© Siemens AG 2016
Price groups
PG 41A, 41B, 41H
4/2 Introduction
4
4/26 SIRIUS 3RT26 contactors for
capacitive loads (AC-6b), 3-pole
4/34 SIRIUS 3RT13 contactors, 4-pole
4/38 - Accessories
4/48 - Spare parts
4/50 3TK1 contactors for resistive loads
(AC-1), 4-pole
4/53 - Accessories and spare parts
for 3TK1 contactors
4/54 3TK20 miniature contactors for
resistive loads (AC-1), 4-pole
Contactors for railway applications
4/62 - SIRIUS 3RT contactors with extended
operating range, 3-pole
4/68 - SIRIUS 3RH2 contactor relays
with extended operating range
4/71 - 3TH4 contactor relays, 8-pole
4/73 - 3TC contactors for switching
DC voltage, 2-pole
4/75 3TC contactors for switching
DC voltage, 1-pole and 2-pole
Note:
You will find 3RT1 contactors
in sizes S00 to S12
- in the Catalog Add-On
IC 10 AO · 2016 in the Information
and Download Center
- in the interactive Catalog CA 01
- in the Industry Mall
Conversion tool
e. g. from 3RT13 to 3RT23: see
www.siemens.com/sirius/conversion-tool
Siemens IC 10 · 2017
© Siemens AG 2016
■ Overview
More information
Home page, see www.siemens.com/sirius Conversion tool e.g. from 3RT13 to 3RT23, see
Industry Mall, see www.siemens.com/product?3RT_3TK_3TC www.siemens.com/sirius/conversion-tool
Online configurator for 3RT20 contactors, see
www.siemens.com/sirius/configurators
4
Size S00 S0
Type 3RT231., 3RT251. 3RT232., 3RT2526
4-pole 3RT23, 3RT25 contactors
Type 3RT2316 3RT2317 3RT2516 3RT2517 3RT2518 3RT2325 3RT2326 3RT2327 3RT2526
Number of main contacts 4 NO 2 NO + 2 NC 4 NO 2 NO + 2 NC
AC, DC operation (p. 4/17, 4/19) (p. 4/23, 4/24) (p. 4/17 ... 4/19) (p. 4/23, 4/24)
AC-1
Ie at 690 V [40 °C / 60 °C] A 18 / 16 22 / 20 18 / 16 22 / 20 22 / 20 35 / 30 40 / 35 50 / 42 40 / 35
P at 400 V 40 °C kW 11.5 14 11.5 14 14 23 26 33 26
60 °C kW 10.5 13 10.5 13 13 20 23 28 23
AC-2 and AC-3
Ie at 400 V NO A 9 12 9 12 16 15.5 15.5 15.5 25
NC A -- -- 9 9 9 -- -- -- 25 (20)1)
P at 400 V (NC for DC operation) NO / kW 4 5.5 4 5.5 / 4 7.5 / 4 7.5 7.5 7.5 11 (7.5)1)
NC
At 230 V NO / kW 2.2 3 3 3 / 2.2 4 / 2.2 4 4 4 5.5
NC
4
Type 3RT2336 3RT2337 3RT2535 3RT2536 3RT2446 3RT2448 3RT1344 3RT1346 3RT1456 3RT1466 3RT1476
Number of main contacts 4 NO 2 NO + 2 NC 3 NO 4 NO 3 NO
AC, DC operation (p. 4/17, 4/18, 4/20) (p. 4/23, 4/25) (p. 4/11) (p. 4/36) (p. 4/12)
AC-1 ( 690 V)
Ie 40 °C A 60 110 60 70 140 160 110 140 275 400 690
60 °C A 55 95 55 60 130 140 100 120 250 380 650
P at 400 V 40 °C kW 36 63 36 39 92 105 72 92 180 263 454
At 230 V 40 °C kW 21 36 21 23 53 61 42 53 105 151 261
At 500 V 40 °C kW -- -- -- -- -- -- -- -- 225 329 568
At 690 V 40 °C kW -- -- -- -- 159 182 -- -- 310 454 783
at 1 000 V 60 °C kW -- -- -- -- -- -- -- -- 165 247 410
AC-2 and AC-3
Ie/400 V A -- -- 35 41 44 44 -- -- 97 138 170
P at 400 V kW -- -- 18.5 22 22 22 -- -- 55 75 90
At 230 V kW -- -- 11 11 12.7 12.7 -- -- 30 37 55
At 500 V kW -- -- -- -- 29.9 29.9 -- -- 55 90 110
At 690 V kW -- -- -- -- 38.2 38.2 -- -- 90 132 160
Size -- 00
Type 3TK1. 3TK20
4-pole 3TK contactors
4
■ Overview
Standards Sizes S6 to S12: AC/DC operation (50/60 Hz AC and DC)
IEC 60947-1, EN 60947-1, • Withdrawable coils with integrated coil circuit (varistor)
IEC 60947-4-1, EN 60947-4-1, • Auxiliary and control conductors: Screw terminals
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) • Main conductors: Busbar connections
The contactors are suitable for use in any climate. Operating mechanism types
They are finger-safe according to IEC 60529.
Two types of solenoid operation are available:
3RT.4 contactors are used for switching resistive loads (AC-1)
or as contactors, that normally only have to carry the current, • Conventional operating mechanisms
for example for variable-speed operating mechanisms. • Solid-state operating mechanism
The accessories and spare parts of the 3RT contactors can also - The operating mechanism for the contactors features solid-
4
be used here, see from page 3/75 onwards. state control of the contactor coil. Overvoltage damping of
the operating mechanism coil is already integrated in the
For a general description of 3RT contactors, sizes S3 to S12, electronics. The operating mechanisms are powered via a
see from page 3/15 onwards. supply voltage with an operating range from 0.7 to 1.25 x Us,
optionally also controlled depending on the chosen mode of
Size S3: AC or AC/DC operation operation. Alternatively, control is via the separate 24 V DC
• Coil circuits (varistors, diodes, etc.) retrofittable control signal input. Various rated voltage ranges for AC/DC
• Auxiliary switches can be retrofitted control are available.
- This version is additionally available with a 24 V DC PLC
• Main and control conductors: Screw terminals relay output and a remaining lifetime indicator (RLT).
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/24229/td • System Manual "SIRIUS – System Overview",
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/24229/faq https://support.industry.siemens.com/cs/WW/en/view/60311318
• Manual "SIRIUS – SIRIUS 3RT Contactors/Contactor Assemblies",
https://support.industry.siemens.com/cs/WW/en/view/60306557
• Application Manual "SIRIUS Controls with IE3/IE4 Motors,
https://support.industry.siemens.com/cs/ww/en/view/94770820
- Screw terminals W mm 70 x 140 x 196 120 x 172 x 217 145 x 210 x 251 160 x 214 x 271
- Spring-type terminals mm 70 x 140 x 200 --
• Basic unit with mounted function
module or solid-state time-delayed
auxiliary switch block
- Screw/spring-type terminals mm 70 x 140 x 226 --
Permissible mounting position
NSB0_00478c
22,5° 22,5°
The contactors are designed for operation on a vertical 90° 90°
mounting surface.
NSB0_00477a
4
• AC operation, 50/60 Hz, Closing VA 326/326 -- --
for USA/Canada P.f. 0.62/0.55 -- --
Closed VA 22/22 -- --
P.f. 0.38/0.4 -- --
• AC/DC operation Closing for AC operation VA -- 163 --
P.f. -- -- --
Closed for AC operation VA -- 3.1 --
P.f. -- -- --
Closing for DC operation W -- 761) --
Closed for DC operation W -- 1.8 --
Power consumption of the solenoid operating mechanism
(for cold coil and rated range Us min ... Us max)
• Conventional operating mechanisms
- AC operation Closing for Us min/Us max VA -- 250/300 490/590 700/830
P.f. -- 0.9
Closed at Us min/Us max VA -- 4.8/5.8 5.6/6.7 7.6/9.2
P.f. -- 0.8 0.9
- DC operation Closing for Us min/Us max W -- 300/360 540/650 770/920
Closed at Us min/Us max W -- 4.3/5.2 6.1/7.4 8.5/10
• Solid-state operating mechanism
- AC operation Closing for Us min/Us max VA -- 190/280 400/530 560/750
P.f. -- 0.8
Closed at Us min/Us max VA -- 3.5/4.8 5.5/8.5 5.6/9
P.f. at Us min/Us max -- 0.6/0.6 0.5/0.4
- DC operation Closing for Us min/Us max W -- 250/320 440/580 600/800
Closed at Us min/Us max W -- 2.1/2.8 2.8/3.4 3/3.6
PLC control input (IEC 61131-2, type 2) V DC -- 24, at 30 mA power consumption
• Operating range V DC -- 17 ... 30
Operating times for 1.0 x Us2)
• AC operation Closing delay ms 13 ... 50 50 ... 70 --
Opening delay ms 10 ... 21 38 ... 57 --
• DC operation Closing delay ms -- 50 ... 70 --
Opening delay ms -- 38 ... 57 --
Operating times
(Total break time = Opening delay + Arcing time)
• Conventional operating mechanisms
- For Us min ... Us max Closing delay ms -- 25 ... 50 35 ... 50 50 ... 70
Opening delay ms -- 40 ... 60 50 ... 80 70 ... 100
• Solid-state operating mechanism, actuated via A1/A2
- For Us min ... Us max Closing delay ms -- 100 ... 120 110 ... 130 125 ... 150
Opening delay ms -- 80 ... 100
• Solid-state operating mechanism, actuated via PLC input
- For Us min ... Us max Closing delay ms -- 40 ... 60 50 ... 65 65 ... 80
Opening delay ms -- 80 ... 100
• Arcing time ms -- 10 ... 15
1) In the case of DC coils, increased starting currents (2.6 A on average)
arise during the first 200 ms. For direct control from a PLC, we recommend
special 3RT204. -.KB4. coupling contactors with adapted power
consumption, suitable for a PLC output current of 2 A (see page 3/64).
2)
The OFF-delay of the NO contact and the ON-delay of the NC contact
are increased if the contactor coils are attenuated against voltage peaks
(varistor +2 to 5 ms, diode assembly: 2x to 6x).
4
- 2 conducting paths in series Up to 24 V A 130 140 250 380 500
60 V A 130 140 250 380 500
110 V A 130 140 250 380 500
220 V A 1.75 2.5
440 V A 0.42 0.65
600 V A 0.27 0.37
- 3 conducting paths in series Up to 24 V A 130 140 250 380 500
60 V A 130 140 250 380 500
110 V A 130 140 250 380 500
220 V A 4 250 380 500
440 V A 0.8 1.4
600 V A 0.45 0.75
Switching frequency
Switching frequency z in operating cycles/hour
• Contactors without overload relays No-load switching 1/h 5 000 1 000 2 000
frequency AC
AC/DC no-load switching 1/h -- 1 000 2 000
frequency
• Rated operation Acc. to AC-1 (AC/DC) 1/h 650 600
Acc. to AC-3 (AC/DC) 1/h 800 1 000
Dependence of the switching frequency z’ on
the operational current I’ and operational voltage U ’:
z’ = z (Ie/I’ ) (Ue/U ’)1.5 1/h
• Finely stranded without end sleeve mm² 16 ... 70 16 ... 120 70 ... 240
4
• Finely stranded without end sleeve mm² 16 ... 70 16 ... 120 120 ... 185
• Stranded mm² 16 ... 70 16 ... 120 120 ... 240
• AWG cables, solid or stranded AWG 6 ... 2/0 6 ... 250 kcmil 250 ... 500 kcmil
• Ribbon cable conductors mm Min. 3 x 9 x 0.8, Min. 3 x 9 x 0.8, Min. 6 x 9 x 0.8,
(Number x Width x Thickness) max. 6 x 15.5 x 0.8 max. 10 x 15.5 x 0.8 max. 20 x 24 x 0.5
Both clamping points connected
(minimum cross-section 16 mm²)
• Finely stranded with end sleeve (DIN 46228-1) mm² Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
• Finely stranded without end sleeve mm² Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
NSB0_00481
• Stranded mm² Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 70, max. 2 x 240
• AWG cables, solid or stranded AWG Max. 2 x 1/0 Max. 2 x 3/0 Min. 2 x 2/0,
max. 2 x 500 kcmil
• Ribbon cable conductors mm Max. 2 x (6 x 15.5 x 0.8) Max. 2 x (10 x 15.5 x 0.8) Max. 2 x (20 x 24 x 0.5)
(Number x Width x Thickness)
Busbar connections
• Connecting bar (max. width) mm 17 25
Cable lug connection 1) 2)
4
3RT244.-1.. .0
Size Rated data AC-1, Auxiliary contacts Rated control supply SD Screw terminals PU PS* PG
tu: 40 °C voltage Us (UNIT,
Opera- Ratings of Ident. Version SET, M)
tional AC loads No.
current Ie
(p.f. = 0.95) at 50 Hz and Article No. Price
up to 230 V 400 V 690 V per PU
690 V
A kW kW kW NO NC V d
For screw fixing and snap-on mounting onto
TH 35 and TH 75 standard mounting rails
AC operation
1/L1 3/L2 5/L3 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 14 22
A2(–)
2/T1 4/T2 6/T3 14 22
3RT146.
Size Rated data AC-1, Auxiliary Rated control SD Screw terminals PU PS* PG
tu: 40 °C contacts supply voltage (UNIT,
Opera- Ratings of AC loads (p f. = 0.95) at Us SET, M)
tional Version Article No. Price
current Ie per PU
up to
690 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V AC/DC d
Conventional operating mechanisms
S6 275 105 180 225 310 2 2 96 ... 127 5 3RT1456-6NF36 1 1 unit 41B
200 ... 277 2 3RT1456-6NP36 1 1 unit 41B
S10 400 151 263 329 454 2 2 96 ... 127 5 3RT1466-6NF36 1 1 unit 41B
200 ... 277 2 3RT1466-6NP36 1 1 unit 41B
S12 690 261 454 568 783 2 2 96 ... 127 5 3RT1476-6NF36 1 1 unit 41B
200 ... 277 2 3RT1476-6NP36 1 1 unit 41B
For 24 V DC control signal input · with indication of remaining lifetime (RLT)
e.g. for control by PLC
A1 + -
ON OFF
1/L1 3/L2 5/L3 13 21 31 43
PLC
S6 275 105 180 225 310 1 1 96 ... 127 5 3RT1456-6PF35 1 1 unit 41B
200 ... 277 5 3RT1456-6PP35 1 1 unit 41B
S10 400 151 263 329 454 1 1 200 ... 277 5 3RT1466-6PP35 1 1 unit 41B
S12 690 261 454 568 783 1 1 200 ... 277 5 3RT1476-6PP35 1 1 unit 41B
■ Overview
Standards Mountable auxiliary contacts
IEC 60947-1, EN 60947-1, Size S00
IEC 60947-4-1, EN 60947-4-1,
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) Four auxiliary contacts, including no more than three NC
The contactors are suitable for use in any climate. Sizes S0 and S2
They are finger-safe according to IEC 60529. Four additional auxiliary contacts, including no more than
For accessories and spare parts, see page 3/75 onwards. two NC
With sizes S0 and S2, two auxiliary contacts 1 NO + 1 NC
are included in the basic version.
