IM 01C25A01-01E
Contents
1. Introduction 1
1.1 For Safe Use of Product...............................................2
1.2 Warranty.......................................................................3
1.3 ATEX Documentation...................................................4 2
2. Handling Cautions
2.1
2.2
Model and Specifications Check..................................6
Selecting the Installation Location...............................6
3
2.3 Pressure Connection...................................................6
2.4 Installation of an Explosion-Protected Instrument.......6
2.5 EMC Conformity Standards...................................... 31 4
2.6 Pressure Equipment Directive (PED)....................... 31
2.7 Safety Requirement Standards................................. 32
3. Installation 5
3.1 Mounting................................................................... 33
3.2 Mounting the Diaphragm Seals.......................................33
3.3 Diaphragm Seals Installation Consideration............. 34 6
3.4 Mounting the Flushing Connection Ring................... 35
3.5 Affixing the Teflon Film.............................................. 36
3.6 Rotating Transmitter Section..................................... 37 7
3.7 Changing the Direction of Integral Indicator............. 37
4. Installing Impulse Piping
4.1 Impulse Piping Installation Precautions.................... 38
4.2 Impulse Piping Connection Examples...................... 40
4.3 Process Piping Installation Precautions (EJ115).41
5. Wiring
5.1 Wiring Precautions.................................................... 43
5.2 Connections of External Wiring to Terminal Box....... 43
5.3 Wiring........................................................................ 46
5.4 RTD Cable Connection (EJX910A/EJX930A).......... 48
5.5 Grounding................................................................. 50
5.6 Power Supply Voltage and Load Resistance............ 50
6. Operation
6.1 Preparation for Starting Operation............................ 51
6.2 Zero Point Adjustment............................................... 51
6.3 Local Parameter Setting........................................... 52
7. Errors and Countermeasures
IM 01C25A01-01E
11th Edition
<1. Introduction> 1
1. Introduction
This installation manual provides the basic guidelines [EJX series Communication Manual]
for installation and wiring procedures of the DPharp EJX Models Document No. Style
series and EJA-E series transmitters with BRAIN and DPharp HART 5/HART 7
HART protocols and is composed of the information IM 01C25T01-06EN —
Communication Type
extracted from the product users’ manuals as listed in DPharp FOUNDATION Fieldbus
IM 01C25T02-01E —
Table 1.1. It does not provide the information including Communication Type
wiring procedures of the transmitters with FOUNDATION DPharp BRAIN Communication
IM 01C25T03-01E —
Fieldbus, Profibus and Modbus protocols, product Type
DPharp PROFIBUS PA
specific functional specifications and explanations, IM 01C25T04-01EN —
Communication Type
operation, maintenance and trouble-shooting.
EJX910A and EJX930A HART
IM 01C25R02-01E —
Communication Type
WARNING EJX910A and EJX930A Fieldbus
Communication Type
IM 01C25R03-01E —
Introduction
and specifications as listed Table 1.1, read them
[EJA-E series Hardware Manual]
thoroughly and fully understand how to operate the
instrument before operating it. Models Document No. Style
EJA110E, EJA120E
EJA130E, EJA310E, EJA430E IM 01C25B01-01E S1
Users’ manual for each product consists of a hardware and EJA440E
manual describing installation, wiring, operation, EJA210E IM 01C25C01-01E S1
maintenance and specification including detailed model EJA510E and EJA530E IM 01C25F01-01E S1
and suffix code information, and a communication EJA118E and EJA438E IM 01C25H01-01E S1
manual describing information specific to each EJA115E IM 01C25K01-01E S1
communication protocol type, including safety manual for
safety instrumented system. [EJA-E series Communication Manual]
These manuals can be downloaded from the website Models Document No. Style
of Yokogawa or purchased from the Yokogawa DPharp HART 5/HART 7
IM 01C25T01-06EN —
representatives. Communication Type
DPharp FOUNDATION Fieldbus
Website address: http://www.yokogawa.com/fld/ IM 01C25T02-01E —
Communication Type
DPharp BRAIN Communication
IM 01C25T03-01E —
Type
Table 1.1 PDF Manual List and Applicable Style Code DPharp PROFIBUS PA
IM 01C25T04-01EN —
Communication Type
[EJX series Hardware Manual]
Models Document No. Style
EJX110A S3 Regarding This Manual
EJX120A S1
IM 01C25B01-01E
EJX130A, EJX310A, EJX430A • This manual should be passed on to the end user.
S2
and EJX440A • The contents of this manual are subject to change
EJX210A IM 01C25C01-01E S2
without prior notice.
EJX510A and EJX530A S2
IM 01C25F01-01E • All rights reserved. No part of this manual may be
EJX610A and EJX630A S1
EJX118A and EJX438A IM 01C25H01-01E S2 reproduced in any form without Yokogawa’s written
EJX115A IM 01C25K01-01E S1 permission.
EJX910A S2 • Yokogawa makes no warranty of any kind with regard
IM 01C25R01-01E
EJX930A S1 to this manual, including, but not limited to, implied
warranty of merchantability and fitness for a particular
purpose.
• If any question arises or errors are found, or if any
information is missing from this manual, please
inform the nearest Yokogawa sales office.
NOTE WARNING
Draws attention to information essential for
• The instrument must be installed by an expert
understanding the operation and features.
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
Direct current operators.
• Please confirm that voltages between the power
Functional grounding terminal supply and the instrument before connecting the
power cables and that the cables are not powered
before connecting.
IM 01C25A01-01E
<1. Introduction> 3
(c) Operation (h) Authorized Representative in EEA
In relation to the CE Marking, The authorized
WARNING representative for this product in the EEA (European
Economic Area) is:
• Wait 5 min. after power is turned off, before Yokogawa Europe B.V.
opening the covers. Euroweg 2, 3825 HD Amersfoort,The Netherlands
• Do not open the cover in wet weather or humid
environment. If the cover is opened, stated
enclosure protection is not applicable.
1.2 Warranty
• The warranty shall cover the period noted on the
quotation presented to the purchaser at the time of
(d) Maintenance purchase. Problems occurred during the warranty
period shall basically be repaired free of charge.
WARNING • In case of problems, the customer should contact the
Yokogawa representative from which the instrument
• Please do not carry out except being written was purchased, or the nearest Yokogawa office.
to maintenance descriptions. When these
1
• If a problem arises with this instrument, please inform
procedures are needed, please contact nearest us of the nature of the problem and the circumstances
Introduction
YOKOGAWA office. under which it developed, including the model
• Care should be taken to prevent the build up of specification and serial number. Any diagrams,
drift, dust or other material on the display glass data and other information you can include in your
and name plate. In case of its maintenance, soft communication will also be helpful.
and dry cloth is used.
• Responsible party for repair cost for the problems
shall be determined by Yokogawa based on our
investigation.
(e) Explosion Protected Type Instrument
• The Purchaser shall bear the responsibility for
repair costs, even during the warranty period, if the
WARNING malfunction is due to:
• Users of explosion proof instruments should refer - Improper and/or inadequate maintenance by the
first to section 2.4 (Installation of an Explosion purchaser.
Protected Instrument) of this manual. - Failure or damage due to improper handling, use
• For TIIS flameproof type instruments, be sure or storage which is out of design conditions.
to read “INSTALLATION AND OPERATING - Use of the product in question in a location
PRECAUTIONS FOR TIIS FLAMEPROOF not conforming to the standards specified by
EQUIPMENT” at the end of this manual. Yokogawa, or due to improper maintenance of the
• The use of this instrument is restricted to those installation location.
who have received appropriate training in the - Failure or damage due to modification or repair
device. by any party except Yokogawa or an approved
• Take care not to create sparks when accessing the representative of Yokogawa.
instrument or peripheral devices in a hazardous - Malfunction or damage from improper relocation of
location. the product in question after delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/lightening,
(f) Modification or other natural disasters, or disturbances, riots,
warfare, or radioactive contamination.
WARNING Trademarks:
• ‘DPharp’, ‘EJX’, ‘EJA’, ‘FieldMate’ and ‘BRAIN
• Yokogawa will not be liable for malfunctions or TERMINAL’ are registered trademarks of Yokogawa
damage resulting from any modification made to Electric Corporation. Company names and product
this instrument by the customer. names used in this material are registered trademarks
or trademarks of their respective owners.
• In this manual, trademarks or registered trademarks
(g) Product Disposal are not marked with ™ or ®.
The instrument should be disposed of in accordance with
local and national legislation/regulations.
IM 01C25A01-01E
<1. Introduction> 4
1.3 ATEX Documentation
This is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C25A01-01E
<2. Handling Cautions> 5
2. Handling Cautions
When the transmitter is delivered, visually check them EJ110 B
to make sure that no damage occurred during shipment. EJ120 1 D
Also check that all transmitter mounting hardware shown EJ130 2 G
- -
EJ310 3 J
in Figure 2.1 is included. If the transmitter was ordered
EJ430 4 K
without the mounting bracket or without the process EJ440 M
connector, the transmitter mounting hardware is not
included. 1
B
2
Table 2.1 Applicable Model Code for Mounting 1 D
3
Hardware EJX910A 2 G
4
- - J
EJX930A 3
Applicable B
Suffix code Part name Qty 4 K
model C
M
D
EJ110 Process connector bolt 4
1
EJ120 Process Process connector 2
2
EJ130 connections EJ210 - -
Process connector 3
EJX910A 1,2,3 and 4 2
gasket 4
EJX930A
EJ210 Process connector bolt 2
EJ510 2
Process EJ530 F
EJ310 Process connector 1 - -
connections EJX610A L
Handling Cautions
EJ430 Process connector EJX630A
1,2,3 and 4 1
EJ440 gasket
EJ110 EJ118 B
- -
EJ120 U-bolt 1 EJ438 J
EJ130
EJ310 B
U-bolt nut 2 D
EJ430 Mounting bracket EJ115 - -
EJ440 B,D,G,J,K and J
EJ118 M* Mounting bracket K
1
EJ438 (L or flat type) F0201.ai
EJ115
EJX910A Transmitter mounting Cable gland and RTD cable
4 (EJX910A and EJX930A only)
EJX930A bolt
U-bolt (S)
U-bolt (L)
F0202.ai
IM 01C25A01-01E
<2. Handling Cautions> 6
2.1 Model and Specifications 2.3 Pressure Connection
Check
The model name and specifications are indicated on the WARNING
name plate attached to the case.
• Never loosen the process connector bolts when an
instrument is installed in a process. The device is
under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluid.
• When draining toxic process fluids that have
condensed inside the pressure detector, take
appropriate steps to prevent the contact of such
fluids with the skin or eyes and the inhalation of
vapors from these fluids.
IM 01C25A01-01E
<2. Handling Cautions> 7
• Intrinsically Safe Apparatus Parameters
WARNING [Groups C, D, E, F and G]
Vmax = 30 V Ci = 6 nF
The range setting switch must not be used in a Imax = 225 mA Li = 0 µH
hazardous area. Pmax = 1 W
Handling Cautions
Protocol Type (Except for EJX90A)
RP12.6 “Installation of Intrinsically Safe Systems
Caution for FM intrinsically safe type. (Following for Hazardous (Classified) Locations” and the
contents refer “DOC. No. IFM022-A12”) National Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be
Note 1. EJX/EJA-E Series pressure transmitters with
FMRC Approved.
optional code /FS1 are applicable for use in
• Dust-tight conduit seal must be used when
hazardous locations.
installed in a Class II, III, Group E, F and G
• Applicable Standard: FM3600, FM3610, FM3611,
environments.
FM3810
• Associated apparatus manufacturer’s installation
• Intrinsically Safe for Class I, Division 1, Groups A,
drawing must be followed when installing this
B, C & D. Class II, Division 1, Groups E, F & G and
apparatus.
Class III, Division 1, Class I, Zone 0 in Hazardous
• The maximum power delivered from the barrier
Locations, AEx ia IIC
must not exceed 1 W.
• Nonincendive for Class I, Division 2, Groups
• Note a warning label worded “SUBSTITUTION
A, B, C & D. Class II, Division 2, Groups F & G
OF COMPONENTS MAY IMPAIR INTRINSIC
and Class I, Zone 2, Groups IIC, in Hazardous
SAFETY,” and “INSTALL IN ACCORDANCE WITH
Locations.
DOC. No. IFM022-A12”
• Enclosure: Type 4X
• Temperature Class: T4 Note 4. Maintenance and Repair
• Ambient temperature: –60 to 60°C • The instrument modification or parts replacement
by other than authorized representative of
Note 2. Entity Parameters
Yokogawa Electric Corporation is prohibited and
• Intrinsically Safe Apparatus Parameters
will void Factory Mutual Intrinsically safe and
[Groups A, B, C, D, E, F and G]
Nonincendive Approval.
Vmax = 30 V Ci = 6 nF
Imax = 200 mA Li = 0 µH [Intrinsically Safe]
Pmax = 1 W Hazardous Location Nonhazardous Location
* Associated Apparatus Parameters Class I, II, III, Division 1,
(FM approved barriers) Groups A, B, C, D, E, F, G
Class 1, Zone 0 in
Voc ≤ 30 V Ca > 6 nF Hazardous (Classified) General
Isc ≤ 200 mA La > 0 µH Locations AEx ia IIC Purpose
Pmax ≤ 1W Pressure Transmitters Safety Barrier Equipment
+ + + +
Supply – – – –
F0204.ai
IM 01C25A01-01E
<2. Handling Cautions> 8
[Nonincendive] IFM024-A12
Hazardous Location Nonhazardous Location
Class I, II, Division 2, Installation Diagram for Intrinsically Safe
Groups A, B, C, D, F, G (Division 1 Installation)
Class 1, Zone 2, Group IIC,
in Hazardous (Classified)
General Terminator
Locations
Purpose
Pressure Transmitters Equipment
+ Pressure
+ + − Transmitter
Supply – –
Not Use +
Safety Barrier − Field Instruments
F0205.ai
[Entity Model]
Class I, II & III, Division 1, Groups A, B, C, D, E, F Note 1. Barrier must be installed in an enclosure that
& G, Temperature Class T4 Ta=60°C, Type 4X and meets the requirements of ANSI/ISA 61010-1.
