.AR Tdead3Trip 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip

3458 1.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault

3459 1.AR: CB? CLOSE YES NO CB ready interrogation before


NO reclosing

3460 1.AR SynRequest YES NO Request for synchro-check after


NO 3pole AR

3461 2.AR: START YES NO AR start allowed in this cycle


NO

3462 2.AR: T-ACTION 0.01..300.00 sec; ∞ 0.20 sec Action time

3464 2.AR Tdead 1Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults

3465 2.AR Tdead 2Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults

3466 2.AR Tdead 3Flt 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults

3467 2.AR Tdead1Trip 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip

3468 2.AR Tdead3Trip 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip

3469 2.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault

3470 2.AR: CB? CLOSE YES NO CB ready interrogation before


NO reclosing

3471 2.AR SynRequest YES NO Request for synchro-check after


NO 3pole AR

3472 3.AR: START YES NO AR start allowed in this cycle


NO

3473 3.AR: T-ACTION 0.01..300.00 sec; ∞ 0.20 sec Action time

3475 3.AR Tdead 1Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults

3476 3.AR Tdead 2Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults

3477 3.AR Tdead 3Flt 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults

7SD610 Manual 6-89


C53000-G1176-C145-1
Functions

Addr. Setting Title Setting Options Default Setting Comments


3478 3.AR Tdead1Trip 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip

3479 3.AR Tdead3Trip 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip

3480 3.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault

3481 3.AR: CB? CLOSE YES NO CB ready interrogation before


NO reclosing

3482 3.AR SynRequest YES NO Request for synchro-check after


NO 3pole AR

3483 4.AR: START YES NO AR start allowed in this cycle


NO

3484 4.AR: T-ACTION 0.01..300.00 sec; ∞ 0.20 sec Action time

3486 4.AR Tdead 1Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults

3487 4.AR Tdead 2Flt 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults

3488 4.AR Tdead 3Flt 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults

3489 4.AR Tdead1Trip 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip

3490 4.AR Tdead3Trip 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip

3491 4.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault

3492 4.AR: CB? CLOSE YES NO CB ready interrogation before


NO reclosing

3493 4.AR SynRequest YES NO Request for synchro-check after


NO 3pole AR

3420 AR WITH DIFF YES YES AR with differential protection ?


NO

3421 AR w/ SOTF-O/C YES YES AR with switch-onto-fault over-


NO current

3423 AR WITH I.TRIP YES YES AR with intertrip ?


NO

3424 AR w/ DTT YES YES AR with direct transfer trip


NO

3425 AR w/ BackUpO/C YES YES AR with back-up overcurrent


NO

3430 AR TRIP 3pole YES NO 3pole TRIP by AR


NO

3431 DLC / RDT Without Without Dead Line Check / Reduced


Reduced Dead Time (RDT) Dead Time
Dead Line Check (DLC)

3433 T-ACTION ADT 0.01..300.00 sec; ∞ 0.20 sec Action time

3434 T-MAX ADT 0.50..3000.00 sec 5.00 sec Maximum dead time

3435 ADT 1p allowed YES NO 1pole TRIP allowed


NO

6-90 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

Addr. Setting Title Setting Options Default Setting Comments


3436 ADT CB? CLOSE YES NO CB ready interrogation before
NO reclosing

3437 ADT SynRequest YES NO Request for synchro-check after


NO 3pole AR

3438 T U-stable 0.10..30.00 sec 0.10 sec Supervision time for dead/live
voltage

3440 U-live> 30..90 V 48 V Voltage threshold for live line or


bus

3441 U-dead< 2..70 V 30 V Voltage threshold for dead line


or bus

6.9.4 Information Overview

The most important device information is explained in brief insofar as it is not ex-
plained in the following lists or described in detail in the preceding text.
“!%/.$5F\FOH” (FNo ) to “!%/.Q$5” (FNo )
The appropriate interrupt cycle is blocked. If a blocking already exists when the auto-
reclosure is started, the blocked cycle is not run and may be skipped (if other cycles
allow). The same applies accordingly if auto-reclosure was already started outside the
blocked cycle. If a current cycle is blocked, automatic reclosure is locked out dynam-
ically; there are then no further automatic reclosures.
“$5&\F=RQH5HO” (FNo ) to “$5&\F=RQH5HO” (FNo )
The automatic reclosure is ready for the appropriate reclosure cycle. The information
indicates which cycle will be run next. For example, external protective functions can
be set to accelerated or overreaching tripping before the appropriate reclosure.
“$5LVEORFNHG” (FNo )
The automatic reclosure is blocked (e.g. circuit breaker not ready). The information in-
dicates to the system management that there will be a final tripping, i.e. without reclos-
ure for a coming network fault. If the automatic reclosure has been started, this infor-
mation does not appear.
“$5LV127UHDG\” (FNo )
The automatic reclosure is not ready for reclosure at the moment. In addition to the
“$5LVEORFNHG” (FNo ) mentioned above there are also obstructions during
the course of the auto-reclosure cycles such as “active time run out” or “last reclaim
time running”. The information is particularly helpful when testing because no protec-
tion test with reclosure can be initiated during this indication.
“$5LQSURJUHVV” (FNo )
This information appears with starting of the automatic reclosure circuit, i.e. with the
first trip command which can start the automatic reclosure circuit. If the reclosure at-
tempt was successful (or all in the case of several), this information disappears at the
end of the last reclaim time. If no reclosure attempt was successful or reclosure was
blocked, it ends with the last — the final — trip command.

7SD610 Manual 6-91


C53000-G1176-C145-1
Functions

“$56\QF5HTXHVW” (FNo )


Measuring request to an external synchronism checker. The information appears at
the end of a dead time after three-pole tripping if a synchronism request was param-
eterized for the corresponding cycle. Reclosure only takes place when the synchro-
nism checker has granted release “!6\QFUHOHDVH” (FNo ).
“!6\QFUHOHDVH” (FNo )
Release of reclosure by an external synchronism checker if this was requested by the
output information “$56\QF5HTXHVW” (FNo ).

F.No. Alarm Comments


127 AR ON/OFF Auto Reclose ON/OFF (via system port)

2701 >AR ON >Auto reclose ON

2702 >AR OFF >Auto reclose OFF

2703 >BLOCK AR >BLOCK Auto reclose

2711 >AR Start >External start of internal Auto reclose

2712 >Trip L1 AR >AR: Ext. Trip L1 for internal AR

2713 >Trip L2 AR >AR: Ext. Trip L2 for internal AR

2714 >Trip L3 AR >AR: Ext. Trip L3 for internal AR

2715 >Trip 1p for AR >Ext. 1pole Trip for internal Auto Recl.

2716 >Trip 3p for AR >Ext. 3pole Trip for internal Auto Recl.

2727 >AR RemoteClose >AR: Remote Close signal

2731 >Sync.release >AR: Synchronism from ext. sync.-check

2737 >BLOCK 1pole AR >AR: Block 1pole AR-cycle

2738 >BLOCK 3pole AR >AR: Block 3pole AR-cycle

2739 >BLK 1phase AR >AR: Block 1phase-fault AR-cycle

2740 >BLK 2phase AR >AR: Block 2phase-fault AR-cycle

2741 >BLK 3phase AR >AR: Block 3phase-fault AR-cycle

2742 >BLK 1.AR-cycle >AR: Block 1st AR-cycle

2743 >BLK 2.AR-cycle >AR: Block 2nd AR-cycle

2744 >BLK 3.AR-cycle >AR: Block 3rd AR-cycle

2745 >BLK 4.-n. AR >AR: Block 4th and higher AR-cycles

2746 >Trip for AR >AR: External Trip for AR start

2747 >Pickup L1 AR >AR: External pickup L1 for AR start

2748 >Pickup L2 AR >AR: External pickup L2 for AR start

2749 >Pickup L3 AR >AR: External pickup L3 for AR start

2750 >Pickup 1ph AR >AR: External pickup 1phase for AR start

2751 >Pickup 2ph AR >AR: External pickup 2phase for AR start

6-92 7SD610 Manual


C53000-G1176-C145-1
Automatic Reclosure

F.No. Alarm Comments


2752 >Pickup 3ph AR >AR: External pickup 3phase for AR start

2781 Auto recl. OFF Auto recloser is switched OFF

2782 Auto recl. ON Auto recloser is switched ON

2783 AR is blocked AR: Auto-reclose is blocked

2784 AR is NOT ready Auto recloser is NOT ready

2787 CB not ready AR: Circuit breaker not ready

2788 AR T-CBreadyExp AR: CB ready monitoring window expired

2801 AR in progress Auto-reclose in progress

2809 AR T-Start Exp AR: Start-signal monitoring time expired

2810 AR TdeadMax Exp AR: Maximum dead time expired

2818 AR evolving Flt AR: Evolving fault recognition

2820 AR Program1pole AR is set to operate after 1p trip only

2821 AR Td. evol.Flt AR dead time after evolving fault

2839 AR Tdead 1pTrip AR dead time after 1pole trip running

2840 AR Tdead 3pTrip AR dead time after 3pole trip running

2841 AR Tdead 1pFlt AR dead time after 1phase fault running

2842 AR Tdead 2pFlt AR dead time after 2phase fault running

2843 AR Tdead 3pFlt AR dead time after 3phase fault running

2844 AR 1stCyc. run. AR 1st cycle running

2846 AR 3rdCyc. run. AR 3rd cycle running

2845 AR 2ndCyc. run. AR 2nd cycle running

2847 AR 4thCyc. run. AR 4th or higher cycle running

2848 AR ADT run. AR cycle is running in ADT mode

2851 AR Close Auto-reclose Close command

2852 AR Close1.Cyc1p AR: Close command after 1pole 1st cycle

2853 AR Close1.Cyc3p AR: Close command after 3pole 1st cycle

2854 AR Close 2.Cyc AR: Close command after 2nd cycle

2861 AR T-Recl. run. AR: Reclaim time is running

2862 AR Successful Auto reclose cycle successful

2863 AR Lockout Auto reclose Lockout

2864 AR 1p Trip Perm AR: 1pole trip permitted by internal AR

2865 AR Sync.Request AR: Synchro-check request

2871 AR TRIP 3pole AR: TRIP command 3pole

2889 AR 1.CycZoneRel AR 1st cycle zone extension release

7SD610 Manual 6-93


C53000-G1176-C145-1
Functions

F.No. Alarm Comments


2890 AR 2.CycZoneRel AR 2nd cycle zone extension release

2891 AR 3.CycZoneRel AR 3rd cycle zone extension release

2892 AR 4.CycZoneRel AR 4th cycle zone extension release

2893 AR Zone Release AR zone extension (general)

2894 AR Remote Close AR Remote close signal send

2796 AR on/off BI AR: Auto-reclose ON/OFF via BI

6-94 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

6.10 Circuit Breaker Failure Protection

6.10.1 Method of Operation

General The circuit breaker failure protection provides rapid back-up fault clearance, in the
event that the circuit breaker fails to respond to a trip command from a feeder protec-
tion.
Whenever e.g. a short-circuit protection relay of a feeder issues a trip command to the
circuit breaker, this is repeated to the breaker failure protection (Figure 6-36). A timer
T–BF in the breaker failure protection is started. The timer runs as long as a trip com-
mand is present and current continues to flow through the breaker poles.

Busbar

Protection
trip Circuit breaker failure protection

T–BF 0
I> BF &
Feeder
Feeder protection Trip
(internal or external) busbar

Figure 6-36 Simplified function diagram of circuit breaker failure protection with current flow
monitoring

Normally, the breaker will open and interrupt the fault current. The current monitoring
stage I> BF quickly resets (typical 10 ms) and stops the timer T–BF.
If the trip command is not carried out (breaker failure case), current continues to flow
and the timer runs to its set limit. The breaker failure protection then issues a com-
mand to trip the back-up breakers and interrupt the fault current.
The reset time of the feeder protection is not relevant because the breaker failure pro-
tection itself recognizes the interruption of the current.
For protection functions where the tripping criteria is not dependent on current (e.g.
Buchholz protection), current flow is not a reliable criterion for proper operation of the
breaker. In such cases, the circuit breaker position can be derived from the auxiliary
contacts of the breaker. Therefore, instead of monitoring the current, the condition of
the auxiliary contacts is monitored (see Figure 6-37). For this purpose, the outputs
from the auxiliary contacts must be fed to binary inputs on the relay (refer also to Sec-
tion 6.13.2).

7SD610 Manual 6-95


C53000-G1176-C145-1
Functions

Busbar

L+

Protection
trip Circuit breaker failure protection

T–BF 0
Feeder protection
Feeder &
Trip
(internal or external) busbar

Figure 6-37 Simplified function diagram of circuit breaker failure protection controlled by the
circuit breaker auxiliary contact(s)

Current Flow Each of the phase currents and an additional plausibility current (see below) are fil-
Monitoring tered by numerical filter algorithms so that only the fundamental frequency is used for
further evaluation.
Special features recognise the instant of current interruption. With sinusoidal currents,
current interruption is detected after approx. 10 ms. With d.c. transient current compo-
nents present in the fault current and/or in the current transformer secondary circuit
after interruption (e.g. current transformers with linearized core) or if the current trans-
formers are saturated by the d.c. component in the fault current, it can take one a.c.
cycle before the disappearance of the primary current is reliably detected.
The currents are monitored and compared with the set threshold. Besides the three
phase currents, two further current detectors are provided in order to allow a plausibil-
ity check (see Figure 6-38):
The earth current (residual current IE = 3·I0) is preferably used as plausibility current.
If the residual current from the starpoint of the current transformer set is connected to
the device this is used for 3·I0. If the residual current is not available the device calcu-
lates it with the formula
3·I0 = IL1 + IL2 + IL3.
Additionally, three times the negative sequence current 3·I2 is used for plausibility
check. This is calculated by the 7SD610 according to the equation:
3·I2 = IL1 + a2 · IL2 + a · IL3
where
a = ej120°.

These plausibility currents do not have any direct influence on the basic functionality
of the breaker failure protection but they allow a plausibility check in that at least two
current thresholds must have been exceeded before any of the breaker failure delay
times can be started, thus providing high security against false operation.

6-96 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

 ,!%)

Current
criterion
IL1
,! & >1 L1>

&

IL2
,! & >1 L2>

&

IL3
,! & >1 L3>

&

3I2
,! >1
plausi-
bility

3I0
,!

Figure 6-38 Current flow monitoring with the plausibility currents 3· I0 and 3·I2

Processing of the The position of the circuit breaker is derived from the central function control of the de-
Circuit Breaker vice (refer also to Section 6.13.2). Evaluation of the breaker auxiliary contacts is car-
Auxiliary Contacts ried out in the breaker failure protection function only when the current flow monitoring
has not picked up. Once the current flow criterion has picked up during the trip signal
from the feeder protection, the circuit breaker is assumed to be open as soon as the
current disappears, even if the associated auxiliary contact does not (yet) indicate that
the circuit breaker has opened (Figure 6-39). This gives preference to the more relia-
ble current criterion and avoids overfunctioning due to a defect e.g. in the auxiliary
contact mechanism or circuit. This interlock feature is provided for each individual
phase as well as for three-pole trip.
It is possible to disable the auxiliary contact criterion. If you set the parameter switch
&KN%5.&217$&7 (Figure 6-40 above) to 1R, the breaker failure protection can only
be started when current flow is detected. The position of the auxiliary contacts is then
not evaluated even if the auxiliary contacts are connected to the device.
On the other hand, current flow is not a reliable criterion for proper operation of the
circuit breaker for faults which do not cause detectable current flow (e.g. Buchholz pro-

7SD610 Manual 6-97


C53000-G1176-C145-1
Functions

tection). Information regarding the position of the circuit breaker auxiliary contacts is
required in these cases to check the correct response of the circuit breaker. For this
purpose, the binary input “!%)6WDUWZR,” is provided (Figure 6-40 left). This input
initiates the breaker failure protection even if no current flow is detected.

L1>
& S Q

Start only L1 R

FNo 351 1) & CBaux L1 closed

>CB1 Pole L1
1
FNo 354 2) >1 ) if phase dedicated auxiliary contacts available
2
>CB1 3p Open ) if series connection of NC contacts available

Figure 6-39 Interlock of the auxiliary contact criterion — example for phase L1

Common Phase Common phase initiation is used, for example, for lines without automatic reclosure,
Initiation for lines with only three-pole automatic reclosure, for transformer feeders, or if the bus-
bar protection trips. This is the only available initiation mode if the actual 7SD610 mod-
el is able to trip three-pole only.
If the breaker failure protection is intended to be initiated by further external protection
devices, it is recommended, for security reasons, to connect two starting criteria to the
7SD610 device: the trip command to the input “!%)6WDUWSROH” and an additional
release signal (e.g. fault detection, pickup) to the input “!%)UHOHDVH”. For Buchholz
protection it is recommended that the trip command is connected to the 7SD610 by
two separate wire pairs in order to achieve dual-channel initiation of the breaker failure
protection.
Nevertheless, it is possible to initiate the breaker failure protection in single-channel
mode should a separate release criterion not be available. The binary input “!%)5H
OHDVH” must then not be assigned to any physical input of the device during configu-
ration.
The scheme functionality is shown in Figure 6-40. When the trip signal appears from
any internal or external feeder protection and at least one current flow criterion (ac-
cording to Figure 6-38) is present, the breaker failure protection is initiated and the cor-
responding delay time(s) is (are) started.
If the current criterion is not fulfilled for any of the phases the position of the circuit
breaker auxiliary contact(s) is interrogated provided that this is available. If the circuit
breaker poles have individual auxiliary contacts, the series connection of the three
normally closed (NC) auxiliary contacts is used. The circuit breaker has operated cor-
rectly after a three-pole trip command only when none of the phases carries current
and when all three NC auxiliary contacts have closed.
If an internal protection function or an external protection device trips without current
flow, the internal input “Start internal w/o I” or the external input “!%)6WDUWZR,”
is used to initiate the breaker failure protection. In these cases the breaker auxiliary
contact position is the only criterion for the response of the circuit breaker.

6-98 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

Initiation can be blocked via the binary input “!%/2&.%NU)DLO” (e.g. during testing
of the feeder protection relay). Additionally, an internal blocking option is provided.

 &KN%5.&217$&7
(similar to Fig 6-39)
CBaux≥1pole closed
<HV
(from Fig 6-38) 1R
L1> >1
L2> >1
L3>
&
Start internal w/o l
>1
FNo 1439 >1 & Start L123
>BF Start w/o l &

Start internal 3pole FNo 1461


>1 BF Start
FNo 1415
>BF Start 3pole Configuration
not allocated
„1“
FNo 1432
allocated
>BF release
FNo 1403
>BLOCK BkrFail &
Internal blocking

Figure 6-40 Breaker failure protection with common phase initiation

Phase Segregated Phase segregated initiation of the breaker failure protection is necessary if the circuit
Initiation breaker poles can be operated individually, e.g. if single-pole automatic reclosure is
used. This is possible if the device is able to trip single-pole.
If the breaker failure protection is intended to be initiated by further external protection
devices, it is recommended, for security reasons, to connect an additional release sig-
nal (e.g. fault detection, pickup) at the input “!%)UHOHDVH”, besides the trip com-
mands at the inputs “!%)6WDUW/”, “!%)6WDUW/”, and “!%)6WDUW/”. Fig-
ure 6-41 shows the connections of this dual-channel initiation.
Nevertheless, it is possible to initiate the breaker failure protection in single-channel
mode should a separate release criterion not be available. The binary input “!%)UH
OHDVH” must then not be assigned to any physical input of the device during configu-
ration.
If the external protection device does not provide a general fault detection signal, a
general trip signal can be used instead. Alternatively, the parallel connection of a sep-
arate set of trip contacts can produce such a release signal as shown in Figure 6-42.
The starting condition logic for the delay times is shown in Figure 6-43. In principle, it
is designed similar to that for the common phase initiation, but, individually for each of
the three phases. Thus, current flow and initiation conditions are processed for each
phase. In case of single-pole interruption during an automatic reclose cycle, current
disappearance is reliably monitored for the tripped breaker pole only.

7SD610 Manual 6-99


C53000-G1176-C145-1
Functions

Initiation of a single-phase, e.g. “Start L1 only” is valid when the starting input (= trip
command of any feeder protection) appears for only this phase and current flow is de-
tected in at least this phase. If current flow is not detected, the auxiliary contact posi-
tion can be interrogated according to Figure 6-39, dependent on the setting (&KN%5.
&217$&7 = <HV).

external 7SD610
prot. device
Trip L1 >BF Start L1

Trip L2 >BF Start L2

Trip L3 >BF Start L3

Pick-up >BF Release

L+ L–

Figure 6-41 Breaker failure protection with phase segregated initiation — example for initia-
tion by an external protection device with release by a fault detection signal

external 7SD610
prot. device
Trip L1 >BF Start L1
Trip L1

Trip L2 >BF Start L2


Trip L2

Trip L3 >BF Start L3


Trip L3

L+ >BF Release

L–
Figure 6-42 Breaker failure protection with phase segregated initiation — example for initia-
tion by an external protection device with release by a separate set of trip con-
tacts

The auxiliary contact criterion is also processed for each individual breaker pole. If
however the breaker auxiliary contacts are not available for each individual breaker
pole, then a single-pole trip command is assumed to be executed only once the series
connection of the normally open (NO) auxiliary contacts is interrupted. This informa-
tion is provided to the breaker fail protection by the function control of the device (refer
to Section 6.13.2).

6-100 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

 &KN%5.&217$&7
CBaux L1 closed
<HV
1R >1
L1>
Start internal L1
>1
FNo 1435 & Start only L1
>BF Start L1 &

CBaux L2 closed
<HV
1R >1
L2>
Start internal L2
>1
FNo 1436 & Start only L2
>BF Start L2 &

CBaux L3 closed
<HV
1R >1
L3>
Start internal L3
>1
FNo 1437
& & Start only L3
>BF Start L3

>2

CBaux ≥1p closed


<HV
1R
L1> >1
L2> >1
L3>
&

Start internal w/o I


>1 >1 & Start L123
FNo 1439 &
>BF Start w/o I

Start internal 3pole


>1
FNo 1415
Configuration FNo 1461
>BF START 3pole
not allocated >1 BF Start
„1“
FNo 1432
allocated
>BF Release
FNo 1403
>BLOCK BkrFail &
Internal blocking

Figure 6-43 Initiation conditions with phase segregated initiation

7SD610 Manual 6-101


C53000-G1176-C145-1
Functions

The three-phase starting signal “Start L123” is generated if trip signals appear in more
than one pole (regardless from which protection function). Phase segregated initiation
is then blocked. The input “!%)6WDUWZR,” (e.g. from Buchholz protection) op-
erates in three-phase mode as well. The function is the same as with common phase
initiation.
The additional release-signal “!%)UHOHDVH” (if assigned to a binary input) affects all
starting conditions. Initiation can be blocked via the binary input “!%/2&.%NU)DLO”
(e.g. during test of the feeder protection relay). Additionally, an internal blocking option
is provided.

Delay Timers When the starting conditions are fulfilled, the associated timers are started. The circuit
breaker pole(s) must open before the associated time has elapsed.
Different delay timers are provided for operation after common phase initiation and
phase segregated initiation. A further time stage can be used for two-stage breaker
failure protection.
With single-stage breaker failure protection, the trip command is routed to the adjacent
circuit breakers should the local feeder breaker fail (refer to Figure 6-36 or 6-37). The
adjacent circuit breakers are all those which must trip in order to interrupt the fault cur-
rent, i.e. the breakers which feed the busbar or the busbar section to which the feeder
under consideration is connected. The possible initiation conditions for the breaker
failure protection are those discussed above. Depending on the application of the
feeder protection, common phase or phase segregated initiation conditions may oc-
cur. Tripping by the breaker failure protection is always three-pole.
The simplest solution is to start the delay timer 7 (Figure 6-44). The phase-segregat-
ed initiation signals are omitted if the feeder protection always trips three-pole or if the
circuit breaker is not capable of single-pole tripping.
If different delay times are required after a single-pole trip and three-pole trip by the
feeder protection it is possible to use the timer stages 7SROH and 7SROH ac-
cording to Figure 6-45.

 7 (Trip
Start only L1 busbar)
FNo 1494
Start only L2
>1 7
BF T2-TRIP(bus)
Start only L3

Start L123

Figure 6-44 Single-stage breaker failure protection with common phase initiation

With two-stage breaker failure protection, the trip command of the feeder protection is
usually repeated, after a first time stage, to the feeder circuit breaker, often via a sec-
ond trip coil or set of trip coils, if the breaker did not responded to the original trip com-
mand. A second time stage monitors the response to this repeated trip command and
trips the breakers of the relevant busbar section, if the fault has not yet been cleared
after this second time.

6-102 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

 7SROH

Start only L1
>1 7
Start only L2 (Trip
busbar)
Start only L3
FNo 1476
 7SROH >1
BF T1-TRIP L123

7
Start L123

Figure 6-45 Single-stage breaker failure protection with different delay timers

For the first time stage, different time delays can be selected for a single-pole trip and
three-pole trip by the feeder protection. Additionally, you can select (parameter S
5(75,3 7 ) whether this repeated trip should be single-pole or three-pole.

 7SROH  S5(75,3 7 (accordingly for


other phases)
Start only L1
7 <HV FNo 1472
>1 &
Start only L2 1R Start only L1
BF T1-TRIP 1pL1
Start only L3
(Trip repetition
 7SROH feeder breaker)
FNo 1476
>1
7 BF T1-TRIP L123
Start L123

 7 (Trip
busbar)
FNo 1494
> 1 7 BF T2-TRIP (bus)

Figure 6-46 Two-stage breaker failure protection with phase segregated initiation — one
phase

Circuit Breaker not There may be cases when it is immediately apparent that the circuit breaker associat-
Operational ed with a feeder protection relay cannot clear a fault, e.g. when the tripping voltage or
the tripping energy is not available.
In such a case it is not necessary to wait for the response of the feeder circuit breaker.
If provision has been made for the detection of such a condition (e.g. control voltage
monitor or air pressure monitor), the monitor alarm signal can be fed to the binary input
“!&%IDXOW\” (FNo ) of the 7SD610. On occurrence of this alarm and a trip com-
mand by the feeder protection, a separate timer 7%NU'HIHFWLYH, which is normal-
ly set to 0, is started (Figure 6-47). Thus, the adjacent circuit breakers (busbar) are
tripped immediately in case the feeder circuit breaker is not operational.

7SD610 Manual 6-103


C53000-G1176-C145-1
Functions

(all initiation FNo 1461  7%NU'HIHFWLYH


conditions BF Start
Fig 6-40/6-43)
FNo 1493
FNo 378 T0
>CB faulty
& BF TRIP CBdefec

Figure 6-47 Circuit breaker not operational

Transfer Trip to the The 7SD610 has the facility to give an additional intertrip signal to the circuit breaker
Remote End Circuit at the remote line end in the event that the local feeder circuit breaker fails. For this,
Breaker the transmission of the trip command required.
In 7SD610 the concerned trip command — normally the command for the adjacent
breakers — is fed to the binary input for the intertrip function. This can be achieved
externally by connection of the trip output to the binary input “!,QWHUWULSSRO”
(see also Section 6.3). An easier way is to realize this intertrip using the user defined
functions (CFC).

End Fault An end fault is defined here as a short-circuit which has occurred at the end of a line
Protection or protected object, between the circuit breaker and the current transformer set.
This situation is shown in Figure 6-48. The fault is located — as seen from the current
transformers (= measurement location) — on the busbar side, thus, it will not be re-
garded by the feeder protection relay as a feeder fault. It can only be detected by a
bus-bar protection. Nevertheless, a trip command given to the feeder circuit breaker
cannot clear the fault since the opposite end continues to feed the fault. Thus, the fault
current does not stop flowing even though the feeder circuit breaker has properly re-
sponded to the trip command.

Busbar

Trip by
protection

ISC
Feeder

Figure 6-48 End fault between circuit breaker and current transformers

The end fault protection has the task to recognize this situation and to transmit a trip
signal to the remote end of the protected object to clear the fault. For this purpose, the
output command “%)(QG)OW75,3” is available to trigger the intertrip input of the
differential protection — if applicable, together with other commands that need to be
transferred. This can be achieved by external connection or via CFC.
The end fault is recognized when the current continues flowing although the circuit
breaker auxiliary contacts indicate that the breaker is open. In the 7SD610, an addi-

6-104 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

tional criterion is the presence of any breaker failure protection initiate signal. The
scheme functionality is shown in Figure 6-49. If the breaker failure protection is initiat-
ed and current flow is recognized (current criteria “L∗>” according Figure 6-38), but no
circuit breaker pole is closed (auxiliary contact criterion “any pole closed”), then a timer
7(QG)DXOW is started, after which an intertrip signal is transmitted to the opposite
end of the protected object.

(from Fig 6-38)


L1>
L2> >1
L3>  7(1')DXOW

FNo 1461
BF Start
&
FNo 1495
T 0
& %)(QG)OW75,3
≥1 pole closed

Figure 6-49 Function block diagram of end fault protection

Circuit Breaker The pole discrepancy supervision has the task to detect discrepancies in the position
Pole Discrepancy of the three circuit breaker poles. Under steady-state conditions, either all three poles
Supervision of the breaker must be closed, or all three poles must be open. Discrepancy is permit-
ted only for a short time interval during a single-pole automatic reclose cycle.
The scheme functionality is shown in Figure 6-50. The signals which are processed
here are the same as those used for the breaker failure protection. The pole discrep-
ancy condition is established when at least one pole is closed (“any pole closed”) and
at the same time not all poles are closed (“any pole open”).
Additionally, the current criteria (from Figure 6-38) are processed. Pole discrepancy
can only be detected when current is not flowing through all three poles (<3), i.e.
through only one or two poles. When current is flowing through all three poles, all three
poles must be closed even if the breaker auxiliary contacts indicate a different status.
If pole discrepancy is detected, this is annunciated by a fault detection signal. This sig-
nal identifies the pole which was open before the trip command of the pole discrepan-
cy supervision occurred.

7SD610 Manual 6-105


C53000-G1176-C145-1
Functions

L1> FNo 1497


& %)&%GLVFU/

(from Figure 6-38)


L2> FNo 1498
& %)&%GLVFU/

L3> FNo 1499


& %)&%GLVFU/

<3  73ROH'LVFUHS

FNo 1500
T 0
any pole closed & %)&%GLVFU75,3
any pole open

Figure 6-50 Function block diagram of pole discrepancy supervision

6.10.2 Applying the Function Parameter Settings

General The breaker failure protection and its ancillary functions (end fault protection, pole dis-
crepancy supervision) can only operate if they were configured as HQDEOHG during
setting of the scope of functions (see Section 5.1, address ).

Breaker Failure The complete breaker failure protection including its ancillary functions is switched Off
Protection or On under address  )&7%UHDNHU)DLO.
The current threshold ,!%) (address ) should be selected such that the protec-
tion will operate with the smallest expected short-circuit current. To ensure this, the
value should be 10 % less than the minimum anticipated fault current. On the other
hand, the value should not be set lower than necessary.
Normally, the breaker failure protection evaluates the current flow criterion as well as
the position of the breaker auxiliary contact(s). If the auxiliary contact(s) status is not
available in the device, this criterion cannot be processed. In this case, set address
 &KN%5.&217$&7 to 1R.
The breaker failure protection in the 7SD610 can be operated single-stage or two-
stage

Two-stage Breaker With two-stage operation, the trip command is repeated after a time delay T1 to the
Failure Protection local feeder breaker, normally to a different set of trip coils of this breaker. A choice
can be made whether this trip repetition shall be single-pole or three-pole if the initial
feeder protection trip was single-pole (provided single-pole trip is possible). This
choice is made in address  S5(75,3 7 . Set this parameter to <HV if you
wish single-pole trip for the first stage, otherwise to 1R.
If the breaker does not respond to this first stage trip, the adjacent circuit breakers
must be tripped provided the fault has not yet been cleared. The adjacent breakers are

6-106 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

those of the other feeders on the busbar or bus-bar section and — if desired — the
breaker at the remote end of the protected object.
In the 7SD610, after a further delay time 7 (address ), the adjacent circuit
breakers (i.e. the breakers of the busbar zone and — if desired — the breaker at the
remote end) are tripped provided the fault has not yet been cleared. An example of the
time sequence is illustrated in Figure 6-51.
Separate delay times can be set:
− for single- or three-pole trip repetition to the local feeder circuit breaker after 1-pole
trip of the feeder protection under address  7SROH,
− for three-pole trip repetition to the local feeder circuit breaker after 3-pole trip of the
feeder protection under address  7SROH,
− for trip of the adjacent circuit breakers (busbar zone and remote end if applicable)
under address  7.
The delay times are set dependant on the maximum operating time of the feeder cir-
cuit breaker and the reset time of the current detectors of the breaker failure protec-
tion, plus a safety margin which allows for any tolerance of the delay timers. The time
sequence is illustrated in Figure 6-51. For sinusoidal currents one can assume that the
reset time of the current detectors is less than 15 ms but if current transformer satura-
tion is expected then 25 ms should be assumed.

Fault inception
Fault clearance time normal

Prot. CB operating time Reset Safety


trip (local) I> BF margin

Initiation breaker
failure protection

Time delay T1 of breaker Trip command Reset Safety


failure protection repetition I> BF margin

Time delay T2 of breaker CB operating time


failure protection (adjacent CBs)

Total fault clearance time with breaker failure

Figure 6-51 Time sequence example for normal clearance of a fault, and with circuit breaker
failure, using two-stage breaker failure protection

Single-stage With single-stage operation, the adjacent circuit breakers (i.e. the breakers of the bus-
Breaker Failure bar zone and — if desired — the breaker at the remote end) are tripped after a delay
Protection time 7 (address ) following initiation, should the fault not have been cleared
within this time.
The timers 7SROH (address ) and 7SROH (address ) are then set to
∞ since they are not needed.

7SD610 Manual 6-107


C53000-G1176-C145-1
Functions

But you may use the T1–timers for single-stage protection if you wish to utilize the fa-
cility of setting different delay times after single-pole trip and three-pole trip of the feed-
er protection. In this case, set the desired times under addresses  7SROH
and  7SROH but set address  S5(75,3 7 to 1R to avoid a single-
pole trip to the bus-bar. And set 7 (address ) to ∞ or equal to 7SROH. Be
sure that the correct trip commands are assigned to the desired trip relay(s).

Fault inception
Fault clearance time normal

Prot. CB operating time Reset Safety


trip I> BF margin

Initiation breaker
failure protection

Time delay T2 of breaker CB operating time


failure protection (adjacent CBs)

Total fault clearance time with breaker failure

Figure 6-52 Time sequence example for normal clearance of a fault, and with circuit breaker
failure, using single-stage breaker failure protection

The delay times are determined from the maximum operating time of the feeder circuit
breaker, the reset time of the current detectors of the breaker failure protection, plus
a safety margin which allows for any tolerance of the delay timers. The time sequence
is illustrated in Figure 6-52. For sinusoidal currents one can assume that the reset time
of the current detectors is less than 15 ms but if current transformer saturation is ex-
pected then 25 ms should be assumed.

Circuit Breaker not If the circuit breaker associated with the feeder is not operational (e.g. control voltage
Operational failure or air pressure failure), it is apparent that the local breaker cannot clear the
fault. Time delay before tripping the adjacent breakers is not necessary in this case. If
the relay is informed about this disturbance (via the binary input “!&%IDXOW\”, the
adjacent circuit breakers (busbar and remote end if applicable) are tripped after the
time 7%NU'HIHFWLYH (address ) which is usually set to .
Address  7ULS%NU'HIHFW determines to which output the trip command is
routed in the event that the breaker is not operational when a feeder protection trip oc-
curs. Select that output which is used to trip the adjacent breakers (busbar trip).

End Fault Protec- The end fault protection can be switched 2Q or 2II separately under address 
tion (QG)OWVWDJH. An end fault is a short-circuit between the circuit breaker and the
current transformer set of the feeder. The end fault protection presumes that the de-
vice is informed about the circuit breaker position via breaker auxiliary contacts con-
nected to binary inputs.
If, during an end fault, the circuit breaker is tripped by a busbar protection (the fault is
a busbar fault as determined from the location of the current transformers), the fault

6-108 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Failure Protection

current will continue to flow, because the fault is fed from the remote end of the feeder
circuit.
The time 7(QG)DXOW (address ) is started when, during the fault detection con-
dition of the feeder protection, the circuit breaker auxiliary contacts indicate open
poles and, at the same time, current flow is detected (address ). The trip com-
mand of the end fault protection is intended for the transmission of an intertrip signal
to the remote end circuit breaker.
Thus, the delay time must be set such that it can bridge out short transient apparent
end fault conditions which may occur during switching of the breaker.

Pole Discrepancy The pole discrepancy supervision can be switched 2Q or 2II separately under ad-
Supervision dress  3ROH'LVFUHSDQF\. It is only useful if the breaker poles can be operated
individually. It avoids that only one or two poles of the local breaker are open continu-
ously. It has to be provided with either the breaker auxiliary contacts of each pole or
the series connection of the normally open contacts (NO contacts) and the normally
closed contacts (NC contacts) to binary inputs on the device. If these conditions are
not fulfilled, switch the pole discrepancy supervision 2II.
The delay time 73ROH'LVFUHS (address ) determines how long a breaker
pole discrepancy condition of the feeder circuit breaker, i.e. only one or two poles
open, may be present before the pole discrepancy supervision issues a three-pole trip
command. This time must clearly be longer than the duration of a single-pole automat-
ic reclose cycle. The time should be less than the permissible duration of an unbal-
anced load condition which is caused by the unsymmetrical position of the circuit
breaker poles. Conventional values are 2 s to 5 s.

6.10.3 Setting Overview

Note: The indicated secondary current values for setting ranges and default settings
refer to IN = 1 A. For the nominal current 5 A these values are to be multiplied by 5.

Addr. Setting Title Setting Options Default Setting Comments


3901 FCT BreakerFail ON ON Breaker Failure Protection is
OFF
3902 I> BF 0.05..20.00 A 0.10 A Pick-up threshold I>
3903 1p-RETRIP (T1) NO YES 1pole retrip with stage T1 (local trip)
YES
3904 T1-1pole 0.00..30.00 sec; ∞ 0.00 sec T1, Delay after 1pole start (local trip)
3905 T1-3pole 0.00..30.00 sec; ∞ 0.00 sec T1, Delay after 3pole start (local trip)
3906 T2 0.00..30.00 sec; ∞ 0.15 sec T2, Delay of 2nd stage (busbar trip)
3907 T3-BkrDefective 0.00..30.00 sec; ∞ 0.00 sec T3, Delay for start with defective bkr.
3908 Trip BkrDefect. NO NO Trip output selection with defective bkr
trips with T1-trip-signal
trips with T2-trip-signal
trips with T1 and T2-trip-signal
3909 Chk BRK CONTACT NO YES Check Breaker contacts
YES

7SD610 Manual 6-109


C53000-G1176-C145-1
Functions

Addr. Setting Title Setting Options Default Setting Comments


3921 End Flt. stage ON OFF End fault stage is
OFF
3922 T-EndFault 0.00..30.00 sec; ∞ 2.00 sec Trip delay of end fault stage
3931 PoleDiscrepancy ON OFF Pole Discrepancy supervision
OFF
3932 T-PoleDiscrep. 0.00..30.00 sec; ∞ 2.00 sec Trip delay with pole discrepancy

6.10.4 Information Overview

F.No. Alarm Comments


1401 >BF on >BF: Switch on breaker fail protection
1402 >BF off >BF: Switch off breaker fail protection
1403 >BLOCK BkrFail >BLOCK Breaker failure
1432 >BF release >BF: External release
1439 >BF Start w/o I >BF: External start 3pole (w/o current)
1415 >BF Start 3pole >BF: External start 3pole
1435 >BF Start L1 >BF: External start L1
1436 >BF Start L2 >BF: External start L2
1437 >BF Start L3 >BF: External start L3
1440 BkrFailON/offBI Breaker failure prot. ON/OFF via BI
1451 BkrFail OFF Breaker failure is switched OFF
1452 BkrFail BLOCK Breaker failure is BLOCKED
1453 BkrFail ACTIVE Breaker failure is ACTIVE
1461 BF Start Breaker failure protection started
1493 BF TRIP CBdefec BF Trip in case of defective CB
1472 BF T1-TRIP 1pL1 BF Trip T1 (local trip) - only phase L1
1473 BF T1-TRIP 1pL2 BF Trip T1 (local trip) - only phase L2
1474 BF T1-TRIP 1pL3 BF Trip T1 (local trip) - only phase L3
1476 BF T1-TRIP L123 BF Trip T1 (local trip) - 3pole
1494 BF T2-TRIP(bus) BF Trip T2 (busbar trip)
1495 BF EndFlt TRIP BF Trip End fault stage
1496 BF CBdiscrSTART BF Pole discrepancy pickup
1497 BF CBdiscr L1 BF Pole discrepancy pickup L1
1498 BF CBdiscr L2 BF Pole discrepancy pickup L2
1499 BF CBdiscr L3 BF Pole discrepancy pickup L3
1500 BF CBdiscr TRIP BF Pole discrepancy Trip

6-110 7SD610 Manual


C53000-G1176-C145-1
Thermal Overload Protection

6.11 Thermal Overload Protection

6.11.1 Function Description

The thermal overload protection prevents damage to the protected object caused by
thermal overloading, particularly in case of transformers, rotating machines, power re-
actors and cables. It is in general not necessary for overhead lines, since no meaning-
ful temperature prize can be calculated because of the great variations in the environ-
mental conditions (temperature, wind). In this case, however, a current-dependent
alarm stage can signal an imminent overload.
The unit computes the temperature rise according to a thermal single-body model as
per the following thermal differential equation
I 2
-------- + ------- ⋅ Θ = ------- ⋅  -------------
dΘ 1 1
dt τ th τ th k ⋅ I N

with Θ – currently valid temperature rise referred to the final temperature rise
for the maximum permissible line current k · IN
τth – thermal time constant for temperature rise
k – k–factor which states the maximum permissible continuous current
referred to the rated current of the current transformers
I – currently valid r.m.s. current
IN – rated current of current transformers
The solution of this equation under steady-state conditions is an e–function whose
asymptote shows the final temperature rise Θend. When the temperature rise reaches
the first settable temperature threshold Θalarm, which is below the final temperature
rise, a warning alarm is given in order to allow an early load reduction. When the sec-
ond temperature threshold, i.e. the final temperature rise or tripping temperature, is
reached, the protected object is disconnected from the network. The overload protec-
tion can, however, also be set on $ODUP2QO\. In this case only an alarm is output
when the final temperature rise is reached.
The temperature rises are calculated separately for each phase in a thermal replica of
the square of the associated phase current. This guarantees a true r.m.s. value meas-
urement and also includes the effect of harmonic content. A choice can be made
whether the maximum calculated temperature rise of the three phases, the average
temperature rise, or the temperature rise calculated from the phase with maximum
current should be decisive for evaluation of the thresholds.
The maximum permissible continuous thermal overload current Imax is described as a
multiple of the rated current IN:
Imax = k · IN
In addition to the k-factor, the time constant τth as well as the alarm temperature Θalarm
must be entered in the protection.
Apart from the thermal alarm stage, the overload protection also includes a current
overload alarm stage Ialarm, which can output an early warning that an overload cur-
rent is imminent, even when the temperature rise has not yet reached the alarm or trip
temperature rise values.
The overload protection can be blocked via a binary input. In doing so, the thermal rep-
lica are also reset to zero.

7SD610 Manual 6-111


C53000-G1176-C145-1
Functions

 7,0(&2167$17
 &$/&0(7+2'
 .²)$&725
 Θ$/$50
IL1
i2 Θ Θmax
IL2 )1R
Θ
IL3 Θ> & O/L Q Alarm
Θ(Imax)

 ,$/$50 Θ≥1 & )1R


ThOverload TRIP

I> ≥1 )1R
L1 & O/L I Alarm
L2
L3
)1R
>BLK ThOverload
 7KHU29(5/2$' ≥1
2II
“1“ $ODUPRQO\
2Q

Figure 6-53 Logic diagram of the thermal overload protection

6.11.2 Setting the Function Parameters

General Informa- A precondition for the use of the thermal overload protection is that 2YHUORDG =
tion H[LVW was configured under address  (Section 5.1). It can be switched 2Q or
2II under address 7KHU29(5/2$'. Furthermore $ODUP2QO\ can be set.
With that latter setting the protection function is active but only outputs an alarm when
the tripping temperature is reached, i.e. the output function “2/2))” is not active.

k–Factor The rated current of the device is taken as the base current for detecting an overload.
The setting factor k is set under address  .)$&725. It is determined by the re-
lation between the permissible thermal continuous current and this rated current:
I max
k = ------------
IN

The permissible continuous current is at the same time the current at which the e–
function of the temperature rise has its asymptote. It is not necessary to determine the
tripping temperature since it results automatically from the final rise temperature at
k · IN. Manufacturers of electrical machines usually state the permissible continuous
current. If no data are available, k is set to 1.1 times the rated current of the protected
object. For cables, the permissible continuous current depends on the cross section,
the insulation material, the design and the way they are laid, and can be derived from
the relevant tables.
Please note that the overload capability of electrical equipment relates to its primary
current. This has to be considered if the nominal primary current of the equipment dif-
fers from the rated current of the current transformers.

6-112 7SD610 Manual


C53000-G1176-C145-1
Thermal Overload Protection

Example:
Belted cable 10 kV 150 mm2
Permissible continuous current Imax = 322 A
Current transformers 400 A/5 A
322 A
k = --------------- = 0.805
400 A

Setting value .)$&725 = 

Time Constant τ The thermal time constant τth is set under the address  7,0(&2167$17. This
is also to be stated by the manufacturer. Please note that the time constant must be
set in minutes. Quite often other values for determining the time constant are stated
which can be converted into the time constant as follows:
• 1–s current
τ th perm. 1-s current 2
--------- = ------ ⋅  --------------------------------------------------------
1
min 60 perm. contin. current

• permissible current for application time other than 1 s, e.g. for 0.5 s
τ th perm. 0.5–s current 2
--------- = -------- ⋅  --------------------------------------------------------
0.5
min 60 perm. contin. current

• t6–time; this is the time in seconds for which a current of 6 times the rated current
of the protected object may flow
τ th
--------- = 0.6 ⋅ t6
min

Example:
Cable as above with
permissible 1–s current 13.5 kA
τ th 13500 A 2
--------- = ------ ⋅  ---------------------- = ------ ⋅ 42 = 29.4
1 1 2
min 60  322 A  60

Setting value 7,0(&2167$17 =  min

Alarm Stages By setting a thermal alarm stage Θ$/$50 (address ) an alarm can be output
before the tripping temperature is reached, so that a trip can be avoided by early load
reduction or by switching over. The percentage is referred to the tripping temperature.
The current overload alarm setpoint ,$/$50 (address ) is stated as a factor of
the rated device current and should be set equal to or slightly below the permissible
continuous current k · IN. It can also be used instead of the thermal alarm stage. In this
case the thermal alarm stage is set to 100 % and thus practically ineffective.

Calculating the The thermal replica is calculated individually for each phase. Address  &$/&
Temperature Rise 0(7+2' decides whether the highest of the three calculated temperatures (ΘPD[) or
their arithmetic average ($YHUDJH Θ) or the temperature calculated from the phase
with maximum current (Θ#,PD[) should be decisive for the thermal alarm and trip-
ping stage.

7SD610 Manual 6-113


C53000-G1176-C145-1
Functions

Since an overload usually occurs in a balanced way, this setting is of minor impor-
tance. If unbalanced overloads are to be expected, however, these options lead to dif-
ferent results.
Averaging should only be used if a rapid thermal equilibrium is possible in the protect-
ed object, e.g. with belted cables. If the three phases are, however, more or less ther-
mally isolated (e.g. single conductor cables or overhead lines), one of the maximum
settings should be chosen at any rate.

6.11.3 Setting Overview

Note: The indicated setting ranges and default settings refer to a secondary rated cur-
rent of IN = 1 A. For the secondary rated current of IN = 5 A these values are to be
multiplied by 5. For the setting of primary values the transformation ratio of the current
transformers must also be taken into consideration.

Addr. Setting Title Setting Options Default Setting Comments


4201 Ther. OVER LOAD OFF OFF Thermal overload protection
ON
Alarm Only

4202 K-FACTOR 0.10..4.00 1.10 K-Factor

4203 TIME CONSTANT 1.0..999.9 min 100.0 min Time Constant

4204 Θ ALARM 50..100 % 90 % Thermal Alarm Stage

4205 I ALARM 0.10..4.00 A 1.00 A Current Overload Alarm Setpoint

4206 CALC. METHOD Theta Max Theta Max Method of Acquiring Tempera-
Average \T ture
\T @ Imax

6.11.4 Information Overview

F.No. Alarm Comments


1503 >BLK ThOverload >BLOCK Thermal Overload Protection

1511 Th.Overload OFF Thermal Overload Protection OFF

1512 Th.Overload BLK Thermal Overload Protection BLOCKED

1513 Overload ACT Overload Protection ACTIVE

1516 O/L Θ Alarm Overload Alarm! Near Thermal Trip

1515 O/L I Alarm Overload Current Alarm (I alarm)

1517 Winding O/L Winding Overload

1521 ThOverload TRIP Thermal Overload TRIP

6-114 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

6.12 Monitoring functions

The device incorporates comprehensive monitoring functions which cover both hard-
ware and software; the measured values are continuously checked for plausibility, so
that the current and voltage transformer circuits are also included in the monitoring
system to a large extent. Furthermore, binary inputs are available for supervision of
the trip circuits.

6.12.1 Function Description

6.12.1.1 Hardware Monitoring

The complete hardware from the measurement inputs to the output relays is moni-
tored for faults and inadmissible states by monitoring circuits and by the processor.

Auxiliary and The processor voltage of 5 V is monitored by the hardware as the processor cannot
Reference Voltages operate if the voltage drops below the minimum value. The device is put out of oper-
ation. When the voltage has returned the processor system is restarted.
Failure or switch-off of the supply voltage puts the system out of operation; this status
is signalled by a fail-safe contact. Transient dips in supply voltage will not disturb the
function of the relay (see also Section 10.1.2 in the Technical Data).
The processor monitors the offset and the reference voltage of the ADC (analog-to-
digital converter). In case of inadmissible deviations the protection is blocked; persist-
ent faults are signalled.

Back-up Battery The back-up battery guarantees that the internal clock continues to work and that me-
tered values and alarms are stored if the auxiliary voltage fails. The charge of the bat-
tery is checked regularly. If the voltage drops below the permissible minimum the
alarm “)DLO%DWWHU\” is output.
If the device is not fed with auxiliary voltage for more than 12 to 24 hours, the internal
back-up battery is switched off automatically, i.e. the time is not registered any more.
Messages and fault recordings keep stored.

Memory Modules All working memories (RAMs) are checked during start-up. If a fault occurs, the start
is aborted and an LED starts flashing. During operation the memories are checked
with the help of their checksum.
For the program memory (EPROM), the cross-check sum is cyclically generated and
compared to a stored reference program cross-check sum.
For the parameter memory (EEPROM), the cross-check sum is cyclically generated
and compared to the cross-check sum that is newly calculated after each parameter-
ization operation.
If a fault occurs the processor system is restarted.

7SD610 Manual 6-115


C53000-G1176-C145-1
Functions

Scanning The scanning frequency and the synchronism between the internal back-up modules
Frequency is continuously monitored. If deviations cannot be corrected by another synchroniza-
tion, the device puts itself out of operation; the “Device OK” relay drops off.

Measured Value There are four measurement inputs in the current path. If the three phase currents and
Acquisition: the ground current of the current transformer starpoint or of an separate summation
Currents current transformer of the protected line are connected to the device, the sum of the
four digitized current values must always be zero. A fault in the current path is recog-
nized when
iF = |iL1 + iL2 + iL3 + kI · iE | > Σ,7+5(6+2/'· IN + Σ,)$&725· Σ|i|
Factor kI (parameter ,H2ZQ,S) considers the possibly different ratio of a separate
IE–transformer (e.g. summation current transformer). Σ,7+5(6+2/'and Σ,)$&
725are setting parameters. The component Σ,)$&725· Σi takes into account per-
missible current proportional transformation errors in the input converters which may
particularly occur under conditions of high short-circuit currents (Figure 6-54). The re-
setting ratio is approx. 97 %. Σi is the sum of all rectified currents.
Σi = |iL1 |+|iL2 |+|iL3|+ |kI · iE |
As soon as a summation current fault is detected after or before a system disturbance,
the differential protection is blocked. This fault is reported with “)DLOXUHΣ,“. For not
causing a blocking due to a transformation ratio fault (saturation) in case of high short-
circuit currents, this monitoring function is not available during a system fault.

Note:
Current sum monitoring can only operate properly when the residual current of the
protected line is fed to the fourth current input (I4) of the relay.

iF
IN

Slope:
Σ,)$&725

Σ,7+5(6+2/'

Σi
IN
Figure 6-54 Summation current monitoring

6-116 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

6.12.1.2 Software Monitoring

Watchdog For continuous monitoring of the program sequences, a watchdog timer is provided in
the hardware (hardware watchdog) which will reset and completely restart the proces-
sor system in the event of processor failure or if a program falls out of step.
A further software watchdog ensures that any error in the processing of the programs
will be recognized. Such errors also lead to a reset of the processor.
If such an error is not eliminated by restarting, another restart attempt is initiated. If the
fault is still present after three restart attempts within 30 s, the protection system will
take itself out of service, and the red LED “Blocked” lights up. The “Device OK” relay
drops off and signals the malfunction by its break contact.

6.12.1.3 Monitoring of External Transformer Circuits

The device detects and signals most of the interruptions or short-circuits in the sec-
ondary circuits of current or voltage transformers or wrong connections (an important
commissioning aid). For this the measured values are checked in the background at
cyclic intervals, as long as no pickup condition exists.

Current Symmetry In healthy network operation it can be expected that the currents will be approximately
balanced. The monitoring of the values in the device ensures this balance. For this the
lowest phase current is set in relation to the highest. An unbalance is recognized when
|Imin | / |Imax | < %$/)$&725, provided that
Imax / IN > %$/$1&(,/,0,7 / IN

Imax is the highest, Imin the lowest of the three phase currents. The balance factor
%$/)$&725, is the measure for the balance of the phase currents, limiting value
%$/$1&(,/,0,7 is the lowest threshold of the operating range of this monitoring
(see Figure 6-55). Both parameters can be set. The resetting ratio is approx. 97 %.
This fault is indicated with “)DLO,%DODQFH“.

Imin
IN
Slope:
%$/)$&725,

%$/$1&(,/,0,7 Imax
IN
Figure 6-55 Current balance monitoring

7SD610 Manual 6-117


C53000-G1176-C145-1
Functions

Voltage Symmetry In healthy network operation it can be expected that the voltages are nearly balanced.
If measured-circuit voltages are fed to the line, this symmetry is controlled by the de-
vice. For the monitoring function not picking up during a single earth fault, which can
also be a permanent operating state in non-earthed networks, the phase-to-phase
voltages are being considered.
Thus the lowest phase-to-phase voltage is set in relation to the highest. An unbalance
is recognized when
|Umin | / |Umax | < %$/)$&7258 provided that |Umax| > %$/$1&(8/,0,7
Umax is the highest, Umin the lowest of the three phase-to-phase voltages. The sym-
metry factor %$/)$&7258 is the measure for the asymmetry of the phase voltages,
limiting value %$/$1&(8/,0,7 is the lowest threshold of the operating range of this
monitoring (see Figure 6-56). Both parameters can be set. The resetting ratio is ap-
prox. 97 %.
This fault is indicated with “)DLO8EDODQFH“.

Umin
V
Slope:
%$/)$&7258

%$/$1&(8/,0,7 Umax
V
Figure 6-56 Voltage balance monitoring

Broken-wire During steady-state operation the open-circuit supervision registers interruptions in


Monitoring the secondary circuit of the current transformers. In addition to the hazard potential
caused by high voltages in the secondary circuit, this kind of interruptions simulates
differential currents to the differential protection, such as those evoked by short-cir-
cuits in the protected object.
The broken-wire monitor scans the current of each phase and picks up when the cur-
rent experiences an abrupt drop to 0 (from > 0.1·IN), however, in such a way that no
corresponding drop appears in the earth current. The differential protection is blocked
immediately in the relevant phase. This blocking has an impact on both ends of the
protected object. The device issues the message “%URNHQ,ZLUH” indicating also the
phase.
The blocking is cancelled as soon as the device is again fed with current in the relevant
phase. It is also cancelled if, for the period the short-circuit current flows through the
line, a high short-circuit current (> 1.5 ·IN) is registered by the other device of the dif-
ferential protection system.

6-118 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

Note:
The broken-wire monitor only operates if the earth current of a separate earth current
transformer at the protected line or if no earth current is fed to the fourth current input
(I4) of the relay.

6.12.1.4 Trip Circuit Supervision

The differential protection 7SD610 is equipped with an integrated trip circuit supervi-
sion. Depending on the number of available binary inputs that are not connected to the
common potential, supervision with one or two binary inputs can be selected. If the al-
location of the necessary binary inputs does not comply with this monitoring mode, an
alarm (with the number of the non-compliant circuit) is given. If two binary inputs are
used, disturbances in the trip circuit can be recognized in any circuit state; with one
binary input, circuit breaker disturbances cannot be recognized. If single-pole tripping
is possible, trip circuit supervision can be performed for each circuit breaker pole as
long as the necessary binary inputs are available.

