You are on page 1of 78

s

DESIGO™ PX
Mounting and installation guide
Version 2.1 and higher

CA110396en_03
31 Jan 2009 Building Technologies
Table of Contents

1 Introduction ...................................................................................................4
1.1 Revision history ..............................................................................................4
1.2 About this document .......................................................................................5
1.3 Supplementary documentation .......................................................................5
1.4 What this document describes........................................................................6

2 Safety guidelines ..........................................................................................8


2.1 System-specific regulations ............................................................................8
2.2 Device-specific regulations ...........................................................................10

3 The devices .................................................................................................11


3.1 PXC....D automation stations ("compact" series).........................................12
3.2 PXC... automation stations ("compact" series) .............................................13
3.3 PXC....D automation stations ("modular" series) .........................................15
3.4 PXC...-U automation stations ("modular" series) ..........................................18
3.5 PXM… operator units....................................................................................20
3.6 PXR system controllers.................................................................................21
3.7 PXE-CRS system controller..........................................................................22
3.8 PXG80-W and PXG80-WN web controllers..................................................23
3.9 PXG80-N BACnet router...............................................................................24

4 The control panel ........................................................................................25


4.1 Control panel requirements ..........................................................................25
4.2 Mounting methods ........................................................................................26
4.2.1 Compact automation stations, system controllers,
Web controllers and routers..........................................................................26
4.2.2 Modular automation stations PXC...-U .........................................................27
4.2.3 Modular automation stations PXC00-100-200....D .......................................27
4.2.4 PXM… operator units....................................................................................28
4.3 Overall control panel layout ..........................................................................29

5 Mounting instructions ................................................................................30


5.1 Additional information ...................................................................................30
5.2 Compact automation stations, system controllers,
Web interfaces and routers...........................................................................31
5.2.1 DIN rail mounting ..........................................................................................31
5.2.2 Wall mounting ...............................................................................................31
5.3 Modular automation stations.........................................................................32
5.3.1 DIN rail mounting PXC00-100-200....D.........................................................32
5.3.2 Mounting in the control panel door PXC...-U ................................................32
5.3.3 Wall mounting PXC...-U ................................................................................33
5.4 PXM… Operator units...................................................................................35
5.4.1 Mounting in the control panel door ...............................................................35
5.4.2 DIN rail mounting ..........................................................................................35
5.4.3 Direct mounting on modular automation station ...........................................36

6 Wiring...........................................................................................................37
6.1 Additional safety guidelines ..........................................................................37
6.2 AC 24 V supply cables..................................................................................38
6.2.1 Basic wiring for compact-series automation stations (excluding PXC10-TL)38
6.2.2 PXR, PXE, PXG80-W, PXG80-WN, PXG80-N .............................................39
6.2.3 Basic wiring for modular automation stations ...............................................39
6.2.4 Cables...........................................................................................................40
6.3 AC 230 V supply cables for PXC10-TL.........................................................41

2/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Table of Contents 31 Jan 2009
6.4 signal and PPS2 cables................................................................................ 42
6.4.1 Measured value input (LG-Ni 1000 sensors)................................................ 42
6.4.2 Signal inputs ................................................................................................. 42
6.4.3 Room unit (PPS2)......................................................................................... 42
6.5 Data cables (for modem and tool) ................................................................ 43
6.5.1 COM1 / COM2 (RS232) ............................................................................... 43
6.5.2 RS485........................................................................................................... 43
6.5.3 RJ45 (Tool, and operator unit)...................................................................... 43
6.6 LONWORKS bus cable ................................................................................... 44
6.7 Lightning and overvoltage protection for the LONWORKS bus....................... 44

7 LONWORKS network: Principles ................................................................. 48


7.1 Specification ................................................................................................. 48
7.2 Basic topological structure............................................................................ 49
7.3 Free topology................................................................................................ 50
7.4 Line topology ................................................................................................ 51
7.5 LONWORKS accessories................................................................................ 52
7.5.1 Bus terminators ............................................................................................ 52
7.5.2 Physical repeaters ........................................................................................ 52

8 Ethernet networks ...................................................................................... 53

9 Telephone networks (remote management) ............................................ 54

10 Connection diagrams................................................................................. 55
10.1 Compact automation stations, AC 24 V ....................................................... 55
10.1.1 Connecting the field devices for PXC12, 12-T, 22, 22-T, 36, 36-S, 52........ 60
10.1.2 Connecting the field devices for PXC....D .................................................... 62
10.1.3 Connecting the room units............................................................................ 64
10.2 PXC10-TL automation station, AC 230 V ..................................................... 65
10.2.1 Connecting the field devices......................................................................... 66
10.2.2 Connecting the room units............................................................................ 66
10.3 Automation stations ("modular") series ........................................................ 67
10.4 PXR… system controllers............................................................................. 69
10.5 PXE-CRS system controller ......................................................................... 69
10.6 Web controllers PXG80-W and PXG80-WN................................................. 70
10.7 PXG80-N BACnet router .............................................................................. 70

11 Disposal....................................................................................................... 71

12 Dimensions ................................................................................................. 72
12.1 Automation stations (compact series), system controllers, Web controllers
and routers ................................................................................................... 72
12.2 Automation station PXC10-TL (AC 230 V) ................................................... 74
12.3 Automation stations, "modular" series.......................................................... 75
12.4 PXM… operator units ................................................................................... 77

3/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Table of Contents 31 Jan 2009
1 Introduction
1.1 Revision history

Preliminary remark This document is supplemented by the following document:


M8102E "Installation guide, DESIGO I/O module system" [1]

Reason The I/O modules can be used for the DESIGO, UNIGYR and VISONIK systems.
For this reason they are described in a separate document applicable to all three
ranges.

Document changes Section


First edition Complete manual
Revision for V2.1 • Addition of PXR, PXE, PXG80-W,
(08.2002) PXR80-WN, PXG80-N (3.4, 10 and 12)
• PPS2 signal cables (6.3)
• Data cables (6.4)
• LONWORKS bus specifications (7.1)
• Topologies with repeaters (7.2, 7.3)
• Ethernet (8)
• Telephone networks (9)
Revision for V2.2 • New document number CA110396
(05.2003) • Addition of PXC10-TL
• Telephone networks (9)
• Serial topology Æ line topology
• MMI Æ HMI
• Elimination of Landis & Staefa (drawings)
Correction 09.2003 • Pin numbers of "null modem" cable (page 43)
Corrections 11.2003 • Extension modules PXA11 and PXA20-T removed and
replaced by PXA30-T (pages 15 and 65)
• Note concerning Ethernet networks (chapter 8):
The planned Ethernet manual has been canceled.
Instead, refer to chapters 3 and 16 in the DESIGO
Technical principles manual [4].
Corrections V2.3 • Added PXM10 Local operator unit
(20.09.2004) • Added PXA30-K11 Extension module
• Reference to technical principles manual V2.3
(CM110523) instead of V2.2 (CA110393)
Corrections V2.35 • Added PXM20-E operator unit for Ethernet, including
(23.09.2005) mounting hints on page 36
• Added extension modules PXA30…
• List of supplementary documents (1.3)
• Several small corrections
Corrections V2.36 • Added automation stations PXC12-E.D and PXC22-E.D
(31.07.2006) • Added extension modules PXA30-RS and PXA30-W0
• Replaced LON by LONWORKS
• Several small corrections
Corrections V2.37 • Added automation stations PXC..- D PXC..-T.D and
(30. 03.2007) PXC..-E.D
• Added extension modules PXA30-RS1 and PXA30-RS2
• Added notes and reference documents concerning TX-I/O
modules
• LonWorks bus installation and lightning protection
(Sections 6.6 and 6.7), and principles (Section 7)
• Several small corrections
Corrections V4 • Added automation stations PXC….D and PXC…-E.D as
(31 Jan 2009) well as option modules PXA40-…
• Several small corrections

4/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Introduction 31 Jan 2009
1.2 About this document

Main target groups The mounting and installation guide is aimed at the following groups:
Control panel engineers
Electricians

Purpose The mounting and installation guide contains the following information for the target
groups referred to above:
Correct installation and wiring of the automation stations in the DESIGO PX system and
of the PXM… operator units. This applies both to the control panel wiring and the
connection to the plant.
To ensure an overall understanding of the system, this guide also provides an overview
of the automation station range and its structure.

Further use The mounting and installation guide is also useful for in-house project engineers at
Siemens Building Automation or in systems houses, especially in relation to the
following:
Various options for installing the automation stations
Regulations and notes

Scope The mounting and installation guide contains all the necessary information in text and
illustrations for the target groups referred to above and for the purposes described.
However, it does not contain information on plant-specific installation and wiring, which
can be found in the relevant project documents.

1.3 Supplementary documentation

[1] CM2M8102 Mounting and installation guide DESIGO I/O-Module


Information applicable to the DESIGO PX devices is not
repeated in the present guide if it also appears in document
M8102E on the DESIGO I/O module system.
You will find an appropriate reference in the relevant
sections, e.g. 4.1, "Control panel requirements".
[2] CM2Z8102 Technical principles I/O module system
[3] CM110664 DESIGO Technical principles V2.35 and higher
[4] CM110523 DESIGO Technical principles V2.3
[5] CA110335d LON networks Checklist
[6] CM110666 Ethernet, TCP/IP and BACnet on Ethernet/IP Principles
[7] CM2N8170 TX-I/O™ Assortment overview
[8] CM2N8172 ff Data sheets of the TX-I/O™ modules
[9] CM2N8183 Data sheet TX-I/O™ Power supply module and
bus connection module
[10] CM110561 TX-I/O™ Functions and operation
[11] CM110562 TX-I/O™ Engineering and installation guide
[12] CM2N8180 Data sheet P-bus interface module
[13] CM110641 ff TX-I/O™ Engineering documentation V2.37
[14] CM110641 ff TX-I/O™ Engineering documentation V4

5/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Introduction 31 Jan 2009
1.4 What this document describes

Overview The hardware for the DESIGO PX building automation and control system covers the
following categories:
Automation stations, system controllers, Web controllers, routers and operator units
Control panel
Cable connections

Hardware categories
Telephone network
Ethernet

10396Z07en_01
Control panel
BACnet
Router
Modem
DESIGO INSIGHT PXG80-N PXG80-W(N) Modem Web browser
PXM20 PXM20-E
Operator units Router Web controller
LONWORKS bus

PXX-L11
Automation stations
PXX-L12 TXS1.12F10 TXI1.OPEN
PXM10

PPS2
QAX... Modem Modem Modem
PXC...-U PXC...(-T) PXC10-TL PXC12...D PXC00...D PXC100...D TXM1.....
P-Bus PXC22...D PXC200...D TX-I/O modules
PXC36...D PXA40-...
3rd
LONWORKS Party
Wiring to the
bus bus
field devices

Building T T T T T T
services
plant RXC... (see 3rd party
document device /
110334) System

The following is a brief description of the categories shown above:

Category Brief description


Control panel The following equipment is installed in the control panel:
– DESIGO PX automation stations (compact and modular series)
– For DESIGO PX modular: I/O modules, connected via the P
bus to the automation stations
– PXM… operator units
– System controllers, type PXR (for integration of the room level)
and type PXE (for integration of third-party devices and
systems)
– PXG80-W and PXG80-WN Web controllers
– PXG80-N BACnet router
This document describes the correct procedures for the
installation and wiring of the automation stations and the
operator unit in the control panel.
Technical This refers to the connected plant, e.g.: heating, ventilation, air
equipment conditioning, electrical plant etc.
Operator unit An PXM… operator unit allows the building operator to monitor
and control the technical equipment.