Class I, Zone 0, AEx ia IIC, Temperature Class T4
Note 2. Control equipment connected to the Associ
Ta=60°C, Type 4X
ated Apparatus must not use or generate more
[FISCO Model]
than 250 Vrms or Vdc.
Class I, II & III, Division 1, Groups A, B, C, D, E, F
& G, Temperature Class T4 Ta=60°C, Type 4X and Note 3. Installation should be in accordance with ANSI/
Class I, Zone 0, AEx ia IIC, Temperature Class T4 ISA 12.06.01 “Installation of Intrinsi cally Safe
Ta=60°C, Type 4X Systems for Hazardous (Classified) Locations”
• Nonincendive Approval and the National Electrical Code (ANSI/NFPA
Class I, Division 2, Groups A, B, C & D 70) Sections 504 and 505.
Temperature Class T4 Ta=60°C, Type 4X and
Note 4. The configuration of Associated Apparatus must
Class II, Division 2, Groups F & G Temperature
be Factory Mutual Research Approved under
Class T4 Ta=60°C, Type 4X and Class I, Zone 2,
FISCO Concept.
Group IIC, Temperature Class T4 Ta=60°C, Type
4X Note 5. Associated Apparatus manufacturer’s installa
• Electrical Connection: 1/2 NPT female, M20 tion drawing must be followed when installing
female this equipment.
• Caution for FM Intrinsically safe type. (Following
Note 6. No revision to drawing without prior Factory
contents refer to “DOC. No. IFM024-A12 p.1, p.2,
Mutual Research Approval.
p.3, p.4-1 and p.4-2.”)
Note 7. Terminator must be FM Approved.
Note 8. Note a warning label worded “SUBSTITU TION
OF COMPONENTS MAY IMPAIR INTRINSIC
SAFETY”, and “INSTALL IN ACCORDANCE
DOC.NO.IFM024-A12 P.1 TO 4.”
IM 01C25A01-01E
<2. Handling Cautions> 9
Electrical Data: to the bus cable has to be passive, meaning that the
apparatus is not allowed to provide energy to the system,
• Rating 1 (Entity)
except to a leakage current of 50 µA for each connected
For Groups A, B, C, D, E, F, and G or Group IIC
device.
Maximum Input Voltage Vmax: 24 V
Maximum Input Current Imax: 250 mA Supply unit
Maximum Input Power Pmax: 1.2 W
Trapezoidal or rectangular output characteristic only
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 µH Uo = 14...17.5 V (I.S. maximum value)
or
Io according to spark test result or other assessment.
• Rating 2 (FISCO)
No specification of Lo and Co is required on the
For Groups A, B, C, D, E, F, and G or Group IIC
certificate or label.
Maximum Input Voltage Vmax: 17.5 V
Maximum Input Current Imax: 380 mA Cable
Maximum Input Power Pmax: 5.32 W
The cable used to interconnect the devices needs to
Maximum Internal Capacitance Ci: 3.52 nF
comply with the following parameters:
Maximum Internal Inductance Li: 0 µH
or Loop resistance R’: 15...150 Ω/km
• Rating 3 (FISCO) Inductance per unit length L’: 0.4...1 mH/km
For Groups C, D, E, F, and G or Group IIB Capacitance per unit length C’: 45...200 nF/km.
Maximum Input Voltage Vmax: 17.5 V C’=C’ line/line + 0.5 C’ line/screen, if both lines are 2
Maximum Input Current Imax: 460 mA floating or C’=C’ line/line + C’ line/screen, if the screen
Handling Cautions
Maximum Input Power Pmax: 5.32 W is connected to one line.
Maximum Internal Capacitance Ci: 3.52 nF Length of spur cable: max. 60 m
Maximum Internal Inductance Li: 0 µH Length of trunk cable: max. 1 km (Group IIC) or 5 km
Note: In the rating 1, the output current of the barrier must be (Group IIB)
limited by a resistor “Ra” such that Io=Uo/Ra. In the rating Length of splice: max.1 m
2 or 3, the output characteristics of the barrier must be the
type of trapezoid which are certified as the FISCO model Terminators
(See “FISCO Rules”). The safety barrier may include
a terminator. More than one field instruments may be At each end of the trunk cable an FM approved line
connected to the power supply line. terminator with the following parameters is suitable:
FISCO Rules R = 90...100 Ω
The FISCO Concept allows the interconnection of C = 0...2.2 mF
intrinsincally safe apparatus to associated apparatus System evaluations
not specifically examined in such combination. The
criterion for such interconnection is that the voltage (Ui), The number of passive device like transmitters, actuators,
the current (Ii) and the power (Pi) which intrinsically hand held terminals connected to a single bus segment is
safe apparatus can receive and remain intrinsically not limited due to I.S. reasons. Furthermore, if the above
safe, considering faults, must be equal or greater than rules are respected, the inductance and capacitance of
the voltage (Uo, Voc, Vt), the current (Io, Isc, It) and the the cable need not to be considered and will not impair
power (Po) which can be provided by the associated the intrinsic safety of the installation.
apparatus (supply unit).
HAZARDOUS AREA SAFE AREA
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii Supply Unit and
Terminator
Safety Barrier
In addition, the maximum unprotected residual (FISCO Model)
(FISCO Model)
capacitance (Ci) and inductance (Li) of each apparatus Ex i
(other than the terminators) connected to the fieldbus U
U
must be less than or equal to 5 nF and 10 µH
I
respectively.
IM 01C25A01-01E
<2. Handling Cautions> 10
Installation Diagram for Nonincendive Note 11. If ordinary location wiring methods are used,
(Division 2 Installation) the transmitter shall be connected to FM
Approved associated non-incendive field wiring
Terminator apparatus.
Electrical data:
+
SUPPLY Vmax: 32V
−
Pressure Ci: 3.52 nF
Transmitter
Li: 0 µH
+
−
Transmitter FNICO Rules
The FNICO Concept allows the interconnection of
nonincendive field wiring apparatus to associated
+ nonincendive field wiring apparatus not specifically
Transmitter
− examined in such combination. The criterion for such
interconnection is that the voltage (Vmax), the current
Hazardous location (Imax) and the power (Pmax) which nonincendive field
wiring apparatus can receive and remain nonincendive,
Non-Hazardous location considering faults, must be equal or greater than the
Terminator voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the
FM Approved power (Po) which can be provided by the associated
Associated Nonincendive Field nonincendive field wiring apparatus (supply unit). In
+ − Wiring Apparatus
General Purpose Vt or Voc addition the maximum unprotected residual capacitance
Equipment It or Isc (Ci) and inductance (Li) of each apparatus (other than
+ − Ca terminators) connected to the Fieldbus must be less than
La
F0225.ai
or equal to 5nF and 10uH respectively.
In each N.I. Fieldbus segment only one active source,
Note 1. Installation should be in accordance with the
normally the associated nonincendive field wiring
National Electrical Code ® (ANSI/NFPA 70)
apparatus, is allowed to provide the necessary power for
Article 500.
the Fieldbus system. The allowed voltage (Uo, Voc or
Note 2. The configuration of Associated Nonincendive Vt) of the associated nonincendive field wiring apparatus
Field Wiring Apparatus must be FM Approved. used to supply the bus cable must be limited to the range
14Vdc to 17.5Vdc. All other equipment connected to the
Note 3. Approved under FNICO Concept.
bus cable has to be passive, meaning that the apparatus
Note 4. Dust-tight conduit seal must be used when is not allowed to provide energy to the system, except
installed in Class II and Class III environments. a leakage current of 50É A for each connected device.
Separately powered equipment needs galvanic isolation
Note 5. Associated Apparatus manufacturer’s
to ensure the nonincendive field wiring Fieldbus circuit
installation drawing must be followed when
remains passive.
installing this apparatus.
Note 6. No revision to drawing without prior FM Cable
Approvals. The cable used to interconnect the devices needs to
Note 7. Terminator must be FM Approved. comply with the following parameters:
Note 8. The nonincendive field wiring circuit concept Loop resistance R’: 15...150 Ω/km
allows interconection of nonincendive field Inductance per unit length L’: 0.4...1 mH/km
wiring apparatus with associated nonincendive Capacitance per unit length C’: 80....200 nF/km
field wiring apparatus, using any of the wiring C’ =C’ line/line+0.5 C’ line/screen, if both lines
methods permitted for unclassified locations. are floating or C’ = C’ line/line + C’ line/screen, if
thescreen is connected to one line.
Note 9. Installation requirements; Length of spur cable: max. 30 m
Vmax ≥ Voc or Vt Length of trunk cable: max. 1 km
Imax = see note 10. Length of splice: max = 1 m
Ca ≥ Ci + Ccable
La ≥ Li + Lcable Terminators
Note 10. For this current controlled circuit, the parameter At the end of each trunk cable an FM Approved line
(Imax 3 ) is not required and need not be terminator with the following parameters is suitable:
aligned with parameter (Isc 3 ) of the barrier or R= 90...100 Ω
associated nonincendive field wiring apparatus. C = 0 ....2.2 uF
IM 01C25A01-01E
<2. Handling Cautions> 11
c. FM Intrinsically Safe for Fieldbus Type for Note 2. Control equipment connected to the Associ ated
EJX90A Apparatus must not use or generate more than
250 Vrms or Vdc.
EJX multivariable transmitter with optional code
/FS15 are applicable for use in hazardous locations. Note 3. Installation should be in accordance with ANSI/
• Applicable standard: FM3600, FM3610, FM3611, ISA 12.06.01 “Installation of Intrinsi cally Safe
FM3810, ANSI/NEMA250, IEC60079-27 Systems for Hazardous (Classified) Locations”
• FM Intrinsically Safe Approval and the National Electrical Code (ANSI/NFPA
[Entity Model] 70) Sections 504 and 505.
Class I, II & III, Division 1, Groups A, B, C, D, F & Note 4. The configuration of Associated Apparatus must
G, Temperature Class T4 Ta=60ºC, Type 4X and be Factory Mutual Research Approved under
Class I, Zone 0, AEx ia IIC, Temperature Class T4 FISCO Concept.
Ta=60ºC, Type 4X
[FISCO Model] Note 5. Associated Apparatus manufacturer’s installa
Class I, II & III, Division 1, Groups A, B, C, D, F & tion drawing must be followed when installing
G, Temperature Class T4 Ta=60ºC, Type 4X and this equipment.
Class I, Zone 0, AEx ia IIC, Temperature Class T4 Note 6. No revision to drawing without prior Factory
Ta=60ºC, Type 4X Mutual Research Approval.
• Nonincendive Approval
Class I, Division 2, Groups A, B, C & D Note 7. Terminator must be FM Approved.
Temperature Class T4 Ta=60ºC, Type 4X and 2
Note 8. Note a warning label worded “SUBSTITU TION
Class II, Division 2, Groups F & G Temperature OF COMPONENTS MAY IMPAIR INTRINSIC
Handling Cautions
Class T4 Ta=60ºC, Type 4X and Class I, Zone 2, SAFETY”, and “INSTALL IN ACCORDANCE
Group IIC, Temperature Class T4 Ta=60ºC, Type DOC.NO.IFM026-A12 P.1 TO 4.”
4X and Class III, Division 1, Temperature Class T4
Ta=60ºC, Type 4X Electrical Data:
• Electrical Connection: 1/2 NPT female, M20 • Rating 1 (Entity)
female For Groups A, B, C, D, F, and G or Group IIC
• Caution for FM Intrinsically safe type. (Following Maximum Input Voltage Vmax: 24 V
contents refer to “DOC. No. IFM026-A12 p.1 to Maximum Input Current Imax: 250 mA
p.4.”) Maximum Input Power Pmax: 1.2 W
IFM026-A12 Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH
Installation Diagram for Intrinsically Safe or
• Rating 2 (FISCO)
(Division 1 Installation)
For Groups A, B, C, D, F, and G or Group IIC
Maximum Input Voltage Vmax: 17.5 V
Terminator
Maximum Input Current Imax: 380 mA
Maximum Input Power Pmax: 5.32 W
+ Pressure Maximum Internal Capacitance Ci: 3.52 nF
– Transmitter
Maximum Internal Inductance Li: 0 μH
+
or
– Field Instruments • Rating 3 (FISCO)
For Groups C, D, F, and G or Group IIB
Maximum Input Voltage Vmax: 17.5 V
+
– Field Instruments Maximum Input Current Imax: 460 mA
Maximum Input Power Pmax: 5.32 W
Hazardous Location
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH
Non-Hazardous Location
Terminator Sensor Circuit: Uo=6.51 V, Io=4 mA,
Po=6 mW, Co=34 µF, Lo=500 mH
+ –
Safety Barrier Note: In the rating 1, the output current of the barrier must be
limited by a resistor “Ra” such that Io=Uo/Ra. In the rating
+ – 2 or 3, the output characteristics of the barrier must be the
F0226.ai
type of trapezoid which are certified as the FISCO model
(See “FISCO Rules”). The safety barrier may include
Note 1. Barrier must be installed in an enclosure that a terminator. More than one field instruments may be
meets the requirements of ANSI/ISA 61010-1. connected to the power supply line.