Supervision Using If two binary inputs are used, they are connected according to Figure 6-57, one in par-
Two Binary Inputs allel to the assigned command relay contact of the protection and the other parallel to
the circuit-breaker auxiliary-contact.
A precondition for the use of the trip circuit supervision is that the control voltage for
the circuit breaker is higher than the sum total of the minimum voltages drops at the
two binary inputs (UCtrl > 2·UBImin). As at least 19 V are needed at each binary input,
supervision can be used with a control voltage over approximately 38 V.

UCtrl
L+ 7SD610
)1R
UBI1 >TripC1 TripRel
7SD610
TR )1R
>TripC1 Brk.Rel

Legend:
TR — Trip relay contact
CB — Circuit breaker
UBI2 CBC — Circuit breaker coil
Aux.1 — Circuit breaker auxiliary contact (make)
CB
CBC Aux.1 Aux.2 Aux.2 — Circuit breaker auxiliary contact (break)
UCtrl — Control voltage (trip voltage)
UBI1 — Input voltage of 1st binary input
UBI2 — Input voltage of 2nd binary input
Note: The diagram shows the circuit breaker in closed
L– state.

Figure 6-57 Principle of the trip circuit supervision with two binary inputs

The trip circuit supervision with two binary inputs recognizes not only interruptions of
the trip circuit and failures of the control voltage but monitors also the reactions of the
circuit breaker with the help of the position of the circuit breaker auxiliary contacts.

7SD610 Manual 6-119


C53000-G1176-C145-1
Functions

Depending on the state of the trip relay and the circuit breaker, the binary inputs are
triggered (logic state “H” in Table 6-3) or short-circuited (logic state “L”).
A state in which both binary inputs are not activated (“L”) is only possible in intact trip
circuits for a short transition phase (trip relay contact closed but circuit breaker not yet
open).
This state is only permanent in the event of interruptions or short-circuits in the trip cir-
cuit, a battery voltage failure or a malfunction in the mechanical system of the circuit
breaker. Therefore, this state is one of the supervision criteria.

Table 6-3 Status table of the binary inputs depending on TR and CB

No. Trip relay Circuit breaker Aux.1 Aux.2 BI 1 BI 2


1 open ON closed open H L
2 open OFF open closed H H
3 closed ON closed open L L
4 closed OFF open closed L H

The states of the two binary inputs are queried periodically, approximately every
500 ms. Only after n = 3 of these consecutive state queries have recognized a fault is
an alarm output (see Figure 6-58). These repeated measurings determine the delay
time of the alarm and thus avoid that an alarm is output during short-time transient
phases. After the fault is removed in the trip circuit, the fault message is reset auto-
matically after the same time.

)1R
>TripC1Tr.Rel T T
)1R
& FAIL: Trip cir.
)1R
>TripC1Br.Rel T approx. 1 to 2 s

Figure 6-58 Logic diagram of the trip circuit supervision with two binary inputs

Supervision Using The binary input is connected in parallel according to Figure 6-59 to the assigned com-
One Binary Input mand relay of the protection device. The circuit breaker auxiliary-contact is bridged
with the help of a high-impedance equivalent resistance R.
The control voltage for the circuit breaker should be approximately twice as high as
the minimum voltage drop at the binary input (UCtrl > 2·UBImin). Since at least 19 V are
necessary for the binary input, this supervision can be used with a control voltage over
approximately 38 V.

6-120 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

UCtrl
L+ 7SD610
)1R
UBI >TripC1 TripRel
7SD610
TR

Legend:
TR — Trip relay contact
CB — Circuit breaker
R CBC — Circuit breaker coil
Aux.1 — Circuit breaker auxiliary contact (make)
Aux.2 — Circuit breaker auxiliary contact (break)
R — Equivalent resistance
CB CBC Aux.1 Aux.2
UCrtl — Control voltage (trip voltage)
UBI — Input voltage of binary input
Note: The diagram shows the circuit breaker in closed state.

L–
Figure 6-59 Principle of the trip circuit supervision with one binary input

In normal operation the binary input is energized when the trip relay contact is open
and the trip circuit is intact (logic state “H”), as the monitoring circuit is closed via the
auxiliary contact (if the circuit breaker is closed) or via the equivalent resistance R. The
binary input is short-circuited and thus deactivated only as long as the tripping relay is
closed (logic state “L”).
If the binary input is permanently deactivated during operation, an interruption in the
trip circuit or a failure of the (trip) control voltage can be assumed.
As the trip circuit supervision does not work during a system fault condition, the closed
trip contact does not lead to an alarm. If, however, the trip contacts of other devices
also operate on the trip circuit in parallel, the alarm must be delayed with $ODUP'H
OD\(see also Figure 6-60). After the fault in the trip circuit is removed, the alarm is
reset automatically after approximately 1.5 to 2 seconds.

 $ODUP'HOD\
)1R
>TripC1 TripRel )1R
& T Tr
FAIL: Trip cir.
Fault
Tr approx. 1 to 2 s

Figure 6-60 Logic diagram of the trip circuit supervision with one binary input

6.12.1.5 Fault Reactions

Depending on the kind of fault detected, an alarm is output, the processor is restarted
or the device is put out of operation. If the fault is still present after three restart at-
tempts the protection system will take itself out of service and indicate this condition
by drop-off of the “Device OK” relay, thus indicating the device failure. The red LED
“Blocked” on the device front lights up, provided that there is an internal auxiliary volt-
age, and the green LED “RUN” goes out. If the internal auxiliary voltage fails, too, all

7SD610 Manual 6-121


C53000-G1176-C145-1
Functions

LEDs are dark. Table 6-4 shows a summary of the monitoring functions and the fault
reactions of the device.

Table 6-4 Summary of the fault reactions of the device

Supervision Possible causes Fault reaction Alarm Output


2
Auxiliary voltage External (aux. voltage) Device out of operation All LEDs dark DOK ) drops off
failure Internal (converter) or alarm, if possible “(UURU 9“
Measured value ac- Internal (converter or ref- Protection out of opera- LED “ERROR” DOK2) drops off
quisition erence voltage) tion, alarm “(UURU$'FRQY“
Back-up battery Internal (back-up battery) Alarm “)DLO%DWWHU\´ as allocated
Hardware watchdog Internal (processor Device out of operation LED “ERROR“ DOK2) drops off
failure)
Software watchdog Internal (program flow) Restart attempt1) LED “ERROR“ DOK2) drops off
Working memory Internal (RAM) Restart attempt1), LED flashes DOK2) drops off
Restart abort
device out of operation
Program memory Internal (EPROM) Restart attempt1) LED “ERROR“ DOK2) drops off
Parameter Internal (EEPROM or Restart attempt1) LED “ERROR“ DOK2) drops off
memory RAM)
Scanning Internal (clock generator) Device out of operation LED “ERROR“ DOK2) drops off
frequency
1 A/5 A–setting 1/5 A jumper wrong Alarms: “,1 $ ZURQJ“ DOK2) drops off
Protection out of opera- “(UURU$'FRQY“
tion LED “ERROR“
Calibration data Internal (EEPROM or Alarm: “$ODUP12FDOLEU” as allocated
RAM) Using default values
Modules Module does not Alarms: “(UURU%RDUG“ DOK2) drops off
comply with ordering Protection out of opera- and if applicable
number tion “(UURU$'FRQY“
Summation Internal (measured data Alarm ´)DLOXUHΣ,“ as allocated
current acquisition)
Current symmetry External (system or Alarm “)DLO,%DODQFH“ as allocated
transformer)
Wire break External (system or Alarm “%URNHQ:LUH“ as allocated
transformer)
Voltage symmetry External (system or Alarm “)DLO8%DODQFH“ as allocated
current transforme)r
Trip circuit External (trip circuit or Alarm “)$,/7ULSFLU“ as allocated
supervision control voltage)
1) After three unsuccessful attempts the device is put out of operation
2)
DOK = “Device OK” relay

6-122 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

6.12.1.6 Group Alarms

Certain messages of the monitoring functions are already combined to group alarms.
Table 6-5 shows an overview of these group alarms an their composition.

Table 6-5 Group alarms

Group alarm Composed of


FNo Designation FNo Designation
161 Fail I Superv. 289 Failure Σi
163 Fail I balance
164 Fail U Superv. 167 Fail U balance
160 Alarm Sum Event 289 Failure Σi
163 Fail I balance
167 Fail U balance
361 >FAIL:Feeder VT
177 Fail Battery
193 Alarm NO calibr
183 Error Board 1
184 Error Board 2 1)
185 Error Board 3 1)
186 Error Board 4 1)
187 Error Board 5 1)
188 Error Board 6 1)
189 Error Board 7 1)
140 Error Sum Alarm 144 Error 5V
192 Error1A/5Awrong
181 Error A/D-conv.
1) depending on the identification number of printed circuit boards

6.12.2 Setting the Function Parameters

The sensitivity of the measurement supervision can be altered. Experiential values set
ex works are sufficient in most cases. If an extremely high operational unbalance of
the currents and/or voltages is to be expected in the relevant application, or if during
operation some or other monitoring function is activated sporadically, the parameter
should be set less sensitive.

Symmetry The symmetry supervision can be switched 2Q or 2II in address  0($685(
Supervision 683(59.
Address $ %$/$1&(8/,0,7determines the threshold voltage (phase-to-
phase) above which the voltage symmetry supervision is effective (see also Figure 6-
56). Address $ %$/)$&7258 is the associated balance factor, i.e. the gradi-
ent of the symmetry characteristic (Figure 6-56). This parameter can only be changed
with DIGSI® 4 under “Additional Settings”.

7SD610 Manual 6-123


C53000-G1176-C145-1
Functions

Address $ %$/$1&(,/,0,7 determines the threshold current above which


the current balance supervision is effective (also see Figure 6-55). Address $
%$/)$&725, is the associated balance factor, i.e. the gradient of the balance
characteristic (Figure 6-55).

Wire Break The wire break supervision can be switched 2Q or 2II in address  %52.(1
Supervision :,5(.

Summated Current The summated current supervision can be switched 2Q or 2II in address  )$67
Supervision 6L683(59.
Address $ Σ,7+5(6+2/' determines the threshold current above which the
summation current supervision (see Figure 6-54) responds (absolute share, only re-
ferred to IN). The relative share (referred to the maximum phase current) for the re-
sponse of the summated current supervision (Figure 6-54) is set in address $ Σ,
)$&725. This parameter can only be changed with DIGSI® 4 under “Additional Set-
tings”.

Note:
Current sum monitoring can operate properly only when the residual current of the
protected line is fed to the fourth current input (I4) of the relay.

Trip Circuit When address  7ULS&LUF6XSHUY was configured (Section 5.1), the number
Supervision of circuits that are to be monitored was set. If the trip circuit supervision function is not
used at all, 1RQH[LVW is set there.
The trip circuit supervision can be switched 2Q or 2II in address  )&77ULS
6XSHUY. The number of the binary inputs per trip circuit is entered under address
 1RRI%,. If the routing of the binary inputs required for this does not comply
with the selected supervision mode, an alarm is output (with the number of the non-
compliant trip circuit).
The trip circuit alarm is delayed for approximately 1 s to 2 s in supervision with two bi-
nary inputs, whereas the delay can be set under address  $ODUP'HOD\in su-
pervision with one binary input. 1 s to 2 s are sufficient if only device 7SD610 operates
on the trip circuits as the trip circuit supervision does not operate during a system fault.
If, however, the trip contacts of other devices work also on the trip circuit in parallel,
the alarm must be delayed for longer than the longest possible duration of a tripping
command.

6.12.3 Setting Overview

Measurement Note: The indicated setting ranges and default settings refer to a secondary rated cur-
Supervision rent of IN = 1 A. For the secondary rated current of IN = 5 A these values are to be

6-124 7SD610 Manual


C53000-G1176-C145-1
Monitoring functions

multiplied by 5. For the setting of primary values the transformation ratio of the trans-
formers must also be taken into consideration.

Addr. Setting Title Setting Options Default Setting Comments


2901 MEASURE. SUPERV ON ON Measurement Supervision
OFF

2902A BALANCE U-LIMIT 10..100 V 50 V Voltage Threshold for Balance Monitoring

2903A BAL. FACTOR U 0.58..0.95 0.75 Balance Factor for Voltage Monitor

2904A BALANCE I LIMIT 0.10..1.00 A 0.50 A Current Balance Monitor

2905A BAL. FACTOR I 0.10..0.95 0.50 Balance Factor for Current Monitor

2908 BROKEN WIRE ON ON Fast broken current-wire supervision


OFF

2921 FAST Σ i SUPERV ON ON State of fast current summation supervis


OFF

2906A ΣI THRESHOLD 0.10..2.00 A 0.25 A Summated Current Monitoring Threshold

2907A ΣI FACTOR 0.00..0.95 0.50 Summated Current Monitoring Factor

Trip Circuit
Supervision

Addr. Setting Title Setting Options Default Setting Comments


4001 FCT TripSuperv. ON OFF TRIP Circuit Supervision is
OFF

4002 No. of BI 1..2 2 Number of Binary Inputs per trip cir-


cuit

4003 Alarm Delay 1..30 sec 2 sec Delay Time for alarm

6.12.4 Information Overview

Hardware and Soft-


ware Monitoring
F.No. Alarm Comments
140 Error Sum Alarm Error with a summary alarm
144 Error 5V Error 5 V
160 Alarm Sum Event Alarm Summary Event
177 Fail Battery Failure: Battery empty
181 Error A/D-conv. Error: A/D converter
182 Alarm Clock Alarm: Real Time Clock
183 Error Board 1 Error Board 1

7SD610 Manual 6-125


C53000-G1176-C145-1
Functions

F.No. Alarm Comments


184 Error Board 2 Error Board 2
185 Error Board 3 Error Board 3
186 Error Board 4 Error Board 4
187 Error Board 5 Error Board 5
188 Error Board 6 Error Board 6
189 Error Board 7 Error Board 7
192 Error1A/5Awrong Error: 1A/5A jumper different from setting
193 Alarm NO calibr Alarm: NO calibration data available

Measurement
Supervision
F.No. Alarm Comments
161 Fail I Superv. Failure: General Current Supervision
289 Failure Σi Alarm: Current summation supervision
163 Fail I balance Failure: Current Balance
164 Fail U Superv. Failure: General Voltage Supervision
167 Fail U balance Failure: Voltage Balance
197 MeasSup OFF Measurement Supervision is switched OFF
295 Broken wire OFF Broken wire supervision is switched OFF
296 Σi superv. OFF Current summation superv is switched OFF
290 Broken Iwire L1 Alarm: Broken current-wire detected L1
291 Broken Iwire L2 Alarm: Broken current-wire detected L2
292 Broken Iwire L3 Alarm: Broken current-wire detected L3

Trip Circuit
Supervision
F.No. Alarm Comments
6854 >TripC1 TripRel >Trip circuit superv. 1: Trip Relay
6855 >TripC1 Bkr.Rel >Trip circuit superv. 1: Breaker Relay
6856 >TripC2 TripRel >Trip circuit superv. 2: Trip Relay
6857 >TripC2 Bkr.Rel >Trip circuit superv. 2: Breaker Relay
6858 >TripC3 TripRel >Trip circuit superv. 3: Trip Relay
6859 >TripC3 Bkr.Rel >Trip circuit superv. 3: Breaker Relay
6861 TripC OFF Trip circuit supervision OFF
6865 FAIL: Trip cir. Failure Trip Circuit
6866 TripC1 ProgFAIL TripC1 blocked: Binary input is not set
6867 TripC2 ProgFAIL TripC2 blocked: Binary input is not set
6868 TripC3 ProgFAIL TripC3 blocked: Binary input is not set

6-126 7SD610 Manual


C53000-G1176-C145-1
Function Control

6.13 Function Control

The function control is the control centre of the device. It coordinates the sequence of
protection and ancillary functions, processes their decisions and the information com-
ing from the system. Among these are
• Switch-in recognition,
• Recognition of the circuit breaker status,
• Fault detection/pickup logic,
• Tripping logic.

6.13.1 Switch-in Recognition

When a protected object is switched in, several measures may be necessary or desir-
able; e.g. for manual closure onto a fault usually instantaneous tripping is desired.
This is done in overcurrent protection by bypassing the delay of one current stage. For
every short-circuit protection function which can be delayed, at least one stage can be
selected that is instantaneously active in the event of a manual closing, as mentioned
in the relevant sections. Also see Section 6.1.3 under the subtitle “Circuit Breaker Sta-
tus”, page 6-17.
The manual closing command must be transmitted to the device via a binary input.
The command is set to a defined length (to be set under address $ 6,7LPH
0DQ&O) to be independent of the actual duration of an individual manual closing op-
eration. Figure 6-61 shows the logic diagram.

 6,7LPH0DQ&O
FNr 356
FNr 561
>Manual Close
& T Man.Clos.Detect.
FNr 2851
AR Close
Figure 6-61 Logic diagram of the manual closing procedure

If the 7SD610 is equipped with an integrated auto-reclosure function, the integrated


manual closing logic differentiates automatically between an external control com-
mand via the binary input and an automatic reclosure through the internal auto-reclose
function. Thus the binary input “!0DQXDO&ORVH” can be connected directly to the
closing coil of the circuit breaker (Figure 6-62).
If, however, external closing commands are possible which must not activate the man-
ual closing function (e.g. external reclosure device), the binary input “!0DQXDO
&ORVH” must be activated by a separate contact of the control-discrepancy switch
(Figure 6-63).

7SD610 Manual 6-127


C53000-G1176-C145-1
Functions

L+
Control 7SD610
discrep.
switch
FNr 356
>Manual Close

FNr 2851
AR Close
CB CBC
Legend:
CB — Circuit breaker
CBC — Circuit breaker closing coil
L–
Figure 6-62 Manual closing with internal auto-reclosure function

L+
Control
7SD610
External discrep.
switch
AR device FNr 356
>Manual Close
Reclose
command

CB CBC
Legend:
CB — Circuit breaker
CBC — Circuit breaker closing coil
L–
Figure 6-63 Manual closing with external auto-reclosure device

6.13.2 Recognition of the Circuit Breaker Status

Several protection and ancillary functions require information on the status of the cir-
cuit breaker for proper functioning. This is e.g. helpful for
− the conditions when connecting the protected object (cf. Sub-section 6.7.1),
− start of the dead times before auto-reclosure (cf. Sub-section 6.9.1),
− plausibility check before auto-reclosure (cf. Sub-section 6.9.1),
− the enabling condition for the high-current switch-on-to-fault protection
(I>>> stage, cf. 6.7.1), also for all ends of the protected object,
− the circuit breaker failure protection (cf. Sub-section 6.10.1),
− the verification of the reset conditions for the tripping command (cf. Sub-section
6.13.4),
− the trip circuit check with the help of the TRIP–CLOSE–test cycle (cf. Sub-section
6.13.5).

6-128 7SD610 Manual


C53000-G1176-C145-1
Function Control

The device is equipped with a circuit breaker position logic (Figure 6-64), which offers
different options depending on which auxiliary contacts of the circuit breaker are avail-
able and on how they are connected to the device.
In most cases it is sufficient to have the status of the circuit breaker signalled by its
auxiliary contact to the device via a binary input. This is valid if the circuit breaker is
always operated three-pole. In this case the make contact of the auxiliary contact is to
be connected to a binary input which must be allocated to the input function “!&%S
&ORVHG” (FNo ). Then the other inputs are not assigned and the logic is limited to
the transmission of this input information.
If the breaker poles can be operated individually and e.g. only the series-connected
break contacts are available, the associated binary input is also allocated to function
“!&%S2SHQ” (FNo ). The other inputs are not assigned either in that case.
If the breaker poles can be closed individually and the auxiliary contacts are acces-
sible individually, each auxiliary contact should be assigned its own binary input as far
as possible if the device can and is supposed to perform single-pole tripping. With the
help of this connection, the device can process a maximum amount of information.
Three binary inputs are necessary for this:
− “!&%$X[/” (FNo ), for the auxiliary contact of pole L1,
− “!&%$X[/” (FNo ), for the auxiliary contact of pole L2,
− “!&%$X[/” (FNo ), for the auxiliary contact of pole L3,
The entries FNo  and FNo  are not used in this case.
If the breaker poles can be closed individually, two binary inputs are sufficient if both
the series-connected make contacts and the series-connected break contacts of the
auxiliary contacts of the three poles are available. The series circuit of the make con-
tacts is allocated on the input function “!&%S&ORVHG” (FNo ) and the series
circuit of the closing contacts on the input function “!&%S2SHQ” (FNo ) in this
case.
Please note that Figure 6-64 shows the entire logic of all connection possibilities. Only
a part of the inputs is used for the respective application as described above.
The 8 output signals of the circuit breaker status logic can be processed by the indi-
vidual protection and ancillary functions. The output signals are blocked if the signals
transmitted from the circuit breaker are not plausible: for example, the circuit breaker
cannot be open and closed at the same time, or an open circuit pole cannot be live.
In 7SD610 the position of the circuit breaker poles recognized by the device is also
transmitted to the remote end device. This way the position of the circuit breaker poles
is also recognized by at the other end. The high-current switch-on-to-fault protection
(see 6.7.1) makes use of this function.
Special binary inputs are available for the auto-reclosure function and for the circuit
breaker check; they are to be handled in the same way and additionally allocated if
necessary. These inputs have an analogue meaning to the inputs described above
and are identified with “/6 ...” for easier distinction:
− “!&%S&ORVHG” (FNo ) for the series circuit of the make contacts of the
auxiliary contacts,
− “!&%S2SHQ” (FNo ) for the series circuit of the closing contacts of the aux-
iliary contacts,
− “!&%3ROH/” (FNo ) for the auxiliary contact of pole L1,
− “!&%3ROH/” (FNo ) for the auxiliary contact of pole L2,

7SD610 Manual 6-129


C53000-G1176-C145-1
Functions

− “!&%3ROH/” (FNo ) for the auxiliary contact of pole L3.

CB auxiliary contacts:

FNo 380 R380


L1 L2 L3
>CB 3p Open
(Series-connected break contacts)

R380 ≥1
& any pole closed

FNo 351 R351


L1
>CB Aux. L1
≥1
& L1 closed

R351 ≥1
& L1 open

FNo 352 R352


L2
>CB Aux. L2
≥1
& L2 closed

R352 ≥1
& L2 open

L3 FNo 353 R353


>CB Aux. L3
≥1
& L3 closed

R353 ≥1
& L3 open

FNo 379 R379


L1 L2 L3
>CB 3p Closed
(Series-connected make contacts)

≥1
& any pole open
R379

8
L1, L2, L3 Circuit breaker
auxiliary contacts Plausibility
FNr ... Binary input with FNo
IRES check
R ... Binary input is allocated 3

Figure 6-64 Circuit breaker position logic

6-130 7SD610 Manual


C53000-G1176-C145-1
Function Control

6.13.3 Fault Detection Logic of the Entire Device

Phase-segregated The fault detection logic combines the pickup signals of all protection functions. For
Pickup those protection functions which allow phase-segregated pickup, the pickup is output
per phase. When a protection function detects a ground fault, a device group alarm is
output. Thus the alarms “5HOD\3,&.83/”, “5HOD\3,&.83/”, “5HOD\3,&.
83/” and “5HOD\3,&.83(” are available.
These alarms can be allocated to LEDs or output relays. Some protection functions
can also indicate the phase pickup as a group signal for the local displaying of fault
messages and for the transmission of the messages to a PC or a central control sys-
tem, e.g. “'LII)OW/(” for differential protection pickup L1–L2–E; only one of
these is displayed at a time and represents the entire pickup image.

General Pickup The pickup signals are ORed and lead to a general pickup of the device. It is signalled
with the alarm “5HOD\3,&.83”. If no protection function of the device has picked up
any longer, “5HOD\3,&.83” disappears (message: “*RLQJ”).
The general pickup is the precondition for a number of internal and external sequence
functions. Among these functions, which are controlled by the general pickup, are:
• Start of a fault log: All fault messages are entered into the fault log from the begin-
ning of the general pickup to the drop-off.
• Initialization of the fault recording: The recording and availability of fault wave form
can additionally be made subject to the presence of a trip command.
• Creation of spontaneous messages: Certain fault messages can be displayed as so
called spontaneous messages (see “Spontaneous Alarms” below). This display can
additionally be made subject to the presence of a trip command.
• Start of the action time of the auto-reclosure (if available and used).
External functions can be controlled via an output contact. Examples are:
• Reclosure devices,
• Further additional devices or similar.

Spontaneous Spontaneous alarms are alarms that are displayed automatically after a general pick-
Alarms up of the device or after the trip command of the device. In the case of 7SD610 they
are the following:
• “5HOD\3,&.83“: pickup of the differential protection with phase indication;
• “387LPH: the operating time from the general pickup to the dropoff of the
device, the time is given in ms;
• “75,37LPH: the operating time from the general pickup to the first trip
command of the device, the time is given in ms.

7SD610 Manual 6-131


C53000-G1176-C145-1
Functions

6.13.4 Tripping Logic of the Entire Device

Three-pole Three-pole tripping is the usual action of the device in the event of a fault, single-pole
Tripping tripping, however, is also possible depending on the version ordered (see below). If a
single-pole tripping is generally not possible or not desired, the output function “5HOD\
75,3/” is used for the output of commands to the circuit-breaker. In these cases
the following subtitle on “Single-pole Tripping” is not relevant.

Single-pole Single-pole tripping is advisable only for overhead lines on which auto-reclosures are
Tripping to be executed and which are equipped with circuit breakers suitable for single-pole
tripping on both ends. In this case the faulty phase can be tripped single-pole with sub-
sequent reclosure in the event of a single-phase fault; in the event of two-phase or
three-phase faults with or without ground fault a three-pole tripping is effected in gen-
eral.
Preconditions for pole-segregated tripping concerning the device are,
• that the device is suitable for pole-segregated tripping (according to the order spec-
ification),
• that the tripping protection function is suitable for pole-segregated tripping (for ex-
ample, not for overload protection),
• that the binary input “!S7ULS3HUP” is allocated and activated or that the internal
auto-reclosure function is ready for auto-reclosure after single-pole tripping.
In all other cases tripping will be three-pole. The binary input “!S7ULS3HUP” is the
logic inversion of a three-pole coupling and is activated by an external auto-reclosure
device as long as this is ready for a single-pole auto-reclosure cycle.
With the 7SD610, three-pole coupling of the trip command is also possible if tripping
only concerns one phase but more than one phase has picked up. This can be the
case e.g. if two short-circuits occur in two different places of which only one is within
the range of the differential protection zone. This is achieved with the help of setting
parameter SROHFRXSOLQJwhich can be set to ZLWK3LFNXS (each multiphase
pickup leads to three-pole tripping) or ZLWK7ULS (three-pole tripping in the event of
a multi-pole trip command).
The tripping logic combines the trip signals of all protection functions. Trip commands
are output per phase if the protection functions allow single-pole tripping. The relevant
alarms are “5HOD\75,3/”, “5HOD\75,3/” and “5HOD\75,3/”.
These alarms can be allocated to LEDs or output relays. In the event of a three-pole
tripping all three messages are displayed.
If single-pole tripping is possible, the protection functions can also output a group sig-
nal for the local displaying of alarms and for the transmission of the alarms to a PC or
a central control system, e.g. “'LII75,3S/”, “'LII75,3S/”, “'LII
75,3S/” for single-pole tripping by the differential protection and “'LII75,3
/” for three-pole tripping. Only one of these alarms is displayed at a time. The
alarms are also used for the commands to the circuit breaker.

6-132 7SD610 Manual


C53000-G1176-C145-1
Function Control

Single-pole The single-pole tripping after a two-phase fault is a special case. If a phase-to-phase
Tripping after a fault clear of ground occurs in a grounded system, the fault may be cleared by a single-
Two-phase Fault pole auto-reclosure, since this is sufficient to interrupt the short-circuit current loop.
The phase selected for this must be the same on both line ends and should be the
same everywhere else within the system.
The setting parameter 7ULSSK)OW allows to select whether this tripping should be
SROHOHDGLQJ‘, i.e. single-pole tripping of the leading phase, or SROHODJJLQJ
‘, i.e. single-pole tripping of the lagging phase. Standard setting is SROH, i.e. three-
pole tripping after two-phase faults (default setting). Ø
Table 6-6 shows a summary of the conditions for single-pole or three-pole tripping.

Table 6-6 Single- and three-pole tripping depending on the type of fault

Type of fault Parameter Output signals for tripping


(of protection 7ULSSK)OW 5HOD\75,3 5HOD\75,3 5HOD\75,3 5HOD\75,3
functions) S/ S/ S/ SK
L1 (any) X
L2 (any) X
L3 (any) X
L1 E (any) X
L2 E (any) X
L3 E (any) X
L1 L2 SROH X
L1 L2 SROHOHDGLQJ‘ X
L1 L2 SROHODJJLQJ‘ X
L2 L3 SROH X
L2 L3 SROHOHDGLQJ‘ X
L2 L3 SROHODJJLQJ‘ X
L1 L3 SROH X
L1 L3 SROHOHDGLQJ‘ X
L1 L3 SROHODJJLQJ‘ X
L1 L2 E (any) X
L2 L3 E (any) X
L1 L3 E (any) X
L1 L2 L3 (any) X
L1 L2 L3 E (any) X
E (any) X

General tripping All tripping signals of the protection functions are OR’d and lead to the alarm “5HOD\
75,3“. This can be allocated to an LED or output relay.

7SD610 Manual 6-133


C53000-G1176-C145-1
Functions

Terminating the Once a trip command is output, it is stored separately for each pole (each of the three
Trip Command poles after three-pole tripping, see Figure 6-65). At the same time a minimum trip com-
mand duration 70LQ75,3&0' is started to ensure that the command is sent to the
circuit breaker long enough if the tripping protection function should drop off too quick-
ly. The trip commands cannot be terminated until the last protection function has
dropped off (no function activated) AND the minimum trip command time is over.
Another condition for terminating the trip command is that the circuit breaker is open
(with single-pole tripping the relevant circuit breaker pole). The current must have
fallen below the value that corresponds to the setting value 3ROH2SHQ&XUUHQW (ad-
dress $, refer to “Circuit Breaker Status” in Section 6.1.3, page 6-17) plus 10 %
of the fault current.

)1R
Trip L1 S Q Dev. Trip L1
from protection fucntions

CB open L1
& R
)1R
Trip L2 S Q Dev. Trip L2
CB open L2
& R
)1R
Trip L3 S Q Dev. Trip L3
CB open L3
& R

&

70LQ75,3&0' 

≥1
T

Figure 6-65Storage and termination of the trip command

Reclosure Inter- When tripping the circuit breaker with a protection function the manual reclosure must
locking often be blocked until the cause for the protection function operation is found. 7SD610
therefore provides the integrated reclosure interlocking function.
The interlocking state (“/2&.287”) is realized by a RS flipflop which is protected
against auxiliary voltage failure (see Figure 6-66). The RS flipflop is set via a binary
input “!/RFNRXW6(7” (FNo ). With the output alarm “/2&.287” (FNo ), if in-
terconnected correspondingly, a reclosure of the circuit breaker (e.g. for automatic re-
closure, manual close signal, synchronization, closing via control) can be blocked.
Only once the cause for the protection operation is known, should the interlocking be
reset by a manual reset via binary input “!/RFNRXW5(6(7” (FNo ).

)1R )1R
>Lockout Set S Q LOCKOUT
)1R R
>Lockout Reset

Figure 6-66 Reclosure lockout

6-134 7SD610 Manual


C53000-G1176-C145-1
Function Control

Conditions which cause reclosure interlocking and control commands which have to
be interlocked can be set individually. The two inputs and the output can be wired via
the correspondingly allocated binary inputs and outputs or be linked via user-defined
logic functions (CFC).
If, for example, each trip by the protection function has to cause a reclosing lock-out,
then combine the tripping command “5HOD\75,3” (FNo ) with the binary input
“!/RFNRXW6(7” (FNo ). If automatic reclosure is applied, only the final trip of the
protection function should establish reclosing lock-out. Then combine the output alarm
“)LQDO7ULS” (FNo ) with the interlocking input “!/RFNRXW6(7” (FNo ), so
that the interlocking function is not established when an automatic reclosure is still ex-
pected to come.
In the most simple case the output alarm “/2&.287” (FNo ) can be allocated to
the output which trips the circuit breaker without creating further links. Then the trip-
ping command is maintained until the interlock is reset via the binary reset input. Nat-
urally it has to be ensured in advance that the close coil at the circuit breaker — as is
usually done — is locked as long as a tripping command is maintained.
The output alarm “/2&.287” can also be applied to interlock certain closing com-
mands (externally or via CFC), e.g. by combining the output alarm with the binary input
“!&ORVH&PG%OR” (FNo ) or by connecting the inverted alarm with the bay inter-
locking of the branch.
The reset input “!/RFNRXW5(6(7” (FNo ) resets the interlocking state. This input
is initiated by an external device which is protected against unauthorized or uninten-
tional operation. The interlocking state can also be controlled by internal sources, e.g.
a function key, operation of the device or using DIGSI® 4 on a PC.
For each case please make sure the corresponding logical combinations, security
measures, etc. are taken into account for the routing of the binary inputs and outputs
(Section 5.2) and are also considered for the setting of user-defined logic functions
(Section 5.3), if necessary.

“No Trip no Flag” The storage of alarms allocated to local LEDs and the availability of spontaneous
alarms can be made dependent on the device sending a trip command. Fault event
information is then not output when one or more protection functions have picked up
due to a fault but no tripping occurred because the fault was removed by another de-
vice (e.g. on a different line). The information is thus limited to faults on the protected
line “no trip – no flag”.
Figure 6-67 shows the logic diagram of this function.

 )OW'LVS/('/&'
ZLWK3LFNXS
“1“ ZLWK7ULS

Device TRIP &


Reset LED and spontaneous alarms
Device dropoff

Figure 6-67 Logic diagram of the “no–trip–no–flag” function (command-dependent alarms)

7SD610 Manual 6-135


C53000-G1176-C145-1
Functions

CB Operation The number of trips caused by the device 7SD610 is counted. If the device is to be
Statistics used for single-pole tripping, this number is counted for each CB pole individually.
Furthermore, the current switched for each pole is acquired, output as an alarm and
summated in a memory.
If the device is equipped with an integrated auto-reclosure function, the automatic
closing commands are counted, separately for reclosure after single-pole trip, after
three-pole trip, as well as separately for the first reclosure cycle and further reclosure
cycles.
The levels of these counted and metered values are buffered against auxiliary voltage
failure. They can be set to zero or to any other initial value. For further information see
Section 7.1.2.

6.13.5 Circuit Breaker Test

The differential protection 7SD610 allows an easy check of the trip circuits and the cir-
cuit breakers.
The test programs according to Table 6-7 are available for the test. Of course, single-
pole tests are available only if the device is suitable for single-pole tripping.
The output alarms mentioned must be allocated to the relevant command relays (ac-
cording to Section 5.2.4) that are used for controlling the circuit breaker coils.
The test is started via the operation panel on the front of the device or via the PC with
DIGSI® 4. To know how to proceed refer to Section 7.3. Figure 6-68 shows the chron-
ological sequence of one TRIP–CLOSE test cycle. The set times are those stated in
Section 6.1.1 for “Trip Command Duration” and “Circuit Breaker Test”.
Where the circuit breaker auxiliary contacts transmit the status of the circuit breaker
or of its poles to the device via binary inputs, the test cycle can only be initiated if the
circuit breaker is closed.
The information on the circuit breaker status during the circuit breaker test is not au-
tomatically adopted by the position logic according to 6.13.2 (Figure 6-64). It is rather
that for the circuit breaker test special binary inputs are provided for the status feed-
backs that are to be taken into consideration when allocating the binary inputs, as de-
scribed in Section 6.13.2. (Page 6-129).
The device displays the states of the test sequence with the relevant alarms.

6-136 7SD610 Manual


C53000-G1176-C145-1
Function Control

Table 6-7 Circuit breaker test programs

Con- Test programs Circuit Output alarms (FNo)


sec. breaker
no.
1 Single-pole OFF/ON cycle phase CB1-TESTtrip L1 (7325)
L1
2 Single-pole OFF/ON cycle phase CB1-TESTtrip L2 (7326)
LS 1
L2
3 Single-pole OFF/ON cycle phase CB1-TESTtrip L3 (7327)
L3
4 Three-pole OFF/ON cycle CB1-TESTtrip 123 (7328)

Associated close command CB1-TEST close (7329)

TRIP

CLOSE

70LQ75,3&0' 77&%WHVWGHDG 70D[&/26(&0' t


  
Figure 6-68 TRIP–CLOSE test cycle

6.13.6 Setting the function parameters

The parameters for the tripping logic of the entire device and the circuit breaker test
have already been set in Sections 6.1.3 and 6.1.1.
Address  )OW'LVS/('/&' still decides whether the alarms that are allocated
to local LEDs and the spontaneous alarms that appear on the local display after a fault
should be stored on every pickup of a protection function ('LVSOD\7DUJHWVRQ
HYHU\ SLFNXS) or whether they should be stored only when a tripping command is
given ('LVSOD\7DUJHWVRQ 75,3RQO\).

7SD610 Manual 6-137


C53000-G1176-C145-1
Functions

6.13.7 Setting Overview

Fault Display

Addr. Setting Title Setting Options Default Setting Comments


610 FltDisp.LED/LCD Display Targets on every Pickup Display Targets on every Fault Display on LED / LCD
Display Targets on TRIP only Pickup

6.13.8 Information Overview

Circuit Breaker
Test

F.No. Alarm Comments


7325 CB1-TESTtrip L1 CB1-TEST TRIP command - Only L1
7326 CB1-TESTtrip L2 CB1-TEST TRIP command - Only L2

7327 CB1-TESTtrip L3 CB1-TEST TRIP command - Only L3

7328 CB1-TESTtrip123 CB1-TEST TRIP command L123

7329 CB1-TEST close CB1-TEST CLOSE command

7345 CB-TEST running CB-TEST is in progress

7346 CB-TSTstop FLT. CB-TEST canceled due to Power Sys. Fault

7347 CB-TSTstop OPEN CB-TEST canceled due to CB already OPEN

7348 CB-TSTstop NOTr CB-TEST canceled due to CB was NOT READY

7349 CB-TSTstop CLOS CB-TEST canceled due to CB stayed CLOSED

7350 CB-TST .OK. CB-TEST was succesful

CB1tst L1 CB1-TEST trip/close - Only L1

CB1tst L2 CB1-TEST trip/close - Only L2

CB1tst L3 CB1-TEST trip/close - Only L3

CB1tst 123 CB1-TEST trip/close Phases L123

6-138 7SD610 Manual


C53000-G1176-C145-1
Commissioning Tools

6.14 Commissioning Tools

6.14.1 Function Description

The device is provided with a large commissioning and monitoring tool that checks the
communication and the whole differential protection system. Using a personal compu-
ter in conjunction with a web-browser this tool enables the user to chart the state of
the system and the communication of the differential protection precisely.
The necessary operator software is integrated in the device; online-help can be found
on the DIGSI® 4–CD and is also available in the Internet.
To ensure a proper communication between the device and the PC browser the trans-
mission speed must be equal for both. Furthermore, the user must set an IP-address
so that the browser can identify the device.
Thanks to the “IBS-tool” the user is able to operate the device with the PC. On the PC-
screen the front panel of the device is simulated, a function that can also be deactivat-
ed.

6.14.2 Setting Parameters

The parameters of the “IBS-tool” can be set separately for the front operating interface
and the rear service interface. The addresses corresponding to the interface that en-
able the communication with the PC and the “IBS-tool” are the most relevant ones.
Addresses  to  are to configure the front interface. The 12-digit IP-address
is formatted as follows: ***.***.***.***. There is a 3-digit block in each of the following
setting addresses:  ,3$ $[[[ ,  ,3% [%[[ ,  ,3&
[[&[ and  ,3' [[[' .
The address  180/2&. determines if the differential protection device should
be operated with the “IBS–tool” from the PC. When setting <HV, the devices cannot
be operated by the simulation of the PC. This is the normal state during operation.
Once this address is set to 1R during commissioning, all device parameters can be
changed to correct, for example, false or inconsistent settings.
In address  /&31&3 set if your PC-interface supports LCP (Link Control Proto-
col) and NCP (Network Control Protocol). To make possible the long-distance data
transmission for a point-to-point connection the setting must be <HV (default setting).
When using a star coupler only one device (master-device) requires the setting <HV,
the other device requires 1R.
Addresses  ,3$ $[[[ ,  ,3% [%[[ ,  ,3&
[[&[ and  ,3' [[[' ,  180/2&. and  /&31&3 are
to configure the rear interface.

7SD610 Manual 6-139


C53000-G1176-C145-1
Functions

6.14.3 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


4401 IP-A (A.x.x.x) 0..255 141 IP-address ×××.xxx.xxx.xxx(Position 1-3)

4402 IP-B (x.B.x.x) 0..255 142 IP-address xxx.×××.xxx.xxx(Position 4-6)

4403 IP-C (x.x.C.x) 0..255 255 IP-address xxx.xxx.×××.xxx(Position 7-9)

4404 IP-D (x.x.x.D) 0..255 150 IP-address xxx.xxx.xxx.×××(Pos. 10-12)

4405 NUM LOCK YES YES Num Lock


NO

4406 LCP/NCP NO YES Front interface supports LCP/NCP mode


YES

4411 IP-A (A.x.x.x) 0..255 141 IP-address ×××.xxx.xxx.xxx(Position 1-3)

4412 IP-B (x.B.x.x) 0..255 142 IP-address xxx.×××.xxx.xxx(Position 4-6)

4413 IP-C (x.x.C.x) 0..255 255 IP-address xxx.xxx.×××.xxx(Position 7-9)

4414 IP-D (x.x.x.D) 0..255 160 IP-address xxx.xxx.xxx.×××(Pos. 10-12)

4415 NUM LOCK YES YES Num Lock


NO

4416 LCP/NCP NO YES Service interface supports LCP/NCP mode


YES

6-140 7SD610 Manual


C53000-G1176-C145-1
Ancillary Functions

6.15 Ancillary Functions

The auxiliary functions of the 7SD610 relay include:


• processing of messages,
• processing of operational measured values,
• storage of fault record data.

6.15.1 Processing of Messages

For the detailed fault analysis, the information regarding the reaction of the protection
device and the measured values following a system fault are of interest. For this pur-
pose, the device provides information processing which operates in a threefold man-
ner:

Indicators (LEDs) Important events and states are indicated with optical indicators (LED) on the front
and Binary Outputs plate. The device furthermore has output relays for remote indication. Most of the sig-
(Output Relays) nals and indications can be marshalled, i.e. routing can be changed from the preset-
ting with delivery. In Section 5.2 the state of the delivered relay (presetting) and mar-
shalling facilities are extensively discussed.
The output relays and the LEDs may be operated in a latched or unlatched mode
(each may be individually set).
The latched state is saved against loss of auxiliary supply. It is reset:
− locally by operation of the key LED reset on the front of the device,
− from remote via a binary input,
− via one of the serial interfaces,
− automatically on detection of a new fault.
Condition messages should not be latched. Also, they cannot be reset until the crite-
rion to be reported has reset. This applies to e.g. messages from monitoring functions,
or similar.
A green LED indicates that the device is in service (“RUN”); it can not be reset. It ex-
tinguishes if the self-monitoring of the microprocessor recognizes a fault or if the aux-
iliary supply fails.
In the event that the auxiliary supply is available while there is an internal device fail-
ure, the red LED (“ERROR”) is illuminated and the device is blocked.

Information on the Events and states can be obtained from the LCD on the front plate of the device. A
Integrated Display personal computer can be connected to the front interface or the service interface for
(LCD) or to a Per- retrieval of the information.
sonal Computer
In the quiescent state, i.e. as long as no system fault is present, the LCD can display
selectable operational information (overview of the operational measured values). In

7SD610 Manual 6-141


C53000-G1176-C145-1
Functions

the event of a system fault, information regarding the fault, the so-called spontaneous
messages, are displayed instead. The quiescent state information is displayed again
once the fault messages have been acknowledged. The acknowledgement is identical
to the resetting of the LEDs (see above).
The device in addition has several event buffers for operational messages, switching
statistics, etc., which are saved against loss of auxiliary supply by means of a battery
buffer. These messages can be displayed on the LCD at any time by selection via the
keypad or transferred to a personal computer via the serial service or PC interface.
The retrieval of events/alarms during operation is extensively described in Sub-section
7.1.1.
Following a system fault, it is possible to for example retrieve important information re-
garding its progress, such as pick-up and trip. The start of the fault is time stamped
with the absolute time of the internal system clock. The progress of the disturbance is
output with a relative time referred to the instant of fault detection (first pickup of a pro-
tection function), so that the duration of the fault until tripping and up to reset of the trip
command can be ascertained. The resolution of the time information is 1 ms.
With a PC and the protection data processing program DIGSI® 4 it is also possible to
retrieve and display the events with the convenience of visualisation on a monitor and
a menu-guided dialogue. The data may be printed or stored for evaluation at a later
time and place.
The protection device stores the messages of the last eight system faults; in the event
of a ninth fault, the oldest is erased.
A system fault starts with the recognition of the fault by the fault detection, i.e. first pick-
up of any protection function, and ends with the reset of the fault detection, i.e. dropout
of the last protection function, or after the expiry of the auto-reclose reclaim time, so
that several unsuccessful auto-reclose cycles are also stored cohesively. Accordingly
a system fault may contain several individual fault events (from fault detection up to
reset of fault detection).

Information to a If the device has a serial system interface, stored information may additionally be
Control Centre transferred via this interface to a centralised control and storage device. Several com-
munication protocols are available for the transfer of this information.

6.15.2 Measurement during Operation

Displaying of A number of measured values and the values derived from these are available for a
Measured Values query in site or for data transmission (see Table 6-8).
Precondition for a correct display of primary and percentage values is the complete
and correct entry of the nominal values of the instrument transformers and the power
equipment as well as the transformation ratio of the current and voltage transformers
in the ground paths according to Section 6.1.1.
Depending on the version ordered, the connection of the device, and the configured
protection functions, only a part of the measured operating values listed in Table 6-8
is available. The residual voltage 3U0 is the e-n-voltage multiplied by √3 — if Uen is
connected — or calculated from the phase-to-ground-voltages 3U0 = UL1 + UL2 + UL3.

6-142 7SD610 Manual


C53000-G1176-C145-1
Ancillary Functions

For this the three voltage inputs phase-to-ground must be connected. Overload meas-
ured values can appear only if the overload protection was configured ([LVW.

Table 6-8 Operational measured values of the local device

Measured values primary secondary


IL1, IL2, IL3 Phase currents A A
3I0 Ground current (residual current) A A
ϕ(IL1–IL2), ϕ(IL2–IL3), Phase angle of the phase currents ° —
ϕ(IL3–IL1) towards each other
I1, I2 Positive and negative sequence A A
component currents
UL1–L2, UL2–L3, UL3–L1 Phase-to-phase voltages kV V
UL1–E, UL2–E, UL3–E Phase-to-ground voltages kV V
3U0 Displacement voltage kV V
(Residual voltage)
ϕ(UL1–UL2), ϕ(UL2– Phase angle of the phase voltages ° —
UL3), ϕ(UL3–UL1) towards each other
ϕ(UL1–IL1), ϕ(UL2–IL2), Phase angle of the phase voltages ° —
ϕ(UL3–IL3) towards the phase currents
U1, U2 Positive and negative sequence kV V
component voltages
S, P, Q Apparent, active and reactive power MVA, MW, —
MVAR
cos ϕ Power factor (abs) (abs)
f Frequency Hz Hz
ΘL1/ΘTRIP, ΘL2/ΘTRIP, Thermal value of each phase, % —
ΘL3/ΘTRIP referred to the tripping value
Θ/ΘTRIP Thermal resultant value, % —
referring to the tripping value,
calculated according to the param-
eterized method

The operational measured values are also calculated in the event of a running fault
and approximately every 0.2 s.

Differential The differential and stabilization values of the differential protection are listed in Table
Protection Values 6-9.

7SD610 Manual 6-143


C53000-G1176-C145-1
Functions

Table 6-9 Measured values of the differential protection

Measured values % referring to


IDiffL1, IDiffL2, IDiffL3 Calculated differential currents Rated operating current 1)
of the three phases
IStabL1, IStabL2, Calculated restraint currents Rated operating current 1)
IStabL3 of the three phases
1) for lines according to address  (see Section 6.1.3),
for transformers calculated from address  (see Section 6.1.3) IN = SN /(√3·UN)

Remote Measured During communication, the data of the opposite end of the protected object can also
Values be read out. The currents and voltages involved as well as phase shifts between the
local and transfer measured quantities can be displayed. This is especially helpful for
checking the correct and coherent phase allocation at both line ends and for the veri-
fication of the vector group if a power transformer is within the protected zone. Further-
more, the device address of the other device is transmitted so that all important data
of both ends are available in the substation. All possible data are listed in Table 6-10.

Table 6-10 Operational measured values transmitted from the other end and compared with
the local values

Data % referring to
Device ADR Device address of the remote device (abs)
IL1, IL2, IL3 remote Phase currents of the remote device Rated operat. current 1)
IL1, IL2, IL3 local Phase currents of the local device Rated operat. current 1)
ϕ(IL1), ϕ(IL2), ϕ(IL3) Phase angles between the remote °
and the local phase currents
UL1, UL2, UL3 remote Voltages of the remote device Rated operat. voltage/√3 2)
UL1, UL2, UL3 local Voltages of the local device Rated operat. voltage/√3 2)
ϕ(UL1), ϕ(UL2), ϕ(UL3) Phase angles between the remote °
and the local voltages
1
) for lines according to address  (see Section 6.1.3),
for transformers calculated from address  (see Section 6.1.3) IN = SN /(√3·UN)
2
) according to address  (see Section 6.1.3)

Transmission In 7SD610 the protection communication is registered in statistics. The delay times of
Statistic the information between the devices via interfaces (run and return) are measured
steadily. The values are kept stored in the Statistic folder. The availability of the trans-
mission media is also specified. The availability is indicated in %/min and %/h. This
allows the user to assess the transmission quality.

6-144 7SD610 Manual


C53000-G1176-C145-1
Ancillary Functions

“IBS-tool” The “IBS-tool” enables the user to chart on a PC-screen the currents, voltages (if con-
nected to the system) and their phase angles for both devices connected to the differ-
ential protection system. In addition to phasor diagrams showing the measured values
also numerical values, frequency and device addresses are indicated. For more de-
tails refer to Section 7.1.3.2.

6.15.3 Fault Recording

The differential protection 7SD610 is equipped with a fault recording function. The in-
stantaneous values of the measured quantities
iL1, iL2, iL3, 3 i0, uL1, uL2, uL3, 3 u0 and IdiffL1, IdiffL2, IdiffL3, IstabL1, IstabL2, IstabL3
(voltages depending on the connection) are sampled at 1 ms intervals (for a frequency
of 50 Hz) and stored in a cyclic buffer (20 samples per period). During a system fault
these data are stored over a time span that can be set (5 s at the longest for each fault
record). Up to 8 faults can be stored. The total capacity of the fault record memory is
approx. 15 s. The fault recording buffer is updated when a new fault occurs, so that
acknowledging is not necessary. Fault recording can be initiated, additionally to the
protection pickup, via the integrated operator panel, the serial operator interface and
the serial service interface.
For the differential protection system of a protected object both fault records of both
ends are synchronized by time management. This ensures that all fault records oper-
ate with exactly the same time basis. Therefore equal measured values are coincident
at both ends.
The data can be retrieved via the serial interfaces by means of a personal computer
and evaluated with the protection data processing program DIGSI ® 4 and the graphic
analysis software DIGRA 4. The latter graphically represents the data recorded during
the system fault and calculates additional information such as the impedance or RMS
values from the measured values. A selection may be made as to whether the currents
and voltages are represented as primary or secondary values. Binary signal traces
(marks) of particular events e.g. “fault detection”, “tripping” are also represented.
If the device has a serial system interface, the fault recording data can be passed on
to a central device via this interface. The evaluation of the data is done by applicable
programs in the central device. Currents and voltages are referred to their maximum
values, scaled to their rated values and prepared for graphic representation. In addi-
tion, internal events are recorded as binary traces (marks), e.g. “fault detection”, “trip-
ping”.
In the event of transfer to a central device, the request for data transfer can be exe-
cuted automatically and can be selected to take place after each fault detection by the
protection, or only after a trip.

7SD610 Manual 6-145


C53000-G1176-C145-1
Functions

6.15.4 Setting the Function Parameters

Data Storage for The configuration of the fault recording memory is done in the sub-menu 2VFLOOR
Fault Recording JUDSKLF)DXOW5HFRUGLQJVof the menu 6HWWLQJV. A distinction is made be-
tween the reference instant and the storage criterion of the fault recording (address
 :$9()250&$3785(). Normally the reference instant is the occurrence of device
fault detection, i.e. the pickup of any protection function is allocated with the time
stamp 0. The pickup can also be the storage criterion (6DYHZ3LFNXS) or the de-
vice trip command (6DYHZ75,3) can be the storage criterion. The device trip com-
mand can also be used as reference time (6WDUWZ75,3); in this case it is also the
storage criterion.
A fault event starts with the fault detection of any protection function and ends with the
reset of the last fault detection. Usually this is also the extent of a fault recording (ad-
dress  6&23(2) :$9()250'$7$ = )DXOWHYHQW). If automatic reclosure is
implemented, the entire system disturbance — possibly with several reclose attempts
— up to the ultimate fault clearance can be stored (address  6&23(2) :$9(
)250'$7$ = 3RZHU6\VWHPIDXOW). This facilitates the representation of the en-
tire system fault history, but also consumes storage capacity during the auto-reclosure
dead time(s).
The actual storage time encompasses the pre-trigger time 35(75,*7,0( (ad-
dress ) ahead of the reference instant, the normal recording time and the post-fault
time 32675(&7,0( (address ) after the storage criterion has reset. The max-
imum permissible storage period per fault recording 0$;/(1*7+ is set in address
. A maximum recording time of 5 s is available per fault recording. In total up to
8 fault records with a total recording time of max. 15 s can be stored.
The fault recording can also be triggered via a binary input, via the keypad on the front
of the device or with a PC via the operation or service interface. The storage is then
dynamically triggered. The length of the fault recording is set in address  %LQ,Q
&$377,0( (maximum length however is 0$;/(1*7+, address  . The pre-
and post-fault times are additive. If the time for the binary input is set to ∞, the duration
of the storage is as long as the binary input is initiated (static), the maximum length
however still is 0$;/(1*7+ (address ).

6-146 7SD610 Manual


C53000-G1176-C145-1
Ancillary Functions

6.15.5 Setting Overview

Addr. Setting Title Setting Options Default Setting Comments


402A WAVEFORMTRIGGER Save with Pickup Save with Pickup Waveform Capture
Save with TRIP
Start with TRIP

403A WAVEFORM DATA Fault event Fault event Scope of Waveform Data
Power System fault

410 MAX. LENGTH 0.30..5.00 sec 1.00 sec Max. length of a Waveform Capture
Record

411 PRE. TRIG. TIME 0.05..0.50 sec 0.10 sec Captured Waveform Prior to Trigger

412 POST REC. TIME 0.05..0.50 sec 0.10 sec Captured Waveform after Event

415 BinIn CAPT.TIME 0.10..5.00 sec; ∞ 0.50 sec Capture Time via Binary Input

6.15.6 Information Overview

F.No. Alarm Comments


4 >Trig.Wave.Cap. >Trigger Waveform Capture

203 Wave. deleted Waveform data deleted

FltRecSta Fault Recording Start

7SD610 Manual 6-147


C53000-G1176-C145-1
Functions

6.16 Processing of Commands

General In addition to the protective functions described so far, a control command process is
integrated in the SIPROTEC® 7SD610 to coordinate the operation of circuit breakers
and other equipment in the power system. Control commands can originate from four
command sources:
− Local operation using the keypad on the local user interface of the device
− Local or remote operation using DIGSI ® 4,
− Remote operation via system interface IEC (e.g. SICAM),
− Automatic functions (e.g. using a binary input).
The number of switchgear devices that can be controlled is basically limited by the
number of available and required binary inputs and outputs. For the output of control
commands it has be ensured that all the required binary inputs and outputs are con-
figured and provided with the correct properties (see also Subsection 5.2.4 under “Bi-
nary Outputs for Switching Devices”).
If specific interlocking conditions are needed for the execution of commands, the user
can program the device with bay interlocking by means of the user-defined logic func-
tions (CFC) (see Section 5.3).
The “Control of Switchgear” is described in Section 7.4.

6.16.1 Types of Commands

Two types of commands can be issued with this device:


− Control commands,
− Internal / pseudo commands.

Control Commands These commands operate binary outputs and change the power system status:
− Commands for the operation of circuit breakers (asynchronous) as well as com-
mands for the control of isolators and earth switches,
− Step commands, e.g. for raising and lowering transformer taps,
− Tap change commands with configurable time settings (Petersen coils).

Internal / Pseudo These commands do not directly operate binary outputs. They serve to initiate internal
Commands functions, simulate or acknowledge changes of state.
− Manual entry execution to change the feedback indication of plant such as the sta-
tus and switching condition, for example in the case of the physical connection to
the auxiliary contacts is not available. A manual entry execution is captured and can
be displayed accordingly.

6-148 7SD610 Manual


C53000-G1176-C145-1
Processing of Commands

− Additionally, tagging commands can be issued to establish internal settings, such


as switching authority (remote / local), parameter set changeover, data transmis-
sion inhibit and metering counter reset or initialization.
− Acknowledgment and resetting commands for setting and resetting internal buffers.
− Status information commands for setting / deactivating the “information status” for
the information value of an object:
− Controlling activation of binary input status,
− Blocking binary outputs.

