Local Control Unit Plus DC Power

for Business-Critical Continuity™

(LCU+,M221S,M222S,M223S,M224S)

Next Generation Introduction


Controller Unit The next generation Local Control Unit (LCU+, M221S,M222S,M223S,M224S) is
a powerful control unit used in DC power applications. The LCU+ enables remote
monitoring of the telecom site's AC mains supply, DC power plant, battery
backup, site environment, etc.
The LCU+ enables advanced battery management such as sophisticated boost
charge control, remaining time prediction, constant current test, scheduled test
Features and Benefits and fast test. Furthermore, with basic energy saving function, the LCU+ is surely
 Flexible and scalable to satisfy your a cost-efficient product.
present and future needs
The information and alarms, from a specific site, can be monitored or checked
 Minimized installation time as a result
of easily configurable file upload/ by means of a simple web browser or special monitoring software. When using
download a web browser, no additional software is needed and the web browser login
 Sophisticated boost charge
monitor the site is password protected.
management gives long battery life-
Designed for global use, the LCU+ withstands high telecom standards, and
span
provides great reliability and availability.
 Automatic battery test including
advanced scheduled test / constant
test / fast test
 High quality failure information due to
intelligent alarm setup through using
PLC
 Lower operating cost due to energy
saving standby function for rectifier

Notes: PLC = Programmable Logic Controller

Next Generation Controller Unit M221S


Local Control Unit Plus DC Power
for Business-Critical Continuity™

Technical specifications
General
Power Supply 19 to 60 VDC
Power Consumption 5W
EMC EN 300 386, 2001 class B, FCC part 15 class B
Safety IEC 60950 -1, EN 60950 -1, UL 60950 -1
Approvals CE, UL
Operating Temperature -5°C ~ 40°C
Storage Temperature - 40°C to + 75°C/- 40°F to + 167°F
Relative Humidity 5%RH ~ 95%RH
Elevation ≤ 2000m (derating is necessary above 2000m)
Ethernet port Green: Operating
Yellow: Minor alarm
RS232 port Red: Major or critical alarm

Mechanical Data
LED Functional keys
Dimensions (W×D×H) 43×211.5×86.8mm
Weight <0.8kg M221S
M222S (without Ethernet)

Inputs/Outputs
M221S M222S M223S M224S
Display
LCD with 8X16 characters No display
Communication Interface RS232, Ethernet RS232 RS232, Ethernet RS232 Ethernet port Green: Operating
HTTP, SNMP √ √ Yellow: Minor alarm
Protocol RS232 port Red: Major or critical alarm
YDN23 √ √ √ √
1 battery currents, 1 bus voltage, 1 battery voltage, 2 temperatures, 4
Analog
midpoint battery voltage
2 load fuses, 4 battery fuses, 1 bi-stable contactor statues, 4 user M223S
Inputs M224S (without Ethernet)
inputs(Optional, need extra board)
Digital
load fuse and battery fuse can be configured as midpoint battery voltage,
load fuse and battery fuse
1 LVD mono or bistable contactors, 1 LVD mono contactor, 8 user relay
Outputs YDN23
outputs(Optional, need extra board)

Examples of Alarms
DC Power Plant Alarms AC mains failure, Rectifier failure, High voltage shutdown,Fan failure,
Thermal derating (of rectifier output due to high temperature)

AC Power Embedded Power Precision Cooling


Emerson Network Power.
Connectivity Monitoring Racks & Integrated Cabinets
The global leader in enabling
DC Power Outside Plant Services
Business-Critical Continuity™
Embedded Computing Power Switching & Controls Surge Protection

www.emersonnetworkpower.com Business-Critical Continuity, Emerson Network Power