IM 01C25A01-01E
<2. Handling Cautions> 12
● FISCO Rules System evaluations
The FISCO Concept allows the interconnection of The number of passive device like transmitters,
intrinsincally safe apparatus to associated apparatus actuators, hand held terminals connected to a single
not specifically examined in such combination. The bus segment is not limited due to I.S. reasons.
criterion for such interconnection is that the voltage (Ui), Furthermore, if the above rules are respected, the
the current (Ii) and the power (Pi) which intrinsically inductance and capacitance of the cable need not to
safe apparatus can receive and remain intrinsically be considered and will not impair the intrinsic safety of
safe, considering faults, must be equal or greater than the installation.
the voltage (Uo, Voc, Vt), the current (Io, Isc, It) and the HAZARDOUS AREA SAFE AREA
power (Po) which can be provided by the associated
Supply Unit and
apparatus (supply unit). Terminator
Safety Barrier
(FISCO Model)
(FISCO Model)
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii Ex i
U
In addition, the maximum unprotected residual
U
capacitance (Ci) and inductance (Li) of each apparatus
I
(other than the terminators) connected to the fieldbus
must be less than or equal to 5 nF and 10 µH Hand- Terminator
respectively. held-
Terminal Data
Ci ≤ 5nF, Li ≤ 10µH
In each I.S. fieldbus segment only one active source, Field Instruments
(Passive)
normally the associated apparatus, is allowed to provide F0227.ai
the necessary power for the fieldbus system. The allowed I.S. fieldbus system complying with FISCO model
voltage(Uo, Voc,Vt) of the associated apparatus used to
supply the bus cable must be limited to the range of 14 V
dc to 17.5 V dc. All other equipment connected to the bus ● Installation Diagram for Nonincendive
cable has to be passive, meaning that the apparatus is (Division 2 Installation)
not allowed to provide energy to the system, except to a
leakage current of 50 µA for each connected device. Terminator
Supply unit +
SUPPLY
–
Trapezoidal or rectangular output characteristic only Pressure
Transmitter
Uo = 14...17.5 V (I.S. maximum value)
+
Transmitter
Io according to spark test result or other assessment. –
Cable +
– Transmitter
IM 01C25A01-01E
<2. Handling Cautions> 13
Note 4. Dust-tight conduit seal must be used when 14Vdc to 17.5Vdc. All other equipment connected to the
installed in Class II and Class III environments. bus cable has to be passive, meaning that the apparatus
is not allowed to provide energy to the system, except
Note 5. Associated Apparatus manufacturer’s
a leakage current of 50 µA for each connected device.
installation drawing must be followed when
Separately powered equipment needs galvanic isolation
installing this apparatus.
to ensure the nonincendive field wiring Fieldbus circuit
Note 6. No revision to drawing without prior FM remains passive.
Approvals.
Note 7. Terminator must be FM Approved.
Cable
The cable used to interconnect the devices needs to
Note 8. The nonincendive field wiring circuit concept
comply with the following parameters:
allows interconection of nonincendive field
wiring apparatus with associated nonincendive Loop resistance R’: 15...150 Ω/km
field wiring apparatus, using any of the wiring Inductance per unit length L’: 0.4...1 mH/km
methods permitted for unclassified locations. Capacitance per unit length C’: 45....200 nF/km
Note 9. Installation requirements; C’ =C’ line/line+0.5 C’ line/screen, if both lines are
Vmax ≥ Voc or Vt floating or C’ = C’ line/line + C’ line/screen, if the
Imax = see note 10. screen is connected to one line.
Ca ≥ Ci + Ccable Length of spur cable: max. 60 m
La ≥ Li + Lcable Length of trunk cable: max. 1 km (Group IIC) or 2
5 km (Group IIB)
Note 10. For this current controlled circuit, the parameter Length of splice: max = 1 m
Handling Cautions
(Imax) is not required and need not be aligned
with parameter (Isc) of the barrier or associated Terminators
nonincendive field wiring apparatus. At the end of each trunk cable an FM Approved line
Note 11. If ordinary location wiring methods are used, the terminator with the following parameters is suitable:
transmitter shall be connected to FM Approved R= 90...100 Ω
associated nonincendive field wiring apparatus. C = 0 ....2.2 mF
Electrical data: d. FM Explosionproof
Vmax: 32V
Ci: 3.52 nF Caution for FM explosionproof type.
Li: 0 µH Note 1. EJX/EJA-E Series pressure transmitters with
● FNICO Rules optional code /FF1 or /V1F are applicable for
use in hazardous locations.
The FNICO Concept allows the interconnection of • Applicable Standard: FM3600, FM3615, FM3810,
nonincendive field wiring apparatus to associated ANSI/NEMA 250
nonincendive field wiring apparatus not specifically • Explosionproof for Class I, Division 1, Groups B, C
examined in such combination. The criterion for such and D.
interconnection is that the voltage (Vmax), the current • Dust-ignitionproof for Class II/III, Division 1,
(Imax) and the power (Pmax) which nonincendive field Groups E, F and G.
wiring apparatus can receive and remain nonincendive, • Enclosure: Type 4X
considering faults, must be equal or greater than the • Temperature Class: T6
voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the • Ambient Temperature: –40 to 60°C
power (Po) which can be provided by the associated • Supply Voltage: 42 V dc max.
nonincendive field wiring apparatus (supply unit). In 32 V dc max. (FOUNDATION Fieldbus and
addition the maximum unprotected residual capacitance PROFIBUS PA type)
(Ci) and inductance (Li) of each apparatus (other than 9 to 28 V dc, 27 mW (Low Power type)
terminators) connected to the Fieldbus must be less than 9 to 30 V dc, 250 mW (RS485 Modbus
or equal to 5nF and 20uH respectively. Communication Type)
In each N.I. Fieldbus segment only one active source, • Output signal: 4 to 20 mA
normally the associated nonincendive field wiring 15 mA (FOUNDATION Fieldbus and PROFIBUS PA
apparatus, is allowed to provide the necessary power for type)
the Fieldbus system. The allowed voltage (Uo, Voc or 1 to 5 V (Low Power type)
Vt) of the associated nonincendive field wiring apparatus RS485 Modbus (RS485 Modbus Communication
used to supply the bus cable must be limited to the range Type)
IM 01C25A01-01E
<2. Handling Cautions> 14
Note 2. Wiring Note 2. In order to avoid confusion, unnecessary
• All wiring shall comply with National Electrical marking is crossed out on the label other
Code ANSI/NFPA70 and Local Electrical Codes. than the selected type of protection when the
• When installed in Division 1, “FACTORY SEALED, transmitter is installed.
CONDUIT SEAL NOT REQUIRED.”
• Wiring connection for output signal code Q (Low
2.4.2 CSA Certification
Power type) shall follow the diagram below.
a. CSA Intrinsically Safe for HART/BRAIN
Pressure Transmitters
Protocol Type (Except for EJX90A)
SUPPLY +
Voltmeter Caution for CSA Intrinsically safe and nonincendive
A Power Supply type. (Following contents refer to “DOC No. ICS013-
+ + A13”)
– – Note 1. EJX/EJA-E Series pressure transmitters with
SUPPLY – optional code /CS1 are applicable for use in
hazardous locations.
Three-Wire Connection Certificate: 1606623
Pressure Transmitters [For CSA C22.2]
SUPPLY + • Applicable Standard: C22.2 No.0, C22.2 No.0.4,
Voltmeter C22.2 No.25, C22.2 No.94, C22.2 No.157,
A Power Supply C22.2 No.213, C22.2 No.60079-0,
+ +
C22.2 No.61010-1 , C22.2 No.61010-2-030
– – • Intrinsically Safe for Class I, Division 1, Groups
A, B, C & D, Class II, Division 1, Groups E, F & G,
SUPPLY – Class III, Division 1
Four-Wire Connection • Nonincendive for Class I, Division 2, Groups A, B,
F0218.ai
C & D, Class II, Division 2, Groups F & G, Class III,
Division 1
Note 3. Operation
• Enclosure: Type 4X
• Keep the “WARNING” nameplate attached to the
• Temp. Code: T4
transmitter.
• Amb. Temp.: –50* to 60°C
WARNING: OPEN CIRCUIT BEFORE * –15°C when /HE is specified.
REMOVING COVER. FACTORY SEALED, • Process Temperature: 120°C max.
CONDUIT SEAL NOT REQUIRED. INSTALL IN [For CSA E60079]
ACCORDANCE WITH THE USERS MANUAL IM • Applicable Standard: CAN/CSA E60079-11,
01C25. CAN/CSA E60079-15, IEC 60529:2001
• Take care not to generate mechanical sparking • Ex ia IIC T4, Ex nL IIC T4
when accessing to the instrument and peripheral • Ambient Temperature: –50 to 60°C
devices in a hazardous location. • Max. Process Temp.: 120°C
Note 4. Maintenance and Repair • Enclosure: IP66/IP67
• The instrument modification or parts replacement Note 2. Entity Parameters
by other than authorized representative of • Intrinsically safe ratings are as follows:
Yokogawa Electric Corporation is prohibited and Maximum Input Voltage (Vmax/Ui) = 30 V
will void Factory Mutual Explosionproof Approval. Maximum Input Current (Imax/Ii) = 200 mA
e. FM Intrinsically Safe and Explosion Proof Maximum Input Power (Pmax/Pi) = 0.9 W
Combination for HART/BRAIN Protocol Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
Type
• Type "n" or Nonincendive ratings are as follows:
EJX/EJA-E Series pressure transmitters with Maximum Input Voltage (Vmax/Ui) = 30 V
optional code /FU1 or /V1U1 can be selected the Maximum Internal Capacitance (Ci) = 10 nF
type of protection (FM Intrinsically Safe or FM Maximum Internal Inductance (Li) = 0 µH
Explosionproof) for use in hazardous locations. • Installation Requirements
Note 1. For the installation of this transmitter, once a Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
particular type of protection is selected, any Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
other type of protection cannot be used. The Voc ≤ Vmax, Isc ≤ Imax,
installation must be in accordance with the Ca ≥ Ci + Ccable, La ≥ Li + Lcable
description about the type of protection in this Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
instruction manual. parameters of barrier.
IM 01C25A01-01E
<2. Handling Cautions> 15
Note 3. Installation • CSA Intrinsically Safe Approval
• In any safety barreir used output current must Class I, Division 1, Groups A, B, C, & D; Class II,
be limited by a resistor 'R' such that Io=Uo/R or Division 1, Groups E, F & G; Class III; Ex ia IIC T4
Isc=Voc/R. Ambient Temperature: –40* to 60°C (–40* to
• The safety barrier must be CSA certified. 140°F) Encl. Type 4X, IP66/IP67
• Input voltage of the safety barrier must be less * –15°C when /HE is specified.
than 250 Vrms/Vdc. • CSA Nonincendive Approval
• Installation should be in accordance with Canadian Class I, Division 2, Groups A, B, C, & D; Class II,
Electrical Code Part I and Local Electrical Code. Division 2, Groups F & G; Class III; Ex nL IIC T4
• Dust-tight conduit seal must be used when Ambient Temperature: –40* to 60°C (–40* to
installed in Class II and III environments. 140°F) Encl. Type 4X, IP66/ IP67
* –15°C when /HE is specified.
• The instrument modification or parts replacement
by other than authorized representative of Caution for CSA Intrinsically Safe Type.
Yokogawa Electric Corporation and Yokogawa (Following Contents Refer to “DOC. No.
Corporation of America is prohibited and will ICS018)
void Canadian Standards Intrinsically safe and
nonincendive Certification. Installation Diagram for Intrinsically Safe
(Division 1 Installation)
[Intrinsically Safe]
Hazardous Location Nonhazardous Location Terminator
Group IIC, Zone 0 2
Class I, II, III, Division 1, +
General Pressure
Groups A, B, C, D, E, F, G –
Handling Cautions
Purpose Transmitter
Pressure Transmitters Safety Barrier Equipment
+ + + + +
– Field Instruments
Supply – – – –
+
F0206.ai – Field Instruments
[Nonincendive]
Hazardous Location Nonhazardous Location Hazardous Location
IM 01C25A01-01E
<2. Handling Cautions> 16
• Rating 2 (FISCO) Note 2. Dust-tight conduit seal must be used when
For Groups A, B, C, D, E, F, and G or Group IIC installed in class II and III environments.
Ui (vmax) = 17.5 V dc
Note 3. Do not alter drawing without authorization from
Ii (Imax) = 380 mA
CSA.
Pi (Pmax) = 5.32 W
Ci = 3.52 nF Electrical Data:
Li = 0 μH
• Rating (including FNICO)
or
Ui or Vmax = 32 V
• Rating 3 (FISCO)
Ci = 3.52 nF
For Groups C, D, E, F, and G or Group IIB
Li = 0 μH
Ui (vmax) = 17.5 V dc
Ii (Imax) = 460 mA c. CSA Explosionproof Type
Pi (Pmax) = 5.32 W
Caution for CSA explosionproof type.
Ci = 3.52 nF
Li = 0 μH Note 1. EJX/EJA-E Series pressure transmitters with
Installation requirements; optional code /CF1 or /V1F are applicable for
Po ≤ Pi Uo ≤ Ui Io ≤ Ii, use in hazardous locations.
Co ≥ Ci + Ccable Lo ≥ Li + Lcable • Certificate: 2014354
Vmax ≥ Voc Imax ≥ Isc • Applicable Standard: C22.2 No.0,
Ca ≥ Ci + Ccable La ≥ Li + Lcable C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are parameters C22.2 No.30, C22.2 No.94, C22.2 No.61010-1,
of barrier. C22.2 No.61010-2-030, C22.2 No.60079-0,
C22.2 No.60079-1
Caution for CSA Non-incendive Type.
• Explosion-proof for Class I, Groups B, C and D.
(Following contents refer to “DOC. No. • Dustignition-proof for Class II/III, Groups E, F and
ICS018) G.
Installation Diagram for Non-incendive or Type of • Enclosure: Type 4X
protection “n” (Division 2 Installation) • Temperature Code: T6...T4
• Ex d IIC T6...T4
Terminator • Enclosure: IP66/IP67
• Maximum Process Temperature: 120°C (T4),
+
–
SUPPLY 100°C (T5), 85°C (T6)
Pressure • Ambient Temperature: –50* to 75°C (T4),
Transmitter
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specified.
+
Transmitter • Supply Voltage: 42 V dc max.
–
32 V dc max. (FOUNDATION Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
+
–
Transmitter 9 to 30 V dc, 250 mW (RS485 Modbus
Communication Type)
• Output Signal: 4 to 20 mA dc
Hazardous location
15 mA (FOUNDATION Fieldbus and PROFIBUS PA
Non-Hazardous location type)
Terminator 1 to 5 V (Low Power type)
RS485 Modbus (RS485 Modbus Communication
Type)
+ –
CSA Certified Note 2. Wiring
Equipment [nL]
+ – • All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
F0230.ai • In hazardous location, wiring shall be in conduit as
shown in the figure.
