Professional Documents
Culture Documents
Abstract-For a vertically integrated utility in a developing country, Several recent DGA data along with historically available
the diagnosis of oil-immersed power transformers condition is not data can be used to evaluate and diagnose the condition of an
frequently performed due to limited budget and lack of past aged transformer. However, these are not easy to implement
historical data. Dissolved Gas Analysis (DGA) for oil samples has by a regulated utility authority in a developing country where
been the most widely used diagnosis tool for transformer condition
assessment for many years. However, the interpretation of DGA
the reliability is not the main concern. Delivering the energy to
results becomes very difficult and uncertain when only one or two the end users is a key objective. The main concern is to supply
sets of data are available. The aim of this paper is to address the the power to a large population, where the growth is
issue of DGA interpretation with very limited test data. This paper tremendous. Condition assessment becomes a challenging task,
will present DGA tests results from 38 power transformers in a due to the limited budget and lack of past historical data.
developing country and will propose a maintenance decision
making procedure using the IEC 60599-2007 and Duval’s Triangle The aim of this paper is to address the issue of DGA
schemes. Limitation of the methodology proposed in this paper and interpretation with very limited test data. This paper presents
further possible development will also be highlighted in this paper.1 DGA tests results from 38 power transformers in a developing
country and will propose a maintenance decision making
I. INTRODUCTION procedure using the IEC 60599-2007 and Duval’s triangle.
Limitation of the methodology proposed in this paper and
Oil-immersed power transformers are one of the most further possible development will also be highlighted in this
critical and expensive assets in power network. These are paper.
sealed equipments with major parts (core, coils) are being
immersed in oil. Analysis of transformer oil is frequently used
for transformer condition assessment. This is often done by
useful test on transformer oil, known as Dissolved Gas-in-Oil II. A BRIEF REVIEW ON IEC 60599- 2007
Analysis, DGA [1]. 2
IEC 60599- 2007 provides practical guides in interpreting
dissolved gas-in-oil in electrical equipment. This standard
The author *) would like to acknowledge with thanks to PT. guide gives high diagnostic accuracy by using ratio-based
Indonesia Power for the opportunity to pursue Master of diagnostic method [1, 5]. Using this guide, three main steps are
Engineering Program in School of Information Technology followed to diagnose the condition of a transformer [3].
and Electrical Engineering, University of Queensland during
2007-2008, through the master degree scholarship program 1) Typical values evaluation
based on SK Direksi No.93.K/010/IP/2006. The DGA data from a particular transformer must be
evaluated by two typical values: typical concentration values
2 and rate of increase of different gases.
2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-073 page 1
with incipient fault diagnosis and evaluation must be followed %CH4 = [CH4/(CH4+C2H4+C2H2)]x100% (4)
by a ratio-based diagnostic method and single gas ratio
method. IEC 60599- 2007 introduces gas typical %C2H4 = [C2H4/(CH4+C2H4+C2H2)]x100% (5)
concentration value as shown at Table I. This standard
strongly recommends that every individual network must %C2H2 = [C2H2/(CH4+C2H4+C2H2)]x100% (6)
build their own typical concentration values, since nature of
each network will differ from one to another. However, if
there are no other experience and data available, those values BGR and Duval’s Triangle can be represented in graphical
may be used as initial guidelines [2]. form where the ratios become the coordinates of the point in
the graph (Fig. 1 and 2). The point will give diagnosis on a
TABLE I particular incipient fault in transformer. Note that the “red dot”
RANGES OF 90% TYPICAL GAS CONCENTRATION VALUES OBSERVED IN on the graphical representation informs the type of fault
POWER TRANSFORMERS IN PPM [3]
condition for particular transformer.
All Transformers NO OLTC Communicating OLTC
C2H2 - 2-20 60-280
H2 50-150 Six types of incipient faults can be diagnosed. Those are
CH4 30-130 partial discharge (PD), low energy discharge (D1), high energy
C2H4 60-280 discharge (D2), thermal fault type T1 (Temp.< 300°C),
C2H6 20-90 thermal fault type T2 (300°C < Temp.<700°C) and thermal
CO 400-600
CO2 3800-14000
fault type T3 (Temp.>700°C).
