Cooling and Dehumidifying Heat Load Estimate for SUMMER

Estmated By SRI CONDITION DB 'F WB 'F


Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room F.GEN.WARD 9600 8000
Classification 691.2 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 50.0 200.0
North 0.0 23 0.56 0 WEST 60.0 240.0
South 50.0 12 0.56 336 EAST 0.0 0.0
West 60.0 163 0.56 5477 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 691 sft
Solar and trans gain-walls&roof ROOF HEIGH 10 ft
North 0.0 19.0 0.36 0 FALSE CEILIN 9 ft
South 200.0 31.0 0.36 2232 NO OF F.A.C 1 PER HR.
West 240.0 27.0 0.36 2333 NO. OF PEOP 12
East 0.0 33.0 0.36 0 GUINIE PIGS 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING L 1.5 W/S. FT
Roof -Sun 691.2 50.0 0.51 17626 EQUIPMENT 1.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY F 1
Roof -Shaded 27.0 0.48 0 SH PER PERS 245 Btu/hr
Transmission gain-except walls & roof LH PER PERS 205 Btu/hr
All glass 110.0 30.0 1.13 3729 BPF 0.12
Partition 440.0 25.0 0.36 3960 CFM/PERSON 12
Ceiling 691.2 25.0 0.42 7258 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAIN 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CEIL 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation
Outsideair 144 30.0 1.08 0.12 560 PARTITIONS 0 (1 if Mod.Partitions exists els
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exis
People 12 245 0 2940 PRE-COOLING 0 (1 if Pre-cooling/TFA exists
Lights 691 1.5 3.413 3539 ADP&SHR 0 (1 if ADP & SHR revised els
Equipment 1.00 1 3413 3413 Motor bkw 0.650IF ADP & SHR REVISED,CO
Guinie Pigs 0 32 0 SHR 0.95 REV. ESHR
Rabbits 0 61 0 ADP 52.28 REV. ADP
Rats 0 22 0 TR 6.35 REV. TR
Mice 0 3.3 0 Dehumd. CF 2937 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCRE
Room sensible heat-sub total 55620
2%Duct leakage& 2%R.A.Heat Regain 10% 4999 FRESH AIR REQUIREMENT
Room Sensible Heat Total 60619 NOS CFM/PER
Room Latent Heat PEOPLE 12 12
Infiltration 0 EXHAUST
outsideair 144 68.2 0.68 0.12 801 NO. OF A/CH 1
People 12 205 2460 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 3261
Duct leakage& R.A.Heat Regain + Safe 10% 80 DIFF. -13.0
Room Latent Heat Total 3341
Room Total Heat (Sensible + Latent) 63959 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 144 30.0 1.08 0.88 4106 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 144 68.2 0.68 0.88 5873 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 73938 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 2218 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 76156 ( Tadp + (BF(Tedb - T adp)))
tons 6.35 5. SUPPLY AIR CFM
Sensible heat factor 0.95 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.28 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 19.11 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 2937 bypassing RA only, use deh. CFM
for SUMMER Cooling and Dehumidifying Heat Load Es
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room F.GEN.WARD
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
200.0 GLASS 0.560 Item Sun gain Factor Btu/hr
0.0 ALL GLAS 1.130 Solar gain glass
0.0 PARTITIO 0.360 North 0.0 23 0.56 0
240.0 M.PARTN 0.150 South 50.0 12 0.56 336
0.0 CEILING 0.424 West 60.0 163 0.56 5477
0.0 M.CLG.PA 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.28 South 200.0 10.0 0.36 720
0.93 52 0.00 West 240.0 6.0 0.36 518
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 691.2 29.0 0.51 10223
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 110.0 9.0 1.13 1119
Partition 440.0 4.0 0.36 634
Ceiling 691.2 4.0 0.42 1161
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 144 9.0 1.08 0.12 168
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 12 245 0 2940
(1 if ADP & SHR revised else 0) Lights 691 1.5 3.413 3539
F ADP & SHR REVISED,CONSIDER FOLWG Equipment 1.00 1 3413 3413
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 32466
R REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 2683
ACH NET (CFM) Room Sensible Heat Total 35149
144 Room Latent Heat
0 Infiltration 0
115 115 outsideair 144 81.9 0.68 0.12 962
144 People 12 205 2460
Guinie Pigs 0 15 0
RE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 3422
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 171
Room Latent Heat Total 3593
( ROOM O/L AIR) 55.78 0F Room Total Heat (Sensible + Latent) 38742
FM+CFMoa)) Outside Air Heat
termine supply CFM air qty temp diff const 1 - bf
ly air qty. formula Sensible 144 9.0 1.08 0.88 1232
B TEMPERATURE #VALUE! F 0
hum diff const
X Trm)/CFMsa) Latent 144 81.9 0.68 0.88 7053
STURE CONTENT 78.93901 Gr./lb Grand Total Heat SubTotal 47027
Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 1411
TEMPERATURE 51.44 0F Re- heat 1656
GRAND TOTAL HEAT 50094
3080.56 F 0
tons 4.17
Sensible heat factor 0.91
T ewb = 0
F Indicated adp 'f 52.28
T lwb = 0
F Selected adp 'F 55.00
ture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 19.11
se deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 1703
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 200.0 GLASS 0.560
SOUTH 50.0 200.0 0.0 ALL GLAS 1.130
WEST 60.0 240.0 0.0 PARTITIO 0.360
EAST 0.0 0.0 240.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PA 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 691 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.28
NO. OF PE 12 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 1.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.91 REV. ESHR 0.97
ADP 52.28 REV. ADP 50
TR 4.17 REV. TR 0.00
Dehumd. 1703 REV. AIR QTY CFM 0
Reheat,KW 0.48 RE- HEAT IN KWTO INCREASE 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 12 12 144
EXHAUST 0
NO. OF A 1 115 115
TOTAL FRESH AIR 144

