OPERATING MANUAL
FOR
TELEPAC
MICROCONTROLLER
Synchronizer
2
Introduction
Salient Features
1. Fully programmable.
2. Complete protection for AC from unhealthy condition.
3. All set points programmable from keypad..
4. Password protection for controller.
5. Different Passwords for Normal set points, Offset Set points
& Alarm Configuration set point.
6. on site selection of Single Phase/Three Phase.
7. 16 char. 2 lines LCD display with back lit on controller front panel.
8. Simple 4 Key keypad for on site programming.
9. Separate alarm contacts for AC 1 fail alarm AC 2 fail alarm, power fail
10. on site selection of Single AC/Dual AC operation.
11. Automatic display of AC parameters one by one in Run Mode.
12. Status & Healthy indication by LED on front panel.
13. Alarm indication by LED on front panel.
14. Room temperature sensing by precise sensor.
15. Separate outputs for each fan and compressor.
16. Direct display of Line voltage & actual current drawn by compressor.
17. Direct display of actual room temperature.
18. Sequencing of comp. for equal run hours, Site selectable.
19. Automatic Timer mode operation if Room sensor fails.
20. All Faults Autoreset.
21. Smoke fire & D.G. sensing.
22. Fault log History.(last 10 faults)
23. Compressor hour run 4 digit display.
24. Time remaining for change over display.
25. Total hour run from installation.
26. Single Phasing/Reverse Phasing Protection in case of Three Phase
Controller.
27. Communication between 15 units ( 1 Master /14 Slaves) in each zone.
28. Communication between multiple zones possible.
29. Offset Feature for On site calibration.
30. Sensor fail mode On-time & Off-Time.
31. Seperate settable on delay for compressor.
3
FRONT VIEW :
BLUE STAR
TELEPAC
AC 1 AC 2
4
Technical Specifications
Terminals : 1) Power unit for each AC, separate o/ps for 2 Fans
& Compressor.
2) Temperature sensor.
3) AC1 fail alarm relay o/p.
4) AC2 fail alarm relay o/p.
5) Power fail alarm relay o/p
KEY DESIGNATIONS
1) FUN : Thıs key is used to change the controller from RUN mode to
FUNCTION selection mode.
2) ENTER : When this key is pressed the parameter entered by user gets
accepted by the controller.
FAULTS/PROTECTIONS
CONTROLLER FUNCTIONS
User can see all set points by pressing FUN key.To enter any function, you
are required to first enter the password.
7
System setting:
• To change any parameter user will have to enter the password . When
you press INC/DEC key ,the display will indicate will show .
Enter Setting(*10
Password: 0000 Shiycle:024
Enter the system password with the help of INC/DEC key . Press the Enter
key to accept the value .Now user can enter/change into any set points. If
password is not correct display shows “ 0”
When correct passwor is entered user can change the set points.
İ.e. By default the setpoint is 24c. İn that case the CP1 set point will be 24c
and CP2 set point will be Sys Temp Setpt + differential.
8
3.CP Differential:-
CP Differential
2.0 C
By default the setpoint is 24c. İn that case the CP1 set point will be 24c and
CP2 set point will be Sys Temp Setpt + differential.
• Change the Room High Set Pt with the help of INC/DEC key. Press
Enter key.
• Change the Room Low Set Pt with the help of INC/DEC key. Press
Enter key.
• Use INC/DEC keys to change set points.Press Enter key at the end.
Display shows
OV SetPts
260V
OV SetPts
460V
• To change the set point of A/C OV use INC/DEC key. Press Enter key at
the end.
•
9. A/C UNDER VOLTAGE:-
This fun is used for setting the under voltage set point of A/C.
The A/C UV is displayed in Volt.
Display shows
UV SetPts
160V
10
UV SetPts
160V
• Change the set point of CP1 Temp with the help of INC/DEC key. Press
Enter key.
• User can change the cut in temp.set point of CP2 with the help of
INC/DEC key. Press Enter key at the end.
No of CPs (1-2)
1
No of CPs (1-2)
2
OFFSET FUNCTIONS:
IMP NOTE: Offset functions are not visible normally. If user wants to access
offset functions follow these steps.
1. First enter password =6
2. Now OFFSET functions are open & visible to user.User can
change/modify them.
After power ON/OFF or password is locked, again the offset functions are
inaccessible & only be opened if password = 6.
ROOM Temp.+
0.0c
• Change the set point of Room Temp - offset with the help of INC/DEC
key. Press Enter key.
ROOM Temp.-
0.0c
• Change the set point of Room Temp - offset with the help of INC/DEC
key. Press Enter key.
CP1 Current+
0.0A
• Change the set point of A/C1 Volt + offset with the help of INC/DEC
key. Press Enter key.
CP1 Current-
0.0A
• Change the set point of A/C1 Volt - offset with the help of INC/DEC
key. Press Enter key.
13
CP2 Current+
0.0A
• Change the set point of A/C2 Volt +/- offset with the help of INC/DEC
key. Press Enter key.
• Change the set point of A/C2 Volt - offset with the help of INC/DEC key.
Press Enter key.
CP1 Voltage+
0v
• Change the set point of A/C1 Volt + offset with the help of INC/DEC
key. Press Enter key.
CP1 Voltage-
0v
• Change the set point of A/C1 Volt - offset with the help of INC/DEC
key. Press Enter key.
14
CP2 Voltage+
0v
• Change the set point of A/C2 Volt +/- offset with the help of INC/DEC
key. Press Enter key.
• Change the set point of A/C2 Volt - offset with the help of INC/DEC key.
Press Enter key.
DELAY FUNCTIONS:
IMP NOTE: DELAY functions are not visible normally.
If user wants to access Delay functions follow these
steps.
