You are on page 1of 3

Project: SIKAR & PANCHKULA S/s Sale Order: 4200367476

Customer: PGCIL-CGL

BILL OF MATERIAL

Document Name Identity


General arrangement YN1M301768-AAX
Schematic diagram YN1M301768-CAX
Wiring table YN1M301768-DAY
Label List YN1M301768-LAY

REVISION TABLE

Rev.No. Revision Note Approved Week


01 Revised as per cust. Comments KH 47
02 Revised as manufactured KH 52

(**) – Items will be housed in Station Control Room

Design Checked by 400/220kV SUBSTATION AUTOMATION SYSTEM


MURALI ANIVILLA 4200367476
400kV/220kV SIKAR & PANCHKULA SUBSTATION
Drawing Checked by Rev
KANNAN Panel: SAS-2 YN1M301768-AY 02

Drawn by Issued by Year Week Sheet


K.HAJIRA SASE 11 30 BILL OF MATERIALS 1 of 3
Project: SIKAR & PANCHKULA S/s Sale Order: 4200367476
Customer: PGCIL-CGL

1. Common items for SAS for 400/220kV System: 1 Set (comprising of)

Sl. Description Article No. Qty


No. (No.)
1. Panel Details.

a. Type: VSG 800, Panel Dimensions: 800(W) x 800(D) x 1MYN528001-RL 1 no.


2000(H), Colour : Exterior : RAL7032, Texture Finish, Interior :
Glossy White, Powder Coated. Base Frame: 47mm, AVP:
15mm. Make: ABB
b. AC MOUNTING PLATE: Mounting plate for AC fuses, 1 no.
universal socket and toggle switch.
C1. BUSSMANN/S&S make fuse fitting, 1MYN567003-D 4 no.
BUSSMANN/S&S make HRC fuse 10A
C2. BUSSMANN/S&S make fuse fitting, 1MYN567003-A 1 no.
BUSSMANN/S&S make HRC fuse 2A
C3. BUSSMANN/S&S make fuse fitting, 1MYN567003-C 1 no.
BUSSMANN/S&S make HRC fuse 6A
C4. BUSSMANN/S&S make fuse fitting, 1MYN567004-C 2 no.
Neutral Link 15A
C5. BUSSMANN/S&S make fuse fitting, 1MYN567003-B 2 no.
BUSSMANN/S&S make HRC fuse 4A
d. Universal Socket (Box type) With switch Rating:5A/15A 230V 1MYN538103-001 1 no.
AC
e. Toggle switch ON/OFF, 1-Pole, 6A, 240V AC IN5399-3002-1 1 no.
f. Thermostat, 30D to 90D IN7635-3001 1 no.
Rating: 15A, 230V AC
IN5374-3001-1
g. DOOR SWITCH: Single pole, Rating:5A,230 V AC 1 no.
h. CFL LAMP: Space heater Rating 50W 230 V AC IN6677-3001-2 1 no.
i. COMPACT FILAMENT LAMP 3BYN591500-001 1 no.
Rating: 11W 230V AC
j. Disconnecting type terminal blocks Elmex make 1MYN266003-002 SET

Design Checked by 400/220kV SUBSTATION AUTOMATION SYSTEM


MURALI ANIVILLA 4200367476
400kV/220kV SIKAR & PANCHKULA SUBSTATION
Drawing Checked by Rev
KANNAN Panel: SAS-2 YN1M301768-AY 02

Drawn by Issued by Year Week Sheet


K.HAJIRA SASE 11 30 BILL OF MATERIALS 2 of 3
Project: SIKAR & PANCHKULA S/s Sale Order: 4200367476
Customer: PGCIL-CGL

Sl. Description Article No. Qty


No. (No.)
j. Fans for Cooling, Make: HICOOL, 230V AC, 18W, 4 nos
0.10/0.125A and 50/60Hz.
2. Redundant Station (Standby) HMI consisting of:
a. Advantech / Portwell Laxson make, 19” rack mountable 1MYN900010-SV 1 No.
Industrial grade PC, Intel C2D 2.93GHz, 3 GB DDR2 RAM,
160 GB IDE HDD, CD& DVD R/W drive,(24x-CD&40x-DVD),
2 X serial ports,1 X parallel port,1xVGA port,3 X USB ports,1
internal USB port, 2 X dual port Intel PRO1000MT server
adapter, SMPS Suitable for 230V AC supply,
Windows server-2008-32bit
b. Alan make DC-AC Inverter (1000 VA), Input 230V AC and 1MYN769010-006 1 No.
220V DC, O/P : 230V AC,
Refer annexure-1&2 for inverter sizing.
3. Communication Gateway consisting of:
a. Advantech / Portwell Laxson make, 19” rack mountable YN1M301768-TC 1 No.
Industrial grade PC, Intel C2D 2.93GHz, 2 GB DDR2 RAM,
160 GB IDE HDD, CD& DVD R/W drive,(24x-CD&40x-DVD),
2 X serial ports,1 X parallel port,1 X VGA port,3 X USB ports,1
internal USB port, 1 X dual port Intel PRO1000MT server
adapter, SMPS Suitable for 230V AC supply,
Installed with ABB make MicroSCADA COM 500 software.
Windows XP SP3 Operating System.
4. Ethernet LAN consisting of:
a. Ruggedcom make, 10/100 Mbps Managed Ethernet switches 1MYN900010-TB 1
(with RJ45 connectors for station level devices)
No.
5 D link switch for server 1MYN900010-UM 1 No

6 ABB Make, NSK5 MODEM 1KYN588006-AAA 4 Nos.

7 LIU Unit YN1M300922-LIAs per


annex-
A&B
8 Armoured FO cable, Unarmoured FO cable and LAN cables As per
YN1M301768-TF
required for automation. annex-
A&B
9 RS232/RS485 Convertor with 220V DC 1MYN172006-003 2 Nos.
10 RS232/RS485 Convertor with 48V DC 1MYN172006-001 2 Nos.

Design Checked by 400/220kV SUBSTATION AUTOMATION SYSTEM


MURALI ANIVILLA 4200367476
400kV/220kV SIKAR & PANCHKULA SUBSTATION
Drawing Checked by Rev
KANNAN Panel: SAS-2 YN1M301768-AY 02

Drawn by Issued by Year Week Sheet


K.HAJIRA SASE 11 30 BILL OF MATERIALS 3 of 3