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 56.38 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 78.93901 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 1846.73 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room M.GEN.WARD 8610 8455
Classification 655.18 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 0.0 0.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 40.0 240.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 40.0 12 0.56 269 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 655 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 0.0 19.0 0.36 0 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 12
East 240.0 33.0 0.36 2851 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 655.2 50.0 0.51 16708 EQUIPMENT 1.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 40.0 30.0 1.13 1356 BPF 0.12
Partition 720.0 25.0 0.36 6480 CFM/PERSO 12
Ceiling 655.2 25.0 0.42 6880 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 144 30.0 1.08 0.12 560 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 12 245 0 2940 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 655 1.5 3.413 3354 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 1.00 1 3413 3413 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.94 REV. ESHR
Rabbits 0 61 0 ADP 52.11 REV. ADP
Rats 0 22 0 TR 5.54 REV. TR
Mice 0 3.3 0 Dehumd. C 2460 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 47029
2%Duct leakage& 2%R.A.Heat Regain 10% 4140 FRESH AIR REQUIREMENT
Room Sensible Heat Total 51169 NOS CFM/PER
Room Latent Heat PEOPLE 12 12
Infiltration 0 EXHAUST
outsideair 144 68.2 0.68 0.12 801 NO. OF A/ 1
People 12 205 2460 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 3261
Duct leakage& R.A.Heat Regain + Safe 5% 163 DIFF. -13.0
Room Latent Heat Total 3424
Room Total Heat (Sensible + Latent) 54592 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 144 30.0 1.08 0.88 4106 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 144 68.2 0.68 0.88 5873 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 64571 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 1937 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 66508 ( Tadp + (BF(Tedb - T adp)))
tons 5.54 5. SUPPLY AIR CFM
Sensible heat factor 0.94 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.11 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 19.26 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 2460 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load Es
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room M.GEN.WARD
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
240.0 GLASS 0.560 Item Sun gain Factor Btu/hr
240.0 ALL GLAS 1.130 Solar gain glass
240.0 PARTITIO 0.360 North 0.0 23 0.56 0
0.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PA 0.150 East 40.0 12 0.56 269
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.11 South 0.0 10.0 0.36 0
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 240.0 12.0 0.36 1037
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 655.2 29.0 0.51 9690
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 40.0 9.0 1.13 407
Partition 720.0 4.0 0.36 1037
Ceiling 655.2 4.0 0.42 1101
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 144 9.0 1.08 0.12 168
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 12 245 0 2940
(1 if ADP & SHR revised else 0) Lights 655 1.5 3.413 3354
F ADP & SHR REVISED,CONSIDER FOLWG Equipment 1.00 1 3413 3413
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 25634
IR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 2000
ACH NET (CFM) Room Sensible Heat Total 27634
144 Room Latent Heat
0 Infiltration 0
109 109 outsideair 144 81.9 0.68 0.12 962
144 People 12 205 2460
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 3422
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 171
Room Latent Heat Total 3593
P. ( ROOM O/L AIR) 55.80 0F Room Total Heat (Sensible + Latent) 31227
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 144 9.0 1.08 0.88 1232
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 144 81.9 0.68 0.88 7053
OISTURE CONTENT 80.8968 Gr./lb Grand Total Heat SubTotal 39512
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 1185
LB TEMPERATURE 51.44 0F Re- heat 1744
GRAND TOTAL HEAT 42442
2603.52 F 0
tons 3.54
Sensible heat factor 0.88
T ewb = 0
F Indicated adp 'f 52.11
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 19.26
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 1328
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 240.0 GLASS 0.560
SOUTH 0.0 0.0 240.0 ALL GLAS 1.130
WEST 0.0 0.0 240.0 PARTITIO 0.360
EAST 40.0 240.0 0.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PA 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 655 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.11
NO. OF PE 12 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 1.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.88 REV. ESHR 0.97
ADP 52.11 REV. ADP 50
TR 3.54 REV. TR 0.00
Dehumd. 1328 REV. AIR QTY CFM 0
Reheat,KW 0.51 RE- HEAT IN KWTO INCREASE 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 12 12 144
EXHAUST 0
NO. OF A 1 109 109
TOTAL FRESH AIR 144

