1.3.1.1 Drawing Sheet Sizes. work practices, and selecting personal protective equipment.
FPN No. 2: ANSI Z535.4-1998, Product Safety Signs and Labels,
(a) Electrical plans and drawings shall be drawn provides on drawing sheets guidelines for the design of safety signs and labels for application of the following standard sizes: to products.
760 mm x 1 000 mm ----------------------------------------------------------------
600 mm x 900 mm 500 mm x 760 mm (e) Headroom. The minimum headroom of (b) In cases such as projects of large magnitude, working spaces about exemption in the ervice equipment, switchboards, panelboards, or use of the standard drawing sheets may be motor control granted by the office of the centers shall be 2 000 mm. Where the electrical local building official. Refer to Appendix E. equipment exceeds (c) For a dwelling unit having a floor area of not 2 000 m in height, the minimum headroom shall more than 50 not be less than the square meters with a total load not exceeding 3 height of the equipment. 680 VA, a drawing Exception: In existing dwelling units, service sheet of size 297 mm x 420 mm (A3 size) is equipment or permitted. panelboards that do not exceed 200 amperes shall be permitted in ---------------------------------------------------------- paces where the headroom is less than 2 000 1.10.1.16 Flash Protection. Switchboards, mm. panelboards, industrial ---------------------------------------------------------- control panels, meter socket enclosures, and motor control centers that (a) Occupancy Limitation. In dwelling units are in other than dwelling occupancies and are and guest rooms or likely to require guest suites of hotels, motels, and similar examination, adjustment, servicing, or occupancies, the voltage maintenance while energized shall not exceed 230 volts, nominal, between shall be field marked to warn licensed electrical conductors that supply practitioner or nonlicensed electrical practitioner the terminals of the following: under the supervision of a licensed (1) Luminaires (lighting fixtures) electrical practitioner of potential electric arc (2) Cord-and-plug-connected loads 1440 volt- flash hazards. The amperes, nominal, marking shall be located so as to be clearly or less or less than ¼ hp visible to licensed electrical practitioner or non-licensed electrical ---------------------------------------------------------------- practitioner under the 2.10.1.8 Ground-Fault Circuit-Interrupter supervision of a licensed electrical practitioner Protection for before examination, Personnel. adjustment, servicing, or maintenance of the FPN: See 2.15.1.9 for ground-fault circuit-interrupter protection equipment. for personnel on FPN No. 1: NFPA 70E-2004, Standard for Electrical Safety in the feeders. Workplace, (a) Dwelling Units. All 125-volt and/or 250 provides assistance in determining severity of potential exposure, planning safe volts, single-phase, 15- and 20-ampere receptacles installed in the two appliances located within dedicated space locations specified in (1) for each appliance that, through (8) shall have ground-fault circuit- in normal use, is not easily moved from one interrupter protection for place to another and that personnel. is cord-and-plug connected in accordance with (1) Bathrooms 4.0.1.7(a)(6), (a)(7), (2) Garages, and also accessory buildings that or (a)(8). have a floor located Exception No. 3 to (5): A receptacle supplying at or below grade level not intended as habitable only a permanently rooms and limited to installed fire alarm or burglar alarm system storage areas, work areas, and areas of similar shall not be required to use have ground-fault circuit-interrupter protection. Exception No. 1 to (2): Receptacles that are not (6) Kitchens — where the receptacles are readily accessible. installed to serve the Exception No. 2 to (2): A single receptacle or a countertop surfaces duplex receptacle for (7) Laundry, utility, and wet bar sinks — where two appliances located within dedicated space the receptacles are for each appliance that, installed within 1 800 mm of the outside edge of in normal use, is not easily moved from one the sink place to another and that (8) Boathouses is cord-and-plug connected in accordance with 4.0.1.7(a)(6), (a)(7), 2.10.1.11 Branch Circuits Required. Branch or (a)(8). circuits for lighting and Receptacles installed under the exceptions to for appliances, including motor-operated 2.10.1.8(a)(2) shall appliances, shall be provided not be considered as meeting the requirements of to supply the loads calculated in accordance with 2.10.3.3(g) 2.20.2.1. In addition, (3) Outdoors. Receptacles installed under the branch circuits shall be provided for specific exceptions to loads not covered by 2.10.1.8(a)(5) shall not be considered as meeting 2.20.2.1 where required elsewhere in this Code the requirements of and for dwelling unit 2.10.3.3(g). loads as specified in 2.10.1.11(c). (4) Crawl spaces — at or below grade level (a) Number of Branch Circuits. The minimum (5) Unfinished basements — for purposes of this number of branch section, circuits shall be determined from the total unfinished basements are defined as portions or calculated load and the size areas of the basement or rating of the circuits used. In all installations, not intended as habitable rooms and limited to the number of circuits storage areas, work shall be sufficient to supply the load served. In areas, and the like no case shall the load Exception No. 1 to (5): Receptacles that are not on any circuit exceed the maximum specified by readily accessible. 