MODULE
Installation and User Manual

First, ATERSA and his team thank are grateful for your confidence by purchasing
our products for your photovoltaic installation. This manual contains important
information about handling, installation and maintenance. Please carefully read and
understand this manual before any handling. ATERSA not liable for damages caused
due to improper handling, installation or maintenance.

INDEX

1.-GENERAL SAFETY 1
2.- TRANSPORT AND HANDLING 1
3.- WARNINGS 2
4.- POSITIONING AND INCLINATION 2
5.- INSTALLATION 3
5.1.- Mechanical Installation 3
5.1.1.- Directly on the Structure 3
5.1.2.- Hook Fixing System 4
5.1.3.-Guide Insertion 5
5.2.- Electrical Installation 5
5.2.1.- Electrical Connection of the Juntion Box 5
5.2.2.- Ground Connection 7
5.3.- Installation and Guiding of Electrical Cables 8
6.- MAINTENANCE 8
7.- TECHNICAL SPECIFICATIONS 8
8.- GUARANTEE AND CERTIFICATES 8

EN-MU-41 (4)-E
MODULE 1
Installation and User Manual

1.-GENERAL SAFETY
The safety instructions contained in this manual must be strictly followed in order to
guarantee the safety of the user and the integrity of the module..
x Ensure that the installation instructions provided in this document are followed. Guarantees or claims
will not be valid if the described process has not been followed
x The cable pathway must provide mechanical support for the conductors and must provide sufficient
protection, in accordance with the Low Voltage Electrotechnical Regulations (REBT).
x If not otherwise specified, it is recommended that requirements of the latest national or international
electrical standards be used.
x It must be handled by qualified personnel only. When exposed to the light, the modules generate
electricity. If several modules are connected in series, dangerously high voltages may be generated.
To reduce potential electrical hazards during the installation process, it is advisable to cover the
modules with an opaque material. Do not touch the terminals with both hands and always use
insulated tools on the electrical connections.
x Only allow access to the facility by qualified personnel.
x Reversing the polarity of the cables destroys the bypass diodes of the junction box.
x In normal conditions, the module can produce more current or voltage than the indicated for standard
measurement conditions. So that, when dimensioning the system (cables section, fuses,…) the Isc
and Voc values should be multiplied by 1,25.
x Keep children and animals away from PV modules.
x Install the modules in a strong structure and that this maintains the fire safety class.
x Avoid uneven shade on the PV module surface. Shaded cells may become hot (“hot spot”
phenomenon) which may result in permanent damage to the module.
x Follow all safety precautions of other system components used.
x Use module for its intended function only.

2.- TRANSPORT AND HANDLING


The modules must be handled carefully during transport, storage and unpacking.
x Store modules in a dry and ventilated room.
x Do NOT place modules on an uneven surface
x Do NOT place excessive loads on the module or twist the module frame, it may cause severe micro-
cracks at the cell level
x Do NOT stand, step, walk and/or jump on the module.
x Do NOT drop module or allow objects to fall on module.
x Do NOT mark the modules with sharp instrument. Avoid the contact of module back sheet with sharp
objects, as scratches may directly affect product safety
x Do not use the junction box to hold or transport the module.
x Broken or damaged modules must be handled carefully and with appropriate protective
equipment.(Broken glass can be sharp and can cause injury if it is not handled int he right way .
x When carrying a bigger module, two or more people should carry it by its frame and wear non-slip
gloves (to avoid injury by a slipping module, cuts by the edge of a frame etc.
x Module placement unsafely before installation can cause breakage, excessive deformation ... that
affect the reliability of the module.
x Modules must NOT be manipulated from the central part of the long sides of the frame.´

EN-MU-41 (4)-E
MODULE 2
Installation and User Manual

3.- WARNINGS
Failure to follow these instructions could result in the destruction of the equipment or
personal injury.
x NO debe intentar reparase ni emplearse ningún modulo roto, ya que el contacto con alguna parte de
este puede provocar en una electrocución.
x NO exponer directamente la parte trasera a la luz solar.
x Work ONLY under dry conditions, with dry modules and Insulated tools.
x Do NOT install the module where flammable gases or vapors are present.
x Do NOT drill holes in the frame or glass of the module.
x Do NOT treat back sheet and front surface of the module with paint and adhesives.
x Do NOT artificially concentrate light on the module.
x Do NOT wear metallic jewelry while installing or trouble shooting the module.
x Do NOTdisassemble, modify or adapt the module or remove any part of the module.
x Be sure to completely ground all modules.
x Do not touch terminals while module is exposed to light or during installation.
x The connectors must be protected from dust, sund, wather,..., If the connectors are to remain
disconnected in the field.

