Type ICX
Outdoor open type cutout
Product features
−− 7.8 kV, 15 kV, 15/27 kV, 27 kV, or 38 kV on 100 A
7.8 kV, 15 kV, and 15/27 kV only on 200 A
−− 110, 125, 150, 170, or 180 kV BIL
180 kV BIL available as V silicone only
−− 100 A, 200 A continuous current fused and up to 16 kA
interrupting current on 15 kV, 100 A only
−− 300 A disconnect blade
−− Porcelain, polymer concrete, or silicone insulators available
−− Seacoast design
−− Cutout/arrester combo
−− Kick-out spring available for the 100 A and 200 A tubes.
Description
The ICX cutout is used on overhead distribution systems to
provide overcurrent protection and visible indication of fuse
operation. The ICX provides a visible break sectionalizing point for
maintenance personnel and is equipped with hooks for use with
a portable loadbreak tool. This allows the ICX to be used as a
loadbreak switch to open the circuit with load current flowing.
Ratings Interchangeability
The ICX is offered in several frame sizes to properly match each The ICX cutout is designed to be electrically and mechanically
system BIL. Each fuse support has “universal” contacts that interchangeable with the Hubbell (A.B. Chance) type “C”
accommodate a 100 A fuseholder, a 200 A fuseholder, or a 300 A and Cooper type “L” cutouts. Testing has confirmed the
disconnect blade. performance of the ICX fuseholder and fuse support with S&C
and Chance.
Design features
The ICX 100 A fuse is provided with a moisture-proof tube Standards and design testing
as a standard offering. Cutouts perform by expelling gases The ICX cutout meets or exceeds all applicable requirements of
during interruption from the bottom of the fuse tube. For the IEEE C37.41 and C37.42 standards.
highest interrupting rating, a link extender rod is attached to
the fuse tube cap, improving the efficiency of gas expulsion Warranty
and arc interruption. Fuse tubes are clearly labeled to indicate A ten-year warranty is offered on silicone and polymer concrete
interrupting capability. ICX cutouts and a five-year warranty is offered on porcelain ICX
cutouts.
Options and construction details
7.75
[197]
C 4.12-5.12
4.12-5.12
[105-130] [105-130] 7.75
C [197]
1.56
[40] 2.69-4.00 1.50
FR [68-102] [38]
FR
D
D
17-20 DEG
1.00
[25]
E E
Bracket dimensions
.312 .375 .38
[8] [10] [10]
1.5
1.6 1.6 [38]
[40] [40]
Digit 4 Digit 11
Digit 2 Cutout cap Cutout insulator material
Voltage level Digit 6
S = 100A Solid cap Arrester type
1 = 15 kV Digit 9 (Blank) = Porcelain
L = 100A Link extender C = Polymer normal duty Cutout terminals
J = Silicone
2 = 27 kV
T = 200A Solid cap H = Polymer heavy duty 1 = Clamshell Z = Polymer concrete
3 = 38 kV (use (only available for
150 kV BIL M = 200A Link extender R = Polymer riser pole 2 = Eyebolt 110 and 125 kV BIL
insulator) cutouts)
C
Digit 3 Digit 5 Digits 7-8 Digit 10
Insulator BIL Bracket Arrester voltage Special options
03 = 3 kV 15 = 15 kV 1 = None
1 = 110 kV BIL U = Standard combo
06 = 6 kV 18 = 18 kV 8 = 12" lead
2 = 125 kV BIL Contact factory for B = Arrester bird guard
other options 09 = 9 kV 21 = 21 kV
5 = 150 kV BIL S = Seacoast cutout
10 = 10 kV 24 = 24 kV
X = No arrester but in
12 = 12 kV 27 = 27 kV combo box
ICX Cutouts
15 kV, 110 kV BIL
Digit 11
Additional options
