You are on page 1of 15

1.3.1.1 Drawing Sheet Sizes. work practices, and selecting personal protective equipment.

FPN No. 2: ANSI Z535.4-1998, Product Safety Signs and Labels,


(a) Electrical plans and drawings shall be drawn provides
on drawing sheets guidelines for the design of safety signs and labels for application
of the following standard sizes: to products.

760 mm x 1 000 mm ----------------------------------------------------------------


600 mm x 900 mm
500 mm x 760 mm (e) Headroom. The minimum headroom of
(b) In cases such as projects of large magnitude, working spaces about
exemption in the ervice equipment, switchboards, panelboards, or
use of the standard drawing sheets may be motor control
granted by the office of the centers shall be 2 000 mm. Where the electrical
local building official. Refer to Appendix E. equipment exceeds
(c) For a dwelling unit having a floor area of not 2 000 m in height, the minimum headroom shall
more than 50 not be less than the
square meters with a total load not exceeding 3 height of the equipment.
680 VA, a drawing Exception: In existing dwelling units, service
sheet of size 297 mm x 420 mm (A3 size) is equipment or
permitted. panelboards that do not exceed 200 amperes
shall be permitted in
----------------------------------------------------------
paces where the headroom is less than 2 000
1.10.1.16 Flash Protection. Switchboards, mm.
panelboards, industrial
----------------------------------------------------------
control panels, meter socket enclosures, and
motor control centers that (a) Occupancy Limitation. In dwelling units
are in other than dwelling occupancies and are and guest rooms or
likely to require guest suites of hotels, motels, and similar
examination, adjustment, servicing, or occupancies, the voltage
maintenance while energized shall not exceed 230 volts, nominal, between
shall be field marked to warn licensed electrical conductors that supply
practitioner or nonlicensed electrical practitioner the terminals of the following:
under the supervision of a licensed (1) Luminaires (lighting fixtures)
electrical practitioner of potential electric arc (2) Cord-and-plug-connected loads 1440 volt-
flash hazards. The amperes, nominal,
marking shall be located so as to be clearly or less or less than ¼ hp
visible to licensed
electrical practitioner or non-licensed electrical ----------------------------------------------------------------
practitioner under the
2.10.1.8 Ground-Fault Circuit-Interrupter
supervision of a licensed electrical practitioner
Protection for
before examination,
Personnel.
adjustment, servicing, or maintenance of the FPN: See 2.15.1.9 for ground-fault circuit-interrupter protection
equipment. for personnel on
FPN No. 1: NFPA 70E-2004, Standard for Electrical Safety in the feeders.
Workplace, (a) Dwelling Units. All 125-volt and/or 250
provides assistance in determining severity of potential exposure,
planning safe
volts, single-phase, 15-
and 20-ampere receptacles installed in the two appliances located within dedicated space
locations specified in (1) for each appliance that,
through (8) shall have ground-fault circuit- in normal use, is not easily moved from one
interrupter protection for place to another and that
personnel. is cord-and-plug connected in accordance with
(1) Bathrooms 4.0.1.7(a)(6), (a)(7),
(2) Garages, and also accessory buildings that or (a)(8).
have a floor located Exception No. 3 to (5): A receptacle supplying
at or below grade level not intended as habitable only a permanently
rooms and limited to installed fire alarm or burglar alarm system
storage areas, work areas, and areas of similar shall not be required to
use have ground-fault circuit-interrupter protection.
Exception No. 1 to (2): Receptacles that are not (6) Kitchens — where the receptacles are
readily accessible. installed to serve the
Exception No. 2 to (2): A single receptacle or a countertop surfaces
duplex receptacle for (7) Laundry, utility, and wet bar sinks — where
two appliances located within dedicated space the receptacles are
for each appliance that, installed within 1 800 mm of the outside edge of
in normal use, is not easily moved from one the sink
place to another and that (8) Boathouses
is cord-and-plug connected in accordance with
4.0.1.7(a)(6), (a)(7), 2.10.1.11 Branch Circuits Required. Branch
or (a)(8). circuits for lighting and
Receptacles installed under the exceptions to for appliances, including motor-operated
2.10.1.8(a)(2) shall appliances, shall be provided
not be considered as meeting the requirements of to supply the loads calculated in accordance with
2.10.3.3(g) 2.20.2.1. In addition,
(3) Outdoors. Receptacles installed under the branch circuits shall be provided for specific
exceptions to loads not covered by
2.10.1.8(a)(5) shall not be considered as meeting 2.20.2.1 where required elsewhere in this Code
the requirements of and for dwelling unit
2.10.3.3(g). loads as specified in 2.10.1.11(c).
(4) Crawl spaces — at or below grade level (a) Number of Branch Circuits. The minimum
(5) Unfinished basements — for purposes of this number of branch
section, circuits shall be determined from the total
unfinished basements are defined as portions or calculated load and the size
areas of the basement or rating of the circuits used. In all installations,
not intended as habitable rooms and limited to the number of circuits
storage areas, work shall be sufficient to supply the load served. In
areas, and the like no case shall the load
Exception No. 1 to (5): Receptacles that are not on any circuit exceed the maximum specified by
readily accessible. 2.20.2.9.