4
■ Application
The contactors are suitable:
• For switching resistive loads
• For isolating systems with ungrounded or poorly grounded
neutral conductors
• For system transfers when alternative AC power supplies are
used
• For use as contactors which only carry current and do not
have to switch in case of inductive loads – e.g. variable-speed
operating mechanisms
• For switching mixed loads in distribution systems (e.g. for
supplying heaters, lamps, motors, PC power supply units)
with p.f. > 0.8 according to IEC 60947-4-1 test conditions for
utilization category AC-1
For a general description of 3RT contactor, sizes S00 to S2, see
from page 3/15 onwards.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16165/td • System Manual "SIRIUS – System Overview",
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16165/faq https://support.industry.siemens.com/cs/WW/en/view/60311318
• Manual "SIRIUS – SIRIUS 3RT Contactors/Contactor Assemblies",
https://support.industry.siemens.com/cs/WW/en/view/60306557
• Application Manual "SIRIUS Controls with IE3/IE4 Motors",
https://support.industry.siemens.com/cs/ww/en/view/94770820
General data
Dimensions (W x H x D) (The values in
AC or DC operation brackets apply for
DC operation)
H
• Basic units
- Screw terminals mm 45 x 58 x 73 60 x 85 x 97 (107) 75 x 114 x 130
D
4
Solenoid coil operating range
• AC operation At 50 Hz 0.8 ... 1.1 x Us 0.8 ... 1.1 x Us
At 60 Hz 0.85 ... 1.1 x Us 0.8 ... 1.1 x Us
• DC operation At 50 °C 0.8 ... 1.1 x Us --
At 60 °C 0.85 ... 1.1 x Us --
• AC/DC operation -- 0.8 ... 1.1 x Us
Power consumption of the solenoid coils
(for cold coil and 1.0 x Us)
• AC operation, 50 Hz, standard version
- Closing VA -- 77 190
- P.f. -- 0.82 0.72
- Closed VA -- 9.8 16
- P.f. -- 0.25 0.37
• AC operation, 50/60 Hz, standard version
- Closing VA 27/24.3 37/33 81/79 210/188
- P.f. 0.8/0.75 0.8/0.75 0.72/0.74 0.69/0.65
- Closed VA 4.2/3.3 5.7/4.4 10.5/8.5 17.2/16.5
- P.f. 0.25/0.25 0.25/0.25 0.25/0.28 0.36/0.39
• AC operation, 60 Hz, USA, Canada
- Closing VA 31.7 43 87 212
- P.f. 0.77 0.77 0.76 0.67
- Closed VA 4.8 6.5 9.4 18.5
- P.f. 0.25 0.25 0.28 0.37
• AC/DC operation
- Closing for AC operation VA -- 40
- P.f. -- 0.64/0.5
- Closed for AC operation VA -- 2
- P.f. -- 1
- Closing for DC operation W -- 25
- Closed for DC operation W -- 1
• DC operation W 4 5.9 --
(closing = closed)
Operating times for 0.8 ... 1.1 x Us1)
Total break time = Opening delay + Arcing time
• AC operation
- Closing delay ms 8 ... 35 8 ... 33 9 ... 38 8 ... 40 10 ... 80
- Opening delay ms 3.5 ... 14 4 ... 15 4 ... 16 4 ... 16 10 ... 18
• DC operation
- Closing delay ms 30 ... 100 50 ... 170 --
- Opening delay ms 7 ... 13 15 ... 17.5 --
• AC/DC operation
- Closing delay ms -- 50 ... 110
- Opening delay ms -- 35 ... 55
• Arcing time ms 10 ... 15 10 10 ... 20
1) With size S00, DC operation: Operating times for 0.85 to 1.1 x Us.
Type 3RT2316 3RT2317 3RT2325 3RT2326 3RT2326- 3RT2327 3RT2336 3RT2336- 3RT2337
. .. .. -4AA0 .. .. .-4AA0
Size S00 S0 S2
Rated data of the main contacts
Load rating with AC
Utilization category AC-1,
switching resistive loads
• Rated operational currents Ie At 40 °C, up to 690 V A 18 22 35 40 50 60 110
At 60 °C, up to 690 V A 16 20 30 35 42 55 95
• Rated power of AC loads At 230 V kW 6 7.5 11 13 16 21 36
P.f. = 0.95 (at 60 °C) 400 V kW 10.5 13 20 23 28 36 63
• Minimum conductor At 40 °C mm2 2.5 4 10 16 35
cross-section for loads with Ie At 60 °C mm2 2.5 6 10 16 35
4
4
3RT231. -1A.00 3RT231.-2A. 00 3RT232.-1A. 00 3RT232. -2A.00 3RT233. -1A.00
Rated data AC-1, Auxiliary contacts Rated control supply SD Screw terminals SD Spring-type
tu: 40/60 °C voltage Us terminals
Opera- Ratings of Ident. Version
tional AC loads No.
current Ie (p.f. = 0.95) Article No. Price Article No. Price
up to at 50 Hz and per PU per PU
690 V 400 V
A kW NO NC V AC d d
For screw fixing and snap-on mounting
onto TH 35 standard mounting rail
Size S001)
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
60 / 55 36 11 1 1 24, 50 Hz 5 3RT2336-1AB00 --
110, 50 Hz 5 3RT2336-1AF00 --
230, 50 Hz } 3RT2336-1AP00 --
110 / 95 63 11 1 1 24, 50 Hz 5 3RT2337-1AB00 --
110, 50 Hz 5 3RT2337-1AF00 --
230, 50 Hz } 3RT2337-1AP00 --
1)
For size S00: Coil operating range Other voltages according to page 4/49 on request.
- at 50 Hz: 0.8 to 1.1 x Us
- at 60 Hz: 0.85 to 1.1 x Us.
For accessories and spare parts, see page 3/75 onwards.
2) Minimum conductor cross-section 10 mm².
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
Size S2
Version for AC-3 motor loads
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1/L1 3/L2 5/L3 7/L4 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
Other voltages according to page 4/49 on request. For accessories and spare parts, see page 3/75 onwards.
4
3RT231. -1B. 40 3RT231.-2B. 40 3RT232. -1B. 40 3RT232. -2B. 40
Rated data AC-1, Auxiliary contacts Rated control supply SD Screw terminals SD Spring-type
tu: 40/60 °C voltage Us terminals
Opera- Ratings of AC loads Ident. Version
tional (p f. = 0.95) No.
current Ie at 50 Hz and Article No. Price Article No. Price
up to per PU per PU
690 V 400 V
A kW NO NC V DC d d
For screw fixing and snap-on mounting
onto TH 35 standard mounting rail
Size S00
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
18 / 16 12 / 11 -- -- -- 24 2 3RT2316-1BB40 } 3RT2316-2BB40
220 5 3RT2316-1BM40 5 3RT2316-2BM40
22 / 20 14.5 / 13 -- -- -- 24 } 3RT2317-1BB40 } 3RT2317-2BB40
220 5 3RT2317-1BM40 5 3RT2317-2BM40
Size S0
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1/L1 3/L2 5/L3 7/L4 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
3RT233. -1N. 30
Rated data AC-1, Auxiliary contacts Rated control SD Screw terminals SD Spring-type terminals
tu: 40/60 °C supply for auxiliary and control
Opera- Ratings of AC loads Ident. Version voltage Us circuits
tional (p f. = 0.95) No.
current Ie at 50 Hz and Article No. Price Article No. Price
up to per PU per PU
690 V 400 V
A kW NO NC V AC/DC d d
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S2
With integrated coil circuit (varistor)
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1/L1 3/L2 5/L3 7/L4 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
60 / 55 36 11 1 1 20 ... 33 } 3RT2336-1NB30 --
175 ... 280 5 3RT2336-1NP30 --
110 / 95 63 11 1 1 20 ... 33 5 3RT2337-1NB30 --
175 ... 280 5 3RT2337-1NP30 --
Other voltages according to page 4/49 on request. For accessories and spare parts, see page 3/75 onwards.
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
Rated data Auxiliary contacts Rated control SD Screw terminals SD Spring-type terminals
AC-2/AC-3, AC-1, Ident. Version supply for auxiliary and control
tu: Up to 60 °C tu: 40/60 °C No. voltage Us circuits
Opera- Ratings of Operational Article No. Price Article No. Price
tional three-phase current Ie per PU per PU
current Ie motors up to
at 50 Hz and
At 400 V 400 V 690 V
A kW A NO NC V AC/DC d d
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S2
Version for AC-3 motor loads
With integrated coil circuit (varistor)
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1/L1 3/L2 5/L3 7/L4 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
Other voltages according to page 4/49 on request. For accessories and spare parts, see page 3/75 onwards.
■ Overview
Standards With sizes S0 and S2, two auxiliary contacts 1 NO + 1 NC
are included in the basic version.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1, Mountable auxiliary contacts
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches)
Size S00 to S2
The contactors are suitable for use in any climate.
They are finger-safe according to IEC 60529. Four additional auxiliary contacts, including no more than
two NC.
The accessories for the 3-pole SIRIUS 3RT2 contactors can also
be used for the 4-pole versions, see from page 3/75 onwards. For a general description of sizes S00 to S2 of 3RT2 contactors,
see from page 3/15 onwards.
■ Application
4
The contactors are suitable: Note:
• For changing the polarity of hoisting gear motors Single device for pole reversal; not suitable for reversing duty.
• For switching two separate loads 3RT25 contactors are not suitable for switching a load between
two current sources.
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16169/faq
https://support.industry.siemens.com/cs/ww/en/ps/16169/td Manuals, see https://support.industry.siemens.com/cs/ww/en/ps/16169/man
NSB0_00477a
Total break time = Opening delay + Arcing time 3RT2316, page 4/15 page 4/15
page 4/15
Rated data of the main contacts
Load rating with AC
Utilization category AC-1,
switching resistive loads
• Rated operational currents Ie At 40 °C up to 690 V A 18 22 40 60 70
At 60 °C up to 690 V A 16 20 35 55 60
• Rated power of At 230 V kW 6 7.5 13.3 21 23
AC loads 400 V kW 10.5 13 23 36 39
P.f. = 0.95 (at 60 °C)
• Minimum conductor cross-section At 40 °C mm2 2.5 4 10 16 25
for loads with Ie
Utilization categories AC-2 and AC-3 AC1) DC1)
• Rated operational currents Ie NO up to 400 V A 9 12 16 25 35 41
(at 60 °C) NC up to 400 V A 9 25 20 35 41
• Rated power of NO at 230 V kW 2.2 3 4 5.5 11
slipring or squirrel-cage motors NC at 230 V kW 2.2 5.5 11
At 50 and 60 Hz NO at 400 V kW 4 5.5 7.5 11 18.5 22
NC at 400 V kW 4 11 7.5 18.5 22
Load rating with DC
Utilization category DC-1,
switching resistive load (L/R 1 ms)
• Rated operational currents Ie (at 60 °C)
- 1 conducting path Up to 24 V A 16 20 35 55 60
60 V A 16 20 20 23
110 V A 2.1 4.5
220 V A 0.8 1
440 V A 0.6 0.4
- 2 conducting paths in series Up to 24 V A 16 20 35 55
60 V A 16 20 35 45
110 V A 12 35 45
220 V A 1.6 5
440 V A 0.8 1
Utilization category DC-3/DC-52),
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational currents Ie (at 60 °C)
- 1 conducting path Up to 24 V A 16 20 20 35
60 V A 0.5 5 6
110 V A 0.15 2.5
220 V A 0.75 1
440 V A -- 0.09 0.1
- 2 conducting paths in series Up to 24 V A 16 20 35 55
60 V A 5 35 45
110 V A 0.35 15 25
220 V A -- 3 5
440 V A -- 0.27
1)
Values for devices with AC and DC operation: For 3RT2526 with
DC operation, different values apply to AC-2 and AC-3 for the NC.
2)
For Us > 24 V, the rated operational currents Ie for the NC contact current
paths are equal to 50 % of the values for the NO contact current paths.
4
3RT251. -1A . 00 3RT251.-2A.00 3RT252.-1A. 00 3RT252. -2A . 00 3RT253. -1A. 00
Rated data Auxiliary contacts Rated control SD Screw terminals SD Spring-type
AC-2/AC-3, AC-1, Ident. No. Version supply voltage terminals
tu: Up to 60 °C tu: 40/60 °C Us
Opera- Ratings of three- Operational Article No. Price Article No. Price
tional phase motors current Ie per PU per PU
current Ie at 50 Hz and up to
At 400 V 400 V 690
A kW A NO NC V AC d d
For screw fixing and snap-on mounting
onto TH 35 standard mounting rail
Size S001)
1 R1 R3 3
A1(+)
A2(–)
2 R2 R4 4
A2(–)
2 R2 R4 4 14 22
A2(–)
2 R2 R4 4 14 22
A2(–)
2 R2 R4 4
9 4 18 / 16 -- -- -- 24 } 3RT2516-1BB40 2 3RT2516-2BB40
220 5 3RT2516-1BM40 5 3RT2516-2BM40
12/91) 5.5/41) 22 / 20 -- -- -- 24 2 3RT2517-1BB40 2 3RT2517-2BB40
220 5 3RT2517-1BM40 5 3RT2517-2BM40
16/91) 7.5/41) 22 / 20 -- -- -- 24 2 3RT2518-1BB40 2 3RT2518-2BB40
220 5 3RT2518-1BM40 5 3RT2518-2BM40
Size S0
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1 R1 R3 3 13 21
A1(+)
A2(–)
2 R2 R4 4 14 22
2) 2)
25 (20) 11 (7.5) 40 / 35 11 1 1 24 2 3RT2526-1BB40 2 3RT2526-2BB40
220 5 3RT2526-1BM40 5 3RT2526-2BM40
1) Values for NO contact/NC contact. The NC contact can switch no more Other voltages according to page 4/49 on request.
than 4 kW.
2)
Value in brackets for NC contact (the deviating value for the NC contact
For accessories and spare parts, see page 3/75 onwards.
applies only for devices with DC operation).
4
3RT253. -1N.30
Rated data Auxiliary contacts Rated control SD Screw terminals SD Spring-type
AC-2/AC-3, AC-1, Ident. No. Version supply voltage terminals
tu: Up to 60 °C tu: 40/60 °C Us for auxiliary and
control circuits
Opera- Ratings of three- Operational Article No. Price Article No. Price
tional phase motors current Ie per PU per PU
current Ie at 50 Hz and up to
At 400 V 400 V 690
A kW A NO NC V AC/DC d d
For screw fixing and snap-on mounting
onto TH 35 standard mounting rail
Size S2
With integrated coil circuit (varistor)
Auxiliary contacts 1 NO + 1 NC, Ident. No. 11
1 R1 R3 3 13 21
A1(+)
A2(–)
2 R2 R4 4 14 22
■ Overview
Standards Auxiliary switches
IEC 60947-1, EN 60947-1, The variance of unassigned auxiliary switches has been in-
IEC 60947-4-1, EN 60947-4-1, creased; for available versions, see "Selection and ordering
IEC 60947-5-1, EN 60947-5-1, data", page 4/31. Details of deviating versions are available on
IEC 60831-1, EN 60831-1, request.
IEC 61921, EN 61921
In sizes S00 and S0, the auxiliary switch block which is snapped
The 3RT26 contactors are suitable for use in any climate. onto the capacitor contactor contains the three leading NO con-
They are finger-safe according to IEC 60529. tacts and one unassigned auxiliary contact. In addition, another
one (S00) or two (S0) unassigned auxiliary contacts are pro-
Function vided in the basic unit.