6.16.2 Steps in the Command Sequence

Safety mechanisms in the command sequence ensure that a command can only be
released after a thorough check of preset criteria has been successfully concluded.
Additionally, user-defined interlocking conditions can be configured separately for
each device. The actual execution of the command is also monitored afterwards. The
entire sequence of a command is described briefly in the following:

Check Sequence • Command entry (e.g. using the keypad on the local user interface of the device)
− Check password → access rights;
− Check switching mode (interlocking activated/deactivated) → selection of deac-
tivated interlocking status.
• User configurable interlocking checks that can be selected for each command
− Switching authority (local, remote),
− Switching direction control (target state = present state),
− Zone controlled/bay interlocking (logic using CFC),
− System interlocking (centrally via SICAM),
− Double operation (interlocking against parallel switching operation),
− Protection blocking (blocking of switching operations by protective functions).
• Fixed commands
− Timeout monitoring (time between command initiation and the beginning of the
execution can be controlled),
− Configuration in process (if setting modification is in process, commands are re-
jected or delayed),
− Equipment not present at output (if controllable equipment is not assigned to a
binary output, then the command is denied),
− Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is de-
nied),
− Component hardware malfunction,

7SD610 Manual 6-149


C53000-G1176-C145-1
Functions

− Command in progress (only one command can be processed at a time for each
circuit breaker or switch),
− 1- out of -n-check (for schemes with multiple assignments, such as common
ground, it is checked whether a command has already been initiated for the af-
fected output relay).

Monitoring the − Interruption of a command because of a cancel command,


Command Execu-
− Running time monitor (feedback message monitoring time).
tion

6.16.3 Interlocking

Interlocking is executed by the user-defined logic (CFC). The interlocking checks of a


SICAM/SIPROTEC®-system are classified into:
• System interlocking checked by a central control system (for a busbar)
• Zone controlled/bay interlocking checked in the bay device (for the feeder)
System interlocking relies on the system data base in the central control system. Zone
controlled/bay interlocking relies on the status of the circuit breaker and other switches
that are connected to the relay.
The extent of the interlocking checks is determined by the configuration and interlock-
ing logic of the relay.
Switchgear which is subject to system interlocking in the central control system is
marked with a parameter (in the routing matrix).
For all commands the user can select the operation mode with interlocking (normal
mode) or without interlocking (test mode):
− for local commands by reprogramming the settings with password check,
− for automatic commands via command processing with CFC,
− for local / remote commands by an additional interlocking command via Profibus.

6.16.3.1 Interlocked/Non-Interlocked Switching

The command checks that can be selected for the SIPROTEC®-relays are also re-
ferred to as “standard interlocking”. These checks can be activated (interlocked) or de-
activated (non interlocked) via DIGSI® 4.
Deactivated interlock switching means the configured interlocking conditions are not
checked in the relay.
Interlocked switching means that all configured interlocking conditions are checked in
the command check. If a condition could not be fulfilled, the command will be rejected
by a message with a minus added to it (e.g. “CO-”), immediately followed by an oper-

6-150 7SD610 Manual


C53000-G1176-C145-1
Processing of Commands

ation response information. Table 6-11 shows some types of commands and messag-
es. For the device the messages designated with *) are displayed in the event logs, for
DIGSI® 4 they appear in spontaneous messages.

Table 6-11 Types of command and messages


Type of command Abbrev. Message
Control issued CO CO+/–
Manual tagging (positive / negative) MT MT+/–
Input blocking IB IB+/– *)
Output blocking OB OB+/– *)
Control abortion CA CA+/–

The “plus” appearing in the message is a confirmation of the command execution: the
command execution was as expected, in other words positive. The “minus” is a neg-
ative confirmation, the command was rejected. Figure 6-69 shows the messages re-
lating to command execution and operation response information for a successful op-
eration of the circuit breaker.
The check of interlocking can be programmed separately for all switching devices and
tags that were set with a tagging command. Other internal commands such as manual
entry or abort are not checked, i.e. carried out independent of the interlocking.

(9(17/2*


4&2FORVH


4)%FORVH
Figure 6-69 Example of a message when closing the circuit breaker Q0

Standard The standard interlocking includes the checks for each device which were set during
Interlocking the configuration of inputs and outputs, see Subsection 5.2.4 under “Binary Outputs
for Switching Devices”.
An overview for processing the interlocking conditions in the relay is shown by Figure
6-70.

7SD610 Manual 6-151


C53000-G1176-C145-1
Functions

Device with Source Switching Authority Switching Mode


of Command =
On/Off
LOCAL
& Local
SAS REMOTE1),
Local &
DIGSI

AUTO
&
Remote &
Switching Authority
(Local/Remote)
& DIGSI

Switching Authority DIGSI


DIGSI or
Remote
&

Switching Mode Non-Interlocked


Local
or SCHEDULED=ACT .y/n
&
Switching Mode
Remote
Interlocked
&
or
SCHEDULED=ACT.y/n
System Interlock.*)y/n Command
Field Interlocking y/n or Output
feedback Indication Protection Blockingy/n to Relay
On/Off Double Oper. Blocky/n
SW. Auth. LOCA> y/n
Protection Blocking Sw. Auth. REMOTEy/n
52 Close
52 Open

Event *) Starting With Version 4.2


Condition

1)
Source REMOTE also includes SAS.
LOCALCommand via substation controller.
REMOTECommand via telecontrol system to substation controller and from substation con-
troller to device.
Figure 6-70 Standard Interlocking Arrangements

The display shows the configured interlocking reasons. The are marked by letters ex-
plained in the following table 6-12.

Table 6-12 Interlocking commands

Interlocking commands Abbrev. Message


Control authorization L L
System interlock S S

6-152 7SD610 Manual


C53000-G1176-C145-1
Processing of Commands

Interlocking commands Abbrev. Message


Zone controlled Z Z
Target state = present state P P
(check switch position)
Block by protection B B

Figure 6-71 shows all interlocking conditions (which usually appear in the display of
the device) for three switchgear items with the relevant abbreviations explained in
table 6-12. All parameterized interlocking conditions are indicated
(see Figure 6-71).

,QWHUORFNLQJ

4&ORVH2SHQ6²=3%
4&ORVH2SHQ6²=3%

4&ORVH2SHQ6²=3%

Figure 6-71 Example of configured interlocking conditions

Control Logic using For zone controlled/field interlocking, control logic can be programmed, using the
CFC CFC. Via specific release conditions the information “released” or “bay interlocked”
are available.

6.16.4 Recording and Acknowledgement of Commands

During the processing of the commands, independent of the further message routing
and processing, command and process feedback information are sent to the message
processing centre. These messages contain message cause indication. The messag-
es are entered in the event list.

Acknowledgement All messages which relate to commands that were issued from the device front “Com-
of Commands to mand Issued = Local” are transformed into a corresponding response and shown in
the Device Front the display of the device.

Acknowledgement The messages which relate to commands with the origin “Command Issued = Local/
of Commands to Remote/DIGSI” must be send independent of the routing (configuration on the serial
Local/Remote/Digsi digital interface) to the initiating point.
The acknowledgement of commands is therefore not executed by a response indica-
tion as it is done with the local command but by ordinary command and feedback in-
formation recording.

7SD610 Manual 6-153


C53000-G1176-C145-1
Functions

Monitoring of Feed- The processing of commands monitors the command execution and timing of feed-
back Information back information for all commands. At the same time the command is sent, the moni-
toring time is started (monitoring of the command execution). This time controls
whether the device achieves the required final result within the monitoring time. The
monitoring time is stopped as soon as the feedback information arrives. If no feedback
information arrives, a response “Timeout command monitoring time” appears and the
process is terminated.
Commands and information feedback are also recorded in the event list. Normally the
execution of a command is terminated as soon as the feedback information (FB+) of
the relevant switchgear arrives or, in case of commands without process feedback in-
formation, the command output resets.
The “plus” appearing in a feedback information confirms that the command was suc-
cessful, the command was as expected, in other words positive. The “minus” is a neg-
ative confirmation and means that the command was not fulfilled as expected.

Command Output The command types needed for tripping and closing of the switchgear are described
and Switching in Section 5.2 and Subsection 5.2.1.
Relays

6.16.5 Information Overview

F.No. Alarm Comments


Cntrl Auth Control Authority

ModeLOCAL Control mode LOCAL

ModeREMOTE Control mode REMOTE

6-154 7SD610 Manual


C53000-G1176-C145-1
Control During Operation 7
This chapter describes interaction possibilities with the SIPROTEC® 7SD610 device
during operation. The information that can be obtained and the procedure for retriev-
ing the data are discussed. Methods of influencing the device functions during opera-
tion and controlling the system using the device are covered.
Detailed knowledge about the device functions is not required at this point. However,
the configuration of the device covered in Chapter 5 — especially configuration of the
input and output functions — is assumed to have already taken place.
Please note that the examples shown are general and may differ in wording or details
from the device at hand. Also, depending on the model variant, some of the functions
discussed below may not be available.

7.1 Read-out of Information 7-2


7.2 Control of Device Functions 7-28
7.3 Circuit Breaker Test Function 7-41
7.4 Control of Switchgear 7-45

7SD610 Manual 7-1


C53000-G1176-C145-1
Control During Operation

7.1 Read-out of Information

General The device provides a great deal of information that can be obtained on-site or from
data transfer:
• Messages,
• Operating measurement and metered values,
• Waveform data in oscillographic fault records.
This information is individually discussed below. Methods for viewing, retrieving, ac-
knowledging, and storing this information on a PC are also explained.

7.1.1 Messages

7.1.1.1 Output of Messages

Messages provide operating information about the power system, the device, and the
measurements. Other messages give an overview of important events such a network
fault and the operation of device functions. The information provided is useful in
checking overall operation of the device during testing and commissioning.
Password entry is not required to read messages.
The messages generated in the device can be presented in various ways:
• Display using light-emitting diodes (LEDs) on the front of the device,
• Operation of output relays connected to external signalling equipment,
• Display in the LCD on the front of the device,
• Display on the screen of a PC running the DIGSI® 4 program, connected to the op-
erating or service interface of the device,
• Transfer to a master station using one of the serial system interfaces (if available).

Light-Emitting The green light-emitting diode with the label “RUN” lights continuously during normal
Diodes operation.
The red LED with the label “ERROR” indicates that the processor system has recog-
nized an internal problem. If this LED lights up, then the device is not operational.
Chapter 9 discusses steps to take if a failure occurs in the device.
The other LEDs on the front of the device display the messages in accordance with
the configuration, as discussed in Chapter 5. The description of each LED illumination
should then be indicated on the label strips.
If the messages for the LEDs are latched, then the memory can be reset with the LED
key LED . This key simultaneously serves as a functional check for all of the LEDs ex-
cept the “RUN” and “ERROR” LEDs. While the key is pressed, all of these LEDs must
light.

7-2 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

LEDs that display a condition should light for as long as the condition is maintained.
The LED action is therefore generally not latched. Of course, these LEDs are also in-
cluded in the function check with the LED key LED .

Output Relays Indications can be configured to output relays for external indication (e.g. annunciator,
sequence-of-events recorder, RTU, etc), and operate like LEDs. See also Chapter 5
for details.

Front Panel To retrieve messages using the front panel:


First press the 0(18 key MENU. The 0$,10(18 appears. The first menu item $QQXQ
FLDWLRQ) is marked.
All menus and message lists begin with a title. The number in the upper right corner
of the display indicates presently selected menu entry or message, and, behind the
slash, the total number of menu entries or messages (see Figure 7-1, each first line).
Press the key to go to the $1181&,$7,21 sub-menu, as shown in Figure 7-1. In
this menu the messages can be reached by entering the associated selection number,
or by selecting the desired entry using the and keys and moving further with the
key. This procedure is described in more detail below.

0$,10(18

!$QQXQFLDWLRQ²!
0HDVXUHPHQW²! $1181&,$7,21

!(YHQW/RJ²!
7ULS/RJ²!
Figure 7-1 Selection of messages on the operator control panel — example

PC–Interfaces A personal computer running the DIGSI® 4 program can be connected to the operat-
ing interface on the front of the device to retrieve the messages. A PC can also be con-
nected to the service interface on the back of the device. This connection typically ap-
plies when the PC is hard-wired with several devices, using a data bus (station com-
puter) or modem.
Details about the operation of DIGSI® 4 are contained in the “DIGSI® 4 Device Oper-
ation” handbook, order no. E50417-H1176-C097.

7SD610 Manual 7-3


C53000-G1176-C145-1
Control During Operation

Figure 7-2 Function selection screen in DIGSI® 4 — example

If the DIGSI® 4 2QOLQH directory is opened with a double-click, the operating func-
tions for the device appear in the navigation window (Figure 7-2). By double clicking
on $QQXQFLDWLRQ, the tree structure expands and shows the individual message
groups. The groups are described in detail below.

System (SCADA) The system interface (if available) is generally hardwired and transfers all device in-
Interface formation to a master station via data cable or optical fibre cable.

Division of The messages are categorized as follows:


Messages
• Event Log: these are operating messages that can occur during the operation of the
device. They include information about the status of device functions, measurement
data, system data, and similar information.
• Trip Log: these are fault messages from the last eight network faults that were proc-
essed by the device.
• Switching statistics; these messages count the trip commands initiated by the de-
vice, close commands, values of accumulated circuit currents and interrupted cur-
rents.
• Erasing and setting the messages named above.
A complete list of all message and output functions that can be generated by the de-
vice, with the associated information number (FNo), can be found in the Appendix.
The lists also indicate where each message can be sent. The lists are based on a
SIPROTEC® 4 device with the maximum complement of functions. If functions are not
present in the specific version of the device, or if they are set as “'LVDEOHG” in device
configuration, then the associated messages cannot appear.

7-4 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

7.1.1.2 Event Log (Operating Messages)

Operating messages contain information that the device generates during operation
and about the operation. Up to 200 operating messages are stored in chronological
order in the device. New messages are added at the end of the list. If the memory has
been exceeded, then the oldest message is overwritten for each new message.
Faults in the power system are indicated with “1HWZRUN)DXOW” and the present fault
number. The fault messages (7ULS/RJ) contain details about the history of faults.
This topic is discussed in Subsection 7.1.1.3.
All predefined operating messages are listed and explained in a table in Appendix A.7.
In a specific case, of course, only the appropriate messages appear in the display. The
appendix also shows whether the message is only issued as “ON” (to indicate an
event), or as “ON” and “OFF” (to designate the beginning and end of a condition).

From the With the device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front The first menu item ($QQXQFLDWLRQ) is marked.
Press the key to enter the $1181&,$7,21 menu (see Figure 7-1).
Here, select the menu item (YHQW/RJ (already marked). The (9(17/2* table ap-
pears.
If no messages are present, then the text “OLVWLVHPSW\” appears. Otherwise im-
portant events and changes in conditions are listed in chronological order (see Figure
7-3 as an example). Upon entering the menu, the newest (last) message is displayed
at first. The applicable date and time are noted in the display line directly above the
message. If the memory for the operating messages is not full, then the end of the en-
tries is indicated by “(1'”.

(9(17/2*


5HVHW/('21

Figure 7-3 Example of an operating message in the operating field of the device

The [ and keys can be used to move up and down in the Event Log.
Press the MENU key to return to the 0$,10(18.

:
From PC with Click on $QQXQFLDWLRQ. The options appear in the data window (Figure 7-4).
DIGSI® 4
Double click on the desired message group in the data window, in this case (YHQW
/RJ. A date and time appear in the data window as shown in Figure 7-4.
Double click on the date and time and the contents of the message group are dis-
played in another window.

7SD610 Manual 7-5


C53000-G1176-C145-1
Control During Operation

Figure 7-4 Selection of operational messages in DIGSI® 4 — example

Figure 7-5 Example of operational messages in DIGSI® 4

7.1.1.3 Trip Log (Fault Messages)

Spontaneous The spontaneous messages appear automatically in the display, after a general pick-
Messages up of the device. The most important data about a fault can be viewed on the device
front in the sequence shown in Figure 7-6.
The spontaneous messages can be acknowledged by pressing the LED key. After ac-
knowledgement, the default display is shown.

7-6 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

'LII3LFNXS/( Protection function that had picked up first, e.g.


differencial protection, with phase information;
387LPHPV Elapsed time from pick-up until drop-off;
75,37LPHPV Elapsed time from pick-up until the first trip com-
mand of a protection function;
differential protection mostly 0

Figure 7-6 Display of spontaneous messages in the display

Retrieved The messages for the last eight network faults can be retrieved. The definition of a net-
messages work fault is such that the time period from fault detection up to final clearing of the
system fault is considered to be one network fault. If auto-reclosure occurs, then the
network fault ends after the last reclosing shot, which means after a successful or final-
unsuccessful reclosing. Therefore, the entire clearing process, including the reclosing
attempt (or all reclosing attempts), occupies only one fault log buffer. Within a network
fault, several fault events can occur (from the first pick-up of a protective function to
the last drop-out of a protective function). Without auto-reclosing, every fault event is
a network fault.
Altogether up to 600 indications can be stored. Oldest data are erased for newest data
when the buffer is full.
All available indications are displayed and explained in the Appendix A.7. In a specific
case, of course, only the applicable messages appear on the display.

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front The first menu item ($QQXQFLDWLRQ) is marked.
Press the key to enter the $1181&,$7,21 sub-menu (see Figure 7-1).
Using the key, select the sub-menu item 7ULS/RJ and move to the Trip Log sub-
menu using the key. The 75,3/2* selection appears.
In this sub-menu, the indications for the last 8 network faults can be selected, again
using the and keys. See the example in Figure 7-7.
If no messages are present for a fault, then entrance is denied and “/LVW(PSW\” is
displayed.
The messages within a fault record are listed in chronological order and numbered,
from the oldest to the newest.
The inception of a fault is identified with the date and time in hours, minutes, and sec-
onds (resolution to ms). See the example in Figure 7-7.
The individual messages that are associated with the fault are tagged with a relative
time. At least one complete individual message always appears in the display.

75,3/2*

!/DVW)DXOW²! /$67)$8/7
!QG/DVW)DXOW²! 

etc 1HWZRUN)DXOW21

Figure 7-7 Example of fault messages in the front display

7SD610 Manual 7-7


C53000-G1176-C145-1
Control During Operation

Use the and keys to move up and down in the fault messages.
Use the key to move back into the 75,3/2* level; or press the MENU key to go back
to the 0$,10(18.

:
From PC with Click on $QQXQFLDWLRQ. The options appear in the data window (see Figure 7-2).
DIGSI® 4
Double click on the desired message group in the data window, in this case the 7ULS
/RJ. A list appears in the data window, as shown in Figure 7-8.
By double clicking on an entry in the list view, the associated contents of the network
fault is displayed in another window. The entries are chronologically listed with the
newest message appearing first.

Figure 7-8 Selection of fault messages in DIGSI® 4 — example

7-8 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

Figure 7-9 Example of fault messages in DIGSI® 4

7.1.1.4 Saving and Erasing the Messages

Normally, erasing the messages is not necessary because the oldest messages are
automatically erased when new events are entered, if the memory is full at the time.
However, erasure of the stored messages may be useful, for instance, after revision
of the plant, so that in the future the memory only contains information about actual
events. Erasing the memory takes place separately for each of the message groups.

Note:
When the Trip Log (fault messages) is erased, then the fault records are erased, too,
and all corresponding counters are set to zero. If, however, a fault record is erased (cf.
Sub-section 7.1.4), the fault messages are unaffected.

From the If erasure is desired, first press the MENU key. The 0$,10(18 appears. The first menu
Device Front item $QQXQFLDWLRQ is marked.
Press the key to enter the $1181&,$7,21 menu (see Figure 7-1).
Using the key, select the item 6HW5HVHW, and switch to the sub-menu using the
key.
Here, select the message group to be erased using the key, and then press the
ENTER key. See Figure 7-10 as an example.

7SD610 Manual 7-9


C53000-G1176-C145-1
Control During Operation

Password No. 5 (for setting changes) is required at this point. After entering the pass-
word and confirming with the ENTER key, the safety question “$UH\RXVXUH?” ap-
pears. The response “<(6” is the default (Figure 7-10). Confirm with the ENTER key, if
the message group should really be erased. If the message group should not be
erased, press the key so that the response “12” is highlighted, and confirm this an-
swer with the ENTER key. Before confirming with the ENTER key, the responses can be tog-
gled between “<(6” and “12” using the and keys. Alternatively, the ESC key can
be pressed to cancel the erasure procedure.

6(75(6(7 Select the associated message group or press


 the associated number key to select the mes-
!(YHQW/RJ
!7ULS/RJ sages to be erased.

Etc

3:6HWWLQJV" Enter Password No. 5 (for setting change) and


ENTER
  confirm with ENTER

Confirm “<HV” with the ENTER key and complete


$UH\RXVXUH" the erasing of the selected messages, or
!<HV1R switch to “1R” with the key and cancel the
erasure with the ENTER key.
Figure 7-10 Erasing messages from the front panel

:
From PC with Operating the device from the PC via DIGSI 4 enables the user to save the above de-
DIGSI® 4 scribed messages on your hard disc before clearing them from the device. Proceed
as if reading out the messages. However, instead of opening the information list by
making a double-click on the event group, select the option File > Save in the menu of
the DIGSI window. Then DIGSI automatically creates a directory for the event group.
For more details also refer to the instruction manual of DIGSI 4, ordering no. E50417-
H1100-C097, Section 9.4.
If all event groups required are stored in the PC, they can be deleted from the device
- as before described - via the front panel.
Naturally all messages stored via DIGSI 4 can be deleted from your hard disc like any
other object.

7.1.1.5 General Interrogation

:
From PC with The present condition of a SIPROTEC® device can be examined by using DIGSI® 4
DIGSI® 4 to view the contents of the “General Interrogation” annunciation.
The messages are found by double-clicking on $QQXQFLDWLRQ(see Figure 7-2),
double-clicking on *HQHUDO,QWHUURJDWLRQ, and double-clicking on the date and
time that appear in the right window. All of the messages that are needed for a general
interrogation are shown along with the actual values and states.

7-10 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

7.1.1.6 Spontaneous Messages

:
From PC with The spontaneous messages that can be displayed via DIGSI® 4 are refreshed imme-
DIGSI® 4 diately.
Find the message groups by clicking on $QQXQFLDWLRQ (Figure 7-2).
Double click 6SRQWDQHRXV$QQXQFLDWLRQ in the data window. The date and time
appear in the data window. By double clicking on them, the Spontaneous Annunciation
window opens, as shown in the following figure. Each entering message appears im-
mediately, without requiring that an update be initiated.

Figure 7-11 Spontaneous annunciation window — example

7.1.2 Switching Statistics

The messages in switching statistics are counters for the accumulation of interrupted
currents by each of the breaker poles, the number of trips issued by the device to the
breaker. The interrupted currents are in primary terms.
Switching statistics can be viewed on the LCD of the device, or on a PC running
DIGSI® 4 and connected to the operating or service interface.
A password is not required to read switching statistics; however, a password is re-
quired to change or delete the statistics.
In 7SD610 the statistics register the data of the protection communication. The trans-
mission time of the information from device to device via protection data interfaces
(coming and going) is measured steadily and registered in the folder “Statistic”. The
availability of the means of transmission is also indicated. The availability is indicated
in %/min and %/h. This enables the user to assess the transmission quality.

7SD610 Manual 7-11


C53000-G1176-C145-1
Control During Operation

7.1.2.1 Viewing the Switching Statistics

For each trip command initiated by a protective element of the device, the magnitude
of interrupted current for each circuit breaker pole is determined and stored. The cur-
rent magnitudes are added to previously interrupted currents, and the accumulated
values are stored.

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front The first menu item $QQXQFLDWLRQ is marked.
Press the key to enter the $1181&,$7,21 sub-menu (see Figure 7-1).
Use the key to select the item 6WDWLVWLF, and switch to the list of statistics values
using the key. The 67$7,67,& list appears. See Figure 7-12.

67$7,67,&6

Σ ,/ N$
Σ ,/ N$
Etc.
Figure 7-12 Switching statistics viewed from the front display — example

:
From PC with Under $QQXQFLDWLRQ (Figure 7-2), the switching statistics can be found by double
DIGSI® 4 clicking. Double click on 6WDWLVWLF. The contents of the statistic counters is dis-
played in another window. See Figure 7-13.

Figure 7-13 List of statistic values in DIGSI® 4 — example

7-12 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

7.1.2.2 Resetting and Setting the Switching Statistics

The memories and counters for switching statistics are secured against a loss of pow-
er supply voltage. The values can, however, be set to zero, or to any desired value
within certain setting limits.

From the In the 67$7,67,& (see previous sub-section) sub-menu (see previous sub-section),
Device Front select the value to be set by using the key, and then press the ENTER key. See Figure
7-14 for an example of changing the trip counter. After a password is entered, the cur-
sor blinks and the number value is highlighted in a box. The number can be overwritten
using the number keys. If the new value is outside of the allowable range, either above
or below, then the maximum or minimum limit value appears at the bottom edge of the
screen. Confirm the change with the ENTER key.

67$7,67,&6

∑,/ N$
7ULS&RXQW ! ENTER
7ULS&RXQW 
2SHU+UV 

0D[ 2147483648

Figure 7-14 Setting statistics values from the device front — example

:
From PC with In the 6WDWLVWLF window (see previous sub-section), mark the value that is to be set.
DIGSI® 4 With the right mouse button, open a context menu and select 6HW. See Figure 7-15.
After the password for individual settings is entered, the previous value in the window
can be overwritten.

Figure 7-15 Setting statistic values in DIGSI® 4 — example

7SD610 Manual 7-13


C53000-G1176-C145-1
Control During Operation

7.1.3 Measured Values

Operating measured values are determined in the background by the processor sys-
tem. They can be called up at the front of the device, read out via the operating inter-
face using a PC with DIGSI® 4, or transferred to a central master station via the sys-
tem interface (if available).
No password entry is required to view the measured values. The values are updated
every few seconds.
Most measured values can be displayed in primary quantities, secondary quantities,
and percentages based on nominal values. A precondition for correct display is that
the nominal values be correctly set in the power system data.

7.1.3.1 Measured Values

Default Display Under normal conditions, the so-called default display is the default image in the relay
display. It shows measured values of the protected equipment. Depending on the relay
type, a number of predefined basic displays are available. Using the and keys,
one of the displayed images may be selected (see example in Figure7-16).

 , 8/( 8//
/
/
/   

Figure 7-16 Default displays — example

Read-out of In the 7SD610 with maximum functionality the measured values as shown in Table 7-
Measured Values 1 to 7-3 are available.
The displacement voltage 3U0 is either measured directly (3U0 = √3·Uen, if Uen is con-
nected to the voltage input U4) or calculated (from 3U0 = |UL1-E + UL2-E + UL3-E|).
The power measurements P, Q are positive, if real power or inductive reactive power
flows into the protected object. This is assuming that this direction has been parame-
terized as “forward”.
The sign of the power factor cos ϕ corresponds to the sign of the real power.
In addition to those measured values listed in the table, it is possible to retrieve user
defined measurement, metering and set points, if these were generated during the
configuration of the device according to Section 5.2 and/or 5.3.
The differential and stabilization values of the differential protection according to Table
7-2 can also be read out.
Remote measured values come from the remote end of the protected object. Currents,
voltages and the phase displacement between local and remote measured values can
be viewed. Furthermore the address of the partner device is transmitted to the substa-

7-14 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

tion. Thus all important data are available in one place. The remote measured values
are listed in Table 7-3.

Table 7-1 Operational measured values of the local device

Measured values primary secondary


IL1, IL2, IL3 phase currents A A
3I0 earth currents A A
ϕ(IL1–IL2), ϕ(IL2–IL3), phase angles of phase currents ° —
ϕ(IL3–IL1) in relation
I1, I2 positive and negative sequence A A
currents
UL1–L2, UL2–L3, UL3–L1 line voltages kV V
UL1–E, UL2–E, UL3–E phase–earth voltages kV V
3U0 displacement voltage kV V
ϕ(UL1–UL2), ϕ(UL2–UL3), phase angles of phase voltages in ° —
ϕ(UL3–UL1) relation
ϕ(UL1–IL1), ϕ(UL2–IL2), phase angles of phase voltages in ° —
ϕ(UL3–IL3) relation to phase currents
U1, U2 positive and negative sequence kV V
voltages
S, P, Q apparent, real, and reactive power MVA, MW, —
MVAR
cos ϕ power factor (abs) (abs)
f frequency Hz Hz
ΘL1/Θtrip, ΘL2/Θtrip, thermal value of each line % —
ΘL3/Θtrip related to trip value
Θ/Θtrip thermal value, % —
related to trip value, calculated
according to the configured method

Table 7-2 Measured values of the differential protection

Measured values % referred to


IDiffL1, IDiffL2, IDiffL3 calculated differential currents of the operational nominal
three lines current 1)
IStabL1, IStabL2, IStabL3 calculated stabilization currents operational nominal
of the three lines current 1)
1
) for lines acc. to address  (refer to Subsection 6.1.3),
for transformers acc. to address  (refer to Subsection 6.1.3) IN = SN /(√3·UN)

7SD610 Manual 7-15


C53000-G1176-C145-1
Control During Operation

Table 7-3 Operating measured values transmitted from the other end in comparison with
the local operating measured values

Data % referred to
Device ADR device address of the remote device (absolute)
IL1, IL2, IL3 remote phase currents of the remote device operating nominal current 1)
IL1, IL2, IL3 local phase currents of the local device operating nominal current 1)
ϕ(IL1), ϕ(IL2), ϕ(IL3) phase angles between remote and °
local phase currents
UL1, UL2, UL3 remote voltages of remote device operating nominal voltage /√3 2)
UL1, UL2, UL3 local voltages of local device operating nominal voltage / √3 2)
ϕ(UL1), ϕ(UL2), ϕ(UL3) phase angles between remote and °
local voltages
1
) for lines acc. to address  (refer to Subsection 6.1.3),
for transformers acc. to address  (refer to Subsection 6.1.3) IN = SN /(√3·UN)
2
) acc. to address  (refer to Subsection 6.1.3)

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of meas-
ured values using the key. The 0($685(0(17 selection appears. See figure 7-17.

0$,10(18

$QQXQFLDWLRQ²!
!0HDVXUHPHQW²!
0($685(0(17

!2SHUDWLRQSUL
!2SHUDWLRQVHF
Etc.

Figure 7-17 Selection of measured values on the front — example

The measured values are divided into the following groups:


01 2SHUDWLRQSUL Operating measured values, primary.
11 2SHUDWLRQVHF Operating measured values, secondary.
21 3HUFHQW Operating measured values, in percent of nominal quanti-
ties.
51 8VHU'HILQHG Measured values that are defined by the user during initial
setting of the device (see Section 5.3).
61 6HW3RLQWV Impulse counter generated by the user defined logic CFC
(according to section 5.3).

7-16 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

71 6HWSRLQWV 09 Threshold values generated by the user defined logic CFC


(according to section 5.3).
If a measured value is not available, then instead of the measured value, 3 dots ap-
pear. If the value is undefined (e.g., cos ϕ, when no current is flowing), then “–––” ap-
pears (3 horizontal bars). If a measured value overruns, then “” (3 asterisks) is
displayed.
Use the key to select the measured value group that has the values desired, and
switch to the display of this group with the key. Figure 7-18 shows an example for
the display of operating measured values.

0($685(0(17

!2SHUDWLRQSUL 23(5$7,2135,
!2SHUDWLRQVHF 
!,/ $
Etc. !,/ $

Etc.

Figure 7-18 Viewing operating measured values on the front display

Move up and down in the table of measured value groups using the and keys.
Use the key to return to the 0($685(0(17 sub-menu. Use the MENU key to return to
the 0$,10(18.

:
From PC with The measured value groups are found under Measurement (Figure 7-2) with a double
DIGSI® 4 click, as shown in Figure 7-19, left.

Figure 7-19 Measurement window in DIGSI® 4

7SD610 Manual 7-17


C53000-G1176-C145-1
Control During Operation

The measured values are divided into the following groups:


• 3ULPDU\ ORFDO with
2SHUDWLRQDOYDOXHVSULPDU\,
• 6HFRQGDU\ ORFDO with
2SHUDWLRQDOYDOXHVVHFRQGDU\,
• 5DWHGLQ ORFDOUHPRWH with
'LIIHUHQWLDODQ5HVWUDLQW&XUUHQW
$QJOHV
0HDVXUHPHQWVIURPUHOD\
0HDVXUHPHQWVIURPUHOD\,
related to nominal operational values.
• 2WKHUV with
7KHUPDORYHUORDGYDOXHV,
8VHUGHILQHGPHDVXUHGYDOXHV,
8VHUGHILQHGFRXQWHU,
6HWSRLQWYDOXHRIPHDVXUHGYDOXH,
i.o.w. only such values that were generated in the configuration (according to Sec-
tion 5.2) and/or with the user definable logic CFC (according to Section 5.3).
If a measured value is not available, then instead of the measured value, 3 dots ap-
pear. If the value is undefined (e.g., cos ϕ, when no current is flowing), then “–––” ap-
pears (3 horizontal bars). If the measured value overruns, then “” (3 asterisks)
are displayed.
Double click on the desired measure value group; e.g. 3ULPDU\ ORFDO . The next
sub-group is displayed.
Double click on the desired sub-group; e.g. 2SHUDWLRQDOYDOXHVSULPDU\.
By double clicking on an entry in the list on the right side of the window, the associated
contents of the measured value group are displayed in another window, as shown in
Figure 7-20.

Figure 7-20 Example of measured values shown in DIGSI® 4

7-18 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

7.1.3.2 Illustrating Measured Values

The IBS-Tool The IBS-tool allows to illustrate the measured values of both ends of the protected ob-
ject during commissioning and during operation. The IBS-tool offers a wide range of
commissioning and monitoring functions that allows a detailed illustration of the differ-
ential protection communication and the power system conditions via a personal com-
puter equipped with a browser. For more details refer to the “Online Help” for the IBS-
tool. The “Online Help” can be downloaded from the INTERNET download area under
http://www.ev.siemens.de/en/pages/siprote1.htm.

Local Measured With the IBS-tool the user can view the remote measured values according to Table
Values 7-4 on the PC-screen. Currents and voltages appear as vector diagrams and are indi-
cated as numerical values (such as angles and frequency). See Figure 7-21.

Table 7-4 Operational measured values of the local device

Measured values primary secondary


IL1, IL2, IL3 phase currents A A
3I0 earth current A A
ϕ(IL1–IL2), ϕ(IL2–IL3), phase angles of phase currents ° —
ϕ(IL3–IL1) in relation
UL1–E, UL2–E, UL3–E phase–earth voltages kV V
3U0 displacement voltage kV V
ϕ(UL1–UL2), ϕ(UL2–UL3), phase angles of phase voltages ° —
ϕ(UL3–UL1) in relation
ϕ(UL1–IL1), ϕ(UL2–IL2), phase angles of phase voltages ° —
ϕ(UL3–IL3) in relation to phase currents
f frequency Hz Hz

7SD610 Manual 7-19


C53000-G1176-C145-1
Control During Operation

Local Measurement – Primary Values

Currents: Voltages:
+90° +90°

±180° 0° ±180° 0°

–90° –90°

Address: 2 Frequency: 50.00 Hz


IL1 = 199.71 A, 0.0 ° UL1E = 132.71 kV, 10.4 °
IL2 = 200.44 A, –119.6 ° UL2E = 133.44 kV, –109.3 °
IL3 = 199.34 A, 120.1 ° UL3E = 132.34 kV, 130.3 °
3I0 = 0.17 A, 159.9 ° 3U0 = 0.00 kV, 0.0 °
Figure 7-21 Local measured values — example for voltages and currents

Remote Measured For the remote device; the local measured values can be compared with the remote
Values measured values, refer to Table 7-5. Figure 7-22 gives an example.

Table 7-5 Operating measured values transmitted from the other ends in comparison with
the local operating measured values

Data % referred to
Device ADR device address of the remote device (absolute)
IL1, IL2, IL3 remote phase currents of the remote device operating nominal current 1)
IL1, IL2, IL3 local phase currents of the local device operating nominal current 1)
ϕ(IL1), ϕ(IL2), ϕ(IL3) phase angles between remote and °
local phase currents
1
) for lines acc. to address  (refer to Subsection 6.1.3),
for transformers acc. to address  (refer to Subsection 6.1.3) IN = SN /(√3·UN)
2) acc. to address  (refer to Subsection 6.1.3)

7-20 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

Table 7-5 Operating measured values transmitted from the other ends in comparison with
the local operating measured values

Data % referred to
UL1, UL2, UL3 remote voltages of remote device operating nominal voltage /√3 2)
UL1, UL2, UL3 local voltages of local device operating nominal voltage / √3 2)
ϕ(UL1), ϕ(UL2), ϕ(UL3) phase angles between remote and °
local voltages
1) for lines acc. to address  (refer to Subsection 6.1.3),
for transformers acc. to address  (refer to Subsection 6.1.3) IN = SN /(√3·UN)
2
) acc. to address  (refer to Subsection 6.1.3)

Remote Measurement

Currents: Voltages:
+90° +90°

±180° 0° ±180° 0°

–90° –90°

Local Address: 2
IL1L = 24.96 %, 0.0 ° UL1EL = 99.94 %, 10.4 °
IL2L = 25.06 %, –119.9 ° UL2EL = 100.50 %, –109.3 °
IL3L = 24.92 %, 120.1 ° UL3EL = 99.66 %, 130.4 °

Remote Address: 1
IL1R = 23.22 %, 172.2 ° UL1ER = 94.94 %, 4.7 °
IL2R = 23.30 %, 52.4 ° UL2ER = 94.68 %, –115.0 °
IL3R = 23.17 %, –67.7 ° UL3ER = 95.48 %, 124.7 °
Constellation Data:
IdiffL1 = 2.63 % Frequency = 50.00 Hz
IdiffL2 = 3.21 %
IdiffL3 = 2.72 %
Figure 7-22 Local and remote measured values — example for voltages and (flowing) currents

7SD610 Manual 7-21


C53000-G1176-C145-1
Control During Operation

Values Measured The differential protection and stabilization values are listed below the local and re-
by the Differential mote addresses (Figure 7-22). Additionally the position of the differential and stabili-
Protection zation values can be viewed in the pickup characteristic. See Figure 7-23.

Tripping Characteristics

Differential Parameter IDIFF> : 20.00 %


% of IN
150 %

100 %

50 %

Adaptive
Stabilization
% of IN

50 % 100 % 150 %
IdiffL1 = 3.30 % IstabL1 = 33.30 %
IdiffL2 = 1.74 % IstabL2 = 30.74 %
IdiffL3 = 7.10 % IstabL3 = 32.10 %

Figure 7-23 Pickup characteristic of the differential protection - example showing an operating state

7-22 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

7.1.3.3 Setting and Retrieval of User Defined Set-points

In the 7SD610 measured value set-points can be configured with the user definable
logic CFC (see Section 5.3). If during normal operation a measured value reaches one
of these set-points, the device generates an alarm which is indicated as an operational
event. As is the case for all operational messages, it is also possible in this case to
output the information to LED and/or output relay and via the interfaces.
If such set-points were defined during the configuration of the device, they can be
viewed and — with password No. 5 — they can be changed:

From the With the device ready for operation, first press the MENU key. The0$,10(18 appears.
Device Front
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of meas-
ured values using the key. The 0($685(0(17 selection appears.
There, select the menu item 6HW3RLQWV 09 with the key, and switch to the
list of limit values using the key (see Figure 7-24).

0HDVXUHPHQW 

!6HW3RLQWV 09  6(732,176 09 
5HVHW  
,//LPLW $
,//LPLW $
u.s.w.

3:6HWWLQJV" Enter password Nr. 5 (for individual para-


ENTER
  meters) and confirm with ENTER

,//LPLW  ENTER

$UH\RXVXUH"
ENTER
!<HV1R(VFDSH
Figure 7-24 Setting of set-points on the device front — example

With the keys and paging up and down in the set-point table is possible.
To change a set-point, it must be marked by means of the keys and and sub-
sequently the key ENTER must be pressed.
A prompt for the entry of password No. 5 (for individual parameters) appears. After en-
try of the password and confirmation thereof with ENTER , the current value appears in a
frame with a flashing cursor. The current value must be overwritten with the desired
new value with the numeric keys. If the permissible range for the setting value is ex-
ceeded to the top or the bottom, the maximum or minimum set point value appears at
the bottom of the display when the value is entered.
Press the ENTER .key. The new value now appears in the list of set point values.
In the same way, further set points, if available, can be modified.

7SD610 Manual 7-23


C53000-G1176-C145-1
Control During Operation

If this level is exited with the key or MENU the query “$UH\RXVXUH"”, with the de-
fault answer “<HV” appears (Figure 7-23). Confirm with the key ENTER , if the modified
value must be accepted. If the value must not be modified the key, so that the an-
swer “1R” is marked, and confirm with the ENTER key. If the value is to be modified once
more, mark “$ERUW”, confirm this with the ENTER key and re-enter the value.

:
From PC with Set points are only available in online-mode. The metered value groups are found un-
DIGSI® 4 der 0HDVXUHPHQW (Figure 7-25) with a double click. Select 2WKHU and then 6HW
3RLQWV 0HDVXUHG9DOXHV Figure 7-25).
By double clicking on an entry in the list view in the right side of the window, the limit
values are loaded. Mark the number of the value that is to be changed. With the right
mouse button, open the context menu and click on 6HW, as shown in Figure 7-25. A
password inquiry (password no. 5 for individual settings) occurs. Next, the dialogue
field 6HW0HWHUHG9DOXH is opened. Enter the desired value in the entry field. Then
click on 2..
The entered value is transferred to the device and the display within the window in Fig-
ure 7-25 is updated.

Figure 7-25 Setting of set-points in DIGSI® 4 — example

7.1.3.4 Retrieval and Resetting of User Defined Pulse Metered Values (PMV)

In the 7SD610 it is possible to define pulse metered values with the user definable log-
ic (CFC) (see Section 5.3).
If such pulse metered values were defined during the configuration of the device, they
can — with password No. 5 — be reset to 0:

7-24 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

From the With the device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of meas-
ured values using the key. The 0($685(0(17 selection appears.
There select with key the menu item 8VHU'HILQHG&RXQWHUand switch to the
5(6(7 option with the key (refer to Figure 7-26).

5HVHW

0HWHUUHV !

Figure 7-26 Resetting of pulse metered values on the device front

With the keys and you may page up and down in the table, if several positions
are available.
If one of the memories should be reset, mark it with the keys and , and then se-
lect it by pressing the ENTER key.
A prompt to enter the password No. 5 (for individual parameters) appears. After entry
of the password and confirmation with ENTER , the reset command is executed.
Press the ENTER key. The display confirms the entry with “&KDQJH2.&RQWLQXH”.
Confirm again by pressing the ENTER key. The resetting is complete.
If further counters are available, they can be reset in the same manner.
With the key, a return to the level 0HDVXUHPHQW is possible, with the MENU key, you
may jump to the 0$,10(18.

:
From PC with Double click on 0HDVXUHPHQW (Figure 7-2). Select 2WKHU and then 8VHU'HILQHG.
DIGSI® 4
By double clicking on an entry in the list view in the right side of the window, the limit
values are loaded. Mark the number of the value that is to be changed. With the right
mouse button, open the context menu and click on 6HW. A password inquiry (password
for individual settings) occurs. Next, the dialogue field 6HW9DOXH is opened. Enter
the desired value in the entry field, if applicable, the value . Then click on 2..
The new value is transferred to the relay.

7.1.4 Fault Records

Waveform or rms data is stored in the device and can be graphically represented on
a personal computer using DIGSI® 4, together with the graphic program DIGRA 4.
The settings associated with fault recording — such as duration and pre- and post-trig-
ger times — had been are set according to Chapter 6.

7SD610 Manual 7-25


C53000-G1176-C145-1
Control During Operation

7.1.4.1 Viewing Fault Records

:
From PC with To view the fault recording data on a screen, one of the programs DIGRA® 4 or Com-
DIGSI® 4 trade Viewer (included with SIMATIC Manager) is needed. Do the following:
Double click on 2VFLOORJUDSKLF5HFRUGV (Figure 7-27). The folders listed in the
right window show an overview of oscillographic records. The records are identified
with a network fault number, a fault record number, and the date and time.
By double clicking on an fault record in the list view in the right side of the window, one
of the above programs is opened, and the selected waveform data are loaded. (See
also DIGSI® 4, Operating Handbook, order no. E50417–H1176–C097, Subsection
8.3.3).

Figure 7-27 Retrieval of fault records in DIGSI® 4 – example

DIGRA® 4 provides support in the analysis of faults on the power system. The pro-
gram graphically prepares the data recorded during a fault, and calculates additional
measurement quantities, such as impedances or rms values.
The quantities can be represented in these views:
• Time signals
• Phasor diagrams
• Locus diagrams
• Harmonics
Selection takes place using the menu bar (9LHZ), or clicking in the symbol bar above
the represented switching fields. Figure 7-28 shows all four views simultaneously.
The recorded data read into the PC memory are first shown in full on the screen. Cur-
rent, and possibly voltage, for each phase and the ground are represented separately.
The fault number, data and time, network, and feeder are also displayed.
Representation of primary or secondary quantities can be selected. The base values
for currents and voltages are the nominal values of the transformers (CTs or VTs). An
identical scale is used for all currents, relative to the largest occurring current value,
and for all voltages, relative to the largest occurring voltage value.

7-26 7SD610 Manual


C53000-G1176-C145-1
Read-out of Information

Figure 7-28 DIGRA 4 — Diagrams in the four possible views

During configuration any signal can be selected in its properties to be displayed in the
fault record. (See chapter 5.2.3.)
Further details about the many possibilities that DIGRA® 4 offers can be found in the
DIGRA handbook (Order No. E50417–H1176–C070).

7.1.4.2 Saving the Fault Records

Storage of Fault Oscillographic records that are received from the device are not automatically saved
Recording Data in the PC. The data can, however, be saved in files.
For more details, see the DIGSI® 4 Operating Handbook, Order No. E50417–H1176–
C097, Section 9.4.
The oscillographic records stored in the device do not need to be erased, since the
data are stored in a revolving buffer. The oldest data are automatically overwritten by
the newest data.

7SD610 Manual 7-27


C53000-G1176-C145-1
Control During Operation

7.2 Control of Device Functions

You may change individual functions and messages in a 7SD610 while the device is
in-service. Some examples are given above, including erasing stored information
(Sub-section 7.1.1.4) and setting/resetting counters and set-points (Sub-sections
7.1.2.2 and 7.1.3.4). In this section, three other control capabilities are discussed.
They are correcting the date and time, changing the settings group, and affecting in-
formation at the system interface during test operations.

7.2.1 Read and Set Date and Time

Whether and by which synchronization source the internal clock should be set was al-
ready determined in Section 5.5, “Date and Time Stamping”. Once the device is not
supplied with power, the internal time clock (RTC) continues working by taking its pow-
er from the integrated buffer battery. Right after the running up of the device it displays
a plausible time. The time then is changed automatically by the synchronization
source linked to the device or is altered manually. Before initiating a synchronization
process which is going to stamp a valid time, different types of time indication in the
device display are possible. The following paragraph gives you more details about this
matter.
In a differential protection system with 7SD610 devices the time is usually synchro-
nized by only one device, the so-called “Absolute time master”. Generally it is the de-
vice with index 1. It synchronizes the partner-device via the protection communication.
The time can therefore only be changed in this device. However, the state and time
can be read out in all devices of a differential protection system at any time.

Time Status Besides the display of date and time, the status of these readings is also provided. The
text of the status display can have the appearances given in Table 7-6, under regular
conditions of time control.

Table 7-6 Time Status


Status Bits No.
 1
synchronized
67 2
(5 3
(567 4
not synchronized
16(5 5
16 6

7-28 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

The text symbols, or “status bits”, for the time status have the following meanings:

16 Not synchronized Time was neither set manually nor synchronized after
power-up.
(5 Time error At the moment, there is no cyclical synchronization
within the tolerance times (time can jump)

67 Daylight savings The latest synchronization signal received supplied a


time daylight savings time bit

Representation of Various representations of the date and time stamp may be given in the '$7(7,0(
the Time sub-menu and in all messages stamped with the date and time. The year number
stored in the device and the values of the status bits “Not synchronized” and “Time er-
ror” determine the representations. The possible representations and the associated
causes are listed in Table 7-7.

Table 7-7 Representations of Date and Time:

Item Display (Example) Year Time Error Time Invalid


Date Time

1 HHHHHHHH " Year = 1990 irrelevant

2  " Yes No

3 " " 1990<Year<2090 Yes Yes

4   No No

5 HH"HHHHHH " No Yes

? appearing in the date and time field indicate that the clock synchronisation has been
lost.
• Item 1 appears if the internal clock RTC did not have a valid time upon start-up. The
messages in the memory buffers are dated 01/01/1990.
Corrective action: Set the date and time manually (see margin header “Changing
the Time” below).
• Item 2 appears if the time was actually set, but not synchronized. This can happen:
− briefly upon device power-up,
− if synchronization is lost; that is, if the cyclical synchronization is interrupted for a
time longer than the set tolerance time.
Corrective action: If an external synchronizing source is being used, check the
source and the connection.
• Item 3 is displayed if the RTC had a valid value upon device start-up but the time
was neither manually set nor synchronized since.
Corrective action: Set the date and time manually, or wait until the cyclical synchro-
nization takes effect.

7SD610 Manual 7-29


C53000-G1176-C145-1
Control During Operation

• Item 4 displays the normal condition; that is, the time is synchronized cyclically ac-
cording to the type of operation.
• Item 5 is displayed if synchronization via the system interface is marked as “invalid”.

Changing the Time The time can be changed


− by setting the time manually, using the integrated control panel or DIGSI® 4,
− by adjusting the settings for time control.
The date and time can be manually set during operation, provided the device allows
this. A precondition is that the appropriate type of operation for time control must be
selected (see Section 5.7).
When the source of time synchronization is “internal” or “pulse via binary input” the
date and time can be manually set during operation at any instant. The annunciations
“time error ON” and “time error OFF” appear in the annunciation log to indicate time
synchronization and loss of time synchronization, respectively.
In the other operating modes, manual adjustments are only accepted if the synchroni-
zation is momentarily lost. The messages “time error ON” and “time error OFF” are giv-
en when manually changing the year in the IRIG B mode.
Without healthy or external time synchronisation the free running date and time can
also be relatively adjusted (+/– 23:59:59) using the entry field 'LII²WLPH.
This input possibility is not to be confused with the parameter 2IIVHW (see Section
5.7), which affects the specific general offset to the received synchronization time of
the radio clock receiver (e.g. local time vs. GMT time).

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Select 6HWWLQJV, and in the sub-menu 6(783(;75$6. To set the date and time
manually, choose the selection 'DWH7LPH and move to the '$7(7,0( display us-
ing the key. See Figure 7-29.

6(783(;75$6

!'DWH7LPH²! '$7(7,0(
!&ORFN6HWXS²! 6WDWXV
!
'LII²WLPH

Figure 7-29 Manual date and time adjustment from the front panel

To change one of the previous settings (date, time, differential time), mark the item us-
ing the and keys, and then press the ENTER key.
The actual setting appears in a frame with a blinking cursor. Overwrite this setting with
the desired new one using the number keys. Be careful to enter the format properly.
Confirm the change with the ENTER key.
To change the time offset or the tolerance time for a clock error signal, select &ORFN
6HWXS under 6(783(;75$6, as shown in Figure 7-30. Under 2IIVHW, the time off-
set can be changed. Under (UURU7LPH, the time delay for the alarm can be adjust-

7-30 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

ed. These adjustments are done in the same manner as setting the time, by overwrit-
ing the displayed values and confirming with the ENTER key.
To return to the S(783(;75$6 level, press the key, several times if necessary. To
return to the 0$,10(18, press the MENU key.

6(783(;75$6

!'DWH7LPH²!
!&ORFN6HWXS²! &/2&.6(783

2IIVHW!PLQ
(UURU7LPHPLQ

6RXUFH,QWHUQDO

Figure 7-30 Date and time settings from the front panel

:
From PC with To manually change the date and time of the device:
DIGSI® 4
Click on 'HYLFH in the menu bar as shown in Figure 7-31. Select the command 6HW
&ORFN.

Figure 7-31 Selecting the command 6HW&ORFN in DIGSI® 4

A dialog field, 6HWFORFN GDWHLQGHYLFH, is opened. The displayed values


are the present date and time. The day of the week is automatically derived from the
date — and cannot be edited.
• Edit the input fields 'DWH and 7LPH. The format depends on your regional settings
of the PC. See Figure 7-32.
Date: mm/dd/yyyy or dd.mm.yyyy
Time: hh.mm.ss
Click on 2. to transfer the entered values into the device. The previous values are
changed and the dialog field is closed.

7SD610 Manual 7-31


C53000-G1176-C145-1
Control During Operation

Figure 7-32 Dialog Field: 6HWFORFN GDWHLQGHYLFH

• To change the time offset or tolerance time for clock signal error, double click on
6HWWLQJV in the navigation window. See Figure 7-33.

Figure 7-33 Setting window in DIGSI® 4

Double click on 7LPH6\QFKURQL]DWLRQ in the data window. This give access to


change (Figure 7-34):
− Source of time synchronisation,
− Monitoring (Time delay for alarm),
− Time format for display,
− Time correction (offset to the time signal).

7-32 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

Figure 7-34 Time synchronization and time format settings in DIGSI® 4

If you realize during operation that the time offset and tolerance time are set too sen-
sitive, these parameters settings can be changed according to the description in Sec-
tion 5.5.

7.2.2 Changeover of Setting Groups

Four different setting groups for the protective functions are available. The active
group can be changed onsite while the 7SD610 is in-service by using the integrated
operating field on the device or the operating interface on a PC running DIGSI® 4. Al-
ternatively, you may decide that the active setting group be remotely controlled via bi-
nary inputs or the system (SCADA) interface.
Password No. 5 (password for individual settings) is required to change setting
groups.
The first setting group is called group A. The others are groups B, C, and D. If setting
group changing is to be used, then settings for the groups to be employed must have
been entered (see Section 6) and the switching process must be (QDEOHG under Ad-
dress  *US&KJH237,21.

From the When the device is ready for operation, first press the MENU key. The 0$,10(18 ap-
Device Front pears.
Using the key, select the menu item 6HWWLQJV and switch to the settings with the
key. The selection 6(77,1*6 appears.
Using the key, select the item &KDQJH*URXS and move to the selection of groups
with the key. The sub-menu &+$1*(*5283 appears, as shown in Figure 7-35.
The first Address  is marked. The address displays the setting group presently
in effect (in Figure 7-35, the active group is *URXS$).

7SD610 Manual 7-33


C53000-G1176-C145-1
Control During Operation

Using the key, select Address  and confirm with the ENTER key.
Enter the password for individual settings, and confirm.
Using the key, select one of the four groups A, B, C, or D, or give control to another
source.
If %LQDU\,QSXW (activation using binary inputs) is selected, setting group switching
is controlled by binary inputs, provided appropriate configuration has been done and
the necessary physical connections are present (see Section 5.2).
If YLD3URWRFRO is chosen, setting group changes can be controlled via the system
serial interface.

&+$1*(*5283 The currently-active setting group is displayed un-



$&7,9(*5283 der Address .
*URXS$

The setting group can be changed under Address


&+$1*(WR : by pressing the ENTER key, after entering the
!*URXS$
password, two possible alternatives are displayed
in a new window each time:

!*URXS$
*URXS% Using the keys, select one of the alterna-
*URXS& tives and confirm with the ENTER key;
*URXS'
YLD%LQDU\,QSXW
YLD3URWRFRO
The next question (“$UH\RXVXUH"”) is an-
swered with <HV and the selected alternative is
$UH\RXVXUH" confirmed, or is answered with 1R using the
ENTER <HV1R key and the change is cancelled with the ENTER key.

Figure 7-35 Switching setting groups from the front panel

Control of the setting groups can always be regained by switching to one of the groups
A through D.
The key can be used to return to the 6(77,1*6 sub-menu; the MENU key can be
pressed to returns to the 0$,10(18.

:
From PC with By opening the 2QOLQH directory with a double click in DIGSI® 4, the operating func-
DIGSI® 4 tions for the device appear in the left part of the window. See Figure 7-36.

7-34 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

Figure 7-36 Function selection window in DIGSI® 4 - example

Double click on 6HWWLQJV to find &KDQJH*URXS in the data window (Figure 7-36
right).
Double click on &KDQJH*URXS. The &KDQJH*URXS window is opened, as shown
in Figure 7-37.

Figure 7-37 Setting group switching in DIGSI® 4

7SD610 Manual 7-35


C53000-G1176-C145-1
Control During Operation

The active setting group is displayed. To switch to another setting group, click on the
field 9DOXH and select the desired option from the drop-down list. Before closing the
window, transfer the change to the device. This is done by clicking on the button
'LJVL→'HYLFH. A request for Password No. 7 (password for setting groups) is
given. Enter the correct password, and then click on 2..

7.2.3 Test Messages to the System (SCADA) Interface during Test Operation

Depending on the type of protocol, all messages and measured values transferred via
the system (SCADA) interface can be identified with an added message “test opera-
tion”- bit while the devive is being tested onsite (test mode). This identification pre-
vents the messages from being incorrectly interpreted as resulting from an actual pow-
er system event. As another option, all messages and measured values normally
transferred via the SCADA interface can be blocked during the testing (“Block data
transmission”).
A password for test and diagnostics is required (password no. 4) to block the messag-
es and measured values.
Data transmission block can be accomplished by controlling binary inputs, by using
the operating panel on the device, or via DIGSI ® 4.
If binary inputs are used, then the appropriate inputs must have been configured.

From the With the device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Using the key, highlight the menu item 7HVW'LDJQRVH, and then press the
key to enter sub-menu. 7(67',$*126( will appear at the top of the menu.
At this point, highlight the menu item 7HVW(QDEOH using the key, and then press
the key to enter sub-menu. 7(67(1$%/( will appear at the top of the menu. See
Figure 7-38.