6/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Introduction 31 Jan 2009
Connections The following connections are generally provided to and from the control panel:
• Local Operating Network (LONWORKS):
A bus cable is used to connect the automation stations with each other, and to
connect the PXR system controller to the RXC room controllers.
• P bus / island bus (DESIGO PX modular only):
A bus cable is routed from the modular automation stations to the I/O modules.
• Wiring to field devices (sensors, control valves, motors, etc.).
• Data cables:
COM-ports to modems or printers; Ethernet
• Telephone lines (if modem is in control panel)
• Ethernet

Housing types This document describes the DESIGO PX devices listed below.
Construction is described in Section 5, "Mounting instructions".

Types Devices Main features for mounting


Modular series PXC100.D Modular automation stations – DIN rail mounting
PXC100-E.D – Right side: island bus
PXC200.D connector
PXC200-E.D – Left side: Connector for
PXC00.D System controllers PXX… extension modules
PXC00-E.D – On top: Interface for PXA40-
… option modules
– Housing with plug-in screw
terminal blocks
Modular series PXC64-U Modular automation stations – Control panel door mounting
PXC128-U – Wall mounting
PXC00-U System controller – Housing with plug-in screw
terminal blocks
– Plug-in unit with two slots for
extension modules
Compact series PXC.. , Compact automation stations – DIN rail mounting
PXC….D – Wall mounting
– Housing with plug-in screw
PXR... System controllers (for
terminal blocks
integration of the room level)

PXE-CRS System controller (integration of


third-party devices and systems)

PXG80-W, Web controllers


PXG80-WN

PXG80-N BACnet router

Operator units PXM10, Operator units – Control panel door mounting


PXM20, – DIN rail mounting
PXM20-E – Can be mounted on modular
automation stations

7/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Introduction 31 Jan 2009
2 Safety guidelines

Take careful note This section contains general and system-specific regulations. It includes important
of this information information for your own safety and for the safety of the entire system.

..Safety notice In this document, any regulations or instructions preceded by the warning triangle
shown here must be strictly adhered to. Failure to do so will endanger the safety of
people and property.

. General regulations Please observe the following general regulations applicable to planners and project
engineers:
Electricity and high-voltage power regulations of the country concerned
Other applicable country-specific regulations
Electrical installation regulations for the relevant country
Regulations of the power supply company
General schematics, wiring schedules, plans, specifications and requirements of the
customer or the relevant engineering company.
Third-party regulations, for example as specified by general contractors or building
owners.

2.1 System-specific regulations

Safety The electrical safety of Siemens building automation and control systems is primarily
based on the use of extra-low voltage which is strictly segregated from the mains
voltage.

SELV, PELV Depending on the earthing of this extra-low voltage, either SELV or PELV is used, in
accordance with HD 384 "Electrical systems in buildings":
Unearthed = SELV (Safety Extra Low Voltage)
Earthed = PELV (Protection by Extra Low Voltage)

. Equipment safety Equipment safety is ensured by measures which include the following:
– AC 24 V extra-low voltage supply (SELV or PELV)
– Double isolation between AC 230 V mains voltage and SELV/PELV circuits and
housings
Always observe the specific regulations for electrical wiring as described in the
following sections.

. Earthing of G0 The following points are important in relation to the earthing of G0:
(system neutral) • In principle, G0 of the AC 24 V operating voltage may be either earthed or unearthed.
• The deciding factors are local regulations and common practice.
• There may also be functional reasons which make earthing either essential or
unacceptable.
Recommendation for the • AC 24 V systems should generally be earthed unless this contradicts the
earthing of G0 manufacturer's guidelines.
• To avoid earth loops, ensure that systems with PELV are connected to earth at one
point only in the system, usually at the transformer (unless otherwise stated).
• Earth loops can also be avoided by using electrically isolated connections to PC
interfaces (PC tools).

8/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Safety guidelines 31 Jan 2009
. Mains and The following regulations apply to mains and operating voltage:
operating voltage
Description Regulations
AC230V operating The supply must conform to PELV requirements. Acceptable
voltage deviation of AC 230 V rated voltage at device: +/-10 %
(PXC10-TL only)
AC 24 V operating The supply must conform to SELV or PELV requirements.
voltage Acceptable deviation of AC 24 V rated voltage at device:
+/-20 %
Specification for • Safety isolating transformer to EN 61558, with double
AC 24 V isolation, designed for continuous operation, for the supply
transformers of SELV or PELV circuits.
• For reasons of power efficiency the power drawn from the
transformer should be at least 50 % of the nominal load.
• The transformer rating must be at least 25 VA. Smaller
transformers have an unfavorable ratio between no-load
voltage and full-load voltage (> + 20 %).
Protection of the Transformers must be fused on the secondary side, in
AC 24 V operating accordance with the effective load of all the connected devices
voltage based on the transformer size:
– Conductor G (system potential) must always be fused.
– Where specified, conductor G0 (system neutral) must also
be fused.
Mains voltage Transformers must be fused on the primary side:
protection Control panel protection (control circuit protection)

. Beware of inter- Any introduction or transfer of dangerous voltages to the system's extra-low voltage
ference voltages circuits (for example due to incorrect wiring) endangers people and property directly,
and can lead to partial or complete destruction of the building automation and control
system.

. Lightning protection All cables leaving the building are highly vulnerable to overvoltages from atmospheric
discharge (lightning). These overvoltages are linked inductively, capacitively or electri-
cally to electronic systems and can cause interference and damage to sensitive com-
ponents.

Overvoltages of this kind must be dissipated to earth and so rendered harmless. This
can be achieved with the help of gas-filled overvoltage discharge devices, varistors,
diodes and capacitors and inductors.

For optimum protection, specialist companies such as Siemens or Phoenix use various
combinations of these devices to create special protection modules.

Mains filters High-frequency interference or brief power transients may occur in the supply cables in
areas with high-density emitted interference. This interference affects not only trans-
formers on the primary side but also components connected to the secondary side.

If interference of this kind is anticipated, a mains filter must be fitted on the transformer
primary side. Mains filters must be installed as closely as possible to the mains
transformers and earthed.

9/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Safety guidelines 31 Jan 2009
Interference The switching of inductive loads causes power transients which introduce interference
suppression of power into the system. In addition, sparking can cause damage to the switch contacts. In
components order to prevent such interference all power components must be equipped with an
efficient means of interference protection. Transzorbers, MOVs (metal oxide varistors)
or RC elements must be connected directly to the terminals of inductive devices such
as transformers, contactors, relays. The breakdown voltage of the transzorbers or
MOVs must be between 1.7 times and twice the relevant rated voltage.

Diodes or RC elements can be used for interference suppression for inductive direct-
current devices.

The transzorbers, MOVs, diodes and RC elements must be properly matched to the
power components concerned, and connected with short wires.

2.2 Device-specific regulations

. Connection of field devices

Devices with different The voltage circuits of these devices must be adequately isolated from each other, to
voltage circuits allow direct connection without the need for additional isolation.

Interfaces for different Connections via interfaces carry with them the intrinsic risk that dangerous voltages
voltage circuits can be distributed across the building. In all cases, you must ensure that the necessary
isolation is provided and that all the relevant installation regulations have been
observed.

10/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Safety guidelines 31 Jan 2009
3 The devices
Aim of this section The following provides an overview of the DESIGO PX devices and introduces you to
the main features of these devices.

Simple example The following is a schematic diagram of a modular automation station in the control
panel and shows the connections to the field devices.

Control panel

LonWorks
T1
Ethernet
AC 24 V

N1 U1 U2

Island bus

U3 U4

10396Z08en
M1 M2 M3

Key T1 Transformer AC 230 V / AC 24 V


N1 Automation station
U1 Power supply module
U2 I/O row with outgoing connections to devices located inside the control
panel
U3 Bus connection module
U4 I/O row with connections to the external field devices
M1 Heating coil pump
M2, M3 Supply air fan, extract air fan

11/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.1 PXC....D automation stations
("compact" series)

Basic design The compact-series automation stations feature a plastic housing which accommodates
all the electronics and the screw terminal blocks.
These devices are either wall-mounted in the control panel or mounted on DIN rails

Types Communications
BACnet / LonTalk PXC12.D PXC22.D PXC36.D
BACnet / LonTalk and BACnet / PXC12-T.D PXC22-T.D PXC36-T.D
PTP (point to point) (from V2.37)
BACnet / IP PXC12-E.D PXC22-E.D PXC36-E.D
Total number of inputs / outputs 12 22 36
Number of universal inputs (UI) 4 12 18
Number of digital inputs (DI) 2 - 4
Number of analog outputs (AO) 4 4 6
Number of relay outputs (DO) 2 6 8

Construction 3 4 9 10

6 7
DO1 DO2 DO3 DO4 DO5 DO6

RUN
2 FAULT
11
LOW BATT
COM
INFO
SERVICE
1 12

9215Z03
5 15 14 13
1 Plastic housing
2 Front cover
3 Plug-in screw terminal block (operating voltage)
4 Plug-in screw terminal block (relays)
5 Plug-in screw terminal block (inputs, outputs)
6 LED indicators for relay outputs
7 LED indicators for device and system status
8 Service pin (Network identification)
9 Plug-in screw terminal block (LONWORKS bus,
PXC….D and PXC…-T.D only)
10 Network interface RJ45 (BACnet / IP, PXC…-E.D only)
11 USB device interface (for future use)
12 RJ45 Interface for operator unit and tool (RJ45, PXC….D and PXC…-T.D only)
13 RJ45 interface for operator unit
14 USB host interface (modem, PXC…-T.D only)
15 Plug-in screw terminal block (room units)

12/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.2 PXC... automation stations ("compact" series)

Basic design The compact-series automation stations feature a metal housing which accommodates
all the electronics and the screw terminal blocks.
These devices are either wall-mounted in the control panel or mounted on DIN rails
The PXC10-TL automation station is optimized for direct wall mounting and is equipped
with a AC 230 V power supply.