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 56.62 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 80.8968 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 1472.30 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room DYALISIS 5865 8000
Classification 422.28 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 0.0 0.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 0.0 0.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 422 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 0.0 19.0 0.36 0 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1.5 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 3
East 0.0 33.0 0.36 0 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 422.3 50.0 0.51 10769 EQUIPMENT 1.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 0.0 30.0 1.13 0 BPF 0.12
Partition 840.0 25.0 0.36 7560 CFM/PERSO 12
Ceiling 422.3 25.0 0.42 4434 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 106 30.0 1.08 0.12 410 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 3 245 0 735 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 422 1.5 3.413 2162 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 1.00 1 3413 3413 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.96 REV. ESHR
Rabbits 0 61 0 ADP 52.54 REV. ADP
Rats 0 22 0 TR 3.68 REV. TR
Mice 0 3.3 0 Dehumd. C 1682 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 31702
2%Duct leakage& 2%R.A.Heat Regain 10% 2607 FRESH AIR REQUIREMENT
Room Sensible Heat Total 34309 NOS CFM/PER
Room Latent Heat PEOPLE 3 12
Infiltration 0 EXHAUST
outsideair 106 68.2 0.68 0.12 587 NO. OF A/ 2
People 3 205 615 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 1202
Duct leakage& R.A.Heat Regain + Safe 5% 60 DIFF. -13.0
Room Latent Heat Total 1262
Room Total Heat (Sensible + Latent) 35571 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 106 30.0 1.08 0.88 3010 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 106 68.2 0.68 0.88 4306 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 42887 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 1287 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 44173 ( Tadp + (BF(Tedb - T adp)))
tons 3.68 5. SUPPLY AIR CFM
Sensible heat factor 0.96 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.54 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 18.88 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 1682 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load Es
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room DYALISIS
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
180.0 GLASS 0.560 Item Sun gain Factor Btu/hr
180.0 ALL GLAS 1.130 Solar gain glass
240.0 PARTITIO 0.360 North 0.0 23 0.56 0
240.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PA 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.54 South 0.0 10.0 0.36 0
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 422.3 29.0 0.51 6246
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 0.0 9.0 1.13 0
Partition 840.0 4.0 0.36 1210
Ceiling 422.3 4.0 0.42 709
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 106 9.0 1.08 0.12 123
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 3 245 0 735
(1 if ADP & SHR revised else 0) Lights 422 1.5 3.413 2162
F ADP & SHR REVISED,CONSIDER FOLWG Equipment 1.00 1 3413 3413
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 16816
IR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 1118
ACH NET (CFM) Room Sensible Heat Total 17935
36 Room Latent Heat
0 Infiltration 0
70 106 outsideair 106 81.9 0.68 0.12 705
106 People 3 205 615
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 1320
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 66
Room Latent Heat Total 1386
P. ( ROOM O/L AIR) 56.23 0F Room Total Heat (Sensible + Latent) 19321
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 106 9.0 1.08 0.88 903
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 106 81.9 0.68 0.88 5171
OISTURE CONTENT 81.76413 Gr./lb Grand Total Heat SubTotal 25395
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 762
LB TEMPERATURE 51.44 0F Re- heat 726
GRAND TOTAL HEAT 26884
1787.74 F 0
tons 2.24
Sensible heat factor 0.93
T ewb = 0
F Indicated adp 'f 52.54
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 18.88
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 879
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 180.0 GLASS 0.560
SOUTH 0.0 0.0 180.0 ALL GLAS 1.130
WEST 0.0 0.0 240.0 PARTITIO 0.360
EAST 0.0 0.0 240.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PA 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 422 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1.5 PER HR. 1 53.1 52.54
NO. OF PE 3 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 1.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.93 REV. ESHR 0.97
ADP 52.54 REV. ADP 50
TR 2.24 REV. TR 0.00
Dehumd. 879 REV. AIR QTY CFM 0
Reheat,KW 0.21 RE- HEAT IN KWTO INCREASE 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 3 12 36
EXHAUST 0
NO. OF A 2 70 106
TOTAL FRESH AIR 106

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 57.14 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 81.76413 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 984.93 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room OPD&CONSULATION 4000 3626
Classification 130.54 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 0.0 0.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 0.0 0.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 1500 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 0.0 19.0 0.36 0 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 20
East 0.0 33.0 0.36 0 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 1500.0 50.0 0.51 38250 EQUIPMENT 1.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 0.0 30.0 1.13 0 BPF 0.12
Partition 840.0 25.0 0.36 7560 CFM/PERSO 12
Ceiling 1500.0 25.0 0.42 15750 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 250 30.0 1.08 0.12 972 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 20 245 0 4900 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 1500 1.5 3.413 7679 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 1.00 1 3413 3413 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.94 REV. ESHR
Rabbits 0 61 0 ADP 52.14 REV. ADP
Rats 0 22 0 TR 9.56 REV. TR
Mice 0 3.3 0 Dehumd. C 4248 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 80743
2%Duct leakage& 2%R.A.Heat Regain 10% 7511 FRESH AIR REQUIREMENT
Room Sensible Heat Total 88254 NOS CFM/PER
Room Latent Heat PEOPLE 20 12
Infiltration 0 EXHAUST
outsideair 250 68.2 0.68 0.12 1390 NO. OF A/ 1
People 20 205 4100 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 5490
Duct leakage& R.A.Heat Regain + Safe 5% 275 DIFF. -13.0
Room Latent Heat Total 5765
Room Total Heat (Sensible + Latent) 94019 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 250 30.0 1.08 0.88 7128 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 250 68.2 0.68 0.88 10196 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 111343 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 3340 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 114683 ( Tadp + (BF(Tedb - T adp)))
tons 9.56 5. SUPPLY AIR CFM
Sensible heat factor 0.94 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.14 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 19.24 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 4248 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load Es
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room OPD&CONSULATION
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
180.0 GLASS 0.560 Item Sun gain Factor Btu/hr
180.0 ALL GLAS 1.130 Solar gain glass
240.0 PARTITIO 0.360 North 0.0 23 0.56 0
240.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PA 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.14 South 0.0 10.0 0.36 0
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 1500.0 29.0 0.51 22185
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 0.0 9.0 1.13 0
Partition 840.0 4.0 0.36 1210
Ceiling 1500.0 4.0 0.42 2520
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 250 9.0 1.08 0.12 292
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 20 245 0 4900
(1 if ADP & SHR revised else 0) Lights 1500 1.5 3.413 7679
F ADP & SHR REVISED,CONSIDER FOLWG Equipment 1.00 1 3413 3413
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 44417
IR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 3879
ACH NET (CFM) Room Sensible Heat Total 48295
240 Room Latent Heat
0 Infiltration 0
250 250 outsideair 250 81.9 0.68 0.12 1670
250 People 20 205 4100
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 5770
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 288
Room Latent Heat Total 6058
P. ( ROOM O/L AIR) 55.83 0F Room Total Heat (Sensible + Latent) 54354
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 250 9.0 1.08 0.88 2138
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 250 81.9 0.68 0.88 12246
OISTURE CONTENT 80.95944 Gr./lb Grand Total Heat SubTotal 68738
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 2062
LB TEMPERATURE 51.44 0F Re- heat 2904
GRAND TOTAL HEAT 73703
4497.93 F 0
tons 6.14
Sensible heat factor 0.89
T ewb = 0
F Indicated adp 'f 55.00
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 16.72
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 2675
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 180.0 GLASS 0.560
SOUTH 0.0 0.0 180.0 ALL GLASS 1.130
WEST 0.0 0.0 240.0 PARTITION 0.360
EAST 0.0 0.0 240.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PAN 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 1500 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.14
NO. OF PE 20 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 1.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.89 REV. ESHR 0.97
ADP 55.00 REV. ADP 50
TR 6.14 REV. TR 0.00
Dehumd. 2675 REV. AIR QTY CFM 0
Reheat,KW 0.85 RE- HEAT IN KWTO INCREASE A 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 20 12 240
EXHAUST 0
NO. OF A 1 250 250
TOTAL FRESH AIR 250