TABLE II
Discharge of high energy fault may include power follow-
RANGES OF 90% TYPICAL RATE OF GAS INCREASE OBSERVED IN POWER through on the equipment which will be evidenced by paper
TRANSFORMERS (PPM/YEAR) [3] destruction and carbonization, metal fusion and also
All Transformers NO OLTC Communicating OLTC carbonization in oil.
C2H2 - 0-4 21-37
H2 35-132
CH4 10-120
Brownish paper will be the evidence for thermal fault with
C2H4 32-146 temperature below 300°C. For thermal fault with temperature
C2H6 5-90 at 300°C < T < 700°C paper carbonization become the
CO 260-1060 evidence. Oil carbonization, metal coloration or metal fusion
CO2 1700-10000 are the evidence for thermal fault with temperature above
700°C.
R1 = C2H2/C2H4 (1)
R2 = CH4/H2 (2)
R3 = C2H4/C2H6 (3)
2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-073 page 2
Figure 1.a. BGR (C2H2/C2H4,CH4/H2) on Sumatra Island, Indonesia. They are located in the area
which has ambient temperature between 23°-32°C and
humidity between 61-98% along the year. Note that all
transformers are equipped with On Load Tap Changer (OLTC)
facilities.
2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-073 page 3
TABLE VI
SINGLE GAS RATIO INTERPRETATION RESULTS ON
71%
80% 11 FAULTY TRANSFORMERS
70% Single Gas Ratio Results
Numbers 60% Tag. Paper Excessive O2 Communica
ofTransform 50% Involvement Consumption ting OLTC
ers (%) 29%
40%
30% T-003 No Yes No
20% T-006 No Yes No
10% T-008 No Yes No
0% T-009 No Yes No
healthy considered fault
T-012 No No Yes
Transformers Diagnosis
T-022 No Yes No
T-023 No Yes No
Figure 3. Typical concentration values evaluation result T-027 No Yes No
T-031 No Yes No
Rate of increase of different gases evaluation could not be T-032 No Yes No
performed since the DGA data were only single data. No T-034 No No Yes
previous data were available.
The eleven transformers with incipient fault diagnosis were After the implementation of Single Gas Ratio Method,
then evaluated using two main ratio-based diagnostic complementary diagnosis has been achieved to support the
methods, BGR and Duval’s Triangle. In this step, the type of diagnosis results from the main ratio-based diagnostic
fault in a particular transformer could be diagnosed (Table V). methods. Table VI has summarized those complementary
diagnoses.
2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-073 page 4
However, more comprehensive results in fault diagnosis
can be established when the DGA data results are also been
completed with
1. Multi point DGA result data, in order to analyze the
severity and evolution of fault.
2. Typical values for power transformers in the
corresponding network, including typical concentration
values and typical rate of gas increase.
3. Transformer data, such as manufacture and operation
year, loading data, fault history data, oil treatment history
data, type of oil preservation system data, numbers of
OLTC operation data.
4. Laboratory accuracy data from the laboratory who
conduct the dissolved gas in oil analysis, in order to
analyze the uncertainty of diagnosis (determines the
confident level in diagnosing) [2].
5. Another complementary test results data such as furanic
compounds analysis or degree of polymerization
measurement to analyze paper involvement.
VI. CONCLUSIONS
REFERENCES
[1]. L. R. Lewand- Doble Engineering Company, “Techniques for
Interpretation of Data for DGA from Transformers”, IEEE Conference,
2006
[2]. M. Duval and J. Dukarm, ”Improving the Reliability of Transformer
Gas-in-Oil Diagnosis”, IEEE Elec. Insul. Mag. Vol. 21, No. 4, pp. 21-
27, 2005
[3]. Mineral Oil-Impregnated Electrical Equipment in Service- Guide to the
Interpretation of Dissolved and Free Gases Analysis, IEC Publication
60599 (2007).
[4]. Oil-Filled Electrical Equipment- Sampling of Gases and of Oil for
Analysis of Free and Dissolved Gases- Guidance, IEC Publication
60567 (2005)
[5]. Serveron Corp., “DGA Diagnostic Methods”, Serveron White Paper,
2007
2008 Australasian Universities Power Engineering Conference (AUPEC'08) Paper P-073 page 5