2.20.2.9. Exception No. 2 to (5): A single receptacle or a (b) Load Evenly Proportioned Among duplex receptacle for Branch Circuits. Where the load is calculated on the basis of volt- 2.10.1.12 Arc-Fault Circuit-Interrupter amperes per square meter or Protection. per square foot, the wiring system up to and (a) Definition: Arc-Fault Circuit Interrupter. including the branchcircuit panelboard(s) shall An arc-fault circuit be provided to serve not less than the interrupter is a device intended to provide calculated load. This load shall be evenly protection from the effects proportioned among of arc faults by recognizing characteristics multioutlet branch circuits within the unique to arcing and by panelboard(s). Branch-circuit functioning to de-energize the circuit when an overcurrent devices and circuits shall only be arc fault is detected. required to be installed (b) Dwelling Unit Bedrooms. All 115-volt to serve the connected load. and/or 230-volt, single (c) Dwelling Units. phase, 15- and 20-ampere branch circuits (1) Small-Appliance Branch Circuits. In addition supplying outlets installed in to the number of dwelling unit bedrooms shall be protected by a branch circuits required by other parts of this listed arc-fault circuit section, two or more 20- interrupter, combination type installed to ampere small-appliance branch circuits shall be provide protection of the provided for all branch circuit. This requirement shall become receptacle outlets specified by 2.10.3.3(b). effective January 1, (2) Laundry Branch Circuits. In addition to the 2014. number of branch FPN: For information on types of arc-fault circuit interrupters, see UL 1699-1999, circuits required by other parts of this section, at Standard for Arc-Fault Circuit Interrupters. least one additional Exception: The location of the arc-fault circuit 20-ampere branch circuit shall be provided to interrupter shall be supply the laundry permitted to be at other than the origination of receptacle outlet(s) required by 2.10.3.3(f). This the branch circuit in circuit shall have no compliance with (a) and (b): other outlets. (a) The arc-fault circuit interrupter installed (3) Bathroom Branch Circuits. In addition to the within 1800 mm of the number of branch branch circuit overcurrent device as measured circuits required by other parts of this section, at along the branch least one 20-ampere circuit conductors. branch circuit shall be provided to supply (b) The circuit conductors between the branch bathroom receptacle circuit overcurrent outlet(s). Such circuits shall have no other device and the arc-fault circuit interrupter shall outlets. be installed in a metal Exception: Where the 20-ampere circuit supplies raceway or a cable with a metallic sheath. a single bathroom, outlets for other equipment within the same 2.10.2.3 Outlet Devices. Outlet devices shall bathroom shall be have an ampere rating permitted to be supplied in accordance with that is not less than the load to be served and shall comply with 2.10.2.5(a)(1) and (a)(2). FPN: See Examples D1(a), D1(b), D2(b), and D4(a) in Appendix 2.10.2.3(a) and (b). D. (a) Lampholders. Where connected to a branch circuit having a (3) Receptacle Ratings. Where connected to a rating in excess of 20 amperes, lampholders branch circuit shall be of the heavy-duty supplying two or more receptacles or outlets, type. A heavy-duty lampholder shall have a receptacle ratings shall rating of not less than 660 conform to the values listed in Table watts if of the admedium type, or not less than 2.10.2.3(b)(3), or where larger 750 watts if of any than 50 amperes, the receptacle rating shall not other type. be less than the (b) Receptacles. branch-circuit rating. (1) Single Receptacle on an Individual Branch Exception No. 1: Receptacles for one or more Circuit. A single cord-and-plugconnected arc welders shall be receptacle installed on an individual branch permitted to have ampere ratings not circuit shall have an less than the minimum branch-circuit conductor ampere rating not less than that of the branch ampacity permitted circuit. by 6.30.2.1(a) or (b) as applicable for arc Exception No. 1: A receptacle installed in welders. accordance with Exception No. 2: The ampere rating of a 4.30.7.1(b). receptacle installed for Exception No. 2: A receptacle installed electric discharge lighting shall be permitted to exclusively for the use of a be based on cord-and-plug-connected arc welder shall be 4.10.6.9(c). permitted to have an Table 2.10.2.3(b)(3) Receptacle Ratings for ampere rating not less than the minimum Various Size Circuits branch-circuit conductor Circuit Receptacle ampacity determined by 6.30.2.1(a) for arc Rating Rating welders. (Amperes) (Amperes) FPN: See the definition of receptacle in Article 1.0. Not over (2) Total Cord-and-Plug-Connected Load. 15 15 Where connected to a 