You are on page 1of 3

SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -June 2008) Rev 3 30-Jun-08

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Verify Test Equipment (Safety Assessment) SAIC-A-2009 22-Jan-14 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

RABIGH II PROJECT, Interconnecting Package (UO1) 111580 GSCA / Raymond


EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
COMPANY USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Note TEST EQUIPMENT SAFETY ASSESSMENT (Notes 1-7) ... Perform along with SAIC-A-2011.
On New & Existing Projects, Test Equipment shall be thoroughly inspected & certified for safety (new & existing test equipment).
1
Responsible persons shall be Project QA/QC Mgr and designated Hydrotest Engineer and Mechanical Inspector(s).

Regular inspection/maintenance of appropriate test equipment is mandatory to assure Safety on Company Projects. Use of
2 existing equipment is permitted if equipment does not exhibit signs of deterioration & is regularly inspected (Per Note 7) and meets
GI-2.102 Safety Requirements. Recommended is use of corrosion inhibitor when equipment is not in use for long periods.

Check component corrosion & wear (especially small fittings, nipples, etc) on existing equipment, especially test pumps. A thorough
visual exam includes accessible internal components (use mirror & sunlight technique), a UT exam or hammer test (never hammer
3 pressurized piping). Perform this exam in presence of COMPANY Inspection for new projects just prior to testing existing manifolds.
Fittings and components found with heavy corrosion or thinning (verified wall loss) shall be replaced. Heavily Corroded fittings give a
dull sound when hammer tested (new steel = ringing sound). Perform UT on suspect fittings or replace ASAP.

Existing Manifolds proposed for use on projects without detailed code construction documents (Engineering calcs & Inspection) must
be certified for fitness and safety. Existing test reports alone are not acceptable support documents. Code construction detail,
calculations (SIS sheet), appropriate Inspection and NDE are necessary for Safety. Unknown piping schedules can be determined by
4
using a UT Thickness meter. Ratings for most fittings are stamped/visible. Weld quality is verified by VT or RT. Test manifolds
frequently used, older than two years and stored in ambient conditions are highly susceptible to accelerated internal corrosion and
thinning of components due to corrosive nature of test waters used in many locations. Detail Manifold Arrangement Dwgs.

Fabricated test components (blinds, spools, welded couplings, etc) are of proper code construction, receive inspection and are
properly identification/marked for their pressure rating, inspection acceptance/fitness (Insp Ok, initial, date). Never allow uninspected
5
non-code test component use. Components found unfit for testing (non-code, under thickness or schedule & without calculations,
deteriorated, damaged, corroded) are reported and removed ASAP from Company Projects.

Manifold design shall include limiting factor for all components (isolation valves, piping, fittings, tubing, etc). that are calculated (by
design) to provide a PRESSURE RATING of 20% above the maximum expected system for test. Isolation valves shall be one Class
higher than systems tested. Example: Project's greatest System Class = Class 900, CS (Normal), pressure rating 2,220 psi (test
pressure = 3,350 psi). A manifold is needed to meet COMPANY safety requirements. Step 1: Maximum test pressure for Class 900
6 systems = 2,220 x 1.5 = 3,330, round up to nearest increment of 25 = 3,350 psi. Step 2: Manifold minimum design pressure (manifold
test pressure) SHALL = 3,350 x 1.2 = 4,020 psi. Step 3: Manifold isolation valve must be Class 1500 minimum (one class above Class
900) See ASME B16.34 Tables & Para 7.2 = a 110% pressurization rule for valve seat closure tests. Step 5: Components (piping,
fitting, tubing, etc) are rated for 4,020 psi minimum and have engineering calcs to support their use. Manifolds without construction
details (arrangement drawings) are not accepted until CERTIFIED & RATED for Safety.

Perform safety checks for Notes 1-6 at least yearly* & before the start-up of pressure testing on projects. *Observation: The
Diving Industry requires appropriate test equipment maintenance inspections on an annual basis. Scuba Tanks are pressurized
frequently to 3,200 psi, often on a daily basis. Annual inspections use remote visual means (fiberscope). Corroded Tanks are replaced
7
before they fail. Pressure Testing equipment sees similar and even greater pressures and service use. Safety of Test Crews, Inspectors
& personnel on Projects deserve similar consideration. Keep Test equipment in good condition (Coated as needed, clean, legibly
rated for pressure, legibly marked "as inspected, and regularly inspected).

A Test Manifold & Appurtanances (Piping, Fittings, Hoses) - Verify Test Package Content before Testing
Manifold Arrangement Drawing(s) attests to equipment safety:
A) Fabrication is per code construction with
component details listed such (Class, size, schedule piping, type
isolation valve, etc). B)
G.I.-2.102,
Maximum Safe Test Pressure Rating based on limiting factor.
Para. 5.1.5.5 S-
A1 C) Each test manifold is identified with a unique
PM-G000-1520-
number (certificate) D) Shows actual
0007, Sec-6.4.4
arrangement including hose configuration used
Note 1: Manifold permanent marking (unique ID #,
pressure rating) is legible, traceable & certified for safety (Support
documenation).
G.I.-2.102,
Para. 5.1.5.5
Manifold Design Pressure Rating (Compare SIS for manifold & the
Safety
A2 system to be tested) exceeds system test pressure by 20%.
Note 6 S-PM-
G000-1520-
0007, Sec-6.4.4

Page 1 of 3
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -June 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Verify Test Equipment (Safety Assessment) SAIC-A-2009 22-Jan-14 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

RABIGH II PROJECT, Interconnecting Package (UO1) 111580 GSCA / Raymond

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

B Verification of Actual Test Equipment Set-up (Manifold Arrangement)

Test Set-up* matches actual Test Manifold Arrangement.