Note 1. Installation should be in accordance with • WARNING:
Canadian Electrical Code Part I and local A SEAL SHALL BE INSTALLED WITHIN 50cm OF
Electrical Code. THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
IM 01C25A01-01E
<2. Handling Cautions> 17
• WARNING: Note 3. Operation
WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT • WARNING:
REQUIRED. AFTER DE-ENERGIZING, DELAY 5 MINUTES
UNE FOIS INSTALLÉ DANS CL I, DIV 2, AUCUN BEFORE OPENING.
JOINT N'EST REQUIS. APRÉS POWER-OFF, ATTENDRE 5 MINUTES
Non-Hazardous Hazardous Locations Division 1 AVANT D'OUVRIR.
Locations • WARNING:
Non-hazardous WHEN AMBIENT TEMPERATURE ≥ 65°C, USE
Location Equipment 50 cm Max.
THE HEAT-RESISTING CABLES ≥ 90°C.
QUAND LA TEMPÉRATURE AMBIANTE ≥ 65°C,
UTILISEZ DES CÂBLES RÉSISTANTES Á LA
42 V DC Max. Conduit CHALEUR ≥ 90°C.
4 to 20 mA DC Sealing Fitting
Signal • Take care not to generate mechanical sparking
Transmitter
when accessing to the instrument and peripheral
F0208.ai
devices in a hazardous location.
Non-Hazardous Hazardous Locations Division 2
Locations Note 4. Maintenance and Repair
Non-hazardous • The instrument modification or parts replacement
Location Equipment by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void 2
42 V DC Max. Canadian Standards Explosionproof Certification.
4 to 20 mA DC Sealing Fitting
Handling Cautions
Signal d. CSA Intrinsically Safe and Explosion-proof
Transmitter
F0209.ai Combination for HART/BRAIN Protocol
Type (Except for EJX90A)
• All wiring shall comply with local installation
requirements and local electrical code. EJX/EJA-E Series pressure transmitters with
• In hazardous locations, the cable entry devices optional code /CU1 or /V1U1 can be selected the
shall be of a certified flameproof type, suitable for type of protection (CSA Intrinsically Safe or CSA
the conditions of use and correctly installed. Explosionproof) for use in hazardous locations.
• Unused apertures shall be closed with suitable Note 1. For the installation of this transmitter, once a
flameproof certified blanking elements. (The plug particular type of protection is selected, any
attached is flameproof certified.) other type of protection cannot be used. The
• Wiring connection for output signal code Q (Low installation must be in accordance with the
Power type) shall follow the diagram below. description about the type of protection in this
Pressure Transmitters instruction manual.
IM 01C25A01-01E
<2. Handling Cautions> 18
• Type of Protection and Marking code:
Ex ia IIC T4 Ga WARNING
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
• Group: II • In the case where the enclosure of the Pressure
• Category: 1G, 2D Transmitter is made of aluminium, if it is mounted
• Ambient Temperature for EPL Ga: in an area where the use of category 1 G
–50 to 60°C apparatus is required, it must be installed such,
• Ambient Temperature for EPL Db: that, even in the event of rare incidents, ignition
–30* to 60°C sources due to impact and friction sparks are
* –15°C when /HE is specified.
excluded.
• Process Temperature (Tp.): 120°C max. • Electrostatic charge may cause an exlosion
• Maximum Surface Temperature for EPL Db: hazard. Avoid any actions that cause the
T85°C (Tp.: 80°C) generation of electrostatic charge, such as rubbing
T100°C (Tp.: 100°C) with a dry cloth on coating face of the product.
T120°C (Tp.: 120°C) • In case of the enclosure of the Pressure
• Enclosure: IP66 / IP67 Transmitter with paint layers, if it is mounted in an
Note 2 Electrical Data area where the use of category 2D apparatus is
• In type of explosion protection intrinsic safety Ex ia required, it shall be installed in such a way that the
IIC or Ex ia IIIC, only for connection to a certified risk from electrostatic discharges and propagating
intrinsically safe circuit with following maximum brush discharges caused by rapid flow of dust is
values: avoided.
Ui = 30 V • To satisfy IP66 or IP67, apply waterproof glands to
Ii = 200 mA the electrical connection port.
Pi = 0.9 W • When the lightning protector option is specified,
(Linear Source) the apparatus is not capable of withstanding the
Maximum internal capacitance; Ci = 27.6 nF 500V insulation test required by EN60079-11. This
Maximum internal inductance; Li = 0 µH must be taken into account when installing the
apparatus.
Note 3. Installation
• Refer to the control drawing. All wiring shall comply
with local installation requirements. b. ATEX Intrinsically Safe for HART Protocol
[Control Drawing] Type for EJX90A
Hazardous Location Nonhazardous Location Caution for ATEX Intrinsically safe type.
Pressure Transmitters
Note 1. EJX multivariable transmitter with optional
+ + code /KS2 are applicable for use in hazardous
Supply Safety Barrier *1
– – locations.
• No. KEMA 06ATEX 0037X
• Applicable Standard:
EN 50014:1997, EN 50020:2002,
EN 50284:1999, EN 50281-1-1:1998
F0210.ai
*1: In any safety barriers used the output current must be • Type of Protection and Marking code:
limited by a resistor “R” such that Io=Uz/R. EEx ia IIC T4
• Group: II
Note 4. Maintenance and Repair • Category: 1G, 1D
• The instrument modification or parts replacement • Ambient Temperature for gas-proof:
by other than authorized representative of –50* to 60°C
Yokogawa Electric Corporation is prohibited and * –15°C when /HE is specified.
will void DEKRA Intrinsically safe Certification. • Process Temperature (Tp.): 120°C max.
• Maximum Surface Temperature for dust-proof:
Note 5. Special Conditions for Safe Use T85°C (Tamb.: –40* to 60°C, Tp.: 80°C)
T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)
* –15°C when /HE is specified.
• Enclosure: IP66 and IP67
IM 01C25A01-01E
<2. Handling Cautions> 19
Note 2. Electrical Data [Installation Diagram] (for EJX910A and EJX930A)
[Supply/Output circuit (terminals + and -)]
● Without pulse output
In type of explosion protection intrinsic safety EEx
ia IIC, only for connection to a certified intrinsically Hazardous Location Nonhazardous Location
safe circuit with following maximum values:
Ui = 30 V Pressure Transmitters
Ii = 200 mA + +
Supply Safety Barrier*1
Pi = 0.9 W
– –
Effective internal capacitance; Ci = 10 nF
Sensor out
Effective internal inductance; Li = 0 mH
RTD sensor
[Pulse Output circuit (terminals - and pulse)] *2
In type of explosion protection intrinsic safety EEx
ia IIC, only for connection to a certified intrinsically
safe circuit with following maximum values: ● With pulse output
Ui = 30 V
Hazardous Location Nonhazardous Location
Ii = 200 mA
Pi = 0.9 W Pressure Transmitters
Ci = 10 nF +
Safety Barrier*1
Li = 0 mH + –
[External temperature input circuit (connector)] Supply
– 2
In type of explosion protection intrinsic safety EEx
Pulse
ia IIC, with following maximum values:
Handling Cautions
+
Uo = 30 V +
Sensor out
Io = 95.4 mA Safety Barrier*1
Po= 468 mW RTD sensor –
*2
Co = 11 nF
Lo= 3.9 mH
Note 3. Installation F0211.ai
IM 01C25A01-01E
<2. Handling Cautions> 20
c. ATEX Intrinsically Safe for Fieldbus Type
(Except for EJX90A) WARNING
Caution for ATEX Intrinsically safe type.
• In the case where the enclosure of the Pressure
Note 1. EJX/EJA-E series pressure transmitters with Transmitter is made of aluminium, if it is mounted
optional code /KS26 are applicable for use in in an area where the use of category 1 G
hazardous locations. apparatus is required, it must be installed such,
• No. KEMA 04ATEX1116 X that even in the event of rare incidents, ignition
• Applicable Standard: EN 60079-0:2009, sources due to impact and friction sparks are
EN 60079-11:2007/EN 60079-11:2012, excluded.
EN 60079-26:2007, EN 60079-27:2008, • Electrostatic charge may cause an explosion
EN 61241-11:2006 hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing
Note 2. Ratings
with a dry cloth on coating face of the product.
Type of Protection and Marking Code:
• In the case where the enclosure of the Pressure
Ex ia IIC/IIB T4 Ga
Transmitter is made of aluminum, if it is mounted in
Ex ia IIIC T85°C T100°C T120°C Db
an area where the use of category 2D apparatus is
Group: II
required, it shall be installed in such a way that the
Category: 1G, 2D
risk from electrostatic discharges and propagating
Ambient Temperature for EPL Ga: –40 to 60°C
brush discharges caused by rapid flow of dust is
Ambient Temperature for EPL Db: –30* to 60°C
* –15°C when /HE is specified. avoided.
Maximum Process Temperature (Tp.): 120°C • To satisfy IP66 or IP67, apply waterproof glands to
Maximum Surface Temperature for EPL Db. the electrical connection port.
T85°C (Tp.: 80°C) • When the lightning protector option is specified,
T100°C (Tp.: 100°C) the apparatus is not capable of withstanding the
T120°C (Tp.: 120°C) 500V insulation test required by EN60079-11.
Ambient Humidity: This must be taken into account when installing
0 to 100% (No condensation) the apparatus.
Degree of Protection of the Enclosure:
IP66 / IP67
Electrical Data Note 6. Installation Instructions
• When combined with Trapezoidal and Rectangular [Installation Diagram]
output characteristic FISCO model IIC barrier
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W, Terminator
Ci = 3.52 nF, Li = 0 μH
• When combined with Linear characteristic barrier + Pressure
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W, − SUPPLY Transmitter
Ci = 3.52 nF, Li = 0 μH
• When combined with Trapezoidal or Rectangular +
− Transmitter
output characteristic FISCO model IIB barrier
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
Ci = 3.52 nF, Li = 0 μH + Transmitter
−
Note 3. Installation
• All wiring shall comply with local installation Hazardous Location
requirements. (Refer to the installation diagram)
Non-Hazardous Location
Note 4. Maintenance and Repair Terminator
• The instrument modification or parts replacement
+ −
by other than authorized representative of
Safety Barrier
Yokogawa Electric Corporation is prohibited and + − F0231.ai
will void DEKRA Intrinsically safe Certification.
Note 5. Special Conditions for Safe Use
IM 01C25A01-01E
<2. Handling Cautions> 21
• In the rating 1(*1), the output current of the barrier Ambient Temperature for EPL Ga:
must be limited by a resistor ‘Ra’ such that Io = Uo/ –40 to 60°C
Ra. Ambient Temperature for EPL Db:
• In the rating 2(*2), the output of the barrier must be –30* to 60°C
the characteristics of the trapezoid or the rectangle * –15°C when /HE is specified.
and this transmitter can be connected to Fieldbus Maximum Process Temperature (Tp.): 120°C
equipment which are in according to the FISCO Maximum Surface Temperature for EPL Db.
model. T85°C (Tp.: 80°C)
• The terminators may be built in by a barrier. T100°C (Tp.: 100°C)
• More than one transmitter may be connected to T120°C (Tp.: 120°C)
the power supply line. Ambient Humidity:
• The terminator and the safety barrier shall be 0 to 100% (No condensation)
certified. Degree of Protection of the Enclosure:
Electrical data: IP66/IP67
Maximum Input Voltage Ui: 24 V Electrical Data
• When combined with Trapezoidal or Rectanglar
Maximum Input Current Ii: 250 mA
*1: output characteristic FISCO model IIC barrier
Maximum Input Power Pi: 1.2 W
Rating 1 [Supply circuit (terminals + and -)]
Maximum Internal Capacitance Ci: 3.52 nF
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,
Maximum Internal Inductance Li: 0 μH
Ci = 3.52 nF, Li = 0 µH
or
[Sensor circuit]
2
Maximum Input Voltage Ui: 17.5 V
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Handling Cautions
Maximum Input Current Ii: 380 mA
Co = 4.8 µF, Lo = 100 mH
Maximum Input Power Pi: 5.32 W
• When combined with Linear characteristic barrier
Maximum Internal Capacitance Ci: 3.52 nF
[Supply circuit (terminals + and -)]
Maximum Internal Inductance Li: 0 μH
*2: Ui = 24 V, Ii = 250 mA, Pi = 1.2 W,
or
Rating 2 Ci = 3.52 nF, Li = 0 µH
Maximum Input Voltage Ui: 17.5 V
[Sensor circuit]
Maximum Input Current Ii: 460 mA
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Maximum Input Power Pi: 5.32 W
Co = 4.8 µF, Lo = 100 mH
Maximum Internal Capacitance Ci: 3.52 nF • When combined with Trapezoidal or Rectanglar
Maximum Internal Inductance Li: 0 μH output characteristic FISCO model IIB barrier
[Supply circuit (terminals + and -)]
d. ATEX Intrinsically Safe for Fieldbus Type Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
for EJX90A Ci = 3.52 nF, Li = 0 µH
[Sensor circuit]
Caution for ATEX Intrinsically safe type. Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W,
Note 1. EJX multivariable transmitter with optional Co = 4.8 µF, Lo = 100 mH
code /KS26 are applicable for use in hazardous Note 3. Installation
locations: • All wiring shall comply with local installation
• No. KEMA 06ATEX0278 X requirements. (Refer to the installation diagram)
• Applicable Standard: EN 60079-0:2009,
EN 60079-11:2012, EN 60079-26:2007 Note 4. Maintenance and Repair
• The instrument modification or parts replacement
Note 2. Ratings by other than authorized representative of
Type of Protection and Marking Code: Yokogawa Electric Corporation is prohibited and
Ex ia IIC/IIB T4 Ga will void DEKRA Intrinsically safe Certification.
Ex ia IIIC T85°C T100°C T120°C Db
Group: II Note 5. Special Conditions for Safe Use
Category: 1G, 2D
IM 01C25A01-01E
<2. Handling Cautions> 22
• The terminators may be built in by a barrier.
WARNING • More than one transmitter may be connected to
the power supply line.