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 58.71 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 80.959441 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 2924.52 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room LAB 4860 7500
Classification 328.05 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 0.0 0.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 0.0 0.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 328 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 0.0 19.0 0.36 0 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 4
East 0.0 33.0 0.36 0 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 328.0 50.0 0.51 8364 EQUIPMENT 5.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 0.0 30.0 1.13 0 BPF 0.12
Partition 840.0 25.0 0.36 7560 CFM/PERSO 12
Ceiling 328.0 25.0 0.42 3444 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 55 30.0 1.08 0.12 213 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 4 245 0 980 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 328 1.5 3.413 1679 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 5.00 1 3413 17065 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.97 REV. ESHR
Rabbits 0 61 0 ADP 52.69 REV. ADP
Rats 0 22 0 TR 4.18 REV. TR
Mice 0 3.3 0 Dehumd. C 2160 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 41523
2%Duct leakage& 2%R.A.Heat Regain 10% 2224 FRESH AIR REQUIREMENT
Room Sensible Heat Total 43747 NOS CFM/PER
Room Latent Heat PEOPLE 4 12
Infiltration 0 EXHAUST
outsideair 55 68.2 0.68 0.12 304 NO. OF A/ 1
People 4 205 820 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 1124
Duct leakage& R.A.Heat Regain + Safe 5% 56 DIFF. -13.0
Room Latent Heat Total 1180
Room Total Heat (Sensible + Latent) 44927 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 55 30.0 1.08 0.88 1559 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 55 68.2 0.68 0.88 2230 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 48716 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 1461 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 50177 ( Tadp + (BF(Tedb - T adp)))
tons 4.18 5. SUPPLY AIR CFM
Sensible heat factor 0.97 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.69 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 18.75 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 2160 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load E
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room LAB
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
180.0 GLASS 0.560 Item Sun gain Factor Btu/hr
180.0 ALL GLAS 1.130 Solar gain glass
240.0 PARTITION 0.360 North 0.0 23 0.56 0
240.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PA 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.69 South 0.0 10.0 0.36 0
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 328.0 29.0 0.51 4851
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 0.0 9.0 1.13 0
Partition 840.0 4.0 0.36 1210
Ceiling 328.0 4.0 0.42 551
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 55 9.0 1.08 0.12 64
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 4 245 0 980
(1 if ADP & SHR revised else 0) Lights 328 1.5 3.413 1679
F ADP & SHR REVISED,CONSIDER FOLWG Equipment 5.00 1 3413 17065
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 28618
AIR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 933
ACH NET (CFM) Room Sensible Heat Total 29552
48 Room Latent Heat
0 Infiltration 0
55 55 outsideair 55 81.9 0.68 0.12 365
55 People 4 205 820
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 1185
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 59
Room Latent Heat Total 1244
P. ( ROOM O/L AIR) 55.71 0F Room Total Heat (Sensible + Latent) 30796
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 55 9.0 1.08 0.88 468
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 55 81.9 0.68 0.88 2678
OISTURE CONTENT 74.05458 Gr./lb Grand Total Heat SubTotal 33941
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 1018
LB TEMPERATURE 51.44 0F Re- heat 447
GRAND TOTAL HEAT 35407
2214.70 F 0
tons 2.95
Sensible heat factor 0.96
T ewb = 0
F Indicated adp 'f 52.69
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 18.75
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 1459
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 180.0 GLASS 0.560
SOUTH 0.0 0.0 180.0 ALL GLAS 1.130
WEST 0.0 0.0 240.0 PARTITION 0.360
EAST 0.0 0.0 240.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PA 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 328 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.69
NO. OF PE 4 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 5.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.96 REV. ESHR 0.97
ADP 52.69 REV. ADP 50
TR 2.95 REV. TR 0.00
Dehumd. 1459 REV. AIR QTY CFM 0
Reheat,KW 0.13 RE- HEAT IN KWTO INCREASE 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 4 12 48
EXHAUST 0
NO. OF A 1 55 55
TOTAL FRESH AIR 55