20 15 or 20 branch circuit supplying two or more receptacles 30 30 or outlets, a 40 40 or 50 receptacle shall not supply a total cord-and-plug- 50 50 connected load in (4) Range Receptacle Rating. The ampere rating excess of the maximum specified in Table of a range 2.10.2.3(b)(2). Table 2.10.2.3(b)(2) Maximum Cord-and- receptacle shall be permitted to be based on a Plug-Connected single range demand Load to Receptacle load as specified in Table 2.20.3.16. Rece 2.10.2.5 Permissible Loads. In no case shall the Circ ptacl Maxi load exceed the uit e mum branch-circuit ampere rating. An individual Ratin Ratin Load g branch circuit shall be g (Am (Am permitted to supply any load for which it is (Am peres peres rated. A branch circuit peres ) ) ) supplying two or more outlets or receptacles 15 or shall supply only the 15 12 20 loads specified according to its size as specified 20 16 20 in 2.10.2.5(a) through 30 24 30 (d) and as summarized in 2.10.2.6 and Table 2.10.2.6. or 50-ampere (a) 15- and 20-Ampere Branch Circuits. A 15- branch circuit shall be permitted to supply or 20-ampere cooking appliances that are branch circuit shall be permitted to supply fastened in place in any occupancy. In other than lighting units or other dwelling units, such utilization equipment, or a combination of both, circuits shall be permitted to supply fixed and shall comply with lighting units with heavyduty lampholders, 2.10.2.5(a)(1) and (a)(2). infrared heating units, or other utilization Exception: The small appliance branch circuits, equipment. laundry branch (d) Branch Circuits Larger Than 50 circuits, and bathroom branch circuits required Amperes. Branch circuits in a dwelling unit(s) larger than 50 amperes shall supply only by 2.10.1.11(c)(1), (c)(2), and (c)(3) shall supply nonlighting outlet loads. only the receptacle 2.10.2.6 Branch-Circuit Requirements — outlets specified in that section. Summary. (1) Cord-and-Plug-Connected Equipment Not The requirements for circuits that have two or Fastened in Place. more outlets or The rating of any one cord-and-plug-connected receptacles, other than the receptacle circuits of utilization equipment 2.10.1.11(c)(1) and not fastened in place shall not exceed 80 percent (c)(2), are summarized in Table 2.10.2.6. This of the branch-circuit table provides only a ampere rating. summary of minimum requirements. See (2) Utilization Equipment Fastened in Place. The 2.10.2.1, 2.10.2.2, and total rating of 2.10.2.3 for the specific requirements applying utilization equipment fastened in place, other to branch circuits. than luminaires (lighting 2.10.2.7 Common Area Branch Circuits. fixtures), shall not exceed 50 percent of the Branch circuits in dwelling branch-circuit ampere units shall supply only loads within that rating where lighting units, cord-and-plug- dwelling unit or loads connected utilization associated only with that dwelling unit. Branch equipment not fastened in place, or both, are circuits required for also supplied. the purpose of lighting, central alarm, signal, (b) 30-Ampere Branch Circuits. A 30-ampere communications, or branch circuit shall other needs for public or common areas of a be permitted to supply fixed lighting units with two-family or multifamily heavy-duty dwelling shall not be supplied from equipment lampholders in other than a dwelling unit(s) or that supplies an utilization equipment in individual dwelling unit. any occupancy. A rating of any one cord-and- Table 2.10.2.6 Summary of Branch-Circuit plug-connected Requirements utilization equipment shall not exceed 80 Circuit 15 A 20 A 30 A 40 A 50 A percent of the branch-circuit Rating ampere rating. Conduc 14 12 10 8 6 tors (c) 40- and 50-Ampere Branch Circuits. A 40- 14 14 14 12 12 (min. size): flexible cords are permitted to be permanently Circuit connected, receptacles wires1 Taps shall be permitted to be omitted for such cords. Fixture (c) Appliance Outlets. Appliance receptacle wires outlets installed in a and dwelling unit for specific appliances, such as cords — see laundry equipment, shall 2.40.1. be installed within 1 800 mm of the intended 5 location of the appliance. Overcu 2.10.3.3 Dwelling Unit Receptacle Outlets. rrent 15 A 20 A 30 A 40 A 50 A This section provides Protect ion requirements for 125-volt, 15- and 20-ampere Outlet receptacle outlets. devices Receptacle outlets required by this section shall : Any be in addition to any Lamph Any Heav type Heavy Heav receptacle that is part of a luminaire (lighting olders type y duty 15 duty y duty permitt 15 or 40 or fixture) or appliance, max. 30 A 50 A ed 20 A 50 A A located within cabinets or cupboards, or located Recept acle more than 1 700 mm rating2 above the floor. Maxim Permanently installed electric baseboard heaters um 15 A 20 A 30 A 40 A 50 A equipped with Load Permiss See See See See See factory-installed receptacle outlets or outlets ible 2.10.2 2.10.2 2.10.2 2.10.2 2.10.2 provided as a separate load .5(a) .5(a) .5(b) .5(c) .5(c) assembly by the manufacturer shall be permitted 1These gauges are for copper conductors. as the required outlet 2For receptacle rating of cord-connected electric- or outlets for the wall space utilized by such discharge luminaires (lighting fixtures), see permanently installed 4.10.6.9(c). heaters. Such receptacle outlets shall not be connected to the heater circuits. 