Exception No. 2 to (5): A single receptacle or a (b) Load Evenly Proportioned Among
duplex receptacle for Branch Circuits. Where
the load is calculated on the basis of volt- 2.10.1.12 Arc-Fault Circuit-Interrupter
amperes per square meter or Protection.
per square foot, the wiring system up to and (a) Definition: Arc-Fault Circuit Interrupter.
including the branchcircuit panelboard(s) shall An arc-fault circuit
be provided to serve not less than the interrupter is a device intended to provide
calculated load. This load shall be evenly protection from the effects
proportioned among of arc faults by recognizing characteristics
multioutlet branch circuits within the unique to arcing and by
panelboard(s). Branch-circuit functioning to de-energize the circuit when an
overcurrent devices and circuits shall only be arc fault is detected.
required to be installed (b) Dwelling Unit Bedrooms. All 115-volt
to serve the connected load. and/or 230-volt, single
(c) Dwelling Units. phase, 15- and 20-ampere branch circuits
(1) Small-Appliance Branch Circuits. In addition supplying outlets installed in
to the number of dwelling unit bedrooms shall be protected by a
branch circuits required by other parts of this listed arc-fault circuit
section, two or more 20- interrupter, combination type installed to
ampere small-appliance branch circuits shall be provide protection of the
provided for all branch circuit. This requirement shall become
receptacle outlets specified by 2.10.3.3(b). effective January 1,
(2) Laundry Branch Circuits. In addition to the 2014.
number of branch FPN: For information on types of arc-fault circuit interrupters, see
UL 1699-1999,
circuits required by other parts of this section, at Standard for Arc-Fault Circuit Interrupters.
least one additional Exception: The location of the arc-fault circuit
20-ampere branch circuit shall be provided to interrupter shall be
supply the laundry permitted to be at other than the origination of
receptacle outlet(s) required by 2.10.3.3(f). This the branch circuit in
circuit shall have no compliance with (a) and (b):
other outlets. (a) The arc-fault circuit interrupter installed
(3) Bathroom Branch Circuits. In addition to the within 1800 mm of the
number of branch branch circuit overcurrent device as measured
circuits required by other parts of this section, at along the branch
least one 20-ampere circuit conductors.
branch circuit shall be provided to supply (b) The circuit conductors between the branch
bathroom receptacle circuit overcurrent
outlet(s). Such circuits shall have no other device and the arc-fault circuit interrupter shall
outlets. be installed in a metal
Exception: Where the 20-ampere circuit supplies raceway or a cable with a metallic sheath.
a single bathroom,
outlets for other equipment within the same 2.10.2.3 Outlet Devices. Outlet devices shall
bathroom shall be have an ampere rating
permitted to be supplied in accordance with that is not less than the load to be served and
shall comply with
2.10.2.5(a)(1) and (a)(2).
FPN: See Examples D1(a), D1(b), D2(b), and D4(a) in Appendix
2.10.2.3(a) and (b).
D. (a) Lampholders. Where connected to a branch
circuit having a (3) Receptacle Ratings. Where connected to a
rating in excess of 20 amperes, lampholders branch circuit
shall be of the heavy-duty supplying two or more receptacles or outlets,
type. A heavy-duty lampholder shall have a receptacle ratings shall
rating of not less than 660 conform to the values listed in Table
watts if of the admedium type, or not less than 2.10.2.3(b)(3), or where larger
750 watts if of any than 50 amperes, the receptacle rating shall not
other type. be less than the
(b) Receptacles. branch-circuit rating.
(1) Single Receptacle on an Individual Branch Exception No. 1: Receptacles for one or more
Circuit. A single cord-and-plugconnected arc welders shall be
receptacle installed on an individual branch permitted to have ampere ratings not
circuit shall have an less than the minimum branch-circuit conductor
ampere rating not less than that of the branch ampacity permitted
circuit. by 6.30.2.1(a) or (b) as applicable for arc
Exception No. 1: A receptacle installed in welders.
accordance with Exception No. 2: The ampere rating of a
4.30.7.1(b). receptacle installed for
Exception No. 2: A receptacle installed electric discharge lighting shall be permitted to
exclusively for the use of a be based on
cord-and-plug-connected arc welder shall be 4.10.6.9(c).
permitted to have an Table 2.10.2.3(b)(3) Receptacle Ratings for
ampere rating not less than the minimum Various Size Circuits
branch-circuit conductor Circuit Receptacle
ampacity determined by 6.30.2.1(a) for arc Rating Rating
welders. (Amperes) (Amperes)
FPN: See the definition of receptacle in Article 1.0. Not over
(2) Total Cord-and-Plug-Connected Load. 15
15
Where connected to a 20
15 or 20
branch circuit supplying two or more receptacles 30
30
or outlets, a 40
40 or 50
receptacle shall not supply a total cord-and-plug- 50
50
connected load in (4) Range Receptacle Rating. The ampere rating
excess of the maximum specified in Table
of a range
2.10.2.3(b)(2).