• In the case where the enclosure of the Pressure • The terminator and the safety barrier shall be
Transmitter is made of aluminium, if it is mounted certified.
in an area where the use of category 1G apparatus Electrical data:
is required, it must be installed such, that even in Supply circuit
the event of rare incidents, ignition sources due to Maximum Input Voltage Ui: 24 V
impact and friction sparks are excluded. Maximum Input Current Ii: 250 mA
*1:
• Electrostatic charge may cause an explosion Maximum Input Power Pi: 1.2 W
Rating 1
hazard. Avoid any actions that cause the Maximum Internal Capacitance Ci: 3.52 nF
generation of electrostatic charge, such as rubbing Maximum Internal Inductance Li: 0 μH
with a dry cloth on coating face of the product. or
• In the case where the enclosure of the Pressure Maximum Input Voltage Ui: 17.5 V
Transmitter is made of aluminum, if it is mounted in Maximum Input Current Ii: 380 mA
an area where the use of category 2D apparatus is Maximum Input Power Pi: 5.32 W
required, it shall be installed in such a way that the Maximum Internal Capacitance Ci: 3.52 nF
risk from electrostatic discharges and propagating Maximum Internal Inductance Li: 0 μH
brush discharges caused by rapid flow of dust is *2:
or
avoided. Rating 2
Maximum Input Voltage Ui: 17.5 V
• To satisfy IP66 or IP67, apply waterproof glands to Maximum Input Current Ii: 460 mA
the electrical connection port. Maximum Input Power Pi: 5.32 W
• When the lightning protector option is specified, Maximum Internal Capacitance Ci: 3.52 nF
the apparatus is not capable of withstanding the Maximum Internal Inductance Li: 0 μH
500V insulation test required by EN60079-11.
This must be taken into account when installing Sensor circuit
the apparatus.
Maximum Output Voltage Uo: 7.63 V
Maximum Output Current Io: 3.85 mA
Maximum Output Power Po: 0.008 W
Note 6. Installation instructions
Maximum Internal Capacitance Co: 4.8 μF
[Installation Diagram]
Maximum Internal Inductance Lo: 100 mH
IM 01C25A01-01E
<2. Handling Cautions> 23
• Maximum Surface Temperature for dust-proof:
T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specified.
WARNING
Note 2. Electrical Data • Electrostatic charge may cause an explosion
• Supply voltage: 42 V dc max. hazard. Avoid any actions that cause the
32 V dc max. (FOUNDATION Fieldbus and generation of electrostatic charge, such as rubbing
PROFIBUS PA type) with a dry cloth on coating face of the product.
9 to 28 V dc, 27 mW (Low Power type) • In the case where the enclosure of the Pressure
9 to 30 V dc, 250 mW (RS485 Modbus Transmitter is made of aluminium, if it is mounted
Communication Type) in an area where the use of category 2D apparatus
• Output signal: 4 to 20 mA is required, it shall be installed in such a way
15 mA (FOUNDATION Fieldbus and PROFIBUS PA that the risk from electrostatic discharges and
type) propagating brush discharges caused by rapid
1 to 5 V (Low Power type) flow of dust is avoided.
RS485 Modbus (RS485 Modbus Communication • The instrument modification or parts replacement
Type) by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
Note 3. Installation
will void the certification.
• All wiring shall comply with local installation
requirement.
• Cable glands, adapters and/or blanking elements
2
f. ATEX Intrinsically Safe and ATEX
with a suitable IP rating shall be of Ex d IIC/Ex tb
Flameproof Combination for HART/BRAIN
Handling Cautions
IIIC certified by ATEX and shall be installed so as
Protocol Type (Except for EJX90A)
to maintain the specific degree of protection (IP
Code) of the equipment. EJX/EJA-E Series pressure transmitters with optional
• Wiring connection for output signal code Q (Low code /KU22 or /V1U1 can be selected the type of
Power type) shall follow the diagram below. protection ATEX Flameproof, Intrinsically Safe. Ex ia,
Pressure Transmitters or Ex ic for use in hazardous area.
SUPPLY + Note 1. For the installation of this transmitter, once a
Voltmeter particular type of protection is selected, any
A Power Supply
other type of protection cannot be used. The
+ +
installation must be in accordance with the
– – description about the type of protection in this
user’s manual.
SUPPLY –
Note 2. For combined approval types
Three-Wire Connection
Once a device of multiple approval type is
Pressure Transmitters
installed, it should not be re-installed using any
SUPPLY + other approval types. Apply a permanent mark
Voltmeter in the check box of the selected approval type
A Power Supply
+ +
on the certification label on the transmitter to
distinguish it from unused approval types.
– –
ATEX Intrinsically Safe Ex ic
SUPPLY –
Caution for ATEX intrinsically safe Ex ic
Four-Wire Connection • Applicable Standard:
F0220.ai
EN 60079-0:2009/EN 60079-0:2012,
Note 4. Operation EN 60079-11:2012
• Keep the “WARNING” label attached to the • Type of Protection and Marking Code:
transmitter. II 3G Ex ic IIC T4 Gc
WARNING: AFTER DE-ENERGIZING, DELAY • Ambient Temperature: –30* to +60°C
* –15°C when /HE is specified.
5 MINUTES BEFORE OPENING. WHEN THE
AMBIENT TEMP.≥65°C, USE HEAT-RESISTING • Ambient Humidity:
CABLE AND CABLE GLAND ≥90°C. 0 to 100% (No condensation)
• Take care not to generate mechanical sparking • Maximum Process Temperature: 120°C
when accessing to the instrument and peripheral • IP Code: IP66
devices in a hazardous location. • Ambient pollution degree: 2
• Overvoltage category: I
Note 5. Special Conditions for Safe Use
IM 01C25A01-01E
<2. Handling Cautions> 24
Note 1. Electrical Data • Maximum Process Temperature: 120°C
Ui = 30 V • Ambient Humidity:
Ci = 27.6 nF 0 to 100% (No condensation)
Li = 0 µH • IP Code: IP66
• Ambient pollution degree: 2
Note 2. Installation
• Overvoltage category: I
• All wiring shall comply with local installation
requirements. (refer to the control drawing) Note 1. Electrical Data
• Cable glands, adapters and/or blanking elements Ui = 32 V
shall be of Ex “n”, Ex “e” or Ex “d” and shall be Ci = 3.52 nF
installed so as to maintain the specified degree of Li = 0 µH
protection (IP Code) of the transmitters.
Note 2. Installation
Note 3. Maintenance and Repair • All wiring shall comply with local installation
• The instrument modification or parts replacement requirements. (refer to the control drawing)
by other than authorized representative of • When installing the transmitter in “ic” FISCO
Yokogawa Electric Corporation is prohibited and system or FNICO system, follow the installation
will void ATEX intrinsically safe. requirements of each system.
[Control Drawing] • Cable glands, adapters and/or blanking elements
shall be of Ex “n”, Ex “e” or Ex “d” and shall be
Hazardous Area Nonhazardous Area
installed so as to maintain the specified degree of
protection (IP Code) of the transmitters.
Pressure +
Associated
Transmitters Apparatus
Note 3. Maintenance and Repair
– • The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
F0212.ai will void ATEX intrinsically safe.
[Control Drawing]
Note 4. Specific Conditions of Use
Hazardous Area Nonhazardous Area
WARNING Transmitter
+
Associated
– Apparatus
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product. F0233.ai
• When the lightning protector option is specified, • Above drawing shows the installation of Entity
the apparatus is not capable of withstanding the system.
500V insulation test required by EN60079-11. This When installing the transmitters in “ic” FISCO
must be taken into account when installing the system or FNICO system, follow the installation
apparatus. requirements of each system.
Note 4. Specific Conditions of Use
g. ATEX Intrinsically Safe Ex ic for Fieldbus
Type (Except for EJX90A) WARNING
Caution for ATEX Intrinsically safe Ex ic.
• Electrostatic charge may cause an explosion
EJX/EJA-E Series pressure transmitters with optional
hazard. Avoid any actions that cause the
code /KN26 are applicable for use in hazardous
gerenation of eletrostatic charge, such as rubbing
locations.
with a dry cloth on coating face of the product.
• Applicable Standard:
• When the lightning protector option is specified,
EN 60079-0:2009/EN 60079-0:2012,
the apparatus is not capable of withstanding the
EN 60079-11:2012
500V insulation test required by EN60079-11. This
• Type of Protection and Marking Code:
must be taken into account when installing the
II 3G Ex ic IIC T4 Gc
apparatus.
• Ambient Temperature: –30* to +60°C
* –15°C when /HE is specified.
IM 01C25A01-01E
<2. Handling Cautions> 25
(2) Electrical Connection (6) Name Plate
A mark indicating the electrical connection type is Name plate
stamped near the electrical connection port. These
marks are as followed.
Screw Size Marking
ISO M20 × 1.5 female M
ANSI 1/2 NPT female N or W Tag plate for flameproof type
No. KEMA 07ATEX0109 X
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Enlcosure : IP66/IP67
TEMP. CLASS T6 T5 T4
MAX PROCESS TEMP.(Tp.) 85 100 120 °C
Tamb. -50 to 75 80 75 °C
T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)
*3 D
WARNING
Location of the mark
Handling Cautions
Ex ia IIC T4 Ga Ta: -50 TO 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
• All wiring shall comply with local installation IP66/IP67
MAX. PROCESS TEMP.(Tp.) 120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
requirements and the local electrical code. Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
WARNING
MAX. PROCESS TEMP. 120°C
Ui=30V, Ci=27.6nF, Li=0µH
when access to the instrument and peripheral Tag plate for intrinsically safe Ex ia for Fieldbus
devices in a hazardous location. No. KEMA 04ATEX1116 X
Ex ia IIC/IIB T4 Ga Ta:-40 to 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) to 60°C
MAX PROCESS TEMP.(Tp.):120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Enclosure: IP66/IP67
FISCO field device(IIC/IIB)
(5) Maintenance and Repair Entity parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0μH
*3 D
WARNING WARNING
The instrument modification or parts replacement by POTENTIAL ELECTROSTATIC CHARGING HAZARD - SEE USER'S MANUAL.
other than an authorized Representative of Yokogawa Tag plate for intrinsically safe Ex ic for Fieldbus
Electric Corporation is prohibited and will void the Ex ic IIC T4 Gc
IP66
certification. Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=32V, Ci=3.52nF, Li=0µH
WARNING
F0215-2.ai
IM 01C25A01-01E
<2. Handling Cautions> 26
[EJX90A] Note 1. For the installation of this transmitter, once a
Tag plate for intrinsically safe for HART/BRAIN particular type of protection is selected, any
No. KEMA 06ATEX0037 X
EEx ia IIC T4
other type of protection cannot be used. The
IP66 and IP67
Tamb. -50(-15) to 60°C MIN Tamb.for DUST -40(-15°C)
MAX PROCESS TEMP.(Tp) 120°C
installation must be in accordance with the
description about the type of protection in this
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Supply/Pulse circuit
Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=10 nF, Li=0 mH
Sensor circuit
Uo=30 V, Io=95.4 mA, Po=468 mW, Co=11 nF, Lo=3.9 mH
instruction manual.
*3 D Note 2. For combined approval types, once a device of
multiple approval type is installed, it should not
be re-installed using any other approval types.
Tag plate for intrinsically safe Ex ia for Fieldbus
No. KEMA 06ATEX0278 X
Apply a permanent mark in the check box of the
Ex ia IIC/IIB T4 Ga Ta: -40 to 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°C
MAX PROCESS TEMP.(Tp.): 120°C selected approval type on the certification label
T85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C)
ENCLOSURE: IP66/IP67
Supply circuit on the transmitter to distinguish it from unused
FISCO field device(IIC/IIB)
Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH
Sensor circuit approval types.
Uo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH
IM 01C25A01-01E
<2. Handling Cautions> 27
Note 4. Specific Condition of Use [Ex ic]
Hazardous Location Nonhazardous Location
WARNING
EJX/EJA-E Series Associated apparatus
• Electrostatic charge may cause an explosion Pressure Transmitters
hazard. Avoid any actions that cause the + +
generation of electrostatic charge, such as rubbing Supply
– –
with a dry cloth on coating face of the product.
• In the case where the enclosure of the pressure
F0237.ai
transmitter is made of aluminum, if it is mounted
in an area where the use of EPL Ga equipment is Note 4. Specific Condition of Use
required, it shall be installed in such a way that ,
even in the event of rare incidents, ignition sources
WARNING
due to impact and friction sparks are excluded.
• When the lightning protector option is specified, • Electrostatic charge may cause an explosion
the apparatus is not capable of withstanding the hazard. Avoid any actions that cause the
500 V insulation test required by IEC 60079-11. generation of electrostatic charge, such as rubbing
This must be taken into account when installing with a dry cloth on coating face of the product.
the apparatus. • The apparatus is not capable of dielectric strength
tests required by IEC 60079-11. 2
This must be taken into account when installing
b. IECEx Intrinsically Safe Ex ic for HART/
Handling Cautions
the apparatus.
BRAIN Protocol Type (Except for EJX90A)
Caution for IECEx Intrinsically safe Ex ic.
c. IECEx Intrinsically Safe Ex ia for Fieldbus
Note 1. EJX/EJA-E series pressure transmitters with Type (Except for EJX90A)
optional code /SU21 are applicable for use in
hazardous locations Caution for IECEx Intrinsically safe Ex ia.
• No. IECEx DEK 13.0061X Note 1. EJX/EJA-E Series pressure transmitters with
• Applicable Standard: IEC 60079-0:2011, optional code /SS26 are applicable for use in
IEC 60079-11:2011 hazardous locations.
• Ex ic IIC T4 Gc • No. IECEx DEK 12.0016X
• Ambient Temperature: –30* to 60°C • Applicable Standard: IEC 60079-0:2011,
* -15 °C when /HE is specified.
