Professional Documents
Culture Documents
Draft Report
Report
September
2018
Conducted by
Aastha Engineering Solution
Pvt. Ltd.
September- 2018
CONTENTS
LIST OF FIGURES ........................................................................................................................................ 4
Study Team ..................................................................................................................................................... 5
DIAGNOSTIC INSTRUMENTS DEPLOYED DURING ENERGY AUDIT .............................................. 5
abbreviations ................................................................................................................................................... 6
Executive Summary ........................................................................................................................................ 7
1.0 Introduction .............................................................................................................................................. 9
1.1 About Dinning Park Restaurant & Lounge Bar .................................................................................... 9
2.0 BUILDING ENERGY SYSTEMS: SALIENT FEATURES ............................................................. 10
2.1 Electricity Mains Supply ................................................................................................... 10
2.2 Connected Electrical Loads ............................................................................................... 10
2.3 Energy Consumption during study period ......................................................................... 11
2.4 Month-wise Energy Consumption ..................................................................................... 12
2.5 Specific Energy Consumption ........................................................................................... 12
2.6 Unit Energy Charge (NRs. per kWh)................................................................................. 13
3.0 Energy Conservation (ENCON) Opportunities......................................................................................... 14
3.1: Energy Saving Opportunities by Switching into LED Lights .......................................... 14
3.2: Energy Saving Opportunity by changing route of the 3-phase supply to the kitchen
building .................................................................................................................................... 15
3.3: Energy Conservation by phase balance ............................................................................ 17
3.4: Demand Charge Reduction by Load Shifting:.................................................................. 18
3.5: Energy Conservation by Rerouting of Inverter Line: ....................................................... 18
3.6: Energy Conservation by Replacing old Induction motor: ................................................ 19
3.7: Energy Conservaion by Reactive power Compensation: ................................................. 19
4.0 Application of Renewable Energy Technologies ..................................................................................... 21
4.1 Installation of Solar Photovoltaic Power System .............................................................. 21
5.0 No cost Imporvement and visibilty oppurtunity within the building...................................................... 24
5.1 Achieving Energy Efficiency through Behavioral Change ............................................... 24
LIST OF FIGURES
Figure 1 Satellite View of Dinning Park Restaurant and Lounge Bar ............................................................. 9
Figure 2 Contribution of different types of loads ......................................................................................... 11
Figure 3 Building wise installed Load and Daily Energy Consumption Pattern............................................. 15
Figure 4 Proposed Rerouting of Supply to kitchen DB ................................................................................. 16
Figure 5 Comparison of Phase currents Dinning Park .................................................................................. 17
Figure 6 Demand Pattern Dinning Park......................................................................................................... 18
Figure 7 Space to place PV modules on Dinning Park ................................................................................... 21
STUDY TEAM
ABBREVIATIONS
AC Air Conditioning
DB Distribution Board
DG Diesel Generator
PF Power Factor
PV Photovoltaic
UV Ultra Violet
EXECUTIVE SUMMARY
Rationale
construction, and operations in this age. As a project delivery firm with a national grasp, we believe
the challenge is in the planning, not the executing. Our activities span the full spectrum of facility,
technology and process design; by applying technology and innovation optimally to these, our
Dining Park Restaurant and Bar have embarked upon a effort to reduce their energy consumption
and costs and as a result making their services more cost competitive, the business more profitable,
and as a result reduce their businesses carbon footprint. The Dining Park Restaurant was selected as
the facility for Aastha Engineering Solution Pvt. Ltd. to conduct energy audit. Any energy
conservation measures recommended in this report have proven as commercially reliable based on
The energy audit at Dining Park premises was conducted in the month of September 2018, covering
The Dining Park is located at Old-Baneshwor, Kathmandu and has three building including a
banquet a with a total built up floor area of 1,571 square meters
The electricity used for the audited building is received through 11 kV NEA feeder line which
supplies power to the all buildings within the premises through a 11/0.4 kV transformer of 100
kVA capacity.
A TOD meter has been installed for the building to measure its electrical consumption and
was upgraded from 50 kVA to 100 kVA since Jestha of 2075.
The monthly maximum demand recorded during the audited period (month of September) was
found to be 30 kVA, as against the total connected load of 56 kW.
The average daily consumption for the month of September was found to be 501 kWh per day,
out of which 168 kWh was the consumption during peak hour, 290 kWh was the consumption
during normal hour and 43 kWh was the consumption during off-peak hour.
There is also provision of backup diesel generator of 125 kVA supply to the building.
The major electrical loads of the building consist of ovens, fridges, lights, fans, office
computers, printers, photocopy machines, split-type air conditioning units and electrical
heating and cooking units.
Energy Conservation Proposals and Payback Summary:
The total annual energy consumption of the building was estimated to be 1,42,227 kWh while the identified
annual energy savings potentials add up to 45,986 kWh amounting to 32.33 % of the consumption. The
following table lists the top six energy saving opportunities that resemble savings of worth 4.93 Lakh NRs
annually, against an investment of 9.49 Lakh NRs and offer an overall simple payback period of 2.22 Years.
Rerouting of Inverter
4 Line 8,870 95,179 50,000 0.5253238
Installation of 9 kWp
Solar PV module for
5 10657.17 1,14,351 7,20,000 6.29
10 % of total
Electrical Load
Energy Conservation
by balancing Phases
6 Significant Signigicant Less Less
1.0 INTRODUCTION
1.1 About Dinning Park Restaurant & Lounge Bar
Dinning Park Restaurant& Lounge Bar is a finest and luxurious multi-cuisine restaurant located in
the booming, and rapidly expanding education and Business hub area at Mid - Baneshwor. The
property addresses intriguing atmosphere that blends with hygienic and excellent taste of food
accompanied by warm and friendly service with total seating capacity of 200. It is accessible in 10-
15 drive from International Airport and 15- minute walking distance from the Pashupati Nath
Temple.