Types Automation station Description


PXC10-TL Automation station for 10 physical data points
PXC12, PXC12-T *) Automation station for 12 physical data points
PXC22, PXC22-T *) Automation station for 22 physical data points
PXC36 *) Automation station for 36 physical data points
PXC36-S As PXC36, but with four manual switches
PXC52 Automation station for 52 physical data points

*) replaced by types PXC....D (see 3.1)

Construction 5

00319 b

3
1

1 Metal housing
2 Front cover
3 LED indicators
4 Printed circuit board
5 Plug-in screw terminal block
6 Upper terminals for operating voltage, bus system and input peripherals
7 Lower terminals for output peripherals

13/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
PXC10-TL (with integrated
AC 230 V supply) 01881
2 1

3 4

1 Plastic housing
2 Front cover
3 LED displays
4 Terminals for operating voltage, bus systems, as well as input and output
peripherals

14/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.3 PXC....D automation stations
("modular" series)

Basic design The compact construction enables the automation stations to be mounted on a
standard mounting rail.

Island bus devices can be positioned on the standard rail directly aside the automation
stations. The island bus is self-building.

Automation stations
for connection of TX-I/O-modules via island bus

Up to 200 data points Over 200 data points


Automation station BACnet / LonTalk PXC100.D PXC200.D
Automation station BACnet / IP PXC100-E.D PXC200-E.D

System controllers
for integration via extension modules PXX...

System controller BACnet / LonTalk PXC00.D


System controller BACnet / IP PXC00-E.D

Extension module LONWORKS


for integration of DESIGO RXC and LonMark compatible 3rd party devices (together with PXC00….D)
Type Data sheet
Integration of max. 60 devices PXX-L11 CM1N9282
Integration of max. 120 devices PXX-L12

15/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
Option module for Automation stations and system controllers PXC00 / 100 / 200.D (BACnet/LonTalk)
The option module can be mounted in place of the front cover.

T
Module PXA40-...
Interfaces
USB Host (for modem via PXA-C3) X
Network functions
PTP Dial-in XWP (modem) 1) X

Option module for Automation stations and system controllers PXC00 / 100 / 200-E.D (BACnet/IP)
The option module can be mounted in place of the front cover.

Module W0 W1 W2 T
PXA40-...
Interfaces
Ethernet RJ45 X X X
USB Host (für Modem via PXA-C3) X X X X
Remote management
PTP Dial-in DESIGO INSIGHT (Modem) X X X X
1)

PPP via Ethernet RJ45 1) X X X


Web functions
Generic Web functions X 2) X X
Graphic Web functions X 2) X
Send alarms via SMS (Modem) X X X
Send alarms via E-Mail (RJ45) X X X

1)
The modem connection can be configured as follows:
– either for Remote Management (XWP)
– or for Remote Management PX WEB generic / graphical and alarming with SMS.
2)
Web functions for one automation station only

16/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
Mechanical design

PXC....D 4 5 5 5
8 8

6
3

2 7

9222z01
5 8

PXA40-...

9222z16
1 Plastic housing
2 Cover to interface for extension module
3a Front cover
3b PXM40-... option module
4 Plug-in terminal block with screw terminals (operating voltage)
5 Interface for network, operator units, tool, etc.
6 LED display for devices and system status
7 Island bus connector (not on PXC00…)
8 Slider for mounting on DIN rail

17/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.4 PXC...-U automation stations
("modular" series)

Basic design The modular-series automation stations consist of the device base, and a plug-in unit,
with slots for optional plug-in modules.
They are suitable for wall-mounting in the control panel or can be mounted in the
control-panel door.

Types Automation Description


station
PXC64-U Automation station with P bus for I/O modules, up to 64 load units
PXC128-U Automation station with P bus for I/O modules, up to 128 load units
PXC00-U System controller fort he integration via PXA30-K11 or PXA30-RS;
without P-Bus interface
PXA30-T Extension module for serial communications (modem)
PXA30-N Extension module for BACnet / IP
PXA30-NT Extension module for BACnet / IP und Modem
PXA30-W0 Extension module for WEB (generic, for one automation station)
PXA30-W1 Extension module for WEB (generic)
PXA30-W2 Extension module for WEB (graphic)
PXA30-K11 Extension module for the integration of KNX / EIB
PXA30-RS Extension module for the integration of M-Bus and Modbus
PXA30-RS1 100 / 400 / 1000 data points
PXA30-RS2

Load units The "load units" allow the project engineer to calculate the maximum number of I/O
modules which can be connected to the automation station.

18/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
Construction 6 7 8
00255a

4
1
5

1 Plug-in unit
2 Front cover (a PXM… operator unit can be fitted instead of the front cover)
3 Battery
4/5 Extension modules
6 Device base
7 Plug-in connection for automation station for device supply and bus
electronics
8 Housing with pcb for device supply
9 Plug-in terminal blocks with reversible support bracket (here used for wall
mounting)

19/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.5 PXM… operator units

Basic design The PXM… operator units feature a plastic housing with an integrated processor and
LCD display.
They are suitable for mounting in a control panel door, wall-mounting in the control
panel or mounting on DIN rails. The operator units can also be snap-mounted on any
modular automation station.

Types Operator unit Description


PXM10 Local operator unit
PXM20 Operator unit for BACnet / LonTalk
PXM20-E Operator unit for Ethernet

Construction 1
00320 F

4 3

1 Plastic housing
2 LCD display
3 Spring mechanism for mounting on DIN rails
4/5 RJ45 socket

20/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.6 PXR system controllers

Basic design The PXR… system controllers are used to integrate the DESIGO RXC room controller
range into the DESIGO building automation and control system.
The system controllers have a metal housing which accommodates all the electronics
and the screw terminal blocks.
These devices are either wall-mounted in the control panel or mounted on DIN rails.

Types System Description


controllers
PXR11 System controller suitable for the integration of 60 RXC devices
PXR12 System controller suitable for the integration of 120 RXC devices

Construction 5
01451

1
3

2 4

1 Metal housing
2 Front cover
3 LED indicators
4 Printed circuit board
5 Upper connection terminals for Operating voltage, HMI / Tool, BACnet, Modem
6 Lower connection terminals for Tool, LONWORKS
7 Clip for mounting on DIN rail

21/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.7 PXE-CRS system controller

Basic design The PXE-CRS system controller is used to integrate third-party equipment and systems
into the DESIGO building automation and control system.
The system controller has a metal housing which accommodates all the electronics and
the screw terminal blocks.
The device is suitable for wall-mounting in the control panel or mounting on DIN rails.

Types System controller Description


PXE-CRS System controller (hardware platform)

Housing 5
01471

1
3

2 4

1 Metal housing
2 Front cover
3 LED indicators
4 Printed circuit board
5 Upper connection terminals for Operating voltage, HMI / Tool, LONWORKS,
Modem
6 Lower connection terminals for Third party (COM1): RS232 or RS485
7 Clip for mounting on DIN rail

22/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.8 PXG80-W and PXG80-WN web controllers

Basic design The PXG80-W and PXG80-WN Web controllers are designed for remote display and
operation of one or more DESIGO PX automation stations with a standard Internet
browser.
The system controllers have a metal housing which accommodates all the electronics
and the screw terminal blocks.
The device is suitable for wall-mounting in the control panel or mounting on DIN rails.

Types System controller Description


PXG80-W Web controller for modem connection
PXG80-WN Web controller with Ethernet / Intranet connection

Housing 5
01541

1
3

2 4

1 Metal housing
2 Front cover
3 LED indicators
4 Printed circuit board
5 Upper connection terminals for Operating voltage, Modem, Ethernet (PXG80-
WN only)
6 Lower connection terminals for HMI / Tool, LONWORKS, Modem
7 Clip for mounting on DIN rail

23/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
3.9 PXG80-N BACnet router

Basic design The BACnet router is used wherever PX automation stations are required to
communicate via Ethernet/IP.
The automation stations are interconnected via LONWORKS, and form a network
segment. Local LONWORKS networks are connected via Ethernet/IP (backbone). A
BACnet router is required for each LONWORKS network.
The controller has a metal housing which accommodates all the electronics and the
screw terminal blocks.
The device is suitable for wall-mounting in the control panel or mounting on DIN rails.

Types System controller Description


PXG80-N BACnet router for LONWORKS – Ethernet/IP

Housing
5
00405

1
3

2 4

1 Metal housing
2 Front cover
3 LED indicators
4 Printed circuit board
5 Upper connection terminals for Operating voltage, Ethernet
6 Lower connection terminals for HMI / Tool, LONWORKS
7 Clip for mounting on DIN rail

24/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The devices 31 Jan 2009
4 The control panel
Topics in this section This section contains information about:
• Control panel requirements
• Options for mounting the DESIGO PX devices
• Complete layout of control panel

4.1 Control panel requirements

Take careful note For the engineering and implementation of the control panel it is essential to read the
of this information relevant sections in the mounting and installation guide, manual M8102E for DESIGO
I/O modules [1], namely Section 4.1 about the control panel requirements and 4.2 on
EMC-compliant control panels.

Space requirements When mounting units in the control panel, note the following:
– Mounting depth
– Ensure sufficient clearance from the cable trunking, so that the screw terminal blocks
can be plugged in and removed without difficulty after the automation stations have
been mounted.
– The automation stations can be mounted directly adjacent to each other. However,
to allow easy access to the cover, it is advisable to allow approximately 2 cm
clearance between devices.
– Reserve enough free space for later expansion.

Orientation In principle, the devices can be mounted either horizontally or vertically. However, for
technical reasons associated with the control panel, horizontal mounting is
recommended.

25/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The control panel 31 Jan 2009
4.2 Mounting methods
4.2.1 Compact automation stations, system controllers,
Web controllers and routers

These devices are suitable for the following methods of mounting in the control panel:
• DIN rail mounting
• Wall mounting

Mounting methods DIN rail mounting Wall mounting


00330 A

00329

10396Z01

10396Z02
• The PXC10-TL automation station is also designed for Mounting in a control
panel door:

Mounting in a control panel door DIN rail mounting Wall mounting


01879

26/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The control panel 31 Jan 2009
4.2.2 Modular automation stations PXC...-U

The modular automation stations are suitable for the following two methods of control
panel mounting:
• Mounting in control panel door
• Wall mounting

Mounting methods Mounting in control panel door Wall mounting

00234 00235

4.2.3 Modular automation stations PXC00-100-200....D

The modular automation stations are suitable for mounting on standard mounting rails

Mounting on standard rail


10396z12
(PXA40-...)

35.5
96

70 4
81 (PXA40-...)