Table 2.10.2.3(b)(2) Maximum Cord-and- receptacle shall be permitted to be based on a
Plug-Connected single range demand
Load to Receptacle load as specified in Table 2.20.3.16.
Rece 2.10.2.5 Permissible Loads. In no case shall the
Circ
ptacl Maxi load exceed the
uit
e mum branch-circuit ampere rating. An individual
Ratin
Ratin Load
g branch circuit shall be
g (Am
(Am permitted to supply any load for which it is
(Am peres
peres rated. A branch circuit
peres )
)
) supplying two or more outlets or receptacles
15 or shall supply only the
15 12
20 loads specified according to its size as specified
20 16
20 in 2.10.2.5(a) through
30 24
30
(d) and as summarized in 2.10.2.6 and Table
2.10.2.6. or 50-ampere
(a) 15- and 20-Ampere Branch Circuits. A 15- branch circuit shall be permitted to supply
or 20-ampere cooking appliances that are
branch circuit shall be permitted to supply fastened in place in any occupancy. In other than
lighting units or other dwelling units, such
utilization equipment, or a combination of both, circuits shall be permitted to supply fixed
and shall comply with lighting units with heavyduty lampholders,
2.10.2.5(a)(1) and (a)(2). infrared heating units, or other utilization
Exception: The small appliance branch circuits, equipment.
laundry branch (d) Branch Circuits Larger Than 50
circuits, and bathroom branch circuits required Amperes. Branch circuits
in a dwelling unit(s) larger than 50 amperes shall supply only
by 2.10.1.11(c)(1), (c)(2), and (c)(3) shall supply nonlighting outlet loads.
only the receptacle 2.10.2.6 Branch-Circuit Requirements —
outlets specified in that section. Summary.
(1) Cord-and-Plug-Connected Equipment Not The requirements for circuits that have two or
Fastened in Place. more outlets or
The rating of any one cord-and-plug-connected receptacles, other than the receptacle circuits of
utilization equipment 2.10.1.11(c)(1) and
not fastened in place shall not exceed 80 percent (c)(2), are summarized in Table 2.10.2.6. This
of the branch-circuit table provides only a
ampere rating. summary of minimum requirements. See
(2) Utilization Equipment Fastened in Place. The 2.10.2.1, 2.10.2.2, and
total rating of 2.10.2.3 for the specific requirements applying
utilization equipment fastened in place, other to branch circuits.
than luminaires (lighting 2.10.2.7 Common Area Branch Circuits.
fixtures), shall not exceed 50 percent of the Branch circuits in dwelling
branch-circuit ampere units shall supply only loads within that
rating where lighting units, cord-and-plug- dwelling unit or loads
connected utilization associated only with that dwelling unit. Branch
equipment not fastened in place, or both, are circuits required for
also supplied. the purpose of lighting, central alarm, signal,
(b) 30-Ampere Branch Circuits. A 30-ampere communications, or
branch circuit shall other needs for public or common areas of a
be permitted to supply fixed lighting units with two-family or multifamily
heavy-duty dwelling shall not be supplied from equipment
lampholders in other than a dwelling unit(s) or that supplies an
utilization equipment in individual dwelling unit.
any occupancy. A rating of any one cord-and-
Table 2.10.2.6 Summary of Branch-Circuit
plug-connected
Requirements
utilization equipment shall not exceed 80 Circuit
15 A 20 A 30 A 40 A 50 A
percent of the branch-circuit Rating
ampere rating. Conduc
14 12 10 8 6
tors
(c) 40- and 50-Ampere Branch Circuits. A 40- 14 14 14 12 12
(min.
size): flexible cords are permitted to be permanently
Circuit connected, receptacles
wires1
Taps
shall be permitted to be omitted for such cords.
Fixture (c) Appliance Outlets. Appliance receptacle
wires outlets installed in a
and dwelling unit for specific appliances, such as
cords
— see laundry equipment, shall
2.40.1. be installed within 1 800 mm of the intended
5 location of the appliance.
Overcu 2.10.3.3 Dwelling Unit Receptacle Outlets.
rrent
15 A 20 A 30 A 40 A 50 A This section provides
Protect
ion requirements for 125-volt, 15- and 20-ampere
Outlet receptacle outlets.
devices Receptacle outlets required by this section shall
:
Any be in addition to any
Lamph Any Heav
type Heavy Heav receptacle that is part of a luminaire (lighting
olders type y duty
15 duty y duty
permitt 15 or 40 or fixture) or appliance,
max. 30 A 50 A
ed 20 A 50 A
A located within cabinets or cupboards, or located
Recept
acle more than 1 700 mm
rating2 above the floor.
Maxim Permanently installed electric baseboard heaters
um 15 A 20 A 30 A 40 A 50 A
equipped with
Load
Permiss See See See See See factory-installed receptacle outlets or outlets
ible 2.10.2 2.10.2 2.10.2 2.10.2 2.10.2 provided as a separate
load .5(a) .5(a) .5(b) .5(c) .5(c) assembly by the manufacturer shall be permitted
1These gauges are for copper conductors. as the required outlet
2For receptacle rating of cord-connected electric-
or outlets for the wall space utilized by such
discharge luminaires (lighting fixtures), see
permanently installed
4.10.6.9(c).
heaters. Such receptacle outlets shall not be
connected to the heater
circuits.