The 3RT26 contactors for capacitive loads (AC-6b) are special
4
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16171/td https://support.industry.siemens.com/cs/ww/en/ps/16171/man
Type 3RT26
Size S00 ... S2
Contact endurance of the main contacts
The characteristic curves show the contact endurance of the contactors
when switching capacitive loads (AC-6b) depending on the reactive 10+6 IC01_00386b
power QN and rated operational voltage. 8
Electrical durability (operating cycles)
6
The rated operational current Ie in accordance with utilization category
AC-6b (breaking of 1.35 times the rated operational current) is specified 4 3RT2617
for a contact service life of approximately 150 000 to 200 000 operating 3RT2625
cycles.
2 3RT2626
3RT2627
10+5 3RT2628
3RT2636
3RT2637
10+4
100 2 4 6 8 101 2 4 6 8 102
Reactive power QN [kvar] / 400 V
4
H
NSB0_00478c
360° 22,5° 22,5°
The contactors are designed for operation on a vertical
mounting surface.
Mechanical endurance
• Basic units with mounted auxiliary switch block Operat- 3 million
ing cy-
cles
Electrical endurance kvar 12.5 16.7 20 25 33 50 75
For apparent power at 400 V Operat- 300 000 200 000 150 000 200 000 150 000
ing
cycles
Rated insulation voltage Ui V 690
(Pollution degree 3)
Rated impulse withstand voltage Uimp kV 6
Protective separation between coil and main contacts V 400
According to IEC 60947-1, Appendix N
Permissible ambient temperature
• Mode1) °C -25 ... +60
• During storage °C -55 ... +80
Degree of protection acc. to IEC 60529
• On front IP20
• Connecting terminal IP20 IP00 (for higher degree
of protection, use additional
terminal covers)
Touch protection acc. to IEC 60529 Finger-safe Finger-safe for vertical
touching from the front
Shock resistance
• Rectangular pulse g/ms 6.7/5 and 7.5/5 and 8.3/5 and 5.3/10 6.8/5 and 4/10
4.2/10 4.7/10
• Sine pulse g/ms 10.5/5 and 11.8/5 and 13.5/5 and 8.3/10 10.6/5 and 6.2/10
6.6/10 7.4/10
Short-circuit protection
Main circuit
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
acc. to IEC 60947-4-1/EN 60947-4-1
- Type of coordination "1" A 25 ... 40 32 ... 80 40 ... 80 50 ... 100 63 ... 100 100 ... 160 160 ... 200
Auxiliary circuit
• With fuse links of operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
• With miniature circuit breaker with C characteristic A 10
With short-circuit current Ik = 400 A
1)
A clearance of 10 mm is required for side-by-side mounting at ambient
temperatures > 60 °C.
- Closing VA -- 77 190
- P.f. -- 0.82 0.72
- Closed VA -- 9.8 16
- P.f. -- 0.25 0.37
• AC operation, 50/60 Hz, standard version
- Closing VA 49 81/79 210/188
- P.f. 0.8 0.72/0.74 0.69/0.65
- Closed VA 7.8 10.5/8.5 17.2/16.5
- P.f. 0.25 0.25/0.28 0.36/0.39
• DC operation
- Closing W 4 5.9 --
- Closed W 4 5.9 --
Maximum permissible residual current of the electronics
(with 0 signal)1)
• AC operation (230 V/Us) mA 41) 7 --
• DC operation (24 V/Us) mA 101) 16 --
Operating times for 0.8 ... 1.1 x Us2)
Total break time = Opening delay + Arcing time
• AC operation
- Closing delay ms 8 ... 33 9 ... 38 8 ... 40 10 ... 80
- Opening delay ms 4 ... 15 4 ... 16 10 ... 18
• DC operation
- Closing delay ms 30 ... 100 55 ... 80 50 ... 170 --
- Opening delay ms 7 ... 13 16 ... 17 15 ... 18 --
• Arcing time ms 10 ... 15
1) 2)
Size S00: The 3RT2916-1GA00 additional load module is recommended With size S00, DC operation: Operating times at 0.85 to 1.1 x Us.
for higher residual currents, see page 3/118.
4
Load rating with AC
Utilization category AC-6b
Switching of AC capacitors
Rated operational current Ie for AC
• At ambient temperature of 40 °C A 18.9 25.3 30.2 37.8 50 75.8 113.4
• At ambient temperature of 60 °C A 18 24 29 36 47.6 72.2 108
Rated operational reactive power 230 V, 50/60 Hz kvar 0 ... 7.2 3 ... 9.6 4 ... 11.5 5 ... 14 6 ... 19 10 ... 29 14 ... 43
at rated operational current 400 V, 50/60 Hz kvar 0 ... 12.5 6 ... 16.7 7 ... 20 8 ... 25 11 ... 33 17 ... 50 25 ... 75
500 V, 50/60 Hz kvar 0 ... 15 7 ... 21 8 ... 25 10 ... 31 14 ... 41 21 ... 63 31 ... 94
690 V, 50/60 Hz kvar 0 ... 21 10 ... 29 11 ... 34 14 ... 43 19 ... 57 29 ... 86 43 ... 129
Switching frequency
No-load switching frequency AC operation 1/h 500
DC operation 1/h 500
Max. switching frequency z
in operating cycles/hour
• At Ie/AC-6b and at 230 V, 50/60 Hz 1/h 180 100
400 V, 50/60 Hz 1/h 180 100 100 / 801)
480 V, 50/60 Hz 1/h 180 100 70 60 50
500 V, 50/60 Hz 1/h 180 100 65 55 45
600 V, 50/60 Hz 1/h 180 100 45 40 32
690 V, 50/60 Hz 1/h 180 150 100 72 36 30 25
s and u rated data
Rated insulation voltage V AC 600
Rated operational reactive power 110 ... 120 V kvar 3.4 4.6 5.5 6.3 8.3 14 19
at AC-6b, three-phase, 200 ... 208 V kvar 6.2 8.3 10 11 15 25 34
at operational voltage 220 ... 230 V kvar 6.9 9.2 11 13 17 27 38
460 ... 480 V kvar 14 18 22 25 33 55 75
575 ... 600 V kvar 17 23 27 31 41 69 94
Short-circuit protection At 600 V kA 5 10
Fuse for main circuit Class RK5 A 40 80 100 250
1)
Operating cycles/h: 100 with AC operation; 80 with AC/DC operation.
4
3RT2617-1A.05 3RT262.-1A. 05 3RT2628-1A.05 3RT263.-1A.05
with infeed terminal
Utilization category AC-6b Auxiliary Rated control supply SD Screw terminals PU PS* PG
Switching of AC capacitors contacts, voltage Us1) (UNIT,
at an ambient temperature of 60 °C unassigned SET, M)
Version
Capacitor rating at Article No. Price
operational voltage 50/60 Hz per PU
At 230 V At 400 V At 500 V At 690 V
kvar kvar kvar kvar NO NC V AC Hz d
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
Size S00
0 ... 7.2 0 … 12.5 0 ... 15 0 ... 21 1 1 24 50/60 5 3RT2617-1AB03 1 1 unit 41B
110 5 3RT2617-1AF03 1 1 unit 41B
230 5 3RT2617-1AP03 1 1 unit 41B
0 ... 7.2 0 … 12.5 0 ... 15 0 ... 21 0 2 24 50/60 5 3RT2617-1AB05 1 1 unit 41B
110 5 3RT2617-1AF05 1 1 unit 41B
230 5 3RT2617-1AP05 1 1 unit 41B
Size S02)
3 ... 9.6 6 … 16.7 7 ... 21 10 ... 29 1 2 24 50 5 3RT2625-1AB05 1 1 unit 41B
110 5 3RT2625-1AF05 1 1 unit 41B
230 5 3RT2625-1AP05 1 1 unit 41B
4 ... 11.5 7 … 20 8 ... 25 11 ... 34 1 2 24 50 5 3RT2626-1AB05 1 1 unit 41B
110 5 3RT2626-1AF05 1 1 unit 41B
230 5 3RT2626-1AP05 1 1 unit 41B
5 ... 14 8 … 25 10 ... 31 14 ... 43 1 2 24 50 5 3RT2627-1AB05 1 1 unit 41B
110 5 3RT2627-1AF05 1 1 unit 41B
230 5 3RT2627-1AP05 1 1 unit 41B
6 ... 19 11 … 33 14 ... 41 19 ... 57 1 2 24 50 5 3RT2628-1AB05 1 1 unit 41B
110 5 3RT2628-1AF05 1 1 unit 41B
230 5 3RT2628-1AP05 1 1 unit 41B
Size S23)
10 ... 29 17 ... 50 21 ... 63 29 ... 86 1 1 24 50 5 3RT2636-1AB03 1 1 unit 41B
110 5 3RT2636-1AF03 1 1 unit 41B
230 5 3RT2636-1AP03 1 1 unit 41B
10 ... 29 17 ... 50 21 ... 63 29 ... 86 0 2 24 50 5 3RT2636-1AB05 1 1 unit 41B
110 5 3RT2636-1AF05 1 1 unit 41B
230 5 3RT2636-1AP05 1 1 unit 41B
14 ... 43 25 … 75 31 ... 94 43 ... 129 1 1 24 50 5 3RT2637-1AB03 1 1 unit 41B
110 5 3RT2637-1AF03 1 1 unit 41B
230 5 3RT2637-1AP03 1 1 unit 41B
14 ... 43 25 … 75 31 ... 94 43 ... 129 0 2 24 50 5 3RT2637-1AB05 1 1 unit 41B
110 5 3RT2637-1AF05 1 1 unit 41B
230 5 3RT2637-1AP05 1 1 unit 41B
1)
Coil operating range Other voltages according to page 4/49 on request.
- at 50 Hz: 0.8 to 1.1 x Us
- at 60 Hz: 0.85 to 1.1 x Us.
For accessories and spare parts, see page 3/75 onwards.
2) Three-phase infeed terminal 3RV2925-5AB available, see page 3/114.
With 3RT2628, the three-phase infeed terminal is included in the scope of
delivery.
3) Three-phase infeed terminal 3RV2935-5A available, see page 3/114.
4
3RT262.-1N. 35 3RT2628-1N. 35 3RT263.-1N .35
with infeed terminal
Utilization category AC-6b Auxiliary Rated control SD Screw terminals PU PS* PG
Switching of AC capacitors contacts, supply voltage Us1) (UNIT,
at an ambient temperature of 60 °C unassigned SET, M)
Version
Capacitor rating at Article No. Price
operational voltage 50/60 Hz per PU
At 230 V At 400 V At 500 V At 690 V
kvar kvar kvar kvar NO NC V AC V DC d
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
Size S02)
3 ... 9.6 6 … 16.7 7 ... 21 10 ... 29 1 2 21 ... 28 21 ... 28 5 3RT2625-1NB35 1 1 unit 41B
95 ... 130 95 ... 130 5 3RT2625-1NF35 1 1 unit 41B
200 ... 280 200 ... 280 5 3RT2625-1NP35 1 1 unit 41B
4 ... 11.5 7 … 20 8 ... 25 11 ... 34 1 2 21 ... 28 21 ... 28 5 3RT2626-1NB35 1 1 unit 41B
95 ... 130 95 ... 130 5 3RT2626-1NF35 1 1 unit 41B
200 ... 280 200 ... 280 5 3RT2626-1NP35 1 1 unit 41B
5 ... 14 8 … 25 10 ... 31 14 ... 43 1 2 21 ... 28 21 ... 28 5 3RT2627-1NB35 1 1 unit 41B
95 ... 130 95 ... 130 5 3RT2627-1NF35 1 1 unit 41B
200 ... 280 200 ... 280 5 3RT2627-1NP35 1 1 unit 41B
6 ... 19 11 … 33 14 ... 41 19 ... 57 1 2 21 ... 28 21 ... 28 5 3RT2628-1NB35 1 1 unit 41B
95 ... 130 95 ... 130 5 3RT2628-1NF35 1 1 unit 41B
200 ... 280 200 ... 280 5 3RT2628-1NP35 1 1 unit 41B
Size S23)
10 ... 29 17 ... 50 21 ... 63 29 ... 86 0 2 20 ... 33 20 ... 33 5 3RT2636-1NB35 1 1 unit 41B
83 ... 155 83 ... 155 5 3RT2636-1NF35 1 1 unit 41B
175 ... 280 175 ... 280 5 3RT2636-1NP35 1 1 unit 41B
14 ... 43 25 … 75 31 ... 94 43 ... 129 0 2 20 ... 33 20 ... 33 5 3RT2637-1NB35 1 1 unit 41B
83 ... 155 83 ... 155 5 3RT2637-1NF35 1 1 unit 41B
175 ... 280 175 ... 280 5 3RT2637-1NP35 1 1 unit 41B
1)
Coil operating range: 0.7 to 1.3 x Us Other voltages according to page 4/49 on request.
2) Three-phase infeed terminal 3RV2925-5AB available, see page 3/114.
With 3RT2628, the three-phase infeed terminal is included in the scope of
For accessories and spare parts, see page 3/75 onwards.
delivery.
3) Three-phase infeed terminal 3RV2935-5A available, see page 3/114.
■ Overview
Standards The contactors are suitable for use in any climate.
They are finger-safe according to IEC 60529.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1, The contactors are suitable for switching mixed loads in
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) distribution systems (e.g. for supplying heaters, lamps, motors,
PC power supply units) with p.f. > 0.8 according to
IEC 60947-4-1 test conditions for utilization category AC-1.
■ Technical specifications
More information
Technical specifications, see Manuals, see
4
https://support.industry.siemens.com/cs/ww/en/ps/16166/td https://support.industry.siemens.com/cs/ww/en/ps/16166/man
NSB0_00478c
360° 22,5° 22,5°
The contactors are designed for operation on a vertical mounting surface.
For DC operation and up to 22.5° inclination in front, the coil operating
range is reduced to 0.85 ... 1.1 x Us.
4
• Rated operational currents Ie at 60 °C, at 400 V A --
• Rated power of At 230 V kW --
slipring or squirrel-cage motors 400 V kW --
at 50 and 60 Hz
Maximum AC breaking current
(e.g. for isolation of load distributions)
• at 50 and 60 Hz At 400 V A 520 760
Load rating with DC
Utilization category DC-1,
switching resistive load (L/R 1 ms)
• Rated operational currents Ie (at 40 °C)
- 1 conducting path Up to 24 V A 70 80
60 V A 23 60
110 V A 4.5 9
220 V A 1 2
440 V A 0.4 0.6
- 2 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 5 10
440 V A 1 1.8
- 3 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 70 80
440 V A 2.9 4.5
- 4 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 70 80
440 V A 2.9 4.5
Utilization category DC-3/DC-5,
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational currents Ie (at 40 °C)
- 1 conducting path Up to 24 V A 20
60 V A 6 6.5
110 V A 2.5
220 V A 1
440 V A 0.15
- 2 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 7
440 V A 0.42
- 3 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 35
440 V A 0.8
- 4 conducting paths in series Up to 24 V A 70 80
60 V A 70 80
110 V A 70 80
220 V A 70 80
440 V A 0.8
3RT134. -1. . .0
4
A2(–)
2/T1 4/T2 6/T3 8/T4
A2(–)
2/T1 4/T2 6/T3 8/T4
Other voltages according to page 4/49 on request. For accessories, see page 4/37 onwards.
For spare parts, see page 4/48 onwards.
■ Overview
Auxiliary switches Coupling links for control by PLC
See from page 4/40 onwards See pages 4/39 and 4/45
The auxiliary switches can be designed as positively driven • Operation with 24 V DC
contacts in 3RH contactor relays or also as mirror contacts in the • Operating range 17 to 30 V
case of 3RT power contactors. • Low power consumption of 0.5 W
For more information on positively driven operation and mirror • An LED indicates the switching state.
contacts, see Manuals "More Information" on page 4/38.