7(67',$*126(

'HYLFH5HVHW²!
!7HVW(QDEOH²! 7(67(1$%/(
%ON'DWD7UDQV²! 
+DUGZDUH7HVW²! !7HVWPRGH2))
6HW5HVHW²! 
6,(0(16,QWHUQ
Figure 7-38 Applying test mode from the front panel

To switch to test mode, press the ENTER key, enter the password for test and diagnos-
tics, and confirm with the ENTER key. A new window appears with the options 21 and
2)). Use the and keys to select the desired mode, and press the ENTER key. The
question “$UH\RXVXUH"” is displayed. Highlight the desired response and press
the ENTER key. If the mode is changed, the device responds with the message “&RQ
WURO([HFXWHG”.

7-36 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

Use the key to return to the 7(67',$*126( level; press the MENU key to return to
the 0$,10(18.
The procedure for changing the Block Data Transmission mode is the same. See Fig-
ure 7-39 (simplified).

7(67',$*126(

!%ON'DWD7UDQV²! %/.'$7$75$16
+DUGZDUH7HVW²! 
!'DWD6WRS2))


Figure 7-39 Applying data transmission block from the front panel (simplified)

The settings for the test mode and the data transmission block are normally 2)). Def-
initions:
− 7HVWPRGH – With the 21 setting, the “test mode“-bit is transferred for messages
compatible with IEC 60870–5–103.
− 'DWD6WRS – With the 21 setting, no messages or measured values are trans-
ferred (“data tranmission block”).

:
From PC with Click on 'HYLFH in the menu bar to reach the commands %ORFN'DWD7UDQVPLV
DIGSI® 4 VLRQ or 7HVW0RGH. See Figure 7-40.

Figure 7-40 Applying “Test Mode” or “Block Data Transmission” in DIGSI® 4

Click on %ORFN'DWD7UDQVPLVVLRQ to activate or deactivate the transfer block.


After entry of Password No. 4 for test and diagnostics, and confirmation with 2., the
setting change is complete.
Activation is indicated with a check mark in front of the command.

7SD610 Manual 7-37


C53000-G1176-C145-1
Control During Operation

Follow the same procedure for the command 7HVW0RGH, if this option is desired.

Note:
Remember to change the settings for Test Mode or Block Data Transmission back
to the desired, in-service settings (both typically 2))) when the tests are complete.

7.2.4 Changeover of Operating Mode

During testing and station revision it is possible to change the operating mode of a de-
vice in order to perform such work with minimum effect on running operation.
The following modes are available:
• Log out device: logging out a device from the differential protection system with the
circuit breaker being switched off. The device at the other end remains in operation;
thus, the other end may remain switched on. As the local circuit breaker is open (as
well as the outgoing disconnector) revision work can be done at the local feeder
without affecting operation at the other end.
• Test mode: All currents from the other device are set to zero in the local device.
Thus the local device has been isolated from the differential protection system and
can be checked. If the device had been logged off before (see above), all the other
device can operate normally. Otherwise, the differential protection system is
blocked in both devices. Emergency operation with time overcurrent protection is
feasible.
• Commissioning mode: All tripping commands of the differential protection system
are blocked. The differential system as an entity can be checked using primary or
secondary values.
The first two modes are in particular relevant for operation. For mode changeover
Password No. 2 is required (for switching/tagging/manual overwriting). Every mode
that has been changed is stored in the device safe from an auxiliary voltage failure.

From the With a device ready for operation first press the MENU key. The MAIN MENU appears.
Device Front
Select the item &RQWURO with and move to the selection of control options using
. The selection &21752/ appears.
With select the item 7DJJLQJV and move to the selection of 7$**,1*6 (see Fig-
ure 7-41) using .
Then select the item Set with and move to the next display 6(7 with (see Figure
7-41).

7-38 7SD610 Manual


C53000-G1176-C145-1
Control of Device Functions

7$**,1* 

'LVSOD\²! 
!6HW²!  6(7 

!/RJRXW 2))
7HVWPRGH 2))

Figure 7-41 Set taggings at the front cover — example

Using the and keys you can select the mode to be set.
With you indicate your intention to change the corresponding mode. The password
for interlocked switching (No. 2) will then be requested.
Having entered and confirmed the password with ENTER , you can change over to: 21 for
mode setting, 2)) for deleting this mode. Every mode can be determined separately.
Press the ENTER key. Answer the question “$UH\RXVXUH"” with Yes, confirm with
ENTER .

If the feeder is still current-carrying, or if the circuit breaker is signalled to be closed by


the auxiliary contacts, the device will refuse tag setting for this mode and will show a
corresponding message on the display.
When the mode has been confirmed, testing and revision works can be done as de-
scribed above. As the mode set has been saved as tag message, the auxiliary voltage
may also be switched off.
With the key you return to the 0($685(0(17 level, with MENU you can return to the
0$,10(18.
In order to change to normal operation proceed in the same way and set the corre-
sponding modes to “2))”.

:
From PC with When you double-click to open the 2QOLQH directory in DIGSI® 4 you will see the op-
DIGSI® 4 erating functions in the left part of the display window (Figure 7-42).

Figure 7-42 Function selection window in DIGSI® 4 — example

7SD610 Manual 7-39


C53000-G1176-C145-1
Control During Operation

In the Control subdirectory you can click on the Taggings under )XQFWLRQ6HOHF
WLRQ in the right window.
Double-click 7DJJLQJV. A dialogue box “7DJJLQJ” is opened. (Figure 7-43).

Figure 7-43 Tagging dialogue box

In the “1DPH” column the different modes have been listed, “6WDWXV” refers to the cur-
rent state with “2))” meaning that the mode is not effective, “21” meaning that it is
effective.
By clicking one of buttons under “6FKHGXOHG” you can change the desired mode. In
a security query you will be requested to confirm this.
Then you will be requested to enter the password for switching/tagging/substituting. If
you want to make multiple changes, you only have to enter the password before im-
plementing the first action.
Having entered the password, confirm with the “2.” button.
If the feeder is still current-carrying, or if the circuit breaker has been signalled closed
by the auxiliary contacts, the device refuses tag setting for this mode and displays a
corresponding message on the monitor.
When the mode has been confirmed, testing and revision works can be done as de-
scribed above. As the mode set has been saved as tag indication, the auxiliary voltage
may also be switched off.

7-40 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Test Function

7.3 Circuit Breaker Test Function

The circuit breaker and the trip circuits can be tested during normal operation by exe-
cution of a TRIP and CLOSE command via the device.
A prerequisite for this test is that the required test commands were allocated to the cor-
responding command relays during the configuration of the device. It is also possible
to test the individual circuit breaker poles, provided that the device is capable of single-
pole tripping, the circuit breaker is capable of single-pole tripping and that the wiring
and routing has been done accordingly.
A maximum of 4 test programs is available (refer to Table 7-8). For the circuit breaker
CB1 it may be possible to initiate single- and three-pole TRIP/CLOSE cycles. In the
event of three-pole tripping, only item 4 is important.

Table 7-8 Circuit breaker test programs

Item Test Program Operational Messages


1 1-pole TRIP/CLOSE–cycle phase L1 &%²7(6775,3FRPPDQG²2QO\/
2 1-pole TRIP/CLOSE–cycle phase L2 &%²7(6775,3FRPPDQG²2QO\/
3 1-pole TRIP/CLOSE–cycle phase L3 &%²7(6775,3FRPPDQG²2QO\/
4 3-pole TRIP/CLOSE–cycle &%²7(6775,3FRPPDQG/
associated close command &%²7(67&/26(FRPPDQG

In the event that circuit breaker auxiliary contacts are used to derive the switching
state of the circuit breaker via binary inputs to the device, the test cycle can only be
initiated when the circuit breaker is in the closed position.
A further prerequisite for the initiation of the test is that no protection function in the
device has picked up, and that the circuit breaker is ready.
The device indicates the status of the test sequence with corresponding messages in
the display or on the monitor of a PC. If the device refuses to run or terminates the test
sequence, it is likely that one of the preconditions for the execution of the test cycle
has not been satisfied. The reason for the refusal or termination is also shown in the
front display or monitor of the PC.

&%7(67UXQQLQJ Circuit breaker test in progress


&%767VWRS)/7 Circuit breaker test cannot be started as a system fault is present
&%767VWRS23(1 Circuit breaker test cannot be started as the circuit breaker is not
closed
&%767VWRS127U Circuit breaker test cannot be started as the circuit breaker is not
ready
&%767VWRS&/26 Circuit breaker test has been terminated as the CB is still closed (pri-
or to CB test reclosure)
&%7672. Circuit breaker test cycle has been completed successfully

7SD610 Manual 7-41


C53000-G1176-C145-1
Control During Operation

The following diagram shows the test sequence in principal:

TRIP

CLOSE

T TRIP CMD.MIN. T PAUSE TEST T CLS. CMD MAX. t


Figure 7-44 TRIP-CLOSE test cycle

The initiation of the test is done via the keypad and display on the front of the device
or with a PC running DIGSI® 4. Entry of the password (password No. 4 for test and
diagnostics) is required.

DANGER!
A successful initiation of a test cycle may cause closure of the circuit breaker if
an external reclose device is available!

From the With the device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Select the 7HVW'LDJQRVH option using the key and enter the sub-menu 7(67
',$*126( with the key.
With the key, the &%WHVW (21) is now marked and the test program is selected
with the key.
A prompt for entry of password No. 4 (test and diagnostics) appears. After entry of the
password and confirmation with ENTER , the query “%UHDNHUFORVHG"” appears, with
the default response “Yes” (Figure 7-45). This must be confirmed by pressing the ENTER
key if the circuit breaker is definitely closed.
If circuit breaker auxiliary contacts are connected and marshalled, the device rejects
the test cycle when the auxiliary contacts indicate that the circuit breaker is not closed,
even if the operator confirms the opposite. Only if no auxiliary contacts are marshalled,
will the device rely on the confirmation by the operator.
If the test cycle should be cancelled, press the key in response to the above query,
so that the answer “1R” is marked. This must be confirmed with the ENTER key. Prior to
the confirmation with the ENTER it is possible to toggle between “Yes” and “1R” with the
and keys. Alternatively, the test sequence may also be cancelled by pressing
the ESC key.

7-42 7SD610 Manual


C53000-G1176-C145-1
Circuit Breaker Test Function

0$,10(18 

!6HWWLQJV 
>7HVW'LDJQRVH  7(67',$*126( 

!6,(0(16LQWHUQ 
!&%WHVW 

&%7HVW  Select the desired test program or press the



!&%WVW/  relevant numeric key to select the desired test
>&%WVW/  sequence.

u.s.w.
6
3:7HVW'LDJQRVH" Enter password Nr. 4 (for test and diagnostics)
ENTER
  and confirm with ENTER .

Press the ENTER to confirm with “<HV” and


%UHDNHUFORVHG" thereby execute the selected breaker test cy-
!<HV 1R cle, or change to ”1R” with the key to termi-
nate the test when ENTER is pressed.

After confirmation that the CB is closed, the CB


&%7HVW 
 test cycle is executed, subsequently a feed-
!&%WVW/  back message stating successful completion
&RQWURO([HFXWHG of the test , or a relevant alarm appears.

Figure 7-45 Circuit breaker trip test cycle from the front of the device

:
From PC with If the 2QOLQH directory in DIGSI® 4 is opened with a double click, the operation func-
DIGSI® 4 tions of the device appear in the left hand side of the window.
By clicking on the 7HVWIXQFWLRQ, a list of the available functions appears on the
right hand side of the display (Figure 7-46).
By a double click on the &LUFXLWEUHDNHUWHVW, a dialogue window is opened in
which the desired test sequence can be marked for selection.
Following a double click, a prompt for the entry of password No. 4 (for test and diag-
nosis) appears.
After entry of the password and confirmation with 2N the test sequence is executed.
In the spontaneous event window, the execution of the test is displayed with the cor-
responding control responses and messages.

7SD610 Manual 7-43


C53000-G1176-C145-1
Control During Operation

Figure 7-46 Circuit breaker trip test in DIGSI® 4

7-44 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

7.4 Control of Switchgear

A SIPROTEC® 4 device 7SD610 contains control functions that allow for opening and
closing of power system switching devices (i.e. circuit breakers). Local control is pos-
sible utilizing different elements of the 7SD610. Breaker control from a remote location
is also possible using the SCADA interface or DIGSI® 4. (Performing control functions
with a PC running DIGSI® 4, connected to the front serial port, is considered a “re-
mote” operation for breaker control purposes.) Some control actions from a 7SD610
include unsynchronized commands for circuit breakers, disconnectors, ground switch-
es, etc.
Safety mechanisms in the command path ensure a command can only take place if
the check of previously defined safety criteria is concluded positively.

Note:
It is an important precondition for the switchgear control that the corresponding binary
inputs and outputs were allocated during the configuration (according to Section 5.2).
Furthermore the lockout conditions must have been made available for the device by
means of user-definable logic functions (according to Section 5.3).

If a power system switching device has auxiliary contacts that indicate the position of
the device and these contacts are connected to the 7SD610 and configured as
double-point indications then the switching device provides feedback indication that
are monitored for plausibility of control actions. If a switching device does not indicate
either the closed or open position, the display for the switching device indicates an in-
valid position in the 7SD610. All subsequent control operations to the equipment are
interlocked.
Control from a 7SD610 to a power system equipment can originate from four sources:
− Local operation using the operator control panel,
− Binary inputs,
− Remote operation using the SCADA interface,
− Operation with a PC, via the operating interface and DIGSI® 4.
Switching priority for the four command sources is set using the Switching Authority.
For Interlocked Switching, all programmed interlocking conditions are checked before
a control operation is performed. If one of the conditions is not met, then the command
is rejected and an error message is recorded and displayed. The following tests can
be activated (on) or deactivated (off) for a switching device:
• Switching authority (Local/Remote),
• Zone controlled (Field interlocking e.g., logic in CFC),
• Substation controller, to be implemented with Version 4.2,
• Double operation (blocking of multiple control operations),
• Blocking by protection (control operations blocked by protective functions),
• Device position (check SCHEDULED = ACTUAL comparison).

7SD610 Manual 7-45


C53000-G1176-C145-1
Control During Operation

7.4.1 Display Equipment Position and Control

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Using the key, select the menu item &RQWURO, and go to editing the control func-
tions with the key. The selection &21752/ appears (See Figure 7-47).

0$,10(18

0HVVXUHPHQW²!
!&RQWURO²! &21752/

!%UHDNHU6ZLWFK²!
7DJJLQJ²!

Figure 7-47 Control selections from the front panel

Select, by means of the key, the item %UHDNHU6ZLWFK, and continue with the
item by pressing the key. The selection %5($.(56:,7&+ appears. See Figure
7-48.
Select'LVSOD\ (default) and press the key. The selection ',63/$< appears, in
which the positions of all planned switching devices can be read out.

%5($.(56:,7&+

!'LVSOD\²! ',63/$<
!&RQWURO²! 
!%UHDNHU23(1
!'LVF6ZLW&/26

Figure 7-48 Display of switch positions in the HMI (example)

The key can be used to return to %5($.(56:,7&+.


To control a switching device, select the option &RQWURO in the %5($.(56:,7&+
sub-menu and press the key to go to the table of operating resources that can be
controlled. See Figure 7-49. All planned switching devices appear. The actual position
of each switch is displayed first. Use the and keys to move to the desired
switch.

%5($.(56:,7&+

!'LVSOD\²!
!&RQWURO²! &21752/

%UHDNHU!&/26
'LVF6ZLW&/26
*QG6ZLW2))

Figure 7-49 Control of switching devices from the operator control panel (example)

7-46 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

Select the switch to be controlled using the and keys and press the ENTER key.
Enter Password No. 1 (for interlocked switching) and acknowledge with the ENTER key.
Note: if the switching mode is 121²,17(5/2&.(' 7HVW (Sub-section 7.4.7), all
switching operations are only possible with Password No. 2 (for non-interlocked
switching).
A new window appears. Depending on the operating and command type of the select-
ed switching device, various options are offered. Move between them using the and
keys.

&2175
!23(1
36!&/26(21
7UH(VFDSH21

Figure 7-50 Selection window for control operations on the front panel (example)

To perform control, confirm with the ENTER key. A safety inquiry appears, “$UH\RX
VXUH"”. If the response is “<(6”, the switching operation is initiated (provided the Lo-
cal command is allowed). A message is displayed and recorded indicating the results
of the control action. Acknowledge this by pressing the ENTER key once again.
The command is not executed if the switching operation is restricted. The operation
may be restricted for reasons pertaining to, for example, switching authority (see Sub-
section 7.4.6) or interlocking (see Sub-section 7.4.7). A message is displayed and re-
corded indicating the results of the control action. Acknowledge the message by
pressing the ENTER key. Parameters to set control properties can be examined in the
display. Refer to Sub-section 7.4.4.
The key can be used to return to %5($.(56:,7&+. Press the MENU key to return
to the 0$,10(18.

:
From PC with When the 2QOLQH window in DIGSI® 4 is opened with a double click, the operating
DIGSI® 4 functions for the device appear in the left part of the window (Figure 7-36). Clicking on
&RQWURO displays the associated function selection in the data window. See Figure 7-
51.

Figure 7-51 Window for control of operating resources in DIGSI® 4 (example)

7SD610 Manual 7-47


C53000-G1176-C145-1
Control During Operation

By double clicking on %UHDNHU6ZLWFKHV, a dialog field is opened in which the


present status of each switch is visible. See Figure 7-52. Control can be performed
from this dialog box provided the switching authority is set to 5(027(.
The switching authority is first transferred to DIGSI® 4 at the moment the control win-
dow shown in Figure 7-52 is opened. The configuration matrix discussed in Section
5.2 determines the control devices that have information displayed in this field.

Figure 7-52 Dialog box for performing control in DIGSI® 4 (example)

A description of the switching device is displayed in the left column of the dialog field.
This represents the contents of the /RQJ7H[W column within the configuration ma-
trix.
The actual position of the switch is displayed in the 6WDWXV column (23(1,&/26(,
,QWHUPHGLDW). The switching possibilities are displayed in the 6FKHGXOHG column.
Four control fields are shown in the right part of the dialog field. If a check mark is dis-
played in one of these fields, $% (Access Block = Block Input Acquisition), 7% (Trans-
mission Block = Serial Interface Blocked), 75 (Manual Overwriting), and &% (Chatter
Block), the associated block function is set or the feedback indications of the device
have been simulated.
Normally, operating devices are switched in the LQWHUORFNHG 1RUPDO mode.
The configured interlocking conditions are checked before a control command is car-
ried out. As soon as a control command is entered in the 6FKHGXOHG column, Pass-
word No. 1 for interlocked switching is requested for safety reasons. Further control
possibilities remain possible until the control dialog field is closed, or the switching
mode is changed.
If a control command is successfully executed, then the display of the actual condition
of the affected switch is updated in the window.
Operating resources can be switched without interlocking condition checks; however,
the correct Password No. 2 for non-interlocked switching must be entered. Mark the
option 8QORFN by clicking on the field.

7-48 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

DANGER!
Only highly qualified personnel who have an exact knowledge of the power sys-
tem conditions shall perform non-interlocked switching. Inappropriate switch-
ing operations can lead to death, serious personnel injury and property dam-
age.

7.4.2 Manual Overwriting

When using the Control with Feedback feature, the device checks the feedback in-
dications before and after a control command is issued. If for some reason, the phys-
ical connection from a circuit breaker auxiliary contact to the binary inputs of the device
is broken, inadvertently shorted, or disconnected, commands may be blocked. If this
situation occurs, and the affected switching device is to be operated, the desired de-
vice position indication can be simulated through “manual overwriting” (Input Tag-
ging). The entered device position indication in the 7SD610 can be used to simulate
and check interlocking conditions.
To accomplish manual overwriting in the 7SD610 the binary inputs of the affected de-
vice must be decoupled first. $% (Access Block = Block Input Acquisition) This decou-
pling of the system is accomplished by setting the respective status. The decoupling
is discussed in Sub-section 7.4.3.

From the To enter the desired position indication for a switching device:
Device Front
With a 7SD610 ready for operation, first press the MENU key. The 0$,10(18 appears.
Using the key, select the menu item &RQWURO and go to the control functions with
the key. The selection &21752/ appears.
By pressing the key, the %5($.(56:,7&+ sub-menu is entered (see Figure 7-
53).
Select the item 0DQ2YHUZULWH using the key, and move to the next selection
using the key. 0$129(5:5,7( appears, as shown in Figure 7-53.
The actual position of each switching device is displayed. Move to the desired switch
using the and keys.

%5($.(56:,7&+

'LVSOD\³!
&RQWURO²!
!0DQ2YHUZULWH²! 0$129(5:5,7(
6HWVWDWXV³! 
%UHDNHU!23(1
'LVF6ZLW&/26
*QG6ZLW23(1

Figure 7-53 Manual overwriting for switching devices from the front panel

7SD610 Manual 7-49


C53000-G1176-C145-1
Control During Operation

By pressing the ENTER key, a selection window is opened for the marked switch, in
which manual overwriting can be done with the options 23(1&/26(. See Figure 7-
54.
Make the selection using the and keys, and confirm with the ENTER key.
Enter Password No. 2 (for non-interlocked switching) and acknowledge with the ENTER
key.

0$12
!23(1
!%UH&/26!23(1
!'LVF&/26

Figure 7-54 Selection window for manual overwriting of a switch position, front panel

A safety inquiry appears: “$UH\RXVXUH"” Provided manual overwriting is allowed,


a response of “<(6” results in an appropriate message on the display. Acknowledge
the message by pressing the ENTER key again.
Manual overwriting is cancelled if the process is restricted because, for example, “LQ
SXWLJQRUHG” is not set (see Subsection 7.4.3). Manual overwriting is also canceled
if the user aborts the procedure. The display provides an appropriate message if man-
ual overwriting is canceled. Acknowledge the message by pressing the ENTER key.
Return to the %5($.(56:,7&+ sub-menu using the key, or the 0$,10(18 by
pressing the MENU key.

:
From PC with For safety reasons, manual overwriting is only possible locally using the keypad on the
DIGSI® 4 front panel of the device. The feature is not available in DIGSI® 4.

7.4.3 Set Status

A feature of the 7SD610 that is especially useful during testing and commissioning of
the device is the capability of temporarily removing the coupling between a switching
device and the 7SD610, or between the SCADA and the 7SD610, without physically
disconnecting the equipment. This type of separation is also necessary, for instance,
if a switch position feedback message is not functioning properly (refer to Sub-section
7.4.2). The menu item 6(767$786 is used to perform the decoupling.
The menu displays a list of all planned switching devices and associated status infor-
mation identified by a letter. The letters have the following meanings:
• T Device is tagged (manually overwritten).
• I Input ignored, which means the acquisition of an input status is de-coupled from
the process (from the switch-gear).
• B Blocked, which means data transmissions to the central device (or SCADASCA-
DA) are blocked.

7-50 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

• C Chatter block active, which means, because of frequent message changes, the
chatter block was set.
• O Output block active, which means the command output is de-coupled from the
process (from the system).
• – None of the listed limitations is in effect.

Note:
Input ignored only works for physical inputs! Do not set the block for indications cre-
ated by CFC.

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Using the key, select the menu item &RQWURO and go to editing the control func-
tions with the key. The selection &21752/ appears.
Enter the %5($.(56:,7&+ menu by pressing the key.
Select the item 6HW6WDWXV with the key and switch to the next option using the
key. 6(767$786 appears, as shown in Figure 7-55.

%5($.(56:,7&+

'LVSOD\³!
&RQWURO²!
!0DQ2YHUZULWH²!
!6HWVWDWXV³! 6(767$786

%UHDNHU7,2
'LVF6ZLW!
*QG6ZLW

1. 2. 3. 4. 5. Column
Figure 7-55 Set status at the front panel (example)

Move the cursor, using the and keys, to each of the second (Input Ignore) and
fifth (Control Block) columns of the switching device for which a status change is de-
sired. Entries in this table can only be made in these two columns.
Press the ENTER key. A selection window is opened that displays the meaning of the
field and the change options that are available.
The second column is reserved for setting Input Ignore (I); the fifth for setting the out-
put block (O). The first, third, and fourth columns can only be read in this menu.
The example in Figure 7-55 shows the position for the circuit breaker (52) was tagged
(T) after the input ignore (I) was set, which means the message input was de-coupled
from the system. The output block is active (O), so the command output is also de-
coupled from the system. For the disconnect switch and the ground switch, no limita-
tions are set.
Select the desired changes using the and keys, and confirm with the ENTER key.

7SD610 Manual 7-51


C53000-G1176-C145-1
Control During Operation

Enter Password No. 2 (for non-interlocked switching) and acknowledge with the ENTER
key.
A safety inquiry appears: “$UH\RXVXUH"” If the response is “<(6”, and provided
the return routing is allowed, then the display gives an appropriate message.
To return to the %5($.(56:,7&+ level, press the key as necessary. Press the
MENU key to return to the 0$,10(18.

:
From PC with For safety reasons, Status changes are only possible locally using the keypad on the
DIGSI® 4 front panel of the device. Status changes are not possible in DIGSI® 4.

7.4.4 Interlocking

Operating equipment such as circuit breakers, disconnectors and ground switches


can be subject to interlocking conditions. These conditions can be viewed at the de-
vice under the menu item ,17(5/2&.; however, the conditions cannot be changed.
The Interlock display has an object table similar to the one described for Set Status.
The table provides the set interlocking conditions, which prevent, or could prevent, a
local control operation. Letters identify the interlocking conditions. The meanings of
the letters are:
• L Local/Remote (Switching Authority),
• S Equipment is subject to System Interlocking (in Substation Controller). Com-
mands entered locally are sent to the central computer or controller,
• Z Zone controlled (Field- or Bay-Interlocking),
• P Check switch position (test actual vs. scheduled),
• B Blocking by picked-up protection elements,
• – Non-Interlocked.

:
From PC with With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
DIGSI® 4
Using the key, select the menu item &RQWURO and move to editing the control func-
tions with the key. The selection &21752/ appears.
Select the item ,QWHUORFN with the key and switch to the next selection using the
key. The selection ,17(5/2&. appears. See Figure 7-56.

7-52 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

&21752/

!7DJJLQJ²!!
!,QWHUORFN²! ,17(5/2&.

!%UHDNHU/²=3%
!'LVF6ZLW/²=3%

*QG6ZLW/²=3%

1. 2. 3. 4. 5. Column
Figure 7-56 Example of interlocking conditions for switching equipment, front panel

:
From PC with Interlocking is set for each switching device during project planning (see Sub-section
DIGSI® 4 5.2.4) using the matrix and the dialog box “Object Properties”. Readout of the actively
set interlocking is always possible, across the entire path, without a password.
If the 2QOLQH window in DIGSI® 4 is opened with a double click, the operating func-
tions for the device appear in the left part of the window (Figure 7-36). Double clicking
on 6HWWLQJV brings up the function selection in the right side of the window. By dou-
ble clicking on 0DVNLQJ,2, the matrix is opened. Mark the switching device (in the
line for the operating message of the switching device). Using the right mouse key, the
properties of the switching device can now be called up. The conditions for ,QWHU
ORFN6ZLWFKLQJ, among other items, are recognizable in the dialog box that opens.
Active test conditions are identified with a check mark.

7.4.5 Tagging

To identify unusual operating conditions in the power system, tagging can be done.
The tagging can, for example, be entered as additional operating conditions in inter-
locking checks, which are set up with CFC. Tagging is configured in the same way as
for operating devices.

:
From PC with With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
DIGSI® 4
Using the key, select the menu item &RQWURO and move to editing the control func-
tions with the key. The selection &21752/ appears.
Select the item 7DJJLQJ with the key and switch to the next selection using the
key. The selection 7$**,1* appears. See Figure 7-57.
• The status of the tagging is displayed 7DJJLQJ → 'LVSOD\,
• or changed using
• 7DJJLQJ → 6HW.

7SD610 Manual 7-53


C53000-G1176-C145-1
Control During Operation

0$,10(18

$QQXQFLDWLRQ²!
0HDVXUHPHQW²!
&RQWURO²! &21752/

%UHDNHU6ZLWFK²!
7DJJLQJ²! 7$**,1*
,QWHUORFN²! 
'LVSOD\²!
6HW²!

Figure 7-57 Tagging equipment from the HMI

:
From PC with For safety reasons, tag only locally using the keypad on the front panel of the device.
DIGSI® 4 Do no tag with DIGSI 4.

7.4.6 Switching Authority

Switching authority determines the command sources that are permitted for control.

From the With a device ready for operation, first press the MENU key. The0$,10(18 appears.
Device Front
Using the key, select the menu item &RQWURO and move to editing the control func-
tions with the key. The selection&21752/ appears.
Here, select the menu item &RQWURO$XWK with the key and switch to the next
selection using the key. The selection &21752/$87+ appears (see Figure 7-58).
Pressing the ENTER key opens a selection window in which the options /2&$/5(027(
are offered.

&21752/

!,QWHUORFN–> 3
>&RQWURO$XWK–> 4 &21752/$87+

6ZLWFK$XWK!/RFDO

3:8QORFN&RQWURO" Enter password No. 2 (for non-interlocked


ENTER
  switching) and acknowledge with ENTER

&21752
!5HPRWH
6ZLWF/RFDO/RFDO ENTER

Figure 7-58 Setting switching authority with the operator control panel

7-54 7SD610 Manual


C53000-G1176-C145-1
Control of Switchgear

Choose the desired option using the and keys, and confirm with the ENTER key.
Acknowledge the subsequent message pressing the ENTER key.
Use the key to return to the 6:,7&+$87+ level; the MENU key to return to the 0$,1
0(18.

:
From PC with For safety reasons, switching authority can only be changed locally using the keypad
DIGSI® 4 on the front panel of the device. Switching authority cannot be changed with DIGSI ® 4.
To perform control with DIGSI® 4, switching authority at the device must be set to 5(
027(, or the test conditions for remote control of switching authority must not be set
to active. Switching authority is first transferred to DIGSI® 4 when the control window
(see Figure 7-52) is opened.

7.4.7 Switching Mode

The switching mode can be changed during operation; so, for example, non-inter-
locked switching can be enabled during the commissioning of the installed equipment.

DANGER!
Only highly qualified personnel who have an exact knowledge of the power sys-
tem conditions shall perform non-interlocked switching. Inappropriate switch-
ing operations can lead to death, serious personnel injury and property dam-
age.

From the With a device ready for operation, first press the MENU key. The 0$,10(18 appears.
Device Front
Using the key, select the menu item &RQWURO and move to editing the control func-
tions with the key. The selection &21752/ appears.
Here, select the menu item 6ZLWFK0RGH with the key and switch to the next se-
lection using the key. The selection 6:,7&+02'( appears (see Figure 7-59).

&21752/ 6:,
 !,17(5/2&.('
!6ZLWFK$XWK²! ,1121²,17(5/2&.('
!6ZLWFK0RGH²! 12

Figure 7-59 Operating menu for switching mode using front panel

Pressing the ENTER key opens a selection window in which the options ,17(5/2&.('
121,17(5/2&.(' are offered.
Make the choice using the and keys, and confirm with the ENTER key.
Acknowledge the safety inquiry that follows by again pressing the ENTER key. Use the
key to return to the &21752/ level. Press the MENU key to return to the 0$,10(18.

7SD610 Manual 7-55


C53000-G1176-C145-1
Control During Operation

:
From PC with When the 2QOLQH window in DIGSI® 4 is opened with a double click, the operating
DIGSI® 4 functions for the device appear in the left part of the window (Figure 7-36). Clicking on
&RQWUROV brings up the function selection in the right side of the window (Figure 7-
51). By double clicking on %UHDNHU6ZLWFKHV, a dialog field is opened in which,
among other options, the option for interlocked and non-interlocked (Unlock) switching
is offered.
To switch operating resources without a check of the associated interlocking condi-
tions, mark the option 8QORFN by clicking in that field, see section 7.3.1.
To set the switching mode for interlocked switching, the aforementioned option field
must not be marked. The marking is removed by clicking in the field again.
Further switching operations are possible until the dialogue field %UHDNHU6ZLWFK
HV is closed, or the switching mode is changed.

7.4.8 Control Messages

In the course of system control, the device generates several messages that docu-
ment the process. For example, messages may be given to report the end of a com-
mand or provide the reason for a command denial.

7.4.9 Other Commands

If the device is equipped with a serial interface for connection to the System (SCADA)
interface. it can receive standardized commands (according to the supported protocol)
and transmit them to the respective switching devices, or activate internal functions,
e.g. block inputs/outputs or set tags (manual overwrite), or release processing of func-
tions in the CFC. This command processing is determined during project planning and
configuration of the matrix.

7-56 7SD610 Manual


C53000-G1176-C145-1
Installation and Commissioning 8
This section is primarily for personnel who are experienced in installing, testing, and
commissioning protective and control systems, and are familiar with applicable safety
rules, safety regulations, and the operation of the power system.
Installation of the 7SD610 is described in this section. Hardware modifications that
might be needed in certain cases are explained. Connection verifications required be-
fore the device is put in service are also given. Commissioning tests are provided.
Some of the tests require the protected object (line, transformer, etc.) to carry load.

8.1 Mounting and Connections 8-2


8.2 Checking the Connections 8-20
8.3 Commissioning 8-25
8.4 Final Preparation of the Device 8-49

7SD610 Manual 8-1


C53000-G1176-C145-1
Installation and Commissioning

8.1 Mounting and Connections

Warning!
The successful and safe operation of the device is dependent on proper handling, in-
stallation, and application by qualified personnel under observance of all warnings and
hints contained in this manual.
In particular the general erection and safety regulations (e.g. IEC, ANSI, DIN, VDE,
EN or other national and international standards) regarding the correct use of hoisting
gear must be observed. Non-observance can result in death, personal injury, or sub-
stantial property damage.

Preconditions Verification of the ratings of the 7SD610 according to Sub-section 3.2.1 as well as
matching to ratings of the external equipment must have been completed.

8.1.1 Installation

Panel Flush q Removal of the 4 covering caps located on the corners of the front cover, reveal the
Mounting 4 slots in the mounting flange.
q Insert the device into the panel cut-out and fasten with four screws. Refer to Figure
10-5 in Section 10.13 for dimensions.
q Replace the four covers.
q Connect the ground on the rear plate of the device to the protective ground of the
panel. Use at least one M4 screw for the device ground. The cross-sectional area
of the ground wire must be greater than or equal to the cross-sectional area of any
other control conductor connected to the device. Furthermore, the cross-section of
the ground wire must be at least 2.5 mm2.
q Connect the plug terminals and/or the screwed terminals on the rear side of the de-
vice according to the wiring diagram for the panel.
When using forked lugs or directly connecting wires to screwed terminals, the
screws must be tightened so that the heads are even with the terminal block before
the lugs or wires are inserted.
A ring lug must be centred in the connection chamber so that the screw thread fits
in the hole of the lug.
Section 2.1 has pertinent information regarding wire size, lugs, bending radii, etc.

8-2 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Elongated
holes SIEMENS SIPROTEC
RUN ERROR 7SD610

+$8370(18
0HOGXQJHQ
0HVVZHUWH

MENU

LED ESC ENTER

Meldungen F1 7 8 9

Messwerte F2 4 5 6

Störfall-
meldung F3 1 2 3

F4 0 +/-

Figure 8-1 Panel mounting of a 7SD610

Rack Mounting and To install the device in a frame or cubicle, two mounting brackets are required. The
Cubicle Mounting ordering codes are stated in the appendix in Section A.1.1.
q Loosely screw the two mounting brackets in the rack with four screws.
q Remove the 4 covers at the corners of the front cover. The 4 slots in the mounting
flange are revealed and can be accessed.
q Fasten the device to the mounting brackets with four screws.
q Replace the four covers.
q Tighten the mounting brackets to the rack using eight screws.
q Connect the ground on the rear plate of the device to the protective ground of the
rack. Use at least one M4 screw for the device ground. The cross-sectional area of
the ground wire must be greater than or equal to the cross-sectional area of any oth-
er control conductor connected to the device. Furthermore, the cross-section of the
ground wire must be at least 2.5 mm2.

7SD610 Manual 8-3


C53000-G1176-C145-1
Installation and Commissioning

Mounting bracked
SIEMENS SIPROTEC
RUN ERROR 7SD610

+$8370(18
0HOGXQJHQ
0HVVZHUWH

MENU

LED ESC ENTER

Meldungen F1 7 8 9

Meßwerte F2 4 5 6

Störfall-
meldung F3 1 2 3

F4 0 +/-

Mounting bracked

Figure 8-2 Installing a 7SD610 in a rack or cubicle

q Connect the plug terminals and/or the screwed terminals on the rear side of the de-
vice according to the wiring diagram for the rack.
When using forked lugs or directly connecting wires to screwed terminals, the
screws must be tightened so that the heads are even with the terminal block before
the lugs or wires are inserted.
A ring lug must be centred in the connection chamber so that the screw thread fits
in the hole of the lug.
Section 2.1 has pertinent information regarding wire size, lugs, bending radii, etc.

Panel Surface q Secure the device to the panel with four screws. Refer to Figure 10-6 in Section
Mounting 10.13 for dimensions.
q Connect the ground of the device to the protective ground of the panel. The cross-
sectional area of the ground wire must be greater than or equal to the cross-sec-
tional area of any other control conductor connected to the device. Furthermore, the
cross-section of the ground wire must be at least 2.5 mm2.
q Solid, low-impedance operational grounding (cross-sectional area ≥ 2.5 mm2) must
be connected to the grounding surface on the side. Use at least one M4 screw for
the device ground.
q Connect the screwed terminals on the top and bottom of the device according to the
wiring diagram for the panel. Section 2.2 has pertinent information regarding wire
size, lugs, bending radii, etc.

8-4 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

8.1.2 Termination variants

Outline diagrams are shown in Appendix A.2. Connection examples for current and
voltage transformer circuits are provided in Appendix A.3. It must be checked that the
setting configuration of the 3RZHU6\VWHP'DWD 36\VWHP'DWD corre-
sponds with the connections to the device.

Currents The Figures A-3 and A-4 show examples of the current transformer connection op-
tions.
For the normal connection according to Figure A-3 address  must be set to,
WUDQVIRUPHU = ,QSURWOLQH, and furthermore address  must be set to ,
,SK&7 = .
For the connection as shown in Figure A-4 the setting of address  must also be
,WUDQVIRUPHU = ,QSURWOLQH. The factor  ,,SK&7 may deviate
from 1. For notes on how to calculate the factor, refer to Subsection 6.1.1 under “Con-
nection of the Currents”.

Voltages This Section is only relevant if the measured voltages are connected to the device, a
condition which was already set during the configuration (address , see Section
5.1).
The Figures A-5 and A-6 show examples of the voltage transformer connection op-
tions.
For the normal connection as shown in Figure A-5 the fourth voltage measuring input
U4 is not used. Correspondingly address  must be set to 8WUDQVIRUPHU =
1RWFRQQHFWHG. The factor in address  8SK8GHOWD must however be set
to 1.73 (this factor is used internally for the conversion of measurement and fault re-
cording values).
Figure A-6 shows the additional connection of an e-n-winding of the voltage transform-
er set. Address  8WUDQVIRUPHU = 8[WUDQVIRUPHU must be set. The factor
in address  8SK8GHOWD depends on the transformation ratio of the e-n-wind-
ing. For more information refer to “Connecting the Voltage” in Subsection 6.1.1.

Binary Inputs and The configuration of the binary inputs and outputs, i.e. the individual adaptation to the
Outputs system conditions, is described in Section 5.2. The preset allocation of the binary in-
puts and outputs of the device can be found in Tables A-1 and A-2 in Section A.4 of
Appendix A. Also check if the labels on the front panel correspond to the configured
message functions.

Changing Setting If binary inputs are used to switch setting groups, note:
Groups with Binary
• Two binary inputs must be dedicated to the purpose of changing setting groups
Inputs
when four groups are to be switched. One binary input must be set for “!6HW
*URXS%LW”, the other input for “!6HW*URXS%LW”. If either of these input
functions is not assigned, then it is considered as not controlled.
• To control two setting groups, one binary input set for “!6HW*URXS%LW” is
sufficient since the binary input “!6HW*URXS%LW”, which is not assigned, is
considered to be not controlled.

7SD610 Manual 8-5


C53000-G1176-C145-1
Installation and Commissioning

• The status of the signals controlling the binary inputs to activate a particular setting
group must remain constant as long as that particular group is to remain active.
Table 8-1 shows the relationship between “!6HW*URXS%LW”, “!6HW*URXS%LW
”, and the setting groups A to D. Principal connection diagrams for the two binary in-
puts are illustrated in Figure 8-3. The figure illustrates an example in which both Set
Group Bits 0 and 1 are configured to be controlled (actuated) when the associated bi-
nary input is energized (high).

Table 8-1 Setting group selection with binary inputs — example

Binary Input Events


!6HW*URXS%LW !6HW*URXS%LW Active Group

no no Group A
yes no Group B
no yes Group C
yes yes Group D
no = not energized
yes= energized

Selector switch for


setting group
A
B
L–
L+ C
D Binary input set for: 
“!6HW*URXS%LW”, High

A 7SD610
B
L+ C L–
D
Binary input set for: 
”!6HW*URXS%LW”, High

Figure 8-3 Connection diagram (example) for setting group switching with binary inputs

Trip Circuit Super- It must be noted that two binary inputs or one binary input and one bypass resistor R
vision must be connected in series. The pick-up threshold of the binary inputs must therefore
be substantially below half the rated control DC voltage.
If two binary inputs are used for the trip circuit supervision, these binary inputs must
be volt-free i.o.w. not be commoned with each other or with another binary input.
If one binary input is used, a bypass resistor R must be employed (refer to Figure 8-
4). This resistor R is connected in series with the second circuit breaker auxiliary con-
tact (Aux2), to also allow the detection of a trip circuit failure when the circuit breaker
auxiliary contact 1 (Aux1) is open, and the command relay contact has reset. The val-
ue of this resistor must be such that in the circuit breaker open condition (therefore

8-6 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Aux1 is open and Aux2 is closed) the circuit breaker trip coil (TC) is no longer picked
up and binary input (BI1) is still picked up if the command relay contact is open.

UCTR
L+ 7SD610

UBI !57&6WDWXV
7SD610
RTC

Legend:
RTC —
Relay Tripping Contact
R CB —
Circuit Breaker
TC —
circuit breaker Trip Coil
Aux1 —
circuit breaker Auxiliary contact
(closed when CB is closed)
TC Aux1 Aux2 Aux2 — circuit breaker Auxiliary contact
CB (closed when CB is open)
R — bypass Resistor
UCTR — Control voltage (trip voltage)
UBI — input voltage for Binary Input
L–
Figure 8-4 Trip circuit supervision with one binary input

This results in an upper limit for the resistance dimension, Rmax, and a lower limit Rmin,
from which the optimal value of the arithmetic mean should be selected.
R max + R min
R = ---------------------------------
2

In order that the minimum voltage for controlling the binary input is ensured, Rmax is
derived as:
U CRT – U BI min
R max =  -------------------------------------- – R CBTC
 I BI (High) 

So the circuit breaker trip coil does not remain energized in the above case, R min is
derived as:
U CTR – U TC (LOW)
R min = R TC ⋅  -----------------------------------------------
 U TC (LOW) 

IBI (HIGH) Constant current with BI on (=1.7 mA)


UBI min Minimum control voltage for BI
=19 V for delivery setting for nominal voltage of 24/48/60 V
=88 V for delivery setting for nominal voltage of 110/125/220/250 V
UCTR Control voltage for trip circuit
RCBTC DC resistance of circuit breaker trip coil
UCBTC (LOW) Maximum voltage on the circuit breaker trip coil that does not lead to tripping

If the calculation results that Rmax < Rmin, then the calculation must be repeated, with
the next lowest switching threshold UBI min, and this threshold must be implemented
in the relay using plug-in bridges (see Sub-section 8.1.3).
For the power consumption of the resistance:
U CTR 2
P R = I ⋅ R =  ---------------------------- ⋅ R
2
 R + R CBTC

7SD610 Manual 8-7


C53000-G1176-C145-1
Installation and Commissioning

Example:
IBI (HIGH) 1.7 mA (from SIPROTEC® 7SD610)
UBI min 19 V for delivery setting for nominal voltage 24/48/60 V
88 V or delivery setting for nominal voltage 110/125/220/250 V
UCTR 110 V from trip circuit (control voltage)
RCBTC 500 Ω from trip circuit (resistance of CB trip coil)
UCBTC (LOW) 2 V from trip circuit (max. voltage not to trip breaker)

R max =  ---------------------------------- – 500 Ω


110 V – 19 V
 1.7 mA 

R min = 500 Ω  ------------------------------ – 500 Ω


110 V – 2 V
 2V 

R max = 53 kΩ

R min = 27 kΩ

R max + R min
R = -------------------------------- = 40 kΩ
2

The closest standard value of 39 kΩ is selected; the power is:


2
P R =  ---------------------------------------- ⋅ 39 kΩ
110 V
 39 kΩ + 0.5 kΩ

P R ≥ 0.3 W

8-8 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

8.1.3 Hardware Modifications

8.1.3.1 General

Hardware modifications might be necessary or desired. For example, a change of the


pick-up threshold for some of the binary inputs might be advantageous in certain ap-
plications. Terminating resistors might be required for the communication bus. In ei-
ther case, hardware modifications are needed. If modifications are done or interface
modules are replaced, please observe the details in Subsections 8.1.3.2 to 8.1.3.5.

Power Supply There are different input ranges for the power supply voltage. Refer to the data for the
Voltage 7SD610 ordering numbers in Section A.1 of Appendix A. The power supplies with the
ratings 60/110/125 VDC and 110/125/220/250 VDC / 115 VAC are interconvertible.
Jumper settings determine the rating. The assignment of these jumpers to the supply
voltages are illustrated below in Section 8.1.3.3 under subtitle “Processor board CPU”.
When the relay is delivered, these jumpers are set according to the name-plate stick-
er. Generally, they need not be altered.

Nominal Currents Jumper settings determine the rating of the current input transducers of the device.
When the relay is delivered, these jumpers are set according to the name-plate sticker
to 1 A or 5 A. The physical arrangements of these jumpers that correspond to the dif-
ferent current ratings are described below in Section 8.1.3.3 under subtitle „Input/Out-
put Board I/O–11“.

Note:
If nominal current ratings are changed exceptionally, then the new ratings must be re-
corded under address  &76(&21'$5< in the 3RZHU6\VWHP'DWD
36\VWHP'DWD (see Sub-section 6.1.1).

Control Voltages When the device is delivered from the factory, the binary inputs are set to operate with
for Binary Inputs a voltage that corresponds to the rated voltage of the power supply. In general, to op-
timize the operation of the inputs, the pick-up voltage of the inputs should be set to
most closely match the actual control voltage being used. Each binary input has a
pick-up voltage that can be independently adjusted; therefore, each input can be set
according to the function performed.
A jumper position is changed to adjust the pick-up voltage of a binary input. The phys-
ical arrangement of the binary input jumpers in relation to the pick-up voltages is ex-
plained below in Section 8.1.3.3 under “Processor board CPU” and “Input/Output
Board I/O–11”.

Note:
If the 7SD610 performs trip circuit monitoring, two binary inputs, or one binary input
and a resistor, are connected in series. The pick-up voltage of these inputs must be
less than half of the nominal DC voltage of the trip circuit.

7SD610 Manual 8-9


C53000-G1176-C145-1
Installation and Commissioning

Interface Modules The serial interface modules can be replaced. Which kind of interfaces and how the
interfaces can be replaced is described in „Interface Modules”, Section 8.1.3.4.

Termination of If the device is equipped with a serial RS 485 port, the RS 485 bus must be terminated
Serial Interfaces with resistors at the last device on the bus to ensure reliable data transmission. For
this purpose, terminating resistors are provided on the CPU–board and on the inter-
face modules. The physical arrangement and jumper positions on the CPU–board are
explained in Subsection 8.1.3.3 under “Processor board CPU”, for the interface mod-
ules see Subsection 8.1.3.4 under “Serial Interfaces with Bus Capability”.
As delivered from the factory, the resistors are switched out.

8.1.3.2 Disassembling the Device

If changes to jumper settings are required to modify the rating of the power supply, the
nominal rating of the current inputs, the pick-up voltage of binary inputs, or the state
of the terminating resistors, proceed as follows:

Caution!
Jumper-setting changes that affect nominal values of the device render the ordering
number and the corresponding nominal values on the nameplate sticker invalid. If
such changes are necessary, the changes should be clearly and fully noted on the de-
vice. Self-adhesive stickers are available that can be used as replacement stickers.

o Prepare area of work. Provide a grounded mat for protecting components subject to
damage from electrostatic discharges (ESD). The following equipment is needed:
− screwdriver with a 5 to 6 mm wide tip,
− 1 Philips screwdriver,
− 4.5 mm socket or nut driver.
o Unfasten the screw-posts of the D-subminiature connector on the back panel at loca-
tion “A”.
This activity does not apply if the device is for surface mounting.
o If the device has more communication interfaces on the rear, the screws located diag-
onally to the interfaces must be removed.
This activity is not necessary if the device is for surface mounting.
o Remove the four caps on the front cover and loosen the screws that become accessi-
ble.
o Carefully pull off the front cover. The front cover is connected to the CPU board with
a short ribbon-cable.
o Refer to Figures 8-5 for the physical arrangement of the printed boards.

8-10 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Caution!
Electrostatic discharges through the connections of the components, wiring, plugs,
and jumpers must be avoided. Wearing a grounded wrist strap is preferred. Otherwise,
first touch a grounded metal part.

o At one end, disconnect the ribbon-cable between the front cover and the CPU board
(å). To disconnect the cable, push up the top latch of the plug connector and push
down the bottom latch of the plug connector. Carefully set aside the front cover.
o Disconnect the ribbon-cables between the CPU board (å) and the I/O-11 board ().
o Remove the boards and set them on the grounded mat to protect them from electro-
static damage. A greater effort is required to withdraw the CPU board, especially in
versions of the device for surface mounting, because of the plug connectors.
o Check the jumpers according to Figures 8-6 to 8-10 and the following notes. Change
or remove the jumpers as necessary.

The order of the boards is shown in Figure 8-5.

1 Processor printed circuit board CPU


Prozessorbaugruppe
with power supply
2 Input/output printed circuit board I/O-11

Slot 5 Slot 19
1 2
BI1 to BI6 and Binary inputs (BI)
BI5 BI7
Figure 8-5 Front view of the device after removal of the front cover (simplified and scaled
down)

7SD610 Manual 8-11


C53000-G1176-C145-1
Installation and Commissioning

8.1.3.3 Jumper Settings on Printed Circuit Boards

Processor board The design of a jumper setting for the processor board CPU is shown in Figure 8-6.
CPU The preset rated voltage of the integrated power supply is checked according to Table
8-2, the quiescent state of the life contact is checked according to Table 8-3, the pick-up
voltages of the binary inputs BI1 through BI5 are checked according to Table 8-4, and
the integrated RS232/RS485 interface is checked according to Tables 8-5 to 8-7.
Before the jumpers of the RS232/RS485 can be checked, the interface modules (if
available) must be removed.

3
2
1
X51
F1

X40
1
3
X53

2
1
2

3
1
2
X55

4
2
4
2
X22

X21
3
1
3
1
X52
3 4
2
1

4
2
4
2
4
2
X25

X23
3
1
3
1
3
1
X24

X104
X106
1
2
3

X107

X111
X110
Service
321 321

108 interface
321
3X
1
2

(Port C)
3 2 1 X103

X105
X90
123

X109

Operator
interface Time
synchronization
(Port A)

+ –
G1

Figure 8-6 Processor board CPU with representation of the jumper settings required for the
module configuration

8-12 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Table 8-2 Jumper settings for the nominal voltage of the integrated power supply on the
processor board

Jumper Nominal voltage


DC 60/110/125 V DC 110/125/220/250 V DC 24/48 V
AC 115 V
X51 1–2 2–3
X52 1–2 and 3–4 2–3 not fitted
X53 1–2 2–3
X55 not fitted 1–2
Can be interchanged Not changeable

Table 8-3 Jumper setting for the quiescent state of the life contact on the processor
board CPU
Jumper Open in the quiescent state Closed in the quiescent state Presetting
X40 1–2 2–3 2–3

Table 8-4 Jumper settings for the pick-up voltages of the binary inputs BI1 through BI5
on the processor board CPU

Binary Inputs Jumper 19 VDC Pick-up 1) 88 VDC Pick-up 2)


BI1 X21 1–2 2–3
BI2 X22 1–2 2–3
BI3 X23 1–2 2–3
BI4 X24 1–2 2–3
BI5 X25 1–2 2–3
1) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC

RS485 interface can be changed to RS232 interface and versa by setting of jumpers.
Jumpers X105 through X110 must be set on the same position!

Table 8-5 Jumper setting for the RS232/RS485 service interface on the processor board
CPU

Jumper RS232 RS485


X103 and X104 1–2 1–2
X105 to X110 1–2 2–3

When the device is delivered from the factory, the jumper setting corresponds to the
configuration ordered.

7SD610 Manual 8-13


C53000-G1176-C145-1
Installation and Commissioning

Table 8-6 Jumper setting for the CTS (Clear-To-Send) on the processor board CPU

Jumper /CTS from RS232 interface /CTS controlled by /RTS


X111 1–2 2–3

When the device is delivered from the factory, the jumper setting corresponds to the
configuration ordered.
With RS232 (12th digit of ordering code = 0, 1): position 1–2
With RS485 (12th digit of ordering code = 2: position 2–3
Jumper X90 has no function. It is set 1–2.
The last device on a serial RS 485 bus must be terminated with resistors via the jump-
ers X103 and X104 unless they are terminated by external means.

Table 8-7 Jumper setting for the termination resistors o the RS485 port on the processor
board CPU

Jumper Termination resistor Termination resistor as delivered


effective (on) ineffective (off)
X103 2–3 1–2 1–2
X104 2–3 1–2 1–2

Note: Both jumpers X103 and X104 must be set on the same position!
Terminating resistors can also be implemented outside the device (e.g. in the plug
connectors, see Table 8-11 for pin-assignment) as shown in Figure 8-7. In that case
the terminating resistors provided on the interface card or on the processor board CPU
must be switched out (X103 and X104 in position 1–2).

+5 V
392 Ω
A/A´
221 Ω
B/B´
392 Ω

Figure 8-7 External terminating resistors

8-14 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Input/Output Board The design of a jumper setting for the input/output board I/O–11 is shown in Figure 8-
I/O–11 8. The pick-up voltages of the binary inputs BI6 and BI7 are controlled according to
Table 8-8.

LMH
X21
1

LMH
X60 X22
3
2
1
5A
1A

1A 5A
1 2 3
X61

T10 T9
X62
X73 X72 X71

(AD2)
1A 5A
1
2
3

1 2 3

(AD1)
1
2
3

(AD0)
L
H

X63

T11 T8
1A 5A

1 2 3

X64

X65
IEE IE
1A 5A
1 2 3

Figure 8-8 Input/output board I/O–11 with representation of the jumper settings re-
quired for the module configuration

7SD610 Manual 8-15


C53000-G1176-C145-1
Installation and Commissioning

Table 8-8 Jumper settings for the pick-up voltages of the binary inputs BI6 and B7 on the
input/output board I/O–11

Binary Inputs Jumper 19 VDC Pick-up 1) 88 VDC Pick-up 2)


BI6 X21 1–2 2–3
BI7 X22 1–2 2–3
1
) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC

The preset rated currents of the current transformer are checked on the input/output
board I/O–11. All jumpers must be set unitary for one rated current, i.e. one jumper
(X61 to X64) for each current transformer, additionally there is one common jumper
X60.
The jumper X65 is in position “IE”.

Jumpers X71, X72 and X73 on the input/output board I/O–11 are used to set the bus
address and must not be changed. Table 8-9 shows the factory setting of the jumpers.

Table 8-9 Factory jumper setting for module identification on the input/output board I/O–11

Jumper Presetting
X71 1–2 (H)
X72 1–2 (H)
X73 2–3 (L)

8-16 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

8.1.3.4 Interface Modules

The interface modules are located on the processor board CPU (å in Figure 8-5). Fig-
ure 8-9 shows the CPU board and the location of the interface modules.

Port
(Rear Side)

D
Protection Data Interface 1

System Interface
B

Figure 8-9 Processor board CPU with interface modules

Serial Interfaces Using interfaces with bus capability requires a termination for the last device at the
with Bus Capability bus, i.e. terminating resistors must be switched to the line. Talking about the 7SD610
this refers to the version with the RS485 interface.
The terminating resistors are connected to the corresponding interface module that is
mounted to the processor input/output board CPU (å in Figure 8-5). Figure 8-9 shows
the printed circuit board of the CPU and the allocation of the modules.

7SD610 Manual 8-17


C53000-G1176-C145-1
Installation and Commissioning

The module for the RS485 interface is illustrated in Figure 8-10. When it leaves the
facilities the jumpers are set in such a way that the terminating resistors are switched
off. The two jumpers of a module must always be plugged in the same direction.
Terminating resistors can also be implemented outside the device (e.g. in the plug
connectors). In that case the terminating resistors provided on the interface card or on
the processor board CPU must be switched out.

1 2 3
X3

8X
1 X6
2 X7
Terminating resistors 3 X4
X12 X5
Jumper 1 2 3 1 2 3
Connected Disconnected 1

X11
2
X3 2-3 1-2*) 3
X10
1 2 3 1
X4 2-3 1-2*) 2
3
*) Factory Setting

X13
C53207-
A324-B180

Figure 8-10 Location of the jumpers for the terminating resistors of the RS485–interface
module

Terminating resistors can also be implemented outside the device (e.g. in the plug
connectors, see Table 8-11 for pin-assignment) as shown in Figure 8-7. In that case
the terminating resistors provided on the interface card must be switched out (X3 and
X4 inposition 1–2).