2.10.3 Required Outlets FPN: Listed baseboard heaters include instructions that may not
permit their
2.10.3.1 General. Receptacle outlets shall be
installation below receptacle outlets.
installed as specified in (a) General Provisions. In every kitchen,
2.10.3.3 through 2.10.3.14. family room, dining
(a) Cord Pendants. A cord connector that is room, living room, parlor, library, den, sunroom,
supplied by a bedroom, recreation
permanently connected cord pendant shall be room, or similar room or area of dwelling units,
considered a receptacle receptacle outlets
outlet. shall be installed in accordance with the general
(b) Cord Connections. A receptacle outlet shall provisions specified
be installed in 2.10.3.3(a)(1) through (a)(3).
wherever flexible cords with attachment plugs (1) Spacing. Receptacles shall be installed so
are used. Where that no point
measured horizontally along the floor line in any individual branch circuit
wall space is more rated 15 amperes or greater.
than 1 800 mm from a receptacle outlet. (2) No Other Outlets. The two or more small-
(2) Wall Space. As used in this section, a wall appliance branch
space shall include circuits specified in 2.10.3.3(b)(1) shall have no
the following: other outlets.
a. Any space 600 mm or more in width Exception No. 1: A receptacle installed solely
(including space for the electrical supply
measured around corners) and unbroken along to and support of an electric clock in any of the
the floor line by rooms specified in
doorways, fireplaces, and similar openings 2.10.3.3(b)(1).
b. The space occupied by fixed panels in exterior Exception No. 2: Receptacles installed to
walls, provide power for
excluding sliding panels supplemental equipment and lighting on gas-
c. The space afforded by fixed room dividers fired ranges, ovens, or
such as counter-mounted cooking units.
freestanding bar-type counters or railings (3) Kitchen Receptacle Requirements.
(3) Floor Receptacles. Receptacle outlets in Receptacles installed in a
floors shall not be kitchen to serve countertop surfaces shall be
counted as part of the required number of supplied by not fewer
receptacle outlets unless than two small-appliance branch circuits, either
located within 450 mm of the wall. or both of which shall
(b) Small Appliances. also be permitted to supply receptacle outlets in
(1) Receptacle Outlets Served. In the kitchen, the same kitchen and
pantry, breakfast in other rooms specified in 2.10.3.3(b)(1).
room, dining room, or similar area of a dwelling Additional small-appliance
unit, the two or more branch circuits shall be permitted to supply
20-ampere small-appliance branch circuits receptacle outlets in the
required by 2.10.1.11(c)(1) kitchen and other rooms specified in
shall serve all wall and floor receptacle outlets 2.10.3.3(b)(1). No smallappliance branch circuit
covered by 2.10.3.3(a), shall serve more than one kitchen.
all countertop outlets covered by 2.10.3.3(c),
and receptacle outlets for (c) Countertops. In kitchens and dining rooms
refrigeration equipment. of dwelling units,
Exception No. 1: In addition to the required receptacle outlets for counter spaces shall be
receptacles specified by installed in accordance
2.10.3.3, switched receptacles supplied from a with 2.10.3.3(c)(1) through (c)(5).
general-purpose (1) Wall Counter Spaces. A receptacle outlet
branch circuit as defined in 2.10.3.21(a)(1), shall be installed at
Exception No. 1, shall be each wall counter space that is 300 mm or wider.
permitted. Receptacle outlets
Exception No. 2: The receptacle outlet for shall be installed so that no point along the wall
refrigeration equipment line is more than 600
shall be permitted to be supplied from an mm measured horizontally from a receptacle
outlet in that space. Figure 2.10.3.3 Determination of Area Behind
Exception: Receptacle outlets shall not be Sink or Range.
required on a wall directly Exception to (5): To comply with the conditions
behind a range or sink in the installation specified in (1) or (2),
described in Figure 2.10.3.3. receptacle outlets shall be permitted to be
(2) Island Counter Spaces. At least one mounted not more than
receptacle shall be 300 mm below the countertop. Receptacles
installed at each island counter space with a long mounted below a
dimension of 600 countertop in accordance with this exception
mm or greater and a short dimension of 300 mm shall not be located
or greater. Where a where the countertop extends more than 150 mm
rangetop or sink is installed in an island counter beyond its support
and the width of the base.
counter behind the rangetop or sink is less than (1) Construction for the physically impaired
300 mm, the rangetop (2) On island and peninsular countertops where
or sink is considered to divide the island into the countertop is
two separate countertop flat across its entire surface (no backsplashes,
spaces as defined in 2.10.3.3(c)(4). dividers, etc.) and there
(3) Peninsular Counter Spaces. At least one are no means to mount a receptacle within 500
receptacle outlet shall mm above the
be installed at each peninsular counter space countertop, such as an overhead cabinet
with a long dimension of (d) Bathrooms. In dwelling units, at least one
600 mm or greater and a short dimension of 300 receptacle outlet shall
mm or greater. A be installed in bathrooms within 900 mm of the
peninsular countertop is measured from the outside edge of each
connecting edge. basin. The receptacle outlet shall be located on a
(4) Separate Spaces. Countertop spaces wall or partition that
separated by rangetops, is adjacent to the basin or basin countertop.
