Professional Documents
Culture Documents
Transformer Introduction 2
Special Transformers 10
Annexures A, B, C 12-14
A Transformer
Primary Secondary
Voltage Voltage
Core
1
TRANSFORMER INTRODUCTION
a) Alternating current can be readily transformed from low to high voltage and vice versa.
b) The alternating voltage can be raised or lowered as required at different stages in an electrical network, such
as generation, transformation, distribution and utilization
c) This is made possible with a device called a transformer.
d) The function of a transformer is to transfer current, voltage and power from one series of windings (coils) to
another. The transformer consists of two inductive coils; these are electrically separated but linked through a
common magnetic circuit. These two coils have a high mutual inductance. One of the two coils is connected
to a source of alternating voltage. This coil into which electrical energy is fed is called the Primary Winding (P).
The other winding is connected to a load. The electrical energy is transformed into this winding and drawn out to
the load. This winding is called the Secondary Winding (S)
e) Generally a transformer is categorized according to its transformation action:
• Step-up Transformer: A transformer in which Vs > Vp. A step up transformer is a transformer which
converts low alternating voltage to high alternating voltage.
• Step-down Transformer: A transformer in which Vp > Vs. A step down transformer is a transformer which
converts high alternating voltage to low alternating voltage.
f) A transformer can also be used as an isolation device.
• The circuit on the primary side of the transformer is electrically isolated from the circuit on the
secondary side of the circuit.
• Isolation transformers usually have the same secondary voltage as the primary.
• They are mainly used to isolate a piece of equipment from the AC mains for safety reasons.
• Television set is an example of the need for isolation transformers for diagnostic and repair work.
2
PCB TRANSFORMERS
(Cat. P1, pg. 73 & 74 of Catalogue)
These transformers can be manufactured by the transformer workshop as per specifications indicated in the catalogue.
Applications
These are used in printed circuit boards, e.g. for Timers manufactured by our Electronics Workshop.
Part Numbers
The Standard part no. for PCB transformers is as per catalogue.
The Part no. for Specially Manufactured PCB Transformers is PCB100.
NB!
• The information on all documents must be consistent
• With regard to COD customers manufacturing will not proceed until proof of payment has been received and
confirmed by the relevant authority
3
POWER TRANSFORMERS - SINGLE PHASE
(Cat. T1, pg. 77 of Catalogue)
These transformers can be manufactured by the transformer workshop as per specifications indicated in the catalogue.
The maximum voltage we can offer per winding is 1000V and the maximum VA rating we offer is 50KVA, air cooled
Isolation Transformers
An isolation transformer is a transformer used to transfer electrical power from a source of alternating current (AC)
power to some equipment or device while isolating the powered device from the power source, usually for safety
• Domestic Applications
Vacuum cleaners and power tools head the list of "noisy" electrical devices because they induce high
levels of interference back into the power line they are connected to. This is why running a vacuum cleaner
may cause interference on your television set, radios, sensitive electronics such as computers and
analytical equipment, and communications systems. Isolation transformers are increasingly finding their
way into home special line current circuits to keep this noise and interference limited to the circuits
supplying the tools.
• Industrial Applications
Large manufacturers also run separate circuits for noisy tools and sensitive electronics. Isolation
transformers in the lines to the noisy devices minimize the length of wiring the interference may traverse.
A further complication in long or expansive buildings is the possible large voltage potential between two
electrical grounding grids on opposite ends of the building, because of inductance and leakage in what
may be connected to these grids. This introduces noise, buzz, hum and pops into communications and
computer networks, and unacceptable noise in audio systems.
• Theaters
Theaters may have large distances and separate power circuits between projection and audio systems.
Isolation transformers on AC and audio lines prevent the exchange of noise between these systems.