Digit 4 Digit 6
Terminal connectors Special options
K = Kick-out spring
on fuse tube
C = Clamshell N = None
Digit 2 S = Seacoast design
Insulator BIL E = Eyebolt F = Wildlife guard silicone
X 1
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = Porcelain N = No bracket AM11 = 100A, 10 kA asym, solid cap
J = Silicone A = NEMA A
LM11 = 100A, 16 kA asym, link extender
B = NEMA B
Z = Polymer concrete KA21 = 200A, 10 kA asym, link extender
F = NEMA B with 6"
S = Seacoast design carriage bolts
PA21 = 200A, 12 kA asym, link extender
porcelain
L = Extended (7.8 kV)
CA31 = 300A, solid blade
0000 = Fuse support only (no tube)
Digit 11
Digit 4 Digit 6 Additional options
Terminal connectors Special options
C = Seacoast silicone
C = Clamshell N = None and kickout spring
Digit 2
Insulator BIL E = Eyebolt F = Wildlife guard K = Kick-out spring on
fuse tube
R = Rotatable D = Bottom terminal
2 = 125 kV BIL S = Seacoast design
(bottom terminal) rotated 90° silicone
X 2
Digit 3 Digit 5 Digit 7-10
Fuse supports Bracket Fuseholder
N = Porcelain N = No bracket AM12 = 100A, 8 kA asym, solid cap
Z = Polymer concrete B = NEMA B BA22 = 200A, 10 kA asym, solid cap (15 kV)
(125 kV BIL) F = NEMA B with 6"
carriage bolts DA32 = 300A, solid blade
S = Seacoast design
porcelain L = Extended WA22 = 200A, 10 kA asym, link extender
(15/27 kV)
X
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = Porcelain N = No bracket AM12 = 100A, 8 kA asym, solid cap
J = Silicone A = NEMA A MM12 = 100A, 12 kA asym, link extender
B = NEMA B
S = Seacoast design BA22 = 200A, 10 kA asym, solid cap (15 kV)
porcelain F = NEMA B with 6"
carriage bolts DA32 = 300A, Solid blade
L = Extended VA22 = 200A, 12 kA asym, link extender
0000 = Fuse support only (no tube)
Digit 11
Additional options
C = Seacoast silicone
Digit 2 Digit 4 Digit 6 and kickout spring
Insulator BIL Terminal connectors Special options
K = Kick-out spring
on fuse tube
4 = 150 kV BIL C = Clamshell N = None (100 A only)
600 mm creep
(silicone only) E = Eyebolt F = Wildlife guard
S = Seacoast design
5 = 150 kV BIL D = Bottom terminal silicone
R = Rotatable
(bottom terminal) rotated 90°
X
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = Porcelain N = No bracket TM12 = 100A, 10 kA asym, link extender
J = Silicone A = NEMA A
X 6
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = Porcelain N = No bracket
AM12 = 100A, 8 kA asym, solid cap (27 kV)
A = NEMA A
MM12 = 100A, 12 kA asym, link extender (27 kV)
S = Seacoast design
porcelain B = NEMA B
BA22 = 200A, 10 kA asym, solid cap (15 kV)
F = NEMA B with 6"
carriage bolts DA32 = 300A, Solid blade (27 kV)
L = Extended VA22 = 200A, 12 kA asym, link extender (27 kV)
TM12 = 100A, 10 kA asym, link extender (38 kV)
0000 = Fuse support only (no tube)
X 8 J
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = No bracket
J = Silicone MM12 = 100A, 12 kA asym, link extender
A = NEMA A
DA32 = 300A, Solid blade
B = NEMA B
AM12 = 100A, 8 kA asym, solid cap
F = NEMA B with 6"
carriage bolts TM12 = 100A, 10 kA asym, solid cap (38 kV)
L = Extended
0000 = Fuse support only (no tube)
Digit 4 Digit 6
Terminal connectors Special options
C = Clamshell N = None
Digit 11
Digit 2 Additional options
Insulator BIL E = Eyebolt F = Wildlife guard