27/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The control panel 31 Jan 2009
4.2.4 PXM… operator units

The operator units are suitable for the following methods of control panel mounting:
• Mounting in control panel door
• DIN rail mounting
• Direct mounting on modular automation station

Mounting methods Mounting in control panel door DIN rail mounting


00331

00332

Mounting on modular-series
automation station
00333

Note Mounting a PXM20-E on a PXC…-U


PXM20-E, mounted on a PXC…U, which
is mounted in the control panel door:
Requires an additional hole in the panel
door for the Ethernet cable, see page 36

28/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies The control panel 31 Jan 2009
4.3 Overall control panel layout

General layout The following diagram shows a simple control panel with a PXC...-U.
It serves as a general example of how to arrange the modules and devices efficiently.

Control panel Door


00321

1 2

3 4

230V~ 24V~

5 6

Modules in door • Modular automation station: Installation in door (view from the back)
• Left-hand terminal block: Connection of AC 24 V operating voltage (top) and
P bus (bottom)
• Right-hand terminal block: Connection of communication module

Modules inside the 1 Terminal strip for power section


control panel 2 I/O module groups with direct connections from mains and extra low voltage to
field devices (control)
3 Fuses and isolating elements
4 I/O module groups with direct connections from mains and extra low voltage to
devices inside the control panel (control)
5 Mains voltage area with relays and contactors
6 Transformer AC 230/24 V for control section

29/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies The control panel 31 Jan 2009
5 Mounting instructions
Topics in this section • Additional information
• Mounting instructions for the installation of the DESIGO PX devices in the control
panel door and for wall mounting (in the control panel).

5.1 Additional information

Relevant The information in the following documents must be observed when mounting devices
documents in the control panel:
1. This mounting and installation guide
2. All project-specific documentation
In addition to the control panel wiring diagrams, these documents also include a
detailed drawing showing the layout of the equipment in the control panel.

Important The project-specific implementation documents must not contradict the basic rules and
instructions contained in this guide.

Before mounting Please note the information and instructions in the following sections:
Section 4.1 "Control panel requirements"
Section 6.1 "Additional safety guidelines"
Section 12 "Dimensions"
(especially in relation to the amount of spacing required)

After mounting Label the automation stations with separate labels in a suitable position and taking
account of how the automation stations are mounted (in the control panel door or on
the control panel wall).

30/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
5.2 Compact automation stations, system
controllers, Web interfaces and routers
5.2.1 DIN rail mounting

Mounting the device

1 2 1 2
00346a

10396Z04
1

2
1 2

The device is snap-mounted directly onto the rail system.

5.2.2 Wall mounting

Raising the lugs Mounting the device


00344a

00345

Raise the top left and bottom right Drill screw holes for the lugs, as in the dimen-
lugs and position them vertically sions diagram on page 75) and secure the
(e.g. with a screwdriver). device with two screws to the control panel wall.

Mounting the device


10396Z03

31/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
5.3 Modular automation stations
5.3.1 DIN rail mounting PXC00-100-200....D

Mounting the device

1 2 1 2

10396Z11
1 2
The device is snap-mounted directly onto the rail system.

5.3.2 Mounting in the control panel door PXC...-U

Removing the plug-in unit Mounting the housing Mounting the plug-in unit
00200 00201

1 3
8221J02

7 5
4

2
6

Remove the plug-in unit from Push housing into the housing cut-out Push the unit into the housing and
housing. prepared in accordance with the secure with the two screws supplied.
dimensions diagram.
Cut-outs for connectors to
communication cards: break out as
required.

32/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
5.3.3 Wall mounting PXC...-U

Removing the plug-in unit

00200

Remove the plug-in unit from the


housing.

Preparing the housing


00209 00210

3 4

2 4

Remove the plug-in screw terminal Swivel the mounting brackets to the
blocks from the housing. back.

Mounting the housing


00211

00212

5'
6

Screw housing to the wall. Re-insert terminal blocks.

33/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
Inserting the plug-in unit

00202

11 9
8

10

11

Push the unit into the housing and secure with the
two screws supplied.

During commissioning Preparing the battery ready for use

00253 2 00254

3
1

Do not remove the insulating strip from the battery until


shortly before commissioning.

34/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
5.4 PXM… Operator units
5.4.1 Mounting in the control panel door

Mounting the unit


00132 G

A drilling and cut-out template is included in the packaging.


After the cut-out has been made, install the operator unit and
secure it with the two screws supplied.

5.4.2 DIN rail mounting

Mounting the unit Removing the unit

1 2
00129 K 00130 F

The operator unit is snap-mounted To remove the operator unit, release the
directly onto the rail system. spring mechanism at the back of the
operator unit (e.g. with screwdriver).

35/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
5.4.3 Direct mounting on modular automation station

Removing the front cover of the automation station


00131

First remove the front cover of the modular automation station.

Mounting the operator unit


00128 F

Install the operator unit in the opening of the automation station


and secure it to the automation station with the two screws
supplied.
The plug-in connection ensures automatic electrical
connection.

Note Mounting a PXM20-E on a PXC…-U


PXM20-E, mounted on a PXC…U, which is mounted in the control panel door:
This requires an additional hole in the panel door for the Ethernet cable
Connector without bending protection due to the narrow space available!
00131 F

22.5
24
25

138

138

36/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Mounting instructions 31 Jan 2009
6 Wiring
Introduction Before starting the wiring first read "Safety guidelines" in Section 2 and the " Additional
safety guidelines" below.

Topics in this section The following topics are covered:


• Additional safety guidelines
• Wiring the AC 24 V supply cables
• Wiring the bus cable

Note Section 8 of the mounting and installation guide, M8102E [1], for the DESIGO I/O
module system contains information about optimizing EMC and includes examples of
wiring with an AC 24 V supply.

6.1 Additional safety guidelines

Safety notes The following notes are closely related to the information in Section 2.2, "Device-
specific regulations" and therefore require your careful attention.

Cable routing, trunking cross-section


Route the device connections in cable trunking as usual.
Recommendation: When selecting the cable trunking cross-section, allow for a reserve
of at least 20%.

Conductors and All conductor types and cross-sections must comply with the specifications below:
terminals
Description Specification
Cable material Use standard stranded cables and wires. Either connect the
ends directly or reinforce them with connector sleeves or pins.
.Important: If extra-low voltage conductors are routed next
to mains voltage conductors the regulations demand that they
have the same insulation rating as mains voltage conductors.

Device terminals The device terminals are suitable for wires with:
• A minimum diameter of 0.5 mm
• Max. 2 x 1.5 mm2 or 1 x 2.5 mm2

The terminals used are lift-type terminals; the fixed contact plate
between the wire end and the end of the screw protects the wire.
.Important: Always use the original plug-in terminals for
connections.

Tightening torque When using electric screwdrivers for wiring terminals always set the torque to
0.5...0.6 Nm or 50...60 Ncm.

Transformer sizing for Transformer sizing is carried out by the project engineers in accordance with the
AC 24 V information set out in the technical principles manual for the I/O module system,
document Z8102E [2].

37/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.2 AC 24 V supply cables
6.2.1 Basic wiring for compact-series automation stations
(excluding PXC10-TL)

The following diagram shows the basic wiring of the supply cables of compact
automation stations with an AC 24 V operating voltage (PELV):
Connect automation stations and field devices by their terminals (G, G0) in a star
configuration.

The PXC10-TL automation station is equipped with an integrated AC 230 V power


supply (see page 41).
L N 00261D

T AC 230 V

G AC 24 V G0

F1
...A

G G G G0 G0 G0

Field devices

TE G0 G

L N

T
10396Z05

AC 230 V

G AC 24 V G0

F1
...A

G G G G0 G0 G0

Field devices

24V

AO AO UI UI
CP+

CP-

N Compact automation station


T Safety isolating transformer AC 230 V/AC 24 V to EN 61 558
F1 Extra-low voltage fuse for max. power consumption, AC 24 V
G System potential (SP)
G0 System neutral (SN)

Note Use the shortest possible cables between the G0 distribution point and the PXC...
The G0 distribution point is the common point in the star configuration.

38/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.2.2 PXR, PXE, PXG80-W, PXG80-WN, PXG80-N

System controllers, Web controllers and routers also have an AC 24 V supply (max.
power consumption: 6 VA per device).
However, this does not include any field devices.

6.2.3 Basic wiring for modular automation stations

The following diagram shows the basic wiring of the supply cables for modular
automation stations with an AC 24 V operating voltage (PELV):
Connect the automation stations and I/O modules from the terminals (G, G0) in a star
configuration.
L N 00258D

T AC 230 V

G AC 24 V G0

F1
...A

G G0 G G0 G G0 G G0

I/O module bars

N Modular automation station


T Safety isolating transformer AC 230 V/AC 24 V to EN 61 558
F1 Extra-low voltage fuse for max. power consumption at AC 24 V
G System potential (SP)
G0 System neutral (SN)

Note Use the shortest possible cables between the G0 distribution point and the PXC...
The G0 distribution point is the common point in the star configuration.

39/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.2.4 Cables

Cable material The G and G0 cables for the AC 24 V supply voltage should be as follows:
Stranded wire with 1 mm2, 1.5 mm2 or 2.5 mm2 cross-section
Single or in two-core cable

Required cable The following table lists the required cross-sections for different cable lengths, always
cross-sections at max. load, for all automation stations:

Cable length Cross-section


3.5 m 1.0 mm2
5m 1.5 mm2
8m 2.5 mm2

Rules and For rules and recommendations concerning the wiring of the AC 24 V supply cables,
recommendations refer to the mounting and installation guide M8102E for the DESIGO I/O module
system [1]:
Section 8.4 "Wiring of AC 24 V supply cables"
Section 8.5 "Examples of wiring AC 24 V supply cables

Fixing the cables in the The following diagrams show the correct procedure for connecting screened and
control panel unscreened cables to the screen and cable fixing rails in the control panel.
To ensure good connection to the screen, use only standard commercial screen
terminals to ensure good screen connections.

Fixing the cables Fixing the cables in the control panel

Schirmanschluss I/O - Module


Automations-
station
8202Z13D

Trägerschiene

Schirmschiene

Kabelbefestigungs-
schiene

Kabel ungeschirmt
Kabel geschirmt

The screen rail must not be used for cable tension relief.

40/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.3 AC 230 V supply cables for PXC10-TL

The following figure shows the basic wiring of the supply cables for the PXC10-TL
automation station according to PELV:

01880

X21 X22

GND

GND

CP+
CP-
D1

D2
D3

D4
X1

X2
X3

X4
M

M
M M

X23 X24

GND
RXD

24 V
TXD

RTS
CTS

CLA
CLB
Q11
Q14
Q12

Q21
Q24
Q22
N
L

F1
L

TE

N1

N1 Automation station PXC10-TL


F1 AC 230 V fuse
TE Technical earth

Note The unused terminals must not be used (safe clearance to mains voltage)

Lines • Conventional AC 230 V installation as per local safety regulations


• Recommendation: Run 230 V lines separate from 24 V lines
• The supply lines must be fused by means of a cord grip at the automation station.