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 55.92 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 74.05458 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 1513.79 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room ELECTRICAL 4000 2900
Classification 104.4 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 0.0
Solar gain glass SOUTH 0.0 0.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 0.0 0.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 105 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 0.0 19.0 0.36 0 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 2
East 0.0 33.0 0.36 0 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 105.0 50.0 0.51 2678 EQUIPMENT 6.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 0.0 30.0 1.13 0 BPF 0.12
Partition 840.0 25.0 0.36 7560 CFM/PERSO 12
Ceiling 105.0 25.0 0.42 1103 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 24 30.0 1.08 0.12 93 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 2 245 0 490 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 105 1.5 3.413 538 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 6.00 1 3413 20478 Motor bkw 0.650 IF ADP & SHR REVISED,CO
Guinie Pigs 0 32 0 SHR 0.98 REV. ESHR
Rabbits 0 61 0 ADP 52.86 REV. ADP
Rats 0 22 0 TR 3.32 REV. TR
Mice 0 3.3 0 Dehumd. C 1812 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 35157
2%Duct leakage& 2%R.A.Heat Regain 10% 1246 FRESH AIR REQUIREMENT
Room Sensible Heat Total 36403 NOS CFM/PER
Room Latent Heat PEOPLE 2 12
Infiltration 0 EXHAUST
outsideair 24 68.2 0.68 0.12 133 NO. OF A/ 1
People 2 205 410 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 543
Duct leakage& R.A.Heat Regain + Safe 5% 27 DIFF. -13.0
Room Latent Heat Total 571
Room Total Heat (Sensible + Latent) 36974 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 24 30.0 1.08 0.88 684 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 24 68.2 0.68 0.88 979 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 38637 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 1159 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 39796 ( Tadp + (BF(Tedb - T adp)))
tons 3.32 5. SUPPLY AIR CFM
Sensible heat factor 0.98 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.86 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 18.60 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 1812 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load E
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room ELECTRICAL
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
180.0 GLASS 0.560 Item Sun gain Factor Btu/hr
180.0 ALL GLASS 1.130 Solar gain glass
240.0 PARTITION 0.360 North 0.0 23 0.56 0
240.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PANL 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 0.0 -2.0 0.36 0
1 53.1 52.86 South 0.0 10.0 0.36 0
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 105.0 29.0 0.51 1553
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 0.0 9.0 1.13 0
Partition 840.0 4.0 0.36 1210
Ceiling 105.0 4.0 0.42 176
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 24 9.0 1.08 0.12 28
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 2 245 0 490
(1 if ADP & SHR revised else 0) Lights 105 1.5 3.413 538
IF ADP & SHR REVISED,CONSIDER FOLWG Equipment 6.00 1 3413 20478
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE AD 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 26691
AIR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 399
ACH NET (CFM) Room Sensible Heat Total 27090
24 Room Latent Heat
0 Infiltration 0
18 18 outsideair 24 81.9 0.68 0.12 160
24 People 2 205 410
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 570
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 29
Room Latent Heat Total 599
P. ( ROOM O/L AIR) 55.64 0F Room Total Heat (Sensible + Latent) 27689
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 24 9.0 1.08 0.88 205
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 24 81.9 0.68 0.88 1176
OISTURE CONTENT 71.5715978 Gr./lb Grand Total Heat SubTotal 29070
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 872
LB TEMPERATURE 51.44 0F Re- heat 174
GRAND TOTAL HEAT 30116
1835.88 F0
tons 2.51
Sensible heat factor 0.98
T ewb = 0
F Indicated adp 'f 52.86
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 18.60
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 1348
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 0.0 180.0 GLASS 0.560
SOUTH 0.0 0.0 180.0 ALL GLASS 1.130
WEST 0.0 0.0 240.0 PARTITION 0.360
EAST 0.0 0.0 240.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PAN 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 105 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.86
NO. OF PE 2 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 6.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.98 REV. ESHR 0.97
ADP 52.86 REV. ADP 50
TR 2.51 REV. TR 0.00
Dehumd. 1348 REV. AIR QTY CFM 0
Reheat,KW 0.05 RE- HEAT IN KWTO INCREASE A 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 2 12 24
EXHAUST 0
NO. OF A 1 18 18
TOTAL FRESH AIR 24