The kitchen building had the highest connected load as well as the highest monthly energy
consumption, followed by banquet building and kitchen building.
Energy Energy
Building Load (kWh) (kWh) per
(kW) per day month
Banquet 17.574 134.936 4048.08
Admin
Building 12.926 84.436 2533.08
kitchen
building 24.557 251.084 7532.52
Total 55.057 470.456 14113.68
At present there are 57 numbers of Fluorescent Tube Lights (FTL), 17 CFLs of each 12 watt are mounted in
the various locations of the audited buildings. The FTL consumes typically 40watt as the tubes are fitted
along with the inefficient electro-magnetic chokes.
Recommendation:
It is recommended to replace the FTL and CFL devices by energy efficient LED lights (LED=Light emitting
diode) as per following Cost Benefit Table.
Table 5 Recommended Summary and Simple Payback period for switching to LED light
3.2: Energy Saving Opportunity by changing route of the 3-phase supply to the kitchen
building
Present Situation
Though banquet load center is far from MDB we didn't observe significant voltage drop since it is
lightly loaded and also due to high value of diversity factor. But Kitchen Building is the heavily
loaded building among other building it is suffered from significant voltage drop. Sometimes L-N
(Line to Neutral) voltage is observed around 200 V.
Figure 3 Building wise installed Load and Daily Energy Consumption Pattern
kWh
Average Monthly Energy consumption in Kitchen 7532.52
kWh
Average Annual Energy consumption in Kitchen 90390.24
V
Observed voltage (average) 205
9825.0261 kWh
Energy loss due to voltage drop
Recommendation:
It is recommended to supply DB on ground floor of kitchen building directly from MDB as per
cost benefit table as below:
Here 3- Phase is not in the balanced condition which leads to unequal voltage across the phases and
circulating currents will cause internal heating of transformer. It is also reducing the performance
of the three phase machines. Form our measurement as well as TOD meter reading of September
2018 the blue phase is most loaded phase where yellow phase is lightly loaded.
Recommendation:
It is recommended to balance phases by shifting some of the heavy loads to lightly loaded phases.
Here we can shift 5 kVA inverter which is connected in Blue Phase in Kitchen DB through 32 A
MCB to Yellow Phase.
Here demand curve is not uniform showing extreme variation in connected loads in whole day.
NEA apply Demand Charge of 315 per KVA.
Recommendation:
It is recommended to shift non- emergency loads like Water filters, Pump running Induction
motors to off- peak time to reduce Demand Charge as load shifting is most key aspect of demand
management.
Here as we measured the out-going current from inverter we found that there is significant difference
in current going from live and returning from neutral suggesting there is leakage of currents to the
Earth. We observe this difference in current up to 12A. Here inverter is supplying most of the
lighting loads and important devices like computers etc.
Recommendation:
It is recommended to Re-route the supply from the inverter by maintaining proper insulation and
Earthing with sufficient earth resistance.
Here the motor on the way to banquet hall is very old and performance is very poor. We can see the
performance table as below:
Recommendation:
Here more than 50% of the load consists of inductive loads. But no power factor correction
measures are taken. It will increase demand charge and copper loss of transformer and conductors.
Recommendation:
It is recommended to install fixed capacitor bank of capacity 20kVAR. It will save electricity bills
mainly by two way:
Here,
Reduction in Energy loss due to capacitor bank= 11.87% *70525 kWh =8371
Annual
Energy
saving 8371.39643 kWh
Total
annual
saving 89825.0837 NRs.
Investment 150000 NRs.
Simple pay
back
period 1.66991216 year
30 solar PV modules (each 315 Wp) of dimension 1954mm ˣ 982mmm can be used to generate solar
energy. The tilt angle of 25 degree has been considered in this case. The solar electricity generated
during the day time could be used in the same building and at the same time the surplus electricity
could be feed to the NEA grid line.
The estimated energy generation from the solar PV System is calculated below:
There are also 8 pieces of 12 V, 200 Ah flooded lead acid batteries operating 5kVA single phase
inverter surplus energy can be stored in it. Considering DOD and efficiency it can supply 13.68
kWh of energy to the load which will reduce peak demand charge which is NRs. 315 per kW.
Battery Size (Ah) Nos DOD Voltage (V) Efficiency Total capacity watt hour
200 8 0.75 12 0.95 13680
Social science can improve our understanding of individual and societal responses to their
surroundings; it has been used to investigate people's relationship with energy, energy use and
energy efficiency behavior change initiatives/measures. Behavior change to reduce energy
consumption is complex and involves a wide range of different possible measures to address it but
following measures are applicable on such behavior change.
Feedback measures: Putting display board of the energy consumption per day at the entrance
of the building. Block metering and communicating with staffs.
Policy, Communication and engagement: Energy saving awareness within the staffs. Some
cases even small penalty system can be experimented. Green staff reward concept could be
useful tool for changing the behavior.
Technological interventions with smart switch, timer switch and occupancy sensors.
Centralized switching mechanism for each floor in which the switching off could be possible
measure for the holidays and off-hours.
About 4 to 5% energy could be saved from the use of electrical equipments such as lighting,
computer, fan, A/Cs and heaters.