The 3RH2924-1GP11 coupling link has an integrated surge
Snap-on auxiliary switch blocks suppressor (varistor) for the contactor coil being switched and is
A maximum of eight auxiliary contacts can be attached, please mounted onto the size S0 contactor coil via a coil connection
module.
4
note the following:
• Of these eight auxiliary contacts, there must be no more than Sealable covers
four NC contacts. See page 4/46
• Ensure the symmetry of laterally mounted auxiliary switch
blocks When contactors and contactor relays are used in safety-related
applications, it must be ensured that it is impossible to operate
Surge suppressors without LED the contactors manually.
See page 4/44 For SIRIUS contactors there are sealable covers available for
this purpose as accessories; these prevent accidental manual
(also for spring-type terminals) operation. These are transparent molded-plastic caps with a
All 3RT13 contactors can be retrofitted with RC elements or bracket that enables the contactor to be sealed.
varistors for damping opening surges in the coil. Diodes or
diode assemblies (comprising noise suppression diodes and
Zener diodes for short break times) can be used.
With these contactors, varistors, RC elements and diode
assemblies can be plugged on directly at the coil terminals,
either on the top or underneath.
The plug-in direction of the diodes and diode assemblies is
determined by a coding device.
Note:
The OFF-delay of the NO contact and the ON-delay of the
NC contact are increased if the contactor coils are attenuated
against voltage peaks (noise suppression diode 6 to 10 times;
diode assembly 2 to 6 times, varistor +2 to 5 ms).
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16209/td https://support.industry.siemens.com/cs/ww/en/ps/16209/man
Type 3RH1924-1GP11
Version Coupling links for control by PLC
General data
Rated insulation voltage Ui (pollution degree 3) V 300
Protective separation between coil and contacts V AC Up to 300
acc. to IEC 60947-1, Appendix N
Permissible ambient temperature
• During operation °C -25 ... +60
• During storage °C -40 ... +80
Degree of protection acc. to IEC 60529
• Connections IP20
Conductor cross-sections
4
• Solid mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve mm² 2 x (0.5 ... 1.5)
• Terminal screws M3
Control side
Rated control supply voltage Us V DC 24
Operating range V DC 17 ... 30
Power consumption at Us W 0.5
Nominal current input mA 20
Release voltage V 4
Function display Yellow LED
Protection circuit Varistors
Load side
Mechanical endurance Operat- 20 x 106
ing cy-
cles
Electrical endurance at Ie Operat- 1 x 105
ing cy-
cles
Switching frequency Operat- 5 000
ing cy-
cles/h
Make-time ms Approx. 7
Break-time ms Approx. 4
Bounce time ms Approx. 2
Contact material AgSnO
Switching voltage AC/DC V 24 ... 250
Permissible residual current of the electronics (with 0 signal) mA 2.5
3RH1921-1HA. ., 3RH1921-2HA. . ,
3RH1921-1FA. . 3RH1921-2FA. .
4
Type NO NC NO NC d d
Auxiliary switch blocks for snapping onto the front
Size S3
4-pole auxiliary switch blocks
• According to EN 50012
3RT134. 31 3 1 -- -- 13 21 33 43 } 3RH1921-1HA31 } 3RH1921-2HA31
14 22 34 44
22 2 2 -- -- 13 21 31 43 } 3RH1921-1HA22 } 3RH1921-2HA22
14 22 32 44
13 1 3 -- -- 13 21 31 41 } 3RH1921-1HA13 } 3RH1921-2HA13
14 22 32 42
• According to EN 50005
3RT134. 40 4 -- -- -- 13 23 33 43 } 3RH1921-1FA40 } 3RH1921-2FA40
14 24 34 44
31 3 1 -- -- 13 23 33 41 } 3RH1921-1FA31 } 3RH1921-2FA31
14 24 34 42
22 2 2 -- -- 13 23 31 41 } 3RH1921-1FA22 } 3RH1921-2FA22
14 24 32 42
04 -- 4 -- -- 11 21 31 41 } 3RH1921-1FA04 2 3RH1921-2FA04
12 22 32 42
22 U -- -- 2 2 17 27 35 45 } 3RH1921-1FC22 2 3RH1921-2FC22
18 28 36 46
4
Type NO NC NO NC d d
Auxiliary switch blocks for snapping
onto the front according to EN 50005
Size S3
2-pole auxiliary switch blocks
with cable entry on one side
according to EN 50005
• Cable entry from above
3RT134. 11 1 1 -- -- 13 21 } 3RH1921-1LA11 --
14 22
20 2 -- -- -- 13 23 } 3RH1921-1LA20 --
14 24
02 -- 2 -- -- 11 21 } 3RH1921-1LA02 --
12 22
14 22
20 2 -- -- -- 13 23 } 3RH1921-1MA20 --
14 24
02 -- 2 -- -- 11 21 } 3RH1921-1MA02 --
12 22
.4
01 -- 1 -- -- .1 } 3RH1921-1CA01 } 3RH1921-2CA01
.2
10 -- -- 1 -- .7 } 3RH1921-1CD10 --
.8
01 -- -- -- 1 .5 } 3RH1921-1CD01 --
.6
3RH1921-1DA11, 3RH1921-2DA11,
3RH1921-1JA11, 3RH1921-2JA11,
3RH1921-1EA. ., 3RH1921-2EA. . ,
3RH1921-1KA. . 3RH1921-2KA..
4
Type NO NC d d
Laterally mountable auxiliary switch blocks,
mounting left or right,
2-pole
Size S3 Left Right
According to EN 50012
• First laterally mountable auxiliary switch block
3RT134. 1 1 21 13 31 43 } 3RH1921-1DA11 } 3RH1921-2DA11
22 14 32 44
62 54 72 84
According to EN 50005
• First laterally mountable auxiliary switch block
3RT134. 2 -- 53 63 73 83 } 3RH1921-1EA20 } 3RH1921-2EA20
54 64 74 84
1 1 51 63 71 83 } 3RH1921-1EA11 --
52 64 72 84
-- 2 51 61 71 81 } 3RH1921-1EA02 } 3RH1921-2EA02
52 62 72 82
4
3RH1921-2JE11
For contactors Contacts SD Screw terminals SD Spring-type terminals
14 24 32 42
22 14 32 44
62 54 72 84
1)
1 NO + 1 NC standard auxiliary switches.
Surge suppressors
For Version Rated control supply voltage Us1) SD Article No. Price PU PS* PG
contactors per PU (UNIT,
SET,
M)
AC operation DC operation
Type V AC V DC d
Surge suppressors without LED
Size S3 (also for spring-type terminals)
For fitting onto the coil terminals at top or bottom
3RT134. Varistors 24 ... 48 24 ... 70 } 3RT1926-1BB00 1 1 unit 41B
U 48 ... 127 70 ... 150 } 3RT1926-1BC00 1 1 unit 41B
127 ... 240 150 ... 250 } 3RT1926-1BD00 1 1 unit 41B
240 ... 400 -- } 3RT1926-1BE00 1 1 unit 41B
400 ... 600 5 3RT1926-1BF00 1 1 unit 41B
3RT1926-1B.00
3RT134. RC elements 24 ... 48 24 ... 70 } 3RT1936-1CB00 1 1 unit 41B
48 ... 127 70 ... 150 } 3RT1936-1CC00 1 1 unit 41B
127 ... 240 150 ... 250 } 3RT1936-1CD00 1 1 unit 41B
240 ... 400 -- } 3RT1936-1CE00 1 1 unit 41B
3RT1936-1C. 00 400 ... 600 -- 5 3RT1936-1CF00 1 1 unit 41B
3RT134. Diode assemblies for DC operation
4
Power consumption: 0.5 W at 24 V DC
Permissible residual current of the electronics
(with "0" signal): 2.5 mA
Rated operational current Ie:
• AC-15/AC-14 at 230 V: 3 A
3RH1924-1GP11 • DC-13 at 230 V: 0.1 A
Technical specifications, see page 4/39.
For Rated control supply voltage Us1) Time setting range t SD Screw terminals PU PS* PG
contactors (UNIT,
SET,
M)
Article No. Price
Type V s d per PU
Electronic timing relay blocks with semiconductor output
Size S3
For mounting onto top-lying coil terminals,
for contactors with screw terminals only
• ON-delay (varistor integrated)
3RT134.2) 24 ... 66 AC/DC 0.05 ... 1 5 3RT1926-2CG11 1 1 unit 41H
0.5 ... 10 5 3RT1926-2CG21 1 1 unit 41H
5 ... 100 5 3RT1926-2CG31 1 1 unit 41H
90 ... 240 AC/DC 0.05 ... 1 } 3RT1926-2CH11 1 1 unit 41H
0.5 ... 10 } 3RT1926-2CH21 1 1 unit 41H
3RT1926-2C. . . 5 ... 100 } 3RT1926-2CH31 1 1 unit 41H
• OFF-delay with control signal
(varistor integrated)
3RT134.2) 24 ... 66 AC/DC 0.05 ... 1 10 3RT1926-2DG11 1 1 unit 41H
0.5 ... 10 5 3RT1926-2DG21 1 1 unit 41H
5 ... 100 20 3RT1926-2DG31 1 1 unit 41H
90 ... 240 AC/DC 0.05 ... 1 5 3RT1926-2DH11 1 1 unit 41H
0.5 ... 10 5 3RT1926-2DH21 1 1 unit 41H
3RT1926-2D. . . 5 ... 100 10 3RT1926-2DH31 1 1 unit 41H
1)
The AC voltages are valid for 50 and 60 Hz. Technical specifications, see page 4/38.
2) In addition to these, no other auxiliary contacts are permitted.
3RA1942-2G
1) Can also be used for 4-pole contactors with sizes S2 and S3.
Terminal modules/adapters
For con- Size Version SD Article No. Price PU PS* PG
tactors per PU (UNIT,
SET,
M)
Type d
Single-phase infeed terminals
3RT134. S3 Conductor cross-section: 95 mm2 2 3RA1943-3L 1 1 unit 41B
Covers
For con- Size Version SD Article No. Price PU PS* PG
tactors per PU (UNIT,
SET,
M)
Type d
Terminal covers
3RT134. S3 Additional touch protection, 5 3RT1946-4EA4 1 1 unit 41B
to be fitted at the box terminals
(2 units required per contactor)
Sealable covers
3RT134.1) S3 1 unit required per contactor 15 3RT1926-4MA10 1 5 units 41B
IC01_00162
3RT1926-4MA10
1) Exception: Contactors with auxiliary switch block mounted onto the front.
4
Q1, Q3 and Q2
LED modules for displaying contactor operation
3RT134. S3 The connecting leads have to be 5 3RT1926-1QT00 1 5 units 41B
extended.
For snapping into the location hole of an
inscription label on the front of a contactor
either directly on the contactor or on the
front auxiliary switch.
The LED module is connected to coil ter-
minals A1 and A2 of the contactor and
indicates its energized state.
Yellow LED.
Rated voltage:
24 ... 240 V AC/DC with reverse polarity
3RT1926-1QT00 protection
mounted on contactor
Self-adhesive labels
for SIRIUS devices
3RT134. S3 • 19 mm × 6 mm, pastel turquoise 15 3RT1900-1SB60 100 3 060 units 41B
3RT1900-1SB20
• 19 mm × 6 mm, zinc/yellow 15 3RT1900-1SD60 100 3 060 units 41B
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/20).
Note:
Contactors with AC and DC coils have different depths. It is only
possible to replace AC coils with AC coils or DC coils with DC
ones.
Contacts
For contactors Version SD Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Size Type d
Contacts with fixing parts
Main contacts (4 NO contacts) for utilization category AC-1
S3 3RT1344 (1 set = 4 movable and 8 fixed switching elements 5 3RT1944-6E 1 1 unit 41B
3RT1346 with fixing parts) 5 3RT1946-6E 1 1 unit 41B
■ Options
Rated control supply voltages, possible on request (change of the 10th and 11th digits of the Article No.)
Delivery time on request
Rated control supply Contactor type 3RT231, 3RT232, 3RT233, 3RT244 3RT134 3RT2617,
voltage Us 3RT251 3RT252 3RT253 3RT262, 3RT263
Size S00 S0 S2 S3 S00 to S2
Sizes S00 to S3
AC operation1)
Solenoid coils for 50 Hz (exception: Size S00: 50 and 60 Hz2))
24 V AC B0 B0 B0 B0 B0 B0
42 V AC D0 D0 D0 D0 -- --
48 V AC H0 -- -- H0 -- --
4
110 V AC F0 F0 F0 F0 F0 F0
230 V AC P0 P0 P0 P0 P0 P0
240 V AC -- -- U0 U0 U0 --
400 V AC V0 V0 V0 V0 V0 --
Solenoid coils for 50 and 60 Hz2)
24 V AC B0 C2 C2 C2 C2 C2
42 V AC D0 D2 D2 D2 -- --
48 V AC H0 H2 H2 H2 H2 --
110 V AC F0 G2 G2 G2 -- --
220 V AC N2 N2 N2 N2 N2 N2
230 V AC P0 L2 L2 L2 L2 L2
Solenoid coils (for USA and Canada3))
50 Hz 60 Hz
110 V AC 120 V AC K6 K6 K6 K6 K6 --
220 V AC 240 V AC P6 P6 P6 P6 -- --
Solenoid coils (for Japan)
50/60 Hz4) 60 Hz5)
100 V AC 110 V AC G6 G6 G6 G6 -- G6
200 V AC 220 V AC N6 N6 N6 N6 -- N6
400 V AC 440 V AC R6 R6 R6 R6 -- R6
DC operation1)
12 V DC A4 A4 -- -- -- --
24 V DC B4 B4 -- -- B4 B4
42 V DC D4 D4 -- -- D4 --
48 V DC W4 W4 -- -- W4 --
60 V DC -- -- -- -- E4 --
110 V DC F4 F4 -- -- F4 F4
125 V DC G4 G4 -- -- G4 --
220 V DC M4 M4 -- -- M4 --
230 V DC P4 -- -- -- -- --
Examples
AC operation 3RT2325-1AP00 Contactor with screw terminals; with solenoid coil for 50 Hz for rated control supply voltage of 230 V AC
3RT2325-1AG20 Contactor with screw terminals; with solenoid coil for 50/60 Hz for rated control supply voltage of 110 V AC
DC operation 3RT2526-2BB40 Contactor with spring-type terminals; for rated control supply voltage of 24 V DC
3RT2526-2BG40 Contactor with spring-type terminals; for rated control supply voltage of 125 V DC
1) For deviating coil voltages and operating ranges of sizes S00 and S0, 4) Coil operating range
a SITOP 24 V DC power supply with wide-range input can be used for the - Size S00: at 50/60 Hz: 0.85 to 1.1 x Us
coil control, see page 15/1 onwards. - Sizes S0 to S3: at 50 Hz: 0.8 to 1.1 x Us; at 60 Hz: 0.85 to 1.1 x Us.
2) Coil operating range 5)
Coil operating range at 60 Hz: 0.8 to 1.1 x Us.
- at 50 Hz: 0.8 to 1.1 x Us; at 60 Hz: 0.85 to 1.1 x Us.
3) Coil operating range
- Size S00: at 50 Hz: 0.85 to 1.1 x Us; at 60 Hz: 0.8 to 1.1 x Us
- Sizes S0 to S3: at 50 Hz and 60 Hz: 0.8 to 1.1 x Us.