• Telecommunications
Telecommunications and computer centers use isolation transformers to segregate potential interference
issues in much the same way as theaters
4
POWER TRANSFORMERS - SINGLE PHASE
(Cat. T1, pg. 77 of Catalogue)
Bucket Codes
• Extra Tappings
T-EX1 Extra Tapping below 25A
T-EX2 Extra Tapping 25-50A
T-EX3 Extra Tapping 50-100A
• Perspex
T-PER1 Perspex terminal shield up to 200VA
T-PER2 Perspex terminal shield 225VA to 1KVA
T-PER3 Perspex terminal shield 1.5- 20KVA
Purpose: Safety precaution for users and workers
• Screen
T-SCN1 Earth Screen & Terminal up to 200VA
T-SCN2 Earth Screen & Terminal 225VA to 1KVA
T-SCN3 Earth Screen & Terminal 1.5- 20KVA
Purpose: A metallic material (typically copper foil) between the primary and secondary windings offering isolation to
ground between the two windings. Separation of dangerous active components is done by use of a conductive
shield, which is located between the two parts and is connected to an external earth terminal.
NB!
• The information on all documents must be consistent
• With regard to COD customers manufacturing will not proceed until proof of payment has been received and
confirmed by the relevant authority
5
POWER TRANSFORMERS - THREE PHASE
(Cat. T1, pg. 78 of Catalogue)
Three-phase transformers are connected in delta or Star configurations. A Star -delta transformer has its primary
winding connected in a Star and its secondary winding connected in a delta (see figure 1-1). A delta-Star transformer
has its primary winding connected in delta and its secondary winding connected in a Star (see figure 1-2).
6
POWER TRANSFORMERS - THREE PHASE
(Cat. T1, pg. 78 of Catalogue)
Delta Connections
A delta system is a good short-distance distribution system. It is used for neighborhood and small commercial loads
close to the supplying substation. Only one voltage is available between any two wires in a delta system. The delta
system can be illustrated by a simple triangle. A wire from each point of the triangle would represent a three-phase,
three-wire delta system. The voltage would be the same between any two wires (see figure 1-3).
Figure 1-3:
Star Connections
In a Star system the voltage between any two phase conductors will always give the same voltage on a three phase
system. However, the voltage between any one of the phase conductors (X1, X2, X3) and the neutral (X0) will be less
than the phase to phase voltage. For example, if the voltage between the phase conductors of any two phases of a
three wire system is 208v, then the voltage from any phase conductor to neutral will be 120v. In a Star system, the
voltage between any two power conductors will always be 1.732 (which is the square root of 3) times the voltage
between the neutral and any one of the phase conductors. The phase-to-ground voltage can be found by dividing the
phase-to-phase voltage by 1.732 (see figure 1-4).
Figure 1-4:
7
POWER TRANSFORMERS - THREE PHASE
(Cat. T1, pg. 78 of Catalogue)
These transformers can be manufactured by the transformer workshop as per specifications indicated in the
catalogue. The maximum voltage we can offer per winding is 1000V and the maximum VA rating we offer is
30KVA. If a screen is required or Extra tapping’s this must be indicated on the order.
• VA Rating
• Primary Voltage
• Secondary voltage
• 3 phase Transformer connections
Star Calculations
E.g If the voltage between any two phase conductors is 400V then the voltage between any of the phase conductors
and neutral will be 400V ÷ 1.732 ( ) = 230.9V
Therefore in the star system 1.732 x 230.9V = 400V (voltage between phases)
Part Numbers
The Standard Transformer part no. for a Three Phase Transformer is indicated as T-X KVA
e.g. T-5KVA for a 5000VA 3 phase transformer Or T-0.25kva for a 250VA 3 phase transformer.
Bucket Codes
• Tapping
T-EX1 Extra Tapping below 25A
T-EX2 Extra tapping 25-50A
T-EX3 Extra tapping 50-100A
• Perspex
T-PER1 Perspex terminal shield up to 200VA
T-PER2 Perspex terminal shield 225VA to 1KVA
T-PER3 Perspex terminal shield 1.5- 20KVA
• Screen
T-SCN1 Earth Screen & Terminal up to 200VA
T-SCN1 Earth Screen & Terminal 225VA to 1KVA
T-SCN1 Earth Screen & Terminal 1.5- 20KV
The customer is required to complete a Non Cancellation form and a Power Transformer Data Request/order
form. See Annexure A, & C
NB!
• The information on all documents must be consistent
• With regard to COD customers manufacturing will not proceed until proof of payment has been received and
confirmed by the relevant authority
8
UNREGULATED TRANSFORMERS VDC & VR
(Cat. T1, pg. 79 of Catalogue)
These transformers can be manufactured by the transformer workshop as per specifications indicated in the
catalogue. The maximum voltage we can offer per winding is 525V on the primary and 110V on the secondary. The
maximum VA rating we offer is 1000VA.