IEC 60079-11:2011, IEC 60079-26: 2006
• Max. Process Temp.: 120°C
• Ex ia IIC/IIB T4 Ga
• IP Code: IP66
• Ambient Temperature: –40 to 60°C
• Overvoltage Category: I
• Max. Process Temp.: 120°C
Note 2. Electrical Data
Note 2. Electrical Data
Maximum Input Voltage (Ui) = 30 V
• Intrinsically safe ratings are as follows:
Maximum Internal Capacitance (Ci) = 27.6 nF
[Entity]
Maximum Internal Inductance (Li) = 0 μH
Maximum Input Voltage (Ui) = 24 V
Note 3. Installation Maximum Input Current (Ii) = 250 mA
• The pressure transmitter is allowed to be installed Maximum Input Power (Pi) = 1.2 W
in “nL” systems, on condition that the output Maximum Internal Capacitance (Ci) = 3.52 nF
parameters of “nL” source (associated energy- Maximum Internal Inductance (Li) = 0 μH
limited apparatus) are suitable to the above [FISCO IIC]
mentioned input parameters of the pressure Maximum Input Voltage (Ui) = 17.5 V
transmitter and the cable parameters. Maximum Input Current (Ii) = 380 mA
• Cable glands, adapters and/or blanking elements Maximum Input Power (Pi) = 5.32 W
shall be of Ex “n”, Ex “e” or Ex “d” and shall be Maximum Internal Capacitance (Ci) = 3.52 nF
installed so as to maintain the specified degree of Maximum Internal Inductance (Li) = 0 μH
protection of the equipment. [FISCO IIB]
• The instrument modification or parts replacement Maximum Input Voltage (Ui) = 17.5 V
by other than authorized representative of Maximum Input Current (Ii) = 460 mA
Yokogawa Electric Corporation is prohibited and Maximum Input Power (Pi) = 5.32 W
will void IECEx certification. Maximum Internal Capacitance (Ci) = 3.52 nF
Maximum Internal Inductance (Li) = 0 μH
IM 01C25A01-01E
<2. Handling Cautions> 28
Note 3. Installation Note 4. Specific Condition of Use
[Ex ia]
WARNING
Terminator
• Electrostatic charge may cause an explosion
+ Pressure
hazard. Avoid any actions that cause the
– Transmitter generation of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product.
+ • In the case where the enclosure of the pressure
– Field Instruments
transmitter is made of aluminum, if it is mounted
in an area where the use of EPL Ga equipment is
+ required, it shall be installed in such a way that ,
– Field Instruments
even in the event of rare incidents, ignition sources
due to impact and friction sparks are excluded.
Hazardous Location
• When the lightning protector option is specified,
Non-Hazardous Location the apparatus is not capable of withstanding the
Terminator
500 V insulation test required by IEC 60079-11.
–
This must be taken into account when installing
+
Safety Barrier the apparatus.
+ – F0238.ai
• In the rating 1(*1), the output current of the barrier d. IECEx Intrinsically Safe Ex ic for Fieldbus
must be limited by a resistor ‘Ra’ such that Io = Uo/ Type (Except for EJX90A)
Ra. Caution for IECEx Intrinsically safe Ex ic.
• In the rating 2(*2), the output of the barrier must be
the characteristics of the trapezoid or the rectangle Note 1. EJX/EJA-E Series pressure transmitters with
and this transmitter can be connected to Fieldbus optional code /SS26 are applicable for use in
equipment which are in according to the FISCO hazardous locations.
model. • No. IECEx DEK 13.0064X
• The terminators may be built in by a barrier. • Applicable Standard: IEC 60079-0:2011,
• More than one transmitter may be connected to IEC 60079-11:2011
the power supply line. • Ex ic IIC T4 Gc
• The terminator and the safety barrier shall be • Ambient Temperature: –30* to 60°C
* -15 °C when /HE is specified.
certified.
• Max. Process Temp.: 120°C
Electrical data:
• IP Code: IP66
Maximum Input Voltage Ui: 24 V • Overvoltage Category: I
Maximum Input Current Ii: 250 mA
*1: Note 2. Electrical Data
Maximum Input Power Pi: 1.2 W
Rating 1 • Intrinsically safe ratings are as follows:
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH Maximum Input Voltage (Ui) = 32 V
or Maximum Internal Capacitance (Ci) = 3.52 nF
Maximum Input Voltage Ui: 17.5 V Maximum Internal Inductance (Li) = 0 μH
Maximum Input Current Ii: 380 mA Note 3. Installation
Maximum Input Power Pi: 5.32 W • The instrument modification or parts replacement
Maximum Internal Capacitance Ci: 3.52 nF by other than authorized representative of
Maximum Internal Inductance Li: 0 μH Yokogawa Electric Corporation and will void IECEx
*2:
or Intrinsically safe and type n certification.
Rating 2
Maximum Input Voltage Ui: 17.5 V • The pressure transmitter is allowed to be installed
Maximum Input Current Ii: 460 mA in “nL” systems, on condition that the output
Maximum Input Power Pi: 5.32 W parameters of “nL” source (associated energy-
Maximum Internal Capacitance Ci: 3.52 nF limited apparatus) are suitable to the above
Maximum Internal Inductance Li: 0 μH mentioned input parameters of the pressure
transmitter and the cable parameters.
IM 01C25A01-01E
<2. Handling Cautions> 29
• When installing the transmitter in “ic” FISCO Note 2. Electrical Data
system or FNICO system, follow the installation • Intrinsically safe ratings are as follows:
requirements of each system. Maximum Input Voltage (Vmax/Ui) = 30 V
• Cable glands, adapters and/or blanking elements Maximum Input Current (Imax/Ii) = 200 mA
shall be of Ex “n”, Ex “e” or Ex “d” and shall be Maximum Input Power (Pmax/Pi) = 0.9 W
installed so as to maintain the specified degree of Maximum Internal Capacitance (Ci) = 10 nF
protection of the equipment. Maximum Internal Inductance (Li) = 0 µH
• For multiple types of protection, the selected Ex • Type "n" ratings are as follows:
marking on the marking plate shall be checked at Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Internal Capacitance (Ci) = 10 nF
the time of installation.
Maximum Internal Inductance (Li) = 0 µH
[Ex ic]
• Installation Requirements
Hazardous Location Nonhazardous Location Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
EJX/EJA-E Series Associated apparatus
Pressure Transmitters Voc ≤ Vmax, Isc ≤ Imax,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
+ + Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
Supply
– – parameters of barrier.
Note 3. Installation
F0237.ai
• In any safety barrier used output current must be
• Above drawing shows the installation of entity limited by a resistor 'R' such that Io=Uo/R.
2
system. When installing the transmitter in “ic” • The safety barrier must be IECEx certified.
Handling Cautions
FISCO system or FNICO system, follow the • Input voltage of the safety barrier must be less
installation requirements of each system. than 250 Vrms/Vdc.
• The instrument modification or parts replacement
Note 4. Specific Condition of Use by other than authorized representative of
Yokogawa Electric Corporation and will void IECEx
WARNING Intrinsically safe and type n certification.
[type n]
e. IECEx Intrinsically Safe / type n for HART/ Hazardous Location Nonhazardous Location
BRAIN Protocol Type (Except for EJX9A) Group IIC, Zone 2
Caution for IECEx Intrinsically safe and type n. EJX Series Pressure IECEx Certified
Transmitters Equipment [nL]
Note 1. EJX Series differential, gauge, and absolute + +
pressure transmitters with optional code /SU2
Supply – –
are applicable for use in hazardous locations
Not Use
• No. IECEx CSA 05.0005 Safety Barrier
• Applicable Standard: IEC 60079-0:2000, F0217.ai
IEC 60079-11:1999, IEC 60079-15:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50 to 60°C
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
IM 01C25A01-01E
<2. Handling Cautions> 30
f. IECEx Intrinsically Safe / type n for Fieldbus [Intrinsically safe]
Type (Except for EJX90A)
Terminator
Caution for IECEx Intrinsically safe and type n.
Note 1. EJX/EJA-E Series pressure transmitters with + Pressure
optional code /SS25 are applicable for use in – Transmitter
hazardous locations.
• No. IECEx CSA 05.0012 +
– Field Instruments
• Applicable Standard:
IEC 60079-0:2000, IEC 60079-11:1999,
IEC 60079-15:2001 +
• Ex ia IIC/IIB T4, Ex nL IIC T4 – Field Instruments
• Ambient Temperature: –40* to 60°C
* –15°C when /HE is specified. Hazardous Location
• Max. Process Temp.: 120°C Non-Hazardous Location
• Enclosure: IP66 and IP67 Terminator
IM 01C25A01-01E
<2. Handling Cautions> 31
• Ambient Temperature: –50 to 75°C (T4), Note 4. Maintenance and Repair
–50 to 80°C (T5), –50 to 75°C (T6) • The instrument modification or parts replacement
• Supply Voltage: 42 V dc max. by other than authorized representative of
32 V dc max. (FOUNDATION Fieldbus and Yokogawa Electric Corporation is prohibited and
PROFIBUS PA type) will void IECEx Certification.
9 to 28 V dc, 27 mW (Low Power type) • Electrical Connection
9 to 30 V dc, 250 mW (RS485 Modbus A mark indicating the electrical connection type is
Communication Type) stamped near the electrical connection port. These
• Output Signal: 4 to 20 mA dc marks are as followed.
15 mA (FOUNDATION Fieldbus and PROFIBUS PA
Screw Size Marking
type)
1 to 5 V (Low Power type) ISO M20 × 1.5 female M
RS485 Modbus (RS485 Modbus Communication ANSI 1/2 NPT female N or W
Type)
Note 2. Wiring
• In hazardous locations, the cable entry devices
shall be of a certified flameproof type, suitable for
the conditions of use and correctly installed.
Location of the mark
• Unused apertures shall be closed with suitable
flameproof certified blanking elements. 2
F0222.ai
• Wiring connection for output signal code Q (Low
Handling Cautions
Power type) shall follow the diagram below.
Pressure Transmitters
2.5 EMC Conformity Standards
SUPPLY +
Voltmeter EN 61326-1 Class A, Table 2 (for use in industrial
A Power Supply locations)
+ + EN 61326-2-3
– –
EN 61326-2-5 (for Fieldbus)
SUPPLY –
CAUTION
Three-Wire Connection
Pressure Transmitters To meet EMC regulations, Yokogawa recommends
that customers run signal wiring through metal
SUPPLY +
Voltmeter conduits or use shielded twisted-pair cabling when
A Power Supply installing EJX/EJA-E Series transmitters in a plant.
+ +
– –
(1) General
Note 3. Operation
• WARNING: • EJX/EJA-E Series pressure transmitters are
AFTER DE-ENERGIZING, DELAY 5 MINUTES categorized as piping under the pressure accessories
BEFORE OPENING. section of directive 97/23/EC, which corresponds to
• WARNING: Article 3, Paragraph 3 of PED, denoted as Sound
WHEN THE AMBIENT TEMP.≥65°C, USE HEAT- Engineering Practice (SEP).
RESISTING CABLE AND CABLE GLAND ≥90°C. • EJX110A-MS, EJX110A-HS,
• Take care not to generate mechanical sparking EJX110A-VS, EJA110E with /HG, EJ130,
when accessing to the instrument and peripheral EJ440, EJ510-D, EJ530-D,
devices in a hazardous location. EJX610A-D, and EJX630A-D can be used above
• Electrostatic charge may cause an explosion 200 bar and therefore considered as a part of a
hazard. Avoid any actions that cause the pressure retaining vessel where category III, Module
generation of electrostatic charge, such as rubbing H applies. These models with option code /PE3
with a dry cloth on coating face of the product. conform to that category.
IM 01C25A01-01E
<2. Handling Cautions> 32
(2) Technical Data *1: PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 97/23/EC. Refer to
• Models without /PE3 General Specification for maximum working pressure of a
transmitter.
Article 3, Paragraph 3 of PED, denoted as Sound
*2: Referred to Table 1 covered by ANNEX II of EC Directive
Engineering Practice (SEP). on Pressure Equipment Directive 97/23/EC
• Models with /PE3
Module: H (3) Operation
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas CAUTION
Group of fluid: 1 and 2
• The temperature and pressure of fluid should
Capsule PS*1 PS.V
Model
code (bar)
V(L)
(bar.L)
Category*2 be maintained at levels that are consistent with
normal operating conditions.
EJA110E M, H, V
160 0.01 1.6 • The ambient temperature should be maintained
EJ110 F, L at a level that is consistent with normal operating
Article 3,
EJX110A Paragraph 3 conditions.
(SEP) • Please take care to prevent water hammer and the
EJA110E M, H, V 250 0.01 2.5
with code like from inducing excessive pressures in pipes
/HG and valves. If phenomena are likely, install a safety
EJ110 valve or take some other appropriate measure to
with code / M, H, V 250 0.01 2.5 III
prevent pressure from exceeding PS.
PE3
Article 3,
• Take appropriate measures at the device or
EJ130 M, H 500 0.01 5.0 Paragraph 3 system level to protect transmitters if they are to be
(SEP) operated near an external heat source.
EJ130
with code / M, H 500 0.01 5.0 III
PE3
Article 3, 2.7 Safety Requirement
EJ310 L, M, A, B 160 0.01 1.6 Paragraph 3
(SEP) Standards
Article 3,
EJ430 H, A, B 160 0.01 1.6 Paragraph 3 Applicable standard: EN 61010-1, EN 61010-2-30,
(SEP) C22.2 No.61010-1, C22.2 No.61010-2-030
Article 3,
EJ440 C, D 500 0.1 5.0 Paragraph 3 (1) Pollution Degree 2
(SEP)
EJ440 "Pollution degree" describes the degree to which
with code / C, D 500 0.1 5.0 III a solid, liquid, or gas which deteriorates dielectric
PE3
strength or surface resistivity is adhering. " 2 " applies
A, B, C 100 0.1 10 Article 3,
EJ510 to normal indoor atmosphere. Normally, only non-
Paragraph 3
EJX610A D 700 0.1 70 conductive pollution occurs. Occasionally, however,
(SEP)
EJ510, temporary conductivity caused by condensation must
EJX610A be expected.
D 700 0.1 70 III
with code /
PE3 (2) Installation Category I
A, B, C 100 0.1 10 Article 3,
EJ530, "Overvoltage category(Installation category)"
Paragraph 3
EJX630A D 700 0.1 70 describes a number which defines a transient
(SEP)
EJ530, overvoltage condition. It implies the regulation for
EJX630A
D 700 0.1 70 III
impulse withstand voltage. " I " applies to electrical
with code / equipment which is supplied from the circuit when
PE3
appropriate transient overvoltage control means
L 160 0.01 1.6 Article 3,
EJX910A Paragraph 3
(interfaces) are provided.