4.-POSITIONING AND INCLINATION


The modules may be installed on plots of land, terraces, roofs and patios. ATERSA
provides a series of accessories for installations on façades, windows, balconies, walls
and cornices.
In order to ensure optimum performance the modules must not be placed in the shadow
of other objects (plants, snow, buildings, construction elements, other modules, etc.),
at least during the main hours of daylight.
The panels must face south if installed in the northern hemisphere.Guidelines for
achieving maximum annual power output from a fixed installation are provided below. A
design period will be established in order to calculate the size of generator in accordance
with the consumption requirements and radiation. To determine the optimum
inclination we will use the following table (1):

1 SOLAR LIGHT
DESIGN PERIOD INCLINATION

WINTER Latitude +10º

SUMMER Latitude -20º


INCLINATION

ANNUAL Latitude -10º

SOUTH HORIZONTAL
(North hemisphere)

Do not install the solar module in a location where it could be immersed in water or
continually exposed to water, e.g. from a sprinkler.
EN-MU-41 (4)-E
MODULE 3
Installation and User Manual


The installation in a saline environment must be done with isolators to prevent galvanic
corrosion between the module and the support structure.

2
When solar modules are connected in series,
they must all face the same direction and have
the same angle of inclination. There must also
be a proper gap (minimum 30cm) between
the module and the surface for ventilation
purposes.
RECOMMENDED

IMPORTANT: Do NOT install the modules


with the junction box in the lower side. View
image (2).

The ATERSA modules design allows the correct


evacuation of water. They have open edges in
NO
the inside tube.

5.- INSTALLATION
The modules must be installed on independent fixed structures. The structure must not
transmit stress to the modules.

5.1.- Mechanical Installation


5.1.1.-Directly on the Structure
The longest side of the aluminium frame has a series of 6,7mm diameter drill holes.
Use M6 stainless steel screws to install it on the structure and the proper torque
values should be between 6 to 8Nm. The following screw system should be
employed (3) .

3
FRAME

M6 SCREW

* Nota: Use M6 DIN 9021 washer for Hook V4 profile. *M6 WASHER

Use M6 DIN 125 washer for Hook V1 profile.

M6 WASHER
STRUCTURE
M6 GROWER WASHER
M6 NUT

EN-MU-41 (4)-E
MODULE 4
Installation and User Manual

The placement of the screws, will be always at the distance B (except for ½ 6” 4x9
format modules, where the distance must be C), as shown in the image of the anex
(11-12). Minimum 4 screws per module must be situated.

*Note: In corrosive environments (salt spray), place nylon washers to insulate the
panel from the metal parts of the structure.

5 .1.2.- Hook Fixing System


The aluminium frames of ATERSA’s photovoltaic modules have side channels that make
it easier to fix the module onto the profiles of the installation.
The Hook Fixing System is used to install the modules.This system can be installed on
standard structures , “U” type guide rail or guide insertion.

Installation on standard structures:


Fixing on standard structures is carried out using the dead-end clamp, the M8x20
serrated head Allen screw, flat washer and M8 nut. View image (4).

4 DEAD-END CLAMP

M8x20 ALLEN SCREW

M8 WHASER
M8 NUT

Installation on “U” type guide rail:


For this type of installation you need a 41x41mm or 41x21mm "U" type perforated
profile. These elements do not come with the Hook Fixing System.
The assembled fixing should look like the picture shown in next figure: (5).

5
DEAD-END CLAMP

M8x20 ALLEN SCREW

M8 GUIDE NUT

*Note: In corrosive environments (salt spray), place nylon washers to insulate the
panel from the metal parts of the structure.

EN-MU-41 (4)-E
MODULE 5
Installation and User Manual

Installation
Put the first two fixing sets in place, and ensure they are vertically aligned. Fully
tighten the Allen screw (6).

