STG GENERATOR TRIP LOGIC


S NO PROT CODE DESCRIPTION CLASS-A CLASS-B CLASS-C CLASS-GT
1 87O OVERALL DIFFERENTIAL PROTN X X
2 87G GEN DIFFERENTIAL PROTN X
3 64F GEN ROTOR E/F PROTN X
4 26 GEN STATOR FRAME TEMP HIGH X
5 5 EMERGENCYTRIP PUSHBUTTON OPTD X
6 64G2 95% STATOR E/F PROTN X
7 40G LOSS OF EXCITATION WITH U/V PROT X
8 27/40G LOSS OF EXCITATION WITHOUT U/V PROT X
9 81.3 OVER FREQUENCY PROTN X
10 TURBINE PROTECTION TRIP X
11 81.2 UNDER FREQUENCY PROTN X
12 78G OUT OF STEP PROTN X
13 46 G GEN NEGATIVE PHASE SEQUENCE PROTN-I X
14 61B DEAD MACHINE PROTN X
15 32G REVERSE POWER PROTN X
16 32.2 LOW FORWARD POWER PROTN X
17 99 GEN OVERFLUX PROTN X
18 51.2 VOLT. RESTRAINT O/C PROTN X
19 27 UNDER VOLTAGE PROTN X
20 59.2 OVER VOLTAGE PROTN X
21 51B LOCAL BREAKER BACKUP PROTN X
22 48G GEN NEGATIVE PHASE SEQUENCE PROTN-II X
23 21G BACKUP IMPEDANCE PROTN X
24 59N NEUTRAL DISPLACEMENT PROTN X
25 64 G1 100% GEN STATOR E/F PROTN ANNUNCIATION ONLY
26 51.1 GEN O/C PROTN WITH TIME DELAY UNIT ANNUNCIATION ONLY
27 60 PT FUSE FAILURE PROTN ANNUNCIATION ONLY

NOTE

CLASS-A 11 KV GTG CB TRIP AND EX FIELD BKR TRIP

CLASS-B TURBINE TRIP

CLASS-C 11 KV GTG CB TRIP AND EX FIELD BKR TRIP

CLASS-GT 110 KV GTG BREAKER TRIP