2.10.3 Required Outlets FPN: Listed baseboard heaters include instructions that may not permit their 2.10.3.1 General. Receptacle outlets shall be installation below receptacle outlets. installed as specified in (a) General Provisions. In every kitchen, 2.10.3.3 through 2.10.3.14. family room, dining (a) Cord Pendants. A cord connector that is room, living room, parlor, library, den, sunroom, supplied by a bedroom, recreation permanently connected cord pendant shall be room, or similar room or area of dwelling units, considered a receptacle receptacle outlets outlet. shall be installed in accordance with the general (b) Cord Connections. A receptacle outlet shall provisions specified be installed in 2.10.3.3(a)(1) through (a)(3). wherever flexible cords with attachment plugs (1) Spacing. Receptacles shall be installed so are used. Where that no point measured horizontally along the floor line in any individual branch circuit wall space is more rated 15 amperes or greater. than 1 800 mm from a receptacle outlet. (2) No Other Outlets. The two or more small- (2) Wall Space. As used in this section, a wall appliance branch space shall include circuits specified in 2.10.3.3(b)(1) shall have no the following: other outlets. a. Any space 600 mm or more in width Exception No. 1: A receptacle installed solely (including space for the electrical supply measured around corners) and unbroken along to and support of an electric clock in any of the the floor line by rooms specified in doorways, fireplaces, and similar openings 2.10.3.3(b)(1). b. The space occupied by fixed panels in exterior Exception No. 2: Receptacles installed to walls, provide power for excluding sliding panels supplemental equipment and lighting on gas- c. The space afforded by fixed room dividers fired ranges, ovens, or such as counter-mounted cooking units. freestanding bar-type counters or railings (3) Kitchen Receptacle Requirements. (3) Floor Receptacles. Receptacle outlets in Receptacles installed in a floors shall not be kitchen to serve countertop surfaces shall be counted as part of the required number of supplied by not fewer receptacle outlets unless than two small-appliance branch circuits, either located within 450 mm of the wall. or both of which shall (b) Small Appliances. also be permitted to supply receptacle outlets in (1) Receptacle Outlets Served. In the kitchen, the same kitchen and pantry, breakfast in other rooms specified in 2.10.3.3(b)(1). room, dining room, or similar area of a dwelling Additional small-appliance unit, the two or more branch circuits shall be permitted to supply 20-ampere small-appliance branch circuits receptacle outlets in the required by 2.10.1.11(c)(1) kitchen and other rooms specified in shall serve all wall and floor receptacle outlets 2.10.3.3(b)(1). No smallappliance branch circuit covered by 2.10.3.3(a), shall serve more than one kitchen. all countertop outlets covered by 2.10.3.3(c), and receptacle outlets for (c) Countertops. In kitchens and dining rooms refrigeration equipment. of dwelling units, Exception No. 1: In addition to the required receptacle outlets for counter spaces shall be receptacles specified by installed in accordance 2.10.3.3, switched receptacles supplied from a with 2.10.3.3(c)(1) through (c)(5). general-purpose (1) Wall Counter Spaces. A receptacle outlet branch circuit as defined in 2.10.3.21(a)(1), shall be installed at Exception No. 1, shall be each wall counter space that is 300 mm or wider. permitted. Receptacle outlets Exception No. 2: The receptacle outlet for shall be installed so that no point along the wall refrigeration equipment line is more than 600 shall be permitted to be supplied from an mm measured horizontally from a receptacle outlet in that space. Figure 2.10.3.3 Determination of Area Behind Exception: Receptacle outlets shall not be Sink or Range. required on a wall directly Exception to (5): To comply with the conditions behind a range or sink in the installation specified in (1) or (2), described in Figure 2.10.3.3. receptacle outlets shall be permitted to be (2) Island Counter Spaces. At least one mounted not more than receptacle shall be 300 mm below the countertop. Receptacles installed at each island counter space with a long mounted below a dimension of 600 countertop in accordance with this exception mm or greater and a short dimension of 300 mm shall not be located or greater. Where a where the countertop extends more than 150 mm rangetop or sink is installed in an island counter beyond its support and the width of the base. counter behind the rangetop or sink is less than (1) Construction for the physically impaired 300 mm, the rangetop (2) On island and peninsular countertops where or sink is considered to divide the island into the countertop is two separate countertop flat across its entire surface (no backsplashes, spaces as defined in 2.10.3.3(c)(4). dividers, etc.) and there (3) Peninsular Counter Spaces. At least one are no means to mount a receptacle within 500 receptacle outlet shall mm above the be installed at each peninsular counter space