Technical specifications
General
Power Supply 19 to 60 VDC
Power Consumption 5W
EMC EN 300 386, 2001 class B, FCC part 15 class B
Safety IEC 60950 -1, EN 60950 -1, UL 60950 -1
Approvals CE, UL
Operating Temperature -5°C ~ 40°C
Storage Temperature - 40°C to + 75°C/- 40°F to + 167°F
Relative Humidity 5%RH ~ 95%RH
Elevation ≤ 2000m (derating is necessary above 2000m)
Ethernet port Green: Operating
Yellow: Minor alarm
RS232 port Red: Major or critical alarm
Mechanical Data
LED Functional keys
Dimensions (W×D×H) 43×211.5×86.8mm
Weight <0.8kg M221S
M222S (without Ethernet)
Inputs/Outputs
M221S M222S M223S M224S
Display
LCD with 8X16 characters No display
Communication Interface RS232, Ethernet RS232 RS232, Ethernet RS232 Ethernet port Green: Operating
HTTP, SNMP √ √ Yellow: Minor alarm
Protocol RS232 port Red: Major or critical alarm
YDN23 √ √ √ √
1 battery currents, 1 bus voltage, 1 battery voltage, 2 temperatures, 4
Analog
midpoint battery voltage
2 load fuses, 4 battery fuses, 1 bi-stable contactor statues, 4 user M223S
Inputs M224S (without Ethernet)
inputs(Optional, need extra board)
Digital
load fuse and battery fuse can be configured as midpoint battery voltage,
load fuse and battery fuse
1 LVD mono or bistable contactors, 1 LVD mono contactor, 8 user relay
Outputs YDN23
outputs(Optional, need extra board)
Examples of Alarms
DC Power Plant Alarms AC mains failure, Rectifier failure, High voltage shutdown,Fan failure,
Thermal derating (of rectifier output due to high temperature)