refrigerators, or sinks shall be considered as Exception: The receptacle shall not be required
separate countertop to be mounted in the
spaces in applying the requirements of wall or partition where it is installed on the side
2.10.3.3(c)(1), (c)(2), and or face of the basin
(c)(3). cabinet not more than 300 mm below the
(5) Receptacle Outlet Location. Receptacle countertop.
outlets shall be located (e) Outdoor Outlets. For a one-family dwelling
above, but not more than 500 mm above, the and each unit of a
countertop. Receptacle two-family dwelling that is at grade level, at
outlets rendered not readily accessible by least one receptacle outlet
appliances fastened in place, accessible at grade level and not more than 2
appliance garages, sinks, or rangetops as 000 mm above grade
covered in 2.10.3.3(c)(1), shall be installed at the front and back of the
Exception, or appliances occupying dedicated dwelling.
space shall not be For each dwelling unit of a multifamily dwelling
considered as these required outlets. where the dwelling
unit is located at grade level and provided with 2.10.3.11 Guest Rooms or Guest Suites.
individual exterior (a) General. Guest rooms or guest suites in
entrance/egress, at least one receptacle outlet hotels, motels, and
accessible from grade similar occupancies shall have receptacle outlets
level and not more than 2 000 mm above grade installed in
shall be installed. See accordance with 2.10.3.3(a) and 2.10.3.3(d).
2.10.1.8(a)(3). Guest rooms or guest
(f) Laundry Areas. In dwelling units, at least suites provided with permanent provisions for
one receptacle outlet cooking shall have
shall be installed for the laundry. receptacle outlets installed in accordance with
Exception No. 1: In a dwelling unit that is an all of the applicable
apartment or living area rules in 2.10.3.3.
in a multifamily building where laundry (b) Receptacle Placement. In applying the
facilities are provided on the provisions of
premises and are available to all building 2.10.3.3(a), the total number of receptacle
occupants, a laundry outlets shall not be less than
receptacle shall not be required. the minimum number that would comply with
Exception No. 2: In other than one-family the provisions of that
dwellings where laundry section. These receptacle outlets shall be
facilities are not to be installed or permitted, a permitted to be located
laundry receptacle conveniently for permanent furniture layout. At
shall not be required. least two receptacle
(g) Basements and Garages. For a one-family outlets shall be readily accessible. Where
dwelling, at least receptacles are installed
one receptacle outlet, in addition to any provided behind the bed, the receptacle shall be located to
for laundry prevent the bed from
equipment, shall be installed in each basement contacting any attachment plug that may be
and in each attached installed or the receptacle
garage, and in each detached garage with shall be provided with a suitable guard.
electric power. See 2.10.3.13 Show Windows. At least one
2.10.1.8(a)(2) and (a)(5). Where a portion of the receptacle outlet shall be
basement is finished installed directly above a show window for each
into one or more habitable rooms, each separate 3 600 linear mm or
unfinished portion major fraction thereof of show window area
shall have a receptacle outlet installed in measured horizontally at
accordance with this section. its maximum width.
(h) Hallways. In dwelling units, hallways of 3 2.10.3.14 Heating, Air-Conditioning, and
000 mm or more in Refrigeration
length shall have at least one receptacle outlet. Equipment Outlet. A 125-volt and/or 250 volts,
As used in this subsection, the hall length shall single-phase, 15- or
be considered the 20-ampere-rated receptacle outlet shall be
length along the centerline of the hall without installed at an accessible
passing through a location for the servicing of heating, air-
doorway. conditioning, and refrigeration
equipment. The receptacle shall be located on garages, and detached
the same level and garages with electric power.
within 7 600 mm of the heating, air- b. For dwelling units, attached garages, and
conditioning, and refrigeration detached garages
equipment. The receptacle outlet shall not be with electric power, at least one wall switch–
connected to the load controlled lighting outlet
side of the equipment disconnecting means. shall be installed to provide illumination on the
Exception: A receptacle outlet shall not be exterior side of
required at one- and twofamily dwellings for the outdoor entrances or exits with grade level
service of evaporative coolers. access. A vehicle door in a
FPN: See 2.10.1.8 for ground-fault circuit-interrupter garage shall not be considered as an outdoor
requirements.
entrance or exit.
2.10.3.21 Lighting Outlets Required. Lighting
c. Where one or more lighting outlet(s) are
outlets shall be
installed for interior
installed where specified in 2.10.3.21(a), (b),
stairways, there shall be a wall switch at each
and (c).
floor level, and landing
(a) Dwelling Units. In dwelling units, lighting
level that includes an entryway, to control the
outlets shall be
lighting outlet(s) where
installed in accordance with 2.10.3.21(a)(1),
the stairway between floor levels has six risers
(a)(2), and (a)(3).
or more.