countertop, such as an overhead cabinet with a long dimension of (d) Bathrooms. In dwelling units, at least one 600 mm or greater and a short dimension of 300 receptacle outlet shall mm or greater. A be installed in bathrooms within 900 mm of the peninsular countertop is measured from the outside edge of each connecting edge. basin. The receptacle outlet shall be located on a (4) Separate Spaces. Countertop spaces wall or partition that separated by rangetops, is adjacent to the basin or basin countertop. refrigerators, or sinks shall be considered as Exception: The receptacle shall not be required separate countertop to be mounted in the spaces in applying the requirements of wall or partition where it is installed on the side 2.10.3.3(c)(1), (c)(2), and or face of the basin (c)(3). cabinet not more than 300 mm below the (5) Receptacle Outlet Location. Receptacle countertop. outlets shall be located (e) Outdoor Outlets. For a one-family dwelling above, but not more than 500 mm above, the and each unit of a countertop. Receptacle two-family dwelling that is at grade level, at outlets rendered not readily accessible by least one receptacle outlet appliances fastened in place, accessible at grade level and not more than 2 appliance garages, sinks, or rangetops as 000 mm above grade covered in 2.10.3.3(c)(1), shall be installed at the front and back of the Exception, or appliances occupying dedicated dwelling. space shall not be For each dwelling unit of a multifamily dwelling considered as these required outlets. where the dwelling unit is located at grade level and provided with 2.10.3.11 Guest Rooms or Guest Suites. individual exterior (a) General. Guest rooms or guest suites in entrance/egress, at least one receptacle outlet hotels, motels, and accessible from grade similar occupancies shall have receptacle outlets level and not more than 2 000 mm above grade installed in shall be installed. See accordance with 2.10.3.3(a) and 2.10.3.3(d). 2.10.1.8(a)(3). Guest rooms or guest (f) Laundry Areas. In dwelling units, at least suites provided with permanent provisions for one receptacle outlet cooking shall have shall be installed for the laundry. receptacle outlets installed in accordance with Exception No. 1: In a dwelling unit that is an all of the applicable apartment or living area rules in 2.10.3.3. in a multifamily building where laundry (b) Receptacle Placement. In applying the facilities are provided on the provisions of premises and are available to all building 2.10.3.3(a), the total number of receptacle occupants, a laundry outlets shall not be less than receptacle shall not be required. the minimum number that would comply with Exception No. 2: In other than one-family the provisions of that dwellings where laundry section. These receptacle outlets shall be facilities are not to be installed or permitted, a permitted to be located laundry receptacle conveniently for permanent furniture layout. At shall not be required. least two receptacle (g) Basements and Garages. For a one-family outlets shall be readily accessible. Where dwelling, at least receptacles are installed one receptacle outlet, in addition to any provided behind the bed, the receptacle shall be located to for laundry prevent the bed from equipment, shall be installed in each basement contacting any attachment plug that may be and in each attached installed or the receptacle garage, and in each detached garage with shall be provided with a suitable guard. electric power. See 2.10.3.13 Show Windows. At least one 2.10.1.8(a)(2) and (a)(5). Where a portion of the receptacle outlet shall be basement is finished installed directly above a show window for each into one or more habitable rooms, each separate 3 600 linear mm or unfinished portion major fraction thereof of show window area shall have a receptacle outlet installed in measured horizontally at accordance with this section. its maximum width. (h) Hallways. In dwelling units, hallways of 3 2.10.3.14 Heating, Air-Conditioning, and 000 mm or more in Refrigeration length shall have at least one receptacle outlet. Equipment Outlet. A 125-volt and/or 250 volts, As used in this subsection, the hall length shall single-phase, 15- or be considered the 20-ampere-rated receptacle outlet shall be length along the centerline of the hall without installed at an accessible passing through a location for the servicing of heating, air- doorway. conditioning, and refrigeration equipment. The receptacle shall be located on garages, and detached the same level and garages with electric power. within 7 600 mm of the heating, air- b. For dwelling units, attached garages, and conditioning, and refrigeration detached garages equipment. The receptacle outlet shall not be with electric power, at least one wall switch– connected to the load controlled lighting outlet side of the equipment disconnecting means. shall be installed to provide illumination on the Exception: A receptacle outlet shall not be exterior side of required at one- and twofamily dwellings for the outdoor entrances or exits with grade level service of evaporative coolers. access. A vehicle door in a FPN: See 2.10.1.8 for ground-fault circuit-interrupter garage shall not be