Rated control supply Contactor type 3RT1456-6A, Rated control supply Contactor type 3RT1456-6N, 3RT1456-6P,
voltage 3RT1466-6A, voltage 3RT1466-6N, 3RT1466-6P,
3RT1476-6A 3RT1476-6N 3RT1476-6P.
Us min ... Us max Size S6, S10, S12 Us min ... Us max Size S6, S10, S12 S6, S10, S12
Sizes S6 to S12
AC/DC operation (50/60 Hz AC, DC)
Conventional operating mechanisms1) Solid-state operating mechanisms2)
23 ... 26 V AC/DC B3 21 ... 27.3 V AC/DC B3 --
42 ... 48 V AC/DC D3 96 ... 127 V AC/DC F3 F3
110 ... 127 V AC/DC F3 200 ... 277 V AC/DC P3 P3
200 ... 220 V AC/DC M3
220 ... 240 V AC/DC P3
240 ... 277 V AC/DC U3
380 ... 420 V AC/DC V3
440 ... 480 V AC/DC R3
500 ... 550 V AC/DC S3
575 ... 600 V AC/DC T3
1) Operating range: 0.8 x Us min to 1.1 x Us max. 2) Operating range: 0.7 x Us min to 1.25 x U s max.
■ Overview
Standards The contactors are used mainly for resistive loads (AC-1 and
p.f. 0.95). They are also suitable for switching mixed loads in
IEC 60947-1, EN 60947-1, distribution systems (e. g. for supplying heaters, lamps, motors,
IEC 60947-4-1, EN 60947-4-1, PC power supply units) with p.f. according to
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) IEC 60947-4-1; test conditions for utilization category AC-1.
The contactors also comply with the requirements of the
NFC 63-110 and NFC 20–040 standards. Control circuit
The contactors are suitable for use in any climate. They are The solenoid coils of the 3TK10 to 3TK13 contactors
finger-safe according to IEC 60529. Terminal covers may have to (operating current up to 350 A) are designed as plug-in coils.
be fitted onto the connecting bars, depending on the configura- Surge suppression
tion with other devices.
The solenoid coils of the 3TK1 contactors can be connected at
4
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16167/td https://support.industry.siemens.com/cs/ww/en/ps/16167/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16167/faq
Type 3TK1
Rated data of the auxiliary contacts
General data
Standards IEC 60947-5-1
Rated insulation voltage Ui V 690
(pollution degree 3)
Conventional thermal current Ith = A 10
rated operational current Ie/AC-12
Load rating with AC
Rated operational current Ie/AC-15/AC-14
• For rated operational voltage Ue 24 V A 6
110 V A 6
125 V A 6
220 V A 6
230 V A 6
380 V A 4
400 V A 4
500 V A 1
660 V A 1
690 V A 1
Load rating with DC
Rated operational current Ie/DC-12 --
Rated operational current Ie/DC-13
• For rated operational voltage Ue 24 V A 6
60 V A 6
110 V A 1.8
125 V A --
220 V A 0.6
440 V A --
600 V A --
s and u rated data of the auxiliary contacts
Rated voltage, max. V AC 600
Switching capacity A 600, P 600
D
W
NSB0_00649a
22,5° 22,5°
Upright mounting position also permissible 90° 90°
4
Electrical endurance at Ie/AC-1 at 55 °C Operating cycles Mill. 0.8 0.4 0.65 0.5 0.4
Rated insulation voltage Ui (pollution degree 3) V 1 000
Ambient temperature
• During operation °C -25 ... +55
• During storage °C -50 ... +70
Degree of protection acc. to IEC 60529 IP00
Touch protection acc. to IEC 60529 Finger-safe with terminal covers
Shock resistance, sine pulse g/ms 10/15
Short-circuit protection
Main circuit
Fuse links, operational class gG: LV HRC, type 3NA; DIAZED, type 5SB;
NEOZED, type 5SE acc. to IEC 60947-4-1/EN 60947-4-1
• Type of coordination "1" A 250 355 630 1 000
• Type of coordination "2" A 250 315 630 850
Auxiliary circuit
Short circuit test with fuse links of operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
Control
Solenoid coil operating range 0.85 ... 1.1 x Us
Power consumption of the solenoid coils (for cold coil and 1.0 x Us)
• 50 Hz
- Closing VA 820 1 100 3 500
- P.f. 0.4 0.35 0.26
- Closed VA 44 52 125
- P.f. 0.34 0.35 0.4
• 60 Hz
- Closing VA 990 1 200 4 000
- P.f. 0.35 0.31 0.22
- Closed VA 52 65 140
- P.f. 0.35 0.34 0.43
Operating times at 1.0 x Us
• Closing delay ms 20 ... 40 30 ... 60
• Opening delay ms 7 ... 15 10 ... 20
• Arcing time ms 10
Rated data of the main contacts
Load rating with AC
Utilization category AC-1, switching resistive loads
• Rated operational currents Ie At 40 °C up to 690 V A 200 250 300 350 550 800 1 000
At 50 °C up to 690 V A 180 230 270 310 470 650 850
• Rated power of AC loads At 230 V kW 76 95 114 132 208 303 378
with p.f. = 0.95 (at 40 °C) 400 V kW 132 165 197 230 362 527 658
500 V kW 165 206 247 288 452 658 828
690 V kW 227 284 341 397 624 908 1 135
• Minimum conductor cross-section for loads with Ie At 40 °C mm² 95 150 185 240 185 240 300
Utilization categories AC-2 and AC-3
• Rated operational currents Ie Up to 400 V A 120 145 210 550 700
Up to 690 V A 120 210 550 --
• Rated power of squirrel-cage/ At 230 V kW 30 45 75 110 160 220
slipring motors at 50 Hz and 60 Hz 400 V kW 55 75 110 200 280 370
• Short-time current at 40 °C in cold state up to 10 s A 900 1 200 1 600 5 300 6 400
Switching frequency
Switching frequency z in operating cycles/hour
• Contactors without overload relays No-load switching 1/h 3 600
frequency
• Rated operation for utilization category AC-1 1/h 300
Dependence of the switching frequency z’ on the AC-3 1/h 300
operational current I’ and operational voltage U ’:
z’ = z (Ie/I’ ) (Ue/U ’)1.5 1/h
3TK13
Rated data AC-1 Auxiliary Rated control supply SD Screw terminals PU PS* PG
contacts voltage Us (UNIT,
Operational Rating of three-phase AC loads Version SET, M)
current Ie (p f. = 0.95) Article No. Price
Up to 690 V at per PU
(at 40 °C)
230 V 400 V 690 V 1 000 V
A kW kW kW kW NO NC V AC d
For screw fixing
1/L1 3/L2 5/L3 7/L4 13 21 31 43
A1
A2
2/T1 4/T2 6/T3 8/T4 14 22 32 44
200 75 130 225 205 2 2 220 ... 230, 50 Hz 5 3TK1042-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 20 3TK1042-0AU0 1 1 unit 41B
110/120, 50/60 Hz 15 3TK1042-0AF0 1 1 unit 41B
24, 50 Hz 20 3TK1042-0AB0 1 1 unit 41B
250 90 165 280 200 2 2 220 ... 230, 50 Hz 5 3TK1142-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 30 3TK1142-0AU0 1 1 unit 41B
110/120, 50/60 Hz 20 3TK1142-0AF0 1 1 unit 41B
24, 50 Hz 20 3TK1142-0AB0 1 1 unit 41B
300 110 195 340 325 2 2 220 ... 230, 50 Hz 5 3TK1242-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 30 3TK1242-0AU0 1 1 unit 41B
110/120, 50/60 Hz 20 3TK1242-0AF0 1 1 unit 41B
24, 50 Hz 30 3TK1242-0AB0 1 1 unit 41B
350 130 230 395 370 2 2 220 ... 230, 50 Hz 5 3TK1342-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 20 3TK1342-0AU0 1 1 unit 41B
110/120, 50/60 Hz 20 3TK1342-0AF0 1 1 unit 41B
24, 50 Hz 30 3TK1342-0AB0 1 1 unit 41B
550 205 360 620 510 2 2 220 ... 230, 50 Hz1) 5 3TK1442-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 20 3TK1442-0AU0 1 1 unit 41B
110/120, 50/60 Hz 15 3TK1442-0AF0 1 1 unit 41B
800 300 525 905 575 2 2 220 ... 230, 50 Hz1) 5 3TK1542-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 30 3TK1542-0AU0 1 1 unit 41B
110/120, 50/60 Hz 15 3TK1542-0AF0 1 1 unit 41B
1 000 375 655 1 135 -- 2 2 220 ... 230, 50 Hz1) 5 3TK1742-0AP0 1 1 unit 41B
230 ... 240, 50 Hz 30 3TK1742-0AU0 1 1 unit 41B
110/120, 50/60 Hz 20 3TK1742-0AF0 1 1 unit 41B
1)
At 60 Hz: 240 V. Other voltages according to page 4/53 on request.
Surge suppressors
3TK10 ... 3TK13 RC elements 24 ... 48 20 3TK1930-0A 1 1 unit 41B
110 ... 415 5 3TK1930-0B 1 1 unit 41B
3TK14 ... 3TK17 48 ... 110 15 3TK1934-0C 1 1 unit 41B
220 ... 600 5 3TK1934-0D 1 1 unit 41B
Terminal covers
3TK10, 3TK11 For mounting onto contactors -- 5 3TK1940-0A 1 2 units 41B
4
3TK12, 3TK13 5 3TK1942-0A 1 2 units 41B
3TK14, 3TK15 5 3TK1944-0A 1 2 units 41B
3TK17 5 3TK1946-0A 1 2 units 41B
Mechanical interlocking of two identical contactors
3TK10, 3TK11 Locking devices, auxiliary contacts 2 NC -- 5 3TK1920-0A 1 1 unit 41B
3TK12, 3TK13 5 3TK1922-0A 1 1 unit 41B
3TK14 ... 3TK17 Mechanical interlocks including mounting plate 5 3TK1924-0A 1 1 unit 41B
Spare parts
For contactors Version Auxiliary contacts SD Article No. Price PU PS* PG
Connections per PU (UNIT,
Type d SET, M)
14 22 32 44
54 62 72 84
Contacts with fixing parts
3TK10 4 moving and 8 fixed contacts -- 20 3TK1960-0A 1 1 unit 41B
3TK11 20 3TK1961-0A 1 1 unit 41B
3TK12 20 3TK1962-0A 1 1 unit 41B
3TK13 20 3TK1963-0A 1 1 unit 41B
3TK14 20 3TK1964-0A 1 1 unit 41B
3TK15 20 3TK1965-0A 1 1 unit 41B
3TK17 20 3TK1967-0A 1 1 unit 41B
Arc chutes
3TK10 1 arc chute, 4-pole -- 30 3TK1950-0A 1 1 unit 41B
3TK11 30 3TK1951-0A 1 1 unit 41B
3TK12 30 3TK1952-0A 1 1 unit 41B
3TK13 30 3TK1953-0A 1 1 unit 41B
3TK14 30 3TK1954-0A 1 1 unit 41B
3TK15 30 3TK1955-0A 1 1 unit 41B
3TK17 30 3TK1957-0A 1 1 unit 41B
Solenoid coils
3TK10, 3TK11 AC operation1) -- 3TK1970-0A..
3TK12, 3TK13 3TK1972-0A..
3TK14 ... 3TK17 3TK1974-0A..
1) Rated control supply voltages, possible on request:
The 10th and 11th digits of the Article No. must be supplemented
according to the table. Delivery time on request.
AC operation
50 Hz 60 Hz
24 V -- B0 --
110 V 120 V F0 F0
220 ... 230 V 240 V P0 P0
230 ... 240 V -- U0 U0
■ Overview
Standards 3TK20 miniature contactors with 6.3 mm x 0.8 mm flat connec-
tors are coded and can be used in the plug-in base with solder
IEC 60947-1, EN 60947-1, pin connections for printed circuit boards (see page 3/150).
IEC 60947-4-1, DIN EN 60947-4-1
The 3TK20 miniature contactors are suitable for use in any Ratings of three-phase motors
climate. The miniature contactors with screw terminals are The quoted rating (in kW) refers to the output power on the motor
finger-safe according to IEC 60529. shaft (according to the nameplate).
Connection methods The power rating specifications of the contactors in kW are
guide values for 4-pole standard motors at 50 Hz AC and
The miniature contactors are available in versions with screw specified voltage (e.g. 400 V). The actual starting and rated data
terminals, 6.3 mm plug-in terminals and solder pin connections of the motor to be switched must be considered when selecting
for soldering to printed circuit boards.
4
the units.
■ Application
Contactors with plug-in terminals
The main area of application for the 3TK20 miniature contactors
with flat connectors is in household equipment. These contac-
tors are also suitable for simple electric controllers.
No auxiliary switch blocks can be retrofitted.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16168/td https://support.industry.siemens.com/cs/ww/en/ps/16168/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16168/faq
Type 3TK20
Contact endurance of the main contacts
The characteristic curves show the contact endurance
of the contactors when switching inductive AC loads Operating cycles at
(AC-3) depending on the breaking current and rated
230 V
500 V
690 V
400 V
Type 3TK20
Size 00
General data
Dimensions (W x H x D) mm 45 x 48 x 63
D
W
4
Rated insulation voltage Ui
(Pollution degree 3)
• Screw terminals V 690
• Plug-type terminal 6.3 mm x 0.8 mm V 500
• Solder pin connections V 500
Rated impulse withstand voltage Uimp
(Pollution degree 3)
• Screw terminals kV 6
• Plug-type terminal 6.3 mm x 0.8 mm kV 6
• Solder pin connections kV 6
Protective separation between coil and main contacts V Up to 300
According to IEC 60947-1, Appendix N
Permissible ambient temperature1)
• During operation °C -25 ... +55
• During storage °C -55 ... +80
Degree of protection acc. to IEC 60529
• On front IP20 (with screw terminals)
• Connecting terminal IP20 (with screw terminals)
Touch protection acc. to IEC 60529 Finger-safe (for screw terminals)
Shock resistance
• Rectangular pulse
- AC operation g/ms 8.3/5 and 5.2/10
- DC operation g/ms 11.3/5 and 9.2/10
• Sine pulse
- AC operation g/ms 13/5 and 8/10
- DC operation g/ms 17.4/5 and 12.9/10
Short-circuit protection
Main circuit2)
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
acc. to IEC 60947-4-1/EN 60947-4-1
- Type of coordination "1" A 25
- Type of coordination "2" 3) A 10
- Weld-free A 10
• Miniature circuit breaker with C characteristic A 10
Auxiliary circuit
Short-circuit test
• With fuse links of operational class gG: A 6
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
1) Applies to 50/60 Hz coil:
At 50 Hz, 1.1 x Us, with side-by-side mounting and 100 % ON period the
max. ambient temperature is +40 °C.
2)
According to excerpt from IEC 60947-4-1:
- Type of coordination "1"
Destruction of the contactor and the overload relay is permissible.
The contactor and/or overload relay can be replaced if necessary.
- Type of coordination "2"
The overload relay must not suffer any damage. Contact welding on
the contactor is permissible, however, if the contacts can be easily
separated.
3) A short-circuit current of Iq 6 kA applies to type of coordination "2".
Type 3TK20
Size 00
Control
Solenoid coil operating range1) 0.8 ... 1.1 x Us
Solenoid coil power consumption (for cold coil and 1.0 x Us)
Standard version
• AC operation, 50 Hz
- Closing VA 15
- P.f. 0.41
- Closed VA 6.8
- P.f. 0.42
• AC operation, 60 Hz
- Closing VA 14.4
- P.f.