(1) Habitable Rooms. At least one wall switch-
Exception to (a)(2)a, (a)(2)b, and (a)(2)c: In
controlled lighting
hallways, stairways, and
outlet shall be installed in every habitable room
at outdoor entrances, remote, central, or
and bathroom.
automatic control of lighting
Exception No. 1: In other than kitchens and
shall be permitted.
bathrooms, one or more
(3) Storage or Equipment Spaces. For attics,
receptacles controlled by a wall switch shall be
underfloor spaces,
permitted in lieu of
utility rooms, and basements, at least one
lighting outlets.
lighting outlet containing a
Exception No. 2: Lighting outlets shall be
switch or controlled by a wall switch shall be
permitted to be controlled
installed where these
by occupancy sensors that are (1) in addition to
spaces are used for storage or contain equipment
wall switches or (2)
requiring servicing.
located at a customary wall switch location and
At least one point of control shall be at the usual
equipped with a
point of entry to these
manual override that will allow the sensor to
spaces. The lighting outlet shall be provided at
function as a wall
or near the equipment
switch.
requiring servicing.
(2) Additional Locations. Additional lighting
outlets shall be .20.2 Branch Circuit Load Calculations
installed in accordance with (a)(2)a, (a)(2)b, and 2.20.2.1 General. Branch-circuit loads shall be
(a)(2)c. calculated as shown in
a. At least one wall switch-controlled lighting 2.20.2.3, 2.20.2.5, and 2.20.2.7.
outlet shall be 2.20.2.3 Lighting Load for Specified
installed in hallways, stairways, attached Occupancies. A unit load of
not less than that specified in Table 2.20.2.3 for Hospitals 17
occupancies specified Hotels and motels, 39b
therein shall constitute the minimum lighting including apartment 22
load. The floor area for houses without 33
each floor shall be calculated from the outside provision for cooking 33
dimensions of the by 3
building, dwelling unit, or other area involved. tenantsa 11
For dwelling units, the Industrial commercial 6
calculated floor area shall not include open (loft) buildings 3
porches, garages, or Lodge rooms
unused or unfinished spaces not adaptable for Office buildings
future use. Restaurants
FPN: The unit values herein are based on minimum load Schools
conditions and 100
percent power factor and may not provide sufficient capacity for Stores
the installation Warehouses (storage)
contemplated.
In any of the preceding
2.20.2.5 Other Loads — All Occupancies. In occupancies except
all occupancies, the one-family dwellings
minimum load for each outlet for general-use and individual
receptacles and outlets dwelling units of two-
not used for general illumination shall not be family and
less than that calculated multifamily dwellings:
in 2.20.2.5(a) through (l), the loads shown being Assembly halls and
based on nominal auditoriums
branch-circuit voltages. Halls, corridors,
Exception: The loads of outlets serving closets, stairways
switchboards and switching Storage spaces
frames in telephone exchanges shall be waived aSee 2.20.2.5(j).
from the calculations. bSee 2.20.2.5(k).
(a) Specific Appliances or Loads. An outlet for (b) Electric Dryers and Household Electric
a specific appliance Cooking Appliances.
or other load not covered in 2.20.2.5(b) through Load calculations shall be permitted as specified
(l) shall be calculated in 2.20.3.15 for
based on the ampere rating of the appliance or electric dryers and in 2.20.3.16 for electric
load served. ranges and other cooking
Table 2.20.2.3 General Lighting Loads by appliances.
Occupancy (c) Motor Loads. Outlets for motor loads shall
Unit Load Type of Occupancy be calculated in
Volt-Amperes per accordance with the requirements in 4.30.2.2,
Square Meter 4.30.2.4, and 4.40.1.6.
Armories and 11 (d) Luminaires (Lighting Fixtures). An outlet
auditoriums 39b supplying
Banks 33 luminaire(s) [lighting fixture(s)] shall be
Barber shops and 11 calculated based on the
beauty parlors 22 maximum volt-ampere rating of the equipment
Churches 22 and lamps for which
Clubs 33 the luminaire(s) [fixture(s)] is rated.
Court rooms 6 (e) Heavy-Duty Lampholders. Outlets for
Dwelling unitsa 22 heavy-duty lampholders
Garages — 22 shall be calculated at a minimum of 600 volt-
commercial (storage) 22 amperes.
(f) Sign and Outline Lighting. Sign and outline guest suites of hotels and
lighting outlets motels, the outlets specified in (j)(1), (j)(2), and
shall be calculated at a minimum of 1200 volt- (j)(3) are included in
amperes for each the general lighting load calculations of 2.20.2.3.
required branch circuit specified in Section No additional load
6.0.1.5(a). calculations shall be required for such outlets.