41/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.4 signal and PPS2 cables

The following applies jointly to the signal cables of field devices such as temperature
sensors, room units or signal inputs.
– Use twisted, 2-core or multi-core round cable without a screen (standard installation
cable)
– Single conductors and ribbon cable must not be used
– Signal conductors may be routed together with mains cables (AC 230 V), but they
MUST be segregated from the mains in accordance with regulations, and in
compliance with SELV requirements.
– Signal conductors must NOT be routed in the same cable as mains conductors.

6.4.1 Measured value input (LG-Ni 1000 sensors)

Additional notes:
– Max. length of single cable: 100 m
– Exception for T1 sensors: 200 m
– Common signal ground is not admissible for LG-Ni1000 and Pt 1000 sensors
(source of measurement errors)
– Recommended cable cross-section: A ≥ 1 mm2

6.4.2 Signal inputs

Additional notes:
– Max. length of single conductor with diameter ∅ ≥ 0.6 mm: 100 m
– Common signal ground may be used for more than one signal input.

6.4.3 Room unit (PPS2)

A maximum of five QAX... room units can be connected via this bus. Each room unit
must have a different address (set by jumper on pcb).

Additional notes:
– Cable type: 2-core, twisted pair, unscreened
– Cores are interchangeable (polarity is irrelevant)
– Auxiliary terminals may be required when connecting several cables
– It is not permissible to connect several conductors in parallel in order to
increase the cable cross-sectional area.

A Diam Max. length of


[mm2] [mm] single cable [m]
1.00 1.15 125
0.75 0.98 115
0.50 0.80 75

42/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.5 Data cables (for modem and tool)
6.5.1 COM1 / COM2 (RS232)

– 9-core standard screened cable


– Max. length 3 m.

STOP Caution! Wiring of "Null modem" cables for connection with DESIGO INSIGHT:
.
Trouble-free operation is only guaranteed if
– the "Null modem" cable is wired according to one of the following schemes
– the flow control of the modem is set to "None" or "Xon / Xoff".

DESIGO PX supports the following "Null modem" cables:

1–4 1–7
2–3 2–3
3–2 3–2
4–1/6 4–6/8
5–5 5–5
6–4 6–4
7–8 7–1
8–7 8–4
9–9 9–9

6.5.2 RS485

– Standard RS bus cable


– Max. length 1,200 m.

6.5.3 RJ45 (Tool, and operator unit)

Refer to " LONWORKS bus" on the next page.

43/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
6.6 LONWORKS bus cable

Electrical safety The LONWORKS installation must be implemented as a safety extra low voltage network
(SELV) in accordance with EN 50090-2-2. Refer also to the data sheets for the
individual DESIGO RXC devices.

A safe distance of at least 10 mm must be maintained between the bus cable and any
mains power and other non-SELV networks.
Exception: Bus cables with an insulation rating of at least 2.5 kV.

Screen connection If shielded cables are used, the shield must be connected to earth as follows:

Rb = Typically 470 kΩ, 1/4 W, ±5%


Cc = Typically 0.1 μF, 10%, metal film capacitor, ≥100V

The capacitive earthing prevents equipotential bonding currents through the cable
shield. Static charges are diverted with a high-level resistor.
The cable shield should be earthed at least once in each segment. In the case of high-
level interference, earthing may be advisable at each node.

Cables routed outside Echelon recommends the use of shielded bus cables for all networks or parts of
the building networks that leave the building.
These cables must be integrated into a lightning protection arrangement.

6.7 Lightning and overvoltage protection for the


LONWORKS bus

Lightning protection • The LONWORKS bus must be included in the protective measures required for
measures power networks
• Planning and installation of lightning protection equipment must be carried
out by qualified staff who are familiar with the relevant safety regulations and
standards

44/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
External lightning External lightning protection comprises lightning arresters, lightning conductors and
protection grounding equipment.
External lightning protection is required for buildings where lightning is likely to occur,
due to the geographical location, type of construction or usage, or where lightning can
cause severe damage. For public buildings and buildings with assembly rooms,
lightning protection is mandatory. The necessity for installing lightning protection
equipment for buildings is governed by national regulations.

Internal lightning Internal lightning protection is based on consistent potential equalization, which means
protection that all metal parts and pieces of metal equipment such as water, heating and gas
pipes, metal panels, etc., must be connected to the equipotential bonding rail.
Internal lightning protection is required in buildings that house overvoltage-sensitive
electronic equipment. This kind of lightning protection comprises measures aimed at
providing protection against the effects of lightning currents and its electrical and
magnetic fields on metal and electrical conductors and equipment.

External
lightning protection

10396z003en
LONWORKS bus cable
(Earthing of screen if screened cable)

AC 230/400 V

Piping

Equipotential bonding rail

Foundation ground

Figure: Lightning protection with potential equalization

Effect of lightning Lightning protection protects bus devices against large and high energy surge voltages
protection that adversely affect bus lines. If protective action is no longer ensured (e.g. because
the permissible number of overvoltage discharges has been exceeded), bus inter-
ference will occur (bus has a small resistance).
Please note that this kind of bus interference does not produce any message.
Damaged lightning protection devices must immediately be replaced.

Planning lightning The standard presently applicable for the installation of lightning protection equipment
protection equipment is DIN VDE 0185 or IEC 1024-1. This standard does not specify whether lightning
protection measures are required for a certain type of building.
If lightning protection is required for a building, active lines (refer to Figure on the
previous page) must be connected to lightning arresters. This is also recommended
when, for example:

45/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
• Power is supplied to the building via low-voltage overhead cables
• Metal items or equipment are attached to the building (e.g. metal stacks or antennas)
• There is another building with lightning protection equipment nearby

Note When planning lightning protection, the lightning arresters must be matched to the type
of overvoltage protection (refer to supplier specifications).

Lightning arresters for Lightning arresters provide multiple discharge of powerful partial lightning currents.
primary protection They are to be installed in the AC 230 / 400 V network and in the LONWORKS network.

AC 230 / 400 V network Lightning arresters (class B) for AC 230 / 400 V networks:
• Nominal discharge current of at least 10 kA (10/350 µs)
• Protective level < 4 kV

LONWORKS network Lightning arrester for the LONWORKS network:


• Nominal discharge current of at least 1 kA (10/350 µs)
• Protective level < 1 kV

Recommended type
DEHN type BCT MLC BD 48 Art. No. 919 345
www.dehn.de

Cable routing between Lightning arresters


buildings When running cables between buildings, lightning arresters must be installed where the
bus cable enters the building. These must be connected to the closest potential
equalization point.

Overvoltage protection, secondary protection


The overvoltage protection is integrated in the automation stations
(Protection in conformance with EN 61000-4-5).

Overvoltage arrester
(secondary protection, External
built in automation station) lightning protection

Lightning arrester
(primary protection, 3rd party device)
LONWORKS bus
AC 24 V
G / AC 24 V
G0 / TE

Bus

PE

230/400 V
Automation
station

Equipotential bonding rail


10396z104en

46/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
Recommendations for Loops are often the cause of EMC interference due to overvoltages resulting from
the installation lightning. Loops are formed when 2 independent networks (e.g. the LONWORKS network
and AC 24 V) are connected to a bus device.

Bus

Large loop area: Bad!

AC 24 V

10396z005en
Small loop area: Good! Bus

24 V

Lightning produces considerable surge voltages in loops which cause short-circuits in


the devices, destroying electronic components.

When doing planning work, it must be ensured that loops are avoided wherever
possible and that loop surfaces will be as small as possible. The creation of loops must
be seen across the entire installation and all conductive parts are to be included
because the total loop surface is decisive for its effect.

Please also note the following


• Bus cables and power cables should be run parallel as close as possible This also
applies to earthed parts if the bus devices operate in connection with them
• The distance from line ends to earthed parts and other line ends should be as great
as possible
• The distance to lightning protection equipment (e.g. to arresters) should be adequate

47/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Wiring 31 Jan 2009
7 LONWORKS network: Principles
Topics in this section • Information on the engineering and installation of DESIGO PX plant:
• LONWORKS bus (Specification and topology)
• LONWORKS accessories (Bus terminations, Router, Repeaters)

This information applies to all DESIGO PX devices with a LONWORKS connection


(PXC... automation stations, PXR, PXE, PXG80-W, PXG80-WN and PXG80-N system
controllers, and to PXM20 operator units.
For technical data on specific devices refer to the relevant data sheets.

7.1 Specification

LONWORKS bus FTT-10A (Free Topology Technology) transceivers are used in the DESIGO PX
automation stations and system controllers.

Transfer medium TP/FT-10 (Twisted Pair/Free Topology)

Admissible topologies • Free topology (including star and ring topologies)


• Line topology (bus topology)

Tested cable types Echelon tests the electrical properties of various types of cable.
The results are published in the LonWorks bulletin "Junction Box and Wiring Guidelines
for Twisted Pair LonWorks Networks".
The following cable types have been validated for the TP/CT-10 channel:

Cable type AWG Cross-section


TIA 568A Category 5 24AWG 0.5mm
Belden 8471 16AWG 1.3mm
Belden 85102 16AWG 1.3mm
Level IV NEMA 22AWG 0.65mm

The list contains both shielded and unshielded cables that are suitable.
Generally no shield is required for cables routed inside a building.
Echelon recommends the use of shielded bus cables for all networks or parts of
networks that leave the building.

48/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies LonWorks network: Principles 31 Jan 2009
Recommended cable The German company, ConCab has developed its own cable for use in LONWORKS
type networks. We recommend the use of this cable in future, if possible.

Manufacturer: ConCab kabel gmbh; http://www.concab.net/


Cable type: [2x02Y AWG23(St) + 2x2Y AWG20] halogen-free
Item No. 935 123 120 06
Conductors 2 x 0.57mm LONWORKS bus cable, foil-screen pair based
(Cu) (AWG23) on Cat 5 specification ISO/IEC 11801
Wire insulation 02Y, white/orange
2 x 0.8 mm Unscreened for SELV
(AWG20) (Safety extra low voltage)
Wire insulation 2Y, red/blue

Jacket Halogen-free polymer, (H), light violet,


flame-retardant to IEC 60332-1
External diameter 7.6 mm ± 0.3 mm
Marking LON-CNP EN 14908-2 93512312006
Insulation voltage Wire/wire 700 V
Wire/outer 4 kV
jacket
Temperature range: For fixed cables –25 °C to 70 °C
Bend radius Single 40 mm
Multiple 80 mm

STOP Caution • The use of cables not approved by Echelon can lead to communication problems.
We do not, therefore, recommend the use of other types of cable as we cannot
provide support in the event of communication problems in such cases.
• Untwisted cables must not be used in LONWORKS twisted-pair networks.
These cables can impair functioning in the network and in some cases can result in
damage to connected nodes.