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 55.72 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 71.571598 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 1372.35 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room CONFERENCE 4860 7500
Classification 328.05 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 40.0 210.0
Solar gain glass SOUTH 0.0 0.0
North 40.0 23 0.56 515 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 0.0 0.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 0.0 12 0.56 0 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 328 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 210.0 19.0 0.36 1436 FALSE CEIL 9 ft
South 0.0 31.0 0.36 0 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 15
East 0.0 33.0 0.36 0 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 328.0 50.0 0.51 8364 EQUIPMENT 2.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 40.0 30.0 1.13 1356 BPF 0.12
Partition 490.0 25.0 0.36 4410 CFM/PERSO 12
Ceiling 328.0 25.0 0.42 3444 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 180 30.0 1.08 0.12 700 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 15 245 0 3675 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 328 1.5 3.413 1679 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 2.00 1 3413 6826 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.90 REV. ESHR
Rabbits 0 61 0 ADP 51.34 REV. ADP
Rats 0 22 0 TR 4.63 REV. TR
Mice 0 3.3 0 Dehumd. C 1727 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 34624
2%Duct leakage& 2%R.A.Heat Regain 10% 2558 FRESH AIR REQUIREMENT
Room Sensible Heat Total 37182 NOS CFM/PER
Room Latent Heat PEOPLE 15 12
Infiltration 0 EXHAUST
outsideair 180 68.2 0.68 0.12 1001 NO. OF A/ 1
People 15 205 3075 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 4076
Duct leakage& R.A.Heat Regain + Safe 5% 204 DIFF. -13.0
Room Latent Heat Total 4280
Room Total Heat (Sensible + Latent) 41462 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 180 30.0 1.08 0.88 5132 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 180 68.2 0.68 0.88 7341 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 53935 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 1618 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 55553 ( Tadp + (BF(Tedb - T adp)))
tons 4.63 5. SUPPLY AIR CFM
Sensible heat factor 0.90 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 51.34 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 19.94 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 1727 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load E
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room CONFERENCE
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
0.0 GLASS 0.560 Item Sun gain Factor Btu/hr
210.0 ALL GLASS 1.130 Solar gain glass
140.0 PARTITION 0.360 North 40.0 23 0.56 515
140.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PAN 0.150 East 0.0 12 0.56 0
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 210.0 -2.0 0.36 -151
1 53.1 0.00 South 0.0 10.0 0.36 0
0.93 52 51.34 West 0.0 6.0 0.36 0
0.83 50 0.00 East 0.0 12.0 0.36 0
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 328.0 29.0 0.51 4851
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 40.0 9.0 1.13 407
Partition 490.0 4.0 0.36 706
Ceiling 328.0 4.0 0.42 551
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 180 9.0 1.08 0.12 210
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 15 245 0 3675
(1 if ADP & SHR revised else 0) Lights 328 1.5 3.413 1679
IF ADP & SHR REVISED,CONSIDER FOLWG Equipment 2.00 1 3413 6826
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE A 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 21487
AIR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 1244
ACH NET (CFM) Room Sensible Heat Total 22731
180 Room Latent Heat
0 Infiltration 0
55 55 outsideair 180 81.9 0.68 0.12 1202
180 People 15 205 3075
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 4277
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 214
Room Latent Heat Total 4491
P. ( ROOM O/L AIR) 55.94 0F Room Total Heat (Sensible + Latent) 27223
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 180 9.0 1.08 0.88 1540
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 180 81.9 0.68 0.88 8817
OISTURE CONTENT 90.305796 Gr./lb Grand Total Heat SubTotal 37579
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 1127
LB TEMPERATURE 51.44 0F Re- heat 1875
GRAND TOTAL HEAT 40581
1906.50 F
0
tons 3.38
Sensible heat factor 0.84
T ewb = 0
F Indicated adp 'f 51.34
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 19.94
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 1056
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 40.0 210.0 0.0 GLASS 0.560
SOUTH 0.0 0.0 210.0 ALL GLAS 1.130
WEST 0.0 0.0 140.0 PARTITION 0.360
EAST 0.0 0.0 140.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PA 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 328 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 0.00
NO. OF PE 15 0.93 52 51.34
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 2.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.84 REV. ESHR 0.97
ADP 51.34 REV. ADP 50
TR 3.38 REV. TR 0.00
Dehumd. 1056 REV. AIR QTY CFM 0
Reheat,KW 0.55 RE- HEAT IN KWTO INCREASE 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 15 12 180
EXHAUST 0
NO. OF A 1 55 55
TOTAL FRESH AIR 180