M, H 250 0.01 2.5 (SEP)
(3) Altitude of installation site:
EJX910A
with code / M, H 250 0.01 2.5 III Max. 2,000 m above sea level
PE3
Article 3, (4) Indoor/Outdoor use
EJX930A M, H 500 0.01 5.0 Paragraph 3
(SEP)
EJX930A
with code / M, H 500 0.01 5.0 III
PE3
IM 01C25A01-01E
<3. Installation> 33
3. Installation
Vertical pipe mounting Vertical pipe mounting
IMPORTANT (Process connector upside) (Process connector downside)
Installation
F00301.ai
IM 01C25A01-01E
<3. Installation> 34
3.2.1 EJ210 3.3 Diaphragm Seals Installation
The transmitter is mounted on a process using its Consideration
high pressure side flange as shown in Figure 3.5. The
customer should prepare the mating flange, gasket, stud IMPORTANT
bolts and nuts.
• When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
Gasket level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.7).
• Correctly install the diaphragm seals on the high
and low pressure sides of the process, checking
the label on each seal.
• To avoid measuring error duets temperature
Stud bolt
difference between the two diaphragm seals,
Nut F0305.ai capillary tube must be bound together. The
Figure 3.5 EJ210 Mounting capillary tube must be securely fixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
3.2.2 EJ118 and EJ438 extra tube portion (coil diameter of 300 mm or
Mount the diaphragm seals using the flanges as shown in more) and secure the coiled tube with a clamp.
Figure 3.6. The mating flange, gasket, bolts and nuts are
to be procured by the customer. Low
Flange
IMPORTANT pressure
Nut side
Bolt Diaphragm Install the sealed diaphragm
so that the shank positions
downward.
ød Minimum
High liquid level
Gasket
pressure
The product is side 50 mm minimum
shipped with these Correctly install the diaphragm
parts assembled. seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW). F0306.ai The transmitter should
be installed as low as
Figure 3.6 Mounting the Diaphragm Seals
possible below the
position where the high
pressure side
diaphragm seal is
installed.
F0307.ai
IM 01C25A01-01E
<3. Installation> 35
(P–P0) (–)
h= × 0.102 [mm]
ds
h≤0: Install the transmitter at least h (mm) below the Figure 3.8 Example of Installation to Tank
HP process connection (Caution on Installation)
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
3.4 Mounting the Flushing
P0: Minimum working pressure limit of the transmitter (Pa
abs) See below table. Connection Ring
[For fill fluid code A, B, C, D, E]
Wetted parts Process connection size 3.4.1 Mounting to Pressure Detector 3
Capillary
material
length
code Section
code 2, 8 3 4,W
Installation
1 to 5m 6790 3190 The flushing connection ring is mounted to the pressure
SW
6 to 10m 10030 3520 detector section as shown in Figure 3.9.
1 to 5m 6790 3190 At the factory shipment, the flushing connection ring is
SE
6 to 10m 10030 3520
1 to 5m 3190 already assembled and attached to process detector
SY section.
6 to 10m 3520
1 to 5m 19150 6140
HW Pressure-detector section
6 to 10m 8290
1 to 5m 9620 3620
TW
6 to 10m 4210
1 to 5m 9540 4750 Ring
UW
6 to 10m 6050
[For fill fluid code 1, 2, 4]
Wetted parts Process connection size Spiral gasket
Capillary
material code
length Groove for
code 2, 8 3 4,W installing Ring holder
1 to 5m 2570 320 spiral gasket
SW
6 to 10m 4680 530
1 to 5m 2570 320 View from pressure Vent/Drain plug
SE detector section
6 to 10m 4680 530
1 to 5m 320 F0309.ai
SY
6 to 10m 530 Figure 3.9 Mounting to Pressure Detector Section
1 to 5m 10220 2050
HW
6 to 10m 3450
1 to 5m 4270 570 (1) Mount the ring holder on the ring and loosely tighten
TW
6 to 10m 960 the mounting screws.
ds: Specific gravity of fill fluid (at 25°C). See below table. (2) Place the spiral gasket in the ring groove. With the
ring correctly aligned and flush with the face of the
Fill fluid
A, 1, 4 B C, 2 D E pressure detector, securely tighten each ring holder’s
code
ds: Specific 1.90 to mounting screws.
1.07 0.94 1.09 1.09 (3) Position the ring so that the vent/drain plugs are
gravity 1.92
aligned straight up and down.
IM 01C25A01-01E
<3. Installation> 36
3.4.2 Mounting to Process Flange 3.5 Affixing the Teflon Film
Tighten the bolts to completely close the gap between the
ring and the pressure detector section. IMPORTANT
The mating flange, gasket, stud bolts and nuts are to
procured by the customer. The FEP Teflon option includes a teflon film and
fluorinated oil. Before mounting the transmitter to the
process flange, affix the teflon film as follows:
F0310.ai
Teflon film
Figure 3.10 Mounting to Process Flange PART No.
EJ210 F9347YD
2 inch EJ118
F9347YA
IMPORTANT EJ438
3 inch F9347XA
Fluorinated oil
• Confirm that there is no gap between the ring [PART No. : F9145YN]
and the process-detector section after they are Diaphragm
mounted on the process flange. A gap can lead to
a sudden, explosive release of process fluids. Gasket area
• When mounting or removing the ring, take care not F0311.ai
to tilt the pressure detector downward as the ring Figure 3.11 Affixing the Teflon Film
can slip off and cause injury.
• When re-mounting the ring, use the new spiral
gasket as shown in below table.
IM 01C25A01-01E
<3. Installation> 37
3.6 Rotating Transmitter Section 3.7 Changing the Direction of
The transmitter section can be rotated approximately Integral Indicator
360° (180° to either direction or 360° to one direction
from the original position at shipment, depending on the IMPORTANT
configuration of the instrument.) It can be fixed at any
angle within above range. Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area before
1) Remove the two setscrews that fasten the transmitter
disassembling and reassmbling an indicator.
section and capsule assembly, using the Allen
wrench.
An integral indicator can be installed in the following
2) Rotate the transmitter section slowly and stop it at
three directions.
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than the
F0313.ai
above limit.
Figure 3.13 Integral Indicator Direction
Vertical impulse piping type
IMPORTANT
Pressure-detector section 3
Stopper
The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on ATEX flameproof type
Installation
Rotate 0 to ±180° segments
transmitters. When the shrouding bolt is driven
clockwise by an Allen wrench, it is going in and cover
lock is released, and then the cover can be opened.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding bolt
Conduit connection to a torque of 0.7 N·m.
Integral 90°
Pressure-detector section indicator 90°
F0312.ai
Amplifier cover
F0314.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 38
57 mm 54 mm 51 mm
F0402.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 39
1) Screw nipples into the connection ports on the 4.1.2 Routing the Impulse Piping
transmitter side of the 3-valve manifold, and into
the impulse piping connecting ports on the process (1) Process Pressure Tap Angles
connectors. (To maintain proper sealing, wind sealing
tape around the nipple threads.) If condensate, gas, sediment or other extraneous
2) Mount the 3-valve manifold on the 50 mm (2-inch) material in the process piping gets into the impulse
pipe by fastening a U-bolt to its mounting bracket. piping, pressure measurement errors may result. To
Tighten the U-bolt nuts only lightly at this time. prevent such problems, the process pressure taps must
3) Install the pipe assemblies between the 3-valve be angled as shown in Figure 4.5 according to the kind of
manifold and the process connectors and lightly fluid being measured.
tighten the ball head lock nuts. (The ball-shaped ends
of the pipes must be handled carefully, since they will NOTE
not seal properly if the ball surface is scratched or
otherwise damaged.) • If the process fluid is a gas, the taps must be
4) Now tighten the nuts and bolts securely in the vertical or within 45° either side of vertical.
following sequence: • If the process fluid is a liquid, the taps must be
Process connector bolts → transmitter-end ball head horizontal or below horizontal, but not more than
lock nuts → 3-valve manifold ball head lock nuts → 45° below horizontal.
3-valve manifold mounting bracket U-bolt nuts • If the process fluid is steam or other condensing
vapor, the taps must be horizontal or above
Direct-Mounting Type 3-Valve Manifold horizontal, but not more than 45° above horizontal.
[Gas] [Liquid] [Steam]
1) Mount the 3-valve manifold on the transmitter. (When
Pressure 45° 45°
mounting, use the two gaskets and the four bolts
taps
provided with the 3-valve manifold. Tighten the bolts 45° 45°
evenly.)
2) Mount the process connectors and gaskets on the top
Process
piping
45° 45° 4
of the 3-valve manifold (the side on which the impulse F0405.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 40
(4) Temperature Difference Between Impulse 4.2 Impulse Piping Connection
Piping (for differential pressure
transmitters)
Examples
Figure 4.6, 4.7, and 4.8 shows examples of typical
If there is a temperature difference between the high
impulse piping connections. Before connecting the
and low impulse lines, the density difference of the fluids
transmitter to the process, study the transmitter
in the two lines will cause an error in the measurement
installation location, the process piping layout, and
pressure. When measuring flow, impulse lines must be
the characteristics of the process fluid (corrosiveness,
routed together so that there is no temperature difference
toxicity, flammability, etc.), in order to make appropriate
between them.
changes and additions to the connection configurations.
(5) Condensate Pots for Steam Flow
Note the following points when referring to these piping
Measurement (for differential pressure examples.
transmitters)
• If the impulse line is long, bracing or supports should
If the liquid in the impulse piping repeatedly condenses be provided to prevent vibration.
or vaporizes as a result of changes in the ambient or • The impulse piping material used must be compatible
process temperature, this will cause a difference in the with the process pressure, temperature, and other
fluid head between the high pressure and low pressure conditions.
sides. To prevent measurement errors due to these head • A variety of process pressure tap valves (main valves)
differences, condensate pots are used when measuring are available according to the type of connection
steam flow. (flanged, screwed, welded), construction (globe, gate,
(6) Preventing Wind Speed Effects in Very Low or ball valve), temperature and pressure. Select the
Differential Pressure Measurement type of valve most appropriate for the application.
(for differential pressure transmitters)
Liguid Gas Steam
Drain plug
Pipe (opened to atmosphere
at low pressure side) F0407.ai
IM 01C25A01-01E
<4. Installing Impulse Piping> 42
• A variety of process piping-mounted stop valves are
available according to the type of connection (flanged,
screwed, welded), construction (globe, gate, or ball
valve), temperature and pressure.
Select the type of valve most appropriate for the
application.
Stop valve
Manifold
Process piping
Union or flange
Stop valve
Process piping
F0410.ai
IM 01C25A01-01E
<5. Wiring> 43
5. Wiring
5.2 Connections of External
NOTE
Wiring to Terminal Box
For FOUNDATION Fieldbus, PROFIBUS PA, and Mod
bus communication types, please refer to each ● Terminal Configuration
communication manual.
RTD cable connection*
IMPORTANT
Terminal 4 [B]*
• Lay wiring as far as possible from electrical noise
sources such as large capacity transformers,
motors, and power supplies. Terminal 1 Terminal 3 [A]
• Remove electrical connection dust cap before Terminal 2
wiring.
• All threaded parts must be treated with *For EJX9A only. F0527.ai
Wiring
protected features. *1: When using an external indicator or check meter, the
internal resistance must be 10 Ω or less. A check meter
• The terminal box cover is locked by an Allen head
or indicator cannot be connected when /AL option is
bolt (a shrouding bolt) on ATEX flameproof type specified.
transmitters. When the shrouding bolt is driven *2: Not available for FOUNDATION Fieldbus and PROFIBUS
clockwise using an Allen wrench, it gose in. The PA communication types.
cover lock can then be released and the cover can
be opened by hand. ● Terminal Wiring for 1 to 5 V output
When a cover is closed it should be locked by a SUPPLY +
1
Power supply terminals
– 2
shrouding bolt without fail. Tighten the shrouding + 3 1 to 5 V DC with HART communication
VOUT –
bolt to a torque of 0.7 N·m. 2 terminals
Ground terminal
SUPPLY +
1
– Power supply and output terminals
2
Figure 5.1 Shrouding Bolt
CHECK +
3
External indicator (ammeter) terminals *1*2
– 2
Ground terminal
*1: When using an external indicator or check meter, the
internal resistance must be 10Ω or less.
*2: Not available for FOUNDATION Fieldbus communication
type.
F0528.ai
IM 01C25A01-01E
<5. Wiring> 44
5.2.1 Power Supply Wiring Connection 5.2.3 Status Output Connection
When option code /AL is specified, connect the external
IMPORTANT wiring as shown in Figure 5.7.
To configure and activate the process alarm function and
Connecting with the commercial AC power supply
status output, it is necessary to set some parameters.
will damage the device. Be sure to use the DC power
Refer to each communication manual for procedures.
supply in the predetermined range.
Transmitter
24V DC
terminal box Shielded cable
Connect the power supply wiring to the SUPPLY + and – +
Distributor
terminals. – 250Ω
■ 1 to 5 V output, HART
Connect the HART communicator or configuration tool to
the SUPPLY - and VOUT (+) terminals. (Use hooks.)
PC/FieldMate F0532.ai
IM 01C25A01-01E
<5. Wiring> 45
5.2.4 Connection Example for EJX910A and EJX930A
Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART protocol type)
Connection Description
Analog Output Transmitter Electrical Terminal
Distributor
In this case, + 24V DC
Communication is SUPPLY +
possible (up to a distance – 250Ω
of 2km when a CEV cable –
is used.) PULSE B* * Either B or +
Pulse Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
Shielded Cable
In this case,
No communication is SUPPLY + E
possible.
–
* *1
PULSE B *2 R Electric counter
* Either B or +
When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to
Simultaneous example 1 to 3.
Analog Distributor (or communication medium : ex. EP card) 5
For the shielded cables in this example of
-Pulse Output *3 Shielded Cable
24V DC
flowmeter installation, use two-wire separately
Example 1 SUPPLY +
Wiring
shielded cables.
In this case, Communica – *2 R 250Ω
-tion is possible(up to a * E(10.5 to 30V DC) This supply voltage requires a power sourse
distance of 2km when a
PULSE B Counting input with a maximum output current of no less than
CEV cable is used). * Either B or + Common E/R.