Other documents For more information on the technical principles, refer to the following documents,
available in PDF format on the Internet:

• LONMARK® Layer 1 – 6 Interoperability Guidelines


http://www.lonmark.org/technical_resources/guidelines/docs/LmPhy34.pdf

• LONMARK® FTT-10A Free Topology Transceiver User's Guide


http://www.echelon.com/support/documentation/manuals/transceivers/078-0156-01G.pdf

• Junction Box and Wiring Guideline for Twisted Pair LONWORKS® Networks
http://www.echelon.com/support/documentation/bulletin/005-0023-01M.pdf

7.2 Basic topological structure

The diagram below shows the basic structure and subdivisions of networks:
10396z01en

Physical
LONWORKS segment LONWORKS segment
repeater

49/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies LonWorks network: Principles 31 Jan 2009
7.3 Free topology

Free topologies may incorporate star or ring configurations. They are suitable for
almost all types of building. However, there are restrictions on the maximum length of
the cable (total of all conductors).

Where longer distances need to be covered, a physical bus repeater can be used, or a
line topology must be configured (see next page).
Only one physical repeater may be connected in series, i.e. a maximum of one physical
repeater between two devices (nodes).

STOP Caution! LonWorks routers must NOT be used, as their memory buffer is too small.
.
10396z02en
LONWORKS segment

1st physical segment 2nd physical segment


1) 250 m

Bus terminator
52,3 Ω RXZ01.1

PXC...-U PXC...-U
PXC... PXC... PXC... Physical
PXE-CRS repeater PXC...
PXR...
Bus terminator
52,3 Ω RXZ01.1

QAX...
PXM20
LONWORKS bus

PXC...
PXE-CRS
PXC...-U PXR...
PXC... PXC... PXC...
PXE-CRS
PXR...
PXC...

PXC...-U PXC...-U
DESIGO
TOOSET
QAX...
PXC...-U PXC...-U

1)
Guidelines for each Max. cable length (ConCab or category 5) 450 m
physical segment (total of all conductors including those to room units)
Max. cable length (all cables together) 450 m
1)
Max. distance between two nodes 250 m
2)
Max. number of devices (nodes) per physical segment 64
The bus terminator should be located at the key point of the 52.3 Ω (RXZ01.1)
physical segment, i.e. where the data traffic is at its heaviest
(e.g. automation station or a system controller etc.)

1)
Valid for the recommended ConCab cable type and to Cat 5 cables.
The maximum cable distance between the two nodes the furthest apart (all nodes,
not only adjacent nodes) in a given physical segment must not exceed 250 m.
Other cables tested:
— JY(St)Y 2x2x0.8 Î 320 m / 500 m (max. distance between nodes/max. length)
— Level IV Î 400 m / 500 m (max. distance between nodes/max. length)
— Belden 8471 Î 500 m / 500 m (max. distance between nodes/max. length)

2)
BACnet places a heavier load on the LONWORKS bus than LonMark. For this reason
we recommend that not more than 30 PX devices should be used per segment
(comprising 1 … 2 physical segments).
Refer also to Section "System limits" in the DESIGO technical principles manual [3].

50/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies LonWorks network: Principles 31 Jan 2009
7.4 Line topology

A line topology is used primarily in cases where a long bus cable is required (>450 m).
Note, however, that the length of the LONWORKS spur connections must not exceed
3m.

10396z03en

LONWORKS segment

max. 900 m 1st physical bus segment 2nd physical bus segment

Bus terminators
PXM20 105 Ω RXZ02.1
Bus terminator Bus terminator
105 Ω RXZ02.1 Distributor 105 Ω RXZ02.1
AC 24 V LONWORKS bus

Physical
repeater
PXC...-U PXC...-U PXC...-U
PXC... PXC... PXC...

max. 3 m
PXE-CRS PXE-CRS
PXR... PXR...

DESIGO
QAX... TOOLSET PXM20

1)
Guidelines for each Max. cable length (ConCab or Category 5) 900 m
physical segment Max. stub length 3 m 1)
2)
Max. number of devices (nodes) per physical segment 64
Bus terminators at each end of the physical segment 105 Ω (RXZ02.1) each
end

1)
STOP Caution! The length of the spur connection is limited to 3 m. This must be taken into
. account in cases where PXM20 operator units and DESIGO TOOLSET are used.
1)
Valid for the recommended ConCab cable type and to Cat 5 cables.
Other cables tested:
− JY(St)Y 2x2x0.8 Î 900 m / 750 m (FTT / FTT&LPT only)
− Level IV Î 1400 m / 1150 m (FTT / FTT&LPT only)
− Belden 8471 Î 2700 m / 2200 m (FTT / FTT&LPT only)
2)
BACnet places a heavier load on the LONWORKS bus than LonMark. For this reason
we recommend that not more than 30 PX devices should be used per segment
(comprising 1 … 2 physical segments).
Refer also to Section "System limits" in the DESIGO Technical principles manual [3].

51/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies LonWorks network: Principles 31 Jan 2009
7.5 LONWORKS accessories
7.5.1 Bus terminators

Bus terminators are used for the electrical termination of the LONWORKS bus.
Depending on the topology involved, these terminators may have an impedance of
52.3 (RXZ01.1, for free topologies) or 105 (RXZ02.1, for line topologies). The bus
terminators are not integral components of the DESIGO PX devices and must be
installed separately.

7.5.2 Physical repeaters

Repeaters are used where:


– the total cable length in a physical segment exceeds 450 m (in a free topology)
– or 900 m (in a line topology)
No more than ONE physical repeater may be used for each LONWORKS segment.

Recommendation The following devices have been tested by Siemens Building Technologies:

Company Designation Types


SysMik GmbH Dresden 2-way repeater *) RPT-FTT10x2-CC 230 V AC
RPT-FTT10x2-CC 24 V AC/DC

STOP Caution! *) Repeaters from SysMik GmbH:


. Use only versions with terminals (cage clamp terminals). In versions with an
RJ45 socket, pins 1+3, 2+6 and 4+5 are interconnected internally.
With the DESIGO RXC and DESIGO PX ranges, however, pin 3 of the RJ45 socket
for the LONWORKS bus is connected to G0 (the power supply for the PXM20
operator unit).
This applies to the following devices: PXR, RXZ03.1, PXC..., PXE-CRS

Other documentation For a detailed description of further topologies and their layout refer to Section
"Network architecture" of the DESIGO Technical principles manual [3].

52/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies LonWorks network: Principles 31 Jan 2009
8 Ethernet networks

10396Z06
Hub /
Switch

Ethernet
max. 100 m
BACnet Ethernet
Router max. 100 m

LON max. 900 m

.
.
PXC...-E.D PXA30-N, PXC...-U .
PXC... PXA30-NT, .
PXE-CRS PXC...-U PXA30-W0, .
PXR... PXA30-W1, .
PXA30-W2

The PXG80-N BACnet routers are interconnected via RJ45 patch cables and
hubs/switches. Note the following requirements:

Cables:
– Standard Ethernet cable, at least Category 5
– Max. length 100 m.
– Screened or unscreened
STP (Shielded Twisted Pair) or UTP (Unshielded Twisted Pair)

Hub / Switch
– Standard IT products
– Where possible, use switches to reduce data traffic and conflicts.
– Use dual-speed 10/100 Mbit products, as the BACnet router only supports 10 Mbit
technology, while most IT networks are based on 100 Mbits.
Even if communications only use 10 Mbit technology, dual speed products should be
used in order to protect capital investment into the future.

Other documentation For further information refer to:


• DESIGO Technical principles manual [3], chapters 3 and 16
• Ethernet, TCP/IP and BACnet on Ethernet/IP Principles [6]

53/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Ethernet networks 31 Jan 2009
9 Telephone networks
(remote management)
10396z002
DESIGO TOOLSET DESIGO INSIGHT WEB-Client

PXM...

.
BACnet / LonTalk .

PXA30-T
PXA30-NT

PXC64-U PXC... PXC10-TL PXC... PXC... PXG80-W


PXC128-U PXR... PXC12-T PXR... PXR... (WEB controller)
PXE... PXC22-T PXE... PXE...

.
.
I/O modules .
.

Remote management via the public telephone network is possible as follows:


• Communication between DESIGO PX, DESIGO INSIGHT, and DESIGO TOOLSET
• Communication between a web client and DESIGO PX.

Other documentation The following issues are described in detail in the DESIGO Technical principles manual
[3], chapter "Communication":
• Hardware requirements
• Modem
• Engineering and commissioning communication.

54/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Telephone networks (remote management) 31 Jan 2009
10 Connection diagrams
10.1 Compact automation stations, AC 24 V
9211A01
PXC12 1 2 3 4 5 6 7
PXC12-T

CP +
CP –
CLA
CLB
G0
TE

X1

X2
X3

X4

X5

X6
M

M
G
HMI RS232 / COM2
AC 24 V TOOL LONWORKS

1 2
QAX...

max. AC 250 V, 5A RES./ 2A G.P./ 2 FLA / 12 LRA


Q11
Q14
Q12

Q21
Q24
Q22

Y1
Y2

Y3
Y4
51 52 70 71

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket (for PXM10 or PXM20 operator unit or DESIGO TOOLSET)
3 CLA/CLB LONWORKS bus
4 CP+/CP- PPS2 bus (for QAX... room units)
5 9-core standard screened cable for modem connection (PXC12-T only)
6/7 X1 ... X6 6 universal inputs
51 ... 52 Q11 ... Q22 2 relay outputs
70 ... 71 Y1 ... Y4 4 universal outputs

9211A02
PXC22 1 2 3 4 5 6 7 8
PXC22-T
GND

GND
CP +
CP –
CLA
CLB
G0

D1

D2
D3

D4
TE

X1

X2
X3

X4

X5

X6
X7

X8
M

M
G

HMI RS232 / COM2


AC 24 V TOOL LONWORKS

1 2
QAX...

max. AC 250 V, 5A RES./ 2A G.P./ 2 FLA / 12 LRA


Q11
Q14
Q12

Q21
Q24
Q22

Q31
Q34
Q32

Q41
Q44
Q42

Q51
Q54
Q52

Q61
Q64
Q62

Y1
Y2

Y3
Y4

51 52 53 54 55 56 70 71

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket (for PXM10 or PXM20 operator unit or DESIGO TOOLSET)
3 CLA/CLB LONWORKS bus
4 CP+/CP- PPS2 bus (for QAX... room units)
5 9-core standard screened cable for modem connection (PXC22-T only)
6/7 X1 ... X8 8 universal inputs
8 D1 ... D4 4 binary inputs (counters possible)
51 ... 56 Q11 ... Q62 6 relay outputs
70 ... 71 Y1 ... Y4 4 universal outputs