4
0.36
- Closed VA 6.1
- P.f. 0.46
• AC operation, 50/60 Hz1)
- Closing VA 16.5/13.2
- P.f. 0.43/0.38
- Closed VA 8.0/5.4
- P.f. 0.48/0.42
For USA and Canada
• AC operation, 50 Hz
- Closing VA 14.6
- P.f. 0.38
- Closed VA 6.5
- P.f. 0.40
• AC operation, 60 Hz
- Closing VA 14.4
- P.f. 0.30
- Closed VA 6.0
- P.f. 0.44
• DC operation (closing = closed) W 3
Permissible residual current of the electronic circuit2) (with 0 signal)
• AC operation mA 3 x (230 V/Us)
• DC operation mA 1 x (230 V/Us)
Operating times at 1.0 x Us
• AC operation
- Closing delay ms 5 ... 18
- Opening delay ms 3 ... 21
- Dead interval To use the 3TK20 AC-operated contactor in reversing duty an additional
dead interval of 50 ms is required along with an NC contact interlock.
• DC operation
- Closing delay ms 19 ... 31
- Opening delay ms 3 ... 4
• Arcing time ms 10 ... 15
1)
Applies to 50/60 Hz coil:
At 50 Hz, 1.1 x Us, with side-by-side mounting and 100 % ON period
the max. ambient temperature is +40 °C.
2)
The 3TX4490-1J additional load module is recommended for higher
residual currents (see page 3/118).
4
500 V kW 13
690/660 V kW 17 --
• Minimum conductor cross-section for loads with Ie mm2 2.5
Utilization categories AC-2 and AC-3
• Rated operational current Ie Up to 220 V A 9.0
230 V A 9.0
380 V A 9.0
400 V A 8.4
500 V A 6.5
660 V A 5.2 --
690 V A 5.2 --
• Rated power for motors At 110 V kW 1.2
with slipring or squirrel cage 115 V kW 1.2
At 50 and 60 Hz 120 V kW 1.3
127 V kW 1.4
200 V kW 2.2
220 V kW 2.4
230 V kW 2.5
240 V kW 2.6
380 V kW 4.0
400 V kW 4.0
415 V kW 4.0
440 V kW 4.0
460 V kW 4.0
500 V kW 4.0
575 V kW 4.0 --
660 V kW 4.0 --
690 V kW 4.0 --
• Power loss per conducting path At Ie/AC-3 W 0.3
Utilization category AC-4
(Contact endurance approx. 200 000 operating cycles at Ia = 6 x Ie)
• Rated operational current Ie Up to 400 V A 2.6
690 V A 1.8 --
• Rated power for motors with squirrel cage At 110 V kW 0.32
At 50 and 60 Hz 115 V kW 0.33
120 V kW 0.35
• Max. permissible rated operational current 127 V kW 0.37
Ie/AC-4 r Ie/AC-3 up to 500 V, for reduced contact 200 V kW 0.58
endurance and reduced switching frequency. 220 V kW 0.64
230 V kW 0.67
240 V kW 0.70
380 V kW 1.10
400 V kW 1.15
415 V kW 1.20
440 V kW 1.27
460 V kW 1.33
500 V kW 1.45
575 V kW 1.30 --
660 V kW 1.10 --
690 V kW 1.15 --
Type 3TK20
Size 00
Conductor cross-sections
Main and auxiliary conductors Screw terminals
(1 or 2 conductors can be connected)
• Solid mm2 2 x (0.5 ... 2.5), 1 x 4
• Finely stranded with end sleeve mm2 2 x (0.5 ... 1.5), 1 x 2.5
• AWG cables, solid or stranded AWG 2 x (20 ... 14), 1 x 12
• Pin-end connector (DIN 46231) mm2 1 x 1 ... 2.5
• Terminal screw M3
• Prescribed tightening torque for terminal screws Nm 0.8 ... 1.3
lb.in 7 ... 11
4
Flat connectors
Type 3TK20
Size 00
Auxiliary contacts
General data
Standards IEC 60947-5-1
Rated insulation voltage Ui V 690
(Pollution degree 3)
Conventional thermal current Ith = A 10
Rated operational current Ie/AC-12
Load rating with AC
Rated operational current Ie/AC-15/AC-14
• For rated operational voltage Ue 24 ... 230 V A 4
380 ... 400 V A 3
500 V A 2
660 V A 1
690 V A 1
Load rating with DC
Rated operational current Ie/DC-12
• For rated operational voltage Ue 24 V A 4
48 V A 2.2
110 V A 1.1
125 V A 1.1
220 V A 0.5
440 V A --
600 V A --
Rated operational current Ie/DC-13
• For rated operational voltage Ue 24 V A 2.1
48 V A 1.1
110 V A 0.52
125 V A 0.52
220 V A 0.27
440 V A --
600 V A --
460/575 V hp --
- Three-phase At 115 V hp --
200 V hp 3 3 (1 for 3TK20. . -6)
230 V hp 3 3 (1 for 3TK20. . -6)
460/575 V hp 5 --
s, u and U rated data of the auxiliary contacts
Rated voltage, max. V AC 600
Auxiliary switch blocks, max. V AC 300
Switching capacity A 600, Q 300
Uninterrupted current at 240 V AC A 10
AC operation
Solenoid coils for 50 and 60 Hz AC
50 Hz 60 Hz
24 V AC 29 V AC B0
110 V AC 132 V AC F0
230/220 V AC 276 V AC P01)
DC operation
24 V DC B4
1)
Operating range at AC-1 and 220 V: 0.85 to 1.15 x Us;
lower operating range limit according to IEC 60947.
Other voltages and delivery time on request.
* You can order this quantity or a multiple thereof.
4/60 Siemens IC 10 · 2017 Illustrations are approximate.
© Siemens AG 2016
4
A2( ) 2 4 6 8 A2( ) 2 4 6 R2 A2( ) 2 4 R2 R4
AC operation
Solenoid coils for 50 and 60 Hz AC
50 Hz 60 Hz
24 V AC 29 V AC B0
110 V AC 132 V AC F0
230/220 V AC 276 V AC P01)
DC operation
24 V DC B4
1) Operating range at AC-1 and 220 V: 0.85 to 1.15 x Us;
lower operating range limit according to IEC 60947.
Other voltages and delivery time on request.
■ Overview
Standards Operating range of contactor operating mechanisms
IEC 60947-4-1, DIN EN 60947-4-1, Sizes S00 to S3
IEC 60077-2, DIN EN 60077-2
The solenoid coils of the 3RT2 contactors have an extended coil
The contactors are finger-safe according to IEC 60529 operating range from max. 0.7 to 1.25 x Us and are fitted as
(exception: S3 series resistor). The auxiliary conductor and standard with surge suppressors. The opening delay is conse-
coil terminals are all spring-type terminals. quently 2 to 5 ms longer than for standard contactors.
Ambient temperature Sizes S6 to S12
The permissible ambient temperature for operation of the The operating mechanism for the 3RT10 contactors features
contactors (across the full coil operating range) is -40 to +70 °C. solid-state control of the contactor coil. Overvoltage damping
of the operating mechanism coil is already integrated in the elec-
4
Performance range tronics. The operating mechanisms are powered via a supply
3RT contactors are available in all sizes from S00 to S12 up to voltage with an operating range of 0.7 to 1.25 x Us, optionally
250 kW or 500 A (AC-3 at 400 V). also controlled depending on the chosen mode of operation.
Alternatively, control is via the separate 24 to 110 V DC control
signal input.
Three rated voltage ranges are available as direct voltage (DC):
• 24 V DC
• 72 V DC
• 110 V DC
■ Application
Besides standard approval in compliance with IEC 60974-4-1, 3RT201 contactors with series resistor
the contactors with an extended operating range are also
approved in compliance with IEC 60077-2, thus fulfilling the Control and auxiliary circuits
requirement for use in railway applications. The solenoid coils of these contactors have an extended coil
Thus, their suitability for increased requirements such as an operating range from 0.7 to 1.25 x Us and are fitted as standard
with a surge suppressor (suppressor diode or varistor as
• extended temperature range in comparison with the regular preferred).
standard IEC 60497-4-1 or
• extended operating range of the solenoid coils or also The DC solenoid systems of the contactors are modified
• increased resistance to mechanical oscillations and vibrations (to holding excitation) by means of a series resistor.
is warranted. The design of the terminals in the spring-type 3RT201 to 3RT204 contactors with solid-state operating
connection system also contributes toward vibration resis- mechanism, extended operating range
tance.
Control and auxiliary circuits
3RT20 contactors with conventional coil
The solenoid coils of these contactors have an extended coil
Control and auxiliary circuits operating range from 0.7 to 1.25 x Us1) and are fitted as stan-
These contactors have an extended operating range from dard with varistors to provide protection against overvoltage.
0.7 to 1.25 x Us; on size S00 the coils are fitted with suppressor The contactors are energized via upstream control electronics
diodes, on size S0 with varistors. An additional series resistor is that ensure the coil operating range of 0.7 to 1.25 x Us1) at an
not required. ambient temperature of 70 °C. They are supplied as complete
Note: units with integrated coil electronics. A varistor is integrated for
damping opening surges in the coil.
An additional auxiliary switch block cannot be mounted.
The possibility of mounting auxiliary switches is the same as that
Side-by-side mounting for equivalent standard contactors for switching motors in the
A clearance of 10 mm is required for side-by-side mounting at matching size (see overview diagrams of the 3RT20 contactors
ambient temperatures > 60 °C 70 °C. from page 3/7 onwards).
Side-by-side mounting
With these contactor versions in sizes S00 and S0, side-by-side
mounting is permitted at ambient temperatures up to 70 °C.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16177/td • System Manual "SIRIUS – System Overview",
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16177/faq https://support.industry.siemens.com/cs/WW/en/view/60311318
• Manual "SIRIUS – SIRIUS 3RT Contactors/Contactor Assemblies",
https://support.industry.siemens.com/cs/WW/en/view/60306557
• Application Manual "SIRIUS Controls with IE3/IE4 Motors",
https://support.industry.siemens.com/cs/ww/en/view/94770820
4
Size S00 S0
General data
Upright mounting position
• Contactors with series resistor Special version (on request)
• Contactors with conventional coil Special version (on request)
Ambient temperature
• During operation °C -40 ... +701) -40 ... +70
• During storage °C -55 ... +80
Control
Solenoid coil operating range DC 0.7 ... 1.25 x Us
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Contactors with series resistor Closing W 13 --
Closed W 4.0 --
• Contactors with conventional operating Closing W 2.8 -- 4.5 --
mechanism Closed W 2.8 -- 4.5 --
• Contactors with solid-state operating Closing W -- 4.0 4.5 -- 6.7 13.2
mechanism Closed W -- 0.7 0.75 -- 0.8 1.56
1) 3RT20. .-. K contactors without the article number suffix "-0LA2" are cou- All details and technical specifications not mentioned here
pling contactors that are certified for the -25 to +60 °C temperature range. are identical to those of the basic units, see from page 3/19
For railway applications, an additional certification approves these
contactors with a minimum distance of 10 mm for the extended tempera- onwards.
ture range from -40 to +70 °C.
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
1)
12 3 5.5 5.5 5.5 10 1 -- 24 } 3RT2017-2KB41 1 1 unit 41B
110 5 3RT2017-2KF41 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 } 3RT2017-2KB42 1 1 unit 41B
110 5 3RT2017-2KF42 1 1 unit 41B
With conventional coil, fitted with varistor
• 1 NO, Ident. No. 10 • 1 NC, Ident. No. 01
A1(+) 1/L1 3/L2 5/L3 13 A1(+) 1/L1 3/L2 5/L3 21
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
1)
12 3 5.5 5.5 5.5 10 1 -- 24 5 3RT2017-2LB41 1 1 unit 41B
110 5 3RT2017-2LF41 1 1 unit 41B
1)
12 3 5.5 5.5 5.5 01 -- 1 24 5 3RT2017-2LB42 1 1 unit 41B
110 5 3RT2017-2LF42 1 1 unit 41B
With series resistor, fitted with suppressor diode
E1(+) 1/L1 3/L2 5/L3
A2(–)
2/T1 4/T2 6/T3
A2(–)
2/T1 4/T2 6/T3
12 3 5.5 5.5 5.5 --2) -- 13) 24 5 3RT2017-2LB42-0LA0 1 1 unit 41B
110 5 3RT2017-2LF42-0LA0 1 1 unit 41B
16 4 7.5 10 11 --2) -- 13) 24 5 3RT2018-2LB42-0LA0 1 1 unit 41B
110 5 3RT2018-2LF42-0LA0 1 1 unit 41B
1)
It is not possible to mount an auxiliary switch block. A clearance of 10 mm For accessories and spare parts, see page 3/75 onwards.
is required for side-by-side mounting at ambient temperatures > 60 °C.
2) One 4-pole auxiliary switch block according to EN 50005 can be mounted
from -40 to 70 °C; no clearance required.
3) NC contact cannot be used because it is used for switching of the series
resistor.
* You can order this quantity or a multiple thereof.
4/64 Siemens IC 10 · 2017 Illustrations are approximate.
© Siemens AG 2016
4
3RT201. -2X. 41-0LA2 3RT201. -2X.42-0LA2 3RT202. -2K. 40 3RT202.-2X. 40-0LA2
Rated data according to IEC 60947-4-1 Auxiliary contacts Rated control SD Spring-type terminals PU PS* PG
AC-2 and AC-3 supply voltage (UNIT,
tu: 70 °C Us SET, M)
Operational Rating of three-phase motors Ident. No. Version
current Ie at Article No. Price
per PU
400 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V DC d
3RT20 contactors for switching motors
Size S00
With solid-state operating mechanism, with integrated varistor
• 1 NO, Ident. No. 10 • 1 NC, Ident. No. 01
A1(+) 1/L1 3/L2 5/L3 13 A1(+) 1/L1 3/L2 5/L3 21
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
1)
12 3 5.5 5.5 5.5 10 1 -- 24 5 3RT2017-2XB41-0LA2 1 1 unit 41B
110 5 3RT2017-2XF41-0LA2 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 5 3RT2017-2XB42-0LA2 1 1 unit 41B
110 5 3RT2017-2XF42-0LA2 1 1 unit 41B
16 4 7.5 10 11 101) 1 -- 24 5 3RT2018-2XB41-0LA2 1 1 unit 41B
110 5 3RT2018-2XF41-0LA2 1 1 unit 41B
16 4 7.5 10 11 011) -- 1 24 5 3RT2018-2XB42-0LA2 1 1 unit 41B
110 5 3RT2018-2XF42-0LA2 1 1 unit 41B
Size S0
With conventional operating mechanism
(coupling contactors)
1 NO + 1 NC, Ident. No. 11
A2(–)
2/T1 4/T2 6/T3 14 22
17 4 7.5 10 11 11 1 1 24 2 3RT2025-2KB40 1 1 unit 41B
110 5 3RT2025-2KF40 1 1 unit 41B
25 5.5 11 11 11 11 1 1 24 2 3RT2026-2KB40 1 1 unit 41B
110 5 3RT2026-2KF40 1 1 unit 41B
32 7.5 15 18.5 18.5 11 1 1 24 5 3RT2027-2KB40 1 1 unit 41B
110 5 3RT2027-2KF40 1 1 unit 41B
With solid-state operating mechanism
1 NO + 1 NC, Ident. No. 11
A2(–)
2/T1 4/T2 6/T3 14 22
A2(–)
2/T1 4/T2 6/T3 14 22
A2(–)
2/T1 4/T2 6/T3 14 22
4
3RT1055 -2XB46-0LA2 3RT1064 -2XB46-0LA2 3RT1075 -2XB46-0LA2
Size Rated data according to IEC 60947-4-1 Auxiliary Rated control SD Article No. Price PU PS* PG
AC-2 and AC-3, contacts, supply per PU (UNIT,
tu: Up to 70 °C lateral voltage Us SET, M)
Opera- Ratings of three-phase motors Version
tional at 50 Hz and
current Ie
400 V 400 V
A kW NO NC V DC d
Solid-state operating mechanism ·
with 24 ... 110 V DC control signal input
e. g. for control by PLC
A1 + - Spring-type terminals
ON OFF
1/L1 3/L2 5/L3 13 21 31 43 for coil and auxiliary
PLC
switch terminals
■ Overview
DC operation Uninterrupted duty at temperatures > +60 °C reduces the
mechanical endurance, the current carrying capacity of the
IEC 60947-4-1, EN 60947-4-1 conducting paths and the switching frequency.