6 +1.5
20 -1.5 mm

Attach the other two fixing sets, aligning them vertically and move them along the rail
until they reach the panel.
Check that the modules are horizontally and vertically aligned and fully tighten the
screws to ensure the modules are firmly fixed to the guide rail.
The final fixing sets should be attached in the same way as the first two but in reverse.
Take a module that is already in place and then attach the set of fixings.
The proper torque values should be between 16 to 19Nm.
The placement of the dead end clamp (Hook clamp or another type), will be always at
the distance B (except for ½ 6” 4x9 format modules, where the distance must be C),as
shown in the image of the annex (11-12). Minimum 4 dead end clamps per module
must be situated.
Assembly drawings depending on the applied load are displayed in annex.(View images
13-14)

5.1.3.- Guide Instertion

The modules are ready for installation by inserting into a guide system.
After insertion into the guide rails, panels must be fixed to prevent free sliding on the
guides.

5.2.- Electrical Installation


5.2.1.- Electrical Connection of the Juntion Box

CABLE SECTION (Copper section):


Appropriate cable sections must be used to prevent voltage drops, which could cause a
drop in the power of the installation. As a rule, voltage drops in excess of 1,5% must
not be allowed.
(*)Check table of intensities max. of manufacturer's cable and the applicable
regulations.

EN-MU-41 (4)-E
MODULE 6
Installation and User Manual

TOTAL SECTION (External diameter):


A direct cable connection can be made to the direct connect junction box using (max.
4mm2,AWG12) the cable termination spring clips in the junction box. In the manner
shown below, direct connection of cable sizes AWG14 and AWG12 can be
accommodated. The sealing grommet in the 2 rail assembly can accommodate
insulation diameters up to 8.0mm (0.31 inches). To ensure proper termination, cable
insulation should be stripped as shown in figure(7).
7 X= 11mm, 0.43 inches

Modules of 36 cells and ½ 36 cells

ELECTRICAL CONNECTION:
On multi-stranded conductors, it is recommended to use wire pins or at least to twist
the strand bundle to ensure all strands are captured in the spring clip. To open the
spring clip window for the cable, use the appropriate tool (see ATERSA product) or a
little screw, to insert vertically into the window as seen in figure 1.View image (8)

Figure 1 Figure 2
Modules of 36 cells and ½ 36 cells

The cable can be inserted through the opened window into the clip (figure 2). Once the
cable is installed, lift the screw and the cable is fixed. Attention to the polarity of the
wires. Make sure that the cable is inside the clip and is fixed correctly, if the cable is not
installed correctly the juntion box will be deteriorated (electric arc).
After termination, tighten the grommet nut to compress the grommet around the
cable. Tightening torque for cable screw nut max. 1.5 Nm (0.34 lbf) depends on the
type of cable isolation. Hold cable screw joint with tool.
Connection boxes with integrated cable glands are used with 4mm² cable (AWG 12).
+0.2
The tightening torque is 1.3 Nm (0.29 lbf). For this is recommended the use of a
slotted socket wrench with wrench size oh 13mm (0.51 inches). ,
The cable must fulfill the requirements to be used in photovoltaic systems. On models
72 and 60 cells, ATERSA provides wiring junction box installed. In these cases,
provided cables may not be modified, deleted, or be replaced by other. The cable used
by ATERSA in its modules is for outdoors use, UV resistent, double isolation layer, 1kV,
working temperature range -40ºC to 110ºC, rated 600/1000 V..
EN-MU-41 (4)-E
MODULE 7
Installation and User Manual

For the junction box to maintain its Class II safety standard, the cables must also be
Class II.
It is not recommended to connect modules in series with a total Voc higher than the
system Vmax .(View electrical characteristics). View image (9).

9.2

9.1

Series installation

Parallel installation

5.2.2.- Ground connection 10


Connect the modules and the support
structure to ground, which will ensure that
any current leakage to any of the
components of the installation will not
reach the installer or user under any
circumstances.
The module frame material is aluminium.
Ground wires must be connected to the
module’s frame at the ground location.
View imagen (10).

2
The ground wire must be 4mm .To ground the modules, you must use a stainless steel
2
lug terminal 4mm and a self-tapping screw between 4,2x4,5mm and 4,2x16mm. Esto
2
irá unido a un terminal de ojete semiaislado de 4mm .Ver imagen (10).
Make sure the lug terminal is placed between the wire and module frame. The wire
must fully clamped with the lug terminal and must make good contact with the frame.
There are two drill holes in the solar modules for this purpose, which are marked with a
ground connection (Earthing hole 4mm). View image of annex (11-12). The proper
torque values should be between 1,5 to 2Nm.
The photovoltaic system will be earthed according to the local and national regulations.

EN-MU-41 (4)-E
MODULE 8
Installation and User Manual

5.2.- Installation and guiding of the electrical cables


All the cables used in the installation must be secured in order to prevent movements
that could cause damage or breakages.