Replacing The interface modules can be replaced. Figure 8-9 shows the printed circuit board
Interface Modules CPU and the interface modules. The ordering numbers of the exchange modules are
listed in Appendix A.1.1, (Accessories).
Please note the following:
• Interface modules can only be exchanged for devices with flush mounting housing.
Interface modules for devices with surface mounting housing must be exchanged
in our manufacturing centre.
• Use only interface modules that can be ordered as an option of the device (see also
Appendix A.1).
• With interfaces with bus capability, ensure that the bus termination is correct; see
head margin “Serial Interfaces with Bus Capability” above (page 8-17).

8-18 7SD610 Manual


C53000-G1176-C145-1
Mounting and Connections

Table 8-10 Exchange interface modules for devices with flush mounting housing

Interface Mounting Location Exchange Module


RS232
System Interface B RS485
LWL 820 nm
Protection Data Interface 1 D FO5 to FO8

8.1.3.5 To Reassemble the Device

To reassemble the device, proceed as follows:


o Carefully insert the boards into the housing. The installation locations of the boards
are shown in Figure 8-5.
For the model of the device designed for surface mounting, use the metal lever to in-
sert the CPU board. The installation is easier with the lever.
o First insert the plug connectors on the ribbon cable in the input/output board I/O–11
and then on the processor board CPU. Be careful not to bend any of the connecting
pins! Do not use force!
o Insert the plug connector of the ribbon cable between the processor board CPU and
the front cover in the socket on the front cover.
o Press the latches of the plug connectors together.
o Replace the front cover and secure to the housing with the screws.
o Replace the covers.
o Re-fasten the interfaces on the rear of the device housing.
This activity is not necessary if the device is for surface mounting.

7SD610 Manual 8-19


C53000-G1176-C145-1
Installation and Commissioning

8.2 Checking the Connections

8.2.1 Data Connections

The following tables list the pin-assignments for the various serial interfaces of the de-
vice and the time synchronization interface.

PC Operating Inter- When the recommended communication cable is used, correct connection between
face at Front the SIPROTEC® device and the PC is automatically ensured. See the Appendix A,
Subsection A.1.1 for an ordering description of the cable.

System (SCADA) When a serial interface of the device is connected to a central substation control sys-
Interface tem, the data connection must be checked. A visual check of the transmit channel and
the receive channel is important. Each connection is dedicated to one transmission di-
rection. The data output of one device must be connected to the data input of the other
device, and vice versa.
The data cable connections are designated in sympathy with DIN 66020 and ISO
2110 (see also Table 8-11):
− TxD data transmit
− RxD data receive
− RTS request to send
− CTS clear to send
− DGND signal/chassis ground
The cable shield is to be grounded at only both ends.
The physical arrangement of the connectors is illustrated in Subsection 2.1.5, Figure
2-14.

Table 8-11 Pin-assignment of the D-subminiature ports

Pin No. Operating RS232 RS485 RS485


interface
1 Shield (with shield ends electrically connected)
2 RxD RxD – –
3 TxD TxD A/A' (RxD/TxD–N) B/B' (RxD/TxD–P)
4 – – – CNTR–A (TTL)
5 DGND DGND C/C' (DGND) C/C' (DGND)
6 – – – +5 V (max. load 100 mA)
7 RTS RTS –*) –
8 CTS CTS B/B' (RxD/TxD–P) A/A' (RxD/TxD–N)
9 – – – –

*) Pin 7 also may carry the RS232 RTS signal to an RS485 interface. Pin 7 must therefore
not be connected!

8-20 7SD610 Manual


C53000-G1176-C145-1
Checking the Connections

RS 485 The RS485 interface is capable of half-duplex service with the signals A/A’ and B/B’
Termination with a common relative potential C/C’ (DGND). Verify that only the last device on the
bus has the terminating resistors connected, and that the other devices on the bus do
not. Jumpers for the terminating resistors are on the processor p.c.b. (see Figure 8-6)
and/or an the interface modules RS 485 (Figure 8-10). It is also possible that the ter-
minating resistors are arranged externally (Figure 8-7).
If the bus is extended, make sure again that only the last device on the bus has the
terminating resistors switched in, and that all other devices on the bus do not.

Time Either 5 VDC, 12 VDC or 24 VDC time synchronization signals can be processed if the
Synchronization connections are made as indicated in Table 8-12.
Interface

Table 8-12 Pin-assignment for the D-subminiature port of the time synchronization
interface
Pin-No. Designation Signal meaning
1 P24_TSIG Input 24 V
2 P5_TSIG Input 5 V
3 M_TSIG Return Line
4 M_TSYNC*) Return Line*)
5 Screen Shield potential
6 – –
7 P12_TSIG Input 12 V
8 P_TSYNC*) Input 24 V*)
9 Screen Shield potential

*) occupied, but must not be connected

Optical Fibres Refer to Subsection 8.2.2 for differential protection communication.


For the system (SCADA) interface, signals transmitted over optical fibres are unaffect-
ed by interference. The fibres guarantee electrical isolation between the connections.
Transmit and receive connections are identified with the symbols for transmit
and for receive.
The character idle state for the optical fibre interface is “Light off.” If this setting is to
be changed, use the operating program DIGSI® 4, as described in Section 5.4.

Warning!
Laser injection! Do not look directly into the fibre-optic elements!

7SD610 Manual 8-21


C53000-G1176-C145-1
Installation and Commissioning

8.2.2 Checking the Differential Protection Communication

The differential protection communication is conducted either directly from device to


device via optical fibres or via communication converters and a communication net-
work or a dedicated transmission medium.

Optical Fibres The direct optical fibre connection is visually checked like the other optical fibre con-
nections. There is one connection for each direction. Therefore the output of the one
device must be connected to the input of the other device and vice versa. Transmis-
sion and receiving connections are identified with the symbols for transmit
and for receive. The visual check of the assignment of the transmission and
receive channels is relevant. For use of the FO5–modules and the recommended fibre
type for short distances, laser class 1 is valid. Higher laser powers can occur in other
cases.

Warning!
Laser injection! Do not look into the LEDs or fibre-optic elements! Do not use optical
instruments! Laser class 3A according to EN 60825–1.

Communication Optical fibres are usually used for the connections between the devices and commu-
Converter nication converters. The optical fibres are checked in the same manner as the optical
fibre direct connections.
Set address  &211(&29(5 (see also Section 6.4.2) to configure the correct
type of connection.

Further For further connections a visual control is sufficient for the time being. Electrical and
connections functional controls are done during commissioning (Section 8.3.5).

8.2.3 Checking Power Plant Connections

Warning!
Some of the following test steps will be carried out in presence of hazardous voltages.
They shall be performed only by qualified personnel which is thoroughly familiar with
all safety regulations and precautionary measures and pay due attention to them.

Caution!
Operating the device on a battery charger without a connected battery can lead to un-
usually high voltages and consequently, the destruction of the device. For limit values
see Sub-section 10.2.1 under Technical Data.

8-22 7SD610 Manual


C53000-G1176-C145-1
Checking the Connections

Before the device is energized for the first time, the device should be in the final oper-
ating environment for at least 2 hours to equalize the temperature and to minimize hu-
midity and avoid condensation. Connection are checked with the device at its final lo-
cation. The plant must first be switched off and grounded.
o Protective switches (e.g. test switches, fuses, or miniature circuit breakers) for the
power supply and the measured voltages must be opened.
o Check the continuity of all current and voltage transformer connections against the
system and connection diagrams:
q Are the current transformers grounded properly?
q Are the polarities of the current transformers the same?
q Is the phase relationship of the current transformers correct?
q Are the voltage transformers grounded properly (if used)?
q Are the polarities of the voltage transformers correct (if used)?
q Is the phase relationship of the voltage transformers correct (if used)?
q Is the polarity for current input I4 correct (if used)?
q Is the polarity for voltage input U4 correct (if used, e.g. with open delta winding)?
o Check the functions of all test switches that may be installed for the purposes of sec-
ondary testing and isolation of the device. Of particular importance are test switches
in current transformer circuits. Be sure these switches short-circuit the current trans-
formers when they are in the test mode (open).
o The short-circuit feature of the current circuits of the device are to be checked. An
ohmmeter or other test equipment for checking continuity is needed.
q Remove the front panel of the device (see Figure 8-5).
q Remove the ribbon cable connected to the I/O–11 board ( in Figure 8-5), and pull
the board out until there is no contact between the board and the rear connections
of the device.
q At the terminals of the device, check continuity for each pair of terminals that re-
ceives current from the CTs.
q Firmly re-insert the I/O–11 board. Carefully connect the ribbon cable. Do not bend
any connector pins! Do not use force!
q Check continuity for each of the current terminal-pairs again.
q Attach the front panel and tighten the screws.
o Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A
to 5 A for the meter is appropriate.
o Close the protective switches to apply voltage to the power supply. Check the polarity
and magnitude of the voltage at the device terminals.
o The measured steady-state current should correspond to the quiescent power con-
sumption of the device. Transient movement of the ammeter merely indicates the
charging current of capacitors.
o Remove the voltage from the power supply by opening the protective switches.
o Disconnect the measuring equipment; restore the normal power supply connections.

7SD610 Manual 8-23


C53000-G1176-C145-1
Installation and Commissioning

o Apply voltage to the power supply.


o Close the protective switches for the voltage transformers (if used).
o Verify that the voltage phase rotation at the device terminals is correct.
o Open the protective switches for the voltage transformers (if used) and the power sup-
ply.
o Check the trip circuits to the power system circuit breakers.
o Check the close circuits to the power system circuit breakers (if used).
o Verify that the control wiring to and from other devices is correct.
o Check the signalling connections.
o Close the protective switches to apply voltage to the power supply.
o If communication converters are used, check the auxiliary voltage supply for the com-
munication converters.
o If the communication converter is connected to the communication network, its
“device-ready”-relay (DR) picks up. This also signalizes that the clock pulse of the
communication network is recognized. Further checks are performed according to
Subsection 8.3.5.
o Please also observe carefully the documentation on the communication converter.

8-24 7SD610 Manual


C53000-G1176-C145-1
Commissioning

8.3 Commissioning

Warning!
Hazardous voltages are present in this electrical equipment during operation. Non–
observance of the safety rules can result in severe personal injury or property dam-
age.
Only qualified personnel shall work on and around this equipment after becoming thor-
oughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
Particular attention must be drawn to the following:
• The earthing screw of the device must be connected solidly to the protective earth
conductor before any other electrical connection is made.
• Hazardous voltages can be present on all circuits and components connected to the
supply voltage or to the measuring and test quantities.
• Hazardous voltages can be present in the device even after disconnection of the
supply voltage (storage capacitors!).
• The limit values stated in the Technical data (Chapter 10) must not be exceeded at
all, not even during testing and commissioning.

When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip and
close commands to the circuit breakers and other primary switches are disconnected
from the device unless expressly stated.

DANGER!
Current transformer secondary circuits must have been short-circuited before
the current leads to the device are disconnected!
If test switches are installed that automatically short-circuit the current transformer
secondary circuits, it is sufficient to place them into the “Test” position provided the
short-circuit functions has been previously tested.

For the commissioning switching operations have to be carried out. A prerequisite for
the prescribed tests is that these switching operations can be executed without dan-
ger. They are accordingly not meant for operational checks.

Warning!
Primary tests must only be carried out by qualified personnel, who are familiar with the
commissioning of protection systems, the operation of the plant and the safety rules
and regulations (switching, earthing, etc.).

7SD610 Manual 8-25


C53000-G1176-C145-1
Installation and Commissioning

8.3.1 Testing mode and transmission blocking

If the device is connected to a substation control system or a server, the user is able
to modify, in some protocols, information that is transmitted to the substation (see Sec-
tion A.5 “Protocol Dependent Functions” in Appendix A).
In the WHVWLQJPRGH all messages sent from a SIPROTEC®4–device to the substa-
tion are marked with an extra test bit so that the substation is able to identify them as
messages announcing no real faults. Furthermore the WUDQVPLVVLRQEORFNLQJ
function leads to a total blocking of the message transmission process via the system
interface in the testing mode.
Refer to Subsection 7.2.3 to know how the testing mode and the transmission blocking
can be enabled and disabled. Please note that it is necessary to be 2QOLQH during
the configuration of the device with DIGSI® 4 to be able to use the testing mode.

8.3.2 Checking the System (SCADA) Interface

Preliminary Provided that the device is equipped with a system (SCADA) interface that is used for
Notes the communication with a substation, it is possible to test via the DIGSI® 4 operational
function if messages are transmitted correctly. Do not apply this test feature while the
device is in service on a live system!

DANGER!
The transmission and reception of messages via the system (SCADA) interface
by means of the testing mode is the real exchange of information between the
SIPROTEC®4 device and the substation. Connected equipment such as circuit
breakers or disconnectors can be operated as a result of these actions!

Note:
After termination of this test, the device will reboot. All annunciation buffers are
erased. If required, these buffers should be extracted with DIGSI® 4 prior to the test.

The system interface test is carried out 2QOLQH using DIGSI® 4:


q Double-click on the 2QOLQH directory to open the required dialogue box.
q Click on 7HVW and the functional options appear on the right side of the window.
q Double-click on 7HVWLQJ0HVVDJHVIRU6\VWHP,QWHUIDFH shown in the list
view. The dialogue box *HQHUDWH,QGLFDWLRQV opens (refer to Figure 8-11).

Structure of the In the column ,QGLFDWLRQ, all message texts that were configured for the system in-
Dialogue Box terface in the matrix will then appear. In the column 6WDWXV6FKHGXOHG the user has
to define the value for the messages to be tested. Depending on the type of message
different entering fields are available (e.g. message 21 / message 2))). By double-
clicking onto one of the fields the required value can be selected from the list.

8-26 7SD610 Manual


C53000-G1176-C145-1
Commissioning

Figure 8-11 Dialogue box: Generate indications

Changing the Clicking for the first time onto one of the field in column $FWLRQ you will be asked for
Operating State password no. 6 (for hardware test menus). Having entered the correct password mes-
sages can be issued. To do so, click on 6HQG. The corresponding message is issued
and can be read out either from the event log of the SIPROTEC®4 device as well as
from the central master computer.
As long as the windows is open, further tests can be performed.

Test in Message For all information that is transmitted to the central station the following is to be
Direction checked under 6WDWXV6FKHGXOHG
q Make sure that each checking process is carried out carefully without causing any
danger (see above and refer to DANGER!)
q Click on 6HQG and check whether the transmitted information reaches the central
station and shows the desired reaction.

Test in Command The information beginning with “>” is transmitted towards the device. This kind of in-
Direction formation must be sent by the central station. Check whether the reaction is correct.
f

Exiting the Test To end the system interface test, click on &ORVH. The device is briefly out of service
Mode while the processor system starting up. The dialogue box closes.

7SD610 Manual 8-27


C53000-G1176-C145-1
Installation and Commissioning

8.3.3 Checking the Binary Inputs and Outputs

Preliminary Notes The binary inputs, outputs, and LEDs of a SIPROTEC®4 device can be individually
and precisely controlled using DIGSI® 4. This feature is used to verify control wiring
from the device to plant equipment (operational checks), during commissioning. This
test feature shall not be used while the device is in service on a live system.

DANGER!
Changing the status of a binary input or output using the test feature of DIGSI® 4
results in an actual and immediate corresponding change in the SIPROTEC ® de-
vice. Connected equipment such as circuit breakers or disconnectors will be
operated as a result of these actions!

Note: After termination of the hardware test, the device will reboot. Thereby, all annun-
ciation buffers are erased. If required, these buffers should be extracted with DIGSI® 4
prior to the test.
The hardware test can be done using DIGSI® 4 in the online operating mode:
q Open the 2QOLQH directory by double-clicking; the operating functions for the de-
vice appear.
q Click on 7HVW; the function selection appears in the right half of the screen.
q Double-click in the list view on +DUGZDUH7HVW. The dialogue box of the same
name opens (see Figure 8-12).

Figure 8-12 Dialogue box for hardware test — example

8-28 7SD610 Manual


C53000-G1176-C145-1
Commissioning

Structure of the The dialogue box is divided into three groups: %, for binary inputs, 5(/ for output re-
Test Dialogue Box lays, and /(' for light-emitting diodes. Each of these groups is associated with an ap-
propriately marked switching area. By double-clicking in an area, components within
the associated group can be turned on or off.
In the 6WDWXV column, the present (physical) state of the hardware component is dis-
played. The binary inputs and outputs are indicated by an open or closed switch sym-
bol, the LEDs by a dark or illuminated LED symbol.
The possible intended condition of a hardware component is indicated with clear text
under the 6FKHGXOH column, which is next to the 6WDWXV column. The intended con-
dition offered for a component is always the opposite of the present state.
The right-most column indicates the commands or messages that are configured
(masked) to the hardware components.

Changing the To change the condition of a hardware component, click on the associated switching
Hardware field in the 6FKHGXOH column.
Conditions
Password No. 6 (if activated during configuration) will be requested before the first
hardware modification is allowed. After entry of the correct password a condition
change will be executed.
Further condition changes remain possible while the dialog box is open.

Test of the Binary Each individual output relay can be energized allowing a check of the wiring between
Outputs the output relay of the 7SD610 and the plant, without having to generate the message
that is assigned to the relay. As soon as the first change of state for any one of the
output relays is initiated, all output relays are separated from the internal device func-
tions, and can only be operated by the hardware test function. This implies that a
switching signal to an output relay from e.g. a protection function or control command
cannot be executed.
q Ensured that the switching of the output relay can be executed without danger (see
above under DANGER!).
q Each output relay must be tested via the corresponding 6ROO–cell in the dialog box.
q The test sequence must be terminated (refer to margin heading “Exiting the Proce-
dure”), to avoid the initiation of inadvertent switching operations by further tests.

Test of the Binary To test the wiring between the plant and the binary inputs of the 7SD610 the condition
Inputs in the plant which initiates the binary input must be generated and the response of the
device checked.
To do this, the dialogue box +DUGZDUH7HVW must again be opened to view the phys-
ical state of the binary inputs. The password is not yet required.
q Each state in the plant which causes a binary input to pick up must be generated.
q The response of the device must be checked in the 6WDWXV–column of the dialogue
box. To do this, the dialogue box must be updated. The options may be found below
under the margin heading “Updating the Display”.
If however the effect of a binary input must be checked without carrying out any switch-
ing in the plant, it is possible to trigger individual binary inputs with the hardware test
function. As soon as the first state change of any binary input is triggered and the

7SD610 Manual 8-29


C53000-G1176-C145-1
Installation and Commissioning

password nr. 6 has been entered, all binary inputs are separated from the plant and
can only be activated via the hardware test function.
q Terminate the test sequence (see above under the margin heading „Exiting the Pro-
cedure“).

Test of the LED’s The LED’s may be tested in a similar manner to the other input/output components.
As soon as the first state change of any LED has been triggered, all LEDs are sepa-
rated from the internal device functionality and can only be controlled via the hardware
test frunction. This implies that no LED can be switched on anymore by e.g. a protec-
tion function or operation of the LED reset key.

Updating the When the dialog box +DUGZDUH7HVW is opened, the present conditions of the hard-
Display ware components at that moment are read in and displayed. An update occurs:
− for each harware component, if a command to change the condition is successfully
performed,
− for all hardware components if the 8SGDWH button is clicked,
− for all hardware components with cyclical updating if the $XWRPDWLF8SGDWH
VHF field is marked.

Exiting the To end the hardware test, click on &ORVH. The dialog box closes. The device becomes
Procedure unavailable for a brief start-up period immediately after this. Then all hardware com-
ponents are returned to the operating conditions determined by the plant settings.

8.3.4 Checking for Breaker Failure Protection

If the device is equipped with the breaker failure protection and this function is used,
the interaction with the breakers of the power plant must be tested.
Because of the manifold application facilities and various configuration possibilities of
the power plant it is not possible to give detailed description of the test steps neces-
sary to verify the correct interaction between the breaker failure protection and the
breakers. It is important to consider the local conditions and the protection and plant
drawings.
It is advised to isolate the circuit breaker of the tested feeder at both sides, i.e. to keep
the busbar disconnector and the line disconnector open, in order to ensure operation
of the breaker without risk.

Caution!
Tripping of the complete busbar or busbar section may occur even during tests at the
local feeder breaker. Therefore, it is recommended to interrupt the tripping commands
to the adjacent (busbar) breakers e.g. by switch-off of the associated control voltage.
Nevertheless ensure that trip remains possible in case of a real primary fault if parts
of the power plant are in service.

8-30 7SD610 Manual


C53000-G1176-C145-1
Commissioning

The trip command of the tested differential protection is made ineffective so that the
local breaker can be tripped only by the breaker failure protection function.
The following lists do not claim to cover all possibilities. On the other hand, they may
contain items that can be bypassed in the actual application.

Circuit Breaker The circuit breaker auxiliary contact(s) form an essential part of the breaker failure pro-
Auxiliary Contacts tection system in case they have been connected to the device. Make sure that the
correct assignment has been checked (Subsection 8.3.3).

External Initiation If the breaker failure protection is intended to be initiated by external protection devic-
Conditions es, each of the external initiation conditions must be checked. Depending on the de-
vice version and the setting on the breaker failure protection, single-pole trip or single-
and three-pole trip are possible. Note that the internal pole discrepancy supervision or
the pole discrepancy supervision of the breaker itself may lead to a later three-pole trip
after single-pole trip during the tests. Reconsider the settings of the breaker failure
protection and its ancillary functions. Refer to Subsection 6.10.2 (addresses 
etc.) if more information is desired.
At least the tested phase of the device must be subjected to a test current to enable
initiation of the breaker failure protection. This may be a secondary injected current.
Following every initiation the message “%)6WDUW” (FNo ) must appear in the
fault annunciations (trip log) or in the spontaneous messages.
The following applies for phase segregated initiation:
q Start by single-pole trip command L1 of the external protection:
Binary inputs “!%)6WDUW/” (FNo ) and if necessary “!%)UHOHDVH” (FNo
); look up in the trip log or spontaneous messages.
Trip command depending on the settings.
q Start by single-pole trip command L2 of the external protection:
Binary inputs “!%)6WDUW/” (FNo ) and if necessary “!%)UHOHDVH” (FNo
); look up in the trip log or spontaneous messages.
Trip command depending on the settings.
q Start by single-pole trip command L3 of the external protection:
Binary inputs “!%)6WDUW/” (FNo ) and if necessary “!%)UHOHDVH” (FNo
); look up in the trip log or spontaneous messages.
Trip command depending on the settings.
q Start by three-pole trip command L1, L2, L3 of the external protection via all three
binary inputs:
Binary inputs “!%)6WDUW/” (FNo ) and “!%)6WDUW/” (FNo ) and
“!%)6WDUW/” (FNo ), and if necessary “!%)UHOHDVH” (FNo ); look
up in the trip log or spontaneous messages.
Trip command three-pole.
The following applies for common phase initiation:
q Start by three-pole trip command L123 of the external protection:
Binary inputs “!%)6WDUWSROH” (FNo ) and if necessary “!%)UHOHDVH”
(FNo ); look up in the trip log or spontaneous messages.
Trip command three-pole (dependent on settings).
Switch off test current.

7SD610 Manual 8-31


C53000-G1176-C145-1
Installation and Commissioning

The following applies if initiation without current flow is possible:


q Start by trip command of the external protection without current flow:
Binary inputs “!%)6WDUWZR,” (FNo ) and if necessary “!%)UHOHDVH”
(FNo ); look up in the trip log or spontaneous messages.
Trip command three-pole (dependent on settings).

Busbar trip The most important thing is the check of the correct distribution of the trip commands
to the adjacent circuit breakers in case the local breaker fails.
The adjacent circuit breakers are those of all feeders which must be tripped in order
to ensure interruption of the fault current should the local breaker fail. In other words,
the adjacent breaker are those of all feeders which may feed the same busbar or bus-
bar section as the faulty feeder.
The identification of the adjacent feeders depends widely on the topology of the bus-
bar and its possible arrangement or switching states. That is why a generally detailed
test description cannot be specified.
In particular if multiple busbars are concerned the trip distribution logic to the other
breakers must be checked. It must be verified for each busbar section that all breakers
connected to the same section are tripped in case the concerned feeder breaker fails,
and no other breakers.

Remote Trip If the trip command of the breaker failure protection or its ancillary functions (e.g. end
fault protection) is intended to trip also the circuit breaker of the remote end of the con-
cerned feeder, the correct transmission and reception of this remote trip must be
checked. Practically, this is performed in conjunction with the transmission checks ac-
cording to Subsection 8.3.8.

Termination of the After completion of the tests, re-establish all provisory measures which might have
Checks been taken for the above tests. Ensure that the states of all switching devices of the
plant are correct, that interrupted trip commands are reconnected and control voltages
are switched on, that setting values which might have been altered are reverted to cor-
rect values, and that protective function are switched to the intended state (on or off).

8.3.5 Checking the Communication Topology

General The communication topology can either be checked from the PC using DIGSI® 4 or a
web browser via the “IBS-Tool”. If you choose to work with the IBS-Tool, please note
the Help files referring to the “IBS-Tool”.
You can either connect the PC to the device locally using the operator interface at the
front, or the service interface at the rear of the device (Figure 8-13). Or you can log
into the device using a modem via the service interface (example in Figure 8-14).
If you use the “IBS-Tool”:

8-32 7SD610 Manual


C53000-G1176-C145-1
Commissioning

q Make sure that the 12-digit IP-address valid for the browser is set correctly accord-
ing to the following format: ***.***.***.***. A three-digit block of the IP address is in-
serted into each address from  to , or 4411to 4414.
q Set the address  or  180/2&. to No, if you are directly interfaced to the
device. You will then have the option to operate the device with the “IBS-Tool”.
q If you are interfaced to the devices via modem you can set the address  or
 180/2&. to No. You will then have the option to access both devices with
the “IBS-Tool”.

7SD610 7SD610

:
Figure 8-13 PC interfacing directly to the device — schematic example

7SD610 7SD610

HP
0RG HP
0RG

: 0RG
HP

Figure 8-14 PC interfacing via modem — schematic example

Checking a For two devices linked with fibre optical cables (as in Figure 8-13 or 8-14), this con-
Connection Using nection is checked as follows.
Direct Link
o Both devices at the link ends have to be switched on.
o Check in the Event Log (see also Subsection 7.1.1.2) or spontaneous annunciations
(see Subsection 7.1.1.6) for the following:
q If the message “3,ZLWK” (protection data interface 1 connected with, FNo. )
is provided with the device index of the other device, a link has been established
and one device has recognized the other.
o In the event of a communication link error the message “3,'DWDIDXOW” (FNo.
) or will be displayed. In this case, check the fibre optical cable link again.

7SD610 Manual 8-33


C53000-G1176-C145-1
Installation and Commissioning

q Have the devices been linked correctly and no cables been interchanged?
q Are the cables free from mechanical damage, intact. and the connectors locked?
q Repeat check if necessary.
Proceed with “Consistency of Topology and Parameterization”.

Checking a If a communication converter is used, please note the instructions enclosed with the
Connection with device. The communication converter has a test setting where its outputs are looped
the Communication back to the inputs.
Converter
Links via the communication converter are tested by means of local loop-back (Figure
8-15, left).

Remote
Local Communication Communication
Converter Converter

optical CC–1 electrical Communication Network electrical CC–2 optical


7SD610 7SD610

local

:
Figure 8-15 Differential protection communication via communication converter and communication network
— schematic example

o Both devices at the link ends have to be switched on.


o First configure the communication converter KU–1:
q Disconnect the auxiliary supply voltage from both poles.

DANGER!
Before opening the communication converter, it is absolutely necessary to iso-
late it from the auxiliary supply voltage at all poles! There is a danger to life by
energized parts!

q Open the communication converter.


q Set the jumpers to the matching position for the correct interface type and transmis-
sion rate; they must be identical with the parameterization of the 7SD610 (address
 &211(&29(5, see also Subsection 6.4.2).
q Move the communication converter into test position (jumper X32 in position 2–3).
q Close the communication converter housing.
o Reconnect the auxiliary supply voltage for the communication converter.
o The communication network (X.21 or G.703.1) must be active and connected to the
communication converter. Check this by means of the “device ready”–contact of the
communication converter (continuity at the NO contact).

8-34 7SD610 Manual


C53000-G1176-C145-1
Commissioning

o If the “device ready”–contact of the communication converter does not close, check
the connection between the communication converter and the net (communication de-
vice). The communication device must emit the correct transmitter clock to the com-
munication converter.
o Change the interface parameters at the 7SD610 (at the device front or via DIGSI® 4):
q Address  &211(&29(5 = F.optic direct.
o Check the Event Log (see also Subsection 7.1.1.2) or spontaneous annunciations
(see also Subsection 7.1.1.6):
q Message  “3,'DWDUHIOHF21” (Protection interface 1 data reflection
ON).
q If the message is not transmitted check for the following:
−- Has the 7SD610 fibre optical transmitting terminal output been correctly
linked with the fibre optical receiving terminal input of the communication
converter and vice versa (No erroneous interchanging)?
−- Does the 7SD610 device have the correct interface module and is it working
correctly?
−- Are the fibre optic cables intact?
−- Are the parameter settings for interface type and transmission rate at the
communication converter correct (see above; note the DANGER instruc-
tion!)?
q Repeat the check after correction if necessary.
o Reset the interface parameters at the 7SD610 correctly:
q Address  &211(&29(5 = required setting.
o Disconnect the auxiliary supply voltage of the communication converter at both poles.
Note the above DANGER instruction!
o Reset the communication converter to normal position (X32 in position 1-2) and close
the housing again.
o Reconnect the supply voltage of the communication converter.
Perform the above check at the other end with the device being connected there and
its corresponding communication converter.
Continue with “Consistency of Topology and Parameterization“.

Consistency of Having performed the above checks, the linking of the device pair — including their
Topology and communication converters if applicable — has been completely tested and connected
Parameterization to auxiliary supply voltage. Now the devices communicate by themselves.
o Now check the Event Log (see also Subsection 7.1.1.2) or spontaneous annunciations
(see also Subsection 7.1.1.6) of the device where you are working:
q Message FNo.  “3,ZLWK” (protection data interface 1 linked with) followed
by the device index of the other device.
q If the devices are connected, the message FNo.  “7RSROFRPSOHWH” (Topol-
ogy complete) will appear.

7SD610 Manual 8-35


C53000-G1176-C145-1
Installation and Commissioning

q And if the device parameterization is also consistent, i.e. the prerequisites for set-
ting the Configuration of the Scope of Functions (Section 5.1), the Power System
Data 1 (6.1.1), the General Protection Data (6.1.3), the settings for Protection Data
Interfaces and Differential Protection Topology (Section 6.4.2) have been consid-
ered, the fault message, i.e. FNo. 3229 “3,'DWDIDXOW” will disappear. The
communication and consistency test has now been completed.
q If the fault message of the interface being checked does not disappear, however,
the fault must be found and eliminated. Table 8-11 lists messages that indicate such
faults.

Table 8-13 Messages announcing inconsistency

FNo Setting Meaning / Measures


3233 DT inconsistent “Device table inconsistent”: the indexing of the devices is in-
consistent (missing numbers or one number used twice,
see Section 6.4.2
3234 DT unequal “Device table unequal”: the ID-numbers of the devices are
unequal (see Section 6.4.2)
3235 Par. different “Parametrization different”: different functional parameters were
set for the devices. They have to be equal at both ends:
Differential protection available or not (see Section 5.1),
Transformer in protected zone or not (see Section 5.1),
Nominal frequency (see Section 6.1.1),
Operational power or current (see Section 6.1.3)

Now, there may be no more fault messages of the protection data interfaces.

“IBS-Tool” The topology can be displayed as a graph on the monitor using the “IBS-Tool”. For this
you need a personal computer and a web browser. Figure 8-16 exemplifies a differen-
tial protection system for two ends. The devices have been properly linked (green
shaded squares) and work as differential protection (Status: Differential Mode). The
PC has been interfaced to the device with index 2 (PC–connected relay). The trans-
mission time between device 2 and device 1 is 0.080 ms.

8-36 7SD610 Manual


C53000-G1176-C145-1
Commissioning

Communication Topology

PC-connected relay
Address: 17 Address: 16

Index: 2 Index: 1
0.080 ms
Status: Status:
Differential Mode Differential Mode

Figure 8-16 Example of a topology with two ends communicating correctly

8.3.6 Checking the Instrument Transformer Connections of One Line End

Should secondary test equipment be connected to the device, it is to be removed or,


if applying, test switches should be in normal operation position.

Note:
It must be taken into consideration that tripping can occur even at the opposite ends
of the protected object, if connections were made wrong.

Before energizing the object to be protected at any end, short-circuit protection must
be ensured at least at the feeding ends. If a separate back-up protection (e.g. overcur-
rent protection) is available, this has to be put into operation and switched to alert first.

Voltage and Rotary If the device has been connected to voltage transformers, these connections are
Field Test checked using primary values. For devices without voltage transformer connection the
rest of this margin header may be omitted.
The voltage transformer connections are individually tested at either end of the object
to be protected. At the other end the circuit breaker remains open first.
o Having closed the local circuit breaker, none of the measurement monitoring functions
in the device may respond.
q If there was a fault message, however, the Event Log (see also Subsection 7.1.1.2)
or spontaneous messages (see also Subsection 7.1.1.6) could be checked to in-
vestigate the reason for it.
q At the indication of symmetry monitoring there might actually be asymmetries of the
primary system. If they are part of normal operation, the corresponding monitoring
function is set less sensitive (see Subsection 6.12.2 under “Voltage Symmetry”,
page 6-118).
The voltages can be read on the display at the front, or called up in the PC via the op-
erator or service interface, and compared with the actual measured quantities as pri-

7SD610 Manual 8-37


C53000-G1176-C145-1
Installation and Commissioning

mary or secondary values (refer to Subsection 7.1.3.1). Apart from the absolute values
of the line-earth and line-line voltages, voltage phase differences are indicated so that
the correct phase sequence and polarity reversal of individual voltage transformers
can be seen. The voltages can also be read with the “IBS-Tool” (see below, “Current
Test”).
o The voltages should be almost equal. All the three angles ϕ(ULx–ULy) must be approx-
imately 120°.
q If the measured quantities are not plausible, the connections must be checked and
revised after switching off the line. If the phase difference angle between two volt-
ages is 60° instead of 120°, one voltage must be polarity-reversed. The same ap-
plies if there are phase-to-phase voltages which almost equal the phase-to-ground
voltages instead of having a value that is √3 greater. The measurements are to be
repeated after setting the connections right.
q In general, the phase rotation is a clockwise phase rotation. If the system has an
counter-clockwise phase rotation, this must go for both ends of the protected object.
The measured value allocation must be checked and corrected, if required, after the
line has been isolated. The phase rotation check must then be repeated.
o Open the miniature circuit breaker of the feeder voltage transformers. The measured
voltages in the operational measured values (Subsection 7.1.3.1) appear with a value
close to zero (small measured voltages are of no concern).
q Check in the event log (Section 7.1.1.2) or spontaneous messages (Section
7.1.1.6) that the VT mcb trip was noticed (message “!)$,/)HHGHU9721”). A
precondition is that the position of the VT mcb is connected to the device via a bi-
nary input.
o Close the VT mcb: The above message appears in the event log as “2))”, i. e.
“!)$,/)HHGHU97 2))”).
q If one of the events does not appear, the connection and routing of these signals
(Subsection 5.2.4) must be checked.
q If the “21”-state and “2))”-state are swapped, the contact type (H-active or L-ac-
tive) must be checked and remedied (Subsection 5.2.4).
o The protected object is switched off.
o The check must be carried out for both ends.

8.3.7 Checking the Instrument Transformer Connections of Both Line Ends

Current Test The connections of the current transformers are tested with primary values. A load
current of at least 5 % of the rated operational current is required. Any direction is pos-
sible.
This test cannot replace visual inspection of the correct current transformer connec-
tions. Therefore, the inspection according to Section 8.2.3. is a prerequisite.
o The current transformer connections are tested at each end of the protected object.
The current flows through the protected object.

8-38 7SD610 Manual


C53000-G1176-C145-1
Commissioning

o After closing the circuit breakers, none of the measured value monitoring functions in
the 7SD610 must respond. However, in the event of a monitoring signal, the reason
for this signal can be investigated in the Event Log (see Section 7.1.1.2) or in the spon-
taneous messages (Section 7.1.1.6).
q If current summation errors occur, check the matching factors (see Section 6.1.1,
“Connection of the Currents”).
q Messages from the symmetry monitoring could occur because there actually are
asymmetrical conditions in the primary system. If they are part of normal operation,
the corresponding monitoring function is set less sensitive (see Section 6.12.2,
“Symmetry Supervision”).
Currents can be viewed as primary or secondary measured values in the front display
panel or via the operator or service interface with a personal computer, and compared
with the actually measured values (see also Section 7.1.3.1). The absolute values as
well as the phase differences of the currents are indicated so that the correct phase
sequence and polarity of individual transformers can also be seen.
The “IBS Tool” provides comfortable read-out possibilities for all measured values with
visualisation using phasor diagrams (Figure 8-17).
o The current amplitudes must be approximately the same. Each one of the three angles
ϕ(ILx–ILy) must be approximately 120°.
q If the measured values are not plausible, the connections must be checked and cor-
rected after switching off the protected object and short-circuiting the current trans-
formers. If, for example, the phase difference between two currents is 60° instead
of 120°, one of the currents must have a reversed polarity. The same is the case, if
a substantial earth current 3I0 occurs:
− 3I0 ≈ phase current ⇒ one or two phase currents are missing,
− 3I0 ≈ doubled phase current ⇒ one or two phase currents have a reversed po-
larity.
o The measurements are to be repeated after setting the connections right.
o The previously stated tests of the measured values are to be repeated at the other end
of the tested current path. The current value of the other end can also be read out lo-
cally as percentage values as well as the phase angles (cf. Subsection 7.1.3).
In the “IBS Tool”, the local and remote measured values can be graphically displayed.
Figure 8-18 shows an example.

7SD610 Manual 8-39


C53000-G1176-C145-1
Installation and Commissioning

Local Measurement – Primary Values

Currents: Voltages:
+90° +90°

±180° 0° ±180° 0°

–90° –90°

Address: 2 Frequency: 50.00 Hz


IL1 = 199.71 A, 0.0 ° UL1E = 132.71 kV, 10.4 °
IL2 = 200.44 A, –119.6 ° UL2E = 133.44 kV, –109.3 °
IL3 = 199.34 A, 120.1 ° UL3E = 132.34 kV, 130.3 °
3I0 = 0.17 A, 159.9 ° 3U0 = 0.00 kV, 0.0 °
Figure 8-17 Local measured values in the “IBS Tool” — example of plausible measured values

Polarity Check If the device is connected with voltage transformers, the local measured values al-
ready provide a polarity test.
A load current of at least 5 % of the rated operational current is required. Any direction
is possible but must be known.
o With closed circuit breakers, the power values can be viewed as primary and second-
ary measured values in the front display panel or via the operator or service interface
with a personal computer (see also Subsection 7.1.3.1).
Here, again, the IBS Tool is a comfortable help as the vector diagrams also show the
correlation between the currents and voltages (Figure 8-18). Cyclically and acyclically
swapped phases can easily be detected.
o With the aid of the measured power values you are able to verify that they correlate to
the load direction, reading either at the device itself or in DIGSI® 4 (Figure 8-19).
P positive, if active power flows into the protected object,
P negative, if active power flows towards the busbar,
Q positive, if (inductive) reactive power flows into the protected object,
Q negative, if (inductive) reactive power flows towards the busbar.

8-40 7SD610 Manual


C53000-G1176-C145-1
Commissioning

Remote Measurement

Currents: Voltages:
+90° +90°

±180° 0° ±180° 0°

–90° –90°

Local Address: 2
IL1L = 24.96 %, 0.0 ° UL1EL = 99.94 %, 10.4 °
IL2L = 25.06 %, –119.9 ° UL2EL = 100.50 %, –109.3 °
IL3L = 24.92 %, 120.1 ° UL3EL = 99.66 %, 130.4 °

Remote Address: 1
IL1R = 23.22 %, 172.2 ° UL1ER = 94.94 %, 4.7 °
IL2R = 23.30 %, 52.4 ° UL2ER = 94.68 %, –115.0 °
IL3R = 23.17 %, –67.7 ° UL3ER = 95.48 %, 124.7 °
Constellation Data:
IdiffL1 = 2.63 % Frequency = 50.00 Hz
IdiffL2 = 3.21 %
IdiffL3 = 2.72 %
Figure 8-18 Local and remote measured values in the “IBS Tool” — examples for plausible measured values

Therefore, the power results and their components must have opposite signs at both
ends.
It must be taken into consideration that high charging currents, which might occur with
long overhead lines or with cables, are capacitive, i.e. correspond to a negative reac-
tive power into the line. In spite of a resistive-inductive load, this may lead to a slightly
negative reactive power at the feeding end whereas the other end shows an increased
negative reactive power. The lower the load current for the test, the higher the signif-
icance of the influence. In order to get unambiguous results, you should increase the
load current if necessary.

7SD610 Manual 8-41


C53000-G1176-C145-1
Installation and Commissioning

P
Positive active power in
the direction of the line
SLoad

jQ

Positive reactive power Negative reactive power


in the direction of the line in the direction of the line

Figure 8-19 Complex (apparent) power

o The power measurement provides an initial indication as to whether the measured val-
ues of one end have the correct polarity.
• If the reactive power is correct but the active power has the wrong sign, cyclic phase
swapping of the currents (right) or of the voltages (left) might be the cause.
• If the active power direction is correct but the reactive power has the wrong sign,
cyclic phase swapping of the currents (left) or of the voltages (right) might be the
cause.
• If both the active power and the reactive power have the wrong sign, the polarity
according to the address  &76WDUSRLQW is to be checked and corrected.
The phase angles between currents and voltages must also be conclusive. Each one
of the three phase angles ϕ (ULx–ILx) must be approximately the same and must rep-
resent the operating status. In the event of power in the direction of the protected ob-
ject, they represent the current phase displacement (cos ϕ positive); in the event of
power in the direction of the busbar they are higher by 180° (cos ϕ negative). However,
charging currents might have to be taken into consideration (see above).
o The measurements may have to be repeated after correction the connections.
o The above described tests of the measured values also have to be performed at the
other end of the tested current path. The current and voltage values as well as the
phase angles of the other end can also be read out locally as percentage values (Sub-
section 7.1.3). Note that currents flowing through the object (without charging cur-
rents) ideally have opposite signs at both ends, i.e. turned by 180°.
In the “IBS Tool” the local and remote measured values can be shown graphically. You
can see an example in Figure 8-18.
o The protected object is now switched off, i.e. the circuit breakers are opened.

Polarity Check for If the standard connection of the device is used whereby the current measuring input
the Current I4 is connected in the starpoint of the set of current transformers (refer also to the con-
Input I4 nection circuit diagram in the Appendix, Figure A-3), then the correct polarity of the
earth current path in general automatically results.
If however the current I4 is derived from a separate summation CT (e.g. a core balance
CT) an additional direction check with this current is necessary.

8-42 7SD610 Manual


C53000-G1176-C145-1
Commissioning

o The test is done with a disconnected trip circuit and primary load current. It must be
noted that during all simulations that do not exactly correspond with cases that may
occur in practice, the non-symmetry of measured values may cause the measured val-
ue monitoring to pick up. These must therefore be ignored during such tests.
.

DANGER!
Working on measurement transformers requires the highest precautions!
Short-circuit the secondary side of the current transformers before any current
connections to the device are opened!

o To generate a displacement voltage, the e–n winding of one phase in the voltage
transformer set (e.g. L1) is bypassed (refer to Figure 8-20). If no connection on the
e–n windings of the voltage transformer is available, the corresponding phase is open
circuited on the secondary side. Via the current path only the current from the current
transformer in the phase from which the voltage in the voltage path is missing, is con-
nected; the other CTs are short-circuited. If the line carries load in the first quadrant,
the protection is in principle subjected to the same conditions that exist during an earth
fault in the direction of the line.
o The same manipulation is carried out with the current and voltage transformers at the
other end.

L1
Bus
L2
bar
L3

(alternatively
disconnect here)

e
bypass one n
phase

Ue Un UL1 UL2 UL3 Un


IL1
IL2
IL3

I4

7SD610

Line
Figure 8-20 Polarity testing for I4, example with current transformers configured in a
Holmgreen connection

o Figure 8-21 illustrates an example corresponding to the circuit in Figure 8-20, when
the current flows in direction of the object to be protected. The currents IL2 and IL3 are
almost zero, an earth current 3I0 of the same value as IL1 appears. Accordingly, the
voltage UL1E is missing and a zero sequence voltage 3U0 appears.

7SD610 Manual 8-43


C53000-G1176-C145-1
Installation and Commissioning

o In the event of a polarity fault, 3I0 is in opposite phase with IL1 or the zero sequence
voltage 3U0 supplements the other two voltages to a (here false) voltage star. Open
the circuit breakers, short-circuit current transformers and set current and voltage
transformer connections right. Repeat test.
o Having finished the test, open all circuit breakers, short-circuit current transformers
and restore current and voltage transformer connections.

Local Measurement – Primary Values

Currents: Voltages:
+90° +90°

±180° 0° ±180° 0°

–90° –90°

Address: 2 Frequency: 50.00 Hz


IL1 = 199.71 A, 0.0 ° UL1E = 0.71 kV, 10.4 °
IL2 = 0.00 A, 0.0 ° UL2E = 133.44 kV, –109.3 °
IL3 = 0.00 A, 0.3 ° UL3E = 132.34 kV, 130.4 °
3I0 = 199.37 A, –0.1 ° 3U0 = 133.00 kV, -169.8 °

Figure 8-21 Local measured values — example for single-phase, asymmetrical test

Measuring Differen- The test for two ends is terminated with the reading of the differential and stabilizing
tial and Stabilizing currents which simultaneously check that the current transformer connections have
Currents been restored correctly after the I4 test (if performed).
o Read out the differential and stabilizing currents. They are available for every phase
at the device display or in DIGSI® 4 amongst the measured values (cf. Subsection
7.1.3.1).
q The differential currents must be low, at least one scale less than the currents flow-
ing through. If high charging currents are to be expected in long overhead lines or
cables, these are additionally included in the differential currents.

8-44 7SD610 Manual


C53000-G1176-C145-1
Commissioning

Remote Measurement

Differential
% of IN
150 %

100 %

50 %

Adaptive
Stabilization
% of IN

50 % 100 % 150 %
IdiffL1 = 3.30 % IstabL1 = 33.30 %
IdiffL2 = 1.74 % IstabL2 = 30.74 %
IdiffL3 = 7.10 % IstabL3 = 32.10 %

Figure 8-22 Differential and stabilizing currents — example for plausible currents

q The stabilizing currents result from the pickup value ,',))! (address , cf.
Subsection 6.2.2) in addition to the sum of the fault currents to be tolerated: such
as the locally permissible current transformer error according to address  (
$/)$/)B1 (cf. Subsection 6.1.1) the permissible current transformer faults at the
other end according to that setting there, as well as the internal estimation of the
system errors (frequency, synchronization and delay time difference errors). With
the default values for ,',))! (0.3 IN) and ($/)$/)B1 (5.0 % = 0.05) there is
I stab I I
----------- = 0.3 + 0.05 ⋅ -------- + 0.05 ⋅ -------- + System Fault
I NB I N1 I N2

Set value Permiss. Lo- Permiss. Re-


,',))! cal CT error mote CT error

7SD610 Manual 8-45


C53000-G1176-C145-1
Installation and Commissioning

with
I the actual current flowing,
INB the nominal operating current as parameterized,
IN1 the primary nominal current of the local current transformers,
IN2 the primary nominal current of the current transformers of the remote end.
In the “IBS-Tool”, the differential and stabilizing currents are displayed as a graph in a
characteristics diagram. One example is illustrated in Figure 8-22.
o If there is a differential current in the size of twice the through-flowing current, you may
assume a polarity reversal of the current transformer(s) at one line end. Check the po-
larity again and set it right after short-circuiting all the three current transformers. If you
have modified these current transformers, also perform a power and angle test.
o Finally, open circuit breaker again.
o If parameter settings have been changed for the tests, reset them to the values nec-
essary for operation.

8.3.8 Remote Tripping, Remote Signalling etc.

As soon as the communication between the devices has been established, the func-
tions that depend on the transmission can be tested.
This applies in particular to
q remote tripping via a binary input (cf. Section 6.3),
q transmission of further remote commands or remote signals (cf. Section 6.6),
q tripping of the remote circuit breaker by breaker failure protection and/or end fault
protection (cf. Subsection 8.3.4),
q verification of remote circuit breaker positions.
The “IBS-Tool” can be used to achieve the latter. It contains a sheet where the circuit
breaker position is notified. Note that the circuit breaker position can only be indicated
reliably, if the circuit breaker's auxiliary contacts have been signalled to the corre-
sponding device via binary inputs. Without these auxiliary contacts the devices can
only deduce the circuit breaker positions from the current flow. But as the current may
be zero even if the circuit breaker is closed, you must expect wrong indications. The
circuit breaker position is, however, always interpreted by the protection functions in
such a way that it goes on the safe side if in doubt.
For all the other commands and information to be transmitted, generate the source of
the information and check that the desired effect is created at the receiving end. Also
note the following:

DANGER!
Make sure that switching operations produced by remote command can be per-
formed without any danger during the actual switching state!

8-46 7SD610 Manual


C53000-G1176-C145-1
Commissioning

8.3.9 Testing User Defined Functions

7SD610 has a vast capability for allowing functions to be defined by the user, espe-
cially with the CFC logic. Any special function or logic added to the device must be
checked.
Naturally, general test procedures cannot be given. Rather, the configuration of these
user defined functions and the necessary associated conditions must be known and
verified. Of particular importance are possible interlocking conditions of the switch-
gear (circuit breakers, isolators, etc.). They must be considered and tested.

8.3.10 Trip and Close Test with the Circuit Breaker

The circuit breaker and tripping circuits can be conveniently tested by the device
7SD610.
The procedure is described in detail in Section 7.3.
If the check does not produce the expected results, the cause may be established from
the text in the display of the device or the PC. If necessary, the connections of the cir-
cuit breaker auxiliary contacts must be checked:
It must be noted that the binary inputs used for the circuit breaker auxiliary contacts
must be assigned separately for the CB-test. It is accordingly not sufficient that the
auxiliary contacts are assigned to the binary inputs with FNo  to and/
or(depending on the options of the auxiliary contacts); in addition, the corre-
sponding FNos  to  and/or  and/or  (depending on the options of the
auxiliary contacts) must be configured (see also Section 6.13.2). These are exclusive-
ly used for the CB-test. In addition, the ready state of the circuit breaker for the CB-
test must be indicated to the binary input FNo .

8.3.11 Stability Check and Triggering Oscillographic Recordings

At the end of commissioning, an investigation of switching operations of the circuit


breaker(s), under load conditions, should be done to assure the stability of the protec-
tion during the dynamic processes. Oscillographic recordings obtain the maximum in-
formation about the behaviour of the 7SD610.

Requirements Along with the capability of recording waveform data during system faults, the 7SD610
also has the capability of capturing the same data when commands are given to the
device via the service program DIGSI® 4, the serial interfaces, or a binary input. For
the latter, the binary input must be assigned to the function “!7ULJ:DYH&DS”
(FNo 4). Triggering for the oscillographic recording then occurs when the input is en-
ergized. For example, an auxiliary contact of the circuit breaker may be used to control
the binary input for triggering.

7SD610 Manual 8-47


C53000-G1176-C145-1
Installation and Commissioning

An oscillographic recording that is externally triggered (that is, without a protective el-
ement pickup or device trip) is processed by the device as a normal fault recording
with the exception that data are not given in the fault messages (trip log). The exter-
nally triggered record has a number for establishing a sequence.

Triggering with To trigger oscillographic recording with DIGSI® 4, click on 7HVW in the left part of the
DIGSI® 4 window. Double click the entry 7HVW:DYH)RUP in the list in the right part of the win-
dow to trigger the recording. See Figure 8-23.
A report is given in the bottom left region of the screen. In addition, message segments
concerning the progress of the procedure are displayed.
The DIGRA program or the Comtrade Viewer program is required to view and analyse
the oscillographic data. Refer to Subsection 7.1.4

Figure 8-23 Triggering oscillographic recording with DIGSI® 4

8-48 7SD610 Manual


C53000-G1176-C145-1
Final Preparation of the Device

8.4 Final Preparation of the Device

Tighten the used screws at the terminals; those ones not being used should be slightly
fastened. Ensure all pin connectors are properly inserted.

Caution!
Do not use force! The tightening torques according to Chapter 2 must not be exceed-
ed as the threads and terminal chambers may otherwise be damaged!

Verify that all service settings are correct. This is a crucial step because some setting
changes might have been made during commissioning. The protective settings under
device configuration, input/output configuration are especially important (Section 5.1)
as well as the power system data, and activated Groups A through D (if applicable).
All desired elements and functions must be set 21. See Chapter 6. Keep a copy of all
of the in-service settings on a PC.
Check the internal clock of the device. If necessary, set the clock or synchronize the
clock if it is not automatically synchronized. For assistance, refer to Subsection 7.2.1.
The annunciation memory buffers should be cleared, particularly the operational mes-
sages (event log) and fault messages (trip log). Future information will then only apply
for actual system events and faults. To clear the buffers, press 0$,10(18 → $Q
QXQFLDWLRQ → 6HW5HVHW. Refer to Subsection 7.1.1 if further assistance is need-
ed. The numbers in the switching statistics should be reset to the values that were ex-
isting prior to the testing, or to values in accordance with the user’s practices. Set the
statistics by pressing 0$,10(18 → $QQXQFLDWLRQ → 6WDWLVWLF. Refer to Sub-
section 7.1.2 if more information is needed.
Press the ESC key, several times if necessary, to return to the default display.
Clear the LEDs on the front panel by pressing the LED key. Any output relays that were
picked up prior to clearing the LEDs are reset when the clearing action is performed.
Future indications of the LEDs will then apply only for actual events or faults. Pressing
the LED key also serves as a test for the LEDs because they should all light when the
button is pushed. Any LEDs that are lit after the clearing attempt are displaying actual
conditions.
The green “581” LED must be on. The red “(5525” LED must not be lit.
Close the protective switches. If test switches are available, then these must be in the
operating position.
The device is now ready for operation.

7SD610 Manual 8-49


C53000-G1176-C145-1
Installation and Commissioning

8-50 7SD610 Manual


C53000-G1176-C145-1
Maintenance and Fault Tracing 9
General comments about the routine checks and maintenance activities to ensure the
high reliability of the 7SD610 are given in this chapter. A procedure for replacing com-
ponents such as the buffer battery is discussed. Troubleshooting advice is provided.
A procedure for replacing the power supply fuse is described. Some comments con-
cerning the return of a device to the factory are given.

9.1 General 9-2


9.2 Routine Checks 9-3
9.3 Maintenance 9-4
9.4 Fault Tracing 9-7
9.5 Corrective Action/Repairs 9-9
9.6 Return 9-13

7SD610 Manual 9-1


C53000-G1176-C145-1
Maintenance and Fault Tracing

9.1 General

Siemens numerical protective and control SIPROTEC® 4 devices are designed to re-
quire no special maintenance. All measurement and signal processing circuits are fully
solid state. All input modules are also fully solid state. The output relays are hermeti-
cally sealed or provided with protective covers.
Since the device is almost completely self-monitored, from the measuring inputs to the
output relays, hardware and software problems are automatically reported. The self-
monitoring ensures the high availability of the device and generally allows for a cor-
rective rather than preventive maintenance strategy. Therefore, maintenance checks
in short intervals are not required.
Operation of the device is automatically blocked when a hardware failure is detected.
The “live status” relay drops out to provide an alarm by its breaking contact. If a prob-
lem is detected in the external measuring circuits, the device normally only provides
messages.
Recognized software failures result in the resetting and restarting of the processor
system. If such a failure is not resolved by the restart, further restart attempts are ini-
tiated. If a problem is still present after three restart attempts, the device is automati-
cally taken out of service. Then the “live status” contact drops out to provide an alarm
and the red “ERROR” LED on the front panel illuminates.
The reaction of the device to failures and problems can be viewed in chronological se-
quence in the operational messages (event log). See Sub-section 7.1.1. The messag-
es can be used to diagnose the problem.
When the device communicates with a master control system of the substation or oth-
er central control systems, the event and alarm messages are also sent over the serial
interface.