Electric counter *1 (or communication medium : ex. EP card)
Transmitter Electrical Terminal
For the shielded cables in this
Example 2 Recorder or
example of flowmeter installation,
In this case, Communica Shielded Cable other instrument
use two-wire separately shielded
-tion is possible (up to a 250Ω cables.
distance of 200m when a
SUPPLY + *2
E(16.4 to 30V DC)
This supply voltage requires a power
CEV cable is used) and R
= 1kΩ). – R
Counting input sourse with a maximum output current
PULSE * of no less than E/R+25mA.
B Common
The supply voltage requires output
* Either B or +
Electric counter *1 impedance no more than 1/1000 of R
Transmitter Electrical Terminal (load resistance).
Recorder or
other instrument
Example 3 250Ω
In this case, No communi
-cation is possible (when SUPPLY + E(16.4 to 30V DC) This supply voltage requires
R*2 a power sourse with a
shielded cable is not used). – Counting input maximum output current of
* no less than E/R+25mA.
PULSE B Common
* Either B or + Electric counter *1
Transmitter Electrical Terminal
IM 01C25A01-01E
<5. Wiring> 46
5.2.5 External Temperature Connection • Pulse output and Alarm, Status Output or
(for EJX910A and EJX930A) Simultaneous Analog-Pulse Output
Connect the RTD cable assembly to the Juck Terminal. (for EJX910A and EJX930A)
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
F0505.ai
instrument
Figure 5.8 External Temperature Connection
5.3 Wiring
Receiver
5.3.1 Loop Configuration instrument
F0506.ai
(3) Intrinsically Safe Type (for EJX910A and
Figure 5.9 Connection between Transmitter and EJX930A)
Distributor
• Analog Output
Hazardous Location Nonhazardous Location
Power
supply
Anaolg input
F0509.ai
IM 01C25A01-01E
<5. Wiring> 47
• Simultaneous Analog-Pulse Output • Four wire connection
Fasten the negative side wiring of both power supply
Hazardous Location Nonhazardous Location
and signal line to the SUPPLY - terminal.
Transmitter terminal box I/O module Hazardous Location Nonhazardous Location
Safety barrier
(Isolated type)
Transmitter terminal box
Distributor
Power (Power supply unit)
supply
Analog input
Power
supply
Receiver
Pulse input instrument
Safety barrier
(Isolated type)
F0510.ai F0530.ai
Figure 5.12 Connection between Transmitter, Figure 5.14 Connection between Transmitter,
barrier and receiver Distributor and Receiver
Wiring
In either three-wire or four-wire connection, metal conduit for waterproofing.
recommended wiring distance is 200 m or less, and
the use of shielded cable is recommended.
Receiver
instrument
F0529.ai
IM 01C25A01-01E
<5. Wiring> 48
(2) Flameproof Type • RTD connection components: EJX multivariable
transmitter, two cable glands, and RTD cable.
Wire cables through a flameproof packing adapter, or use
Two cable glands are attached.
a flameproof metal conduit.
Electrical connection
Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box Cable gland
connection port and to the threads on the flameproof
packing adapter for waterproofing. RTD cable
with connector
Drain plug
F0512.ai
IM 01C25A01-01E
<5. Wiring> 49
Procedure (7) Rotate the running coupler another half turn to
securely tighten the seal on the RTD cable.
(1) Disassemble the cable gland: loosen the running
coupler to separate the backnut from the entry. (8) Use a protection conduit, if necessary.
(2) Remove the protection cap over the transmitter In this case, insert the cable through the conduit and
electrical connection and install the entry on the attach it to the Backnut.
electrical connection. Note that a non-hardening
sealant should be applied to the threads for a 1/2 NPT CAUTION
connection and a gasket should be used for an M20
connection. After the cable is secured as explained above, do not
tighten the running coupler any further; to do so could
damage the RTD connection.
Do not pull the cable or subject it to excessive
mechanical shock.
F0518.ai
(4) Insert the RTD cable and firmly plug its connector into
the connecting port in the transmitter's terminal box.
F0522.ai 5
Procedure
Wiring
(1) Remove the protection cap protecting the RTD
electrical connection and insert the RTD cable.
F0519.ai
F0523.ai
CAUTION
Do not pull the cable or subject it to excessive
mechanical shock.
F0521.ai
IM 01C25A01-01E
<5. Wiring> 50
5.4.3 Cable Connection RTD Terminal Box 5.5 Grounding
Side
Grounding is always required for the proper operation of
EJX multivariable transmitter RTD I/F is for 3-wire Type transmitters. Follow the domestic electrical requirements
RTD, Pt100. as regulated in each country. For a transmitter with a
Heed the following when wiring an RTD of the 2- or 4-wire built-in lightning protector, grounding should satisfy
type. ground resistance of 10Ω or less.
Ground terminal
(inside)
CAUTION
Ground terminal
Please use only the cables provided with this (outside)
instrument.
When wiring, be sure not to damage the cable's
insulation or its core. F0525.ai
All the cable cores must have sufficient insulation Figure 5.19 Ground Terminals
around them.
Do not let the signal line contact the shield line.
Do not allow the shield line or the signal line to come 5.6 Power Supply Voltage and
the earth potential voltage.
Load Resistance
2-Wire 3-Wire 4-Wire For 4 to 20 mA output only.
When configuring the loop, make sure that the external
load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
A B A B b Aa B b 600
F0524.ai
RTD Terminal A a B b
250
2-Wire White - Blue1 and Blue2 -
3-Wire White - Blue1 Blue2
4-Wire White open Blue1 Blue2
IM 01C25A01-01E
<6. Operation> 51
6. Operation
NOTE Burnout direction switch
Burnout Direction H L H L
6.1 Preparation for Starting Switch Position
Self-diagnostic error
on the integral indicator
(Faulty transmitter) 6.2 Zero Point Adjustment
After completing preparations for operating the
F0601.ai
transmitter, adjust the zero point.
Verify and Change Transmitter Zero point adjustment can be done by turning the 6
transmitter’s zero-adjustment screw or by using the
Parameter Setting and Values
communicator. This section describes the procedure
Operation
The parameters related to the following items are set at for the zero-adjustment screw. For the zero-adjustment
factory as specified in order. via communication, procedure, please refer to each
• Calibration range communication manual.
• Integral indicator display
• Output mode IMPORTANT
• Software damping (optional)
Other parameters like following are shipped with the Do not turn off the power to the transmitter
default setting. immediately after performing a zero point adjustment.
• Low-cut Powering off within 30 seconds of performing this
• Process alarm setting procedure will return the zero point to its previous
• Static pressure range setting.
• Signal characterizer
• Write protection
To confirm or change the values, please refer to each 6.2.1 Adjusting Zero Point for Differential
communication manual. Pressure Transmitters
Before adjusting zero point, make sure that the equalizing
Output Status Setting at CPU Failure and valve is open.
Hardware Write Protection
Set the switches as shown in the figure below to set the
burn-out direction and write protection. The Burnout
switch is set to the H side for delivery (unless option code
/C1 or /C2 is specified in the order), and the hardware Zero-adjustment screw cover
write protection switch is set to E side except EJX910A F0603.ai
and EJX930A. The setting of the switches can be Figure 6.2 External Zero Adjustment Screw
confirmed via communication.
IM 01C25A01-01E
<6. Operation> 52
The zero-adjustment screw is located inside the cover. 6.3 Local Parameter Setting
Use a slotted screwdriver to turn the zero-adjustment
screw. Equalize the transmitter, then turn the screw
clockwise to increase the output or counterclockwise to WARNING
decrease the output. The zero point adjustment can be
made with a resolution of 0.01% of the setting range. The The local push button on the integral indicator must
degree of zero adjustments varies with the screw turning not be used in a hazardous area. When it is necessary
speed; turn the screw slowly to make a fine adjustment, to use the push button, operate it in a non- hazardous
quickly to make a rough adjustment. location.
Adjust the transmitter output to the actual measured Figure 6.3 External Adjustment Screw
value obtained by a digital manometer or a glass gauge.
Integral indicator
[Example]
The measuring range of 50 to 250 kPa; the actual
measured value of 130 kPa.
130–50
Actual measured value= x100=40.0% Push-button
250–50 F0605.ai
(=10.4mA)
Figure 6.4 Range –Setting Switch (push button)
Turn the screw to match the output signal to the actual
measured value.
IM 01C25A01-01E
<6. Operation> 53
screw
Process
Measurement Zero adjustment
Display push
Activate LPS mode
push
*
1. Tag Number Select Tag number Save/Cancel the value
*
2. Press Unit Edit Press unit Save/Cancel the value
push *
3. Press LRV Edit Press LRV Save/Cancel the value
*
4. Press URV Edit Press URV Save/Cancel the value
push *
5. Damping Time Edit Damping time Save/Cancel the value
*
6. Output Mode Select Output mode Save/Cancel the value
push *
7. Display Out1 Edit Display Out1 Save/Cancel the value
push
9. URV-Apply Press Set URV Save/Cancel the value
Operation
Process
Measurement
Display F0606.ai
*: Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART
parameter “Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.
Figure 6.5
IM 01C25A01-01E
<7. Errors and Countermeasures> 54
The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.
IM 01C25A01-01E
<7. Errors and Countermeasures> 55
Table 7.2 Alarm Message Summary (For EJX910A and EJX930A, HART protocol type)
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 01 Sensor problem. Outputs the signal (High or Low) set Replace capsule if the error recurs
CAP.ERR with burnout direction switch. after the transmitter is restarted.
Capsule temperature sensor problem. [status output: undefined] Replace capsule.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor problem. Replace amplifier.
AMP.ERR Amplifier EEPROM problem.
Amplifier problem.
A/D Converter problem.
AL. 03 External temperature sensor Check external temperature sensor.
ET.ERR disconnection.
— No device ID is found. Continues to operate and output. Replace amplifier.
AL. 10 Differential pressure is outside When PV is Pres Check input or replace capsule when
PRESS measurement range limit of capsule. Output AO upper limit or AO Lower necessary.
limit.
AL. 11 Static pressure exceeds limit. When PV is SP
ST. PRSS Output AO upper limit or AO Lower
limit.
AL. 12 Capsule temperature is outside range Continues to operate and output. Use heat insulation or make lagging
CAP.TMP (–50 to 130°C). to keep temperature within range.
AL. 13 Amplifier temperature is outside range
AMP.TMP (–50 to 95°C).
AL. 14 External temperature is outside range. When PV is ET
EXT. TMP Output AO upper limit or AO Lower
AL. 15 External temperature sensor resistance limit.
EXT. TMP is out specification.
AL. 16 PLS Pulse output is out specification. Continues to operate and output. Check settings and change them.
AL. 30 Differential pressure exceeds specified When PV is Pres. Check input and range setting, and
PRS.RNG range. Output AO upper limit or lower limit. change them as needed.
AL. 31 Static pressure exceeds specified When PV is SP
SP. RNG range. Output AO upper limit or lower limit.
AL. 32 Flow exceeds specified range. When PV is Flow
F. RNG Output AO upper limit or lower limit.
AL. 33 External temperature exceeds specified When PV is ET
ET. RNG range. Output AO upper limit or lower limit.
AL. 35 P.HI Input pressure exceeds specified Continues to operate and output. Check input.
AL. 36 P.LO threshold. 7
AL. 37 SP.HI Input static pressure exceeds specified
IM 01C25A01-01E
<7. Errors and Countermeasures> 56
Integral 4-20mA Output
Cause Countermeasure
indicator operation during error
AL. 79 Displayed value exceeds limit. Continues to operate and output. Check settings and change them as
OV. DISP needed.
AL.87 Flange temperature exceeds a preset It depends on the Diag Out Option Check the heater failure.
FLG. HI upper limit. setting.
AL.87 Flange temperature is below a preset Check the capsule temp. and
FLG. LO lower limit. Off: Continue to operate and output. Amplifier temp.
Burnout:Outputs AO upper limit or AO
lower limit. Adjust Flg Temp Coef.
Fall back:Outputs Diag Out Fixed Val.
AL.88 Differential pressure/pressure Continue to operate and output. Check process condition.
INVR.DP fluctuation does not reach the reference
level required to blockage detection so
that no blockage detection is carried
out.
AL.88 Low-pressure-side fluctuation does not
INVR.SL reach the reference fluctuation level
required to blockage detection.
AL.88 High-pressure-side fluctuation does not
INVR.SH reach the reference fluctuation level
required to blockage detection.
AL.88 BlkF can not be used for blockage
INVR.F detection for some reasons.
AL.89 Appointed the diagnosis range outside.
ILBD.OV
AL.89 B Blocking (both-side blockage) is It depends on the Diag Out Option Check process condition.
B BLK detected. setting.
AL.89 High-pressure-side blockage is
H BLK detected. Off: Continue to operate and output.
Burnout: Outputs AO upper limit or AO
AL.89 Low-pressure-side blockage is
lower limit.
L BLK detected.
Fall back: Outputs Diag Out Fixed Val.
AL.89 Pressure fluctuation amplitude of high-
H LRG pressure side is large.
AL.89 Pressure fluctuation amplitude of low-
L LRG pressure side is large.
AL.89 A Blocking (single-side blockage) is
A BLK detected.
AL. 90 SIM Under Simulation Mode for flow. Simulate input output. Check Simulation Mode.
AL. 91 F. SIM Under Simulation Mode for device Output the setting value of Simulate- Check Simulation Mode.
AL. 91 P. SIM variables. Value.
AL.91 SP. SIM
AL. 91
ET. SIM
AL. 91
TF. SIM
AL. 91
PCT. SIM
AL. 91
AO. SIM
IM 01C25A01-01E
57
Revision Information
Title : EJX and EJA-E Series
Differential Pressure and Pressure Transmitters Installation Manual
Manual No. : IM 01C25A01-01E
IM 01C25A01-01E
58
IM 01C25A01-01E
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Phone : 81-422-52-5555
Branch Sales Offices
Osaka, Nagoya, Hiroshima, Kurashiki, Fukuoka, Kitakyusyu
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111
Printed in Japan