1.First enter password = “06”
2.Now DELAY functions are open & visible to
user.User can change/modify them.
After power ON/OFF or password is locked, again the
DELAY functions are inaccessible & can only be
opened if password = 06
Change the Delay of AC1 FAN ON Delay with the help of INC/DEC
key. Press Enter key.
15
Change the Delay of AC2 FAN ON Delay with the help of INC/DEC
key. Press Enter key
3.CP1 ON DELAY:-
It shows the on delay for AC1
CP1 ON Dly
30s
4.CP2 ON DELAY:-
It shows the on delay for AC2
CP2 ON Dly
35s
Change the Delay of AC2 ON Delay with the help of INC/DEC key.
Press Enter key.
CP OL Sense
5s
CP UL Sense
5s
• Change the Delay of Room High Sense with the help of INC/DEC
key. Press Enter key.
• Change the Delay of Room low Sense with the help of INC/DEC
key. Press Enter key.
OV Sense
5s
UV Sense
5s
In case room sensor fails, controller will be in Timer Mode. Only one
A/C will be ON whose Cut in set point is less than the other.The A/C will be
working with respect to the cycle on/off time set pts are given below.
Change the cycle On / Off time set pts with the help off INC/DEC key. Press
Enter key. A/C will remain ON for ON Time & OFF for OFF Time.
18
STATUS PARAMETER:-
1. SHİFT CYCLE BALANCE TİME:-
The temperature set points of A/Cs will be interchanged after cycle
time That change over time is user setable . This fun is used to
change the set point of Cycle Time , 0240M means 240 minutes so
cycle time is 240 minutes.
This function shoes the balance time for next shift cycle.
• Display shows
• Change the Delay of shift cycle balance time with the help of
INC/DEC key. Press Enter key
• Display shows
Hysteresis FUNCTIONS:
IMP NOTE: Hysteresis functions are not visible
normally. If user want to access Hysteresis functions
follow these steps.
1. First enter password = “06”
2. Now Hysteresis functions are open & visible to
user.User can change/modify them.
After power ON/OFF or password is locked, again the
Hysteresis functions are inaccessible & only be
opened if password = 06
If user wants to set any Hysteresis use Hysteresis functions
in settings. The Hysteresis parameters are as follows.
AC OV CutOff Hys
10V
• Change the Hysteresis of AC OV Cutoff Hysteresis with the help
of INC/DEC key. Press Enter key.
NetWork functions
IMP NOTE: NetWork functions are not visible
normally. If user wants to access NetWork functions
follow these steps.
4. First enter password = “06”
2. Now NetWork functions are open & visible to
user.User can change/modify them.
After power ON/OFF or password is locked, again the
NetWork functions are inaccessible & only be opened
if password = 06
If user wants to set IP Adderess of unit or unit No it will
change over NETWORK Settings. The Network parameters are as
follows.
1. ZONE İD :-
• Press ENT key till Display shows
Zone ID(1-15)
1
22
• Change the zone ID with the help of INC/DEC key. Press Enter
key.
2. UNIT ID :-
• Press ENT key till Display shows
Unit ID(1-15)
1
• Change the unit ID with the help of INC/DEC key. Press Enter
key.
3. Reset Unit ID :-
Press ENT key till Display shows
Reset Unit ID
NO
• Reset the unit id with the help of INC/DEC key. Press Enter key.
4. Selection of MASTER/SLAVE :-
• Press ENT key till Display shows
MASTER/SLAVE
MASTER
• Select MASTER/SLAVE with the help of INC/DEC key. Press
Enter key.
6. BAUD RATE :-
Press ENT key till Display shows
BAUD RATE
9600
• Change the BAUD RATE with the help of INC/DEC key. Press
Enter key.
Password FUNCTIONS:
IMP NOTE: Password functions are not visible
normally. If user wants to access Password functions
follow these steps.
6. First enter password = “06”
2. Now Password functions are open & visible to
user.User can change/modify them.
After power ON/OFF or password is locked, again the
Password functions are inaccessible & only be
opened if password = 06
If user wants to set any Password use Password functions in
settings. The Password parameters are as follows.
1. System Settings :-
• Press ENT key till Display shows
System Settings
6
2. Offset Settings :-
Offset Settings
6
• Change the Offset Settings Password with the help of INC/DEC
key. Press Enter key.
3. Delay Setting :-
Press ENT key till Display shows
Delay Settings
6
• Change the Delay Setting Password with the help of INC/DEC
key. Press Enter key.
4. Status Parameter :-
• Press ENT key till Display shows
Status Parameter
6
5. Control Parameter :-
Press ENT key till Display shows
Control Parameter
6
6. Network Settings :-
• Press ENT key till Display shows
Network Settings
6
• Change the Network Settings with the help of INC/DEC key.
• Press Enter key.
7. Password Setting :-
Press ENT key till Display shows
Password Settings
6
8. Fault History :-
• Press ENT key till Display shows
Fault History
5
• Change the Fautl History with the help of INC/DEC key. Press
Enter key.
9. Fault Reset :-
• Press ENT key till Display shows
Fault Reset
6
• Change the Fautl reset the help of INC/DEC key. Press Enter
key.
26
Fault Reset :-
Using this function the faults can be reset.
DEBUG WINDOW:-
Thıs function shows the status of the units connected
in the network.
The display shows as follows
Unit Connection
Slave 01 NO
Exit Function:
Using this function the user can exit from the function
menu to Run mode.
PASSWORD :-
Now password is of 4 digits & default factory set password will be “06”.
If user wish to change the password,he has to enter first this default
password & then by going into password function he can enter his own
password.Now next time the controller will give access to password entered
by user OR the factory set password which is 06.
To view/change the offset set points, user has to enter the correct Offset
Password which is 06 (Factory set).
27
28