55/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
9211A03
PXC36 1 2 3 4 5 6 7 8 9
PXC36-S

GND

GND
CP +
CP –
CLA
CLB

X10
X11

X12
G0

D1

D2
D3

D4
TE

X1

X2
X3

X4

X5

X6
X7

X8

X9
M

M
G
HMI RS232
AC 24 V TOOL LONWORKS Modem / Printer

QAX... 10 11

GND
GND

GND

GND
D10
D11

D12
D9
D5

D6
D7

D8
max. AC 250 V, 5A RES./ 2A G.P./ 2 FLA / 12 LRA
Q11
Q14
Q12

Q21
Q24
Q22

Q31
Q34
Q32

Q41
Q44
Q42

Q51
Q54
Q52

Q61
Q64
Q62

Y1
Y2

Y3
Y4

Y5
Y6
51 52 53 54 55 56 70 71 72

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket (for PXM10 or PXM20 operator unit or DESIGO TOOLSET)
3 CLA/CLB LONWORKS bus
4 CP+/CP- PPS2 bus (for QAX... room units)
6 ... 8 X1 ... X12 12 universal inputs
9 D1 ... D4 4 binary inputs (counters possible)
10 ... 11 D5 ... D12 8 binary inputs
51 ... 56 Q11 ... Q62 6 relay outputs
70 ... 72 Y1 ... Y6 6 universal outputs

PXC52
9211A04

1 2 3 4 5 6 7 8 9 10
GND

GND

GND

GND
CP +
CP –
CLA
CLB

X10
X11

X12
G0

D1

D2
D3

D4

D5

D6
D7

D8
TE

X1

X2
X3

X4

X5

X6
X7

X8

X9
M

M
G

HMI RS232
AC 24 V TOOL LonWorks Modem / Printer

QAX... 11 12 13
GND

GND

GND

GND
D10
D11

D12

D13

D14
D15

D16
X13

X14
X15

X16

D9
M

max. AC 250 V, 5A RES./ 2A G.P./ 2 FLA / 12 LRA


Q101
Q104
Q102

Q111
Q114
Q112

Q121
Q124
Q122
Q71
Q74
Q72

Q81
Q84
Q82

Q91
Q94
Q92
Q31
Q34
Q32

Q41
Q44
Q42

Q51
Q54
Q52

Q61
Q64
Q62
Q11
Q14
Q12

Q21
Q24
Q22

Y1
Y2

Y3
Y4

Y5
Y6

Y7
Y8

51 52 53 54 55 56 57 58 59 60 61 62 70 71 72 73

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket (for PXM10 or PXM20 operator unit or DESIGO TOOLSET)
3 CLA/CLB LONWORKS bus
4 CP+/CP- PPS2 bus (for QAX... room units)
6 ... 8 X1 ... X16 16 universal inputs
11
9 D1 ... D4 4 binary inputs (counters possible)
10/12/13 D5 ... D16 12 binary inputs
51 ... 62 Q11 ... Q122 12 relay outputs
70 ... 73 Y1 ... Y8 8 universal outputs

56/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
PXC12.D, PXC12-T.D

22 23

CLA
CLB
B

D
HMI / TOOL
DI1 DI2

HMI

9215A11
58 59 60 61 62
E C

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4…9 DO1, DO2 2 Digital outputs (Relays)
22, 23 CLA, CLB LonWorks-Bus
25 … 30 AO1 … AO4 4 Analog outputs
31 … 36 UI5 … UI8 4 Universal inputs
58 … 60 DI1, DI2 2 Digital inputs
61, 62 CP+, CP– PPS2 bus (for QAX... room units)
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit
D HMI / Tool RJ45 socket for operator unit and tool
E USB Host interface (modem, PXC…-T.D only)

PXC22.D, PXC22-T.D

22 23

CLA
CLB
B

D
HMI / TOOL

HMI
E C 9215A12

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4 … 21 DO1 … DO6 6 Digital outputs (Relays)
22, 23 CLA, CLB LonWorks-Bus
25 … 30 AO1 … AO4 4 Analog outputs
31 … 52 UI5 … UI16 12 Universal inputs
61, 62 CP+, CP– PPS2 bus (for QAX... room units)
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit
D HMI / Tool RJ45 socket for operator unit and tool
E USB Host interface (modem, PXC…-T.D only)

STOP Caution! • Observe the technical data for the relay outputs.
• Local installation regulations must be observed.

57/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
PXC36.D, PXC36-T.D

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8

B
DI1 DI2

D
HMI / TOOL

DI3 DI4

HMI

9215A13
E C

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4 … 27 DO1 … DO8 8 Digital outputs (Relays)
28, 29 CLA, CLB LONWORKS bus
30 ... 38 AO1 … AO6 6 Analog outputs
39 ... 73 UI7 … UI24 18 Universal inputs
74 ... 79 DI1 … DI4 4 digital inputs
80, 81 CP+, CP– PPS2 bus (for QAX... room units)
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit
D HMI / Tool RJ45 socket for operator unit and tool
E USB Host interface (modem, PXC…-T.D only)

PXC12-E.D

CLA
CLB

DI1 DI2

HMI
9215A02

58 59 60 61 62
C

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4…9 DO1, DO2 2 Digital outputs (Relays)
25 … 30 AO1 … AO4 4 Analog outputs
31 … 36 UI5 … UI8 4 Universal inputs
58 … 60 DI1, DI2 2 Digital inputs
61, 62 CP+, CP– PPS2 bus (for QAX... room units)
A Ethernet socket
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit

STOP Caution! • Observe the technical data for the relay outputs.
• Local installation regulations must be observed.

58/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
PXC22-E.D

CLA
CLB
B

HMI

9215A01
C

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4 … 21 DO1 … DO6 6 Digital outputs (Relays)
25 … 30 AO1 … AO4 4 Analog outputs
31 … 52 UI5 … UI16 12 Universal inputs
61, 62 CP+, CP– PPS2 bus (for QAX... room units)
A Ethernet socket
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit

PXC36-E.D

DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8

DI1 DI2
B

DI3 DI4

HMI
9215A14

1, 2 24 V ~, ⊥ Operating voltage AC 24 V
3 Functional earth
4 … 27 DO1 … DO8 8 Digital outputs (Relays)
30 ... 38 AO1 … AO6 6 Analog outputs
39 ... 73 UI7 … UI24 18 Universal inputs
74 ... 79 DI1 … DI4 4 Digitale Eingänge
80, 81 CP+, CP– PPS2 bus (for QAX... room units)
A Ethernet socket
B USB Device interface (not supported)
C HMI RJ45 socket for operator unit

STOP Caution! • Observe the technical data for the relay outputs.
• Local installation regulations must be observed.

59/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.1.1 Connecting the field devices
for PXC12, 12-T, 22, 22-T, 36, 36-S, 52

Field device supply voltage from system transformer

G AC 24 V G0 00322 A de
Active and passive
sensors
G G G G0 G0 G0

B Passive Fühler
z.B. QAM...
M (Ni1000)

M Aktive Fühler
z.B. QFM...
G (Feuchte)
B
M

TE G0 G X... M X...

00323D

Magnetic valves G AC 24 V G0

G G G G0 G0 G0 Magnetventile
z.B. M3P... +ZM z.B. MX...461...
1 1 G0 (GN)
2 2 G (GL)
3 YM
4 3 Y

TE G0 G

Y... N

G AC 24 V G0 00334D
Motorized valves

G G G G0 G0 G0 Motorventile

G0
G

TE G0 G

Y... N

60/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
G AC 24 V G0 00335D
Damper actuators

G G G G0 G0 G0 Klappenantriebe
GBB161.1E

2
1
8
4
5

TE G0 G

Y... N

Field device supply from separate transformer

G AC 24 V G0 00324D
Magnetic valves (example)

G G G G0 G0 G0 Magnetventile
z.B. M3P... +ZM z.B. MX...461
1 1 G0 (GN)
2 2 G (GL)
3 YM
4 3 Y

TE G0 G X... M X... G G0

G AC 24 V G0

Y... N AC 230 V

L N

61/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.1.2 Connecting the field devices for PXC....D

STOP Note! In the automation stations described in this data sheet, system neutral (G0) and
measuring ground (–) are NOT CONNECTED.
For active 4-wire field devices, this connection is made in the device.
For active 3-wire field devices, you have to make an additional connection:
c either on the terminals of the field device
d or between one of the (–) terminals of the automation station and G0
(in existing plants where there are only 3 conductors installed).

Field device supply voltage from system transformer

Counter inputs Counter inputs faster than 1 Hz must be shielded if they are routed in the same trunking
as analog inputs for more than 10 m.

G AC 24 V G0
Passive sensors
(e.g. QAM... , Ni 1000) G G G G0 G0 G0

Active sensors
(e.g. QFM... , humidity)
24V

9215A03

AO AO UI UI
CP+

CP-

N
B QAM...
(Ni1000)
M

M QFM...
(r.h.)
G
B
M

G AC 24 V G0
Magnetic valves
(e.g. M3P... + ZM G G G G0 G0 G0
or MX...461...)

24V
9215A04

AO AO UI UI
CP+

CP-

N M3P... + ZM MX...461...

2 1 G0 (GN)
1 2 G (GL)
4 4 YM
3 3 Y

62/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
G AC 24 V G0
Motorized valves
G G G G0 G0 G0

24V

9215A05
AO AO UI UI

CP+

CP-
N
1
2 G0
G

Y
G AC 24 V G0
Damper actuators
(e.g. GBB161.1E)
G G G G0 G0 G0

24V

AO AO UI UI
CP+

CP-

N GBB161.1E

1
2 2
1
8

9215A06
Field device supply from separate transformer

G AC 24 V G0
9215A07

Magnetic valves
(e.g. M3P... + ZM
G G G G0 G0 G0
or MX...461...)

24V L N

AC 230 V

G
AC 24 V
G0
STOP Note!

AO AO UI UI
Do NOT earth
CP+

CP-

N the local
1 1 G0 (GN) transformer
2 2 G (GL)
3 YM
4 4 Y

M3P... + ZM MX...461...

63/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.1.3 Connecting the room units

01045

4 3 2 1
N Automation
station

CP+
CP–
C+
C–
R1
R... Max. 5 room
PPS2
units (parallel)

CP+ 4 3 2 1 4 3 2 1
CP–

PPS2 • Twisted pair

CP+

CP+
CP–

CP–
C+

C+
C–

C–
R2 R3 bus cable
• Reversible
polarity
• Cable length,
N
see page 42

9215A08
24V

4 3 2 1

CP+
CP–
AO AO UI UI
CP+
CP-

C+
C–
R1
PPS2

4 3 2 1 4 3 2 1
CP+

CP+
CP–

CP–
C+

C+
C–

C–

R2 R3

Note • The room units are connected in parallel (max. five devices).
• To distinguish between them, they can be addressed by use of jumpers (address
plug on the printed circuit board). The factory-setting is Address 1.