K = Kick-out spring
R = Rotatable D = Bottom terminal on fuse tube
7 = 170 kV BIL (bottom terminal) rotated 90°
X 7 N
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = No bracket
N = Porcelain XA26 = 200A, 8 kA sym, link extender
A = NEMA A
S = Seacoast design YM16 = 100A, 8 kA sym, link extender
porcelain B = NEMA B
SA24 = 200A, 10 kA asym, link extender
F = NEMA B with 6"
carriage bolts (15/27 kV)
0000 = Fuse support only (no tube)
L = Extended
X 7 N
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
L = Extended
C = Clamshell N = None
Digit 11
Digit 2 Additional options
Insulator BIL E = Eyebolt F = Wildlife guard
K = Kick-out spring
R = Rotatable D = Bottom terminal on fuse tube
7 = 170 kV BIL (bottom terminal) rotated 90°
X 7 N
Digit 3 Digit 5 Digits 7-10
Fuse supports Bracket Fuseholder
N = No bracket
N = Porcelain RM15 = 100A, 10 kA asym, link extender
A = NEMA A
S = Seacoast design FA35 = 300A, disconnect
porcelain B = NEMA B
ZM15 = 100A, 8 kA sym, link extender
F = NEMA B with 6"
carriage bolts 0000 = Fuse support only (no tube)
L = Extended
Replacement fuseholders
Interrupting Corresponding
Style number Voltage rating (kV) BIL (kV) Current rating (A) rating (kAIC) Cap type cutout*
7194C60G01MP 15 110 100 10 Solid AM11
7194C60G02MP 15 110 100 16 Link extender LM11
7194C60G03 7.8 110 200 12 Link extender PA21
7194C60G19 15 110 200 10 Link extender KA21
7194C60G04 15 110 300 - Solid disconnect blade CA31
7194C60G05MP 27 125 or 150 100 8 Solid AM12
7194C60G06MP 27 125, 150, or 180 100 12 Link extender MM12
7194C60G07 15 125 or 150 200 10 Solid BA22
7194C60G08 27 125 or 150 300 - Solid disconnect blade DA32
7194C60G08 38 150 300 - Solid disconnect blade DA32
7194C60G11MP 27 170 100 12 Link extender RM14
7194C60G12 38 170 300 - Solid disconnect blade FA34
7194C60G26 27 125 or 150 200 12 Link extender VA22
7194C60G29 38 170 100 10 Link extender RM15
* Used with ICX cutouts having the following characters in digit positions 7-10 of the ABB cutout style number.
Interrupting
Style number Voltage rating (kV) BIL (kV) Current rating (A) rating (kAIC) Cap type
3A31186A01 15 110 100 10 Solid
9861A62A05 15 110 100 16 Link extender
9861A62A08 7.8 110 200 12 Link extender
3A31187A01 15/27 125 or 150 200 10 Solid
3A31186A01 27 125 or 150 100 8 Solid
9861A62A06 27 125, 150, or 180 100 12 Link extender
9861A62A07 27 170 100 12 Link extender
9861A62A11 38 170 100 10 Link extender
Brackets
Style number Type
366C723A05 NEMA A
403A101A03 NEMA B
367C802A04 Extended
ABB Inc.
Medium Voltage Apparatus
3022 NC 43 North
Pinetops, NC 27864
USA
Phone: +1 252 827 3212
Fax: +1 252 827 4286
www.abb.com/mediumvoltage
Note:
The information contained in this document is for general information purposes
only. While ABB strives to keep the information up to date and correct, it makes
no representations or warranties of any kind, express or implied, about the
completeness, accuracy, reliability, suitability or availability with respect to the
information, products, services, or related graphics contained in the document for
any purpose. Any reliance placed on such information is therefore strictly at your
own risk. ABB reserves the right to discontinue any product or service at any time.