6.- MAINTENANCE
ATERSA solar modules hardly require any maintenance but you must follow a set of
guidelines to ensure good condition.
x Maintenance work should be carried out by qualified personnel, as it could involve working with
dangerously high voltages.
x Check that dirt has not accumulated on the glass of the panel.
x Should this be the case, clean the glass with a sponge and soapy water
x In case if water is not available,Module can be dry cleaned with the help of a soft cloth or with soft
sponge to remove dirt, dust.
x DO NOT use brushes or abrasive products as they can damage the glass and reduce the power
module.
x DO NOT use any chemical abrasive cleaners, degreasers, or cleaning.
x DO NOT use water jet cleaning system.
x DO NOT clean the panels at their hottest (midday).
x Check the cables and electrical connections.
x DO NOT use lubricant oils or sprays to connect the connectors..
x Appropriate electrically insulating Personal Protective Equipment (PPE) must be worn during any
cleaning or inspection operations.
x Check that the mechanical components are not damaged.

7.- TECHNICAL SPECIFICATIONS


Our solar modules are made from high-efficiency square cells that are capable of
producing power with low solar radiation. All the models from 75W to 320W have by-
pass diodes in the junction box.
The technical characteristics of the modules are shown in the attached table and
grapichs. View table on page 9 (Polycrystalline) and page 10 (Monocrystalline).

8.- GUARANTEE AND CERTIFICATES


ATERSA guarantees the power output for up to 25 years and provides a 10-year
warranty covering manufacturing flaws.
According to the norm IEC 61730-1, the application class for this product (ATERSA
module) is class A, which corresponds to modules working in voltages above 50V or
powers above 240W where the access to a general contact is forecasted. The modules
clasified for security within this category fulfill the requirements for ClassII.
The modules comply with IEC 61215:2005 and IEC 61730 standards, in addition to
being manufactured under strict UNE-EN ISO 9001:2008, UNE-EN ISO 14001:2004
quality standards.and OHSAS 18001:2007.

EN-MU-41 (4)-E
Polycrystalline
ELECTRICAL CHARACTERISTICS A-75P A-80P A-140P A-150P A-160P A-255P A-260P A-265P A-290P A-295P A-300P A-305P A-310P A-315P A-320P

Format ½ 6” 4x9 6” 4x9 6” 6x10 6” 6x12

Power 75 W 80 W 140 W 150 W 160 W 255 W 260 W 265 W 290 W 295 W 300 W 305 W 310 W 315 W 320 W

Tolerance ± 8% ± 8% ± 5% ± 5% ± 5% (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W)
MODULE

Number of cells in series 36 ½ 36 60 72

Module Efficiency 14,63% 13,65% 14,39% 15,42% 16,45% 15,68% 15,96,% 16,27% 14,90% 15,16% 15,42% 15,67% 15,93% 16,19% 16,45%

Max. Power Current (Imp) 4,05 A 4,22 A 7,98 A 8,10 A 8,43 A 8,29 A 8,35 A 8,40 A 8,07 A 8,14 A 8,21 A 8,27 A 8,35 A 8,43 A 8,51 A
Installation and User Manual

Max. Power Voltage (Vmp) 18,52 V 18,99 V 17,54 V 18,52 V 18,99 V 30,76 V 31,20 V 31,55 V 35,93 V 36,23 V 36,52 V 36,88 V 37,14 V 37,37 V 37,61 V

Short-circuit Current (Isc) 4,24 A 4,42 A 8,42 A 8,47 A 8,84 A 8,88 A 8,95 A 9,01 A 8,67 A 8,78 A 8,89 A 8,78 A 8,83 A 8,88 A 8,93 A

Open Circuit Voltage (Voc) 23,20 V 23,40 V 22,30 V 23,20 V 23,40 V 37,80 V 37,98 V 38,14 V 44,67 V 44,82V 44,97 V 45,97 V 46,14 V 46,31 V 46,49 V

Isc (α) Temperature Coefficient 0,04%/ºC 0,04%/ºC 0,04%/ºC 0,04%/ºC

Voc (β) Temperature Coefficient -0,32%/ºC -0,32%/ºC -0,32%/ºC -0,32%/ºC

P (γ) Temperature Coefficient -0,43%/ºC -0,43%/ºC -0,43%/ºC -0,43%/ºC

Max. System Voltage 1000 V 1000 V 1000 V 1000 V

PHYSICAL CHARACTERISTICS

Dimensions (mm ± 2mm) 778x659x35 1476x659x35 1645x990x40 1965x990x40

Laminate Dim. (mm ± 2mm; Fig. 13) No No 1639x984x32 No


A (mm) (Figure 12) 619 619 938 938
B (mm) (Figure 12) 68 200 284,5 445,5
C (mm) (Figure 12) 192 416 500,5 660,5