(g) Show Windows. Show windows shall be (1) All general-use receptacle outlets of 20-
calculated in ampere rating or less,
accordance with either of the following: including receptacles connected to the circuits in
(1) The unit load per outlet as required in other 2.10.1.11(c)(3)
provisions of this (2) The receptacle outlets specified in
section 2.10.3.3(e) and (g)
(2) At 200 volt-amperes per 300 mm of show (3) The lighting outlets specified in 2.10.3.21(a)
window and (b)
(h) Fixed Multioutlet Assemblies. Fixed (k) Banks and Office Buildings. In banks or
multioutlet assemblies office buildings, the
used in other than dwelling units or the guest receptacle loads shall be calculated to be the
rooms or guest suites of larger of (1) or (2):
hotels or motels shall be calculated in (1) The computed load from 2.20.2.5
accordance with (h)(1) or (h)(2). (2) 11 volt-amperes/m2
For the purposes of this section, the calculation (l) Other Outlets. Other outlets not covered in
shall be permitted to 2.20.2.5(a) through
be based on the portion that contains receptacle (k) shall be calculated based on 180 volt-
outlets. amperes per outlet.
(1) Where appliances are unlikely to be used 2.20.2.7 Loads for Additions to Existing
simultaneously, each Installations.
1 500 mm or fraction thereof of each separate (a) Dwelling Units. Loads added to an existing
and continuous length dwelling unit(s)
shall be considered as one outlet of not less than shall comply with the following as applicable:
180 volt-amperes. (1) Loads for structural additions to an existing
(2) Where appliances are likely to be used dwelling unit or
simultaneously, each for a previously unwired portion of an existing
300 mm or fraction thereof shall be considered dwelling unit, either of
as an outlet of not less which exceeds 46.5 m2 (500 ft2), shall be
than 180 volt-amperes. calculated in accordance
(i) Receptacle Outlets. Except as covered in with 2.20.2.3 and 2.20.2.5.
2.20.2.5(j) and (k), (2) Loads for new circuits or extended circuits in
receptacle outlets shall be calculated at not less previously wired
than 180 volt-amperes dwelling units shall be calculated in accordance
for each single or for each multiple receptacle on with either 2.20.2.3 or
one yoke. A single 2.20.2.5, as applicable.
piece of equipment consisting of a multiple (b) Other Than Dwelling Units. Loads for new
receptacle comprised of circuits or extended
four or more receptacles shall be calculated at circuits in other than dwelling units shall be
not less than 90 voltamperes per receptacle. This calculated in accordance
provision shall not be applicable to the with either 2.20.2.3 or 2.20.2.5, as applicable.
receptacle outlets specified in 2.10.1.11(c)(1) 2.20.2.9 Maximum Loads. The total load shall
and (c)(2). not exceed the rating
(j) Dwelling Occupancies. In one-family, two- of the branch circuit, and it shall not exceed the
family, and maximum loads
multifamily dwellings and in guest rooms or specified in 2.20.2.9(a) through (c) under the
conditions specified 2.20.3.4 Show-Window and Track Lighting.
therein. (a) Show Windows. For show-window lighting,
(a) Motor-Operated and Combination Loads. a load of not less
Where a circuit than 660 volt-amperes/linear meter shall be
supplies only motor-operated loads, Article 4.30 included for a show
shall apply. Where a window, measured horizontally along its base.
circuit supplies only air-conditioning equipment, FPN: See 2.20.2.5(g) for branch circuits supplying show windows.
refrigerating Table 2.20.3.3 Lighting Load Demand
equipment, or both, Article 4.40 shall apply. For Factors
circuits supplying Portion of
loads consisting of motor-operated utilization Lighting
equipment that is Load to
fastened in place and has a motor larger than hp Which Demand
Type of
in combination with Demand Factor
Occupancy
other loads, the total calculated load shall be Factor (Percent)
based on 125 percent of Applies
the largest motor load plus the sum of the other (Volt-
loads. Amperes)
(b) Inductive Lighting Loads. For circuits First 3000
supplying lighting units or less at
that have ballasts, transformers, or From 3001
100
autotransformers, the calculated Dwelling to 120,000
35
load shall be based on the total ampere ratings of units at
25
such units and not on Remainder
the total watts of the lamps. over
(c) Range Loads. It shall be permissible to 120,000 at
apply demand factors for First 50,000
range loads in accordance with Table 2.20.3.16, or less at
40
including Note 4. Hospitals* Remainder
20
2.20.3 Feeder and Service Load Calculations over
2.20.3.1 General. The calculated load of a 50,000 at
feeder or service shall not Hotels and
First 20,000
be less than the sum of the loads on the branch motels,
or less at
circuits supplied, as including
From
determined by Part II of this article, after any apartment 50
20,001 to
applicable demand houses 40
100,000 at
factors permitted by Parts III or IV or required without 30
Remainder
by Part V have been provision
over
applied. for cooking
100,000 at
FPN: See Examples D1(a) through D10 in Appendix D. See by tenants*
2.20.2.9(b) for the
maximum load in amperes permitted for lighting units operating at First 12,500
less than 100 or less at
percent power factor. Warehouse 100
Remainder
2.20.3.3 General Lighting. The demand factors s (storage) 50
over
specified in Table 12,500 at
2.20.3.3 shall apply to that portion of the total Total volt-
branch-circuit load All others 100
amperes
calculated for general illumination. They shall *The demand factors of this table shall not apply to the
not be applied in calculated load of feeders or
determining the number of branch circuits for services supplying areas in hospitals, hotels, and motels
general illumination. where the entire lighting is
likely to be used at one time, as in operating rooms,
ballrooms, or dining rooms. 4.30.2.4, 4.30.2.5, and 4.30.2.6 and with
(b) Track Lighting. For track lighting in other 4.40.1.6 for hermetic
than dwelling units refrigerant motor compressors.