9-2 7SD610 Manual


C53000-G1176-C145-1
Routine Checks

9.2 Routine Checks

Routine checks of the characteristic curves or pick-up values of the protective ele-
ments are not necessary because they form part of the continuously supervised
firmware programs. The normally scheduled interval for plant maintenance can be
used for carrying out operational testing of the protective and control equipment. The
maintenance serves mainly to check the serial or hardwired interfaces of the device,
i.e. the coupling with the plant.
The steps listed below are recommended for routine checks. If a problem is detected
during these checks, refer to Section 9.4.
o Verify that the green “RUN” LED is lit on the front panel and the red “ERROR” LED is
not.
o Check that the states of the LEDs on the front panel give an accurate image of the
conditions of the device and the plant. Investigate any problems or uncertainties.
o Press the LED key. All of the LEDs should temporarily light except for the “ERROR”
LED. Only the LEDs indicating specific present conditions should remain lit.
o Read the measurement values and compare them to an independent source to check
the measuring circuits of the 7XX999. Refer to Subsection 7.1.3 for assistance.
o Review the messages given in the event log. Be sure there are no reports of unknown
problems or abnormal occurrences related to the device, the measuring circuits, or the
power system. See Sub-section 7.1.1.2 for help.
o Perform a reset (reboot) of the device. A complete check of the hardware is done. The
device is effectively out of service during the reset, which lasts for about 10 to 15 sec-
onds. To perform the reset from the operator control panel, press the MENU key and use
the and keys to select the 'HYLFH5HVHW under the 7(67',$*126( sub-
menu. Press the ENTER key, enter Password No. 4 for test and diagnostics, and answer
with <HV. During the reset, the “ERROR” and “RUN” LEDs are lit. After a successful
reset, the default display reappears and the LEDs return to indicate normal operation.
The device is then back in-service. To perform the reset with DIGSI® 4, establish the
2QOLQH mode, select 'HYLFH in the menu bar, and then 5HVHW Enter the password
for test and diagnostics; then 2..
o Other testing can be done with DIGSI® 4 on-line. In Hardware Test under Test, the
conditions of all of the binary inputs, binary outputs, and LEDs can be monitored. Com-
pare the indicated conditions with the actual conditions. Do not change the states of
the device components because the power station is immediately affected!

Warning!
Alterations of the states of the binary inputs, outputs, and LEDs must not be done with
test features during normal operation. Any such change immediately affects the inputs
and outputs of the device, and therefore the connected switching devices! This in-
cludes, for instance, non-interlocked primary switching!

o The trip and close circuits for circuit breakers and other primary equipment can be ver-
ified with operator control actions. Refer to Section 7.3 for details.
o The IBS-tool enables the user to check measured data and states at both ends of the
protected object. For more details see Subsection 7.1.3.2.

7SD610 Manual 9-3


C53000-G1176-C145-1
Maintenance and Fault Tracing

9.3 Maintenance

9.3.1 Replacing the Buffer Battery

The battery is used to retain the annunciation memories and fault recording data in the
event of an interruption of the power supply. The battery also maintains the internal
system clock with calendar after a loss of the power supply.
The battery is checked by the processor at regular intervals. If the capacity of the bat-
tery is found to be declining, an alarm is generated. The battery should be changed
when this alarm is given, or at the latest, after 10 years of service.
Recommended Battery:
Lithium Battery 3 V/1 Ah, Type CR 1/2 AA. For example:
− VARTA Order Number 6127 101 501

The battery is located near the front edge of the CPU printed circuit board. The front
panel of the device must be removed to change the battery.
To replace the battery:
o Save the annunciations and fault records. These are the data under the Annunciation
sub-menu (all items in this sub-menu). The records and data are lost when the battery
is removed. The simplest and fastest method is to use the save feature in DIGSI® 4
when the program is on-line.
Note: All of the protective and control settings, including the input/output configuration
and the CFC logic, are not affected by a power supply interruption. The settings are
stored independently of the battery. The settings are not lost when the battery is re-
moved, nor are the settings affected if the device operates without a battery.
o Have the replacement battery ready.

Caution!
Do not short the battery! Do not reverse the polarity of the battery! Do not lay the bat-
tery on the ground mat used to protect components from electrostatic discharges! Do
not recharge the battery!

o Isolate the power supply by opening the protective switches for both terminals.

Caution!
Electrostatic discharges through the connections of the components, wiring, and con-
nectors must be avoided. Wearing a grounded wrist strap is preferred; otherwise, first
touch a grounded metal part before handling the internal components. Do not insert or
remove interface connectors under live conditions!

9-4 7SD610 Manual


C53000-G1176-C145-1
Maintenance

Warning!
Hazardous voltages may exist in the device, even after the power supply is discon-
nected and the boards are withdrawn from the case! Capacitors can still be charged!

o Remove the covers on the front panel and loosen the screws that are securing the
front panel.
o Carefully pull off the front panel and bend it aside. The front panel is connected to the
internal CPU printed circuit board with a short ribbon-cable.
o Disconnect the ribbon-cable that links the front panel and the CPU board (å), at the
side of the front panel. To disconnect the cable, push up on the top latch of the plug
connector and push down on the bottom latch of the plug connector. Carefully set
aside the front panel.
o The battery is located on the bottom-front side of the CPU (¯) board. See Figure 9-1.

Battery grip

Battery

+ –
G1

Slot 5 Slot 19 ¯ Processor board CPU


¯ ° ° Input/output board I/O

Figure 9-1 Front view without front panel – position of buffer battery (simplified and re-
duced)

o Remove the old battery from the snap-on connector using the plastic battery grip
shown in Figure 9-1.
o Remove the battery grip from the old battery, and place the grip on the new battery.
o Observing the polarity and firmly insert the new battery into the snap-on connector
shown in Figure 9-1.

7SD610 Manual 9-5


C53000-G1176-C145-1
Maintenance and Fault Tracing

o Connect the ribbon-cable between the CPU (¯) board and the front panel. Be espe-
cially careful not to bend any of the connector pins! Do not use force! Be sure that the
plug connectors latch.
o Carefully replace the front panel being mindful of the ribbon-cable. Fasten the panel
to the case with the screws.
o Replace the covers.
o Close the protective switches to apply voltage to the power supply.
o After the device is operating, data saved in DIGSI® 4 can be loaded back into the de-
vice.
If the internal system clock is not automatically synchronized via a serial interface,
then the clock should be set at this point. Refer to Subsection 7.2.1 if assistance is
needed to set the clock.

Warning!
The used battery contains Lithium. Do not throw the battery into the trash! It must be
disposed off in line with the applicable regulations!
Do not reverse the polarity! Do not completely discharge! Do not throw the bat-
tery into a fire! Explosion hazard!

9.3.2 Replacing Interface Modules

The serial interface modules are replaceable. If an interface is suspected to be defect,


the module can be replaced by a different module (only for test or definitely).
The replacing procedure is described precisely in Subsection 8.1.3.4. If a module is
replaced, please observe the hints for disassembly in Subsection 8.1.3.2 and reas-
sembly of the device in Subsection 8.1.3.5.

9-6 7SD610 Manual


C53000-G1176-C145-1
Fault Tracing

9.4 Fault Tracing

If a device reports a problem or failure, the procedure below is recommended.


If none of the LEDs on the front panel are lit, then verify:
q Are the modules placed correctly and locked by the front panel?
q Are the plug-in connectors of the ribbon cables plugged properly into the modules
and are the interlockings latched correctly?
q Are the voltage magnitude and polarity correct for the power supply? Connection
drawings are shown in Section A.2 of Appendix A.
q Has the fuse in the power supply not blown. The location of the fuse is shown in
Figure 9-5. If the fuse needs to be replaced, see Sub-section 9.5.2.
If the red “ERROR” LED is on and the green “RUN” LED is off, then the device has
recognized an internal fault. Re-initializing the device can be attempted (see Section
9.2).

If you see the following display, the device has arrived “monitor”-mode. In this case
you may initialize the device via DIGSI® 4:

021,725

(TXLSPHQWGDWD²!
8VHULQWHUIDFH²!
6\VWHP,IDFH²!
5HVHW²!
6LHPHQVLQWHUQ²!

Figure 9-2 Monitor menu in the display

q Connect the SIPROTEC® 4 device to the PC and open the DIGSI® 4 application in
the PC.
q Select ,QLWLDOL]HGHYLFH in the menu 'HYLFH (Figure 9-3).

Figure 9-3 Initializing device via DIGSI® 4 — example

7SD610 Manual 9-7


C53000-G1176-C145-1
Maintenance and Fault Tracing

q Enter password No. 7. The display becomes blank. After a successful initialization,
the LEDs return to indicate normal operation and the default display reappears. The
device settings are downloaded to the device provided they had been saved in the
PC after commissioning (refer to Section 8.4). The device is then in-service.

Further Assistance If these steps do not resolve the problem, please call your local Siemens representa-
tive or customer hot-line.
Our customer hot-line needs the following information to assist you:
− the complete order number of the device (“MLFB”),
− the serial number of the device (BF ...),
− the firmware version,
− the boot system version.
This information can be read out from the device panel. From the 0$,10(18 select
6HWWLQJV → 6HWXS([WUDV. The ordering code and the serial number can also be
found on the name plate sticker on the device housing.
If a device file had been created on the harddisk of the PC, the information can be
found in the device file using DIGSI® 4 in online mode as shown in Figure 9-4.
q Open the DIGSI® 4 application in the PC and select the device.
q Open the device in 2IIOLQH mode.
q Select )LOH → 3URSHUWLHV from the menu bar. The desired information is shown.

Figure 9-4 Retrieving the device data in the device properties — example

9-8 7SD610 Manual


C53000-G1176-C145-1
Corrective Action/Repairs

9.5 Corrective Action/Repairs

9.5.1 Software Procedures

A restart of the processor system, as described in Section 9.2, can be done as an at-
tempt to solve a problem. Setting changes can be made to solve simple problems,
such as sporadic alarms from elements of the measured value supervision. These at-
tempts of solving problems can be done while the device is in service.
If a processor restart or setting change does not remedy the problem, then no further
action should be done while the device is in service. Instead, replace the device with
a tested spare.

9.5.2 Hardware Procedures

Hardware modifications or repair should be limited in scope to changes that are abso-
lutely necessary. Some examples of hardware repair are changing the mini-fuse in the
power supply and replacing a printed circuit board or module.
Hardware modifications or repair should only be done by experienced personnel. Do
not insert or extract a printed circuit board unless the device is completely isolated.
Soldering work must not be done on the printed circuit boards.

Disassembling the The device must be disassembled if work is to be done on the printed circuit boards.
Device The procedure below should be used.
o Prepare area of work. Provide a grounded mat for protecting components subject to
damage from electrostatic discharges (ESD). The following equipment is needed:
− Screwdriver with a 5 to 6 mm or 1/4 inch tip.
− #1 Phillips screwdriver.
− 4.5 mm socket or nut driver.
o Isolate the power supply by opening the protective switches (test switches, fuses, or
miniature circuit breakers) for both terminals.

o Disconnect all communication cables from the device. Carefully remove optical fibres
S

from the device. Apply protective caps to the fibre ends and the communication ports
on the device.
These activities do not apply if the device is for surface mounting.

Warning!
Laser injection! Do not look directly into the fibre-optic elements!

7SD610 Manual 9-9


C53000-G1176-C145-1
Maintenance and Fault Tracing

o Unfasten the screw-posts of the D-subminiature connector on the back panel at loca-
tion “A”.
This activity does not apply if the device is for surface mounting.
o If the device has more communication interfaces at locations “B” and/or “C” on the
rear, the screws located diagonally to the interfaces must be removed.
These activities are not necessary if the device is for surface mounting.
o Remove the corner covers on the front panel and loosen the screws that are holding
the front panel to the device case.
o Carefully pull off the front panel. The front panel is connected to the CPU board with
a short ribbon-cable.
On devices with detached operator panel, the front panel can be pulled off directly
(without a ribbon cable).

Caution!
Electrostatic discharges through the connections of the components, wiring, and con-
nectors must be avoided! Wearing a grounded wrist strap is preferred; otherwise, first
touch a grounded metal part. Do not insert or remove interface connectors under live
conditions!

Warning!
Hazardous voltages may exist in the device, even after the power supply is discon-
nected and the boards are withdrawn from the case! Capacitors can still be charged!

o At one end, disconnect the ribbon-cable that links the front panel and the CPU board
(å), at the side of the front panel. To disconnect the cable, push up on the top latch of
the plug connector and push down on the bottom latch of the plug connector. Carefully
set aside the front panel.
For the surface mounted device, the 7-pin connector X16 must be disconnected from
the CPU board behind the D-subminiature port, and the ribbon-cable that runs to the
68-pin connector on the back must be detached.
o Disconnect the ribbon-cable between the CPU board and the I/O board.
o The boards can be removed and laid on the grounded mat to protect them from ESD
damage.
A greater effort is required to remove the CPU board from the device designed for sur-
face mounting, because of the type of connectors.

Replacing the
Power Supply Fuse
o Keep ready replacement fuse 5 x 20 mm. Verify the correct rating, correct character-
istic (T) as well as the correct coding.
This data is printed on the module (see Figure 9-5). The type of fuse depends on the
auxiliary supply voltage (refer to Table 9-1).
o The processor module CPU, which also incorporates the power supply (refer to Figure
8-5 in Sub-section 8.1.3) must be removed and placed on a surface suitable for elec-
trostatically sensitive devices (ESD).

9-10 7SD610 Manual


C53000-G1176-C145-1
Corrective Action/Repairs

o Remove the defective fuse. Figure 9-5 illustrates the fuse.

2 3 4

C53207-A324-B30-
C53207-A324-B40-
C53207-A324-B20-
F1
B20 T4H250V
B30 B40 T2H250V

Figure 9-5 Power supply mini-fuse on the processor printed circuit board CPU

Table 9-1 Assigning of the mini-fuse rating to the device auxiliary voltage rating

7SD610∗ Version Rated Auxiliary Voltages Fuse Type


–2∗∗∗∗–∗∗∗∗ 24 V to 48 V DC T4H250V
–4∗∗∗∗–∗∗∗∗ 60 V to 125 VDC T2H250V
–5∗∗∗∗–∗∗∗∗ 110 V to 250 VDC; 115 VAC T2H250V

o Install the new fuse into the holder.


o Carefully install the processor board CPU in the case.

Reassembling the To reassemble the device:


Device
o Connect the ribbon-cable between the I/O board and the CPU board. Be especially
careful not to bend any of the connector pins! Do not use force! Be sure the connectors
latch.
o Connect the ribbon-cable between the CPU board and the front panel. Be especially
careful not to bend any of the connector pins! Do not use force! Be sure the plug con-
nectors latch. For a model with detached operator panel, first connect the ribbon-cable
from the 68-pin connector on the back of the device to the CPU board. Then attach
connector X16 under the D-subminiature port on the CPU board. The X16–connector
can be plugged in either direction.
o Carefully replace the front panel being mindful of the ribbon-cables. Fasten the front
panel to the case with the screws.
o Replace the covers.

The following steps are not applicable for the surface mount version:

7SD610 Manual 9-11


C53000-G1176-C145-1
Maintenance and Fault Tracing

o Align and fix the rear interfaces again.


o Attach all D-subminiature plugs to the matching D-subminiature sockets.
o Screw in all the fibre optical connectors where applicable.

Warning!
Laser injection! Do not look directly into the fibre-optic elements!

Close the protective switches to apply voltage to the power supply. If the green “RUN”
LED does not light, there is a fault in the power supply. The device should be sent to
the factory. See Section 9.6.

9-12 7SD610 Manual


C53000-G1176-C145-1
Return

9.6 Return

Siemens strongly recommends that no further repairs on defective devices, boards,


or components be done. Special electronic components are used for which proce-
dures for preventing electrostatic discharges must be followed. Most importantly, spe-
cial production techniques are necessary to avoid damaging the wave-soldered multi-
layer boards, the sensitive components, and the protective varnish.
If a problem cannot be solved by the procedures described in Section 9.5, then the
complete device (including front cover) should be returned to the factory.
The original transport packaging material should be used for returning a device. If al-
ternative packaging material is used, then the device and other contents must be pro-
vided with protection against shock and vibration according to IEC 60255–21–1
Class 2 and IEC 60255–21–2 Class 1.
Before returning a device, retrieve and save all of the configuration, function and con-
trol settings, and any important information. Note any changes that were made to the
jumpers on the internal printed circuit boards after the device was first delivered.

Note:
Repaired devices are returned from the factory with all jumpers on the printed circuit
boards set in the original positions according to the ordering number. All configuration,
function and control parameters have the default setting.

7SD610 Manual 9-13


C53000-G1176-C145-1
Maintenance and Fault Tracing

9-14 7SD610 Manual


C53000-G1176-C145-1
Technical Data 10
This chapter provides the technical data of the SIPROTEC® 4 7SD610 device and its
individual functions, including the limiting values that must not be exceeded under any
circumstances. The electrical and functional data of fully equipped 7SD610 devices
are followed by the mechanical data, with dimensional drawings.

10.1 General Device Data 10-2


10.2 Differential Protection 10-10
10.3 Intertripping, External Direct Local and Remote Tripping 10-12
10.4 Direct Remote Trip or Transmission of Binary Information (optional) 10-12
10.5 Protection Data Interface and Differential Protection Topology 10-13
10.6 Time Overcurrent Protection 10-14
10.7 High-Current Switch-on-to-Fault Protection 10-19
10.8 Automatic Reclosure Function (optional) 10-19
10.9 Circuit Breaker Failure Protection (optional) 10-20
10.10 Thermal Overload Protection 10-21
10.11 Monitoring Functions 10-23
10.12 Supplementary Functions 10-24
10.13 Dimensions 10-26

7SD610 Manual 10-1


C53000-G1176-C145-1
Technical Data

10.1 General Device Data

10.1.1 Analog Inputs and Outputs

Nominal frequency fN 50 Hz or 60 Hz (adjustable)

Current Inputs Nominal current IN 1 A or 5 A


Power consumption per phase and earth path
– at IN = 1 A approx. 0.05 VA
– at IN = 5 A approx. 0.3 VA
Current overload capability per input
– thermal (rms) 500 A for 1 s
150 A for 10 s
20 A continuous
– dynamic (pulse) 1250 A (half cycle)

Requirements for For a maximum fault current


Current Transform- the current transformers must not be
ers saturated under steady-state conditions.
I F cont max
The accuracy limiting factor must be n’ ≥ -------------------------- AND n’ ≥ 30
at least 30 I N prim

Maximum ratio between primary I prim max


currents of current transformers --------------------- ≤ 8
I prim min
at the ends of the protected object

Voltage Inputs Nominal voltage UN 80 V to 125 V (adjustable)


Power consumption per phase at 100 V ≤0.1 VA
Voltage overload capability per phase
– thermal (rms) 230 V continuous

10.1.2 Power Supply

Direct Voltage Voltage supply via integrated DC/DC converter:


Nominal power supply direct voltage UNDC 24/48 VDC 60/110/125 VDC
Permissible voltage ranges 19 to 58 VDC 48 to 150 VDC

Nominal power supply direct voltage UNDC 110/125/220/250 VDC


Permissible voltage ranges 88 to 300 VDC

Permissible AC ripple voltage,


peak to peak ≤15 % of the nominal power supply voltage
Power consumption
– quiescent approx. 6.5 W
– energized approx. 10 W

10-2 7SD610 Manual


C53000-G1176-C145-1
General Device Data

Bridging time for failure/short-circuit ≥50 ms at UH = 48 V and UNDC ≥ 110 V


of the power supply ≥20 ms at UH = 24 V and UNDC = 60 V

Alternating Voltage Voltage supply via integrated AC/DC converter


Nominal power supply alternating voltage UNAC 115 VAC
Permissible voltage ranges 92 to 132 VAC
Power consumption
– quiescent approx. 10 VA
– energized approx. 17 VA
Bridging time for failure/short-circuit
of the power supply ≥ 50 ms

10.1.3 Binary Inputs and Outputs

Binary Inputs Number 7 (allocatable)


Nominal voltage 24 VDC to 250 VDC in 2 ranges, bipolar
Switching thresholds adjustable with jumpers
– for nominal voltages 24/48 VDC Upickup ≥ 19 VDC
60/110/125 VDC Udropoff ≤ 14 VDC
– for nominal voltages 110/125/ Upickup ≥ 88 VDC
220/250 VDC Udropoff ≤ 66 VDC
Current consumption, energized approx. 1.8 mA
independent of the control voltage
Maximum permissible voltage 300 VDC
Input interference suppression 220 nF coupling capacitance at 220 V
with recovery time >60 ms

Binary Outputs Alarm/command relays (see also General Diagrams in Section A.2 of Appendix A)
Number 3, each with 1 NO contact (commoned)
2, each with 1 NO contact (voltfree)
(allocatable)
Switching capability MAKE 1000 W/VA
BREAK 30 VA
40 W ohmic
25 W for L/R ≤ 50 ms
Alarm relay 1, with 1 NO or NC contact
(switch selectable)
Switching capability MAKE 1000 W/VA
BREAK 30 VA
40 W ohmic
25 W for L/R ≤ 50 ms
Switching voltage 250 V

7SD610 Manual 10-3


C53000-G1176-C145-1
Technical Data

Permissible current per contact 5 A continuous


30 A for 0.5 s
Permissible total current on 5 A continuous
common paths 30 A for 0.5 s

10.1.4 Communications Interfaces

Protection Data See Section 10.5


Interface

Operation Interface – Connection front panel, non-isolated, RS 232


9-pin DSUB socket
for connecting a personal computer
– Operation with DIGSI® 4
– Transmission speed min. 4 800 Baud; max. 115200 Baud
factory setting: 38400 Baud; parity: 8E1
– Maximum transmission distance 15 m (50 ft)

Service/Modem RS232/RS485 i isolated interface for data transfer


Interface acc. ordered version
(optional)
Operation with DIGSI® 4
RS232
– Connection for flush mounted case rear panel, mounting location “C”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
shielded data cable
– Test voltage 500 V; 50 Hz
– Transmission speed min. 4 800 Baud; max. 115200 Baud
factory setting: 38400 Baud
– Maximum transmission distance 15 m (50 ft)
RS485
– Connection for flush mounted case rear panel, mounting location “C”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
shielded data cable
– Test voltage 500 V; 50 Hz
– Transmission speed min. 4800 Baud; max. 115200 Baud
factory setting: 38400 Baud
– Maximum transmission distance 1000 m (3300 ft)

10-4 7SD610 Manual


C53000-G1176-C145-1
General Device Data

System (SCADA) RS232/RS485/Optical floating interface for data transfer


Interface (optional) to a master terminal
acc. to ordered version
RS232
– Connectionfor flush mounted case rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
– Test voltage 500 V; 50 Hz
– Transmission speed min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance 15 m (50 ft)
RS485
– Connection for flush mounted case rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
– Test voltage 500 V, 50 Hz
– Transmission speed min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance 1000 m (3300 ft)
Optical fibre
– Connector Type ST–connector
for flush mounted case rear panel, mounting location “B”
for surface mounted case at the inclined housing on the case bottom
– Optical wavelength λ = 820 nm
– Laser class 1 acc. EN 60825–1/ –2 using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
– Permissible optical signal attenuation max. 8 dB, using glass fibre 62.5/125 µm
– Maximum transmission distance 2 km (1.2 miles)
– Character idle state selectable; factory setting: “Light off”

Time Synchroniza- – Signal type DCF77/IRIG B-Signal


tion
– Connectionfor flush mounted case rear panel, mounting location “A”
9-pin DSUB socket
for surface mounted case at the terminal on the case bottom
– Nominal signal voltages optional 5 V, 12 V or 24 V
– Signal level and burden:
Nominal signal input voltage
5V 12 V 24 V
UIHigh 6.0 V 15.8 V 31 V
UILow 1.0 V at IILow = 0.25 mA 1.4 V at IILow = 0.25 mA 1.9 V at IILow = 0.25 mA

7SD610 Manual 10-5


C53000-G1176-C145-1
Technical Data

IIHigh 4.5 mA to 9.4 mA 4.5 mA to 9.3 mA 4.5 mA to 8.7 mA


RI 890 Ω at UI = 4 V 1930 Ω at UI = 8.7 V 3780 Ω at UI = 17 V
640 Ω at UI = 6 V 1700 Ω at UI = 15.8 V 3560 Ω at UI = 31 V

10.1.5 Electrical Tests

Specifications Standards: IEC 60255 (Product standards)


ANSI/IEEE C37.90.0; C37.90.0.1;
C37.90.0.2
UL 508
DIN 57435 Part 303
See also standards for individual functions

Insulation Tests Standards: IEC 60255–5 and 60870–2–1


– High voltage test (routine test) 2.5 kV (rms); 50 Hz
all circuits except power supply,
binary inputs, and
communication/time sync. interfaces
– High voltage test (routine test) 3.5 kVDC
only power supply and binary inputs
– High Voltage Test (routine test) 500 V (rms); 50 Hz
only isolated communication
/time sync. interfaces
– Impulse voltage test (type test) 5 kV (peak); 1.2/50 µs; 0.5 Ws; 3 positive
all circuits except communication and 3 negative surges in intervals of 5 s
/time sync. interfaces, class III

EMC Tests; Inter- Standards: IEC 60255–6 and –22 (Product standards)
ference Immunity EN 50082–2 (Generic standard)
(Type Tests) DIN 57435 Part 303
– High frequency test 2.5 kV (Peak); 1 MHz; τ = 15 ms;
IEC 60255–22–1, class III 400 surges per s; test duration 2 s
and VDE 0435 part 303, class III Ri = 200 Ω
– Electrostatic discharge 8 kV contact discharge;
IEC 60255–22–2 class IV 15 kV air discharge, both polarities;
and IEC 61000–4–2, class IV 150 pF; Ri = 330 Ω
– Irradiation with HF field, non-modulated10 V/m; 27 MHz to 500 MHz
IEC 60255–22–3 (report) class III
– Irradiation with HF field, amplitude 10 V/m; 80 MHz to 1000 MHz; 80 % AM;
modulated; IEC 61000–4–3, class III 1 kHz
– Irradiation with HF field, 10 V/m; 900 MHz; repetition frequency
pulse modulated 200 Hz; duty cycle of 50 %
IEC 61000–4–3/ENV 50204, class III

10-6 7SD610 Manual


C53000-G1176-C145-1
General Device Data

– Fast transient disturbance/burst 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
IEC 60255–22–4 and repetition rate 300 ms; both polarities;
IEC 61000–4–4, class IV Ri = 50 Ω; test duration 1 min
– High energy surge voltages impulse: 1.2/50 µs
(SURGE), IEC 61000–4–5
installation class 3
power supply common mode: 2 kV; 12 Ω; 9 µF
diff. mode: 1 kV; 2 Ω; 18 µF
analogue inputs, binary inputs common mode: 2 kV; 42 Ω; 0.5 µF
and outputs diff. mode: 1 kV; 42 Ω; 0.5 µF
– Line conducted HF, amplitude 10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
modulated; IEC 61000–4–6, class III
– Power system frequency magnetic 30 A/m continuous; 300 A/m for 3 s; 50 Hz
field; IEC 61000–4–8, class IV; 0.5 mT; 50 Hz
IEC 60255–6
– Oscillatory surge withstand capability 2.5 to 3 kV (peak value); 1 to 1.5 MHz
ANSI/IEEE C37.90.1 decaying wave; 50 surges per s;
duration 2 s; Ri = 150 Ω to 200 Ω
– Fast transient surge withstand cap- 4 kV to 5 kV; 10/150 ns; 50 surges per s;
ability, ANSI/IEEE C37.90.1 both polarities; duration 2 s; Ri = 80 Ω
– Radiated electromagnetic interference 35 V/m; 25 MHz to 1000 MHz
ANSI/IEEE Std C37.90.2 amplitude and pulse modulated
– Damped oscillations 2.5 kV (peak value), polarity alternating;
IEC 60694, IEC 61000–4–12 100 kHz, 1 MHz, 10 MHz and 50 MHz;
Ri = 200 Ω

EMC Tests; Inter- Standard: EN 50081–* (Generic standard)


ference Emission
– Conducted interference, 150 kHz to 30 MHz
(Type Tests)
only power supply voltage limit class B
IEC–CISPR 22
– Radio interference field strength 30 MHz to 1000 MHz
IEC–CISPR 22 limit class B

10.1.6 Mechanical Stress Tests

Vibration and Standards: IEC 60255–21 and IEC 60068–2


Shock During
– Vibration sinusoidal
Operation
IEC 60255–21–1, class 2 10 Hz to 60 Hz: ±0.075 mm amplitude
IEC 60068–2–6 60 Hz to 150 Hz: 1 g acceleration
frequency sweep rate 1 octave/min
20 cycles in 3 orthogonal axes.

7SD610 Manual 10-7


C53000-G1176-C145-1
Technical Data

– Shock half-sine shaped


IEC 60255–21–2, class 1 acceleration 5 g, duration 11 ms,
IEC 60068–2–27 3 shocks in each direction of
3 orthogonal axes
– Seismic vibration sinusoidal
IEC 60255–21–2, class 1 1 Hz to 8 Hz: ± 3.5 mm amplitude
IEC 60068–3–3 (horizontal axis)
1 Hz to 8 Hz: ± 1.5 mm amplitude
(vertical axis)
8 Hz to 35 Hz: 1 g acceleration
(horizontal axis)
8 Hz to 35 Hz: 0.5 g acceleration
(vertical axis)
Frequency sweep rate1 octave/min
1 cycle in 3 orthogonal axes

Vibration and Standards: IEC 60255–21 and IEC 60068–2


Shock During
– Vibration sinusoidal
Transport
IEC 60255–21–1, class 2 5 Hz to 8 Hz: ±7.5 mm amplitude
IEC 60068–2–6 8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate1 octave/min
20 cycles in 3 orthogonal axes
– Shock half-sine shaped
IEC 60255–21–2, class 1 acceleration 15 g; duration 11 ms;
IEC 60068–2–27 3 shocks in each direction of
3 orthogonal axes
– Continuous shock half-sine shaped
IEC 60255–21–2, class 1 acceleration 10 g; duration 16 ms;
IEC 60068–2–29 1000 shocks in each direction of
3 orthogonal axes

10.1.7 Climatic Stress Tests

Ambient Tempera- Standards: IEC 60255–6


tures
– recommended operating temperature –5 °C to +55 °C (+23 °F to +131 °F)
– limiting temporary (transient) –20 °C to +70 °C Visibility of display
may be impaired
operating temperature (–4 °F to 158 °F) above +55 °C/130 °F
in quiescent state, i.e. no pickup and no indications

– limiting temperature during storage –25 °C to +55 °C (–13 °F to 131 °F)


– limiting temperature during transport –25 °C to +70 °C (–13 °F to 158 °F)
Storage and transport of the device with factory packaging!

Humidity Permissible humidity mean value p. year ≤75 % relative humidity


on 56 days per year up to 93 % relative
humidity; condensation not permissible!

10-8 7SD610 Manual


C53000-G1176-C145-1
General Device Data

All devices shall be installed such that they are not exposed to direct sunlight, nor sub-
ject to large fluctuations in temperature that may cause condensation to occur.

10.1.8 Service Conditions

The device is designed for use in an industrial environment or an electrical utility en-
vironment, for installation in standard relay rooms and compartments so that proper
installation and electromagnetic compatibility (EMC) is ensured. In addition, the follow-
ing are recommended:
• All contactors and relays that operate in the same cubicle, cabinet, or relay panel
as the numerical protective device should, as a rule, be equipped with suitable
surge suppression components.
• For substations with operating voltages of 100 kV and above, all external cables
should be shielded with a conductive shield grounded at both ends. The shield must
be capable of carrying the fault currents that could occur. For substations with lower
operating voltages, no special measures are normally required.
• Do not withdraw or insert individual modules or boards while the protective device
is energized. When handling the modules or the boards outside of the case, stand-
ards for components sensitive to electrostatic discharge (ESD) must be observed.
The modules, boards, and device are not endangered when the device is complete-
ly assembled.

10.1.9 Construction

Housing 7XP20
Dimensions see drawings, Section 10.13
Weight (mass), approx.
– in flush mounted case, size 1/2 5,0 kg
– in surface mounted case, size 1/2 9,5 kg
Degree of protection acc. IEC 60529
– for the device
in surface mounted case IP 51
in flush mounted case
front IP 51
rear IP 50
– for human safety IP 2x with closed protection cover

7SD610 Manual 10-9


C53000-G1176-C145-1
Technical Data

10.2 Differential Protection

Pickup Values Differential currentIDIFF> 0.10 A to 20.00 A1) (steps 0.01 A)


Differential current
when switching onto a fault IDIFF switch on 0.10 A to 20.00 A1) (steps 0.01 A)
Differential current
High set differential currentIDIFF>> 0.5 A to 100.0 A1) (steps 0.01 A)
or ∞ (stage disabled)
Tolerances
– IDIFF>–stage 5 % of setting value
– IDIFF>>–stage 5 % of setting value
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Tripping Time The tripping time depends on the communication speed.


Pickup/trip times of the IDIFF>>–stages approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


minimum 16 ms 18 ms 24 ms
typical 20 ms 23 ms 32 ms

Drop-off time of the IDIFF>>–stages approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


typical 39 ms 42 ms 52 ms

Pickup / trip commands of the IDIFF>–stages approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


minimum (50 Hz) 34 ms 39 ms 47 ms
minimum(60 Hz) 32 ms 36 ms 43 ms
typical 38 ms 44 ms 57 ms

Drop-off time of the IDIFF>–stages approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


typical 30 ms 35 ms 45 ms

Delay Times Delay time of the IDIFF>–stage 0.00 s to 60.00 s (steps 0.01 s)
TI-DIFF> or ∞ (stage disabled)
Delay time of the IDIFF>–stage 0.00 s to 60.00 s (steps 0.01 s)
for 1-phase pickup T3I0 1PHAS or ∞ (stage disabled for 1-phase pickup)
Expiry tolerance 1 % of setting value or 10 ms
The times set are pure delay times

10-10 7SD610 Manual


C53000-G1176-C145-1
Differential Protection

Auto-Stabilization Current transformer error at each end of the protected object


Ratio between operating accuracy limit factor
and nominal accuracy limit factor n’/n 1.00 to 10.00 (steps 0.01)
Transformer error at n’/n 0.5 % to 50.0 % (steps 0.1 %)
Transformer error at n × IN (class) 0.5 % to 50.0 % (steps 0.1 %)
Further stabilizing quantities Frequency deviation,
(adaptive auto-stabilization) delay time differences, harmonics,
synchronous quality, jitter

Inrush Stabilization Stabilization ratio


2nd harmonic I2fN/IfN 10 % to 45 % (steps 1 %)
Maximum current for stabilization 1
1.1 A to 25.0 A ) (steps 0.1 A)
Crossblock function can be enabled and disabled
Max. action time for crossblock 0.00 s to 60.00 s (steps 0.01 s)
CROSSB 2HM or ∞ (active until drop off)
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Conditioning for Vector group matching 0 to 11 (× 30°) (steps 1)


Transformers
Star-point conditioning earthed or unearthed
(optional)
(for each winding)

Emergency Communication failure see Section 10.6


Operation

Frequency Frequency correction within range 0.8 ≤ f/fN ≤ 1.2


stable when starting machine

7SD610 Manual 10-11


C53000-G1176-C145-1
Technical Data

10.3 Intertripping, External Direct Local and Remote Tripping

Intertrip Intertripping of the opposite end


when singe-end tripping can be enabled and disabled

External Direct Operating time, total approx. 12 ms


Local Tripping
Trip time delay 0.00 s to 30.00 s (steps 0.01 s)
Expiry tolerance 1 % of setting value or 10 ms
The set times are pure delay times.

External Direct Tripping of remote end by a command that is coupled into a binary input
Remote Tripping
Operating times, total approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


minimum 15 ms 18 ms 24 ms
typical 18 ms 21 ms 31 ms

Drop-off times, total approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


typical 13 ms 15 ms 26 ms

Trip time delay 0.00 s to 30.00 s(steps 0.01 s)


Trip time delay 0.00 s to 30.00 s(steps 0.01 s)
Expiry tolerance 1 % of setting value or 10 ms
The set times are pure delay times.

10.4 Direct Remote Trip or Transmission of Binary Information (optional)

Remote Commands Number of possible remote commands 4


Operating times, total approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


minimum 15 ms 18 ms 24 ms
typical 18 ms 21 ms 31 ms

Drop-off times, total approx.

transmission speed 512 kBit/s 128 kBit/s 64 kBit/s


typical 13 ms 15 ms 26 ms

10-12 7SD610 Manual


C53000-G1176-C145-1
Protection Data Interface and Differential Protection Topology

10.5 Protection Data Interface and Differential Protection Topology

Topology Number of devices for protected object 2

Protection Data – Connection optical fibre mounting position “D”


Interface for flush mounted case on the rear side
for surface mounted case on the bottom side
Connection modules for protection data interface(s), depending on the ordering
version:

Module Type of Optical Perm. Path Distance,


Type of Fibre
in Device Connector Wavelength Attenuation typical
FO5 1) ST Multimode 820 nm 8 dB 1.5 km
62.5/125 µm
FO6 2) ST Multimode 820 nm 16 dB 3.5 km
62.5/125 µm
FO7 2) ST Monomode 1300 nm 7 dB 10 km
9/125 µm
FO8 2) FC Monomode 1300 nm 18 dB 35 km
9/125 µm

1
) Laser class 1 according to EN 60825–1/ –2 using glass fibre 62.5/125 µm
2) Laser class 3A according to EN 60825–1/ –2

Character idle state “Light off”

Protection Data Direct connection:


Communication
Transmission speed 512 kBit/s
Type of fibre
Optical wavelength
see Table above
Permissible path attenuation
Transmission distance
Connection via communication networks:
Communication converter see Appendix A, Section A.1.1 Accessories
Supported network interfaces G701.1 with 64 kBit/s;
X21 with 64 or 128 or 512 kBit/s
Connection to communication converter see table above under module FO5
Transmission speed 64 kBit/s with G701.1
512 kBit/s or 128 kBit/s or
64 kBit/s with X21
Max. transmission time 0.1 ms to 30 ms (steps 0.1 ms)
Max. transmission time difference 0.000 ms to 3.000 ms (steps 0.001 ms)

7SD610 Manual 10-13


C53000-G1176-C145-1
Technical Data

10.6 Time Overcurrent Protection

Operating Modes As emergency overcurrent protection or back-up overcurrent protection:


Emergency overcurrent protection operates on communication failure
Back-up overcurrent protection operates independent on any events

Characteristics Definite time stages (definite) IPh>>, 3I0>>, IPh>, 3I0>


Inverse time stage (IDMT) IP, 3I0P
one of the characteristics according to
Figure 10-1 to 10-3 can be selected

Current Stages High set stages IPh>> (phases) 0.10 A to 25.00 A1) (steps 0.01 A)
or ∞ (ineffective)
TIPh>> (phases) 0.00 s to 30.00 s (steps 0.01 s)
or ∞ (ineffective)
3I0>> (earth) 0.05 A to 25.00 A1) (steps 0.01 A)
or ∞ (ineffective)
T3I0>> (earth) 0.00 s to 30.00 s (steps 0.01 s)
or ∞ (ineffective)
Overcurrent stages IPh> (phases) 0.10 A to 25.00 A1) (steps 0.01 A)
(definite time) or ∞ (ineffective)
TIPh> (phases) 0.00 s to 30.00 s (steps 0.01 s)
or ∞ (ineffective)
3I0> (earth) 0.05 A to 25.00 A1) (steps 0.01 A)
or ∞ (ineffective)
T3I0> (earth) 0.00 s to 30.00 s (steps 0.01 s)
or ∞ (ineffective)
Overcurrent stages IP (phases) 0.10 A to 4.00 A1) (steps 0.01 A)
(inverse time acc. IEC) or ∞ (ineffective)
TIP (phases) 0.05 s to 3.00 s (steps 0.01 s)
or ∞ (ineffective)
TIPadd (phases) 0.00 s to 30.00 s (steps 0.01 s)
or ∞ (ineffective)
3I0P (earth) 0.05 A to 4.00 A1) (steps 0.01 A)
or ∞ (ineffective)
T3I0P (earth) 0.05 s to 3.00 s (steps 0.01 s)
or ∞ (ineffective)
T3I0Padd (earth) 0.00 s to 30.00 s (steps 0.01 s)
Overcurrent stages IP (phases) 0.10 A to 4.00 A1) (steps 0.01 A)
(inverse time acc. ANSI) or ∞ (ineffective)
DIP (phases) 0.50 s to 15.00 s (steps 0.01 s)
or ∞ (ineffective)
TIPadd (phases) 0.00 s to 30.00 s (steps 0.01 s)

10-14 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

3I0P (earth) 0.05 A to 4.00 A1) (steps 0.01 A)


or ∞ (ineffective)
D3I0P (earth) 0.50 s to 15.00 s (steps 0.01 s)
or ∞ (ineffective)
T3I0Padd (earth) 0.00 s to 30.00 s (steps 0.01 s)
Tolerances currents 3 % of set value or 1% of nominal current
with definite time times 1 % of set value or 10 ms
Tolerances currents Pickup at 1.05 ≤ I/IP ≤ 1.15;
with inverse time or 1.05 ≤ I/3I0P ≤ 1.15
(IEC) times 5 % ± 15 ms for 2 ≤ I/IP ≤ 20
and TIP/s ≥ 1;
or 2 ≤ I/3I0P ≤ 20
and T3I0P/s ≥ 1
(ANSI) times 5 % ± 15 ms for 2 ≤ I/IP ≤ 20
and DIP/s ≥ 1;
or 2 ≤ I/3I0P ≤ 20
and D3I0P/s ≥ 1
The set times are pure delay times with definite time protection.
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Further Definite Overcurrent IPh >STUB 0.10 A to 25.00 A1) (steps 0.01 A)
Stages; Stub Pro- (phases) or ∞ (ineffective)
tection
TIPh STUB 0.00 s to 30.00 s (steps 0.01 s)
(phases) or ∞ (ineffective)
3I0 >STUB 0.05 A to 25.00 A1) (steps 0.01 A)
(earth) or ∞ (ineffective)
T3I0 STUB 0.00 s to 30.00 s (steps 0.01 s)
(earth) or ∞ (ineffective)
Tolerances currents 3 % of setting value or 1% of rated current
times 1 % of setting value or 10 ms
Enable via special binary input is necessary.
The set times are pure delay times.
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Operating Times of Pickup time, minimum approx. 23 ms with fN = 50 Hz


Definite Stages approx. 21 ms with fN = 60 Hz
Pickup time, typical approx. 28 ms with fN = 50 Hz
approx. 26 ms with fN = 60 Hz
Dropoff time, typical approx. 31 ms with fN = 50 Hz
approx. 27 ms with fN = 60 Hz

Drop-off to Pickup Current stages approx. 0.95 for IP/IN ≥ 0.5


Ratios

7SD610 Manual 10-15


C53000-G1176-C145-1
Technical Data

100 100
t [s] t [s]

30 30
20 20

10 Tp 10
3.2
5 5
1.6 Tp
3 3
2 3.2
0.8 2

1 1 1.6
0.4

0.5 0.5 0.8


0.2
0.3 0.3 0.4
0.2 0.1
0.2
0.2
0.1 0.05
0.1
0.1
0.05
0.05 0.05
1 2 3 5 7 10 20 1 2 3 5 10 20
I/Ip I/Ip
0.14 13.5
Normal inverse: - ⋅ Tp
t = -------------------------------- [s] Very inverse: 1
- ⋅ T p [s]
t = --------------------------
(Type A) ( I ⁄ Ip )
0.02
–1 (Type B) (I ⁄ I ) – 1
p

100 1000
t [s]

300
t [s]
20 200

10 100

5 50
3 30 Tp
2 20 3.2

1 Tp 10 1.6
3.2
0.5 5 0.8
0.3 1.6 3
0.4
0.2 2
0.8
0.2
0.1 1
0.4
0.05 0.1 0.2 0.05 0.1
0.05 0.5
1 2 3 5 10 20 1 2 3 5 7 10 20
I/Ip I/Ip
80
Extremely inverse: t = ---------------------------- ⋅ T [s] 120
2 p Longtime inverse: t = ---------------------------- ⋅ T [s]
(Type C) (I ⁄ I ) – 1 1 p
p (I ⁄ I ) – 1
p
t trip time
Tp setting value time multiplier Note: For earth fault read 3I0p instead of
I fault current
Ip setting value current Ip and T3I0p instead of Tp

Figure 10-1 Trip time characteristics of inverse time overcurrent protection, acc. IEC (phases and earth)

10-16 7SD610 Manual


C53000-G1176-C145-1
Time Overcurrent Protection

100 100
t [s] t [s]

30 30
20 20

10 10
7 7
5 D [s] 5
3 15 3
2 10 2

1 5 1 D [s]
0.7 0.7
15
0.5 0.5
2 10
0.3 0.3
0.2 1 0.2 5

0.1 0.5 0.1


0.07 2
0.07 0.5 1
0.05 0.05
1 2 3 5 10 20 1 2 3 5 10 20
I/Ip I/Ip
 8.9341   0.2663 
INVERSE - + 0.17966 ⋅ D
t =  ------------------------------------- [s] SHORT INVERSE - + 0.03393 ⋅ D
t =  ------------------------------------- [s]
 ( I ⁄ I )2.0938 – 1   ( I ⁄ I ) 1.2969 – 1 
p p

100 100
t [s] D [s] t [s]
50 50
15
10
20 20
5
10 10

5 2 5 D [s]
3 3 15
1
2 2 10
0.5
1 1 5

0.5 0.5
2
0.3 0.3
0.2 0.2 1

0.1 0.1 0.5

0.05 0.05
1 2 3 5 10 20 1 2 3 5 10 20
I/Ip I/Ip
 0.0103 
t =  ------------------------- + 2.18592 ⋅ D [s]
5.6143
LONG INVERSE (I ⁄ I ) – 1 MODERATELY INVERSE - + 0.0228 ⋅ D
t =  -------------------------------- [s]
p  ( I ⁄ I )0.02 – 1 
p
Figure 10-2 Trip time characteristics of inverse time overcurrent protection, acc. ANSI/IEEE, (phases and earth)

7SD610 Manual 10-17


C53000-G1176-C145-1
Technical Data

100 100
t [s] t [s]

30 30
20 20

10 10

5 5
3 3
D [s]
2 2
15
10
1 1 D [s]
15
0.5 5
0.5
0.3 0.3 10
2
0.2 0.2
5
0.1 1
0.1
2
0.5 0.5 1
0.05 0.05
1 2 3 5 10 20 1 2 3 5 10 20
I/Ip I/Ip
 3,922   5.64 
VERY INVERSE - + 0.0982 ⋅ D [s]
t =  -------------------------- EXTREMELY INVERSE - + 0.02434 ⋅ D [s]
t =  --------------------------
 ( I ⁄ I )2 – 1   ( I ⁄ I )2 – 1 
p p

100

t [s]

30
20
t trip time
10
D setting value time multiplier
I fault current
5 Ip setting value current
D [s]
3 15
2 10

1 5

0.5
2
0.3
0.2 1 Note: For earth fault read 3I0p in-
stead of Ip and D3I0p instead of DIp
0.1
0.5

0.05
1 2 3 5 10 20
I/Ip
 0.4797 
DEFINITE INVERSE - + 0.21359 ⋅ D
t =  ------------------------------------- [s]
 ( I ⁄ I )1.5625 – 1 
p

Figure 10-3 Trip time characteristics of inverse time overcurrent protection, acc. ANSI/IEEE (phases and earth)

10-18 7SD610 Manual


C53000-G1176-C145-1
High-Current Switch-on-to-Fault Protection

10.7 High-Current Switch-on-to-Fault Protection

Pickup High current pickup I>>> 0.10 A to 15.00 A1) (steps 0.01 A)
High current pickup I>>>> 1.00 A to 25.00 A1) (steps 0.01 A)
or ∞ (ineffective)
Dropout to pickup ratio approx. 0.90
Pickup tolerance ≤ 3 % of set value or 1% of IN
1) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Times Shortest tripping time approx. 13 ms

10.8 Automatic Reclosure Function (optional)

Automatic Number of reclosures max. 8,


Reclosures first 4 with individual settings
Operating modes 1-pole, 3-pole or 1-/3-pole
Control with pickup or trip command
Action times 0.01 s to 300.00 s; ∞ (steps 0.01 s)
Initiation possible without pickup
and action time
Dead times for all cycles 0.01 s to 1800.00 s; ∞ (steps 0.01 s)
Dead times after evolving fault 0.01 s to 1800.00 s; (steps 0.01 s)
recognition
Reclaim time after reclosure 0.50 s to 300.00 s (steps 0.01 s)
Lock-out time after dynamic blocking 0.5 s (fix)
Blocking time after manual closing 0.50 s to 300.00 s; 0 (steps 0.01 s)
Start signal monitoring time 0.01 s to 300.00 s (steps 0.01 s)
Circuit-breaker supervision time 0.01 s to 300.00 s (steps 0.01 s)

Adaptive Dead Operating modes with voltage measurement or


Time / with close command transmission
Dead Line Check
Action time 0.01 s to 300.00 s; ∞ (steps 0.01 s)
Initiation possible without pickup and action time
Maximum dead time 0.50 s to 3000.00 s; ∞ (steps 0.01 s)
Voltage measurement dead line 2 V to 70 V (phase-to-earth)(steps 1 V)
Voltage measurement live line 30 V to 90 V (phase-to-earth)(steps 1 V)
Measuring time 0.10 s to 30.00 s (steps 0.01 s)
Delay for close comm. transmission 0.00 s to 300 s; ∞ (steps 0.01 s)

7SD610 Manual 10-19


C53000-G1176-C145-1
Technical Data

10.9 Circuit Breaker Failure Protection (optional)

Circuit Breaker Current flow monitoring 0.25 A to 20.00 A1) (steps 0.01 A)
Supervision Dropoff to pickup ratio approx. 0.95
Pickup tolerance 5 % of set value or 0.01 A1)
Breaker status monitoring
– with three-pole control binary input for CB auxiliary contact
– with individual pole control 1 binary input each for each pole, or
1 binary input each for NO and NC contacts
Note: Breaker failure protection can operate without the mentioned breaker auxiliary contacts but with re-
duced functionality. Processing of the auxiliary contacts are necessary for:
Breaker failure protection without or with insufficient current flow (e.g. Buchholz protection),
end fault protection, pole discrepancy supervision.
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Starting Conditions for beaker failure protection single-pole trip internally


three-pole trip internally
single-pole trip externally via
three-pole trip externally binary
inputs
three-pole trip without current

Times Pickup time approx. 3 ms with measured quantities


present
approx. 20 ms after switch-on of
measured quantities
Reset time ≤15 ms with sinusoidal meas. quantities,
≤25 ms maximum
Delay times for all stages 0.00 s to 30.00 s; ∞ (steps 0.01 s)
Time tolerance 1 % of setting value or 10 ms

End Fault with signal transmission to the opposite line end


Protection
Delay time 0.00 s to 30.00 s; ∞ (steps 0.01 s)
Time tolerance 1 % of setting value or 10 ms

Pole Discrepancy Starting criterion any pole open and any pole closed
Supervision
Supervision time 0.00 s to 30.00 s; ∞ (steps 0.01 s)
Time tolerance 1 % of setting value or 10 ms

10-20 7SD610 Manual


C53000-G1176-C145-1
Thermal Overload Protection

10.10 Thermal Overload Protection

Setting Ranges Factor k according to IEC 60255–8 0.10 to 4.00 (steps 0.01)
Time factor τ 1.0 min to 999.9 min (steps 0.1 min)
Alarm temperaturerise Θalarm/Θtrip 50 % to 100 % related to the trip
temperature rise (steps 1 %)
Current alarm stage Ialarm 0.10 A to 4.00 A1) (steps 0.01 A)
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Calculation Calculation method temperature rise maximum temperature rise of 3 phases


Method means of temperature rise of 3 phases
temperature rise from maximum current

Tripping see Figure 10-4


Characteristic
I  2  I pre  2
 ------------- – -------------
Tripping characteristic  k ⋅ I N  k ⋅ I N
t = τ ⋅ ln -------------------------------------------------
for (I/ k · IN) ≤ 8 I 2
 ------------
 k ⋅ I N – 1
-

Meaning of abbreviations: t tripping time


τ thermal time constant
I actual load current
Ipreprevious load current
k setting factor according to
IEC 60255–8
IN rated current of protected object

Drop-off Θ/Θtrip drop-off with Θalarm


Ratios
Θ/Θalarm approx. 0.99
I/Ialarm approx. 0.95

Tolerances Relating to k · IN 2 % or 10 mA1); class 2 % according to


IEC 60 255–8
Relating to tripping time 3 % or 1 s; class 3 % according to
IEC 60 255–8 for I/(k ·IN) > 1.25
1
) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

7SD610 Manual 10-21


C53000-G1176-C145-1
Technical Data

100 100

t [min] t [min]

50 Parameter: 50
Setting value;
Time constant
30 30
τ [min]
20 20
1000

Parameter:
10 10 Setting value;
500 Time constant

5 5
τ [min]

200 1000
3 3

2 2
100 500

1 1
50

200

0.5 0.5

20 100
0.3 0.3

0.2 0.2
10 50

0.1 0.1
5
20
1 2 1 2 5 10
0.05 0.05

1 2 3 4 5 6 7 8 10 12 1 2 3 4 5 6 7 8 10 12
I / (k·IN) I / (k·IN)

without previous load current with 90 % previous load current

2
I 2
 ------------- I  2  I pre 
 -------------
 k ⋅ I  –  k ⋅ I 
- - --------------
k ⋅ I  N N
N
t = τ ⋅ ln -------------------------------- [min] t = τ ⋅ ln --------------------------------------------------- [min]
I 2
 -------------
2
 -------------- – 1
I
- –1
k ⋅ I  k ⋅ I 
N N

Figure 10-4 Tripping characteristic of the overload protection

10-22 7SD610 Manual


C53000-G1176-C145-1
Monitoring Functions

10.11 Monitoring Functions

Measured Values Current sum IF = |i L1 + iL2 + iL3 + kI· iE | >


Σ,7+5(6+2/' · IN + Σ,)$&725 · Σ|i|
– SUM.I Threshold 0.05 A to 2.00 A1) (steps 0.01)
– SUM.I factor 0.00 to 0.95 (steps 0.01)
Current symmetry |Imin | / |Imax | < %$/)$&725,
as long as Imax / IN > %$/,/,0,7 / IN
– BAL.FACTOR I 0.10 to 0.95 (steps 0.01)
– BAL.I LIMIT 0.10 A to 1.00 A1) (steps 0.01 A)
Voltage symmetry |Umin | / |Umax | < %$/)$&7258
as long as |Umax | > %$/8/,0,7
– BAL.FACTOR U 0.58 to 0.95 (steps 0.01)
– BAL.U LIMIT 10 V to 100 V (steps 1 V)
Open circuit Monitoring of current transformer circuits
on current step change in one phase
without residual current
1) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.

Trip Circuit Super- Number of supervised trip circuits 1 to 3


vision
Operation of each trip circuit with 1 binary input or with 2 binary inputs
Alarm delay 1 s to 30 s (steps 1 s)

7SD610 Manual 10-23


C53000-G1176-C145-1
Technical Data

10.12 Supplementary Functions

Operational Operational measured values of currents IL1; IL2; IL3; 3I0; I1; I2
Measured Values in A primary and secondary and % of IN oper
– Tolerance 1 % of measured value or 1 % of IN
Phase angles of currents ϕ(IL1–IL2); ϕ(IL2–IL3); ϕ(IL3–IL1) in °
– Tolerance 1° at rated current
Operational measured values of voltages U L1–L2; UL2–L3; UL3–L1
in kV primary and V secondary
– Tolerance 1 % of measured value or 1 % of U N
Operational measured values of voltages U L1–E; UL2–E; UL3–E
iin kV primary and V secondary
– Tolerance 1 % of measured value or 1 % of U N
Operational measured values of voltages U L1–E; UL2–E; UL3–E
in % of UN oper /√3
– Tolerance 2 % of measured value or 2 % of UN
Operational measured values of voltages 3U0; U1; U2
in kV primary and V secondary
– Tolerance 1 % of measured value or 1 % of U N
2 % for 3U0 if 3U0 is not connected
Phase angles of voltages ϕ(UL1–UL2); ϕ(UL2–UL3); ϕ(UL3–UL1) in °
– Tolerance 1° at rated voltage
Operational measured values of power S; P; Q (apparent; active; reactive power)
in MVA, MW or Mvar primary
– Tolerance 2 % of measured value of apparent power
or 1 MVA/MW/Mvar
Operational measured values of
power factor cos ϕ
– Tolerance 0.02
Operational measured values
of frequency f in Hz
– Range 10 Hz to 75 Hz
– Tolerance 20 mHz within range fN ±10 %
and I ≥ IN or U ≥ UN
Operational measured value ΘL1; ΘL2; ΘL3; Θres
for thermal value referred to tripping temperature rise Θtrip
Measured values of
the differential protection IDIFFL1; IDIFFL2; IDIFFL3;
IREST L1; IRESTL2; IRESTL3
in % of operational rated current
Remote measured values of currents IL1; IL2; IL3 of remote end in % of IN oper;
ϕ(IL1); ϕ(IL2); ϕ(IL3) (remote vs. local) in °
Remote measured values of voltages UL1; UL2; UL3 of remote end in % of UN oper;
ϕ(UL1); ϕ(UL2); ϕ(UL3) (remote vs. local) in°

10-24 7SD610 Manual


C53000-G1176-C145-1
Supplementary Functions

Fault Event Storage of the messages of the last 8 faults


Data Log with a total of max. 200 messages

Fault Recording Number of stored fault records max. 8


Storage period max. 5 s for each fault
(start with pickup or trip) approx. 15 s in total
Sampling rate at fN = 50 Hz 1 ms
Sampling rate at fN = 60 Hz 0.83 ms
The fault recordings are synchronized between the ends.