64/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.2 PXC10-TL automation station, AC 230 V

01880
PXC10-TL
X21 X22

GND

GND

CP+
CP-
D1

D2
D3

D4
X1

X2
X3

X4
M

M
M M

X23 X24

GND
RXD

24 V
TXD

RTS
CTS

CLA
CLB
Q11
Q14
Q12

Q21
Q24
Q22
N
L

F1
L

TE

N1

X21 X1 Universal input


M Mass
X2 Universal input
X3 Universal input
M Mass
X4 Universal input
D1 Binary input
GND Ground
D2 Binary input
D3 Binary input

X22 GND Ground


D4 Binary input
free
free
free
free
free
free
CP+ PPS2 bus (for QAX... room units)
CP– PPS2 bus (for QAX... room units)

65/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
X23 N Nullleiter AC 230 V
L Phase AC 230 V
Do not connect anything (isolation clearance)
Q11 Relay 1 AC230V Com
Q14 AC230V NO
Q12 AC230V NC
Do not connect anything (isolation clearance)
Q21 Relay 2 AC230V Com
Q24 AC230V NO
Q22 AC230V NC

X24 RXD RS232 interface COM1 Receive Data


TXD Transceive Data
GND Ground
RTS Request to send
CTS Clear to send
24 V Operator Unit
CLA LONWORKS Bus
CLB LONWORKS Bus
free
free

Auxiliary terminals GND (Signal Ground) may be connected to system ground (technical panel
ground) (PELV)
M M-terminals (2 blocks): These terminals may only be used as measuring
neutral

10.2.1 Connecting the field devices

Same as for compact automation stations (page 61).

10.2.2 Connecting the room units

Same as for compact automation stations (page 64).

66/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.3 Automation stations ("modular") series

PXC....D

HMI
(A)
(C)
T
24 V~

CLA
CLB
(B)

HMI / TOOL
(E)

(F)

(G)
HMI

9222Z10
PXC...-E.D

T (A)
24 V~
(D)

(F)

(G)
HMI

9222Z11
1, 2 24 V ~, ⊥ Operating voltage AC 24 V
Plug-in screw terminal block
3 Functional ground
(A) USB host interface (for modem via PXA-C3 adapter cable)
4,5 (B) CLA, CLB LONWORKS bus Plug-in screw terminal blocks
(C) HMI RJ45 interface (LONWORKS) for operator unit PXM20 (tool as well)
(D) RJ45 interface for Ethernet
(Operator unit PXM20-E can be connected to hub/switch)
(E) HMI / Tool RJ45 interface (LONWORKS and serial) for PXM10, PXM20 and tool
(F) USB device interface (for future applications)
(G) HMI RJ45 interface (serial) for operator unit PXM10

Connecting TX-I/O See Planning and Installation Guide TX-I/O, CM110562.


modules and field
devices

67/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
01546 B
PXC64-U
C1 G
1
C2 G0
8
C3 PD

C4 2 PU

S PC
9
S CP+
4
CLA CP–
10
CLB

HMI/TOOL

1 G/G0 Supply voltage AC 24 V


2 PD P bus Synchronization cable
PU Data cable, bi-directional
PC Reference voltage DC 23 V (against G0)
4 CP+/CP- PPS2 bus (for QAX... room units)
10 CLA/CLB LONWORKS bus
Front HMI / TOOL RJ45 (for PXM10 / PXM20 operator unit or DESIGO
TOOLSET)
Bot- Modem 9-pin sub-D connector for modem (on the optional PXA30-T
tom extension module, see diagram, page 15)
Ethernet RJ45 connector
KNX / EIB 9-pin sub-D connector (on the optional PXA30-K11 extension
bus module, see diagram, page 15)
Service RJ45 connector (on the PXA30-K11 extension module)
RS232, • 9-pin sub-D connector for M-Bus
RS485 • Plug-in screw terminal block for Modbus
(PXA30-RS)

PXC128-U The PXC128-U automation station incorporates a second P bus:


• Terminals of P-bus 1: PD1, PU1 and PC1
• Terminals of P-bus 2: PD2, PU2 and PC2

Connecting the field For information on connecting the field devices, refer to the mounting and installation
devices guide for the I/O module system, CM2M8102 [1].

Connecting the room units As for the compact-series automation stations (page 64).

PXC00-U The PXC00-U automation station does not have a P bus connection

68/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.4 PXR… system controllers
01530 A

1 2 3 5
ALN

CLA
CLB
G0
TE

G
HMI/TOOL RS232 / COM2
AC 24 V
6 VA
LON ®

LON ®

TOOL

CLA
CLB
FLN
51 52

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket for PXM20 operator unit or DESIGO TOOLSET
3 CLA/CLB LONWORKS bus
5 COM2 9-pin RS232 connector for modem
51 HMI/TOOL RJ45 socket (for RXT10 tool)
52 CLA/CLB LONWORKS bus

10.5 PXE-CRS system controller


01531 A

1 2 3 5
ALN
CLA
CLB
G0
TE

HMI/TOOL RS232 / COM2


AC 24 V
6 VA
LON ®

RS232 / COM1 RS484 / COM1


SHLD
GND

3rd
+
-

53 54

1 TE Functional earth
G/G0 Supply voltage AC 24 V
2 HMI / TOOL RJ45 socket (for PXM20 operator unit or DESIGO TOOLSET)
3 CLA/CLB LONWORKS bus
4 CP+/CP- PPS2 bus (for QAX... room units)
5 COM2 9-pin RS232 connector for modem
53 COM1 9-pin RS232 connector for third-party bus
54 COM1 RS485 terminals for third-party bus

69/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
10.6 Web controllers PXG80-W and PXG80-WN
01542 A

1 5 6
WEB

G0
TE

G
AC 24 V RS232 / COM2 RJ45
6 VA Modem Ethernet

LON

HMI RS232 / COM1


TOOL Modem (nicht benutzt)

CLA
CLB
ALN
51 52 53

1 TE Functional earth
G/G0 Supply voltage AC 24 V
5 COM1 9-pin RS232 connector for modem
6 RJ45 connector for Ethernet (PXG80-WN only)
51 HMI / TOOL RJ45 socket (for PXM20 operator unit or DESIGO TOOLSET)
53 COM2 9-pin RS232 connector for modem (not used)

10.7 PXG80-N BACnet router


01547 A

1 6
MLN
G0
TE

AC 24 V RJ45
6 VA Ethernet

LON

HMI
TOOL
CLA
CLB

ALN
51 52

1 TE Functional earth
G/G0 Supply voltage AC 24 V
6 RJ45 socket for Ethernet connection
51 HMI / TOOL RJ45 socket (for PXM20 operator unit or DESIGO TOOLSET)
52 CLA/CLB LONWORKS network connection

70/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Connection diagrams 31 Jan 2009
11 Disposal

Take careful note The devices described in this document were manufactured using environment-
of this information compatible materials and processes, and using as little energy as possible.

Disposal When disposing of these devices and components either due to defects, or because
they have reached the end of their service life, please note:
• All parts must be properly disposed of, i.e. dismantled and separated into their
various constituent materials before disposal. Observe any notes on materials and
disposal that may be attached to individual components. Always aim for maximum
re-use of the basic materials, and minimum negative impact on the environment.
• Start by removing any potentially hazardous materials from the devices and dispose
of these separately as hazardous waste. Potentially hazardous materials include
batteries and LCD displays, for example.
• Then separate the remainder into the different kinds of materials for recycling.
• Never dispose of electronic or electrical equipment as domestic waste.
• Always use the most environmentally compatible method of disposal, in line with the
latest developments in environmental protection, recycling and waste management.

In case of any problems or questions related to disposal, please contact your supplier,
an appropriate waste management company or Siemens Building Automation. Siemens
Building Automation is always willing to provide you with all the necessary information
to help you dispose of devices and system components in a timely and environmentally
safe manner.

71/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Disposal 31 Jan 2009
12 Dimensions
Contents of this section This section contains dimension diagrams for the automation stations, the PXM…
operator units, the system controllers and the Web controllers.

Units of measurement All dimensions are given in mm.

12.1 Automation stations (compact series), system


controllers, Web controllers and routers

PXC12....D und PXC22....D


50,2 271,5
7
149,4

44,3

35.5
90

38,5
50,8
58
61,7

9215M01
PXC36....D
50 292.6
7
35.5
176
150
94
45

51
73
77.2
9215M02

72/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
28 28 01543

5
B B

176
28

5
A 52

A = PXC12, PXC12-T 216


PXC22, PXC22-T: 216
PXC36, PXC36-S: 270
PXC52: 343
PXR11, PXR12 216
PXE-CRS 216
PXG80-W 216
PXG80-WN 216
PXG80-N 216

B = Facility for mounting on DIN rail

73/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
12.2 Automation station PXC10-TL (AC 230 V)

01837

139
1,5 95 (42,5)

144 19

144
15

26 26 26 26 144
max. 3
18
4,5
14

138 -0/+1
39
39 35
36 29
106
50

36
72 138 -0/+1
106
108

74/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
12.3 Automation stations, "modular" series

Automations stations, System controllers PXC....D

74
4.5

(PXA40-...)
35.5
96
90
93

45
43

192 44
199 66
4 70

9222m14
81 (PXA40-...)

Option modules PXA40-...


40

9222m15

143 15

75/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
Automations stations, System controllers PXC...-U

Mounting in
control panel door

17
55
00232 K

min. 40 mm
22.5

24
max R2

0
+1
25
PXM...

138
+1
1380
137

150
min. 80 mm

15 27 109
min. 100 mm
136
210
For PXM20-E only *)

*) This hole is required for the Ethernet cable


when an operator unit PXM20-E is moun-
ted on top of the automation station
(see page 36)

Wall mounting
17

55 min. 40 mm

00233 K
18 40,7
14,5
PXM...

137

150

81
22,7

5,2
min. 80 mm

15 27 109 124,5 min. 100 mm


136
210

76/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
12.4 PXM… operator units

01544 F

A A

117
210 37

A = Facility for mounting on DIN rail

5,6 176,8 11,6 00267


Drilling and
cut-out template
64,6

ø 4,8
47,4

77/78

Siemens Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22 © 2001 - 2009 Siemens Switzerland Ltd.
www.buildingtechnologies.siemens.com Subject to change

78/78

Building Technologies Mounting and installation guide CA110396en_03


Building Technologies Dimensions 31 Jan 2009

You might also like