D (mm) (Figure 12) 389 738 822,5 982,5

Weight (kg approx) 6,20 11,90 21,50 24


Frame type Hook V1 Hook V1 Hook V4 Hook V4

Connection Box (*) TYCO IP65 TYCO IP65 TYCO IP65 TYCO IP65
Cables (**) No No Yes (1100mm, Negro) Yes (1250mm, Negro)

Protection Diodes (Nº/Type) 2 / SCHOTTKY Sl1010 2 / SCHOTTKY Sl1010 3 / SCHOTTKY Sl1010 3 / SCHOTTKY Sl1010

Protection Diodes (Amperes/Vmax/Tj) 18A / 45V / m175ºC 18A / 45V / m175ºC 18A / 45V / m175ºC 18A / 45V / m175ºC
Max. Reverse Current (during 2h) 20,25 A 20,25 A 20,25 A 20,25 A
Serial Fuse (A) (***) 15 15 15 15
Max. Nº Modules in Serie 43 41 24 21
Max. Nº Modules in Parallel (****) 2 2 2 2

Electrical specifications measured in STC. TONC: 47±2ºC * Tyco Electronics Corporation. *** Overcurrent protection (Max.
Recommended).

** Solar Cable 4mm2 **** Without any additional protection.

EN-MU-41 (4)-E
9
Monocrystalline
ELECTRICAL CHARACTERISTICS A-75M A-80M A-150M A-160M A-250M A-255M A-260M A-265M A-270M A-295M A-300M A-305M A-310M A-315M A-320M

Format ½ 6” 4x9 6” 4x9 6” 6x10 6” 6x12

Power 75 W 80 W 150 W 160 W 250 W 255 W 260 W 265 W 270 W 295 W 300 W 305 W 310 W 315 W 320 W

Tolerance ± 8% ± 8% ± 5% ± 5% (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W) (0/+5 W)
MODULE

Number of cells in series 36 ½ 36 60 72

Module Efficiency 14,63% 15,60% 15,42% 16,45% 15,35% 15,66% 15,97% 16,27% 16,57% 15,16% 15,42% 15,68% 15,94% 16,19% 16,52%

Max. Power Current (Imp) 4,13 A 4,28 A 8,25 A 8,56 A 8,24 A 8,34 A 8,44 A 8,54 A 8,59 A 8,13 A 8,22 A 8,31 A 8,40 A 8,45 A 8,52 A
Installation and User Manual

Max. Power Voltage (Vmp) 18,21 V 18,63 V 18,21 V 18,63 V 30,35 V 30,57 V 30,79 V 31,03 V 31,44 V 36,31 V 36,51 V 36,71 V 36,91 V 37,30 V 37,56 V

Short-circuit Current (Isc) 4,39 A 4,55 A 8,79 A 9,11 A 8,79 A 8,89 A 8,99 A 9,04 A 9,07 A 8,68 A 8,76 A 8,84 A 8,92 A 8,94 A 8,99 A

Open Circuit Voltage (Voc) 22,57 V 22,84 V 22,57 V 22,84 V 37,62 V 37,76 V 37,90 V 38,40 V 38,65 V 44,37 V 44,63 V 44,89 V 45,15 V 45,72 V 46,08 V

Isc (α) Temperature Coefficient 0,03%/ºC 0,03%/ºC 0,03%/ºC 0,03%/ºC

Voc (β) Temperature Coefficient -0,34%/ºC -0,34%/ºC -0,34%/ºC -0,34%/ºC

P (γ) Temperature Coefficient -0,43%/ºC -0,43%/ºC -0,43%/ºC -0,43%/ºC

Max. System Voltage 1000 V 1000 V 1000 V 1000 V

PHYSICAL CHARACTERISTICS

Dimensions (mm ± 2mm) 778x659x35 1476x659x35 1645x990x40 1965x990x40

Laminate Dim. (mm ± 2mm; Fig. 13) No No 1639x984x32 No


A (mm) (Figure 12) 619 619 938 938
B (mm) (Figure 12) 68 200 284,5 445,5
C (mm) (Figure 12) 192 416 500,5 660,5