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 56.96 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 90.3058 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 1235.51 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM
Cooling and Dehumidifying Heat Load Estimate for SUMMER
Estmated By SRI CONDITION DB 'F WB 'F
Date 18/03/2010 OUTSIDE 104.0 83.0
Coustomer M/s.Tanuku Corporate Hosipital ROOM 74.0 63.0
Location Tanuku DIFFERENCE 30.0
Room STAFF 14520 8540
Classification 1116 GLASS, WALL & PARTITION AREAS (ft
AHU Tag No SYSTEM-2 GLASS WALLS
Item Sun gain Factor Btu/hr NORTH 0.0 80.0
Solar gain glass SOUTH 0.0 240.0
North 0.0 23 0.56 0 WEST 0.0 0.0
South 0.0 12 0.56 0 EAST 120.0 300.0
West 0.0 163 0.56 0 NW 0.0 0.0
East 120.0 12 0.56 806 NE 0.0 0.0
NW 0.0 138 0.56 0 SW 0.0 0.0
NE 0.0 12 0.56 0 SE 0.0 0.0
SW 0.0 85 0.56 0 OTHER DATA TO BE FILLED
SE 0.0 12 0.56 0 AREA 1116 sft
Solar and trans gain-walls&roof ROOF HEIG 10 ft
North 80.0 19.0 0.36 547 FALSE CEIL 9 ft
South 240.0 31.0 0.36 2678 NO OF F.A 1 PER HR.
West 0.0 27.0 0.36 0 NO. OF PEO 20
East 300.0 33.0 0.36 3564 GUINIE PIG 0
NW 0.0 21.0 0.36 0 RABBITS 0
NE 0.0 25.0 0.36 0 RATS 0
SW 0.0 29.0 0.36 0 MICE 0
SE 0.0 33.0 0.36 0 LIGHTING 1.5 W/S. FT
Roof -Sun 1116.0 50.0 0.51 28458 EQUIPMENT 1.0 KW
Roof -Sun-Ins 0.0 50.0 0.12 0 DIVERSITY 1
Roof -Shaded 27.0 0.48 0 SH PER PE 245 Btu/hr
Transmission gain-except walls & roof LH PER PE 205 Btu/hr
All glass 120.0 30.0 1.13 4068 BPF 0.12
Partition 200.0 25.0 0.36 1800 CFM/PERSO 12
Ceiling 1116.0 25.0 0.42 11718 EXHAUST 0
Floor 0.0 25.0 0.42 0 FLOOR GAI 0 (1 if fl. gain exists else 0)
Infiltration and Outside air ROOF(0)/CE 0
Infiltration 0 ROOF 0 (1 if Roof provided Insulation e
Outsideair 240 30.0 1.08 0.12 933 PARTITION 0 (1 if Mod.Partitions exists else
Internal Heat CEILING 1 (1 if Mod.Ceiling Panels exists
People 20 245 0 4900 PRE-COOLI 0 (1 if Pre-cooling/TFA exists els
Lights 1116 1.5 3.413 5713 ADP&SHR 0 (1 if ADP & SHR revised else 0
Equipment 1.00 1 3413 3413 Motor bkw 0.650IF ADP & SHR REVISED,CON
Guinie Pigs 0 32 0 SHR 0.93 REV. ESHR
Rabbits 0 61 0 ADP 52.02 REV. ADP
Rats 0 22 0 TR 8.56 REV. TR
Mice 0 3.3 0 Dehumd. C 3702 REV. AIR QTY CFM
Motor BKW 0.65 1 3413 2218 Reheat,KW N/A RE- HEAT IN KWTO INCREA
Room sensible heat-sub total 70818
2%Duct leakage& 2%R.A.Heat Regain 10% 6519 FRESH AIR REQUIREMENT
Room Sensible Heat Total 77337 NOS CFM/PER
Room Latent Heat PEOPLE 20 12
Infiltration 0 EXHAUST
outsideair 240 68.2 0.68 0.12 1335 NO. OF A/ 1
People 20 205 4100 TOTAL FRESH AIR
Guinie Pigs 0 15 0
Rabbits 0 18 0 PRE-COOLING COIL
Rats 0 11 0 DB 'F WB 'F
Mice 0 1.7 0 LEV. COND 56.0 55.9
Vap.Trans 0 INSIDE 69.0 58.9
Room Latent Heat Sub-Total 5435
Duct leakage& R.A.Heat Regain + Safe 5% 272 DIFF. -13.0
Room Latent Heat Total 5706
Room Total Heat (Sensible + Latent) 83043 1. SUPPLY AIR TEMP. ( ROOM O/L AIR)
Outside Air Heat Trm-( RSH/(1.08 x (De. CFM+CFMoa))
air qty temp diff const 1 - bf * If above is too high. Determine supply CFM
Sensible 240 30.0 1.08 0.88 6843 for desired diff. By supply air qty. formula
hum diff const 2. ENTERING DRY BULB TEMPERATURE
Latent 240 68.2 0.68 0.88 9788 ( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
Grand Total Heat SubTotal 99674 3. ENTERING AIR MOISTURE CONTENT
Heat gain% +leak gain%+ hp pump%+dehum 3% 2990 (CFM oa*Woa+CFM ra*Wrm)/CFM da
Re- heat N/A 4. LEAVING DRY BULB TEMPERATURE
GRAND TOTAL HEAT 102664 ( Tadp + (BF(Tedb - T adp)))
tons 8.56 5. SUPPLY AIR CFM
Sensible heat factor 0.93 ( RSH/1.08 X (Trm-Tsa)
Indicated adp 'f 52.02 From psychrometric chart
Selected adp 'F 55.00
Dehumidifier rise (1-bf)*(rm temp -adp) 19.34 # when bypassing a mixture of OA & RA use supply
Dehumidified air qty (Cfm) S.heat/(1.08*deh.r 3702 bypassing RA only, use deh. CFM
e for SUMMER Cooling and Dehumidifying Heat Load E
RH TH GR/LB Estmated By SRI
41% 47.1 137.0 Date 18/03/2010
55% 28.5 68.8 Coustomer M/s.Tanuku Corporate Hosipital
18.6 68.2 Location Tanuku
Room STAFF
RTITION AREAS (ft ) U' FACTORS
2
Classification
PARTNS WALL 0.360 AHU Tag No SYSTEM-1
0.0 GLASS 0.560 Item Sun gain Factor Btu/hr
0.0 ALL GLASS 1.130 Solar gain glass
200.0 PARTITION 0.360 North 0.0 23 0.56 0
0.0 M.PARTN 0.150 South 0.0 12 0.56 0
0.0 CEILING 0.424 West 0.0 163 0.56 0
0.0 M.CLG.PAN 0.150 East 120.0 12 0.56 806
0.0 FLOOR 0.424 NW 0.0 138 0.56 0
0.0 ROOF 0.510 NE 0.0 12 0.56 0
SW 0.0 85 0.56 0
The ADP Table SE 0.0 12 0.56 0
FOR 70.0 & 55%RH Solar and trans gain-walls&roof
SHR ADP North 80.0 -2.0 0.36 -58
1 53.1 52.02 South 240.0 10.0 0.36 864
0.93 52 0.00 West 0.0 6.0 0.36 0
0.83 50 0.00 East 300.0 12.0 0.36 1296
0.77 48 0.00 NW 0.0 0.0 0.36 0
0.73 46 0.00 NE 0.0 4.0 0.36 0
0.71 44 0.00 SW 0.0 8.0 0.36 0
0.68 42 0.00 SE 0.0 12.0 0.36 0
0.66 38 0.00 Roof -Sun 1116.0 29.0 0.51 16506
0.64 32 0.00 Roof -Sun- 0.0 29.0 0.12 0
Roof -Shaded 6.0 0.48 0
Transmission gain-except walls & roof
All glass 120.0 9.0 1.13 1220
Partition 200.0 4.0 0.36 288
Ceiling 1116.0 4.0 0.42 1875
(1 if fl. gain exists else 0) Floor 0.0 4.0 0.42 0
Infiltration and Outside air
(1 if Roof provided Insulation else 0) Infiltration 0
(1 if Mod.Partitions exists else 0) Outsideair 240 9.0 1.08 0.12 280
(1 if Mod.Ceiling Panels exists else 0) Internal Heat
(1 if Pre-cooling/TFA exists else 0) People 20 245 0 4900
(1 if ADP & SHR revised else 0) Lights 1116 1.5 3.413 5713
IF ADP & SHR REVISED,CONSIDER FOLWG Equipment 1.00 1 3413 3413
REV. ESHR 0.97 Guinie Pigs 0 32 0
REV. ADP 50 Rabbits 0 61 0
0.00 Rats 0 22 0
REV. AIR QTY CFM 0 Mice 0 3.3 0
RE- HEAT IN KWTO INCREASE A 0.00 Motor BK 0.65 1 3413 2218
Room sensible heat-sub total 39322
AIR REQUIREMENT 2%Duct leakage& 2%R.A.Heat Rega 10% 3369
ACH NET (CFM) Room Sensible Heat Total 42692
240 Room Latent Heat
0 Infiltration 0
186 186 outsideair 240 81.9 0.68 0.12 1603
240 People 20 205 4100
Guinie Pigs 0 15 0
PRE-COOLING COIL Rabbits 0 18 0
RH TH GR/LB Rats 0 11 0
99.5 23.8 66.7 Mice 0 1.7 0
1 25.6 58.2 Vap.Trans 0
Room Latent Heat Sub-Total 5703
-1.8 8.5 Duct leakage& R.A.Heat Regain + S 5% 285
Room Latent Heat Total 5988
P. ( ROOM O/L AIR) 55.84 0F Room Total Heat (Sensible + Latent) 48680
CFM+CFMoa)) Outside Air Heat
Determine supply CFM air qty temp diff const 1 - bf
pply air qty. formula Sensible 240 9.0 1.08 0.88 2053
ULB TEMPERATURE #VALUE! F 0
hum diff const
ra X Trm)/CFMsa) Latent 240 81.9 0.68 0.88 11756
OISTURE CONTENT 82.189451 Gr./lb Grand Total Heat SubTotal 62488
*Wrm)/CFM da Heat gain% +leak gain%+ hp pump%+de 3% 1875
LB TEMPERATURE 51.44 0F Re- heat 2838
GRAND TOTAL HEAT 67201
3942.12 F
0
tons 5.60
Sensible heat factor 0.88
T ewb = 0
F Indicated adp 'f 52.02
T lwb = 0
F Selected adp 'F 55.00
ixture of OA & RA use supply CFM, when Dehumidifier rise (1-bf)*(rm temp -adp) 19.34
use deh. CFM Dehumidified air qty (Cfm) S.heat/(1.08*deh.rise 2044
difying Heat Load Estimate for MONSOON
CONDITION DB 'F WB 'F RH TH GR/LB
OUTSIDE 83.0 80.0 87% 43.6 150.7
ROOM 74.0 63.0 55% 28.5 68.8
DIFFERENC 9.0 15.0 81.9