or guest rooms or guest suites of hotels or 2.20.3.12 Fixed Electric Space Heating. Fixed
motels, an additional load of electric space heating
150 volt-amperes shall be included for every 600 loads shall be calculated at 100 percent of the
mm of lighting track total connected load.
or fraction thereof. Where multicircuit track is However, in no case shall a feeder or service
installed, the load shall load current rating be
be considered to be divided equally between the less than the rating of the largest branch circuit
track circuits. supplied.
2.20.3.5 Receptacle Loads — Other Than Exception: Where reduced loading of the
Dwelling Units. conductors results from
Receptacle loads calculated in accordance with units operating on duty-cycle, intermittently, or
2.20.2.5(h) and (i) from all units not
shall be permitted to be made subject to the operating at the same time, the authority having
demand factors given in jurisdiction may
Table 2.20.3.3 or Table 2.20.3.5. grant permission for feeder and service
Table 2.20.3.5 Demand Factors for Non- conductors to have an
dwelling Receptacle ampacity less than 100 percent, provided the
Loads conductors have an
Porti ampacity for the load so determined.
on of 2.20.3.13 Small Appliance and Laundry
Rece Loads — Dwelling Unit.
ptacle (a) Small Appliance Circuit Load. In each
Load dwelling unit, the load
to shall be calculated at 1 500 volt-amperes for
Dema
Whic each 2-wire smallappliance branch circuit
nd
h required by 2.10.1.11(c)(1). Where the load is
Facto
Dema subdivided through two or more feeders, the
r
nd calculated load for each
(Perc
Facto shall include not less than 1 500 volt-amperes
ent)
r for each 2-wire smallappliance branch circuit.
Appli These loads shall be permitted to be included
es with the general lighting load and subjected to
(Volt- the demand factors
Ampe provided in Table 2.20.3.3.
res) Exception: The individual branch circuit
First permitted by 2.10.3.3(b)(1),
10 Exception No. 2, shall be permitted to be
kVA excluded from the
or calculation required by 2.20.3.13.
less at (b) Laundry Circuit Load. A load of not less
100
Rema than 1500 voltamperes shall be included for each
50
inder 2-wire laundry branch circuit
over installed as required by 2.10.1.11(c)(2). This
10 load shall be permitted to
kVA be included with the general lighting load and
at subjected to the demand
2.20.3.11 Motors. Motor loads shall be factors provided in Table 2.20.3.3.
calculated in accordance with 2.20.3.14 Appliance Load — Dwelling Unit(s).
It shall be mounted cooking units, and other household
permissible to apply a demand factor of 75 cooking appliances individually rated in excess
percent to the nameplate of 1¾ kW shall be
rating load of four or more appliances fastened
permitted to be calculated in accordance with
in place, other than
electric ranges, clothes dryers, space-heating Table 2.20.3.16.
equipment, or airconditioning equipment, that Kilovolt-amperes (kVA) shall be considered
are served by the same feeder or service equivalent to kilowatts
in a one-family, two-family, or multifamily (kW) for loads calculated under this section.
dwelling. Where two or more single-phase ranges are
2.20.3.15 Electric Clothes Dryers — Dwelling supplied by a 3-phase, 4-
Unit(s). The load for
wire feeder or service, the total load shall be
household electric clothes dryers in a dwelling
unit(s) shall be either calculated on the basis of
5 000 watts (volt-amperes) or the nameplate twice the maximum number connected between
rating, whichever is any two phases.
larger, for each dryer served. The use of the FPN No. 1: See Example D8 in Appendix D.
demand factors in Table FPN No. 2: See Table 2.20.3.17 for commercial cooking
equipment.
2.20.3.15 shall be permitted. Where two or more FPN No. 3: See the examples in Appendix D.
single-phase dryers
are supplied by a 3-phase, 4-wire feeder or
service, the total load shall
be calculated on the basis of twice the maximum
number connected
between any two phases.
Table 2.20.3.15 Demand Factors for
Household
Electric Clothes Dryers
Number of Demand Factor
Dryers (Percent)
100%
1–4
85%
5
75%
6
65%
7
60%
8
55%
9
50%
10
47%
11
% = 47 – (number of
12–22
dryers - 11)
23 35%
% = 35 – [0.5 ×
24–42 (number of dryers -
23)]
43 and over 25%

2.20.3.16 Electric Ranges and Other Cooking


Appliances —
Dwelling Unit(s). The load for household
electric ranges, wallmounted ovens, counter-

You might also like