Part Numbers
The Standard VDC Transformer part no. indicates the VA rating with voltages e.g.
T-500VDC/24 or T- 500VDC/24 400V
The Special Transformer part no. indicates only the VA rating i.e. T-VDC. Standard
items primary voltage is 230VAC
Components
The VDC transformers use rectifiers or diodes and Capacitors. The VR transformers us a Rectifier or diode only.
Applications
VDC: Contactors, relays and valves. VR: Brakes and clutches only.
Rectifier
A transformer rectifier unit (TRU) is used to convert AC into relatively smooth DC.
Example of a rectifier:
Use of Diodes
Diodes in their basic forms are used for rectification (or conversion) of AC into DC, for example, in a battery charger
circuit, as shown. Example of a diode:
9
UNREGULATED TRANSFORMERS VDC & VR
(Cat. T1, pg. 79 of Catalogue)
Capacitor
DC Smoothing Capacitor: A Smoothing Capacitor is used to generate
ripple free DC. Smoothing capacitor is also called Filter capacitor and its
function is to convert half wave / full wave output of the rectifier into smooth
DC. The power rating and the capacitance are two important aspects to be
considered while selecting the smoothing capacitor. The power rating must
be greater than the off load output voltage of the power supply.
NB!
• The information on all documents must be consistent
• With regard to COD customers manufacturing will not proceed until proof of payment has been received and
confirmed by the relevant authority
SPECIAL TRANSFORMERS
(Cat. T1, pg. 79 of Catalogue)
DIN Transformers
Safety isolating transformer for DIN-rail
Application:
• Safety isolating transformer in general applications
• Electric appliances where 12 or 24 VAC is necessary
• Industrial environments where delivery of SELV (safety extra-low voltage) or PELV (protective extra-low voltage) is
necessary
• Connecting loads that need to be isolated from the main supply and to create interference suppression
These transformers can be manufactured by the transformer workshop as per specifications indicated in the catalogue.
These Range from DT10212 to DT15612 and 100VA to 200VA DIN transformers
Application:
Used for swimming pool lighting
These transformers can be manufactured by the transformer workshop as per
specifications indicated in the catalogue. These are type SP-120VA and
SP-300VA or SP-120VA Open and SP-300VA Open
10
MAINS POWER SUPPLIES
(Cat. BC1, pg. 84 of Catalogue)
These transformers can be manufactured by the transformer workshop as per specifications indicated in the
catalogue. These include the MD range and VAP range. Other voltages can be made according to customer
specifications but only in the VA rating of the specific product.
Application:
A power supply allows electronics to function and charge. This completes the circuit. Without the device, cell
phones or computers could not operate. The power supply converts outlet electricity to charge and power
appliances and equipment in your home.
An Autotransformer has only one single voltage winding which is usually "tapped" at various points along it to
provide a percentage of the primary voltage supply across its secondary load. The autotransformer has the usual
magnetic core but only one winding, which is common to both the primary and secondary circuits.
Application:
Different starting methods are employed for starting induction motors because they draw more starting current
during starting. To prevent damage to the windings due to the high starting current flow, different types of starters are
employed. To limit the starting current surge, large induction motors are started at reduced voltage and then have full
supply voltage reconnected when they run up to near rotated speed.
11
ANNEXURE A
Confidentiality Caution: If you have received this communication in error, please note that it is intended for the addressee
only, is privileged and confidential and dissemination or copying is prohibited. Please notify us immediately by telephone
and please discard this communication.
To: ______________________________________________________________________________________________________
Subject:_____________________________________________________________________________________________________
± 7 - 14 Working Days
We thank you for your valued order and wish to point out that this order cannot be processed without signed acknowledgement of the
below conditions: kindly complete and return both pages.
Regards
__________________________
Sales Department
Signature___________________________ Date:____________________________
ANNEXURE B
ANNEXURE C
AC/DC DYNAMICS
POWER TRANSFORMER DATA REQUEST/ORDER FORM
CONNECTION REQUIRED
DELTA DELTA
STAR STAR
Company: ___________