GLASS, WALL & PARTITION AREAS (ft2) U' FACTORS


GLASS WALLS PARTNS WALL 0.360
NORTH 0.0 80.0 0.0 GLASS 0.560
SOUTH 0.0 240.0 0.0 ALL GLASS 1.130
WEST 0.0 0.0 200.0 PARTITION 0.360
EAST 120.0 300.0 0.0 M.PARTN 0.150
NW 0.0 0.0 0.0 CEILING 0.424
NE 0.0 0.0 0.0 M.CLG.PAN 0.150
SW 0.0 0.0 0.0 FLOOR 0.424
SE 0.0 0.0 0.0 ROOF 0.510
OTHER DATA TO BE FILLED
AREA 1116 sft The ADP Table
ROOF HEI 10 ft FOR 70.0 & 55%RH
FALSE CEI 9 ft SHR ADP
NO OF F.A 1 PER HR. 1 53.1 52.02
NO. OF PE 20 0.93 52 0.00
GUINIE PI 0 0.83 50 0.00
RABBITS 0 0.77 48 0.00
RATS 0 0.73 46 0.00
MICE 0 0.71 44 0.00
LIGHTING 1.5 W/S. FT 0.68 42 0.00
EQUIPMEN 1.0 KW 0.66 38 0.00
DIVERSIT 1 0.64 32 0.00
SH PER P 245 Btu/hr
LH PER P 205 Btu/hr
BPF 0.12
CFM/PERS 12
EXHAUST 0
FLOOR GA 0 (1 if fl. gain exists else 0)
ROOF(0)/C 0
ROOF 0 (1 if Roof provided Insulation else 0)
PARTITIO 0 (1 if Mod.Partitions exists else 0)
CEILING 1 (1 if Mod.Ceiling Panels exists else 0)
PRE-COOL 0 (1 if Pre-cooling/TFA exists else 0)
ADP&SHR 0 (1 if ADP & SHR revised else 0)
Motor bkw 0.650IF ADP & SHR REVISED,CONSIDER FOLWG
SHR 0.88 REV. ESHR 0.97
ADP 52.02 REV. ADP 50
TR 5.60 REV. TR 0.00
Dehumd. 2044 REV. AIR QTY CFM 0
Reheat,KW 0.83 RE- HEAT IN KWTO INCREASE A 0.00

FRESH AIR REQUIREMENT


NOS CFM/PER ACH NET (CFM)
PEOPLE 20 12 240
EXHAUST 0
NO. OF A 1 186 186
TOTAL FRESH AIR 240

PRE-COOLING COIL
DB 'F WB 'F RH TH GR/LB
LEV. CON 56.0 55.9 99.5 23.8 66.7
INSIDE 69.0 58.9 1 25.6 58.2

DIFF. -13.0 -1.8 8.5

1. SUPPLY AIR TEMP. ( ROOM O/L AIR) 56.69 0F


Trm-( RSH/(1.08 x (De. CFM+CFMoa))
* If above is too high. Determine supply CFM
for desired diff. By supply air qty. formula
2. ENTERING DRY BULB TEMPERATURE #VALUE! 0F
( CFM oa x Toa)+(CFMra X Trm)/CFMsa)
3. ENTERING AIR MOISTURE CONTENT 82.189451 Gr./lb
(CFM oa*Woa+CFM ra*Wrm)/CFM da
4. LEAVING DRY BULB TEMPERATURE 51.44 0F
( Tadp + (BF(Tedb - T adp)))
5. SUPPLY AIR CFM 2283.66 0F
( RSH/1.08 X (Trm-Tsa)
From psychrometric chart T ewb = 0
F
T lwb = 0
F
# when bypassing a mixture of OA & RA use supply CFM, when
bypassing RA only, use deh. CFM