D (mm) (Figure 12) 389 738 822,5 982,5

Weight (kg approx) 6,20 11,90 21,50 24


Frame type Hook V1 Hook V1 Hook V4 Hook V4

Connection Box (*) TYCO ip65 TYCO IP65 TYCO IP65 TYCO Ip65
Cables (**) No No Yes (1100mm, Negro) Yes (1250mm, Negro)

Protection Diodes (Nº/Type) 2 / SCHOTTKY 2 / SCHOTTKY 3 / SCHOTTKY 3 / SCHOTTKY

Protection Diodes (Amperes/Vmax/Tj) 18A / 45V / m175ºC 18A / 45V / m175ºC 18A / 45V / m175ºC 18A / 45V / m175ºC

Max. Reverse Current (during 2h) 15,1 A 15,1 A 15,1 A 15,1 A


Serial Fuse (A) (***) 15 15 15 15
Max. Nº Modules in Serie 43 41 24 21
Max. Nº Modules in Parallel (****) 2 2 2 2

Electrical specifications measured in STC. TONC: 47±2ºC * Optionally ATERSA have available junction boxes with *** Overcurrent protection (Max.
QUAD (Ip54) version on request. Recommended).

** Solar Cable 4mm2 **** Without any additional protection.

EN-MU-41 (4)-E
10
ANNEX
Installation and User Manual
UNE-EN ISO 9001 UNE-EN ISO 14001 OHSAS 18001
ER-0979/1997 GA-2009/0396 SST-0134/2012

EN Professional Photovoltaic Module

ANNEX

Printed on recycled paper

Dispose of the device at an environmental disposal point when it reaches the end of its useful life

EN-MU-41 (4)-E
EN-MU-41 (4)-E
Module Laminate
A 32 984
Dimensions in mm
Dimensions in mm
11 General dimensions Polycrystalline modules

225±25.0
15
B

A
C

595±25.0
6,7 D

1639
*

595±25.0
40
38
HOOK V4

225±25.0
35
29
HOOK V1 A 80 mm.
5 11 mm. B 13 mm.
9 mm. B 10 mm. (6” 4x9 / ½ 6” 4x9)
* The areas marked in the drawing (A and B) are intended for the
fixation of the laminate and ensure proper installation.
ANNEX

Always use fastening systems that do not damage the


laminate/module
EN-MU-41 (4)-E
Module Laminate
A 32 984
Dimensions in mm
Dimensions in mm
12 General dimensions Monocrystalline modules

225±25.0
15
B

A
C

595±25.0
6,7 D

1639
*

595±25.0
40
38
HOOK V4

225±25.0
35
29
HOOK V1 A 80 mm.
5 11 mm. B 13 mm.
9 mm. B 10 mm. (6” 4x9 / ½ 6” 4x9)
* The areas marked in the drawing (A and B) are intended for the
fixation of the laminate and ensure proper installation.
ANNEX

Always use fastening systems that do not damage the


laminate/module
ANNEX

13 Module assembly drawings depending on the applied mechanical load


Polycrystalline and Monocrystalline
13.1
2400Pa
Clamping method Hook M8 (*) Clamping method Other(*)
Long side Long side
0000000000000

0000000000000
Guide instertion Clamping method Hook M8 (*) Clamping method Other(*)
Short side Short side
0000000000000

0000000000000

0000000000000
13.2 Module with 72 cells and 4.0 mm. of thickness of the glass.
5400Pa With 3.2 mm. 2.400 Pa.

Clamping method Hook M8 (*) Clamping method Other(*) Directly on the Structure
Long side Screws
A Long side A B B
0000000000000

0000000000000

B B B B B B

Distance A: 60mm (Minimum)/ Distance B: module 72 cells B = 445.5 mm; modulel 60 cells B = 284.5 mm

14 Laminate assembly drawings depending on the applied mechanical load


14.1 Laminates 60 cells 2400Pa
Special clamps for laminates (*)
E F E F
G
0000000000000

E
F 80 mm.
11 mm. G 13 mm.
E = 225 ± 25.0 mm
E E Using two sidebars at distance E from
Long side the edge and a central.

(*) The areas marked in the drawing (A and B) are intended for the fixation of the laminate and ensure
proper installation.
Always use fastening systems that do not damage the laminate.
According to standard IEC 61215:2005
Note: ATERSA reserves the right to modify the product specifications without notice.
For more extensive information about the terms of the warranty and certificates y, please see our website: www.atersa.com

EN-MU-41 (4)-E