Statistics Number of trip events caused by pole segregated


7SD610
Number of auto-reclose events caused segregated according to set cycle
by 7SD610
Total of interrupted currents
caused by 7SD610 pole segregated
Availability of transmission availability in %/min and %/h
Delay time of transmission resolution 0.01 ms

Real Time Clock Resolution for operational messages 1 ms


and Buffer Battery
Resolution for fault messages 1 ms
Buffer battery 3 V/1 Ah, type CR 1/2 AA
self-discharging time approx. 10 years

7SD610 Manual 10-25


C53000-G1176-C145-1
Technical Data

10.13 Dimensions

Housing for Panel


Flush Mounting or
Cubicle Installation

29.5 172 34 29.5 172 29 30


150
Monting plate Monting plate 145
266

244

266

244

2 2

34

Side view (with screwed terminals) Side view (with plug-in terminals) Rear view

146 +2

5 or M4
255.8 ± 0.3
245 + 1

6
Dimensions in mm
5.4

13.2 105 ± 0.5


7.3 131.5 ± 0.3

Panal cut-out

Figure 10-5 Dimensions 7SD610 for panel flush mounting or cubicle installation

10-26 7SD610 Manual


C53000-G1176-C145-1
Dimensions

Housing for Panel


Surface Mounting

165
144 10.5 260
31 45
29.5
46 60

150

266
280
320
344

1 15
9 16 30
71 Dimensions in mm

Front view Side view

Figure 10-6 Dimensions 7SD610 for panel surface mounting

7SD610 Manual 10-27


C53000-G1176-C145-1
Technical Data

10-28 7SD610 Manual


C53000-G1176-C145-1
Appendix A
This appendix is primarily a reference for the experienced user. This Chapter provides
ordering information for the models of 7SD610. General diagrams indicating the ter-
minal connections of the 7SD610 models are included. Connection examples show
the proper connections of the device to primary equipment in typical power system
configurations. Tables with all settings and all information available in a 7SD610
equipped with all options are provided.

A.1 Ordering Information and Accessories A-2


A.2 General Diagrams A-6
A.3 Connection Examples A-8
A.4 Preset Configurations A-10
A.5 Protocol Dependent Functions A-12

7SD610 Manual A-1


C53000-G1176-C145-1
Appendix

A.1 Ordering Information and Accessories

7 8 9 10 11 12 13 14 15

Differential Protection for Two End Operation 7SD610 _ _ 0

Measured Current Inputs


IPh = 1 A, IE = 1 A 1
IPh = 5 A, IE = 5 A 5

Auxiliary Voltage (Power Supply, Pick-up Threshold of Binary Inputs)


DC 24 to 48 V, binary input threshold 17 V 2) 2
DC 60 to 125 V 1), binary input threshold 17 V 2) 4
DC 110 to 250 V 1), AC 115 V, binary input threshold 73 V 2) 5

Housing, Number of Binary Inputs (BI) and Outputs (BO)


Flush mounting housing with screwed terminals, 1/3 x 19“, 7 BI, 5 BO, 1 Life Status Contact B
Surface mounting housing with two-tier terminals 1/3 x 19“, 7 BI, 5 BO, 1 Life Status Contact F
Flush mounting housing with plug-in terminals 1/3 x 19“, 7 BI, 5 BO, 1 Life Status Contact K

Region-Specific Default/Language Settings and Function Versions


Region GE: 50 Hz; IEC; German language (can be changed) A
Region world: 50/60 Hz; IEC/ANSI, English language (can be changed) B
Region US: 60 Hz; ANSI; US-English language (can be changed) C

System Interface (Port B)


No system interface 0
IEC Protocol, electrical RS232 1
IEC Protocol, electrical RS485 2
IEC Protocol, optical 820 nm, ST–plug 3

DIGSI/Modem Interface and Protection Data Interface 1 (Port C)


See additional specification M 9
12
Additional Specification M + M
Digsi/Modem Interface (Port C)
No DIGSI–Interface 0
DIGSI 4, electrical RS232 1
DIGSI 4, electrical RS485 2

Protect Data Interface 1 (Port D)


Optical 820 nm, 2 ST-plugs, optical fibre up to a length of 1.5 km, for direct connection or communication networks A
Optical 820 nm, 2 ST-plugs, optical fibre up to a length of 3.5 km, for direct connection via multimode fibre B
Optical 1300 nm, 2 ST-plugs, optical fibre up to a length of 10 km, for direct connection via monomode fibre C
Optical 1300 nm, 2 FC-plugs, optical fibre up to a length of 35 km, for direct connection via monomode fibre D

1) with plug-in jumper one of the 2 voltage ranges can be selected


2) for each binary input one of three pick-up threshold ranges can be selected with plug-in jumper

continued next page A-3

A-2 7SD610 Manual


C53000-G1176-C145-1
Ordering Information and Accessories

7 8 9 10 11 12 13 14 15
7SD610 _ _ 0
Differential Protection for Two End Operation

Functions 1
Only three-pole tripping without automatic reclosure 0
Only three-pole tripping with automatic reclosure 1
Single-/three-pole tripping without automatic reclosure 2
Single-/three-pole tripping with automatic reclosure 3

Backup Functions
without B
with emergency / backup time-overcurrent protection C

Additional Functions 1
4 Remote Commands Transformer Expansion (Vector Group Adaptation)
without without A
without with E
with without J
with with N

Ordering example: 7SD6101–4BA39–2BJ0 +M1A

Differential protection for two end operation


here: pos. 12 = 9 pointing at M1A, i.e. version with DIGSI-interface RS232 on the rear side
Protection Interface 1: 820 nm direct connection or communication networks

7SD610 Manual A-3


C53000-G1176-C145-1
Appendix

A.1.1 Accessories

Communication Converter for the serial connection of the differential protection system 7SD610 to the
Converter synchronous communication interfaces X21 or G703.
Name Order No.
Optical–electrical communication converter 7XV5662-0AA00

Voltage Transform-
er Miniature Circuit Nominal varies Order No.
Breaker Thermal 1.6 A; magnetic 6 A 3RV1611-1AG14

Interface Exchange interface modules


Modules
Name Order No.
RS232 C73207-A322-D631-1
RS485 C73207-A322-D632-1
LWL 820 nm C73207-A322-D633-1
F05 with ST–plug; 820 nm; C53207-A322-D651-1
multimode fibre up to a length of 1.5 km 1)
F06 with ST–plug; 820 nm; C53207-A322-D652-1
multimode fibre up to a length of 3 km
F07 with ST–plug; 1300 nm; C53207-A322-D653-1
monomode fibre up to a length of 10 km
F08 with FC–plug; 1300 nm; C53207-A322-D654-1
monomode fibre up to a length of 35 km
1
) is also used for the connection to an optical-electrical communication converter

Terminal Block
Covering Caps Covering cap for terminal block type Order No.
18 terminal voltage, 12 terminal current block C73334-A1-C31-1
12 terminal voltage, 8 terminal current block C73334-A1-C32-1

Short Circuit Links


Short circuit links for purpose/terminal type Order No.
Voltage connections, 18 terminal, or 12 terminal C73334-A1-C34-1
Current connections,12 terminal, or 8 terminal C73334-A1-C33-1

Plug-in Connectors
Connector Type Order No.
2 pin C73334-A1-C35-1
3 pin C73334-A1-C36-1

A-4 7SD610 Manual


C53000-G1176-C145-1
Ordering Information and Accessories

Mounting Bracket
for 19"-Racks Name Order No.
Angle Strip (Mounting Rail) C73165-A63-C200-2

Battery
Lithium-Battery 3 V/1 Ah, Type CR 1/2 AA Order No.
VARTA 6127 101 501

Interface Cable An interface cable is necessary for communication between the SIPROTEC device
and a PC. Requirements for the computer are Windows 95 or Windows NT4 and the
operating software DIGSI® 4.
Interface cable between PC or SIPROTEC device Order No.
Cable with 9-pin male/female connections 7XV5100-4

Operating Software Software for setting and operating SIPROTEC® 4 devices


DIGSI® 4
Operating Software DIGSI® 4 Order No.
DIGSI® 4, basic version with license for 10 computers 7XS5400-0AA00
DIGSI® 4, complete version with all option packages 7XS5402-0AA0

Graphical Analysis Software for graphical visualization, analysis, and evaluation of fault data. Option
Program DIGRA package of the complete version of DIGSI® 4
Graphical analysis program DIGRA® Order No.
Full version with license for 10 machines 7XS5410-0AA0

DIGSI REMOTE 4 Software for remotely operating protective devices via a modem (and possibly a star
connector) using DIGSI® 4. (Option package of the complete version of DIGSI® 4.
DIGSI REMOTE 4 Order No.
Full version with license for 10 machines 7XS5440-1AA0

SIMATIC CFC 4 Graphical software for setting interlocking (latching) control conditions and creating
additional function is SIPROTEC 4 devices. Option package for the complete version
of DIGSI® 4.
SIMATIC CFC 4 Order No.
Full version with license for 10 machines 7XS5450-0AA0

7SD610 Manual A-5


C53000-G1176-C145-1
Appendix

A.2 General Diagrams

A.2.1 Panel Flush Mounting or Cubicle Mounting

7SD610∗−∗B/K

Q1 BO1 R1
IL1
Q2 BO2 R2
Q3 BO3 R3
IL2
Q4 R4
Q5 R5
IL3 BO4
Q6 R6
Q7 R7
I4 BO5
Q8 R8
R15 UL1
R17 UL2
R18 UL3
R16
R13 U4
R14
F5 BI1
F6 BI2
F7 BI3
Live status 1 2
F3
F8 BI4
contact 3 2
F9 BI5 F4
F10 +
R9 BI6 Power F1
(~)
R10 supply - F2
R11 BI7
R12
Protection Data Assignment of Pins of Interfaces,
refer to Table 8-11 and 8-12 in
Interface 1 D

Service interface C
Subsection 8.2.1

System interface B

Time synchronization A

Operator interface

Earthing at the
rear wall
Interference suppression
capacitors at the
relay contacts,
Ceramic, 4.7 nF, 250 V

Figure A-1 General diagram for 7SD610∗–∗B/K (panel flush mounting or cubicle mounting)

A-6 7SD610 Manual


C53000-G1176-C145-1
General Diagrams

A.2.2 Panel Surface Mounting

7SD610∗−∗F

15 BO1 43
IL1
30 BO2 58
14 BO3 42
IL2
29 57
13 56
IL3 BO4
28 41
12 55
I4 BO5
27 40
45 UL1
44 UL2
60 UL3
59
26 U4
25

37 BI1
36 Live status 1 2
31
BI2
35 BI3 contact 3 2
32
34 BI4
+
33 BI5 Power (~)
10
52 supply - 11
54 BI6
39 Earthing
53 BI7 terminal (16)
38
2 IN SYNC
17 IN 12 V
3 COM SYNC
Time synchronization 18 COMMON
4 IN 5 V
19 IN 24 V
1 Screen

8-11 in Subsection 8.2.1


Protection Data
Interfaces, refer to Table

D
Assignment of Pins of

Interface 1

Service interface C

System interface B

Operator interface

Earthing at the
side wall Interference suppression
capacitors at the
relay contacts,
Ceramic, 4.7 nF, 250 V

Figure A-2 General diagram 7SD610∗–∗F (panel surface mounting)

7SD610 Manual A-7


C53000-G1176-C145-1
Appendix

A.3 Connection Examples

Current Trans-
former Connection
Examples
Panel surface mounted
Flush mounted/cubicle
IL1
15 Q1 Q2 30
IL2
14 Q3 Q4 29
IL3
13 Q5 Q6 28
K k

I4
L l 12 Q7 Q8 27

7SD610

L1 L2 L3

Figure A-3 Current connections to three current transformers with a star-point connection
for earth current (residual , neutral current), normal circuit layout — appropri-
ate for all networks

Panel surface mounted


Flush mounted/cubicle
IL1
15 Q1 Q2 30
IL2
14 Q3 Q4 29
IL3
13 Q5 Q6 28
K k

I4
L l 27 Q8 Q7 12

7SD610
L1 L2 L3

K
k

L
l
Important! Cable shield grounding must be done on the cable side!
Note:Change of Address 0201 setting changes polarity of 3I0 Current
Input, i.e. terminal Q7 must be connected to that CT terminal p
ing in the same direction as the starpoint of the phase current
(towards “Line side” in this diagram)

Figure A-4 Current connections to three current transformers and a separate neutral current
transformer (summation transformer) for earth current — preferred for effectively
or low-resistive earthed networks

A-8 7SD610 Manual


C53000-G1176-C145-1
Connection Examples

Voltage Trans-
L1
former Connection
L2
Examples
L3

Panel surface mounted


Flush mounted/cubicle
UL1
45 R15
UL2
44 R17
UL3
60 R18

59 R16

7SD610

Figure A-5 Voltage connections to three Wye-connected voltage transformers (normal cir-
cuit layout)

L1

L2
L3

Panel surface mounted


Flush mounted/cubicle
UL1
45 R15
UL2
44 R17
UL3
60 R18

e n 59 R16

U4
26 R13

25 R14

7SD610

Figure A-6 Voltage connections to three Wye-connected voltage transformers with


additional open-delta windings (e–n–winding)

7SD610 Manual A-9


C53000-G1176-C145-1
Appendix

A.4 Preset Configurations

Binary Inputs
Table A-1 Binary input presettings

Binary Input LCD Text Function No. Remarks


BI 1 >Intertrip 3pol 3504 Intertrip signal for remote end,
H–active
BI 2 >Reset LED 0005 Reset of latched indications,
H–active
BI 3 >Diff block 3525 Block differential protection,
H–active
BI 4 >DTT Trip L123 4417 Direct local trip (three-pole),
H–active
BI 5 >BLOCK O/C I>> 7104 Block stages of the time-overcurrent
>BLOCK O/C I> 7105 protection,
>BLOCK O/C Ip 7106 H-active
>BLOCK O/C Ie>> 7107
>BLOCK O/C Ie> 7108
>BLOCK O/C Iep 7109
>BLOCK I-STUB 7130
>BLOCK O/CIe>>> 7132
BI 6 >Test mode 3194 Switch over to test mode,
H–active
BI 7 >CB1 Ready 0371 Circuit breaker ready for TRIP-CLOSE
cycle (CB check before AR),
H-active

Binary Outputs
Table A-2 Binary output presettings

Binary LCD Text Function No. Remarks


Output
BO1 Relay PICKUP L1 0503 Device (general) pickup phase L1,
non-latched
BO2 Relay PICKUP L2 0504 Device (general) pickup phase L2,
non-latched
BO3 Relay PICKUP L3 0505 Device (general) pickup phase L3,
non-latched
BO4 Relay TRIP 0511 Device (general) trip command,
non-latched
BO5 Relay TRIP 0511 Device (general) trip command,
non-latched

A-10 7SD610 Manual


C53000-G1176-C145-1
Preset Configurations

LEDs
Table A-3 LED presettings

LED LCD Text Function No. Remarks


LED1 Relay TRIP 0511 Device (general) trip command,
latched
LED2 Relay PICKUP L1 0503 Device (general) pickup phase L1,
latched
LED3 Relay PICKUP L2 0504 Device (general) pickup phase L2
latched
LED4 Relay PICKUP L3 0505 Device (general) pickup phase L3,
latched
LED5 Par. different 3235 Different parameters are set in the 2
devices; non-latched
LED6 PI1 Data fault 3229 Protection data interface 1 faulty,
non-latched
LED7 DT inconsistent 3233 Inconsistencies between devices:
DT unequal 3234 Device table, both devices with the
Equal IDs 3487 same address, non-latched

Preset CFC–Charts 7SD610 provides a CFC configuration sheet with preset logical functions. These con-
vert the binary inputs “!'DWD6WRS” and “!7HVW'LII” from single point indication
(SP) into internal single point indication (IntSP).

1HJDWRU
1(* 3/&B%($
1HJDWRU ²
IN: 'HYLFH!'DWD6WRS63 %2; <%2 OUT: 'HYLFH8QORFN'7,QW63

7LPHU
7,0(5 3/&B%($ 25
7LPHU ² 25 3/&B%($
0 %25 4%2 25²*DWH ²
IN: 'LII3URW!7HVW'LII63 %26 47%2 %2; <%2
10 ,7[PV 47%2 %2;
10 ,7[PV

,19(57 &20
1(* 3/&B%($ %22/B72B,& 3/&B%($
1HJDWRU ² %RROWRLQWHUQ ²
IN: 'LII3URW!7HVW'LII63 %2; <%2 16#0 :25,*,1 ,(%2 OUT: 'LII3URW7HVW'LII,QW63
'0 16#0 :3523
%8,/'B', 3/&B%($ 0 ,7,0[P
&UHDWH'RXEOH ² %275,*
0 %27<3B'3B, <: :9$/
%29$/2))
IN: 'LII3URW!7HVW'LII63 %29$/21

7SD610 Manual A-11


C53000-G1176-C145-1
Appendix

A.5 Protocol Dependent Functions

Protocol →
IEC 60870–5–103
Function ↓
Operational measured Yes
values
Metering values Yes
Fault recording Yes
User-defined alarms and Yes
switching objects
Time synchronization Via Protocol;
DCF77/IRIG B;
Interface;
Binary Input
Alarms with Time Stamp Yes

Commissioning Tools:
Alarm and measured Yes
value transmission
blocking
Generate test alarms Yes

A-12 7SD610 Manual


C53000-G1176-C145-1
A.6 List of Settings
C53000-G1176-C145-1
7SD610 Manual

Note: Depending on the version and the variant ordered some addresses are not used or have different default settings. The setting ranges and
presettings listed in the following table refer to a nominal current value IN = 1 A. For a secondary nominal current value IN = 5 A the current values
are to be multiplied by 5. For setting primary values the transformation ratio of the transformer also must be taken into consideration.

Addr. Setting Title Function Setting Options Default Setting Comments


201 CT Starpoint Power System Data 1 towards Line towards Line CT Starpoint
towards Busbar
203 Unom PRIMARY Power System Data 1 0.4..800.0 kV 11.0 kV Rated Primary Voltage
204 Unom SECONDARY Power System Data 1 80..125 V 100 V Rated Secondary Voltage (L-L)
205 CT PRIMARY Power System Data 1 10..5000 A 400 A CT Rated Primary Current
206 CT SECONDARY Power System Data 1 1A 1A CT Rated Secondary Current
5A
210 U4 transformer Power System Data 1 not connected not connected U4 voltage transformer is
Udelta transformer
211 Uph / Udelta Power System Data 1 0.10..9.99 1.73 Matching ratio Phase-VT To Open-Delta-
VT
220 I4 transformer Power System Data 1 not connected not connected I4 current transformer is
Neutral Current (of the pro-
tected line)
221 I4/Iph CT Power System Data 1 0.010..5.000 1.000 Matching ratio I4/Iph for CT’s
230 Rated Frequency Power System Data 1 50 Hz 50 Hz Rated Frequency
60 Hz
240A TMin TRIP CMD Power System Data 1 0.02..30.00 sec 0.10 sec Minimum TRIP Command Duration
241A TMax CLOSE CMD Power System Data 1 0.01..30.00 sec 1.00 sec Maximum Close Command Duration
242 T-CBtest-dead Power System Data 1 0.00..30.00 sec 0.10 sec Dead Time for CB test-autoreclosure
251 K_ALF/K_ALF_N Power System Data 1 1.00..10.00 1.00 k_alf/k_alf nominal
253 E% ALF/ALF_N Power System Data 1 0.5..50.0 % 5.0 % CT Error in % at k_alf/k_alf nominal
254 E% K_ALF_N Power System Data 1 0.5..50.0 % 10.0 % CT Error in % at k_alf nominal

List of Settings
301 ACTIVE GROUP Change Group Group A Group A Active Setting Group is
Group B
Group C
A-13

Group D
A-14

Appendix
Addr. Setting Title Function Setting Options Default Setting Comments
302 CHANGE Change Group Group A Group A Change to Another Setting Group
Group B
Group C
Group D
Binary Input
Protocol
402A WAVEFORMTRIG- Oscillographic Fault Save with Pickup Save with Pickup Waveform Capture
GER Records Save with TRIP
Start with TRIP
403A WAVEFORM DATA Oscillographic Fault Fault event Fault event Scope of Waveform Data
Records Power System fault
410 MAX. LENGTH Oscillographic Fault 0.30..5.00 sec 1.00 sec Max. length of a Waveform Capture
Records Record
411 PRE. TRIG. TIME Oscillographic Fault 0.05..0.50 sec 0.10 sec Captured Waveform Prior to Trigger
Records
412 POST REC. TIME Oscillographic Fault 0.05..0.50 sec 0.10 sec Captured Waveform after Event
Records
415 BinIn CAPT.TIME Oscillographic Fault 0.10..5.00 sec; ∞ 0.50 sec Capture Time via Binary Input
Records
610 FltDisp.LED/LCD Device Display Targets on every Display Targets on every Fault Display on LED / LCD
Pickup Pickup
Display Targets on TRIP only
1103 FullScaleVolt. Power System Data 2 0.4..800.0 kV 11.0 kV Measurement: Full Scale Voltage (100%)
1104 FullScaleCurr. Power System Data 2 10..5000 A 400 A Measurement: Full Scale Current (100%)
1106 OPERATION POWER Power System Data 2 0.2..1000.0 MVA 7.6 MVA Operational power of protection zone
1130A PoleOpenCurrent Power System Data 2 0.05..1.00 A 0.10 A Pole Open Current Threshold
1132A SI Time all Cl. Power System Data 2 0.01..30.00 sec 0.10 sec Seal-in Time after ALL closures
1134 Line status Power System Data 2 with Pole Open Current with Pole Open Current Line status
Threshold only Threshold only
C53000-G1176-C145-1

with CBaux AND Pole Open


Current
7SD610 Manual

1150A SI Time Man.Cl Power System Data 2 0.01..30.00 sec 0.30 sec Seal-in Time after MANUAL closures
1155 3pole coupling Power System Data 2 with Pickup with Trip 3 pole coupling
with Trip
C53000-G1176-C145-1
7SD610 Manual
Addr. Setting Title Function Setting Options Default Setting Comments
1156A Trip2phFlt Power System Data 2 3pole 3pole Trip type with 2phase faults
1pole, leading phase
1pole, lagging phase
1161 VECTOR GROUP U Power System Data 2 0..11 0 Vector group numeral for voltage
1162 VECTOR GROUP I Power System Data 2 0..11 0 Vector group numeral for current
1163 TRANS STP IS Power System Data 2 Solid Earthed Solid Earthed Transformer starpoint is
Not Earthed
1201 STATE OF DIFF. Differential Protection OFF ON State of differential protection
ON
1210 I-DIFF> Differential Protection 0.10..20.00 A 0.30 A I-DIFF>: Pickup value
1213 I-DIF>SWITCH ON Differential Protection 0.10..20.00 A 0.30 A I-DIFF>: Value under switch on condition
1217A T-DELAY I-DIFF> Differential Protection 0.00..60.00 sec; ∞ 0.00 sec I-DIFF>: Trip time delay
1218A T3I0 1PHAS Differential Protection 0.00..60.00 sec; ∞ 0.00 sec Delay 1ph-faults (comp/isol. star-point)
1233 I-DIFF>> Differential Protection 0.8..100.0 A; ∞ 1.2 A I-DIFF>>: Pickup value
1301 I-TRIP SEND Intertrip YES NO State of transmit. the intertrip command
NO
1302 I-TRIP RECEIVE Intertrip Alarm only Trip Reaction if intertrip command is receiv.
Trip
1303 T-ITRIP BI Intertrip 0.00..30.00 sec 0.02 sec Delay for intertrip via binary input
1304 T-ITRIP PROL BI Intertrip 0.00..30.00 sec 0.00 sec Prolongation for intertrip via bin.input
1501 STATE PROT I 1 Protection Interface (Port ON ON State of protection interface 1
D+E) OFF
1502 CONNEC. 1 OVER Protection Interface (Port Direct connection with fibre Direct connection with fibre Connection 1 over
D+E) optic cabel optic cabel
Communication converter
with 64 kBit/s
Communication converter
with 128 kBit/s
Communication converter
with 512 kBit/s

List of Settings
1505A PROT 1 T-DELAY Protection Interface (Port 0.1..30.0 ms 30.0 ms Maximal permissible delay time
D+E)
1506A PROT 1 UNSYM. Protection Interface (Port 0.000..3.000 ms 0.000 ms Transmission time difference
A-15

D+E)
A-16

Appendix
Addr. Setting Title Function Setting Options Default Setting Comments
1509 T-DATA DISTURB Protection Interface (Port 0.05..2.00 sec 0.10 sec Time delay for data disturbance alarm
D+E)
1510 T-DATAFAIL Protection Interface (Port 0.0..60.0 sec 6.0 sec Time del for transmission failure alarm
D+E)
1701 ID OF RELAY 1 Differential Topology 1..65534 1 Identification number of relay 1
1702 ID OF RELAY 2 Differential Topology 1..65534 2 Identification number of relay 2
1710 LOCAL RELAY Differential Topology relay 1 relay 1 Local relay is
relay 2
2201 FCT Direct Trip DTT Direct Transfer Trip ON OFF Direct Transfer Trip (DTT)
OFF
2202 Trip Time DELAY DTT Direct Transfer Trip 0.00..30.00 sec; ∞ 0.01 sec Trip Time Delay
2301 INRUSH REST. Differential Protection OFF OFF Inrush Restraint
ON
2302 2nd HARMONIC Differential Protection 10..45 % 15 % 2nd. harmonic in % of fundamental
2303 CROSS BLOCK Differential Protection NO NO Cross Block
YES
2305 MAX INRUSH PEAK Differential Protection 1.1..25.0 A 15.0 A Maximum inrush-peak value
2310 CROSSB 2HM Differential Protection 0.00..60.00 sec; ∞ 0.00 sec Time for Crossblock with 2nd harmonic
2401 FCT HS/SOTF-O/C Instantaneous High- ON ON Inst. High Speed/SOTF-O/C is
Speed SOTF Overcurrent OFF
2404 I>>> Instantaneous High- 0.10..15.00 A; ∞ 1.50 A I>>> Pickup
Speed SOTF Overcurrent
2405A I>>>> Instantaneous High- 1.00..25.00 A; ∞ ∞A I>>>> Pickup
Speed SOTF Overcurrent
2601 Operating Mode Backup overcurrent ON ON Operating mode
Only Emergency protection
OFF
2610 Iph>> Backup overcurrent 0.10..25.00 A; ∞ 2.00 A Iph>> Pickup
C53000-G1176-C145-1

2611 T Iph>> Backup overcurrent 0.00..30.00 sec; ∞ 0.30 sec T Iph>> Time delay
0.05..25.00 A; ∞
7SD610 Manual

2612 3I0>> PICKUP Backup overcurrent 0.50 A 3I0>> Pickup


2613 T 3I0>> Backup overcurrent 0.00..30.00 sec; ∞ 2.00 sec T 3I0>> Time delay
2614 I>> Telep/BI Backup overcurrent NO YES Instantaneous trip via Teleprot./BI
YES
C53000-G1176-C145-1
7SD610 Manual
Addr. Setting Title Function Setting Options Default Setting Comments
2615 I>> SOTF Backup overcurrent NO NO Instantaneous trip after SwitchOnToFault
YES
2620 Iph> Backup overcurrent 0.10..25.00 A; ∞ 1.50 A Iph> Pickup
2621 T Iph> Backup overcurrent 0.00..30.00 sec; ∞ 0.50 sec T Iph> Time delay
2622 3I0> Backup overcurrent 0.05..25.00 A; ∞ 0.20 A 3I0> Pickup
2623 T 3I0> Backup overcurrent 0.00..30.00 sec; ∞ 2.00 sec T 3I0> Time delay
2624 I> Telep/BI Backup overcurrent NO NO Instantaneous trip via Teleprot./BI
YES
2625 I> SOTF Backup overcurrent NO NO Instantaneous trip after SwitchOnToFault
YES
2630 Iph> STUB Backup overcurrent 0.10..25.00 A; ∞ 1.50 A Iph> STUB Pickup
2631 T Iph STUB Backup overcurrent 0.00..30.00 sec; ∞ 0.30 sec T Iph STUB Time delay
2632 3I0> STUB Backup overcurrent 0.05..25.00 A; ∞ 0.20 A 3I0> STUB Pickup
2633 T 3I0 STUB Backup overcurrent 0.00..30.00 sec; ∞ 2.00 sec T 3I0 STUB Time delay
2634 I-STUB Telep/BI Backup overcurrent NO NO Instantaneous trip via Teleprot./BI
YES
2635 I-STUB SOTF Backup overcurrent NO NO Instantaneous trip after SwitchOnToFault
YES
2640 Ip> Backup overcurrent 0.10..4.00 A; ∞ ∞A Ip> Pickup
2642 T Ip Time Dial Backup overcurrent 0.05..3.00 sec; ∞ 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip Backup overcurrent 0.50..15.00; ∞ 5.00 Time Dial TD Ip
2646 T Ip Add Backup overcurrent 0.00..30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP Backup overcurrent 0.05..4.00 A; ∞ ∞A 3I0p Pickup
2652 T 3I0p TimeDial Backup overcurrent 0.05..3.00 sec; ∞ 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p Backup overcurrent 0.50..15.00; ∞ 5.00 Time Dial TD 3I0p
2656 T 3I0p Add Backup overcurrent 0.00..30.00 sec 0.00 sec T 3I0p Additional Time Delay
2660 IEC Curve Backup overcurrent Normal Inverse Normal Inverse IEC Curve

List of Settings
Very Inverse
Extremely Inverse
Long time inverse
A-17
A-18

Appendix
Addr. Setting Title Function Setting Options Default Setting Comments
2661 ANSI Curve Backup overcurrent Inverse Inverse ANSI Curve
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
2670 I(3I0)p Tele/BI Backup overcurrent NO NO Instantaneous trip via Teleprot./BI
YES
2671 I(3I0)p SOTF Backup overcurrent NO NO Instantaneous trip after SwitchOnToFault
YES
2680 SOTF Time DELAY Backup overcurrent 0.00..30.00 sec 0.00 sec Trip time delay after SOTF
2901 MEASURE. SUPERV Measurement Supervision ON ON Measurement Supervision
OFF
2902A BALANCE U-LIMIT Measurement Supervision 10..100 V 50 V Voltage Threshold for Balance Monitoring
2903A BAL. FACTOR U Measurement Supervision 0.58..0.95 0.75 Balance Factor for Voltage Monitor
2904A BALANCE I LIMIT Measurement Supervision 0.10..1.00 A 0.50 A Current Balance Monitor
2905A BAL. FACTOR I Measurement Supervision 0.10..0.95 0.50 Balance Factor for Current Monitor
2906A ΣI THRESHOLD Measurement Supervision 0.10..2.00 A 0.25 A Summated Current Monitoring Threshold
2907A ΣI FACTOR Measurement Supervision 0.00..0.95 0.50 Summated Current Monitoring Factor
2908 BROKEN WIRE Measurement Supervision ON ON Fast broken current-wire supervision
OFF
2921 FAST Σ i SUPERV Measurement Supervision ON ON State of fast current summation supervis
OFF
3401 AUTO RECLOSE Auto Reclose OFF ON Auto-Reclose Function
ON
3402 CB? 1.TRIP Auto Reclose YES NO CB ready interrogation at 1st trip
NO
C53000-G1176-C145-1

3403 T-RECLAIM Auto Reclose 0.50..300.00 sec 3.00 sec Reclaim time after successful AR cycle
3404 T-BLOCK MC Auto Reclose 0.50..300.00 sec; 0 1.00 sec AR blocking duration after manual close
7SD610 Manual

3406 EV. FLT. RECOG. Auto Reclose with Pickup with Trip Evolving fault recognition
with Trip
3407 EV. FLT. MODE Auto Reclose Stops Auto Reclose starts 3pole AR-cycle Evolving fault (during the dead time)
starts 3pole AR-cycle
C53000-G1176-C145-1
7SD610 Manual
Addr. Setting Title Function Setting Options Default Setting Comments
3408 T-Start MONITOR Auto Reclose 0.01..300.00 sec 0.50 sec AR start-signal monitoring time
3409 CB TIME OUT Auto Reclose 0.01..300.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time
3410 T RemoteClose Auto Reclose 0.00..300.00 sec; ∞ 0.20 sec Send delay for remote close command
3411A T-DEAD EXT. Auto Reclose 0.50..300.00 sec; ∞ ∞ sec Maximum dead time extension
3420 AR WITH DIFF Auto Reclose YES YES AR with differential protection ?
NO
3421 AR w/ SOTF-O/C Auto Reclose YES YES AR with switch-onto-fault overcurrent
NO
3423 AR WITH I.TRIP Auto Reclose YES YES AR with intertrip ?
NO
3424 AR w/ DTT Auto Reclose YES YES AR with direct transfer trip
NO
3425 AR w/ BackUpO/C Auto Reclose YES YES AR with back-up overcurrent
NO
3430 AR TRIP 3pole Auto Reclose YES YES 3pole TRIP by AR
NO
3431 DLC / RDT Auto Reclose Without Without Dead Line Check / Reduced Dead Time
Dead Line Check (DLC)
3433 T-ACTION ADT Auto Reclose 0.01..300.00 sec; ∞ 0.20 sec Action time
3434 T-MAX ADT Auto Reclose 0.50..3000.00 sec 5.00 sec Maximum dead time
3435 ADT 1p allowed Auto Reclose YES NO 1pole TRIP allowed
NO
3436 ADT CB? CLOSE Auto Reclose YES NO CB ready interrogation before reclosing
NO
3437 ADT SynRequest Auto Reclose YES NO Request for synchro-check after 3pole AR
NO
3438 T U-stable Auto Reclose 0.10..30.00 sec 0.10 sec Supervision time for dead/live voltage
3440 U-live> Auto Reclose 30..90 V 48 V Voltage threshold for live line or bus
3441 U-dead< Auto Reclose 2..70 V 30 V Voltage threshold for dead line or bus

List of Settings
3450 1.AR: START Auto Reclose YES YES Start of AR allowed in this cycle
NO
3451 1.AR: T-ACTION Auto Reclose 0.01..300.00 sec; ∞ 0.20 sec Action time
A-19
A-20

Appendix
Addr. Setting Title Function Setting Options Default Setting Comments
3453 1.AR Tdead 1Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3454 1.AR Tdead 2Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3455 1.AR Tdead 3Flt Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3456 1.AR Tdead1Trip Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV. Auto Reclose 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3459 1.AR: CB? CLOSE Auto Reclose YES NO CB ready interrogation before reclosing
NO
3460 1.AR SynRequest Auto Reclose YES NO Request for synchro-check after 3pole AR
NO
3461 2.AR: START Auto Reclose YES NO AR start allowed in this cycle
NO
3462 2.AR: T-ACTION Auto Reclose 0.01..300.00 sec; ∞ 0.20 sec Action time
3464 2.AR Tdead 1Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3466 2.AR Tdead 3Flt Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3467 2.AR Tdead1Trip Auto Reclose 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3468 2.AR Tdead3Trip Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV. Auto Reclose 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR: CB? CLOSE Auto Reclose YES NO CB ready interrogation before reclosing
NO
3471 2.AR SynRequest Auto Reclose YES NO Request for synchro-check after 3pole AR
NO
3472 3.AR: START Auto Reclose YES NO AR start allowed in this cycle
NO
3473 3.AR: T-ACTION Auto Reclose 0.01..300.00 sec; ∞ 0.20 sec Action time
C53000-G1176-C145-1

3475 3.AR Tdead 1Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
7SD610 Manual

3477 3.AR Tdead 3Flt Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip Auto Reclose 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3479 3.AR Tdead3Trip Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
C53000-G1176-C145-1
7SD610 Manual
Addr. Setting Title Function Setting Options Default Setting Comments
3480 3.AR: Tdead EV. Auto Reclose 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE Auto Reclose YES NO CB ready interrogation before reclosing
NO
3482 3.AR SynRequest Auto Reclose YES NO Request for synchro-check after 3pole AR
NO
3483 4.AR: START Auto Reclose YES NO AR start allowed in this cycle
NO
3484 4.AR: T-ACTION Auto Reclose 0.01..300.00 sec; ∞ 0.20 sec Action time
3486 4.AR Tdead 1Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt Auto Reclose 0.01..1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip Auto Reclose 0.01..1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3490 4.AR Tdead3Trip Auto Reclose 0.01..1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV. Auto Reclose 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE Auto Reclose YES NO CB ready interrogation before reclosing
NO
3493 4.AR SynRequest Auto Reclose YES NO Request for synchro-check after 3pole AR
NO
3901 FCT BreakerFail Breaker Failure ON ON Breaker Failure Protection is
OFF
3902 I> BF Breaker Failure 0.05..20.00 A 0.10 A Pick-up threshold I>
3903 1p-RETRIP (T1) Breaker Failure NO YES 1pole retrip with stage T1 (local trip)
YES
3904 T1-1pole Breaker Failure 0.00..30.00 sec; ∞ 0.00 sec T1, Delay after 1pole start (local trip)
3905 T1-3pole Breaker Failure 0.00..30.00 sec; ∞ 0.00 sec T1, Delay after 3pole start (local trip)
3906 T2 Breaker Failure 0.00..30.00 sec; ∞ 0.15 sec T2, Delay of 2nd stage (busbar trip)
3907 T3-BkrDefective Breaker Failure 0.00..30.00 sec; ∞ 0.00 sec T3, Delay for start with defective bkr.
3908 Trip BkrDefect. Breaker Failure NO NO Trip output selection with defective bkr

List of Settings
trips with T1-trip-signal
trips with T2-trip-signal
trips with T1 and T2-trip-sig-
nal
A-21
A-22

Appendix
Addr. Setting Title Function Setting Options Default Setting Comments
3909 Chk BRK CONTACT Breaker Failure NO YES Check Breaker contacts
YES
3921 End Flt. stage Breaker Failure ON OFF End fault stage is
OFF
3922 T-EndFault Breaker Failure 0.00..30.00 sec; ∞ 2.00 sec Trip delay of end fault stage
3931 PoleDiscrepancy Breaker Failure ON OFF Pole Discrepancy supervision
OFF
3932 T-PoleDiscrep. Breaker Failure 0.00..30.00 sec; ∞ 2.00 sec Trip delay with pole discrepancy
4001 FCT TripSuperv. Trip Circuit Supervision ON OFF TRIP Circuit Supervision is
OFF
4002 No. of BI Trip Circuit Supervision 1..2 2 Number of Binary Inputs per trip circuit
4003 Alarm Delay Trip Circuit Supervision 1..30 sec 2 sec Delay Time for alarm
4201 Ther. OVER LOAD Thermal Overload OFF OFF Thermal overload protection
ON
Alarm Only
4202 K-FACTOR Thermal Overload 0.10..4.00 1.10 K-Factor
4203 TIME CONSTANT Thermal Overload 1.0..999.9 min 100.0 min Time Constant
4204 Θ ALARM Thermal Overload 50..100 % 90 % Thermal Alarm Stage
4205 I ALARM Thermal Overload 0.10..4.00 A 1.00 A Current Overload Alarm Setpoint
4206 CALC. METHOD Thermal Overload Theta Max Theta Max Method of Acquiring Temperature
Average \T
\T @ Imax
4401 IP-A (A.x.x.x) Commissioning Tool 0..255 141 IP-address ×××.xxx.xxx.xxx(Position 1-3)
4402 IP-B (x.B.x.x) Commissioning Tool 0..255 142 IP-address xxx.×××.xxx.xxx(Position 4-6)
4403 IP-C (x.x.C.x) Commissioning Tool 0..255 255 IP-address xxx.xxx.×××.xxx(Position 7-9)
4404 IP-D (x.x.x.D) Commissioning Tool 0..255 150 IP-address xxx.xxx.xxx.×××(Pos. 10-12)
4405 NUM LOCK Commissioning Tool YES YES Num Lock
C53000-G1176-C145-1

NO
4406 LCP/NCP Commissioning Tool NO YES Front interface supports LCP/NCP mode
7SD610 Manual

YES
4411 IP-A (A.x.x.x) Commissioning Tool 0..255 141 IP-address ×××.xxx.xxx.xxx(Position 1-3)
4412 IP-B (x.B.x.x) Commissioning Tool 0..255 142 IP-address xxx.×××.xxx.xxx(Position 4-6)
C53000-G1176-C145-1
7SD610 Manual
Addr. Setting Title Function Setting Options Default Setting Comments
4413 IP-C (x.x.C.x) Commissioning Tool 0..255 255 IP-address xxx.xxx.×××.xxx(Position 7-9)
4414 IP-D (x.x.x.D) Commissioning Tool 0..255 160 IP-address xxx.xxx.xxx.×××(Pos. 10-12)
4415 NUM LOCK Commissioning Tool YES YES Num Lock
NO
4416 LCP/NCP Commissioning Tool NO YES Service interface supports LCP/NCP
YES mode

List of Settings
A-23
A.7 List of Information
A-24

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3 >Synchronize Internal Real Time Clock (>Time Device SP * * LED BI BO
Synch)
4 >Trigger Waveform Capture (>Trig.Wave.Cap.) Oscillographic Fault SP ON * LED BI BO
Records
5 >Reset LED (>Reset LED) Device SP * * LED BI BO
7 >Setting Group Select Bit 0 (>Set Group Bit0) Change Group SP * * LED BI BO
8 >Setting Group Select Bit 1 (>Set Group Bit1) Change Group SP * * LED BI BO
15 >Test mode (>Test mode) Device SP ON * LED BI BO 135 53 1 GI
OFF
16 >Stop data transmission (>DataStop) Device SP * * LED BI BO 135 54 1 GI
51 Device is Operational and Protecting (Device Device OUT ON * LED BO 135 81 1 GI
OK) OFF
52 At Least 1 Protection Funct. is Active (ProtAc- Device IntSP ON * LED BO 192 18 1 GI
tive) OFF
55 Reset Device (Reset Device) Device OUT * * LED BO 192 4 1
56 Initial Start of Device (Initial Start) Device OUT ON * LED BO 192 5 1
60 Reset LED (Reset LED) Device OUT_Ev ON * LED BO 192 19 1
67 Resume (Resume) Device OUT ON * LED BO 135 97 1
C53000-G1176-C145-1

68 Clock Synchronization Error (Clock SyncError) Device OUT ON * LED BO


OFF
7SD610 Manual

69 Daylight Saving Time (DayLightSavTime) Device OUT ON * LED BO


OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
70 Setting calculation is running (Settings Calc.) Device OUT ON * LED BO 192 22 1 GI
OFF
71 Settings Check (Settings Check) Device OUT * * LED BO
72 Level-2 change (Level-2 change) Device OUT ON * LED BO
OFF
73 Local setting change (Local change) Device OUT * *
110 Event lost (Event Lost) Device OUT_Ev ON * LED BO 135 130 1
113 Flag Lost (Flag Lost) Device OUT ON * M LED BO 135 136 1 GI
125 Chatter ON (Chatter ON) Device OUT ON * LED BO 135 145 1 GI
OFF
126 Protection ON/OFF (via system port) (ProtON/ Device IntSP ON * LED BO
OFF) OFF
127 Auto Reclose ON/OFF (via system port) (AR Auto Reclose IntSP ON * LED BO
ON/OFF) OFF
140 Error with a summary alarm (Error Sum Alarm) Device OUT ON * LED BO 192 47 1 GI
OFF
144 Error 5V (Error 5V) Device OUT ON * LED BO 135 164 1 GI
OFF
160 Alarm Summary Event (Alarm Sum Event) Device OUT * * LED BO 192 46 1 GI
161 Failure: General Current Supervision (Fail I Su- Measurement Super- OUT * * LED BO 192 32 1 GI
perv.) vision

List of Information
163 Failure: Current Balance (Fail I balance) Measurement Super- OUT ON * LED BO 135 183 1 GI
vision OFF
164 Failure: General Voltage Supervision (Fail U Measurement Super- OUT * * LED BO 192 33 1 GI
Superv.) vision
A-25
A-26

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
167 Failure: Voltage Balance (Fail U balance) Measurement Super- OUT ON * LED BO 135 186 1 GI
vision OFF
177 Failure: Battery empty (Fail Battery) Device OUT ON * LED BO 135 193 1 GI
OFF
181 Error: A/D converter (Error A/D-conv.) Device OUT ON * LED BO 135 178 1 GI
OFF
182 Alarm: Real Time Clock (Alarm Clock) Device OUT ON * LED BO 135 194 1 GI
OFF
183 Error Board 1 (Error Board 1) Device OUT ON * LED BO 135 171 1 GI
OFF
184 Error Board 2 (Error Board 2) Device OUT ON * LED BO 135 172 1 GI
OFF
185 Error Board 3 (Error Board 3) Device OUT ON * LED BO 135 173 1 GI
OFF
186 Error Board 4 (Error Board 4) Device OUT ON * LED BO 135 174 1 GI
OFF
187 Error Board 5 (Error Board 5) Device OUT ON * LED BO 135 175 1 GI
OFF
188 Error Board 6 (Error Board 6) Device OUT ON * LED BO 135 176 1 GI
OFF
189 Error Board 7 (Error Board 7) Device OUT ON * LED BO 135 177 1 GI
C53000-G1176-C145-1

OFF
192 Error:1A/5Ajumper different from setting Device OUT ON * LED BO 135 169 1 GI
7SD610 Manual

(Error1A/5Awrong) OFF
193 Alarm: NO calibration data available (Alarm NO Device OUT ON * LED BO 135 181 1 GI
calibr) OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
197 Measurement Supervision is switched OFF Measurement Super- OUT ON * LED BO 135 197 1 GI
(MeasSup OFF) vision OFF
203 Waveform data deleted (Wave. deleted) Oscillographic Fault OUT_Ev ON * LED BO 135 203 1
Records
289 Alarm: Current summation supervision (Failure Measurement Super- OUT ON * LED BO 135 250 1 GI
Σi) vision OFF
290 Alarm: Broken current-wire detected L1 (Broken Measurement Super- OUT ON * LED BO 135 137 1 GI
Iwire L1) vision
291 Alarm: Broken current-wire detected L2 (Broken Measurement Super- OUT ON * LED BO 135 138 1 GI
Iwire L2) vision
292 Alarm: Broken current-wire detected L3 (Broken Measurement Super- OUT ON * LED BO 135 139 1 GI
Iwire L3) vision
295 Broken wire supervision is switched OFF (Bro- Measurement Super- OUT ON * LED BO
ken wire OFF) vision OFF
296 Current summation superv is switched OFF (Σi Measurement Super- OUT ON * LED BO
superv. OFF) vision OFF
301 Power System fault (Pow.Sys.Flt.) Power System Data 2 OUT ON ON 135 231 2 GI
OFF
302 Fault Event (Fault Event) Power System Data 2 OUT * ON 135 232 2
351 >Circuit breaker aux. contact: Pole L1 (>CB Power System Data 2 SP * * LED BI BO 150 1 1 GI
Aux. L1)

List of Information
352 >Circuit breaker aux. contact: Pole L2 (>CB Power System Data 2 SP * * LED BI BO 150 2 1 GI
Aux. L2)
353 >Circuit breaker aux. contact: Phase L3 (>CB Power System Data 2 SP * * LED BI BO 150 3 1 GI
Aux. L3)
356 >Manual close signal (>Manual Close) Power System Data 2 SP * * LED BI BO 150 6 1 GI
A-27
A-28

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
357 >Block all close commands from external Power System Data 2 SP ON * LED BI BO 150 7 1 GI
(>CloseCmd.Blo) OFF
361 >Failure: Feeder VT (MCB tripped) Power System Data 2 SP ON * LED BI BO 192 38 1 GI
(>FAIL:Feeder VT) OFF
366 >CB1 Pole L1 (Pos. Contact=Breaker) (>CB1 Power System Data 2 SP * * LED BI BO 150 66 1 GI
Pole L1)
367 >CB1 Pole L2 (Pos. Contact=Breaker) (>CB1 Power System Data 2 SP * * LED BI BO 150 67 1 GI
Pole L2)
368 >CB1 Pole L3 (Pos. Contact=Breaker) (>CB1 Power System Data 2 SP * * LED BI BO 150 68 1 GI
Pole L3)
371 >Circuit Breaker 1 READY for reclosing (>CB1 Power System Data 2 SP * * LED BI BO 150 71 1 GI
Ready)
378 >CB faulty (>CB faulty) Power System Data 2 SP * * LED BI BO
379 >CB aux. contact 3pole Closed (>CB 3p Power System Data 2 SP * * LED BI BO 150 78 1 GI
Closed)
380 >CB aux. contact 3pole Open (>CB 3p Open) Power System Data 2 SP * * LED BI BO 150 79 1 GI
381 >Single-phase trip permitted from ext.AR (>1p Power System Data 2 SP ON * LED BI BO
Trip Perm) OFF
382 >External AR programmed for 1phase only Power System Data 2 SP ON * LED BI BO
(>Only 1ph AR) OFF
383 >Enable all AR Zones / Stages (>Enable AR- Power System Data 2 SP ON ON LED BI BO
C53000-G1176-C145-1

zones) OFF OFF


385 >Lockout SET (>Lockout SET) Power System Data 2 SP ON * LED BI BO 150 35 1 GI
7SD610 Manual

OFF
386 >Lockout RESET (>Lockout RESET) Power System Data 2 SP ON * LED BI BO 150 36 1 GI
OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
410 >CB1 aux. 3p Closed (for AR, CB-Test) (>CB1 Power System Data 2 SP * * LED BI BO 150 80 1 GI
3p Closed)
411 >CB1 aux. 3p Open (for AR, CB-Test) (>CB1 Power System Data 2 SP * * LED BI BO 150 81 1 GI
3p Open)
501 Relay PICKUP (Relay PICKUP) Power System Data 2 OUT * * M LED BO 192 84 2 GI
503 Relay PICKUP Phase L1 (Relay PICKUP L1) Power System Data 2 OUT * * M LED BO 192 64 2 GI
504 Relay PICKUP Phase L2 (Relay PICKUP L2) Power System Data 2 OUT * * M LED BO 192 65 2 GI
505 Relay PICKUP Phase L3 (Relay PICKUP L3) Power System Data 2 OUT * * M LED BO 192 66 2 GI
506 Relay PICKUP Earth (Relay PICKUP E) Power System Data 2 OUT * * M LED BO 192 67 2 GI
507 Relay TRIP command Phase L1 (Relay TRIP Power System Data 2 OUT * * M LED BO 192 69 2
L1)
508 Relay TRIP command Phase L2 (Relay TRIP Power System Data 2 OUT * * M LED BO 192 70 2
L2)
509 Relay TRIP command Phase L3 (Relay TRIP Power System Data 2 OUT * * M LED BO 192 71 2
L3)
510 General CLOSE of relay (Relay CLOSE) Power System Data 2 OUT * * LED BO 192 128 1
511 Relay GENERAL TRIP command (Relay TRIP) Power System Data 2 OUT * M LED BO 192 68 2
OFF
512 Relay TRIP command - Only Phase L1 (Relay Power System Data 2 OUT * * LED BO
TRIP 1pL1)

List of Information
513 Relay TRIP command - Only Phase L2 (Relay Power System Data 2 OUT * * LED BO
TRIP 1pL2)
514 Relay TRIP command - Only Phase L3 (Relay Power System Data 2 OUT * * LED BO
TRIP 1pL3)
515 Relay TRIP command Phases L123 (Relay Power System Data 2 OUT * * LED BO
A-29

TRIP 3ph.)
A-30

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
530 LOCKOUT is active (LOCKOUT) Power System Data 2 IntSP ON * LED BO
OFF
533 Primary fault current IL1 (IL1 =) Power System Data 2 OUT * ON 150 177 4
OFF
534 Primary fault current IL2 (IL2 =) Power System Data 2 OUT * ON 150 178 4
OFF
535 Primary fault current IL3 (IL3 =) Power System Data 2 OUT * ON 150 179 4
OFF
536 Final Trip (Final Trip) Power System Data 2 OUT ON ON LED BO 150 180 2 GI
545 Time from Pickup to drop out (PU Time) Power System Data 2 OUT
546 Time from Pickup to TRIP (TRIP Time) Power System Data 2 OUT
560 Single-phase trip was coupled 3phase (Trip Power System Data 2 OUT * ON LED BO 150 210 2
Coupled 3p)
561 Manual close signal detected (Man.Clos.De- Power System Data 2 OUT ON * LED BO 150 211 1
tect)
563 CB alarm suppressed (CB Alarm Supp) Power System Data 2 OUT * * LED BO
1000 Number of breaker TRIP commands (# TRIPs=) Statistics OUT
1001 Number of breaker TRIP commands L1 (TripNo Statistics OUT
L1=)
1002 Number of breaker TRIP commands L2 (TripNo Statistics OUT
L2=)
C53000-G1176-C145-1

1003 Number of breaker TRIP commands L3 (TripNo Statistics OUT


7SD610 Manual

L3=)
1027 Accumulation of interrupted current L1 (Σ IL1 =) Statistics OUT
1028 Accumulation of interrupted current L2 (Σ IL2 =) Statistics OUT
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
1029 Accumulation of interrupted current L3 (Σ IL3 =) Statistics OUT
1030 Last fault current Phase L1 (Last IL1 =) Statistics OUT
1031 Last fault current Phase L2 (Last IL2 =) Statistics OUT
1032 Last fault current Phase L3 (Last IL3 =) Statistics OUT
1401 >BF: Switch on breaker fail protection (>BF on) Breaker Failure SP * * LED BI BO
1402 >BF: Switch off breaker fail protection (>BF off) Breaker Failure SP * * LED BI BO
1403 >BLOCK Breaker failure (>BLOCK BkrFail) Breaker Failure SP ON * LED BI BO 166 103 1 GI
OFF
1415 >BF: External start 3pole (>BF Start 3pole) Breaker Failure SP ON * LED BI BO
OFF
1432 >BF: External release (>BF release) Breaker Failure SP ON * LED BI BO
OFF
1435 >BF: External start L1 (>BF Start L1) Breaker Failure SP ON * LED BI BO
OFF
1436 >BF: External start L2 (>BF Start L2) Breaker Failure SP ON * LED BI BO
OFF
1437 >BF: External start L3 (>BF Start L3) Breaker Failure SP ON * LED BI BO
OFF
1439 >BF: External start 3pole (w/o current) (>BF Breaker Failure SP ON * LED BI BO
Start w/o I) OFF

List of Information
1440 Breaker failure prot. ON/OFF via BI (BkrFailON/ Breaker Failure IntSP ON * LED BO
offBI) OFF
1451 Breaker failure is switched OFF (BkrFail OFF) Breaker Failure OUT ON * LED BO 166 151 1 GI
OFF
1452 Breaker failure is BLOCKED (BkrFail BLOCK) Breaker Failure OUT ON ON LED BO 166 152 1 GI
A-31

OFF OFF
A-32

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
1453 Breaker failure is ACTIVE (BkrFail ACTIVE) Breaker Failure OUT * * LED BO 166 153 1 GI
1461 Breaker failure protection started (BF Start) Breaker Failure OUT * ON LED BO 166 161 1 GI
OFF
1472 BF Trip T1 (local trip) - only phase L1 (BF T1- Breaker Failure OUT * ON LED BO
TRIP 1pL1)
1473 BF Trip T1 (local trip) - only phase L2 (BF T1- Breaker Failure OUT * ON LED BO
TRIP 1pL2)
1474 BF Trip T1 (local trip) - only phase L3 (BF T1- Breaker Failure OUT * ON LED BO
TRIP 1pL3)
1476 BF Trip T1 (local trip) - 3pole (BF T1-TRIP Breaker Failure OUT * ON LED BO
L123)
1493 BF Trip in case of defective CB (BF TRIP CBde- Breaker Failure OUT * ON LED BO
fec)
1494 BF Trip T2 (busbar trip) (BF T2-TRIP(bus)) Breaker Failure OUT * ON LED BO
1495 BF Trip End fault stage (BF EndFlt TRIP) Breaker Failure OUT * ON LED BO
1496 BF Pole discrepancy pickup (BF CBdiscr- Breaker Failure OUT * ON LED BO
START) OFF
1497 BF Pole discrepancy pickup L1 (BF CBdiscr L1) Breaker Failure OUT * ON LED BO
OFF
1498 BF Pole discrepancy pickup L2 (BF CBdiscr L2) Breaker Failure OUT * ON LED BO
OFF
C53000-G1176-C145-1

1499 BF Pole discrepancy pickup L3 (BF CBdiscr L3) Breaker Failure OUT * ON LED BO
OFF
7SD610 Manual

1500 BF Pole discrepancy Trip (BF CBdiscr TRIP) Breaker Failure OUT * ON LED BO
1503 >BLOCK Thermal Overload Protection (>BLK Thermal Overload SP * * LED BI BO 167 3 1 GI
ThOverload)
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
1511 Thermal Overload Protection OFF (Th.Overload Thermal Overload OUT ON * LED BO 167 11 1 GI
OFF) OFF
1512 Thermal Overload Protection BLOCKED Thermal Overload OUT ON ON LED BO 167 12 1 GI
(Th.Overload BLK) OFF OFF
1513 Overload Protection ACTIVE (Overload ACT) Thermal Overload OUT ON * LED BO 167 13 1 GI
OFF
1515 Overload Current Alarm (I alarm) (O/L I Alarm) Thermal Overload OUT ON * LED BO 167 15 1 GI
OFF
1516 Overload Alarm! Near Thermal Trip (O/L Θ Thermal Overload OUT ON * LED BO 167 16 1 GI
Alarm) OFF
1517 Winding Overload (Winding O/L) Thermal Overload OUT ON * LED BO 167 17 1 GI
OFF
1521 Thermal Overload TRIP (ThOverload TRIP) Thermal Overload OUT * ON LED BO 167 21 2 GI
2054 Emergency mode (Emer. mode) Device OUT ON ON LED BO 192 37 1 GI
OFF OFF
2701 >Auto reclose ON (>AR ON) Auto Reclose SP * * LED BI BO 40 1 1 GI
2702 >Auto reclose OFF (>AR OFF) Auto Reclose SP * * LED BI BO 40 2 1 GI
2703 >BLOCK Auto reclose (>BLOCK AR) Auto Reclose SP ON * LED BI BO 40 3 1 GI
OFF
2711 >External start of internal Auto reclose (>AR Auto Reclose SP * ON LED BI BO 40 11 2 GI
Start)