The contactor relays are finger-safe according to IEC 60529.
The size S00 contactor relays have spring-type connections for Control and auxiliary circuits
all terminals. The solenoid coils of the contactor relays have an extended coil
operating range from 0.7 to 1.25 x Us and are fitted as standard
Ambient temperature with surge suppressors. The opening delay is consequently 2 to
The permissible ambient temperature for operation of the 5 ms longer than for standard contactors.
contactor relays (across the full coil operating range) is -40 to
+70 °C.
4
■ Application
For operation in installations that are subject both to consider- The size S00 contactor relays are supplied prewired with a
able variations in the control voltage and to high ambient plug-on module containing the series resistor. A surge suppres-
temperatures, e. g. railway applications under extreme climatic sor (a suppressor diode or varistor as preferred) is integrated.
conditions, rolling mills, etc.
A 4-pole auxiliary switch block (according to EN 50005) can be
Also for control supply voltages with battery buffering to extend fitted additionally.
the operating time in the event of battery charge failure.
Side-by-side mounting
Contactor relays with conventional coil Side-by-side-side mounting is permissible at ambient
Control and auxiliary circuits temperatures up to 70 °C.
These contactor relays have an extended operating range from Contactor relays with solid-state operating mechanism
0.7 to 1.25 x Us; the coils are fitted with suppressor diodes as
standard. An additional series resistor is not required. Control and auxiliary circuits
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16174/faq
https://support.industry.siemens.com/cs/ww/en/ps/16174/td Manuals, see https://support.industry.siemens.com/cs/ww/en/ps/16174/man
4
3RH2122-2K. 40 3RH2122-2K.40-0LA0
Rated operational current Contacts Rated control supply SD Spring-type terminals PU PS* PG
Ie/AC-15/AC-14 voltage Us (UNIT,
tu: 70 °C at SET, M)
230 V 400 V 500 V 690 V Version
Article No. Price
per PU
A A A A NO NC V DC d
3RH21 contactor relays
Size S00
With conventional coil, fitted with suppressor diode
Terminal designations according to EN 50011
2 NO + 2 NC, Ident. No. 22E 3 NO + 1 NC, Ident. No. 31E 4 NO, Ident. No. 40E
13 21 31 43 13 21 33 43 13 23 33 43
A1(+) A1(+) A1(+)
A2(–)
14 22 32 44
10 3 2 1 2 21) 24 5 3RH2122-2LB40 1 1 unit 41A
110 2 3RH2122-2LF40 1 1 unit 41A
1)
It is not possible to mount an auxiliary switch block. For accessories, see page 3/75 onwards.
Other voltages according to page 3/73 on request.
3RH2122-2K. 40 3RH2122-2K.40-0LA0
Rated operational current Contacts Rated control supply SD Spring-type terminals PU PS* PG
Ie/AC-15/AC-14 voltage Us (UNIT,
tu: 70 °C at SET, M)
230 V 400 V 500 V 690 V Version
Article No. Price
per PU
A A A A NO NC V DC d
3RH21 contactor relays
Size S00
With series resistor, fitted with suppressor diode
Terminal designations according to EN 50011
2 NO + 1 NC, Ident. No. 21X
E1(+) 13 23 31
A2(–)
14 24 32
10 3 2 1 2 11) 24 5 3RH2122-2KB40-0LA0 1 1 unit 41A
110 5 3RH2122-2KF40-0LA0 1 1 unit 41A
With series resistor, fitted with varistor
Terminal designations according to EN 50011
2 NO + 1 NC, Ident. No. 21X
E1(+) 13 23 31
A2(–)
14 24 32
10 3 2 1 2 11) 24 2 3RH2122-2LB40-0LA0 1 1 unit 41A
110 2 3RH2122-2LF40-0LA0 1 1 unit 41A
With solid-state operating mechanism, with integrated varistor
Terminal designations according to EN 50011
2 NO + 2 NC, Ident. No. 22E
13 21 31 43
A1(+)
A2(–)
14 22 32 44
10 3 2 1 2 21) 24 5 3RH2122-2XB40-0LA2 1 1 unit 41A
110 5 3RH2122-2XF40-0LA2 1 1 unit 41A
1)
4-pole auxiliary switch block according to EN 50005 can be mounted. For accessories, see page 3/75 onwards.
Other voltages according to page 3/73 on request.
■ Overview
Standards Ambient temperature
IEC 60947-4-1, EN 60947-4-1 The permissible ambient temperature for operation of the
contactors (across the full coil operating range) is -50 to +70 °C.
The contactor relays are finger-safe according to IEC 60529. Uninterrupted duty at temperatures < -25 °C and > +55 °C
Terminal covers may have to be fitted onto the connecting bars, reduces the mechanical endurance, the current carrying
depending on the configuration with other devices. capacity of the conducting paths and the switching frequency.
A clearance of 10 mm is required for side-by-side mounting at
ambient temperatures > 55 °C. There is no need to reduce the
technical specifications.
■ Application
4
For operation in installations which are subject both to consider- Control and auxiliary circuits
able variations in the control voltage and to high ambient tem-
peratures, e.g. in railway applications. The solenoid coils of the contactor relays have an extended coil
operating range from 0.7 to 1.25 x Us and are fitted as standard
with varistors to provide protection against overvoltage.
The opening delay is consequently 2 to 5 ms longer than for
standard contactors.
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16176/faq
https://support.industry.siemens.com/cs/ww/en/ps/16176/td Manuals, see https://support.industry.siemens.com/cs/ww/en/ps/16176/man
3TH4244-0L. .
Contacts Rated operational current Contacts1) Rated control supply SD Screw terminals PU PS* PG
4
voltage Us (UNIT,
Ie/AC-15/AC-14 Ident. No. Version Article No. Price SET, M)
acc. to per PU
230 V 400 V 500 V 690 V EN 50011
Number A A A A NO NC V DC d
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
DC operation
13 23 33 43 51 61 71 81
A1(+)
A2( )
14 24 34 44 52 62 72 82
A2( )
14 24 34 44 54 62 72 82
A2( )
14 24 34 44 54 62 72 84
■ Overview
Standards Series resistor
IEC 60947-4-1, EN 60947-4-1 The DC solenoid systems of the 3TC contactors must be modi-
fied (to hold-in coil) by means of a series resistor. This series
The contactors are finger-safe according to IEC 60529 (excep- resistor is supplied separately packed with the contactors.
tion: series resistor). Terminal covers may have to be fitted onto
the connecting bars, depending on the configuration with other With types 3TC48, the series resistor must be attached onto the
devices. right-hand side of the auxiliary switch block by means of the
enclosed mounting parts and sets of links provided, while in the
All specifications and technical specifications not mentioned case of the 3TC44 it must be mounted and wired between the
here are identical to those of the standard 3TC contactors, contactor poles. With types 3TC52 and 3TC56, the series
see page 4/75. resistor must be attached separately next to the contactors.
Ambient temperature
4
Auxiliary contacts
The permissible ambient temperature for operation of the con- The contactors are equipped with two lateral auxiliary switch
tactors (across the full coil operating range) is -50 to +70 °C. Un- blocks each with 1 NO + 1 NC contact. Further auxiliary switch
interrupted duty at temperatures < -25 °C and > +55 °C reduces blocks cannot be fitted to the DC-operated contactors.
the mechanical endurance, the current carrying capacity of the
conducting paths and the switching frequency. One NC contact is required for the series resistor function.
Two NO contacts and one NC contact are thus freely available.
At ambient temperatures > 55 °C, a clearance of 10 mm is
required for side-by-side mounting of size 2 contactors. Reversing contactors
There is no need to reduce the technical specifications.
With the 3TC52 and 3TC56 contactors, the series resistor must
Ratings of three-phase motors be connected using an additional K2 reversing contactor
(3RT1317-1F.40). This contactor is automatically included in the
The quoted rating (in kW) refers to the output power on the motor scope of supply in the same packaging as the contactor.
shaft (according to the nameplate).
The power rating specifications of the contactors in kW are Dimensions
guide values for 4-pole standard motors at 50 Hz AC and spec- Attaching resistors and varistors increases the width of the
ified voltage (e.g. 400 V). The actual starting and rated data of contactors.
the motor to be switched must be considered when selecting the
units.
■ Application
For operation in installations which are subject both to consider- Control and auxiliary circuits
able variations in the control voltage and to high ambient
temperatures, e.g. in railway applications. The solenoid coils of the contactors have an extended coil oper-
ating range from 0.7 to 1.25 x Us and are fitted as standard with
varistors to provide protection against overvoltage. The opening
delay is consequently 2 to 5 ms longer than for standard contac-
tors.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16180/td https://support.industry.siemens.com/cs/ww/en/ps/16180/man
3TC48
Size Utilization Rated opera- Rated power Auxiliary Rated control SD Screw terminals PU PS* PG
category tional current of loads contacts1) supply (UNIT,
Ie voltage Us SET, M)
at at Version
750 V 220 V 440 V 600 V 750 V Article No. Price
per PU
A kW kW kW kW NO NC V DC d
Contactors for switching DC voltage
DC operation
Terminal designations according to EN 50012 and EN 50005
1/L1 3/L2 13 21 31 43
A1
A2
2/T1 4/T2 14 22 32 44
2 DC-1 32 7 14 19.2 24 2 12) 24 5 3TC4417-0LB4 1 1 unit 41B
DC-3/DC-5 7.5 5 9 9 4 110 10 3TC4417-0LF4 1 1 unit 41B
4 DC-1 75 16.5 33 45 56 2 12) 24 15 3TC4817-0LB4 1 1 unit 41B
DC-3/DC-5 75 13 27 38 45 110 15 3TC4817-0LF4 1 1 unit 41B
2)
8 DC-1 170 48 97 132 165 2 1 24 15 3TC5217-0LB4 1 1 unit 41B
DC-3/DC-5 170 41 82 110 110 110 15 3TC5217-0LF4 1 1 unit 41B
12 DC-1 400 88 176 240 300 2 12) 24 15 3TC5617-0LB4 1 1 unit 41B
DC-3/DC-5 400 70 140 200 250 110 15 3TC5617-0LF4 1 1 unit 41B
1)
The number of auxiliary contacts cannot be increased. Other rated control supply voltages according to page 4/82
2) One NC contact used for series resistor. on request.
■ Accessories
For accessories, see Basic units of the 3TC contactors,
from page 4/82.
Spare parts
For contactors Remarks Rated control SD Article No. Price PU PS* PG
supply voltage per PU (UNIT,
Us SET, M)
Size Type V DC d
Arc chutes
For contactors with extended operating range
2 3TC4417-0L. . With cutout for resistor 5 3TY2442-0B 1 1 unit 41B
mounting
Solenoid coils
For contactors with extended operating range
2 3TC44 With series resistor, 24 15 3TY6443-0LB4 1 1 unit 41B
without varistor 110 15 3TY6443-0LF4 1 1 unit 41B
4 3TC48 24 15 3TY6483-0LB4 1 1 unit 41B
110 15 3TY6483-0LF4 1 1 unit 41B
All spare parts not mentioned here are identical to those of the
basic units of the 3TC contactors, see page 4/84.
■ Overview
3TC4 and 3TC5 Auxiliary contacts
IEC 60947-1, EN 60947-1, The contactors are equipped with two lateral auxiliary switch
IEC 60947-4-1, EN 60947-4-1, blocks each with 1 NO + 1 NC contact. On the contactors 3TC48
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) to 3TC56 with AC operation, a second auxiliary switch block can
be mounted on the right and left. On contactors with DC opera-
The contactors are finger-safe according to IEC 60529. tion, expansion of the auxiliary contacts is not possible.
Terminal covers may have to be fitted onto the connecting bars,
depending on the configuration with other devices. 3TC7
The DC motor ratings given in the tables are applicable to the IEC 60947-4-1, EN 60947-4-1
DC-3 and DC-5 utilization categories with two-pole switching
of the load or with the two conducting paths of the contactor The contactors are suitable for use in any climate. They are
suitable for switching and controlling DC motors as well as all
4
connected in series.
other DC circuits.
One contactor conducting path can switch full power up to
220 V. For voltages over 220 V, the two conducting paths are The solenoid excitation is configured for a particularly large
to be switched in series; see "Rated data of the main contacts", operating range. It is between 0.7 or 0.8 and 1.2 Us.
page 4/77. 3TC74 contactors can be used at up to 750 V/400 A and 50 Hz
in AC-1 operation.
For voltages over 750 V, the two conducting paths (3TC74: two
contactors) are to be switched in series; see "Rated data of the
main contacts", page 4/79.
■ Application
The contactors are suitable for switching and controlling A version with an especially large actuating voltage is available
DC motors as well as all other DC circuits. for operation in electrically driven vehicles and in switchgear
with a particularly large coil operating range (see page 4/84).