considered as an outdoor requirements. entrance or exit. 2.10.3.21 Lighting Outlets Required. Lighting c. Where one or more lighting outlet(s) are outlets shall be installed for interior installed where specified in 2.10.3.21(a), (b), stairways, there shall be a wall switch at each and (c). floor level, and landing (a) Dwelling Units. In dwelling units, lighting level that includes an entryway, to control the outlets shall be lighting outlet(s) where installed in accordance with 2.10.3.21(a)(1), the stairway between floor levels has six risers (a)(2), and (a)(3). or more. (1) Habitable Rooms. At least one wall switch- Exception to (a)(2)a, (a)(2)b, and (a)(2)c: In controlled lighting hallways, stairways, and outlet shall be installed in every habitable room at outdoor entrances, remote, central, or and bathroom. automatic control of lighting Exception No. 1: In other than kitchens and shall be permitted. bathrooms, one or more (3) Storage or Equipment Spaces. For attics, receptacles controlled by a wall switch shall be underfloor spaces, permitted in lieu of utility rooms, and basements, at least one lighting outlets. lighting outlet containing a Exception No. 2: Lighting outlets shall be switch or controlled by a wall switch shall be permitted to be controlled installed where these by occupancy sensors that are (1) in addition to spaces are used for storage or contain equipment wall switches or (2) requiring servicing. located at a customary wall switch location and At least one point of control shall be at the usual equipped with a point of entry to these manual override that will allow the sensor to spaces. The lighting outlet shall be provided at function as a wall or near the equipment switch. requiring servicing. (2) Additional Locations. Additional lighting outlets shall be .20.2 Branch Circuit Load Calculations installed in accordance with (a)(2)a, (a)(2)b, and 2.20.2.1 General. Branch-circuit loads shall be (a)(2)c. calculated as shown in a. At least one wall switch-controlled lighting 2.20.2.3, 2.20.2.5, and 2.20.2.7. outlet shall be 2.20.2.3 Lighting Load for Specified installed in hallways, stairways, attached Occupancies. A unit load of not less than that specified in Table 2.20.2.3 for Hospitals 17 occupancies specified Hotels and motels, 39b therein shall constitute the minimum lighting including apartment 22 load. The floor area for houses without 33 each floor shall be calculated from the outside provision for cooking 33 dimensions of the by 3 building, dwelling unit, or other area involved. tenantsa 11 For dwelling units, the Industrial commercial 6 calculated floor area shall not include open (loft) buildings 3 porches, garages, or Lodge rooms unused or unfinished spaces not adaptable for Office buildings future use. Restaurants FPN: The unit values herein are based on minimum load Schools conditions and 100 percent power factor and may not provide sufficient capacity for Stores the installation Warehouses (storage) contemplated. In any of the preceding 2.20.2.5 Other Loads — All Occupancies. In occupancies except all occupancies, the one-family dwellings minimum load for each outlet for general-use and individual receptacles and outlets dwelling units of two- not used for general illumination shall not be family and less than that calculated multifamily dwellings: in 2.20.2.5(a) through (l), the loads shown being Assembly halls and based on nominal auditoriums branch-circuit voltages. Halls, corridors, Exception: The loads of outlets serving closets, stairways switchboards and switching Storage spaces frames in telephone exchanges shall be waived aSee 2.20.2.5(j). from the calculations. bSee 2.20.2.5(k). (a) Specific Appliances or Loads. An outlet for (b) Electric Dryers and Household Electric a specific appliance Cooking Appliances. or other load not covered in 2.20.2.5(b) through Load calculations shall be permitted as specified (l) shall be calculated in 2.20.3.15 for based on the ampere rating of the appliance or electric dryers and in 2.20.3.16 for electric load served. ranges and other cooking Table 2.20.2.3 General Lighting Loads by appliances. Occupancy (c) Motor Loads. Outlets for motor loads shall Unit Load Type of Occupancy be calculated in Volt-Amperes per accordance with the requirements in 4.30.2.2, Square Meter 4.30.2.4, and 4.40.1.6. Armories and 11 (d) Luminaires (Lighting Fixtures). An outlet auditoriums 39b supplying Banks 33 luminaire(s) [lighting fixture(s)] shall be Barber shops and 11 calculated based on the beauty parlors 22 maximum volt-ampere rating of the equipment Churches 22 and lamps for which Clubs 33 the luminaire(s) [fixture(s)] is rated. Court rooms 6 (e) Heavy-Duty Lampholders. Outlets for Dwelling unitsa 22 heavy-duty lampholders Garages — 22 shall be calculated at a minimum of 600 volt- commercial (storage) 22 amperes. (f) Sign and Outline Lighting. Sign and outline guest suites of hotels and lighting outlets motels, the outlets specified in (j)(1), (j)(2), and shall be calculated at a minimum of 1200 volt- (j)(3) are included in amperes for each the general lighting load calculations of 2.20.2.3. required branch circuit specified in Section No additional load 6.0.1.5(a). calculations