List of Information
2712 >AR: Ext. Trip L1 for internal AR (>Trip L1 AR) Auto Reclose SP * ON LED BI BO 40 12 2 GI
2713 >AR: Ext. Trip L2 for internal AR (>Trip L2 AR) Auto Reclose SP * ON LED BI BO 40 13 2 GI
2714 >AR: Ext. Trip L3 for internal AR (>Trip L3 AR) Auto Reclose SP * ON LED BI BO 40 14 2 GI
2715 >Ext. 1pole Trip for internal Auto Recl. (>Trip 1p Auto Reclose SP * ON LED BI BO 40 15 2 GI
A-33

for AR)
A-34

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
2716 >Ext. 3pole Trip for internal Auto Recl. (>Trip 3p Auto Reclose SP * ON LED BI BO 40 16 2 GI
for AR)
2727 >AR: Remote Close signal (>AR RemoteClose) Auto Reclose SP * ON LED BI BO 40 22 2 GI
2731 >AR: Synchronism from ext. sync.-check Auto Reclose SP * * LED BI BO 40 31 2 GI
(>Sync.release)
2737 >AR: Block 1pole AR-cycle (>BLOCK 1pole Auto Reclose SP ON * LED BI BO 40 32 1 GI
AR) OFF
2738 >AR: Block 3pole AR-cycle (>BLOCK 3pole Auto Reclose SP ON * LED BI BO 40 33 1 GI
AR) OFF
2739 >AR: Block 1phase-fault AR-cycle (>BLK Auto Reclose SP ON * LED BI BO 40 34 1 GI
1phase AR) OFF
2740 >AR: Block 2phase-fault AR-cycle (>BLK Auto Reclose SP ON * LED BI BO 40 35 1 GI
2phase AR) OFF
2741 >AR: Block 3phase-fault AR-cycle (>BLK Auto Reclose SP ON * LED BI BO 40 36 1 GI
3phase AR) OFF
2742 >AR: Block 1st AR-cycle (>BLK 1.AR-cycle) Auto Reclose SP ON * LED BI BO 40 37 1 GI
OFF
2743 >AR: Block 2nd AR-cycle (>BLK 2.AR-cycle) Auto Reclose SP ON * LED BI BO 40 38 1 GI
OFF
2744 >AR: Block 3rd AR-cycle (>BLK 3.AR-cycle) Auto Reclose SP ON * LED BI BO 40 39 1 GI
OFF
C53000-G1176-C145-1

2745 >AR: Block 4th and higher AR-cycles (>BLK 4.- Auto Reclose SP ON * LED BI BO 40 40 1 GI
n. AR) OFF
7SD610 Manual

2746 >AR: External Trip for AR start (>Trip for AR) Auto Reclose SP * ON LED BI BO 40 41 2 GI
2747 >AR: External pickup L1 for AR start (>Pickup Auto Reclose SP * ON LED BI BO 40 42 2 GI
L1 AR)
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
2748 >AR: External pickup L2 for AR start (>Pickup Auto Reclose SP * ON LED BI BO 40 43 2 GI
L2 AR)
2749 >AR: External pickup L3 for AR start (>Pickup Auto Reclose SP * ON LED BI BO 40 44 2 GI
L3 AR)
2750 >AR: External pickup 1phase for AR start Auto Reclose SP * ON LED BI BO 40 45 2 GI
(>Pickup 1ph AR)
2751 >AR: External pickup 2phase for AR start Auto Reclose SP * ON LED BI BO 40 46 2 GI
(>Pickup 2ph AR)
2752 >AR: External pickup 3phase for AR start Auto Reclose SP * ON LED BI BO 40 47 2 GI
(>Pickup 3ph AR)
2781 Auto recloser is switched OFF (Auto recl. OFF) Auto Reclose OUT ON * LED BO 40 81 1 GI
OFF
2782 Auto recloser is switched ON (Auto recl. ON) Auto Reclose IntSP * * LED BO 192 16 1 GI
2783 AR: Auto-reclose is blocked (AR is blocked) Auto Reclose OUT ON * LED BO 40 83 1 GI
OFF
2784 Auto recloser is NOT ready (AR is NOT ready) Auto Reclose OUT * ON LED BO 192 130 1 GI
2787 AR: Circuit breaker not ready (CB not ready) Auto Reclose OUT * * LED BO 40 87 1 GI
2788 AR: CB ready monitoring window expired (AR Auto Reclose OUT * ON LED BO 40 88 2 GI
T-CBreadyExp)
2796 AR: Auto-reclose ON/OFF via BI (AR on/off BI) Auto Reclose IntSP * * LED BO
2801 Auto-reclose in progress (AR in progress) Auto Reclose OUT * ON LED BO 40 101 2 GI

List of Information
2809 AR: Start-signal monitoring time expired (AR T- Auto Reclose OUT * ON LED BO 40 174 1 GI
Start Exp)
2810 AR: Maximum dead time expired (AR Tdead- Auto Reclose OUT * ON LED BO 40 175 1 GI
Max Exp)
A-35

2818 AR: Evolving fault recognition (AR evolving Flt) Auto Reclose OUT * ON LED BO 40 118 2 GI
A-36

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
2820 AR is set to operate after 1p trip only (AR Auto Reclose OUT * * LED BO 40 143 1 GI
Program1pole)
2821 AR dead time after evolving fault (AR Td. Auto Reclose OUT * ON LED BO 40 197 2 GI
evol.Flt) OFF
2839 AR dead time after 1pole trip running (AR Auto Reclose OUT * ON LED BO 40 148 2 GI
Tdead 1pTrip)
2840 AR dead time after 3pole trip running (AR Auto Reclose OUT * ON LED BO 40 149 2 GI
Tdead 3pTrip)
2841 AR dead time after 1phase fault running (AR Auto Reclose OUT * ON LED BO 40 150 2 GI
Tdead 1pFlt)
2842 AR dead time after 2phase fault running (AR Auto Reclose OUT * ON LED BO 40 151 2 GI
Tdead 2pFlt)
2843 AR dead time after 3phase fault running (AR Auto Reclose OUT * ON LED BO 40 154 2 GI
Tdead 3pFlt)
2844 AR 1st cycle running (AR 1stCyc. run.) Auto Reclose OUT * ON LED BO 40 155 2 GI
2845 AR 2nd cycle running (AR 2ndCyc. run.) Auto Reclose OUT * ON LED BO 40 157 2 GI
2846 AR 3rd cycle running (AR 3rdCyc. run.) Auto Reclose OUT * ON LED BO 40 158 2 GI
2847 AR 4th or higher cycle running (AR 4thCyc. Auto Reclose OUT * ON LED BO 40 159 2 GI
run.)
2848 AR cycle is running in ADT mode (AR ADT run.) Auto Reclose OUT * ON LED BO 40 130 2 GI
2851 Auto-reclose Close command (AR Close) Auto Reclose OUT * ON M LED BO 40 128 1 GI
C53000-G1176-C145-1

2852 AR: Close command after 1pole 1st cycle (AR Auto Reclose OUT * * LED BO 40 152 1 GI
7SD610 Manual

Close1.Cyc1p)
2853 AR: Close command after 3pole 1st cycle (AR Auto Reclose OUT * * LED BO 40 153 1 GI
Close1.Cyc3p)
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
2854 AR: Close command after 2nd cycle (AR Close Auto Reclose OUT * * LED BO 192 129 1
2.Cyc)
2861 AR: Reclaim time is running (AR T-Recl. run.) Auto Reclose OUT * * LED BO 40 161 1 GI
2862 Auto reclose cycle successful (AR Successful) Auto Reclose OUT * * LED BO 40 162 1 GI
2863 Auto reclose Lockout (AR Lockout) Auto Reclose OUT * * LED BO 40 163 1 GI
2864 AR: 1pole trip permitted by internal AR (AR 1p Auto Reclose OUT * * LED BO 40 164 1 GI
Trip Perm)
2865 AR: Synchro-check request (AR Sync.Request) Auto Reclose OUT * * LED BO 40 165 2 GI
2871 AR: TRIP command 3pole (AR TRIP 3pole) Auto Reclose OUT * ON LED BO 40 171 2 GI
2889 AR 1st cycle zone extension release (AR 1.Cyc- Auto Reclose OUT * * LED BO 40 160 1 GI
ZoneRel)
2890 AR 2nd cycle zone extension release (AR 2.Cy- Auto Reclose OUT * * LED BO 40 169 1 GI
cZoneRel)
2891 AR 3rd cycle zone extension release (AR 3.Cy- Auto Reclose OUT * * LED BO 40 170 1 GI
cZoneRel)
2892 AR 4th cycle zone extension release (AR 4.Cy- Auto Reclose OUT * * LED BO 40 172 1 GI
cZoneRel)
2893 AR zone extension (general) (AR Zone Re- Auto Reclose OUT * * LED BO 40 173 1 GI
lease)
2894 AR Remote close signal send (AR Remote Auto Reclose OUT * ON LED BO 40 129 1 GI
Close)

List of Information
2895 No. of 1st AR-cycle CLOSE commands 1pole Statistics OUT
(AR #Close1./1p=)
2896 No. of 1st AR-cycle CLOSE commands 3pole Statistics OUT
(AR #Close1./3p=)
A-37
A-38

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
2897 No. of higher AR-cycle CLOSE commands 1p Statistics OUT
(AR #Close2./1p=)
2898 No. of higher AR-cycle CLOSE commands 3p Statistics OUT
(AR #Close2./3p=)
3102 Diff: 2nd Harmonic detected in phase L1 (2nd Differential Protection OUT * * LED BO 92 89 1 GI
Harmonic L1)
3103 Diff: 2nd Harmonic detected in phase L2 (2nd Differential Protection OUT * * LED BO 92 90 1 GI
Harmonic L2)
3104 Diff: 2nd Harmonic detected in phase L3 (2nd Differential Protection OUT * * LED BO 92 91 1 GI
Harmonic L3)
3120 Diff: Active (Diff active) Differential Protection OUT ON * M LED BO 92 92 1 GI
OFF
3132 Diff: Fault detection (Diff. Gen. Flt.) Differential Protection OUT * ON M LED BO
OFF
3133 Diff: Fault detection in phase L1 (Diff. Flt. L1) Differential Protection OUT * ON M LED BO 92 93 2 GI
OFF
3134 Diff: Fault detection in phase L2 (Diff. Flt. L2) Differential Protection OUT * ON M LED BO 92 94 2 GI
OFF
3135 Diff: Fault detection in phase L3 (Diff. Flt. L3) Differential Protection OUT * ON M LED BO 92 95 2 GI
OFF
3136 Diff: Earth fault detection (Diff. Flt. E) Differential Protection OUT * ON M LED BO 92 96 2 GI
C53000-G1176-C145-1

OFF
3137 Diff: Fault detection of I-Diff>> (I-Diff>> Flt.) Differential Protection OUT * ON M LED BO 92 97 2 GI
7SD610 Manual

OFF
3139 Diff: Fault detection of I-Diff> (I-Diff> Flt.) Differential Protection OUT * ON M LED BO 92 98 2 GI
OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3141 Diff: General TRIP (Diff. Gen. TRIP) Differential Protection OUT * ON M LED BO 92 99 2 GI
OFF
3142 Diff: TRIP - Only L1 (Diff TRIP 1p L1) Differential Protection OUT * ON M LED BO 92 100 2 GI
OFF
3143 Diff: TRIP - Only L2 (Diff TRIP 1p L2) Differential Protection OUT * ON M LED BO 92 101 2 GI
OFF
3144 Diff: TRIP - Only L3 (Diff TRIP 1p L3) Differential Protection OUT * ON M LED BO 92 102 2 GI
OFF
3145 Diff: TRIP L123 (Diff TRIP L123) Differential Protection OUT * ON M LED BO 92 103 2 GI
OFF
3146 Diff: TRIP 1pole (Diff TRIP 1pole) Differential Protection OUT * ON LED BO
OFF
3147 Diff: TRIP 3pole (Diff TRIP 3pole) Differential Protection OUT * ON LED BO
OFF
3148 Diff: Differential protection is blocked (Diff Differential Protection OUT ON * LED BO 92 104 1 GI
block) OFF
3149 Diff: Diff. protection is switched off (Diff OFF) Differential Protection OUT ON * LED BO 92 105 1 GI
OFF
3176 Diff: Fault detection L1 (only) (Diff Flt. 1p.L1) Differential Protection OUT * * LED BO
3177 Diff: Fault detection L1E (Diff Flt. L1E) Differential Protection OUT * * LED BO
3178 Diff: Fault detection L2 (only) (Diff Flt. 1p.L2) Differential Protection OUT * * LED BO

List of Information
3179 Diff: Fault detection L2E (Diff Flt. L2E) Differential Protection OUT * * LED BO
3180 Diff: Fault detection L12 (Diff Flt. L12) Differential Protection OUT * * LED BO
3181 Diff: Fault detection L12E (Diff Flt. L12E) Differential Protection OUT * * LED BO
3182 Diff: Fault detection L3 (only) (Diff Flt. 1p.L3) Differential Protection OUT * * LED BO
A-39
A-40

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3183 Diff: Fault detection L3E (Diff Flt. L3E) Differential Protection OUT * * LED BO
3184 Diff: Fault detection L31 (Diff Flt. L31) Differential Protection OUT * * LED BO
3185 Diff: Fault detection L31E (Diff Flt. L31E) Differential Protection OUT * * LED BO
3186 Diff: Fault detection L23 (Diff Flt. L23) Differential Protection OUT * * LED BO
3187 Diff: Fault detection L23E (Diff Flt. L23E) Differential Protection OUT * * LED BO
3188 Diff: Fault detection L123 (Diff Flt. L123) Differential Protection OUT * * LED BO
3189 Diff: Fault detection L123E (Diff Flt. L123E) Differential Protection OUT * * LED BO
3190 Diff: Set Teststate of Diff. protection (Test Diff.) Differential Protection IntSP ON * LED FK BO 92 106 1 GI
OFF
3191 Diff: Set Commissioning state of Diff. (Comm. Differential Protection IntSP ON * LED FK BO 92 107 1 GI
Diff) OFF
3192 Diff: Remote relay in Teststate (TestDiff.remote) Differential Protection OUT ON * LED BO 92 108 1 GI
OFF
3193 Diff: Commissioning state is active (Comm.Diff Differential Protection OUT ON * LED BO 92 109 1 GI
act.) OFF
3194 Diff: >Test Diff. (>Test Diff.) Differential Protection SP ON * LED BI BO
OFF
3195 Diff: >Comm. Diff (>Comm. Diff) Differential Protection SP ON * LED BI BO
OFF
3215 Incompatible Firmware Versions (Wrong Protection Interface OUT ON * LED BO
C53000-G1176-C145-1

Firmware) (Port D+E)


3217 Prot Int 1: Own Datas received (PI1 Data reflec) Protection Interface OUT ON * LED BO
7SD610 Manual

(Port D+E) OFF


3227 >Prot Int 1: Transmitter is switched off (>PI1 Protection Interface SP ON * LED BI BO
light off) (Port D+E) OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3229 Prot Int 1: Reception of faulty datas (PI1 Data Protection Interface OUT ON * LED BO 93 135 1 GI
fault) (Port D+E) OFF
3230 Prot Int 1: Total receiption failure (PI1 Datafail- Protection Interface OUT ON * LED BO 93 136 1 GI
ure) (Port D+E) OFF
3233 Device table has inconsistent numbers (DT in- Protection Interface OUT ON * LED BO
consistent) (Port D+E) OFF
3234 Device tables are unequal (DT unequal) Protection Interface OUT ON * LED BO
(Port D+E) OFF
3235 Differences between common parameters (Par. Protection Interface OUT ON * LED BO
different) (Port D+E) OFF
3239 Prot Int 1: Transmission time to high (PI1 TT Protection Interface OUT ON * LED BO 93 139 1 GI
alarm) (Port D+E) OFF
3243 Prot Int 1: Connected with relay ID (PI1 with) Protection Interface OUT ON *
(Port D+E) OFF
3451 > Logout input signal (>Logout) Differential Topology SP ON * LED BI BO
OFF
3458 System operates in a open Chaintopology Differential Topology OUT ON * LED BO 93 142 1 GI
(Chaintopology) OFF
3464 Communication topology is complete (Topol Differential Topology OUT ON * LED BO
complete) OFF
3475 Relay 1 in Logout state (Rel1Logout) Differential Topology IntSP ON * LED FK BO 93 143 1 GI
OFF

List of Information
3476 Relay 2 in Logout state (Rel2Logout) Differential Topology IntSP ON * LED FK BO 93 144 1 GI
OFF
3484 Local activation of Logout state (Logout) Differential Topology IntSP ON * LED FK BO 93 149 1 GI
OFF
A-41
A-42

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3487 Equal IDs in constellation (Equal IDs) Differential Topology OUT ON * LED BO
OFF
3501 I.Trip: >Intertrip L1 signal input (>Intertrip L1) Intertrip SP ON * LED BI BO
OFF
3502 I.Trip: >Intertrip L2 signal input (>Intertrip L2) Intertrip SP ON * LED BI BO
OFF
3503 I.Trip: >Intertrip L3 signal input (>Intertrip L3) Intertrip SP ON * LED BI BO
OFF
3504 I.Trip: >Intertrip 3 pole signal input (>Intertrip Intertrip SP ON * LED BI BO
3pol) OFF
3505 I.Trip: Received at Prot.Interface 1 L1 Intertrip OUT on * LED BO
(ITrp.rec.PI1.L1) off
3506 I.Trip: Received at Prot.Interface 1 L2 Intertrip OUT on * LED BO
(ITrp.rec.PI1.L2) off
3507 I.Trip: Received at Prot.Interface 1 L3 Intertrip OUT on * LED BO
(ITrp.rec.PI1.L3) off
3511 I.Trip: Sending at Prot.Interface 1 L1 Intertrip OUT ON * LED BO
(ITrp.sen.PI1.L1) OFF
3512 I.Trip: Sending at Prot.Interface 1 L2 Intertrip OUT ON * LED BO
(ITrp.sen.PI1.L2) OFF
3513 I.Trip: Sending at Prot.Interface 1 L3 Intertrip OUT ON * LED BO
C53000-G1176-C145-1

(ITrp.sen.PI1.L3) OFF
3517 I.Trip: General TRIP (ITrp. Gen. TRIP) Intertrip OUT * ON M LED BO
7SD610 Manual

OFF
3518 I.Trip: TRIP - Only L1 (ITrp.TRIP 1p L1) Intertrip OUT * ON M LED BO 93 150 2 GI
OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3519 I.Trip: TRIP - Only L2 (ITrp.TRIP 1p L2) Intertrip OUT * ON M LED BO 93 151 2 GI
OFF
3520 I.Trip: TRIP - Only L3 (ITrp.TRIP 1p L3) Intertrip OUT * ON M LED BO 93 152 2 GI
OFF
3521 I.Trip: TRIP L123 (ITrp.TRIP L123) Intertrip OUT * ON M LED BO 93 153 2 GI
OFF
3522 I.Trip: TRIP 1pole (Diff TRIP 1pole) Intertrip OUT * ON LED BO
OFF
3523 I.Trip: TRIP 3pole (Diff TRIP 3pole) Intertrip OUT * ON LED BO
OFF
3525 >Differential protection blocking signal (> Diff Differential Protection SP ON * LED BI BO
block) OFF
3526 Differential blocking received at PI1 (Diffblk.rec Differential Protection OUT ON * LED BO
PI1) OFF
3528 Differential blocking sending via PI1 (Diffblk.sen Differential Protection OUT ON * LED BO
PI1) OFF
3541 >Remote Trip 1 signal input (>Remote Trip1) Remote Signals SP on * LED BI BO
off
3542 >Remote Trip 2 signal input (>Remote Trip2) Remote Signals SP on * LED BI BO
off
3543 >Remote Trip 3 signal input (>Remote Trip3) Remote Signals SP on * LED BI BO
off

List of Information
3544 >Remote Trip 4 signal input (>Remote Trip4) Remote Signals SP on * LED BI BO
off
3545 Remote Trip 1 received (RemoteTrip1 rec) Remote Signals OUT on * LED BO 93 154 1 GI
off
A-43
A-44

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
3546 Remote Trip 2 received (RemoteTrip2 rec) Remote Signals OUT on * LED BO 93 155 1 GI
off
3547 Remote Trip 3 received (RemoteTrip3 rec) Remote Signals OUT on * LED BO 93 156 1 GI
off
3548 Remote Trip 4 received (RemoteTrip4 rec) Remote Signals OUT on * LED BO 93 157 1 GI
off
4253 >BLOCK Instantaneous SOTF Overcurrent Instantaneous High- SP * * LED BI BO
(>BLOCK SOTF-O/C) Speed SOTF Over-
current
4271 SOTF-O/C is switched OFF (SOTF-O/C OFF) Instantaneous High- OUT ON * LED BO 25 71 1 GI
Speed SOTF Over- OFF
current
4272 SOTF-O/C is BLOCKED (SOTF-O/C BLOCK) Instantaneous High- OUT ON ON LED BO 25 72 1 GI
Speed SOTF Over- OFF OFF
current
4273 SOTF-O/C is ACTIVE (SOTF-O/C ACTIVE) Instantaneous High- OUT * * LED BO 25 73 1 GI
Speed SOTF Over-
current
4281 SOTF-O/C PICKED UP (SOTF-O/C PICKUP) Instantaneous High- OUT * M LED BO 25 81 2 GI
Speed SOTF Over- OFF
current
4282 SOTF-O/C Pickup L1 (SOF O/CpickupL1) Instantaneous High- OUT * ON LED BO 25 82 2 GI
C53000-G1176-C145-1

Speed SOTF Over-


current
7SD610 Manual

4283 SOTF-O/C Pickup L2 (SOF O/CpickupL2) Instantaneous High- OUT * ON LED BO 25 83 2 GI


Speed SOTF Over-
current
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
4284 SOTF-O/C Pickup L3 (SOF O/CpickupL3) Instantaneous High- OUT * ON LED BO 25 84 2 GI
Speed SOTF Over-
current
4285 High Speed-O/C Pickup I>>>> L1 (I>>>>O/C Instantaneous High- OUT * ON LED BO 25 85 2 GI
p.upL1) Speed SOTF Over-
current
4286 High Speed-O/C Pickup I>>>> L2 (I>>>>O/C Instantaneous High- OUT * ON LED BO 25 86 2 GI
p.upL2) Speed SOTF Over-
current
4287 High Speed-O/C Pickup I>>>> L3 (I>>>>O/C Instantaneous High- OUT * ON LED BO 25 87 2 GI
p.upL3) Speed SOTF Over-
current
4289 High Speed/SOTF-O/C TRIP - Only L1 (HS/ Instantaneous High- OUT * ON LED BO 25 89 2 GI
SOF TRIP1pL1) Speed SOTF Over-
current
4290 High Speed/SOTF-O/C TRIP - Only L2 (HS/ Instantaneous High- OUT * ON LED BO 25 90 2 GI
SOF TRIP1pL2) Speed SOTF Over-
current
4291 High Speed/SOTF-O/C TRIP - Only L3 (HS/ Instantaneous High- OUT * ON LED BO 25 91 2 GI
SOF TRIP1pL3) Speed SOTF Over-
current
4292 High Speed/SOTF-O/C TRIP 1pole (HS/SOF Instantaneous High- OUT * ON LED BO 25 94 2
TRIP 1p) Speed SOTF Over-

List of Information
current
4293 High Speed/SOTF-O/C General TRIP (HS/SOF Instantaneous High- OUT * ON LED BO
Gen.TRIP) Speed SOTF Over-
current
A-45
A-46

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
4294 High Speed/SOTF-O/C TRIP 3pole (HS/SOF Instantaneous High- OUT * ON LED BO
TRIP 3p) Speed SOTF Over-
current
4295 High Speed/SOTF-O/C TRIP command L123 Instantaneous High- OUT * ON LED BO 25 95 2 GI
(HS/SOF TRIPL123) Speed SOTF Over-
current
4403 >BLOCK Direct Transfer Trip function (>BLOCK DTT Direct Transfer SP * * LED BI BO
DTT) Trip
4412 >Direct Transfer Trip INPUT Phase L1 (>DTT DTT Direct Transfer SP ON * LED BI BO
Trip L1) Trip OFF
4413 >Direct Transfer Trip INPUT Phase L2 (>DTT DTT Direct Transfer SP ON * LED BI BO
Trip L2) Trip OFF
4414 >Direct Transfer Trip INPUT Phase L3 (>DTT DTT Direct Transfer SP ON * LED BI BO
Trip L3) Trip OFF
4417 >Direct Transfer Trip INPUT 3ph L123 (>DTT DTT Direct Transfer SP ON * LED BI BO
Trip L123) Trip OFF
4421 Direct Transfer Trip is switched OFF (DTT OFF) DTT Direct Transfer OUT ON * LED BO 51 21 1 GI
Trip OFF
4422 Direct Transfer Trip is BLOCKED (DTT BLOCK) DTT Direct Transfer OUT ON ON LED BO 51 22 1 GI
Trip OFF OFF
4432 DTT TRIP command - Only L1 (DTT TRIP 1p. DTT Direct Transfer OUT * ON LED BO 51 32 2
L1) Trip
C53000-G1176-C145-1

4433 DTT TRIP command - Only L2 (DTT TRIP 1p. DTT Direct Transfer OUT * ON LED BO 51 33 2
L2) Trip
7SD610 Manual

4434 DTT TRIP command - Only L3 (DTT TRIP 1p. DTT Direct Transfer OUT * ON LED BO 51 34 2
L3) Trip
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
4435 DTT TRIP command L123 (DTT TRIP L123) DTT Direct Transfer OUT * ON LED BO 51 35 2
Trip
6854 >Trip circuit superv. 1: Trip Relay (>TripC1 Trip Circuit Supervi- SP ON * LED BI BO
TripRel) sion OFF
6855 >Trip circuit superv. 1: Breaker Relay (>TripC1 Trip Circuit Supervi- SP ON * LED BI BO
Bkr.Rel) sion OFF
6856 >Trip circuit superv. 2: Trip Relay (>TripC2 Trip Circuit Supervi- SP ON * LED BI BO
TripRel) sion OFF
6857 >Trip circuit superv. 2: Breaker Relay (>TripC2 Trip Circuit Supervi- SP ON * LED BI BO
Bkr.Rel) sion OFF
6858 >Trip circuit superv. 3: Trip Relay (>TripC3 Trip Circuit Supervi- SP ON * LED BI BO
TripRel) sion OFF
6859 >Trip circuit superv. 3: Breaker Relay (>TripC3 Trip Circuit Supervi- SP ON * LED BI BO
Bkr.Rel) sion OFF
6861 Trip circuit supervision OFF (TripC OFF) Trip Circuit Supervi- OUT ON * LED BO 170 53 1 GI
sion OFF
6865 Failure Trip Circuit (FAIL: Trip cir.) Trip Circuit Supervi- OUT ON * LED BO 170 55 1 GI
sion OFF
6866 TripC1 blocked: Binary input is not set (TripC1 Trip Circuit Supervi- OUT ON * LED BO
ProgFAIL) sion OFF
6867 TripC2 blocked: Binary input is not set (TripC2 Trip Circuit Supervi- OUT ON * LED BO
ProgFAIL) sion OFF

List of Information
6868 TripC3 blocked: Binary input is not set (TripC3 Trip Circuit Supervi- OUT ON * LED BO
ProgFAIL) sion OFF
7104 >BLOCK Backup OverCurrent I>> (>BLOCK O/ Backup overcurrent SP ON * LED BI BO 64 4 1 GI
C I>>) OFF
A-47
A-48

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
7105 >BLOCK Backup OverCurrent I> (>BLOCK O/C Backup overcurrent SP ON * LED BI BO 64 5 1 GI
I>) OFF
7106 >BLOCK Backup OverCurrent Ip (>BLOCK O/C Backup overcurrent SP ON * LED BI BO 64 6 1 GI
Ip) OFF
7107 >BLOCK Backup OverCurrent Ie>> (>BLOCK Backup overcurrent SP ON * LED BI BO 64 7 1 GI
O/C Ie>>) OFF
7108 >BLOCK Backup OverCurrent Ie> (>BLOCK O/ Backup overcurrent SP ON * LED BI BO 64 8 1 GI
C Ie>) OFF
7109 >BLOCK Backup OverCurrent Iep (>BLOCK O/ Backup overcurrent SP ON * LED BI BO 64 9 1 GI
C Iep) OFF
7110 >Backup OverCurrent InstantaneousTrip (>O/C Backup overcurrent SP ON ON LED BI BO 64 10 1 GI
InstTRIP) OFF OFF
7130 >BLOCK I-STUB (>BLOCK I-STUB) Backup overcurrent SP ON * LED BI BO 64 30 1 GI
OFF
7131 >Enable I-STUB-Bus function (>I-STUB ENA- Backup overcurrent SP ON ON LED BI BO 64 31 1 GI
BLE) OFF OFF
7132 >BLOCK Backup OverCurrent Ie>>> (>BLOCK Backup overcurrent SP ON * LED BI BO 64 32 1 GI
O/CIe>>>) OFF
7151 Backup O/C is switched OFF (O/C OFF) Backup overcurrent OUT ON * LED BO 64 51 1 GI
OFF
7152 Backup O/C is BLOCKED (O/C BLOCK) Backup overcurrent OUT ON ON LED BO 64 52 1 GI
C53000-G1176-C145-1

OFF OFF
7153 Backup O/C is ACTIVE (O/C ACTIVE) Backup overcurrent OUT * * LED BO 64 53 1 GI
7SD610 Manual

7161 Backup O/C PICKED UP (O/C PICKUP) Backup overcurrent OUT * M LED BO 64 61 2 GI
OFF
7162 Backup O/C PICKUP L1 (O/C Pickup L1) Backup overcurrent OUT * ON LED BO 64 62 2 GI
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
7163 Backup O/C PICKUP L2 (O/C Pickup L2) Backup overcurrent OUT * ON LED BO 64 63 2 GI
7164 Backup O/C PICKUP L3 (O/C Pickup L3) Backup overcurrent OUT * ON LED BO 64 64 2 GI
7165 Backup O/C PICKUP EARTH (O/C Pickup E) Backup overcurrent OUT * ON LED BO 64 65 2 GI
7191 Backup O/C Pickup I>> (O/C PICKUP I>>) Backup overcurrent OUT * ON M LED BO 64 91 2 GI
7192 Backup O/C Pickup I> (O/C PICKUP I>) Backup overcurrent OUT * ON M LED BO 64 92 2 GI
7193 Backup O/C Pickup Ip (O/C PICKUP Ip) Backup overcurrent OUT * ON M LED BO 64 93 2 GI
7201 O/C I-STUB Pickup (I-STUB PICKUP) Backup overcurrent OUT * ON M LED BO 64 101 2 GI
OFF
7211 Backup O/C General TRIP command (O/C Backup overcurrent OUT * * LED BO 64 111 2
TRIP)
7212 Backup O/C TRIP - Only L1 (O/C TRIP 1p.L1) Backup overcurrent OUT * ON LED BO 64 112 2
7213 Backup O/C TRIP - Only L2 (O/C TRIP 1p.L2) Backup overcurrent OUT * ON LED BO 64 113 2
7214 Backup O/C TRIP - Only L3 (O/C TRIP 1p.L3) Backup overcurrent OUT * ON LED BO 64 114 2
7215 Backup O/C TRIP Phases L123 (O/C TRIP Backup overcurrent OUT * ON LED BO 64 115 2
L123)
7221 Backup O/C TRIP I>> (O/C TRIP I>>) Backup overcurrent OUT * ON LED BO 64 121 2
7222 Backup O/C TRIP I> (O/C TRIP I>) Backup overcurrent OUT * ON LED BO 64 122 2
7223 Backup O/C TRIP Ip (O/C TRIP Ip) Backup overcurrent OUT * ON LED BO 64 123 2
7235 O/C I-STUB TRIP (I-STUB TRIP) Backup overcurrent OUT * ON LED BO 64 135 2

List of Information
7325 CB1-TEST TRIP command - Only L1 (CB1- Testing OUT ON * LED BO 153 25 2 GI
TESTtrip L1) OFF
7326 CB1-TEST TRIP command - Only L2 (CB1- Testing OUT ON * LED BO 153 26 2 GI
TESTtrip L2) OFF
A-49
A-50

Appendix
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
7327 CB1-TEST TRIP command - Only L3 (CB1- Testing OUT ON * LED BO 153 27 2 GI
TESTtrip L3) OFF
7328 CB1-TEST TRIP command L123 (CB1- Testing OUT ON * LED BO 153 28 2 GI
TESTtrip123) OFF
7329 CB1-TEST CLOSE command (CB1-TEST Testing OUT ON * LED BO 153 29 2 GI
close) OFF
7345 CB-TEST is in progress (CB-TEST running) Testing OUT ON * LED BO 153 45 2 GI
OFF
7346 CB-TEST canceled due to Power Sys. Fault Testing OUT_Ev ON *
(CB-TSTstop FLT.)
7347 CB-TEST canceled due to CB already OPEN Testing OUT_Ev ON *
(CB-TSTstop OPEN)
7348 CB-TEST canceled due to CB was NOT Testing OUT_Ev ON *
READY (CB-TSTstop NOTr)
7349 CB-TEST canceled due to CB stayed CLOSED Testing OUT_Ev ON *
(CB-TSTstop CLOS)
7350 CB-TEST was succesful (CB-TST .OK.) Testing OUT_Ev ON *
>Back Light on (>Light on) Device SP ON * BI
OFF
CB1-TEST trip/close Phases L123 (CB1tst 123) Testing - *
CB1-TEST trip/close - Only L1 (CB1tst L1) Testing - *
C53000-G1176-C145-1

CB1-TEST trip/close - Only L2 (CB1tst L2) Testing - *


7SD610 Manual

CB1-TEST trip/close - Only L3 (CB1tst L3) Testing - *


Clock Synchronization (SynchClock) Device IntSP_Ev * * LED BO
Control Authority (Cntrl Auth) Control Authorization IntSP ON * LED 101 85 1 GI
OFF
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function Type of Log-Buffers Configurable in Matrix IEC 60870-5-103
Informa-

Trip (Fault) Log On/Off

Ground Fault Log On/

General Interrogation
tion

Event Log On/Off

Data Unit (ASDU)


Chatter Blocking
Marked in Oscill.

Information-No
Binary Output
Function Key
Binary Input
Record

Type
LED
Off
Controlmode LOCAL (ModeLOCAL) Control Authorization IntSP ON * LED 101 86 1 GI
OFF
Controlmode REMOTE (ModeREMOTE) Control Authorization IntSP ON * LED
OFF
Fault Recording Start (FltRecSta) Oscillographic Fault IntSP ON * LED BO
Records OFF
Group A (Group A) Change Group IntSP ON * LED BO 192 23 1 GI
OFF
Group B (Group B) Change Group IntSP ON * LED BO 192 24 1 GI
OFF
Group C (Group C) Change Group IntSP ON * LED BO 192 25 1 GI
OFF
Group D (Group D) Change Group IntSP ON * LED BO 192 26 1 GI
OFF
Hardware Test Mode (HWTestMod) Device IntSP ON * LED BO
OFF
Stop data transmission (DataStop) Device IntSP ON * LED BO 192 20 1 GI
OFF
Test mode (Test mode) Device IntSP ON * LED BO 192 21 1 GI
OFF
Unlock data transmission via BI (UnlockDT) Device IntSP

List of Information
A-51
A-52

Appendix
F.No. Description Function IEC 60870-5-103 Configurable
in Matrix

Abzweigsteuerbild
Data Unit (ASDU)
Kompatibilitaet
Information-No
Funktionstyp

Grundbild
Position

CFC
601 I L1 (IL1 =) Measurement 192 148 komp 9 1 CFC
134 129 priv 9 1
602 I L2 (IL2 =) Measurement 192 148 komp 9 2 CFC
134 129 priv 9 2
603 I L3 (IL3 =) Measurement 192 148 komp 9 3 CFC
134 129 priv 9 3
610 3I0 (zero sequence) (3I0 =) Measurement CFC
619 I1 (positive sequence) (I1 =) Measurement CFC
620 I2 (negative sequence) (I2 =) Measurement CFC
621 U L1-E (UL1E=) Measurement 192 148 komp 9 4 CFC
134 129 priv 9 4
622 U L2-E (UL2E=) Measurement 192 148 komp 9 5 CFC
134 129 priv 9 5
623 U L3-E (UL3E=) Measurement 192 148 komp 9 6 CFC
134 129 priv 9 6
624 U L12 (UL12=) Measurement 134 129 priv 9 10 CFC
625 U L23 (UL23=) Measurement 134 129 priv 9 11 CFC
C53000-G1176-C145-1

626 U L31 (UL31=) Measurement 134 129 priv 9 12 CFC


631 3U0 (zero sequence) (3U0 =) Measurement CFC
7SD610 Manual

634 U1 (positive sequence) (U1 =) Measurement CFC


635 U2 (negative sequence) (U2 =) Measurement CFC
641 P (active power) (P =) Measurement 192 148 komp 9 7 CFC
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function IEC 60870-5-103 Configurable
in Matrix

Abzweigsteuerbild
Data Unit (ASDU)
Kompatibilitaet
Information-No
Funktionstyp

Grundbild
Position

CFC
134 129 priv 9 7
642 Q (reactive power) (Q =) Measurement 192 148 komp 9 8 CFC
134 129 priv 9 8
643 Power Factor (PF =) Measurement CFC
644 Frequency (Freq=) Measurement 192 148 komp 9 9 CFC
134 129 priv 9 9
645 S (apparent power) (S =) Measurement CFC
801 Temperat. rise for warning and trip (Θ /Θtrip =) Measurement CFC
802 Temperature rise for phase L1 (Θ /ΘtripL1=) Measurement CFC
803 Temperature rise for phase L2 (Θ /ΘtripL2=) Measurement CFC
804 Temperature rise for phase L3 (Θ /ΘtripL3=) Measurement CFC
1000 Number of breaker TRIP commands (# TRIPs=) CFC
1001 Number of breaker TRIP commands L1 (TripNo L1=) CFC
1002 Number of breaker TRIP commands L2 (TripNo L2=) CFC
1003 Number of breaker TRIP commands L3 (TripNo L3=) CFC
1027 Accumulation of interrupted current L1 (Σ IL1 =) CFC
1028 Accumulation of interrupted current L2 (Σ IL2 =) CFC
1029 Accumulation of interrupted current L3 (Σ IL3 =) CFC
1030 Last fault current Phase L1 (Last IL1 =) CFC

List of Information
1031 Last fault current Phase L2 (Last IL2 =) CFC
1032 Last fault current Phase L3 (Last IL3 =) CFC
2895 No. of 1st AR-cycle CLOSE commands 1pole (AR #Close1./1p=) CFC
A-53

2896 No. of 1st AR-cycle CLOSE commands 3pole (AR #Close1./3p=) CFC
A-54

Appendix
F.No. Description Function IEC 60870-5-103 Configurable
in Matrix

Abzweigsteuerbild
Data Unit (ASDU)
Kompatibilitaet
Information-No
Funktionstyp

Grundbild
Position

CFC
2897 No. of higher AR-cycle CLOSE commands 1p (AR #Close2./1p=) CFC
2898 No. of higher AR-cycle CLOSE commands 3p (AR #Close2./3p=) CFC
7731 PHI IL1L2 (local) (Φ IL1L2=) Measurement CFC
7732 PHI IL2L3 (local) (Φ IL2L3=) Measurement CFC
7733 PHI IL3L1 (local) (Φ IL3L1=) Measurement CFC
7734 PHI UL1L2 (local) (Φ UL1L2=) Measurement CFC
7735 PHI UL2L3 (local) (Φ UL2L3=) Measurement CFC
7736 PHI UL3L1 (local) (Φ UL3L1=) Measurement CFC
7737 PHI UIL1 (local) (Φ UIL1=) Measurement CFC
7738 PHI UIL2 (local) (Φ UIL2=) Measurement CFC
7739 PHI UIL3 (local) (Φ UIL3=) Measurement CFC
7742 IDiffL1(% Operational nominal current) (IDiffL1=) Differential and Restraint 134 122 priv 9 1 CFC
Current
7743 IDiffL2(% Operational nominal current) (IDiffL2=) Differential and Restraint 134 122 priv 9 2 CFC
Current
7744 IDiffL3(% Operational nominal current) (IDiffL3=) Differential and Restraint 134 122 priv 9 3 CFC
Current
7745 IRestL1(% Operational nominal current) (IRestL1=) Differential and Restraint 134 122 priv 9 4 CFC
Current
7746 IRestL2(% Operational nominal current) (IRestL2=) Differential and Restraint 134 122 priv 9 5 CFC
C53000-G1176-C145-1

Current
7747 IRestL3(% Operational nominal current) (IRestL3=) Differential and Restraint 134 122 priv 9 6 CFC
7SD610 Manual

Current
7748 Diff3I0 (Differential current 3I0) (Diff3I0=) Differential and Restraint CFC
Current
C53000-G1176-C145-1
7SD610 Manual
F.No. Description Function IEC 60870-5-103 Configurable
in Matrix

Abzweigsteuerbild
Data Unit (ASDU)
Kompatibilitaet
Information-No
Funktionstyp

Grundbild
Position

CFC
7751 Prot Int 1: Delay time (PI1 DT=) Statistics 134 122 priv 9 7 CFC
7753 Prot Int 1: Availability per minute (PI1A/m) Statistics CFC
7754 Prot Int 1: Availability per hour (PI1A/h) Statistics 134 122 priv 9 8 CFC
7761 Relay ID of 1. relay (Relay ID) Measurements from relay 1 CFC
7762 IL1(% of Operational nominal current) (IL1_opN=) Measurements from relay 1 CFC
7763 Angle IL1_rem <-> IL1_loc (ΦI L1=) Measurements from relay 1 CFC
7764 IL2(% of Operational nominal current) (IL2_opN=) Measurements from relay 1 CFC
7765 Angle IL2_rem <-> IL2_loc (ΦI L2=) Measurements from relay 1 CFC
7766 IL3(% of Operational nominal current) (IL3_opN=) Measurements from relay 1 CFC
7767 Angle IL3_rem <-> IL3_loc (ΦI L3=) Measurements from relay 1 CFC
7769 UL1(% of Operational nominal voltage) (UL1_opN=) Measurements from relay 1 CFC
7770 Angle UL1_rem <-> UL1_loc (ΦU L1=) Measurements from relay 1 CFC
7771 UL2(% of Operational nominal voltage) (UL2_opN=) Measurements from relay 1 CFC
7772 Angle UL2_rem <-> UL2_loc (ΦU L2=) Measurements from relay 1 CFC
7773 UL3(% of Operational nominal voltage) (UL3_opN=) Measurements from relay 1 CFC
7774 Angle UL3_rem <-> UL3_loc (ΦU L3=) Measurements from relay 1 CFC
7781 Relay ID of 2. relay (Relay ID) Measurements from relay 2 CFC
7782 IL1(% of Operational nominal current) (IL1_opN=) Measurements from relay 2 CFC
7783 Angle IL1_rem <-> IL1_loc (ΦI L1=) Measurements from relay 2 CFC

List of Information
7784 IL2(% of Operational nominal current) (IL2_opN=) Measurements from relay 2 CFC
7785 Angle IL2_rem <-> IL2_loc (ΦI L2=) Measurements from relay 2 CFC
7786 IL3(% of Operational nominal current) (IL3_opN=) Measurements from relay 2 CFC
A-55

7787 Angle IL3_rem <-> IL3_loc (ΦI L3=) Measurements from relay 2 CFC
A-56

Appendix
F.No. Description Function IEC 60870-5-103 Configurable
in Matrix

Abzweigsteuerbild
Data Unit (ASDU)
Kompatibilitaet
Information-No
Funktionstyp

Grundbild
Position

CFC
7789 UL1(% of Operational nominal voltage) (UL1_opN=) Measurements from relay 2 CFC
7790 Angle UL1_rem <-> UL1_loc (ΦU L1=) Measurements from relay 2 CFC
7791 UL2(% of Operational nominal voltage) (UL2_opN=) Measurements from relay 2 CFC
7792 Angle UL2_rem <-> UL2_loc (ΦU L2=) Measurements from relay 2 CFC
7793 UL3(% of Operational nominal voltage) (UL3_opN=) Measurements from relay 2 CFC
7794 Angle UL3_rem <-> UL3_loc (ΦU L3=) Measurements from relay 2 CFC

n
C53000-G1176-C145-1
7SD610 Manual
Index

A Check
Binary inputs and outputs 8-28
Accessories A-4 Communication topology 8-32
Accuracy limit factor 6-9 Current transformer connections 8-38
Acknowledgement of commands 6-153 Differential protection communication 8-22
Action times (of AR) 6-70 Hardware 8-9
Adaptive dead time (AR) 6-77 Optical fibres 8-21
Alternating voltage (power supply) 10-3 Ordering number 3-3
Ambient temperatures 10-8 Power plant connections 8-22
Annunciations iii System (SCADA) interface 8-26
AR = automatic reclosure 6-69 Voltage transformer connections 8-37
Automatic reclosure 1-9, 5-3, 6-69, 10-19 Circuit breaker auxiliary contacts 6-50, 6-73, 6-95, 6-
Auxiliary contacts of the CB 6-50, 6-73, 6-95, 6-97, 6- 97, 6-104, 6-106, 6-119, 6-129, 6-136
104, 6-106, 6-119, 6-129, 6-136 Circuit breaker failure protection 1-9, 6-95, 10-20
Availability of transmission (differential protection) 6- Circuit breaker status 6-17
144, 7-11, 10-25 Circuit breaker status recognition 6-128
Circuit breaker switch-in recognition 6-127
B Circuit breaker test 6-9, 6-136, 7-41, 8-47
Climatic tests 10-8
Back-up overcurrent protection 6-54 Command acknowledgement 6-153
Battery 9-4, 10-25, A-5 Command processing 6-148
Binary inputs 1-3, 10-3 Command sequence 6-149
Binary inputs as sources 5-19 Command types 6-148
Binary outputs 1-3, 10-3 Commissioning mode 7-38
Binary outputs as destination 5-20 Commissioning tools 6-139
Binary outputs for switching devices 5-21 Common phase initiation (breaker failure) 6-98
Block data transmission 7-36, 8-26 Communication
Breaker failure protection 1-9, 6-95, 10-20 Differential protection 6-40
Broken-wire monitoring 6-118 SCADA 1-6, 4-3
Buffer battery 9-4, 10-25, A-5 Communication converter A-4
Communication interfaces 10-4
C Communication topology (differential protection) 6-40,
8-32
Caution ii
Configuration
CFC 4-24, 5-27, A-5
Commands 5-6
CFC as destination 5-23
Indication buffer as destination 5-23
CFC as source 5-20
Information 5-6
Changeover of setting groups 7-33, 8-5
Measured values 5-6
Charge comparison 6-29
Operator interface 5-37
Performing configuration 5-19
Scope of functions 5-2
Serial interfaces 5-36
Serial port on PC 5-36
Service interface 5-37

7SD610 Manual Index-i


C53000-G1176-C145-1
Index

Configuration sheet (CFC) 5-29 Disassembling the device 8-10, 9-9


Confirmation of setting values 6-3, 6-6 Display contrast 3-6
Conformity i Display equipment position 7-46
Connecting function modules (CFC) 5-30 Double point indication 5-15
Connection examples A-8
Consistency check (CFC) 5-31 E
Construction 10-9
Contact chatter suppression 5-16, 5-25 Electrical interfaces 2-14, 2-20
Control 7-46 Electrical tests 10-6
Device functions 7-28 Emergency overcurrent protection 6-54
During Operation 7-1 End fault protection 6-104, 6-108, 10-20
Messages 7-56 Evaluation of measured values 6-28
Switchgear 7-45 Event log 7-5
Control commands 5-7 Evolving faults (AR) 6-76
Copying setting groups 6-13 Exiting setting mode 6-4, 6-6
Copyright iv External local trip 1-8, 10-12
Corrective action 9-9
Cubicle mounting 2-2, 8-3 F
Current comparison 6-23
Current connections 6-8, 8-5, A-8 Fast charge comparison 6-29
Current flow monitoring (breaker failure) 6-96 Fault detection
Current grading 6-51, 6-60 entire device 6-131
Current symmetry supervision 6-117 Fault messages 7-6
Current transformers Fault recording 4-4, 6-145, 7-25, 10-25
Characteristics 6-9 Fault tracing 9-7
Connection examples A-8 Flush mounting 2-2, 8-2
Errors 6-9, 6-25 Four-line display 4-5
Polarity setting 6-7 Front elements 1-3
Rated value setting 6-7 Front view 2-2, 2-16
Requirements 10-2 Function control 6-127
Function key as source 5-19
Function modules (CFC) 5-28
D
Fuse 9-10
Danger ii
Data failure (differential protection) 6-42 G
Data fault (differential protection) 6-42
Date and time 5-40, 7-28 General diagrams A-6
Dead line check (AR) 6-76 General interrogation 7-10
Default display 7-14 General pickup 6-131
Definite-time overcurrent protection 6-54 General protection data 6-15
Deleting groups 5-18 Graphical analysis program DIGRA A-5
Deleting information 5-18 Group alarms 6-123
Destination (of information) 5-13
Differential protection 1-8, 6-23, 10-10 H
Differential protection topology 6-40, 10-13
Differential protection values 6-143 Hardware monitoring 6-115
DIGRA 4 A-5 High-speed SOTF protection 1-9, 6-50, 10-19
DIGSI REMOTE 4 A-5 Humidity 10-8
DIGSI® 4 A-5
Dimensions 10-26 I
Direct local trip 6-47, 10-12
Direct transfer trip 6-49 IBS-tool 6-139, 7-19, 8-36
Direct voltage (power supply) 10-2 Indication buffer as destination 5-23
Information 5-12

Index-ii 7SD610 Manual


C53000-G1176-C145-1
Index

Information properties 5-13 O


Initialize device 9-7
Input indication 5-6 Operating interface 1-4, 10-4
Inrush restraint 6-26 Operating messages 7-5
Interface cable A-5 Operating software DIGSI A-5
Interface modules 8-18, 9-6, A-4 Operational accuracy limit factor 6-10
Interlocking 6-150, 7-52 Optical interfaces 2-12, 2-18
Internal single point indication 5-14 FC-connector 2-19
Interrogation of circuit-breaker ready (AR) 6-72 ST-connector 2-12, 2-19
Intertrip 6-36, 10-12 Ordering code A-2
Inverse-time overcurrent protection 6-54 Ordering information A-2
Ordering number 3-4, A-2
Oscillographic fault records 4-4, 6-145, 7-25
J Output indication 5-6, 5-14
Jumpers on printed circuit boards 8-12 Overcurrent protection 1-8, 6-54, 10-14
Overload protection 1-9, 6-111, 10-21
Own information 5-16
L
LED as destination 5-22 P
Light-emitting diodes 7-2
List of information A-24 Panel flush mounting 2-2, 8-2
List of settings A-13 Panel surface mounting 2-15, 8-4
Local trip 6-47, 10-12 Parameter conditions iii
Lock-out 6-134 Parameter names iii
Log out device 7-38 Passwords 4-33
Phase segregated initiation (breaker failure) 6-99
Pickup
M
Differential protection 6-29
Maintenance 9-4 Entire device 6-131
Manual overwriting 7-49 Time overcurrent protection 6-59
Measured value synchronization (differential protection) Pickup characteristic (differential protection) 6-28
6-24 Plug-in connectors A-4
Measured value window as destination 5-23 Plug-in terminals 2-9
Measured values 7-14, 10-24 Polarity of current transformers 6-7
Differential protection 7-15, 7-22 Pole discrepancy supervision 6-105, 6-109, 10-20
Graphs 7-19 Power supply 1-4, 10-2
Local 7-15, 7-19 Power supply fuse 9-10
Remote 6-144, 7-16, 7-20 Power system data 1 6-7
Measured voltages 1-3 Power system data 2 6-15
Measurement during operation 6-142 Power transformer with voltage regulation 6-11
Mechanical tests 10-7 Power transformer within the protected zone 6-11, 6-16,
Messages 7-2 6-26, 6-144
Metered value window as destination 5-23 Preset configurations A-10
Monitor operation 9-7 Processing of commands 6-148
Monitoring functions 1-10 Processing of messages 6-141
Mounting brackets 8-3, A-5 Protection data interface 1-4, 6-40, 10-13
Multiple auto-reclosure 6-75
Q
N
Qualified personnel ii
No trip no flag 6-135
Note ii R
Numerical values 6-3, 6-5
Rack mounting 2-2, 8-3

7SD610 Manual Index-iii


C53000-G1176-C145-1
Index

Rated quantities of current transformers 6-7 Setting groups


Rated value settings Changeover 7-33, 8-5
Current transformers 6-7 Copying 6-13
Frequency 6-9 Definition 6-13
Power transformers 6-16 Setting user defined set-points 7-23
Protected lines 6-15 Setting values
Voltage transformers 6-7 Confirmation 6-3
Read-out Numerical 6-3, 6-5
Measured values 7-14 Text 6-3, 6-5
Messages 7-2 Short circuit links A-4
Switching statistics 7-11 Signal idle state 5-38
Rear view 2-4 Singe point indication 5-15
Reassembling the device 8-19, 9-11 Single and three-pole auto-reclosure 6-75
Reboot of processor system 9-3 Single-pole auto-reclosure 6-74
Reclosure interlocking 6-134 Single-pole tripping 6-132
Reducing the configuration matrix 5-11 Single-pole tripping after two-phase fault 6-133
Remote closing 6-78 Single-stage breaker failure protection 6-107
Remote measured values 6-144, 7-16, 7-20 Software monitoring 6-117
Remote tripping 1-8, 6-36, 6-49, 6-104, 10-12 Source (of information) 5-13
Repairs 9-9 Spontaneous messages 7-6, 7-11
Replacing Standard interlocking 6-151
Buffer battery 9-4 Start of auto-reclosure 6-70
Interface modules 8-18, 9-6 Statistics 6-136, 7-11, 10-25
Power supply fuse 9-10 Storage 3-12
Reset of processor system 9-3 Stub protection 6-57, 10-15
Resetting and setting switching statistics 7-13 Surface mounting 2-15, 8-4
Restoration (of metering values) 5-24 Switch-in recognition 6-127
Restoring factory settings 6-14 Switching authority 7-54
Restraint Switching interlock 6-150
Differential protection 6-25 Switching mode 7-55
Inrush 6-26 Switching statistics 7-11
Retrieval Switch-on-to-fault protection 1-9, 6-50
Device configurations 5-23 System (SCADA) interface 1-4, 7-4, 10-5
Device data 9-8
Interface settings 5-38 T
Ordering number 3-4
User defined set-points 7-23 Tagging 7-53
Return (of the device) 9-13 Terminal block covering caps A-4
Routine checks 9-3 Termination RS 485 8-21
Run-time properties (CFC) 5-27 Test mode 7-38
Test operation 7-36, 8-26
S Text values 6-3, 6-5
Thermal differential equation 6-111
Saving and erasing messages 7-9 Thermal overload protection 1-9, 6-111, 10-21
Saving fault records 7-27 Thermal time constant 6-111
Scope of functions 5-2 Three-pole auto-reclosure 6-74
Screw terminal connections 2-5, 2-17 Three-pole coupling 6-18
Serial interfaces 1-4, 5-36 Three-pole intertrip 6-84
Service conditions 10-9 Three-pole tripping 6-132
Service interface 1-4, 10-4 TICKS (CFC) 5-31
Set status 7-50 Time overcurrent protection 1-8, 6-54, 10-14
Time synchronization 1-4, 5-40, 8-21, 10-5
Timing master 5-40

Index-iv 7SD610 Manual


C53000-G1176-C145-1
Index

Transferring metering values 5-24 V


Transmission of binary information 6-49, 10-12
Transmission of measured values (differential protec- Viewing
tion) 6-23 Fault records 7-26
Triggering oscillographic recordings 8-47 Voltage connections 6-8, 8-5, A-9
Trip characteristic Voltage regulation (power transformer) 6-11
Differential protection 6-28 Voltage symmetry supervision 6-118
Inverse time overcurrent protection 10-16 Voltage transformer m.c.b. A-4
Trip circuit supervision 6-119, 8-6 Voltage transformers 5-4
Trip command duration 6-9, 6-134 Connection examples A-9
Trip log 7-6 Rated value setting 6-7
Tripping logic Voltages 1-3
Differential protection 6-30
Entire device 6-132 W
Time overcurrent protection 6-59
Two-stage breaker failure protection 6-106 Warning ii
Types of commands 6-148 Watchdog 6-117
Weak infeed 1-8
U
User defined
Functions (CFC) 1-9, 5-27
Information = Own information 5-16
Limit values 5-16
Measured values 5-16
Pulse metered values 7-24
Set-points 7-23

7SD610 Manual Index-v


C53000-G1176-C145-1
Index

Index-vi 7SD610 Manual


C53000-G1176-C145-1
Corrections

To From
Siemens AG Name:
Dept. EV S D PSN
D–13623 Berlin Company/Dept.:
Germany

Address:
Dear reader,
printing errors can never be entirely eliminated:
therefore, should you come across any when read- Phone no.: Fax no.:
ing this manual, kindly enter them in this form to-
gether with any comments or suggestions for im-
provement that you may have.

Corrections/Suggestions

7SD610 Manual
C53000-G1176-C145-1
Copying of this document and giving it to others and the use
or communication of the contents thereof, are forbidden with-
out express authority. Offenders are liable to the payment of
damages. All rights are reserved in the event of the grant of
Subject to technical alteration a patent or the registration of a utility model or design.

Siemens Aktiengesellschaft Order-no.: C53000-G1176-C145-1


Available from: LZF Fürth-Bislohe
Printed in Germany/Imprimé en Allemagne
AG 0201 0.2 FO 502 En

You might also like