■ Technical specifications
Type 3TC4 and 3TC7 3TC5
Rated data of the auxiliary contacts
Rated insulation voltage Ui (pollution degree 3) V 690
Conventional thermal current Ith = rated operational current Ie/AC-12 A 10 10
AC load
Rated operational current Ie/AC-15/AC-14
• For rated operational voltage Ue 24 V A 10 10
110 V A 10 10
125 V A 10 10
220 V A 6 6
230 V A 5.6 5.6
380 V A 4 4
400 V A 3.6 3.6
500 V A 2.5 2.5
660 V A 2.5 2.5
690 V A -- --
DC load
Rated operational current Ie/DC-12
• For rated operational voltage Ue 24 V A 10 10
60 V A 10 10
110 V A 3.2 8
125 V A 2.5 6
220 V A 0.9 2
440 V A 0.33 0.6
600 V A 0.22 0.4
Rated operational current Ie/DC-13
• For rated operational voltage Ue 24 V A 10 10
48 V A 5 5
110 V A 1.14 2.4
125 V A 0.98 2.1
220 V A 0.48 1.1
440 V A 0.13 0.32
600 V A 0.07 0.21
10 7 20 NSB0_00656
8 NSB0_00655
6 Mill.
10 5 10
4
8
6
4 8
2
6
10 4
8
6 4
4
2
2
0,5
10 3
200 400 50 100 150 200 250 300 a (A) 400
10 20 40 100 600 1 000 a (A)
• AC operation mm 70 x 85 x 100 100 x 183 x 154 135 x 238 x 200 160 x 279 x 251
D
4
- Closed VA/p.f. 11/9/0.28/0.27 --
at 50 Hz/60 Hz
Operating times (at 0.8 ... 1.1 x Us) (The values apply up to and including 20 % undervoltage,
Total break time = Opening delay + Arcing time 10 % overvoltage, as well as when the coil is cold and warm)
• DC operation - Closing delay ms 35 ... 190 90 ... 380 120 ... 400 110 ... 400
- Opening delay1) ms 10 ... 25 17 ... 28 22 ... 35 40 ... 110
• AC operation - Closing delay ms 10 ... 40 20 ... 50
- Opening delay1) ms 5 ... 25 5 ... 30 10 ... 30
• Arcing time - DC-1 ms 20
- DC-3/DC-5 ms 30
Rated data of the main contacts
Load rating with DC
Utilization category DC-1, switching resistive loads (L/R 1 ms)
• Rated operational currents Ie Up to Ue 750 V A 32 75 220 400
(at 55 °C)
• Minimum conductor cross-section mm2 6 25 95 240
• Rated power at Ue At 220 V kW 7 16.5 48 88
( 220 V DC: one conducting path, 440 V kW 14 33 97 176
> 220 V DC: two conducting paths in series) 600 V kW 19.2 45 132 240
750 V kW 24 56 165 300
Utilization categories DC-3 and DC-5,
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational currents Ie Up to 220 V A 32 75 220 400
(at 55 °C) 440 V A 29 75 220 400
600 V A 21 75 220 400
750 V A 7.5 75 170 400
• Rated power at Ue At 110 V kW 2.5 6.5 20 35
( 220 V DC: one conducting path, 220 V kW 5 13 41 70
> 220 V DC: two conducting paths in series) 440 V kW 9 27 82 140
600 V kW 9 38 110 200
750 V kW 4 45 110 250
Switching frequency
Switching frequency z in operating cycles/hour
AC/DC operation
• With resistive load DC-1 h-1 1 500 1 000
• For inductive load DC-3/DC-5 h-1 750 600
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Solid mm2 2 x (2.5 ... 10) 2 x (6 ... 16) --
• Finely stranded with end sleeve mm2 2 x (1.5 ... 4) --
• Stranded with cable lug mm2 2 x 16 2 x 35 2 x 120 2 x 150
• Pin-end connector to DIN 46231 mm2 2 x (1 ... 6) --
• Busbars mm -- 15 x 2.5 25 x 4 2 x (25 x 3)
• Terminal screw M5 M6 M10
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid mm2 2 x (1 ... 2.5)
• Finely stranded with end sleeve mm2 2 x (0.75 ... 1.5)
1)
The opening delay times can increase if the contactor coils are damped Rated data of the auxiliary contacts, see page 4/75.
against voltage peaks. The 3TC44 contactors are not allowed to be fitted
with diodes.
D
W
NSB0_00650c
22,5° 22,5° 22,5° 22,5°
The contactors are designed for operation on a vertical
mounting surface.
4
4
• Critical currents, without arc extinction At 440 V A 7 --
600 V A 13 --
750 V A 15 --
800 V A -- 7
1 200 V A -- 13
1 500 V A -- 15
Utilization categories DC-3 and DC-5,
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational current Ie (at 55 °C) A 400
• Rated power at Ue At 110 V kW 35
( 220 V DC: one conducting path, 220 V kW 70
> 220 V DC: two conducting paths in series) 440 V kW 140
600 V kW 200
750 V kW 250
1 200 V kW -- 400
1 500 V kW -- 500
Permissible rated current for regenerative braking A 400
at 110 ... 600 V
Switching frequency
Switching frequency z in operating cycles/hour
AC/DC operation
• With resistive load DC-1 h-1 750 1 000
• For inductive load DC-3/DC-5 h-1 500
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Stranded with cable lug mm2 2 x ... 150
• Busbars mm 2 x (30 x 4)
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid mm2 1 ... 2.5
• Finely stranded with end sleeve mm2 0.75 ... 1.5
3TC44 3TC48
Size Utilization Opera- Ratings of Auxiliary Rated control SD Screw terminals PU PS* PG
category1) tional DC motors at contacts3) supply (UNIT,
4
A kW kW kW kW kW NO NC V d
3TC44 to 3TC56 2-pole contactors · Operational voltage up to 750 V
Terminal designations according to EN 50012
1/L1 3/L2 13 21 31 43
A1
A2
2/T1 4/T2 14 22 32 44
DC operation
Screw fixing and snap-on mounting onto TH 35 standard mounting rail
2 DC-3, DC-5 32 2.5 5 9 9 4 2 2 24 DC } 3TC4417-0AB4 1 1 unit 41B
110 DC } 3TC4417-0AF4 1 1 unit 41B
220 DC } 3TC4417-0AM4 1 1 unit 41B
Screw fixing
4 DC-3, DC-5 75 6.5 13 27 38 45 2 2 24 DC 2 3TC4817-0AB4 1 1 unit 41B
110 DC 2 3TC4817-0AF4 1 1 unit 41B
220 DC 2 3TC4817-0AM4 1 1 unit 41B
8 DC-3, DC-5 2204) 20 41 82 110 110 2 2 24 DC 15 3TC5217-0AB4 1 1 unit 41B
110 DC 15 3TC5217-0AF4 1 1 unit 41B
220 DC 10 3TC5217-0AM4 1 1 unit 41B
12 DC-3, DC-5 400 35 70 140 200 250 2 2 24 DC 15 3TC5617-0AB4 1 1 unit 41B
110 DC 15 3TC5617-0AF4 1 1 unit 41B
220 DC 15 3TC5617-0AM4 1 1 unit 41B
AC operation, 50 Hz
Screw fixing and snap-on mounting onto TH 35 standard mounting rail
2 DC-3, DC-5 32 2.5 5 9 9 4 2 2 220 / 230 AC5) } 3TC4417-0BP0 1 1 unit 41B
110/110 AC } 3TC4417-0BF0 1 1 unit 41B
Screw fixing
4 DC-3, DC-5 75 6.5 13 27 38 45 2 2 220 / 230 AC5) 2 3TC4817-0BP0 1 1 unit 41B
110 AC 15 3TC4817-0BF0 1 1 unit 41B
8 DC-3, DC-5 2204) 20 41 82 110 110 2 2 220 / 230 AC5) 2 3TC5217-0BP0 1 1 unit 41B
110 AC 10 3TC5217-0BF0 1 1 unit 41B
12 DC-3, DC-5 400 35 70 140 200 250 2 2 220 / 230 AC5) 15 3TC5617-0BP0 1 1 unit 41B
110 AC 15 3TC5617-0BF0 1 1 unit 41B
1) Permissible load for DC-1 utilization category: Other rated control supply voltages according to page 4/82 on
see detailed technical specifications in the reference manual request.
"Switching Devices – Contactors and Contactor Assemblies",
https://support.industry.siemens.com/cs/ww/en/view/35554359. For accessories, see page 4/82.
2)
The following rated operational currents are permitted for reversing duty
with 3TC44 to 3TC56 contactors:
For spare parts, see page 4/84.
Contactor Rated operating voltage
Type 110 V, 220 V 440 V
3TC44 32 A 7A
3TC48 75 A 75 A
3TC52 170 A 170 A
3TC56 400 A 400 A
3)
The fitting of auxiliary switches cannot be altered on DC-operated
contactors.
4)
At > 600 V: Ie = 170 A.
5) Operating range at 220 V AC: 0.85 to 1.15 x Us.
3TC74 3TC78
Size Utiliza- Opera- Ratings of Auxiliary Rated con- SD Screw PU PS* PG
tion cate- tional DC motors at con- trol supply terminals (UNIT,
gory 1) cur- tacts2) voltage Us SET,
4
rent Ie 110 V 220 V 440 V 600 V 750 V 1 200 V 1 500 V Version M)
Article No. Price
per PU
A kW kW kW kW kW kW kW NO NC V d
3TC74 1-pole contactors · Operational voltage up to 750 V
DC operation
Terminal designations acc. to EN 50005
A1 1/L1 13 21 31 43 53 61 71 83
2/T1 14 22 32 44 54 62 72 84
A2
12 DC-3, 400 35 70 140 200 250 -- -- 4 4 230/220 AC3) 15 3TC7414-1CM 1 1 unit 41B
DC-5
3TC78 2-pole contactors · Operational voltage up to 1 500 V
DC operation
Terminal designations acc. to EN 50005
A1 1/L1 3/L2 13 21 31 43 53 61 71 83
2/T1 4/T4 14 22 32 44 54 62 72 84
A2
12 DC-3, 400 35 70 140 200 250 400 500 4 4 24 DC 15 3TC7814-0EB 1 1 unit 41B
DC-5 110 DC 15 3TC7814-0EF 1 1 unit 41B
AC operation, 50 Hz
Terminal designations acc. to EN 50005
Z
1/L1 3/L2 13 21 31 43 53 61 71 83
~A2
~A1
2/T1 4/T2 14 22 32 44 54 62 72 84
12 DC-3, 400 35 70 140 200 250 400 500 4 4 230/220 AC3) 15 3TC7814-1CM 1 1 unit 41B
DC-5
1)
Permissible load for DC-1 utilization category: Other rated control supply voltages according to page 4/82 on
see detailed technical specifications in the reference manual request.
"Switching Devices – Contactors and Contactor Assemblies",
https://support.industry.siemens.com/cs/ww/en/view/35554359. For spare parts, see page 4/84.
2)
The fitting of auxiliary switches cannot be altered on DC-operated
contactors.
3)
Upper operating range limit at 230 V AC: 1.14 x Us.
■ Options
Rated control supply voltages, possible on request (change of the 10th and 11th digits of the Article No.)
Delivery time on request
Rated control supply voltage Contactor type 3TC44 3TC48 3TC52/3TC56 3TC74/3TC78
Us
AC operation
Solenoid coils for 50 Hz
24 V AC B0 B0 -- --
110 V AC F0 F0 F0 --
230/220 V AC P01) P01) P01) M2)
240 V AC U0 U0 -- --
4
■ Accessories
For contactors Version Auxiliary switch block SD Screw terminals PU PS* PG
Auxiliary Left Right (UNIT,
contacts SET,
M)
Article No. Price
per PU
Size Type NO NC d
Second auxiliary switch blocks (for AC operation only)
4 3TC48 2nd auxiliary switch block, left 20 3TY6501-1K 1 1 unit 41B
1 1 53 61 --
54 62
2nd auxiliary switch block, right 20 3TY6501-1L 1 1 unit 41B
1 1 -- 71 83
72 84
8 and 12 3TC52, 2nd auxiliary switch block, left 20 3TY6561-1K 1 1 unit 41B
3TC56 1 1 53 61 --
54 62
2nd auxiliary switch block, right 20 3TY6561-1L 1 1 unit 41B
1 1 -- 71 83
72 84
52 54 62 64
5TY7561-1.
For contactors Version Rated control supply SD Article No. Price PU PS* PG
voltage U s per PU (UNIT,
SET,
M)
Size Type V AC V DC d
Surge suppressors · Varistors
2 3TC441) Varistors2) 24 ... 48 24 ... 70 2 3TX7402-3G 1 1 unit 41B
With line spacer, for 48 ... 127 70 ... 150 2 3TX7402-3H 1 1 unit 41B
mounting onto the coil 127 ... 240 150 ... 250 2 3TX7402-3J 1 1 unit 41B
terminal 240 ... 400 -- 15 3TX7402-3K 1 1 unit 41B
400 ... 600 -- 15 3TX7402-3L 1 1 unit 41B
4 3TC48 Varistors2) 24 ... 48 24 ... 70 2 3TX7462-3G 1 1 unit 41B
For sticking onto the 48 ... 127 70 ... 150 5 3TX7462-3H 1 1 unit 41B
3TX7402-3. contactor base or for 127 ... 240 150 ... 250 2 3TX7462-3J 1 1 unit 41B
mounting separately
4
240 ... 400 -- 5 3TX7462-3K 1 1 unit 41B
400 ... 600 -- 5 3TX7462-3L 1 1 unit 41B
8 and 12 3TC52, Varistors 24 ... 48 -- 2 3TX7462-3G 1 1 unit 41B
3TC56 For sticking onto the 48 ... 127 -- 5 3TX7462-3H 1 1 unit 41B
contactor base or for 127 ... 240 -- 2 3TX7462-3J 1 1 unit 41B
mounting separately 240 ... 400 -- 5 3TX7462-3K 1 1 unit 41B
400 ... 600 -- 5 3TX7462-3L 1 1 unit 41B
3TX7462-3. 8 and 12 3TC52, Varistors2) -- 24 ... 70 5 3TX7522-3G 1 1 unit 41B
3TC56 For separate screw -- 70 ... 150 5 3TX7522-3H 1 1 unit 41B
fixing or snapping -- 150 ... 250 5 3TX7522-3J 1 1 unit 41B
onto TH 35 standard
mounting rail
3TX7522-3.
Surge suppressors · RC elements
4 3TC48 RC elements 24 ... 48 -- 15 3TX7462-3R 1 1 unit 41B
For lateral snapping -- 24 ... 70 5 3TX7522-3R 1 1 unit 41B
onto auxiliary switch or 48 ... 127 -- 2 3TX7462-3S 1 1 unit 41B
TH 35 standard -- 70 ... 150 5 3TX7522-3S 1 1 unit 41B
mounting rail
127 ... 240 -- 2 3TX7462-3T 1 1 unit 41B
-- 150 ... 250 5 3TX7522-3T 1 1 unit 41B
240 ... 400 -- 2 3TX7462-3U 1 1 unit 41B
400 ... 600 -- 5 3TX7462-3V 1 1 unit 41B
3TX7462-3. , 8 and 12 3TC52, RC elements 24 ... 48 -- 5 3TX7522-3R 1 1 unit 41B
3TX7522-3. 3TC56 For lateral snapping 48 ... 127 -- 5 3TX7522-3S 1 1 unit 41B
onto auxiliary switch or 127 ... 240 -- 5 3TX7522-3T 1 1 unit 41B
TH 35 standard 240 ... 400 -- 5 3TX7522-3U 1 1 unit 41B
mounting rail 400 ... 600 -- 5 3TX7522-3V 1 1 unit 41B
Surge suppressors · Diodes
4 to 12 3TC48, Diode assemblies3) -- 24 ... 250 2 3TX7462-3D 1 1 unit 41B
3TC52, (diode and Zener
3TC56 diode) for DC solenoid
system, for sticking
onto the contactor
base or for mounting
separately
3TX7462-3.
1) 2)
The connection piece for mounting the surge suppressor must be bent Includes the peak value of the alternating voltage on the DC side.
slightly. 3)
Not for DC economy circuit.
3TX65.6-3B
Size Type NO NC d
Auxiliary switch blocks
For lateral mounting
2 and 4 3TC44, Auxiliary switch 1 1 13 21 31 43 20 3TY6501-1AA00 1 1 unit 41B
3TC48 block
(replacement for
3TY6 501-1A/-1B) 14 22 32 44
4
14 22
3TY6561-1A Auxiliary switch 1 1 -- 31 43 20 3TY6561-1B 1 1 unit 41B
block, right
32 44
12 3TC74 Auxiliary switch 4 4 13 21 31 43 53 61 71 83 2 3TY2741-2J 1 1 unit 41B
block
14 22 32 44 54 62 72 84
54 62 72 84
For contactors Version Rated control supply SD Article No. Price PU PS* PG
voltage Us per PU (UNIT,
SET,
Size Type V AC/DC d M)
Surge suppressors Varistors
12 3TC7 For sticking onto the 24 15 3TX2746-2F 1 1 unit 41B
contactor base 110 10 3TX2746-2G 1 1 unit 41B
3TY2482-0A
1)
For rated control supply voltages, see page 4/82. The 10th and 11th digits
of the article number must be supplemented accordingly.