shall be required for such outlets. (g) Show Windows. Show windows shall be (1) All general-use receptacle outlets of 20- calculated in ampere rating or less, accordance with either of the following: including receptacles connected to the circuits in (1) The unit load per outlet as required in other 2.10.1.11(c)(3) provisions of this (2) The receptacle outlets specified in section 2.10.3.3(e) and (g) (2) At 200 volt-amperes per 300 mm of show (3) The lighting outlets specified in 2.10.3.21(a) window and (b) (h) Fixed Multioutlet Assemblies. Fixed (k) Banks and Office Buildings. In banks or multioutlet assemblies office buildings, the used in other than dwelling units or the guest receptacle loads shall be calculated to be the rooms or guest suites of larger of (1) or (2): hotels or motels shall be calculated in (1) The computed load from 2.20.2.5 accordance with (h)(1) or (h)(2). (2) 11 volt-amperes/m2 For the purposes of this section, the calculation (l) Other Outlets. Other outlets not covered in shall be permitted to 2.20.2.5(a) through be based on the portion that contains receptacle (k) shall be calculated based on 180 volt- outlets. amperes per outlet. (1) Where appliances are unlikely to be used 2.20.2.7 Loads for Additions to Existing simultaneously, each Installations. 1 500 mm or fraction thereof of each separate (a) Dwelling Units. Loads added to an existing and continuous length dwelling unit(s) shall be considered as one outlet of not less than shall comply with the following as applicable: 180 volt-amperes. (1) Loads for structural additions to an existing (2) Where appliances are likely to be used dwelling unit or simultaneously, each for a previously unwired portion of an existing 300 mm or fraction thereof shall be considered dwelling unit, either of as an outlet of not less which exceeds 46.5 m2 (500 ft2), shall be than 180 volt-amperes. calculated in accordance (i) Receptacle Outlets. Except as covered in with 2.20.2.3 and 2.20.2.5. 2.20.2.5(j) and (k), (2) Loads for new circuits or extended circuits in receptacle outlets shall be calculated at not less previously wired than 180 volt-amperes dwelling units shall be calculated in accordance for each single or for each multiple receptacle on with either 2.20.2.3 or one yoke. A single 2.20.2.5, as applicable. piece of equipment consisting of a multiple (b) Other Than Dwelling Units. Loads for new receptacle comprised of circuits or extended four or more receptacles shall be calculated at circuits in other than dwelling units shall be not less than 90 voltamperes per receptacle. This calculated in accordance provision shall not be applicable to the with either 2.20.2.3 or 2.20.2.5, as applicable. receptacle outlets specified in 2.10.1.11(c)(1) 2.20.2.9 Maximum Loads. The total load shall and (c)(2). not exceed the rating (j) Dwelling Occupancies. In one-family, two- of the branch circuit, and it shall not exceed the family, and maximum loads multifamily dwellings and in guest rooms or specified in 2.20.2.9(a) through (c) under the conditions specified 2.20.3.4 Show-Window and Track Lighting. therein. (a) Show Windows. For show-window lighting, (a) Motor-Operated and Combination Loads. a load of not less Where a circuit than 660 volt-amperes/linear meter shall be supplies only motor-operated loads, Article 4.30 included for a show shall apply. Where a window, measured horizontally along its base. circuit supplies only air-conditioning equipment, FPN: See 2.20.2.5(g) for branch circuits supplying show windows. refrigerating Table 2.20.3.3 Lighting Load Demand equipment, or both, Article 4.40 shall apply. For Factors circuits supplying Portion of loads consisting of motor-operated utilization Lighting equipment that is Load to fastened in place and has a motor larger than hp Which Demand Type of in combination with Demand Factor Occupancy other loads, the total calculated load shall be Factor (Percent) based on 125 percent of Applies the largest motor load plus the sum of the other (Volt- loads. Amperes) (b) Inductive Lighting Loads. For circuits First 3000 supplying lighting units or less at that have ballasts, transformers, or From 3001 100 autotransformers, the calculated Dwelling to 120,000 35 load shall be based on the total ampere ratings of units at 25 such units and not on Remainder the total watts of the lamps. over (c) Range Loads. It shall be permissible to 120,000 at apply demand factors for First 50,000 range loads in accordance with Table 2.20.3.16, or less at 40 including Note 4. Hospitals* Remainder 20 2.20.3 Feeder and Service Load Calculations over 2.20.3.1 General. The calculated load of a 50,000 at feeder or service shall not Hotels and First 20,000 be less than the sum of the loads on the branch motels, or less at circuits supplied, as including From determined by Part II of this article, after any apartment 50 20,001 to applicable demand houses 40 100,000 at factors permitted by Parts III or IV or required without 30 Remainder by Part V have been provision over applied. for cooking 100,000 at FPN: See Examples D1(a) through D10 in Appendix D. See by tenants* 2.20.2.9(b) for the maximum load in amperes permitted for lighting units operating at First 12,500 less than 100 or less at percent power factor. Warehouse 100 Remainder 2.20.3.3 General Lighting. The demand factors s (storage) 50 over specified in Table 12,500 at 2.20.3.3 shall apply to that portion of the total Total volt- branch-circuit load All others 100 amperes calculated for general illumination. They shall *The demand factors of this table shall not apply to the not be applied in calculated load of feeders or determining the number of branch circuits for services supplying areas in hospitals, hotels, and motels general illumination. where the entire lighting is likely to be used at one time, as in operating rooms, ballrooms, or dining rooms. 