Note 1: *Pressure Test Diagram with
an appropriate Legend for symbols, Test Manifold Arrangement (& G.I.-2.102,
pressure hoses/piping) show all high points (vents), low points Para. 5.1.2, S-
B1
(drains), gage locations & provide documentation that attests to the PM-G000-1520-
actual test as performed. In event of testing accident, Loss 0007, Sec-6
Prevention Dept must be able to use diagrams & sketches to
recreate actual test set-up/conditions.

G.I.-2.102,
Blow down valve is adequately rated at higher class than system
Para. 5.1.5.3 S-
B2 under test, and is installed to depressurize the system safely and is
PM-G000-1520-
easily accessible to operator. (Safety Note 6, Isolation valve)
0007, Sec-6.4.2

Temporary Test Piping, spools, fittings to equipment and hose


G.I.-2.102,
B3 connections have adequate* pressure ratings, as marked, stamped
Section 4
or documented in test pkg. (*Match/exceed test pressure)

Hoses are adequately rated, in good condition, safely arranged G.I.-2.102,


B4
(tripping hazards) and protected from Heavy equipment traffic. Section 4

Paddles or spectacle blinds & other fabricated test items for SAES-A-004
isolation are at least the same code class rating of systems under Para. 7.3 / S-
B5
test or have code calcs to support them. Safety Note 5 PM-G000-1520-
0007, Sec-8.3.1

C Test Relief Valve(s)

Relief valve is located in the system under test and near the test
G.I.-2.102,
C1 pump with Isolation valves on the inlet and outlet of the relief valve
Para. 5.1.5
sealed open during the test.

Relief valve(s) of adequate capacity (*SIS Sheet & Calcs available) SAES-A-004
are set to relieve at 5%* above the hydrotest pressure. Para 5.5.1/ S-
C2
*Note: Test pressures less than 85% of SMYS can have PM-G000-1520-
relief valves set at 10% above test pressure. Verify SIS sheets/calcs. 0007, Sec-6.4.5
Tested relief valve(s) with a tag stamped with the word "TEST", the
SAES-A-004
set pressure, and date is checked. Stamp date validity is a period of
Para 5.5.1 / S-
C3 one week for project pressure tests. Stickers are legible & valid.
PM-G000-1520-
A roster is kept for Pressure Relief Valves (M&TE) on
0007, Sec-6.4.1
projects.

D Pressure Gages and Recorders

A minimum of two pressure gages are required for test systems, with
accuracy within 5% of one another.
Note 1: When large systems are tested, Inspection personnel will
determine the need for additional gages. SAES-A-004
Note 2: Elevation changes (hydrostatic head Para 7.1.5 / S-
D1
considerations) & hot weather create pressure testing problems with PM-G000-1520-
frequent popping of relief valves. For this reason, gage accuracy 0007, Sec-8.1.5
within 2% is best. Note 3: Careful handling of
delicate instruments as test gages is practiced by test crews. No
gage damage or mishandling is found.

Page 2 of 3
SAUDI ARAMCO ID/PID - REV 0- 18-May-05 (Standards Cutoff -June 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Verify Test Equipment (Safety Assessment) SAIC-A-2009 22-Jan-14 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

RABIGH II PROJECT, Interconnecting Package (UO1) 111580 GSCA / Raymond

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

SAES-A-004
Pressure gages and pressure recorders are calibrated within (1) Para 7.1.5 / S-
D2
month prior to test. Stickers applied indicate latest calibration date. PM-G000-1520-
0007, Sec-8.1.5

Test gauge is located at bottom of any equipment/system under test G.I.-2.102,


to enable reading test pressures inclusive of hydrostatic head. Sec.4 &
Note: Locate test manifold (with gage) at low points in SAES-A-004,
D3
systems under test. One foot of water (30 cm) @ ambient Para 7.1.5 / S-
temperature = pressure increase of .433 psi. (1-meter = 1.42, 10- PM-G000-1520-
meter = 14 psi). 0007, Sec-6.2

SAES-A-004
All gages have a range such that the test pressure is within 30% to Para 7.1.5 / S-
D4
80% of the full range. PM-G000-1520-
0007, Sec-8.1.5

E Temperature Gages and Recorders (When Required, ie: 24-hr Recorded Tests)

Bubble Leak Test (associated with Pneumatic strength/service test)


surface metal temperatures shall be recorded and compatible with
SAES-A-004
test methods (including test solution used to detect leaks).
Para 5.6.1 / S-
E1 Note: ASME V, Art 10, Man. App. 1, Table 1-1021
PM-G000-1520-
requires surface metal temp measurements during testing (detailed
0007, Sec-6.5.3
in procedure). Record maximum (direct sun) & minimum test
temperatures.

Thermocouples are installed to obtain accurate pipe metal SAES-L-150,


temperature measurements and to determine the acceptance of the Para. 11.3 S-
E2
pressure test where pressure variations due to test water PM-G000-1360-
temperature changes occur, such as in cross-country pipelines. 0001, Sec-25.6

REMARKS:

REFERENCE DOCUMENTS:
1. SAES-A-004, / S-PM-G000-1520-0007, General Requirements for Pressure Testing,
2. GI-2.102, Company General Instruction-Pressure Testing Safely,
3. SAES-L-150, Pressure Testing of Plant Piping and Pipelines, S-PM-G000-1360-0001, General Specification for Piping.
4. Pro Forma Contract Schedule Q (Project Specific)

Contractor / Third-Party Company


Construction Representative* Company PMT
Work is Complete and Ready for Inspection:
T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector Company Inspector


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved:
Name, Organization, T&I Witnessed QC Record Reviewed Work Verified
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 3 of 3

You might also like