4.30.2.4, 4.30.2.5, and 4.30.2.6 and with (b) Track Lighting. For track lighting in other 4.40.1.6 for hermetic than dwelling units refrigerant motor compressors. or guest rooms or guest suites of hotels or 2.20.3.12 Fixed Electric Space Heating. Fixed motels, an additional load of electric space heating 150 volt-amperes shall be included for every 600 loads shall be calculated at 100 percent of the mm of lighting track total connected load. or fraction thereof. Where multicircuit track is However, in no case shall a feeder or service installed, the load shall load current rating be be considered to be divided equally between the less than the rating of the largest branch circuit track circuits. supplied. 2.20.3.5 Receptacle Loads — Other Than Exception: Where reduced loading of the Dwelling Units. conductors results from Receptacle loads calculated in accordance with units operating on duty-cycle, intermittently, or 2.20.2.5(h) and (i) from all units not shall be permitted to be made subject to the operating at the same time, the authority having demand factors given in jurisdiction may Table 2.20.3.3 or Table 2.20.3.5. grant permission for feeder and service Table 2.20.3.5 Demand Factors for Non- conductors to have an dwelling Receptacle ampacity less than 100 percent, provided the Loads conductors have an Porti ampacity for the load so determined. on of 2.20.3.13 Small Appliance and Laundry Rece Loads — Dwelling Unit. ptacle (a) Small Appliance Circuit Load. In each Load dwelling unit, the load to shall be calculated at 1 500 volt-amperes for Dema Whic each 2-wire smallappliance branch circuit nd h required by 2.10.1.11(c)(1). Where the load is Facto Dema subdivided through two or more feeders, the r nd calculated load for each (Perc Facto shall include not less than 1 500 volt-amperes ent) r for each 2-wire smallappliance branch circuit. Appli These loads shall be permitted to be included es with the general lighting load and subjected to (Volt- the demand factors Ampe provided in Table 2.20.3.3. res) Exception: The individual branch circuit First permitted by 2.10.3.3(b)(1), 10 Exception No. 2, shall be permitted to be kVA excluded from the or calculation required by 2.20.3.13. less at (b) Laundry Circuit Load. A load of not less 100 Rema than 1500 voltamperes shall be included for each 50 inder 2-wire laundry branch circuit over installed as required by 2.10.1.11(c)(2). This 10 load shall be permitted to kVA be included with the general lighting load and at subjected to the demand 2.20.3.11 Motors. Motor loads shall be factors provided in Table 2.20.3.3. calculated in accordance with 2.20.3.14 Appliance Load — Dwelling Unit(s). It shall be mounted cooking units, and other household permissible to apply a demand factor of 75 cooking appliances individually rated in excess percent to the nameplate of 1¾ kW shall be rating load of four or more appliances fastened permitted to be calculated in accordance with in place, other than electric ranges, clothes dryers, space-heating Table 2.20.3.16. equipment, or airconditioning equipment, that Kilovolt-amperes (kVA) shall be considered are served by the same feeder or service equivalent to kilowatts in a one-family, two-family, or multifamily (kW) for loads calculated under this section. dwelling. Where two or more single-phase ranges are 2.20.3.15 Electric Clothes Dryers — Dwelling supplied by a 3-phase, 4- Unit(s). The load for wire feeder or service, the total load shall be household electric clothes dryers in a dwelling unit(s) shall be either calculated on the basis of 5 000 watts (volt-amperes) or the nameplate twice the maximum number connected between rating, whichever is any two phases. larger, for each dryer served. The use of the FPN No. 1: See Example D8 in Appendix D. demand factors in Table FPN No. 2: See Table 2.20.3.17 for commercial cooking equipment. 2.20.3.15 shall be permitted. Where two or more FPN No. 3: See the examples in Appendix D. single-phase dryers are supplied by a 3-phase, 4-wire feeder or service, the total load shall be calculated on the basis of twice the maximum number connected between any two phases. Table 2.20.3.15 Demand Factors for Household Electric Clothes Dryers Number of Demand Factor Dryers (Percent) 100% 1–4 85% 5 75% 6 65% 7 60% 8 55% 9 50% 10 47% 11 % = 47 – (number of 12–22 dryers - 11) 23 35% % = 35 – [0.5 × 24–42 (number of dryers - 23)] 43 and over 25%
2.20.3.16 Electric Ranges and Other Cooking
Appliances — Dwelling Unit(s). The load for household electric ranges, wallmounted ovens, counter-